sustainable airport manual v3 - airports going green
TRANSCRIPT
airportsgoinggreen.org
flychicago.org ©Copyright 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Message from Mayor Rahm Emanuel
As Mayor, I am focused on elevating sustainability throughout city government. I am committed to increasing employment and entrepreneurship around energy and making sure that Chicago is the greenest city in the world. We have launched a number of innovative programs. I have vowed to doubling the number of government-owned LEED buildings, to a total of 80; we are building 100 miles of protected bike lanes; and we are creating ten Energy Efficiency Target Zones across the city. Additionally, we have launched competitive building for our recycling program, which will ultimately lead to recycling across Chicago. And we are working to establish the Chicago River as the city’s next recreational frontier, which will create jobs and economic opportunity throughout the city.
I believe every business decision can be a green decision. This requires hard work, cooperation and commitment from local government as well as every individual, business and institution in Chicago. We must all work together to realize our collective environmental goals. The Chicago Department of Aviation’s commitment to green initiatives is an important part of our sustainable vision. This Sustainable Airport Manual guides the integration of the most innovative and progressive sustainable measures in the aviation industry into all administrative, planning, design, construction, daily operations, and maintenance activities for the Chicago Department of Aviation and its tenants. Chicago's two international airports currently provide nonstop service to over 30 countries in addition to a robust domestic network. Combined, O'Hare and Midway serve approximately 85 million passengers annually and serve a vital role in the global economy. As our airports continue to evolve and grow, so too will their efficiency and economic output, providing additional opportunity for Chicago to strengthen its commitment to environmental initiatives and further our ongoing effort to be a leader in green innovation. Sincerely, Rahm Emanuel Mayor City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Message from Commissioner Rosemarie S. Andolino The Chicago Department of Aviation continues to serve as a benchmark for environmental stewardship by embracing the best environmental, social, and fiscally responsible practices at our airports. Our goal is to complement and promote the City of Chicago’s commitment to green initiatives and to enhance the quality of life for our citizens. Under the O’Hare Modernization Program, the City of Chicago introduced the Sustainable Design Manual in 2003, to ensure that sustainable initiatives and measurements were implemented during the build out and modernization of Chicago O’Hare International Airport. The Sustainable Design Manual positioned Chicago as the first in the nation to develop sustainable guidelines for design and construction at airports. It established the model for green airport development and has since received national and international recognition. The Sustainable Design Manual was just the beginning. We continue to expand our focus to incorporate sustainable initiatives for airport planning, operations and maintenance, and concessions and tenants. To encompass all of these areas into one comprehensive document, we have created the Sustainable Airport Manual (SAM) which highlights each topic with a dedicated chapter. This Manual is intended to be a “living document,” one that will continue to grow and evolve, to include emerging new technologies, state-of-the-art design and thought-provoking principles as they develop. We are looking ahead to the future and working with industry experts, airport and airline professionals to collaborate on best practices and lessons learned from airports around the world. This Manual would not have been possible without the collaborative input from so many dedicated individuals. I would like to sincerely thank each of you who contributed to the development of the Sustainable Airport Manual. It is because of your hard work, time and commitment that this document will become the model for sustainable implementation at airports across the globe. Sincerely,
Rosemarie S. Andolino Commissioner Chicago Department of Aviation
…We have to start today and make those incremental benefits that we can continue to learn from, grow from, and continue to enhance in order for us to be better tomorrow…
Rosemarie S. Andolino Commissioner
Chicago Department of Aviation …This is a living document with many features to be updated on a continuous basis. Because technology is changing and new cutting-edge material is becoming available, there are opportunities to make enhancements on a continuous basis…
Sam Mehta San Francisco International Airport
…We want to make sure that people who want to follow a concept back to its origins have the references to do so…we have participation nationally and globally from other airports and we
want this document to have a worldwide bench-mark presence…
Ken Westlake U.S. Environmental Protection Agency
…We are seeing things changing and evolving very quickly …
Doug Widener U.S. Green Building Council – Chicago Chapter
airportsgoinggreen.org
Project Submittal Forms, Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
Au1
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
CONTRIBUTORS
STEERING COMMITTEE Chicago Department of Aviation Rosemarie S. Andolino, Commissioner Amy Malick, Deputy Commissioner Project Oversight Team Ted J. Woosley, Landrum & Brown Eugene Peters, Ricondo & Associates Sara Hassert, Landrum & Brown John Antonoglu, Primera Engineers
COMMITTEE LEADERSHIP Administrative Procedures Sharon Douglas, Chair Atlanta Hartsfield-Jackson International Airport Amy Hanson, Co-Chair Federal Aviation Administration Sustainable Site Management Janell Barrilleaux, Chair Formerly with Denver International Airport Currently with FAA (Northwest Mountain Region) Ken Westlake, Co-Chair U.S. Environmental Protection Agency Water Efficiency Walter Seedlock, Chair Metropolitan Washington Airports Authority Steve Howards, Co-Chair Clean Airport Partnership Energy & Atmosphere Etienne Rouverand, Chair Charles de Gaulle International Airport Doug Widener, Co-Chair U.S. Green Building Council–Chicago Chapter Materials & Resources Sam Mehta, Chair San Francisco International Airport T.J. Schultz, Co-Chair Airport Consultants Council Indoor Environmental Quality Stewart Dalzell, Chair Boston Logan International Airport
Michael Berkshire, Co-Chair Chicago Department of Zoning and Land Use
Planning Construction Practices Kristi McKenney, Chair Oakland International Airport Dennis Probst, Co-Chair Minneapolis / St. Paul - Metropolitan Airports
Commission Document Organization and Process Elizabeth Leavitt, Chair Seattle-Tacoma International Airport Steve Clermont, Co-Chair Center for Transportation and the Environment Planning James Crites, Chair Dallas-Fort Worth International Airport Todd Welty, Co-Chair Reno-Tahoe Airport Authority Operations and Maintenance Paul Manasjan, Chair San Diego County Regional Airport Authority Mark Radtke, Co-Chair United Airlines Concessions and Tenants Intissar Durham, Chair Los Angeles World Airports Paul Shank, Co-Chair Baltimore-Washington International Airport
Au2
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
CONTRIBUTORS (continued)
Abu Dhabi Airports Company James Bennett, CEO Chris Arman, Christine Eid, Alexander Fechney, Nahla Nabil
Atlanta Hartsfield-Jackson International Airport Benjamin DeCosta, Aviation General Manager Terry Ellis, Tiffany Jones, Michael Leaf, Janelle Lyons
Baltimore-Washington International Airport Timothy L. Campbell, Executive Director (MAA) Bill Algie, Robin Bowie, Helen Tremont, Sherry Varner
Boston Logan International Airport Edward Freni, Director of Aviation Katie Choe
Charles de Gaulle International Airport Pierre Graff, Chairman/CEO, Aéroports de Paris Jean-Marie Chevalier, Chief Executive Officer, Aéroports de Paris Management
Dallas-Fort Worth International Airport Jeffrey Fegan, CEO Tomas Rivera, Sabine Schleigh
Denver International Airport Kim Day, Manager of Aviation
Indianapolis International Airport John D. Clark III, CEO (IAA) Greta Hawvermale
Los Angeles World Airports Gina Marie Lindsay, CEO
Metropolitan Washington Airports Authority James E. Bennett, President/CEO
Minneapolis / St. Paul - Metropolitan Airports Commission Jack Lanners, Chairman Jeffrey Hamiel, Executive Director
Oakland International Airport Steve Grossman, Director of Aviation
Portland International Airport Steve Schreiber, Aviation Director Phil Ralston
Reno-Tahoe Airport Authority Krys T. Bart, President/CEO Dean Schultz
San Diego County Regional Airport Authority Thella F. Bowens, President/CEO
San Francisco International Airport John Martin, Airport Director
Seattle-Tacoma International Airport Mark Reis, Managing Director Dave Tomber
St. Louis-Lambert International Airport Rhonda Hamm-Niebruegge, Director of Airports Joletta Golik
Federal Aviation Administration Barry Cooper, Great Lakes Regional Administrator Christina Drouet
United Airlines Ajay Singh, Vice President - Corporate Real Estate Mike Powers
U.S. Environmental Protection Agency Bharat Mathur, Acting Administrator, Region 5
National Airports Corporation Barksy Panka, Environmentalist
Illinois Department of Transportation Susan Shea, Director of Aeronautics Terry Schaddel
American Association of Airport Executives Charles Barclay, President Spencer Dickerson, Senior Executive Vice President Leslie Riegle, Melissa Sabatine
Airports Council International Gregory Principato, President Jessica Steinhilber, Paul Eubanks
Bentley Prince Street Sateria Venable
Broward County Aviation Department Monica Capelluto, Principal Planner
Center for Transportation and the Environment Steve Clermont, Lauren Justice
University of Illinois Sustainable Technology Center James Janssen
U.S. Department of Agriculture Travis Guerrant
Chicago Board of Education Mary Richardson-Lowry
Chicago Department of Aviation John Antonacci, Cyle Cantrell, Mary Donovan, Aaron Frame, Aurelio Garcia, Frank Grimaldi, Dorothy Izewski, George Lyman, Matt Marich, Andrea McKenzie, Khaled Naja, Bill Palivos, David Robbins, Adam Rod, Glen Ryniewski, Larry Rzewski, Bob Schmidt
Chicago Department of Community Development Michael Jasso
Chicago Department of Environment Samantha Bingham, Scott Mehaffey, Leigh Peters, Kimberly Worthington
Chicago Department of Land Use and Zoning Michael Burt, Jocelyn Lim
Au3
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
CONTRIBUTORS (continued)
Chicago Department of Law Mort Ames, Lisa Misher, Dao Ngo
Chicago Department of Water Management Mike Foley, Sid Osakada
City of Chicago – Office of the Mayor Joe Deal
City of Des Plaines Mark Walsten
Chicago Park District Brendan Daley, Khatija Hashmy
Chicago Public Building Commission Deeta Bernstein
Chicago Transit Authority Jorge Perez
North Central Texas Council of Governments Joseph Carlini
Airline Parties Construction Representative Joseph Gabbert
All Source Industries Bobby Rogers
American Society of Civil Engineers Oswald Chong, Marvin Oey
Adrian Smith + Gordon Gill Architects Adrian Smith, Gordon Gill, Gail Borthwick, Jeff Boyer, Christopher Drew, Gregg Herman
AECOM Jim Chilton, Kevin Fuhr, Andres Garcia, Henry Kurzynski, Nate Smith, David Waterman
Aero Jet Wash Shawn Tadayon
Aircraft Service International Group Ed Zwirn, Corey Gilkes
Ardmore Associates Weston Parker
Argonne National Laboratory Justin Pence
BAA USA Carol Fearns, Rob Hale
Bechtel Aviation Services Betsy Huigens
Berghoff Group Carlyn Berghoff
Bowman, Barrett and Associates Ross Anderson
Brookstone Eric Kicherer
CARE Plus Peter Antosh, Eileen Chin, Alan Dadian, Joe Dote, Robert Forgue, Susan Nelson
Caterpillar Paul Cook, Glen Luksik
Charles R Rowe Chuck Rowe
CH2M HILL Johnny Jackson, Larry Martin, Tracy Victorine-Lewis, Michael Vonic
Conestoga-Rovers & Associates Betty LeClerc
Construction Institute Marvin Oey
David Mason & Associates Mia Delgado
DEI Chicago Atif Sheikh, Carrie Westhoff
d’Escoto Hilary Clark
D+G Consulting Group Rhona DiCamillo
Dirección de Aeronáutica- Chile Carlos Aliaga
Dolmen Proyectos Antonio de Garay
Double P Corporation Scott Rubin
Ecogardens Greg Raymond
Efficiency Energy Richard Darlow
Encelium Technologies John Altmann
Enterprise Rent-A-Car Daniel Raftery
Environmental Consulting Group Sandy Webb
Epstein Jennifer O’Connell
Faithful+Gould David McNamara
Au4
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
CONTRIBUTORS (continued) GEI Consultants Robert Acker
Ghafari Associates Annie Ranttila, James Terada
Go Green, Reduce Reuse Resell Cynthia Payne
Grainger Edgar Wright
Gresham, Smith & Partners Jane Ahrens
Grove Snacks Paul Loupakos
Harbour Contractors William Cordray
Harbour Construction Michelle Cecchin, Ray Gooding, William Trudeau
HJ Kessler Associates Helen Kessler
HMS Host Harry Lu, Bradley Maher, Essie Poudhardi
HNTB Shawn Gould, Alexia Paul, Tonya Wells
HOK Colin Rohlfing
Huff & Huff Linda Huff, Holly Moriarty
Ifas Shifani Sood
IKIA Project Management Azita Toloee
Indelible Impressions Construction Norvetta Landon
Jacobsen/Daniels Associates Michael P. Hanlon
Jacobs Jennifer Bartels, Zoe Haseman, Kris Koch, Todd Merrihew, Steven Peters, Justin Ritter
Jamba Juice Amrit Patel
John Deere Terry Oftedal
Jviation William Poole
Kainan University, Taiwan Kuo-Shun Sun
Keystone Water Company Chris Rapp
Kiewit Hank Adams, Pierre Adam
Kimley-Horn Jeff Eaglehouse, Nathan Summers
KYA Design Group Ross Yamasaki
Landrum & Brown Sarah Contreras, Drew Homyk
McDonald’s US Restaurant Catherine Jama, John Rockwell
McDonough Associates Thomas Thornton, Kamil Yenice
McKissack & McKissack Marty Turner
Mead & Hunt Jason Clark, Timothy Dacey
Midwest Energy Efficiency Alliance Christina Pagnusat
Milhouse Engineering and Construction Martin Barenbaum, Adam Hardy, Myesha McClendon
O’Hare Airport Transit System John Sisco
Office of Congressman Rush Younus Suleman
Patten Industries Bill Bayne, Luke Mueller, Tony Yang
PB Americas Martin Carroll, Tom Lyon
Perkins+Will Pat Askew
Potbelly Sandwich Works Kitty Carlson
Primo Water Gretchen Sussman
Regina Webster Doug Arends, John Ellis, Sarah McDougall
Reynolds, Smith & Hill Phil Becker, Mike Lazaruk, Stephen Moulton
Ricondo & Associates Margaret Johnsen, Allison Kloiber
Robinson Hill Group Dee Robinson Reid
Roofing Resources Erich Poch
Au5
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
CONTRIBUTORS (continued)
Roofscapes Melissa Muroff
Ross & Baruzzini Allan Shapiro
Rossi Contractors Jon Gross
Rubinos & Mesia Engineers Mohsen Farahany, Farhad Rezai, Ted Witte
Singh & Associates Chris Leow
SK Jets Nicholas Wooton
Solomon Cordwell Buenz Mark Frisch
Sound Balance Iris Goldschmidt
Stantec Rian Burger
System Development Integration Dan Sullivan
Terry Guen Design Associates Terry Guen
The Astor Company Kevin Flood
The Indak Group Joe Marino
The Sheward Partnership Bill Algie
Thomas Group Josh Ridker
TJ Lambrecht Erik Schneider
Transportation Consulting & Management Demetrio Garcia, Richard Potosnak
Transnorm System Jody Smith
Transsolar Erik Olson
TransSolutions Gloria Bender
TranSystems Rosi Rawson, Ken Yang
Unison Retail Management Victor Franco, Patricia Grzyb, Dorine Litman, Diana Miller, Yolanda Woodruff
Ushio America Gene Siepka
UST Aviation Services Mayank Tripathi
Vanderlande Industries Gaylloyd Dadyala
Walsh Group Jeremy Bubb, Clayton Ziller
Westfield Concession Management Ellery Plowman
W.W. Grainger Patrick Bourke
Special Thanks to: Gregg Cunningham Leah De Leon Cathy Kwiatkowski Gretchen Meyer Karen Pride Tracy Walsh Anna Szczesniak Nicholas Alex Shedd Aquarium
Au6
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
SUSTAINABLE AIRPORT MANUAL REGISTRATION The Sustainable Airport Manual (SAM) is a “living document.” It will continue to grow and evolve, and as such, the SAM will be updated frequently over time. Users of the SAM are encouraged to register to receive future updates.
To register, please visit www.airportsgoinggreen.org.
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
Au7
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
TABLE OF CONTENTS SUSTAINABLE AIRPORT MANUAL INTRODUCTION ………... 16 CHAPTER – ADMINISTRATIVE PROCEDURES ADMINISTRATIVE PROCEDURES INTRODUCTION ………... AP-2 AP.1 Green Meetings ………... AP-5AP.2 Document Reduction Recycling Initiative (DRRI) ………... AP-9AP.3 Corporate Sustainability Policy ………... AP-11AP.4 Green Procurement Policy ………... AP-13AP.5 Recycled Content Paper ………... AP-15 Appendix AP-A Green Product Listing …….…… AP-A-1 CHAPTER – PLANNING PLANNING INTRODUCTION ………... PL-2 PL.1 Define Sustainability Vision Statement ………... PL-10PL.2 Determine Key Stakeholders and hold Initial Project Meeting to
Discuss Sustainability Goals ………... PL-11
PL.3 Sustainability Baseline Assessment and Cost/Benefit Analysis ………... PL-14PL.4 Develop a Sustainability Schematic ………... PL-17PL.5 Project Meeting to Finalize Sustainability Schematic ………... PL-23PL.6 Close the Feedback Loop at Project Completion ………... PL-24 CHAPTER – DESIGN & CONSTRUCTION DESIGN & CONSTRUCTION INTRODUCTION ………... DC-3 2.0 Sustainable Sites 2.1 Construction Activity Pollution Prevention ………... DC-122.2 Adopt CDA Best Management Practices ………... DC-142.3 Brownfield Redevelopment ………... DC-152.4 Alternative Transportation ………... DC-172.5 Stormwater Design ………... DC-262.6 Landscape and Exterior Design to Reduce Heat Islands ………... DC-322.7 Light Pollution Reduction ………... DC-38 3.0 Water Efficiency 3.1 Water Use Reduction, 20% Reduction ………... DC-423.2 Water Use Reduction, 30%-40% Reduction ………... DC-443.3 Water Efficient Landscaping ………... DC-473.4 Innovative Wastewater Technologies ………... DC-53 4.0 Energy & Atmosphere 4.1 Fundamental Building Systems Commissioning ………... DC-554.2 Minimum Energy Performance ………... DC-594.3 Fundamental Refrigerant Management ………... DC-634.4 Optimize Energy Performance ………... DC-654.5 On-Site Renewable Energy ………... DC-754.6 Enhanced Commissioning ………... DC-794.7 Enhanced Refrigerant Management ………... DC-83
Au8
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
4.8 Measurement and Verification ………... DC-854.9 Green Power ………... DC-87 5.0 Materials & Resources 5.1 Storage and Collection of Recyclables ………... DC-895.2 Building and Infrastructure Reuse ………... DC-925.3 Construction Waste Management ………... DC-945.4 Balanced Earthwork ………... DC-975.5 Aggregate Reuse ………... DC-995.6 Material Reuse ………... DC-1015.7 Recycled Content ………... DC-1035.8 Local/Regional Material ………... DC-1075.9 Rapidly Renewable Materials ………... DC-1105.10 Certified Wood ………... DC-1125.11 Furniture and Equipment ………... DC-1135.12 Equipment Salvage and Reuse ………... DC-115 6.0 Indoor Environmental Quality 6.1 Minimum Indoor Air Quality (IAQ) Performance ………... DC-1166.2 Environmental Tobacco Smoke (ETS) Control ………... DC-1186.3 Outdoor Air Delivery Monitoring ………... DC-1216.4 Increased Ventilation ………... DC-1236.5 Construction IAQ Management Plan ………... DC-1266.6 Low-Emitting Materials ………... DC-1316.7 Indoor Chemical and Pollutant Source Control ………... DC-1416.8 Controllability of Systems ………... DC-1436.9 Thermal Comfort ………... DC-1476.10 Daylight and Views ………... DC-1516.11 Noise Transmission ………... DC-156 7.0 Construction Practices 7.1 Clean Fuel Construction Vehicles ………... DC-1587.2 Construction Equipment Maintenance ………... DC-1627.3 Construction Activity Pollution Prevention ………... DC-1647.4 Systems Commissioning ………... DC-1647.5 Construction Waste Management ………... DC-1647.6 Construction IAQ Management Plan ………... DC-1657.7 Low-Emission Construction Vehicles ………... DC-1667.8 Alternative Transportation During Construction ………... DC-1677.9 Construction Material Conveying ………... DC-1737.10 Construction Noise and Acoustical Quality ………... DC-1757.11 Sustainable Temporary Construction Materials ………... DC-177 8.0 Innovation in Design & Construction 8.1 Innovation in Design & Construction ………... DC-1818.2 Innovation in Design & Construction ………... DC-1818.3 Innovation in Design & Construction ………... DC-1818.4 Menu Items ………... DC-1838.5 LEED Accredited Professional ………... DC-1878.6 LEED Certified Project ………... DC-188 9.0 Regional Priority 9.1 Regional Priority ………... DC-189
Au9
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Appendices DC-A Green Airplane Rating System for Operations & Maintenance …….…… DC-A-1DC-B Operations & Maintenance Checklist …….…… DC-B-1DC-C Referenced City of Chicago Specifications and Standards …….…… On CDDC-D Chicago Department of Aviation Best Management Practices
Manual …….…… On CD
CHAPTER – OPERATIONS & MAINTENANCE OPERATIONS & MAINTENANCE INTRODUCTION …….…… OM-3 1.0 Sustainable Sites 1.1 Equipment Maintenance …….…… OM-91.2 LEED Certified Project …….…… OM-111.3 Exterior Facilities Management …….…… OM-131.4 Hardscape Grounds Management …….…… OM-151.5 Integrated Pest Management and Wildlife Deterrence …….…… OM-171.6 Erosion Control …….…… OM-191.7 Landscape Management …….…… OM-211.8 Alternative Commuting Transportation for Employees …….…… OM-251.9 Stormwater Management …….…… OM-281.10 Heat Island Reduction …….…… OM-321.11 Light Pollution Reduction …….…… OM-35 2.0 Water Efficiency 2.1 Establish a Water Baseline …….…… OM-372.2 Retroactive Water Efficiency …….…… OM-402.3 Indoor Water Efficiency …….…… OM-422.4 Water Efficient Landscaping …….…… OM-452.5 Rain Harvesting for Non-Irrigation Usage …….…… OM-482.6 2.7
Innovative Wastewater Management Water Efficient Vehicle Washing
…….…… …….……
OM-50 OM-52
3.0 Energy & Atmosphere 3.1 Refrigerant Management …….…… OM-543.2 Utility Meter Data …….…… OM-563.3 Retroactive Energy Optimization …….…… OM-583.4 Optimize Energy Performance …….…… OM-603.5 Existing Building Commissioning …….…… OM-683.6 Performance Measurement …….…… OM-723.7 On-Site and Off-Site Renewable Energy …….…… OM-763.8 Enhanced Refrigerant Management …….…… OM-803.9 Emissions Reduction Reporting …….…… OM-82 4.0 Materials & Resources 4.1 Solid Waste Management …….…… OM-854.2 Local/Regional Materials …….…… OM-91 5.0 Indoor Environment Quality 5.1 Outdoor Air Introduction and Exhaust System …….…… OM-935.2 Environmental Tobacco Smoke (ETS) Control …….…… OM-955.3 High Performance Cleaning …….…… OM-965.4 Indoor Air Quality (IAQ) Best Management Practices …….…… OM-985.5 Occupant Comfort …….…… OM-106
Au10
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.6 Green Cleaning …….…… OM-110 6.0 Innovation for Operations & Maintenance 6.1 Innovation in Operations …….…… OM-1146.2 Innovation in Operations …….…… OM-1146.3 Innovation in Operations …….…… OM-1146.4 Innovation in Operations …….…… OM-114 7.0 Education & Training 7.1 Community Education …….…… OM-1167.2 Implement Employee Sustainability Training Program …….…… OM-1187.3 Staff Training …….…… OM-120 8.0 Monitoring & Reporting 8.1 Documenting Sustainable Measures …….…… OM-122 Appendices OM-A Green Airplane Rating System for Operations & Maintenance …….…… OM-A-1OM-B Operations & Maintenance Checklist …….…… OM-B-1 CHAPTER – CONCESSIONS & TENANTS CONCESSIONS & TENANTS INTRODUCTION ………... CT-5 SECTION – CONCESSIONS & TENANTS – DESIGN & CONSTRUCTION CT-13 1.0 Sustainable Sites 1.1 Adopt CDA Best Management Practices ………... CT-141.2 Light Pollution Reduction ………... CT-15 2.0 Water Efficiency 2.1 Water Use Reduction ………... CT-162.2 Water Use – Additional Reduction ………... CT-19 3.0 Energy & Atmosphere 3.1 Fundamental Systems Commissioning ………... CT-223.2 Minimum Energy Performance ………... CT-253.3 Optimize Energy Performance ………... CT-273.4 Enhanced Commissioning ………... CT-353.5 Measurement and Verification ………... CT-393.6 Green Power ………... CT-42 4.0 Materials & Resources 4.1 Storage and Collection of Recyclables ………... CT-454.2 Construction Waste Management ………... CT-474.3 Material Reuse ………... CT-504.4 Recycled Content ………... CT-524.5 Local/Regional Materials ………... CT-554.6 Rapidly Renewable Materials ………... CT-574.7 Certified Wood ………... CT-594.8 Furniture and Equipment ………... CT-614.9 Equipment Salvage and Reuse ………... CT-63
Au11
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 Indoor Environmental Quality 5.1 Minimum Indoor Air Quality (IAQ) Performance ………... CT-655.2 Environmental Tobacco Smoke (ETS) Control ………... CT-675.3 Construction IAQ Management Plan ………... CT-695.4 Low-Emitting Materials ………... CT-745.5 Indoor Chemical and Pollutant Source Control ………... CT-845.6 Controllability of Systems ………... CT-865.7 Thermal Comfort ………... CT-905.8 Noise Transmission ………... CT-93 6.0 Construction Practices 6.1 Alternative Transportation During Construction ………... CT-956.2 Construction Noise and Acoustical Quality ………... CT-1006.3 Sustainable Temporary Construction Materials ………... CT-102 7.0 Innovation for Concessions & Tenants – Design & Construction 7.1 Innovation for Concessions & Tenants - Design & Construction ………... CT-1047.2 Innovation for Concessions & Tenants - Design & Construction ………... CT-1047.3 Innovation for Concessions & Tenants - Design & Construction ………... CT-1047.4 Menu Items ………... CT-1057.5 LEED Accredited Professional ………... CT-1107.6 LEED Certified Project ………... CT-111 SECTION – CONCESSIONS & TENANTS –OPERATIONS & MAINTENANCE
CT-112
8.0 Company Policy 8.1 Tenant Environmental Liaison ………... CT-1138.3 Establish and Implement Employee Environmental Training
Program ………... CT-114
8.4 Alternative Transportation ………... CT-1168.5 Community Education ………... CT-123 9.0 Responsible Procurement 9.1 Furniture and Equipment ………... CT-1259.2 Eliminate Use of Polystyrene Foam ………... CT-1279.3 Consumer Disposable Products ………... CT-1289.4 Local/Regional Food Sources ………... CT-1389.5 Sustainable Food Sources ………... CT-140 10.0 Green Interiors 10.1 Minimum Indoor Air Quality (IAQ) Performance ………... CT-14210.2 Environmental Tobacco Smoke (ETS) Control ………... CT-14410.3 LEED Certified Design & Construction ………... CT-14510.4 Green Cleaning ………... CT-14710.5 Measurement and Verification ………... CT-15510.6 Tenant Space Automation Systems ………... CT-15710.7 Occupant Controls ………... CT-15810.8 Thermal Comfort: Employee Verification ………... CT-162 11.0 Water Management 11.1 Utility Meter Data ………... CT-16411.2 Water Management Plan ………... CT-165
Au12
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
11.3 Water Use Reduction ………... CT-169 12.0 Energy Management 12.1 Utility Meter Data ………... CT-17212.2 Energy Management Plan ………... CT-17312.3 Energy Use Reduction ………... CT-17812.4 Optimize Energy Performance ………... CT-18112.5 Green Power ………... CT-190 13.0 Waste Stream Management 13.1 Waste Stream Audit ………... CT-19313.2 Waste Stream Management Plan ………... CT-19513.3 Waste Reduction ………... CT-20013.4 Storage and Collection of Recyclables ………... CT-20313.5 Track and Report Recycling Activity ………... CT-20613.6 Organic Byproduct Recycling ………... CT-20813.7 Surplus Food Sent to Local Organizations ………... CT-21413.8 Deplaned Waste ………... CT-21613.9 Repurposing of Goods ………... CT-21913.10 Reduction of Plastic Waste ………... CT-221 14.0 Venue Specific Considerations 14.1 Heat Island Reduction ………... CT-22514.2 Stormwater Management ………... CT-22814.3 Landscape Management ………... CT-23014.4 Rainwater Harvesting ………... CT-23814.5 Water Efficient Vehicle Washing ………... CT-24014.6 Clean Fuel Vehicles ………... CT-24214.7 Alternative Fuel Infrastructure ………... CT-24414.8 Green Restaurant Certification ………... CT-246 15.0 Innovation for Concessions & Tenants – Operations &
Maintenance
15.1 Innovation for Concessions & Tenants - Operations & Maintenance ………... CT-24815.2 Innovation for Concessions & Tenants - Operations & Maintenance ………... CT-24815.3 Innovation for Concessions & Tenants – Operations & Maintenance ………... CT-24815.4 Community/Cultural Responsibility ………... CT-24915.5 Menu Items ………... CT-251 16.0 Monitoring and Reporting 16.1 Documenting Sustainable Measures ………... CT-252 Appendices CT-A Green Airplane Rating System for Concessions & Tenants …….…… CT-A-1CT-B Concessions & Tenants Checklist …….…… CT-B-1
Au13
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
ABBREVIATIONS
ANSI AOA ARFF
American National Standards Institute Air Operations Area Aircraft Rescue Firefighting American Society of Heating, Refrigeration, and Air-Conditioning Engineers American Society for Testing and Materials Airport Transit System Building Automation System Balanced Earthwork Plan Building Integrated Photovoltaic Best Management Practices Basis of Design Biological Oxygen Demand British Thermal Unit Construction & Demolition California Air Resources Board Chicago Building Code Commercial Buildings Energy Consumption Survey Chicago Department of Aviation Chicago Department of Construction Administration and Permits Chicago Department of Transportation Chicago Energy Conservation Code Chlorofluorocarbon Compact Fluorescent Light bulb Construction General Permit Chartered Institution of Building Services Engineers Capital Improvement Program Credit Interpretation Result Construction Manager Compressed Natural Gas Chlorinated Polyvinyl Chloride Carpet and Rug Institute Center for Resource Solutions Construction Specification Institute Concession & Tenants Chicago Transit Authority Continuously Variable Transmission Commissioning Authority Design & Construction Design for the Environment Department of Health Services Department of Energy Energy Conservation Measure Engineering Document Recycling Initiative Ecological Footprinting Environmental Protection Agency Energy Policy Act Erosion and Sedimentation Control Environmental Tobacco Smoke Federal Aviation Administration Federal Energy Management Program Fit-out, Furniture and Equipment
ASHRAE ASTM ATS BAS BEP BIPV BMP BOD BOD BTU C&D CARB CBC CBECS CDA CDCAP CDOT CECC CFC CFL CGP CIBSE CIP CIR CM CNG CPVC CRI CRS
CSI CT CTA CVT CxA DC DFE DHS DOE ECM EDRI EF EPA EPAct ESC ETS FAA FEMP FF&E
Au14
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
FOD Foreign Object Debris Forest Stewardship Council Full-Time Equivalent Green House Gas Gallons per flush Gallons per minute Ground Tire Rubber Global Warming Potential Hydrochlorofluorocarbon High Density Polyethylene Halfnium Carbide Hydrofluorocarbon Harvard Real-Estate Services Heating, Ventilation, Air Conditioning Indoor Air Quality International Energy Conservation Code Illinois Environmental Protection Agency Illumination Engineering Society of North America Ice Making Head Integrated Pest Management International Performance Measurement and Verification Process Industrial Wastewater Treatment Suystem Los Angeles Community College District Light Emitting Diode Leadership in Energy and Environmental Design LEED Accredited Professional LEED for Existing Buildings LEED for New Construction Low-Emission Vehicle Life Cycle Assessment Life Cycle Cost Analysis Light Duty Vehicles Liquid Natural Gas Master Civil Engineer Medium Density Fiberboard Chicago Midway International Airport Minimum Efficiency Reporting Value Material Safety Data Measurement and Verification Navigational Aids Noise Criteria No Further Recommendation National Institute of Standards and Technology National Pollutant Discharge Elimination System Ozone Depletion Potential Operations & Maintenance O’Hare Modernization Program Owner’s Project Requirements Chicago O’Hare International Airport Oriented Strand Board Pre-Conditioned Air Portland Concrete Cement Phenylcyclohexene
FSC FTE GHG gpf gpm GTR GWP HCFC HDPE HfC HFC HRES HVAC IAQ IECC IEPA IESNA IMH IPM IPMVP IWTS LACCD LED LEED LEED AP LEED-EB LEED-NC LEV LCA LCCA LDV LNG MCE MDF MDW MERV MSD M&V NAVAIDS NC NFR NIST NPDES ODP OM OMP OPR ORD OSB PCA PCC PCH
Au15
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
PDD PDP
Project Definition Document Project Development Process Project Management Office Photovoltaic Polyvinyl Chloride Partial Zero Emissions Vehicle Remote Compressor Unit Resident Engineer Renewable Energy Certificates Request for Proposal Remote Processing Unit Sustainable Airport Guidance Alliance Sustainable Airport Manual South Coast Air Quality Management District Self Contained Unit Sustainable Design Manual Stockholm Environmental Institute State Improvement Plan Sheet Metal and Air Conditioning National Contractors Association Sustainability Management System Standard Operating Procedure Solar Reflectance Index Sustainable Review Panel Stewards of Tomorrow’s Airport Resources Sound Transmission Class Stormwater Pollution Prevention Plan Technology Acceptance Reciprocity Partnership Total Lighting Control Tradable Renewable Certificates Total Suspended Solids Total Volatile Organic Compounds Ultra-Low Sulfur Diesel Fuel United States Department of Agriculture United States Environmental Protection Agency United States Green Building Council Ultraviolet Variable Air Volume Variable Frequency Drive Vinyl Composition Tile Volatile Organic Compounds Wide-Area Network World Business Council Sustainable Development Wood Derived Fuel World Resources Institute Zero-Emissions Vehicle
PMO PV PVC PZEV RCU RE REC RFP RPU SAGA SAM SCAQMD SCU SDM SEI SIP SMACNA SMS SOP SRI SRP STAR STC SWPPP TARP TLC TRC TSS TVOC ULSD USDA USEPA USGBC UV VAV VFD VCT VOC WAN WBCSD WDF WRI ZEV
Au16
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
VISION STATEMENT
The Chicago Department of Aviation is embracing the best possible environmental, social, and fiscally responsible practices to enhance the quality of life and complement the overall mission and goals of the City of Chicago. It is our vision that the Sustainable Airport Manual will become the global industry standard for sustainability planning, development, and everyday functions at airports around the world.
INTRODUCTION
When the original edition of this manual was unveiled as the Sustainable Design Manual (SDM) in December of 2003, Chicago was the first in the nation to develop sustainability guidance for airports. Numerous, wide-ranging OMP projects have since been reviewed and rated according to the standards established by the SDM, resulting in the evolution of a unique process and many industry firsts:
Development of a rating system Development of a green airplane certification award system Recognition of designers and contractors for sustainable accomplishments
The 2003 SDM used the LEED-NC 2.1 rating system as a basis. In 2009, the SDM was updated based on LEED® 2009, as well as lessons-learned from implementation of the previous manual, and the availability of newer technologies. The SDM was updated and became the Design & Construction Chapter of the new Sustainable Airport Manual (SAM) that was unveiled in August 2009. In November 2010, the SAM 2.0 version, which incorporates the new Planning, Operations & Maintenance, and Concessions & Tenants chapters, was released. In November 2011, the new SAM 2.1 version was released, featuring updated standards and regulations, additional case studies, a Green Airplane rating system for Concessions and Tenants Design and Construction projects, and other various document upgrades. SAM v3.0 was released in November 2012. Version 3.0 features additional credit guidance, new credits, revised rating systems, and updated case studies.
PURPOSE
The Sustainable Airport Manual (SAM) is an integral part of Chicago’s ongoing efforts toward implementing more environmentally sustainable buildings and civil infrastructure, incorporating best practice guidance for planning, operations and maintenance of all City airport facilities and functions, and those of its tenants.
The purpose of the SAM is to integrate airport-specific sustainable planning and practices early in the design process, through planning, construction, operations,
Au17
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
maintenance and all airport functions with minimal impact to schedule or budget. To achieve greater success, the SAM should be considered in every step of a project.
While certain elements of the SAM are specific to the Chicago Department of Aviation, they can easily be customized and interpreted for any airport’s unique environment. The vast majority of SAM’s guidance is already applicable to any airport.
Sustainable practices can potentially reduce the environmental impact of the built environment while at the same time creating financial and operational benefits for a project, and social benefits for the community at large. Together, these aspects of sustainability are commonly referred to as the “triple bottom line.”
The SAM provides direction and is a guideline for incorporation of as many sustainable elements into a project as are feasible, beyond those elements that are required through an individual project’s contract specifications and design standards.
PROCESS
The Administrative Procedures chapter is designed to certify the sustainability of airport-related administrative activities associated with the planning, design, construction, maintenance and daily operations. Therefore, the Administrative Procedures section of every checklist will need to be completed for every submission.
The Planning chapter is intended to address the conceptual planning of the airport’s physical environment to facilitate implementation of design, construction, and/or operation and maintenance in a sustainable manner.
The Design & Construction chapter continues the process of incorporating sustainability into major renovations and construction projects.
The Operations & Maintenance chapter is designed to certify the sustainability of ongoing operation of building operations, operational and maintenance procedures, system upgrades, minor space-use changes, and minor facility alterations or additions, and training and educational programs.
The Concessions & Tenants chapter is designed to certify the sustainability of concession and tenant activities, including daily operations, as well as design and construction of tenant space within the terminals.
Users of this Manual can reference the following flow chart to determine the chapters that apply.
Au18
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
This page intentionally left blank.
Au19
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Au20
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
This page intentionally left blank.
Au21
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
LEED STANDARD
The Sustainable Airport Manual (SAM) has been drawn in large part from the Leadership in Energy and Environmental Design Green Building Rating System™ (LEED®) of the U.S. Green Building Council (“USGBC”). All rights reserved. Hereinafter, the SAM will refer to this source document as LEED or LEED 2009. The content of LEED® incorporated in the SAM is used with the permission of and under license with USGBC.
LEED® is the nationally accepted benchmark for the design, construction and operation of high performance green buildings.
Copyrights in the Leadership in Energy and Environmental Design Green Building Rating System (LEED®) and the 2009 Edition Reference Guides, including the Green Building Design and Construction Reference Guide, the Green Interior Design and Construction Reference Guide, the Green Building Operations & Maintenance Reference Guide, and the marks LEED®, U.S. Green Building Council® and USGBC® are the property of the U.S. Green Building Council, Inc. USGBC makes no warranty of habitability, merchantability, fitness for a particular purpose, or anything else concerning any of its rating systems. Neither the LEED® rating system nor LEED certification means or implies that a project is or will be structurally sound or safe, constructed in accordance with application laws, regulations or codes, free of mold or mildew or free of volatile organic compounds or allergens. While USGBC applauds the efforts made in the SAM to address sustainable airport design and construction, USGBC has not approved or endorsed the SAM.
The City of Chicago Department of Aviation strongly encourages all applicable airport projects to seek individual LEED certification in addition to incorporating sustainable elements described in this Manual to the greatest extent possible and practicable.
The SAM is based on existing federal, state, and local regulatory requirements with additional sustainable and best practice environmental strategies and considerations. The guidance provided within does not supersede, but is intended to supplement such regulatory requirements. In Chicago, the existing federal, state, and local regulators and requirements include, but are not limited to:
Federal Aviation Administration
U.S. Environmental Protection Agency
Illinois Environmental Protection Agency
U.S. Department of Agriculture
Au22
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Illinois Department of Transportation
Chicago Department of Aviation Best Management Practices, Standards for Design and Construction, Stormwater Pollution Prevention Plan, Underground Storage Tank Management Plan
City of Chicago Codes and Ordinances
City of Chicago 2003 Water Agenda
O’Hare Modernization Program Balanced Earthwork Plan
Where a standard or specification is referenced in the Manual, it is assumed that it refers to the most current version unless otherwise noted.
Savings from the use of 100% FSC Certified recycled paper made with Green-e certified renewable wind energy*
*for every 500 printed copies
…We want to encourage companies and their employees to be active members and stewards of sustainability…
Amy Hanson Federal Aviation Administration
…What you’re trying to do is maximize your output with the least amount of input; reducing work, reducing materials, reducing your overall environmental footprint…
James Crites Dallas-Ft. Worth International Airport
…If we truly want to be a community, we need to act as a community within our organization…
Rosemarie S. Andolino Commissioner Chicago Department of Aviation
airportsgoinggreen.org
AuAP-1
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
ADMINISTRATIVE PROCEDURES TABLE OF CONTENTS
ADMINISTRATIVE PROCEDURES INTRODUCTION ………... AP-2 AP.1 Green Meetings ………... AP-5AP.2 Document Reduction Recycling Initiative (DRRI) ………... AP-9AP.3 Corporate Sustainability Policy ………... AP-11AP.4 Green Procurement Policy ………... AP-13AP.5 Recycled Content Paper ………... AP-16
AuAP-2
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
INTRODUCTION
The Sustainable Airport Manual (SAM) Green Airplane Rating System for Administrative Procedures (AP) is designed to certify the sustainability of airport-related administrative activities associated with the planning, design, construction, maintenance and daily operations. This chapter will be common to all other chapters of the SAM in order to promote workplace practices, procedures and material use that provide the reduction of energy, water and materials.
The intention is to not only plan, design, construct, maintain and operate an airport in a sustainable manner, but to also be cognizant that the process of administering these activities should integrate sustainability as well.
APPLICABILITY
These administrative procedures are applicable to any type of project. They are intended to be used and followed in everyday operations and activities by anyone acting or operating on behalf of the Chicago Department of Aviation (CDA).
All parties are required to complete the Administrative Procedures section of the checklist for every submission.
PROCESS
Within the Manual’s main body, each administrative procedure “Credit” has five subsections: Intent, Requirements, Submittals, Technology/Strategy, and Case Studies as described below:
Intent: The primary motivations for any sustainable practice.
Requirements: Specifies elements that satisfy the intent. The prerequisites must be achieved; the credits are optional, but contribute to the overall rating.
Submittals: Required and supporting documentation and/or information required to achieve applicable prerequisites or credits. This documentation may include calculations, data, short narratives, policies, documents or references to specifications or material datasheets indicating how the requirements are being met.
Technology/Strategy: Highlights specific ways of meeting the recommendations within the scope for each specific credit. Case studies where available, are presented to help guide the application of sustainable credits to projects and efforts. To aid with consideration of applicable strategies and technologies, they are organized into the following three categories: “Standard Practice,” “Recommended Practice,” and “Best Available Practice.”
o Standard Practice: These are requirements that may be due to standards, specifications, codes, general best management or construction practices. They are practices already in place, and SAM prerequisites, which also serve to meet sustainable goals.
AuAP-3
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
o Recommended Practice: These include recommendations that are expected to have insignificant impacts to cost and are therefore, encouraged to be incorporated.
o Best Available Practice: These are strategies and practices that are expected to enhance the sustainability efforts of the Chicago Department of Aviation (CDA), but are anticipated to potentially have an impact on the cost and/or schedule. A simple cost/benefit analysis can be conducted to determine the practicality of implementation.
Case Study: Examples of credit intent “in action” at airports and/or other industry facilities.
While not all strategies will be applicable, those using this Manual are encouraged to think creatively and to consider the intent of each issue throughout the decision process.
SUBMITTALS
Incorporation of sustainable administrative procedures is expected in every aspect of the operations and activities of the CDA and its contactors. The tracking of the AP credits have been integrated into the SAM Planning checklist, SAM Design & Construction checklist, SAM Operations & Maintenance checklist, and SAM Concessions & Tenant checklist.
In order to achieve points, certain requirements need to be met, as outlined in each credit. In some instances, studies, calculations and data would be appropriate. In other instances, this will be accomplished through short narratives, policies, documents, product and material data or through referenced standards or specifications.
In addition to review of the checklist, the Sustainable Review Panel (SRP) will review any supporting documentation including calculations, policy documents, specifications, and contractor’s submittals as needed to support the achievement of the credit(s). See Section titled Implementation and Review Process for detailed information about the SRP.
IMPLEMENTATION AND REVIEW PROCESS
The SAM and its supporting documentation are administered by the Sustainable Review Panel (SRP), which is intended to consist of representatives of the CDA Management Staff, CDA Design and Construction Staff and Representatives, OMP Project Management Office (PMO) and Master Civil Engineer (MCE), and Airport Planners actively involved in CDA projects. The composition of the SRP is intended to be dynamic depending on needs.
The SRP is responsible for the review of submittals with respect to sustainability and provides technical support to the each project in relation to sustainable practices appropriate. The SRP is responsible for review of every checklist and for the awarding of “Green Airplane Certification” ratings based on the extent of incorporation of sustainable practices as outlined in this Manual and as documented on the submitted SAM Checklist(s).
Other responsibilities of the SRP include preparation and review of sustainable design related specifications, technical memoranda, and miscellaneous documents, as necessary. In addition, the SRP is responsible for presentations and training to project team members with respect to
AuAP-4
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
the application of this Manual. The primary tasks of the SRP are to oversee the application of the Manual and review submittals for their compliance with the Manual.
All projects conducted by or under management of the CDA will follow these procedures. For any and all sustainability-related questions and/or submittals, please use the following email address to submit forms electronically (preferred method):
airports going green.org
For comments, case studies, lessons-learned, new technical recommendations and all project submittal
forms, please email:
AuAP-5
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
AP ADMINISTRATIVE PROCEDURES
AP.1 Prerequisite 1 – Green Meetings
Required
INTENT
Green meeting practices are intended to guide meeting hosts, planners, and attendees toward more eco-friendly meetings. A few extra efforts to incorporate environmental considerations into planning and conducting meetings will help to minimize the negative impact on the environment and educate all participants regarding sustainable meetings.
Green meeting practices are intended to:
Conserve resources Reduce environmental impacts Save money Support Chicago’s commitment to environmental stewardship
REQUIREMENTS
Whenever applicable, follow the green meeting practices outlined below, or your existing corporate sustainability policy, whichever is more stringent.
SUBMITTALS
Include narrative on SAM Checklist and if following your own corporate sustainability policy, please include with submittal for this section.
TECHNOLOGY/STRATEGY
Meeting Greeting
The following are sample text that the meeting host could use to remind participants of the intent to conduct meetings in a green manner:
I want to remind everyone that we are conducting our meeting following green meeting practices, which are intended to:
Conserve resources Reduce environmental impacts Save money; and Support Chicago’s commitment to environmental stewardship.
(Continued on following page)
AuAP-6
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
(Continued from previous page)
We conduct our meetings in an environmentally friendly manner.
Please mute all cell phones for social courtesy and the most efficient use of everyone’s valuable time.
Please use the recycle bins for recyclable items at the end of the meeting.
Help to ensure the lights are turned off as we leave the meeting room.
Meeting Planning
Meeting hosts should consider the following when planning for a meeting:
Reduce the number of copies produced by: Sharing meeting materials Digitizing materials and distributing presentations via email prior to meetings Placing materials on the wall (one large print or presented with projector equipment) If handouts are needed at the meeting, produce handouts: Locally Double-sided Using high post-consumer recycled content paper Using chlorine-free paper Using vegetable-based inks if available for type of printing Print in draft mode (uses less ink) Exhibits and presentation materials: Same suggestions as handouts above; and Reuse display boards, utilize both front and back sides Use low-emitting materials for exhibit displays Recycle cardboard and other packaging materials For the participants not in the building: can they participate by internet/phone? Contact the expected meeting participants ahead of time and present them with the option
of a video/phone conference via the internet/phone, if appropriate. Costs associated with technical support may still be less than travel/fuel costs in some cases.
What if travel cannot be avoided? Can attendees carpool/carshare? Provide attendees with mass transit options, such as CTA or Pace Bus, including directions. Encourage walking and biking by selecting accessible venues, including directions. If overnight stays are involved, suggest hotels nearest the meeting venue that are the most
environmentally friendly (www.greenhotels.com). Consider moving the meeting to the hotel if majority of participants are staying at the same hotel, reducing the need for transportation to and from the hotel.
AuAP-7
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
If the meeting is all day or multiple days in a row, how can it be catered in an environmentally friendly way? Serve drinks from pitchers, reusable utensils and dishes, and request local produce to cut
down on waste when catering for large groups. Plan for the pick-up and compost or donation of leftover food to reduce waste. What if the meeting is held annually? Plan for annual meetings at times of the year when temperatures are less extreme to reduce
energy consumption due to the use of air conditioning/heat. Additional details if conducting off-site meetings, such as a conference or workshop…
Ensure that off-site meeting locations accommodate opportunities for recycling. Recycle newspapers, cans, and glass, including those from your guest room, in marked
containers in the conference area. Participate in the hotel's water, energy, and detergent conservation efforts by following
the instructions posted in your room. Note the conference's efforts to reduce the use of paper by limiting conference handouts
at registration, using folders or handouts printed on high post-consumer recycled content paper, using vegetable-based ink, and encouraging presenters to limit handouts.
Thank the hotel or off-site location host for providing recycling opportunities, reusable utensils and dishes for breaks, etc.
When the conference/meeting/workshop is over…
Collect reusable business card holders/name tags in a bin after last meeting. Collect presentation materials that are not needed by the attendees that can be donated
to local schools, reused or recycled. Have attendees fill out an online survey allowing for feedback about the meeting and
vendors for future reference and improvement. Follow up after the meeting with participants to share green success stories and
lessons-learned including statistics from the meeting, such as quantities of recycled materials. Also include a summary document that provides details of the green meeting.
AuAP-8
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
IMPLEMENTATION
1. Make certain that all appropriate recycling bins are located in public meeting areas and conference rooms.
2. Develop message boards for conference rooms, meeting areas, and copy/production areas. (see following pages)
3. Electronically distribute green meeting practices to all staff, team members and routine stakeholders.
4. Post green meeting practices in meeting rooms. 5. Post green meeting practices on Intranet sites (internal). 6. Post green meeting practices on Internet sites (external, public). 7. Include green meeting practices reminders routinely and during annual team meetings. 8. Include a green meeting reminder at the end of meeting minutes to read “This meeting
was conducted in accordance with green meeting practices.”
AuAP-9
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
AP ADMINISTRATIVE PROCEDURES
AP.2 Prerequisite 2 – Document Reduction and Recycling Initiative (DRRI)
Required
INTENT
Reduce the volume of paper and facilitate the recycling of documents. REQUIREMENTS Follow the Document Reduction and Recycling Initiative (DRRI), which has the following main objectives:
1. Identify and issue only essential paper copies. 2. Promote the use of centralized review rooms for documents and drawings.
3. Provide a simple, yet effective means for recycling documents.
SUBMITTALS None TECHNOLOGY/STRATEGY Identify and Issue Only Essential Paper Copies (Goal: Minimize Quantities) Start by producing only electronic copies. Use electronic distribution media for all documents whenever possible, such as; FTP sites, websites, emails, CDs, digital document libraries, memory sticks, etc. To ensure that only essential paper copies are prepared, there are four (4) questions that need to be asked of each recipient insisting on paper copies:
1. Have you historically performed or do you intend to perform a full review of the applicable document?
2. Does your review require you to look at the entire document/set of plans or only specific sections?
3. Could you conduct your review of the document/plan set and/or the specifications from a digital version?
4. Would you consider reviewing the documents in a designated review room? If it is ultimately determined that paper copies are necessary, follow guidance provided in SAM Credit AP.1 Prerequisite 1 – Green Meetings.
AuAP-10
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Centralized Review Rooms (Goal: Centralize Work Function & Minimize Waste)
The DRRI acknowledges that for reviewers to provide a comprehensive review of any design, a complete set of plans must be provided.
A centralized review room should be in a relatively quiet location accessible to all employees needing to review the materials.
Review the use of centralized review rooms periodically to determine use and find ways to promote additional usage by reviewers.
Document Disposal and Recycling (Goal: Minimize Waste, Support Recycling)
The DRRI encourages the recycling of obsolete paper. Documents/plan sets having sensitive information must be safely and securely recycled. The ideas provided below will assist in recycling of documents:
Ask reviewers to return obsolete documents to the centralized review room.
Setup a notification informing reviewers to return obsolete documents to the nearest recycling location.
Add reminders to documents, such as “Return obsolete documents when review concludes” to closeout checklists.
CASE STUDY Resource Conservation San Francisco International Airport – San Francisco, California
As part of its zero-waste program, SFO has implemented several solid waste reduction measures, including the resource conservation program. The goal of this program is to “educate, encourage and persuade the Airport staff, tenants, and the general public to generate less waste in the course of their daily activities at or travel through the Airport.” The program includes the following:
Paper use reduction. SFO has allocated paper use to each Airport Division at 80 percent of the previous year’s consumption, requiring submittal of a special request if the allocation is prematurely exhausted.
Double sided printing and copying. All SFO printers and copiers have been programmed to produce double sided prints or copies. Educational signage is also posted at all copying machines to enhance the message.
Electronic document transfer. SFO encourages all staff to transmit documents electronically.
AuAP-11
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
AP ADMINISTRATIVE PROCEDURES
AP.3 Corporate Sustainability Policy
1 Point – Required for CT-OM Mentor Certification
INTENT
In keeping with the spirit and intent of this Manual, it is strongly encouraged that companies working in support of CDA on any project establish and adopt their own corporate policy on sustainable practices.
REQUIREMENTS
Establish and adopt a Corporate Sustainability Policy.
SUBMITTALS
Provide an electronic copy of the company’s Corporate Sustainability Policy.
NOTE: If available, please provide an electronic copy of your annual sustainability report documenting any new measures and results.
CASE STUDY Sustainability: Essential to Our Business Coca-Cola
In 2007, the Coca-Cola Company created LIVE POSITIVELY to bring structure and visibility to existing sustainability programs within the company and the Coca-Cola system, as well as to form a program that associates can engage with and use to further understand the company’s sustainability commitment. LIVE POSITIVELY provides a framework to help Coca-Cola consider sustainability as part of everything they do.
The LIVE POSITIVELY sustainability framework was created on the foundation of the company’s commitment to making a positive difference in the world, and it is embedded within the entire business at every level. The LIVE POSITIVELY framework consists of seven core areas key to our business sustainability: Beverage Benefits; Active Healthy Living; Community; Energy Efficiency and Climate Protection; Sustainable Packaging; Water Stewardship; and Workplace. The Coca-Cola system has defined principles for each of the core areas and has set goals for each. In addition to these goals, some of their bottling partners have set their own goals in the core areas and report on their individual business progress in their sustainability reports.
www.sustainability.thecoca-colacompany.com
AuAP-12
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Starbucks Shared Planet Starbucks
The corporation has undertaken actions to reduce their environmental impact and share in their customer’s commitment to the environment. An annual environmental stewardship report is produced to highlight the company’s efforts and successes. At the store level, energy and water conservation and other green building strategies are key priorities. Recycling and other forms of waste diversion are also a focus, and the company has set a goal of 100 percent reusable or recyclable by 2015.
http://www.starbucks.com/responsibility/environment
AuAP-13
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
AP ADMINISTRATIVE PROCEDURES
AP.4 Green Procurement Policy
1 to 4 points
INTENT
Reduce the environmental impact of products and services by developing a Green Purchasing Program. REQUIREMENTS
Refer to SAM Appendix AP-A – Green Product Listing for products and their minimum required content levels. Points for this credit will be awarded based on the number of green products, as defined in Appendix AP-A, procured for general day-to-day office use. The party completing the checklist should only count green products procured for the local office, as opposed to a global level policy. Points are awarded as follows*:
Number of Green Products Procured Points 1-2 1 3-5 2
6-11 3 12+ 4
* Green products not listed in SAM Appendix AP-A must be approved by the SRP in order to receive
points. AND Use a company developed Procurement Policy that finds and evaluates green products prior to purchasing products and services.
SUBMITTALS
Include descriptive narrative in the SAM Checklist of items purchased and used.
NOTE: If available, please provide an electronic copy of your green procurement policy.
TECHNOLOGY/STRATEGY
Introduce environmentally conscious purchasing into company practices. The policy needs to clearly define an objective and establish a sustainability claims verification procedure that can be replicated as necessary. Verification procedures may rely on product certifications such as Green Seal and ENERGY STAR. Evaluate the items that are purchased, identify more environmentally friendly alternatives, and establish a policy to purchase these alternatives when economically feasible. Work with suppliers to identify sustainable products that meet the company’s needs.
AuAP-14
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Standard Practice
None
Recommended Practice
Purchase items with the minimum content levels specified in SAM Appendix AP-A – Green Product Listing
Purchase items in bulk to reduce packaging, transportation impacts and costs When using a company developed policy, the following resources can be used to create
a Procurement Policy. Resources include but are not limited to: o U.S. Environmental Protection Agency’s Environmentally Preferable Purchasing
(EPP) Program guidelines – The EPP Program information can be found on the associated website: www.epa.gov/epp
o U.S. Environmental Protection Agency’s Comprehensive Procurement Guidelines (CPG) – The CPG includes an index of products and their recommended recycled content. More information can be found on the associated website: www.epa.gov/epawaste/conserve/tools/cpg/products/index.htm
o U.S. Environmental Protection Agency’s Water Sense – The partnership program by promoting water efficiency and enhancing the market for water-efficient products, programs and practices. More information can be found on the associated website: www.epa.gov/WaterSense/
o DOE’s Alternative Fuels and Advanced Vehicles Data Center – The data center provides a wide range of information and resources to enable the use of alternative fuels, in addition to other petroleum reduction options such as advanced vehicles, fuel blends, idle reduction and fuel economy. More information can be found on the website: www.afdc.energy.gov/afdc/
o Fair Trade Products – Purchase fair trade products instead of regular products in order to build equitable and sustainable trading partnerships. Examples of some fair trade products include; coffee, bags, boxes, artwork, chocolate, sugar, etc. More information can be found on the Fair Trade Federation’s website: www.fairtradefederation.org
o USDA’s BioPreferred Designated Products – The program aims to increase the purchase and use of renewable, environmentally friendly biobased products while providing “green” jobs and new markets for farmers, manufacturers and vendors. More information can be found on the associated website: http://www.biopreferred.gov/Biobased_Products.aspx
Best Available Practice
None
AuAP-15
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
CASE STUDY
Environmental Purchasing Policy Port of Seattle – Seattle, Washington
The Port of Seattle, which is the authority over Seattle-Tacoma International Airport, has initiated a new strategic plan for 2010’s Priority Actions that consist of an Environmental Purchasing Policy that will execute a contract for the purchase of sustainable office products and paper. The policy focuses on saving money, increasing local products and considering the life cycle effects of a given product. Initial stages focused on the purchase of recycled paper and office products; as of December 2010, 98 percent of paper purchased by Port staff contained recycled content.
http://www.portseattle.org/Environmental/Materials-Management/Green-Purchasing/Pages/default.aspx
Green Procurement Los Angeles World Airports - Los Angeles, California For over 10 years, Los Angeles World Airports (LAWA) has been promoting the use of environmentally and socially responsible products in its operations and is committed to increasing its use of such products. LAWA has developed green procurement language to be included in is procurement contracts to encourage the purchase of environmentally and socially responsible products. As part of the Requests for Proposals and Request for Bid documents, LAWA has purchased recycled content office paper, recycled content plastic bags, Green Seal custodial products and other cleaning chemicals. Green Seal is an independent non-profit organization that develops environmental standards for cleaning and other consumer products. http://www.lawa.org/welcome_LAWA.aspx?id=1036
AuAP-16
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
AP ADMINISTRATIVE PROCEDURES
AP.5 Recycled Content Paper
1 to 3 points
INTENT
Reduce the need for virgin materials, energy, and waste associated with the production of paper by promoting the use of recycled content paper. REQUIREMENTS
Purchase and utilize print/copy paper that is chlorine-bleach free.
AND
For all office paper purchased for routine daily business administration and operations, point values will be assigned based on the recycled content of the paper. Up to 3 points are available by using paper with the following attributes:
SAM Credit Post-consumer recycled content Points
AP.5.1 30% 1
AP.5.2 50% 2
AP.5.3 100% 3
Calculate post-consumer recycled content of office paper using a weighted average based on estimated usage. If the paper is chlorine-bleached, for the purposes of the calculation, it shall be assumed that the post-consumer recycled content is 0% regardless of what it actually is. Example: An office uses 50 boxes of chlorine-free paper with a post-consumer recycled content of 30%, 50 boxes of chlorine-free paper with a post-consumer recycled content of 90%, and 20 boxes of chlorine-bleached paper with a post-consumer recycled content of 100%. The weighted average of all the paper used is 50% and therefore 2 points would be awarded for this credit. Note that the 20 boxes of chlorine-bleached paper are assumed to have 0% recycled content for the purposes of the calculation.
(50/120)(30%) + (50/120)(90%) + (20/120)(0%) = 50% recycled content SUBMITTALS
Include descriptive narrative on the SAM Checklist.
TECHNOLOGY/STRATEGY
The purchase and use of recycled paper assists in closing the recycling loop by utilizing paper that is made from recovered waste paper.
AuAP-17
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
This credit is intended to:
Conserve natural resources Save energy Reduce environmental impacts Reduce pollution Reduce paper waste
Standard Practice None Recommended Practice
Whenever applicable, purchase and utilize recycled office paper in daily business administration and operations.
Best Available Practice None
AuAP-18
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
APPENDIX AP-A
GREEN PRODUCT LISTING
SUSTAINABLE AIRPORT MANUAL - GREEN PRODUCT LISTING
Product Product Type Content Levels
Fertilizer Fertilizer from recovered organic materials 71% minimum biobased contentGarden hose 60-65% postconsumer rubber and/or plasticSoaker hose 60-70% postconsumer rubber and/or plasticPaper-based hydraulic mulch 100% postconsumer paperWood-based hydraulic mulch 100% recovered wood and paper
Lawn and garden edging --- 30-100% recovered plastic and/or rubber, including 30-100% postconsumer content75-100% recovered high density polyethylene, including 25-100% postconsumer content100% recovered mixed plastics/sawdust, including 50% postconsumer content95% recovered high density polyethylene/fiberglass, including 75% postconsumer content95-100% other mixed recovered resins, including 50-100% postconsumer content
Furniture structure 75-100% recovered aluminumCellulose loose-fill and spray-on 75% postconsumer paperParticleboard/fiberboard component 80-100% recovered wood or wood compositeParticleboard/fiberboard component 100% recovered agricultural fiberFabric 100% postconsumer polyethylene terephthalatePlastic furniture component 95% recovered high density polyethylene, including 70-75% postconsumer contentRemanufactured or refurbished furniture 25-75% recovered material, including 25-75% postconsumer contentPlastic 20-100% postconsumer plastic Steel 25-30% recovered steel, including 16% postconsumer contentPaperboard 25-50% recovered corrugated paper, including 25-50% postconsumer contentPaperboard 40% postconsumer solid fiber paper boxesPaperboard 100% recovered industrial paperboard, including 40-80% postconsumer content
Carpet Polyester carpet face fiber 25-100% recovered polyethylene terephthalate, including 25-100% postconsumer contentCarpet Woven, tufted, or knitted fiber and a backing system 7% minimum biobased content
Bonded polyurethane 15-50% old carpet cushion, including 15-50% postconsumer contentJute 40% postconsumer burlapSynthetic fibers 100% recovered carpet fabrication scrapRubber 60-90% recovered tire rubber, including 60-90% postconsumer contentRubber 90-100% postconsumer rubberPlastic 90-100% recovered plasticRubber 85-100% recovered rubber, including 75-100% postconsumer contentPlastic 100% recovered plastic, including 10-100% postconsumer contentBlends 100% postconsumer rubber/plastic composite
Paint -- consolidated latex paint --- 100% postconsumer contentWhite, off-white, pastel colors 20% postconsumer contentGrey, brown, earth tones, and other dark colors 50-99% recovered material, including 50-99% postconsumer content
Diesel fuel additives --- 90% biobased contentGreases - Truck --- 71% minimum biobased contentMobile equipment hydraulic fluid --- 25% re-refined oil in the base stock or 44% biobased contentPenetrating lubricants --- 68% biobased contentRe-refined lubricating oils --- 25% re-refined oil in the base stock
--- 25-30% recovered steel, including 16% postconsumer content100% postconsumer high density polyethylene100% recovered plastic, including 90-100% postconsumer content 100% recovered plastic composites, including 50-100% postconsumer content25% postconsumer aluminum15-40% recovered concreteSteel - See EPA guidance at www.epa.gov/cpg
Plastic fencing --- 90-100% recovered plastic, including 60-100% postconsumer content100% recovered plastic, including 90-100% postconsumer content 95-100% recovered plastic composites, including 50-75% postconsumer contentSteel - See EPA guidance at www.epa.gov/cpg25% postconsumer aluminum
Playground surfaces --- 90-100% postconsumer rubber or plasticRunning tracks --- 90-100% postconsumer rubber or plastic
Adhesive and Mastic Removers --- 58% minimum biobased contentBathroom and Spa Cleaners --- 74% minimum biobased contentCarpet and Upholstery Cleaners - General Purpose
--- 54% minimum biobased content
Carpet and Upholstery Cleaners - Spot Removers
--- 7% minimum biobased content
Dust Suppressants --- 85% minimum biobased contentFloor Strippers --- 78% minimum biobased contentGlass Cleaners --- 49% minimum biobased contentGraffiti and Grease Removers --- 34% minimum biobased contentHand Cleaners --- 64% minimum biobased contentHand Sanitizers --- 73% minimum biobased contentHousehold Cleaners, General Purpose
--- 39% minimum biobased content
Industrial Cleaners --- 41% minimum biobased contentLaundry Products - General Purpose
--- 34% minimum biobased content
Laundry Products - Pretreatment/ Spot Removers
--- 46% minimum biobased content
Multipurpose cleaners --- 56% minimum biobased contentSorbents --- 89% minimum biobased content
---
Floor tiles (heavy duty/commercial)
Hoses
Hydraulic mulch
Plastic lumber landscaping timber and posts
---
Office furniture
Office recycling containers
Mats
Vehicle Maintenance
Paint -- reprocessed latex paint
Bike racks
Park benches and picnic tables
Playground equipment
---
Landscaping Products
Building Interior
Building Finishes
Hardscape Accessories
Carpet cushion
Cleaning Products
AP - A - 1
SUSTAINABLE AIRPORT MANUAL - GREEN PRODUCT LISTING
Product Product Type Content Levels
Bathroom tissue --- 20-100% recovered fiber, including 20-60% postconsumer fiberFacial tissue --- 10-100% recovered fiber, including 10-15% postconsumer fiberGeneral purpose industrial wipers --- 40-100% recovered fiber, including 40% postconsumer fiberPaper towels --- 40-100% recovered fiber, including 40-60% postconsumer fiberPlastic trash bags --- 10-100% postconsumer plastic
Disposable containers --- 72% minimum biobased contentDisposable cutlery --- 48% minimum biobased contentPaper napkins --- 30-100% recovered fiber, including 30-60% postconsumer fiberPaper tray liners --- 100% recovered fiber, including 50-75% postconsumer fiber
Food cleaners --- 53% minimum biobased content
Hydraulic fluids - stationary equipment
--- 44% minimum biobased content
Hydraulic fluids - mobile equipment --- 25% re-refined oil in the base stock or 44% minimum biobased content
2-cycle engine oils --- 34% minimum biobased contentConcrete and asphalt release fluids --- 87% minimum biobased contentChain and cable lubricants --- 77% minimum biobased contentEngine lubricating oils --- 25% re-refined oil in the base stockForming lubricants --- 68% minimum biobased contentGear lubricants --- 25% re-refined oil in the base stock or 58% minimum biobased contentGreases - general --- 49% minimum biobased contentGreases - food grade --- 42% minimum biobased contentGreases - multipurpose --- 72% minimum biobased contentGreases - rail track --- 30% minimum biobased contentGreases - truck --- 71% minimum biobased contentFirearm lubricants --- 49% minimum biobased contentMetalworking fluids - general purpose soluble, semi-synthetic, and synthetics oils
--- 57% minimum biobased content
Metalworking fluids - high performance soluble, semi-synthetic, and synthetics oils
--- 40% minimum biobased content
Metalworking fluids - straight oils --- 66% minimum biobased contentPenetrating lubricants --- 68% minimum biobased content
Alumina oxide --- 100% postconsumer fused alumina oxideCoal ash --- 100% recovered bottom ashGlass --- 100% postconsumer glassGlass/plastic --- 100% recovered glass/plastic, including 20% postconsumer contentSlag --- 100% covered coal slagSlag --- 100% recovered copper and nickel slagSteel --- 25-100% recovered steel, including 16-67% postconsumer contentWalnut shells --- 100% recovered walnut shells
All --- 54% minimum biobased content
All --- 93% minimum biobased content
All --- 41% minimum biobased content
Steel drums --- 25-30% recovered steel, including 16% postconsumer contentPlastic drums --- 30-100% recovered high density polyethylene, including 30-100% postconsumer contentFiber drums --- 100% postconsumer paper
Polyester strapping --- 50-85% recovered polyethylene terephthalate, including 50-80% postconsumer contentPolypropylene strapping --- 10-40% recovered polypropyleneSteel strapping --- Steel - See EPA guidance at www.epa.gov/cpg
Rubber --- 85-100% recovered rubber, including 75-100% postconsumer contentPlastic --- 100% recovered plastic, including 10-100% postconsumer contentRubber/plastic --- 100% postconsumer rubber/plastic composite
Wooden pallets --- 95-100% postconsumer woodPlastic pallets --- 100% postconsumer plastic lumberPlastic pallets --- 25-50% postconsumer thermoformedPaperboard pallets --- 50% postconsumer paperboard
All --- 65% minimum biobased content
Mats
Pallets
Parts wash solution
Blasting grit
Corrosion preventatives
De-Icers - general purpose
Industrial cleaners
Industrial drums
Manual-grade strapping
Oils, Lubricants, Grease
Cafeteria Equipment and Products
Hydraulic Fluids
Paper and Plastic Janitorial Supplies
Cafeteria Services
AP - A - 2
SUSTAINABLE AIRPORT MANUAL - GREEN PRODUCT LISTING
Product Product Type Content Levels
Biobased --- 89% minimum biobased contentPaper --- 100% recovered paper, including 90-100% postconsumer contentOrganic/multi materials --- 100% recovered other organics/multi-materialsPlastic --- 25-100% recovered plasticsTextiles --- 95-100% recovered textiles, including 95-100% postconsumer contentWood --- 100% recovered woodFluid-filled transformers Synthetic ester-based 66% minimum biobased content
Vegetable oil-based 95% minimum biobased content
All --- 59% minimum biobased content
Membrane concrete sealers --- 11% minimum biobased contentPenetrating liquids --- 79% minimum biobased content
Sorbents
Water tank coatings
Wood and concrete sealers
AP - A - 3
…The purpose of this planning chapter is to be an overarching umbrella over the rest of the document…Stake holders are going to be reviewing this document. Many don’t realize they are stakeholders yet…
James Crites Dallas-Ft. Worth International Airport
…What we’re doing here will help us leave a legacy behind
for the next generation…
Rosemarie S. Andolino Commissioner
Chicago Department of Aviation
airportsgoinggreen.org
Project Submittal Forms, Comments, Case Studies, Lessons-Learned, New
Technologies
Please email:
AuPL-1
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
PLANNING TABLE OF CONTENTS
PLANNING INTRODUCTION ………... PL-2 PL.1 Define Sustainability Vision Statement ………... PL-10PL.2 Determine Key Stakeholders and Hold Initial Project Meeting to
Discuss Sustainability Goals ………... PL-11
PL.3 Sustainability Baseline Assessment and Cost/Benefit Analysis ………... PL-14PL.4 Develop a Sustainability Schematic ………... PL-17PL.5 Project Meeting to Finalize Sustainability Schematic ………... PL-23PL.6 Close the Feedback Loop at Project Completion ………... PL-24 Appendix PL-A Planning Checklist ………... PL-A-1
AuPL-2
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
INTRODUCTION
The Sustainable Airport Manual (SAM) Planning Chapter is intended to address the conceptual planning of the airport’s physical environment to facilitate implementation of design, construction, and/or operation and maintenance in a sustainable manner. The Planning chapter also addresses operational guidance documents that outline procedures for the airport’s compliance with federal, state, and local standards, codes, and mandates, as well as daily operational best management practices. Planning is an ongoing pursuit that establishes qualitative and quantitative goals for all projects of all sizes and scopes at the earliest stage based on stakeholder input, collaboration and commitment.
Planning begins at the earliest stages of a project and thereby becomes part of the sustainable fabric and vision that influences later stages of design, construction, and operation for all projects, large and small. With the integration of sustainability into every aspect of airport functions, the consideration of sustainability will become more routine. Moreover, the inclusion of sustainability considerations at the planning stage will result in greater benefits and lower costs than the addition of sustainability features at a later date. Understanding the needs and limitations of airport stakeholders and system conditions is also an important part of planning in order to achieve long term effectiveness.
The Planning chapter outlines a broad integrated approach, customizable to organizational and system conditions and shaped by input from stakeholders. Once system conditions (and options) are defined and understood, the airport can then look to one or more sustainability strategies for inspiration and development of specific goals. The Chapter provides guidance and support in developing, maintaining, or increasing the performance of sustainable initiatives within the overall framework of each airport planning project. It considers sustainable design concepts throughout the planning of airport development projects and programs from inception, thereby increasing the ability of each project to meet and to hopefully exceed various initiatives based on each airport’s optimal conditions.
The approach to sustainability planning outlined in this chapter strives to collectively elevate everyday planning to proactively address environmental issues beyond minimum standards and embrace sustainability as an important achievement. Many airports often struggle with the daily reality of their economic and social concerns, like balancing limited budgets or satisfying customer demands, where sustainability opportunities can be overlooked. Through this process, all of the required elements of the standard planning process can be achieved, while embracing sustainable practices that can potentially reduce the environmental impact of the built environment while at the same time creating financial and operational benefits for a project, and social benefits for the community at large.
The sustainable planning path outlined here will help to define the airport’s sustainability goals and objectives for each project based on system conditions and unique situations. From there, the key stakeholders collectively develop the project’s “Sustainability Schematic,” which is an overall plan outlining the measurable sustainability targets and goals for the project that, when finalized, will become part of the official plan for the project, such as a Project Definition Document (PDD) and/or Capital Improvement Program (CIP) Application, or other applicable planning documentation.
AuPL-3
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
APPLICABILITY
All projects begin with the development of a plan. That plan may be a major program, such as an airport master plan, or it may be a relatively small improvement, such as the addition of a new jet bridge or an update to an airport’s Stormwater Pollution Prevention Plan. Just like cost estimates and schedules, sustainability considerations and goals need to be integrated into the planning process for all projects, regardless of size and scope. Integration of sustainability considerations into the planning process sets the groundwork for inclusion of sustainability features as a project proceeds through the design, implementation, and operational stages.
Planning projects that would be applicable to this SAM Planning Chapter include, but are not limited to the following:
Master Plan
Maintenance Plan
Utilities Plan
Operations Plan
Construction Plan
Deconstruction Plan
Asset Maximization Plan
Facilities Plan
Existing Facility Optimization Plan
Terminal Renewal/Improvement Plan
Facility Re-Use Analysis
Land Use Plan
Noise Compatibility Plan
Regulatory/Code Requirements
o Title V Permit Application or Update
o Air Quality State Implementation Plan (SIP) Update
o NPDES Permit Application or Update
o Stormwater Pollution Prevention Plan (SWPPP) Update
o USACE 404 Permit Application
Other Projects or Strategic Initiatives
o Demand Driven Projects
o Customer Service Projects
o Revenue Opportunities
AuPL-4
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
PROCESS
The process of sustainable airport planning as described in this SAM Planning Chapter involves the creation of an overall plan outlining the measurable sustainability targets and goals for the project that, when finalized, will become part of the official plan for that project, function, or activity. This is to be accomplished primarily through the development of a “Sustainability Schematic.” The sustainable airport planning process can be summarized by reviewing an outline of the credits included in the Chapter:
1. Define Sustainability Vision Statement (SAM Credit PL.1 Prerequisite 1)
2. Determine Key Stakeholders and hold Initial Project Meeting to Discuss Sustainability Goals (SAM Credit PL.2 Prerequisite 2)
3. Sustainability Baseline Assessment and Cost/Benefit Analysis (SAM Credit PL.3 Prerequisite 3) Requires the completion of a preliminary sustainability baseline assessment and the completion of a preliminary cost/benefit analysis for all project alternatives, including the no-project alternative. The cost/benefit analysis enables a comparison of initial versus longer term operational and maintenance costs, while also considering the potential environmental and social impacts that may occur as a result of the project.
4. Develop a Draft Sustainability Schematic (SAM Credit PL.4 Prerequisite 4) Requires the development of a Sustainability Schematic which outlines the steps for sustainability considerations in planning any project or activity, and addresses the following major considerations:
a. Identify and establish sustainability objectives, target goals, and minimum thresholds b. Identify sources of funding c. Provide for and conduct education and public outreach initiatives d. Plan for the integration of SAM guidelines into the specific project elements, as
appropriate to the size and scope of each project e. Plan for sustainable operation and maintenance of completed projects/programs/facilities f. Establish plan to close the feedback loop
5. Project Meeting to Finalize Sustainability Schematic (SAM Credit PL.5 Prerequisite 5)
6. Close the Feedback Loop at Project Completion (SAM Credit PL.6 Prerequisite 6)
AuPL-5
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Within the Chapter’s main body, each sustainable planning “Credit” has five subsections: Intent, Requirements, Submittals, Technology/Strategy, and Case Studies, as described below:
Intent: The primary motivations for any sustainable practice.
Requirements: Specifies institutional, operational, and functional elements that satisfy the intent. The prerequisites must be achieved; other credits are optional, but contribute to the overall sustainable planning process for the project.
Submittals: Required and supporting documentation and/or information required to achieve applicable prerequisites or credits. This documentation indicates how the requirements are being met.
Technology/Strategy: Highlights specific ways of meeting the recommendations within the scope of each specific credit. Case studies where available, are presented to help guide the application of sustainable credits to planning projects and efforts.
Case Study: Examples of credit intent “in action” at airports and/or other industry facilities.
While not all strategies will be applicable to every project, planners are highly encouraged to think creatively and to consider the intent of each issue throughout the decision process. In all cases, it is the responsibility of the planning team to evaluate and review with the appropriate CDA managers any anticipated cost or schedule impact.
AuPL-6
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
THRESHOLDS AND GUIDANCE
For all planning projects involving CDA owned, operated, or leased facilities and for all planning projects involving resources for which CDA has regulatory responsibilities, CDA encourages the targets or goals listed in the following table, as appropriate and applicable to the size and scope of each project. Although the targets or goals included in the following table might be above and beyond the thresholds established by the other chapters of this Manual, the CDA strives for them to be attainable and therefore, encourages innovation and forward-thinking in order for their achievement.
Topic Description and/or Example Measure(s)
Encouraged Target or Goal
Site Selection Locate near mass transit (bus, CTA rail lines, Metra, etc.) and carpooling. Protect and restore site, while minimizing wildlife attractants.
Encourage employees and visitors to utilize mass transit
Protect natural resources
Minimize attraction of wildlife
Stormwater Minimize impervious surfaces, incorporate vegetated roofs, curb breaks and bioswales. Harvest rainwater for reuse.
Slow, intercept and encourage infiltration (landside only), reuse, protect and treat stormwater whenever possible to minimize contamination and runoff
Recover and recycle deicing fluid
Reduction of Heat Islands, roof and non-roof
Examples include, but are not limited to green roofs, green walls, white roofs, and shading. Minimize paved surfaces. Use light colored/high-albedo materials for pavements, roadways, parking lots, sidewalks and plazas.
Integrate into all projects involving structures (occupied and unoccupied)
AuPL-7
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Topic Description and/or Example Measure(s)
Encouraged Target or Goal
Water Efficiency Use low-flow, high-efficiency plumbing fixtures (USEPA WaterSense). Recycle vehicle washwater and reclaim water from cooling towers. Use native, drought tolerant landscaping to minimize maintenance and irrigation needs.
Reduce use of potable water resources by 40%
Energy Efficiency Improve airfield and landside – design for efficiency. Provide pre-conditioned air and 400 Hz power at aircraft gates, and hydrant fueling. Utilize natural daylighting, heat, absorption cooling and ventilation. Minimize building energy loss. Incorporate efficient lighting, HVAC, and human-demand controls, such as occupancy sensors
Reduce total project energy use by 50%
Equipment and Appliances Optimize energy performance, provide high efficiency ,motors, pumps, systems and equipment
100% ENERGY STAR compliant
Generation and/or Integration of Renewable Energy
Examples include, but are not limited to solar applications, wind turbines, geothermal.
Consideration of onsite renewable energy options for at least 5% of total energy usage – dependent upon life cycle costs and benefits achieved
Green Power Utilization of green resources such as biomass, solar, wind, and water to generate electricity.
Encourage development and use of grid-source, renewable energy technologies on a net zero pollution basis, as applicable and appropriate
Materials and Resources Utilize pre-existing buildings and resources.
Reuse and salvage existing resources and materials whenever possible
AuPL-8
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Topic Description and/or Example Measure(s)
Encouraged Target or Goal
Waste Management and Recycling
Divert waste from landfill disposal 100% diversion of recyclable, reusable, or compostable waste from landfill disposal
100% of soils kept onsite (Balanced Earthwork Plan)
Recycled Content of Materials Use materials and products that incorporate recycled content materials, therefore reducing impacts resulting from extraction and processing of new virgin materials
All products contain some percentage of recycled content where applicable
Use of Local/Regional Materials Use materials and products that are extracted and manufactured within the region, thereby supporting the regional economy and reducing the environmental impacts resulting from transportation
100% usage of materials and products that are extracted and manufactured within in a 250 mile radius from the site
Alternative Fuels/Vehicles Examples include, but are not limited to electric, hybrids, CNG, Biodiesel, ULSD, Propane
100% usage of alternative fuels/alternatively fueled vehicles in all vehicles used on airport property unless no reasonable alternatively fueled vehicle option exists
SUBMITTALS
Incorporation of sustainable elements into planning efforts is tracked using the SAM checklist provided in Appendix PL-A – Planning Checklist along with any paperwork and documentation required in the SAM Credits.
SAM GREEN AIRPLANE CERTIFIED PLANNING PROJECTS IMPLEMENTATION AND REVIEW PROCESS
The SAM and its supporting documentation are administered by the Sustainable Review Panel (SRP), which currently consists of representatives of the CDA Management Staff, OMP Project Management Office (PMO) and Master Civil Engineer (MCE), and Airport Planners actively involved in CDA projects. The composition of the SRP is intended to be dynamic depending on each project’s unique needs. The primary tasks of the SRP are to oversee the application of the Manual and review planning submittals for their compliance with the Manual. Planning projects submitted to the SRP for review shall be evaluated to ensure all prerequisites have been met as
AuPL-9
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
outlined in this chapter. Planning projects that meet all planning prerequisites set forth by this Manual will be recognized as “Green Airplane Certified” by the CDA.
Just as any airport can easily customize the Chicago-specific guidance elements within the SAM, the composition of a SRP can also be tailored to an airport’s needs.
All planning projects conducted by or under management of the CDA will follow these procedures. For any and all sustainability-related questions and/or submittals, please use the following email address to submit forms electronically (preferred method):
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
AuPL-10
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
PL PLANNING
PL.1 Prerequisite 1 – Define Sustainability Vision Statement
Required
INTENT The Project Manager shall define in writing, a project description and sustainability vision statement for the project. REQUIREMENTS Regardless of project size, scope, or scale, create a project description outlining what is to be improved, retrofit, upgraded, replaced, enhanced, or corrected as a result of the project completion. The description of the project should be as comprehensive as possible, and include as appropriate, regulatory, guidance, and operational documents. Define in writing, the vision statement, which at a minimum, clearly states the project’s sustainability goals, objectives and opportunities. Whenever possible, specific measures should be listed (e.g., incorporation of solar) including goals and targets (e.g., 50% energy use reduction over standard practices). The vision statement will be unique to every project and situation. It can be simple and goal oriented, or more detailed with thoughts on achieving both goals and specific measures (e.g., to be LEED certified). SUBMITTALS
1. Project Description 2. Sustainability Vision Statement
AuPL-11
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
PL PLANNING
PL.2 Prerequisite 2 – Determine Key Stakeholders and Hold Initial Project Meeting to Discuss Sustainability Goals
Required
INTENT
Determine key stakeholders for the planning project and hold an Initial Project Meeting to discuss project sustainability goals. The meeting with key stakeholders will provide a forum for discussion regarding the overall sustainability goals for the project as initially defined in the Sustainability Vision Statement for the project, while capturing innovative ideas and concepts, and resolving any potential conflicts. As a result of the meeting, it is anticipated that the method and required inputs for the cost/benefit analysis will be determined (see SAM Credit PL.3 Prerequisite 3 – Sustainability Baseline Assessment and Cost/Benefit Analysis), as well as the necessary environmental approvals, permitting requirements, and any other additional approvals that would be needed as part of the project. All of this information will factor into the development of the project’s Sustainability Schematic as described in SAM Credit PL.4 Prerequisite 4 – Develop a Sustainability Schematic. In addition, as a result of this meeting, the project vision statement (SAM Credit PL.1 Prerequisite 1 – Define Sustainability Vision Statement) may require modification pursuant to the sustainability targets and goals identified for the project.
REQUIREMENTS
Early in the project, hold an initial project meeting with CDA Project Manager, SRP, and all additional key stakeholders involved in planning, design, construction, and daily operation/maintenance, as well as local sustainability leaders, community leaders, schools, and businesses that could potentially be affected by the end result of the overall project effort. Each project is unique and therefore, each stakeholder group will have a unique composition. The intent is to include members who may have an interest in the outcome of the project. Enable members to utilize conference calls, net-meetings, webinars, etc. when unable to attend in person. The purpose of the meeting with key stakeholders is to determine the overall sustainability goals for the project, capture innovative ideas and concepts, resolve any potential conflicts (to the greatest extent possible), determine the method and required inputs for cost/benefit analysis, and to determine the necessary environmental approvals, permitting requirements, and any other additional approvals that would be needed as part of the project.
SUBMITTALS
1. Include a descriptive narrative in the SAM Checklist 2. List of stakeholders, including name, title, and role and/or special interest in project –
noting key stakeholders who did not attend and provide evidence that a separate meeting(s) was held for those who were unable to attend initial meeting
3. Meeting Agenda 4. Meeting sign-in sheet including name, company, title, contact information, and role
on project 5. Meeting Minutes and Meeting materials (presentations, handouts, etc.)
AuPL-12
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
CASE STUDY
Sustainable Master Plan Ithaca Tompkins Regional Airport – Ithaca, New York
Ithaca Airport has designed its latest master plan update with sustainability in mind. The Federal Aviation Administration agreed to fund this sustainable master plan as the first in the U.S. The project was the first to integrate sustainability directly into the entire master planning process, instead of having a stand-alone sustainability plan. This approach was chosen so that there would be consistency and alignment between projects and policies arising from the traditional aspects of a master plan as well as the sustainability considerations.
Significant changes to a traditional master plan included performing baseline assessments of 12 sustainability categories and developing goals and targets for improvement. Because the most sustainable projects are the ones that are never built, the project team looked to meet identified facility needs by maximizing existing infrastructure instead of immediately resorting to new construction. When new construction was deemed necessary, policies were put in place to ensure projects are built as sustainably as possible.
The project commenced with an advisory committee kickoff meeting in September 2009 and progressed through the phases of the project with frequent input from committee members.
A concerted effort was made to increase the diversity of viewpoints on the advisory committee beyond the traditional makeup.
The project team reached out to leaders of local sustainability not-for-profits as well as academic experts from nearby Cornell University and Ithaca College. Public outreach efforts also included a project website with downloadable documents and project updates, online passengers, business, and pilot surveys, and involvement with students at both local universities. Copies of the report are available at: www.flyithaca.com
AuPL-13
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Innovative efforts to increase participation in project-related online surveys included using a donation to the Tompkins County Society for the Prevention of Cruelty to Animals (SPCA), which is a neighbor to Ithaca Tompkins Regional Airport and is the first LEED-Certified animal shelter in the country.
Source: Case Study text and photos provided by, and used with the permission of, C&S Companies and Ithaca Tompkins Regional Airport.
AuPL-14
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
PL PLANNING
PL.3 Prerequisite 3 – Sustainability Baseline Assessment and Cost/Benefit Analysis
Required
INTENT
Perform a preliminary sustainability baseline assessment to represent the no-project alternative for comparison purposes. Perform a preliminary cost/benefit analysis for all project alternatives, including the no-project alternative, in order to compare life cycle costs with the range of potential environmental and social impacts as a result of the project, in order to be able to select the alternative that is the most desirable as measured by the appropriate balance of environmental, social, and financial impacts of the project.
REQUIREMENTS
Complete a preliminary sustainability baseline assessment to represent the no-project alternative. The sustainability baseline assessment could include the following, at a minimum, as appropriate to the size and scope of the project; with the level of analysis within each appropriately tailored to the size and scope of the project:
Emissions inventory Greenhouse gas inventory Electrical usage Water usage Stormwater discharges Waste disposal volumes and destinations Recycling programs Indoor environmental quality Cleaning and maintenance programs
Because every project is different, the specific methods of conducting the analysis are not specified here, but left open for definition and refinement based on the nature of the project. The end result of the analysis is intended to inform decisions on the manner in which the project will or will not proceed, particularly relative to sustainability measures. Some examples of considerations that may be helpful to inform the decision making process may include, but are not limited to the following:
Comparison of initial project costs with and without sustainability initiatives Comparison of longer-term costs for operation and maintenance, with and without
sustainability initiatives (i.e., utilities, staffing, cleaning, replacing) Any other associated cost benefit received not in O&M (i.e., less fees paid, reduced
permitting costs) Anticipated environmental benefits to be realized Consideration of applicable grant incentives, rebates and tax credits that may be
available
AuPL-15
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Using a method, model and/or software deemed appropriate by the key stakeholders and project planning team, perform a preliminary cost/benefit analysis of all project alternatives, including the no-project alternative.
As part of this assessment, it is required to research and identify the potential sources of funding for the project. In addition to airport fund sources, there are many opportunities for grants, rebates, tax incentives and credits available from Federal, State and private sources. For example, www.dsireusa.org/ is a comprehensive source of information on state, local, utility and federal incentives and policies that promote renewable energy and energy efficiency. eCivis® Grants Network™ (www.ecivis.com/) provides grants management software for accurate grants information, reporting, and management used by governments and community organizations.
SUBMITTALS
Results of the sustainability baseline assessment, representing the no-project alternative A copy of the cost/benefit analysis calculations or the report produced by the selected
method software A brief narrative describing the results of the cost/benefit analysis for each project
alternative considered Recommendations of the preferred alternative and the principal reasons for selecting it,
based on the results of the cost/benefit analysis
TECHNOLOGY/STRATEGY Each project is unique, and therefore a particular method of conducting the cost/benefit analysis in not prescribed. The details of the analysis are defined as part of the planning process by the stakeholder group and the project planning team. Examples for cost/benefit analyses include, but are not limited to the following:
California Department of Transportation Guide to Benefit-Cost Analysis: http://www.dot.ca.gov/hq/tpp/offices/eab/LCBC_Analysis_Model.html
The Environmental Valuation and Cost Benefit Analysis web site:
www.costbenefitanalysis.org/ Life Cycle Cost Analysis (LCCA) of project alternatives considered in accordance with
the method described by the following, or similar.
Federal Energy Management Program (FEMP): www1.eere.energy.gov/femp/program/lifecycle.html National Institute of Building Sciences, Whole Building Design Guide: www.wbdg.org/resources/lcca.php Federal Highway Administration: www.fhwa.dot.gov/infrastructure/asstmgmt/lcca.cfm
AuPL-16
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
Life Cycle Assessment (LCA) of project alternatives considered in accordance with the method described by the following, or similar.
ISO 14040, Environmental Management Life Cycle Assessment Principles and Framework: www.iso.org/iso/iso_catalogue/catalogue_tc/catalogue_detail.htm?csnumber=37456 EPA National Risk Management Research Laboratory: http://www.epa.gov/nrmrl/
If applicable, provide analysis of Greenhouse Gas (GHG) Emissions, Global Warming
Potential (GWP) or Ozone Depleting Potential (ODP) of project alternatives, using metrics or indices as described by the following, or similar.
EPA GHG Site: www.epa.gov/climatechange/emissions/index.html EPA GWP Site: www.epa.gov/highgwp/scientific.html EPA ODP Site: www.epa.gov/ozone/climate.html Stockholm Environment Institute (SEI): www.co2offsetresearch.org/aviation/MetricsIntro.html
AuPL-17
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
PL PLANNING
PL.4 Prerequisite 4 – Develop a Sustainability Schematic
Required
INTENT
Integrate sustainability into the earliest possible stage of a project. By using a sustainability schematic, the CDA can utilize or organize various internal and external processes to work together toward the same goal of sustainability. A process or processes may be applicable to different organizations at different times for different projects, but when used within a sustainability schematic, synergies are more easily identified and realized. When finalized, the Sustainability Schematic will become part of the official plan for the project, such as the Project Definition Document (PDD) and/or Capital Improvement Program (CIP) Application, or other planning parameter documentation depending on the type of project.
REQUIREMENTS
For all projects, develop a sustainability schematic that addresses the following major principles:
I. Identify and establish sustainability objectives, target goals, and minimum thresholds a. Project Alternatives (including no-project) and innovations a. Procedures and incentives for Stakeholder involvement b. Sustainability baseline assessment results c. Cost/Benefit Analysis results for each project alternative (including the no-project
alternative) d. Environmental Approvals required as part of the project e. Permits required as part of the project f. All other additional approvals required as part of the project g. Use of additional tools and resources to provide supplemental information, as
deemed appropriate i. Examples tools and resources may include, but are not limited to:
1. Design for the Environment (DFE) 2. Ecological Footprinting (EF) 3. Sustainability Management Systems (SMS) 4. Sustainable Airport Guidance Alliance (SAGA) 5. ACRP Sustainability reporting and guidance
h. Establish measurable sustainability goals and targets and quantifiable metrics for the project, as appropriate as a way of tracking and reporting the success/failure of the project.
i. Examples include, but are not limited to: 1. Percent reduction in energy use per square foot of facilities or on
a per passenger or customer basis 2. Percent increase of renewable energy 3. Percent reduction in water use 4. Reduce number of pollutant exceedences and concentration of
pollutants at the “end of the pipe” (e.g. SADF, pH, TDS, petroleum sheens)
AuPL-18
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
5. Identify and reduce sources of pollutants 6. Reduce percentage of failed BMPs 7. Reduce number of noise complaints received and incompatible
land uses authorized in adjacent cities 8. Reduce the volume of solid waste generated from sources airport-
wide 9. Increase volume of recycled waste generated from sources
airport-wide 10. Reduce volume of hazardous waste generated 11. Increase procurement of environmentally-friendly products
II. Identification of Funding Sources
i. Grants
ii. Rebates
iii. Tax Credits
iv. Other
III. Provide for and conduct Education and Public Outreach Initiatives
i. Examples include, but are not limited to:
i. Environmental Stewardship Training (“Eco-Training”) for employees, contractors, tenants, concessionaires
ii. Implement or require training programs as part of tenant leasehold
iii. Provide educational materials to passengers and visitors in public terminal areas, gate holdrooms, parking areas, vehicle roadways/ toll plazas
iv. Use kiosks and informational displays to inform and generate interest
v. Develop short educational videos for passengers to watch on ATS and/or shuttle buses to/from remote parking area
IV. Plan for the integration of SAM guidelines into the following specific project elements, as appropriate to the size and scope of each project:
a. Energy use and carbon emissions inventory
b. Air quality enhancement strategies
c. Fleet and vehicle operations
d. Material and resource use
e. Heating and cooling systems
f. Lighting systems
g. Construction and administrative procedures
h. Indoor quality of life
i. Waste management and recycling
j. Landscape and natural resource management
k. Noise abatement
l. Surface transportation management
m. Water efficiency, quality, and conservation
n. Green building and asset management
AuPL-19
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
V. Plan for sustainable operation and maintenance of completed projects, programs or facilities (see Operations and Maintenance Chapter and Concessions and Tenants Chapter of SAM)
VI. Feedback Loop
a. Plan for original project team and key stakeholders to meet upon full project completion in order to gauge and/or determine:
i. Was the Sustainability Schematic useful? Why or why not?
ii. Was the Sustainability Schematic accurate? Why or why not?
iii. Was the Sustainability Schematic reasonable? Why or why not?
iv. Were the sustainability measures planned implemented? Why or why not?
v. Were additional sustainability measures implemented that were not originally identified?
vi. Were sustainability goals and targets met? Why or why not?
vii. Were the anticipated benefits achieved? Why or why not?
viii. Describe tracking and reporting of results.
ix. Provide overall “lessons learned” through the project
x. Recommend improvements to the process for enhancements to SAM Planning Chapter for future planning projects
SUBMITTALS
Present Sustainability Schematic to CDA Project Manager and Sustainable Review Panel (SRP) for review and comment.
Descriptive narrative in the SAM Checklist. TECHNOLOGY/STRATEGY
The consideration of sustainability has been successfully integrated into the planning process at Dallas Fort-Worth International Airport as shown in the Project Development Process (PDP) Flow-Chart on the following page. The PDP has been provided courtesy of Dallas Fort-Worth International Airport.
CASE STUDY
Complete information regarding Dallas Fort-Worth’s Sustainability Initiative is available at: www.dfwairport.com/sustainability/index.php
AuPL-20
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
PROJECT DEVELOPMENT PROCESS (PDP)AN INTEGRATED APPROACH TO SUSTAINABLE AIRPORT DEVELOPMENT
PHASE 1 – SUSTAINABILITY PLANNING & PROJECT DEFINITION
PROCESS
TASKS
COMMISSIONING
COMMUNICATION
User perspective of potential need.
Sources for potentiallyAct ionable Ideas or Concepts will evolve from:
• Master Plan
• Regulatory/Code Requirements
•Maintenance/Asset Sustainability Plans
• Facilit ies Plan/Land UsePlan
• Pop-Up Projects- Demand Driven- Customer Service- Revenue Opportunity- Other Strategic
Init iatives
• Engage Stakeholders- Baseline Group
• Define Objective Function- Clear and Concise Problem Statement
• Identify Potential Approaches to Address Objective Function
• Set Decision-Making Criteria- Triple Bottom Line Approach
- Financial- Environmental- Social/Regulatory/Operational Impacts
• Integration with existing Infrastructure/Program/Strategic Plan
• Conduct Alternatives Analysis- Triage for Init ial Decision- Rough Order of Magnitude Costs- Scenario Planning for Flexibility- Identify Preferred Alternative
• Make Decision - If YES, advance to Step 2- If NO, reject
• Refine Stakeholder Group - Identify/Acquire addit ional Stakeholders
as deemed appropriate
• Maintain Objective Function- Separate and Distinct from “ Solutions”
• Maintain Decision Criteria- Refine Sustainability Goals and Targets
as required
• Obtain Resources to support Technical Analyses, as required
• Refine Recommended Alternative- Life Cycle Cost Model- Constructability and Phasing Options- Leverage and Integration of
Sustainability Features- NEPA Process (as appropriate)- Project Definit ion
OUTPUT
• Design Intent Document (DID)- Clear Definit ion of
Scope/Program Elements- Owner’s Program Requirements
(OPR)- Performance Characteristics- Customer Expectations- Design Criteria- Sustainability Goals and
Objectives
• Business Case- P&L Development
• Funding Strategy
• Implementation Strategy- Synergistic Packaging of Projects- Priorit ization of Projects- Project Delivery Strategies- Recommended Design Approach- Master Schedule- Budget
• PFC
• O&M
• AIP
• AIRLINE TRUST
• FIC
• GRANT
• PROGRAMMING & DESIGN PREFERRED ALTERNATIVE
• TRACK EXPENSES
• RESOLVE ISSUES
• M/WBE INVOLVEMENT
• COORDINATE TO ENSURE DESIGN CONFORMS TO DID
• CODE REVIEW
• COMPLETE DESIGN DOCUMENTS AND PROVIDE FOR BIDDING
•COMMENCE BID PROCESS
• BID ESTIMATE
• BID
• OBA (if required)
• NTP
• PREPARE CONTRACTS TO ALIGNWITH PERFORMANCE MILESTONES
• CONSTRUCTION KICK-OFF MEETING
• JOINT REVIEW & COST SAVINGSPROPOSAL BY CONTRACTOR
• PROVIDE REGULAR UPDATES TOSPONSOR DEPARTMENT
• STAKEHOLDERS MEET AS NECESSARY TO DISCUSS PROJECT ISSUES
• OTHER TASKS NECESSARY TOEFFECTIVELY / EFFICIENTLY EXECUTE CONTRACT DOCUMENTS & CONSTRUCTION
• PERFORMANCE OF FACILITY ASSET VERIFIED
• TRANSITION NEW FACILITYINTO ESTABLISHEDOWNERSHIP STRUCTURE
• INTEGRATE INTO AIRPORTSYSTEM
• TRAINING
• INITIATE WRAP-UP
• CONTRACT CLOSE-OUT
• COMPLETION / RECONCILE
• CERTIFICATE OF OCCUPANCY
• OWNER’S MANUAL
• ESTABLISH SERVICE CONTRACTS
• SCHEDULE LESSONSLEARNED MEETING
• LESSONS LEARNED MEETING
• REVIEW HOW DEVELOPMENT PROCESS PERFORMED
• DOCUMENT FINDINGSPROJECT SUMMARY
•CONSIDERPROCEDURE/PROCESSREFINEMENTS
PHASE 3 - IMPLEMENTATION PHASE 4 – WRAP-UP
INITIAL MAGNITUDE DEFINE SCOPE FIELD INSPECTION LESSONS LEARNEDJUSTIFICATION/BENEFITS
September 15,2009
PERFORMANCE VERIFICATION DOCUMENTATION
COMMUNICATION, COLLABORATION, COORDINATION
• POPULATE CIP FORM USING INFO FROM STEP 1/2
• IDENTIFY IMPLEMENTATION YEAR
• CAPITAL COMMITTEE APPROVAL
• EXECUTIVE APPROVAL
Step 1 Step 1 Step 2 Step 3 Step 4 Step 1 Step 2Step 1
INITIAL HOLISTIC PROJECTFORMULATION
APPROPRIATEFUNDING
M&VCONSTRUCTIONPROGRAMMING &
DESIGNBIDCIP CLOSE OUT BEST PRACTICES
PHASE 2 - FUNDING
Step 2
NEEDIDENTIFIED
TERMS & DEFINITIONS:DID = EEI STRATEGY + PREFERRED ALTERNATIVE + ASSESSMENT FINDINGS + IMPLEMENTATION STRATEGY M&V =PROJECT CHAMPION = PROOF OF CONCEPT = SPONSOR = ORIGINATING/INITIATING DEPARTMENT, ORGANIZATION, ENTITYSTAKEHOLDER BRIEFING = SUSTAINABLE = TRIAGE = DETERMINATION OF PRIORITIES FOR ACTION IN AN EMERGENCY
Step 2
PROJECT REFINEMENT & DEFINITION
ACRONYMS: ADE = AIRPORT DEVELOPMENT & ENGINEERINGAIP = AIRPORT INFRASTRUCTURE PROGRAMAM = ASSET MANAGEMENTARE = AIRPORT REAL ESTATEBU = BUSINESS UNITCEO = CHIEF EXECUTIVE OFFICERCIP = CAPITAL IMPROVEMENT PROGRAMDHS = DEPARTMENT OF HOMELAND SECURITY DID = DESIGN INTENT DOCUMENTDPS = DFW DEPARTMENT OF PUBLIC SAFETY (POLICE & FIRE)EAD = ENVIRONMENTAL AFFAIRS DIVISIONEEI = EXPLORE – EVALUATE – IDENTIFY OPTION
EPA = ENVIRONMENTAL PROTECTION AGENCY E&TM = ENERGY & TRANSPORTATION MANAGEMENT FAA = FEDERAL AVIATION ADMINISTRATIONFIC = FACILITY IMPROVEMENT CORPORATION ITS = DFW INFORMATION TECHNOLOGY SERVICES M&V = MEASUREMENTS & VERIFICATION M/WBE = MINORITY/WOMEN BUSINESS ENTERPRISE OBA = OFFICIAL BOARD ACTION O&M = OPERATIONS & MAINTENANCE PFC = PASSENGER FACILITY CHARGES RM = RISK MANAGEMENT TSA = TRANSPORTATION SECURITY ADMINISTRATION
C3 2-WAY COMMUNICATION SYSTEM
FEEDBACK – LESSONS LEARNED
End of Process Documentation
DRAFT
DRAFTDRAFT
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
AuPL-23
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
PL PLANNING
PL.5 Prerequisite 5 – Project Meeting to Finalize Sustainability Schematic
Required
INTENT
Upon completion of the Sustainability Schematic, hold a project meeting to finalize the document and prepare it for inclusion in the official Project Definition Document (PDD) and/or Capital Improvement Program (CIP) Application, or other planning documentation as may be applicable.
REQUIREMENTS
Upon completion of the Sustainability Schematic, hold a project meeting(s) with CDA Project Manager, SRP, and all additional key stakeholders involved in planning, design, construction, and daily operation/maintenance of facility, as appropriate and applicable. Enable members to utilize conference calls, net-meetings, webinars, etc. when unable to attend in person. The meeting(s) purpose is to finalize the project’s Sustainability Schematic and prepare it for inclusion in the official Project Definition Document (PDD) and/or Capital Improvement Program (CIP) Application, or other applicable planning documentation.
SUBMITTALS
1. Descriptive narrative in the SAM Checklist 2. Sustainability Schematic 3. Meeting Agenda 4. Meeting sign-in sheet including name, company, title, contact information, and role on
project 5. Meeting Minutes 6. Meeting Materials (presentations, handouts, etc.) 7. If revisions are made to the Sustainability Schematic as a result of this meeting, provide
the revised Final Sustainability Schematic (complete document), a summary of changes made, and a signature sheet for key stake-holders affirming agreement and acceptance of changes.
8. If subsequent follow-up meetings are held, provide items 2-7 for each additional meeting TECHNOLOGY/STRATEGY
Provide the Sustainability Schematic to CDA Project Manager, SRP, and additional key stakeholders well in advance of the meeting. Request that all parties review and bring comments to the meeting. It is anticipated that one meeting would be held to finalize the Sustainability Schematic. However, if revisions are made to the Sustainability Schematic as a result of this meeting, subsequent follow-up meetings may be warranted. If that is the case, allow stake-holders ample review time of revised Sustainability Schematic in advance of each meeting.
AuPL-24
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
November 5, 2012
© 2012 City of Chicago
PL PLANNING
PL.6 Prerequisite 6 – Close the Feedback Loop at Project Completion
Required
INTENT
Due to the dynamic nature of the aviation industry, airport projects lend themselves to continual planning and renewal. The intent of this Prerequisite is to effectively close the feedback loop at project completion in order to determine if key performance indicators, targets, and goals were met as planned, exceeded plan, or were under plan, and the reasons why or why not. This “lessons learned” information can then be compiled and used as valuable background information on future projects. This information can also be used to inform similar project analyses, and enhance and improve the SAM Planning Chapter.
REQUIREMENTS
Examples of the types of information, analyses and comparisons suggested to review as part of the informative process for closing the feedback loop are included in Section VI. Feedback Loop of the Sustainability Schematic described in PL.4 Prerequisite 4 – Develop a Draft Sustainability Schematic.
Create a plan for as many of the key stakeholders as possible to meet upon final project completion, or at a point when the information outlined in the Sustainability Schematic (see Prerequisite 5 – Project Meeting to Finalize Sustainability Schematic) can be reasonably evaluated and measured with actual data. The purpose of the meeting will be to close the feedback loop by determining whether key performance indicators, targets, and goals were met as planned, exceeded plan, or were under plan, and the reasons why or why not. This “lessons learned” information can then be compiled and used as valuable background information on future projects, and ultimately to improve the overall process.
SUBMITTALS
1. Descriptive narrative in the SAM Checklist 2. Meeting Agenda 3. Names, titles, contact information, and role on project for key stake-holders and others
involved in development of the Sustainability Schematic 4. Name, title, contact information and role on project for designated person and back-up
person who will be responsible for keeping an up-to-date list of contact information for all key stake-holders and others involved in the development of the Sustainability Schematic (see Prerequisite 5).
5. Detailed descriptions of lessons-learned relative to the overall process and the Sustainability Schematic, as well as recommendations for enhancements to this SAM Planning Chapter.
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
APPENDIX PL-A
PLANNING CHECKLIST
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
PL-A-1
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
APPENDIX PL-A PLANNING CHECKLIST
POINTS OBTAINED CREDIT DESCRIPTION POINTS NARRATIVE
1.0 Administrative Procedures 8
AP.1
Prerequisite 1 - Green Meetings Guide meeting hosts, planners and attendees toward more eco-friendly meetings and incorporate environmental considerations into planning and conducting meetings in order to minimize the negative impact on the environment.
Prereq
AP.2
Prerequisite 2 - Document Reduction and Recycling Initiative (DRRI) Reduce the volume paper used and facilitate the recycling of documents.
Prereq
AP.3
Corporate Sustainability Policy Keeping with the spirit and intent of this Manual, it is strongly encouraged that companies working in support of CDA on any project establish and adopt their own corporate policy on sustainable practices.
1
AP.4
Green Procurement Policy Reduce the environmental impact of products and services by developing a Green Purchasing Program.
4
AP.5
Recycled Content Paper Reduce the need for virgin materials, energy, and waste associated with the production of paper by promoting the use of recycled content paper.
3
PL-A-2
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
APPENDIX PL-A PLANNING CHECKLIST
See “SUBMITTALS” within each credit for specific submittals to include with checklist.
PL.1 Define Sustainability Vision Statement
PL.2 Determine Key Stakeholders and hold Initial Project Meeting to Discuss Sustainability Goals
PL.3 Sustainability Baseline Assessment and Cost/Benefit Analysis
PL.4 Develop a Sustainability Schematic
PL.5 Project Meeting to Finalize Sustainability Schematic
PL.6 Close the Feedback Loop at Project Completion
…We acknowledge our designers and contractors for their achievements. Going green
doesn’t always have to cost a lot of green. We were able to save over a hundred million dollars by implementing an earthwork management plan and by utilizing recycled asphalt
through our resurfacing program…The Chicago Department of Aviation will continue to evolve as a benchmark for environmental stewardship
in airport design and construction…
Rosemarie S. Andolino Commissioner
Chicago Department of Aviation …the use of green walls inside the terminal can add great aesthetic benefits, as well as improve indoor air quality, and enhance the experience for airport employees and travelers…
Michael Berkshire Chicago Department of Zoning and Land Use Planning
…The key in the design process is to make sure that right up front you have made everyone aware that you intend to include
sustainability in the project…
Ted Woosley Landrum & Brown
airportsgoinggreen.org
Project Submittal Forms, Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
DC-1
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
DESIGN & CONSTRUCTION TABLE OF CONTENTS
DESIGN & INTRODUCTION ………... DC-3 2.0 Sustainable Sites 2.1 Construction Activity Pollution Prevention ………... DC-122.2 Adopt CDA Best Management Practices ………... DC-142.3 Brownfield Redevelopment ………... DC-152.4 Alternative Transportation ………... DC-172.5 Stormwater Design ………... DC-262.6 Landscape and Exterior Design to Reduce Heat Islands ………... DC-322.7 Light Pollution Reduction ………... DC-38 3.0 Water Efficiency 3.1 Water Use Reduction: 20% Reduction ………... DC-423.2 Water Use Reduction: 30%-40% Reduction ………... DC-443.3 Water Efficient Landscaping ………... DC-473.4 Innovative Wastewater Technologies ………... DC-53 4.0 Energy & Atmosphere 4.1 Fundamental Building Systems Commissioning ………... DC-554.2 Minimum Energy Performance ………... DC-594.3 Fundamental Refrigerant Management ………... DC-634.4 Optimize Energy Performance ………... DC-654.5 On-Site Renewable Energy ………... DC-754.6 Enhanced Commissioning ………... DC-794.7 Enhanced Refrigerant Management ………... DC-834.8 Measurement and Verification ………... DC-854.9 Green Power ………... DC-87 5.0 Materials & Resources 5.1 Storage and Collection of Recyclables ………... DC-895.2 Building and Infrastructure Reuse ………... DC-925.3 Construction Waste Management ………... DC-945.4 Balanced Earthwork ………... DC-975.5 Aggregate Reuse ………... DC-995.6 Material Reuse ………... DC-1015.7 Recycled Content ………... DC-1035.8 Local/Regional Material ………... DC-1075.9 Rapidly Renewable Materials ………... DC-1095.10 Certified Wood ………... DC-1115.11 Furniture and Equipment ………... DC-1125.12 Equipment Salvage and Reuse ………... DC-114 6.0 Indoor Environmental Quality 6.1 Minimum Indoor Air Quality (IAQ) Performance ………... DC-1166.2 Environmental Tobacco Smoke (ETS) Control ………... DC-1186.3 Outdoor Air Delivery Monitoring ………... DC-1216.4 Increased Ventilation ………... DC-1236.5 Construction IAQ Management Plan ………... DC-1266.6 Low-Emitting Materials ………... DC-131
DC-2
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.7 Indoor Chemical and Pollutant Source Control ………... DC-1416.8 Controllability of Systems ………... DC-1436.9 Thermal Comfort ………... DC-1476.10 Daylight and Views ………... DC-1516.11 Noise Transmission ………... DC-156 7.0 Construction Practices 7.1 Clean Fuel Construction Vehicles ………... DC-1587.2 Construction Equipment Maintenance ………... DC-1627.3 Construction Activity Pollution Prevention ………... DC-1647.4 Systems Commissioning ………... DC-1647.5 Construction Waste Management ………... DC-1647.6 Construction IAQ Management Plan ………... DC-1657.7 Low-Emission Construction Vehicles ………... DC-1667.8 Alternative Transportation During Construction ………... DC-1687.9 Construction Material Conveyance ………... DC-1737.10 Construction Noise and Acoustical Quality ………... DC-1757.11 Sustainable Temporary Construction Materials ………... DC-177 8.0 Innovation in Design & Construction 8.1 Innovation in Design & Construction ………... DC-1818.2 Innovation in Design & Construction ………... DC-1818.3 Innovation in Design & Construction ………... DC-1818.4 Menu Items ………... DC-1838.5 LEED Accredited Professional ………... DC-1878.6 LEED Certified Project ………... DC-188 9.0 Regional Priority 9.1 Regional Priority ………... DC-189
DC-3
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
INTRODUCTION
After the planning process, projects that move forward will then enter the design and (usually) the construction phase. This chapter continues the process of incorporating sustainability into major renovations and construction projects. At this point, the details of what is being built are beginning to take shape. By integrating sustainable design elements into the design process as early as possible, it is expected that the effectiveness of enhancing a project’s sustainability is maximized while costs due to design and construction changes are minimized. Although sustainable guidance and rating systems for buildings (vertical construction) are prevalent, the civil/infrastructure environment (horizontal construction) guidance is less common. The Design & Construction (D&C) Chapter of the Sustainable Airport Manual (SAM) joins these elements, civil/infrastructure and buildings, and applies them within the realm of an airport environment.
Implementation of sustainable design elements can reduce operational costs and increase occupant productivity. The on-site recycling and reuse of construction waste and materials, for example, reduces transportation cost and the use of regionally-obtainable materials benefits the local economy and reduces life-cycle emissions of those materials. Regardless of the scale and scope of a project, it is anticipated that with the appropriate level of investment in these sustainable elements, all parties including owners, occupants, contractors, and the general public can benefit environmentally and economically. In many cases, there is little or no impact on the project budget or schedule in the implementation of these sustainable elements.
The Design and Construction Chapter of the Sustainable Airport Manual (SAM) has been written with consideration of four general project categories that are relevant to airport design and construction projects. These project categories are defined below:
Civil – Airside: Projects located inside of the Air Operations Area (AOA) that do not include normally occupied structures and consist mainly of horizontal structures such as subsurface utilities, earthwork, pavement, roadways, bridges, tunnels, and water conveyances. Projects may include but are not limited to runways, taxiways and shoulders, airside roads and perimeter roads, stormwater conveyance systems, stormwater detention facilities, electrical lighting systems, navigational aids, airport utility systems, vehicle parking facilities, and fencing.
Civil – Landside: Projects located outside of the AOA that do not include normally occupied structures and consist mainly of horizontal structures such as subsurface utilities, earthwork, pavement, roadways, bridges, tunnels, and water conveyances. Projects may include but are not limited to guard post relocation, roads, tunnels and bridges, perimeter roads, stormwater conveyance systems, stormwater detention facilities, creek relocations, electrical lighting systems, airport utility systems, vehicle parking facilities and fencing, and railroad relocation.
DC-4
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Occupied Buildings: Projects consisting of facilities and associated surroundings that, when construction is complete, will be normally occupied by employees and passengers. These facilities may include but are not limited to terminals, concourses, access guard posts, airport communications building, air rescue and fire fighting facilities, cargo facilities, and air traffic control towers.
Unoccupied Buildings: Projects consisting of facilities and associated surroundings that, when construction is complete, will be unoccupied. These may include but are not limited to pump stations, lighting vaults, and fuel stations.
APPLICABILITY
SAM Design & Construction (DC) certification encourages airport designers and contractors to implement sustainable practices to reduce the environmental impacts of, not only the design features of a given project, but also construction activities, and the operational aspects of the building or infrastructure project. Specifically, the rating system addresses site issues, water and energy usage, materials and resources used for building the project, waste management, and indoor/outdoor environmental quality.
The SAM DC chapter is applicable to all non-terminal construction activities that require design services. In addition, any major renovations defined as major HVAC rehabilitation, envelope modifications, or significant interior remodeling requiring design services will also be included within this chapter. It is intended that the designers and contractors of these types of projects will be evaluated through this process.
DESIGN & CONSTRUCTION SECTIONS
Projects are rated on the achievement of credits depending on the appropriate stage of the project, based on sustainable elements included in the project from the following categories:
AP Administrative Procedures 1.0 Sustainable Site Management 2.0 Water Efficiency 3.0 Energy & Atmosphere 4.0 Materials & Resources 5.0 Indoor Environmental Quality 6.0 Construction Practices 7.0 Innovation in Design & Construction 8.0 Regional Priority
Each category contains a specific number of credits, against which each project is evaluated in order to determine that project’s earned points. The number of points earned is then translated into a rating. There are specific weighted point thresholds (i.e. applicable credits) for each of the four project categories – civil-airside, civil-landside, occupied buildings, and unoccupied buildings, so as not to inadvertently penalize a project for not achieving points that would not be applicable. The list of credits and point thresholds applicable to each project type are summarized in Appendix DC-A – Sustainable Airport Manual Green Airplane Rating System.
DC-5
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
PROCESS
Within the Manual’s main body, each sustainable design credit has five subsections: Intent, Requirements, Submittals, Technology/Strategy, and Case Studies, as described below:
Intent: The primary motivations for any sustainable practice.
Requirements: Specifies institutional, operational, and mechanical design or construction elements that satisfy the intent. The prerequisites must be achieved; the credits are optional, but contribute to the overall project rating.
Submittals: Required and supporting documentation and/or information required to achieve applicable prerequisites or credits. This documentation may include calculations, data, short narratives, policies, documents or references to specification sections or design drawings indicating how the requirements are being met.
Technology/Strategy: Highlights specific ways of meeting the recommendations within the scope for each specific credit. Case studies where available, are presented to help guide the application of sustainable credits to design and construction projects. To aid with consideration of applicable strategies and technologies, they are organized into the following three categories; “Standard Practice,” “Recommended Practice,” and “Best Available Practice.”
o Standard Practice: These are requirements that may be due to standards, specifications, codes, general best management or construction practices. They are practices already in place, and in many cases SAM prerequisites, which also serve to meet sustainable goals.
o Recommended Practice: These include recommendations that are expected to have insignificant impacts to cost and are therefore, encouraged to be incorporated into the design process.
o Best Available Practice: These are strategies and practices that are expected to enhance the environmental design efforts of the Chicago Department of Aviation (CDA), but are anticipated to potentially have an impact on the cost and/or schedule. A simple cost benefit analysis can be conducted to determine the practicality of implementation.
While not all strategies will be applicable to every project category, design and construction teams are highly encouraged to think creatively and to consider the intent of each issue throughout the decision process. In all cases, it is the responsibility of the design and construction teams to evaluate and review with the Chicago Department of Aviation any anticipated cost or schedule impact.
DC-6
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
SUBMITTALS
Sustainable Airport Manual (SAM) Design & Construction Checklists
Incorporation of sustainable elements into the design and construction of a project is tracked using a checklist in order to determine the number of applicable credits described in this Manual. The SAM Design Checklist is completed by the designer. It is then used by the contractor/CM to develop the SAM Construction Checklist. The purpose of the SAM Design Checklist is to indicate proposed sustainable design elements during the design phase, while the purpose of the SAM Construction Checklist is to allow verification and finalization of actual data related to the project’s construction phase. The checklists are provided in Appendix DC-B – Design & Construction Checklists.
NOTE
All design teams must have a LEED Accredited Professional. Their responsibility is to complete or oversee the completion of the SAM Design and Construction Checklists and
their implementation.
In order to achieve points certain requirements need to be met, as outlined in each credit. At periodic review meetings throughout the design process, the design team must demonstrate how and to what extent these credits will be achieved. The means by which this is demonstrated will vary. In some instances, studies and calculations would be appropriate. In other instances, this will be accomplished through product and material data or through referenced standards or specifications.
For some credits, the responsibility to meet the intent of the credit will be primarily the contractor’s responsibility. In these cases, specifications are developed by the designer to clearly detail the execution and submittal requirements the contractor must follow. In addition to review of the checklist, the Sustainable Review Panel (SRP) will review any supporting documentation including calculations, specifications, and contractor’s submittals as needed to support the achievement of the credit(s). See Section titled Implementation and Review Process for detailed information about the SRP.
SAM GREEN AIRPLANE RATING SYSTEM
The SAM Green Airplane Rating System for Design and Construction uses a five tier approach to rating projects based on the four project types. “Green Airplane Certification” symbols are used to designate achievement levels.
DC-7
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
The thresholds for each project type are summarized in the Tables 1 and 2 below:
TABLE 1 –SAM Green Airplane Rating System (Design) Civil-
Airside Civil-
Landside Occupied Buildings
Unoccupied Buildings
8 8 13 12
2-19 2-20 2-42 2-34
20-24 21-25 43-53 35-42
25-28 26-30 54-64 43-51
29-38 31-40 65-86 52-68
39-54 41-57 87-119 69-95
MAXIMUM 54 57 119 95
TABLE 2 –SAM Green Airplane Rating System (Construction) Civil-
Airside Civil-
LandsideOccupied Buildings
Unoccupied Buildings
8 8 13 12
2-21 2-22 2-45 2-36
22-27 23-28 46-57 37-45
28-32 29-34 58-68 46-55
33-43 35-46 69-91 56-73
44-61 47-64 92-127 74-102
MAXIMUM 61 64 127 102 IMPLEMENTATION AND REVIEW PROCESS
The SAM and its supporting documentation are administered by the Sustainable Review Panel (SRP), which currently consists of representatives of the CDA Management Staff, CDA Design and Construction Staff and Representatives, OMP Project Management Office (PMO) and Master Civil Engineer (MCE), and Airport Planners actively involved in CDA projects. The composition of the SRP is intended to be dynamic depending on needs.
The SRP is responsible for the review of project designs with respect to sustainable design and provides technical support to the Construction Manager (CM) of each project in relation to sustainable practices appropriate for the construction phase. The SRP is responsible for review of every design and construction project and for the awarding of “Green Airplane Certification” ratings based on the extent of incorporation of sustainable practices as outlined in this Manual and as documented on the submitted SAM Checklist(s). Other responsibilities of the SRP
Prerequisites
Green Airplanes
Prerequisites
Green Airplanes
DC-8
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
include preparation and review of sustainable design related specifications, technical memoranda, and miscellaneous documents, as necessary. In addition, the SRP is responsible for presentations and training to project team members with respect to the application of this Manual. The primary tasks of the SRP are to oversee the application of the Manual and review design and construction submittals for their compliance with the Manual. The review process is outlined in Figure 1.
Just as any airport can easily customize the Chicago-specific guidance elements within the SAM, the composition of a SRP can also be tailored to an airport’s unique needs.
Design Phase
Current Requests for Proposals (RFPs) for design services include language indicating that requirements of this Manual must be incorporated as part of the design process for all projects. The designer is to incorporate language regarding all supporting specifications and requirements in the Contract Documents consistent with the requirements described in this Manual. After a project is awarded to a Design Team, SRP representatives will meet with the designers during the kick-off meeting to outline the project goals for sustainability. Contract documents require that each design team include at least one LEED Accredited Professional. It is encouraged that the LEED Accredited Professional be present at all sustainability-related meetings, including the project kick-off meeting. The SAM Design Checklist is discussed in detail at the kick-off meeting, as it is one of the primary deliverables from the Design Team, as well as the supporting documents and specifications that must accompany the submittal. At this meeting, the designer is given an electronic copy of the Manual and electronic copies of all relevant specifications, checklists, calculations spreadsheets, and templates, including instructions for completion of each form. Certain credits pertain to specifications and standards that are included in every contract (e.g. 01111 – Construction Air Quality or 01524 – Waste Management). In most cases, the specification indicates the submittal requirements. The credit descriptions in this Manual describe the submittal requirements that must be satisfied in order to meet the credit.
As part of the standard design review process, the SAM Design Checklist and supporting documents are reviewed at each milestone (typically 30%, 60%, 90%, and 100% design submittals) against the goals set forth by the Manual. Review comments on the Checklist are submitted along with the design-related review comments.
At the 100% design milestone, the SRP will meet to discuss the project’s Checklist and collectively determine any final comments for the Design Team before completion. When the 100% design documents have been completed, the SRP meets again to determine and award the Green Airplane Certification for Sustainable Design (i.e. the number of Green Airplanes to be awarded to the project design).
DC-9
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Figure 1 - Sustainable Review Process during Design and Construction
DC-10
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Construction Phase
The Manual is referenced in the General Conditions of the project’s Contract Documents. The contractor is obligated to meet all the requirements of the Manual and the supporting specifications and submittals. Compliance with these requirements is verified by the Construction Manager (CM) prior to project closeout. This is verified by the Sustainable Design Compliance section of the project’s Closeout Log. As the project continues through Bid Issue and then Construction phase, the SRP will meet with the CM and contractor at the pre-construction meeting to discuss the process and the deliverables with emphasis on what is required by the contractor and the CM. At this time, additional opportunities and goals are identified for the construction phase and the contractor and CM are encouraged to raise awareness of sustainable design and construction issues with the remaining staff. The SRP works with the CM as the main point of contact. The CM is required to obtain the required documentation from the Contractor, although in some cases information may be received directly from the Contractor (e.g., the fuel usage logs).
For the construction phase, some up-front submittals are required, e.g. Construction Waste Plan, preconstruction estimates on regional and recycled material quantities that are reviewed at the beginning of the project. Fuel usage is tracked monthly throughout the project’s duration. The SAM Construction Checklist is reviewed and finalized when the project reaches substantial completion.
After substantial completion, the SRP will determine whether all items proposed in the Design Checklist were completed and are reflected in the SAM Construction Checklist or discuss/identify variances. At completion, the SRP will determine and award the Green Airplane Certification for Sustainable Construction.
Commissioning
Whenever applicable, project commissioning is encouraged. Commissioning can provide long-term benefits for the project/building owner, as well as its users and occupants. Commissioning is covered in the Energy & Atmosphere section.
DC-11
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
airports going green.org
For comments, case studies, lessons‐learned, new
technologies or for any and all project submittal forms,
please email:
DC-12
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.1 Prerequisite 1 – Construction Activity Pollution Prevention
Required
INTENT
Reduce pollution from construction activities by controlling soil erosion, waterway sedimentation and airborne dust generation.
REQUIREMENTS
Create and implement an Erosion and Sedimentation Control (ESC) Plan for all construction activities. The ESC Plan shall conform to the erosion and sedimentation requirements of the 2003 EPA Construction General Permit OR local erosion and sedimentation control standards and codes, whichever is more stringent. The Plan shall describe the measures implemented to accomplish the following objectives:
Prevent loss of soil during construction by stormwater runoff and/or wind erosion, including protecting topsoil by stockpiling for reuse
Prevent sedimentation of storm sewer or receiving streams Prevent pollution of the air with dust and particulate matter using BMPs
(See SAM Credit 2.2 Prerequisite 2 – Adopt CDA Best Management Practices)
The Construction General Permit (CGP) outlines the provisions necessary to comply with Phase I and Phase II of the National Pollutant Discharge Elimination System (NPDES) program. While the CGP only applies to construction sites greater than 1 acre, the requirements are applied to all projects for the purposes of this prerequisite. Information on the EPA CGP is available at: www.cfpub.epa.gov/npdes/stormwater/cgp.cfm.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Create an Erosion and Sedimentation Control Plan during the design phase of the project. Consider employing strategies such as temporary and permanent seeding, mulching, earth dikes, silt fencing, sediment traps and sediment basins.
DC-13
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
CDA’s current construction activities meet the basic requirements of this strategy:
Develop an erosion and sediment control strategy plan to be implemented by stages and phases to control erosion at the source and retain sediment on the construction site
Incorporate temporary sedimentation basins, temporary ditch checks, diversion dikes, temporary ditches, pipe slope drains into the construction plans
For dust control: tarp truckloads, sweep streets as needed, stabilize construction entrances, spray site as necessary to minimize fugitive dust
Establish temporary and permanent seeding plans consistent with the following CDA/OMP Specifications:
o CDA/OMP Specification T-901 – Seeding o CDA/OMP Specification P-156 – Temporary Air and Water Pollution, Soil
Erosion, and Sediment Control o CDA/OMP Specification 02905 – Sustainable Airport Landscaping
For any proposed plant species not listed, consult an FAA certified airport biologist to ensure the plants will not attract wildlife
Recommended Practice
None
Best Available Practice
Monitor water quality impacts before and during construction Develop an inventory of topsoil for potential re-use Develop a policy to chip or compost all vegetation for re-use on site
DC-14
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.2 Prerequisite 2 – Adopt CDA Best Management Practices
Required
INTENT
Minimize the environmental impacts of facility operations.
REQUIREMENTS
Adopt the CDA Best Management Practices (BMP) Manual Depending on the project, the owner, tenant, or ultimate occupant must incorporate the
CDA BMP Manual into their tenant or lease agreement
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
The BMP Manual defines the practices and measures used to reduce or eliminate the amount of pollution to the environment surrounding Chicago O’Hare and Midway International Airports. The BMPs are typically in the form of a procedure, activity, or structural control.
Standard Practice
The BMP Manual has been in effect since August 2002. There are a number of practices already implemented at Chicago O’Hare and Midway via this manual. Many of these practices deal with pollution prevention for all airport entities.
Recommended Practice
None
Best Available Practice
None
DC-15
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.3 Brownfield Redevelopment
1 Point
INTENT
Rehabilitate damaged sites where development is complicated by environmental contamination, reducing pressure on undeveloped land.
REQUIREMENTS
Develop on a site documented as contaminated (by means of an ASTM E1903-97 Phase II Environmental Site Assessment or a local Voluntary Cleanup Program).
OR
Develop on a site defined as a brownfield by a local, state or federal government agency.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
During the site selection process, give preference to brownfield sites. Identify tax incentives and property cost savings. Coordinate site development plans with remediation activity, as appropriate.
Standard Practice
The following strategies are required by IEPA* for any development in a brownfield:
Develop and implement a site remediation plan using strategies such as pump-and-treat, bioreactors, land forming and on-site remediation. Remediation would meet the standards identified in the Illinois Tiered Approach to Corrective Action (TACO).
Opportunity to enter into the Illinois Site Remediation Program (voluntary cleanup program) that offers a No Further Remediation (NFR) Letter
*or relevant state agency
DC-16
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Any recommendations are dependent upon site characteristics. Monitoring is suggested as site conditions warrant
Best Available Practice
Cleanup requirements will be dependent on site conditions, applicable remediation standards, and timing requirements
CASE STUDY
Airport Redevelopment Site Stapleton Airport - Denver, Colorado
Stapleton International Airport was abandoned in 1995 to allow for the commissioning of Denver International Airport. After significant contamination remediation, the site was redeveloped to allow for a master-planned community. Using strict environmental standards, contaminated soil was investigated and removed.
www.progressiveengineer.com/features/new_life_old_airport.htm
DC-17
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.4.1 Alternative Transportation: Public Transportation Access
6 Points
INTENT
Reduce pollution and land development impacts from automobile use.
REQUIREMENTS
Locate project within one half-mile walking distance (measured from main building entrance) of an existing or planned and funded commuter rail, light rail, or subway station (measured from the building entrance).
OR
Locate project within one quarter-mile walking distance (measured from main building entrance) of one or more stops for two or more public, campus, or private bus lines usable by building occupants.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Perform a transportation survey of future building occupants to identify transportation needs and share results to encourage knowledge and use of mass transit. Whenever possible, co-locate buildings and mass transit and provide clear directional signage.
Standard Practice
CDA’s current transportation plan meets the basic requirements of this strategy Shuttle buses and ATS transportation are currently available
Recommended Practice
Work with CDA to plan for and implement strategies aimed at the following goals:
Improve and/or increase public transportation access from the City and suburbs Reduce parking needs Improve efficiency of access
DC-18
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
Below are additional suggestions that could further support an inter-modal public transportation network. Teams should consider impact of future implementation.
Provide incentives to employees to use public transportation and shuttles Consolidate rental car facilities and mini-bus transportation to minimize
congestion on terminal roads. Consider the use of an alternate fuel mini-bus fleet to reduce vehicle emissions and carbon footprint.
Operate satellite ‘check-in’ facilities (downtown and suburban locations) to minimize congestion on terminal access roads and encourage use of public transportation
Construct airport to airport (O’Hare-Midway) high-speed rail connection Develop Airport-Downtown express connection, including satellite check-in
facilities Develop additional train/mass transit service to/from the suburbs To ease in local understanding of available modes of alternative transportation,
airports can include mass-transit routes on an airport area map
CASE STUDY
Electric Transit Charles De Gaulle International Airport - Paris, France
In April 2007, Charles de Gaulle International Airport in Paris France commissioned a new automatic metro line, the Charles de Gaulle Véhicule Automatique Léger (CDGVAL). The metro line is a free driverless train transferring passengers and 85,000 airport employees. The CDGVAL links three airport terminals, TGV/RER stations, and long-term parking lots. The CDGVAL is a 100 percent electric, making it possible to save 750 tons of fuel per year and decreases 15 tons of NOx and 2,500 tons of CO2 released annually by the buses. It also decreases travel time between the two furthest points on the system by more than 50 percent.
www.enviro.aero/CharlesDeGaulleAirport.aspx
DC-19
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.4.2 Alternative Transportation: Bicycle Access, Storage and Changing Rooms
1 Point
INTENT
Reduce pollution and land development impacts from automobile use.
REQUIREMENTS
For commercial or institutional buildings, provide secure bicycle racks and/or storage (within 200 yards of a building entrance) for 5% or more of all building users (measured at peak periods).
AND
Provide shower and changing facilities in the building, or within 200 yards of a building entrance, for 0.5% of Full-Time Equivalent (FTE) occupants.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Design the building with transportation amenities such as bicycle racks and showering/changing facilities such that employees are encouraged to use bicycles, therefore reducing parking needs
Bicycle access may require coordination with airport security
Standard Practice
Although bicycle access to secured areas may be limited, perimeter facilities often have bicycle access and shower rooms available
Recommended Practice
Include bicycle storage facilities and changing rooms where possible. Locate perimeter facilities in areas that provide a continuity of safe bicycle access from the adjoining community.
DC-20
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
Provide safe bicycle lanes/paths Provide a centralized facility(s) for secure bicycle storage with convenient
changing/shower areas Provide incentives to employees to bike to work Develop a bicycle-access master plan
CASE STUDY
Bike to Work Plan City of Chicago, Illinois
The Bike 2015 Plan is the City of Chicago’s vision to make bicycling an integral part of daily life. The plan recommends projects, programs and policies through 2015 to encourage use of bicycles as a practical, non-polluting, and affordable mode of transportation. The Bike 2015 Plan has two overall goals:
To increase bicycle use, so that 5 percent of all trips less than five miles are by bicycle. To reduce the number of bicycle injuries by 50 percent from current levels.
The plan has eight chapters, each with a specific goal:
Bikeway Network – Establish a bikeway network that serves all Chicago residents and neighborhoods.
Bicycle-friendly Streets – Make all of Chicago’s streets safe and convenient for bicycling.
Bike Parking – Provide convenient and secure short-term and long-term bike parking throughout Chicago.
Transit – Provide convenient connections between bicycling and public transit. Education – Educate bicyclists, motorists, and the general public about bicycle safety
and the benefits of bicycling. Marketing and Health Promotion – Increase bicycle use through targeted marketing and
health promotion. Law Enforcement and Crash Analysis – Increase bicyclist safety through effective law
enforcement and detailed crash analysis. Bicycle Messengers – Expand the use of bicycle messengers; improve their workplace
safety and public image.
http://bike2015plan.org
DC-21
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.4.3 Alternative Transportation: Low-Emitting and Fuel-Efficient Vehicles (Non-Construction)
3 Points
INTENT
Reduce pollution and land development impacts from automobile use.
REQUIREMENTS
OPTION 1 Provide low-emitting and fuel-efficient vehicles for 3% of Full-Time Equivalent (FTE) occupants
AND
Provide preferred parking for these vehicles.
OR
OPTION 2 Provide preferred parking for low-emitting and fuel-efficient vehicles for 5% of the total vehicle parking capacity of the site. Provide discounted parking rates as an acceptable substitute for preferred parking for low-emitting/fuel efficient vehicles. In order to establish a meaningful incentive in all potential markets, the parking rate must be discounted at least 20%. This approach is acceptable as long as the discounted rate is available for all customers (not limited to the number of customers equal to 5% of the vehicle parking capacity) and publicly posted at the entrance to the parking deck.
OR
OPTION 3 Install alternative-fuel refueling stations for 3% of the total vehicle parking capacity of the site (liquid or gaseous fueling facilities must be separately ventilated or located outdoors).
OR
DC-22
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
OPTION 4 Provide to building occupants, access to a hybrid car sharing program. The following requirements must be met:
One low-emitting or fuel-efficient vehicle/car must be provided per 8 people A car sharing contract demonstrating an agreement of at least 2 years must be provided Documentation of the car sharing program's customers served/car estimates and a
narrative explaining the car-share program and its administration must be provided The low-emitting and fuel-efficient vehicle/car parking must be located in the nearest
available spaces in the nearest available parking area; provide a site plan or area map clearly highlighting the walking path from the parking area to the project site and noting the distance
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Provide transportation amenities such as alternative fuel refueling stations. Consider sharing the costs and benefits of refueling stations with neighboring communities and the airport’s policy on alternative fuel options and preferences.
Standard Practice
CDA already has programs for alternative fuel vehicles within the airport operations. Design so that these programs are enhanced and supported
Recommended Practice
Consider local policies and preferences when considering new alternative fueling infrastructure development.
Best Available Practice
Increase use of alternative fuel vehicles for airport operations particularly indoor cargo operations
Provide preferred parking for staff and public alternative fuel vehicles Install alternative fuel refueling stations for public use Plan for the development of preferred parking and/or lot locations for rental fleets,
which offer alternative fuel rental vehicles Encourage electrical receptacle in public parking garages for charging of electric
vehicles
DC-23
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDIES
Reduced Access Fee for Hybrid Taxis Denver International Airport - Denver, Colorado
The environment will benefit from the reduced carbon emissions and air pollution that result from substituting hybrid taxis for conventional taxis. As a result, one of Denver International Airport’s many sustainable initiatives is to offer fee reductions for hybrid taxis which serve the airport. In addition to this incentive, Denver International Airport established a transportation and maintenance fleet, which is 100% alternative-fueled and includes vehicles powered by compressed natural gas, hybrid technology and biodiesel.
www.greenprintdenver.org/docs/DenverClimateActionPlan.pdf.
Preferred Parking for Carpoolers Denver International Airport - Denver, Colorado
Denver International Airport has launched an aggressive program to encourage carpooling which offers reduced parking costs for carpoolers. Additionally, the airport offers designated locations which include unreserved spaces typically in close proximity to employee or passenger access points.
Hydrogen Fuel Cell Vehicles Los Angeles World Airports – Los Angeles, California
Los Angeles World Airports developed the first hydrogen fueling and generation station at Los Angeles International Airport. This facility demonstrates a comprehensive alternative fueled vehicle program that can be incorporated into daily airport operations both on and off the airfield.
www.aci-na.org/static/entransit/Going%20Green%209-7-07.pdf
DC-24
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.4.4 Alternative Transportation: Parking Capacity
2 Points
INTENT
Reduce pollution and land development impacts from single occupancy vehicle use for employees.
REQUIREMENTS
OPTION 1 — NON-RESIDENTIAL Size parking capacity to meet, but not exceed, minimum local zoning requirements.
AND
Provide preferred parking for carpools or vanpools for 5% of the total provided parking spaces.
OR
OPTION 2 — NON-RESIDENTIAL For projects that provide parking for less than 5% of FTE building occupants:
Provide preferred parking for carpools or vanpools, marked as such, for 5% of total provided parking spaces.
OR
OPTION 3 — ALL Provide no new parking.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Minimize employee parking lot/garage size. Consider sharing parking facilities with adjacent buildings. Consider alternatives that will limit the use of single occupancy vehicles.
Standard Practice
None
DC-25
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
None
Best Available Practice
Provide preferred parking for vanpools and carpools for staff o Preferred Parking refers to the parking spots that are closest to the main
entrance of the project, exclusive of spaces designated for handicapped, or spaces designated for specific users
Parking garages can reduce the overall footprint while providing needed capacity
DC-26
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.5.1 Stormwater Design: Quantity Control
1 Point
INTENT
Limit disruption of natural water hydrology by reducing impervious cover, increasing on-site infiltration, reducing or eliminating pollution from stormwater runoff, and eliminating contaminants.
REQUIREMENTS
CASE 1 — EXISTING IMPERVIOUSNESS IS LESS THAN OR EQUAL TO 50% Implement a stormwater management plan that prevents the post-development peak discharge rate and quantity from exceeding the pre-development peak discharge rate and quantity for the one- and two-year, 24-hour design storms.
OR
Implement a stormwater management plan that protects receiving stream channels from excessive erosion by implementing a stream channel protection strategy and quantity control strategies.
OR
CASE 2 — EXISTING IMPERVIOUSNESS IS GREATER THAN 50% Implement a stormwater management plan that results in a 25% decrease in the volume of stormwater runoff from the two-year, 24-hour design storm.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Design the project site to maintain natural stormwater flows by promoting infiltration. Specify vegetated roofs, pervious paving, and other measures to minimize impervious surfaces. Reuse stormwater volumes generated for non-potable uses such as landscape irrigation, toilet and urinal flushing and custodial uses.
DC-27
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
Because many airside pavements have the potential for deicing fluid and jet fuel contamination, technologies that increase infiltration to the subsurface are not used. On landside projects, or for areas not subject to aviation-related contaminants, these methods are encouraged. A number of green vegetated roofs have already contributed toward this goal.
Recommended Practice
Evaluate pervious pavements for roadways, shoulders, non-traffic pavements, maintenance roads, utility yards, airside and landside parking facilities, and pedestrian areas. Peak storm water runoff rates could be reduced. Storm sewer conveyance systems could be designed with reduced diameter pipes and fewer inlets.
Install landscape to reduce runoff (See SAM Credit 3.3 Water Efficient Landscaping) Evaluate curb breaks and drainage ditches, and/or bioswales.
Best Available Practice
Encourage installation of systems that are flexible to allow use of graywater Use of “extensive” green roof systems encourages filtration and treatment of
rainwater, evaporation of rainfall to the atmosphere and storm water retention. Use plantings consistent with CDA/OMP Specification 02905 – Sustainable Airport Landscaping. For any proposed plant species not listed, consult an FAA certified airport biologist to ensure the plants will not attract wildlife.
Use rainwater cisterns for landside irrigation during the plant growth season. Storm water runoff from the collection systems would be directed into the cisterns for storage. Collected water would be utilized for irrigation during dry periods. Cisterns would attenuate peak storm water runoff flows to the downstream storm sewer systems. Cisterns improve water quality by the removal of sediments due to the reduced velocities of flow in the system. (Sediment must be periodically removed.)
Encourage extensive use of permeable pavement, where applicable
CASE STUDIES
North Air Traffic Control Tower Chicago O’Hare International Airport - Chicago, Illinois
The proposed site for the new North Air Traffic Control Tower was an existing parking lot with an impervious area of 89 percent. The new development greatly reduced the impervious area of the site to 43 percent. Because the existing site had an impervious area greater than 50 percent, in order to meet the requirement of this credit, the rate and quantity of stormwater runoff needed to be reduced by 25 percent. By reducing the impervious area of the new development by 46 percent or 47,200 square feet, the project met the requirements of this credit.
DC-28
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Terminal Building Cooling System Using Collected Snowfall New Chitose Airport - Hokkaido, Japan
The New Chitose Airport terminal building in Hokkaido, Japan, will utilize a new cooling system by the fiscal year 2010. The transport ministry plans to collect snow during the winter and preserve it to provide 30 percent of the building's cooling needs during the summer. Of the snow collected throughout the winter, approximately 45 percent of the snow is preserved for the summertime through the use of heat-insulating materials. The collected snow would be used to chill the liquid of the building's cooling system. This practice could stave off 2,100 tons of carbon dioxide emissions per annum compared to using the building's existing cooling system.
www.goodcleantech.com/2008/10/new_chitose_airport_in_japan_t_1.php
DC-29
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.5.2 Stormwater Design: Quality Control
1 Point
INTENT
Limit disruption and pollution of natural water flows by managing stormwater runoff.
REQUIREMENTS
Implement a stormwater management plan that reduces impervious cover, promotes infiltration, and captures and treats the stormwater runoff from 90% of the average annual rainfall using acceptable CDA Best Management Practices (BMPs). BMPs used to treat runoff must be capable of removing 80% of the average annual post development total suspended solids (TSS) load based on existing monitoring reports. BMPs are considered to meet these criteria if (1) they are designed in accordance with standards and specifications from a state or local program that has adopted these performance standards, or (2) there exists in-field performance monitoring data demonstrating compliance with the criteria. Data must conform to accepted protocol (e.g., Technology Acceptance Reciprocity Partnership [TARP], Washington State Department of Ecology) for BMP monitoring.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Use alternative surfaces (e.g., vegetated roofs, pervious pavement or grid pavers) and non-structural techniques (e.g., rain gardens, vegetated swales, disconnection of imperviousness, rainwater recycling) to reduce imperviousness and promote infiltration thereby reducing pollutant loadings. Use sustainable design strategies (e.g., Low Impact Development, Environmentally Sensitive Design) to design integrated natural and mechanical treatment systems such as constructed wetlands, vegetated filters, and open channels to treat stormwater runoff.
Standard Practice
Due to the potential for deicing fluid contamination, the use of these technologies must be weighed carefully to prevent larger contaminant issues, such as infiltration of ground water. Just as in SAM Credit 2.5.1 Stormwater Design: Quality Control, this credit is more applicable for landside uses or places that are not subject to aviation-related contaminants although some exceptions may be possible.
DC-30
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Evaluate Best Management Practices outlined in Chapter 4, Part 2 (Urban Runoff), on the United States environmental Protection Agency’s Guidance Specifying Management Measures for Sources of Nonpoint Pollution in Coastal Waters, January 1993 (document No EPA-840-B-92-002)
Evaluate first flush systems including slotted edge drains connected to underground holding tanks. First flush sediment would settle in the tanks and be removed at a later date for treatment and/or disposal.
Evaluate detention basins, detention ditches, ditch checks and other CDA BMPs for effective first flush treatment
Evaluate bioswales along roadways and parking areas to encourage groundwater infiltration of stormwater runoff for landside areas. These strategies should be designed to discourage wildlife habitat.
Minimize current treatment of all stormwater by reducing runoff. See SAM Credit 2.5.1 Stormwater Design: Quality Control
Evaluate pervious pavements for roadways, shoulders, non-traffic pavements, maintenance roads, utility yards, airside and landside parking facilities. Peak storm water runoff rates could be reduced. Storm sewer conveyance systems could be designed with reduced diameter pipes.
Install landscape to reduce runoff. See SAM Credits 3.3.1 Water Efficient Landscaping, Reduce by 50% and 3.3.2 Water Efficient Landscaping, No Potable Water Use or No Irrigation.
Install salt-tolerant plants near roadways and parking lots Develop a policy for optimal road salt usage balancing environmental and safety
concerns
Best Available Practice
Develop collection systems for de-icing runoff. The proposed runway and taxiway pavements would contain first flush systems along the edge of pavements and Central Deicing Facilities for aircraft. The first flush system could consist of slotted edge drains connected to underground holding tanks. Glycol contaminated snowmelt and minor storm water runoff would be captured in the tanks and removed for treatment, disposal or recycling.
Incorporate technologies, application techniques and/or designs to minimize glycol residual after application of deicing agents
Central Deicing Facilities could also be utilized to capture excess glycol from aircraft deicing operations in underground storage tanks
Use of “extensive” green roof systems encourages filtration and treatment of rainwater, evaporation of rainfall to the atmosphere and storm water retention
DC-31
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDIES
Central Deicing Facilities Toronto International Airport - Toronto, Ontario Canada
Toronto Airport reports that in an experimental pilot project, they were able to obtain glycol fluids in a concentration of at least 50 percent from recycled spent fluids having an original concentration of 8 to 10 percent. Toronto Airport reports that glycol water quality expedience events were reduced by 62.5 percent from 2001 to 2002 by the use of central deicing facilities.
http://www.aviationdeicing.com/index.php?option=com_content&view=article&id=50&Itemid=54
Fourth Runway at Washington Dulles International Airport Metropolitan Washington Airports Authority - Washington, D.C.
The Metropolitan Washington Airports Authority is taking an innovative approach to protecting the environment encompassing the new fourth runway. Five new biological treatment units (BTU’s) constructed adjacent to the runway will provide a cleansing effect to stormwater runoff in the area.
http://www.metwashairports.com/file/pr2008_11_20a.pdf
Bio-Retention System to Manage and Cleanse Stormwater John Burroughs School - Ladue, Missouri
The bio-retention system is primarily a plant- and soil-based filtration facility for parking lot stormwater runoff. Stormwater runoff flows downhill from the driveway and south parking lot into the highest cell, from which it slowly progresses into two lower cells until finally ending up in the pond. Initially, much of the water passes first through an underground vortex filter that spins under the power of the falling water. The cleaned water is then diverted from the vortex filter into the first bio-retention cell while the debris and impurities removed from the water collect at the bottom of the filter. Once a year, the collected sediment from the bottom of the vortex filter is pumped out for disposal. Water then flows into the three cells of the bio-retention basin, each of which has its own underground water holding chamber as well as above-ground plants and soil. Stands of native grasses and wildflowers in each cell help prevent evapotranspiration by shading the water, enhance soil composition, encourage biological activity, and promote the removal of pollutants before stormwater enters the pond. Another important benefit of the system is the prevention of rapid filling and flushing of the pond.
http://science.jburroughs.org/sdeken/bioretention.htm
Stormwater Quality Initiative Denver International Airport - Denver, Colorado
Denver International Airport was built with a dedicated system for the capture, conveyance, treatment, and discharge of stormwater contaminated with aircraft deicing fluids. The system includes seven dedicated deicing pads, five wastewater retention ponds, and an onsite deicing fluid recycling facility.
www.aci-na.org/static/entransit/Going%20Green%209-7-07.pdf
DC-32
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.6.1 Landscape and Exterior Design to Reduce Heat Islands: Non-Roof
1 Point
INTENT
Reduce heat islands (thermal gradient differences between developed and undeveloped areas) to minimize impact on microclimate and human and wildlife habitat.
REQUIREMENTS
OPTION 1 Use any combination of the following strategies for 50% of the site hardscape (including roads, sidewalks, courtyards and parking lots):
Provide shade from existing tree canopy or within five years of landscape installation; landscaping (trees) must be in place at the time of certification application. Installation should be consistent with CDA/OMP Specification 02905 – Sustainable Airport Landscaping. For any proposed plant species not listed, consult an FAA certified airport biologist to ensure the plants will not attract wildlife.
Provide shade from structures fully covered by solar photovoltaic panels Provide shade from architectural devices or structures that have a solar reflectance
index (SRI2) of at least 29. Implement a maintenance program that ensures these surfaces are cleaned at least every two years to maintain good reflectance.
Have paving materials with an SRI of at least 29 and implement a maintenance program that ensures these surfaces are cleaned at least every two years to maintain good reflectance
Have an open-grid pavement system (at least 50% pervious)
OR
OPTION 2 Place a minimum of 50% of parking spaces under cover (defined as under ground, under deck, under roof, or under a building). Any roof used to shade or cover parking must have an SRI of at least 29.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
DC-33
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Employ strategies, materials and landscaping techniques that reduce heat absorption of exterior materials. Use shade (calculated on June 21, noon solar time) from native or adapted trees and large shrubs, vegetated trellises or other exterior structures supporting vegetation (consistent with CDA/OMP Specification 02905 – Sustainable Airport Landscaping, and for any proposed plant species not listed, consult an FAA certified airport biologist to ensure the plants will not attract wildlife.) Consider the use of new coatings and integral colorants for asphalt to achieve light-colored surfaces instead of blacktop. Position photovoltaic cells to shade impervious surfaces.
Standard Practice
Unless the reflectance is determined directly through in-situ testing, the following default SRI values are to be used:
Material SRI
New Conventional “gray” concrete 35
Old (weathered) ” gray” concrete 19
New “white” concrete 86
Old (weathered) “white” concrete 45
New Asphalt 0
Old asphalt 6
Recommended Practice
Maximize light colored/high albedo pavement, such as portland cement concrete, for roadways, parking lots, sidewalks and plaza areas. Reflectance must be a minimum of 0.3. [‘White’ portland cement – 0.7 to 0.8, typical portland cement – 0.35 to 0.5, typical asphalt pavement – 0.05 (new) to 0.15 (over 5 years)].
Best Available Practice
For Landside projects only, install trees consistent with CDA/OMP Specification Section 02905 – Sustainable Airport Landscaping, and for any proposed plant species not listed, consult an FAA certified airport biologist to ensure the plants will not attract wildlife
A creative combination of the above strategies to reach this goal is encouraged. For example, a task/project can provide 5% shading of dark colored impervious surfaces and 25% light colored/high albedo pavement to achieve this goal.
DC-34
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Evaluate structured parking in lieu of asphalt paved surface lots. This provides additional ‘green’ areas and reduces stormwater runoff from roofs and potentially the size of storm sewer systems.
Evaluate open grid pavement for surface lots and site pavement Evaluate light-colored permeable pavers and concrete Evaluate “green walls” for building façade
DC-35
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.6.2 Landscape and Exterior Design to Reduce Heat Islands: Roof
1 Point
INTENT
Reduce heat islands (thermal gradient differences between developed and undeveloped areas) to minimize impact on microclimate and human and wildlife habitat.
REQUIREMENTS
OPTION 1 Use roofing materials having a Solar Reflectance Index (SRI) equal to or greater than the values in the table below for a minimum of 75% of the roof surface. If more than 75% of the roof area is covered with the SRI material, the SRI value may be lower than the required value if the resulting area-weighted equivalent SRI performance is at least as high as having the required value on 75% of the area.
OR
OPTION 2 Install a vegetated roof for at least 50% of the roof area.
OR
OPTION 3 Install high albedo and vegetated roof surfaces that, in combination, meet the following criteria:
(Area of SRI Roof / 0.75) + (Area of vegetated roof / 0.5) ≥ Total Roof Area
Roof Type Slope SRI Low-Sloped Roof ≤ 2:12 78 Steep-Sloped Roof > 2:12 29
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Consider installing high-albedo and vegetated roofs to reduce heat absorption. SRI is calculated according to ASTM E 1980. Reflectance is measured according to ASTM E 903, ASTM E 1918, or ASTM C 1549. Emittance is measured according to ASTM E 408 or ASTM C 1371. Product information is available from the Cool Roof Rating Council website, at www.coolroofs.org. Also, visit the ENERGY STAR website, www.energystar.gov, to research compliant products.
DC-36
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
White roofs are currently the standard for new construction on airport property. These are acceptable; however, SRI decreases with the age of the roof. Unless a cleaning program is in place, the benefits of white roofs diminish over time. For this reason, along with the benefits of stormwater management, the construction of green roofs is encouraged.
Recommended Practice
Evaluate and utilize an ENERGY STAR compliant roofing system, such as aluminum coating and light-colored coatings. Thermoplastic and white PVC roofing systems meet these standards.
Best Available Practice
Install a “green” vegetated roof on all or portions of new and existing buildings
CASE STUDY
Green Roofs Chicago Department of Aviation - Chicago, Illinois
The Chicago Department of Aviation (CDA) has made vegetated roofs a priority for any large roof construction at ORD or MDW. Although reducing the heat island effect is the primary goal of this credit, the CDA, with its large expanses of impervious pavement also looks to this technology for its stormwater management aspects. Where vegetated roofs are not used or if there is only partial coverage by a vegetated roof, a high reflectance roofing material in accordance with the requirements of this credit is encouraged to be used where applicable.
As of November 2012, there are a total of 13 vegetated roof projects totaling approximately 341,359 square feet at both airports. The projects include the following:
FedEx Cargo Sort Building (ORD) – 174,442 sq. ft
United Airlines Cargo Building (ORD) – 108,816 sq. ft.
South Airfield Lighting Control Vault (ORD) – 14,200 sq. ft
FedEx World Services Center (ORD) – 10,024 sq. ft
North Air Traffic Control Tower Base Building (ORD) – 8,910 sq. ft
Guard Post 1 Canopy (ORD) – 6,500 sq. ft
Enterprise Rental Car Maintenance Facility (ORD) – 3,627 sq. ft
Green Roof installation atop Guard Post 1 at O’Hare
DC-37
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Aircraft Rescue and Firefighting Facility #3 (ORD) – 3,440 sq. ft Elevated Parking Structure (MDW) – 3,179 sq. ft. FedEx Vehicle Maintenance Building (ORD) – 3,170 sp. ft Enterprise Rental Car Facility Customer Service Center (ORD) – 2,847 sq. ft Building #819 – Booster Pump Station (ORD) – 1,287 sq. ft North Air Traffic Control Tower ComEd Building (ORD) – 917 sq. ft
It should be noted that the areas above only include the vegetated roof area. In all cases a highly reflective roof (high SRI value) makes up the balance of the roof area. For example, the UAL Cargo Building has a total roof area of 229,558 sq. ft. of which 47% will is vegetated and the remaining will be a high SRI roof. In comparison, 100% of the Guard Post 1 Canopy is covered by a vegetated roof system.
In all cases, existing and proposed (thus far) vegetated roof systems are extensive, that is low profile (< 6 inches), and plants consist entirely of varieties of Sedum sp. to minimize wildlife attraction. Refer to CDA/OMP Specification 02905 – Sustainable Airport Landscaping, for additional details on acceptable plant species.
DC-38
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 SUSTAINABLE SITES
2.7 Light Pollution Reduction
1 Point
INTENT
Minimize light trespass from the building and site, reduce sky-glow to increase night sky access, improve nighttime visibility through glare reduction, and reduce development impact on nocturnal environments.
REQUIREMENTS
FOR INTERIOR LIGHTING
The angle of maximum candela from each interior luminaire as located in the building shall intersect opaque building interior surfaces and not exit out through the windows.
OR
All non-emergency interior lighting shall be automatically controlled to turn off during non-business hours. Provide manual override capability for after hours use.
AND
FOR EXTERIOR LIGHTING
Only light areas as required to meet FAA Regulation, Airline and Airport operational requirements, security, safety and comfort. Lighting Power Densities shall not exceed ASHRAE/IESNA Standard 90.1-2010 Addendum “I” for the classified zone.
All projects shall be classified under one of the following zones, as defined in IESNA RP-33, and shall follow all of the requirements for that specific zone:
LZ1 — Dark (Developed areas within national parks, state parks forest land and rural areas)
Design exterior lighting so that all site and building-mounted luminaires produce a maximum initial illuminance value no greater than 0.01 horizontal and vertical footcandles at the site boundary and beyond. Document that 0% of the total initial designed fixture lumens are emitted at an angle of 90 degrees or higher from nadir (straight down).
LZ2 — Low (Areas predominantly consisting of; Residential zoning, Neighborhood business districts, Light industrial with limited nighttime use, Residential mixed use areas)
Design exterior lighting so that all site and building mounted luminaires produce a maximum initial illuminance value no greater than 0.10 horizontal and vertical footcandles at the site boundary and no greater than 0.01 horizontal footcandles 10 feet beyond the site boundary.
DC-39
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Document that no more than 2% of the total initial designed fixture lumens are emitted at an angle of 90 degrees or higher from nadir (straight down). For site boundaries that abut public rights-of-way, light trespass requirements may be met relative to the curb line instead of the site boundary.
LZ3 — Medium (All other areas not included in LZ1, LZ2 or LZ4 such as Commercial/Industrial, High-Density Residential)
Design exterior lighting so that all site and building mounted luminaires produce a maximum initial illuminance value no greater than 0.20 horizontal and vertical footcandles at the site boundary and no greater than 0.01 horizontal footcandles 15 feet beyond the site. Document that no more than 5% of the total initial designed fixture lumens are emitted at an angle of 90 degrees or higher from nadir (straight down). For site boundaries that abut public rights-of-way, light trespass requirements may be met relative to the curb line instead of the site boundary.
LZ4 — High (High activity commercial districts in major metropolitan areas. To be LZ4 the area must be so designated by the local jurisdiction)
Design exterior lighting so that all site and building mounted luminaires produce a maximum initial illuminance value no greater than 0.60 horizontal and vertical footcandles at the site boundary and no greater than 0.01 horizontal footcandles 15 feet beyond the site. Document that no more than 10% of the total initial designed site lumens are emitted at an angle of 90 degrees or higher from nadir (straight down). For LZ2, LZ3 & LZ4 - For site boundaries that abut public rights-of-way, light trespass requirements may be met relative to the curb line instead of the site boundary. For ALL Zones - Illuminance generated from a single luminaire placed at the intersection of a private vehicular driveway and public roadway accessing the site, is allowed to use the centerline of the public roadway as the site boundary for 2 times the driveway width.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Adopt site lighting criteria to maintain safe light levels while avoiding off-site lighting and night sky pollution. Minimize site lighting where possible and model the site lighting using a computer model. Technologies to reduce light pollution include full cutoff luminaires, low-reflectance surfaces and low-angle spotlights.
Standard Practice
Use standard cutoffs on exterior lighting, wherever possible and appropriate.
DC-40
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Adopt site lighting criteria to maintain safe light levels while avoiding off-site lighting and night sky pollution
Minimize site lighting where possible The maximum candela value of all interior lighting shall fall within the building (not out
through windows) and the maximum candela value of all exterior lighting shall fall within the property
Consider a parking lot design which allows for a reduction of the available parking areas and the associated exterior lighting during non-use or low use hours
Evaluate smart-lighting control systems and LED light technologies
Best Available Practice
Model the site lighting using a computer model Consider full cutoff luminaries, low-reflectance, non-specular surfaces and low-angle
spotlights for roadway and building lighting
CASE STUDY
Total Lighting Control System T.F. Green International Airport - Providence, Rhode Island
The newly renovated terminal at T.F. Green International Airport implemented an energy-efficient and automated Total Lighting Control (TLC) system by General Electric. The system features programmable networked technology, controlling the internal and external lighting at the facility, including lights in the concourse areas, departure areas, baggage claims and outdoor parking areas.
http://www.glcs.ca/assets/images/geproducts/pdfs/tfgreen.pdf
DC-41
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Spraying site to minimize fugitive dust
Inlet protection
Automated People Mover System at O’Hare
Mass transit drop-off point at O’Hare
DC-42
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3.0 Water Efficiency
3.1 Prerequisite 1 – Water Use Reduction: 20% Reduction
Required
INTENT
Increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.
REQUIREMENTS
Employ strategies that in aggregate use 20% less water than the water use baseline calculated for the building (not including irrigation). The baseline shall meet the requirements of the Energy Policy Act of 1992 (EPAct 1992) and subsequent rulings by the Department of Energy, requirements of the Energy Policy Act of 2005, and the plumbing code requirements as stated in the 2006 editions of the Uniform Plumbing Code or International Plumbing Code as to fixture performance. Calculations are based on estimated occupant usage and shall include only the following fixtures and fixture fittings (as applicable to the building): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and pre-rinse spray valves.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
WaterSense™-certified fixtures and fixture fittings should be used where available. Use high-efficiency fixtures (water closets and urinals) and dry fixtures such as composting toilet systems to reduce the potable water demand. Consider the use of alternate on-site sources of water, such as rainwater, stormwater, or air conditioner condensate, and graywater for non-potable applications such as toilet and urinal flushing, as approved by the manufacturer, and for custodial uses.
Special consideration should be used to distinguish applicability of these technologies in high-volume passenger terminal areas versus office facilities, especially with respect to maintenance.
Standard Practice
Chicago Building Code (CBC) meets the Energy Policy Act of 1992 (EPAct 1992).
Recommended Practice
Must exceed CBC (EPAct 1992) by 20% to meet prerequisite
DC-43
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Use high-efficiency fixtures and valves, automatic flush sensors, aerators on faucets and dual-flush toilets
Use local generation of domestic hot water, as much as possible, to eliminate long piping runs associated with recirculation piping. Unless connecting to an existing hot water recirculating system.
Domestic hot water for general plumbing fixtures should be designed for a temperature of 140° F. maximum, but not less than 120° F
Best Available Practice
Install dry fixtures such as composting toilets and waterless urinals to reduce wastewater volumes
Use instantaneous hot water heating systems (i.e., tankless, on-demand hot water heating)
Use zones or sub-meters to measure and audit water consumption rates at points of use
Use reclaimed water for cooling tower makeup Evaluate pulsed-power electromagnetic water treatment, ultraviolet treatment, or
ozone treatment for cooling tower water Establish a water supply system that supports vehicle maintenance without the
use of potable water by using recycled water or diverted stormwater for vehicle and aircraft washing
CASE STUDY
See SAM Credit 3.2 Water Use Reduction: 30-40% Reduction.
DC-44
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3.0 Water Efficiency
3.2 Water Use Reduction: 30% - 40% Reduction
2 to 4 Points
INTENT
Further increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.
REQUIREMENTS
Employ strategies that in aggregate use less water than the water use baseline calculated for the building (not including irrigation). The minimum water savings percentage for each point threshold is as follows:
SAM Credit Water Reduction Points
3.2.1 30% 2
3.2.2 35% 3
3.2.3 40% 4
Calculate the baseline according to the commercial and/or residential baselines outlined below1. Calculations are based on estimated occupant usage and must include only the following fixtures and fixture fittings (as applicable to the project scope): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and pre-rinse spray valves.
Commercial Fixtures, Fittings, and Appliances
Current Baseline
Commercial toilets 1.6 gallons per flush (gpf)* Except blow-out fixtures: 3.5 (gpf)
Commercial urinals 1.0 (gpf)
1 Tables adapted from information developed and summarized by the U.S. Environmental Protection Agency (EPA) Office of Water based on requirements of the Energy Policy Act (EPAct) of 1992 and subsequent rulings by the Department of Energy, requirements of the EPAct of 2005, and the plumbing code requirements as stated in the 2006 editions of the Uniform Plumbing Code or International Plumbing Code pertaining to fixture performance.
DC-45
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Commercial Fixtures, Fittings, and Appliances
Current Baseline
Commercial lavatory (restroom) faucets 2.2 gallons per minute (gpm) at 60 pounds per square inch (psi), private applications only (hotel or motel guest rooms, hospital patient rooms) 0.5 (gpm) at 60 (psi)** all others except private applications 0.25 gallons per cycle for metering faucets
Commercial prerinse spray valves (for food service applications)
Flow rate ≤ 1.6 (gpm) (no pressure specified; no performance requirement)
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
WaterSense™-certified fixtures and fixture fittings should be used where available. Use high-efficiency fixtures (water dispensers, water closets and urinals) and dry fixtures such as composting toilet systems to reduce the potable water demand. Consider the use of alternate on-site sources of water, such as rainwater, stormwater, or air conditioner condensate, and graywater for non-potable applications such as toilet and urinal flushing, as approved by the manufacturer, and custodial uses.
Standard Practice
None
Recommended Practice
Use high-efficiency fixtures and valves, such as automatic sensors, aerators on lavatories and dual-flush toilets
Best Available Practice
Dry fixtures such as composting toilets and waterless urinals to reduce wastewater volumes
Use reclaimed water for cooling tower makeup Evaluate pulsed-power electromagnetic water treatment, ultraviolet treatment, or
ozone treatment for cooling tower water Establish a water supply system that supports vehicle maintenance without the
use of potable water by using recycled water or diverted stormwater for vehicle and aircraft washing
DC-46
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDIES
Recommendations for Maximizing Environmental Performance: Potable Water Fort Lauderdale Hollywood International Airport - Fort Lauderdale, Florida
Fort Lauderdale-Hollywood International Airport (FLL) was billed for over 65 million gallons of water from October 2005 through September 2006. Significant opportunities exist for further reducing the consumption of potable water and the burden imposed on sewer infrastructure and treatment. FLL currently uses low-flow toilets, sinks, and faucets in its restrooms. New technology, however, now exists that would enable FLL to further improve efficiency. According to the analysis conducted, the installation of lower-flow toilets, sinks, and urinals would cost about $234,000 and further reduce potable water consumption by 43 million gallons annually. This reduced water use would save the airport $281,000 annually and provide a payback of investment in ten months. FLL works cooperatively with tenants to reduce consumption by applying best management practices to sub-metered tenants and assessing the viability of overseeing water use through a centralized control monitoring system. An additional 142 million gallons of water was billed to 141 sub-metered airport related users during that same period of time. It appears that the sub-metered users are a combination of food service establishments (there are 27 such tenants in the airport as of October 2006), rental car companies, airlines, Federal Aviation Administration, Broward County Animal Control, Fort Lauderdale Small Boat Club and others.
http://www.docstoc.com/docs/87186095/Executive-Summary-The-Green-Airport-Initiative-at-Fort-Lauderdale-
Waterless Urinals Los Angeles Community College District - Los Angeles, California
The Los Angeles Community College District's (LACCD) has installed 1,224 cartridge-type waterless urinals at all nine of its community colleges. The waterless urinals are designed to benefit the District in three ways:
1. Each urinal will save approximately 40,000 gallons of water per year. Combined, that's a savings of almost 50 million gallons of water a year (enough water to fill 259 Olympic-sized pools);
2. Less water consumption will result in a decrease in water bills;
3. Waterless urinals will eliminate the need to send wastewater to treatment plants, therefore reducing the sewage costs District-wide.
Installation of the new waterless urinals is currently underway, with expected completion in February 2010.
http://standards.build-laccd.org/projects/dcs/pub/Green%20Papers/released/GP-010.pdf
DC-47
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3.0 Water Efficiency
3.3.1 Water Efficient Landscaping, Reduce by 50%
2 Points
INTENT
Limit or eliminate the use of potable water, or other natural surface or subsurface water resources available on or near the project site, for landscape irrigation.
REQUIREMENTS
Reduce potable water consumption for irrigation by 50% from a calculated mid-summer baseline case.
Reductions shall be attributed to any combination of the following items:
Plant species, density and microclimate factor Irrigation efficiency Use of captured rainwater Use of recycled wastewater Use of water treated and conveyed by a public agency specifically for non-potable uses
If the percent reduction of Potable Water is equal to or greater than 50%, credit for SAM Credit 3.3.1 Water Efficient Landscaping, Reduce by 50% is earned. If the percent reduction of Potable Water is 100% AND the percent reduction of Total Water is equal to or greater than 50%, credit for SAM Credit 3.3.2 Water Efficient Landscaping, No Potable Water Use or No Irrigation is earned in addition to credit for SAM Credit 3.3.1 Water Efficient Landscaping, Reduce by 50%.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Perform a soil/climate analysis to determine appropriate plant material and design the landscape with native or adapted plants to reduce or eliminate irrigation requirements. Where irrigation is required, use high-efficiency equipment and/or climate-based controllers.
Note that these landscaping strategies provide benefits for the following:
SAM Credits 2.5.1 Stormwater Design: Quantity Control and 2.5.2 Stormwater Design: Quality Control
SAM Credits 2.6.1 Landscape and Exterior Design to Reduce Heat Islands: Non-Roof and 2.6.2 Landscape and Exterior Design to Reduce Heat Islands: Roof
SAM Credits 4.2 Prerequisite 2 – Minimum Energy Performance and 4.4 Optimize Energy Performance
DC-48
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Groundwater seepage that is pumped away from the immediate vicinity of buildings slabs and foundations can be used for landscape irrigation and meet the intent of this credit. However, it must be demonstrated that doing so does not affect site stormwater management systems.
Standard Practice
Irrigation systems are not typically installed airside and the lower maintenance tall fescue is used for all projects per the following CDA/OMP Specifications:
o CDA/OMP Specification T-901 – Seeding
o CDA/OMP Specification 02931 – Seeding and Hydro-mulching
o CDA/OMP Specification 02905 – Sustainable Airport Landscaping, is the airport landscaping specification that deals with other plants and landscaping requirements.
Recommended Practice
Do not install an irrigation system Do not install plants that will require irrigation Utilize vegetation which may be acceptable for site use (native and/or low-
maintenance), with special consideration for vegetated green roofs. Utilize vegetation to reduce or eliminate irrigation requirements for landside areas.
Minimize the use of high maintenance lawns and annual plants Establish areas of high and low landscape maintenance areas. Group plants with
similar water-use needs by determining which areas of the site should receive a higher level of care than others and, during drought periods, more irrigation. Coordinate these areas with the irrigation plan. Higher maintenance areas should be located around the major building entries and high traffic areas. Lower maintenance areas should be located on low traffic areas, buffer zones and service areas.
Best Available Practice
Perform a soil and climate analysis to determine the appropriate landscape strategy
Evaluate stormwater and/or graywater cisterns for capturing rainwater from all new roofs for irrigation
If irrigation system must be installed, provide for soil moisture monitoring to reduce reliance on manual control and timed devices, as well as for detecting leaks
DC-49
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Sustainable Airport Landscaping Design Chicago Department of Aviation – Chicago, Illinois
For the Chicago Department of Aviation, the key focus of the landscaping design is that it is aesthetically pleasing and at the same time, low maintenance, ecologically and financially sustainable yet does not compromise airport security and aircraft safety, as defined below:
Minimize Wildlife Hazards – The landscaping criteria are intended to minimize wildlife hazards with particular emphasis on large birds (e.g. waterfowl, gulls, raptors), small mammals that may attract raptors, and small birds that congregate into large flocks (e.g. blackbirds, starlings). In general, landscape that provides food or shelter to these types of birds and small mammals is to be avoided.
Increase Landscape Sustainability – In concert with wildlife management, Airport landscaping must be low-maintenance and environmentally sound. Plants that have little or no maintenance requirements are to be used. Plants that minimize or eliminate fertilization, mowing, pest control, and irrigation are to be used whenever possible. Wherever possible, plants native to the Midwest region of the United States are to be used.
Safety and Security – All Airport safety and security protocols related to the placement of landscape features are adhered to in all cases. This may include sight lines for security-sensitive areas (i.e. guard posts) and the line-of-sight for the air traffic control towers and runway approaches.
Example:
Turf grasses – Low maintenance, drought resistant turf grasses are to be used in place of traditional lawn/turf grass (i.e. Kentucky bluegrass) whenever possible. The list of acceptable turf grasses was based on the following criteria:
Low or Slow Growing – Turf grass species are to grow at a rate that does not require excessive mowing, i.e. more than twice a month during the growing season or no more than six times a year or the mature height of the species does not exceed the recommended mow height.
Drought Tolerant – Turf grass species are to require no additional irrigation except during establishment. The species must be suitable to Chicago’s climate (USDA Zone 5) and precipitation ranges. Kentucky Bluegrass (Poa pratensis) varieties are not acceptable.
Non-Wildlife Attracting – Turf grass species are to be unattractive to wildlife either due to low palatability of the vegetation (e.g. endophyte toxicity) or through low seed production although the latter can be mitigated through mowing. Clover (Trifolium sp.) varieties are not acceptable.
DC-50
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Landside Landscape Uses – Areas where aesthetics will play a larger role such as the terminals, roadway approaches to the airport, landside normally-occupied buildings/facilities, and other areas of high visibility to the public must be designed using low-maintenance plants where possible. Examples of these uses include parking lot islands, roadway medians and/or roadsides, planting beds, large planter containers, building outdoor courtyards or common areas. Some allowances may be made for the use of annuals where appropriate (e.g. hanging planters, small containers, etc.). CDA/OMP Specification 02905 – Sustainable Airport Landscaping, includes a listing of approved plants and trees.
Airside Landscape Uses
Airfield Turf Areas – Areas of the airfield that are within 600’ of any active runway or taxiway are to be planted only with turf grasses. Mowing heights and frequencies are to be strictly enforced within these areas.
Trees – No trees of any kind are to be used anywhere within the AOA (Airside).
Shrubs – The basic landscaping criteria apply for selection of acceptable shrub species. In addition, mass plantings of shrubs or hedge rows are not allowed. Shrubs may be used only as ornamental specimen plants at any normally occupied airside building site or parking lot. Shrubs are not to be placed in open areas of the airfield. Shrubs must be maintained at a height no greater than 6’. Shrubs that mature at a height less than or equal to 6’ are preferable to reduce maintenance.
Green Roofs – Green roof species will typically include Sedum sp. (Stonecrop).
Ornamental Airside Landscaping – Areas where aesthetics are a higher priority, which include terminals, normally-occupied airside buildings/facilities, and the like, should include plants as indicated based on the criteria above, with some exceptions. Examples of these uses include parking lot islands, roadway medians and/or roadsides, planting beds, large planter containers, building outdoor courtyards or common areas.
DC-51
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3.0 Water Efficiency
3.3.2 Water Efficient Landscaping, No Potable Water Use or No Irrigation
2 Points (in addition to credit earned towards SAM Credit 3.3.1)
INTENT
Eliminate the use of potable water, or other natural surface or subsurface water resources available on or near the project site, for landscape irrigation.
REQUIREMENTS
Achieve credit towards SAM Credit 3.3.1 Water Efficient Landscaping, Reduce by 50% and:
Use only captured rainwater, recycled wastewater, recycled graywater, or water treated and conveyed by a public agency specifically for non-potable uses for irrigation.
OR
Install landscaping that does not require permanent irrigation systems. Temporary irrigation systems used for plant establishment are allowed only if removed within one year of installation.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Perform a soil/climate analysis to determine appropriate landscape types and design the landscape with indigenous plants to reduce or eliminate irrigation requirements. Consider using stormwater, graywater, and/or condensate water for irrigation.
Note that these landscaping strategies provide benefits for the following:
SAM Credits 2.5.1 Stormwater Design: Quantity Control and 2.5.2 Stormwater Design: Quality Control
SAM Credits 2.6.1 Landscape and Exterior Design to Reduce Heat Islands: Non-Roof and 2.6.2 Landscape and Exterior Design to Reduce Heat Islands: Roof
SAM Credits 4.2 Prerequisite 2 – Minimum Energy Performance and 4.4 Optimize Energy Performance
Standard Practice
Irrigation systems are not typically installed airside and the lower maintenance tall fescue is used for all projects per the following CDA/OMP Specifications:
o CDA/OMP Specification T-901 – Seeding o CDA/OMP Specification 02931 – Seeding and Hydro-mulching
DC-52
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
o CDA/OMP Specification 02905 – Sustainable Airport Landscaping, is the airport landscaping specification that deals with other plants and landscaping requirements.
Recommended Practice
Do not install an irrigation system Do not install plants that will require irrigation Utilize vegetation which may be acceptable for site use (native and/or low-
maintenance), with special consideration for vegetated green roofs. Utilize vegetation to reduce or eliminate irrigation requirements for landside areas.
Best Available Practice
Perform a soil and climate analysis to determine the appropriate landscape strategy
Evaluate stormwater and/or graywater cisterns for capturing rainwater from all new roofs for irrigation
CASE STUDY
Water Conservation and Management Programs Los Angeles World Airports – Los Angeles, California
Los Angeles World Airport (LAWA) recognizes that water is a precious resource in Southern California and it must be proactive in its water conservation efforts. LAWA has reduced its water consumption in its everyday operations and continues to find ways to re-use water from local treatment sources. As of 2008, Los Angeles International Airport (LAX) used reclaimed water to irrigate 35 percent of its landscaped acres. Each year 40.2 million gallons (123 acre-feet) of water has been conserved through the utilization of reclaimed water. Additionally, the airport’s car wash facilities use recycled water and the landscape irrigation systems are computer controlled. The toilets and sinks have also been converted to low flow fixtures in the terminals and buildings.
www.lawa.org/welcome_LAWA.aspx?id=1036
DC-53
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3.0 Water Efficiency
3.4 Innovative Wastewater Technologies
2 Points
INTENT
Reduce wastewater generation and potable water demand while increasing the local aquifer recharge.
REQUIREMENTS
OPTION 1 Reduce potable water use for building sewage conveyance by 50% through the use of water-conserving fixtures (water closets, urinals) or non-potable water (captured rainwater, recycled graywater, and on-site or municipally treated wastewater).
OR
OPTION 2 Treat 50% of wastewater on-site to tertiary standards. Treated water must be infiltrated or used on-site.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Specify high-efficiency fixtures and fittings and dry fixtures such as composting toilet systems and non-water using urinals to reduce wastewater volumes. Consider reusing stormwater or graywater for sewage conveyance or on-site mechanical and/or natural wastewater treatment systems. Options for on-site wastewater treatment include packaged biological nutrient removal systems and high-efficiency filtration systems.
Standard Practice
None
DC-54
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Use high-efficiency fixtures and valves Utilize fixtures such as dual flush toilets and waterless urinals to reduce
wastewater volumes Evaluate reusing stormwater for non-potable uses
Best Available Practice
Capture graywater from lavatories, showers and institutional dishwashing facilities for sewage conveyance or on-site wastewater treatment systems
CASE STUDY
Port of Portland Headquarters Portland International Airport – Portland, Oregon
In May 2010, the headquarters at Portland International Airport was unveiled, revealing cutting-edge technologies such as an innovative wastewater treatment and recycling system. The system, Living Machine, cleans wastewater through a series of holding tanks, many of which replicate the ecological processes in natural tidal wetlands. The cells alternatively fill and drain, moving the water through specially treated rocks containing microorganisms and plants. The process is so natural that 10 of the cells will appear to visitors as lush plant gardens. Six are located in the lobby at the first-floor entrance, and four are outside an adjoining wall. Based on the experiences at Living Machines installed in over a dozen other buildings around the world, it’s unlikely that visitors will ever suspect the cells are treating water from the building’s sinks, showers and toilets for reuse in toilets. The facility was recently awarded LEED platinum certification.
http://www.portofportland.com/prj_POP_HQP2_Home.aspx
DC-55
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 ENERGY & ATMOSPHERE
4.1 Prerequisite 1 – Fundamental Building Systems Commissioning
Required
INTENT
For occupied buildings, verify that the project’s energy related systems are installed, calibrated and perform according to the owner’s project requirements, basis of design, and construction documents.
REQUIREMENTS
The following commissioning process activities shall be completed by the commissioning team. Designate an individual as the Commissioning Authority (CxA) to lead, review and oversee the completion of the commissioning process activities.
o The CxA shall have documented commissioning authority experience in at least two building projects.
o The individual serving as the CxA shall be independent of the project’s design and construction management, though they may be employees of the firms providing those services. The CxA may be a qualified employee or consultant of the Owner.
o The CxA shall report results, findings and recommendations directly to the Owner.
o For projects smaller than 50,000 gross square feet, the CxA may include qualified persons on the design or construction teams who have the required experience.
The Owner shall document the Owner’s Project Requirements (OPR). The design team shall develop the Basis of Design (BOD). The CxA shall review these documents for clarity and completeness. The Owner and design team shall be responsible for updates to their respective documents.
Develop and incorporate commissioning requirements into the construction documents. Develop and implement a commissioning plan. Verify the installation and performance of the systems to be commissioned. Complete a summary commissioning report.
COMMISSIONED SYSTEMS Commissioning process activities shall be completed for the following energy-related systems, at a minimum:
Heating, ventilating, air conditioning and refrigeration (HVAC&R) systems (mechanical and passive) and associated controls
Lighting and daylighting controls
DC-56
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Domestic hot water systems Renewable energy systems (wind, solar etc.)
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Engage a CxA as early as possible in the design process. Determine the owner’s project requirements, develop and maintain a commissioning plan for use during design and construction and incorporate commissioning requirements in bid documents. Assemble the commissioning team, and prior to occupancy verify the performance of energy consuming systems. Complete the commissioning reports with recommendations prior to accepting the commissioned systems. Owners are encouraged to seek out qualified individuals to lead the commissioning process. Qualified individuals are identified as those who possess a high level of experience in the following areas:
Energy systems design, installation and operation Commissioning planning and process management Hands-on field experience with energy systems performance, interaction, start-up,
balancing, testing, troubleshooting, operation, and maintenance procedures Energy systems automation control knowledge
Although the commissioning process should start as early in the design process as possible, it is allowable to engage a CxA agent to execute fundamental commissioning after construction has begun.
Standard Practice
Commissioning Agents are typically engaged to conduct fundamental commissioning for buildings.
Recommended Practice
Review the design intent and the basis of design documentation Incorporate commissioning requirements into the construction documents Develop and utilize a commissioning plan Verify installation, functional performance, training, operations and maintenance
documentation Complete a commissioning report Provide the owner with a single manual that contains the information required for
re-commissioning systems Engage a commissioning team that does not include individuals directly
responsible for project design or construction management to evaluate both building and site systems as part of the commissioning plan
DC-57
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Priority Systems – high energy consuming systems o Central Building Automation system o All HVAC system equipment o Lighting controls and sensors o Site Lighting o Refrigeration systems o Vertical Transport o Building Envelope o Baggage handling systems (included in process loads: to promote
energy savings, use the exceptional calculation method described in ANSI/ASHRAE/IESNA 90.1-2010 G2.5)
o Information Technology Systems – IT (included in process loads: to promote energy savings, use the exceptional calculation method described in ANSI/ASHRAE/IESNA 90.1-2010 G2.5)
Lower Priority Systems – low energy consuming system. o Emergency Power Generators and Automatic Transfer Switching o Uninterruptible Power Supply systems o Life Safety systems; Fire protection Fire alarm, Egress pressurization o Lightning Protection o Domestic and Process water pumping and mixing systems o Equipment sound control systems o Data and Communication systems o Paging systems o Security systems o Irrigation systems o Plumbing o Illuminated guidance signage
DC-58
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
For Runways, Civil/Stormwater and Roadways/Rail projects this scope should include the following project components.
o For support and ancillary buildings include all of the applicable systems and assemblies noted above
o Runway lighting and illuminated signage o Runway NAVAIDS o Site lighting systems o Traffic signals o Stations (e.g., pump stations, lift stations, drainage pumps) o Heating/Deicing systems o Oil/water separators
Best Available Practice
None
DC-59
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 ENERGY & ATMOSPHERE
4.2 Prerequisite 2 – Minimum Energy Performance
Required
INTENT
Establish the minimum level of energy efficiency for the proposed building and civil infrastructure systems to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
The requirements for this credit will vary based on the type of project: building versus civil.
Select one of the five compliance path options described below. Options 1, 2, and 3 pertain to buildings; 4 and 5 pertain to civil/infrastructure projects.
OPTION 1 — WHOLE BUILDING ENERGY SIMULATION Demonstrate a 10% improvement in the proposed building performance rating for new buildings, or a 5% improvement in the proposed building performance rating for major renovations to existing buildings, compared with the baseline building performance rating. Calculate the baseline building performance rating according to the building performance rating method in Appendix G of ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda2) using a computer simulation model for the whole building project.
Appendix G of Standard 90.1-2010 requires that the energy analysis done for the building performance rating method include all energy costs associated with the building project. To achieve points using this credit, the proposed design must meet the following criteria:
Comply with the mandatory provisions (Sections 5.4, 6.4, 7.4, 8.4, 9.4 and 10.4) in Standard 90.1-2010 (with errata but without addenda).
Include all energy costs associated with the building project. Compare against a baseline building that complies with Appendix G of Standard 90.1-
2010 (with errata but without addenda1). The default process energy cost is 25% of the total energy cost for the baseline building. If the building’s process energy cost is less than 25% of the baseline building energy cost, the submittal must include documentation substantiating that process energy inputs are appropriate.
For the purpose of this analysis, process energy is considered to include, but is not limited to: office and general miscellaneous equipment, computers, elevators and escalators, kitchen
2 Project teams wishing to use ASHRAE approved addenda for the purposes of this credit may do so at their discretion. Addenda must be applied consistently across all SAM credits.
DC-60
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
cooking and refrigeration, laundry washing and drying, lighting exempt from the lighting power allowance (e.g., lighting integral to medical equipment) and other (e.g., waterfall pumps).
Regulated (non-process) energy includes lighting (such as for the interior, parking garage, surface parking, façade, or building grounds, except as noted above), HVAC (such as for space heating, space cooling, fans, pumps, toilet exhaust, parking garage ventilation, kitchen hood exhaust, etc.), and service water heating for domestic or space heating purposes.
Process loads must be identical for both the baseline building performance rating and the proposed building performance rating. However, project teams may follow the exceptional calculation method (ANSI/ASHRAE/IESNA Standard 90.1-2010) to document measures that reduce process loads. Documentation of process load energy savings must include a list of the assumptions made for both the base and the proposed design, and theoretical or empirical information supporting these assumptions.
OR
OPTION 2 — PRESCRIPTIVE COMPLIANCE PATH: ASHRAE Advanced Energy Design Guide Comply with the prescriptive measures of the ASHRAE Advanced Energy Design Guide appropriate to the project scope, outlined below. Project teams must comply with all applicable criteria as established in the Advanced Energy Design Guide for the climate zone in which the building is located.
PATH 1. ASHRAE Advanced Energy Design Guide for Small Office Buildings 2004 The building must meet the following requirements:
Less than 20,000 square feet Office occupancy
PATH 2. ASHRAE Advanced Energy Design Guide for Small Retail Buildings 2006 The building must meet the following requirements:
Less than 20,000 square feet Retail occupancy
PATH 3. ASHRAE Advanced Energy Design Guide for Small Warehouses and Self Storage Buildings 2008
The building must meet the following requirements:
Less than 50,000 square feet Warehouse or self-storage occupancy
OR
OPTION 3 — PRESCRIPTIVE COMPLIANCE PATH: Advanced Buildings™ Core Performance™ Guide
DC-61
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Comply with the prescriptive measures identified in the Advanced Buildings™ Core Performance™ Guide developed by the New Buildings Institute. The building must meet the following requirements:
Less than 100,000 square feet Comply with LEED 2009 Section 1: Design Process Strategies, and Section 2: Core
Performance Requirements Office, school, public assembly, and retail projects less than 100,000 square feet must
comply with LEED 2009 Section 1and Section 2 of the Core Performance Guide Other project types less than 100,000 square feet implement the basic requirements of
the Core Performance Guide Health care, warehouse and laboratory projects are ineligible for this path
OR
OPTION 4 — CIVIL/INFRASTRUCTURE PROJECTS Comply with the following measures based on the type of civil infrastructure project:
Exterior lighting applications (non-aviation related), such as roadways, surface parking lots, and covered parking garages, must meet the minimum illumination requirements of Tables 6-07-1 and 6-07-2 of Section 6-07 of the OMP Design and Construction Standards, Vol. II, Rev. 3 (June 1, 2006). For the purposes of establishing a baseline energy use, a conventional 400-watt lamp shall be assumed for each fixture, except for low-mast applications or covered areas where a 250-watt lamp is applicable. The benchmark standard shall assume that the lamps are run without lighting controls such as timers and motion sensors. Light sensors, however, should be taken into account.
Pumping systems not directly associated with buildings, which includes but is not limited to storm water conveyance pumps, sanitary pump stations, irrigation systems must be designed so that the operating design point (system curve intersect) shall be 60% to 120% of flow rate at the point of maximum operating efficiency. Pump motors must meet the minimum full-load efficiency requirements in ASHRAE/IESNA Standard 90.1-2010, Table 10.8, for 4-pole, enclosed motors at 1800 rpm.
The minimum standards for all aviation facilities and systems including navigation aids and runway/taxiway lighting shall be in accordance with FAA specifications and standards.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Design the building envelope and systems and any powered civil infrastructure systems to meet baseline requirements. Use a computer simulation model, where applicable, to assess the energy performance and identify the most cost-effective energy efficiency measures. Quantify energy performance as compared to a baseline building or civil project.
DC-62
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
If a local code has demonstrated quantitative and textual equivalence following, at a minimum, the U.S. Department of Energy (DOE) standard process for commercial energy code determination, then the results of that analysis may be used to correlate local code performance with ASHRAE 90.1-2010. Details on the DOE process for commercial energy code determination can be found at: http://www.energycodes.gov/regulations/determinations
Standard Practice
The Chicago Energy Conservation Code (CECC 2008) currently requires that buildings meet the 2006 International Energy Conservation Code (IECC) with an alternate compliance path of ASHRAE/IESNA 90.1-2004 standard with some exceptions.
Most exterior lighting, especially those used for roadway lighting, include the use of high pressure sodium or metal halide lamps with power ranging from 250W to 400W although pedestrian and alley applications may include lamps as low as 50W to 150 W. Induction lighting is used at the ramp areas and the South Cargo Tunnel.
Pre-Conditioned Air (PCA), 400 Hertz power, hydrant fueling and energy-efficient mobile loading bridges should be included with any new gates or gate retrofits.
Recommended Practice
Design buildings using the more current ASHRAE/IESNA 90.1-2010 standard.
Best Available Practice
None
SOURCES
Illinois Coalition for Responsible Outdoor Lighting. “Chicago: A Study in Outdoor Lighting Practices and Costs”, 2008. www.illinoislighting.org
American National Standards Institute/Hydraulic Institute (ANSI/HI), “Pump Systems Matter”, March 2005. www.pumps.org
OMP Design and Construction Standards, Vol. II, Rev. 3 (June 1, 2006), §6-07 Lighting
DC-63
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 ENERGY & ATMOSPHERE
4.3 Prerequisite 3 – Fundamental Refrigerant Management
Required
INTENT
Reduce stratospheric ozone depletion.
REQUIREMENTS
Zero use of CFC-based refrigerants in new base building HVAC&R systems. When reusing existing base building HVAC equipment, complete a comprehensive CFC phase-out conversion prior to project completion. Phase-out plans extending beyond the project completion date will be considered on their merits.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
When reusing existing HVAC systems, conduct an inventory to identify equipment that uses CFC-based refrigerants and provide a replacement schedule for these refrigerants. For new buildings, specify new HVAC equipment in the base building that uses no CFC refrigerants.
Standard Practice
Only HCFC and HFC refrigerants have been used for CDA projects where refrigerants were required (typically R-410a, which is an HFC)
Recommended Practice
None
Best Available Practice
Although HCFCs and HFCs have ozone depletion potentials (ODP) that are nearly zero, consideration should also be given to their global warming potentials (GWP) (see SAM Credit 4.7 Enhanced Refrigerant Management). Alternative refrigerants that minimize ODP and GWP compared to HCFCs and HFCs include natural refrigerants such as carbon dioxide, ammonia, and propane. These compounds have an ODP of zero and GWPs which are three orders of magnitude less than most HCFCs and HFCs.
DC-64
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Central Utilities System Toronto Pearson International Airport - Toronto, Ontario Canada
Sustainable principles were implemented in an effort to modernize Toronto Pearson International Airport and increase passenger capacity. A new central utilities plant replaced older equipment with a new HVAC system and a state-of-the-art deicing facility. The new system is supplied with chillers that use non-ozone depleting, chlorine free HFC-134a refrigerant. These chillers were customized to add extra temperature sensing capabilities to allow for closer monitoring of the chiller’s motor temperatures, while enhancing equipment safety though an effective preventative maintenance program.
www.xpedio.carrier.com/idc/groups/public/documents/marketing/casestudy19.pdf
DC-65
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 ENERGY & ATMOSPHERE
4.4 Optimize Energy Performance
1 to 19 Points
INTENT
Achieve increasing levels of energy performance beyond the prerequisite standard to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
The requirements for this credit will vary based on the type of project: building versus civil.
For Occupied and Unoccupied Building projects, the requirements will follow the compliance path options as identified in LEED. There are three compliance options, Options 1 to 3, that apply to buildings as described below. Civil projects will adhere to a compliance path, Option 4, that is similar to Option 1 except that the maximum achievable points will be 6, based on the threshold limits in the table below, or the prescriptive compliance path in Option 5. It is assumed that for any project type or compliance option SAM Credit 4.2 Prerequisite 2 – Minimum Energy Performance has been met.
OPTION 1 – WHOLE BUILDING ENERGY SIMULATION (1 to 19 points) Demonstrate a percentage improvement in the proposed building performance rating compared with the baseline building performance rating. Calculate the baseline building performance according to Appendix G of ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda) using a computer simulation model for the whole building project. The minimum energy cost savings percentage for each point threshold is as follows:
DC-66
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
The minimum energy cost savings percentage for each point threshold by type of project is as follows:
SAM Credit % Energy Reduction Over Baseline*
Points New Buildings
Existing Buildings
Civil**
4.4.1 12% 8% 8% 1 4.4.2 14% 10% 16% 2 4.4.3 16% 12% 24% 3 4.4.4 18% 14% 32% 4 4.4.5 20% 16% 40% 5 4.4.6 22% 18% 48% 6 4.4.7 24% 20% - 7 4.4.8 26% 22% - 8 4.4.9 28% 24% - 9
4.4.10 30% 26% - 10 4.4.11 32% 28% - 11 4.4.12 34% 30% - 12 4.4.13 36% 32% - 13 4.4.14 38% 34% - 14 4.4.15 40% 36% - 15 4.4.16 42% 38% - 16 4.4.17 44% 40% - 17 4.4.18 46% 42% - 18 4.4.19 48% 44% - 19
* Beyond baseline calculated in SAM Credit 4.2 Prerequisite 2 – Minimum Energy Performance ** Maximum available points for civil projects are 6. The rationale for this is that according to
“2003 Commercial Buildings Energy Consumption Survey” by the Energy Information Administration approximately 30% of overall energy use is due to exterior sources, primarily exterior lighting. Therefore, the SAM makes only 6 of the 19 points available to non-building, i.e. civil projects.
Example: An energy simulation indicated that the proposed energy savings for the new air traffic control tower (new building) was 17% over the ASHRAE/IESNA 90.1-2010 standard. The project would then achieve 3 points under this credit.
Appendix G of ASHRAE Standard 90.1-2010 requires that the energy analysis done for the Building Performance Rating Method include ALL of the energy costs within and associated with the building project. To achieve points using this credit, the proposed design must meet the following criteria:
Comply with the mandatory provisions in ASHRAE Standard 90.1-2010, Sections 5.4, 6.4, 7.4, 8.4, 9.4 and 10.4 (without amendments)
Include all the energy costs within and associated with the building project
DC-67
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Compare against a baseline building that complies with Appendix G to ASHRAE Standard 90.1-2010 (without amendments). The default process energy cost is 25% of the total energy cost for the baseline building. For buildings where the process energy cost is less than 25% of the baseline building energy cost, the submittal must include supporting documentation substantiating that process energy inputs are appropriate.
For the purpose of this analysis, process energy is considered to include, but is not limited to: office and general miscellaneous equipment, computers, elevators and escalators, kitchen cooking and refrigeration, laundry washing and drying, lighting exempt from the lighting power allowance (e.g., lighting integral to security operations) and other (e.g., waterfall pumps).
Regulated (non-process) energy includes lighting (such as for the interior, parking garage, surface parking, façade, or building grounds, except as noted above), HVAC (such as for space heating, space cooling, fans, pumps, toilet exhaust, parking garage ventilation, kitchen hood exhaust, etc.), and service water heating for domestic or space heating purposes.
For this credit, process loads shall be identical for both the baseline building performance rating and for the proposed building performance rating. However, project teams may follow the Exceptional Calculation Method (ASHRAE 90.1-2010 G2.5) to document measures that reduce process loads. Documentation of process load energy savings shall include a list of the assumptions made for both the base and proposed design, and theoretical or empirical information supporting these assumptions.
OR
OPTION 2 — PRESCRIPTIVE COMPLIANCE PATH: ASHRAE Advanced Energy Design Guide (1 Point) Comply with the prescriptive measures of the ASHRAE Advanced Energy Design Guide appropriate to the project scope, outlined below. Project teams must comply with all applicable criteria as established in the Advanced Energy Design Guide for the climate zone in which the building is located.
PATH 1. ASHRAE Advanced Energy Design Guide for Small Office Buildings 2004
The building must meet the following requirements:
Less than 20,000 square feet Office occupancy
PATH 2. ASHRAE Advanced Energy Design Guide for Small Retail Buildings 2006
The building must meet the following requirements:
Less than 20,000 square feet Retail occupancy
DC-68
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
PATH 3. ASHRAE Advanced Energy Design Guide for Small Warehouses and Self Storage Buildings 2008
The building must meet the following requirements:
Less than 50,000 square feet Warehouse or self-storage occupancy
OR
OPTION 3 — PRESCRIPTIVE COMPLIANCE PATH: Advanced Buildings™ Core Performance™ Guide (1-3 Points) Comply with the prescriptive measures identified in the Advanced Buildings™ Core Performance™ Guide developed by the New Buildings Institute. The building must meet the following requirements:
Less than 100,000 square feet Comply with Section 1: Design Process Strategies, and Section 2: Core Performance
Requirements Health care, warehouse or laboratory projects are ineligible for this path
Points achieved under Option 3 (1 point):
1 point is available for all office, school, public assembly, and retail projects less than 100,000 square feet that comply with Sections 1 and 2 of the Core Performance Guide
Up to 2 additional points may be awarded to projects that implement performance strategies listed in Section 3, Enhanced Performance. For every three strategies implemented from this section, one point is available.
The following strategies are not eligible for additional points under this Credit: o 3.1-Cool Roofs o 3.8-Night Venting o 3.13-Additional Commissioning
OR
OPTION 4 —COMPLIANCE PATH: CIVIL/INFRASTRUCTURE PROJECTS (1 – 6 Points) Up to 6 points may be awarded to Civil/Infrastructure projects. To obtain points in this credit, the energy usage of the respective infrastructure elements must exceed the benchmark requirements in SAM Credit 4.2 Prerequisite 2 – Minimum Energy Performance, Option 4, by the levels shown below:
DC-69
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Exterior Lighting (non-aviation related)
Exterior lighting applications (non-aviation related), such as roadways, surface parking lots and covered parking garages, the benchmark standard shall be equal to the energy use if all the fixtures on a project used 400-watt or 250-watt lamps, depending on the appropriate application (see also SAM Credit 4.2). Points are awarded when the proposed design reduces the energy use over the benchmark standard by the following levels:
1 point = 8% improvement over benchmark standard
2 points = 16% improvement over benchmark standard
3 points = 24% improvement over benchmark standard
4 points = 32% improvement over benchmark standard
5 points = 40% improvement over benchmark standard
6 points = 48% improvement over benchmark standard
NOTE: For parking lots associated with buildings, the parking lighting should be considered a part of the building’s electrical usage and therefore Options 1, 2, or 3 should be used. This option is to be used only for stand-alone parking areas or structures not directly associated with a building.
Example: The proposed design of a parking lot includes five high-mast light standards with two fixtures each and four lower level pedestrian lighting fixtures. The design calls for LED lighting to be used for all fixtures. The benchmark standard would be calculated such that there are 10 – 400 watt lamps for the parking lighting and 4 – 250 watt lamps for the pedestrian lighting. The benchmark standard is calculated to be 5,000 watts (10×400 + 4×250). The proposed LED lights are rated for 100 watts and 75 watts, respectively, for the parking and pedestrian lighting. Therefore, assuming no special lighting controls, the proposed energy rating for the project is 1,300 watts (10×100 + 4×75), a 74% reduction compared to the benchmark standard. This project would earn 6 points under this credit.
Pumping Systems
Pumping systems not directly associated with buildings, must exceed the minimum full-load efficiency requirements in ASHRAE/IESNA Standard 90.1-2010, Table 10.8, for 4-pole, enclosed motors at 1800 rpm by the following levels:
1 point = 8% improvement over benchmark standard
2 points = 16% improvement over benchmark standard
3 points = 24% improvement over benchmark standard
4 points = 32% improvement over benchmark standard
DC-70
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5 points = 40% improvement over benchmark standard
6 points = 48% improvement over benchmark standard
Airfield Lighting
For runway/taxiway lighting, exceed the minimum FAA specifications by the levels below. Note that the benchmark calculation shall assume that conventional lights are used throughout the project and that the calculation must be based on annual energy consumption and use seasonal climate data for the region, where applicable.
1 point = 8% improvement over benchmark standard
2 points = 16% improvement over benchmark standard
3 points = 24% improvement over benchmark standard
4 points = 32% improvement over benchmark standard
5 points = 40% improvement over benchmark standard
6 points = 48% improvement over benchmark standard
For projects that include multiple infrastructure elements such as those listed above, a weighted average based on the annual energy usage shall apply.
Example: A roadway project that includes a lift station realizes an annual energy savings of 65% over the benchmark standard for roadway lighting and 15% over the benchmark standard for pump systems. If the annual energy usage of the roadway lighting and the lift station is 40,000 kWh and 60,000 kWh, respectively, then the overall annual energy savings for the project is 35%. Therefore, 4 points are earned for this credit.
In some cases, there may be powered infrastructure elements that do not appear in the categories above for Option 4. In those cases, the designer may chose to demonstrate the energy savings based on an appropriate benchmark and submit for SRP review.
OR
Example Calculation:
(65%)(40,000 kWh) + (15%)(60,000 kWh)= 35%
100,000 kWh
= 35% overall energy savings for entire project; therefore 4 points earned for SAM Credit 4.4
DC-71
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
OPTION 5 – PRESCRIPTIVE COMPLIANCE PATH: CIVIL/INFRASTRUCTURE PROJECTS (1 – 3 Points) For civil/infrastructure projects, in lieu of performing a detailed energy usage calculation, a prescriptive compliance path is available. To earn points using this method, the project must meet SAM Credit 4.2 Prerequisite 2 – Minimum Energy Performance, Option 4, where applicable, and use any of the energy saving technologies or strategies listed in the table below.
A point is awarded for each of the following technologies up to a maximum of 3 points for this credit.
Technology/Strategy Points
LED lighting for roadways, parking areas, or pedestrian areas 1
LED runway lights or taxiway lights 1
Nighttime/motion sensor or electronically-controlled ballast activation for roadway, parking, or pedestrian lighting, as applicable, with special consideration for safety.
1
High efficiency motors, >92% at full load for all motor horsepower ratings 1
Variable speed drive for pump motors 1
Solar powered signage, lighting, or equipment 1
The SRP will consider other proposed strategies or technologies 1 NOTE: The awarding of points will be at the discretion of the SRP.
Example: A service road that meets the requirements of SAM Credit 4.2 Prerequisite 2 – Minimum Energy Performance also uses LED fixtures for the roadway lighting (1 point) and uses light sensors to turn these lights on/off automatically depending on ambient light levels (additional 1 point). This project would earn 2 points overall for this credit.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Design the building envelopes, infrastructure, and powered systems to maximize energy performance. Use a computer simulation models or engineering design calculations to assess the energy performance and identify the most cost-effective energy efficiency measures. Quantify energy performance compared with a baseline building or infrastructure system.
Standard Practice
For Buildings: The Chicago Energy Conservation Code (CECC 2008) currently requires that buildings meet the 2006 International Energy Conservation Code (IECC) which has an alternate compliance path of following ASHRAE/IESNA 90.1-2004 standard with some exceptions. LEED 2009 and the SAM require the more current ASHRAE/IESNA 90.1-2010 standard.
DC-72
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
For Civil/Infrastructure: Exterior lighting is typically high pressure sodium or metal halide lamps. Larger pump systems use variable frequency drives and efficient motors. LED lights are standard practice for all taxiways. Newer pump stations have installed variable speed drives and high efficiency motors.
Recommended Practice
Consider the following for buildings and structures:
Use a computer simulation model to assess energy performance and identify the most cost effective energy measures
Provide high-efficiency motors and variable-speed pumping systems Provide energy efficient lighting systems including LED, fluorescent lighting, solar
lighting and the use of lighting sensors or timers Organize circuiting of lighting and building systems so that individual areas may
be separately controlled relative to daylight and heating/cooling zones Orient building to optimize passive solar and/or daylight penetration Optimize architectural features for daylighting and glare control. Consider light
shelves, ceiling design, window placement, and window treatments Provide motion sensors in stairs, toilet rooms, storage rooms and equipment
rooms unless life safety is compromised Provide “Energy Star” compliant equipment and appliances Control air infiltration through all exterior openings including loading docks Use LED lighting, wherever applicable Optimize lighting controls for energy savings and function Provide daylight harvesting control systems Use high performance glazing (double glazed, low-e) and window systems Evaluate appropriate levels of insulation and for building envelope
Consider the following for all civil and infrastructure projects :
Use LED lighting wherever applicable and approved for: o Runways, as approved o Taxiways o Distance remaining signs o In-surface fixtures o Obstruction lighting o NAVAIDS and windsocks o Ramp area lighting o Traffic signals/Stop signs o Directional signs o Other areas, as approved
DC-73
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
o LED lighting for roadways, parking areas, or pedestrian areas
Nighttime/motion sensor or electronically-controlled ballast activation for roadway, parking, or pedestrian lighting, as applicable, with special consideration for safety
High efficiency motors, generators and pumps Variable speed drives for pump motors Solar powered signage, lighting, or equipment
Best Available Practice
Consider the following for buildings and structures:
Evaluate cogeneration for new terminals and concourses Integrate lighting systems with Building Automation System Use spectrally selective glazing Evaluate underfloor air distribution systems in office-type spaces Evaluate thermal mass for building envelope Evaluate “green walls” for building façade Utilize premium efficiency motors where applicable Ground-source heat pumps for pre-heating/pre-cooling of water systems For in-terminal seating – integrated power stations
Consider the following for civil and infrastructure projects:
Use induction lighting Comprehensive “smart” systems for lighting and signage Reduce energy transmission loss Proximity of power sources/on-site generation Nanotechnologies and biomimicry
CASE STUDIES
Delta Airlines Terminal A Boston Logan International Airport - Boston, Massachusetts
Terminal A at Boston Logan International Airport has become the first airport terminal in the country to win certification for its green technology. The terminal, which opened to Delta Air Lines customers in March 2005, received the Leadership in Energy and Environmental Design certification for Environmental Sustainability from the US Green Building Council.
www.boston.com/news/local/articles/2006/08/02/logans_terminal_a_goes_green/
DC-74
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Moving Walkways Boston Logan International Airport - Boston, Massachusetts
Boston Logan International Airport is undergoing tests on energy-efficient moving walkways. The walkways are equipped with EcoStart, which contains a motor efficiency controller that soft starts an electric motor, bringing it from rest to full speed. Once at full speed, the EcoStart monitors the motor and improves its efficiency when operating. Initial test efforts are estimated to conserve approximately 60,000 kilowatt-hours (kWh) per year.
www.automation.com/content/boston-logan-international-airport-saves-energy-on-moving-walks-in-project-with-kone-inc-and-power-efficiency-corporation
Baggage Check-In Building Reno-Tahoe International Airport - Reno, Nevada
The new airport baggage check-in building at Reno-Tahoe International Airport was designed with an efficient HVAC system, in addition to utilization of energy-efficient entryways to reduce heat/cooling loss. This helps the airport monitor and reduce overall energy use.
http://southwest.construction.com/southwest_contractor_projects/2010/1201_InternationalAirport.asp
DC-75
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 ENERGY & ATMOSPHERE
4.5 On-Site Renewable Energy
1 to 7 Points
INTENT
Encourage and recognize increasing levels of on-site renewable energy self-supply in order to reduce environmental and economic impacts associated with fossil fuel energy use.
REQUIREMENTS
Use on-site renewable energy systems to offset building energy cost. Calculate project performance by expressing the energy produced by the renewable systems as a percentage of the building annual energy cost and using the table below to determine the number of points achieved.
Determine the percentage of energy derived from renewable energy equipment against the proposed energy cost calculated for SAM Credit 4.4 Optimize Energy Performance. If no energy model was prepared for SAM Credit 4.4 Optimize Energy Performance, use the Department of Energy (DOE) Commercial Buildings Energy Consumption Survey (CBECS) database to determine the estimated electricity use in the case of a building project. For civil projects, the portion of energy derived from renewable energy systems will be based on the fraction of the total energy replaced with on-site generated renewable energy assuming the project used conventional energy supplies (utility supplied electricity and gas).
SAM Credit 8.4 Menu Items address the use of lesser amounts renewable energy on a project, amounts that do not meet the 1% threshold in this credit.
SAM Credit Percentage of Renewable Energy Points
4.5.1 1% 1
4.5.2 3% 2
4.5.3 5% 3
4.5.4 7% 4
4.5.5 9% 5
4.5.6 11% 6
4.5.7 13% 7
Example: A civil project, for example a pumping station, with a proposed energy consumption calculated at 100,000 kWh per year assuming all its energy was supplied by utility electricity, installed a wind turbine that can generate 6,000 kWh per year or 6% of the total proposed energy consumption. The project would then achieve 3 points under this credit.
DC-76
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Assess the project for non-polluting and renewable energy potential including solar, wind, geothermal, low-impact hydro, biomass and bio-gas strategies. When applying these strategies, take advantage of net metering with the local utility. Energy systems which are not eligible for this credit (but may be applicable under another credit) include architectural features such as daylighting and passive solar techniques, ground source heat pumps using small quantities of deep earth heat and vapor compression systems, and renewable energy from off-site sources.
Standard Practice
The following are Standard Practice:
Solar powered signage Solar powered RPU for weather sensors Solar powered obstruction and barricade lighting Solar thermal water heating has been used at a number of locations, such as the ARFF
Station #2, which has a system that provides hot water for up to 18 full time occupants
Recommended Practice
None
Best Available Practice
The following technologies should be considered for any applicable projects:
Roof-mounted or building integrated photovoltaic panels Electricity generation using bio-fuels (untreated wood waste, agricultural crops or waste,
landfill gas) Solar-thermal water or air heating Geothermal heating systems Geothermal electrical systems
DC-77
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDIES
Wind Turbines Boston Logan International Airport - Boston, Massachusetts
A fleet of miniature wind turbines at Boston Logan International Airport, each 6-foot-tall, placed at the edge of the rooftop of the airport's headquarters, is affixed at a unique angle to capture the winds that gust through Boston Harbor and climb the building's walls. The 20 turbines, installed in July 2008, are expected to generate about 100,000 kilowatt-hours annually, equal to 3% of the building's energy needs.
www.leedbuilding.org/News/USGBCInTheNewsDetails.aspx?ID=3829
Hangar 25 Bob Hope Airport - Burbank, California
Hangar 25 at Bob Hope Airport, Burbank, California, is a $17 million structure designed to be a model of green construction and was built for what a traditional aircraft hangar would cost, according to Andy Meyers, president of Shangri-La Construction. The hangar features solar panels, skylights, artificial grass, low-flush toilets, and massive aerating fans. Situated on a former industrial lot with a cement slab, the hangar property now houses a state-of-the-art green aviation hangar minimizing the 51,000-square-foot building's carbon footprint. Avjet Corp. is the building owner. The building received a Platinum LEED® certification. In addition to providing power to run the tools and machines to maintain the planes, the energy from the solar panels on the roof powers the building's offices, copiers, computers and coffee machines. The building generates 110 percent of the energy it needs and then gives the surplus energy back to the municipal grid. Grates at the building's entrance scrape off contaminants under shoes. No toxic chemicals fill the fire suppression system. The concrete floor has no chemical polymers. In the office area, all of the cabinets are made of Plyboo®, a type of bamboo with a water-based finish.
www.usgbc.org/News/USGBCInTheNewsDetails.aspx?ID=3899
Author: Jerry Berrios, Contra Costa Times, December 10, 2008 See Also: http://3030nclybournavenue.com/files/hangar_project_summary.pdf www.huffingtonpost.com/paige-donner/greening-hollywood-jet-ha_b_150102.html
DC-78
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Solar Power System Denver International Airport ‐ Denver, Colorado
Denver’s second large-scale solar power system became operational in December 2009; this new 1.6 MW Sharp solar power array powers the airport’s fuel-storage and distribution facility. Just a year prior in 2008, the airport introduced the first solar power array that consisted of a two megawatt solar panel system designed to generate over three million kilowatt hours of clean electricity annually. These cost-effective energy systems were developed by a public-private partnership utilizing tax credits and incentives. This initiative shows that airports can embrace renewable energy in a financially viable way and increase the overall sustainability of their operations.
http://files.sharpusa.com/Downloads/Solar/CaseStudy/sol_dow_Denver_Airport_Case_Study.pdf
And
http://www.solarnovus.com/index.php?option=com_content&view=article&id=404:16mw-solar-project-completed-at-denver-international-airport&catid=41:applications-tech-news&Itemid=245
DC-79
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 ENERGY & ATMOSPHERE
4.6 Enhanced Commissioning
2 Points
INTENT
Begin the commissioning process early in the design process and execute additional activities after systems performance verification is completed.
REQUIREMENTS
Implement, or have a contract in place to implement, the following additional commissioning process activities in addition to the requirements of SAM Credit 4.1 Prerequisite 1 – Fundamental Building Systems Commissioning:
Prior to the start of the construction documents phase, designate an independent Commissioning Authority (CxA) to lead, review, and oversee the completion of all commissioning process activities.
o The CxA shall have documented commissioning authority experience in at least two building projects.
o The individual serving as the CxA:
Must be independent of the work of design and construction;
Must not an employee of the design firm, though they may be contracted through them;
Must not be an employee of, or contracted through, a contractor or construction manager holding construction contracts; and
May be a qualified employee or consultant of the Owner.
o The CxA must report results, findings and recommendations directly to the Owner.
The CxA must conduct, at a minimum, 1 commissioning design review of the Owner’s Project Requirements (OPR), Basis of Design (BOD), and design documents prior to mid-construction documents phase and back-check the review comments in the subsequent design submission.
The CxA must review contractor submittals applicable to systems being commissioned for compliance with the OPR and BOD. This review shall be concurrent with A/E reviews and submitted to the design team and the Owner.
DC-80
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
The CxA or other project team members must develop a systems manual that gives future operating staff the information needed to understand and optimally operate the commissioned systems.
The CxA or other project team members must verify that the requirements for training operating personnel and building occupants are completed.
The CxA must be involved in reviewing the operation of the building with operations and maintenance (O&M) staff and occupants within 10 months after substantial completion. A plan for resolving of outstanding commissioning-related issues must be included.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Although it is preferable that the CxA be contracted by the Owner, for the enhanced commissioning credit, the CxA may also be contracted through the design firms or construction management firms not holding construction contracts. The LEED Reference Guide provides detailed guidance on the rigor expected for following process activities:
Commissioning design review Commissioning submittal review Systems manual
Though the commissioning process should start as early in the design process as possible, it is allowable to engage a CxA agent to conduct the design review required after construction has started, so long as the project team agrees to implement any requested changes both to the documents and to construction that may have already occurred.
Standard Practice
None
Recommended Practice
Review the design intent and the basis of design documentation Incorporate commissioning requirements into the construction documents Develop and utilize a commissioning plan Verify installation, functional performance, training, operations and maintenance
documentation Complete a commissioning report Provide the owner with a single manual that contains the information required for
re-commissioning systems Engage a commissioning team that does not include individuals directly
responsible for project design or construction management to evaluate both
DC-81
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
building and site systems as part of the commissioning plan Priority Systems - high energy consuming systems.
o Central Building Automation system o All HVAC system equipment o Lighting controls and sensors o Site Lighting o Refrigeration systems o Vertical Transport o Building Envelope o Baggage handling systems (included in process loads: to promote
energy savings, use the exceptional calculation method described in ANSI/ASHRAE/IESNA 90.1-2010 G2.5)
o Information Technology Systems - IT (included in process loads: to promote energy savings, use the exceptional calculation method described in ANSI/ASHRAE/IESNA 90.1-2010 G2.5)
Lower Priority Systems – low energy consuming system. o Emergency Power Generators and Automatic Transfer Switching o Uninterruptible Power Supply systems o Life Safety systems; Fire protection Fire alarm, Egress pressurization o Lightning Protection o Domestic and Process water pumping and mixing systems o Equipment sound control systems o Data and Communication systems o Paging systems o Security systems o Irrigation systems o Plumbing o Illuminated guidance signage
For Runways, Civil/Stormwater and Roadways/Rail projects this scope should include the following project components.
o For support and ancillary buildings include all of the applicable systems and assemblies noted above
o Runway lighting and illuminated signage o Runway NAVAIDS o Site lighting systems o Traffic signals o Stations (e.g., pump stations, lift stations, drainage pumps) o Heating/Deicing systems o Oil/water separators
DC-82
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
None
CASE STUDY
STAR Program Metropolitan Airports Commission – Minneapolis, Minnesota
Minneapolis – St. Paul International Airport recently launched the Stewards of Tomorrow’s Airport Resources (STAR) initiative. Airport operators develop and implement sustainable solutions that address long-term environmental, operational, financial and social needs. Goals include minimizing impacts to air quality, reducing waste reduction and hazardous materials use, as well as developing alternative energy programs.
www.enviro.aero/MSPSTAR.aspx
DC-83
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 ENERGY & ATMOSPHERE
4.7 Enhanced Refrigerant Management
2 Points
INTENT
Reduce ozone depletion and support early compliance with the Montreal Protocol while minimizing direct contributions to global warming.
REQUIREMENTS
OPTION 1 Do not use refrigerants.
OR
OPTION 2 Complete both of the following:
Select refrigerants and HVAC&R that minimize or eliminate the emission of compounds that contribute to ozone depletion and global warming. The base building HVAC&R equipment shall comply with the following formula, which sets a maximum threshold for the combined contributions to ozone depletion and global warming potential:
LCGWP + LCODP x 105 ≤ 100 Where:
LCODP = [ODPr x (Lr x Life +Mr) x Rc]/Life
LCGWP = [GWPr x (Lr x Life +Mr) x Rc]/Life
LCODP: Lifecycle Ozone Depletion Potential (lb CFC11/Ton-Year)
LCGWP: Lifecycle Direct Global Warming Potential (lb CO2/Ton-Year)
GWPr: Global Warming Potential of Refrigerant (0 to 12,000 lb CO2/lbr)
ODPr: Ozone Depletion Potential of Refrigerant (0 to 0.2 lb CFC11/lbr)
Lr: Refrigerant Leakage Rate (0.5% to 2.0%; default of 2% unless otherwise demonstrated)
Mr: End-of-life Refrigerant Loss (2% to 10%; default of 10% unless otherwise demonstrated)
Rc: Refrigerant Charge (0.5 to 5.0 lbs of refrigerant per ton of cooling capacity)
Life: Equipment Life (10 years; default based on equipment type, unless otherwise demonstrated)
DC-84
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
For multiple types of equipment, a weighted average of all base building level HVAC&R equipment shall be applied using the following formula:
[ Σ (LCGWP + LCODP x 105) x Qunit ] / Qtotal ≤ 100 Where:
Qunit = Cooling capacity of an individual HVAC or refrigeration unit (Tons)
Qtotal = Total cooling capacity of all HVAC or refrigeration
Small HVAC units (defined as containing less than 0.5 lbs of refrigerant), and other equipment such as standard refrigerators, small water coolers, and any other cooling equipment that contains less than 0.5 lbs of refrigerant, are not considered part of the “base building” system and are not subject to the requirements of this credit.
AND
Do not install fire suppression systems that contain ozone-depleting substances (CFCs, HCFCs or Halons).
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Design and operate the facility without mechanical cooling and refrigeration equipment. Where mechanical cooling is used, utilize base building HVAC and refrigeration systems for the refrigeration cycle that minimize direct impact on ozone depletion and global warming. Select HVAC&R equipment with reduced refrigerant charge and increased equipment life. Maintain equipment to prevent leakage of refrigerant to the atmosphere. Utilize fire suppression systems that do not contain HCFCs or Halons.
Standard Practice
None
Recommended Practice
None
Best Available Practice
Use natural refrigerants (carbon dioxide, ammonia, propane) where possible, in order to minimize ODPs and GWPs
DC-85
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 ENERGY & ATMOSPHERE
4.8 Measurement and Verification
3 Points
INTENT
Provide for the ongoing accountability of building energy consumption over time.
REQUIREMENTS
Develop and implement a Measurement and Verification (M&V) Plan consistent with Option D: Calibrated Simulation (Savings Estimation Method 2), or Option B: Energy Conservation Measure Isolation, as specified in the International Performance Measurement & Verification Protocol (IPMVP) Volume III: Concepts and Options for Determining Energy Savings in New Construction, April, 2003.
The M&V period shall cover a period of no less than one year of post-construction occupancy
SUBMITTALS
Include descriptive narrative in SAM Checklist and M&V Plan.
TECHNOLOGY/STRATEGY
Develop an M&V Plan to evaluate building and/or energy system performance. Characterize the building and/or energy systems through energy simulation or engineering analysis. Install the necessary metering equipment to measure energy use. Track performance by comparing predicted performance to actual performance, broken down by component or system as appropriate. Evaluate energy efficiency by comparing actual performance to baseline performance.
While the IPMVP describes specific actions for verifying savings associated with energy conservation measures (ECMs) and strategies, this Credit expands upon typical IPMVP M&V objectives. M&V activities should not necessarily be confined to energy systems where ECMs or energy conservation strategies have been implemented. The IPMVP provides guidance on M&V strategies and their appropriate applications for various situations. These strategies should be used in conjunction with monitoring and trend logging of significant energy systems to provide for the ongoing accountability of building energy performance.
Standard Practice
None
DC-86
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Install continuous metering equipment for the following end-uses: o Lighting systems and controls o Constant and variable motor loads o Variable frequency drive (VFD) operation o Chiller efficiency at variable loads (kW/ton) o Cooling load o Air and water economizer and heat recovery cycles o Air distribution static pressures and ventilation air volumes o Boiler efficiencies o Building-related process energy systems and equipment o Indoor water risers and outdoor irrigation
Develop a Measurement and Verification plan that incorporates the monitoring information from the above end-uses and is consistent with Option B, C or D of the 2001 International Performance Measurement & Verification Protocol (IPMVP) Volume I: Concepts and Options for Determining Energy and Water Savings.
Investigate whether these facilities will be included in the City of Chicago’s Global Building Monitoring System
Consider the recommendations included in the Chicago Climate Action Plan
Best Available Practice
Draft a Measurement and Verification Plan to apply during building operation that compares predicted savings to those achieved
CASE STUDY
Airport Monitoring System San Francisco International Airport – San Francisco, California
Energy and building management systems assist in controlling and monitoring mechanical and electrical systems in airport buildings. The utilities management system at San Francisco International Airport ensures efficient energy distribution and helps to diagnose the maintenance needs for HVAC, lighting, and other electrical systems, as well as optimizes energy consumption.
DC-87
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 ENERGY & ATMOSPHERE
4.9 Green Power
2 Points
INTENT
Encourage the development and use of grid-source, renewable energy technologies on a net zero pollution basis.
REQUIREMENTS
Engage in at least a 2-year renewable energy contract to provide at least 35% of the building’s electricity from renewable sources, as defined by the Center for Resource Solutions Green-e Energy product certification requirements.
OPTION 1 - DETERMINE THE BASELINE ELECTRICITY USE Use the annual electricity consumption from the results of the subparts of SAM Credit 4.4 Optimize Energy Performance.
OR
OPTION 2 - ESTIMATE BASELINE ELECTRICITY USE Use the U.S. Department of Energy Commercial Buildings Energy Consumption Survey database to determine the estimated electricity use.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Determine the energy needs of the building and investigate opportunities to engage in a green power contract. Green power is derived from solar, wind, geothermal, biomass or low-impact hydro sources. Visit www.green-e.org/energy for details about the Green-e program. The power product purchased to comply with credit requirements need not be Green-e certified. Other sources of green power are eligible if they satisfy the Green-e program’s technical requirements. Renewable energy certificates (RECs), tradable renewable certificates (TRCs), green tags and other forms of green power that comply with Green-e’s technical requirements can be used to document compliance with this section.
DC-88
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
Determine the City of Chicago’s Green Power requirements for the task/project and investigate opportunities to engage in a green power contract with the utility
Visit www.green-e.org for details about the Green-e program
Best Available Practice
None
CASE STUDIES
Green Power Los Angeles World Airports - Los Angeles, California
Los Angeles World Airports (LAWA) has embraced energy efficiency for over 20 years. The efficient use of energy and the incorporation of green power are critical factors in sustainable operations at LAWA’s facilities. LAWA has retrofitted existing buildings with energy efficient lighting fixtures, ballasts and bulbs. It has upgraded 80 percent of the building air handling units with variable speed drives and soft-start controls. Additionally, 60 percent of LAWA computer servers have been upgraded to high efficiency servers. Twenty-five percent of Los Angeles International Airport’s (LAX) power comes from green sources. LAX’s Central Utilities Plant co-generates steam to heat and air condition passenger terminals and offices. When feasible, Ontario International Airport (ONT) closes one of the runways at night to save power. ONT is also installing occupancy sensors in their administration areas and encouraging employees to turn off the lights. When appropriate, inefficient fan drives are replaced with variable fan drives.
www.lawa.org/welcome_LAWA.aspx?id=1036
Electricity from Waste Los Angeles World Airports - Los Angeles, California
Over 8,000 tons of food waste produced each year at Los Angeles International Airport is being used to produce methane gas which is then recycled and turned into electricity. This complex process involves food being ground up and mixed with water, creating a slurry, which is then heated up into methane gas and carbon dioxide. Eventually this is transferred offsite to an adjacent power generation plant and converted into electricity.
http://waste360.com/mag/waste_los_angeles_airport
DC-89
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.1 Prerequisite 1 – Storage and Collection of Recyclables
Required
INTENT
Facilitate the reduction of waste generated by building occupants and for civil/infrastructure projects within the airport environment that is hauled to and disposed of in landfills.
REQUIREMENTS
Provide an easily accessible dedicated area or areas that serve the entire building and for the airport environment for the collection and storage of materials for recycling, including (at a minimum) paper, corrugated cardboard, glass, plastics and metals. An area should also be dedicated to collection and storage of plant-based landscaping debris (trimmings), unless the site has no landscaping.
NOTE: For construction waste, see SAM Credits 5.3 Construction Waste Management and 7.5 Construction Waste Management.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Designate an area for recyclable collection and storage that is appropriately sized and located in a convenient area. These areas would likely be designed and sized differently depending on the ultimate use and waste stream of the facility (e.g., terminal, airfield, office, airlines, concessionaires, cargo, hangar, etc.) Identify local waste handlers and buyers for glass, plastic, office paper, e-waste, newspaper, cardboard, metals, fluids, fixtures, and organic wastes. Instruct occupants, employees and contractors on the recycling procedures. Consider employing cardboard balers, aluminum can crushers, recycling chutes and other waste strategies to further enhance the recycling program.
Standard Practice
These items are addressed in varying degrees utilizing appropriate strategies within an airport environment. For additional details, see CDA Best Management Practices (BMPs) Manual. Designate an area for recyclable collection and storage that is appropriately sized and located in a convenient area.
Investigate and incorporate collection rooms for recycling streams that make sense for each facility
DC-90
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Coordinate recyclable waste collection with hauler capability Recycle the following waste, whenever feasible:
o Aluminum o Glass o Paper, newspapers, magazines and cardboard o Carpet o Wood (pallets/crates, etc.) o Food waste/grease and compostables o Organic waste and compostables o Gas & oil filters o Motor oil and Anti-freeze o Scrap metal o Batteries o Light bulbs o Toner cartridges o Tires o Electrical wiring o Electronics including monitors o Deicing fluid o “Foreign Object Debris” (FOD)
Instruct employees, users and occupants on recycling procedures
Best Available Practice
Employ cardboard balers, aluminum can crushers, recycling chutes and other technologies to enhance the recycling program
Reduce use of water bottles by enabling provisions for water dispensers for refills Reduce use of water bottles by providing area and collection capability on non-
secured side of terminal to allow for the dumping of liquids and refill opportunity post security
DC-91
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDIES
Airline Pillow Recycling Oakland International Airport - Oakland, California
Oakland International Airport is one of the first airports in the nation to participate in a pillow recycling program. Instead of being discarded, the pillows are used as insulation or as material in making furniture.
www.airports.org/aci/aci/file/ACI_Priorities/Environment/TRACKER%20FILE_Airport%20environment%20initiatives.pdf
Recycling Initiative Seattle-Tacoma International Airport - Seattle, Washington
In addition to recycling 10 to 12 tons of coffee grounds a month, Sea-Tac also went from recycling 112 tons of material five years ago to an estimated 1,200 tons this year — everything from contaminated soil to motor oil.
www.airports.org/aci/aci/file/ACI_Priorities/Environment/TRACKER%20FILE_Airport%20environment%20initiatives.pdf
Recycling Initiative Baltimore/Washington International Airport - Baltimore, Washington
The Maryland Aviation Administration (MAA) has led an aggressive effort to encourage and increase recycling at Baltimore/Washington International. These efforts include recycling facilities within all areas of the airport, including the airside and landside areas and the terminal and cargo buildings.
www.menv.com/recycling%20award%20071206.shtml
DC-92
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.2 Building and Infrastructure Reuse
1 to 4 Points
INTENT
Extend the life cycle of existing building stock and infrastructure, conserve resources, retain cultural resources, reduce waste and reduce environmental impacts of new buildings and infrastructure as they relate to materials manufacturing and transport.
REQUIREMENTS
Maintain the existing building structure (including structural floor and roof decking) and envelope (the exterior skin and framing, excluding window assemblies and non-structural roofing material) and infrastructure components (pavement, piping, etc.). The minimum percentage building and infrastructure reuse for each point threshold is shown in the table below.
Hazardous materials that are remediated as a part of the project must be excluded from the calculation of the percentage maintained. If the project includes an addition that is more than two (2) times the square footage of the existing building, this credit is not applicable.
AND/OR
Use existing interior nonstructural elements (e.g., interior walls, doors, floor coverings and ceiling systems) in at least 50% (by area) of the completed building, including additions.
If the project includes an addition with square footage more than two times the square footage of the existing building, this credit is not applicable.
SAM Credit Requirement Points
5.2.1 Maintain 55% Existing Walls, Floors, and Roof or Infrastructure 1
5.2.2 Maintain 75% Existing Walls, Floors, and Roof or Infrastructure 2
5.2.3 Maintain 95% Existing Walls, Floors, and Roof or Infrastructure 3
5.2.4 Maintain 50% Interior Non-Structural Elements 1
Note: Only up to three points are available for infrastructure projects. For projects with both building and infrastructure elements, it is at the discretion of the designer to choose which reuse opportunity will be used to calculate the reuse percentage.
DC-93
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Consider reuse of existing, previously occupied buildings, including structure, envelope and elements and infrastructure. Remove elements that pose contamination risk and upgrade components that would improve energy and water efficiency such as windows, mechanical systems and plumbing fixtures.
Standard Practice
Evaluate relocation of existing structures for reuse (with special consideration of historical components)
Consider adaptive reuse of building(s) / structure(s) and potential relocation for the same program use
Evaluate maximizing reuse of existing runway and other infrastructure (e.g., utilities, lighting, etc.)
Quantify the extent of reuse
Recommended Practice
Remove elements that pose contamination risk Upgrade outdated components Seek opportunities to improve the indoor/outdoor and structure sustainability
elements (e.g., increasing daylighting, energy efficiency, low VOC finishes, etc. – see other SAM credits)
Evaluate opportunities for application of deconstruction techniques
Best Available Practice
None
CASE STUDY
Aviation Administration Building Chicago O’Hare International Airport - Chicago, Illinois
The Aviation Administration Building, which houses the Chicago Department of Aviation and the O’Hare Modernization Program offices at O’Hare International Airport (ORD) is a former military administration building built in the 1940s and abandoned in 1999 when the military base at ORD was closed. The building was renovated in 2005 leaving nearly all of the existing exterior walls, roof, and floors in place. The building provides over 160,000 square feet of office and meeting spaces to the CDA and the OMP.
DC-94
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.3 Construction Waste Management
1 to 3 Points
INTENT
Divert construction and demolition debris from disposal in landfills and incineration facilities. Redirect recyclable recovered resources back to the manufacturing process and reusable materials to appropriate sites.
REQUIREMENTS
Recycle and/or salvage non-hazardous construction and demolition debris. Develop and implement a construction waste management plan that, at a minimum, identifies the materials to be diverted from disposal and whether the materials will be sorted on-site. Excavated soil and land-clearing debris do contribute to this credit. Calculations must be done by weight (conversion may be necessary) and must be consistent throughout. The minimum percentage debris to be recycled or salvaged for each point threshold is as follows:
SAM Credit Recycled or Salvaged Points
5.3.1 50% 1
5.3.2 75% 2
5.3.3 90% 3
Section 11-4-1905 of the Chicago City Code, includes applicability requirements. For CDA purposes, all airport projects are applicable regardless of Section 11-4-1905.
SUBMITTALS
Include descriptive narrative on the SAM Checklist indicating the name of the project that will utilize the material, if other than current project or temporary storage locations, and the following:
A design estimate using the construction waste management form in CDA/OMP Specification 01524 – Construction Waste Management, to be provided by the designer with the SAM Design Checklist.
A Waste Management Plan as outlined in CDA/OMP Specification 01524 to be provided by the Contractor no later than 30 days prior to start of construction.
Monthly construction waste management forms provided by the Contractor during construction.
A final construction waste total provided by the Contractor prior to final payment.
The submittal requirements follow the City of Chicago waste ordinance (Chicago Code Section 11-4-1905) with the following exceptions:
DC-95
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
All airport projects, including those not subject to Section 11-4-1905 of the Chicago Code, shall be subject to the submittal requirements of this credit.
Submit documentation to CDA for tracking purposes in addition to documentation required by the ordinance.
Note that the requirements of this credit are very similar to the Chicago construction waste ordinance and CDA/OMP Specification 01524 with the exceptions as noted above. The specification follows the City ordinance with additional provisions for submittal requirements and project applicability.
TECHNOLOGY/STRATEGY
Note that the City of Chicago waste ordinance mandates that a minimum of 50% of construction and demolition (C&D) waste produced on-site (as measured by weight) is diverted from landfill.
It is expected that these practices may lead to savings in material costs due to resource coordination and income generation from recycled/salvaged materials. Due to the large nature of the OMP construction program, for example, many opportunities exist for on-site material recycling, especially for the aggregate and paving materials.
Standard Practice
Utilize designated areas for recycling construction debris on-site, primarily concrete, asphalt, and aggregates. Other materials are typically handled on a site-and-material-specific basis.
Recommended Practice
Thoroughly evaluate cut-and-fill needs to develop a balanced earthwork plan to reduce hauling off-site
Establish goals for diversion from disposal in landfills and incineration facilities and adopt a construction waste management plan to achieve these goals
Consider recycling cardboard, metal, brick, mineral fiber panel, concrete, plastic, wood, glass, gypsum wallboard, carpet and insulation
Construction debris processed into a recycled content commodity that has an open market value (e.g., wood derived fuel [WDF], alternative daily cover material, etc.) may be applied to the construction waste calculation
Designate a specific area(s) on the construction site for segregated collection and labeling of recyclable materials, and track recycling efforts throughout the construction process
DC-96
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Identify construction haulers and recyclers to handle the designated materials. Note that diversion may include donation of materials to charitable organizations and salvage of materials on-site.
Implement deconstruction planning and techniques into all demolition activities. Careful and planned deconstruction of a facility can provide sustainable benefits related to disposal, reuse of materials, etc.
Ensure that employees are aware of waste management and recycling procedures
Best Available Practice
Evaluate use, as appropriate, of pre-cast or pre-fabricated units whenever possible, to reduce on-site waste generation during construction
CASE STUDY
Terminal A Boston Logan International Airport - Boston, Massachusetts
Terminal A’s redevelopment maximized the use of recyclable materials, natural lighting, energy-conservation plans and alternative-fuel utilization. Many of the building materials were recycled or manufactured locally, and more than 75 percent of construction and demolition waste was diverted from landfills.
www.eco-structure.com/projects/signature-logan-terminal-logan-international-airport.aspx
DC-97
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.4 Balanced Earthwork
1 to 2 Points
INTENT
Divert soils from landfills, reduce transportation of soil to off-site locations, and maintain or make soil available for reuse on other on-airport projects.
REQUIREMENTS
Reuse or stockpile for later use, at least 75% of excavation and earthwork soils on airport property and use GPS systems during large-scale grading and earthwork operations. Please count these earthwork quantities under SAM Credit 5.3 Construction Waste Management. Calculations must be done by volume and must be consistent throughout. Hazardous or special waste soils should not be included in the calculation.
All balanced earthwork activities must be conducted in accordance with SAM Credit 2.1 Prerequisite 1 – Construction Activity Pollution Prevention.
SAM Credit Managed On-Airport Points
5.4.1 75% 1
5.4.2 95% 2
SUBMITTALS
Use form similar to submittal for SAM Credit 5.3 Construction Waste Management.
TECHNOLOGY/STRATEGY
Due to the large project limits of many airport infrastructure projects, earthwork can be a significant portion of the scope of work. By maintaining a balanced earthwork policy, the amount of transportation and disposal costs, both financial and environmental, can be reduced.
Standard Practice
The OMP has so far to date managed all earthwork soils on-airport through careful planning and design
Evaluate opportunities for on-site soil management which may include infrastructure elevation changes, development of noise berms, considerations for landscaping needs, etc.
DC-98
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Use GPS systems during large-scale grading and earthwork operations Identify stockpile areas, as well as the potential reuse on concurrent projects
Best Available Practice
None
CASE STUDY
10C-28C Berms 5&6 and 10L Site Prep Chicago O’Hare International Airport - Chicago, Illinois
To make way for the new Runway 10C-28C and 10L Extension, existing soil stockpiles, called Berms 5&6, were relocated to a designated area south of Irving Park Rd. A total of 1.8 million cubic yards of soil was moved and stockpiled on airport property. This constituted 100% of all the material moved from the site.
DC-99
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.5 Aggregate Reuse
1 Point
INTENT
Promote the reuse of aggregate from on-airport property sources.
REQUIREMENTS
Reuse aggregates, including sand, gravel, crushed concrete, and recycled asphalt for at least 10% by weight of all aggregates used for permanent structures and pavement. This does not include aggregates used for temporary structures such as haul roads or check dams. The source of the aggregates must be from on-airport property demolition activities or other on-airport projects. When reusing on-site aggregates, these may not be counted under the recycled content of materials, SAM Credit 5.7 Recycled Content, and should only be counted under this credit. When recycled aggregates from off-airport sources are used, then this would count toward SAM Credit 5.7 Recycled Content.
Exemplary Performance
If a project achieves an aggregate reuse rate greater than 90% by weight of all aggregates used for permanent structures, then an additional point may be claimed under SAM Credit 8.1 Innovation in Design & Construction.
Example: To build a new sidewalk, a project used 100 tons of aggregate in total. Of this amount, 10 tons was recovered from on-airport stockpiles, 20 tons was recovered from a nearby non-airport construction project, and the remainder was virgin material purchased from a quarry. In this case, only the 10 tons recovered from the airport stockpiles would count toward this credit, which would translate to a 10% aggregate reuse rate (10 tons/100 tons total) and therefore the point is achieved. The 20 tons of recovered material from the non-airport source (but not the 10 tons from on-airport source) would be counted under SAM Credit 5.7 Recycled Content.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
None
Standard Practice
Concrete crushing is currently employed at the airport and aggregate stockpiles are usually available. It will be important to identify the appropriate gradation(s) to maximize the reuse potential of aggregates.
DC-100
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Asphalt grindings are also stored on-site and reused as appropriate To further facilitate aggregate reuse, in addition to reusing on-site aggregates, identify
stockpile areas and make aggregates available to other on-airport projects
Recommended Practice
Identify aggregates present on-site that can be incorporated into the final development Identify possible uses of recycled aggregates within each project
Best Available Practice
Where approved and appropriate, consider the use of Warm Mix Asphalt (WMA) for paving, which allows for the use of higher quantities of recycled asphalt pavement (RAP, also known as asphalt grindings). Also see SAM Credit 5.7 Recycled Content.
CASE STUDY
Warm mix asphalt on Runway 4R/22L Boston Logan International Airport - Boston, Massachusetts
Aggregate Industries’ Northeast Region recently placed 25,952 tons of warm mix asphalt on Runway 4R/22L at Boston Logan International Airport, the first airport in the nation to use the environmentally friendly asphalt on a runway repaving project, according to the Massachusetts Port Authority. This article originally appeared in Asphalt Contractor, a Cygnus sister publication. When the Massachusetts Port Authority (Massport) awarded a $6.3-million contract this past summer to repave Runway 4R/22L at Boston Logan International Airport, the priority was to clearly reduce greenhouse emissions and energy during construction. In a statement released earlier, Massport CEO and Executive Director Thomas J. Kinton Jr. said, “Warm mix uses 20 percent less energy to make, produces 20 percent fewer greenhouse emissions when applied, and allows us to use a higher percentage of recycled asphalt pavement in the final product. This project is another example of Massport leading the way as an airport operator to reduce our impact on the environment wherever we can do so in a financially responsible way.” But more importantly, the project provided another way for Massport to continue its environmental stewardship commitment to reduce emissions and recycle valuable resources.
www.airportbusiness.com/publication/article.jsp?pubId=1&id=26379&pageNum=4
DC-101
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.6 Material Reuse
1 to 2 Points
INTENT
Reuse building materials and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
REQUIREMENTS
Use salvaged, refurbished or reused materials, the sum of which constitutes at least 5% or 10%, based on cost, of the total value of materials on the project. The minimum percentage materials reused for each point threshold is as follows:
SAM Credit Reused Materials Points
5.6.1 5% 1
5.6.2 10% 2
Only include materials in Construction Specification Institute (CSI) MasterFormat 1995 Divisions 2-10 in the calculations.
Mechanical, electrical and plumbing components and specialty items such as elevators and equipment cannot be included in this calculation. Include only materials permanently installed in the project. Furniture may be included if it is included consistently in SAM Credit 5.6 Materials Reuse through SAM Credit 5.10 Certified Wood.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
Indicate the name of the project that will utilize the material, if other than current project and temporary storage locations if known.
TECHNOLOGY/STRATEGY
Identify opportunities to incorporate salvaged materials into the building design, and research potential material suppliers. Consider salvaged materials such as beams and posts, flooring, paneling, doors and frames, masonry, fencing, metal railing, manhole frames, lids, and catch basins inlets (CSI Divisions 2 through 10, note: CSI Divisions 11 through 16 are counted in SAM Credit 5.11 Furniture and Equipment).
Use a “virtual warehouse” to maintain a current listing of materials available for reuse on other projects.
DC-102
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
To date, many items have been reused, such as fencing, light standards, and fixtures Prior to the demolition and removal of existing building materials and equipment within a
project area, notify the Chicago Department of Aviation to allow for the harvesting of used building materials and equipment for potential reuse
Recommended Practice
None
Best Available Practice
None
Case Study
Terminal 2 San Francisco International Airport - San Francisco, California
A number of measures were implemented to reduce the carbon footprint of Terminal 2 and San Francisco International Airport. One such strategy was to reuse a significant portion of the infrastructure system of the existing terminal. This method eliminated an estimated 12,300 tons of carbon dioxide emissions.
www.sfoairport.com/web/page/about/T2/sustainability/
DC-103
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.7 Recycled Content
1 to 2 Points
INTENT
Increase demand for building products that incorporate recycled content materials, thereby reducing impacts resulting from extraction and processing of virgin materials.
REQUIREMENTS
Use materials with recycled content such that the sum of postconsumer recycled content plus one-half of the pre-consumer content constitutes at least 10% or 20%, based on cost, of the total value of the materials in the project. The minimum percentage materials recycled for each point threshold is as follows:
SAM Credit Recycled Content Points
5.7.1 10% 1
5.7.2 20% 2
The recycled content value of a material assembly is determined by weight. The recycled fraction of the assembly is then multiplied by the cost of assembly to determine the recycled content value. If specific material cost is not available, assume 45% of total cost (inclusive of materials, labor and equipment) is representative of the material cost.
Only include materials in CSI MasterFormat 1995 Divisions 2-10 in the calculations.
Mechanical, electrical and plumbing components and specialty items such as elevators cannot be included in this calculation. Include only materials permanently installed in the project. Furniture may be included if it is included consistently in SAM Credit 5.6 Materials Reuse through SAM Credit 5.11 Furniture and Equipment.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
The submittals include the following:
A design estimate using the recycled content form in CDA/OMP Specification 01356 – Recycled Content – to be provided by the designer with the SAM Design Checklist
A pre-construction estimate using the recycled content form in CDA/OMP Standard Specification 01356 – Recycled Content to be provided by the contractor
A final construction estimate using the recycled content form in CDA/OMP Standard Specification 01356 – Recycled Content, to be provided by the contractor with the SAM Construction Checklist
DC-104
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Establish a project goal for recycled content materials, and identify material suppliers that can achieve this goal. During construction, ensure that the specified recycled content materials are installed. Consider a range of environmental, economic and performance attributes when selecting products and materials.
Standard Practice
Due to the nature of the program, the OMP uses and generates large amounts of recycled content materials particularly for the infrastructure projects which contain large amounts of paving materials and reinforcing steel. Where manufacturer information does not exist or cannot be obtained, CDA allows the use of the following recycled content percentages as a default for some of the common construction materials:
Material Post-consumer Pre-consumer
Steel 25% -
Copper 65% -
Aluminum 80% -
Reinforced concrete pipe 2% -
Asphaltic paving materials, conventional
45% 45%
Asphaltic paving materials, with roof shingles
67% 45%
Post-consumer Recycled Content is derived from materials that can no longer be used for their original purpose. Pre-consumer Recycled Content consists of raw material diverted from the waste stream during the manufacturing process.
NOTE: The values in the table above are typically very conservative. For example, depending on the process used to make the steel, the recycled content can be anywhere from 25% to 35% for steel produced in a basic oxygen furnace to almost 100% in an electric arc furnace.3 For this reason, the designers and contractors are encouraged to determine this information directly from the manufacturers and to not rely on these default values whenever possible.
Recommended Practice
Establish a project goal for recycled content materials and identify material suppliers that can achieve this goal
Consider the following major building components for specifying maximum
3 Steel Recycling Institute
DC-105
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
recycled content: o Aggregate in cast in place concrete o Fly-ash in cast in place concrete o Aggregate in pre-cast concrete including site work and infrastructure
piping o Fly-ash in pre-cast concrete including site work and infrastructure piping o Bituminous concrete pavement o Unit pavers o Steel reinforcement o Structural steel o Miscellaneous steel o Steel fencing and furnishings o Unit masonry o Ductile iron pipe o Aluminum products o Site generated broken concrete for gabions o Railroad rails o Railroad ties o Railroad track base material o Steel doors and frames o Aluminum doors and windows o Plaster o Terrazzo o Acoustical ceilings o Drywall o Finish flooring including carpet, resilient flooring and terrazzo o Toilet and shower compartments o Special finishes
During construction, ensure that the specified recycled content materials are installed and quantify the total percentage of recycled content materials installed
Additionally, the following websites are provided for guidance only: U.S. General Services Administration - Environmental Products Overview http://www.gsa.gov/portal/content/104543 Architectural Record – Green Product Guide www.archrecord.construction.com/products/green/
Best Available Practice
Encourage aggressive use of permeable pavement with high recycled content, where applicable, such as recycled ground tire rubber (GTR) for permeable asphalt.
DC-106
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Runway 10C/28C East Chicago O’Hare International Airport - Chicago, Illinois
It is estimated that 21% of the materials (based on cost) used for the project have recycled content. These materials include approximately 115,300 cubic yards of reclaimed concrete and bituminous pavement.
SOURCES
“The Inherent Recycled Content of Today’s Steel”, Steel Recycling Institute, October 31, 2001.
“Metal Roofs And Walls Provide Building Owners And Architects With Plenty Of “Green” Options”, Architectural Metal Newsletter (Sheet Metal and Air Conditioning Contractors’ Association), v.12, iss.2, August 24, 2005.
Recycling asphalt grindings at O’Hare
DC-107
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.8 Local/Regional Materials
1 to 3 Points
INTENT
Increase demand for building and all other materials and products that are extracted, harvested or recovered, as well as manufactured within the region, thereby supporting the use of indigenous resources and reducing the environmental impacts resulting from transportation.
REQUIREMENTS
Use building and all other materials or products that have been extracted, harvested or recovered, as well as manufactured, within 500 miles of the project site for a minimum of 10% or 20% (based on cost) of the total materials value. If only a fraction of a product or material is extracted/harvested/recovered and manufactured locally, then only that percentage (by weight) shall contribute to the regional value. An additional point can be achieved if 50% of the materials are extracted, harvested, or recovered, as well as manufactured, within 250 miles of the project site. The minimum percentage of local/regional materials for each point threshold is as follows:
SAM Credit Local/Regional Materials Points
5.8.1 10% 1
5.8.2 20% 2
5.8.3 50% within 250 miles 3
If specific material cost is not available, assume 45% of total cost (inclusive of materials, labor and equipment) is representative of the material cost.
Only include materials in CSI MasterFormat 1995 Divisions 2-10 in the calculations.
Mechanical, electrical and plumbing components and specialty items such as elevators and FAA equipment shall not be included in this calculation. Only include materials permanently installed in the project. Furniture may be included if it is included consistently in SAM Credit 5.6 Materials Reuse through SAM Credit 5.11 Furniture and Equipment.
NOTE: Materials reused and salvaged that satisfy the requirements of SAM Credit 5.6 Material Reuse may also contribute to this credit.
DC-108
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
The submittals include the following:
A design estimate using the local/regional material form in CDA/OMP Specification 01355 – Regional Materials, to be provided by the designer with the SAM Design Checklist
A pre-construction estimate using the local/regional material form in CDA/OMP Specification 01355 – Regional Materials, to be provided by the contractor
A final construction estimate using the local/regional material form in CDA/OMP Specification 01355 – Regional Materials, to be provided by the contractor with the SAM Construction Checklist
TECHNOLOGY/STRATEGY
Establish a project goal for locally sourced materials, and identify materials and material suppliers that can achieve this goal. During construction, ensure that the specified local materials are installed and quantify the total percentage of local materials installed. Consider a range of environmental, economic and performance attributes when selecting products and materials.
Standard Practice
The central location of Chicago makes many materials readily available, especially for infrastructure projects
Due to sole sourcing and limited availability, FAA equipment and specialty items sometimes can not meet the 500 mile criterion.
Recommended Practice
Identify and specify materials that are extracted, processed, or manufactured within 500 miles of Chicago. Materials that may contribute toward this goal include, but are not limited to: concrete, aggregate, asphaltic products, structural steel, masonry, gypsum wallboard, utility structures (manholes, conduit, catch basins, culverts, sewer piping, stormwater piping, etc.), gas and water piping, landscaping materials. NOTE: Piping used indoors for building systems should not be included. Reused and salvaged materials also qualify.
Best Available Practice
None
DC-109
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.9 Rapidly Renewable Materials
1 Point
INTENT
Reduce the use and depletion of finite raw materials and long-cycle renewable materials by replacing them with rapidly renewable materials.
REQUIREMENTS
Use rapidly renewable building materials and products for 2.5% of the total value of all building materials and products used in the project, based on cost. Rapidly renewable building materials and products are made from plants that are typically harvested within a ten-year or shorter cycle.
Only include materials in CSI MasterFormat 1995 Divisions 2-10 in the calculations. Only permanently installed materials should be counted in this credit. Temporary construction materials are counted in SAM Credit 7.11 Sustainable Temporary Construction Materials.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Establish a project goal for rapidly renewable materials and identify products and suppliers that can support achievement of this goal. Consider materials such as bamboo, cotton insulation, agrifiber, linoleum, wheatboard, strawboard and cork. Although not a plant material, also consider wool.
Standard Practice
None
Recommended Practice
Identify materials and suppliers that can achieve this goal Consider materials such as:
o Poplar OSB o Straw board or “agriboard” o Bamboo flooring o Cork o Wool carpets and fabrics o Cotton-batt insulation o Linoleum flooring
DC-110
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
o Sunflower seed board o Wheat grass or Straw board cabinetry and others. o Rice husks for concrete
Best Available Practice
None
DC-111
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.10 Certified Wood
1 Point
INTENT
Encourage environmentally responsible forest management.
REQUIREMENTS
Use a minimum of 50% (based on cost) of wood-based materials and products, which are certified in accordance with the Forest Stewardship Council’s principles and criteria, for wood building components. These components include, but are not limited to, structural framing and general dimensional framing, flooring, sub-flooring, wood doors and finishes. Only include materials permanently installed in the project. Furniture may be included, providing it is included consistently in activities concerning SAM Credit 5.10 Certified Wood.
Only permanently installed materials should be counted in this credit. Sustainable temporary construction materials are counted in SAM Credit 7.11 Sustainable Temporary Construction Materials. Furniture may be included if it is included consistently in SAM Credit 5.6 Materials Reuse through SAM Credit 5.11 Furniture and Equipment.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Establish a project goal for FSC-certified wood products and identify suppliers that can achieve this goal. During construction, ensure that the FSC-certified wood products are installed and quantify the total percentage of FSC-certified wood products installed.
Standard Practice
None
Recommended Practice
Identify suppliers that can achieve this goal during construction Ensure that the FSC-certified wood products are installed and quantify the total
percentage of FSC-certified wood products installed
Best Available Practice
None
DC-112
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.11 Furniture and Equipment
1 Point
INTENT
Reduce the environmental and indoor air quality impacts of the furniture and equipment acquired for use in a building.
REQUIREMENTS
A point is awarded to projects that purchase durable goods (i.e., goods that are replaced infrequently or require capital program outlays to purchase) that meet any of the following sustainable requirements:
Electric-Powered Equipment: Examples include, but are not limited to, office equipment (computers, monitors, copiers, faxes, scanners, and printers), appliances (refrigerators, dishwashers, and water coolers), external power adapters, and televisions and other audiovisual equipment. To achieve a point, 40% of the total purchases of electric-powered equipment (by cost) meet one of the following criteria:
o The equipment is ENERGY STAR labeled (for product categories with developed specifications)
o The equipment (either battery or corded) replaces conventional gas-powered equipment. Examples include, but are not limited to, maintenance equipment and vehicles, landscaping equipment and cleaning equipment.
Furniture: To achieve a point, 40% of the total purchases of furniture (by cost) meet one of the following criteria:
o Purchased furniture contains at least 10% post-consumer or 20% pre-consumer material
o Purchased furniture contains at least 70% material salvaged from off-site sources or outside the airport boundary
o Purchased furniture contains at least 70% material salvaged from on-site sources, such as an equipment reuse program or internal reorganization
o Purchased furniture contains at least 50% rapidly renewable material
o Purchased furniture contains at least 50% FSC-certified wood
o Purchased furniture contains at least 50% material harvested and processed or extracted and processed within 500 miles of the project
DC-113
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Each furniture purchase can receive credit for each sustainable criterion met (i.e., a $100 purchase that contains both 10% post-consumer recycled content and 50% content harvested within 500 miles of the project counts twice in the calculation, for a total of $200 in sustainable purchasing.
To avoid double counting, furniture materials and electric equipment loads should not be counted in previous SAM categories, such as MR Credit 4.8.1 (Regional Materials) or EA Credit 3.4 (Optimize Energy).
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Designers are encouraged to specify items that help achieve the requirements of this credit whenever possible. A continuously updated list of ENERGY STAR labeled equipment can be found on www.energystar.gov. Sustainable furniture can be found from various sources. GREENGUARD Environmental Institute certifies products, including furniture. See www.greenguard.org for a listing of GREENGUARD certified furniture.
Standard Practice
None
Recommended Practice
Specify ENERGY STAR electric equipment and/or sustainable furniture systems, such as GREENGUARD certified furniture
Best Available Practice
None
DC-114
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 MATERIALS & RESOURCES
5.12 Equipment Salvage and Reuse
1 Point
INTENT
Promote the reuse of equipment and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
REQUIREMENTS
Use salvaged, refurbished or reused equipment and materials, in any appreciable amount on the project or make available for reuse equipment and materials for other projects.
Mechanical, electrical, and plumbing components, and specialty items such as pumps and equipment (CSI Divisions 11 through 16, note: CSI Divisions 2 through 10 are counted in SAM Credit 5.6 Material Reuse) can be included. Include only materials permanently installed in the project. Furniture may be included if it is included consistently in SAM Credit 5.6 Material Reuse through SAM Credit 5.10 Certified Wood.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist. Indicate the name of the project that will utilize the material, if other than current project or temporary storage locations.
TECHNOLOGY/STRATEGY
The purpose of this credit is to recognize the reuse of items not covered by SAM Credit 5.6 Material Reuse.
Identify opportunities to incorporate salvaged materials into the design, and research potential material suppliers. Consider salvaged materials such as cabinetry and furniture, pumps, motors, electrical panels, fixtures and tanks.
Explore and encourage the development of a virtual warehouse for salvaged and reusable items.
DC-115
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
In the process of demolition, many projects have reused or made available for reuse old fencing and guard rails. Guard post structures and kiosks are routinely moved around the airport.
To date, many items have been reused, such as fencing and fixtures
Recommended Practice
None
Best Available Practice
None
CASE STUDY
Airport Hangar Demolition Ottawa International Airport - Ottawa, Ontario
The demolition of airport hangers and related facilities can result in substantial recycle and reuse opportunities. Over 90 percent of the building materials generated by the demolition of a hanger facility at the Ottawa airport were diverted from a landfill, with 65 percent being recycled and 25 percent being reused. These materials included asphalt paving, cast iron, copper, aluminum, fencing, concrete blocks, windows, restroom components and light fixtures.
http://www.docstoc.com/docs/3789115/Approach-to-Demolition-of-Airport-Hangars-Saves-Money-Ottawa-Ontario
DC-116
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.1 Prerequisite 1 – Minimum Indoor Air Quality (IAQ) Performance
Required
INTENT
Establish minimum indoor air quality (IAQ) performance to enhance indoor air quality in buildings, thus contributing to the comfort and well-being of the occupants.
REQUIREMENTS
Meet the minimum requirements of Sections 4 through 7 of ASHRAE 62.1-2010, Ventilation for Acceptable Indoor Air Quality. Mechanical ventilation systems shall be designed using the Ventilation Rate Procedure or the applicable local code, whichever is more stringent. Naturally ventilated buildings shall comply with ASHRAE 62.1-2010, paragraph 5.1.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Ventilation systems should meet or exceed the minimum outdoor air ventilation rates as described in the ASHRAE standard. Balance the impacts of ventilation rates on energy use and indoor air quality to optimize for energy efficiency and occupant health. Use the ASHRAE 62 Users Manual for detailed guidance on meeting the referenced requirements.
Standard Practice
Identify potential IAQ conflicts on the site and locate air intakes away from air contaminant source, which might include loading areas, exhaust fans, and cooling towers
Locate air intakes in secure areas for protection from potential security breaches Chicago Building Code uses ASHRAE 62.1-2004
Recommended Practice
Design HVAC systems to meet ventilation requirements of the referenced standard Evaluate carbon or electrostatic filters for use in passenger terminal buildings Provide a security monitoring system and restrict access to outdoor air intakes for
passenger terminal buildings and any other public gathering areas In cases where conflicts with the City of Chicago ventilation code arise, meet the
requirements of the more stringent code
DC-117
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
None
CASE STUDY
H. Weir Cook Terminal Indianapolis International Airport – Indianapolis, Indiana
One of the first airports in the United States to target LEED certification, the new Indianapolis International Airport terminal employs numerous sustainable measures that contribute to the indoor air quality of the building. One such feature includes an energy-efficient under floor heating/cooling system that will be used in the plaza and adjacent public spaces. Also, the high ceiling space of the terminal will have a conventional air volume HVAC system employing stratification principles to conserve energy.
www.airport-technology.com/features/feature554/
DC-118
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.2 Prerequisite 2 – Environmental Tobacco Smoke (ETS) Control
Required
INTENT
Prevent or minimize exposure of building occupants, indoor surfaces, and ventilation air distribution systems to Environmental Tobacco Smoke (ETS).
REQUIREMENTS
OPTION 1 Prohibit smoking in the building Smoking must be prohibited within 25-feet of entryways, outdoor air intakes and
operable windows. Provide signage to allow smoking in designated areas, prohibit smoking in designated areas or prohibit smoking on the entire property.
OR
OPTION 2 Prohibit smoking in the building except in designated smoking areas Smoking must be prohibited within 25-feet from entries, outdoor air intakes and operable
windows Locate designated smoking rooms to effectively contain, capture and remove ETS from
the building. At a minimum, the smoking room must be directly exhausted to the outdoors with no re-circulation of ETS-containing air to the non-smoking area of the building, and enclosed with impermeable deck-to-deck partitions. With the doors to the smoking room closed, operate exhaust sufficient to create a negative pressure with respect to the adjacent spaces of at least an average of 5 Pa (0.02 inches of water gauge) and with a minimum of 1 Pa (0.004 inches of water gauge).
Performance of the smoking room differential air pressures shall be verified by conducting 15 minutes of measurement, with a minimum of one measurement every 10 seconds, of the differential pressure in the smoking room with respect to each adjacent area and in each adjacent vertical chase with the doors to the smoking room closed. The testing will be conducted with each space configured for worst case conditions of transport of air from the smoking rooms to adjacent spaces with the smoking rooms’ doors closed to the adjacent spaces.
OR
DC-119
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
OPTION 3 Prohibit smoking in all common areas of the building Locate any exterior designated smoking areas including balconies where smoking is
permitted, at least 25-feet away from entries, outdoor air intakes and operable windows opening to common areas
Minimize uncontrolled pathways for ETS transfer between individual residential units by sealing penetrations in walls, ceilings and floors in the residential units, and by sealing vertical chases adjacent to the units
All doors in the residential units leading to common hallways shall be weather-stripped to minimize air leakage into the hallway
If the common hallways are pressurized with respect to the residential units then doors in the residential units leading to the common hallways need not be weather-stripped provided that the positive differential pressure is demonstrated as in Option 2 above, considering the residential unit as the smoking room. Acceptable sealing of residential units shall be demonstrated by a blower door test conducted in accordance with ANSI/ASTM-E779-03, Standard Test Method for Determining Air Leakage Rate By Fan Pressurization, AND use the progressive sampling methodology defined in Chapter 4 (Compliance Through Quality Construction) of the Residential Manual for Compliance with California’s 2001 Energy Efficiency Standards (http://www.energy.ca.gov/title24/archive/2001standards/index.html). Residential units must demonstrate less than 1.25 square inches leakage area per 100 square feet of enclosure area (i.e. sum of all wall, ceiling and floor areas).
Verification of the performance of smoking rooms may be accomplished through tracer gas testing as an alternative to blower door testing
NOTE: It is acceptable to not designate any smoking areas and to provide signage to indicate the prohibition of smoking on the property to satisfy the prerequisite requirements.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Prohibit smoking in commercial buildings, or effectively control the ventilation air in smoking rooms.
Standard Practice
Chicago Building Code prohibits smoking within 15-feet of entryways which is less stringent than this credit. The distance must be increased to 25-feet to meet this prerequisite.
DC-120
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Prohibiting smoking in the public areas of buildings and locating any exterior designated smoking areas away from entries and operable windows
Require all parts of the construction sites to be non-smoking Work with labor unions in privately leased tenant spaces to designate these areas as
non-smoking
Best Available Practice
Where applicable, provide a designated smoking room designed to effectively contain, capture and remove ETS from the building. At a minimum, the smoking room must be directly exhausted to the outdoors with no recirculation of ETS-mixed air to the non-smoking area of the building, enclosed with impermeable deck-to-deck partitions and operated at negative pressure.
Performance of the smoking rooms shall be verified by using tracer gas testing methods as described in the ASHRAE Standard 129-1997. Acceptable exposure in non-smoking areas is defined as less than 1% of the tracer gas concentration in the smoking room detectable in the adjoining non-smoking areas. Smoking room testing as described in ASHRAE Standard 129-1997, Section 8, is required in the contract documents and critical smoking facility systems testing results must be included in the building commissioning plan and report or as a separate document.
DC-121
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.3 Outdoor Air Delivery Monitoring
1 Point
INTENT
Provide capacity for ventilation system monitoring to help sustain occupant comfort and wellbeing.
REQUIREMENTS
Install permanent monitoring systems to ensure that ventilation systems maintain design minimum ventilation requirements. Configure all monitoring equipment to generate an alarm when airflow values or carbon dioxide (CO2) levels vary by 10% or more from the design values via either a building automation system alarm to the building operator or via a visual or audible alert to the building occupants.
FOR MECHANICALLY VENTILATED SPACES
Monitor carbon dioxide concentrations within all densely occupied spaces (those with a design occupant density greater than or equal to 25 people per 1000 sq.ft.). CO2 monitoring locations shall be between 3 feet and 6 feet above the floor
For each mechanical ventilation system serving non-densely occupied spaces, provide a direct outdoor airflow measurement device capable of measuring the minimum outdoor airflow rate with an accuracy of plus or minus 15% of the design minimum outdoor air rate, as defined by ASHRAE 62.1-2010
FOR NATURALLY VENTILATED SPACES
Monitor CO2 concentrations within all naturally ventilated spaces. CO2 monitoring shall be located within the room between 3 feet and 6 feet above the floor. One CO2 sensor may be used to represent multiple spaces if the natural ventilation design uses passive stack(s) or other means to induce airflow through those spaces equally and simultaneously without intervention by building occupants.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Install carbon dioxide and airflow measurement equipment and interface with the HVAC system and/or Building Automation System (BAS) to trigger corrective action, if applicable. If such automatic controls are not feasible with the building systems, use the measurement equipment to trigger alarms that inform building operators or occupants in the event of a possible deficiency in outdoor air delivery.
DC-122
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Provide audible feedback to building occupants, who in turn know to inform the building’s engineer, as a satisfactory means of meeting this aspect of the credit requirement for both the densely occupied areas and the other areas with mechanical ventilation systems.
Standard Practice
None
Recommended Practice
Design HVAC systems for passenger terminal and other public assembly and buildings with carbon dioxide monitoring sensors in each space and integrate these sensors with the building automation system (BAS)
Provide real-time control of terminal unit (VAV box) flowrates and total outdoor air flowrates based on carbon dioxide levels
Best Available Practice
None
CASE STUDY
Terminal Building Ventilation System Performance Austin-Bergstrom International Airport - Austin, Texas
The 550,000 terminal building at Austin-Bergstrom International Airport is equipped with technology that provides monitoring and feedback on ventilation system performance to ensure the system is operating to the building’s minimum requirements. Each of the terminal’s cooling systems work for a specific application and operate within individual zones. Units provide cooling for special areas such as electrical and mechanical closets and communications areas. This building is regarded as a model for energy efficient terminal building design.
www.cleanairports.com/reports/austin.pdf
DC-123
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.4 Increased Ventilation
1 Point
INTENT
Provide additional outdoor air ventilation to improve indoor air quality for improved occupant comfort, well-being and productivity.
REQUIREMENTS
FOR MECHANICALLY VENTILATED SPACES
Increase breathing zone outdoor air ventilation rates to all occupied spaces by at least 30% above the minimum rates required by ASHRAE Standard 62.1-2010 as determined by SAM Credit 5.1 Prerequisite 1 – Storage and Collection of Recyclables
FOR NATURALLY VENTILATED SPACES
Design natural ventilation systems for occupied spaces to meet the recommendations set forth in the Carbon Trust “Good Practice Guide 237” [1998]. Determine that natural ventilation is an effective strategy for the project by following the flow diagram process shown in Figure 1.18 of the Chartered Institution of Building Services Engineers (CIBSE) Applications Manual 10: 2005, Natural ventilation in non-domestic buildings.
AND
Use diagrams and calculations to show that the design of the natural ventilation systems meets the recommendations set forth in the CIBSE Applications Manual 10: 2005, Natural ventilation in non-domestic buildings
OR
Use a macroscopic, multi-zone, analytic model to predict that room-by-room airflows will effectively naturally ventilate, defined as providing the minimum ventilation rates required by ASHRAE 62.1-2010 Chapter 6, for at least 90% of occupied spaces
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
DC-124
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
For mechanically ventilated spaces: Use heat recovery, where appropriate, to minimize the additional energy consumption associated with higher ventilation rates.
For naturally ventilated spaces: Follow the eight design steps described in the Carbon Trust Good Practice Guide 237 – 1) Develop design requirements, 2) Plan airflow paths, 3) Identify building uses and features that might require special attention, 4) Determine ventilation requirements, 5) Estimate external driving pressures, 6) Select types of ventilation devices, 7) Size ventilation devices, 8) Analyze the design.
Use public domain software such as NIST’s CONTAM, Multizone Modeling Software, along with LoopDA, Natural Ventilation Sizing Tool, to analytically predict room-by-room airflows.
Standard Practice
None
Recommended Practice
Select and place air diffusers for all mechanically ventilated spaces, particularly office and passenger terminal spaces, following the recommended design approaches in the ASHRAE 2001 Fundamentals, Chapter 32, Space Air Diffusion
Section 6 of ASHRAE 62.1-2010 outlines guidelines for determining ventilation rates for various applications of mechanical ventilation systems
Best Available Practice
Increase air change effectiveness using the following strategies: o Displacement ventilation in passenger terminal areas o Underfloor air distribution in office areas o Operable windows and skylights in cargo buildings
Increase air movement in cargo facilities with ceiling fans Install trickle ventilators in cargo facilities to provide natural winter ventilation Install relief vents or operable skylights in cargo facilities to provide stack effect natural
ventilation
DC-125
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Natural Ventilation Systems Honolulu International Airport - Honolulu, Hawaii
The Overseas Terminal at the Honolulu International Airport was designed with natural ventilation so that occupants and travelers could comfortably experience the natural climate. To enhance air circulation in the terminal, local wind and climate studies were compiled to evaluate the best potential practices to ensure comfortable ventilation for building occupants.
www.wai.com/project.aspx?id=1632&type=600&cat=600
DC-126
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.5.1 Construction IAQ Management Plan: During Construction
1 Point
INTENT
Reduce indoor air quality problems resulting from the construction/renovation process in order to help sustain the comfort and well-being of construction workers and building occupants.
REQUIREMENTS
Develop and implement an Indoor Air Quality (IAQ) Management Plan for the construction and pre-occupancy phases of the building as follows:
During construction meet or exceed the recommended Control Measures of the Sheet Metal and Air Conditioning National Contractors Association (SMACNA) IAQ Guidelines for Occupied Buildings under Construction, 1995, Chapter 3
Protect stored on-site or installed absorptive materials from moisture damage
If permanently installed air handlers are used during construction, filtration media with a Minimum Efficiency Reporting Value (MERV) of 8 shall be used at each return air grille, as determined by ASHRAE 52.2-1999. Replace all filtration media immediately prior to occupancy.
SUBMITTALS
Include descriptive narrative in SAM Checklist including IAQ Management Plan and detailed photographic evidence.
TECHNOLOGY/STRATEGY
Adopt an IAQ management plan to protect the HVAC system during construction, control pollutant sources and interrupt contamination pathways. Sequence the installation of materials to avoid contamination of absorptive materials such as insulation, carpeting, ceiling tile and gypsum wallboard. Coordinate SAM Credits 6.5 Construction IAQ Management Plan and 6.7 Indoor Chemical and Source Pollutant Control to determine the appropriate specifications and schedules for filtration media.
If possible, avoid using permanently installed air handlers for temporary heating/cooling during construction. Consult the LEED 2009 Green Building and Construction Reference Guide for more detailed information on how to ensure the well-being of construction workers and building occupants if permanently installed air handlers must be used during construction.
DC-127
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
During construction meet or exceed the recommended Design Approaches of the Sheet Metal and Air Conditioning National Contractors Association (SMACNA) IAQ Guideline for Occupied Buildings under Construction, 1995, Chapter 3
Protect stored on-site or installed absorptive materials from moisture damage Do not operate air-handling equipment during construction Sequence the installation of materials to avoid contamination of absorptive materials
such as insulation, carpeting, ceiling tile and gypsum wallboard Minimize the use of air handlers during construction. If air handlers are used during
construction, filtration media with a Minimum Efficiency Reporting Value (MERV) of 8 must be used at each return air grill, as determined by ASHRAE 52.2-1999.
Best Available Practice
None
CASE STUDY
Construction Mitigation Program Oakland International Airport – Oakland, California
During the airport’s Terminal Improvement Program, a number of mitigation efforts are being implemented to reduce the construction impact on contractors, tenants, and travelers. A major component of these efforts involves a comprehensive checklist enforcing compliance with these practices. This checklist includes the evaluation of existing measures, the identification of measures that may require revision, and development of recommendations for corrective action.
www.oaklandairport.com/noise/environmental_construct.shtml
DC-128
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.5.2 Construction IAQ Management Plan: Before Occupancy
1 Point
INTENT
Reduce indoor air quality problems resulting from the construction/renovation process in order to help sustain the comfort and well-being of construction workers and building occupants.
REQUIREMENTS
OPTION 1 — Flush-Out After construction ends, prior to occupancy and with all interior finishes installed, perform a building flush-out by supplying a total air volume of 14,000 cu.ft. of outdoor air per sq.ft. of floor area while maintaining an internal temperature of at least 60 degrees F and relative humidity no higher than 60%.
OR
If occupancy is desired prior to completion of the flush-out, the space may be occupied following delivery of a minimum of 3,500 cu. ft. of outdoor air per sq. ft. of floor area to the space. Once a space is occupied, it shall be ventilated at a minimum rate of 0.30 cfm/sq. ft. of outside air or the design minimum outside air rate determined section 5.1, whichever is greater. During each day of the flush-out period, ventilation shall begin a minimum of three hours prior to occupancy and continue during occupancy. These conditions shall be maintained until a total of 14,000 cu. ft./sq. ft. of outside air has been delivered to the space.
NOTE: All finishes must be installed prior to flush-out.
OR
OPTION 2 — Air Testing Conduct baseline IAQ testing, after construction ends and prior to occupancy, using
testing protocols consistent with the United States Environmental Protection Agency Compendium of Methods for the Determination of Air Pollutants in Indoor Air and as additionally detailed in the LEED Reference Guide for Green Building Design and Construction, 2009 Edition.
DC-129
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Demonstrate that the contaminant maximum concentrations listed below are not exceeded.
CONTAMINANT MAXIMUM CONCENTRATION Formaldehyde 50 parts per billion Particulates (PM10) 50 micrograms per cubic meter Total Volatile Organic Compounds (TVOC) 500 micrograms per cubic meter 4-Phenylcyclohexene (4-PCH)* 6.5 micrograms per cubic meter Carbon Monoxide (CO) 9 part per million and no greater than 2
parts per million above outdoor levels
* This test is only required if carpets and fabrics with styrene butadiene rubber (SBR) latex backing material are installed as part of the base building systems.
For each sampling point where the maximum concentration limits are exceeded conduct additional flush-out with outside air and retest the specific parameter(s) exceeded to indicate the requirements are achieved. Repeat procedure until all requirements have been met. When retesting non-complying building areas, take samples from the same locations as in the first test.
The air sample testing shall be conducted as follows: o All measurements shall be conducted prior to occupancy, but during normal
occupied hours, and with the building ventilation system starting at the normal daily start time and operated at the minimum outside air flow rate for the occupied mode throughout the test;
o All interior finishes must be installed, including but not limited to millwork, doors, paint, carpet and acoustic tiles. Movable furnishings such as workstations and partitions should be in place for the testing, although it is not required;
o The number of sampling locations will depend on the size of the building and number of ventilation systems. For each portion of the building served by a separate ventilation system, the number of sampling points shall not be less than one per 25,000 sq.ft., or for each contiguous floor area, whichever is larger, and include areas with the least ventilation and greatest presumed source strength; and
o Air samples must be collected between 3 feet and 6 feet from the floor to represent the breathing zone of occupants, and over a minimum 4-hour period.
SUBMITTALS
Include descriptive narrative in SAM Checklist including IAQ Management Plan and detailed photographic evidence.
DC-130
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Prior to occupancy, perform a building flush-out or test the air contaminant levels in the building. The flush-out is often used where occupancy is not required immediately upon substantial completion of construction. IAQ testing can minimize schedule impacts but may be more costly. Coordinate SAM Credits 6.5 Construction IAQ Management Plan and 6.7 Indoor Chemical and Source Pollutant Control to determine the appropriate specifications and schedules for filtration media.
The intent of this credit is to eliminate indoor air quality problems that occur as a result of construction. Architectural finishes used in tenant build-outs constitute a significant source of air pollutants, and must be addressed in order to qualify for this credit.
Standard Practice
None
Recommended Practice
Replace all filtration media immediately prior to occupancy. Filtration media shall have a Minimum Efficiency Reporting Value (MERV) of 13, as determined by ASHRAE 52.2-1999 for media installed at the end of construction.
Best Available Practice
After construction ends and prior to occupancy, conduct a two-week building flush out with 100% fresh air
DC-131
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.6.1 Low-Emitting Materials: Adhesives and Sealants
1 Point
INTENT
Reduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
REQUIREMENTS
All adhesives and sealants used on the interior of the building (i.e., inside of the weatherproofing system and applied on-site) must comply with the following requirements as applicable to the project scope:
Adhesives, Sealants and Sealant Primers: South Coast Air Quality Management District (SCAQMD) Rule #1168. VOC limits are listed in the table below and correspond to an effective date of July 1, 2005 and rule amendment date of January 7, 2005.
Architectural Applications
VOC Limit [g/L less water] Specialty Applications
VOC Limit [g/L less water]
Indoor Carpet Adhesives 50 PVC Welding 510 Carpet Pad Adhesives 50 CPVC Welding 490 Wood Flooring Adhesives 100 ABS Welding 325 Rubber Floor Adhesives 60 Plastic Cement Welding 250 Subfloor Adhesives 50 Adhesive Primer for Plastic 550 Ceramic Tile Adhesives 65 Contact Adhesives 80 VCT & Asphalt Adhesives 50 Special Purpose Contact Adhesive 250 Drywall & Panel Adhesives 50 Structural Wood Member Adhesive 140 Cove Base Adhesives 50 Sheet Applied Rubber Lining Operations 850 Multipurpose Construction Adhesives 70 Top & Trim Adhesive 250 Structural Glazing Adhesives 100
Substrate Specific Applications
VOC Limit [g/L less water] Sealants VOC Limit
VOC Limit [g/L less water]
Metal to Metal 30 Architectural 250 Plastic Foams 50 Nonmembrane Roof 300 Porous Material (except wood) 50 Roadway 250 Wood 30 Single-Ply Roof Membrane 450 Fiberglass 80 Other 420
Sealant Primers
VOC Limit [g/L less water]
Architectural Non Porous 250 Architectural Porous 775 Other 750
DC-132
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Aerosol Adhesives: Green Seal Standard for Commercial Adhesives GS-36 requirements in effect on October 19, 2000.
Aerosol Adhesives: VOC weight [g/L minus water] General purpose mist spray 65% VOCs by weight General purpose web spray 55% VOCs by weight Special purpose aerosol adhesives (all types) 70% VOCs by weight
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Specify low-VOC materials in construction documents. Ensure that VOC limits are clearly stated in each section of the specifications where adhesives and sealants are addressed. Common products to evaluate include: general construction adhesives, flooring adhesives, fire-stopping sealants, caulking, duct sealants, plumbing adhesives, and cove base adhesives. Review product cut sheets, material safety data sheets (MSDS), signed attestations or other official literature from the manufacturer clearly identifying the VOC contents or compliance with referenced standards.
Standard Practice
Low-VOC materials are becoming more common in the market place
Recommended Practice
Specify Low-VOC adhesives and sealants Consider the use of air scrubbers during the installation and curing of adhesives and
sealers when used inside the passenger terminal or other public spaces
Best Available Practice
Specify that all shop finished material meet the VOC emission requirements. Materials to consider are:
o Primed steel o Finished metals including aluminum o Finished millwork o Finished steel and wood doors and windows
DC-133
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Terminal A Boston Logan International Airport - Boston, Massachusetts
In addition to the implementation of a water-efficient plumbing and irrigation system and energy-efficient electric lighting, specific measures were taken to control the amount and quality of construction contaminates from negatively impacting the interior of the building. Adhesives, sealants, paints and carpets were specified to have very limited or no volatile organic compounds.
www.facilitiesnet.com/facilitiesmanagement/article/Logan-Airport-Becomes-Home-to-Worlds-First-LEEDCertified-Terminal--4962
DC-134
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.6.2 Low-Emitting Materials: Paints and Coatings
1 Point
INTENT
Reduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
REQUIREMENTS
Paints and coatings used on the interior of the building (i.e., inside of the weatherproofing system and applied on-site) must comply with the following criteria as applicable to the project scope:
Architectural paints, coatings and primers applied to interior walls and ceilings must not exceed the VOC content limits established in Green Seal Standard GS-11, Paints, First Edition, May 20, 1993.
o Flats: 50 g/L o Non-Flats: 150 g/L
Anti-corrosive and anti-rust paints applied to interior ferrous metal substrates must not exceed the VOC content limit of 250 g/L established in Green Seal Standard GC-03, Anti-Corrosive Paints, Second Edition, January 7, 1997.
Clear wood finishes, floor coatings, stains, and shellacs applied to interior elements must not exceed the VOC content limits established in South Coast Air Quality Management District (SCAQMD) Rule 1113, Architectural Coatings, rules in effect on January 1, 2004.
o Clear wood finishes: varnish 350 g/L; lacquer 550 g/L o Floor coatings: 100 g/L o Sealers: waterproofing sealers 250 g/L; sanding sealers 275 g/L; all other sealers
200 g/L o Shellacs: Clear 730 g/L; pigmented 550 g/L o Stains: 250 g/L
SUBMITTALS
Include descriptive narrative in SAM Checklist.
DC-135
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Specify low-VOC paints and coatings in construction documents. Ensure that VOC limits are clearly stated in each section of the specifications where paints and coatings are addressed. Track the VOC content of all interior paints and coatings during construction.
Standard Practice
None
Recommended Practice
Specify Low-VOC field applied paints and coating Consider the use of air scrubbers during the installation and curing of paints and
coatings when used inside the terminal or other public spaces
Best Available Practice
Specify that all shop finished material meet the VOC emission requirements. Materials to consider are:
o Primed steel o Finished metals including aluminum o Finished millwork o Finished steel and wood doors and windows
DC-136
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.6.3 Low-Emitting Materials: Flooring Systems
1 Point
INTENT
Reduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
REQUIREMENTS
All flooring must comply with the following as applicable to the project scope:
All carpet installed in the building interior shall meet the testing and product requirements of the Carpet and Rug Institute’s Green Label Plus program
All carpet cushion installed in the building interior shall meet the requirements of the Carpet and Rug Institute Green Label program
All carpet adhesive shall meet the requirements of SAM Credit 6.6.1 Low-Emitting Materials: Adhesives and Sealants: VOC limit of 50 g/L
All of the hard surface flooring must be certified as compliant with the FloorScore® standard (current as of the date of this Rating System, or more stringent version) by an independent third party. Flooring products covered by FloorScore® include vinyl, linoleum, laminate flooring, wood flooring, ceramic flooring, rubber flooring, wall base, and associated sundries.
An alternative compliance path using FloorScore® is acceptable for credit achievement according to the following stipulations. 100% of the non-carpet finished flooring must be FloorScore® certified, and it must comprise, at minimum, at least 25% of the finished floor area. Potential examples of unfinished flooring include floors in mechanical rooms, electrical rooms, and elevator service rooms.
Concrete, wood, bamboo, and cork floor finishes such as sealer, stain and finish must meet the requirements of South Coast Air Quality Management District (SCAQMD) Rule 1113, Architectural Coatings, rules in effect on January 1, 2004. VOC limits are listed below:
o Clear wood finishes: varnish 350 g/L; lacquer 550 g/L o Floor coatings: 100 g/L o Sealers: waterproofing sealers 250 g/L; sanding sealers 275 g/L; all other sealers
200 g/L o Shellacs: Clear 730 g/L; pigmented 550 g/L o Stains: 250 g/L
DC-137
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Tile setting adhesives and grout must meet South Coast Air Quality Management District (SCAQMD) Rule #1168. VOC limits are listed below and correspond to an effective date of July 1, 2005 and rule amendment date of January 7, 2005.
o Ceramic tile adhesive: 65 g/L o Grout and mortar: 250 g/L
All flooring products will meet the testing and product requirements of the California Department of Health Services Standard Practice for The Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers, including 2004 Addenda.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Clearly specify requirements for product testing and/or certification in the construction documents. Select products that are either certified under the Green Label Plus program or for which testing has been done by qualified independent laboratories in accordance with the appropriate requirements.
The Green Label Plus program for carpets and its associated VOC emission criteria in micrograms per square meter per hour, along with information on testing method and sample collection developed by the Carpet & Rug Institute (CRI) in coordination with California’s Sustainable Building Task Force and the California Department of Health Services (DHS), are described in Section 9, Acceptable Emissions Testing for Carpet, DHS Standard Practice CA/DHS/EHLB/R-174, dated 07/15/04. This document is published as Section 01350 Section 9 [dated 2004] by the Collaborative for High Performance Schools [http://www.chps.net/dev/Drupal/node]).
FloorScore® is a voluntary, independent certification program that tests and certifies hard surface flooring and associated products for compliance with criteria adopted in California for indoor air emissions of Volatile Organic Compounds (VOCs) with potential health effects. The program uses a small-scale chamber test protocol and incorporates VOC emissions criteria developed by the California Department of Health Services, which are widely known as Section 1350.
Standard Practice
None
DC-138
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Specify Low-VOC carpet systems. Ensure that VOC limits are clearly stated where carpet systems are addressed. Be attentive to carpet installation requirements.
Consider the use of air scrubbers during the installation and curing of carpet or hard surface floor system adhesives and sealers when used inside the terminal or other public spaces
Best Available Practice
Specify that all shop finished material meet the VOC emission requirements. Materials to consider are:
o Primed steel o Finished metals including aluminum o Finished millwork
DC-139
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.6.4 Low-Emitting Materials: Composite Wood and Agrifiber Products
1 Point
INTENT
Reduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
REQUIREMENTS
Composite wood and agrifiber products used on the interior of the building (defined as inside of the weatherproofing system) shall contain no added urea-formaldehyde resins. Laminating adhesives used to fabricate on-site and shop-applied composite wood and agrifiber assemblies shall contain no added urea-formaldehyde resins.
Composite wood and agrifiber products are defined as: particleboard, medium density fiberboard (MDF), plywood, wheatboard, strawboard, panel substrates and door cores. Materials considered fit-out, furniture, and equipment (FF&E) are not considered base building elements and are not included.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Specify wood and agrifiber products that contain no added urea-formaldehyde resins. Specify laminating adhesives for field and shop applied assemblies that contain no added urea/formaldehyde resins. Review product cut sheets, MSD sheets, signed attestations or other official literature from the manufacturer.
Standard Practice
None
Recommended Practice
Specify wood and agrifiber products with no added urea-formaldehyde resins.
DC-140
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
Specify that all shop finished material meet the VOC emission requirements. Materials to consider are:
o Finished millwork o Finished steel and wood doors and windows
CASE STUDY
Terminal A – Composite Wood Boston Logan International Airport – Boston, Massachusetts
During construction of the new terminal, special measures were taken to utilize composite wood materials. These materials helped reduce any adverse effects of the construction and preserve indoor air quality. In addition to wood composite, adhesives, sealants and very low or no Volatile Compounds (VOCs) were built into the specifications of the new terminal.
DC-141
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.7 Indoor Chemical and Pollutant Source Control
1 Point
INTENT
Minimize exposure of building occupants to potentially hazardous particulates and chemical pollutants.
REQUIREMENTS
Design to minimize and control pollutant entry into buildings and later cross-contamination of regularly occupied areas:
Employ permanent entryway systems at least 10-feet long in the primary direction of travel to capture dirt and particulates from entering the building at all entryways that are directly connected to the outdoors. Acceptable entryway systems include permanently installed grates, grilles, or slotted systems that allow for cleaning underneath. Roll-out mats are only acceptable when maintained on a weekly basis by a contracted service organization.
Sufficiently exhaust each space where hazardous gases or chemicals may be present or used (including garages, housekeeping/laundry areas and copying/printing rooms) to create negative pressure with respect to adjacent spaces with the doors to the room closed. For each of these spaces, provide self-closing doors and deck to deck partitions or a hard lid ceiling. The exhaust rate shall be at least 0.50 cfm/sq.ft., with no air recirculation. The pressure differential with the surrounding spaces shall be at least 5 Pa (0.02 inches of water gauge) on average and 1 Pa (0.004 inches of water) at a minimum when the doors to the rooms are closed.
In mechanically ventilated buildings, provide regularly occupied areas of the building with new air filtration media prior to occupancy that provides a Minimum Efficiency Reporting Value (MERV) of 13 or better. Filtration should be applied to process both return and outside air that is to be delivered as supply air.
Provide containment drains plumbed for appropriate disposal of hazardous liquid wastes in places where water and chemical concentrate mixing occurs for laboratory purposes.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
DC-142
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Design facility cleaning and maintenance areas with isolated exhaust systems for contaminants. Maintain physical isolation from the rest of the regularly occupied areas of the building. Install permanent architectural entryway systems such as grills or grates to prevent occupant-borne contaminants from entering the building. Install high-level filtration systems in air handling units processing both return air and outside supply air. Ensure that air handling units can accommodate required filter sizes and pressure drops.
Standard Practice
None
Recommended Practice
Employ permanent entryway systems (e.g., grills, grates, etc.) to capture dirt, particulates, etc. from entering the building at all high volume entryways
Where chemical use occurs (including housekeeping areas and copying/printing rooms), provide segregated areas with deck to deck partitions with separate outside exhaust at a rate of at least 0.50 cubic feet per minute per square foot, no air re-circulation and maintaining a negative pressure
Provide drains plumbed for appropriate disposal of liquid waste in spaces where water and chemical concentrate mixing occurs
Select finish materials and assemblies that resist mold growth Designate central locations in terminal and office buildings for storage of concentrated
cleaning chemicals and other pollutant sources Install permanent architectural entryway systems such as grills or grates to prevent
occupant-borne contaminants from entering the building
Best Available Practice
Design separate exhaust and plumbing systems for rooms or areas with contaminants to achieve physical isolation from the rest of the building
Encourage the use of electric vehicle uses in indoor cargo facilities
DC-143
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.8.1 Controllability of Systems: Lighting
1 Point
INTENT
Provide a high level of lighting system control by individual occupants or by specific groups in multi-occupant spaces (e.g., classrooms and conference areas) to promote the productivity, comfort and well-being.
REQUIREMENTS
Provide individual lighting controls for 90% (minimum) of the building occupants to enable adjustments to suit individual task needs and preferences.
AND
Provide lighting system controls for all shared multi-occupant spaces to enable lighting adjustment that meets group needs and preferences.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Design the building with occupant controls for lighting. Strategies to consider include lighting controls and task lighting. Integrate lighting systems controllability into the overall lighting design, providing ambient and task lighting while managing the overall energy use of the building.
Standard Practice
None
Recommended Practice
Tie lighting in public areas of passenger terminals to flight schedules or use motion-activated lighting
Design lighting control systems to take advantage of daylight harvesting to reduce artificial lighting when adequate daylight is available
Design terminal areas to provide a variety of levels of light and sound in different areas simultaneously
Provide operable windows in areas that are not noise-sensitive, such as cargo buildings
Provide task lighting or more light switching zones in office areas
DC-144
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
None
CASE STUDY
Jeppesen Landside Terminal - Lighting Denver International Airport - Denver, Colorado
The Jeppesen Terminal at Denver International Airport was designed with energy efficient lighting throughout the building that will contain multi-level lighting, monitoring, and controls, integrated with energy efficient mechanical systems.
DC-145
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.8.2 Controllability of Systems: Thermal Comfort
1 Point
INTENT
Provide a high level of thermal comfort system control by individual occupants or by specific groups in multi-occupant spaces (i.e., classrooms or conference areas) to promote the productivity, comfort and well-being of building occupants.
REQUIREMENTS
Provide individual comfort controls for 50% (minimum) of the building occupants to enable adjustments to suit individual task needs and preferences. Operable windows can be used in lieu of comfort controls for occupants of areas that are 20-feet inside of and 10-feet to either side of the operable part of the window. The areas of operable window must meet the requirements of ASHRAE 62.1-2010 paragraph 5.1 Natural Ventilation.
AND
Provide comfort system controls for all shared multi-occupant spaces to enable adjustments to suit group needs and preferences.
Conditions for thermal comfort are described in ASHRAE Standard 55-2004 to include the primary factors of air temperature, radiant temperature, air speed and humidity.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Design the building and systems with comfort controls to allow adjustments to suit individual needs or those of groups in shared spaces. ASHRAE Standard 55-2004 identifies the factors of thermal comfort and a process for developing comfort criteria for building spaces that suit the needs of the occupants involved in their daily activities. Control strategies can be developed to expand on the comfort criteria to allow adjustments to suit individual needs and preferences.
These strategies may involve system designs incorporating operable windows, hybrid systems integrating operable windows and mechanical systems, or mechanical systems alone. Individual adjustments may involve individual thermostat controls, local diffusers at floor, desk or overhead levels, or control of individual radiant panels, or other means integrated into the overall building, thermal comfort systems, and energy systems design. In addition, designers should evaluate the closely tied interactions between thermal comfort (as required by ASHRAE Standard 55-2004) and acceptable indoor air quality (as required by ASHRAE Standard 62.1-2010, whether natural or mechanical ventilation).
DC-146
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
None
Best Available Practice
Provide under floor air distribution systems with individual diffusers for office spaces
DC-147
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.9.1 Thermal Comfort: Design
1 Point
INTENT
Provide a comfortable thermal environment that supports the productivity and well-being of building occupants.
REQUIREMENTS
Design HVAC systems and the building envelope to meet the requirements of ASHRAE Standard 55-2004, Thermal Comfort Conditions for Human Occupancy. Demonstrate design compliance in accordance with Section 6.1.1 Documentation.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Establish comfort criteria per ASHRAE Standard 55-2004 that support the desired quality and occupant satisfaction with building performance. Design building envelope and systems with the capability to deliver performance to the comfort criteria under expected environmental and use conditions. Evaluate air temperature, radiant temperature, air speed, and relative humidity in an integrated fashion and coordinate these criteria with SAM Credits 6.1 Low-Emitting Materials, 6.3 Outdoor Air Delivery Monitoring and 6.4 Increase Ventilation.
Standard Practice
None
Recommended Practice
None
Best Available Practice
Provide ceiling fans or natural ventilation to increase air movement in cargo spaces Provide humidification in HVAC systems serving office and terminal areas For spaces with humidification, install humidistats in addition to thermostats
DC-148
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Terminal 2 San Francisco International Airport - San Francisco, California
Terminal 2’s design at San Francisco International Airport incorporates a number of measures to reduce the carbon footprint of the facility. The LEED certified building is designed to improve indoor air quality and reduce energy consumption. The design features a waste reduction program and a reclaimed water reuse program.
www.flysfo.com/web/page/about/T2/sustainability/
DC-149
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.9.2 Thermal Comfort: Verification
1 Point (awarded only if credit is earned toward SAM Credit 6.9.1)
INTENT
Provide for the assessment of building thermal comfort over time.
REQUIREMENTS
Provide a permanent monitoring system to ensure building performance to the desired comfort criteria as determined by SAM Credit 6.9.1 Thermal Comfort: Design.
Agree to implement a thermal comfort survey of building occupants within a period of six to 18 months after occupancy. This survey should collect anonymous responses about thermal comfort in the building including an assessment of overall satisfaction with thermal performance and identification of thermal comfort-related problems. Agree to develop a plan for corrective action if the survey results indicate that more than 20% of occupants are dissatisfied with thermal comfort in the building. This plan should include measurement of relevant environmental variables in problem areas in accordance with ASHRAE Standard 55-2004.
Thermal Comfort: Verification, is contingent on the successful completion and award of the credit -Thermal Comfort: Design.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
ASHRAE Standard 55-2004 provides guidance for establishing thermal comfort criteria and the documentation and validation of building performance to the criteria. While the standard is not intended for purposes of continuous monitoring and maintenance of the thermal environment, the principles expressed in the standard provide a basis for design of monitoring and corrective action systems.
Standard Practice
None
Recommended Practice
None
Best Available Practice
None
DC-150
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Harvard Green Campus Initiative Harvard University – Cambridge, Massachusetts
Harvard Real-Estate Services (HRES) facilities team plans to administer occupant surveys and adjust HVAC parameters to respond to comfort issues. The HRES survey is based on requirements of the LEED New Construction version 2.2 Reference Guide. The operations team will view survey results for each residence unit. If greater than 20% of the survey respondents are not comfortable, then the team will identify problem areas within the building. The team will identify the cause of discomfort in each situation and choose from a variety of options to correct the discomfort.
http://www.green.harvard.edu/theresource/
DC-151
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.10.1 Daylight and Views: Views for 75% of Spaces
1 Point
INTENT
Provide for the building occupants a connection between indoor spaces and the outdoors through the introduction of daylight and views into the regularly occupied areas of the building.
REQUIREMENTS
OPTION 1 — CALCULATION Achieve a minimum glazing factor of 2% in a minimum of 75% of all regularly occupied areas.
The glazing factor is calculated as follows:
Glazing =
Window Area (SF)X
Window Geometry
Factor X Actual Tvis X
Window Height Factor Factor Floor Area (SF) Minimum Tvis
OR
OPTION 2 — SIMULATION Demonstrate, through computer simulation, that a minimum daylight illumination level of 25 footcandles has been achieved in a minimum of 75% of all regularly occupied areas. Modeling must demonstrate 25 horizontal footcandles under clear sky conditions, at noon, on the equinox, at 30 inches above the floor.
OR
OPTION 3 — MEASUREMENT Demonstrate, through records of indoor light measurements, that a minimum daylight illumination level of 25 footcandles has been achieved in at least 75% of all regularly occupied areas. Measurements must be taken on a 10-foot grid for all occupied spaces and must be recorded on building floor plans. Measurements must be taken under clear sky conditions, at 30" above the floor, on or about solar noon on the equinox.
OR
OPTION 4 Any of the above calculation methods may be combined to document the minimum daylight illumination in at least 75% of all regularly occupied spaces. The different methods used in each space must be clearly recorded on at minimum a 10-foot grid on all building plans.
DC-152
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
In all cases, only the square footage associated with the portions of rooms or spaces meeting the minimum illumination requirements can be applied towards the 75% of total area calculation required to qualify for this credit. In all cases, provide daylight redirection and/or glare control devices to avoid high-contrast situations that could impede visual tasks. Exceptions for areas where tasks would be hindered by the use of daylight will be considered on their merits.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Design the building to maximize interior daylighting. Strategies to consider include building orientation, shallow floor plates, increased building perimeter, exterior and interior permanent shading devices, high performance glazing and automatic photocell-based controls. Predict daylight factors via manual calculations or model daylighting strategies with a physical or computer model to assess footcandle levels and daylight factors achieved.
Modeling must demonstrate 25 horizontal footcandles under clear sky conditions, at noon, on the equinox, at 30 in. above the floor. Any portion of a room achieving the requirements can qualify for this credit.
Standard Practice
Evaluate building design to maximize interior daylight. Consider: o Building orientation o Shallow floor plates o Increased building perimeter o Floor-to-ceiling heights o Ceiling configurations
Design the building to maximize view opportunities.
Recommended Practice
Provide sky or clerestory lighting as appropriate in cargo and passenger terminal facilities
Coordinate daylight strategy with BAS and lighting control system
Best Available Practice
Provide exterior and interior permanent shading devices Provide spectrally selective glazing to maximize daylight while minimizing heat gain Provide photo-integrated light sensors to dim artificial lights Predict daylighting via calculations or model daylighting strategies to assess
footcandle levels and daylight factors achieved
DC-153
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Humphrey Terminal Design Metropolitan Airports Commission - Minneapolis, Minnesota
Metropolitan Airports Commission, the governing authority for Minneapolis – St. Paul International Airport, has implemented various sustainable strategies for the development of green buildings at the airport. The new Humphrey Terminal optimizes HVAC efficiency, maximizes day-lighting and uses low-flow & automatic fixtures in all restrooms. Construction materials were also recycled and reused.
www.metroairports.org/mac/docs/Star8page.pdf
DC-154
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.10.2 Daylight and Views: Views for 90% of Spaces
1 Point
INTENT
Provide for the building occupants a connection between indoor spaces and the outdoors through the introduction of daylight and views into the regularly occupied areas of the building.
REQUIREMENTS
Achieve direct line of sight to the outdoor environment via vision glazing between 30-inches and 90-inches above finish floor for building occupants in 90% of all regularly occupied areas. Determine the area with direct line of sight by totaling the regularly occupied square footage that meets the following criteria:
In plan view, the area is within sight lines drawn from perimeter vision glazing In section view, a direct sight line can be drawn from the area to perimeter vision glazing
The line of sight may be drawn through interior glazing. For private offices, the entire square footage of the office can be counted if 75% or more of the area has direct line of sight to perimeter vision glazing. For multi-occupant spaces, the actual square footage with direct line of sight to perimeter vision glazing is counted.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Design the space to maximize daylighting and view opportunities. Strategies to consider include lower partition heights, interior shading devices, interior glazing, and automatic photocell-based controls.
Standard Practice
Evaluate building design to maximize interior daylight. Consider: o Building orientation o Shallow floor plates o Increased building perimeter o Floor-to-ceiling heights o Ceiling configurations
Design the building to maximize view opportunities
DC-155
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Provide sky or clerestory lighting as appropriate in cargo and passengers terminal facilities
Coordinate daylight strategy with BAS and lighting control system
Best Available Practice
None
CASE STUDIES
H. Weir Cook Terminal Indianapolis International Airport - Indianapolis, Indiana
The new terminal building at Indianapolis International Airport contains high glass walls and a sweeping roof, where very little heat is transferred from the sun to the inside of the building. During the daylight hours, very little artificial light is required to light the terminal, all leading to energy conservation and cost reduction. The terminal’s high ceiling and high-performance curtain walls minimize solar loads, and a radiantly chilled/heated granite floor help maintain temperature by cooling from the ground up and allowing the warm air to naturally gather at the top of the structure.
www.triplepundit.com/pages/indianapolis-opens-first-sustainable-pos.php
DC-156
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 INDOOR ENVIRONMENTAL QUALITY
6.11 Noise Transmission
1 Point
INTENT
Limit noise levels in noise-sensitive, occupied spaces such as passenger terminals and offices to increase employee productivity and passenger comfort.
REQUIREMENTS
Maintain predicted noise levels in all passenger terminal areas to a Noise Criteria (NC) below 40 and offices and conference rooms below NC30.
OR
Specify exterior glazing with a Sound Transmission Class (STC) of 35 or better per ASTM E413 and ASTM E1332 for all regularly occupied spaces.
SUBMITTALS
Include descriptive narrative in SAM Checklist and show calculations indicating that NC levels are met in all critical areas or submit product data sheets for exterior glazing meeting the STC requirements.
TECHNOLOGY/STRATEGY
There are a number of design techniques that can influence the acoustical quality of indoor spaces. Generally, these can include improved glazing and partitions or less costly design practices such as building and furniture orientation.
Standard Practice
Design spaces in such a way as to orient noise sensitive areas away from major noise sources
Use sound dampening glazing and wall partitions Locate copy machines and printers in separate rooms
Recommended Practice
For office environments, specify acoustical ceiling with an appropriate noise reduction coefficient to meet the requirements of this credit
Choose cubicle partitions that are at least 5 feet tall to provide a sound barrier to workstation occupants
Insulate wall cavities for noise sensitive spaces and extension of partition walls to the structural deck
DC-157
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
Specify laminated glazing to reduce noise transmission for normally occupied spaces
SOURCES
“Silence is Golden: Controlling Sound in Non-Residential Structures” AIA/Architectural Record, Continuing Education Series, May 2007. www.archrecord.construction.com/resources/conteduc/archives/0507marvin-1.asp
Paradis, Richard. “Acoustic Comfort” Whole Building Design Guide, October 27, 2008. www.wbdg.org/resources/acoustic.php
DC-158
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 CONSTRUCTION PRACTICES
7.1 Prerequisite 1 – Clean Fuel Construction Vehicles
Required
NOTE
Due to advancements in available fuels and technologies, as well as changes in regulation, including the City of Chicago Clean Diesel Ordinance for Construction Sites,
this section is currently applicable, but under revision.
INTENT
Minimize air quality impacts during construction.
REQUIREMENTS
All projects must comply with CDA/OMP Specification 01111 – Construction Air Quality. The requirements are summarized below. For additional detail, refer to the CDA/OMP Specification.
The requirements for all off-road vehicles that are on the project site for more than 14 consecutive days are:
All off-road construction vehicles over 50 hp must use ultra-low sulfur diesel (ULSD) fuel conforming to ASTM D975, D5453, D6078, and D613
All off-road diesel-powered vehicles and equipment (both mobile and stationary) over 50 hp must install and/or retrofit with emissions control devices that will reduce emissions prior to utilization of said equipment on the project. The Retrofit Emission Control Devices must consist of diesel oxidation catalysts, diesel particulate filters or similar retrofit equipment control technology that:
o Is included on the EPA Verified Retrofit Technology List (http://epa.gov/cleandiesel/verification/verif-list.htm) or verified by the California Air Resources Board (CARB) (www.arb.ca.gov/diesel/verdev/verdev.htm) or
o Is verified by EPA or represented by the manufacturer in writing, to provide a minimum emissions reduction of 20% PM, 20% CO, and 40% HC when used with Ultra Low Sulfur Diesel fuel.
DC-159
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
o This requirement applies unless the vehicle or equipment is either EPA Tier 2 Rule compliant or meets the horsepower/model year defined in the table below:
Horsepower Range Model Year (or newer) 50-99 2004
100-299 2003 300-599 2001 600-749 2002
750 and up 2006 The requirements for all on-road vehicles that access the project site more than 5 calendar days per month.
All on-road construction vehicles over 50 hp must use ultra-low sulfur diesel (ULSD) fuel conforming to ASTM D975, D5453, D6078, and D613
All diesel powered vehicles meet the idling restrictions described in the specification section. Specifically, vehicles must not idle for more than five consecutive minutes in a 60-minute period when the equipment is not in use except for certain situations, such as traffic conditions or during equipment repairs.
SUBMITTALS
The submittal requirements for compliance with CDA/OMP Specification 01111 – Construction Air Quality and to meet this prerequisite are summarized in the table below:
Submittal Specification
Paragraph Reference
Description Due Date
Contractor/Subcontractor Equipment Verification Report
3.01.B Contractor certifies that vehicles listed on Contractor Equipment Listing are true and accurate and is in compliance with EPA rules.
Prior to start of
construction.
Contractor Equipment Listing
3.01.B Gives a list of all vehicles to be used by Contractor that will be on the Project site and subject to the Fuel Use Requirements in 2.01.
Prior to start of
construction.
Contractor Monthly Fuel Usage Summary Report
3.01.A The form tracks monthly fuel usage for all construction vehicles.
Monthly
Contractor Annual Fuel Usage Summary Report
3.01.A The form tracks annual fuel usage for all construction vehicles in a calendar year (Jan – Dec).
Annual
DC-160
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Submittal Specification
Paragraph Reference
Description Due Date
Equipment Tracking Form
3.01.B Used when new equipment is brought to the project site or old equipment is replaced. Track changes to the Contractor Equipment Listing with this form.
As needed
TECHNOLOGY/STRATEGY
Standard Practice
The OMP currently requires that all off-road construction vehicles over 50 hp use ultra-low sulfur diesel (ULSD) fuel and restrict idling times. In addition, all contractors are required to report fuel usage on a monthly basis. All projects are required to include CDA/OMP Specification 01111 – Construction Air Quality in their contract documents.
Recommended Practice
Contractors are encouraged to identify and incorporate any other measures that may assist in reducing air quality emissions as a result of construction. For example, many cleaner vehicle options now exist for employee shuttle buses and Light Duty Vehicles (LDVs) including compressed natural gas (CNG), hybrid (fuel/electric), flex fuel, and demand on displacement. The availability of cleaner vehicle options is anticipated to expand over time and over the course of the Project. Contractors working on the Project are strongly encouraged to consider these options when making purchase decisions.
Best Available Practice
None
DC-161
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Ultra Low Sulfur Diesel Fuel Mandate Chicago O’Hare Modernization Program - Chicago, Illinois
When the O’Hare Modernization Program (OMP) construction began in September 2005, several years before the EPA was mandating the use of ULSD fuel, the OMP made it a priority to minimize the air quality impacts of such a large construction project. At the time, the availability and cost of the specialized fuel and emissions control equipment caused concern to program officials and contractors alike. However, because of the size and duration of the construction activities, in addition to the need to meet EPA standards by 2010, the program may have bolstered the market for ULSD and the newer, cleaner burning construction.
As of September 2011, approximately 90% of all equipment met Tier 2 emission standards or better. The tier compliance is an emission based standard set by EPA. The higher the tier level the more stringent the emissions will be from the equipment.
DC-162
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 CONSTRUCTION PRACTICES
7.2 Prerequisite 2 – Construction Equipment Maintenance
Required
INTENT
Minimize the environmental impact of construction equipment maintenance activities.
REQUIREMENTS
Follow the requirements of the CDA BMP Manual.
SUBMITTALS
For the SAM Design Checklist, indicate the location in the contract documents where this is required
For the SAM Construction Checklist, the contractor must indicate that all relevant BMPs were implemented
TECHNOLOGY/STRATEGY
By requiring contractors to comply with the CDA BMP Manual, it is anticipated that the impacts due to construction equipment maintenance activities will be reduced. The BMPs include procedures for vehicle washing, maintenance, fueling, chemical storage, and spill control.
Standard Practice
Relevant BMPs (from CDA BMP Manual):
001 – Equipment Vehicle Washing Restrictions 002 – Equipment Vehicle Fueling Controls 003 – Equipment Vehicle Maintenance Requirements 011 – Above Ground Storage Tank Equipment Requirements/Spills 012 – Mobile Tank Trucks (petroleum) Requirements 013 – Chemical Handling/Storage Requirements 014 – Drum Storage Procedures 015 – Battery Storage Procedures 017 – Truck Loading/Unloading Procedures/Spill Control 018 – Spill Control Kits and Spill Response 019 – Good Housekeeping Procedures/Waste Storage 020 – Storm Drain Protection/Identification
DC-163
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
None
Best Available Practice
None
DC-164
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 CONSTRUCTION PRACTICES
7.3 Construction Activity Pollution Prevention
Identical to SAM Credit 2.1 Prerequisite 1 – Construction Activity Pollutant Prevention
Required
INTENT
This credit is identical to SAM Credit 2.1 Prerequisite 1 – Construction Activity Pollutant Prevention and is referenced under this section to emphasize that it is a sustainable construction prerequisite. Points will not be awarded under this credit and the credit is only shown as a reference. Requirements for this credit will be tracked under SAM Credit 2.1 Prerequisite 1 – Construction Activity Pollutant Prevention only.
7.4 Systems Commissioning
Identical to SAM Credit 4.1 Prerequisite 1 – Fundamental Building Systems Commissioning
Required
INTENT
This credit is identical to SAM Credit 4.1 1 – Fundamental Building Systems Commissioning and is referenced under this section to emphasize that it is a sustainable construction prerequisite. Points will not be awarded under this credit and the credit is only shown as a reference. Requirements for this credit will be tracked under SAM Credit 4.1 1 – Fundamental Building Systems Commissioning only.
7.5 Construction Waste Management
Identical to SAM Credit 5.3 Construction Waste Management
No Points – Points awarded under SAM Credit 5.3 Construction Waste Management
INTENT
This credit is identical to SAM Credit 5.3 Construction Waste Management and is referenced under this section to emphasize that it is a sustainable construction credit. Points will not be awarded under this credit and the credit is only shown as a reference. Requirements for this credit will be tracked under SAM Credit 5.3 Construction Waste Management only.
DC-165
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.6 Construction IAQ Management Plan
Identical to SAM Credit 6.5 Construction IAQ Management Plan
No Points – Points awarded under SAM Credit 6.5 Construction IAQ Management Plan
INTENT
This credit is identical to SAM Credit 6.5 Construction IAQ Management Plan and is referenced under this section to emphasize that it is a sustainable construction credit. Points will not be awarded under this credit and the credit is only shown as a reference. Requirements for this credit will be tracked under SAM Credit 6.5 Construction IAQ Management Plan only.
DC-166
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 CONSTRUCTION PRACTICES
7.7 Low-Emission Construction Vehicles
1 Point
INTENT
Minimize air quality impacts during construction.
REQUIREMENTS
In addition to complying with the prerequisite SAM Credit 7.1 Prerequisite 1 – Clean Fuel Construction Vehicles, a point is earned if 50% of all off-road vehicles over 50 hp on the project site for more than 14 consecutive days are EPA Tier 3 compliant or better.
Exemplary Performance
An additional point may be claimed under 8.1 Innovation in Design & Construction if 25% of the off-road vehicles over 50 hp that are on the project site for more than 14 consecutive days are EPA Tier 4a compliant.
SUBMITTALS
Submittal requirements are per CDA/OMP Specification 01111 – Construction Air Quality.
TECHNOLOGY/STRATEGY
Standard Practice
See Standard Practice under SAM Credit 7.1 Prerequisite 1 – Clean Fuel Construction Vehicles
Recommended Practice
In addition to the recommendations in SAM Credit 7.1 Prerequisite 1 – Clean Fuel Construction Vehicles, the contractor is encouraged to use equipment in its existing fleet that meets these guidelines
DC-167
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
In addition to the recommendations in SAM Credit 7.1 Prerequisite 1 – Clean Fuel Construction Vehicles, the contractor is encouraged to purchase new equipment or retrofit existing equipment to meet these guidelines. Consider use of:
o Biodiesel (use regionally derived biofuels) o Other regionally preferred alternative fuels o Diesel-electric hybrid vehicles o Where approved and appropriate, consider the use of Warm Mix Asphalt (WMA)
for paving, which reduces energy usage and emissions. Also see SAM Credit 5.5 Aggregate Reuse.
o GPS for optimizing haul routes and work activities. o Stricter idling controls, including use of idling restrictors. o Newest technology equipment and retrofits.
DC-168
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 CONSTRUCTION PRACTICES
7.8.1 Alternative Transportation During Construction: Staging Area
1 Point
INTENT
Reduce emissions due to construction vehicles by minimizing the amount of traffic to the construction site.
REQUIREMENTS
To meet this credit each project must have a staging area where employees congregate prior to entering the project site.
AND
Use multiple occupancy vehicles to access the project site from the centralized staging area.
SUBMITTALS
Although not required for the SAM Design Checklist, a staging area, with contractor trailer, should be included in the design drawings.
For the SAM Construction Checklist, the contractor must state that the staging area, with contractor trailer, was present and list or describe how employees accessed the project site (e.g., pooled in trucks or shuttle bus).
TECHNOLOGY/STRATEGY
Standard Practice
Most projects typically use heavier duty vehicles such as pick-up trucks or SUVs to provide workers with access to the project site. In some cases, for larger projects, buses are used
Recommended Practice
Establish procedures and make vehicles available for employee car pooling to the project site. For maximum benefit, shuttle buses or vans are preferred over lower occupancy vehicles such as pick-up trucks.
Best Available Practice
Use fuel-efficient vehicles for car pooling employees to the project site
DC-169
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 CONSTRUCTION PRACTICES
7.8.2 Alternative Transportation During Construction: Low-Emitting and Fuel-Efficient Vehicles, 10%
1 Point
INTENT
Reduce emissions from on-road construction vehicles (e.g., foreman pickups or shuttle buses).
REQUIREMENTS
The contractor must use fuel efficient and low emitting vehicles for at least 10% of all on-road, contractor-owned construction vehicles that access the project site more than five calendar days per month. To meet this requirement, the vehicles must have an Air Pollution Score or a Greenhouse Gas Score of 6 or greater according to the EPA Green Vehicle Guide. A partial list of heavier duty vehicles (pick-ups and SUVs) for the 2012 model year that meet these requirements are shown below for reference:
Vehicle Make/Model (Type) Engine/Transmission/Fuel Air Pollution
Score Greenhouse Gas Score
GMC Canyon (Pick-Up) 5.3L/Auto 4WD/Gasoline 6 4
Chevrolet Silverado 15 (Pick-Up) 5.3L/Auto 2WD/ Ethanol-Gasoline 6 (Ethanol) 3 (Ethanol)
Chevrolet Colorado (Pick-Up) 2.9L/Auto 2WD/Gasoline 6 4
Ford F150 (Pick-Up) 3.7L/Auto 2WD/Gasoline 6 3
Toyota Highlander Hybrid (SUV) 3.3L/CVT 4WD/Gasoline 7 7
Chevrolet Equinox (SUV) 2.4L/Auto 2WD/Ethanol-Gasoline 6 (Ethanol) 6 (Ethanol)
Ford Escape Hybrid (SUV) 2.5L/CVT/2WD/Gasoline 7 7
GMC Terrain (SUV) 2.4L/Auto 2WD/Gasoline 6 6
Note: CVT – Continuously Variable Transmission
SUBMITTALS
For the sustainable construction checklist, the contractor must submit a list of its on-road vehicles and identify those which meet the EPA Green Vehicle ratings described above.
DC-170
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
The ratings are based on the Green Vehicle Guide that is prepared annually by the EPA (www.epa.gov/greenvehicles/Index.do). The Air Pollution Score is based on the government emission standards for which the vehicle was certified to comply with and reflects vehicle tailpipe emissions that contribute to local and regional air pollution, creating problems such as haze, and health issues. This score reflects fuel lifecycle emissions of carbon dioxide (CO2) and other greenhouse gases. The scores are on a scale of 1 to 10 with 10 being the highest rating.
Standard Practice
Some hybrid and flex fuel vehicles have been used by various contractors
Recommended Practice
Promote the use of vehicles that meet the requirements above for EPA Air Pollution and Greenhouse Gas Scoring system
Best Available Practice
Consider the use of compressed natural gas (CNG), electric, fuel cell, biodiesel vehicles
CASE STUDY
Alternative Fuel Technology Los Angeles World Airports - Los Angeles, California
Both compressed natural gas (CNG) and liquefied natural gas (LNG) are used, along with propane, to power fleet and maintenance-related vehicles at airports throughout the country. About half of the Los Angeles World Airport fleet operates on these fuels. These emission-reducing vehicles include sedans, pickups, shuttle buses, heavy duty trucks, forklifts and sweepers.
http://abclocal.go.com/kabc/story?section=news/local/los_angeles&id=8093168
DC-171
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 CONSTRUCTION PRACTICES
7.8.3 Alternative Transportation During Construction: Low-Emitting and Fuel-Efficient Vehicles, 50%
1 Point
INTENT
Reduce emissions from on-road construction vehicles.
REQUIREMENTS
The contractor must use fuel efficient and low emitting vehicles for at least 50% of all on-road, contractor-owned construction vehicles that access the project site more than five calendar days per month. To meet this requirement, the vehicles must have an Air Pollution Score or a Greenhouse Gas Score of 6 or greater according to the EPA Green Vehicle Guide. A partial list of heavier duty vehicles (pick-ups and SUVs) for the 2012 model year that meet these requirements are shown below for reference:
Vehicle Make/Model (Type) Engine/Transmission/Fuel Air Pollution
Score Greenhouse Gas Score
GMC Canyon (Pick-Up) 5.3L/Auto 4WD/Gasoline 6 4
Chevrolet Silverado 15 (Pick-Up) 5.3L/Auto 2WD/ Ethanol-Gasoline 6 (Ethanol) 3 (Ethanol)
Chevrolet Colorado (Pick-Up) 2.9L/Auto 2WD/Gasoline 6 4
Ford F150 (Pick-Up) 3.7L/Auto 2WD/Gasoline 6 3
Toyota Highlander Hybrid (SUV) 3.3L/CVT 4WD/Gasoline 7 7
Chevrolet Equinox (SUV) 2.4L/Auto 2WD/Ethanol-Gasoline 6 (Ethanol) 6 (Ethanol)
Ford Escape Hybrid (SUV) 2.5L/CVT/2WD/Gasoline 7 7
GMC Terrain (SUV) 2.4L/Auto 2WD/Gasoline 6 6
Note: CVT – Continuously Variable Transmission
SUBMITTALS
For the sustainable construction checklist, the contractor must submit a list of its on-road vehicles and identify those which meet the EPA Green Vehicle ratins described above.
DC-172
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
The ratings are based on the Green Vehicle Guide that is prepared annually by the EPA (www.epa.gov/greenvehicles/Index.do ). The Air Pollution Score is based on the government emission standards for which the vehicle was certified to comply with and reflects vehicle tailpipe emissions that contribute to local and regional air pollution, creating problems such as haze, and health issues. This score reflects fuel lifecycle emissions of carbon dioxide (CO2) and other greenhouse gases. The scores are on a scale of 1 to 10 with 10 being the highest rating.
Standard Practice
Some hybrid and flex fuel vehicles have been used by various contractors
Recommended Practice
Promote the use of vehicles that meet the requirements above for EPA Air Pollution and Greenhouse Gas Scoring system
Best Available Practice
Consider the use of hybrid diesel-electric, hybrid gasoline-electric, compressed natural gas (CNG), liquefied natural gas (LNG), electric, fuel cell, and biodiesel vehicles
DC-173
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 CONSTRUCTION PRACTICES
7.9 Construction Materials Conveyance
1 Point
INTENT
Reduce emissions from construction activities by minimizing the amount of on-road and off-road vehicle traffic traveling to/from the construction site.
REQUIREMENTS
Use an automatic materials conveyance system as a method for transporting materials to or from a construction site.
SUBMITTALS
For the sustainable construction checklist, the contractor must describe the conveyance system in the narrative.
TECHNOLOGY/STRATEGY
The use of a materials conveyance system not only reduces site traffic but can also aid in logistics, noise reduction, and increased security. The primary focus of a conveyance system will obviously be in those projects in which there is a large area requiring significant grading changes. While it is encouraged that soil be maintained on-site as much as possible, for those case where it is not feasible, a conveyance system would be a potential solution for transport to off-site, on- or near-airport locations.
Standard Practice
Due to the configuration of the airfield and the proximity of the earth stockpiles and sources, there has so far not been a need to use an automatic conveyor system. However, a railroad relocation project was awarded a point under this credit as a result of using the rail line itself to deliver materials for this project
Recommended Practice
Construct Batch Plants as needed on- or near-site or utilize rail transport where available or appropriate
DC-174
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
None
CASE STUDIES
Recycling and Waste Management Conveyor Hartsfield-Jackson Atlanta International Airport - Atlanta, Georgia
Hartsfield-Jackson International Airport in Atlanta has developed innovative programs to handle and process demolition waste for reuse in airport construction projects. The airport utilized an overland belt conveyor system that transported 93 percent of the 21.5 million cubic yards of fill necessary for a new runway’s construction, resulting in reduced truck trips, emission elimination, and diversion of construction material waste from landfills.
www.aci-na.org/static/entransit/Going%20Green%209-7-07.pdf
Materials Management Program Oakland International Airport - Oakland, California
As capital improvement and infrastructure programs increase over the next few years, Oakland International Airport, has implemented a comprehensive construction materials management program to reduce the amount of transport and disposal of construction materials and increase recycling and re-use of these materials.
www.oaklandairport.com/noise/environmental_construct.shtml
DC-175
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 CONSTRUCTION PRACTICES
7.10 Construction Noise and Acoustical Quality
1 Point
INTENT
Improve the exterior noise quality during construction affecting residential areas or other noise sensitive areas.
REQUIREMENTS
Although the City of Chicago has an environmental noise ordinance (Article XXI – Environmental Noise and Vibration Control), it does not apply to construction or demolition work on public improvements authorized by a government body or agency (City Ordinance 11-4-2835).
The requirements of this credit will only apply to noise disturbances that are adjacent to noise sensitive areas, such as residential or institutional (hospitals, schools, libraries, nursing homes) areas. Noise disturbances are defined as any sound which is audible at a distance of 600 feet from its source or any sound which generates a sound pressure level in the public way exceeding 70 dB(A) when measured 10-feet from the source (City Ordinance 11-4-2710).
To achieve a point under this credit, the following requirements must be met during construction for those sites that are near noise sensitive areas as defined by the Chicago City Ordinance:
Meet the noise restrictions listed in the Chicago City Ordinance (Article XXI, Part B) which include, but are not limited to, noise from mechanical stationary sources (11-4-2810), loading and unloading operations (11-4-2830), and construction equipment (11-4-2835) during nighttime hours.
OR
Implement a noise abatement or noise mitigation plan that identifies site specific, mechanical, structural or operational measures to reduce noise disturbances in noise sensitive areas adjacent to the project site.
SUBMITTALS
Although not required for the sustainable design checklist, indicate noise sensitive areas on plans to aid contractor in determining the best noise mitigation strategies.
For the sustainable construction checklist, the contractor must indicate that the requirements of the Chicago Environmental Noise Ordinance have been met or submit a noise mitigation plan identifying the measures taken to reduce noise disturbances in the affected areas.
DC-176
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
The primary paragraph related to construction activities is Chicago City Ordinance 11-4-2835 which basically states that no fuel or electric powered mechanical equipment may be used during the hours of 8:00 p.m. and 8:00 a.m. within 600 feet of any residential areas or hospitals. The ordinance further states that public improvements authorized by a government agency, like the OMP, are not subject to this ordinance, however, a point will be given under this credit for those projects that choose to comply with the ordinance.
There are numerous noise mitigation methods that can be employed some of which are site or equipment specific. The easiest method of noise mitigation is to locate the noise source in an area that is not noise sensitive and to conduct that work during daytime hours, 8:00am to 8:00pm. Where this is not possible, temporary barriers can be erected to mitigate the noise emanating from a source.
Standard Practice
None
Recommended Practice
None
Best Available Practice
None
CASE STUDY
Noise Abatement and Mitigation Procedures Federal Highway Administration
The Federal Highway Administration has identified a number of measures and provisions which help to mitigate construction noise. One such strategy is the utilization of natural and artificial barriers such as ground elevation changes, existing buildings, noise walls, and other structures.
Also, many construction vehicle engine compressors are contained or have baffles to help abate noise levels. Electric compressors are significantly quieter than diesel or gasoline engine powered compressors.
www.fhwa.dot.gov/environment/noise/handbook/07.htm
DC-177
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 CONSTRUCTION PRACTICES
7.11 Sustainable Temporary Construction Materials
1 Point
INTENT
Reduce the use and depletion of finite raw materials and long-cycle renewable materials by replacing them with high recycled content, rapidly renewable materials and FSC certified wood products for temporary uses during construction.
REQUIREMENTS
Temporary construction materials include, but are not limited to, any materials that are used for construction that are not incorporated into the final development such as, erosion control materials, temporary haul roads, shoring materials, formwork, temporary carpentry, and traffic control devices and signage. For the purposes of this calculation, only the material cost, excluding labor and equipment, shall be used. In order to meet the requirements of this credit, one of the following requirements must be met:
Using a recycled content calculation similar to SAM Credit 5.7 Recycled Content, determine the percentage of recycled content in the temporary construction materials based on overall temporary construction material cost. To achieve a point in this credit, the overall recycled content of the temporary construction materials must be 30% or greater by cost.
OR
Using a rapidly renewable content calculation similar to SAM Credit 5.9 Rapidly Renewable Materials, determine the percentage of the rapidly renewable materials based on overall temporary construction material cost. To achieve a point in this credit, the overall recycled content of the temporary construction materials must be 10% or greater by cost.
OR
Using a certified wood calculation similar to SAM Credit 5.10 Certified Wood, determine the percentage of certified wood materials based on the total wood-based material cost. To achieve a point in this credit, the overall recycled content of the temporary construction materials must be 60% or greater by cost.
Do not count temporary construction materials under any of the credits in Section 5.0 - Materials & Resources. Materials such as aggregates may be counted either under SAM Credit 5.5 Aggregate Reuse or this credit, but should only be counted once.
DC-178
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
SUBMITTALS
Although not required for the Sustainable Design Checklist, include specification sections that indicate how these requirements are met.
For the sustainable construction checklist, the contractor must provide a calculation of the actual materials used indicating that at least one of the above requirements was met.
Use calculation templates similar to the SAM Credits in Section 5.0 - Materials & Resources – as appropriate.
TECHNOLOGY/STRATEGY
Many temporary construction materials can help achieve the requirements of this credit. Although not tracked by LEED, CDA has added this credit in order to promote the use of such materials during construction, as well as for final development stages of a project.
Standard Practice
Although many temporary construction materials meet the requirements of this credit, their use is typically not tracked or promoted. The designer is encouraged to specify sustainable materials in construction wherever possible. The contractor is further encouraged to use these types of materials in the cases where they may not be explicitly specified.
Recommended Practice
Materials that may have high recycled content include, but are not limited to:
Temporary steel structures or materials Fencing or metal barricades Plastic traffic control devices (barricades, cones) Temporary piping (HDPE, ductile iron) Steel formwork Plastic erosion control materials (e.g. silt fence)
Materials that have rapidly renewable materials include, but are not limited to:
Poplar oriented strand board (OSB) for formwork or temporary carpentry Coir or jute fabric erosion control blankets and meshes Plant-based cladding and insulation materials Contractor trailer materials such as flooring and finishes
DC-179
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
FSC certified wood products for temporary construction materials may include:
Wood formwork Temporary wood structures or scaffolding
Best Available Practice
None
CASE STUDY
Sustainable Scaffolding Materials Seattle, Washington
When Seattle enacted a Sustainable Building Policy in 2000, all new city-funded renovations and construction projects were required to obtain LEED Silver rating. In response to this initiative, contractors are expected to begin utilizing sustainable materials for construction project scaffolding structures. Most of these types of scaffolding structures are made of bamboo or hybrid-bamboo material, which is regarded as highly sustainable.
www.scaffoldingusa.com/scaffold/seattle-scaffolding.html
DC-180
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Clean fuel construction vehicles
On-site Batch Plant
Balanced Earthwork Plan, in action
Designated material recycling area
DC-181
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8.0 INNOVATION IN DESIGN & CONSTRUCTION
8.1 – 8.3 Innovation in Design & Construction
1 to 3 Points
INTENT
Provide design teams and projects the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
REQUIREMENTS
In writing, identify the intent of the proposed innovation credit, the proposed requirement for compliance, the proposed submittals to demonstrate compliance, and the approach (strategies) that might be used to meet the requirements.
Up to 3 points may be awarded for this credit:
SAM Credit Points
8.1 1
8.2 1
8.3 1
SUBMITTALS
Include descriptive narrative in the SAM Checklist following the criteria in the Requirements section above.
TECHNOLOGY/STRATEGY
Substantially exceed a SAM performance credit such as energy performance or water efficiency and/or apply strategies or measures that demonstrate a comprehensive approach and quantifiable environment and/or health benefits.
Refer to LEED Credit Interpretation Results (CIRs) or the Innovation in the LEED Design Credit Catalog4 for potential strategies that may be considered for innovation. Most will pertain to building related innovations; however the SRP will review proposed innovations by the designer or contractor on a case by case basis. Some examples include green cleaning programs for buildings, educational programs for building occupants related to sustainability, and innovative construction practices that reduce waste such as travelling formwork.
4 Available at www.usgbc.org.
DC-182
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
DFW Sustainability Initiative Dallas / Fort Worth International Airport - Dallas, Texas
In August 2008, DFW Airport initiated an airport-wide Sustainability Policy and Program, which is a key element in the Airport’s Strategic Plan designed to positively impact the environment, the surrounding community, the Airport and its employees. This comprehensive approach encourages project submittals for airport-related facilities to demonstrate compliance to LEED-related policies and the strategies used to meet the requirements.
www.dfwairport.com/sustainability/index.php?ctnid=45185
www.airports.org/aci/aci/file/ACI_Priorities/Environment/TRACKER%20FILE_Airport%20environment%20initiatives.pdf
DC-183
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8.0 INNOVATION IN DESIGN & CONSTRUCTION
8.4 Menu Items (Construction Equipment Retrofit, Photovoltaics, Geothermal Heating/Cooling, Wind Power, Rainwater Harvesting, Permeable Pavement, Trombe or Solar Walls, Green Walls, Warm-Mix Asphalt or Alternative Water Heating)
1 to 5 Points
INTENT
Promote specific technologies and additional strategies considered to be important to the sustainability of the airport environment.
REQUIREMENTS
A point will be awarded for each of the technologies or strategies listed below that are used on a project up to a maximum of 3 points:
Construction Equipment Retrofit – Retrofit all construction equipment over 50 hp and on site for more than 14 calendar days per month to EPA Tier 3 emission standards
Photovoltaics – Use photovoltaic systems to generate electricity. System must generate 0.5 kW or greater
Geothermal Heating/Cooling – Any geothermal system to provide heating and cooling is acceptable
Wind Power – Generate on-site electricity using wind turbines, horizontal or vertical. System must generate 0.5 kW or greater
Rainwater Harvesting – Use cisterns, rain barrels, or other vessels to store rain water for other uses including, but not limited to, irrigation, vehicle washing, and other general, non-potable uses. The harvested rainwater must have an intended use. Minimum storage capacity is 200 gallons.
Permeable Pavement – Use permeable pavement such as concrete, asphalt, or pavers, for at least 5% of the total pavement area of the project not subject to aircraft traffic or 1,000 sq. ft, whichever is greater
Trombe or Solar Walls – Use passive solar preheating of intake air for space heating using wall systems or other building surfaces
Green Walls – Use green, vegetated wall systems on exterior of building envelope for at least 25% of the vertical wall surfaces or the entirety of south and/or west facing walls, whichever is greater
Warm-Mix Asphalt – Use warm-mix asphalt for at least 5% of the total pavement area of the project or 1,000 sq. ft, whichever is greater
Alternative Hot Water Heating – Use solar thermal for 25% or demand (tankless) hot water heating systems for 100% of the project’s hot water demand. Excludes process water demand.
DC-184
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist. Indicate in the narrative which of the above technologies and strategies are being included in the project and, where applicable, indicate where these items are shown in the drawings or specifications.
TECHNOLOGY/STRATEGY
Choose any of the following:
Construction equipment retrofit – The use of particulate traps and catalysts to meet more stringent EPA emissions standards for older construction equipment
Photovoltaics – Photovoltaic or solar-electric systems may be ground-mounted, roof-mounted, or built into the roof or walls of a building, known as building integrated photovoltaic (BIPV)
Geothermal heating/cooling systems – Any geothermal system to provide heating and cooling is an acceptable strategy
Wind power – Generate on-site electricity using wind turbines, horizontal or vertical Rainwater harvesting – Collecting rainwater from the many roofs at an airport would
provide a large source of clean non-potable water. Although the supply would far exceed the demand, the use of harvested rainwater should be taken on a site-specific case by case basis. Although airport irrigation is limited to ornamental planters, other uses such as vehicle washing may be amenable to this technology.
Permeable pavement – The amount of pavement at an airport makes permeable pavement an attractive application for the management of stormwater. Although major pavement areas such as runways, taxiways, and apron areas cannot include permeable pavement, there is a significant amount of non-aviation related pavement areas. Using permeable pavement, unit pavers or permeable asphalt or concrete, may also further contribute to the sustainability of a project because these materials can contain high recycled content materials that are locally available, and may reduce heat island effects for non-roof areas, in addition to their stormwater management aspects. All three of these types of pavements have been demonstrated and are being used by the City of Chicago in its Green Alley Program under the direction of Chicago Department of Transportation (CDOT).
Trombe or Solar walls – These systems use solar energy to heat a thermal mass, usually a concrete wall or an air gap between an interior wall and a dark-colored exterior surface, as means to preheat intake air. On very cold days, the heating system can condition preheated air rather than putting the additional energy in heating cold outside air, thereby realizing an energy savings. In some cases, the wall may also have a photovoltaic component that generates electricity.
Green Walls – Vegetated green wall systems on exterior of building envelope can reduce wall surface temperatures by as much as 18°F (depending on which direction it is
DC-185
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
facing), which also results in significant air conditioning savings, while reducing the heat island effect
Warm-Mix Asphalt - Warm-mix asphalt allows the producers of hot-mix asphalt pavement material to lower the temperatures at which the material is mixed and placed on the road. Reductions of 50°F to 100°F have been documented. Such drastic reductions have the obvious benefits of cutting fuel consumption and decreasing the production of greenhouse gases. In addition, engineering benefits include better compaction on the road, the ability to haul paving mix for longer distances, and extending the paving season by being able to pave at lower temperatures.
Water heating – Solar thermal hot water heating technology uses a solar collector which is simply a heat exchanger designed to convert the sun’s radiant light energy into thermal energy to be stored for later use. This collector uses optics and parabolic concentration technology to heat the fluid media passing through the selectively coated tubing manifold. The fluid media is circulated, via a pump, through the collector and into a storage tank located within the home/building. Other water heating technologies that are encouraged include demand, instantaneous, or tankless water heaters. Demand water heaters heat water directly without the use of a storage tank thus avoiding the standby heat losses associated with conventional storage tank water heaters. When a hot water tap is turned on, cold water travels through a pipe into the unit. Either a gas burner or an electric element heats the water as it passes through coiled piping within the unit. As a result, demand water heaters deliver a constant supply of hot water not limited by the volume of a storage tank.
DC-186
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
What about Green Walls? Tokyo, Japan
During summer, hot walls cause temperatures to rise inside buildings, increasing demand on cooling systems and consuming more energy. A Green Wall surface temperature is reduced by up to 10°C when covered with plants and moist soil. In 1979, Green Wall research by Akira Hoyano (Professor, Tokyo Institute of Technology), a pioneer in passive and low-energy architecture, revealed that the heat energy that passed through a Green Wall was significantly lower than a concrete wall (see below graph).
The Tokyo City Government recently undertook a study to measure the effects of Green Walls on the Heat Island effect, and in essence, to confirm Professor Hoyano's earlier findings. They not only confirmed the findings, but they were able to derive the significance of Green Walls in cooling buildings and combating the Heat Island Effect.
With the Green Wall tests shown here, it was discovered that Green Wall panels reduce the wall temperature by 10°C (see the below graph). It was also concluded that Green Wall panel reduce energy transfer into a building by ~0.24kWh/m2. This is approximately 60% less than that of a Green Roof. The above calculations can be used in the same manner, however, Green Wall energy savings calculations depend greatly on the direction the wall is facing, the sun's angle in your local region, and many other factors that make calculating Green Wall energy savings complex.
DC-187
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8.0 INNOVATION IN DESIGN & CONSTRUCTION
8.5 LEED Accredited Professional
1 Point
INTENT
Support and encourage the design integration required by LEED to streamline the application and certification process.
AND
Facilitate the incorporation of sustainable design and construction elements.
REQUIREMENTS
At least one principal participant of the project team shall be LEED accredited (i.e., LEED Green Associate; LEED Accredited Professional).
SUBMITTALS
Identify the LEED accredited individual(s) in the SAM Checklist and submit proof of their LEED certification.
TECHNOLOGY/STRATEGY
Educate the project team members about green building design and construction, the LEED requirements and application process early in the life of the project. Consider assigning integrated design and construction process facilitation to the LEED accredited individual.
Standard Practice
The OMP requires that each design consultant and/or design management team include a LEED accredited individual on its staff to oversee the design and assist with construction administration
CASE STUDY
Sustainable Airport Planning, Design and Construction Guidelines Los Angeles World Airports - Los Angeles, California
Los Angeles World Airports, with aggressive support from Los Angeles Mayor Antonio Villaraigosa, has begun implementation of the “Sustainable Airport Planning, Design and Construction Guidelines” for all projects at its facilities. The vision encourages every project to include LEED-accredited professionals and follow the “triple bottom line” approach for sustainability.
DC-188
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8.0 INNOVATION IN DESIGN & CONSTRUCTION
8.6 LEED Certified Project
1 Point
INTENT
Promote the incorporation of environmentally sustainable design in building and infrastructure improvements by registering and certifying a project through the LEED certification process and rating system.
REQUIREMENTS
Achieve certification via the LEED process – Certified, Silver, Gold, or Platinum.
SUBMITTALS
Include descriptive narrative in SAM Checklist demonstrating that the project has been registered under LEED during the design process. Provide the LEED submittal documentation and final determination. Indicate what level of LEED certification has been achieved after construction.
TECHNOLOGY/STRATEGY
Educate the project team members about green building design & construction and application of the LEED Rating System early in the life of the project. Consider pursuing LEED for any occupied building project.
Standard Practice
Projects are encouraged to seek LEED certification, where applicable
Recommended Practice
Encourage LEED Silver or better rating for occupied buildings
Best Available Practice
None
CASE STUDY
O’Hare Modernization Program Chicago O’Hare International Airport - Chicago, Illinois
The O’Hare Modernization Program has encouraged several projects to pursue LEED certification, including the North Air Traffic Control Tower and FedEx World Services Center.
http://www.airportbusiness.com/print/Airport-Business-Magazine/A-Model-for-Sustainability/1$30978
DC-189
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
9.0 REGIONAL PRIORITY
9.1 Regional Priority
1 to 4 Points
INTENT
Provide an incentive for the achievement of credits that address geographically-specific environmental priorities.
REQUIREMENTS
Earning one to four of the 6 Regional Priority credits identified by the USGBC regional councils and chapters as having environmental importance for a project’s region. A database of Regional Priority credits and their geographic applicability is available on the USGBC website, www.usgcb.org.
The credits are specific to a project's ZIP code. Use the following link to determine which credits are applicable for a given project based on zip code location:
www.usgbc.org/DisplayPage.aspx?CMSPageID=1984
One point is awarded for each Regional Priority credit achieved; no more than four credits identified as Regional Priority credits may be earned. Projects outside the US are not eligible for Regional Priority credits.
For example, the majority of ORD lies within the 60666 zip code. The following credits are identified as Regional Priority credits for ORD zip code 60666:
SAM Credit 2.4.1 – Alternative Transportation: Public Transportation Access SAM Credit 2.4.3 – Alternative Transportation: Low-Emitting Vehicles SAM Credit 2.4.4 – Alternative Transportation: Parking Capacity SAM Credit 2.5.2 – Stormwater Design: Quality Control LEED 2009 SSc1 – Site Selection LEED 2009 SSc2 – Development Density and Community Connectivity
NOTE: Two LEED credits listed above are applicable for this zip code, but are not SAM Credits outlined in this Manual. Meeting any of the four of the SAM Credits would earn one point for each. However, if the project is pursuing LEED certification, all of the credits would be applicable, but the maximum points allowed is still four.
NOTE: Zip Codes present at ORD in order of decreasing area size include 60666 (Cook Co.), 60106 (DuPage Co.), 60018 (NE boundaries, Rosemont), 60007 (NW boundaries), 60176 (SE boundaries, Schiller Park). The Zip Code at MDW is 60638.
DC-190
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
SUBMITTALS
The submittals for this Credit are the same as for constituent credits; no additional submittals are required.
TECHNOLOGY/STRATEGY
See applicable credits determined by location.
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
APPENDIX DC-A
GREEN AIRPLANE RATING SYSTEM for
DESIGN & CONSTRUCTION
The Sustainable Airport Manual Green Airplane Rating System consists of all the points available for each credit, by project category, for each checklist. The table shows each of the nine credit categories for the Design & Construction chapter of the SAM, their titles and available points. The points that can be achieved vary based on the four project types, Civil-Airside (CA), Civil-Landside (CL), Occupied Buildings (OB), and Unoccupied Buildings (UB), and by checklist, design versus construction. The total points achieved can be used to determine the SAM Green Airplane Rating which is shown at the bottom of the table. For example, a Civil-Airside project during the SAM Design Checklist review would need to earn at least 25 points, but less than 31, to achieve a 3 Green Airplane rating.
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
______________
SUSTAINABLE AIRPORT MANUAL GREEN AIRPLANE RATING SYSTEM_______________
Civil-Airside
Civil-Landside
Occupied Buildings
Unoccupied Buildings
Civil-Airside
Civil-Landside
Occupied Buildings
Unoccupied Buildings
1.0 Administrative Procedures 1 8 8 8 8 8 8 8 8AP.1 Prerequisite 1 Green Meetings Required Required Required Required Required Required Required Required RequiredAP.2 Prerequisite 2 Document Reduction and Recycling Initiative (DRRI) Required Required Required Required Required Required Required Required RequiredAP.3 Corporate Sustainability Policy 1 1 1 1 1 1 1 1 1AP.4 Green Procurement Policy 4 4 4 4 4 4 4 4
AP.5.1 Recycled Content Paper, 30% 1 1 1 1 1 1 1 1AP.5.2 Recycled Content Paper, 50% 1 1 1 1 1 1 1 1AP.5.3 Recycled Content Paper, 100% 1 1 1 1 1 1 1 1
2.0 Sustainable Sites 18 3 5 18 6 3 5 18 6 SS2.1 Prerequisite 1 Construction Activity Pollution Prevention Required Required Required Required Required Required Required Required Required SS pr12.2 Prerequisite 2 Adopt CDA Best Management Practices Required Required Required Required Required Required Required Required Required2.3 Brownfield Redevelopment 1 1 1 1 1 1 1 1 1 SS cr3
2.4.1 Alternative Transportation: Public Transportation Access 6 6 6 SS cr4.12.4.2 Alternative Transportation: Bicycle Access, Storage and Changing Rooms 1 1 1 SS cr4.22.4.3 Alternative Transportation: Low-Emitting and Fuel-Efficient Vehicles (Non-Construction) 3 3 3 SS cr4.32.4.4 Alternative Transportation: Parking Capacity 2 2 2 SS cr4.42.5.1 Stormwater Design: Quantity Control 1 1 1 1 1 1 1 SS cr6.12.5.2 Stormwater Design: Quality Control 1 1 1 1 1 1 1 SS cr6.22.6.1 Landscape and Exterior Design to Reduce Heat Islands: Non-Roof 1 1 1 1 1 1 1 1 1 SS cr7.12.6.2 Landscape and Exterior Design to Reduce Heat Islands: Roof 1 1 1 1 1 SS cr7.2
2.7 Light Pollution Reduction 1 1 1 1 1 1 1 1 1 SS cr83.0 Water Efficiency 10 4 4 10 10 4 4 10 10 WE3.1 Prerequisite 1 Water Use Reduction, 20% Reduction Required Required Required Required Required WE pr1
3.2.1 Water Use Reduction, 30% Reduction 2 2 2 2 2 WE cr3.13.2.2 Water Use Reduction, 35% Reduction 1 1 1 1 1 WE cr3.23.2.3 Water Use Reduction, 40% Reduction 1 1 1 1 1 WE cr3.33.3.1 Water Efficient Landscaping, Reduce by 50% 2 2 2 2 2 2 2 2 2 WE cr1.13.3.2 Water Efficient Landscaping, No Potable Water Use or No Irrigation 2 2 2 2 2 2 2 2 2 WE cr1.2
3.4 Innovative Wastewater Technologies 2 2 2 2 2 WE cr24.0 Energy & Atmosphere 35 15 15 35 35 15 15 35 35 EA4.1 Prerequisite 1 Fundamental Building Systems Commissioning Required Required Required EA pr14.2 Prerequisite 2 Minimum Energy Performance Required Required Required Required Required Required Required Required Required EA pr24.3 Prerequisite 3 Fundamental Refrigerant Management Required Required Required Required Required EA pr3
4.4.1 Optimize Energy Performance, 12% New Buildings, 8% Existing Buildings, 8% Civil 1 1 1 1 1 1 1 1 1 EA cr1.14.4.2 Optimize Energy Performance, 14% New Buildings, 10% Existing Buildings, 16% Civil 1 1 1 1 1 1 1 1 1 EA cr1.24.4.3 Optimize Energy Performance, 16% New, 12% Existing, 24% Civil 1 1 1 1 1 1 1 1 1 EA cr1.34.4.4 Optimize Energy Performance, 18% New, 14% Existing, 32% Civil 1 1 1 1 1 1 1 1 1 EA cr1.44.4.5 Optimize Energy Performance, 20% New, 16% Existing, 40% Civil 1 1 1 1 1 1 1 1 1 EA cr1.54.4.6 Optimize Energy Performance, 22% New, 18% Existing, 48% Civil 1 1 1 1 1 1 1 1 1 EA cr1.64.4.7 Optimize Energy Performance, 24% New, 20% Existing 1 1 1 1 1 EA cr1.74.4.8 Optimize Energy Performance, 26% New, 22% Existing 1 1 1 1 1 EA cr1.84.4.9 Optimize Energy Performance, 28% New, 24% Existing 1 1 1 1 1 EA cr1.9
4.4.10 Optimize Energy Performance, 30% New, 26% Existing 1 1 1 1 1 EA cr1.104.4.11 Optimize Energy Performance, 32% New, 28% Existing 1 1 1 1 1 EA cr1.114.4.12 Optimize Energy Performance, 34% New, 30% Existing 1 1 1 1 1 EA cr1.124.4.13 Optimize Energy Performance, 36% New, 32% Existing 1 1 1 1 1 EA cr1.134.4.14 Optimize Energy Performance, 38% New, 34% Existing 1 1 1 1 1 EA cr1.144.4.15 Optimize Energy Performance, 40% New, 36% Existing 1 1 1 1 1 EA cr1.154.4.16 Optimize Energy Performance, 42% New, 38% Existing 1 1 1 1 1 EA cr1.164.4.17 Optimize Energy Performance, 44% New, 40% Existing 1 1 1 1 1 EA cr1.174.4.18 Optimize Energy Performance, 46% New, 42% Existing 1 1 1 1 1 EA cr1.184.4.19 Optimize Energy Performance, 48% New, 44% Existing 1 1 1 1 1 EA cr1.19
4.5.1 On-Site Renewable Energy, 1% 1 1 1 1 1 1 1 1 1 EA cr2.14.5.2 On-Site Renewable Energy, 3% 1 1 1 1 1 1 1 1 1 EA cr2.24.5.3 On-Site Renewable Energy, 5% 1 1 1 1 1 1 1 1 1 EA cr2.34.5.4 On-Site Renewable Energy, 7% 1 1 1 1 1 1 1 1 1 EA cr2.44.5.5 On-Site Renewable Energy, 9% 1 1 1 1 1 1 1 1 1 EA cr2.54.5.6 On-Site Renewable Energy, 11% 1 1 1 1 1 1 1 1 1 EA cr2.64.5.7 On-Site Renewable Energy, 13% 1 1 1 1 1 1 1 1 1 EA cr2.7
4.6 Enhanced Commissioning 2 2 2 2 2 EA cr34.7 Enhanced Refrigerant Management 2 2 2 2 2 EA cr44.8 Measurement and Verification 3 3 3 3 3 EA cr54.9 Green Power 2 2 2 2 2 2 2 2 2 EA cr65.0 Materials & Resources 21 17 17 21 21 17 17 21 21 MR5.1 Prerequisite 1 Storage and Collection of Recyclables Required Required Required Required Required Required Required Required Required MR pr1
5.2.1 Building and Infrastructure Reuse, Maintain 55% of Existing Walls, Floors, and Roof or Infrastructure 1 1 1 1 1 1 1 1 1 MR cr1.15.2.2 Building and Infrastructure Reuse, Maintain 75% of Existing Walls, Floors, and Roof or Infrastructure 1 1 1 1 1 1 1 1 1 MR cr1.25.2.3 Building and Infrastructure Reuse, Maintain 95% of Existing Walls, Floors, and Roof or Infrastructure 1 1 1 1 1 1 1 1 1 MR cr1.35.2.4 Building and Infrastructure Reuse, Maintain 50% of Interior Non-Structural Elements 1 1 1 1 1 MR cr1.45.3.1 Construction Waste Management, Divert 50% from Landfill 1 1 1 1 1 1 1 1 1 MR cr2.15.3.2 Construction Waste Management, Divert 75% from Landfill 1 1 1 1 1 1 1 1 1 MR cr2.25.3.3 Construction Waste Management, Divert 90% from Landfill 1 1 1 1 1 1 1 1 15.4.1 Balanced Earthwork, 75% Managed On-Airport 1 1 1 1 1 1 1 1 15.4.2 Balanced Earthwork, 95% Managed On-Airport 1 1 1 1 1 1 1 1 1
5.5 Aggregate Reuse, 10% by Weight 1 1 1 1 1 1 1 1 15.6.1 Material Reuse, 5% 1 1 1 1 1 1 1 1 1 MR cr3.15.6.2 Material Reuse, 10% 1 1 1 1 1 1 1 1 1 MR cr3.25.7.1 Recycled Content, 10% 1 1 1 1 1 1 1 1 1 MR cr4.15.7.2 Recycled Content, 20% 1 1 1 1 1 1 1 1 1 MR cr4.25.8.1 Local/Regional Materials, 10% 1 1 1 1 1 1 1 1 1 MR cr5.15.8.2 Local/Regional Materials, 20% 1 1 1 1 1 1 1 1 1 MR cr5.25.8.3 Local/Regional Materials, 50% (within 250 miles) 1 1 1 1 1 1 1 1 1
5.9 Rapidly Renewable Materials 1 1 1 1 1 MR cr65.10 Certified Wood 1 1 1 1 1 MR cr75.11 Furniture and Equipment 1 1 1 1 1 †5.12 Equipment Salvage and Reuse 1 1 1 1 1 1 1 1 16.0 Indoor Environmental Quality 16 0 0 16 7 0 0 16 7 EQ6.1 Prerequisite 1 Minimum Indoor Air Quality (IAQ) Performance Required Required Required Required Required EQ pr16.2 Prerequisite 2 Environmental Tobacco Smoke (ETS) Control Required Required Required Required Required EQ pr26.3 Outdoor Air Delivery Monitoring 1 1 1 EQ cr16.4 Increased Ventilation 1 1 1 EQ cr2
6.5.1 Construction IAQ Management Plan: During Construction 1 1 1 1 1 EQ cr3.16.5.2 Construction IAQ Management Plan: Before Occupancy 1 1 1 1 1 EQ cr3.26.6.1 Low-Emitting Materials: Adhesives and Sealants 1 1 1 1 1 EQ cr4.16.6.2 Low-Emitting Materials: Paints and Coatings 1 1 1 1 1 EQ cr4.26.6.3 Low-Emitting Materials: Flooring Systems 1 1 1 1 1 EQ cr4.36.6.4 Low-Emitting Materials: Composite Wood and Agrifiber Products 1 1 1 1 1 EQ cr4.4
6.7 Indoor Chemical and Pollutant Source Control 1 1 1 1 1 EQ cr56.8.1 Controllability of Systems: Lighting 1 1 1 EQ cr6.16.8.2 Controllability of Systems: Thermal Comfort 1 1 1 EQ cr6.26.9.1 Thermal Comfort: Design 1 1 1 EQ cr7.16.9.2 Thermal Comfort: Verification 1 1 1 EQ cr7.2
6.10.1 Daylight and Views, Daylight 75% of Spaces 1 1 1 EQ cr8.16.10.2 Daylight and Views, Views for 90% of Spaces 1 1 1 EQ cr8.2
6.11 Noise Transmission 1 1 17.0 Construction Practices 7 0 0 0 0 7 7 7 77.1 Prerequisite 1 Clean Fuel Construction Vehicles Required Required Required Required Required Required Required Required Required7.2 Prerequisite 2 Construction Equipment Maintenance Required Required Required Required Required Required Required Required Required7.3 Construction Practice Reference: 2.1 - Construction Activity Pollution Prevention See 2.1 NA NA NA NA 0 0 0 07.4 Construction Practice Reference: 4.1 - Systems Commissioning See 4.1 NA NA 0 07.5 Construction Practice Reference: 5.3 - Construction Waste Management See 5.3 NA NA NA NA 0 0 0 07.6 Construction Practice Reference: 6.5 - Construction IAQ Management Plan See 6.5 NA NA 0 07.7 Low-Emission Construction Vehicles 1 NA NA NA NA 1 1 1 1
7.8.1 Alternative Transportation During Construction: Staging Area 1 NA NA NA NA 1 1 1 17.8.2 Alternative Transportation During Construction: Low-Emitting & Fuel-Efficient Vehicles, 10% 1 NA NA NA NA 1 1 1 17.8.3 Alternative Transportation During Construction: Low-Emitting & Fuel-Efficient Vehicles, 50% 1 NA NA NA NA 1 1 1 1
7.9 Construction Material Conveyence 1 NA NA NA NA 1 1 1 17.10 Construction Noise and Acoustical Quality 1 NA NA NA NA 1 1 1 17.11 Sustainable Temporary Construction Materials 1 NA NA NA NA 1 1 1 18.0 Innovation in Design & Construction 8 7 7 7 7 7 7 8 7 ID8.1 Innovation in Design & Construction 1 1 1 1 1 1 1 1 1 ID cr1.18.2 Innovation in Design & Construction 1 1 1 1 1 1 1 1 1 ID cr1.28.3 Innovation in Design & Construction 1 1 1 1 1 1 1 1 1 ID cr1.3
8.4.1 Menu Item 1 1 1 1 1 1 1 1 1 18.4.2 Menu Item 2 1 1 1 1 1 1 1 1 18.4.3 Menu Item 3 1 1 1 1 1 1 1 1 1
8.5 LEED Accredited Professional 1 1 1 1 1 1 1 1 1 ID cr28.6 LEED Certified Project 1 NA 19.0 Regional Priority 4 0 1 4 1 0 1 4 1 RP
Menu Items (any of the following up to 3 total): Construction Equipment Retrofit, Photovoltaics, Geothermal Heating/Cooling, Wind Power, Rainwater Harvesting, Permeable Pavement, Trombe or Solar Walls, Green Walls, Warm Mix Asphalt, or Alternative Water Heating
LEED 2009 Reference
Design Checklist Construction Checklist
Design & Construction Sustainable Airport Manual Credits
DC-A-2
______________
SUSTAINABLE AIRPORT MANUAL GREEN AIRPLANE RATING SYSTEM_______________
Civil-Airside
Civil-Landside
Occupied Buildings
Unoccupied Buildings
Civil-Airside
Civil-Landside
Occupied Buildings
Unoccupied Buildings
LEED 2009 Reference
Design Checklist Construction Checklist
Design & Construction Sustainable Airport Manual Credits
9.1 Regional Priority: SAM Credit 2.4.1 – Alternative Transportation, Public Transportation Access 1 1 1 RP cr1.19.2 Regional Priority: SAM Credit 2.4.3 – Alternative Transportation, Low-Emitting Vehicles 1 1 1 RP cr1.29.3 Regional Priority: SAM Credit 2.4.4 – Alternative Transportation, Parking Capacity 1 1 1 RP cr1.39.4 Regional Priority: SAM Credit 2.5.2 – Stormwater Design, Quality Control 1 1 1 1 1 1 1 RP cr1.4
TOTAL POINTS POSSIBLE 120 54 57 119 95 61 64 127 102
† Reference LEED-EB MR2.1 and MR2.2 (Jan 2008 version). SAM Green Airplane Rating* CA CL OB UB CA CL OB UBLEED Points
(LEED Rating)
* Minimum points needed to achieve rating. No. of Prerequisites 8 8 13 12 8 8 13 12
2 2 2 2 2 2 2 2
20 21 43 35 22 23 46 3740-49 (Certified)
25 26 54 43 28 29 58 4650-59(Silver)
29 31 65 52 33 35 69 5660-79
(Gold)
39 41 87 69 44 47 92 7480-110(Platinum)
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
DC-A-3
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
APPENDIX DC-B
DESIGN & CONSTRUCTION CHECKLISTS
Instructions for completing SAM Checklist:- see also the Sustainable Airport Manual (SAM) for more information
NOTE: Only blue text and unshaded cells may be changed by the user.
Instructions Example1 Select appropriate checklist from the worksheet tabs below: Design Checklist or Construction Checklist If project is in the design stages, the designer should select the Design Checklist tab and
proceed to complete the information as described below.
2 Fill out title information in blue at the top (WBS no., project name, consultant, date, milestone) and select "Project Category" from the drop-down menu. The "Goal by Project Category" and "Applicable Points by Project Category" columns will automatically be filled in based on the Project Category. The "Total Applicable Points" for the project will automatically be calculated at the end of the checklist (e.g. for the Construction Checklist: Civil-Airside = 63, Civil-Landside = 66, Occupied Building = 129, Unoccupied Building = 104).
WBS No. OH6126.100.40.005North Air Traffic Control TowerWalsh Construction Co.5/12/2009Final ConstructionOccupied Building (OB)
3 For those credits that were achieved, indicate this by putting the appropriate point in the “Points Obtained” column. Note that for “Prerequisite” credits, no point is achieved as these are the minimum performance requirements for sustainability under the SAM. For prerequisites, insert a "Yes" for those that are applicable (some prerequisites do not apply for civil projects).
If the credit requirements for SAM Credit 5.10 – Certified Wood are met, then insert a “1” under the “Points Obtained” column.
4 Indicate where each credit's scope of work is shown/described/documented in the Construction Documents (CDs) under the appropriate column by inserting the drawing and/or specification number that refers to the credit, e.g. reference erosion control drawings and specifications for SAM Credit 2.1 Construction Activity Pollution Prevention; reference the construction waste management specification for SAM Credit 5.3 Construction Waste Management.
Under Reference Drawing/Sheet No. insert e.g. "CG-104 to CG-107, CD-233"AND/ORUnder Reference Specification Section insert e.g. "01524".
5 In the "Narrative" column, describe the scope of work for the project relevant to this credit by replacing the ”Fill in scope of work” phrase with the appropriate description. ORDelete the ”Fill in scope of work” phrase or indicate with “NA” those credits which are not project goals as indicated in the "Goal by Project Category" column. This would include such things as building related credits that are not applicable to a civil/infrastructure project, for example.ORFor credits that were indicated as goals under “Goal by Project Category” but were not achieved, leave the "Points Obtained" column blank and describe the reasons for this in the "Narrative". Include any additional information such as estimated quantities and/or locations.
NOTE: Only blue text and unshaded cells may be changed by the user.
Under SAM Credit 5.3 Construction Waste Management, fill in scope of work: "A total of 89% of C&D waste totaling 2,800 tons was diverted from landfills. This included 2,150 tons of concrete which was sent to the South Airfield concrete recycling plant, 400 tons of reclaimed asphalt which was stockpiled at the South Airfield recycling area near Guard Post #3, 220 tons of scrap metal, fencing, and guard rails that was recycled by an off-site scrap hauler, and misc. construction waste. See attached calculations [include required forms ]."ORFor a Civil-Airside (CA) project, under SAM Credit 6.3 Outdoor Air Delivery Monitoring, delete "Fill in scope of work" and insert "NA" (there is no outdoor air delivery monitoring on a CA project).ORUnder SAM Credit 5.7 Recycled Content, fill in scope of work: "Due to the specialized nature of the materials and due to FAA specification restrictions, the overall recycled content for the construction materials (Div. 2-10) was only 4.5% of the total cost of the materials (minus labor and equipment). Therefore, the point was not achieved. See attached calculations."
6 For some credits, supporting documentation, typically some form of calculations, will also need to be included, if applicable. Credits that require supporting documentation are indicated in the description with ”Fill in scope of work and include supporting documentation”. See SAM for supporting documentation templates. In some cases, the SRP may require additional supporting documentation for the other credits during review process for clarification.
NOTE: Points cannot be awarded for those credits that require supporting documentation without the appropriate documentation.
See first and third example under Step 3 above. Credit SAM Credit 5.3 Construction Waste Management requires a C&D Debris Compliance Form per Specification 01524. SAM Credit 5.7 Recycled Content requires a Recycled Content Calculation Template per Specification 01356.
7 Use US Green Building Council LEED-NC 2009™ guidelines to determine calculations, requirements, or examples in the cases where the SAM does not specify how points may be achieved or supported.
For SAM Credit 4.7 Enhanced Refrigerant Management, the default values for the calculations and some examples are given in the LEED-NC 2009™ Reference Guide under Energy & Atmosphere, Credit 4 (EAc4).
8 SUBMIT THE ENTIRE CHECKLIST, INCLUDING SUPPORTING DOCUMENTATION, WITH EVERY MILESTONE DESIGN REVIEW BY CDA AND AT SUBSTANTIAL CONSTRUCTION COMPLETION.
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
Template Sustainable Airport Manual (SAM) Design Checklist11/5/12
WBS No.Project NameConsultant NameRevised: Revision DateMilestone: XX% SubmittalProject Category: [choose from drop-down menu]
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYCREDIT DESCRIPTION POINTS
REFERENCE DRAWING/SHEET NO.
REFERENCE SPECIFICATION
SECTIONNARRATIVE
1.0 Administrative Procedures 8
AP.1
Prerequisite 1 - Green Meetings Guide meeting hosts, planners and attendees toward more eco-friendly meetings and incorporate environmental considerations into planning and conducting meetings in order to minimize the negative impact on the environment.
Prereq Fill in scope of work
AP.2Prerequisite 2 - Document Reduction and Recycling Initiative (DRRI) Reduce the volume paper used and facilitate the recycling of documents.
Prereq Fill in scope of work
AP.3
Corporate Sustainability Policy Keeping with the spirit and intent of this Manual, it is strongly encouraged that companies working in support of CDA on any project establish and adopt their own corporate policy on sustainable practices.
1 Fill in scope of work
AP.4Green Procurement Policy Reduce the environmental impact of products and services by developing a Green Purchasing Program.
4 Fill in scope of work
AP.5Recycled Content PaperReduce the need for virgin materials, energy, and waste associated with the production of paper by promoting the use of recycled content paper.
3 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
18
2.1Prerequisite 1- Construction Activity Pollution PreventionReduce pollution from construction activities by controlling soil erosion, waterway sedimentation and airborne dust generation.
Prereq Fill in scope of work
2.2 Prerequisite 2 - Adopt CDA Best Management PracticesMinimize environmental impacts of facility operations.
Prereq Fill in scope of work
2.3Brownfield RedevelopmentRehabilitate damaged sites where development is complicated by environmental contamination, reducing pressure on undeveloped land.
1 Fill in scope of work
2.4.1 Alternative Transportation: Public Transportation AccessReduce pollution and land development impacts from automobile use.
6 Fill in scope of work
2.4.2 Alternative Transportation: Bicycle Access, Storage and Changing Rooms Reduce pollution and land development impacts from automobile use.
1 Fill in scope of work
2.4.3Alternative Transportation: Low-Emitting and Fuel-Efficient Vehicles (Non-Construction) Reduce pollution and land development impacts from automobile use.
3 Fill in scope of work
2.4.4Alternative Transportation: Parking Capacity Reduce pollution and land development impacts from single occupancy vehicle use for employees.
2 Fill in scope of work
2.5.1
Stormwater Management: Quantity Control Limit disruption of natural water hydrology by reducing impervious cover, increasing on-site infiltration, reducing or eliminating pollution from stormwater runoff, and eliminating contaminants.
1 Fill in scope of work
2.5.2Stormwater Management: Quality ControlLimit disruption and pollution of natural water flows by managing stormwater runoff.
1 Fill in scope of work
2.6.1
Landscape and Exterior Design to Reduce Heat Islands: Non-RoofReduce heat islands (thermal gradient differences between developed and undeveloped areas) to minimize impact on microclimate and human and wildlife habitat.
1 Fill in scope of work
2.6.2
Landscape and Exterior Design to Reduce Heat Islands: Roof Reduce heat islands (thermal gradient differences between developed and undeveloped areas) to minimize impact on microclimate and human and wildlife habitat.
1 Fill in scope of work
2.7
Light Pollution Reduction Minimize light trespass from the building and site, reduce sky-glow to increase night sky access, improve nighttime visibility through glare reduction, and reduce development impact on nocturnal environments.
1 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
3.0 Water Efficiency 10
3.1Prerequisite 1 - Water Use Reduction, 20% Reduction Increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.
Prereq Fill in scope of work
3.2Water Use Reduction, 30%-40% ReductionFurther increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.
4 Fill in scope of work
3.3.1Water Efficient Landscaping, Reduce by 50% Limit or eliminate the use of potable water, or other natural surface or subsurface water resources available on or near the project site, for landscape irrigation.
2 Fill in scope of work
3.3.2Water Efficient Landscaping, No Potable Water Use or No irrigation Eliminate the use of potable water, or other natural surface or subsurface water resources available on or near the project site, for landscape irrigation.
2 Fill in scope of work
3.4Innovative Wastewater Technologies Reduce wastewater generation and potable water demand while increasing the local aquifer recharge.
2 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
4.0 Energy & Atmosphere 35
4.1
Prerequisite 1 - Fundamental Building Systems CommissioningFor occupied buildings, verify that the project’s energy related systems are installed, calibrated and perform according to the owner’s project requirements, basis of design, and construction documents.
Prereq Fill in scope of work
4.2
Prerequisite 2 - Minimum Energy PerformanceEstablish the minimum level of energy efficiency for the proposed building and civil infrastructure systems to reduce environmental and economic impacts associated with excessive energy use.
Prereq Fill in scope of work
4.3 Prerequisite 3 - Fundamental Refrigerant ManagementReduce stratospheric ozone depletion.
Prereq Fill in scope of work
4.4
Optimize Energy PerformanceAchieve increasing levels of energy performance beyond the prerequisite standard to reduce environmental and economic impacts associated with excessive energy use.
19 Fill in scope of work
4.5
On-Site Renewable EnergyEncourage and recognize increasing levels of on-site renewable energy self-supply in order to reduce environmental and economic impacts associated with fossil fuel energy use
7 Fill in scope of work
4.6Enhanced CommissioningBegin the commissioning process early in the design process and execute additional activities after systems performance verification is completed.
2 Fill in scope of work
4.7Enhanced Refrigerant Management Reduce ozone depletion and support early compliance with the Montreal Protocol while minimizing direct contributions to global warming..
2 Fill in scope of work
4.8 Measurement and VerificationProvide for the ongoing accountability of building energy consumption over time.
3 Fill in scope of work
4.9Green PowerEncourage the development and use of grid-source, renewable energy technologies on a net zero pollution basis.
2 Fill in scope of work
2.0 Sustainable Site Management
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5. 2012© 2012 City of Chicago
08 - CDA-SAM Appendix DC-A and DC-B v3.0 - FINAL.xls DC-B-4 11/2/2012
Template Sustainable Airport Manual (SAM) Design Checklist11/5/12
WBS No.Project NameConsultant NameRevised: Revision DateMilestone: XX% SubmittalProject Category: [choose from drop-down menu]
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5. 2012© 2012 City of Chicago
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
5.0 Materials & Resources 21
5.1
Prerequisite 1 - Storage and Collection of RecyclablesFacilitate the reduction of waste generated by building occupants and for civil/infrastructure projects within the airport environment that is hauled to and disposed of in landfills.
Prereq Fill in scope of work
5.2.1to
5.2.3
Building and Infrastructure ReuseExtend the life cycle of existing building stock and infrastructure, conserve resources, retain cultural resources, reduce waste and reduce environmental impacts of new buildings and infrastructure as they relate to materials manufacturing and transport.
3 Fill in scope of work
5.2.4
Building Reuse, Maintain 50% of Interior Non-Structural ElementsExtend the lifecycle of existing building stock, conserve resources, retain cultural resources, reduce waste and reduce environmental impacts of new buildings as they relate to materials manufacturing and transport.
1 Fill in scope of work
5.3
Construction Waste ManagementDivert construction and demolition debris from disposal in landfills and incineration facilities. Redirect recyclable recovered resources back to the manufacturing process and reusable materials to appropriate sites.
3 01524 Fill in scope of work
5.4Balanced EarthworkDivert soils from landfills, reduce transportation of soil to off-site locations, and maintain or make soil available for reuse on other on-airport projects.
2 Fill in scope of work
5.5 Aggregate ReusePromote the reuse of aggregate from on-airport and off-airport property sources.
1 Fill in scope of work
5.6
Material ReuseReuse building materials and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
2 Fill in scope of work
5.7
Recycled ContentIncrease demand for building products that incorporate recycled content materials, thereby reducing impacts resulting from extraction and processing of virgin materials.
2 01356 Fill in scope of work
5.8
Local/ Regional MaterialsIncrease demand for building and all other materials and products that are extracted, harvested or recovered, as well as manufactured within the region, thereby supporting the use of indigenous resources and reducing the environmental impacts resulting from transportation.
3 01355 Fill in scope of work
5.9Rapidly Renewable MaterialsReduce the use and depletion of finite raw materials and long-cycle renewable materials by replacing them with rapidly renewable materials.
1 Fill in scope of work
5.10 Certified WoodEncourage environmentally responsible forest management .
1 Fill in scope of work
5.11Furniture and EquipmentReduce environmental and indoor air quality impacts of the furniture and equipment acquired for use in a building.
1 Fill in scope of work
5.12
Equipment Salvage and ReusePromote the reuse of equipment and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
1 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
6.0 Indoor Environmental Quality 16
6.1
Prerequisite 1 - Minimum Indoor Air Quality (IAQ) PerformanceEstablish minimum indoor air quality (IAQ) performance to enhance indoor air quality in buildings, thus contributing to the comfort and well-being of the occupants.
Prereq Fill in scope of work
6.2Prerequisite 2 - Environmental Tobacco Smoke (ETS) ControlPrevent or minimize exposure of building occupants, indoor surfaces, and ventilation air distribution systems to Environmental Tobacco Smoke (ETS).
Prereq Fill in scope of work
6.3Outdoor Air Delivery MonitoringProvide capacity for ventilation system monitoring to help sustain occupant comfort and wellbeing.
1 Fill in scope of work
6.4Increased Ventilation Provide additional outdoor air ventilation to improve indoor air quality for improved occupant comfort, well-being and productivity.
1 Fill in scope of work
6.5.1
Construction IAQ Management Plan: During ConstructionReduce indoor air quality problems resulting from the construction/renovation process in order to help sustain the comfort and well-being of construction workers and building occupants.
1 Fill in scope of work
6.5.2
Construction IAQ Management Plan: Before OccupancyReduce indoor air quality problems resulting from the construction/renovation process in order to help sustain the comfort and well-being of construction workers and building occupants.
1 Fill in scope of work
6.6.1Low-Emitting Materials: Adhesives and SealantsReduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
1 Fill in scope of work
6.6.2Low-Emitting Materials: Paints and CoatingsReduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
1 Fill in scope of work
6.6.3Low-Emitting Materials: Flooring SystemsReduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
1 Fill in scope of work
6.6.4Low-Emitting Materials: Composite Wood & Agrifiber ProductsReduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
1 Fill in scope of work
6.7Indoor Chemical and Pollutant Source ControlMinimize exposure of building occupants to potentially hazardous particulates and chemical pollutants.
1 Fill in scope of work
6.8.1
Controllability of Systems: LightingProvide a high level of lighting system control by individual occupants or by specific groups in multi-occupant spaces (e.g., classrooms and conference areas) to promote the productivity, comfort and well-being.
1 Fill in scope of work
6.8.2
Controllability of Systems: Thermal ComfortProvide a high level of thermal comfort system control by individual occupants or by specific groups in multi-occupant spaces (i.e., classrooms or conference areas) to promote the productivity, comfort and well-being of building occupants.
1 Fill in scope of work
6.9.1Thermal Comfort: DesignProvide a comfortable thermal environment that supports the productivity and well-being of building occupants.
1 Fill in scope of work
6.9.2 Thermal Comfort: VerificationProvide for the assessment of building thermal comfort over time.
1 Fill in scope of work
6.10.1
Daylight and Views: Daylight 75% of SpacesProvide for the building occupants a connection between indoor spaces and the outdoors through the introduction of daylight and views into the regularly occupied areas of the building.
1 Fill in scope of work
6.10.2
Daylight and Views: Views for 90% of Spaces Provide for the building occupants a connection between indoor spaces and the outdoors through the introduction of daylight and views into the regularly occupied areas of the building.
1 Fill in scope of work
6.11Noise TransmissionLimit noise levels in noise-sensitive, occupied spaces such as passenger terminals and offices to increase employee productivity and passenger comfort.
1 Fill in scope of work
08 - CDA-SAM Appendix DC-A and DC-B v3.0 - FINAL.xls DC-B-5 11/2/2012
Template Sustainable Airport Manual (SAM) Design Checklist11/5/12
WBS No.Project NameConsultant NameRevised: Revision DateMilestone: XX% SubmittalProject Category: [choose from drop-down menu]
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5. 2012© 2012 City of Chicago
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
7.0 Construction Practices 7
7.1 Prerequisite 1 - Clean Fuel Construction VehiclesMinimize air quality impacts during construction.
Prereq 01111 Fill in scope of work
7.2Prerequisite 2 - Construction Equipment MaintenanceMinimize the environmental impact of construction equipment maintenance activities.
Prereq Fill in scope of work
See2.1 See2.1 7.3 Reference 2.1 - Construction Activity Pollution Prevention See 2.1 See 2.1 See 2.1 See 2.1
See 4.1 See 4.1 7.4 Reference 4.1 - Systems Commissioning See 4.1 See 4.1 See 4.1 See 4.1
See 5.3 See 5.3 7.5 Reference 5.3 - Construction Waste Management See 5.3 See 5.3 See 5.3 See 5.3
See 6.5 See 6.5 7.6 Reference 6.5 - Construction IAQ Management Plan See 6.5 See 6.5 See 6.5 See 6.5
7.7 Low-Emission Construction Vehicles Minimize air quality impacts during construction.
1 Fill in scope of work
7.8.1Alternative Transportation During Construction, Staging Area Reduce emissions due to construction vehicles by minimizing the amount of traffic to the construction site.
1 Fill in scope of work
7.8.2
Alternative Transportation During Construction: Low-Emitting and Fuel- Efficient Vehicles, 10% Reduce emissions from on-road construction vehicles (e.g., foreman pickups or shuttle buses).
1 Fill in scope of work
7.8.3Alternative Transportation During Construction: Low-Emitting and Fuel-Efficient Vehicles, 50% Reduce emissions from on-road construction vehicles.
1 Fill in scope of work
7.9Construction Materials Conveying Reduce emissions from construction activities by minimizing the amount of on-road and off-road vehicle traffic traveling to/from the construction site.
1 Fill in scope of work
7.10Construction Noise and Acoustical QualityImprove the exterior noise quality during construction affecting residential areas or other noise sensitive areas.
1 Fill in scope of work
7.11
Sustainable Temporary Construction MaterialsReduce the use and depletion of finite raw materials and long-cycle renewable materials by replacing them with high recycled content, rapidly renewable materials and FSC certified wood products for temporary uses during construction.
1 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
8.0 Innovation in Design & Construction 8
8.1
Innovation in Design & Construction Provide design teams and projects the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
1Fill in scope of work and include supporting
documentation
8.2
Innovation in Design & Construction Provide design teams and projects the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
1 Fill in scope of work and include supporting
documentation
8.3
Innovation in Design & Construction Provide design teams and projects the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
1 Fill in scope of work and include supporting
documentation
8.4
Menu Items (Construction Equipment Retrofit, Photovoltaics, Geothermal Heating/Cooling, Wind Power, Rainwater Harvesting, Permeable Pavement, Trombe or Solar Walls, Green Walls, Warm-Mix Asphalt or Alternative Water Heating)Promote specific technologies and additional strategies considered to be important to the sustainability of the airport environment.
3 Fill in scope of work
8.5LEED Accredited ProfessionalSupport and encourage the design integration required by LEED to streamline the application and certification process.
1 Provide name of LEED AP Design Professional
8.6
LEED Certified ProjectPromote the incorporation of environmentally sustainable design in building and infrastructure improvements by registering and certifying a project through the LEED certification process and rating system.
1 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
9.0 Regional Priority 4
9.1 Regional Priority 2.4.1 – Alternative Transportation: Public Transportation Access
1 See 2.4.1 See 2.4.2 See 2.4.2
9.2 Regional Priority 2.4.3 – Alternative Transportation: Low-Emitting Vehicles
1 See 2.4.3 See 2.4.3 See 2.4.3
9.3 Regional Priority 2.4.4 – Alternative Transportation: Parking Capacity
1 See 2.4.4 See 2.4.4 See 2.4.4
9.4 Regional Priority 2.5.2 – Stormwater Design: Treatment
1 See 2.5.2 See 2.5.2 See 2.5.2
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
TOTAL POINTS OBTAINED
TOTAL APPLICABLE
POINTS
TOTAL OMP GOALS
TOTAL POSSIBLE
POINTS
127
08 - CDA-SAM Appendix DC-A and DC-B v3.0 - FINAL.xls DC-B-6 11/2/2012
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
Template Sustainable Airport Manual (SAM) Construction Checklist11/5/12
WBS No.Project NameConsultant NameRevised: Revision DateMilestone: XX% SubmittalProject Category: [choose from drop-down menu]
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYCREDIT DESCRIPTION POINTS
REFERENCE DRAWING/SHEET NO.
REFERENCE SPECIFICATION
SECTIONNARRATIVE
1.0 Administrative Procedures 8
AP.1
Prerequisite 1 - Green Meetings Guide meeting hosts, planners and attendees toward more eco-friendly meetings and incorporate environmental considerations into planning and conducting meetings in order to minimize the negative impact on the environment.
Prereq Fill in scope of work
AP.2Prerequisite 2 - Document Reduction and Recycling Initiative (DRRI) Reduce the volume paper used and facilitate the recycling of documents.
Prereq Fill in scope of work
AP.3
Corporate Sustainability Policy Keeping with the spirit and intent of this Manual, it is strongly encouraged that companies working in support of CDA on any project establish and adopt their own corporate policy on sustainable practices.
1 Fill in scope of work
AP.4Green Procurement Policy Reduce the environmental impact of products and services by developing a Green Purchasing Program.
4 Fill in scope of work
AP.5Recycled Content PaperReduce the need for virgin materials, energy, and waste associated with the production of paper by promoting the use of recycled content paper.
3 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
18
2.1Prerequisite 1- Construction Activity Pollution PreventionReduce pollution from construction activities by controlling soil erosion, waterway sedimentation and airborne dust generation.
Prereq Fill in scope of work
2.2 Prerequisite 2 - Adopt DOA Best Management PracticesMinimize environmental impacts of facility operations.
Prereq Fill in scope of work
2.3
Brownfield RedevelopmentDevelop on a site documented as contaminated by ASTM E 1903-97 Phase II Environmental Site Assessment OR classified as a brownfield by a local state and federal government agency and therefore reducing pressure on undeveloped land.
1 Fill in scope of work
2.4.1Alternative Transportation: Public Transportation AccessReduce pollution and land development impacts from automobile use by providing access to public transportation.
6 Fill in scope of work
2.4.2Alternative Transportation: Bicycle Access, Storage & Changing Rooms Reduce pollution and land development impacts from automobile use. Provide secure bicycle storage with convenient changing/shower facilities.
1 Fill in scope of work
2.4.3
Alternative Transportation: Low-Emitting and Fuel-Efficient Vehicles (Non-Construction) Reduce pollution and land development impacts from automobile use by encouraging the use and providing low-emission and Fuel-Efficient vehicles.
3 Fill in scope of work
2.4.4Alternative Transportation: Parking Capacity Reduce pollution and land development impacts from automobile use by limiting the amount of parking in order to encourage alternative transportation.
2 Fill in scope of work
2.5.1
Stormwater Management: Quantity Control Limit disruption and pollution of natural water flows by managing stormwater runoff. Encourage groundwater infiltration. Use detention to reduce storm water flow, velocities and sedimentation loads into the receiving streams.
1 Fill in scope of work
2.5.2Stormwater Management: Quality ControlLimit disruption of natural water flows by eliminating stormwater runoff, increasing onsite infiltration and eliminating contaminants.
1 Fill in scope of work
2.6.1
Landscape & Exterior Design to Reduce Heat Islands: Non-RoofReduce Heat Islands (thermal gradient differences between developed and undeveloped areas) to minimize impact on microclimate and human and wildlife habitat.
1 Fill in scope of work
2.6.2
Landscape & Exterior Design to Reduce Heat Islands: Roof Reduce Heat Islands (thermal gradient differences between developed and undeveloped areas) to minimize impact on microclimate and human and wildlife habitat.
1 Fill in scope of work
2.7Light Pollution Reduction Eliminate light trespass from the building and site, improve night sky access and reduce development impact on nocturnal environments.
1 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
3.0 Water Efficiency 10
3.1 Prerequisite 1 - Water Use Reduction, 20% Reduction Increase potable water efficiency.
Prereq Fill in scope of work
3.2Water Use ReductionMaximize water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.
4 Fill in scope of work
3.3.1Water Efficient Landscaping, Reduce by 50% Limit or eliminate the use of potable water or natural surface or subsurface water resources for landscape irrigation.
2 Fill in scope of work
3.3.2 Water Efficient Landscaping, No Potable Water Use or No irrigation Eliminate the use of potable water for landscape irrigation.
2 Fill in scope of work
3.4Innovative Wastewater Technologies Reduce generation of wastewater and potable water demand, while increasing the local aquifer recharge.
2 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
4.0 Energy & Atmosphere 35
4.1Prerequisite 1 - Fundamental Building Systems CommissioningVerify and ensure that fundamental building elements and systems are designed, installed and calibrated to operate as intended.
Prereq Fill in scope of work
4.2Prerequisite 2 - Minimum Energy PerformanceEstablish the minimum level of energy efficiency for the base building and systems.
Prereq Fill in scope of work
4.3 Prerequisite 3 - Fundamental Refrigerant ManagementReduce stratospheric ozone depletion
Prereq Fill in scope of work
4.4Optimize Energy PerformanceAchieve increasing levels of energy performance above the prerequisite standard to reduce environmental impacts associated with excessive energy use.
19 Fill in scope of work
4.5
On-Site Renewable EnergyEncourage and recognize on-site renewable energy self-supply in order to reduce atmospheric pollutants, operations costs, and the environmental impacts associated with fossil fuel energy use.
7 Fill in scope of work
4.6Enhanced CommissioningBegin commissioning process early during the design process and execute additional activities after system performance verification is complete.
2 Fill in scope of work
4.7 Enhanced Refrigerant Management Reduce ozone depletion while minimizing direct contributions to global warming.
2 Fill in scope of work
4.8 Measurement and VerificationProvide ongoing accountability of building energy consumption over time.
3 Fill in scope of work
4.9Green PowerEncourage the development and use of grid-source, renewable energy technologies on a net zero pollution basis.
2 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
2.0 Sustainable Site Management
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
08 - CDA-SAM Appendix DC-A and DC-B v3.0 - FINAL.xls DC-B-4 11/2/2012
Template Sustainable Airport Manual (SAM) Construction Checklist11/5/12
WBS No.Project NameConsultant NameRevised: Revision DateMilestone: XX% SubmittalProject Category: [choose from drop-down menu]
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
5.0 Materials & Resources 21
5.1Prerequisite 1 - Storage and Collection of RecyclablesFacilitate the reduction of waste generated by building occupants that is hauled and disposed in landfills.
Prereq Fill in scope of work
5.2.1to
5.2.3
Building Reuse, Maintain Existing Walls, Floors, Roof or InfrastructureExtend the lifecycle of existing building stock, conserve resources, retain cultural resources, reduce waste and reduce environmental impacts of new buildings as they relate to materials manufacturing and transport.
3 Fill in scope of work
5.2.4
Building Reuse, Maintain 50% of Interior Non-Structural ElementsExtend the lifecycle of existing building stock, conserve resources, retain cultural resources, reduce waste and reduce environmental impacts of new buildings as they relate to materials manufacturing and transport.
1 Fill in scope of work
5.3
Construction Waste Management, Divert from LandfillDivert construction, demolition and land clearing debris from landfill disposal. Redirect recyclable recovered resources back to the manufacturing process. Redirect reusable materials to appropriate sites.
3 Fill in scope of work
5.4Balanced EarthworkDivert soils from landfills, reduce transport of soils to off-site locations, and maintain or make soils available for reuse on other on-airport projects.
2 Fill in scope of work
5.5 Aggregate ReusePromote the reuse of aggregate from on-airport and off-airport property sources.
1 Fill in scope of work
5.6
Material ReuseReuse building materials and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
2 Fill in scope of work
5.7
Recycled ContentIncrease demand for building products that incorporate recycled content materials, thereby reducing impacts resulting from extraction and processing of virgin materials.
2 Fill in scope of work
5.8
Local/ Regional MaterialsIncrease demand for building materials and products that are extracted and manufactured within the region, thereby supporting the use of indigenous resources, supporting the local economy, and reducing the environmental impacts resulting from transportation.
3 Fill in scope of work
5.9Rapidly Renewable MaterialsReduce the use and depletion of finite raw materials and long-cycle renewable materials by replacing them with rapidly renewable materials.
1 Fill in scope of work
5.10 Certified WoodEncourage environmentally responsible forest management .
1 Fill in scope of work
5.11Furniture and EquipmentReduce environmental and indoor air quality impacts of the furniture and equipment acquired for use in a building.
1 Fill in scope of work
5.12
Equipment Salvage and ReusePromote the reuse of equipment and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
1 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
6.0 Indoor Environmental Quality 16
6.1
Prerequisite 1 - Minimum Indoor Air Quality (IAQ) PerformanceEstablish minimum indoor air quality (IAQ) performance to prevent the development of indoor air quality problems in buildings, thus contributing to the comfort and well being of the occupants.
Prereq Fill in scope of work
6.2Prerequisite 2 - Environmental Tobacco Smoke (ETS) ControlPrevent exposure of building occupants and systems to Environmental Tobacco Smoke (ETS).
Prereq Fill in scope of work
6.3Outdoor Air Delivery MonitoringProvide capacity for ventilation system monitoring to help sustain long-term occupant comfort and well being.
1 Fill in scope of work
6.4Increased Ventilation Provide additional outdoor air ventilation to improve indoor air quality for improved occupant comfort, well being, and productivity.
1 Fill in scope of work
6.5.1
Construction IAQ Management Plan: During ConstructionPrevent indoor air quality problems resulting from the construction/renovation process in order to help sustain the health, comfort and well-being of construction workers and building occupants.
1 Fill in scope of work
6.5.2
Construction IAQ Management Plan: Before OccupancyPrevent indoor air quality problems resulting from the construction/renovation process in order to help sustain the health, comfort and well-being of construction workers and building occupants.
1 Fill in scope of work
6.6.1
Low-Emitting Materials: Adhesives and SealantsReduce the quantity of indoor air contaminants that are odorous, potentially irritating and/or harmful to the health, comfort and well being of installers and occupants.
1 Fill in scope of work
6.6.2
Low-Emitting Materials: Paints and CoatingsReduce the quantity of indoor air contaminants that are odorous, potentially irritating and/or harmful to the health, comfort and well being of installers and occupants.
1 Fill in scope of work
6.6.3
Low-Emitting Materials: Flooring SystemsReduce the quantity of indoor air contaminants that are odorous, potentially irritating and/or harmful to the health, comfort and well being of installers and occupants.
1 Fill in scope of work
6.6.4
Low-Emitting Materials: Composite Wood & Agrifiber ProductsReduce the quantity of indoor air contaminants that are odorous, potentially irritating and/or harmful to the health, comfort and well being of installers and occupants.
1 Fill in scope of work
6.7Indoor Chemical and Pollutant Source ControlAvoid exposure of building occupants to potentially hazardous particulates and chemicals that adversely impact air quality.
1 Fill in scope of work
6.8.1
Controllability of Systems: LightingProvide a high level of lighting system control by individual occupants or groups in multi-occupant spaces (e.g., classrooms and conference areas) and promote their productivity, comfort and well-being.
1 Fill in scope of work
6.8.2
Controllability of Systems: Thermal ComfortProvide a high level of thermal comfort system control by individual occupants or groups in multi-occupant spaces (e.g., classrooms and conference areas) and promote their productivity, comfort and well-being.
1 Fill in scope of work
6.9.1Thermal Comfort: DesignProvide a thermally comfortable environment and assessment over time that supports the productivity and well being of building occupants.
1 Fill in scope of work
6.9.2Thermal Comfort: VerificationProvide a thermally comfortable environment and assessment over time that supports the productivity and well being of building occupants.
1 Fill in scope of work
6.10
Daylight and Views Provide for the building occupants a connection between indoor spaces and the outdoors through the introduction of daylight and views into the regularly occupied areas.
2 Fill in scope of work
6.11Noise TransmissionLimit noise levels in noise-sensitive, occupied spaces such as terminals and offices to increase employee productivity and passenger comfort.
1 Fill in scope of work
08 - CDA-SAM Appendix DC-A and DC-B v3.0 - FINAL.xls DC-B-5 11/2/2012
Template Sustainable Airport Manual (SAM) Construction Checklist11/5/12
WBS No.Project NameConsultant NameRevised: Revision DateMilestone: XX% SubmittalProject Category: [choose from drop-down menu]
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
7.0 Construction Practices 7
7.1 Prerequisite 1 - Clean Fuel Construction VehiclesMinimize air quality impacts during construction.
Prereq 01111 Fill in scope of work
7.2 Prerequisite 2 - Construction Equipment MaintenanceMinimize the environmental impact of site construction activities.
Prereq Fill in scope of work
See2.1 See2.1 7.3 Reference 2.1 - Construction Activity Pollution Prevention See 2.1 See 2.1 See 2.1 See 2.1
See 4.1 See 4.1 7.4 Reference 4.1 - Fundamental Building Systems Commissioning See 4.1 See 4.1 See 4.1 See 4.1
See 5.3 See 5.3 7.5 Reference 5.3 - Construction Waste Management See 5.3 See 5.3 See 5.3 See 5.3
See 6.5 See 6.5 7.6 Reference 6.5 - Construction IAQ Management Plan See 6.5 See 6.5 See 6.5 See 6.5
7.7 Low Emission Construction Vehicles Minimize air quality impacts during construction.
1 Fill in scope of work
7.8.1Alternative Transportation During Construction: Staging Area Minimize the amount of truck and vehicle traffic onto the construction site and reduce emissions from on-road construction vehicles.
1 Fill in scope of work
7.8.2
Alternative Transportation During Construction: Low-Emitting & Fuel-Efficient Vehicles, 10% Minimize the amount of truck and vehicle traffic onto the construction site and reduce emissions from on-road construction vehicles.
1 Fill in scope of work
7.8.3
Alternative Transportation During Construction: Low-Emitting & Fuel-Efficient Vehicles, 50% Minimize the amount of truck and vehicle traffic onto the construction site and reduce emissions from on-road construction vehicles.
1 Fill in scope of work
7.9 Construction Materials Conveying Minimize the amount of truck and vehicle traffic onto the construction site.
1 Fill in scope of work
7.10Construction Noise and Acoustical QualityImprove exterior noise quality during construction affecting residential areas or other noise sensitive areas.
1 Fill in scope of work
7.11
Sustainable Temporary Construction MaterialsReduce the use and depletion of finite raw materials and long-cycle renewable materials by replacing them with high recycled content, rapidly renewable materials, and FSC certified wood products for temporary construction uses.
1 Fill in scope of work
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
8.0 Innovation in Design & Construction 8
8.1Innovation in Design & Construction Provide opportunity for exceptional performance above the requirements set forth above and/or innovative performance in sustainability not covered in the SAM.
1Fill in scope of work and include supporting
documentation
8.2Innovation in Design & Construction Provide opportunity for exceptional performance above the requirements set forth above and/or innovative performance in sustainability not covered in the SAM.
1 Fill in scope of work and include supporting
documentation
8.3Innovation in Design & Construction Provide opportunity for exceptional performance above the requirements set forth above and/or innovative performance in sustainability not covered in the SAM.
1 Fill in scope of work and include supporting
documentation
8.4Menu Items Provide additional credit for strategies and technologies that the OMP considers to be important to the sustainability of the airport environment.
3 Fill in scope of work
8.5LEED Accredited ProfessionalInclude as part of the design team a LEED AP that is familiar with the various aspects of sustainable design.
1 Provide name of LEED AP Design Professional
8.6 LEED Certified ProjectPursue LEED certification for occupied building projects.
1 Provide copy of LEED project registration and
anticipated level of certification
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
9.0 Regional Priority 4
9.1 Regional Priority2.4.1 – Alternative Transportation: Public Transportation Access
1 See 2.4.1 See 2.4.1 See 2.4.1
9.2 Regional Priority2.4.3 – Alternative Transportation: Low-Emitting Vehicles
1 See 2.4.3 See 2.4.3 See 2.4.3
9.3 Regional Priority2.4.4 – Alternative Transportation: Parking Capacity
1 See 2.4.4 See 2.4.4 See 2.4.4
9.4 Regional Priority2.5.2 – Stormwater Design: Treatment
1 See 2.5.2 See 2.5.2 See 2.5.2
POINTS OBTAINED
POINTS BY PROJECT
CATEGORY
GOAL BY PROJECT
CATEGORYPOINTS
TOTAL POINTS OBTAINED
TOTAL APPLICABLE
POINTS
TOTAL OMP GOALS
TOTAL POSSIBLE
POINTS
127
08 - CDA-SAM Appendix DC-A and DC-B v3.0 - FINAL.xls DC-B-6 11/2/2012
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
…Operations and maintenance is the implementation phase. It’s where the rubber meets the
road. All previous chapters have to be integrated with operations and maintenance to make it work…Operations and maintenance is also
the end product of what all of the other chapters produce…
Paul Manasjan San Diego County Regional Airport Authority
…We have to look at life-cycle costs, return on investment; we have to look at the big picture. Design and construction is a very small percentage of the airport costs; the bulk lies in the operations and continued-use…
James Terada Ghafari
…The SAM is going to need to transform, to be improved, and to grow and develop just like all of us want to do as human beings because we
always want to do better and challenge ourselves. This is just the beginning…
Rosemarie S. Andolino Commissioner
Chicago Department of Aviation
airportsgoinggreen.org
Project Submittal Forms, Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
AuOM-1
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
OPERATIONS & MAINTENANCE TABLE OF CONTENTS
OPERATIONS & MAINTENANCE INTRODUCTION …….…… OM-3 1.0 Sustainable Sites 1.1 Equipment Maintenance …….…… OM-91.2 LEED Certified Project …….…… OM-111.3 Exterior Facilities Management …….…… OM-131.4 Hardscape Grounds Management …….…… OM-151.5 Integrated Pest Management and Wildlife Deterrence …….…… OM-171.6 Erosion Control …….…… OM-191.7 Landscape Management …….…… OM-211.8 Alternative Commuting Transportation for Employees …….…… OM-251.9 Stormwater Management …….…… OM-281.10 Heat Island Reduction …….…… OM-321.11 Light Pollution Reduction …….…… OM-35 2.0 Water Efficiency 2.1 Establish a Water Baseline …….…… OM-372.2 Retroactive Water Efficiency …….…… OM-402.3 Indoor Water Efficiency …….…… OM-422.4 Water Efficient Landscaping …….…… OM-452.5 Rain Harvesting for Non-Irrigation Usage …….…… OM-482.6 2.7
Innovative Wastewater Management Water Efficient Vehicle Washing
…….…… …….……
OM-50 OM-52
3.0 Energy & Atmosphere 3.1 Refrigerant Management …….…… OM-543.2 Utility Meter Data …….…… OM-563.3 Retroactive Energy Optimization …….…… OM-583.4 Optimize Energy Performance …….…… OM-603.5 Existing Building Commissioning …….…… OM-683.6 Performance Measurement …….…… OM-723.7 On-Site and Off-Site Renewable Energy …….…… OM-763.8 Enhanced Refrigerant Management …….…… OM-803.9 Emissions Reduction Reporting …….…… OM-82 4.0 Materials & Resources 4.1 Solid Waste Management …….…… OM-854.2 Local/Regional Materials …….…… OM-91 5.0 Indoor Environment Quality 5.1 Outdoor Air Introduction and Exhaust System …….…… OM-935.2 Environmental Tobacco Smoke (ETS) Control …….…… OM-955.3 High Performance Cleaning …….…… OM-965.4 Indoor Air Quality (IAQ) Best Management Practices …….…… OM-985.5 Occupant Comfort …….…… OM-1065.6 Green Cleaning …….…… OM-110 6.0 Innovation for Operations & Maintenance 6.1 Innovation in Operations …….…… OM-1146.2 Innovation in Operations …….…… OM-114
AuOM-2
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
6.3 Innovation in Operations …….…… OM-1146.4 Innovation in Operations …….…… OM-114 7.0 Education & Training 7.1 Community Education …….…… OM-1167.2 Implement Employee Sustainability Training Program …….…… OM-1187.3 Staff Training …….…… OM-120 8.0 Monitoring & Reporting 8.1 Documenting Sustainable Measures …….…… OM-122 Appendices OM-A Green Airplane Rating System for Operations & Maintenance …….…… OM-A-1OM-B Operations & Maintenance Checklist …….…… OM-B-1
AuOM-3
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
INTRODUCTION
There are almost 20,000 airports in the United States today. The day-to-day operation and maintenance of an airport involves various tasks. Airport operators must handle both routine matters as well as unusual circumstances. Their responsibilities, among many, include:
Keeping records Hiring and training personnel Maintaining pavement Maintaining markings, signs, and lighting Providing snow and ice control Overseeing procedures for operation of vehicles on the airfield Providing obstruction lighting Protecting navigational aids Managing emergency preparedness Overseeing handling of hazardous materials - including jet fuel Vehicle maintenance Facility maintenance, from terminals, to office building, to warehouses, trades buildings,
etc. Conducting airport self-inspections Protecting public safety Ensuring wildlife control Overseeing construction projects
While conducting day-to-day operations and activities, airport operators must comply with regulations protecting the environment. All airport operations must be carried out with consideration for how the environment could be adversely affected. Airport environmental concerns may include many things: noise, land use; social impacts, air quality; endangered and threatened species and wildlife, energy supply and natural resources, light pollution, solid waste impacts, stormwater impacts, or construction impacts.
The Sustainable Airport Manual (SAM) Green Airplane Rating System for Operations & Maintenance (O&M) is designed to certify the sustainability of day-to-day building operations, maintenance procedures, system upgrades, minor space-use changes, and minor facility alterations or additions, and training and educational programs.
APPLICABILITY
SAM Operations & Maintenance (SAM O&M) certification encourages airport operators to implement sustainable practices to reduce the environmental impacts of the day-to-day activities and their buildings functional life cycles. Specifically, the rating system addresses exterior building site maintenance programs, water and energy usage, environmentally preferred products and practices for cleaning and alterations, sustainable purchasing policies, waste management, and ongoing indoor/outdoor environmental quality, as well as training and education of employees, tenants and the general public.
The Sustainable Airport Manual (SAM) Operations & Maintenance chapter is applicable to entities and activities that have no customer/passenger contact and do not require design services.
AuOM-4
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
The three main entities are defined below:
1. Chicago Department of Aviation Divisions
The activities of the following CDA divisions and their subgroups and contractors will be evaluated within this chapter:
Design/Construction (maintenance activities) Environmental and Noise Facilities Safety and Security Ground Transportation (Landside) Operations (Landside/Airside) Parking Real Estate/Properties Terminal Building/Landside Vehicle Services
Contractor activities will be included and evaluated under the CDA division or Tenant based on individual contract. Major renovations (defined as major HVAC renovation, envelope modifications and major interior rehabilitation) will be evaluated under the Design and Construction chapter.
2. Tenants
The following are representative of tenants that can be evaluated within this chapter:
Airlines o Airline non-customer contact o Freight handlers non-customer contact
Flight Service Kitchens Landscaping Parking Services Parking Lots Hangars
Tenant entities and activities that have direct customer/passenger contact and/or require design services will be evaluated under the Concessions & Tenants chapter.
3. User-Defined
This category includes entities with operations that have clearly defined boundaries that may not exactly fit into the two categories above or that may be combinations of the above, or some derivation thereof. It is intended to encompass entities that may have multiple tenants or CDA divisions but operating under a single O&M regime, e.g. a building having operations large enough to require its own administrative, custodial, and/or landscape operations.
AuOM-5
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
OPERATIONS & MAINTENANCE SECTIONS
The achievement of credits is dependent on the sustainable elements included in the following categories:
Applies to OPERATIONS & MAINTENANCE activities:
AP Administrative Procedures 1.0 Sustainable Site Management 2.0 Water Efficiency 3.0 Energy & Atmosphere 4.0 Materials & Resources 5.0 Indoor Environmental Quality 6.0 Innovation for Operations & Maintenance 7.0 Education & Training 8.0 Monitoring & Reporting
Each category contains a specific number of credits, against which each project is evaluated in order to determine that project’s earned points. The number of points earned is then translated into a rating. There are specific weighted point thresholds (i.e. applicable credits), so as not to inadvertently penalize a project for not achieving points that would not be applicable. The list of credits and point thresholds applicable to each project type are summarized in Appendix OM-A – Green Airplane Rating System for Operations & Maintenance.
PROCESS
Within the Manual’s main body, each sustainable credit has five subsections: Intent, Requirements, Submittals, Technology/Strategy, and Case Studies, as described below:
Intent: The primary motivations for any sustainable practice.
Requirements: Specifies institutional, operational, and mechanical elements that satisfy the intent. The prerequisites must be achieved; the credits are optional, but contribute to the overall rating.
Submittals: Required and supporting documentation and/or information required to achieve applicable prerequisites or credits. This documentation may include calculations, data, short narratives, policies, documents or references to specification sections or design drawings indicating how the requirements are being met.
Technology/Strategy: Highlights specific ways of meeting the recommendations within the scope for each specific project. Case studies where available, are presented to help guide the application of sustainable credits to operations and maintenance activities. To aid with consideration of applicable strategies and technologies, they are organized into the following three categories; “Standard Practice,” “Recommended Practice,” and “Best Available Practice.”
o Standard Practice: These are requirements that may be due to standards, specifications, codes, general best management or construction practices. They are
AuOM-6
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
practices already in place, and in many cases SAM prerequisites, which also serve to meet sustainable goals.
o Recommended Practice: These include recommendations that are expected to have insignificant impacts to cost and are therefore, encouraged to be incorporated.
o Best Available Practice: These are strategies and practices that are expected to enhance the environmental efforts of the Chicago Department of Aviation (CDA), but are anticipated to potentially increase costs or effort.
Case Study: Examples of credit intent “in action” at airports and/or other industry facilities.
While not all strategies will be applicable, operations and maintenance teams are highly encouraged to think creatively and to consider the intent of each issue throughout the decision process. In all cases, it is the responsibility of the design and construction teams to evaluate and review with the Chicago Department of Aviation any anticipated cost or schedule impact.
SUBMITTALS
Sustainable Airport Manual (SAM) Checklists
Incorporation of sustainable practices and technologies is tracked using a checklist in order to determine the number of applicable credits described in this Manual. The SAM O&M Checklist is completed by the applicant. The checklist is provided in Appendix OM-B – Operations & Maintenance Checklist.
In order to achieve points, certain requirements need to be met, as outlined in each credit. In some instances, studies and calculations would be appropriate. In other instances, this will be accomplished through product and material data or through referenced standards or specifications.
In addition to review of the checklist, the Sustainable Review Panel (SRP) will review any supporting documentation including calculations, specifications, and contractor’s submittals as needed to support the achievement of the credit(s). See Section titled Implementation and Review Process for detailed information about the SRP.
AuOM-7
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
SAM GREEN AIRPLANE RATING SYSTEM
The SAM Green Airplane Rating System for OM uses a five tier approach to rating operations and maintenance activities. Due to the variety of departments, operations, and entities that can be evaluated in this chapter, the rating system is based on the number of Total Applicable Points for each evaluation. The Total Applicable Points are determined on a case by case basis. A credit is deemed applicable if it is obtainable by the entity being evaluated. “Green Airplane Certification” statuses are used to designate achievement levels. The levels are:
OM GREEN AIRPLANE RATING SYSTEM
No. of Green Airplanes
Points Required to Achieve Rating
Total Prerequisites 7
All Applicable Prerequisites + 6 Points
20% of Total Applicable Points
30% of Total Applicable Points
50% of Total Applicable Points
80% of Total Applicable Points
IMPLEMENTATION AND REVIEW PROCESS
The SAM and its supporting documentation are administered by the Sustainable Review Panel (SRP), which currently consists of representatives of the CDA Management Staff, CDA Design and Construction Staff and Representatives, OMP Project Management Office (PMO), Master Civil Engineer (MCE), and Airport Planners actively involved in CDA projects. The composition of the SRP is intended to be dynamic depending on needs.
The SRP is responsible for the review of project initiatives with respect to sustainability and provides technical support to the Project Manager (PM) of each project in relation to sustainable practices. The SRP is responsible for review of every operation and maintenance project and for the awarding of “Green Airplane Certification” ratings based on the extent of incorporation of sustainable practices as outlined in this Manual and as documented on the submitted SAM Checklist(s). Other responsibilities of the SRP include preparation and review of sustainable design related specifications, technical memoranda, and miscellaneous documents, as necessary. In addition, the SRP is responsible for presentations and training to project team members with respect to the application of this Manual. The primary task of the SRP is to oversee the application of the Manual.
AuOM-8
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
For any and all sustainability-related questions and/or submittals, please use the following email address to submit forms electronically (preferred method):
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
AuOM-9
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.1 Prerequisite 1 – Equipment Maintenance
Required
INTENT
Minimize the environmental impact of construction and maintenance equipment and associated maintenance activities.
REQUIREMENTS
Follow the requirements of the City of Chicago Department of Aviation’s (CDA) Best Management Practices (BMP) Manual.
SUBMITTALS
Include a location in the contract documents where the BMP Manual is required.
TECHNOLOGY/STRATEGY
By requiring the City of Chicago divisions, tenants and their contractors to comply with the CDA BMP Manual, it is anticipated that the impacts due to equipment maintenance activities will be reduced. The BMPs include procedures for vehicle washing, maintenance, fueling, chemical storage, and spill control.
Standard Practice
Follow the preferred practices per the BMPs below:
001 – Equipment Vehicle Washing Restrictions 002 – Equipment Vehicle Fueling Controls 003 – Equipment Vehicle Maintenance Requirements 011 – Above Ground Storage Tank Equipment Requirements/Spills 012 – Mobile Tank Trucks (petroleum) Requirements 013 – Chemical Handling/Storage Requirements 014 – Drum Storage Procedures 015 – Battery Storage Procedures 017 – Truck Loading/Unloading Procedures/Spill Control 018 – Spill Control Kits and Spill Response 019 – Good Housekeeping Procedures/Waste Storage 020 – Storm Drain Protection/Identification
Recommended Practice
None
AuOM-10
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Best Available Practice
None
CASE STUDY
Motor Vehicle Maintenance College of Tropical Agriculture and Human Resources – University of Hawaii at Manoa
Excerpt taken from the University of Hawaii at Manoa’s Motor Vehicle Maintenance Document:
Your motor vehicle can be a source of water pollution even if it is not near the water. Oil spilled on a driveway or parking lot and outdoor spills of antifreeze, brake fluid, and other automotive fluids can be washed away by rain into streams and the ocean. There, they can harm aquatic life and make the water unpleasant and sometimes unsafe to swim or fish in. Washing your vehicle can also cause pollution if the dirty water flows into a storm drain and on to the ocean. However, there are several things that you can do to reduce the risks of water pollution from your vehicles. Proper vehicle maintenance and appropriate disposal of waste oil, antifreeze, and other fluids will greatly reduce water pollution risks. Washing your vehicle can cause water pollution. If you live in an urban area and wash your vehicle on the street, in a driveway, or in a paved parking lot, the dirty, soapy water drains off and flows directly into the storm drain, picking up oil and other pollutants as it goes. A better option is to wash your car in an approved car-washing area of your building where water goes into the sewer system, or to take it to a commercial car wash or spray booth that sends its dirty water into the sewer system.
www.ctahr.hawaii.edu/oc/freepubs/pdf/HH-15.pdf
AuOM-11
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.2 LEED Certified Project
1 point
INTENT
Recognize environmentally sensitive building design and construction by enabling high-performance building operations to be achieved in a more efficient and straightforward manner.
REQUIREMENTS
Show that the project has previously been certified under LEED. This includes all LEED rating systems (e.g., Core and Shell, Building Design and Construction, etc).
SUBMITTALS
Include descriptive narrative and areas for which LEED certification was applicable (keep on file and understand what the LEED certification was based on/measures added; identify maintenance activities and schedule to adequately maintain the LEED measures; train personnel on proper maintenance/operating requirements (e.g., HVAC systems, etc.)).
TECHNOLOGY/STRATEGY
Pursue and earn LEED certification for new buildings, existing buildings, or major renovations.
Standard Practice
None
Recommended Practice
None
Best Available Practice
None
AuOM-12
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDY
Delta Air Lines ‘Terminal A’ Boston Logan International Airport – Boston, Massachusetts
The new Delta Air Lines 'Terminal A' at Logan International Airport in Boston has achieved an environmental milestone as the world's first air terminal to earn LEED certification from the U.S. Green Building Council (USGBC). The facility maximizes sustainable building methods and technologies, overcoming the significant obstacles inherent in bringing green design to airports. To combat the accelerated heat island effect and stormwater runoff issues typically caused by impervious surfaces on runways, parking lots and large roofs areas.
www.sustainablebusiness.com/index.cfm/go/news.feature/id/1358
AuOM-13
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.3 Exterior Facilities Management
1 point
INTENT
Encourage environmentally sensitive building exterior practices that provide a clean, well-maintained and safe building exterior while supporting high-performance building operations based on its original state.
REQUIREMENTS
If any of the following are met, 1 point may be awarded:
Utilize green cleaning and maintenance practices and materials (e.g., glass cleaner, blasting agents, corrosion preventers) that minimize environmental impacts to include, but are not limited to, biobased, low-emitting and recycled content materials.
Use adhesives and sealants on building exterior that meet the South Coast Air Quality Management District (SCAQMD) Rule 1168, where applicable.
AND
Use cleaning products that are noted in Appendix AP-A – Green Product Listing, where applicable. A partial list of products may include, but are not limited to:
Glass cleaners – 49% minimum biobased content Grease remover – 34% minimum biobased content Industrial cleaner – 41% minimum biobased content
AND
Use paints and coatings that meet the limits in Appendix AP-A – Green Product Listing or Green Seal’s Standard GS-11, where applicable. A partial list of products may include, but are not limited to:
Reprocessed latex paint – 20% minimum post-consumer content (light colors)/50 percent minimum post-consumer content (dark colors)
Concrete sealers, liquid – 79% minimum biobased content
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Employ an environmentally sensitive, low-impact building/facility exterior plan that helps discourage surrounding wildlife habitat while sustaining ecological and environmental integrity. The plan must employ best management practices that significantly reduce harmful chemical
AuOM-14
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
use, energy waste, water waste, air pollution, solid waste, and/or chemical runoff (e.g., gasoline, oil, antifreeze, salts) compared with standard practices. The plan must address all of the following operational elements that occur on the building and grounds, as applicable:
Cleaning of building exterior Paints and sealants used on building exterior
Standard Practice
None
Recommended Practice
Clean only as often as needed to maintain building appearance and safety Use cleaning products efficiently to make sure cleaning products do not drain into a
sewer Contractor must administer training on the proper use of green chemicals For additional credit opportunities, see SAM Credit AP.4 Green Procurement Policy
Best Available Practice
None
AuOM-15
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.4 Hardscape Grounds Management
1 point
INTENT
Employ an environmentally sensitive, low-impact hardscape management process for building exterior (e.g., sidewalks, paved surfaces and other hardscape) that sustains ecological and environmental integrity while deterring wildlife and maintaining site appearance and safety.
REQUIREMENTS
Within the performance period, have in place low-impact snow and ice removal methods utilizing chemicals that are innovative and ecologically friendly.
AND
Include green cleaning and maintenance practices and materials that minimize environmental impacts. An outline of acceptable materials is available in Appendix AP-A – Green Product Listing.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Employ an environmentally sensitive, low-impact snow and ice removal method utilizing chemicals that are innovative and ecologically friendly. The process must employ best management practices that significantly reduce harmful chemical use, energy waste, water waste, air pollution, solid waste, and/or chemical runoff (e.g., gasoline, oil, antifreeze, salts) compared with standard practices. The process must address all of the following operational elements that occur on the building and grounds, as applicable:
Snow and ice removal Cleaning of sidewalks, pavement and other hardscape methods
Standard Practice
Application of road salt (landside) Airside ground anti-icing/deicing fluid that are environmentally friendly, such as but not
limited to: o Solid: Sodium Formate and Sodium Acetate o Liquid: Potassium Acetate o Biochemical Oxygen Demands (BOD)
AuOM-16
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Recommended Practice
Use anti-icing/deicing that are lower in BOD and toxicity Develop a [landside] policy for optimal road salt usage balancing environmental and
safety concerns Investigate non-electrified snowmelt procedures, including Hydronic runway pavement
for snowmelt and Epoxy overcoat with glycol for controlling snow on runways Use fossil fueled equipment only as frequently as needed to maintain site appearance
and safety, or use low-impact alternatives such as, but not limited to: o Electric powered equipment o Low-noise equipment o Hand raking or sweeping
Use more environmentally friendly deicing chemicals, such as but not limited to: o Magnesium Chloride o Potassium Chloride o Potassium Acetate
Contractor must administer eco-training, such as chemical use and eco-driving to their personnel to ensure appropriate use/applications, and to reduce fuel consumption, greenhouse gas emissions, and accident rate
Best Available Practice
Infrared Radiant Deicing Technology Forced air/hybrid deicing which adds deicing fluid to the airstream to aid in removing ice
and snow Tempered steam technology
CASE STUDY
State-of-the-Art Deicing Facility Philadelphia International Airport – Philadelphia, Pennsylvania
The deicing facility at Philadelphia International Airport captures and disposes deicing fluid runoff in order to protect nearby waterways and the groundwater system. A network of inlets and stormwater drains provide wastewater collection for both deicing aprons. This stormwater drainage system diverts deicing fluid runoff into the recovery collection system during deicing operations.
http://www.phl.org/passengerinfo/Documents/PHLenviro1.pdf
AuOM-17
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.5 Integrated Pest Management and Wildlife Deterrence
1 point
INTENT
Preserve environmental integrity while discouraging the presence of pests/wildlife, in an effort to include methods that maintain and encourage high-performance pest management control.
REQUIREMENTS
Use Integrated Pest Management (IPM) Techniques, such as:
Control dirt, moisture, clutter, foodstuffs, harborage, and building penetrations Use baits and traps rather than pesticide sprays where possible Avoid pesticide applications for prevention of pests Use pesticides only where pests are located Use pesticide specifically formulated for targeted pest
AND
Use wildlife deterrent methods in accordance with United States Department of Agriculture - Wildlife Services.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Over the performance period, have in place a wildlife and pest management plan that addresses overall site management, chemicals, and waste. Include such green landscape management practices such as: applying integrated pest management and deterring wildlife habitat.
Integrated pest management (IPM), defined as managing pests (plants, fungi, insects, and/or animals) in a way that protects human health and the surrounding environment that improves economic returns through the most effective, least-risk option.
The IPM plan includes preferred use of nonchemical methods, definition of emergency conditions, and universal notification providing advance notice of not less than 72 hours under normal conditions, and, 24 hours in emergencies before a pesticide, (other than a least-toxic pesticide) is applied in a building or on surrounding grounds that the building management maintains.
Vegetated roofs must be designed and maintained to not attract wildlife or provide habitat.
AuOM-18
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Standard Practice
None
Recommended Practice
Apply pesticides only during unoccupied hours Ventilate building with significant quantities of outside air during and after applications Completely flush building prior to occupancy Use more than normal outside air ventilation for some period after occupancy Notify occupants prior to occupation If applying outside keep away from air intake Contractor must administer eco-training, such as chemical use, eco-driving, to their
personnel to ensure appropriate use/applications, and to reduce fuel consumption, greenhouse gas emissions, and accident rates
Best Available Practice
None
CASE STUDY
Wildlife Management Program Southwest Florida International Airport – Fort Myers, Florida
The airport utilizes various projects that analyze problematic habitats and species to develop specialized methods of prevention. The formation of a Hazardous Wildlife Working Group in 2005 improved communications between Environmental Compliance, Airport Operations and Airport Maintenance to assist in the implementation of new and innovative deterrence methods. And in March 2008, the airport initiated a Wildlife Hazard Assessment that used a unique methodology that broke down species into hazard guilds, assigning relative risk values to more effectively focus on specific airfield areas that attract the highest risk species.
http://www.flylcpa.com/uploads/newsfiles/file166.pdf
AuOM-19
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.6 Erosion Control
1 point
INTENT
Address landscape operations while preserving and maintaining ecological integrity and site preservation by minimizing soil loss and preventing water pollution.
REQUIREMENTS
Have in place an environmentally sensitive management plan for the site’s natural components pertaining to erosion and sedimentation control for ongoing landscape operations (where applicable). The plan must address both site soil and potential land disturbances. The plan must also include measures that prevent erosion and sedimentation, air and water pollution from dust or particulate matter and restore eroded areas.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Over the maintenance period of the site, have in place a maintenance and best practice plan that addresses overall site management and control. Examples of erosion control methods include, but are not limited to:
Temporary and permanent seeding (in accordance with CDA/OMP Specification 02905 – Sustainable Airport Landscaping, see SAM appendix DC-C Referenced City of Chicago Specifications and Standards)
Mulching Structural control methods (such as: earthen dike, silt fence, sediment traps and
sediment basins) Use of perennial plants (in accordance with CDA/OMP Specification 02905 –
Sustainable Airport Landscaping, see SAM appendix DC-C Referenced City of Chicago Specifications and Standards)
Buffer strips Ditch liners The use of fertilizer as necessary Removing and/or not installing invasive plants
Standard Practice
Follow the Best Management Practice (BMP) guidelines for erosion control
AuOM-20
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Recommended Practice
Identify problems Perform periodic checks Dispose of loose debris Maintain ground cover Clean major sediment sources on paved surfaces Install rolled mats (organic, biodegradable mulch mats used to reduce erosion) and
ensure that they conform to site contours Use natural fiber geotextiles (permeable fabrics) that are biodegradable
Install permeable paving materials to reduce stormwater runoff and allow rain water to infiltrate into the ground and replenish groundwater
Best Available Practice
None
CASE STUDY
Erosion and Sediment Control on Atlanta Hartsfield International Airport Project Hartsfield-Jackson Atlanta International Airport – Atlanta, Georgia
Excessive rain can create excessive soil erosion control problems. Due to the large quantities of soil being moved on the land, the potential for sediment contamination is great. Erosion control measures for this project consisted of the use of slope drains that feed into a detention basin. The basins then serve as collectors of heavy rainfall to prevent flooding.
Rock is often times used in conjunction with the erosion control systems. A more aesthetically pleasing method was a vegetative cover provided by 3.2 million square yards of temporary seeding and 2 million square yards of permanent seeding. Atlanta, in addition, installed a total of 300,000 square yards of turf reinforcement mat and 4,000 square yards of ditch liner will be installed to help anchor the grass within the problem areas.
www.landandwater.com/features/vol47no5/vol47no5_2.html
AuOM-21
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.7 Landscape Management
1 point
INTENT
Maintain the landscape that is aesthetically pleasing and at the same time, low maintenance, ecologically and financially sustainable yet does not compromise Airport security and aircraft safety.
REQUIREMENTS
Currently follow the requirements of the CDA 02905 “Sustainable Airport Landscaping” specifications
AND
Use non-gasoline powered landscape equipment
AND
Use fertilizer only as needed
AND
Prohibit burning and reuse or compost landscape waste on-site.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Over the performance period, have in place a low-impact plan that addresses overall site management, chemicals, fertilizers, and landscape waste. Include such green landscape management practices such as:
Provide proper training methods to current employees Reduce the use of power equipment Discourage wildlife habitat Remove or don’t install invasive plants Use mulching mowers to significantly reduce landscape waste generation, fertilizer
needs, and water consumption through retention of organic matter
Standard Practice
Do not apply pesticides or fertilizers before an expected rainfall (unless specified within the manufactures recommendations)
AuOM-22
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Conduct soil testing as necessary to determine the amount of nutrients needed for a healthy landscape
Never wash spilled chemicals into streets of storm drains Do not store in a manner which allows exposure to storm water
Recommended Practice
Do not apply chemicals within 25-feet (at a minimum) of a body of water Use organic and natural products Use non-potable hot water for weed control to eliminate vegetation in pavement cracks
in place of herbicides Mulching and/or electric mowers Eliminate fertilizer and herbicide use altogether Install rolled mats (organic, biodegradable mulch mats used to reduce erosion) and
ensure that they conform to site contours Use natural fiber geotextiles (permeable fabrics) that are biodegradable Specify non-toxic, non-chemical organic or bio-based materials for landscape planting
and fertilization Top-dress soil with compost to decrease fertilizer and irrigation needs, to control erosion,
and to retain moisture When application of landscape fertilizers, pesticides and other chemicals is necessary,
specify organic or bio-based fertilizers and pesticides Spot treat landscape problem areas instead of chemically treating a larger area than
necessary Use electric lawn mowers, such as the Neuton lawn mower, to reduce the level of noise
and air pollution generated by traditional gasoline-powered mowers (www.neutonpower.com). Electric mowers need no extension cords and have replaceable, rechargeable batteries for extended range.
Use propane- and/or natural gas-powered string trimmers, blowers, and push mowers All diesel-powered equipment to use biodiesel (minimum 20% blend). Since there's little
or no cold weather issue with lawn care, high blends (50%-100%) are possible. No mowing on Air Pollution Action days Install cisterns and other water recycling infrastructure to use stormwater and/or
graywater for irrigation Install high-efficiency irrigation systems (if irrigation is a necessity) with a slow-drip, sub-
soil irrigation and automated linkages to meteorological data Contractor must administer eco-training, such as chemical use, eco-driving, to their
personnel to ensure appropriate use/applications, and to reduce fuel consumption, greenhouse gas emissions, and accident rates
AuOM-23
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Best Available Practice
Establish a centralized landscaping composting facility Utilize a solar or propane mower
CASE STUDIES
Environmental Management Santa Barbara Airport – Santa Barbara, California
Since 2000, the Santa Barbara Airport has been implementing the largest environmental restoration project on the south central coast as mitigation for the Airfield Safety Projects. Approximately one-half of the Airport property is comprised of the Goleta Slough State Marine Park. As proud stewards of the Slough, the Santa Barbara Airport is actively managing 55-acres of the Park that is currently undergoing planting, maintenance, and monitoring, as part of this restoration effort. This coastal wetland is recognized as one of the few remaining saltmarsh habitats in California. At Area I, a 25-acre site on the south side of the Goleta Slough, the Santa Barbara Airport has removed invasive non-native species and planted native plants. These plants were carefully grown by Growing Solutions at the Airport Nursery using seeds collected in the Slough.
www.flysba.com/news_facts/environmental_management
Storm Water Management Plan San Diego International Airport – San Diego, California
San Diego International Airport is responsible for administering approximately 661 acres of public lands on the shore of San Diego Bay. The Storm Water Management Plan is a major element of the Airport’s commitment to preventing, eliminating, and reducing the discharge of polluted storm water into the surrounding environment and San Diego Bay. The Stormwater Management Plan is directed at those activities of the Airport Authority itself, as well as those of the airlines and other airport tenants that have the potential to cause stormwater pollution.
The Storm Water Management Plan is designed to control the pollutants generated by everyday operation of the airport, including: trash, litter and debris; petroleum products that might leak from aircraft and motor vehicles; heavy metals potentially contained in the dust from brake pads, rubber tires, engine exhaust, and the fertilizers and pesticides used to maintain the airport’s landscape and facilities.
www.san.org/sdcraa/airport_initiatives/environmental/protection/stormwater.aspx
AuOM-24
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Landscape Composting Hartsfield-Jackson Atlanta International Airport – Atlanta, Georgia
Composting is performed at the landscape shop located at the former Northwest Airlines hangar. The process combines nitrogen from the green materials (flowers, grass clippings) and carbon from the brown materials (dried leaves and straw). These materials are turned regularly and eventually break down into decomposed organic matter known as compost. All of the materials are derived from routine work at the airport (e.g. grass cutting, raking leaves in the fall, recycled flowers). The materials are added to the compost pile throughout the year. The compost is used as a soil amendment in the various seasonal color beds and containers throughout the Airport property.
http://www.atlanta-airport.com/Airport/Environmental/Composting.aspx
AuOM-25
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.8 Alternative Commuting Transportation for Employees
1 to 4 points
INTENT
To reduce pollution and land development impacts from conventional automobile use for commuting trips.
REQUIREMENTS
Within the performance period, reduce the number of commuting round trips made by regular building occupants, or tenant or division employees, using single-occupant, conventionally powered, and conventionally fueled vehicles. For the purposes of this credit, alternative transportation includes, but is not limited to:
Telecommuting Compressed work weeks Mass/public transit Walking Bicycles or other human-powered conveyances Carpools Vanpools Low-emitting, fuel-efficient or alternative-fuel vehicles
Performance calculations are made relative to a baseline case that assumes all regular occupants commute alone in conventional automobiles. The calculations must account for seasonal variations in the use of alternative commuting methods and, where possible, indicate the distribution of commuting trips using each type of alternative transportation.
Points are earned for percentage increase in employees who utilize the alternative commuting transportation methods within the performance period:
SAM Credit Percentage Increase in Alternative Methods Points
1.8.1 5% 1
1.8.2 10% 2
1.8.3 20% 3
1.8.4 30% 4
Low-emitting vehicles and fuel-efficient vehicles are defined as vehicles that are classified as zero-emission vehicles (ZEVs) by the California Air Resources Board or that have achieved a minimum green score of 40 on the American Council for an Energy Efficient Economy annual vehicle-rating guide.
AuOM-26
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
When developing an alternative transportation program, consider the opportunities and limitations of different options, based on the building’s location and community’s transportation infrastructure/services.
Provide space and infrastructure features such as, but not limited to:
Bicycle racks Changing facilities Preferred parking Access to mass transit Alternative-fuel refueling stations
Offer employees incentives for using alternative transportation such as, but not limited to:
Additional vacation days Cash rewards or pretax options Free or discounted public transportation passes Bicycling equipment or telecommuting equipment to individuals committed to using them
Encourage the use of alternative commuting methods by guaranteeing free rides home for employees who must unexpectedly leave work early or late. Utilize organization resources to communicate with building occupants about alternative transportation options and benefits, and facilitating communication among building occupants for coordinating ride sharing.
Standard Practice
Chicago Department of Aviation (CDA) already has programs in place for alternative fuel vehicles within the airport operations department that is designed so that these programs are enhanced and supported
Recommended Practice
Develop and provide alternative facilities and areas to encourage alternative commuting
Best Available Practice
Provide a centralized facility(s) for employees to store alternative commuting opportunities as well as include incentives to employees for applying alternative commuting means
Increase the awareness of alternative fuel vehicles for airport operations – particularly the indoor cargo operations
Provide preferred parking for staff and public alternative fuel vehicles
AuOM-27
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Plan for a development of preferred parking and/or lot locations for rental fleets, which offer alternative fuel rental vehicles
CASE STUDIES
Bike to Work Plan City of Chicago, Illinois
The Bike 2015 Plan is the City of Chicago’s vision to make bicycling an integral part of daily life. The plan recommends projects, programs and policies through 2015 to encourage use of bicycles as a practical, non-polluting, and affordable mode of transportation. The Bike 2015 Plan has two overall goals:
To increase bicycle use, so that 5 percent of all trips less than five miles are by bicycle. To reduce the number of bicycle injuries by 50 percent from current levels.
The plan has eight chapters, each with a specific goal:
Bikeway Network – Establish a bikeway network that serves all Chicago residents and neighborhoods.
Bicycle-friendly Streets – Make all of Chicago’s streets safe and convenient for bicycling.
Bike Parking – Provide convenient and secure short-term and long-term bike parking throughout Chicago.
Transit – Provide convenient connections between bicycling and public transit. Education – Educate bicyclists, motorists, and the general public about bicycle safety
and the benefits of bicycling. Marketing and Health Promotion – Increase bicycle use through targeted marketing and
health promotion. Law Enforcement and Crash Analysis – Increase bicyclist safety through effective law
enforcement and detailed crash analysis. Bicycle Messengers – Expand the use of bicycle messengers; improve their workplace
safety and public image.
http://bike2015plan.org
Preferred Parking for Carpoolers Denver International Airport – Denver, Colorado
Denver International Airport has launched an aggressive program to encourage carpooling which offers reduced parking cost for carpoolers. Additionally, the airport offers designated locations which include unreserved spaces typically in close proximity to employees or passenger access points.
AuOM-28
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.9.1 Stormwater Management: Landside
1 point
INTENT
Limit disruption of natural water hydrology by reducing impervious cover, increasing on-site infiltration, reducing or eliminating pollution from stormwater runoff, and eliminating contaminants by enhancing the current operating system.
REQUIREMENTS
Reduce impervious surfaces totaling at least 5% of your total site area with permeable surfaces. Those surfaces can include, but are not limited to:
Permeable asphalt / concrete Open grid pavers Aggregate materials Turf or landscaped areas
OR
Harvest rainwater and develop a use for it;
OR
Nonstructural techniques such as, but not limited to:
Rain gardens Vegetated swales Disconnection of imperviousness Rainwater recycling
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Because many airside pavements have the potential for deicing fluid and jet fuel contamination, technologies that increase infiltration to the subsurface are not used. On landside projects, or for areas not subject to aviation-related contaminants, these methods are encouraged; however, other contaminants may be present and need to be addressed.
Maintain natural stormwater flows by promoting infiltration. Maintain procedures that include ongoing monitoring of any installed features that assist in stormwater irrigation, pervious paving, and other measures to minimize impervious surfaces. Any strategies used should discourage
AuOM-29
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
wildlife habitat. Reuse stormwater volumes generated for non-potable uses such as landscape irrigation, toilet and urinal flushing and custodial uses.
Standard Practice
Follow Chicago Department of Aviation’s Best Management Practices
Recommended Practice
Install rain gardens, vegetated swales, disconnection of imperviousness, and rainwater recycling
Installing cisterns or rain barrels Install landscape to reduce runoff. See SAM Credit 2.4 Water Efficient Landscaping Evaluate curb breaks and drainage ditches, and/or bioswales Install high-efficiency irrigation systems (if irrigation is a necessity) with a slow-drip, sub-
soil irrigation Install permeable paving materials to reduce stormwater runoff and allow rain water to
infiltrate into the ground and replenish groundwater
Best Available Practice
Encourage use of permeable pavement, where applicable Where potential for contamination exists, the use of these technologies must be weighed
carefully to prevent larger contaminant issues, such as infiltration of ground water
CASE STUDY
Terminal Building Cooling System New Chitose Airport – Hokkaido, Japan
The New Chitose Airport terminal building in Hokkaido, Japan, will utilize a new cooling system by the fiscal year 2010. The transport ministry plans to collect snow during the winter and preserve it to provide 30% of the building's cooling needs during the summer. Of the snow collected throughout the winter, approximately 45% of the snow is preserved for the summertime through the use of heat-insulating materials. The collected snow would be used to chill the liquid of the building's cooling system. This practice could stave off 2,100 tons of carbon dioxide emissions per annum compared to using the building's existing cooling system.
www.goodcleantech.com/2008/10/new_chitose_airport_in_japan_t_1.php
AuOM-30
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.9.2 Stormwater Management: Airside
1 to 4 points
INTENT
Reduce airside stormwater pollutants by employing environmentally sensitive maintenance techniques within the current operating system.
REQUIREMENTS
Up to 4 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Use sweeper vacuums, glycol recovery vehicles and/or mobile collection units to remove and reuse spent deicing fluid.
1
Develop collection systems for deicing runoff. The proposed runway and taxiway pavements would contain first flush systems along the edge of pavements and Central Deicing Facilities for aircraft. The first flush system could consist of slotted edge drains connected to underground holding tanks. Glycol contaminated snowmelt and minor storm water runoff would be captured in the tanks and removed for treatment, disposal or recycling.
2
Reduce or eliminate deicing chemical contamination by using low Biological Oxygen Demand (BOD), low toxicity, and low corrosivity material (e.g., acetate and urea).
1
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Because of the potential for deicing fluid contamination, the use of these technologies must be weighed carefully to prevent larger contaminant issues, such as infiltration of ground water.
Standard Practice
Follow CDA BMP procedures
Recommended Practice
Follow Best Management Practices outlined in Chapter 4, Part 2 (Urban Runoff), on the United States Environmental Protection Agency’s Guidance Specifying Management
AuOM-31
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Measures for Sources of Nonpoint Pollution in Coastal Waters, January 1993 (document No EPA-840-B-92-002)
Recover and recycle deicing chemicals at application point (e.g., vacuum truck, or other capturing method)
Best Available Practice
Incorporate technologies, application techniques and/or designs to minimize glycol residual after application of deicing agents
Use glycol separation and/or concentration methods to recover spent glycol from storm water or snow melt
Central Deicing Facilities could also be utilized to capture excess glycol from aircraft deicing operations in underground storage tanks
CASE STUDIES
Airport Stormwater Program Seattle-Tacoma Airport – Seattle, Washington
Sea-Tac Airport protects area creeks from flooding, contamination and sediment through its stormwater management program. It manages runoff generated from more than 2,300 acres, including those associated with airfield operations and industrial construction activities. Central to this program is the industrial wastewater treatment system (IWTS). Continual improvements ensure stormwater potentially contaminated by aircraft fueling, de-icing, cleaning and maintenance does not enter nearby streams.
https://www.portseattle.org/Environmental/Pages/default.aspx
Stormwater Quality Initiative Denver International Airport – Denver, Colorado
Denver International Airport was built with a dedicated system for the capture, conveyance, treatment, and discharge of stormwater contaminated with aircraft deicing fluids. The system includes seven dedicated deicing pads, five wastewater retention ponds, and an onsite deicing fluid recycling facility.
www.aci-na.org/static/entransit/Going%20Green%209-7-07.pdf
AuOM-32
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.10 Heat Island Reduction
1 to 2 points
INTENT
Minimize impacts of existing roofs and pavements that cause the heat island effect (thermal gradient differences between developed and undeveloped areas).
REQUIREMENTS
Use any combination of the following strategies when replacing/renovating or maintaining pavement:
For 50% of the site’s hardscape area (including roads, sidewalks, courtyards, and parking lots) complete the following (1 point):
o Provide shade from an existing tree canopy or within five years of landscape installation - landscaping (trees) must be in place at the time of certification application
o Have paving materials with a Solar Reflective Index (SRI) of at least 29 and implement a maintenance program that ensures these surfaces are cleaned at least every two years to maintain good reflectance and minimums
o Have an open-grid pavement system (that consists of at least 50% open area)
AND/OR
For 50% of the roof area use roofing materials having one of the following characteristics (1 point):
o A Solar Reflectance Index (SRI) equal to or greater than the values in the table below for a minimum of 75% of the roof area. Implement a maintenance program that ensures all SRI surfaces are cleaned at least every two years to maintain good reflectance
Roof Type SRI
Low-Sloped Roof 78
Steep-Sloped Roof 29
o Vegetated green roof
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist
AuOM-33
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
TECHNOLOGY/STRATEGY
Employ strategies, materials and landscaping techniques that reduce heat absorption of exterior materials. Use shade (calculated at 10 a.m., 12 noon, and 3 p.m. on the summer solstice [June 21] that will be used as the effective shaded area) from native or adapted trees and large shrubs, vegetated trellises or other exterior structures supporting vegetation. Consider the use of new coatings and integral colorants for asphalt to achieve light-colored surfaces instead of blacktop. Position photovoltaic cells to shade impervious surfaces.
Consider installing high-albedo roofs to reduce heat absorption. SRI is calculated according to ASTM E 1980. Reflectance is measured according to ASTM E 903, ASTM E 1918 or ASTM C 1549. Emittance is measured according to ASTM E 408 or ASTM C 1371. Product information is available from the Cool Roof Rating Council website, at www.coolroofs.org. Also, visit the ENERGY STAR website, www.energystar.gov to research compliant products.
Unless the reflectance is determined directly through in-site testing, the following default SRI values are to be used:
MATERIAL SRI
New Conventional “gray” concrete 35
Old (weathered) “gray” concrete 19
New “white” concrete 86
Old (weathered) “white” concrete 45
New Asphalt 0
Old Asphalt 6
Standard Practice
White roofs are currently the standard for new construction on airport property. These are acceptable; however, SRI decreases with the age of the roof. Unless a cleaning program is in place, the benefits of white roofs diminish over time. For this reason, along with the benefits of stormwater management, the construction of vegetated green roofs is encouraged.
Recommended Practice
Maximize light colored/high albedo pavement, such as Portland Concrete Cement (PCC), for roadways, parking lots, sidewalks and plaza areas. Reflectance must be a minimum of 0.3 (‘White’ portland cement – 0.7 to 0.8, typical PCC – 0.35 to 0.5, typical asphalt pavement – 0.05 (new) to 0.15 (over 5 years)). On an annual basis, test the pervious areas to verify the SRI standard is met as well as to depict improvement.
Install a vegetated green roof
AuOM-34
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Evaluate and utilize an ENERGY STAR compliant roofing system, such as aluminum coating and light-colored coatings. Thermoplastic and white Poly(vinyl chloride) (PVC) roofing systems meet these standards.
Best Available Practice
For Landside projects only, install trees consistent with CDA/OMP Specification 02905 – Sustainable Airport Landscaping, and for any proposed plant species not listed, consult an FAA certified airport biologist to ensure the plants will not attract wildlife
A creative combination of the above strategies to reach this goal is encouraged. For example, a task/project can provide 5% shading of dark colored impervious surfaces and 25% light colored/high albedo pavement to achieve this goal
Install open grid pavement for surface lots and site pavement Install light-colored permeable pavers and concrete Install “green walls” for building façade
CASE STUDIES
Line Station 4 Living Wall Vancouver International Airport – Vancouver, Canada
The first Canadian airport to install a green wall, Vancouver International Airport has erected one on a wall of the SkyTrain Station. One of the largest living walls in North America (the largest at the time in 2009), it measures 55.8 feet x 38 feet, and houses a total of 27,391 individual plants. Landscape architect Randy Sharp used a modular system by G-Sky for this living wall that encompasses 2,107 stainless steel panels. His design concept stresses the connection of the vegetated wall to the rapid transit station to the ground.
www.greenroofs.com/blog/2010/03/26/gpw-yvr-canada-line-station-4-living-wall/
FedEx Cargo Facility Green Roof O’Hare International Airport – Chicago, Illinois
The new FedEx Cargo Facility green roof at the O'Hare International Airport in Chicago is the largest free-standing building vegetated roof in the central United States at 170,000 square feet. This project required utilization and coordination of an uplift-resistant and rapidly executed green roof design due to the active runway status of the O'Hare facility.
www.greenroofs.com/projects/pview.php?id=1166
AuOM-35
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
1.0 SUSTAINABLE SITES
1.11 Light Pollution Reduction
1 point
INTENT
Eliminate light trespass from the building and site, improve night sky access and reduce development impact on nocturnal environments and upgrade existing lighting specifications to meet new standards.
REQUIREMENTS
Interior Lighting: All non-emergency built-in existing interior/indoor lighting with a direct line of sight to any openings in the envelope (translucent or transparent, wall or ceiling) must be automatically controlled to turn off during all after-hours periods during the performance period. The total duration of all programmed after-hours periods annually must equal or exceed 2,190 hours per year (50% of annual nighttime hours). Manual override capability may be provided for occasional after-hours use.
Implement a program to ensure that the lighting control system is being properly used to adjust lighting levels during all after-hours periods.
Exterior and Site Lighting: Choose one of the following options:
OPTION 1 –
If the project achieved LEED – NC SS Credit 8 and/or SAM Design & Construction Credit 2.7 Light Pollution Reduction, the point is earned.
OR
OPTION 2 –
Partially or fully shield all fixtures so that they do not directly emit light to the night sky.
Fully shielded: Exterior light fixtures are shielded or constructed so that light rays emitted by the fixture are projected below the horizontal plane passing through the lowest point on the fixture from which light is emitted.
Partially shielded: Exterior light fixtures are shielded so that the lower edge of the shield is at or below the centerline of the light source or lamp such that light emission above the horizontal plane is minimized.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
AuOM-36
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
TECHNOLOGY/STRATEGY
Implement site lighting criteria to maintain safe light levels while avoiding off-site lighting and night sky pollution. Technologies to reduce light pollution include full-cutoff luminaries and low-reflectance surfaces.
Standard Practice
Minimize site lighting where possible and use standard cutoffs for interior and exterior lighting wherever possible and appropriate
Recommended Practice
Automatic Lighting controls such as motion sensors or timers Adopt site lighting criteria to maintain safe light levels while avoiding off-site lighting and
night sky pollution Low-angle spotlights for roadway and building lighting The maximum candela value of all interior lighting shall fall within the building (not out
through windows) and the maximum candela value of all exterior lighting shall fall within the property
Consider a parking lot design which allows for a reduction of the available parking areas and the associated exterior lighting during non-use or low use hours
Best Available Practice
Fine tune the lighting energy demand while evaluating potential smart-lighting control systems and LED light technologies
CASE STUDY
Total Lighting Control System T.F. Green International Airport – Providence, Rhode Island
The newly renovated terminal at T.F. Green International Airport implemented an energy-efficient and automated Total Lighting Control (TLC) system by General Electric. The system features programmable networked technology, controlling the internal and external lighting at the facility, including lights in the concourse areas, departure areas, baggage claims and outdoor parking areas.
http://www.glcs.ca/assets/images/geproducts/pdfs/tfgreen.pdf
AuOM-37
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
2.0 WATER EFFICIENCY
2.1 Prerequisite 1 – Establish a Water Use Baseline
Required
INTENT
Increase water efficiency within CDA Division and tenant spaces to reduce the burden on municipal water supply and wastewater systems.
REQUIREMENTS
Provide water meter data (if available);
OR
Calculate baseline water usage by taking an inventory of plumbing fixtures. Once the inventory has been completed use the table below to determine the aggregate baseline fixture flow rate by multiplying the number of fixtures by their respective baseline flow rates. The sum of all these flow rates will become the baseline for each subsequent review.
Exceptions from Calculations:
Those appliances & equipment for which water is used toward human consumption may be excluded. For example, bread misters, soda machines, coffee making machines, misters for produce and fixtures used to fill sinks for washing produce.
Equipment, appliances, fixtures and fittings not covered by the Energy Policy Act 1992 and that do not contribute toward the retail process and are not commercially rated may also be excluded. For example, a residential dishwasher in an employee break room.
Fixtures whose flow rates are regulated by health codes may be excluded. For example, fixtures used for filling sinks used for dishwashing in which a certain temperature water must be maintained.
AuOM-38
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Commercial Fixtures, Fittings, and Appliances
Usage Rate Fixture Flow Rate Baseline Flow Rate
Commercial Toilet 4 times per day 1.6 gallons/use 6.4 gallons/day Commercial Urinal 2 times per day 1 gallons/use 2 gallons/day Commercial Lavatory (restroom) Faucet
6 times per day 0.5 gallons/use 3 gallons/day
Kitchen Faucet 2 times per day 1 gallons/use 2 gallons/day Shower 1 time per day 105 gallons/use 105 gallons/day Commercial Pre-Rinse Spray Valves (for food service applications)
3 times per day 95 gallons/use 285 gallons/day
Washing Machine 1 time per day 35 gallons/use 35 gallons/day Dishwasher 1 time per day 8.5 gallons/use 8.5 gallons/day Dishwasher (for food service applications)
5 times per day 200 gallons/use 1,000 gallons/day
Water Fountain 5 times per day 0.01 gallons/use 0.05 gallons/day Ice Machines 1 time per day 30 gallons/use 30 gallons/day * Flow rates have been based on EPAct 1992 where available SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Gather the meter data from one full year. When calculating the aggregate baseline amount only the following fixtures and fixture fittings (as applicable to the space) should be included: toilets, urinals, lavatory faucets, kitchen faucets, showers, and pre-rinse spray valves, washing machines, dishwashers, water fountains and ice machines.
Standard Practice
Comply with CDA/OMP Specification 15410 – Plumbing Fixtures
Recommended Practice
Track water consumption using whole building metering Identify meters and install a separate meter if one is not present
AuOM-39
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Best Available Practice
Track water consumption using submetering for one or more of the following: o Irrigation o Indoor plumbing fixtures o Cooling towers o Domestic hot water o Process water
AuOM-40
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
2.0 WATER EFFICIENCY
2.2 Retroactive Water Efficiency
1 to 5 points
INTENT
Recognize previous improvements and upgrades that had a positive impact on water efficiency.
REQUIREMENTS
Create an inventory of all the water improvements and upgrades undertaken to improve their water efficiency prior to the initial performance review.
This credit is only applicable on the first completed performance review. Subsequent reviews would refer to SAM Credits 2.1 Prerequisite 1 – Establish a Water Baseline and 2.3 Indoor Water Efficiency.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
A point will be awarded for each of the retroactive improvements. Up to 5 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Switched to high efficiency toilets 1
Switched to high efficiency urinals 1
Switched to waterless toilets and urinals
1
Installed low flow kitchen faucets 1
Installed low flow lavatory faucets 1
Installed ENERGY STAR dishwasher 1
Installed ENERGY STAR washing machine
1
AuOM-41
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Standard Practice
None
Recommended Practice
None
Best Available Practice
None
AuOM-42
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
2.0 WATER EFFICIENCY
2.3 Indoor Water Efficiency
1 to 5 points
INTENT
Maximize indoor plumbing fixture and fitting efficiency to reduce the use of potable water and the burden on municipal water supplies and wastewater systems.
REQUIREMENTS
During the performance period have in place strategies and systems that in aggregate produce a reduction in indoor plumbing fixture potable water use from the reported or calculated baseline established in SAM Credit 2.1 Prerequisite 1 – Establish a Water Baseline.
The minimum water savings percentages for each point threshold are as follows:
SAM Credit Water Reduction Points
2.3.1 10% 1
2.3.2 20% 2
2.3.3 30% 3
2.3.4 40% 4
2.3.5 50% 5
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Calculations are based on estimated occupant usage and shall include only the following fixtures and fixture fittings (as applicable to the space): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and pre-rinse spray valves.
WaterSense™- certified fixtures and fixture fittings should be used where available. Use high-efficiency fixtures (water closets and urinals) and dry fixtures such as composting toilet systems to reduce the potable water demand. Consider the use of alternate on-site sources of water, such as rainwater, stormwater, or air conditioner condensate, and graywater for non-potable applications such as toilet and urinal flushing, as approved by the manufacturer, and for custodial uses.
Reduce indoor plumbing fixture and fitting potable water usage through automatic water control systems. Install, where possible, water-conserving indoor plumbing fixtures and fittings that meet or exceed the UPC 2006 or IPG 2006 fixture and fitting requirements in combination with high-efficiency or dry fixture and control technologies.
AuOM-43
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Special consideration should be used to distinguish applicability of these technologies in high-volume passenger terminal areas versus office facilities, especially with respect to maintenance.
Standard Practice
Comply with CDA/OMP Specification 15410 – Plumbing Fixtures
Recommended Practice
Exceed Chicago Building Code (CBC) (EPAct 1992) by 20% Use high-efficiency fixtures and valves Utilize fixtures such as dual flush toilets and waterless urinals to reduce wastewater
volumes Evaluate reusing stormwater for non-potable uses Use local generation of domestic hot water, as much as possible, to eliminate long
piping runs associated with recirculation piping. Unless connecting to an existing hot water recirculating system
Domestic hot water for general plumbing fixtures should be designed for a temperature of 140°F maximum, but not less than 120°F
Install water efficient dishwashers and washing machines Water efficient dishwashers and washing machines
Best Available Practice
While regulatory requirements vary by jurisdiction and a permit and/or a variance may be necessary, graywater can be captured from lavatories, showers, and institutional dishwashing facilities and potentially used for irrigation needs, toilet flushing, sewage conveyance or on-site wastewater treatment systems
CASE STUDIES
Water Use Reduction Double Eagle II Airport – Albuquerque, New Mexico
Use of dual-flush toilets, low flow urinals, and aerators on faucets contributes to an overall water savings of 38% over the standard water fixtures used in a similar building per ASHRAE 90.1-2004.
www.cabq.gov/airport/double-eagle-ii-airport-leadership-in-energy-and-environmental-design-leed
AuOM-44
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Water-Efficient Devices Canberra International Airport - Canberra Australia
Canberra Airport has taken the initiative to install water efficient devices in all new buildings. These devices include 5A reduced flow shower heads, mixer or infrared taps, 3/4.5 dual flush toilets and waterless urinals. These water fittings use significantly less water than the fittings put into most domestic homes.
The biggest users of water inside most buildings are the urinals with a typical modern trough system with automatic sensors using approximately 100,000 liters per year (older trough systems use significantly more). Canberra Airport uses a number of different technologies in order to reduce this water consumption to essentially zero. In the newer buildings Canberra Airport utilizes waterless urinals. In the existing buildings, an alternative water saving device (the Desert Cube Waterless Urinal System) is used, cutting water usage by about 84%.
http://www.fairbairn.com.au/fb-environmental/water.cfm
AuOM-45
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
2.0 WATER EFFICIENCY
2.4 Water Efficient Landscaping
1 to 3 points
INTENT
Limit or eliminate the use of potable water or other natural surface or subsurface resources available on or near the project site for landscape irrigation.
REQUIREMENTS
Reduce potable water or other natural surface or subsurface resource consumption for irrigation compared with current conventional means. If the building does not have separate water metering for irrigation systems, the water-use reduction achievements can be demonstrated through calculations.
Points will be awarded by achieving the following measures:
Technology/Strategy Points
Irrigation controls (e.g., soil moisture sensors, weather data-based controller)
1
Rain water harvesting and graywater (e.g., rain barrels and cisterns)
2
No irrigation (through plant selection/landscape xeriscaping) 3
Potable water: Water suitable for drinking that meets or exceeds EPA drinking water standards; it is supplied from wells or municipal water systems.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Specify water-efficient, climate-tolerant native or adapted plantings. Implement or maintain high-efficiency irrigation technologies, such as micro-irrigation, moisture sensors, or weather data-based controllers. Feed irrigation systems with captured rainwater, graywater (on-site or municipal), municipally reclaimed water, or on-site treated wastewater. Consider not operating an irrigation system. Consider use of xeriscaping principles in arid climates.
AuOM-46
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Standard Practice
Irrigation systems are not typically installed airside and the lower maintenance tall fescue is used for all projects per the following CDA/OMP Master Specifications:
o CDA/OMP Specification T-901 – Seeding o CDA/OMP Specification 02931 – Seeding Hydro-mulching o CDA/OMP Specification 02905 – Sustainable Airport Landscaping, is the airport
landscaping specification that deals with other plants and landscaping requirements
Recommended Practice
No irrigation system Drought tolerant plants Utilize vegetation which may be acceptable for site use (native and/or low-maintenance),
with special consideration for vegetated green roofs. Utilize vegetation to reduce or eliminate irrigation requirements for airside/landside areas
Minimized use of high maintenance grass areas, lawns and annual plants Established areas of high and low landscape maintenance areas. Group plants with
similar water-use needs by determining which areas of the site should receive a higher level of care than others and, during drought periods, more irrigation. Coordinate these areas with the irrigation plan. Higher maintenance areas should be located around the major building entries and high traffic areas. Lower maintenance areas should be located on low traffic areas, buffer zones and service areas.
Best Available Practice
Have a soil and climate analysis to determine the appropriate landscape strategy Evaluation of stormwater and/or graywater cisterns for capturing rainwater from all new
roofs for irrigation If an irrigation system is installed, a soil moisture monitoring system is present to reduce
reliance on manual control and timed devices, as well as for detecting leaks Have incorporated the use of recycled and treated wastewater for the use of irrigation
AuOM-47
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDIES
Sustainability Plan Santa Monica Airport – Santa Monica, California
Reduce water use in all areas of airport operations through: installation of water efficient plumbing fixtures in all Airport buildings controlled by the City; installation of water efficient landscaping and irrigation systems in all landscaped areas of the Airport; and installation of graywater and stormwater capture systems, where feasible for landscape irrigation and building plumbing uses, to reduce the use of potable water resources.
www.smgov.net/uploadedFiles/Departments/Airport/Airport%20Sustainability%20Plan(1).pdf
Green Building Dane County Regional Airport – Madison, Wisconsin
The project incorporates 25 green building strategies including water efficient landscaping, recycled carpet, acoustic ceiling tiles manufactured from recycled soda bottles, non-toxic wood preservative treatment, chlorine free vinyl wall covering, and on-site construction waste recycling. Recycled materials were used throughout the building and construction debris was separated and sorted, with 98% collected for recycling – 40,000 tons. Even some of the aqua blue wall sconces are made from recycled soft drink bottles.
www.msnairport.com/media/tour.aspx
AuOM-48
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
2.0 WATER EFFICIENCY
2.5 Rain Harvesting for Non-Irrigation Usage
3 Points
INTENT
Decrease the demand for potable water for non-irrigation use.
REQUIREMENTS
The CDA and/or the tenant should implement and maintain a rainwater harvesting system for the following processes to include, but is not limited to:
Equipment/Vehicle Washing Aircraft Washing Cooling tower Other non-irrigation uses as approved by the SRP
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the system used.
TECHNOLOGY/STRATEGY
Rain harvesting systems can vary in complexity and sophistication, but in every system must utilize some basic common elements. A catchment area will intercept the rainfall and a cistern will store the collected rainwater. Rooftops provide an idea environment for the catchment and a rain barrel is a simplistic example of a cistern. A downspout running can be used for conveyance between the catchment are and the cistern.
Standard Practice
None
Recommended Practice
The cleaning of building exteriors and hardscapes Install cisterns to collect and store rainwater to be used for landscaping and other
purposes Install rain barrels at the end of downspouts Use swales to collect and guide stormwater to catchment areas
Best Available Practice
None
AuOM-49
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDIES
Consolidated Rental Car Facility Nashville International Airport – Nashville, Tennessee
A new Consolidated Rental Car Facility expected to be completed in November 2011 will feature housing for rental cars, “quick turnaround” facility providing refueling and car wash services, and covered access to the terminal. The facility will incorporate sustainable features including the use of recycled water for washing rental cars.
http://www.nashintl.com/ground_trans/rentalcarfacility.aspx
Rainwater Harvesting and Utilization System Singapore Changi International Airport – Changi, Singapore
A rainwater harvesting and utilization system exists in the Changi Airport. Rainfall from the runways and the surrounding green areas is diverted to two impounding reservoirs. One of the reservoirs is designed to balance the flows during the coincident high runoffs and incoming tides, and the other reservoir is used to collect the runoff. The water is used primarily for non-potable functions such fire-fighting drills and toilet flushing. Collected and treated water accounts for 28 to 33% of the total water used at the airport and has resulted in financial savings.
www.unep.or.jp/ietc/publications/urban/urbanenv-2/9.asp
Rainwater Harvesting – Abbey Wood Regional Prime Contract South West (RPC SW), England – United Kingdom
A rainwater harvesting system was installed at Abbey Wood (North) in Bristol at the Oak Building (formally known as Neighborhood 5) development. The new building, with a capacity to accommodate 600 employees, will collect rainfall in a 15,000 L capacity system, and will be used for toilets and urinals. Based on the average occupancy and existing rainfall rates the system will save an estimated 280,000 L of water per year or enough water to take over 3000 baths and will eliminate the need to draw water for sanitary plumbing purposes.
http://www.mod.uk/NR/rdonlyres/D5BABEEE-B991-4F8C-BAAD-4A40AE4623A1/0/RPC_SW_water.pdf
Rainwater Harvesting – Bovington Regional Prime Contract South West (RPC SW), England – United Kingdom
Bovington Camp, located in Dorset, has been developed as a training facility for maintenance and operation of the Terrier track armored excavating vehicle. As part of the development, two new buildings were required – a junior ranks mess and communal facility serving several hundred people per day, and a building to house the Terrier simulators, and provide training and workshop space for 65 people. A rainwater harvesting system was installed on both buildings, each with a 5,000 L tank capacity. The system is designed to continuously meet the water demands for the toilets and urinals in both buildings, with each taken providing enough water for over 1,000 flushes when full.
http://www.mod.uk/NR/rdonlyres/D5BABEEE-B991-4F8C-BAAD-4A40AE4623A1/0/RPC_SW_water.pdf
AuOM-50
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
2.0 WATER EFFICIENCY
2.6 Innovative Wastewater Management
2 points
INTENT
To reduce wastewater generation and potable water demand while increasing the local aquifer recharge.
REQUIREMENTS
Use a system or technology that uses one of the following:
OPTION 1 –
Reduce potable water use for building sewage conveyance by 50% through the use of water conserving fixtures (water closets, urinals) non-potable water (captured rainwater, recycled graywater, and on-site or municipally treated wastewater).
OR
OPTION 2 –
Currently treats 50% of wastewater on-site to tertiary standards. Treated water must be infiltrated or used on-site.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Specify high-efficiency fixtures and fittings and dry fixtures such as composting toilet systems and non-water using urinals to reduce wastewater volumes. Consider reusing stormwater or graywater for sewage conveyance or on-site mechanical and/or natural wastewater treatment systems. Options for on-site wastewater treatment include packaged biological nutrient removal systems and high-efficiency filtration systems.
Standard Practice
None
Recommended Practice
Uses high-efficiency fixtures and valves Utilizing fixtures such as dual flush toilets and waterless urinals to reduce wastewater
volumes Evaluation or reusing stormwater for non-potable uses
AuOM-51
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Best Available Practice
Capture graywater from lavatories, showers and institutional dishwashing facilities for sewage conveyance or on-site wastewater treatment systems
CASE STUDY
Blackwater Recycling Treatment Plant Canberra Airport – Brindabella, Australia
The Blackwater Recycling Treatment Plant at Canberra Airport was launched in 2007 and is a system designed to take sewer (or “black”) water from the buildings and treat it to a drinkable level using a self-cleaning membrane system and UV safety filters. After the treatment, the water is then used (along with rainwater captured off roofs) in toilets and externally for irrigation (whilst the water is drinkable, it is not used for drinking or showering). This was the first commercial large scale water recycling system in the ACT, and the first at an Australian Airport.
http://www.fairbairn.com.au/fb-environmental/water.cfm
AuOM-52
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
2.0 WATER EFFICIENCY
2.7 Water Efficient Vehicle Washing
1 to 4 points
INTENT
To limit or eliminate the use of potable water or other natural surface or subsurface resources available on or near the project site for vehicle washing.
REQUIREMENTS
Up to 4 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Install low volume, high pressure sprayer nozzles on water hoses
1
Log vehicle washing and meter vehicle wash systems separately to measure water
1
Recycle more than 20% of wash water during vehicle washing 1
Recycle more than 50% of wash water during vehicle washing 1
Potable water: Water suitable for drinking that meets or exceeds EPA drinking water standards; it is supplied from wells or municipal water systems.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Reduce potable water or other natural surface or subsurface resource consumption for vehicle washing compared with current conventional means. If the building does not have separate water metering for vehicle washing systems, the water-use reduction achievements can be demonstrated through calculations.
Standard Practice
Indoor vehicle washing
AuOM-53
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Recommended Practice
Low volume, high pressure sprayer nozzles on water hoses Keep a log of vehicle washing water use Capture wash water for re-use (cistern)
Best Available Practice
Treat wash water for re-use
CASE STUDIES
Terminal 5 London Heathrow International Airport – London, England
Groundwater boreholes and T5’s own rainwater harvesting scheme supply water for non-potable uses such as toilet flushing, irrigation, energy centre cooling and vehicle washing. The system is able to capture and reuse 85% of the rainfall that falls on the entire T5 catchment. Demand from the public water supply is expected to be reduced by 70%.
www.futurarc.com/previous_edition/greenairport_heathrow.cfm
Water Conservation Ordinance #1580 City of Santa Monica, California
The City implemented the Water Conservation Ordinance to minimize the needless waste of water. Activities affected include: watering of landscaping, sidewalk washing, vehicle washing, and serving water in restaurants, among others.
http://www.werf.org/liveablecommunities/studies_santa_ca.htm
AuOM-54
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.1 Prerequisite 1 – Refrigerant Management
Required
INTENT
Reduce stratospheric ozone depletion.
REQUIREMENTS
Do not use chlorofluorocarbon (CFC)-based refrigerants in HVAC&R base building systems unless system replacement or conversion is not economically feasible or it is demonstrated that a phase-out plan for CFC-based refrigerants is in place.
Small HVAC&R units (defined as containing less than 0.5 pounds of refrigerant), standard refrigerators, small water coolers, and any other cooling equipment that contains less than 0.5 pounds of refrigerant are not considered part of the base building system and are exempt.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Specify only non-CFC-based refrigerants in all new building HVAC&R systems. Identify all existing CFC based refrigerant uses and upgrade the equipment if economically feasible and/or develop a phase-out plan that identifies a schedule for future replacement.
Standard Practice
Only HCFC and HFC refrigerants have been used for CDA projects where refrigerants were required (typically R-410a, which is an HFC).
Recommended Practice
None
Best Available Practice
Although Hydrochlorofluorocarbons (HCFCs) and Hafnium carbide (HfCs) have ozone depletion potentials (ODP) that are nearly zero, consideration should also be given to their global warming potentials (GWP) (see SAM Credit 3.8 – Enhanced Refrigerant Management). Alternative refrigerants that minimize ODP and GWP compared to HCFCs and HFCs include natural refrigerants such as carbon dioxide, ammonia, and propane. These compounds have an ODP of zero and GWPs which are three orders of magnitude less than most HCFCs and HFCs.
AuOM-55
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDY
Central Utilities System Toronto Pearson International Airport – Toronto, Ontario Canada
Sustainable principles were implemented in an effort to modernize Toronto Pearson International Airport and increase passenger capacity. A new central utilities plant replaced older equipment with a new HVAC system and a state-of-the-art deicing facility. The new system is supplied with chillers that use non-ozone depleting, chlorine free HFC-134a refrigerant. These chillers were customized to add extra temperature sensing capabilities to allow for closer monitoring of the chiller’s motor temperatures, while enhancing equipment safety though an effective preventative maintenance program.
www.xpedio.carrier.com/idc/groups/public/documents/marketing/casestudy19.pdf
AuOM-56
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.2 Utility Meter Data
1 to 4 points
INTENT
Monitor, track and report utility data to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
Provide utility meter data (if available). (1 point)
AND/OR
The data collected under the first performance review will become the baseline for each subsequent review.
During the performance period have in place strategies and systems that in aggregate produce less energy from the reported baseline established under the first performance review.
The minimum energy savings percentages for each point threshold are as follows:
SAM Credit Energy Reduction Points
3.2.1 10% 1
3.2.2 20% 2
3.2.3 30% 3
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
If a separate utility meter is not in place, it is recommended that one be installed. Meter data should be used to determine where energy consumption can be optimized and areas where submetering may be useful.
Standard Practice
None
AuOM-57
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Recommended Practice
Install utility meters where applicable
Best Available Practice
Install submeters wherever possible
AuOM-58
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.3 Retroactive Energy Optimization
1 to 5 points
INTENT
Recognize previous improvements and upgrades that had a positive impact on energy efficiency.
REQUIREMENTS
Create an inventory of all the energy improvements and upgrades undertaken to improve their energy efficiency prior to the initial performance review.
This credit is only applicable to the first completed performance review. Subsequent reviews would refer to SAM Credits 3.2 Utility Meter Data and 3.4 Optimize Energy Performance.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
A point will be awarded for each of the retroactive improvements. Up to 5 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Switched to LED lighting 1
Switched to CFL lighting 1
Utilized energy saving halogen lamps 1
Utilized high efficiency T8s and T5s 1
Provided the use of lighting sensors or timers
1
Organized circuiting of lighting and systems so that individual areas were separately controlled relative to daylight and heating/cooling zones
1
AuOM-59
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Technology/Strategy Points
Provided motion sensors/occupancy sensors in stairs, restrooms, storage rooms, equipment rooms and office space
1
Optimized lighting controls for energy savings and function
1
Provided high-efficiency motors and variable-speed pumping systems
1
Utilized ENERGY STAR furnaces, exhaust fans, ceiling fans, and air conditioners
1
Standard Practice
None
Recommended Practice
None
Best Available Practice
None
AuOM-60
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.4.1 Optimize Energy Performance: Lighting Power
1 to 5 Points
INTENT
Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
For interior facility lighting, reduce connected lighting power density below that allowed by ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda1) using either the space-by-space method or by applying the lighting power allowance to the project area.
OR
For non-facility/non-aviation exterior lighting applications, a baseline energy use shall be calculated assuming a conventional 400-watt lamp is used for each fixture, except for low-mast applications or covered areas where a 250-watt lamp is applicable. This benchmark standard shall assume that the lamps run without lighting controls such as timers and motion sensors. Light sensors, however, should be taken into account. To meet the requirements of this credit, reduce lighting power for these applications based on the benchmark standard. Non-facility/non-aviation exterior lighting applications may include the following:
Roadways Surface Parking Lots Covered Parking Garages
OR
For aviation lighting, exceed the minimum FAA specifications. The benchmark calculations shall assume that conventional lighting is used throughout the project area and that the calculation must be based on annual energy consumption that takes into account seasonal climate data.
1 Project teams wishing to use ASHRAE approved addenda for the purposes of this credit may do so at their discretion. Addenda must be applied consistently across all SAM credits.
AuOM-61
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Any combination of points earned for reducing energy usage below the standards documented above are as follows (may not exceed 5 points in total).
SAM Credit Lighting Power Density Reduction Below the Standard Points
3.4.1.1 15% 1
3.4.1.2 20% 2
3.4.1.3 25% 3
3.4.1.4 30% 4
3.4.1.5 35% 5
Examples: A 15% reduction in facilities lighting power (1 point) in addition to a 25% reduction in parking lot lighting power (3 points) would total four points earned for this credit. A 25% reduction in facilities lighting power (3 points) in addition to a 25% reduction in parking lot lighting power (3 points), totaling six points, would earn the maximum five points for this credit. SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Ensure the connected lighting power maximizes energy performance. Consider a computer simulation model to assess the performance and identify the most cost-effective energy measures.
Standard Practice
None
Recommended Practice
Consider the following:
Use a computer simulation model to assess energy performance and identify the most cost effective energy measures
Provide energy efficient lighting systems including LED, fluorescent lighting, solar lighting and the use of lighting sensors or timers
Use LED lighting, wherever applicable Use CFL lighting, wherever applicable Utilize energy saving halogen lamps Utilize high efficiency T8s and T5s
Best Available Practice
None
AuOM-62
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.4.2 Optimize Energy Performance: Lighting Control
1 to 3 Points
INTENT
Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
Up to 3 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Daylight controls for daylight areas: Install daylight responsive controls in all regularly occupied daylit spaces within 15 feet of windows and under skylights. Daylight controls must switch or dim electric lights in response to the presence or absence of daylight illumination in the space
1
Daylight controls for 50% of the lighting load: Install daylight responsive controls for 50% or more of the connected lighting load and demonstrate that 50% of the connected lighting load is daylight responsive. Daylight controls must switch or dim electric lights in response to the presence or absence of daylight illumination in the space.
1
Occupancy Sensors: Install occupancy sensors for 75% of the connected lighting load.
1
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Ensure the connected lighting power maximizes energy performance.
Standard Practice
None
AuOM-63
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Recommended Practice
Provide energy efficient lighting systems including LED, fluorescent lighting, solar lighting and the use of lighting sensors or timers
Organize circuiting of lighting and systems so that individual areas may be separately controlled relative to daylight and heating/cooling zones
Provide motion sensors/occupancy sensors in stairs, restrooms, storage rooms, equipment rooms and office space unless life safety is compromised
Optimize lighting controls for energy savings and function
Best Available Practice
Integrate lighting systems with Building Automation System
AuOM-64
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.4.3 Optimize Energy Performance: HVAC
3 to 6 Points
INTENT
Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
OPTION 1 –
Implement one or both of the following strategies:
Equipment Efficiency: (3 pts) Install heating, ventilation and air conditioning (HVAC) systems that comply with the efficiency requirements outlined in the New Buildings Institute’s Advanced Buildings™ Core Performance™ Guide Sections 1.4: Mechanical System Design, 2.9: Mechanical Equipment Efficiency and 3.10: Variable Speed Control.
Appropriate Zoning and Controls: (3 pts) Zone spaces to meet the following requirements:
o Every solar exposure must have a separate control zone o Interior spaces must be separately zoned o Private offices and special occupancies (conference rooms, kitchens, etc.)
must have active controls capable of sensing space use and modulating the HVAC system in response to demand
OR
OPTION 2 –
Reduce design energy cost compared with the energy cost budget for regulated energy components described in the requirements of ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda).
AND
PATH 1 (3 pts) Demonstrate that HVAC system component performance criteria used for space are 15% better than a system in minimum compliance with ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda).
OR
AuOM-65
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
PATH 2 (6 pts) Demonstrate that HVAC system component performance criteria use for space is 30% better than a system that is in minimum compliance with ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda).
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Ensure the HVAC system components maximize energy performance. Review compliance options to determine the most appropriate approach. Option 1 provides a more prescriptive approach to recognizing energy-efficient HVAC design, while Option 2 is performance based.
Standard Practice
None
Recommended Practice
Provide high-efficiency motors and variable-speed pumping systems. Utilize ENERGY STAR furnaces, exhaust fans, ceiling fans, and air conditioners
Best Available Practice
Evaluate under floor air distribution systems in office-type spaces Evaluate the potential for “green walls” Utilize premium efficiency motors where applicable
AuOM-66
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.4.4 Optimize Energy Performance: Equipment and Appliances
1 to 4 Points
INTENT
Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
For all ENERGY STAR qualified equipment and appliances installed, achieve one of the following percentages by rated power:
SAM Credit ENERGY STAR Qualified Equipment* Points
3.4.4.1 70% 1
3.4.4.2 77% 2
3.4.4.3 84% 3
3.4.4.4 90% 4
*As a percentage of ENERGY STAR eligible equipment Excluded are HVAC, lighting and building envelope products.
This requirement applies to appliance, office equipment, electronics and commercial food service equipment. Excluded are HVAC, lighting and building envelope products.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Select energy-efficient equipment and appliances, as qualified by the EPA’s ENERGY STAR Program (https://www.energystar.gov).
Standard Practice
None
Recommended Practice
Provide high-efficiency motors and variable-speed pumping systems. Provide ENERGY STAR compliant equipment such as:
o Dishwashers o Refrigerators o Water Heater
AuOM-67
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
o Computers o Printers o Copiers o Phones o Televisions o Ice machines o Convection ovens o Combination ovens
Best Available Practice
None
CASE STUDIES
Moving Walkways Boston Logan International Airport – Boston, Massachusetts
Boston Logan International Airport is undergoing tests on energy-efficient moving walkways. The walkways are equipped with EcoStart, which contains a motor efficiency controller that soft starts an electric motor, bringing it from rest to full speed. Once at full speed, the EcoStart monitors the motor and improves its efficiency when operating. Initial test efforts are estimated to conserve approximately 60,000 kilowatt-hours (kWh) per year.
www.automation.com/content/boston-logan-international-airport-saves-energy-on-moving-walks-in-project-with-kone-inc-and-power-efficiency-corporation
Baggage Check-In Building Reno-Tahoe International Airport – Reno, Nevada
The new airport baggage check-in building at Reno-Tahoe International Airport was designed with an efficient HVAC system, in addition to utilization of energy-efficient entryways to reduce heat/cooling loss. This helps the airport monitor and reduce overall energy use.
http://southwest.construction.com/southwest_contractor_projects/2010/1201_InternationalAirport.asp
AuOM-68
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.5 Existing Building Commissioning
1 to 6 points
INTENT
Develop and implement an operation of the building’s major energy-using systems and implement a no to low cost option(s) for optimizing energy performance and a plan to achieve energy savings.
REQUIREMENTS
Conduct one of the following options below – 1 to 2 points
OPTION 1 –
Commissioning Process (1 point) Develop a retrocommissioning or ongoing commissioning plan for the building’s major
energy-using systems Conduct the investigation and analysis phase Document the breakdown of energy use in the building List the operating problems that affect occupants’ comfort and energy use, and develop
potential operational changes that will solve them List the identified capital improvements that will provide cost-effective energy savings
and document the cost-benefit analysis associated with each.
OR
OPTION 2 –
ASHRAE Level II, Energy Audit (2 points) Conduct an energy audit that meets the requirements of ASHRAE Level II, energy
survey and analysis Document the breakdown of energy use in the building Perform a savings and cost analysis of all practical measures that meet the owner’s
constraints and economic criteria, along with a discussion of any effect on operations and maintenance procedures
List the identified capital improvements that will provide cost-effective energy savings and document the cost- benefit analysis associated with each.
AND
Implementation (2 Points) Implement one of the two no- or low-cost operational improvements aforementioned and create a capital plan for major retrofits or upgrades. Provide training for management staff that builds
AuOM-69
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
awareness and skills in a broad range of sustainable building operations topics this could include energy efficiency and building, equipment and systems operations, and maintenance.
Demonstrate the observed and/or anticipated financial costs and benefits of measures that have been implemented.
Update the building operating plan as necessary to reflect any changes in the occupancy schedule, equipment run-time schedule, design set-points, and lighting levels.
AND
Ongoing (2 points) Implement an ongoing commissioning program that includes elements of planning, system testing, performance verification, corrective action response, ongoing measurement, and documentation to proactively address operating problems.
Create a written plan that summarizes the overall commissioning cycle for the building by equipment or building system group. The ongoing commissioning cycle must not exceed 24 months. This plan must include a building equipment list, performance measurement frequency for each equipment item, and steps to respond to deviation from expected performance parameters.
Update the building operating plan and/or systems narrative as necessary to reflect any changes in the occupancy schedule, equipment run-time schedule, design setpoints, lighting levels, or system specifications.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Based on the building operating plan and systems narrative:
Confirm that all building systems and equipment are functioning as appropriate according to the equipment schedule
Conduct testing and analysis to ensure that building systems and equipment are functioning correctly
Identify opportunities to make no- or low-cost capital improvements to enhance building performance
Implement no- and low-cost operational improvements that will immediately enhance building performance. Develop a capital plan for the completion of any major retrofits identified through the investigation and analysis phase.
Develop an ongoing commissioning program that addresses the ongoing changes and maintenance needs in an existing building.
AuOM-70
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Standard Practice
Commissioning Agents are typically engaged to conduct fundamental commissioning for buildings.
Recommended Practice
Review the design intent and the basis of design documentation Incorporate commissioning requirements into the construction documents
Develop and utilize a commissioning plan Verify installation, functional performance, training, operations and maintenance
documentation Complete a commissioning report Provide the owner with a single manual that contains the information required for re-
commissioning systems Engage a commissioning team that does not include individuals directly responsible for
project design or construction management to evaluate both building and site systems as part of the commissioning plan
Priority Systems - high energy consuming systems: o Central Building Automation system o All HVAC system equipment o Lighting controls and sensors o Site Lighting o Refrigeration systems o Vertical Transport o Building Envelope o Baggage handling systems (included in process loads: to promote energy
savings, use the exceptional calculation method described in ANSI/ASHRAE/IESNA 90.1-2010 G2.5)
o Information Technology Systems - IT (included in process loads: to promote energy savings, use the exceptional calculation method described in ANSI/ASHRAE/IESNA 90.1-2010 G2.5)
Lower Priority Systems – low energy consuming system: o Emergency Power Generators and Automatic Transfer Switching o Uninterruptible Power Supply systems o Life Safety systems Fire protection Fire alarm, Egress pressurization o Lightning Protection o Domestic and Process water pumping and mixing systems o Equipment sound control systems o Data and Communication systems o Paging systems o Security systems o Irrigation systems
AuOM-71
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
o Plumbing o Illuminated guidance signage
For Runways, Civil/Stormwater and Roadways/Rail projects this scope should include the following project components:
o For support and ancillary buildings include all of the applicable systems and assemblies noted above
o Runway lighting and illuminated signage o Runway NAVAIDS o Site lighting systems o Traffic signals o Stations (e.g., pump stations, lift stations, drainage pumps) o Oil/water separators
Best Available Practice
None
CASE STUDIES
STAR Program Metropolitan Airports Commission – Minneapolis, Minnesota
Minneapolis – St. Paul International Airport recently launched the Stewards of Tomorrow’s Airport Resources (STAR) initiative. Airport operators develop and implement sustainable solutions that address long-term environmental, operational, financial and social needs. Goals include minimizing impacts to air quality, reducing waste reduction and hazardous materials use, as well as developing alternative energy programs. www.enviro.aero/MSPSTAR.aspx
AuOM-72
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.6.1 Performance Measurement: Building Automation System
1 point
INTENT
Provide information to support the ongoing accountability and optimization of building energy performance and identify opportunities for additional energy-saving investments.
REQUIREMENTS
Have in place a computer-based building automation system (BAS) that monitors and controls key building systems that include, but are not limited to:
Heating Cooling Ventilation Lighting
Have a preventive maintenance program in place that ensures BAS components are tested and repaired or replaced according to the manufacturer’s recommended interval. Demonstrate that the BAS is being used to inform decisions regarding changes in building operations and energy-saving investments.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Install and/or maintain a BAS to automatically control key building systems. Ensure that relevant staff is adequately trained to use the system, analyze output, make necessary adjustments, and identify investment opportunities to improve energy performance.
Standard Practice
None
Recommended Practice
Install a Building Automation System
Best Available Practice
None
AuOM-73
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDY
New Building Automation System Kunming New International Airport – Kunming, Yunnan, China
As of December 2008, the Kunming New International Airport has planned to install Honeywell’s Trend Building Automation System to integrate its various control systems, including operation management system, terminal operation system, and parking management system. The adoption of the system enables effective data sharing among the airport’s management systems and increases the airport’s efficiency at a lower cost.
http://www.honeywellnow.com/2009/12/28/honeywells-trend-building-automation-system-to-be-adopted-in-kunming-new-international-airport/
AuOM-74
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.6.2 Performance Measurement: System Level Metering
1 to 2 points
INTENT
Provide accurate energy use information to support energy management and identify opportunities for additional energy-saving improvements.
REQUIREMENTS
Have a developed breakdown of energy use in the building, either through SAM Credits 3.4.1 Optimize Energy Efficiency: Lighting Power, 3.4.2 Optimize Energy Efficiency: Lighting Controls, 3.4.3 Optimize Energy Performance: HVAC or 3.4.4 Optimize Energy Performance: Equipment and Appliances, or by using energy bills, spot metering or other metering to determine the energy consumption of major mechanical systems and other end-use applications. This analysis of major energy use categories must have been conducted within two years prior to the date of application for SAM O&M certification.
Based on the energy use breakdown, employ system-level metering covering at least 40% or 80% of the total expected annual energy consumption of the building. Permanent metering and recording are required. All types of submetering are permitted.
Up to 2 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Demonstrate that system-level metering is in place covering at least 40% of the total expected annual energy consumption of the building. Further, at least one of the two largest energy use categories from the breakdown report must be covered to the extent of 80% or more (i.e., if energy use in the two largest categories is each 100 BTUs/year, at least 80 BTUs/year in one of them must be metered).
1
Demonstrate that system-level metering is in place covering at least 80% of the total expected annual energy consumption of the building. Further, at least two of the three largest energy use categories from the breakdown report must be covered to the extent of 80% or more.
2
Meters must be calibrated within the manufacturer’s recommended interval if the building owner, management organization or tenant owns the meter. Meters owned by third parties (e.g., utilities or governments) are exempt.
AuOM-75
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Identify, through an energy audit, building commissioning or some other means, how the building systems are consuming energy. Based on the energy use profile, develop a metering plan to capture the most significant building loads. Use output from the meters to identify any changes in consumption and opportunities for energy- saving improvements. Have a plan for periodically inspecting the data.
Standard Practice
None
Recommended Practice
Independently meter separate tenants and CDA facilities where applicable Sub-meter building systems by process, floor or location
Best Available Practice
None
CASE STUDY
Energy Efficiency Software Mineta San Jose International Airport – San Jose, California
Deployment of high-performance energy efficiency software to manage the airport's HVAC system, coupled with an addition and an upgrade to the facility's array of chillers, have yielded more than $35,000 in savings from utility costs in the first five months of operation. The measures have also saved 235,000 kilowatt hours (kWh) of electricity and reduced the carbon footprint for the facility by almost 300,000 pounds of CO2 during the same period, according to Optimum Energy, the provider of the software solution, and the airport.
www.greenbiz.com/blog/2009/04/10/green-flies-high-california-airport
AuOM-76
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.7 On-Site and Off-Site Renewable Energy
1 to 6 points
INTENT
Encourage and recognize increasing levels of on-site and off-site renewable energy to reduce environmental impacts associated with fossil fuel energy use.
REQUIREMENTS
OPTION 1 –
Over the performance period, meet some or all of the building’s total energy use with on-site or off-site renewable energy systems. Points are earned according to the following table, which shows the percentages of building energy use met by renewable energy over the performance period.
Off-site renewable energy sources are defined by the Center for Resource Solutions (CRS) Green-e-products certification requirements, or the equivalent. Green power must be procured from a Green-e-certified power marketer or a Green-e-accredited utility program, or through Green-e-certified tradable renewable energy certificates (RECs), or the equivalent. For on-site renewable energy that is claimed for this credit, the associated environmental attributes must be retained or retired and cannot be sold.
SAM Credit On-Site Renewable Energy Off-Site Renewable Energy Points
3.7.1 3% or 25% 1
3.7.2 4.5% or 37.5% 2
3.7.3 6% or 50% 3
3.7.4 7.5% or 62.5% 4
3.7.5 9% or 75% 5
3.7.6 12% or 100% 6
Up to the six-point limit, any combinations of individual actions are awarded the sum of the points allocated to those individual actions. For example, one point would be awarded for implementing three 3% of on-site renewable energy, and two additional points would be awarded for meeting 37.5% of the building’s energy load with renewable power or certificates over the performance period. Projects must submit proof of a contract to purchase RECs for a minimum of two years and must also make a commitment to purchase RECs on an ongoing basis beyond that.
OR
AuOM-77
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
OPTION 2 – Prescriptive Method
Install alternative renewable energy technologies on-site by using any of the following technologies for one point each:
Wind Power: o Generate on-site electricity using wind turbines, horizontal or vertical that
generate 0.5 kW or greater Photovoltaics (solar electric)
o Use the system to generate electricity that has a capacity of 0.5 kW or greater
SUBMITTALS
Include descriptive narrative and calculation in the SAM Checklist.
TECHNOLOGY/STRATEGY
Maintain the use of on-site nonpolluting renewable technologies to contribute to the total energy requirements of the building. Consider and employ solar, geothermal, wind, biomass (other than unsustainably harvested wood), and biogas technologies.
Purchase renewable energy or tradable renewable energy certificates to meet some or all of the building’s energy requirements. Review the building’s electrical consumption trend. Research power providers in the area and select a provider that guarantees that a portion of its delivered electric power is derived from net nonpolluting renewable technologies. If the project is in an open-market state, investigate green power and power marketers licensed to provide power in that state. Grid power that qualifies for this credit originates from solar, wind, geothermal, biomass, or low-impact hydro sources.
Standard Practice
Solar powered signage Solar powered RPU for weather sensors Solar powered obstruction and barricade lighting Solar thermal water heating has been used at a number of locations, such as the ARFF
Station #2, which has a system that provides hot water for up to 18 full-time occupants
Recommended Practice
Purchase renewable energy or tradable renewable energy certificates to meet some or all of the building’s energy requirements
Best Available Practice
The following technologies should be considered for any applicable projects:
Roof-mounted or building integrated photovoltaic panels Electricity generation using bio-fuels (untreated wood waste, agricultural crops or waste,
landfill gas) Electricity generating wind turbines
AuOM-78
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Solar-thermal water or air heating Geothermal heating systems Geothermal electrical systems
CASE STUDIES
Wind Turbines Boston Logan International Airport – Boston, Massachusetts
A fleet of miniature wind turbines at Boston Logan International Airport, each 6-foot-tall, placed at the edge of the rooftop of the airport's headquarters, is affixed at a unique angle to capture the winds that gust through Boston Harbor and climb the building's walls. The 20 turbines, installed in July 2008, are expected to generate about 100,000 kilowatt-hours annually, equal to 3% of the building's energy needs.
www.leedbuilding.org/News/USGBCInTheNewsDetails.aspx?ID=3829
Hangar 25 Bob Hope Airport – Burbank, California
Hangar 25 at Bob Hope Airport in Burbank, California, is a $17 million structure designed to be a model of green construction and was built for what a traditional aircraft hangar would cost, according to Andy Meyers, president of Shangri-La Construction. The hangar features solar panels, skylights, artificial grass, low-flush toilets, and massive aerating fans. Situated on a former industrial lot with a cement slab, the hangar property now houses a state-of-the-art green aviation hangar minimizing the 51,000-square-foot building's carbon footprint. Avjet Corp. is the building owner. The building received a Platinum LEED® certification. In addition to providing power to run the tools and machines to maintain the planes, the energy from the solar panels on the roof powers the building's offices, copiers, computers and coffee machines. The building generates 110% of the energy it needs and then gives the surplus energy back to the municipal grid. Grates at the building's entrance scrape off contaminants under shoes. No toxic chemicals fill the fire suppression system. The concrete floor has no chemical polymers. In the office area, all of the cabinets are made of Plyboo®, a type of bamboo with a water-based finish.
www.usgbc.org/News/USGBCInTheNewsDetails.aspx?ID=3899
Author: Jerry Berrios, Contra Costa Times, December 10, 2008
See Also:
http://3030nclybournavenue.com/files/hangar_project_summary.pdf www.huffingtonpost.com/paige-donner/greening-hollywood-jet-ha_b_150102.html
AuOM-79
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Solar Power System Denver International Airport ‐ Denver, Colorado
Denver’s second large-scale solar power system became operational in December 2009; this new 1.6 MW Sharp solar power array powers the airport’s fuel-storage and distribution facility. Just a year prior in 2008, the airport introduced the first solar power array that consisted of a two megawatt solar panel system designed to generate over three million kilowatt hours of clean electricity annually. These cost-effective energy systems were developed by a public-private partnership utilizing tax credits and incentives. This initiative shows that airports can embrace renewable energy in a financially viable way and increase the overall sustainability of their operations.
http://files.sharpusa.com/Downloads/Solar/CaseStudy/sol_dow_Denver_Airport_Case_Study.pdf
And
http://www.solarnovus.com/index.php?option=com_content&view=article&id=404:16mw-solar-project-completed-at-denver-international-airport&catid=41:applications-tech-news&Itemid=245
AuOM-80
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.8 Enhanced Refrigerant Management
1 point
INTENT
Reduce ozone depletion and support early compliance with the Montreal Protocol (an international agreement designed to protect from ozone depletion) while minimizing direct contributions to global warming.
REQUIREMENTS
Choose one of the following options:
OPTION 1 –
Do not use conventional refrigerants in HVAC&R systems. Naturally ventilate and/or use natural refrigerants such as:
Water Carbon dioxide Propane Ammonia
OR
OPTION 2 –
Use only Hydrofluorocarbons (HFC) Small HVAC units (defined as containing less than 0.5 lbs of refrigerant), and other equipment such as standard refrigerators, small water coolers, and any other cooling equipment that contains less than 0.5 lbs of refrigerant, are not subject to the requirements of this credit.
AND
Do not install fire suppression systems that contain ozone-depleting substances (CFCs, HCFCs or Halons).
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Operate the Facility without mechanical cooling and refrigeration equipment. Where mechanical cooling is needed, use for the refrigeration cycle base building HVAC and refrigeration systems that minimize direct impact on ozone depletion and global warming. Select HVAC&R replacement equipment with reduced refrigerant charge and increased equipment life. Maintain equipment to prevent leakage of refrigerant to the atmosphere. Use fire-suppression systems that do not contain HCFCs or halons.
AuOM-81
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Standard Practice
None
Recommended Practice
Use only Hydrofluorocarbons (HFC)
Best Available Practice
Use natural refrigerants (water, carbon dioxide, ammonia, propane) where possible, in order to minimize ODPs and GWPs
AuOM-82
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
3.0 ENERGY & ATMOSPHERE
3.9 Emissions Reduction Reporting
1 to 4 Points
INTENT
Document the emissions reduction benefits of building efficiency measures to better track CDA’s achievements in climate-altering fossil fuel consumption and resultant emissions.
REQUIREMENTS
Identify building performance parameters that reduce conventional energy use and emissions, quantify those reductions, and report them to a formal tracking program:
Track and record emissions reductions delivered by energy efficiency measures, operational improvements, renewable energy and other building emissions reduction measures, including reductions from the purchase of renewable energy credits
Report emissions reductions using a third-party voluntary reporting or certification program (e.g., EPA Climate Leaders, ENERGY STAR or World Resources Institute (WRI)/World Business Council Sustainable Development (WBCSD) protocols)
Report emissions based on the international framework used to describe greenhouse gas emissions. The World Resources Institute’s Greenhouse Gas Reporting Protocol divides emissions into three categories:
SAM Credit 3.9.1: Emissions are those Green House Gas’ (GHG) that are directly released on-site, such as combustion of fuels and the application of fertilizers on-airport. (1 point)
SAM Credit 3.9.2: Emissions result from energy purchased from off-site sources where fuels are burned. (1 point)
SAM Credit 3.9.3: Emissions include all other GHG-producing activities associated with the activities of an institution, including (2 points):
Commuting Air travel for aviation management activities Waste disposal Embodied emissions from the extraction, production, and manufacturing of purchased
goods
AuOM-83
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
CDA encourages tracking all project achievements to address all significant types of pollutants reduced by energy efficiency. Measure the following for:
SAM Credit 3.9.1
Stationary fuel combustion (natural gas for heating) Mobile fuel consumption (vehicle fleet) Leakage (refrigeration, air conditioning, etc.) Fertilizers
SAM Credit 3.9.2
Electricity generated off-site.
SAM Credit 3.9.3
Commuting Travel Waste disposal Embodied emissions (extraction, production, & transportation of consumed goods) Food Office supplies Construction materials Miscellaneous (coffee mugs, t-shirts, etc.).
Standard Practice
None
Recommended Practice
Install continuous metering equipment for the following end-uses: o Lighting systems and controls o Constant and variable motor loads o Variable frequency drive (VFD) operation o Chiller efficiency at variable loads (kW/ton) o Cooling load o Air and water economizer and heat recovery cycles o Air distribution static pressures and ventilation air volumes o Boiler efficiencies o Building-related process energy systems and equipment
AuOM-84
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
o Indoor water risers and outdoor irrigation
Develop a Measurement and Verification plan that incorporates the monitoring information from the above end-uses and is consistent with Option B, C or D of the 2001 International Performance Measurement & Verification Protocol (IPMVP) Volume I: Concepts and Options for Determining Energy and Water Savings
Investigate whether these facilities will be included in the City of Chicago’s Global Building Monitoring System
Consider the recommendations included in the Chicago Climate Action Plan
Best Available Practice
Draft a Measurement & Verification Plan to apply during building operation that compares predicted savings to those achieved.
CASE STUDY
Emissions Reduction Strategy Boston Logan International Airport – Boston, Massachusetts
Boston Logan initiated the voluntary Air Quality Initiative (AQI) implemented in 2001 with the goal of maintaining levels of nitrogen dioxide emissions associated with the airport at or below the levels from 1999. It is a 15-year program that has four primary commitments:
Expand on existing initiatives at Logan. View the Air Quality Initiative Inventory Tracking of Nitrogen Dioxide Emissions for information on programs in place at place at Logan Airport when the Air Quality Initiative was developed
Retire emissions credits giving priority to mobile sources in order to maintain nitrogen dioxide emissions at or below 1999 levels
Report the status and progress in Massport’s Environmental Data Report (EDR) and Environmental Status and Planning Report (ESPR)
Continue working to decrease air emissions from aviation sources at both a national and international level.
www.massport.com/environment/environmental_reporting/Air%20Quality/EmissionsReductionStrategies.aspx
AuOM-85
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
4.0 MATERIALS & RESOURCES
4.1.1 Waste Management: Waste Stream Audit
3 Points
INTENT
Facilitate the reduction of ongoing waste and toxins generated by building occupants and building operations that are hauled to and disposed of in landfills or incineration facilities.
REQUIREMENTS
Conduct a waste stream audit of the building’s, tenant’s and division’s entire ongoing consumables waste stream (not durable goods or construction waste for facilities alterations and additions). Use the audit’s results to establish a baseline that identifies the types of waste making up the waste stream and the amounts of each type by weight or volume. Identify opportunities for increased recycling and waste diversion. The audit must be conducted during the performance period.
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Understanding waste production patterns in a building is an important first step to waste reduction. Work with your waste hauler or service provider to collect and analyze information on the amounts and types of waste generated by the facility.
Standard Practice
None
Recommended Practice
Use the results of the waste audit as a baseline for evaluating future recycling efforts. Analyze the results of the audit and identify targets for expanding the recycling program. Evaluate the capturing and recycling of specific wastes
Best Available Practice
Create a Five Year Action Plan outlining waste reduction methods that will be undertaken in the coming years
AuOM-86
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDIES
Airport Economizes on Food Residuals Collection Costs Portland International Airport – Portland, Oregon
In January 2002, Portland International Airport conducted two waste characterization studies in order to gain a better understanding of its composition. The studies encompassed one hotel and two flight kitchens and revealed that 35 percent of their waste stream was made up of compostable materials. The waste audit concluded that the waste stream contained mostly coffee grounds, produce, baked goods, and prepared foods such as rice and noodles. From these waste studies, airport staff was able to determine equipment needs and food residuals diversion potential of the partner businesses.
As a result of these studies, the airport implemented a full-time composting program. PDX, along with its partners, divert approximately 7 tons of food waste every week. As of June 2011, the airport has 20 airport businesses, flight kitchens, and hotels participating in the program; in 2010, the program diverted an average of nearly 26 tons per month. Additionally, PDX developed, tested and implemented one of the first public food waste collection stations of any airport in the U.S. In Concourse D, PDX established a set of waste receptacles allowing its passengers to dispose of their leftover burgers, fries, cookies and salads to a composting facility. The station also features a drain for ice and liquids, trays, co-mingled recycling and trash.
http://www.biocycle.net/2005/08/airport-economizes-on-food-residuals-collection-costs/
Waste Audit and Composting Program San Francisco International Airport – San Francisco, California
In 2009, SFO conducted a $15,000 waste audit to determine the percentages of recyclable and compostable materials in their waste stream. The study indicated that over 90% of the waste stream was comprised of compostable materials and recyclables. As a result, two pilot projects were conducted on source separation and food waste composting. The airport now maintains a full-time composting program.
AuOM-87
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
4.0 MATERIALS & RESOURCES
4.1.2 Waste Management: Waste Reduction
2 to 6 Points
INTENT
Facilitate the reduction of waste and toxins generated from the use of products by building occupants and building operations that are hauled to and disposed of in landfills or incineration facilities.
REQUIREMENTS
Currently employed strategies that reduce the waste stream compared to baseline calculated in SAM Credit 4.1.1 Waste Management: Waste Stream Audit.
The waste reduction percentages for each point threshold are as follows:
SAM Credit Waste Reduction Points
4.1.2.1 10% 2
4.1.2.2 20% 3
4.1.2.3 30% 4
4.1.2.4 40% 5
4.1.2.5 50% 6
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Maintain a waste reduction and recycling program that addresses materials with a low cost per unit that are regularly used and replaced through the course of business, and maximize the diversion of materials that are also generated by facility alterations and improvements from disposal of landfills and incineration facilities. These materials include, but are not limited to:
Paper Toner cartridges Glass Plastics Cardboard and old corrugated cardboard Food waste Metals Batteries
AuOM-88
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Electronics Office equipment (computers, monitors, copiers, printers, scanners, and fax machines) Appliances (refrigerators, dishwashers, and water coolers) External power adapters Televisions Other audiovisual equipment
Actual diversion performance must be verified at least annually. Furniture, fixtures, and equipment (FF&E) are not considered base building elements and are excluded from this credit. Mechanical, electrical, and plumbing components and specialty items such as elevators are also excluded
Maintain waste management policies applicable to any facility alterations and additions occurring on the site. Identify licensed haulers and processors of recyclable materials. Identify markets for salvaged materials. Employ deconstruction, salvage, and recycling strategies and processes. Document the cost for recycling, salvaging, and reusing materials. Make source reduction on the job site an integral part of the plan to reduce solid waste. Investigate salvaging or recycling lighting fixture pans when retrofitting.
Standard Practice
Recycling of conventional products such as, but not limited to: paper, glass, etc. Battery and printer cartridge recycling programs are already in place in various locations.
Recommended Practice
In addition to the standard practice include, but not limited to: light bulbs, batteries, electronics, landscape waste, automotive fluids, etc.
Have a reuse or resale program for furniture and electronic goods Create a coordinated waste reduction program that makes used goods available to other
entities Allow private salvage companies to access the site prior to demolition to avoid removal
costs Establish waste reduction goals and specify construction and demolition waste
management policies prior to demolition
Best Available Practice
Establish a program that diverts waste streams to find an on-site use Develop a waste tracking system and have a designated sort area for all waste streams
AuOM-89
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDIES
Sea-Tac Airport Recycling Program Seattle-Tacoma Airport – Seattle, Washington
After expanding their bottle and can collection, the Sea-Tac added office paper collection. Based on the initial success, Sea-Tac has continued to grow their program, which now includes printer cartridges, batteries and coffee grounds.
www.epa.gov/osw/conserve/rrr/rogo/documents/seatac.pdf
Recycling Program Denver International Airport – Denver, Colorado
In 2008, single-stream recycling was implemented and the airport placed 160 new containers placed through the common terminal areas. By 2010, the airport reduced the amount of waste per passenger sent to the landfill from 0.64 pounds per passenger to 0.41 pounds per passenger. The program includes participants from the Department of Aviation offices, tenants, food concessionaires, and the airlines. The airport has recycled the following items:
714 large batteries 2,030 pounds of other batteries 23,571 pounds of electronics 6,475 pounds of fluorescent bulbs 110,500 pounds of restaurant grease 1,375 gallons of antifreeze 819 tires 17,307 gallons of used oil
http://business.flydenver.com/community/enviro/documents/annualReport2009.pdf
Call2Recycle Chicago Department of Aviation – Chicago, Illinois
Call2Recycle is a free rechargeable battery and cellphone collection program that the Chicago Department of Aviation uses on a quarterly basis. Collection locations are available throughout the airport where employees deposit batteries and cellphones. .This program diverts solid waste from the landfill and disposes of the items in a sustainable manner. Following CDA’s example, multiple tenants have expressed interest in joining the program.
http://www.call2recycle.org/
AuOM-90
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Semi-Annual Tenant Cleanup Events Portland International Airport – Portland, Oregon Every six months, the PDX waste minimization team hosts tenant cleanup events where vendors and concessionaires gather material to either be broken down for recycling, salvaged or reused – a “swap meet for the airport tenant community.” In spring 2011, the team brought in an outside consultant to discuss waste minimization strategies and share reuse opportunities; through social networking and “speed-dating” activities, airport businesses are trading, selling or giving away items that might have once ended up in a landfill.
www.portofportland.com/PDFPOP/Env_WstMgtPrgm_Spring2008.pdf Waste Management Brussels International Airport – Brussels, Belgium
Brussels Airport has two waste collection centers for waste created in public areas, shops, restaurants and offices. They also maintain two collection centers for waste produced by technical facilities and cargo companies. At these collection points, trained staff records the flow of waste as well as supervise and assist with sorting.
http://www.brusselsairport.be/en/cf/res/pdf/env/en/env2011en
AuOM-91
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
4.0 MATERIALS & RESOURCES
4.2 Local/Regional Materials
1 to 3 Points
INTENT
Increase demand for materials and products that are extracted, harvested or recovered, as well as manufactured within the region, thereby supporting the local economy and the use of indigenous resources and reducing the environmental impacts resulting from transportation.
REQUIREMENTS
Demonstrate that materials and products purchased within the last year were obtained from local and regional sources.
Using materials or products that have been extracted, harvested or recovered, as well as manufactured, within 500 miles of the project site for a minimum of 10% or 20% (based on cost) of the total materials value. If only a fraction of a product or material is extracted/harvested/recovered and manufactured locally, then only that percentage (by weight) shall contribute to the regional value. An additional point can be achieved if 50% of the materials are extracted, harvested, or recovered, as well as manufactured, within 250 miles of the project site. The minimum percentages of local/regional materials for each point threshold are as follows:
SAM Credit Local/Regional Materials Points
4.2.1 10% 1
4.2.2 20% 2
4.2.3 50% within 250 miles 3
SUBMITTALS
Include descriptive narrative and calculations in SAM Checklist.
TECHNOLOGY/STRATEGY
Establish an ongoing goal for locally sourced materials, and identify materials and material suppliers that can achieve this goal. Quantify the total percentage of local materials used by cost within the performance period. The product purchases shall follow Appendix AP-A – Green Product Listing.
Standard Practice
The central location of Chicago makes many materials and products readily available Due to sole sourcing and limited availability, some specialty items may not meet the 500
mile criterion
AuOM-92
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Recommended Practice
Identify all material and product purchases used on an annual basis for daily operations that are extracted, processed, or manufactured within 500 miles of Chicago. Materials that may contribute toward this goal include but are not limited to: plumbing and electrical supplies, landscaping materials, office supplies, automotive supplies, furniture, computers, appliances, cleaning products, etc.
Best Available Practice
None
CASE STUDY
Local and Regional Materials Double Eagle II Airport – Albuquerque, New Mexico
Over 20% of building materials used on Double Eagle were extracted, processed, and manufactured regionally within 500 miles of the site. This supports local economies and encourages the use of indigenous resources reducing environmental impacts from transportation.
www.cabq.gov/airport/double-eagle-ii-airport-leadership-in-energy-and-environmental-design-leed
AuOM-93
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 INDOOR ENVIRONMENTAL QUALITY
5.1 Prerequisite 1 – Outdoor Air Introduction and Exhaust Systems
Required
INTENT
Establish minimum indoor air quality (IAQ) performance to enhance indoor air quality in buildings, thus contributing to the health and well-being of the occupants.
REQUIREMENTS
Choose one of the following options:
OPTION 1 –
Modify or maintain each outside air intake, supply air fan, and/or ventilation distribution system to supply at least the outdoor air ventilation rate required by ASHRAE 62.1—2010Ventilation Rate Procedure under all normal operating conditions. OR
OPTION 2 –
If meeting ASHRAE 62.1—2010ventilation rates is infeasible because of the physical constraints of the existing ventilation system, modify or maintain the system to supply at least ten cubic feet per minute (cfm) of outdoor air per person under all normal operating conditions.
Demonstrate through design documentation, measurements, or other evidence that the current system cannot provide the flow rates required by ASHRAE 62.1—2010under any operating condition even when functioning properly.
Each air-handling unit in the building must comply with either Option 1 or Option 2 above. If some air- handling units can provide the outside airflow required by ASHRAE 62.1—2010and others cannot, those that can must do so. Buildings that cannot provide at least ten cfm per person of outside air at each air-handling unit under all normal operating conditions cannot earn this prerequisite.
Additionally, meet all the requirements below:
Show compliance with the applicable requirement above (Option 1 or Option 2) through measurements taken at the system level (i.e., the air-handling unit). For variable air volume systems, the dampers, fan speeds, etc. must be set during the test to the worst-case system conditions (minimum outside airflow) expected during normal ventilation operations. Each air handler must be measured; sampling of air handlers is prohibited.
Implement and maintain an HVAC system maintenance program to ensure the proper operations and maintenance of HVAC components as they relate to outdoor air introduction and exhaust.
Test and maintain the operation of all building exhaust systems, including bathroom, shower, kitchen, and parking exhaust systems.
AuOM-94
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Conduct a visual inspection of outside air vents and dampers and remove any outside air vent or louver obstructions that restrict full outside air capacity from entering the distribution system. Conduct airflow monitoring to document outside air cubic feet per minute. Compare measured flow with designed flow for each unit.
Standard Practice
None
Recommended Practice
Conduct airflow monitoring to document outside air cubic feet per minute. Compare measured flow with designed flow for each unit
Best Available Practice
Monitor and adjust outside air flow using a Building Automation System (BAS)
CASE STUDY
Metasys System Toronto Pearson International Airport – Toronto, Ontario
Maintaining comfort is challenging in a facility with large open spaces, glass exteriors and virtually constant in-and out traffic. The HVAC system throughout the terminals and ancillary facilities, including the parking structures, is controlled by the Metasys system, which provides a single-seat interface for monitoring and regulating multiple functions. This system operates on a campus wide-area network (WAN) configured as a dual-redundant fiber optic ring. Management and other authorized personnel can access the system from a central workstation or from their offices and from off-site, by way of the airport intranet.
http://www.johnsoncontrols.com/content/dam/WWW/jci/be/case_studies/Toronto_Airport__08.pdf
AuOM-95
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 INDOOR ENVIRONMENTAL QUALITY
5.2 Prerequisite 2 – Environmental Tobacco Smoke (ETS) Control
Required
INTENT
Prevent or minimize exposure of occupants, indoor surfaces, and ventilation air distribution systems to Environmental Tobacco Smoke (ETS).
REQUIREMENTS
Prohibit smoking in the building and designate exterior smoking areas at least 25 feet from building entries, outdoor air intakes and operable windows.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Prohibit smoking in the building or provide negative-pressure smoking rooms
Standard Practice
The State of Illinois prohibits smoking in almost all public spaces and workspaces The Chicago City Code Section 7-32-010 prohibits smoking within 15-feet of entry ways
Recommended Practice
None
Best Available Practice
None
AuOM-96
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 INDOOR ENVIRONMENTAL QUALITY
5.3 High Performance Cleaning
2 Points
INTENT
Reduce the exposure of occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, and the environment.
REQUIREMENTS
Points are achieved for doing all of the following, as applicable:
Have in place during the performance period a high performance cleaning program that addresses the following:
Purchase of sustainable cleaning and hard floor and carpet care products and equipment meeting the sustainability criteria outlined in SAM Credit 5.6 Green Cleaning. At a minimum, the program must cover the green cleaning materials that are within the CDA Division and tenant’s control.
Establishment of standard operating procedures (SOPs) addressing how an effective cleaning and hard floor and carpet maintenance system will be consistently utilized, managed, and audited.
Development of strategies for promoting and improving hand hygiene, including both hand washing and the use of hand sanitizers.
Development of guidelines addressing the safe handling and storage of cleaning chemicals used within the space, including a plan for managing hazardous spills or mishandling incidents.
Development of requirements for staffing and training of maintenance personnel appropriate to the need of the division or tenant. Specifically address the training of maintenance personnel in the hazards of use, disposal, and recycling of cleaning chemicals, dispensing equipment, and packaging.
Provision for collecting occupant feedback and continuous improvement to evaluate new technologies, procedures, and processes.
SUBMITTALS
Include descriptive narrative in the SAM Checklist outlining details of a written high performance cleaning program.
AuOM-97
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
TECHNOLOGY/STRATEGY
Over the performance period, have in place a high performance cleaning program addressing SOPs, sustainable products and equipment, chemical handling and storage, and staff training. Some additional items to consider include:
Employ cleaning techniques that promote the most efficient use of products such as training on the proper amount of product to use and proper wiping motion for certain tasks
Utilize cleaning techniques that promote the most efficient use of electricity such as working through areas and then turning off the lights in those areas and moving to another section instead of having all the lights on throughout the space for the entire shift
Provide proper training on supply usage such as when to replace paper products and liners as not to throw away usable product. For example, office trash liners that may need emptying but not replacing when possible
Standard Practice
None
Recommended Practice
See Appendix AP-A – Green Product Listing for a listing of products Utilize a High Performance Green Cleaning Program
Best Available Practice
None
CASE STUDY
Green Seal Cleaning Products Chicago Department of Aviation - Chicago, Illinois
Both Chicago airports have implemented the sustainable initiative of using Green Seal certified cleaning products and eliminating the use of aerosol sprays to clean and disinfect airport facilities.
www.explorechicago.org/city/en/about_the_city/green_chicago/green_airport.html
AuOM-98
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 INDOOR ENVIRONMENTAL QUALITY
5.4.1 Indoor Air Quality (IAQ) Best Management Practices: IAQ Management Program
1 to 4 points
INTENT
Enhance indoor air quality by optimizing practices to prevent the development of IAQ problems in indoor spaces, correcting indoor air quality problems when they occur, and maintaining the well-being of the occupants.
REQUIREMENTS
Develop a plan that addresses the following items, where applicable.
Up to 4 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Remodeling and Renovation: Use effective strategies for materials selection and installation such as selection of low emitting and microbial resistant materials and isolate construction activity from occupants
1
Painting: Establish a protocol for painting and ensure that protocol is followed by both in-house personnel and contractors that include the use of low VOC, fast drying paints where feasible, painting during unoccupied hours, and keep lids on paint containers when not in use
1
Integrated Pest Management: See SAM Credit 1.5 Integrated Pest Management and Wildlife Deterrence
1
Shipping and Receiving: Establish and enforce a program to prevent vehicle contaminants from entering the building by preventing idling of vehicles at the loading dock (post signs and enforce the ban), pressurizing the receiving area relative to the outside to ensure that contaminants from the loading area do no enter the building while making company supervisors aware of policy
1
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
The above requirements are based on the EPA Indoor Air Quality Building Education and Assessment Model (I-BEAM), EPA Reference Number 402-C-01-001, December 2002, available at www.epa.gov/iaq/largebldgs/i-beam/index.html.
AuOM-99
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
During the performance period conduct an IAQ audit of the above requirements, where applicable to determine the IAQ status of a given indoor space. Identify and fix problems associated with poor IAQ. Immediately correct problems that can be addressed at no cost. For the remaining problems establish a plan that diagnoses and corrects the issues.
Standard Practice
None
Recommended Practice
Control building’s relative humidity (below 50%) to limit mold and dust mites Exhaust areas of major indoor moisture sources instead of recirculating or dehumidifying
the area Clean wet areas such as showers Remove and dispose of all carpeting, ceiling tiles, and other materials with signs of mold
growth Provide entryways walk off mats, grates and grilles
Best Available Practice
None
CASE STUDIES
Air Quality Hong Kong International Airport – Hong Kong, China
At Hong Kong International Airport (HKIA), they are committed to complying with statutory air quality criteria, understanding and managing their own air emissions and minimizing these where practicable. Amongst other initiatives, HKIA provides the cleanest diesel and gasoline in the airfield area, they are replacing the entire vehicle fleet with electric or fuel efficient/ hybrid vehicles and they have enforced the vehicle idling engine shutdown mandate since June 1st, 2008. Hong Kong International Airport endeavor to maintain a healthy environment for their passengers and staff by monitoring indoor air quality. The air inside Terminal 1 (T1) and Terminal 2 (T2) has received a Good Class certificate from the Environmental Protection Department.
www.hongkongairport.com/eng/csr/environmental-management/air-quality.html
AuOM-100
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Passenger Health and Comfort Indianapolis International Airport – Indianapolis, Indiana
Radiant heating and cooling built into the flooring, along with other ventilation and temperature control features, continuously monitor indoor humidity and air quality. Use of volatile organic compounds (VOCs) and building materials using urea and formaldehyde was strictly limited to help reduce fumes and respiratory irritants for those with asthma and other conditions. Other chemical compounds contributing to ozone depletion were also avoided. Dust control at entryways and isolated use of cleaning products and chemicals to specially ventilated areas help maintain good indoor air quality. Smoking is not allowed inside or outside the airport’s terminal and other facilities.
www.purdue.edu/travel/pdf/NewINDFactSheet.pdf
AuOM-101
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 INDOOR ENVIRONMENTAL QUALITY
5.4.2 Indoor Air Quality Best Management Practices: Outdoor Air Delivery Monitoring
1 point
INTENT
Provide capacity for ventilation system monitoring to help sustain occupants’ comfort and well-being.
REQUIREMENTS
Install permanent, continuous monitoring systems that provide feedback on ventilation system performance to ensure that ventilation systems maintain minimum outdoor rates under all operating conditions.
Sensors must be tested and calibrated at least once every five years or per the manufacturer’s recommendation, whichever is shorter.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Install and maintain permanent ventilation monitoring systems that provide feedback on system performance to ensure minimum ventilation rates.
Standard Practice
None
Recommended Practice
At least 80% of the building’s total outdoor air intake flow serving occupied spaces is monitored
Monitoring system provides feedback to adjust outdoor air flow as needed
Best Available Practice
Outdoor air delivery monitoring is tied to Building Automation System (BAS).
AuOM-102
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 INDOOR ENVIRONMENTAL QUALITY
5.4.3 Indoor Air Quality (IAQ) Best Management Practices: Increased Ventilation
1 point
INTENT
Provide additional outdoor air ventilation to improve indoor air quality (IAQ) for improved occupant comfort, well-being and productivity.
REQUIREMENTS
Increase outdoor air ventilation rates for all air-handling units serving occupied spaces by at least 30% above the minimum required by ASHRAE Standard 62.1-2010 (with errata but without addenda).
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Use heat recovery, where appropriate, to minimize the additional energy consumption associated with higher ventilation rates.
Standard Practice
None
Recommended Practice
Select and place air diffusers for all mechanically ventilated spaces, particularly office and passenger terminal spaces, following the recommended design approaches in the ASHRAE 2001 Fundamentals, Chapter 32, Space Air Diffusion
Section 6 of ASHRAE 62.1-2010 outlines guidelines for determining ventilation rates for various applications of mechanical ventilation systems
Best Available Practice
Increase air change effectiveness using the following strategies: o Displacement ventilation in passenger terminal areas. o Under floor air distribution in office areas.
Operable windows and skylights in cargo buildings Increase air movement in cargo facilities with ceiling fans Install trickle ventilators in cargo facilities to provide natural winter ventilation Install relief vents or operable skylights in cargo facilities to provide stack effect natural
ventilation
AuOM-103
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDY
Displacement Ventilation System San Francisco International Airport – San Francisco, California
Terminal 2 at San Francisco International Airport features an innovative “displacement ventilation” system that introduces fresh, filtered, cool air into the rooms near waist-level, pushing the older, warmer air to rise to the exhaust points. This system provides fresher air and uses over 25% less fan power than most ventilation systems.
www.greenbiz.com/blog/2010/05/06/green-design-takes-flight-san-francisco-international-airport
AuOM-104
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 INDOOR ENVIRONMENTAL QUALITY
5.4.4 Indoor Air Quality (IAQ) Best Management Practices: Reduce Particulates in Air Distribution
1 point
INTENT
Reduce exposure of building occupants and maintenance personnel to potentially hazardous particulate contaminants, which adversely affect air quality, human health, building systems and the environment.
REQUIREMENTS
Have in place filtration media with a minimum efficiency reporting value (MERV) of 13 or greater for all outside air intakes and inside air recirculation returns during the performance period. Establish and follow a regular schedule for maintenance and replacement of these filtration media according to the manufacturer’s recommended interval.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Install and maintain filtration media with a particle removal effectiveness of MERV 13 or greater for all outside air intakes and returns for the recirculation of inside air. Establish and follow a regular schedule for maintenance and replacement of these filters.
Standard Practice
None
Recommended Practice
Provide MERV 13 filters on all outdoor air intakes Create a maintenance schedule and log for filter replacement
Best Available Practice
None
AuOM-105
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDY
Energy Recovery and Air Purification System Reno Tahoe Airport – Reno, Nevada
High efficiency particulate filters rated at 90% efficiency were installed to remove airborne particles. The system is periodically tested for effectiveness and replaced when fully saturated.
http://departements.labo.climoilou.qc.ca/tmb/221-6J3/Conception%20en%20ventilation/%C3%89quipements/Filtration%20chimique/%C3%89tudes%20de%20cas/RenoTahoeInternationalAirport.pdf
AuOM-106
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 INDOOR ENVIRONMENTAL QUALITY
5.5.1 Occupant Comfort: Occupant Controlled Lighting
1 point
INTENT
Provide a high level of lighting control by individual occupants or specific groups in multi-occupant spaces (e.g., classrooms or conference areas) to promote the productivity, comfort, and well-being of building occupants.
REQUIREMENTS
Use lighting controls that enable adjustments to suit the task needs and preferences of individuals for at least 50% of individual workstations.
AND
Use lighting controls that enable adjustments for groups sharing a multi-occupant space or working area for at least 50% of multi-occupant space in the building.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Implement system and occupant control of ambient and task lighting to suit individual preferences and the needs of specific tasks.
Standard Practice
None
Recommended Practice
Tie lighting in public areas of passenger terminals to flight schedules or use motion-activated lighting
Design lighting control systems to take advantage of daylight harvesting to reduce artificial lighting when adequate daylight is available
Design terminal areas to provide a variety of levels of light and sound in different areas simultaneously
Provide operable windows in areas that are not noise-sensitive, such as cargo buildings Provide task lighting or more light switching zones in office areas
AuOM-107
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Best Available Practice
None
CASE STUDY
Lighting Management System Toronto Pearson International Airport – Toronto, Ontario
The lighting management system at Toronto Pearson Airport integrates lighting management, an important function on a campus with annual electric bills totaling $18 million. Lighting management lets allows the airport to use natural light to the fullest extent possible without creating inconvenience for staff. Lighting can be adjusted or switched off automatically based on natural lighting levels, building schedules, ATIMS information and other factors. The program saved an estimated $1 million in electricity in 2004 and is projected to save $1.5 million in 2005.
http://www.torontopearson.com/uploadedFiles/GTAA/Content/Publications/Social_Responsibility/GTAA%20CR%20Online.pdf
AuOM-108
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 INDOOR ENVIRONMENTAL QUALITY
5.5.2 Occupant Comfort: Thermal Comfort Monitoring
1 point
INTENT
Support the appropriate operations and maintenance of buildings and building systems so that they continue to meet target building performance goals over the long term and provide a comfortable thermal environment that supports the productivity and well-being of building occupants.
REQUIREMENTS
Have in place a system for continuous tracking and optimization of systems that regulate indoor comfort and conditions (air temperature, humidity, air speed and radiant temperature) in occupied spaces. Have a permanent monitoring system to ensure ongoing building performance to the desired comfort criteria as determined by ASHRAE SS—2004, Thermal Comfort Conditions for Human Occupancy.
The building must establish continuous monitoring of, at a minimum, air temperature and humidity in occupied spaces. The sampling interval cannot exceed 15 minutes.
Require periodic testing of air speed and radiant temperature in occupied spaces. The use of handheld meters is permitted.
Install alarms for conditions that require system adjustment or repair. Submit a list of the sensors, zone setpoints, and limit values that would trigger an alarm.
Create procedures that deliver prompt adjustments or repairs in response to problems identified. All monitoring devices must be calibrated within the manufacturer’s recommended interval
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Implement systematic monitoring of the actual performance of the building to the comfort criteria defined by ASHRAE SS—2004.
As appropriate, monitoring may include measurement and trending of temperatures, relative humidity, air speed, and radiant temperatures at locations selected according to their variability and effect on occupants’ comfort.
AuOM-109
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Standard Practice
None
Recommended Practice
Locate at least one temperature sensor in each HVAC zone Locate at least one humidity sensor in each humidity zone
Best Available Practice
Tie thermal comfort monitoring systems into a Building Automation System (BAS)
CASE STUDY
Novar Controls System 101 North Tower – Phoenix, Arizona
By installing a building automation system (BAS) to replace older pneumatic controls, the tower enjoys central management, simpler operation, faster responses to any thermal comfort issues that occur, and significant energy savings. The 101 North Tower project includes cooling tower fans, chillers, air handling units, system pumps, and hundreds of dual duct VAV boxes. Novar Controls’ IQ controllers—running on a dedicated high-speed Ethernet network—manage all the building’s functions through Novar Controls’ 963 supervisor operator software.
www.bas-az.com/Images/MK-CS-NOVAR-101NORTH.pdf
AuOM-110
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 INDOOR ENVIRONMENTAL QUALITY
5.6.1 Green Cleaning: Sustainable Cleaning Equipment
1 point
INTENT
Reduce the exposure of occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, and the environment.
REQUIREMENTS
Implement a program for the use of janitorial equipment that reduces building contaminants and minimizes environmental impact. The cleaning equipment program must require the following:
Vacuum cleaners are certified by the Carpet and Rug Institute “Green Label” Testing Program for vacuum cleaners and operate with a sound level of less than 70dBA
Carpet extraction equipment used for restorative deep cleaning is certified by the Carpet and Rug Institute’s “Seal of Approval” Testing Program for deep-cleaning extractors
Powered floor maintenance equipment, including electric and battery-powered floor buffers and burnishers, is equipped with vacuums, guards and/or other devices for capturing fine particulates and operates with a sound level of less than 70dBA
Propane-powered floor equipment has high-efficiency, low-emissions engines with catalytic converters and mufflers that meet the California Air Resources Board (CARB) or Environmental Protection Agency (EPA) standards for the specific engine size and operate with a sound level of less than 90dBA
Automated scrubbing machines are equipped with variable-speed feed pumps and on-board chemical metering to optimize the use of cleaning fluids; alternatively, the scrubbing machines use only tap water with no added cleaning products
Powered equipment is ergonomically designed to minimize vibration, noise, and user fatigue
Equipment is designed with safeguards, such as rollers or rubber bumpers, to reduce potential damage to building surfaces
Keep a log for all powered cleaning equipment to document the date of equipment purchase and all repair and maintenance activities and include vendor specification sheets for each type of equipment in use
SUBMITTALS
Include descriptive narrative in SAM Checklist.
AuOM-111
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
TECHNOLOGY/STRATEGY
Develop, implement, and maintain a policy for the use of low-impact powered cleaning equipment. Evaluate the powered cleaning equipment currently being used and make a plan for upgrading to powered cleaning equipment that reduces building contaminants and minimizes environmental impact.
Standard Practice
None
Recommended Practice
Utilize cleaning equipment that are designed to have a reduced environmental impact while maintaining performance of cleaning
Best Available Practice
Carpet and Rug Institute approved vacuum and carpet cleaning equipment Electric and battery-powered floor buffers and burnishers that operate at less than
70dBA Low-emissions fossil fuel powered floor cleaning equipment that meets the California Air
Resources Board (CARB) or Environmental Protection Agency (EPA) standards for the specific engine size and operate with a sound level of less than 90dBA
Automated scrubbing machines are equipped with variable-speed feed pumps and on-board chemical metering to optimize the use of cleaning fluids
Battery-powered equipment is equipped with environmentally preferable gel batteries Ergonomically designed equipment Equipment is designed with safeguards Keep a log for all powered cleaning equipment to document the date of equipment
purchase and all repair and maintenance activities and include vendor specification sheets for each type of equipment in use
AuOM-112
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
5.0 INDOOR ENVIRONMENTAL QUALITY
5.6.2 Green Cleaning: Entryway Systems
1 point
INTENT
Reduce the exposure of building occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, building finishes, building systems, and the environment.
REQUIREMENTS
Utilize entryway systems (grilles, grates, mats) immediately inside all public entryways within at least ten feet, the mats must be in place immediately inside all public entryways; exclude emergency exits from this requirement.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Use grills, grates or mats to catch and hold dirt particles and prevent contamination of the interior space. Design exterior stone, brick or concrete surfaces to drain away from regularly used entrances.
At entrances, install low-maintenance vegetation consistent with the requirements of SAM Credit 1.7 Landscape Management and avoid plants, including trees and shrubs that produce fruit, flowers or leaves that are likely to be tracked into the building. Select plants based on an integrated pest management (IPM) approach to eliminate pesticide applications that could be tracked into the building.
Provide a water spigot and electrical outlet at each public building entrance for maintenance and cleaning.
Standard Practice
None
Recommended Practice
Utilize entryway systems (grilles, grates, mats) to reduce the amount of dirt, dust, pollen and other particles entering the building at all public entryways, and develop the associated cleaning strategies to maintain those entryway systems as well as exterior walkways. At least 10 feet of mats must be in place immediately inside all public entryways. Public entryways that are not in use or serve only as emergency exits are excluded from the requirements, as are private offices.
AuOM-113
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Best Available Practice
Use grilles, grates, or mats to catch and hold dirt particles and prevent contamination of interior space.
At public entrances, install low-maintenance vegetation within the landscape design and avoid plants, including trees and shrubs that produce fruit, flowers, or leaves that are likely to be tracked into the space. Base plant selection on an integrated pest management approach to eliminate pesticide applications that could be tracked into the space.
Provide a water spigot and electrical outlet at each entrance for maintenance and cleaning.
CASE STUDY
Passenger Health and Comfort Indianapolis International Airport – Indianapolis, Indiana
Dust control at entryways and isolated use of cleaning products and chemicals to specially ventilated areas help maintain good indoor air quality. Smoking is also not allowed inside or outside the airport’s terminal and other facilities.
www.purdue.edu/travel/pdf/NewINDFactSheet.pdf
AuOM-114
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
6.0 INNOVATION IN OPERATIONS & MAINTENANCE
6.1 – 6.4 Innovation in Operations & Maintenance
1 to 4 points
INTENT
Provide building operations, maintenance, and upgrade teams with the opportunity to earn points for environmental benefits achieved beyond those already addressed by the SAM Operations & Maintenance Rating System.
REQUIREMENTS
Achieve significant, measurable environmental performance using an operations, maintenance, or system upgrade strategy not addressed in the SAM Operations & Maintenance Rating System.
SAM Credit 6.1. (1 point) Identify the intent of the proposed innovation credit, the additional environmental benefits delivered, the proposed requirements for compliance, and the proposed performance metrics to demonstrate compliance, and the approaches (strategies) that might be used to meet the requirements; meet the proposed requirements during the performance period.
SAM Credit 6.2 (1 point) same as Credit 6.1.
SAM Credit 6.3 (1 point) same as Credit 6.1.
SAM Credit 6.4 (1 point) same as Credit 6.1.
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Implement and maintain over the performance period actions that provide added environmental benefits. These can be either actions that substantially exceed a current SAM O&M credit requirement or actions not addressed in the SAM O&M chapter that provide substantial added environmental benefits.
AuOM-115
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDY
Active Water Leak Detection Canberra Airport – Canberra, Australia
Water leakages are a very large source of water use, and typically account for 25% of water consumption in non-monitored buildings. Canberra Airport actively manages and monitors its water use, continuously searching for leakages or potential leakages in its buildings. Water sub meters have been connected to all major uses, and our newer buildings are electronically connected to a Building Management System, which provides alarms when leaks are detected. The Airport employs a licensed plumber on site to repair any leaks and inefficient infrastructure. Three full time irrigation plumbing experts also work on site to repair irrigation leaks and monitor water usage.
http://www.fairbairn.com.au/fb-environmental/water.cfm
AuOM-116
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
7.0 EDUCATION & TRAINING
7.1 Community Education
1 point
INTENT
Promote awareness of CDA Divisions and tenant environmental and sustainability initiatives.
REQUIREMENTS
Educate consumers/clients/public about the environmental stewardship committed to and results of the efforts.
SUBMITTALS
Include descriptive narrative in SAM Checklist of methods of community education.
TECHNOLOGY/STRATEGY
Provide and promote education through the following means that include, but are not limited to:
Flyers Pamphlets Press Releases Signage Kiosks Workshops Conferences Website CDA alerts (e-mail blasts) Public exhibits
Standard Practice
Many of these educational outreach programs are already implemented by the CDA and tenants. The internet is the primary outlet for promoting current programs in place by the tenants and CDA.
Recommended Practice
Post environmental education information detailing the efforts of the CDA or tenant Promote customer participation in identifying initiatives that contribute to the CDA and
tenant’s environmental goals Solicit suggestions from customers on how to improve CDA’s environmental and social
programs
AuOM-117
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
Best Available Practice
Recognize and offer incentives to consumers/clients/public if they contribute to the CDA and tenant’s environmental goals
AuOM-118
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
7.0 EDUCATION & TRAINING
7.2 Implement Employee Sustainability Training Program
1 Point
INTENT
In keeping with the spirit and intent of this Manual, it is strongly encouraged that companies working in support of CDA on any project establish and adopt their own employee training program.
REQUIREMENTS
Establish and implement an Employee Sustainability Training Program.
SUBMITTALS
Provide an electronic copy of the company’s Employee Sustainability Training Program and provide descriptive narrative on SAM Checklist documenting training sessions and their respective attendance numbers.
TECHNOLOGY/STRATEGY
As part of the Employee Sustainability Training Program a variety of topics should be covered to provide the employees with an overall understanding of the environmental responsibility that the CDA has committed to and how they can contribute to the organization meeting their sustainability goals. Through the development of a training program it will allow the CDA to provide consistent training to all employees and address facility specific issues.
Training is critical to the following, but not limited to:
Missions and policies Opportunity to constantly be re-evaluated and improved Eco- more complex/more sophisticated systems and software Not yet a SOP, often requires a learning curve Addresses employee changeover Facilitates monitoring, tracking and reporting
Standard Practice
None
Recommended Practice
Individual programs can be tailored to meet each company’s specific environmental goals and can include topics such as:
o Corporate Sustainability Policy o Water Management Plan
AuOM-119
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
o Waste Reduction o Storage and Collection of Recyclables o Composting or Re-use Options o Managing and Disposing of Waste o Systems management, including HVAC and other complex components
Best Available Practice
None
CASE STUDIES
Stationary Engineers of Local 399 Chicago Airport System – Chicago, Illinois
Recognizing the needs of Stationary Engineers to be responsive to the ever changing requirements of the industry, the Local 399 has instituted many training programs to educate their members in the latest technologies available. These training programs also include a focus on green initiatives and sustainability, indoor air quality, energy conservation, LEED (EB) and data center environments of critical systems to name a few.
Such training is meant to maximize operational efficiency while minimizing environmental impacts and providing measurable results which reflects operational cost savings to the owner.
www.iuoe399.org/
Environmental Stewardship Training Program Dallas – Ft. Worth International Airport – Dallas, Texas
The training program solicits the participation of Dallas – Ft, Worth’s (DFW) 1,650 employees in an airport-wide commitment to environmental stewardship.
http://www.nctcog.org/envir/seeclean/EMS/March-DFWAirport-workgroup.pdf
AuOM-120
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
7.0 EDUCATION & TRAINING
7.3 Staff Training
1 point
INTENT
Support and encourage the operations, maintenance, upgrade, and project team integration required for SAM O&M implementation and to streamline the application and certification process.
REQUIREMENTS
At least one principal participant of the project team shall be LEED accredited (i.e., LEED Green Associate; LEED Accredited Professional).
SUBMITTALS
Include descriptive narrative in SAM Checklist.
TECHNOLOGY/STRATEGY
Have someone in your organization study for and successfully complete the LEED accreditation exam or related program approved by the SRP
Provide training for staff to handle day-to-day operations and maintenance involving sustainability, as related to this chapter
Standard Practice
None
Recommended Practice
The Chicago Department of Aviation recommends that any operations and management team include a LEED AP on its staff to assist and oversee the administration of sustainable operations
Best Available Practice
None
AuOM-121
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDY
City Of Atlanta Department of Aviation Hartsfield-Jackson Atlanta International Airport – Atlanta, Georgia
As of August 2009, the City of Atlanta Department of Aviation had six architects and engineers on staff who were LEED certified.
www.airportsgoinggreen.org/Content/Documents/ATL%20Sustainability%20Initiatives_Nissalke.pdf
AuOM-122
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
8.0 MONITORING & REPORTING
8.1 Documenting Sustainable Measures
5 Points
INTENT
Track, document, report and promote the CDA’s Green Commitment and encourage divisions and tenants airport-wide to join the movement.
REQUIREMENTS
Identify a primary contact person for all sustainability-related tracking and communications.
AND
Complete the SAM Checklist in accordance with chapter guidelines.
SUBMITTALS
Complete the SAM Checklist. Include and submit the completed checklist, and submit any progress reports/annual reports that support this credit.
TECHNOLOGY/STRATEGY
Track operating costs to identify any positive impacts related to the sustainable performance improvements to the building and its operations. At a minimum include water, electricity and waste management data to document operating costs on an ongoing basis. Use this data to optimize consumption and waste from operations and identify potential areas of improvement in future checklist and performance periods.
Standard Practice
None
Recommended Practice
None
Best Available Practice
Document overall operating costs (i.e., water/electricity/recycle) for the previous five years (or length of building occupancy, whichever is shorter) and track changes in overall building operating costs over the performance period. Document operating costs and financial impacts of all aspects of SAM O&M implementation on an ongoing basis.
AuOM-123
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
CASE STUDY
Green Airport Initiative (GAI) Fort Lauderdale-Hollywood International Airport – Fort Lauderdale, Florida
The Fort Lauderdale-Hollywood Green Airport Initiative is designed to help airports achieve quick and measurable benefits in environmental quality and energy savings. Broken down into two sections, the second section focuses on documenting cost impacts and identifies the many opportunities the airport will have in the future to reduce its environmental impact and operating costs.
www.cleanairports.com/reports/gai_fllforweb.pdf
AuOM-124
November 5, 2012
© 2012 City of Chicago
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
APPENDIX OM-A
GREEN AIRPLANE RATING SYSTEM for
OPERATIONS & MAINTENANCE
The Sustainable Airport Manual Green Airplane Rating System consists of all the points available for each credit, by project category. The table shows each of the credit categories for the Operations & Maintenance chapter of the SAM, their titles and available points. The total points achieved can be used to determine the SAM Green Airplane Rating.
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
_____________
SUSTAINABLE AIRPORT MANUAL GREEN AIRPLANE RATING SYSTEM
_________________
Potential Points
AP Administrative Procedures 8AP.1 Prerequisite 1 - Green Meetings RequiredAP.2 Prerequisite 2 - Document Reduction and Recycling Initiative (DRRI) RequiredAP.3 Establish and Adopt a Corporate Sustainability Policy 1AP.4 Green Procurement Policy 4
AP.5.1 Recycled Content Paper, 30% 1AP.5.2 Recycled Content Paper, 50% 1AP.5.3 Recycled Content Paper, 100% 1
1.0 Sustainable Sites 181.1 Prerequisite 1 - Equipment Maintenance Required1.2 LEED Certified Project 11.3 Exterior Facilities Management 11.4 Hardscape Grounds Management 11.5 Integrated Pest Management and Wildlife Deterrence 11.6 Erosion Control 11.7 Landscape Management 1
1.8.1 Alternative Commuting Transportation for Employees, 5% 11.8.2 Alternative Commuting Transportation for Employees, 10% 11.8.3 Alternative Commuting Transportation for Employees, 20% 11.8.4 Alternative Commuting Transportation for Employees, 30% 11.9.1 Stormwater Management - Landside 11.9.2 Stormwater Management - Airside 41.10 Heat Island Reduction 21.11 Light Pollution Reduction 12.0 Water Efficiency 222.1 Prerequisite 1 - Establish a Water Use Baseline Required 2.2 Retroactive Water Efficiency 5
2.3.1 Indoor Water Efficiency,10% 12.3.2 Indoor Water Efficiency, 20% 12.3.3 Indoor Water Efficiency, 30% 12.3.4 Indoor Water Efficiency, 40% 12.3.5 Indoor Water Efficiency, 50% 1
2.4 Water Efficient Landscaping 32.5 Rain Harvesting for Non-Irrigation Usage 32.6 Innovative Wastewater Management 22.7 Water Efficient Vehicle Washing 43.0 Energy & Atmosphere 473.1 Prerequisite 1 - Refrigerant Management Required3.2 Utility Meter Data 43.3 Retroactive Energy Optimization 5
3.4.1.1 Optimize Energy Performance: Lighting Power, 15% 13.4.1.2 Optimize Energy Performance: Lighting Power, 20% 13.4.1.3 Optimize Energy Performance: Lighting Power, 25% 13.4.1.4 Optimize Energy Performance: Lighting Power, 30% 13.4.1.5 Optimize Energy Performance: Lighting Power, 35% 1
3.4.2 Optimize Energy Performance: Lighting Control 33.4.3 Optimize Energy Performance: HVAC 6
3.4.4.1 Optimize Energy Performance: Equipment and Appliances, 70% 13.4.4.2 Optimize Energy Performance: Equipment and Appliances, 77% 13.4.4.3 Optimize Energy Performance: Equipment and Appliances, 84% 13.4.4.4 Optimize Energy Performance: Equipment and Appliances, 90% 1
3.5 Existing Building Commissioning 63.6.1 Performance Measurement: Building Automation System 13.6.2 Performance Measurement: System Level Metering 23.7.1 On-Site and Off-Site Renewable Energy, On-site 3%/Off-Site 25% 13.7.2 On-Site and Off-Site Renewable Energy, On-site 4.5%/Off-Site 37.5% 13.7.3 On-Site and Off-Site Renewable Energy, On-site 6%/Off-Site 50% 13.7.4 On-Site and Off-Site Renewable Energy, On-site 7.5%/Off-Site 62.5% 13.7.5 On-Site and Off-Site Renewable Energy, On-site 9%/Off-Site 75% 13.7.6 On-Site and Off-Site Renewable Energy, On-site 12%/Off-Site 100% 1
3.8 Enhanced Refrigerant Management 13.9 Emissions Reduction Reporting 44.0 Materials & Resources 12
4.1.1 Solid Waste Management: Waste Stream Audit 34.1.2.1 Solid Waste Management: On-going Consumables, 20% 24.1.2.2 Solid Waste Management: On-going Consumables, 30% 14.1.2.3 Solid Waste Management: On-going Consumables, 40% 1
4.1.3 Solid Waste Management: Durable Goods 14.1.4 Solid Waste Management: Facility Alterations and Additions 14.2.1 Local and Regional Materials, 10% Extracted, Harvested or Manufactured Regionally 14.2.2 Local and Regional Materials, 20% Extracted, Harvested or Manufactured Regionally 14.2.3 Local and Regional Materials, 50% Extracted, Harvested or Manufactured Locally (within 250 miles) 15.0 Indoor Environmental Quality 135.1 Prerequisite 1 - Outdoor Air Introduction and Exhaust Systems Required5.2 Prerequisite 2 - Environmental Tobacco Smoke (ETS) Control Required5.3 High Performance Cleaning 2
5.4.1 Indoor Air Quality (IAQ) Best Management Practices: IAQ Management Program 45.4.2 Indoor Air Quality (IAQ) Best Management Practices: Outdoor Air Delivery Monitoring 15.4.3 Indoor Air Quality (IAQ) Best Management Practices: Increased Ventilation 15.4.4 Indoor Air Quality (IAQ) Best Management Practices: Reduce Particulates in Air Distribution 15.5.1 Occupant Comfort: Occupant Controlled Lighting 15.5.2 Occupant Comfort: Thermal Comfort Monitoring 15.6.1 Green Cleaning: Sustainable Cleaning Equipment 15.6.2 Green Cleaning: Entryway Systems 16.0 Innovation in Operations & Maintenance 46.1 Innovations in Operations & Maintenance 16.2 Innovations in Operations & Maintenance 16.3 Innovations in Operations & Maintenance 16.4 Innovations in Operations & Maintenance 17.0 Education and Training 37.1 Community Education 17.2 Implement Employee Sustainability Training Program 17.3 Staff Training 18.0 Monitoring and Reporting 58.1 Documenting Sustainable Measures 5
TOTAL POINTS POSSIBLE 132
Prerequisites 7
All Applicable Prerequisites + 6 Points
20% of Total Applicable Points*
30% of Total Applicable Points*
50% of Total Applicable Points*
80% of Total Applicable Points*
* Applicable Points are determined on a case by case basis and are specific to the department, operation, or entity being evaluated. Total Applicable Points are determined using the OM Checklist
Operations & Maintenance
Sustainable Airport Manual Credits
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
OM-A-1
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
APPENDIX OM-B
OPERATIONS & MAINTENANCE CHECKLIST
Instructions for completing SAM Checklist:- see also the Sustainable Airport Manual (SAM) for more information
NOTE: Only blue text and unshaded cells may be changed by the user.
Instructions Example1 Fill out title information in blue at the top: CDA Division or Tenant name, additional
descriptions, date submitted.CDA Vehicle ServicesAnnual Sustainability Review3/12/2011
2 Regardless of whether a credit was achieved or not, indicate credits that are applicable, and therefore potentially achievable, in the "Is Credit Applicable?" column by inputting an "X" for that credit. If the credit is applicable, then the spreadsheet will automatically add the appropriate points in the "Applicable Points" column.
Applicable credits are determined on a case by case basis depending on the entity being evaluated.
If entity being rated is a rental car turn-around facility with vehicle washing, then SAM Credit 2.7 is applicable and therefore an "X" should be inputted under the "Is Credit Applicable?" column. 4 points will automatically be added to the Applicable Points.
3 For those credits that were achieved, indicate this by putting the appropriate point in the “Points Obtained” column. Note that for “Prerequisite” credits, no point is achieved as these are the minimum performance requirements for sustainability under the SAM. For prerequisites, insert a "Yes" for those that are applicable (some prerequisites may not apply for all tenants).
If the credit requirements for SAM Credit 1.7 Landscape Management are met, then insert a “1” under the “Points Obtained” column. For SAM Credit 1.1 Prerequisite 1 - Equipment Maintenance, insert a "Y" or "Yes" in the "Points Obtained" column to indicate compliance with the prerequisite.
4 In the "Narrative" column, describe the scope of work for the project relevant to this credit by replacing the ”Fill in scope of work” phrase with the appropriate description. ORFor credits that were not achieved, leave the " Points Obtained" column blank and describe the reasons for this in the "Narrative". Include any additional information such as estimated quantities and/or locations.
NOTE: Only blue text and unshaded cells may be changed by the user.
Under SAM Credit 3.4 Optimize Energy Performance: Equipment and Appliances, fill in scope of work: "A total of 89% of all ENERGY STAR eligible equipment are ENERGY STAR qualified. This includes all computers and printers, kitchen appliances, and most copiers." Input 3 points in the "Points Obtained" column.ORUnder SAM Credit 3.4 Optimize Energy Performance: Equipment and Appliances, fill in scope of work: "Due to the specialized nature of the computing equipment and peripheral equipment, only the kitchen appliances and copiers were ENERGY STAR qualified. The overall percentage of ENERGY STAR qualified equipment was only 55%. Therefore, the point was not achieved." Leave "Points Obtained" column blank in this case.
5 For some credits, supporting documentation, typically some form of calculations, will also need to be included, if applicable. See SAM for supporting documentation templates. In some cases, the SRP may require additional supporting documentation for the other credits during review process for clarification.
NOTE: Points cannot be awarded for those credits that require supporting documentation without the appropriate documentation.
For SAM Credit 2.1 Prerequisite 1 - Establish a Water Use Baseline, submit, with this checklist, water meter data (if available) and the baseline water use based on the plumbing fixture inventory.
6 SUBMIT THE ENTIRE CHECKLIST, INCLUDING SUPPORTING DOCUMENTATION, FOR EVERY PERFORMANCE PERIOD FOR REVIEW BY THE SRP.
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
Template Sustainable Airport Manual (SAM) Operations & Maintenance Checklist11/5/12
[CDA Division or Tenant Name][Checklist Description, Additional Information]Revised: [Revision Date]
POINTS OBTAINED
IS CREDIT APPLICABLE?
(X)
APPLICABLE POINTS
CREDIT DESCRIPTION POINTS NARRATIVE
AP.0 Administrative Procedures 8
AP.1
Prerequisite 1 - Green Meetings Guide meeting hosts, planners and attendees toward more eco-friendly meetings and incorporate environmental considerations into planning and conducting meetings in order to minimize the negative impact on the environment.
Prereq Fill in scope of work
AP.2 Prerequisite 2 - Document Reduction and Recycling Initiative (DRRI) Reduce the volume paper used and facilitate the recycling of documents.
Prereq Fill in scope of work
AP.3
Corporate Sustainability Policy Keeping with the spirit and intent of this Manual, it is strongly encouraged that companies working in support of CDA on any project establish and adopt their own corporate policy on sustainable practices.
1 Fill in scope of work
AP.4Green Procurement Policy Reduce the environmental impact of products and services by developing a Green Purchasing Program.
4 Fill in scope of work
AP.5Recycled Content PaperReduce the need for virgin materials, energy, and waste associated with the production of paper by promoting the use of recycled content paper.
3 Fill in scope of work
POINTS OBTAINED
IS CREDIT APPLICABLE?
(X)
APPLICABLE POINTS
POINTS
18
1.1Prerequisite 1- Equipment MaintenanceMinimize the environmental impact of construction and maintenance equipment and associated maintenance activities.
Prereq Fill in scope of work
1.2
LEED Certified ProjectRecognize environmentally sensitive building design and construction by enabling high-performance building operations to be achieved in a more efficient and straightforward manner.
1 Fill in scope of work
1.3
Exterior Facilities ManagementTo encourage environmentally sensitive building exterior practices that provide a clean, well-maintained and safe building exterior while supporting high-performance building operations based on its original state.
1 Fill in scope of work
1.4
Hardscape Grounds Management Employ an environmentally sensitive, low-impact hardscape management process for building exterior (e.g., sidewalks, paved surfaces and other hardscape) that sustains ecological and environmental integrity while deterring wildlife and maintaining site appearance and safety.
1 Fill in scope of work
1.5
Integrated Pest Management and Wildlife DeterrencePreserve environmental integrity while discouraging the presence of pests/wildlife, in an effort to include methods that maintain and encourage high-performance pest management control.
1 Fill in scope of work
1.6
Erosion Control To address landscape operations while preserving and maintaining ecological integrity and site preservation by minimizing soil loss and preventing water pollution.
1 Fill in scope of work
1.7
Landscape Management To maintain the landscape that is aesthetically pleasing and at the same time, low maintenance, ecologically and financially sustainable yet does not compromise Airport security and aircraft safety.
1 Fill in scope of work
1.8Alternative Commuting Transportation for EmployeesTo reduce pollution and land development impacts from conventional automobile use for commuting trips.
4 Fill in scope of work
1.9.1
Stormwater Management - LandsideLimit disruption of natural water hydrology by reducing impervious cover, increasing on-site infiltration, reducing or eliminating pollution from stormwater runoff, and eliminating contaminants by enhancing the current operating system.
1 Fill in scope of work
1.9.2Stormwater Management - Airside Reduce airside stormwater pollutants by employing environmentally sensitive maintenance techniques within the current operating system.
4 Fill in scope of work
1.10
Heat Island Reduction To minimize impacts of existing roofs and pavements that causes the heat island effect (thermal gradient differences between developed and undeveloped areas).
2 Fill in scope of work
1.11
Light Pollution Reduction To eliminate light trespass from the building and site, improve night sky access and reduce development impact on nocturnal environments and upgrade existing lighting specifications to meet new standards.
1 Fill in scope of work
POINTS OBTAINED
IS CREDIT APPLICABLE?
(X)
APPLICABLE POINTS
POINTS
2.0 Water Efficiency 22
2.1Prerequisite 1 - Establish a Water Use Baseline Increase water efficiency within CDA Division and tenant spaces to reduce the burden on municipal water supply and wastewater systems
Prereq Fill in scope of work
2.2Retroactive Water EfficiencyRecognize previous improvements and upgrades that had a positive impact on water efficiency.
5 Fill in scope of work
2.3
Indoor Water Efficiency Maximize indoor plumbing fixture and fitting efficiency to reduce the use of potable water and the burden on municipal water supplies and wastewater systems.
5 Fill in scope of work
2.4
Water Efficient LandscapingTo limit or eliminate the use of potable water or other natural surface or subsurface resources available on or near the project site for landscape irrigation.
3 Fill in scope of work
2.5 Rain Harvesting for Non-Irrigation Usage Decrease the demand for potable water for non-irrigation use.
3 Fill in scope of work
2.6Innovative Wastewater Management To reduce wastewater generation and potable water demand while increasing the local aquifer recharge.
2 Fill in scope of work
1.0 Sustainable Sites
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
13 and 14 - CDA AM-Appendix OM-A and OM-B v3.0 - FINAL.xls OM-B-3 11/2/2012
Template Sustainable Airport Manual (SAM) Operations & Maintenance Checklist11/5/12
[CDA Division or Tenant Name][Checklist Description, Additional Information]Revised: [Revision Date]
POINTS OBTAINED
IS CREDIT APPLICABLE?
(X)
APPLICABLE POINTS
CREDIT DESCRIPTION POINTS NARRATIVE
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
2.7Water Efficient Vehicle Washing To limit or eliminate the use of potable water or other natural surface or subsurface resources available on or near the project site for vehicle washing.
4 Fill in scope of work
POINTS OBTAINED
IS CREDIT APPLICABLE?
(X)
APPLICABLE POINTS
POINTS
3.0 Energy & Atmosphere 47
3.1 Prerequisite 1 - Refrigerant ManagementTo reduce stratospheric ozone depletion.
Prereq Fill in scope of work
3.2Utility Meter DataMonitor, track and report utility data to reduce environmental and economic impacts associated with excessive energy use.
4 Fill in scope of work
3.3Retroactive Energy Optimization Recognize previous tenant improvements and upgrades that had a positive impact on energy efficiency.
5 Fill in scope of work
3.4.1
Optimize Energy Performance: Lighting Power Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
5 Fill in scope of work
3.4.2
Optimize Energy Performance: Lighting ControlAchieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
3 Fill in scope of work
3.4.3
Optimize Energy Performance: HVACAchieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
6 Fill in scope of work
3.4.4
Optimize Energy Performance: Equipment & AppliancesAchieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
4 Fill in scope of work
3.5
Existing Building CommissioningThrough a systematic process, to develop and implement an operation of the building’s major energy-using systems and implement a no to low cost option(s) for optimizing energy performance and a plan to achieve energy savings.
6 Fill in scope of work
3.6.1
Performance Measurement: Building Automation System To provide information to support the ongoing accountability and optimization of building energy performance and identify opportunities for additional energy-saving investments.
1 Fill in scope of work
3.6.2Performance Measurement: System Level MeteringTo provide accurate energy use information to support energy management and identify opportunities for additional energy-saving improvements.
2 Fill in scope of work
3.7On-Site and Off-Site Renewable Energy To encourage and recognize increasing levels of on-site and off-site renewable energy to reduce environmental impacts associated with fossil fuel energy use.
6 Fill in scope of work
3.8
Enhanced Refrigerant Management To reduce ozone depletion and support early compliance with the Montreal Protocol (an international agreement designed to protect from ozone depletion) while minimizing direct contributions to global warming.
1 Fill in scope of work
3.9
Emissions Reduction ReportingTo document the emissions reduction benefits of building efficiency measures to better track Chicago Department of Aviation’s (CDA) achievements in climate-altering fossil fuel consumption and resultant emissions.
4 Fill in scope of work
POINTS OBTAINED
IS CREDIT APPLICABLE?
(X)
APPLICABLE POINTS
POINTS
4.0 Materials & Resources 12
4.1.1
Solid Waste Management: Waste Stream Audit To facilitate the reduction of ongoing waste and toxins generated by building occupants and building operations that are hauled to and disposed of in landfills or incineration facilities.
3 Fill in scope of work
4.1.2
Solid Waste Management: Ongoing Consumables To facilitate the reduction of waste and toxins generated from the use of ongoing consumable products by building occupants and building operations that are hauled to and disposed of in landfills or incineration facilities.
4 Fill in scope of work
4.1.3
Solid Waste Management: Durable GoodsTo facilitate the reduction of waste and toxins generated from the use of durable goods by building occupants and building operations that are hauled to and disposed of in landfills or incinerations facilities..
1 Fill in scope of work
4.1.4
Solid Waste Management: Facility Alterations and AdditionsTo divert construction and demolition waste from disposal to landfills and incineration facilities. Redirect recyclable recovered resources to the manufacturing process. Redirect reusable materials to appropriate sites.
1 Fill in scope of work
4.2
Local/Regional Materials Increase demand for materials and products that are extracted, harvested or recovered, as well as manufactured within the region, thereby supporting the local economy and the use of indigenous resources and reducing the environmental impacts resulting from transportation.
3 Fill in scope of work
POINTS OBTAINED
IS CREDIT APPLICABLE?
(X)
APPLICABLE POINTS
POINTS
5.0 Indoor Environmental Quality 13
5.1
Prerequisite 1 - Outdoor Air Introduction and Exhaust SystemsTo establish minimum indoor air quality (IAQ) performance to enhance indoor air quality in buildings, thus contributing to the health and well-being of the occupants.
Prereq Fill in scope of work
5.2Prerequisite 2 - Environmental Tobacco Smoke (ETS) ControlPrevent or minimize exposure of occupants, indoor surfaces, and ventilation air distribution systems to Environmental Tobacco Smoke (ETS).
Prereq Fill in scope of work
5.3
High Performance CleaningReduce the exposure of occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, and the environment.
2 Fill in scope of work
13 and 14 - CDA AM-Appendix OM-A and OM-B v3.0 - FINAL.xls OM-B-4 11/2/2012
Template Sustainable Airport Manual (SAM) Operations & Maintenance Checklist11/5/12
[CDA Division or Tenant Name][Checklist Description, Additional Information]Revised: [Revision Date]
POINTS OBTAINED
IS CREDIT APPLICABLE?
(X)
APPLICABLE POINTS
CREDIT DESCRIPTION POINTS NARRATIVE
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
5.4.1
Indoor Air Quality (IAQ) Best Management Practices: IAQ Management ProgramTo enhance indoor air quality by optimizing practices to prevent the development of IAQ problems in indoor spaces, correcting indoor air quality problems when they occur, and maintaining the well-being of the occupants.
4 Fill in scope of work
5.4.2
Indoor Air Quality (IAQ) Best Management Practices: Outdoor Air Delivery MonitoringTo provide capacity for ventilation system monitoring to help sustain occupants’ comfort and well-being.
1 Fill in scope of work
5.4.3Indoor Air Quality (IAQ) Best Management Practices: Increased Ventilation To provide additional outdoor air ventilation to improve indoor air quality (IAQ) for improved occupant comfort, well-being and productivity.
1 Fill in scope of work
5.4.4
Indoor Air Quality (IAQ) Best Management Practices: Reduce Particulates in Air Distribution To reduce exposure of building occupants and maintenance personnel to potentially hazardous particulate contaminants, which adversely affect air quality, human health, building systems and the environment.
1 Fill in scope of work
5.5.1
Occupant Comfort: Occupant-Controlled LightingTo provide a high level of lighting control by individual occupants or specific groups in multi-occupant spaces (e.g., classrooms or conference areas) to promote the productivity, comfort, and well-being of building occupants.
1 Fill in scope of work
5.5.2
Occupant Comfort: Thermal Comfort MonitoringTo support the appropriate operations and maintenance of buildings and building systems so that they continue to meet target building performance goals over the long term and provide a comfortable thermal environment that supports the productivity and well-being of building occupants.
1 Fill in scope of work
5.6.1
Green Cleaning: Sustainable Cleaning Equipment Reduce the exposure of occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, and the environment.
1 Fill in scope of work
5.6.2
Green Cleaning: Entryway SystemsTo reduce the exposure of building occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, building finishes, building systems, and the environment.
1 Fill in scope of work
POINTS OBTAINED
IS CREDIT APPLICABLE?
(X)
APPLICABLE POINTS
POINTS
6.0 Innovation in Operations & Maintenance 4
6.1
Innovation in Operations & MaintenanceTo provide building operations, maintenance, and upgrade teams with the opportunity to earn points for environmental benefits achieved beyond those already addressed by the SAM Operations & Maintenance Rating System.
1 Fill in scope of work
6.2
Innovation in Operations & MaintenanceTo provide building operations, maintenance, and upgrade teams with the opportunity to earn points for environmental benefits achieved beyond those already addressed by the SAM Operations & Maintenance Rating System.
1 Fill in scope of work
6.3
Innovation in Operations & MaintenanceTo provide building operations, maintenance, and upgrade teams with the opportunity to earn points for environmental benefits achieved beyond those already addressed by the SAM Operations & Maintenance Rating System.
1 Fill in scope of work
6.4
Innovation in Operations & MaintenanceTo provide building operations, maintenance, and upgrade teams with the opportunity to earn points for environmental benefits achieved beyond those already addressed by the SAM Operations & Maintenance Rating System.
1 Fill in scope of work
POINTS OBTAINED
IS CREDIT APPLICABLE?
(X)
APPLICABLE POINTS
POINTS
7.0 Education and Training 3
7.1Community Education Promote awareness of CDA Divisions and tenant environmental and sustainability initiatives..
1 Fill in scope of work
7.2
Implement Employee Sustainability Training ProgramIn keeping with the spirit and intent of this Manual, it is strongly encouraged that companies working in support of CDA on any project establish and adopt their own employee training program.
1 Fill in scope of work
7.3
Staff TrainingTo support and encourage the operations, maintenance, upgrade, and project team integration required for SAM O&M implementation and to streamline the application and certification process.
1 Fill in scope of work
POINTS OBTAINED
IS CREDIT APPLICABLE?
(X)
APPLICABLE POINTS
POINTS
8.0 Monitoring and Reporting 5
8.1Documenting Sustainable Measures Track, document, report and promote the CDA’s Green Commitment and encourage divisions and tenants airport-wide to join the movement.
5 Fill in scope of work
TOTAL POINTS OBTAINED
TOTAL APPLICABLE
CREDITS
TOTAL APPLICABLE
POINTS
TOTAL POSSIBLE
POINTS
132
13 and 14 - CDA AM-Appendix OM-A and OM-B v3.0 - FINAL.xls OM-B-5 11/2/2012
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
…We are creating a performance metric system for our industry that has broader applicability…in looking at the airport community, we constantly challenge ourselves and redefine what we should be- transforming and enhancing our industry over and over…
Rosemarie S. Andolino Commissioner Chicago Department of Aviation
…We are all one community and what we do affects each other. We need to educate people to understand the interrelationships between us…
Paul Manasjan San Diego County Regional Airport Authority
…Concessions and tenants are critical to an airport’s overall functions and success. There will be great benefits achieved through their adoption of sustainable practices…
Rhona DiCamillo D+G Consulting Group
airportsgoinggreen.org
Project Submittal Forms, Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
CT-1
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CONCESSIONS & TENANTS TABLE OF CONTENTS
CONCESSIONS & TENANTS INTRODUCTION ………... CT-5 SECTION – CONCESSIONS & TENANTS – DESIGN & CONSTRUCTION CT-13 1.0 Sustainable Sites 1.1 Adopt CDA Best Management Practices ………... CT-141.2 Light Pollution Reduction ………... CT-15 2.0 Water Efficiency 2.1 Water Use Reduction ………... CT-162.2 Water Use – Additional Reduction ………... CT-19 3.0 Energy & Atmosphere 3.1 Fundamental Systems Commissioning ………... CT-223.2 Minimum Energy Performance ………... CT-253.3 Optimize Energy Performance ………... CT-273.4 Enhanced Commissioning ………... CT-353.5 Measurement and Verification ………... CT-393.6 Green Power ………... CT-42 4.0 Materials & Resources 4.1 Storage and Collection of Recyclables ………... CT-454.2 Construction Waste Management ………... CT-474.3 Material Reuse ………... CT-504.4 Recycled Content ………... CT-524.5 Local/Regional Materials ………... CT-554.6 Rapidly Renewable Materials ………... CT-574.7 Certified Wood ………... CT-594.8 Furniture and Equipment ………... CT-614.9 Equipment Salvage and Reuse ………... CT-63 5.0 Indoor Environmental Quality 5.1 Minimum Indoor Air Quality (IAQ) Performance ………... CT-655.2 Environmental Tobacco Smoke (ETS) Control ………... CT-675.3 Construction IAQ Management Plan ………... CT-695.4 Low-Emitting Materials ………... CT-745.5 Indoor Chemical and Pollutant Source Control ………... CT-845.6 Controllability of Systems ………... CT-865.7 Thermal Comfort ………... CT-905.8 Noise Transmission ………... CT-93 6.0 Construction Practices 6.1 Alternative Transportation During Construction ………... CT-956.2 Construction Noise and Acoustical Quality ………... CT-1006.3 Sustainable Temporary Construction Materials ………... CT-102
CT-2
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 Innovation for Concessions & Tenants – Design &
Construction
7.1 Innovation for Concessions & Tenants - Design & Construction ………... CT-1047.2 Innovation for Concessions & Tenants - Design & Construction ………... CT-1047.3 Innovation for Concessions & Tenants - Design & Construction ………... CT-1047.4 Menu Items ………... CT-1057.5 LEED Accredited Professional ………... CT-1107.6 LEED Certified Project ………... CT-111
CT-3
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
SECTION – CONCESSIONS & TENANTS –OPERATIONS & MAINTENANCE
CT-112
8.0 Company Policy 8.1 Tenant Environmental Liaison ………... CT-1138.2 Establish and Implement Employee Environmental Training
Program ………... CT-114
8.3 Alternative Transportation ………... CT-1168.4 Community Education ………... CT-123 9.0 Responsible Procurement 9.1 Furniture and Equipment ………... CT-1259.2 Eliminate Use of Polystyrene Foam ………... CT-1279.3 Consumer Disposable Products ………... CT-1289.4 Local/Regional Food Sources ………... CT-1389.5 Sustainable Food and Consumer Products ………... CT-140 10.0 Green Interiors 10.1 Minimum Indoor Air Quality (IAQ) Performance ………... CT-14210.2 Environmental Tobacco Smoke (ETS) Control ………... CT-14410.3 LEED Certified Design & Construction ………... CT-14510.4 Green Cleaning ………... CT-14710.5 Measurement and Verification ………... CT-15510.6 Tenant Space Automation Systems ………... CT-15710.7 Occupant Controls ………... CT-15810.8 Thermal Comfort: Employee Verification ………... CT-162 11.0 Water Management 11.1 Utility Meter Data ………... CT-16411.2 Water Management Plan ………... CT-16511.3 Water Use Reduction ………... CT-169 12.0 Energy Management 12.1 Utility Meter Data ………... CT-17212.2 Energy Management Plan ………... CT-17312.3 Energy Use Reduction ………... CT-17812.4 Optimize Energy Performance ………... CT-18112.5 Green Power ………... CT-190 13.0 Waste Stream Management 13.1 Waste Stream Audit ………... CT-19313.2 Waste Stream Management Plan ………... CT-19513.3 Waste Reduction ………... CT-20013.4 Storage and Collection of Recyclables ………... CT-20313.5 Track and Report Recycling Activity ………... CT-20613.6 Organic Byproduct Recycling ………... CT-20813.7 Surplus Food Sent to Local Organizations ………... CT-21413.8 Deplaned Waste ………... CT-21613.9 Repurposing of Goods ………... CT-21913.10 Reduction of Plastic Waste ………... CT-221
CT-4
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 Venue Specific Considerations 14.1 Heat Island Reduction ………... CT-22514.2 Stormwater Management ………... CT-22814.3 Landscape Management ………... CT-23014.4 Rainwater Harvesting ………... CT-23814.5 Water Efficient Vehicle Washing ………... CT-24014.6 Clean Fuel Vehicles ………... CT-24214.7 Alternative Fuel Infrastructure ………... CT-24414.8 Green Restaurant Certification ………... CT-246 15.0 Innovation for Concessions & Tenants – Operations &
Maintenance
15.1 Innovation for Concessions & Tenants - Operations & Maintenance
………... CT-238
15.2 Innovation for Concessions & Tenants - Operations & Maintenance
………... CT-238
15.3 Innovation for Concessions & Tenants - Operations & Maintenance
………... CT-238
15.4 Community/Cultural Responsibility ………... CT-24915.5 Menu Items ………... CT-251 16.0 Monitoring and Reporting 16.1 Documenting Sustainable Measures ………... CT-252 Appendices CT-A Green Airplane Rating System for Concessions & Tenants ………... CT-A-1CT-B Concessions & Tenants Checklist ………... CT-B-1
CT-5
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
INTRODUCTION
Airport concessions and tenants are businesses that have selected the airport as the location for their business. They have signed a lease and utilize airport infrastructure and services. They are an integral part of any airport’s day-to-day functions, and therefore inherently part of the overall service any airport provides to both the travelling and neighboring public.
Airport concessions provide an important passenger service amenity while providing significant financial benefits to the airport. Concessions include news and gifts, specialty retail stores, food and beverage, duty-free shops and many other services. Passengers arrive early for a departing flight or they have time before their connecting flight to shop, grab a bite to eat, or relax in the spa. Many airports have become shopping destinations with retail and food options typical of a shopping mall.
Airport tenants include a wide range of organizations and services, ranging from advertising, car rental, hotel, airlines, government agencies, organizations providing aircraft and aviation services, organizations handling cargo and mail, aircraft owners and fixed-base operators and often non-aviation businesses as well.
The Sustainable Airport Manual (SAM) Green Airplane Rating System for Concessions & Tenants is designed to certify the sustainability of concession and tenant activities, including daily operations as well as design and construction of new facilities within the terminals.
This chapter is divided into two types of activities:
Design & Construction - Pertains to the build-out or interior renovations within the terminals or existing buildings
Operations & Maintenance - Pertains to all tenants with customer/passenger interaction
Due to the variation in the types of tenants, general tenant types have been defined based on their location and general nature of service. These are defined as:
Design & Construction
Terminal Food Service Tenants: Concessionaires and tenants located within the terminal or other existing conditioned spaces that provide food services for a majority of their operations to passengers or customers. Examples include but are not limited to restaurants, taverns, snack shops, coffee shops, and bakeries.
Terminal Non-Food Service Tenants: Concessionaires and tenants located within the terminal or other existing conditioned space that do not provide food services for a majority of their operations to passengers or customers. Examples include but are not limited to book stores, gift shops, newspaper stands, and other retail merchandise venues.
Operations & Maintenance
Food Service Tenant: Concessionaires and tenants located within the terminal or other existing conditioned spaces that provide food services for a majority of their operations to passengers or
CT-6
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
customers. Examples include but are not limited to restaurants, taverns, snack shops, coffee shops, and bakeries.
Full Service: Tenants that have table service (i.e. a restaurant with a wait staff) and have some measure of control over the consumables and waste generated by the customers within their space.
Counter Service: Tenants that provide mainly carry-out service by means of a counter. While tables may be present within/near the space, the tenant does not provide service via wait staff.
To-Go, Kiosk: Tenants that sell food products from a free standing location, such as a kiosk. All products are prepared off-site and sold pre-packaged.
Non-Food Service Tenant: Concessionaires and tenants located within the terminal or other existing conditioned spaces that do not provide food services for a majority of their operations to passengers or customers. Examples include but are not limited to book stores, gift shops, newspaper stands, and other retail merchandise venues.
Buildout: Tenants that sell products within a space where the tenant has control over layouts, configuration, lighting, etc.
Free-Standing, Kiosk: Tenants that sell products in a free-standing area within the terminal corridors.
Non-Terminal Tenants: Tenants located outside of the terminal in existing conditioned spaces or buildings that service passengers or customers. Examples include rental car facilities not located in the terminal, fixed base operators, commercial developments, gas stations, and hotels.
Food Service Tenant: Tenants offering food service in a location outside of the terminals.
Non-Food Service Tenant: Tenants offering a non-food service or retail in a location outside of the terminals.
APPLICABILITY
SAM Concessions & Tenants (CT) focuses on the evaluation of all airport tenants who have direct customer interaction. Tenants who do not have direct customer interaction should refer to the Operations & Maintenance (OM) chapter of the SAM. Some tenants may have operations that include both non-customer interaction and direct customer interaction. An airline, for example, has both types of operations and would be evaluated under both chapters; the terminal activities (with direct customer interaction) would be reviewed following this CT chapter, while the OM chapter would be applied where no direct customer interaction occurs, such as activities at aircraft gates and maintenance hangars.
Given the nature of the construction activities that may go on inside terminal spaces or other existing airport facilities, all tenant build-out projects and minor interior rehabilitation not
CT-7
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
involving HVAC and envelope replacement, regardless of owner, would fall under the CT Design & Construction section. As an example, a Chicago Department of Aviation (CDA) food court renovation would be rated under the CT chapter. In the case where a tenant is building a new, stand-alone facility, e.g. a car rental facility that is not within an existing airport building or terminal, then the tenant should use the Design & Construction (DC) chapter of the SAM. A tenant build-out involving an existing building where the core and shell are reused but the interior requires a major interior rehabilitation including HVAC and envelope modifications would also fall under the Design & Construction (DC) chapter.
CONCESSIONS & TENANTS SECTIONS
This chapter is split into two sections: the CT-Design & Construction section and the CT- Operations & Maintenance section. The CT-Design & Construction section only pertains to the build-out or interior renovations within the terminals or existing buildings. Any construction or major renovations of non-terminal tenant spaces would follow the guidelines of the SAM Design & Construction (DC) chapter. The CT-Operations & Maintenance section pertains to all tenants with customer/passenger interaction.
Tenants are rated on the achievement of credits depending on the appropriate category of the initiative/effort, based on sustainable elements included in the project from the following categories:
CT – Design & Construction
AP Administrative Procedures (applies to both types of tenant activities) 1.0 Sustainable Sites 2.0 Water Efficiency 3.0 Energy & Atmosphere 4.0 Materials & Resources 5.0 Indoor Environmental Quality 6.0 Construction Practices 7.0 Innovation for in Design/Construction
CT – Operations & Maintenance
AP Administrative Procedures (applies to both types of tenant activities) 8.0 Company Policy
NOTE:
In order to qualify for review within the Concessions & Tenants Chapter, the tenant must have direct customer/passenger interaction. Tenants who do not have direct
interaction should refer to the Operations & Maintenance Chapter. This chapter also applies to any CDA design or construction within the terminals
CT-8
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
9.0 Responsible Procurement 10.0 Green Buildings 11.0 Energy Management 12.0 Waste Stream Management 13.0 Green Cleaning 14.0 Venue Specific Considerations 15.0 Innovation for Concessions & Tenants 16.0 Monitoring & Reporting
Each category contains a specific number of credits, against which each tenant or tenant project is evaluated in order to determine the total number points earned. The CDA recognizes that certain credits may only be applicable to some tenants, and for that reason the total potential points may vary from tenant to tenant. There will be floating point thresholds (i.e. applicable credits) for each tenant so as not to inadvertently penalize a tenant for not achieving points that would not be applicable. The percentage of points earned out of total applicable points is then translated into a rating. A list of the applicable credits is summarized in Appendix CT-A – Sustainable Airport Manual Green Airplane Rating System – Concessions & Tenants.
PROCESS
Within the Manual’s main body, each sustainable credit has five subsections: Intent, Requirements, Submittals, Technology/Strategy, and Case Studies, as described below:
Intent: The primary motivations for any sustainable practice.
Requirements: Specifies institutional, operational, and mechanical design or construction elements that satisfy the intent. The prerequisites must be achieved; the credits are optional, but contribute to the overall rating.
Submittals: Required and supporting documentation and/or information required to achieve applicable prerequisites or credits. This documentation may include calculations, data, short narratives, policies, documents or references to specification sections or design drawings indicating how the requirements are being met.
Technology/Strategy: Highlights specific ways of meeting the recommendations within the scope for each specific credit. Case studies where available, are presented to help guide the application of sustainable credits to Concession & Tenants projects and efforts. While the tenant may undertake the above Technologies/Strategies at other airports, for the purposes of this credit activities only apply to operations at CDA Airports. To aid with consideration of applicable strategies and technologies, they are organized into the following three categories; “Standard Practice,” “Recommended Practice,” and “Best Available Practice.”
o Standard Practice: These are requirements that may be due to standards, specifications, codes, general best management or construction practices. They are practices already in place, and SAM prerequisites, which also serve to meet sustainable goals.
CT-9
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
o Recommended Practice: These include recommendations that are expected to have insignificant impacts to cost and are therefore, encouraged to be incorporated.
o Best Available Practice: These are strategies and practices that are expected to enhance the sustainability efforts of the Chicago Department of Aviation (CDA), but are anticipated to potentially have an impact on the cost and/or schedule. Tenants are encouraged to explore the cost/environmental benefit ratio for such guidelines to the greatest extent practicable.
Case Study: Examples of credit intent “in action” at airports and/or other industry facilities.
While not all strategies will be applicable, concessionaires and tenants are highly encouraged to think creatively and to consider the intent of each issue throughout the decision process.
SUBMITTALS
Sustainable Airport Manual (SAM) Checklists
Incorporation of sustainable elements into Terminal Tenant’s design and construction are tracked using the SAM CT-Design & Construction Checklist. Incorporation of sustainable initiatives and practice into Tenants daily operations are tracked using the SAM CT- Operations & Maintenance Checklist. The checklists are provided in Appendix CT-B – Concessions & Tenants Checklist.
In order to achieve points, certain requirements need to be met, as outlined in each credit. In some instances, studies and calculations would be appropriate. In other instances, this will be accomplished through product and material data or through referenced standards or specifications.
In addition to review of the checklist, the Sustainable Review Panel (SRP) will review any supporting documentation including calculations, specifications, and contractor’s submittals as needed to support the achievement of the credit(s). See Section titled Implementation and Review Process for detailed information about the SRP.
SAM GREEN AIRPLANE RATING SYSTEM
CONCESSIONS & TENANTS – DESIGN & CONSTRUCTION
The SAM Green Airplane Rating System for CT – Design & Construction uses a five tier approach to rating a tenant similar to the Design & Construction rating system. “Green Airplane Certification” symbols are used to designate achievement levels. The levels are:
CT-10
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CT-DC GREEN AIRPLANE RATING SYSTEM
No. of Green Airplanes
Points Required to Achieve Rating
Terminal Food Service
Tenant
Terminal Non-Food
Service Tenant
Non-Terminal Tenant
Prerequisites 7 6 9
6-20 6-17 6-30
21-25 18-22 31-38
26-30 23-27 39-46
31-41 28-36 47-61
42-52 37-46 62-78
CONCESSIONS & TENANTS – OPERATIONS & MAINTENANCE
The SAM Green Airplane Rating System for CT –Operations & Maintenance uses a three tier approach to rating a tenant. “Green Airplane Certification” levels are used to designate achievements. The levels are:
Achiever: Tenant has completed the SAM review process and, at a minimum, accomplished all SAM Prerequisites.
Leader: Tenant has gone beyond the minimum expectations of the SAM Prerequisites and demonstrated a commitment to sustainable initiatives.
Mentor: Tenant has achieved the highest level of green airplane certification and meets several CDA requirements above and beyond the prerequisite credits. Tenant is a resource and a good example to other tenants and regularly promotes, advocates and improves upon their sustainability achievements.
In order to achieve SAM Mentor Certification, Food Service Tenants must also obtain the following ten (10) SAM Credits:
1) SAM Credit AP.3 – Corporate Sustainability Policy 2) SAM Credit 8.2 – Establish and Implement Employee Sustainability Training Program 3) SAM Credit 9.2 – Eliminate the Use of Polystyrene Foam 4) SAM Credit 9.3.2 – Consumer Disposable Products: Bio-based Content 5) SAM Credit 9.3.4 – Consumer Disposable Products: Post-Consumer Recycled Paper 6) SAM Credit 9.4 – Local/Regional Food Sources 7) SAM Credit 9.5 – Sustainable Food and Consumer Products 8) SAM Credit 13.1 – Waste Stream Audit 9) SAM Credit 13.4 – Storage and Collection of Recyclables
10) SAM Credit 13.6.1 – Organic Byproduct Recycling: Food Waste
CT-11
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CT-DC GREEN AIRPLANE RATING SYSTEM
Certification Level
Points Required to Achieve Rating
Terminal Tenants Non-Terminal Tenants
Food Service Tenant* Non-Food Service
Tenant
Full Service
Counter Service
To-Go, Kiosk
Buildout Free-
Standing, Kiosk
Food Service Tenant*
Non-Food Service Tenant
Prerequisites 4 4 4 4 4 5 5
Achiever 6-43 6-40 6-27 6-36 6-21 6-54 6-47
Leader 44-69 41-65 28-43 37-57 22-34 55-87 48-75
Mentor* 70-88 66-82 44-55 58-73 35-44 88-110 76-95
*In addition to the points above, Food Service Tenants must also meet all prerequisites and the following credits, where applicable, to achieve a Mentor rating: AP.3, 8.2, 9.2, 9.3.2.1, 9.3.4.1, 9.4, 9.5, 13.1, 13.5, and 13.7.1
IMPLEMENTATION AND REVIEW PROCESS
The SAM and its supporting documentation are administered by the Sustainable Review Panel (SRP), which currently consists of representatives from; the CDA Management Staff, CDA Concession & Tenant Staff and Representatives, and Airport Planners actively involved in CDA projects. The composition of the SRP is intended to be dynamic depending on needs.
The SRP is responsible for the submittals with respect to sustainability and provides technical support. CT Design & Construction reviews will take place as needed while performance reviews using CT Operations & Maintenance can take place routinely, such as annually or on the anniversary of the tenant’s lease agreement. The SRP is responsible for the review and awarding of “Green Airplane Certifications” based on the extent of incorporation of sustainable practices as outlined in this Manual and as documented on the submitted SAM Checklist(s).
In addition, the SRP is responsible for presentations and training to tenants with respect to the application of this Manual. The primary tasks of the SRP are to oversee the application of the Manual and review submittals for their compliance with the Manual.
For any and all sustainability-related questions and/or submittals, please use the following email address to submit forms electronically (preferred method):
CT-12
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
CT-13
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Chicago Department of Aviation
SUSTAINABLE AIRPORT MANUAL
CONCESSIONS & TENANTS
DESIGN & CONSTRUCTION
SECTION
NOTE:
Please refer to page CT-5 for introduction and applicability of this section.
CT-14
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
1.0 SUSTAINABLE SITES
1.1 Prerequisite 1 – Adopt CDA Best Management Practices
Required
INTENT
Minimize the environmental impacts of facility operations.
REQUIREMENTS
Adopt the CDA Best Management Practices (BMP) Manual.
Depending on the project, the owner, tenant, or ultimate occupant must incorporate the CDA BMP Manual into their tenant or lease agreement.
SUBMITTALS
Include confirmation that all applicable BMPs are followed. Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
The BMP Manual defines the practices and measures used to reduce or eliminate the amount of pollution to the environment surrounding Chicago O’Hare and Midway International Airports. The BMPs are typically in the form of a procedure, activity, or structural control.
Standard Practice
The BMP Manual has been in effect since August 2002. There are a number of practices already implemented at Chicago O’Hare and Midway via this manual. Many of these practices deal with pollution prevention for all airport entities.
Recommended Practice
None
Best Available Practice
None
CT-15
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
1.0 SUSTAINABLE SITES
1.2 Light Pollution Reduction
1 Point
INTENT
Minimize light trespass from the tenant space, reduce sky-glow to increase night sky access, improve nighttime visibility through glare reduction, and reduce development impact on nocturnal environments.
REQUIREMENTS
FOR INTERIOR LIGHTING
The angle of maximum candela from each interior luminaire as located in the space shall intersect opaque building interior surfaces and not exit out through the windows.
OR All non-emergency interior lighting shall be automatically controlled to turn off during non-business hours. Provide manual override capability for after hours use.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Adopt site lighting criteria to maintain safe light levels while avoiding off-site lighting and night sky pollution.
Standard Practice
Install and utilize motion sensor lighting controls to turn off lighting during non-business hours or when space is not occupied and in use
Recommended Practice
Minimize lighting where possible and model the lighting using a computer model Evaluate smart-lighting control systems and LED light technologies
CT-16
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 Water Efficiency
2.1 Prerequisite 1 – Water Use Reduction
Required
INTENT
Increase water efficiency within tenant spaces to reduce the burden on municipal water supply and wastewater systems.
REQUIREMENTS
Employ strategies that in aggregate use 20% less water than the water use baseline calculated for the space. The baseline shall meet the requirements of the Energy Policy Act (EPAct) of 1992 and subsequent rulings by the Department of Energy, requirements of the Energy Policy Act of 2005, and the plumbing code requirements as stated in the 2006 editions of the Uniform Plumbing Code or International Plumbing Code as to fixture performance. Calculations are based on estimated occupant usage and shall include only the following fixtures and fixture fittings (as applicable to the tenant space): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and pre-rinse spray valves.
Commercial Fixtures and Fittings Minimum Requirement Commercial Toilets 1.28 gallons per flush (gpf)*
Except blow-out fixtures: 3.5 gpf 1.6/1.1 gpf – Dual Flush
Commercial Urinals 0.8 gpf Commercial Lavatory (restroom) Faucets 1.8 gallons per minute gpm at 60 pounds per
square inch (psi), private applications only (hotel or motel guest rooms, hospital patient rooms) 0.5 gpm at 60 psi** all others except private applications 0.25 gallons per cycle for metering faucets
Commercial Pre-Rinse Spray Valves (for food service applications)
Flow rate ≤ 1.6 gpm (no pressure specified; no performance requirement)
Commercial Clothes Washing–less than 80lbs
9 gallon/CF/cycle
Commercial Dishwashers Undercounter – high temp 1.98 gallon/rack Undercounter – low temp 1.95 gallon/rack Door type – high temp 1.44 gallon/rack Door type – low temp 1.85 gallon/rack Single tank rack conveyor – high temp 1.13 gallon/rack Single tank rack conveyor – low temp 1.23 gallon/rack Multi-tank rack conveyor – high temp 1.1 gallon/rack Multi-tank rack conveyor – low temp 0.99 gallon/rack
CT-17
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Commercial Fixtures and Fittings Minimum Requirement Flight type 180 gallon/hour Commercial Ice Machines ice machine (ice making head) IMH H
<450 lb/day <25 gal/100 lb ice
ice machine (ice making head) IMH H>450lb/day
<25 gal/100 lb ice
ice machine (w/o remote compressor) H< 1000lb/day
<25 gal/100 lb ice
ice machine (w/o remote compressor) H> 1000 lb/day
<25 gal/100 lb ice
ice machine (w/o remote compressor) H> 934 lb/day
<25 gal/100 lb ice
ice machine (w/o remote compressor) H> 934 lb/day
<25 gal/100 lb ice
ice machine self contained unit <35 gal/100 lb ice ice machine water cooled MUST BE ON CHILLED LOOP Ice machines once through water cooled BANNED Food Steamers Steam cooker – batch cooking 815 gallon/hour/plan
Steam cooker – high production/cook to order
84 gallon/hour/plan
Combination Oven Countertop or stand mounted 40 gph Roll-in 60 gph Other Equipment Performance baseline based on industry
standards *Based on 15 inch fryer **AV = adjusted volume = (1.63 x freezer volume) + refrigerator volume
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
WaterSense™-certified fixtures and fixture fittings should be used where available. Use high-efficiency fixtures (water closets and urinals) and dry fixtures such as composting toilet systems to reduce the potable water demand. Consider the use of alternate on-site sources of water, (e.g., rainwater, stormwater, or air conditioner condensate), and graywater for non-potable applications (e.g., toilet and urinal flushing), as approved by the manufacturer, and for custodial uses.
Special consideration should be used to distinguish applicability of these technologies in high-volume passenger terminal areas versus office facilities, especially with respect to maintenance.
CT-18
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
Chicago Building Code (CBC) meets the Energy Policy Act of 1992 (EPAct 1992)
Recommended Practice
Must exceed CBC (EPAct 1992) by 20% to meet prerequisite Use high-efficiency fixtures and valves, automatic flush sensors, aerators on
faucets and dual-flush toilets Use local generation of domestic hot water, as much as possible, to eliminate
long piping runs associated with recirculation piping. Unless connecting to an existing hot water recirculating system.
Domestic hot water for general plumbing fixtures should be designed for a temperature of 140°F maximum, but not less than 120°F
Best Available Practice
Install dry fixtures such as composting toilets and waterless urinals to reduce wastewater volumes
Use instantaneous hot water heating systems (i.e., tankless, on-demand hot water heating)
Use zoned or sub-metering to measure and audit water consumption rates at points of use
CT-19
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
2.0 Water Efficiency
2.2 Water Use - Additional Reduction
2 to 6 Points
INTENT
Further increase water efficiency within tenant space to reduce the burden on municipal water supply and wastewater systems.
REQUIREMENTS
Employ strategies that in aggregate use less water than the water use baseline calculated for the tenant space.
The minimum water savings percentage for each point threshold is as follows:
SAM Credit Water Reduction Points
2.2.1 30% 2
2.2.2 35% 4
2.2.3 40% 6
Calculate the baseline according to the commercial baselines outlined below1. Calculations are based on estimated occupant usage and must include only the following fixtures and fixture fittings (as applicable to the project scope): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and pre-rinse spray valves.
1 Tables adapted from information developed and summarized by the U.S. Environmental Protection Agency (EPA) Office of Water based on requirements of the Energy Policy Act (EPAct) of 1992 and subsequent rulings by the Department of Energy, requirements of the EPAct of 2005, and the plumbing code requirements as stated in the 2006 editions of the Uniform Plumbing Code or International Plumbing Code pertaining to fixture performance.
CT-20
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Commercial Fixtures and Fittings Current Baseline Commercial Toilets 1.6 gallons per flush (gpf)*
Except blow-out fixtures: 3.5 (gpf) Commercial Urinals 1.0 (gpf) Commercial Lavatory (restroom) Faucets 2.2 gallons per minute (gpm) at 60 pounds
per square inch (psi), private applications only (hotel or motel guest rooms, hospital patient rooms) 0.5 (gpm) at 60 (psi)** all others except private applications 0.25 gallons per cycle for metering faucets
Commercial Pre-Rinse Spray Valves (for food service applications)
Flow rate ≤ 1.6 (gpm) (no pressure specified; no performance requirement)
Commercial Clothes Washing–less than 80lbs 9 gallon/CF/cycle Commercial Dishwashers Undercounter – high temp 1.98 gallon/rack Undercounter – low temp 1.95 gallon/rack Door type – high temp 1.44 gallon/rack Door type – low temp 1.85 gallon/rack Single tank rack conveyor – high temp 1.13 gallon/rack Single tank rack conveyor – low temp 1.23 gallon/rack Multi-tank rack conveyor – high temp 1.1 gallon/rack Multi-tank rack conveyor – low temp 0.99 gallon/rack Flight type 180 gallon/hour Commercial Ice Machines ice machine (ice making head) IMH H <450
lb/day <25 gal/100 lb ice
ice machine (ice making head) IMH H>450lb/day
<25 gal/100 lb ice
ice machine (w/o remote compressor) H< 1000lb/day
<25 gal/100 lb ice
ice machine (w/o remote compressor) H> 1000 lb/day
<25 gal/100 lb ice
ice machine (w/o remote compressor) H> 934 lb/day
<25 gal/100 lb ice
ice machine (w/o remote compressor) H> 934 lb/day
<25 gal/100 lb ice
ice machine self contained unit <35 gal/100 lb ice ice machine water cooled MUST BE ON CHILLED LOOP Ice machines once through water cooled BANNED Food Steamers Steam cooker – batch cooking 815 gallon/hour/plan
CT-21
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Commercial Fixtures and Fittings Current BaselineSteam cooker – high production/cook to order 84 gallon/hour/plan
Combination Oven Countertop or stand mounted 40 gph Roll-in 60 gph Other Equipment Performance baseline based on industry
standards *Based on 15 inch fryer **AV = adjusted volume = (1.63 x freezer volume) + refrigerator volume
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
For many retail applications, process water (water use related to the product of service provided) far outweighs water used for toilets, sinks and showers. Process water also includes water used in cooling systems or any other equipment not directly related to the Energy Policy Act of 1992 (e.g. faucets, toilets, urinals, and showerheads). In addition to specifying water-efficient fixtures and appliances, consider alternative sources of water for non-potable applications such as toilet and urinal flushing, mechanical systems, cleaning, vehicle washing and other applications that do not require potable water.
WaterSense™-certified fixtures and fixture fittings should be used where available. Use high-efficiency fixtures (water dispensers, water closets and urinals) and dry fixtures such as composting toilet systems to reduce the potable water demand. Consider the use of alternate on-site sources of water, such as rainwater, stormwater, or air conditioner condensate, and graywater for non-potable applications such as toilet and urinal flushing, as approved by the manufacturer, and custodial uses.
Standard Practice
None
Recommended Practice
Use high-efficiency fixtures and valves, such as automatic sensors, aerators on lavatories and dual-flush toilets
Best Available Practice
Dry fixtures such as composting toilets and waterless urinals to reduce wastewater volumes
CT-22
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3.0 ENERGY & ATMOSPHERE
3.1 Prerequisite 1 – Fundamental Systems Commissioning
Required
INTENT
Verify that the project’s energy related systems are installed, calibrated and perform according to the owner’s project requirements, basis of design, and construction documents.
REQUIREMENTS
The following commissioning process activities shall be completed by the commissioning team. Designate an individual as the Commissioning Authority (CxA) to lead, review and oversee the completion of the commissioning process activities.
o The CxA shall have documented commissioning authority experience in at least two building projects.
o The individual serving as the CxA shall be independent of the project’s design and construction management, though they may be employees of the firms providing those services. The CxA may be a qualified employee or consultant of the Owner.
o The CxA shall report results, findings and recommendations directly to the Owner.
o For projects smaller than 50,000 gross square feet, the CxA may include qualified persons on the design or construction teams who have the required experience.
The Owner shall document the Owner’s Project Requirements (OPR). The design team shall develop the Basis of Design (BOD). The CxA shall review these documents for clarity and completeness. The Owner and design team shall be responsible for updates to their respective documents.
Develop and incorporate commissioning requirements into the construction documents.
Develop and implement a commissioning plan.
Verify the installation and performance of the systems to be commissioned.
Complete a summary commissioning report.
COMMISSIONED SYSTEMS Commissioning process activities shall be completed for the following energy-related systems, at a minimum:
Heating, ventilating, air conditioning and refrigeration (HVAC&R) systems (mechanical and passive) and associated controls
CT-23
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Lighting and daylighting controls Domestic hot water systems Renewable energy systems (wind, solar etc.)
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Engage a CxA as early as possible in the design process. Determine the owner’s project requirements, develop and maintain a commissioning plan for use during design and construction and incorporate commissioning requirements in bid documents. Assemble the commissioning team, and prior to occupancy verify the performance of energy consuming systems. Complete the commissioning reports with recommendations prior to accepting the commissioned systems. Owners are encouraged to seek out qualified individuals to lead the commissioning process. Qualified individuals are identified as those who possess a high level of experience in the following areas:
Energy systems design, installation and operation Commissioning planning and process management Hands-on field experience with energy systems performance, interaction, start-up,
balancing, testing, troubleshooting, operation, and maintenance procedures Energy systems automation control knowledge
Although the commissioning process should start as early in the design process as possible, it is allowable to engage a CxA agent to execute fundamental commissioning after construction has begun.
Standard Practice
Commissioning Agents are typically engaged to conduct fundamental commissioning
Recommended Practice
Review the design intent and the basis of design documentation Incorporate commissioning requirements into the construction documents Develop and utilize a commissioning plan Verify installation, functional performance, training, operations and maintenance
documentation Complete a commissioning report Provide the owner with a single manual that contains the information required for
re-commissioning systems
CT-24
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Engage a commissioning team that does not include individuals directly responsible for project design or construction management to evaluate both space and site systems as part of the commissioning plan
Priority Systems - high energy consuming systems. o All HVAC system equipment o Lighting controls and sensors o Lighting o Refrigeration systems o Information Technology Systems - IT (included in process loads: to
promote energy savings, use the exceptional calculation method described in ANSI/ASHRAE/IESNA 90.1-2010 G2.5)
Lower Priority Systems – low energy consuming system. o Emergency Power Generators and Automatic Transfer Switching o Uninterruptible Power Supply systems o Life Safety systems; Fire protection Fire alarm, Egress pressurization o Lightning Protection o Domestic and Process water pumping and mixing systems o Equipment sound control systems o Data and Communication systems o Paging systems o Security systems o Plumbing o Illuminated guidance signage
Best Available Practice
None
CT-25
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3.0 ENERGY & ATMOSPHERE
3.2 Prerequisite 2 – Minimum Energy Performance
Required
INTENT
Establish the minimum level of energy efficiency for the tenant space systems to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
Design portions of the tenant’s space to comply with the ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda2) to complete the following:
Comply with the mandatory provisions (Sections 5.4, 6.4, 7.4, 8.4, 9.4 and 10.4) in Standard 90.1-2010 (with errata but without addenda)
Achieve the prescriptive requirements (Sections 5.5, 6.5, 7.5 and 9.5) or performance requirements (Section 11) of ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda)
Reduce connected lighting power density 10% below that allowed by ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda) using either the Space-by-Space Method or by applying the whole lighting power allowance to the entire tenant space
Install ENERGY STAR equipment for 50% (by rated-power) of ENERGY STAR eligible items. This requirement includes; appliances, office equipment, electronics, and commercial food service equipment. Excluded are heating, ventilating and air conditioning (HVAC) and lighting.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Design the tenant space and systems to meet baseline requirements. Use a computer simulation model, where applicable, to assess the energy performance and identify the most cost-effective energy efficiency measures.
If a local code has demonstrated quantitative and textual equivalence following, at a minimum, the U.S. Department of Energy (DOE) standard process for commercial energy code determination, then the results of that analysis may be used to correlate local code performance
2 Project teams wishing to use ASHRAE approved addenda for the purposes of this credit may do so at their discretion. Addenda must be applied consistently across all SAM credits.
CT-26
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
with ASHRAE 90.1-2010. Details on the DOE process for commercial energy code determination can be found at: http://www.energycodes.gov/regulations/determinations.
Standard Practice
The Chicago Energy Conservation Code (CECC 2008) currently requires that buildings meet the 2006 International Energy Conservation Code (IECC) with an alternate compliance path of ASHRAE/IESNA 90.1-2004 standard with some exceptions
Recommended Practice
Design tenant space using the more current ASHRAE/IESNA 90.1-2010 standard
Best Available Practice
None
CT-27
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3.0 ENERGY & ATMOSPHERE
3.3 Optimize Energy Performance
1 to 19 Points
INTENT
Achieve increasing levels of energy performance beyond the prerequisite standard to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
Select one of the two compliance path options described below. Project teams documenting achievement using any of the 2 options are assumed to be in compliance with SAM Credit 3.2 Minimum Energy Performance.
OPTION 1 – ENTIRE SPACE ENERGY SIMULATION (1 to 19 points)
Demonstrate a percentage improvement in the proposed space performance rating compared with the baseline space performance rating. Calculate the baseline space performance according to Appendix G of ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda) using a computer simulation model for the whole tenant space project.
CT-28
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
The minimum energy savings percentages for each point threshold are as follows:
SAM Credit % Energy Reduction Over Baseline* Points
3.3.1 8% 1
3.3.2 10% 2
3.3.3 12% 3
3.3.4 14% 4
3.3.5 16% 5
3.3.6 18% 6
3.3.7 20% 7
3.3.8 22% 8
3.3.9 24% 9
3.3.10 26% 10
3.3.11 28% 11
3.3.12 30% 12
3.3.13 32% 13
3.3.14 34% 14
3.3.15 36% 15
3.3.16 38% 16
3.3.17 40% 17
3.3.18 42% 18
3.3.19 44% 19 * Baseline calculated in SAM Credit 3.2 Minimum Energy Performance
All energy uses associated with the project must be included in the energy simulation model. Improvements to non-regulated loads must be documented as described below. Regulated energy systems include HVAC (heating, cooling, fans, and pumps), service water heating, and lighting. Process loads for tenants may include refrigeration equipment, cooking and food preparation, clothes washing, and other major support appliances. Merchandise for sale that is plugged in, and small moveable appliances are not candidates for improved energy performance.
Appendix G of ASHRAE Standard 90.1-2010 requires that the energy analysis done for the Building Performance Rating Method include ALL of the energy costs within and associated with the building project. To achieve points using this credit, the proposed design must meet the following criteria:
Comply with the mandatory provisions in ASHRAE Standard 90.1-2010, Sections 5.4, 6.4, 7.4, 8.4, 9.4 and 10.4 (with errata but without addenda)
Include all the energy costs within and associated with the tenant space project
CT-29
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Compare against a baseline space that complies with Appendix G to ASHRAE Standard 90.1-2010 (with errata but without addenda). There is no default process energy cost.
For the purpose of this analysis, process energy is considered to include, but is not limited to, office and general miscellaneous equipment, computers, elevators and escalators, kitchen cooking and refrigeration, laundry washing and drying, lighting exempt from the lighting power allowance (e.g. lighting integral to security operations) and other (e.g. waterfall pumps).
Regulated (non-process) energy includes lighting, HVAC (such as for space heating, space cooling, fans, pumps, toilet exhaust, kitchen hood exhaust, etc.), and service water heating for domestic or space heating purposes.
For this credit, process loads shall be identical for both the baseline tenant space performance rating and for the proposed tenant space performance rating. However, project teams may follow the Exceptional Calculation Method (ASHRAE 90.1-2010 G2.5) to document measures that reduce process loads. Documentation of process load energy savings shall include a list of the assumptions made for both the base and proposed design, and theoretical or empirical information supporting these assumptions.
OR
OPTION 2 — PRESCRIPTIVE COMPLIANCE PATH (1 to 10 points)
Comply with the prescriptive measures identified below. The tenant space must meet the following requirements below. Points will be awarded based on the number of appliance types or technologies implemented from the tables below. Points earned for this credit are as follows:
All Tenants
Points Number of Technologies/ Strategies
Implemented from Table 1
1 1
2-3 3
4-5 5
6-7 7
8+ 10
CT-30
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Table 1 - All Tenants:
Technology/Strategy Requirement
LED Lighting For at least 30% of lighting load
CFL Lighting For at least 60% of lighting load
Energy-Efficient Halogen Lamps High pressure, krypton or xenon containing lamps (argon not acceptable)
T8 and T5 Fluorescent Lamps Where applicable
Light Sensors or Timers Where applicable
Motion-Controlled Sensors Where applicable
ENERGY STAR Rated Appliances and Electronic Equipment
At least one ENERGY STAR item type but must be for all items of that type, e.g. all computers, all printers
ENERGY STAR Rated Ventilation Equipment
Includes exhaust and ceiling fans; at least one ENERGY STAR item type but must be for all items of that type, e.g. all exhaust fans
ENERGY STAR Rated HVAC Equipment
Includes furnaces and air conditioning units; at least one ENERGY STAR item type but must be for all items of that type, e.g. all exhaust fans
Appliances listed in Table 2 Per each item in Table 2 (maximum of 5 items)
User-Defined The SRP will consider other proposed strategies and technologies. Points will be awarded at the discretion of the SRP.
Table 2 – Food Service Tenants:
Appliances Eligible for Additional Points toward Credit Requirements:
Appliance Type Power Source
Minimum Efficiency Max Idle
Rate Water Use
Energy Star Category
Fryers elec 80% 1000 W* n/a Yes Large vat fryers elec 80% 1250 W n/a Pending Steam cooker-bach coating
elec 50% 135 W/pan 2
gph/pan Yes
Steam cooker- high production/cook to order
elec 50% 275 W/pan 3
gph/pan Yes
Hot food holding cabinets
elec 20 W/ft2 n/a Yes
Solid door reach-in refrigerators
elec 0.06V+1.22 kWh/day n/a n/a Yes
Solid door reach-in freezers
elec 0.29V+0.97 kWh/day n/a n/a Yes
CT-31
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Appliance Type Power Source
Minimum Efficiency Max Idle
Rate Water Use
Energy Star Category
Solid door reach-in refrigerator/freezer
elec 0.27AV-0.71 kWh/day** n/a n/a Yes
Glass door reach-in refrigerators
elec 0.086V+2.39 kWh/day n/a n/a Pending
Ice cream freezer elec 0.39V+0.82 kWh/day n/a n/a Yes
Undercounter dish machines- high temp
elec N/a 900 W 1
gal/rack Yes
Undercounter dish machines- low temp
elec N/a 500 W 1.7
gal/rack Yes
Door type dish machine- high temp
elec N/a 1000 W 0.95
gal/rack Yes
Door type dish machine- low temp
elec N/a 600 W 1.18
gal/rack Yes
Single tank rack conveyor dish machine- high temp
elec N/a 2000 W 0.7
gal/rack Yes
Single tank rack conveyor dish machine- low temp
elec N/a 1600 W 0.79
gal/rack Yes
Multi-tank rack conveyor dish machine- high temp
elec N/a 2600 kW
0.54
gal/rack Yes
Multi-tank rack conveyor dish machine- low temp
elec N/a 2000 W 0.54
gal/rack Yes
Ice machine [ice making head] IMH H<450 lb/day
elec 9.23-0.0077H kWh/100
lb ice n/a
20 gal/100 lb
ice
Yes [but with lower water
use] Ice machine [ice making head] IMH H ≥ 450 lb/day
elec 6.20-0.0010H kWh/100
lb ice n/a
20 gal/100 lb
ice
Yes [but with lower water
use] Ice machine [w/o remote compressor] H< 1000 lb/day
elec 8.05-0.0035H kWh/100lb ice
n/a 20
gal/100 lb ice
Yes [but with lower water
use]
Ice machine [w/o remote compressor] H ≥ 1000 lb/day
elec 4.64 kWh/100lb ice n/a 20
gal/100 lb ice
Yes [but with lower water
use]
Ice machine [w remote compressor] H< 934 lb/day
elec 8.05-0.0035H kWh/100lb ice
n/a 20
gal/100 lb ice
Yes [but with lower water
use]
CT-32
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Appliance Type Power Source
Minimum Efficiency Max Idle
Rate Water Use
Energy Star Category
Ice machine [w remote compressor] H≥ 934 lb/day
elec 4.82 kWh/100 lb ice n/a 20
gal/100 lb ice
Yes [but with lower water
use]
Ice machine self-contained unit H< 175 lb/day
elec 16.7-0.0436H kWh/ 100
lb ice n/a
30 gal/100 lb
ice
Yes [but with lower water
use] Ice machine contained unit H≥ 175 lb/day
elec 9.11 kWh/100lb ice n/a 30
gal/100 lb ice
Yes [but with lower water
use] Ice machine water cooled IMH H<500 lb/day [note: must be on a chilled loop]
elec 7.02-0.005H kWh/100lb
ice n/a
20 gal/100 lb
ice
Ice machine water cooled IMH H≥ 500lb/day <1436 lb/day [note: must be on a chilled loop]
elec 5.13-0.001H kWh/100lb
ice n/a
20 gal/100 lb
ice
Ice machine water cooled IMH H≥ 1436 lb/day [note: must be on a chilled loop]
elec 3.7 kWh/100lb ice n/a 20
gal/100 lb ice
Ice machine water cooled SCU H<200 lb/day [note: must be on a chilled loop]
elec 10.6-0.177H kWh/100lb
ice n/a
30 gal/100 lb
ice
Ice machine water cooled SCU H≥200 lb/day [note: must be on a chilled loop]
elec 7.07 kWh/100lb ice n/a 30
gal/100 lb ice
Ice machine water cooled once-through [open loop]
BANNED BANNED BANNED BANNED
Griddles elec 70% 350 w/ft2 n/a Pending
Range elec 80%
Convection ovens [full size]
elec 70% 1750 W n/a Pending
Combination ovens [countertop or island]
elec 60% 800 W/pan 15 gph Pending
Combination ovens [roll-in]
elec 60% 800 W/pan 20 gph Pending
CT-33
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Appliance Type Power Source
Minimum Efficiency Max Idle
Rate Water Use
Energy Star Category
Bread toaster [light duty]
elec 3600 W [8% duty cycle]
= 2 pop-ups
Pre-rinse spray valves
n/a n/a n/a s 1.2 gpm n/a
Kitchen exhaust hood
n/a
35% reduction in design [full speed]
ventilation rate [cfm] or demand controlled
ventilation
n/a n/a n/a
Fryers gas 50% 9000
BTU/h* n/a Yes
Large vat fryers gas 50% 12000 BTU/h
Pending
Steam cooker- bach coating
gas 38% 2100
BTU/h/pan 2 gph/pan Yes
Steam cooker- high production/ cook to order
gas 38% 4300
BTU/h/pan 3 gph/pan Yes
Griddles gas 38% 2700
BTU/h/ft2 n/a Pending
Convection ovens [full size]
gas 43% 13000 BTU/h
n/a Pending
Combination ovens gas 40% 2850
BTU/h/pan 15 gph Pending
Combination ovens gas 40% 2850
BTU/h/pan 20 gph Pending
Rack ovens- single gas 50% 29000 BTU/h
n/a Pending
Rack ovens- double
gas 50% 35000 BTU/h
n/a Pending
Broiler [underfired] gas 35% 12500
BTU/h/ft2 peak input
n/a No
Conveyor oven [small = < 25 inch bell]
gas 42% 29000 BTU/h
n/a Pending
Conveyor oven [large = > 25 inch bell]
gas 42% 58000 BTU/h
n/a Pending
Clothes washer 2.00 MEF 6.0 WF n/a
*Based on 15 inch fryer **AV = adjusted volume = (1.63 x freezer volume) + refrigerator volume
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
CT-34
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
For some tenants, regulated loads will represent the primary energy use. For others, process loads will be the biggest energy use. In either case, look at the equipment and systems that use energy and identify strategies to reduce energy use. Consider first cost, maintenance, replacement costs, and any potential benefit or detriment to staff or customers when selecting strategies. Design the tenant space and systems to maximize energy performance. Use a computer simulation model to assess energy performance and identify the most cost-effective energy efficiency measures. Quantify energy performance compared with the baseline benchmark. Install energy efficient equipment, such as retail display lighting, dishwashers and enclosed refrigerator cases. Utilize heat recovery and heat rejection strategies. Work with equipment manufacturers to improve energy efficiency, particularly for volume build applications. Small independent tenants can use historic utility bills from similar stores, generic retail energy data, and data from their local utility or computer modeling. Regardless of the methodology used by any tenant in setting their energy budget, the credit narrative should include a description of the methodology used and assumptions made.
Standard Practice
The Chicago Energy Conservation Code (CECC 2008) currently requires that buildings meet the 2006 International Energy Conservation Code (IECC) which has an alternate compliance path of following ASHRAE/IESNA 90.1-2004 standard with some exceptions. LEED 2009 and the SAM require the more current ASHRAE/IESNA 90.1-2010 standard.
Recommended Practice
Use a computer simulation model to assess energy performance and identify the most cost effective energy measures
Provide high-efficiency motors and variable-speed pumping systems Provide energy efficient lighting systems including LED, fluorescent lighting, solar
lighting and the use of lighting sensors or timers Organize circuiting of lighting and tenant space systems so that individual areas
may be separately controlled relative to daylight and heating/cooling zones Optimize architectural features for daylighting and glare control. Consider light
shelves, ceiling design, window placement, and window treatments Provide motion sensors in stairs, toilet rooms, storage rooms and equipment
rooms unless life safety is compromised Provide ENERGY STAR compliant equipment and appliances Use LED lighting, wherever applicable Optimize lighting controls for energy savings and function Provide daylight harvesting control systems Use high performance glazing (double glazed, low-e) and window systems Utilize high efficiency motors, generators and pumps where applicable
CT-35
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
Consider the following for tenant spaces:
Integrate lighting systems with Tenant Space Automation System Use spectrally selective glazing Evaluate underfloor air distribution systems in office-type spaces Evaluate “green walls” for tenant space Utilize premium efficiency motors where applicable
CT-36
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3.0 ENERGY & ATMOSPHERE
3.4 Enhanced Commissioning
2 Points
INTENT
Begin the commissioning process early in the design process and execute additional activities after systems performance verification is completed.
REQUIREMENTS
Implement, or have a contract in place to implement, the following additional commissioning process activities in addition to the requirements of SAM Credit 3.1 Fundamental Systems Commissioning:
Prior to the start of the construction documents phase, designate an independent Commissioning Authority (CxA) to lead, review, and oversee the completion of all commissioning process activities.
o The CxA shall have documented commissioning authority experience in at least two building projects.
o The individual serving as the CxA: Must be independent of the work of design and construction;
Must not an employee of the design firm, though they may be contracted through them;
Must not be an employee of, or contracted through, a contractor or construction manager holding construction contracts; and
May be a qualified employee or consultant of the Owner.
o The CxA must report results, findings and recommendations directly to the Owner.
The CxA must conduct, at a minimum, one commissioning design review of the Owner’s Project Requirements (OPR), Basis of Design (BOD), and design documents prior to mid-construction documents phase and back-check the review comments in the subsequent design submission.
The CxA must review contractor submittals applicable to systems being commissioned for compliance with the OPR and BOD. This review shall be concurrent with A/E reviews and submitted to the design team and the Owner.
The CxA or other project team members must develop a systems manual that gives future operating staff the information needed to understand and optimally operate the commissioned systems.
CT-37
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
The CxA or other project team members must verify that the requirements for training operating personnel and tenant space occupants are completed.
The CxA must be involved in reviewing the operation of the space with occupants within 10 months after substantial completion. A plan for resolving of outstanding commissioning-related issues must be included.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Although it is preferable that the CxA be contracted by the Owner, for the enhanced commissioning credit, the CxA may also be contracted through the design firms or construction management firms not holding construction contracts. The LEED Reference Guide provides detailed guidance on the rigor expected for following process activities:
Commissioning design review Commissioning submittal review Systems manual
Though the commissioning process should start as early in the design process as possible, it is allowable to engage a CxA agent to conduct the design review required after construction has started, so long as the project team agrees to implement any requested changes both to the documents and to construction that may have already occurred.
Standard Practice
None
Recommended Practice
Review the design intent and the basis of design documentation Incorporate commissioning requirements into the construction documents Develop and utilize a commissioning plan Verify installation, functional performance, training, operations and maintenance
documentation Complete a commissioning report Provide the owner with a single manual that contains the information required for
re-commissioning systems Engage a commissioning team that does not include individuals directly
responsible for project design or construction management to evaluate tenant systems as part of the commissioning plan
Priority Systems - high energy consuming systems o All HVAC system equipment
CT-38
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
o Lighting controls and sensors o Lighting o Refrigeration systems o Information Technology Systems - IT (included in process loads: to
promote energy savings, use the exceptional calculation method described in ANSI/ASHRAE/IESNA 90.1-2010 G2.5)
Lower Priority Systems – low energy consuming systems o Emergency Power Generators and Automatic Transfer Switching o Uninterruptible Power Supply systems o Life Safety systems; Fire protection Fire alarm, Egress pressurization o Lightning Protection o Domestic and Process water pumping and mixing systems o Equipment sound control systems o Data and Communication systems o Paging systems o Security systems o Plumbing o Illuminated guidance signage
Best Available Practice
None
CT-39
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3.0 ENERGY & ATMOSPHERE
3.5 Measurement and Verification
3 Points
INTENT
Provide for the ongoing accountability of tenant energy consumption over time.
REQUIREMENTS
TERMINAL TENANTS (3 points): Develop and implement a Measurement and Verification (M&V) Plan consistent with Option B, C, or D of the 2001 International Performance Measurement & Verification Protocol (IPMVP) Volume I: Concepts and Options for Determining Energy and Water Savings. The M&V period shall cover a period of no less than one year of post-construction occupancy.
AND
Complete one or more of the following: Install submetering equipment to measure and record energy use within the tenant
space. Negotiate a lease whereby energy costs are paid by the tenant and not included in the
base rent.
NON-TERMINAL TENANTS (3 points): Develop and implement a Measurement and Verification (M&V) Plan consistent with Option D: Calibrated Simulation (Savings Estimation Method 2), or Option B: Energy Conservation Measure Isolation, as specified in the International Performance Measurement & Verification Protocol (IPMVP) Volume III: Concepts and Options for Determining Energy Savings in New Construction, April, 2003. The M&V period shall cover a period of no less than one year of post-construction occupancy.
SUBMITTALS
Include descriptive narrative in the SAM Checklist and M&V Plan.
TECHNOLOGY/STRATEGY
Develop an M&V Plan to evaluate space and/or energy system performance. Characterize the space and/or energy systems through energy simulation or engineering analysis. Install the necessary metering equipment to measure energy use. Track performance by comparing predicted performance to actual performance, broken down by component or system as appropriate. Evaluate energy efficiency by comparing actual performance to baseline performance.
CT-40
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
While the IPMVP describes specific actions for verifying savings associated with energy conservation measures (ECMs) and strategies, this Credit expands upon typical IPMVP M&V objectives. M&V activities should not necessarily be confined to energy systems where ECMs or energy conservation strategies have been implemented. The IPMVP provides guidance on M&V strategies and their appropriate applications for various situations. These strategies should be used in conjunction with monitoring and trend logging of significant energy systems to provide for the ongoing accountability of tenant energy performance.
Standard Practice
None
CT-41
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Install continuous metering equipment for the following end-uses: o Lighting systems and controls o Constant and variable motor loads o Variable frequency drive (VFD) operation o Chiller efficiency at variable loads (kW/ton) o Cooling load o Air and water economizer and heat recovery cycles o Air distribution static pressures and ventilation air volumes o Boiler efficiencies o Indoor water risers
Develop a Measurement and Verification plan that incorporates the monitoring information from the above end-uses and is consistent with Option B, C or D of the 2001 International Performance Measurement & Verification Protocol (IPMVP) Volume I: Concepts and Options for Determining Energy and Water Savings
Consider the recommendations included in the Chicago Climate Action Plan
Best Available Practice
Draft a Measurement & Verification Plan to apply during tenant operation that compares predicted savings to those achieved
CT-42
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3.0 ENERGY & ATMOSPHERE
3.6 Green Power
2 Points
INTENT
Encourage the development and use of grid-source, renewable energy technologies on a net zero pollution basis in order to off-set your carbon footprint.
REQUIREMENTS
Engage in at least a 2-year renewable energy contract to provide at least 35% of the tenant’s electricity from renewable sources, as defined by the Center for Resource Solutions Green-e Energy product certification requirements.
OPTION 1 – DETERMINE THE BASELINE ELECTRICITY USE
Use the annual electricity consumption from the results of the subparts of SAM Credit 3.3 Optimize Energy Performance.
OR
OPTION 2 – ESTIMATE BASELINE ELECTRICITY USE
Use the U.S. Department of Energy Commercial Buildings Energy Consumption Survey database to determine the estimated electricity use.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Determine the energy needs of the tenant space and investigate opportunities to engage in a green power contract. Green power is derived from solar, wind, geothermal, biomass or low-impact hydro sources. Visit www.green-e.org/energy for details about the Green-e program. The power product purchased to comply with credit requirements need not be Green-e certified. Other sources of green power are eligible if they satisfy the Green-e program’s technical requirements. Renewable energy certificates (RECs), tradable renewable certificates (TRCs), green tags and other forms of green power that comply with Green-e’s technical requirements can be used to document compliance with this section.
CT-43
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
Investigate opportunities to engage in a green power contract with the utility Visit www.green-e.org for details about the Green-e program
Best Available Practice
None
CASE STUDIES
Energy Efficient Burger King Burger King – Waghausel, Germany
The eco-friendly design developed in cooperation with Wirsol Solar AG (Baden-Württemberg) utilizes state-of-the-art technologies and renewable energy to power one-third of the restaurant’s energy consumption, thus reducing energy costs by 45% and the emission of CO2
by more than 120 metric tons every year.
The 20/20 design is complemented with the latest eco-friendly technologies and energy efficient construction elements including:
Interior heat recovery ventilation system that cools and heats the restaurant, saving 73% of energy consumption per year
Long-lasting interior and exterior LED bulbs saving more than 55% of energy consumption annually
Excess heat loss is captured to generate hot water, conserving 50% of energy usage annually
A wind turbine contributing up to 2,500 kWh to the restaurant’s power supply was added to the traditional exterior BK® logo sign
Photovoltaic and wind energy systems that save up to 45% of electricity annually; More than 720 solar photovoltaic modules generate over 53,500 kWh of electricity per
year, which equals the annual consumption of five U.S. households A solar-powered electric vehicle charging station for hybrid cars A rainwater reclamation system for outside irrigation
In addition, the restaurant kitchen features the revolutionary Duke Flexible Batch Broiler, which maximizes cooking flexibility while reducing gas consumption and related costs by 52 percent electricity consumption and costs by 90 percent. All BURGER KING® restaurants in North America have installed this new broiler and the international rollout is expected to be completed by the end of 2012.
www.restaurantnewsresource.com/article46521.html
CT-44
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Electricity from Waste Los Angeles World Airports - Los Angeles, California
Over 8,000 tons of food waste produced each year at Los Angeles International Airport is being used to produce methane gas which is then recycled and turned into electricity. This complex process involves food being ground up and mixed with water, creating slurry, which is then heated up into methane gas and carbon dioxide. Eventually this is transferred offsite to an adjacent power generation plant and converted into electricity.
www.wasteage.com/mag/waste_los_angeles_airport/
CT-45
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 MATERIALS & RESOURCES
4.1 Prerequisite 1 – Storage and Collection of Recyclables
Required
INTENT
Facilitate the reduction of waste generated by tenant space occupants that is hauled to and disposed of in landfills.
REQUIREMENTS
Provide an easily accessible dedicated area or areas that serve the tenant space for the collection and storage of materials for recycling, including (at a minimum) paper, corrugated cardboard, glass, plastics and metals. An area should also be dedicated to collection and storage of compostable food waste.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Designate an area for recyclable collection and storage that is appropriately sized and located in a convenient area. These areas would likely be designed and sized differently depending on the ultimate use and waste stream of the facility (e.g. office, airlines, concessionaires, etc.) Identify local waste handlers and buyers for glass, plastic, office paper, e-waste, newspaper, cardboard, metals, fluids, fixtures, and organic wastes. Instruct employees, occupants, and contractors on the recycling procedures. Consider employing cardboard balers, aluminum can crushers, recycling chutes and other waste strategies to further enhance the recycling program.
Standard Practice
Investigate and incorporate collection rooms for recycling streams that make sense for each tenant space
Designate an area for recyclable collection and storage that is appropriately sized and located in a convenient area
CT-46
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Coordinate recyclable waste collection with hauler capability Recycle the following waste, whenever feasible:
o Aluminum o Glass o Paper, newspapers, magazines and cardboard o Carpet o Wood (pallets/crates, etc.) o Food waste/grease and compostables o Organic waste and compostables o Scrap metal o Batteries o Light bulbs o Toner cartridges o Electrical wiring o Electronics including monitors
Instruct employees, users and occupants on recycling procedures
Best Available Practice
Employ cardboard balers, aluminum can crushers, recycling chutes and other technologies to enhance the recycling program
CT-47
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 MATERIALS & RESOURCES
4.2 Construction Waste Management
1 to 3 Points
INTENT
Divert construction and demolition debris from disposal in landfills and incineration facilities. Redirect recyclable recovered resources back to the manufacturing process and reusable materials to appropriate sites.
REQUIREMENTS
Recycle and/or salvage nonhazardous construction and demolition debris. Develop and implement a construction waste management plan that, at a minimum, identifies the materials to be diverted from disposal and whether the materials will be sorted on-site. Calculations must be done by weight (conversion may be necessary) and must be consistent throughout. The minimum percentage debris to be recycled or salvaged for each point threshold is as follows:
SAM Credit Recycled or Salvaged Points
4.2.1 50% 1
4.2.2 75% 2
4.2.3 100% 3
Section 11-4-1905 of the Chicago City Code, includes applicability requirements. For CDA purposes, all airport projects are applicable regardless of Section 11-4-1905.
SUBMITTALS
Include descriptive narrative on the SAM Checklist indicating the name of the project that will utilize the material, if other than current project or temporary storage locations, and the following:
A design estimate using the construction waste management form in CDA/OMP Specification 01524 – Construction Waste Management, to be provided by the designer with the SAM Design Checklist.
A Waste Management Plan as outlined in CDA/OMP Specification 01524 to be provided by the Contractor no later than 30 days prior to start of construction
Monthly construction waste management forms provided by the Contractor during construction
A final construction waste total provided by the Contractor prior to final payment
The submittal requirements follow the City of Chicago waste ordinance (Chicago Code Section 11-4-1905) with the following exceptions:
CT-48
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
All airport projects, including those not subject to Section 11-4-1905 of the Chicago Code, shall be subject to the submittal requirements of this credit
Submit documentation to CDA for tracking purposes in addition to documentation required by the ordinance
Note that the requirements of this credit are very similar to the Chicago construction waste ordinance and CDA/OMP Specification 01524 with the exceptions as noted above. The specification follows the City ordinance with additional provisions for submittal requirements and project applicability.
TECHNOLOGY/STRATEGY
Note that the City of Chicago waste ordinance mandates that a minimum of 50% of construction and demolition (C&D) waste produced on-site (as measured by weight) is recycled.
It is expected that these practices may lead to savings in material costs due to resource coordination and income generation from recycled/salvaged materials.
Standard Practice
Utilize designated areas for recycling construction debris on-site
Recommended Practice
Establish goals for diversion from disposal in landfills and incineration facilities and adopt a construction waste management plan to achieve these goals
Consider recycling cardboard, metal, brick, mineral fiber panel, concrete, plastic, wood, glass, gypsum wallboard, carpet and insulation
Construction debris processed into a recycled content commodity that has an open market value (e.g., wood derived fuel [WDF], alternative daily cover material, etc.) may be applied to the construction waste calculation
Designate a specific area(s) on the construction site for segregated collection and labeling of recyclable materials, and track recycling efforts throughout the construction process
Identify construction haulers and recyclers to handle the designated materials. Note that diversion may include donation of materials to charitable organizations and salvage of materials on-site
Implement deconstruction planning and techniques into all demolition activities. Careful and planned deconstruction of a facility can provide sustainable benefits related to disposal, reuse of materials, etc.
Ensure that employees are aware of waste management and recycling procedures
CT-49
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
Evaluate use, as appropriate, of pre-cast or pre-fabricated units whenever possible, to reduce on-site waste generation during construction
CT-50
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 MATERIALS & RESOURCES
4.3 Material Reuse
1 to 2 Points
INTENT
Reuse building materials and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
REQUIREMENTS
Use salvaged, refurbished or reused materials, the sum of which constitutes at least 5% or 10%, based on cost, of the total value of materials on the project. The minimum percentage materials reused for each point threshold is as follows:
SAM Credit Reused Materials Points
4.3.1 5% 1
4.3.2 10% 2
Only include materials in Construction Specification Institute (CSI) MasterFormat 1995 Divisions 2-10 in the calculations.
Mechanical, electrical and plumbing components and specialty items such as elevators and equipment cannot be included in this calculation. Include only materials permanently installed in the project. Furniture may be included if it is included consistently in SAM Credit 4.3 Materials Reuse through SAM Credit 4.7 Certified Wood. For terminal tenant spaces, do not include the existing shell of the space, i.e. walls, floor, ceiling, if not included in original project scope of work.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
Indicate the name of the project that will utilize the material, if other than current project and temporary storage locations if known.
TECHNOLOGY/STRATEGY
Identify opportunities to incorporate salvaged materials into the space design, and research potential material suppliers. Consider salvaged materials such as beams and posts, flooring, paneling, doors and frames, masonry, and metal railing (CSI Divisions 2 through 10, note: CSI Divisions 11 through 16 are counted in SAM Credit 4.9 – Equipment Salvage and Reuse).
Use a “virtual warehouse” to maintain a current listing of materials available for reuse on other projects.
CT-51
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
Prior to the demolition and removal of existing materials and equipment within a project area, notify the Chicago Department of Aviation to allow for the harvesting of used materials and equipment for potential reuse
Recommended Practice
None
Best Available Practice
None
CT-52
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 MATERIALS & RESOURCES
4.4 Recycled Content
1 to 2 Points
INTENT
Increase demand for building products that incorporate recycled content materials, thereby reducing impacts resulting from extraction and processing of virgin materials.
REQUIREMENTS
Use materials with recycled content such that the sum of post-consumer recycled content plus 1/2 of the pre-consumer content constitutes at least 10% or 20%, based on cost, of the total value of the materials in the project. The minimum percentage materials recycled for each point threshold is as follows:
SAM Credit Recycled Content Points
4.4.1 10% 1
4.4.2 20% 2
The recycled content value of a material assembly is determined by weight. The recycled fraction of the assembly is then multiplied by the cost of assembly to determine the recycled content value. If specific material cost is not available, assume 45% of total cost (inclusive of materials, labor and equipment) is representative of the material cost.
Only include materials in CSI MasterFormat 1995 Divisions 2-10 in the calculations.
Mechanical, electrical and plumbing components and specialty items such as elevators cannot be included in this calculation. Include only materials permanently installed in the project. Furniture may be included if it is included consistently in SAM Credit 4.3 Materials Reuse through SAM Credit 4.8 Furniture and Equipment.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
The submittals include the following:
A design estimate using the recycled content form in CDA/OMP Specification 01356 – Recycled Content, to be provided by the designer with the SAM Design Checklist
A pre-construction estimate using the recycled content form in CDA/OMP Specification 01356 – Recycled Content, to be provided by the contractor
A final construction estimate using the recycled content form in CDA/OMP Specification 01356 – Recycled Content, to be provided by the contractor with the SAM Construction Checklist
CT-53
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Establish a project goal for recycled content materials, and identify material suppliers that can achieve this goal. During construction, ensure that the specified recycled content materials are installed. Consider a range of environmental, economic and performance attributes when selecting products and materials.
Standard Practice
It has become commonplace for manufacturers to provide recycled content of their building materials. If the information does not exist or cannot be obtained, CDA allows the use of the following recycled content percentages as a default for some of the common construction materials:
Material Post-consumer Pre-consumer
Steel 25% -
Copper 65% -
Aluminum 80% -
Reinforced concrete pipe 2% -
Asphaltic paving materials, conventional
45% 45%
Asphaltic paving materials, with roof shingles
67% 45%
Post-consumer Recycled Content is derived from materials that can no longer be used for their original purpose. Pre-consumer Recycled Content consists of raw material diverted from the waste stream during the manufacturing process.
Note that the values in the table above are typically very conservative. For example, depending on the process used to make the steel, the recycled content can be anywhere from 25% to 35% for steel produced in a basic oxygen furnace to almost 100% in an electric arc furnace.3 For this reason, the designers and contractors are encouraged to determine this information directly from the manufacturers and to not rely on these default values whenever possible.
Recommended Practice
Establish a project goal for recycled content materials and identify material suppliers that can achieve this goal
Consider the following major components for specifying maximum recycled content:
3 Steel Recycling Institute
CT-54
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
o Wall and partition materials o Components of concrete and cement o Steel reinforcement o Structural steel o Miscellaneous steel o Steel fencing and furnishings o Unit masonry o Ductile iron pipe o Aluminum products o Steel doors and frames o Aluminum doors and windows o Plaster o Terrazzo o Acoustical ceilings o Drywall o Finish flooring including carpet, resilient flooring and terrazzo o Toilet and shower compartments o Special finishes
During construction, ensure that the specified recycled content materials are installed and quantify the total percentage of recycled content materials installed
Additionally, the following websites are provided for guidance only: U.S. General Services Administration - Environmental Products Overview http://www.gsa.gov/portal/content/104543
Architectural Record – Green Product Guide www.archrecord.construction.com/products/green/
Best Available Practice
Encourage aggressive use of permeable pavement with high recycled content, where applicable, such as recycled ground tire rubber (GTR) for permeable asphalt
CASE STUDY
Recycled Content Island Wood Campus – Bainbridge Island, Washington
The builders used concrete with a flyash content of 50%. A countertop made of recycled yogurt containers, toilet partitions made of recycled plastic, 100%-recycled-content cellulose insulation, recycled-glass wall tiles, walk-off mats made from recycled tires, and a recycled soybean-shell bio-composite countertop are all part of the portfolio of recycled-content building materials used at Island Wood. In addition, throw rugs in the bunkrooms were woven from upholstery remnants and discarded clothing.
www.casestudies.cascadiagbc.org/overview.cfm?ProjectID=497
CT-55
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 MATERIALS & RESOURCES
4.5. Local/Regional Materials
1 to 3 Points
INTENT
Increase demand for building and all other materials and products that are extracted, harvested or recovered, as well as manufactured within the region, thereby supporting the use of indigenous resources and reducing the environmental impacts resulting from transportation.
REQUIREMENTS
Use building and all other materials or products that have been extracted, harvested or recovered, as well as manufactured, within 500 miles of the project site for a minimum of 10% or 20% (based on cost) of the total materials value. If only a fraction of a product or material is extracted/harvested/recovered and manufactured locally, then only that percentage (by weight) shall contribute to the regional value. An additional point can be achieved if 50% of the materials are extracted/harvested/recovered, as well as manufactured, within 250 miles of the project site. The minimum percentage of local/regional materials for each point threshold is as follows:
SAM Credit Local/Regional Materials Points
4.5.1 10% 1
4.5.2 20% 2
4.5.3 50% within 250 miles 3
If specific material cost is not available, assume 45% of total cost (inclusive of materials, labor and equipment) is representative of the material cost.
Only include materials in CSI MasterFormat 1995 Divisions 2-10 in the calculations.
Mechanical, electrical and plumbing components and specialty items such as elevators and FAA equipment shall not be included in this calculation. Only include materials permanently installed in the project. Furniture may be included if it is included consistently in SAM Credit 4.3 Materials Reuse through SAM Credit 4.8 Furniture and Equipment.
NOTE: Materials reused and salvaged that satisfy the requirements of SAM Credit 4.3 may also contribute to this credit.
CT-56
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
The submittals include the following:
A design estimate using the recycled content form in CDA/OMP Specification 01355 – Regional Materials, to be provided by the designer with the SAM Design Checklist
A pre-construction estimate using the recycled content form in CDA/OMP Specification 01355 – Regional Materials, to be provided by the contractor
A final construction estimate using the recycled content form in CDA/OMP Specification 01355 – Regional Materials, to be provided by the contractor with the SAM Construction Checklist
TECHNOLOGY/STRATEGY
Establish a project goal for locally sourced materials, and identify materials and material suppliers that can achieve this goal. During construction, ensure that the specified local materials are installed and quantify the total percentage of local materials installed. Consider a range of environmental, economic and performance attributes when selecting products and materials.
Standard Practice
The central location of Chicago makes many materials readily available
Recommended Practice
Identify and specify materials that are extracted, processed, or manufactured within 500 miles of Chicago. Materials that may contribute toward this goal include but are not limited to: concrete, aggregate, asphaltic products, structural steel, masonry, gypsum wallboard, utility structures, gas and water piping. Note that piping used indoors for building systems should not be included. Reused and salvaged materials also qualify.
Best Available Practice
None
CT-57
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 MATERIALS & RESOURCES
4.6 Rapidly Renewable Materials
1 Point
INTENT
Reduce the use and depletion of finite raw materials and long-cycle renewable materials by replacing them with rapidly renewable materials.
REQUIREMENTS
Use rapidly renewable building materials and products for 2.5% of the total value of all building materials and products used in the project, based on cost. Rapidly renewable building materials and products are made from plants that are typically harvested within a ten-year or shorter cycle.
Only include materials in CSI MasterFormat 1995 Divisions 2-10 in the calculations. Only permanently installed materials should be counted in this credit. Temporary construction materials are counted in SAM Credit 6.3 Sustainable Temporary Construction Materials.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Establish a project goal for rapidly renewable materials and identify products and suppliers that can support achievement of this goal. Consider materials such as bamboo, cotton insulation, agrifiber, linoleum, wheatboard, strawboard and cork. Although not a plant material, also consider wool.
Standard Practice
None
Recommended Practice
Identify materials and suppliers that can achieve this goal Consider materials such as:
o Poplar OSB o Straw board or “agriboard” o Bamboo flooring o Cork o Wool carpets and fabrics o Cotton-batt insulation o Linoleum flooring
CT-58
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
o Sunflower seed board o Wheat grass or Straw board cabinetry and others. o Rice husks for concrete
Best Available Practice
None
CASE STUDY
Renewable Flooring Shakey’s Pizza Restaurant Flooring – Ontario, Canada Shakey's Pizza on Victoria Gardens Lane houses bamboo flooring, a renewable product that is kinder to the Earth when used over other hardwoods. The restaurant selected the areas near the buffet, bar and restrooms to put in bamboo flooring.
http://rancho.shakeys.com/GreenReport.aspx
CT-59
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 MATERIALS & RESOURCES
4.7 Certified Wood
1 Point
INTENT
Encourage environmentally responsible forest management.
REQUIREMENTS
Use a minimum of 50% (based on cost) of wood-based materials and products, which are certified in accordance with the Forest Stewardship Council’s principles and criteria, for wood building components. These components include, but are not limited to, structural framing and general dimensional framing, flooring, sub-flooring, wood doors and finishes. Only include materials permanently installed in the project. Furniture may be included, providing it is included consistently in activities concerning SAM Credit 4.8 Furniture and Equipment.
Only permanently installed materials should be counted in this credit. Sustainable temporary construction materials are counted in SAM Credit 6.3 Sustainable Temporary Construction Materials. Furniture may be included if it is included consistently in SAM Credit 4.3 Materials Reuse through SAM Credit 4.8 Furniture and Equipment.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Establish a project goal for FSC-certified wood products and identify suppliers that can achieve this goal. During construction, ensure that the FSC-certified wood products are installed and quantify the total percentage of FSC-certified wood products installed.
Standard Practice
None
Recommended Practice
Identify suppliers that can achieve this goal during construction Ensure that the FSC-certified wood products are installed and quantify the total
percentage of FSC-certified wood products installed
Best Available Practice
None
CT-60
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Certified Wood Floors DOSA Restaurant – San Francisco Bay, California
Where possible, all new wood framing including plywood for shear walls is Forest Stewardship Council (FSC) certified. Also, booths, banquettes and custom sofas were constructed with FSC certified wood for their framework. Cabinetry and millwork was fabricated locally using Durapalm plywood and/or FSC certified cherry wood. Low-VOC finishes are used to provide clean and durable surfaces.
http://dosasf.com/fillmore_eco.htm
CT-61
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 MATERIALS & RESOURCES
4.8 Furniture and Equipment
1 Point
INTENT
Reduce the environmental and indoor air quality impacts of the furniture and equipment acquired for use in tenant space.
REQUIREMENTS
A point is awarded to projects that purchase durable goods (i.e. goods that are replaced infrequently or require capital program outlays to purchase) that meet any of the following sustainable requirements:
Electric-Powered Equipment: Examples of electric-powered equipment include, but are not limited to, office equipment (computers, monitors, copiers, faxes, scanners, and printers), appliances (refrigerators, dishwashers, and water coolers), external power adapters, and televisions and other audiovisual equipment. To achieve a point, 40% of the total purchases of electric-powered equipment (by cost) meet one of the following criteria:
o The equipment is ENERGY STAR labeled (for product categories with developed specifications).
o The equipment (either battery or corded) replaces conventional gas-powered equipment. Examples include, but are not limited to, maintenance equipment and vehicles, landscaping equipment and cleaning equipment.
Furniture: To achieve a point, 40% of the total purchases of furniture (by cost) meet one of the following criteria:
o Purchased furniture contains at least 10% post-consumer or 20% pre-consumer material.
o Purchased furniture contains at least 70% material salvaged from off-site sources or outside the airport boundary.
o Purchased furniture contains at least 70% material salvaged from on-site sources, such as an equipment reuse program or internal reorganization.
o Purchased furniture contains at least 50% rapidly renewable material. o Purchased furniture contains at least 50% FSC-certified wood. o Purchased furniture contains at least 50% material harvested and processed or
extracted and processed within 500 miles of the project.
Each furniture purchase can receive credit for each sustainable criterion met (i.e. a $100 purchase that contains both 10% post-consumer recycled content and 50% content harvested within 500 miles of the project counts twice in the calculation, for a total of $200 in sustainable purchasing.
CT-62
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
To avoid double counting, furniture materials and electric equipment loads should not be counted in previous SAM categories, such as SAM Credit 4.5 Local/Regional Materials or Credit 3.3 Optimize Energy Performance.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Designers are encouraged to specify items that help achieve the requirements of this credit whenever possible. A continuously updated list of ENERGY STAR labeled equipment can be found on www.energystar.gov. Sustainable furniture can be found from various sources. GREENGUARD Environmental Institute certifies products, including furniture. See www.greenguard.org for a listing of GREENGUARD certified furniture.
Standard Practice
None
Recommended Practice
Specify ENERGY STAR electric equipment and/or sustainable furniture systems, such as GREENGUARD certified furniture
Best Available Practice
None
CASE STUDY
Green Restaurant Green McDonald’s – Cary, North Carolina
High efficiency and Energy Star rated appliances were installed in the kitchen and the bathrooms were fitted with air blade hand dryers that use 25 percent less energy and take half the time to dry than conventional driers.
www.skanska-sustainability-case-studies.com/pdfs/60/60_McDonalds_v001.pdf
CT-63
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4.0 MATERIALS & RESOURCES
4.9 Equipment Salvage and Reuse
1 Point
INTENT
Promote the reuse of equipment and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
REQUIREMENTS
Use salvaged, refurbished or reused equipment and materials, in any appreciable amount on the project or make available for reuse equipment and materials for other projects.
Mechanical, electrical, and plumbing components, and specialty items such as pumps and equipment (CSI Divisions 11 through 16, note: CSI Divisions 2 through 10 are counted in SAM Credit 4.3 Material Reuse) can be included. Include only materials permanently installed in the project. Furniture may be included if it is included consistently in SAM Credit 4.3 Material Reuse through SAM Credit 4.7 Certified Wood.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
Indicate the name of the project that will utilize the material, if other than current project or temporary storage locations.
TECHNOLOGY/STRATEGY
The purpose of this credit is to recognize the reuse of items not covered by SAM Credit 4.3 Material Reuse.
Identify opportunities to incorporate salvaged materials into the design, and research potential material suppliers. Consider salvaged materials such as cabinetry and furniture, pumps, motors, electrical panels, fixtures and tanks.
Explore and encourage the development of a virtual warehouse for salvaged and reusable items.
Standard Practice
None
CT-64
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
In the process of demolition, reuse or make available mechanical, electrical, and plumbing components
Best Available Practice
None
CT-65
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.1 Prerequisite 1 – Minimum Indoor Air Quality (IAQ) Performance
Required
INTENT
Establish minimum indoor air quality (IAQ) performance to enhance indoor air quality in tenant space, thus contributing to the comfort and well-being of the occupants.
REQUIREMENTS
Meet the minimum requirements of Sections 4 through 7 of ASHRAE 62.1-2010, Ventilation for Acceptable Indoor Air Quality. Mechanical ventilation systems shall be designed using the Ventilation Rate Procedure or the applicable local code, whichever is more stringent. Naturally ventilated spaces shall comply with ASHRAE 62.1-2010, paragraph 5.1.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Ventilation systems should meet or exceed the minimum outdoor air ventilation rates as described in the ASHRAE standard. Balance the impacts of ventilation rates on energy use and indoor air quality to optimize for energy efficiency and occupant health. Use the ASHRAE 62 Users Manual for detailed guidance on meeting the referenced requirements.
Standard Practice
Identify potential IAQ conflicts on the site and locate air intakes away from air contaminant source, which might include loading areas, exhaust fans, and cooling towers
Locate air intakes in secure areas for protection from potential security breaches Chicago Building Code uses ASHRAE 62.1-2004
Recommended Practice
Design HVAC systems to meet ventilation requirements of the referenced standard Evaluate carbon or electrostatic filters Provide a security monitoring system and restrict access to outdoor air intakes
CT-66
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
In cases where conflicts with the City of Chicago ventilation code arise, meet the requirements of the more stringent code
Best Available Practice
None
CASE STUDY
Green Restaurant Green McDonald’s – Cary, North Carolina An indoor air quality management plan was implemented during construction and a pre-occupancy flush out involving MERV (Minimum Efficiency Reporting Value) 13 air filters was carried out to ensure good air quality prior to occupancy. The ventilation system provides 30 percent more ventilation than the ASHRAE 2004 standards prescribe and carbon dioxide sensors were installed at various heights throughout the building to monitor indoor air quality.
www.skanska-sustainability-case-studies.com/pdfs/60/60_McDonalds_v001.pdf
CT-67
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.2 Prerequisite 2 – Environmental Tobacco Smoke (ETS) Control
Required
INTENT
Prevent or minimize exposure of occupants, indoor surfaces, and ventilation air distribution systems to Environmental Tobacco Smoke (ETS).
REQUIREMENTS
OPTION 1 –
Prohibit smoking within the tenant space Smoking must be prohibited within 25 feet of entryways, outdoor air intakes and
operable windows. Provide signage to allow smoking in designated areas, prohibit smoking in designated areas or prohibit smoking on the entire property.
OR
OPTION 2 –
Prohibit smoking in the tenant space except in designated smoking areas Smoking must be prohibited within 25 feet from entries, outdoor air intakes and operable
windows Locate designated smoking rooms to effectively contain, capture and remove ETS from
the tenant space. At a minimum, the smoking room must be directly exhausted to the outdoors with no re-circulation of ETS-containing air to the non-smoking area of the tenant space, and enclosed with impermeable deck-to-deck partitions. With the doors to the smoking room closed, operate exhaust sufficient to create a negative pressure with respect to the adjacent spaces of at least an average of 5 Pa (0.02 inches of water gauge) and with a minimum of 1 Pa (0.004 inches of water gauge).
Performance of the smoking room differential air pressures shall be verified by conducting 15 minutes of measurement, with a minimum of one measurement every 10 seconds, of the differential pressure in the smoking room with respect to each adjacent area and in each adjacent vertical chase with the doors to the smoking room closed. The testing will be conducted with each space configured for worst case conditions of transport of air from the smoking rooms to adjacent spaces with the smoking rooms’ doors closed to the adjacent spaces.
NOTE: It is acceptable to not designate any smoking areas and to provide signage to indicate the prohibition of smoking on the property to satisfy the prerequisite requirements.
CT-68
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Prohibit smoking or effectively control the ventilation air in smoking rooms.
Standard Practice
The State of Illinois prohibits smoking in almost all public spaces and workspaces
The Chicago City Code Section 7-32-010 prohibits smoking within 15-feet of entry ways
Recommended Practice
Require all parts of the construction sites to be non-smoking
Best Available Practice
Where applicable, provide a designated smoking room designed to effectively contain, capture and remove ETS from the tenant space. At a minimum, the smoking room must be directly exhausted to the outdoors with no recirculation of ETS-mixed air to the non-smoking area of the tenant space, enclosed with impermeable deck-to-deck partitions and operated at negative pressure.
Performance of the smoking rooms shall be verified by using tracer gas testing methods as described in the ASHRAE Standard 129-1997. Acceptable exposure in non-smoking areas is defined as less than 1% of the tracer gas concentration in the smoking room detectable in the adjoining non-smoking areas. Smoking room testing as described in ASHRAE Standard 129-1997, Section 8, is required in the contract documents and critical smoking facility systems testing results must be included in the commissioning plan and report or as a separate document.
CT-69
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.3.1 Construction IAQ Management Plan: During Construction
1 Point
INTENT
Reduce indoor air quality problems resulting from the construction/renovation process in order to help sustain the comfort and well-being of construction workers and tenant space occupants.
REQUIREMENTS
Develop and implement an Indoor Air Quality (IAQ) Management Plan for the construction and pre-occupancy phases of the tenant space as follows:
During construction meet or exceed the recommended Control Measures of the Sheet Metal and Air Conditioning National Contractors Association (SMACNA) IAQ Guidelines for Occupied Buildings under Construction, 1995, Chapter 3
Protect stored on-site or installed absorptive materials from moisture damage
If permanently installed air handlers are used during construction, filtration media with a Minimum Efficiency Reporting Value (MERV) of 8 shall be used at each return air grille, as determined by ASHRAE 52.2-1999. Replace all filtration media immediately prior to occupancy.
SUBMITTALS
Include descriptive narrative in the SAM Checklist including IAQ Management Plan and detailed photographic evidence.
TECHNOLOGY/STRATEGY
Adopt an IAQ management plan to protect the HVAC system during construction, control pollutant sources and interrupt contamination pathways. Sequence the installation of materials to avoid contamination of absorptive materials such as insulation, carpeting, ceiling tile and gypsum wallboard. Coordinate SAM Credits 5.3 Construction IAQ Management Plan and 5.5 Indoor Chemical and Pollutant Source Control to determine the appropriate specifications and schedules for filtration media.
If possible, avoid using permanently installed air handlers for temporary heating/cooling during construction. Consult the LEED 2009 Green Building and Construction Reference Guide for more detailed information on how to ensure the well-being of construction workers and occupants if permanently installed air handlers must be used during construction.
Standard Practice
None
CT-70
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
During construction meet or exceed the recommended Design Approaches of the Sheet Metal and Air Conditioning National Contractors Association (SMACNA) IAQ Guideline for Occupied Buildings under Construction, 1995, Chapter 3
Protect stored on-site or installed absorptive materials from moisture damage Do not operate or protect air-handling equipment during construction from dust Sequence the installation of materials to avoid contamination of absorptive materials
such as insulation, carpeting, ceiling tile and gypsum wallboard Minimize the use of air handlers during construction. If air handlers are used during
construction, filtration media with a Minimum Efficiency Reporting Value (MERV) of 8 must be used at each return air grill, as determined by ASHRAE 52.2-1999.
Best Available Practice
None
CASE STUDIES
Construction Mitigation Program Oakland International Airport – Oakland, California
During the airport’s Terminal Improvement Program, a number of mitigation efforts were implemented to reduce the construction impact on contractors, tenants, and travelers. A major component of these efforts involves a comprehensive checklist enforcing compliance with these practices. This checklist includes the evaluation of existing measures, the identification of measures that may require revision, and development of recommendations for corrective action.
www.oaklandairport.com/noise/environmental_construct.shtml
Green Restaurant Green McDonald’s – Cary, North Carolina An indoor air quality management plan was implemented during construction and a pre-occupancy flush out involving MERV (Minimum Efficiency Reporting Value) 13 air filters was carried out to ensure good air quality prior to occupancy. The ventilation system provides 30 percent more ventilation than the ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers) 2004 standards prescribe and carbon dioxide sensors were installed at various heights throughout the building to monitor indoor air quality.
www.skanska-sustainability-case-studies.com/pdfs/60/60_McDonalds_v001.pdf
CT-71
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.3.2 Construction IAQ Management Plan: Before Occupancy
1 Point
INTENT
Reduce indoor air quality problems resulting from the construction/renovation process in order to help sustain the comfort and well-being of construction workers and tenant space occupants.
REQUIREMENTS
OPTION 1 — Flush-Out
After construction ends, prior to occupancy and with all interior finishes installed, perform a flush-out by supplying a total air volume of 14,000 cu.ft. of outdoor air per sq.ft. of floor area while maintaining an internal temperature of at least 60 degrees F and relative humidity no higher than 60%.
OR
If occupancy is desired prior to completion of the flush-out, the space may be occupied following delivery of a minimum of 3,500 cu.ft. of outdoor air per sq.ft. of floor area to the space. Once a space is occupied, it shall be ventilated at a minimum rate of 0.30 cfm/sq.ft. of outside air or the design minimum outside air rate determined section 5.1, whichever is greater. During each day of the flush-out period, ventilation shall begin a minimum of three hours prior to occupancy and continue during occupancy. These conditions shall be maintained until a total of 14,000 cu.ft./sq.ft. of outside air has been delivered to the space.
NOTE: All finishes must be installed prior to flush-out.
OR
OPTION 2 — Air Testing
Conduct baseline IAQ testing, after construction ends and prior to occupancy, using testing protocols consistent with the United States Environmental Protection Agency Compendium of Methods for the Determination of Air Pollutants in Indoor Air and as additionally detailed in the LEED Reference Guide for Green Building Design and Construction, 2009 Edition.
CT-72
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Demonstrate that the contaminant maximum concentrations listed below are not
exceeded.
CONTAMINANT MAXIMUM CONCENTRATION Formaldehyde 50 parts per billion Particulates (PM10) 50 micrograms per cubic meter Total Volatile Organic Compounds (TVOC) 500 micrograms per cubic meter 4-Phenylcyclohexene (4-PCH)* 6.5 micrograms per cubic meter Carbon Monoxide (CO) 9 part per million and no greater than 2
parts per million above outdoor levels
* This test is only required if carpets and fabrics with styrene butadiene rubber (SBR) latex backing material are installed as part of the base building systems.
For each sampling point where the maximum concentration limits are exceeded conduct additional flush-out with outside air and retest the specific parameter(s) exceeded to indicate the requirements are achieved. Repeat procedure until all requirements have been met. When retesting non-complying areas, take samples from the same locations as in the first test.
The air sample testing shall be conducted as follows:
o All measurements shall be conducted prior to occupancy, but during normal occupied hours and with the ventilation system starting at the normal daily start time and operated at the minimum outside air flow rate for the occupied mode throughout the test.
o All interior finishes must be installed, including but not limited to millwork, doors, paint, carpet and acoustic tiles. Movable furnishings such as workstations and partitions should be in place for the testing, although it is not required.
o The number of sampling locations will depend on the size of the tenant space and number of ventilation systems. For each portion of the tenant space served by a separate ventilation system, the number of sampling points shall not be less than one per 25,000 sq.ft., or for each contiguous floor area, whichever is larger, and include areas with the least ventilation and greatest presumed source strength.
o Air samples must be collected between 3 feet and 6 feet from the floor to represent the breathing zone of occupants, and over a minimum 4-hour period.
SUBMITTALS
Include descriptive narrative in the SAM Checklist including IAQ Management Plan and detailed photographic evidence.
CT-73
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Prior to occupancy, perform a flush-out or test the air contaminant levels in the tenant space. The flush-out is often used where occupancy is not required immediately upon substantial completion of construction. IAQ testing can minimize schedule impacts but may be more costly.
The intent of this credit is to eliminate indoor air quality problems that occur as a result of construction. Architectural finishes used in tenant build-outs constitute a significant source of air pollutants, and must be addressed in order to qualify for this credit.
Standard Practice
None
Recommended Practice
Replace all filtration media immediately prior to occupancy. Filtration media shall have a Minimum Efficiency Reporting Value (MERV) of 13, as determined by ASHRAE 52.2-1999 for media installed at the end of construction.
Best Available Practice
After construction ends and prior to occupancy, conduct a two-week flush out with 100% fresh air
CASE STUDY
Green Restaurant Green McDonald’s – Cary, North Carolina An indoor air quality management plan was implemented during construction and a pre-occupancy flush out involving MERV (Minimum Efficiency Reporting Value) 13 air filters was carried out to ensure good air quality prior to occupancy. The ventilation system provides 30 percent more ventilation than the ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers) 2004 standards prescribe and carbon dioxide sensors were installed at various heights throughout the building to monitor indoor air quality.
www.skanska-sustainability-case-studies.com/pdfs/60/60_McDonalds_v001.pdf
CT-74
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.4.1 Low-Emitting Materials: Adhesives and Sealants
1 Point
INTENT
Reduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
REQUIREMENTS
All adhesives and sealants used within the tenant space (i.e., inside of the weatherproofing system and applied on-site) must comply with the following requirements as applicable to the project scope:
Adhesives, Sealants and Sealant Primers: South Coast Air Quality Management District (SCAQMD) Rule #1168. VOC limits are listed in the table below and correspond to an effective date of July 1, 2005 and rule amendment date of January 7, 2005.
Architectural Applications
VOC Limit [g/L less water] Specialty Applications
VOC Limit [g/L less water]
Indoor Carpet Adhesives 50 PVC Welding 510 Carpet Pad Adhesives 50 CPVC Welding 490 Wood Flooring Adhesives 100 ABS Welding 325 Rubber Floor Adhesives 60 Plastic Cement Welding 250 Subfloor Adhesives 50 Adhesive Primer for Plastic 550 Ceramic Tile Adhesives 65 Contact Adhesives 80 VCT & Asphalt Adhesives 50 Special Purpose Contact Adhesive 250 Drywall & Panel Adhesives 50 Structural Wood Member Adhesive 140 Cove Base Adhesives 50 Sheet Applied Rubber Lining Operations 850 Multipurpose Construction Adhesives 70 Top & Trim Adhesive 250 Structural Glazing Adhesives 100
Substrate Specific Applications
VOC Limit [g/L less water] Sealants VOC Limit
VOC Limit [g/L less water]
Metal to Metal 30 Architectural 250 Plastic Foams 50 Nonmembrane Roof 300 Porous Material (except wood) 50 Roadway 250 Wood 30 Single-Ply Roof Membrane 450 Fiberglass 80 Other 420
Sealant Primers
VOC Limit [g/L less water]
Architectural Non Porous 250 Architectural Porous 775 Other 750
CT-75
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
• Aerosol Adhesives: Green Seal Standard for Commercial Adhesives GS-36 requirements in effect on October 19, 2000.
Aerosol Adhesives: VOC weight [g/L minus water] General purpose mist spray 65% VOCs by weight General purpose web spray 55% VOCs by weight Special purpose aerosol adhesives (all types) 70% VOCs by weight
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Specify low-VOC materials in construction documents. Ensure that VOC limits are clearly stated in each section of the specifications where adhesives and sealants are addressed. Common products to evaluate include: general construction adhesives, flooring adhesives, fire-stopping sealants, caulking, duct sealants, plumbing adhesives, and cove base adhesives. Review product cut sheets, MSD sheets, signed attestations or other official literature from the manufacturer clearly identifying the VOC contents or compliance with referenced standards.
Standard Practice
Low VOC materials are becoming more common in the market place
Recommended Practice
Specify Low-VOC adhesives and sealants Consider the use of air scrubbers during the installation and curing of adhesives and
sealers when used inside the passenger terminal or other public spaces
Best Available Practice
Specify that all shop finished material meet the VOC emission requirements. Materials to consider are:
o Primed steel o Finished metals including aluminum o Finished millwork o Finished steel and wood doors and windows
CT-76
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Non-Voc Material DOSA Restaurant – San Francisco Bay, California
No-VOC epoxy flooring/wall coatings are used throughout back-of-house areas for a clean durable finish. Unlike typical epoxy coatings or fiberglass-reinforced panels (FRP), these eco-friendly epoxy formulas will not off-gas or contribute to VOC's in the interior environment.
http://dosasf.com/fillmore_eco.htm
CT-77
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.4.2 Low-Emitting Materials: Paints and Coatings
1 Point
INTENT
Reduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
REQUIREMENTS
Paints and coatings used within the tenant space (i.e., inside of the weatherproofing system and applied on-site) must comply with the following criteria as applicable to the project scope:
Architectural paints, coatings and primers applied to interior walls and ceilings must not exceed the VOC content limits established in Green Seal Standard GS-11, Paints, First Edition, May 20, 1993.
o Flats: 50 g/L o Non-Flats: 150 g/L
Anti-corrosive and anti-rust paints applied to interior ferrous metal substrates must not exceed the VOC content limit of 250 g/L established in Green Seal Standard GC-03, Anti-Corrosive Paints, Second Edition, January 7, 1997.
Clear wood finishes, floor coatings, stains, and shellacs applied to interior elements must not exceed the VOC content limits established in South Coast Air Quality Management District (SCAQMD) Rule 1113, Architectural Coatings, rules in effect on January 1, 2004.
o Clear wood finishes: varnish 350 g/L; lacquer 550 g/L o Floor coatings: 100 g/L o Sealers: waterproofing sealers 250 g/L; sanding sealers 275 g/L; all other sealers
200 g/L o Shellacs: Clear 730 g/L; pigmented 550 g/L o Stains: 250 g/L
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Specify low-VOC paints and coatings in construction documents. Ensure that VOC limits are clearly stated in each section of the specifications where paints and coatings are addressed. Track the VOC content of all interior paints and coatings during construction.
CT-78
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
Specify Low-VOC field applied paints and coating Consider the use of air scrubbers during the installation and curing of paints and
coatings when used inside the terminal
Best Available Practice
Specify that all shop finished material meet the VOC emission requirements. Materials to consider are:
o Primed steel o Finished metals including aluminum o Finished millwork o Finished steel and wood doors and windows
CASE STUDY
Low VOC Paints DOSA Restaurant – San Francisco Bay, California
All paints are specified throughout the interior are low-VOC, low-odor formulas. Its washable finish in any sheen, quick dry-time, and seamless touch-up means a long-lasting paint finish. The finish on cabinetry is also low-VOC.
http://dosasf.com/fillmore_eco.htm
CT-79
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.4.3 Low-Emitting Materials: Flooring Systems
1 Point
INTENT
Reduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
REQUIREMENTS
All flooring must comply with the following as applicable to the project scope:
All carpet installed shall meet the testing and product requirements of the Carpet and Rug Institute’s Green Label Plus program
All carpet cushion installed in shall meet the requirements of the Carpet and Rug Institute Green Label program
All carpet adhesive shall meet the requirements of SAM Credit 5.4.1 Low-Emitting Materials: Adhesives and Sealants VOC limit of 50 g/L
All of the hard surface flooring must be certified as compliant with the FloorScore® standard (current as of the date of this Rating System, or more stringent version) by an independent third party. Flooring products covered by FloorScore® include vinyl, linoleum, laminate flooring, wood flooring, ceramic flooring, rubber flooring, wall base, and associated sundries.
An alternative compliance path using FloorScore® is acceptable for credit achievement according to the following stipulations. 100% of the non-carpet finished flooring must be FloorScore® certified, and it must comprise, at minimum, at least 25% of the finished floor area. Potential examples of unfinished flooring include floors in mechanical rooms, electrical rooms, and elevator service rooms.
Concrete, wood, bamboo, and cork floor finishes such as sealer, stain and finish must meet the requirements of South Coast Air Quality Management District (SCAQMD) Rule 1113, Architectural Coatings, rules in effect on January 1, 2004. VOC limits are listed below.
o Clear wood finishes: varnish 350 g/L; lacquer 550 g/L o Floor coatings: 100 g/L o Sealers: waterproofing sealers 250 g/L; sanding sealers 275 g/L; all other sealers
200 g/L o Shellacs: Clear 730 g/L; pigmented 550 g/L o Stains: 250 g/L
CT-80
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Tile setting adhesives and grout must meet South Coast Air Quality Management District (SCAQMD) Rule #1168. VOC limits are listed below and correspond to an effective date of July 1, 2005 and rule amendment date of January 7, 2005.
o - Ceramic tile adhesive: 65 g/L o - Grout and mortar: 250 g/L
All flooring products will meet the testing and product requirements of the California Department of Health Services Standard Practice for The Testing Of Volatile Organic Emissions From Various Sources Using Small-Scale Environmental Chambers, including 2004 Addenda
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Clearly specify requirements for product testing and/or certification in the construction documents. Select products that are either certified under the Green Label Plus program or for which testing has been done by qualified independent laboratories in accordance with the appropriate requirements.
The Green Label Plus program for carpets and its associated VOC emission criteria in micrograms per square meter per hour, along with information on testing method and sample collection developed by the Carpet & Rug Institute (CRI) in coordination with California’s Sustainable Building Task Force and the California Department of Health Services (DHS), are described in Section 9, Acceptable Emissions Testing for Carpet, DHS Standard Practice CA/DHS/EHLB/R-174, dated 07/15/04. This document is available at:
www.dhs.ca.gov/ps/deodc/ehlb/iaq/VOCS/Section01350_7_15_2004_FINAL_PLUS_ADDENDUM-2004-01.pdf (also published as Section 01350 Section 9 [dated 2004] by the Collaborative for High Performance Schools [www.chps.net]).
FloorScore® is a voluntary, independent certification program that tests and certifies hard surface flooring and associated products for compliance with criteria adopted in California for indoor air emissions of Volatile Organic Compounds (VOCs) with potential health effects. The program uses a small-scale chamber test protocol and incorporates VOC emissions criteria developed by the California Department of Health Services, which are widely known as Section 1350.
Standard Practice
None
Recommended Practice
Specify Low-VOC carpet systems. Ensure that VOC limits are clearly stated where carpet systems are addressed. Be attentive to carpet installation requirements.
CT-81
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
Consider the use of air scrubbers during the installation and curing of carpet or hard surface floor system adhesives and sealers when used inside the terminal
Specify that all shop finished material meet the VOC emission requirements. Materials to consider are:
o Primed steel o Finished metals including aluminum
CASE STUDY
Low-Emitting Flooring DOSA Restaurant – San Francisco Bay, California
Porcelain tile flooring that is produced in a closed-loop process that recycles 100% of raw material and water wastes was specified throughout the dining, bar, and lounge areas. The porcelain contains no added VOC's. With the proper use and maintenance these materials help reduce overall off-gassing in efforts to meet interior air quality standards. No sealants or waxes are required that could add harmful VOC's to a building. (Most quarried stones must be sealed and waxed to maintain appearance).Tile in the employee bathroom is Crossville EcoCycle made from 40% recycled ceramic. Also, Plyboo Neopolitan Strand bamboo flooring, which is used throughout the restaurant, is not only a beautiful, unique look- its durability is suited for high-traffic areas with hardness twice that of red oak; it's the hardest bamboo flooring on the market. The bamboo flooring is 100% bamboo with no fillers and it is urea-formaldehyde-free (PlybooPure), containing no VOC's.
http://dosasf.com/fillmore_eco.htm
CT-82
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.4.4 Low-Emitting Materials: Composite Wood and Agrifiber Products
1 Point
INTENT
Reduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
REQUIREMENTS
Composite wood and agrifiber products used on the interior of the tenant space (defined as inside of the weatherproofing system) shall contain no added urea-formaldehyde resins. Laminating adhesives used to fabricate on-site and shop-applied composite wood and agrifiber assemblies shall contain no added urea-formaldehyde resins.
Composite wood and agrifiber products are defined as: particleboard, medium density fiberboard (MDF), plywood, wheatboard, strawboard, panel substrates and door cores. Materials considered fit-out, furniture, and equipment (FF&E) are not considered base building elements and are not included.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Specify wood and agrifiber products that contain no added urea-formaldehyde resins. Specify laminating adhesives for field and shop applied assemblies that contain no added urea/formaldehyde resins. Review product cut sheets, MSD sheets, signed attestations or other official literature from the manufacturer.
Standard Practice
None
Recommended Practice
Specify wood and agrifiber products with no added urea-formaldehyde resins
CT-83
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
Specify that all shop finished material meet the VOC emission requirements. Materials to consider are:
o Primed steel o Finished metals including aluminum o Finished millwork o Finished steel and wood doors and windows
CT-84
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.5 Indoor Chemical and Pollutant Source Control
1 Point
INTENT
Minimize exposure of occupants to potentially hazardous particulates and chemical pollutants.
REQUIREMENTS
Design to minimize and control pollutant entry into tenant spaces and later cross-contamination of regularly occupied areas:
Sufficiently exhaust each space where hazardous gases or chemicals may be present or used (including housekeeping/laundry areas and copying/printing rooms) to create negative pressure with respect to adjacent spaces with the doors to the room closed. For each of these spaces, provide self-closing doors and deck to deck partitions or a hard lid ceiling. The exhaust rate shall be at least 0.50 cfm/sq.ft., with no air recirculation. The pressure differential with the surrounding spaces shall be at least 5 Pa (0.02 inches of water gauge) on average and 1 Pa (0.004 inches of water) at a minimum when the doors to the rooms are closed.
In mechanically ventilated spaces, provide regularly occupied areas of the tenant space with new air filtration media prior to occupancy that provides a Minimum Efficiency Reporting Value (MERV) of 13 or better. Filtration should be applied to process both return and outside air that is to be delivered as supply air.
Provide containment drains plumbed for appropriate disposal of hazardous liquid wastes in places where water and chemical concentrate mixing occurs for laboratory purposes
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Design facility cleaning and maintenance areas with isolated exhaust systems for contaminants. Maintain physical isolation from the rest of the regularly occupied areas of the tenant space. Install high-level filtration systems in air handling units processing both return air and outside supply air. Ensure that air handling units can accommodate required filter sizes and pressure drops.
Standard Practice
None
CT-85
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Where chemical use occurs (including housekeeping areas and copying/printing rooms), provide segregated areas with deck to deck partitions with separate outside exhaust at a rate of at least 0.50 cubic feet per minute per square foot, no air re-circulation and maintaining a negative pressure
Provide drains plumbed for appropriate disposal of liquid waste in spaces where water and chemical concentrate mixing occurs
Select finish materials and assemblies that resist mold growth Designate central locations in the tenant space for storage of concentrated cleaning
chemicals and other pollutant sources
Best Available Practice
Design separate exhaust and plumbing systems for rooms or areas with contaminants to achieve physical isolation from the rest of the tenant space
CT-86
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.6.1 Controllability of Systems: Lighting
1 Point
INTENT
Provide a high level of lighting system control by individual occupants or by specific groups in multi-occupant spaces (e.g. classrooms and conference areas) to promote the productivity, comfort and well-being of occupants.
REQUIREMENTS
Provide individual lighting controls for 90% (minimum) of the tenant space occupants to enable adjustments to suit individual task needs and preferences.
AND
Provide lighting system controls for all shared multi-occupant spaces to enable lighting adjustment that meets group needs and preferences.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Design the tenant space with occupant controls for lighting. Strategies to consider include lighting controls and task lighting. Integrate lighting systems controllability into the overall lighting design, providing ambient and task lighting while managing the overall energy use of the space.
Standard Practice
None
Recommended Practice
Use motion-activated lighting Design lighting control systems to take advantage of daylight harvesting to reduce
artificial lighting when adequate daylight is available Design areas to provide a variety of levels of light and sound in different areas
simultaneously Provide task lighting or more light switching zones in office areas
CT-87
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
None
CASE STUDY
Occupant Lighting Controls Hertz Corporate – North America and Europe
In 2008, Hertz undertook a number of initiatives to manage and reduce energy usage at its locations in North America and Europe. Initial efforts have focused on Quick Hitters that are energy initiatives that can immediately address interior/exterior lighting, HVAC, and process loads (car wash, vacuum systems). Examples include HVAC Thermostat controls, LED exit signs, lighting occupancy controls, photocells, and time clocks.
https://images.hertz.com/pdfs/green_initiatives_2010.pdf
CT-88
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.6.2 Controllability of Systems: Thermal Comfort
1 Point
INTENT
Provide a high level of thermal comfort system control by individual occupants or by specific groups in multi-occupant spaces (i.e. classrooms or conference areas) to promote the productivity, comfort and well-being of occupants.
REQUIREMENTS
Provide individual comfort controls for 50% (minimum) of the occupants to enable adjustments to suit individual task needs and preferences. Operable windows can be used in lieu of comfort controls for occupants of areas that are 20 feet inside of and 10 feet to either side of the operable part of the window. The areas of operable window must meet the requirements of ASHRAE 62.1-2010 paragraph 5.1 Natural Ventilation.
AND
Provide comfort system controls for all shared multi-occupant spaces to enable adjustments to suit group needs and preferences.
Conditions for thermal comfort are described in ASHRAE Standard 55-2004 to include the primary factors of air temperature, radiant temperature, air speed and humidity.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Design the tenant space and systems with comfort controls to allow adjustments to suit individual needs or those of groups in shared spaces. ASHRAE Standard 55-2004 identifies the factors of thermal comfort and a process for developing comfort criteria for tenant spaces that suit the needs of the occupants involved in their daily activities. Control strategies can be developed to expand on the comfort criteria to allow adjustments to suit individual needs and preferences.
These strategies may involve system designs incorporating operable windows, hybrid systems integrating operable windows and mechanical systems, or mechanical systems alone. Individual adjustments may involve individual thermostat controls, local diffusers at floor, desk or overhead levels, or control of individual radiant panels, or other means integrated into the overall space, thermal comfort systems, and energy systems design. In addition, designers should evaluate the closely tied interactions between thermal comfort (as required by ASHRAE Standard 55-2004) and acceptable indoor air quality (as required by ASHRAE Standard 62.1-2010, whether natural or mechanical ventilation).
CT-89
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
Provide individual thermal controls for occupants
Best Available Practice
Provide underfloor air distribution systems with individual diffusers for office spaces
CT-90
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.7.1 Thermal Comfort: Design
1 Point
INTENT
Provide a comfortable thermal environment that supports the productivity and well-being of occupants.
REQUIREMENTS
Design HVAC systems and the tenant space to meet the requirements of ASHRAE Standard 55-2004, Thermal Comfort Conditions for Human Occupancy. Demonstrate design compliance in accordance with the Section 6.1.1 Documentation.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Establish comfort criteria per ASHRAE Standard 55-2004 that support the desired quality and occupant satisfaction with tenant space performance. Design space and systems with the capability to deliver performance to the comfort criteria under expected environmental and use conditions. Evaluate air temperature, radiant temperature, air speed, and relative humidity in an integrated fashion and coordinate these criteria with SAM Credit 5.1 Minimum Indoor Air Quality Performance.
Standard Practice
None
Recommended Practice
None
Best Available Practice
Provide ceiling fans or natural ventilation to increase air movement Provide humidification in HVAC systems serving office For spaces with humidification, install humidistats in addition to thermostats
CT-91
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.7.2 Thermal Comfort: Employee Verification
1 Point (awarded only if credit is earned toward SAM Credit 5.7.1)
INTENT
Provide for the assessment of tenant space thermal comfort over time.
REQUIREMENTS
Agree to implement a thermal comfort survey of employees within a period of 6 to 18 months after occupancy. This survey should collect anonymous responses about thermal comfort in the tenant space including an assessment of overall satisfaction with thermal performance and identification of thermal comfort-related problems. Agree to develop a plan for corrective action if the survey results indicate that more than 20% of occupants are dissatisfied with thermal comfort in the space. This plan should include measurement of relevant environmental variables in problem areas in accordance with ASHRAE Standard 55-2004.
Thermal Comfort: Employee Verification is contingent on the successful completion and award of the credit -Thermal Comfort: Design.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
ASHRAE Standard 55-2004 provides guidance for establishing thermal comfort criteria and the documentation and validation of performance to the criteria. While the standard is not intended for purposes of continuous monitoring and maintenance of the thermal environment, the principles expressed in the standard provide a basis for design of monitoring and corrective action systems.
Standard Practice
None
Recommended Practice
None
Best Available Practice
None
CT-92
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Benchmarking Building Quality University of California – Berkley, California
At the Center for Built Environment at the University of California, Berkeley, they created a standardized environmental quality assessment survey that measures employees’ satisfaction with their workplace environment quickly and at a low price. A standard set of core questions is used to measure satisfaction with environmental factors such as indoor air quality, thermal comfort, and acoustics. The survey has been used to evaluate the performance of 22 buildings in the United States.
www.stanford.edu/group/narratives/classes/08-09/CEE215/ReferenceLibrary/CBE%20Research%20Thermal%20Comfort/A%20Web-Based%20Occupant%20Satisfaction%20Survey.pdf
CT-93
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
5.0 INDOOR ENVIRONMENTAL QUALITY
5.8 Noise Transmission
1 Point
INTENT
Limit noise levels in noise-sensitive, occupied spaces such as terminals and offices to increase employee productivity and passenger comfort.
REQUIREMENTS
Maintain predicted noise levels in all passenger terminal areas to a Noise Criteria (NC) below 40 and offices and conference rooms below NC30.
OR
Specify exterior glazing with a Sound Transmission Class (STC) of 35 or better per ASTM E413 and ASTM E1332 for all regularly occupied spaces.
SUBMITTALS
Include descriptive narrative in the SAM Checklist and show calculations indicating that NC levels are met in all critical areas or submit product data sheets for exterior glazing meeting the STC requirements.
TECHNOLOGY/STRATEGY
There are a number of design techniques that can influence the acoustical quality of indoor spaces. Generally, these can include improved glazing and partitions or less costly design practices such as tenant space and furniture orientation.
Standard Practice
Design spaces in such a way as to orient noise sensitive areas away from major noise sources
Use sound dampening glazing and wall partitions Locate copy machines and printers in separate rooms
CT-94
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
For office environments, specify acoustical ceiling with an appropriate noise reduction coefficient to meet the requirements of this credit
Choose cubicle partitions that are at least 5 feet tall to provide a sound barrier to workstation occupants
Insulate wall cavities for noise sensitive spaces and extension of partition walls to the structural deck
Best Available Practice
Specify laminated glazing to reduce noise transmission for normally occupied spaces
CT-95
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 CONSTRUCTION PRACTICES
6.1.1 Alternative Transportation During Construction: Staging Area
1 Point
INTENT
Reduce emissions due to construction vehicles by minimizing the amount of traffic to the construction site.
REQUIREMENTS
To meet this credit each project must have a staging area where employees congregate prior to entering the project site
AND
Use multiple occupancy vehicles to access the project site from the centralized staging area.
SUBMITTALS
Although not required for the SAM CT Design Checklist, a staging area, with contractor trailer, should be included in the design drawings.
For the SAM CT Construction Checklist, the contractor must state that the staging area, with contractor trailer, was present and list or describe how employees accessed the project site (e.g., pooled in trucks or shuttle bus).
TECHNOLOGY/STRATEGY
Standard Practice
Most projects typically use heavier duty vehicles such as pick-up trucks or SUVs to provide workers with access to the project site. In some cases, for larger projects, buses are used.
Recommended Practice
Establish procedures and make vehicles available for employee car pooling to the project site. For maximum benefit, shuttle buses or vans are preferred over lower occupancy vehicles such as pick-up trucks.
Best Available Practice
Use fuel-efficient vehicles for car pooling employees to the project site
CT-96
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 CONSTRUCTION PRACTICES
6.1.2 Alternative Transportation During Construction: Low-Emitting & Fuel-Efficient Vehicles, 10%
1 Point
INTENT
Reduce emissions from on-road construction vehicles (examples include foreman pickups or shuttle buses).
REQUIREMENTS
The contractor must use fuel efficient and low-emitting vehicles for at least 10% of all on-road, contractor-owned construction vehicles that access the project site more than five calendar days per month. To meet this requirement, the vehicles must have an Air Pollution Score or a Greenhouse Gas Score of 6 or greater according to the EPA Green Vehicle Guide. A partial list of heavier duty vehicles (pick-ups and SUVs) for the 2012 model year that meet these requirements are shown below for reference:
Vehicle Make/Model (Type) Engine/Transmission/Fuel Air Pollution
Score Greenhouse Gas Score
GMC Canyon (Pick-Up) 5.3L/Auto 4WD/Gasoline 6 4
Chevrolet Silverado 15 (Pick-Up) 5.3L/Auto 2WD/ Ethanol-Gasoline 6 (Ethanol) 3 (Ethanol)
Chevrolet Colorado (Pick-Up) 2.9L/Auto 2WD/Gasoline 6 4
Ford F150 (Pick-Up) 3.7L/Auto 2WD/Gasoline 6 3
Toyota Highlander Hybrid (SUV) 3.3L/CVT 4WD/Gasoline 7 7
Chevrolet Equinox (SUV) 2.4L/Auto 2WD/Ethanol-Gasoline 6 (Ethanol) 6 (Ethanol)
Ford Escape Hybrid (SUV) 2.5L/CVT/2WD/Gasoline 7 7
GMC Terrain (SUV) 2.4L/Auto 2WD/Gasoline 6 6
Note: CVT – Continuously Variable Transmission SUBMITTALS
For the sustainable construction checklist, the contractor must submit a list of its on-road vehicles and identify those which meet the EPA Green Vehicle ratings described above.
TECHNOLOGY/STRATEGY
The ratings are based on the Green Vehicle Guide that is prepared annually by the EPA (www.epa.gov/greenvehicles/Index.do). The Air Pollution Score is based on the government emission standards for which the vehicle was certified to comply with and reflects vehicle tailpipe emissions that contribute to local and regional air pollution, creating problems such as haze, and health issues. This score reflects fuel lifecycle emissions of carbon dioxide (CO2) and other greenhouse gases. The scores are on a scale of 1 to 10 with 10 being the highest rating.
CT-97
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
Utilize hybrid and flex fuel vehicles
Recommended Practice
Promote the use of vehicles that meet the requirements above for EPA Air Pollution and Greenhouse Gas Scoring system
Best Available Practice
Operate compressed natural gas (CNG), electric, fuel cell, biodiesel vehicles
CT-98
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 CONSTRUCTION PRACTICES
6.1.3 Alternative Transportation During Construction: Low-Emitting & Fuel-Efficient Vehicles, 50%
1 Point
INTENT
Reduce emissions from on-road construction vehicles.
REQUIREMENTS
The contractor must use fuel efficient and low-emitting vehicles for at least 50% of all on-road, contractor-owned construction vehicles that access the project site more than five calendar days per month. To meet this requirement, the vehicles must have an Air Pollution Score or a Greenhouse Gas Score of 6 or greater according to the EPA Green Vehicle Guide. A partial list of heavier duty vehicles (pick-ups and SUVs) for the 2012 model year that meet these requirements are shown below for reference:
Vehicle Make/Model (Type) Engine/Transmission/Fuel Air Pollution
Score Greenhouse Gas Score
GMC Canyon (Pick-Up) 5.3L/Auto 4WD/Gasoline 6 4
Chevrolet Silverado 15 (Pick-Up) 5.3L/Auto 2WD/ Ethanol-Gasoline 6 (Ethanol) 3 (Ethanol)
Chevrolet Colorado (Pick-Up) 2.9L/Auto 2WD/Gasoline 6 4
Ford F150 (Pick-Up) 3.7L/Auto 2WD/Gasoline 6 3
Toyota Highlander Hybrid (SUV) 3.3L/CVT 4WD/Gasoline 7 7
Chevrolet Equinox (SUV) 2.4L/Auto 2WD/Ethanol-Gasoline 6 (Ethanol) 6 (Ethanol)
Ford Escape Hybrid (SUV) 2.5L/CVT/2WD/Gasoline 7 7
GMC Terrain (SUV) 2.4L/Auto 2WD/Gasoline 6 6
Note: CVT – Continuously Variable Transmission SUBMITTALS
For the sustainable construction checklist, the contractor must submit a list of its on-road vehicles and identify those which meet the EPA Green Vehicle ratings described above.
TECHNOLOGY/STRATEGY
The ratings are based on the Green Vehicle Guide that is prepared annually by the EPA (www.epa.gov/greenvehicles/Index.do ). The Air Pollution Score is based on the government emission standards for which the vehicle was certified to comply with and reflects vehicle tailpipe emissions that contribute to local and regional air pollution, creating problems such as haze, and health issues. This score reflects fuel lifecycle emissions of carbon dioxide (CO2) and other greenhouse gases. The scores are on a scale of 1 to 10 with 10 being the highest rating.
CT-99
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
Utilize hybrid and flex fuel vehicles
Recommended Practice
Promote the use of vehicles that meet the requirements above for EPA Air Pollution and Greenhouse Gas Scoring system
Best Available Practice
Operate compressed natural gas (CNG), electric, fuel cell, and/or biodiesel vehicles
CT-100
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 CONSTRUCTION PRACTICES
6.2 Construction Noise and Acoustical Quality
1 Point
INTENT
Improve the exterior noise quality during construction affecting residential areas or other noise sensitive areas.
REQUIREMENTS
Although the City of Chicago has an environmental noise ordinance (Article XXI – Environmental Noise and Vibration Control), it does not apply to construction or demolition work on public improvements authorized by a government body or agency (City Ordinance 11-4-2835).
The requirements of this credit will only apply to noise disturbances that are in the terminal area. Noise disturbances are defined as any sound which is audible at a distance of 600 feet from its source or any sound which generates a sound pressure level in the public way exceeding 70 dB(A) when measured 10 feet from the source (City Ordinance 11-4-2710).
To achieve a point under this credit, the following requirements must be met during construction for those sites that are near noise sensitive areas as defined by the Chicago City Ordinance:
Meet the noise restrictions listed in the Chicago City Ordinance (XXI, Part B) which include, but are not limited to, noise from mechanical stationary sources (11-4-2810), loading and unloading operations (11-4-2830), and construction equipment (11-4-2835) during nighttime hours.
OR
Implement a noise abatement or noise mitigation plan that identifies site specific, mechanical, structural or operational measures to reduce noise disturbances in noise sensitive areas adjacent to the project site.
SUBMITTALS
Although not required for the sustainable design checklist, indicate noise sensitive areas on plans to aid contractor in determining the best noise mitigation strategies.
For the sustainable construction checklist, the contractor must indicate that the requirements of the Chicago Environmental Noise Ordinance have been met or submit a noise mitigation plan identifying the measures taken to reduce noise disturbances in the affected areas.
TECHNOLOGY/STRATEGY
The primary paragraph related to construction activities is Chicago City Ordinance 11-4-2835 which states that no fuel or electric powered mechanical equipment may be used during the hours of 8:00pm and 8:00am and within 600 feet of a residential area or hospital. The ordinance
CT-101
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
further states that public improvements authorized by a government agency, like the OMP, are not subject to this ordinance, however, a point will be given under this credit for those projects that choose to comply with the above mentioned ordinance.
There are numerous noise mitigation methods that can be employed some of which are site or equipment specific. The easiest method of noise mitigation is to locate the noise source in an area that is not noise sensitive and to conduct that work during daytime hours, 8:00am to 8:00pm. Where this is not possible, temporary barriers can be erected to mitigate the noise emanating from a source.
For reference, see Commonwealth of Massachusetts, Section 721.560 – Construction Noise Control.
Standard Practice
None
Recommended Practice
None
Best Available Practice
None
CT-102
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6.0 CONSTRUCTION PRACTICES
6.3 Sustainable Temporary Construction Materials
1 Point
INTENT
Reduce the use and depletion of finite raw materials and long-cycle renewable materials by replacing them with high recycled content, rapidly renewable materials and FSC certified wood products for temporary uses during construction.
REQUIREMENTS
Temporary construction materials include, but are not limited to, any materials that are used for construction that are not incorporated into the final development such as formwork, temporary carpentry, and signage. For the purposes of this calculation, only the material cost, excluding labor and equipment, shall be used. In order to meet the requirements of this credit, one of the following requirements must be met:
Using a recycled content calculation similar to SAM Credit 4.4 Recycled Content, determine the percentage of recycled content in the temporary construction materials based on overall temporary construction material cost. To achieve a point in this credit, the overall recycled content of the temporary construction materials must be 30% or greater by cost.
OR
Using a rapidly renewable content calculation similar to SAM Credit 4.6 Rapidly Renewable Materials determine the percentage of the rapidly renewable materials based on overall temporary construction material cost. To achieve a point in this credit, the overall recycled content of the temporary construction materials must be 10% or greater by cost.
OR
Using a certified wood calculation similar to SAM Credit 4.7 Certified Wood, determine the percentage of certified wood materials based on the total wood-based material cost. To achieve a point in this credit, the overall recycled content of the temporary construction materials must be 60% or greater by cost.
Do not count temporary construction materials under any of the credits in Section 4.0 – Materials & Resources.
SUBMITTALS
Although not required for the CT Design Checklist, include specification sections that indicate how these requirements are met.
For the CT Construction Checklist, the contractor must provide a calculation of the actual materials used indicating that at least one of the above requirements was met.
CT-103
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Use calculation templates similar to the SAM Credits in Section 4.0 – Materials & Resources as appropriate.
TECHNOLOGY/STRATEGY
Many temporary construction materials can help achieve the requirements of this credit. Although not tracked by LEED, CDA has added this credit in order to promote the use of such materials during construction, as well as for final development stages of a project.
Standard Practice
Although many temporary construction materials meet the requirements of this credit, their use is typically not tracked or promoted. The designer is encouraged to specify sustainable materials in construction wherever possible. The contractor is further encouraged to use these types of materials in the cases where they may not be explicitly specified.
Recommended Practice
Materials that may have high recycled content include, but are not limited to:
Temporary steel structures or materials Metal barricades Temporary piping (HDPE, ductile iron) Steel formwork
Materials that have rapidly renewable materials include, but are not limited to:
Poplar oriented strand board (OSB) for formwork or temporary carpentry Plant-based cladding and insulation materials
FSC certified wood products for temporary construction materials may include:
Wood formwork Temporary wood structures or scaffolding
Best Available Practice
None
CT-104
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 INNOVATION FOR CONCESSIONS & TENANTS – DESIGN & CONSTRUCTION
7.1 – 7.3 Innovation for Design & Construction
1 to 3 Points
INTENT
Provide design teams and projects the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
REQUIREMENTS
In writing, identify the intent of the proposed innovation credit, the proposed requirement for compliance, the proposed submittals to demonstrate compliance, and the approach (strategies) that might be used to meet the requirements.
Up to three points are available for this credit:
SAM Credit Points
7.1 1
7.2 1
7.3 1
SUBMITTALS
Include descriptive narrative in the SAM Checklist following the criteria in the Requirements section above.
TECHNOLOGY/STRATEGY
Substantially exceed a SAM performance credit such as energy performance or water efficiency and/or apply strategies or measures that demonstrate a comprehensive approach and quantifiable environment and/or health benefits.
Refer to LEED Credit Interpretation Results (CIRs) or the Innovation in the LEED Design Credit Catalog4 for potential strategies that may be considered for innovation. Most will pertain to building related innovations; however the SRP will review proposed innovations by the designer or contractor on a case by case basis.
4 Available at www.usgbc.org.
CT-105
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 INNOVATION FOR CONCESSIONS & TENANTS – DESIGN/CONSTRUCTION
7.4 Menu Items (Green Walls, LED lights, Recycled Content Finishes, Rapidly Renewable Finishes, Instantaneous Hot Water Heating, Non-Terminal Tenant Options)
1 to 3 Points
INTENT
Promote specific technologies and additional strategies considered to be important to the sustainability of the airport environment.
REQUIREMENTS
A point will be awarded for each of the technologies or strategies listed below that are used on a project up to a maximum of 3 points:
Green Walls – Use green, vegetated wall systems LED Lighting – Use LED lighting within the tenant spaces Recycled Content Finishes – Use recycled content materials such as recycled glass for
floors, countertops, tabletops, walls, shelves, cabinets, tiles or any areas within the tenant space
Rapidly Renewable Finishes – Use rapidly renewable materials such as bamboo, strawboard, wheatboard, cork, etc. within the tenant space
Instantaneous Hot Water Heating – Use demand, tankless, instantaneous water heating technology
For Non-Terminal Tenants: o Construction Equipment Retrofit – Retrofit all construction equipment over 50 hp
and on site for more than 14 calendar days per month to EPA Tier 3 emission standards
o Photovoltaics – Use photovoltaic systems to generate electricity. System must generate 0.5 kW or greater
o Geothermal Heating/Cooling – Any geothermal system to provide heating and cooling is acceptable
o Wind Power – Generate on-site electricity using wind turbines, horizontal or vertical. System must generate 0.5 kW or greater
o Rainwater Harvesting – Use cisterns, rain barrels, or other vessels to store rain water for other uses including, but not limited to, irrigation, vehicle washing, and other general, non-potable uses. The harvested rainwater must have an intended use. Minimum storage capacity is 200 gallons.
CT-106
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
o Permeable Pavement – Use permeable pavement such as concrete, asphalt, or pavers, for at least 5% of the total pavement area of the project not subject to aircraft traffic or 1,000 sq. ft, whichever is greater
o Trombe or Solar Walls – Use passive solar preheating of intake air for space heating using wall systems or other building surfaces
o Green Walls – Use green, vegetated wall systems on exterior of building envelope for at least 25% of the vertical wall surfaces or the entirety of south and/or west facing walls, whichever is greater
o Warm-Mix Asphalt – Use warm-mix asphalt for at least 5% of the total pavement area of the project or 1,000 sq. ft, whichever is greater
o Alternative Hot Water Heating – Use solar thermal for 25% or demand (tankless) hot water heating systems for 100% of the project’s hot water demand. Excludes process water demand.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist. Indicate in the narrative which of the above technologies and strategies are being included in the project and, where applicable, indicate where these items are shown in the drawings or specifications.
TECHNOLOGY/STRATEGY
Choose any of the following:
Green Walls – Vegetated green wall systems can result in significant air conditioning savings. Green walls fall in to two categories:
o Green facades: Made up of climbing plants growing directly on a wall o Living walls: Modular panels often made of steel containers, geotextiles, irrigation
systems, growing medium and vegetation LED Lighting – LED lights use up to 90% less energy than incandescent light sources,
have a longer lifetime, greater durability and reliability Recycled Content Finishes – Recycled content finishes use readily recycled materials
like glass, marble, stone, etc. that can be obtained locally and don’t require excessive processing like virgin materials
Rapidly Renewable Finishes – Rapidly renewable finishes are natural, non-petroleum-based building materials (petroleum based materials are non-renewable) that have harvest cycles under 10 years. Such materials include bamboo, straw, cork, natural linoleum products (such as Marmoleum), wool, wheatboard, strawboard, etc.
Instantaneous Hot Water Heating – Instantaneous hot water heating technology uses include demand, instantaneous, or tankless water heaters. Demand water heaters heat water directly without the use of a storage tank thus avoiding the standby heat losses associated with conventional storage tank water heaters. When a hot water tap is turned on, cold water travels through a pipe into the unit. Either a gas burner or an electric
CT-107
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
element heats the water as it passes through coiled piping within the unit. As a result, demand water heaters deliver a constant supply of hot water not limited by the volume of a storage tank.
For Non-Terminal Tenants: o Construction equipment retrofit – The use of particulate traps and catalysts to
meet more stringent EPA emissions standards for older construction equipment o Photovoltaics – Photovoltaic or solar-electric systems may be ground-mounted,
roof-mounted, or built into the roof or walls of a building, known as building integrated photovoltaic (BIPV)
o Geothermal heating/cooling systems – Any geothermal system to provide heating and cooling is an acceptable strategy
o Wind power – Generate on-site electricity using wind turbines, horizontal or vertical
o Rainwater harvesting – Collecting rainwater from the many roofs at an airport would provide a large source of clean non-potable water. Although the supply would far exceed the demand, the use of harvested rainwater should be taken on a site-specific case by case basis. Although airport irrigation is limited to ornamental planters, other uses such as vehicle washing may be amenable to this technology.
o Permeable pavement – The amount of pavement at an airport makes permeable pavement an attractive application for the management of stormwater. Although major pavement areas such as runways, taxiways, and apron areas cannot include permeable pavement, there is a significant amount of non-aviation related pavement areas. Using permeable pavement, unit pavers or permeable asphalt or concrete, may also further contribute to the sustainability of a project because these materials can contain high recycled content materials that are locally available, and may reduce heat island effects for non-roof areas, in addition to their stormwater management aspects. All three of these types of pavements have been demonstrated and are being used by the City of Chicago in its Green Alley Program under the direction of Chicago Department of Transportation (CDOT).
o Trombe or Solar walls – These systems use solar energy to heat a thermal mass, usually a concrete wall or an air gap between an interior wall and a dark-colored exterior surface, as means to preheat intake air. On very cold days, the heating system can condition preheated air rather than putting the additional energy in heating cold outside air, thereby realizing an energy savings. In some cases, the wall may also have a photovoltaic component that generates electricity.
o Green Walls – Vegetated green wall systems on exterior of building envelope can reduce wall surface temperatures by as much as 18°F (depending on which direction it is facing), which also results in significant air conditioning savings, while reducing the heat island effect
CT-108
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
o Warm-Mix Asphalt - Warm-mix asphalt allows the producers of hot-mix asphalt pavement material to lower the temperatures at which the material is mixed and placed on the road. Reductions of 50°F to 100°F have been documented. Such drastic reductions have the obvious benefits of cutting fuel consumption and decreasing the production of greenhouse gases. In addition, engineering benefits include better compaction on the road, the ability to haul paving mix for longer distances, and extending the paving season by being able to pave at lower temperatures.
o Water heating – Solar thermal hot water heating technology uses a solar collector which is simply a heat exchanger designed to convert the sun’s radiant light energy into thermal energy to be stored for later use. This collector uses optics and parabolic concentration technology to heat the fluid media passing through the selectively coated tubing manifold. The fluid media is circulated, via a pump, through the collector and into a storage tank located within the home/building. Other water heating technologies that are encouraged include demand, instantaneous, or tankless water heaters. Demand water heaters heat water directly without the use of a storage tank thus avoiding the standby heat losses associated with conventional storage tank water heaters. When a hot water tap is turned on, cold water travels through a pipe into the unit. Either a gas burner or an electric element heats the water as it passes through coiled piping within the unit. As a result, demand water heaters deliver a constant supply of hot water not limited by the volume of a storage tank.
CT-109
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Living Green Wall El Japonez – Mexico City, Mexico
Located in Mexico City, Restaurant Japonez offers hungry souls searching for Asian-inspired dishes a serene landscape seated between a stunning living wall, wood, and an incredible glass enclosure. More than decorative in nature, the wall helps keep the thermostat steady throughout the year while infusing the interior spaces with fresh air.
www.inhabitat.com/2009/03/11/green-wall-by-serrano-cherrem-architects/
CT-110
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 INNOVATION FOR CONCESSIONS & TENANTS – DESIGN/CONSTRUCTION
7.5 LEED Accredited Professional
1 Point
INTENT
Support and encourage the design integration required by LEED to streamline the application and certification process.
AND
To facilitate the incorporation of sustainable design and construction elements.
REQUIREMENTS
At least one principal participant of the project team shall be LEED accredited (i.e., LEED Green Associate; LEED Accredited Professional).
SUBMITTALS
Identify the LEED accredited individual(s) in the SAM Checklist and submit proof of their LEED certification.
TECHNOLOGY/STRATEGY
Educate the project team members about green building design and construction, the LEED requirements and application process early in the life of the project. Consider assigning integrated design and construction process facilitation to the LEED accredited individual.
Standard Practice
None
Recommended Practice
The CDA requires that each design consultant and/or design management team include a LEED accredited individual on its staff to oversee the design and assist with construction administration
Best Available Practice
None
CT-111
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
7.0 INNOVATION FOR CONCESSIONS & TENANTS – DESIGN/CONSTRUCTION
7.6 LEED Certified Project
1 to 4 Points
INTENT
Promote the incorporation of environmentally sustainable design in building and infrastructure improvements by registering and certifying a project through the LEED certification process and rating system.
REQUIREMENTS
Achieve certification via the LEED Retail Commercial Interior (or other applicable LEED category) process – Certified, Silver, Gold, or Platinum. Up to four points are available for this credit:
SAM Credit Certification
Level Points
7.6.1 Certified 1
7.6.2 Silver 2
7.6.3 Gold 3
7.6.4 Platinum 4
SUBMITTALS
Include descriptive narrative in the SAM Checklist demonstrating that the project has been registered under LEED during the design process. Provide the LEED submittal documentation and final determination. Indicate what level of LEED certification has been achieved after construction.
TECHNOLOGY/STRATEGY
Educate the project team members about green building design & construction and application of the LEED Rating System early in the life of the project. Consider pursuing LEED for any occupied building project.
Standard Practice
Projects are encouraged to seek LEED certification, where applicable
Recommended Practice
Encourage LEED Silver or better rating for Retail Commercial Interior buildings
CT-112
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Chicago Department of Aviation
SUSTAINABLE AIRPORT MANUAL
CONCESSIONS & TENANTS
OPERATIONS & MAINTENANCE
SECTION
NOTE:
Please refer to page CT-5 for introduction and applicability of this section.
CT-113
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8.0 COMPANY POLICY
8.1 Prerequisite 1 – Tenant Environmental Liaison
Required
INTENT
Facilitate the dissemination of environmental information within the workplace and create a link with CDA staff for environmental issues.
REQUIREMENTS
Designate an employee to serve as the tenant’s environmental liaison. Liaison will be expected to attend any CDA Green Tenant Meetings and serve as the primary point of contact during the conduct of SAM reviews.
SUBMITTALS
Include the name and contact information of the tenant liaison in the SAM Checklist as well as a descriptive narrative of any environmental/sustainability training the liaison has received.
TECHNOLOGY/STRATEGY
Standard Practice
Designate one person in the organization to serve as the environmental liaison. Said liaison will be tasked with reviewing the Sustainable Airport Manual and identifying any credits applicable to the tenant.
Recommended Practice
The environmental liaison will educate co-workers about the environmental policies of the tenant and integrate them into the tenant’s Environmental Employee Training Program (See SAM Credit 8.23 Establish and Implement Environmental Employee Sustainability Training Program).
Best Available Practice
Promote and maintain relationships with external organizations, collaborate with other tenants to preserve and enhance the environmental quality of the Airport
CT-114
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8.0 COMPANY POLICY
8.2 Establish and Implement Employee Sustainability Training Program
2 Points – Required for CT-OM Mentor Certification
INTENT
In keeping with the spirit and intent of this Manual, it is strongly encouraged that companies working in support of CDA on any project establish and adopt their own employee training program.
REQUIREMENTS
Establish and implement an Employee Sustainability Training Program.
SUBMITTALS
Provide an electronic copy of the company’s Employee Sustainability Training Program and provide descriptive narrative on SAM Checklist documenting training sessions and their respective attendance numbers.
TECHNOLOGY/STRATEGY
As part of the Employee Sustainability Training Program a variety of topics should be covered to provide the employees with an overall understanding of the environmental, social and fiscal responsibility that the company has committed to and how they can contribute to the organization meeting their sustainability goals. Through the development of a training program it will allow the company to provide consistent training to all employees and address facility specific issues.
Standard Practice
None
Recommended Practice
Individual programs can be tailored to meet each company’s specific sustainability goals and can include topics such as:
o Corporate Sustainability Policy o Water Management Plan o Waste Reduction o Storage and Collection of Recyclables o Composting or Re-use Options o Managing and Disposing of Waste o CDA’s Green Commitment
CT-115
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
None
CASE STUDIES
Employee Training Ben & Jerry’s Ice Cream
During the first two days of training, new employees are told about the company's environmental involvement including recycling. A bulletin board in the stores displays letters from headquarters and any new initiatives.
www.mwcog.org/environment/recycling/hotel/mentor/BEN.HTM
Environmental Stewardship Training Program Dallas – Ft. Worth International Airport – Dallas, Texas
The Training program solicits the participation of Dallas – Ft, Worth’s (DFW) 1,650 employees in an airport-wide commitment to environmental stewardship.
http://www.nctcog.org/envir/seeclean/EMS/March-DFWAirport-workgroup.pdf
CT-116
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8.0 COMPANY POLICY
8.3.1 Alternative Transportation: Public Transportation Access
3 to 6 Points
INTENT
Reduce pollution and land development impacts from automobile use.
REQUIREMENTS
Demonstrate that a percentage of total employees are using public transportation. Points will be awarded as follows:
SAM Credit Percentage of Employees Points
8.3.1.1 25% 3
8.3.1.2 50% 4
8.3.1.3 75% 5
8.3.1.4 100% 6
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Perform a transportation survey of employees to identify current usage and encourage knowledge and utilization of mass transit. There are numerous public transportation options in the vicinity of the airport system:
Chicago Transit Authority (CTA) Blue Line, Orange Line Chicago Transit Authority (CTA) Local Bus Routes Metra Pace Bus Service CDA Employee Shuttle bus or ATS in conjunction with any of the above
Standard Practice
None
Recommended Practice
Supply public transit route information and schedules to employees Provide Pre-Tax Deductions from paychecks to cover public transportation needs
CT-117
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
Offer incentives to employees to use public transportation, examples may include: o Transit pass subsidies o Emergency Ride Home Program so that employees are not penalized for not
having a vehicle if they or a member of their family needs to leave for an emergency
o Gift cards or monetary incentives (non-transit related)
CT-118
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8.0 COMPANY POLICY
8.3.2 Alternative Transportation: Bicycle Access, Storage and Changing Rooms
2 Points
INTENT
Reduce pollution and land development impacts from automobile use.
REQUIREMENTS
Provide secure bicycle racks and/or storage
AND
Provide shower and changing facilities in the building, within 200 yards of a building entrance.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Include amenities such as bicycle racks and showering/changing facilities such that employees are encouraged to use bicycles, therefore reducing parking needs. The showering/changing facilities may be shared with other tenants or nearby buildings.
Bicycle access may require coordination with airport security.
Standard Practice
None
Recommended Practice
Supply local bike path information to employees Clearly display the location(s) of secure bicycle parking, lockers and showers
Best Available Practice
Provide incentives to employees to bike to work, examples may include: o Discounts on bicycle accessories and maintenance at local bike shops o Emergency Ride Home Program so that employees are not penalized for not
having a vehicle if they or a member of their family needs to leave for an emergency
o Gift cards or monetary incentives Offer a bike safety course to promote biking to work
CT-119
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8.0 COMPANY POLICY
8.3.3 Alternative Transportation: Low-Emitting and Fuel-Efficient Vehicles
1 to 4 Points
INTENT
Reduce pollution and land development impacts from employees’ personal vehicle use. Fleet vehicle use is addressed in SAM Credit 14.6 of this chapter. For the installation of alternative fuel infrastructure see SAM Credit 14.7.
REQUIREMENTS
Demonstrate that a percentage of total employees are utilizing low-emitting and fuel-efficient vehicles for commuting to work. Points will be awarded as follows:
SAM Credit % of Employees Points
8.3.3.1 5% 1
8.3.3.2 25% 2
8.4.3.3 50% 3
8.4.3.4 100% 4
To meet this requirement, the vehicles must have an Air Pollution Score or a Greenhouse Gas Score of 6 or greater according to the EPA Green Vehicle Guide.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Perform a transportation survey of employees to identify current usage. \
The Green Vehicle Guide is prepared annually by the EPA (www.epa.gov/greenvehicles). The Air Pollution Score is based on the government emission standards for which the vehicle was certified to comply with and reflects vehicle tailpipe emissions that contribute to local and regional air pollution, creating problems such as haze, and health issues. This score reflects fuel lifecycle emissions of carbon dioxide (CO2) and other greenhouse gases. The scores are on a scale of 1 to 10 with 10 being the highest rating.
Standard Practice
None
CT-120
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Provide preferred parking for alternative fuel vehicles
Best Available Practice
Offer incentives to employees to use low-emitting and fuel-efficient vehicles, examples may include:
o Fuel gift cards o Other monetary incentives
Install electrical receptacles for charging of electric vehicles
CT-121
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8.0 COMPANY POLICY
8.3.4 Alternative Transportation: Carpooling
1 to 4 Points
INTENT
Reduce pollution and land development impacts from single occupancy vehicle use for employees.
REQUIREMENTS
Demonstrate that a percentage of total employees are carpooling. Points will be awarded as follows:
SAM Credit % of Employees Points
8.4.4.1 5% 1
8.4.4.2 25% 2
8.4.4.3 50% 3
8.4.4.4 100% 4
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Minimize employee parking lot/garage size. Consider sharing parking facilities with adjacent buildings. Consider alternatives that will limit the use of single occupancy vehicles.
Standard Practice
Provide preferred parking for carpools or vanpools, marked as such
Recommended Practice
Offer incentives to employees who participate in carpools or vanpools: o Employee preference on work shift scheduling with their carpoolers/vanpoolers o Emergency Ride Home Program so that employees are not penalized for not
having a vehicle if they, a member of their family, or a member of their carpool/vanpool needs to leave for an emergency
o Fuel gift cards o Other monetary incentives
CT-122
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
None
CT-123
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8.0 COMPANY POLICY
8.4 Community Education
1 Point
INTENT
Promote awareness of tenant environmental and sustainability initiatives.
REQUIREMENTS
Educate consumers/clients/public about the environmental stewardship to which the tenant has committed, and the results of these efforts.
SUBMITTALS
Include descriptive narrative in the SAM Checklist of methods of community education.
TECHNOLOGY/STRATEGY
Provide and promote education through the following means that include, but are not limited to:
Flyers Pamphlets Press Releases Signage Kiosks Workshops Conferences Website Public exhibits
Standard Practice
None
Recommended Practice
Post environmental education information around tenant space detailing the efforts of the concessionaire or tenant
Promote customer participation to initiatives that contribute to the tenant’s environmental goals
Solicit suggestions from customers on how to improve company’s environmental and social programs
CT-124
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
Offer incentives to consumers/clients/public if they contribute to the tenant’s environmental goals
CASE STUDY
Make a Difference Starbucks
For the good of the planet, Starbucks is encouraging everyone to switch from paper cups to reusable travel mugs. Since 1985 the company has been offering a discount to customers who bring in a reusable travel mug. This endeavor is aimed to aid in their long-term goal of 100% reusable or recyclable cups by 2015.
http://voices.yahoo.com/going-green-starbucks-help-difference-7042726.html?cat=7
CT-125
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
9.0 RESPONSIBLE PROCUREMENT
9.1 Sustainable Furniture
1 Point
INTENT
Reduce the environmental and indoor air quality impacts of the furniture acquired for use in the tenant space.
REQUIREMENTS
A point is awarded for the purchase of durable goods (i.e. goods that are replaced infrequently or require capital program outlays to purchase) that meet any of the following sustainable requirements:
Furniture: To achieve a point, 40% of the total purchases of furniture (by cost) meet one of the following criteria:
o Purchased furniture contains at least 10% post-consumer or 20% pre-consumer material
o Purchased furniture contains at least 70% material salvaged from off-site sources or outside the airport boundary
o Purchased furniture contains at least 70% material salvaged from on-site sources, such as an equipment reuse program or internal reorganization
o Purchased furniture contains at least 50% rapidly renewable material o Purchased furniture contains at least 50% FSC-certified wood o Purchased furniture contains at least 50% material harvested and processed or
extracted and processed within 500 miles of the project
Each furniture purchase can receive credit for each sustainable criterion met (i.e. a $100 purchase that contains both 10% post-consumer recycled content and 50% content harvested within 500 miles of the project counts twice in the calculation, for a total of $200 in sustainable purchasing.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Designers are encouraged to specify items that help achieve the requirements of this credit whenever possible. Sustainable furniture can be found from various sources. GREENGUARD Environmental Institute certifies products, including furniture. See www.greenguard.org for a listing of GREENGUARD certified furniture.
CT-126
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
Specify sustainable furniture systems, such as GREENGUARD certified furniture
Best Available Practice
None
CASE STUDY
GustOrganics- New York Taranta- Boston, Massachusetts
GustOrganics and Taranta, in partnership with the Green Restaurant Association (GRA), have completed a number of sustainable and cost effective initiatives. Among a handle full of other green initiatives, GustOrganics Restaurant has also installed an energy efficient refrigerator, oven and freezer and initiated a recycling and composting program. Taranta Restaurant saved $1,300 a year by switching over to a hand dryer, and continues to see annual savings for upgrading to more energy efficient light bulbs.
http://www.dinegreen.com/restaurants/cases.asp
CT-127
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
9.0 RESPONSIBLE PROCUREMENT
9.2 Eliminate Use of Polystyrene Foam
1 point – Required for CT-OM Mentor Certification
INTENT
Reduce the environmental impact of polystyrene production and disposal.
REQUIREMENTS
Eliminate polystyrene foam in tenant operations.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Eliminating use of polystyrene foam accomplishes multiple goals because it is a petroleum based product that uses HCFCs during production, and it does not readily degrade after disposal.
Standard Practice
None
Recommended Practice
To the greatest extent possible, eliminate the use of polystyrene foam products as part of a responsible procurement practice
Best Available Practice
None
CASE STUDY
Food Service Waste Reduction Ordinance San Francisco International Airport – San Francisco, California
The Food Service Waste Reduction ordinance, effective June 1, 2007, prohibits any establishment that serves food prepared in San Francisco from using polystyrene foam (Styrofoam) to-go containers. The Ordinance further requires that any containers used be either recyclable or compostable in the City's programs.
http://www.sfgov2.org/index.aspx?page=886
CT-128
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
9.0 RESPONSIBLE PROCUREMENT
9.3.1 Consumer Disposable Products: Eliminate the use of Disposables
1 to 3 points
INTENT
Reduce the need for virgin materials and reduce the volume of solid waste generated by tenant activities.
REQUIREMENTS
Offer non disposable options for up to 3 points, which may be awarded by achieving use of any of the following options. 1 point is earned for one option; 2 points for two options; and three points for 3+ options:
Reusable napkins
Reusable hand towels
Reusable utensils
Reusable dishes
Reusable glasses/mugs
Other reusable items
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Eliminate the use of disposable products in favor of reusable options.
Standard Practice
None
CT-129
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Replace disposable products with reusable: o Napkins o Hand towels o Utensils o Dishes o Glasses/Mugs
Best Available Practice
None
CASE STUDY
Sustainable Tableware San Francisco International Airport (SFO) – San Francisco, California
SFO food and beverage tenants are encouraged to provide sustainable food/beverage packaging, including using compostable bio-resin or paper bottles for water. Concessions vendors are “required to use biodegradable tableware and source separate all food service wastes for direct transport to off-Airport composting facilities.”
http://www.flysfo.com/web/page/about/T2/sustainability/
CT-130
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
9.0 RESPONSIBLE PROCUREMENT
9.3.2 Consumer Disposable Products: Bio-Based Content
2 to 4 points – Required for CT-OM Mentor Certification
INTENT
Reduce the need for virgin materials and reduce the volume of solid waste generated by tenant activities.
REQUIREMENTS
Whenever applicable, purchase and utilize bio-based organic/plant based products and containers for customers and in employee break rooms and kitchens to facilitate composting.
Point values will be assigned based on the percentage of total disposable products purchased by overall cost. Up to 4 points are available by calculating items with the following attributes:
SAM Credit Percentage Points
9.3.2.1 25% 2
9.3.2.2 50% 4
Example: A concessionaire calculates that of their $100,000 total consumer disposable product purchases, $27,500 are bio-based.
$27,500 = 27.5% bio-based content $100,000
Therefore, 2 points are earned for this credit.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the types of products used and calculations.
TECHNOLOGY/STRATEGY
Establish a buying procedure that eliminates the need for virgin paper products and plastic containers. During everyday operations, ensure that the specified organic items are being offered to the public and employees.
Potential items to include in the calculation, but not limited to, are:
Take-out containers Take-out bags Cold cups
CT-131
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Hot cups Plates Bowls Soup/chili cups Cutlery and straws Plastic bags Cup sleeves Cup carriers Bottles and jars Coasters Toothpicks
Standard Practice
None
Recommended Practice
None
Best Available Practice
When possible the tenant should use items made from plant based products. A variety of vendors now offer products that are not made of plastic or paper but rather:
Sugarcane Corn Wheat Plant based fiber Potatoes
CT-132
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDIES
Eat Toasty, Be Green™ Quizno’s Subs
In 2010 Quiznos switched to new packaging which is made from renewable or recycled content that will reduce the chain’s environmental footprint. The new packaging includes:
100 % compostable wax-coated paper cups Pulp salad bowls made from renewable sugarcane Plastic lids made of 30% post-consumer recycled PET bottles Napkins made from 100% recycled material and fibers (90 percent post-consumer) Catering lunch boxes made of 100% recycled paperboard (35% post-consumer)
In addition, Quiznos employees also switched to uniforms made 100% from recycled soda pop bottles.
www.quiznos.com/subsandwiches/about/begreen.html
Earth Fresh Initiative Baja Fresh Mexican Grill
In 2010 the food chain established their “Earth Fresh” initiative which focused on using sustainable food packaging and plates. The plates are made of a byproduct of wheat harvests and are certified by the Biodegradable Products Institute. Through the production of the natural unbleached burrito wrappers versus their traditional paper, they experienced a saving of a 46% reduction in water waste and a 21% reduction in wood pulp use. Another added benefit was the 16% reduction in solid waste and the cutting of their greenhouse gas emissions by 10%.
www.packagingdigest.com/article/449839-Baja_Fresh_introduces_new_greener_packaging_at_some_locations.php
CT-133
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
9.0 RESPONSIBLE PROCUREMENT
9.3.3 Consumer Disposable Products: Post-Consumer Recycled Plastic
1 to 3 points
INTENT
Reduce the need for virgin materials and reduce the volume of solid waste generated by tenant activities.
REQUIREMENTS
Whenever applicable, purchase and utilize recycled products and containers for customers and in employee break rooms and kitchens.
Point values will be assigned based on the percentage of total disposable plastic products purchased by overall cost. Up to 3 points are available by calculating items with the following attributes:
SAM Credit Percentage Points
9.3.3.1 30% 1
9.3.3.2 60% 2
9.3.3.3 100% 3
Example: A concessionaire uses $20,000 worth of disposable plastic cutlery, $10,000 worth of straws, $29,000 worth of plates, $11,000 worth of plastic bags and $30,000 worth of take-out containers, representing all plastic food service disposables which total $100,000. Of these items, only the plastic bags ($11,000) contain no post-consumer recycled plastic.
$89,000 = 89% Post-Consumer Recycled Plastic Content
$100,000
Therefore, 2 points are earned for this credit.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the types of products used and calculations.
TECHNOLOGY/STRATEGY
Establish a buying procedure that eliminates the need for virgin plastic products and containers. During everyday operations, ensure that the specified recycled are being offered to the public and employees.
CT-134
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Tenants should use recycled items with high post-consumer content. Post-consumer means that the item’s recycled content comes from products that have been previously used and sent for recycling.
Potential items to include in the calculation, but not limited to, are:
Take-out containers Cold cups Plates Bowls Cutlery and straws Plastic bags Bottles
Standard Practice
None
Recommended Practice
Use post-consumer recycled plastic products wherever possible
Best Available Practice
None
CT-135
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
9.0 RESPONSIBLE PROCUREMENT
9.3.4 Consumer Disposable Products: Post-Consumer Recycled Paper
1 to 3 points – Required for CT-OM Mentor Certification
INTENT
Reduce the need for virgin materials and reduce the volume of solid waste generated by tenant activities.
REQUIREMENTS
Whenever applicable, purchase and utilize recycled products and containers for customers and in employee break rooms and kitchens.
Point values will be assigned based on the percentage of total disposable paper products purchased by overall cost. Up to 3 points are available by calculating items with the following attributes:
SAM Credit Percentage Points
9.3.4.1 30% 1
9.3.4.2 60% 2
9.3.4.3 100% 3
Example: A concessionaire uses $30,000 worth of hot cups, $10,000 worth of cold cups, $10,000 worth of paper bags, $15,000 worth of cup sleeves, $10,000 worth of cup carriers, $15,000 worth of paper napkins, $5,000 worth of paper towels, $4,000 worth of receipt tape, and $1,000 worth of office paper, representing all paper items which total $100,000. Of these items, all contain post-consumer recycled paper with the exception of the receipt tape.
$96,000 = 96% of paper products contain Recycled Paper Content $100,000
Therefore, 2 points are earned for this credit.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the types of products used and calculations.
TECHNOLOGY/STRATEGY
Establish a buying procedure that eliminates the need for virgin paper products and containers. During everyday operations, ensure that the specified recycled are being offered to the public and employees.
CT-136
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Tenants should use recycled items with high post-consumer content. Post-consumer means that the item’s recycled content comes from products that have been previously used and sent for recycling.
Potential items to include in the calculation, but not limited to, are:
Take-out containers Food wrapper Cold cups Hot cups Plates Bowls Paper bags Cup sleeves Cup carriers Paper napkins Paper towels Bath tissue Facial tissue Seat covers Placemats Office paper Receipt tape Customer checks
Standard Practice
None
Recommended Practice
Use post-consumer recycled paper products wherever possible
Best Available Practice
None
CT-137
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDIES
Eat Toasty, Be Green™ Quiznos Subs
In 2010 Quiznos switched to new packaging which is made from renewable or recycled content that will reduce the chain’s environmental footprint. The new packaging includes:
100% compostable wax-coated paper cups Pulp salad bowls made from renewable sugarcane Plastic lids made of 30% post-consumer recycled PET bottles Napkins made from 100% recycled material and fibers (90% post consumer) Catering lunch boxes made of 100% recycled paperboard (35% post consumer)
In addition, Quiznos employees also switched to uniforms made 100% from recycled soda pop bottles.
www.quiznos.com/subsandwiches/about/begreen.html
Recycled Paper Akasha Restaurant – California
Akasha Restaurant uses recycled paper content for its menu and other collateral paper products. Menus covers are made of recycled chip board.
http://askmissa.com/2011/02/24/akasha-restaurant-in-culver-city-eco-friendly-locally-sourced-organic-cuisine/
Recycled Paper Starbucks
Starbucks uses paper bags, napkins, shopping bags, cardboard boxes, paper towels, receipt tape and tissue paper that all contain varying amounts of pre- and post- consumer recycled content.
http://www.starbucks.com/responsibility/environment/recycling
CT-138
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
9.0 RESPONSIBLE PROCUREMENT
9.4 Local/Regional Food Sources
2 to 4 Points – Required for CT-OM Mentor Certification
INTENT
Reduce the environmental and transportation impacts associated with food production and distribution.
REQUIREMENTS
Tenants agree to source local/regional products for both direct sale and in food preparation. Points are awarded based on the percentage of the tenant’s total food purchases by cost that are obtained within 250 miles using the following table:
SAM Credit Percentage Within 250 miles
Points
9.4.1 25% 2
9.4.2 50% 4
Exemplary Performance – 4 additional points available
Additional credit will be given if a tenant sources local products. Exemplary Performance points are awarded based on the percentage of the tenant’s total food purchases by cost that are within 100 miles using the following table:
SAM Credit Percentage Within
100 miles Additional
Points
9.4.3 25% 2
9.4.4 50% 4
Example: Of a tenant’s total food purchases, which is $10,000, $7,000 is sourced within 250 miles and $3,000 is sourced from over 250 miles away. Of that $7,000, $4,000 is sourced from within 100 miles. Therefore, 70% of purchases are within a 250 mile area so 4 points can be claimed under SAM Credit 9.4. Of the total purchases, 40% is sourced within 100 miles and an additional 2 points can be claimed for Exemplary Performance.
Purchases within 250 miles
= $7,000 = 70% of purchases sourced within 250 miles
Total Purchases $10,000
CT-139
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Purchases within 100 miles
= $4,000 = 40% of purchases sourced within 100 miles
Total Purchases $10,000
NOTE: 100 mile purchases are included in the 250 mile purchases.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the percentage of local/regional food sources utilized.
TECHNOLOGY/STRATEGY
Food grown in local and surrounding areas tends to offer a selection of items that are fresher than produce flown or trucked in from other states and countries. Fresh products retain their nutrients better than frozen or canned options and support local businesses in the process.
Concessionaires can establish a relationship with area farms that sell direct to consumers and incorporate local and seasonal goods into their menu and operations. Produce can be used in the general food offerings and specialty dishes relative to seasonal items can be sold.
Standard Practice
None
Recommended Practice
Purchases are produced or harvested within a 250 mile radius of the site Purchase products from local farm cooperatives or community supported agriculture
(CSA) organizations.
Best Available Practice
Purchases are produced or harvested within a 100 mile radius of the site
CASE STUDY
Slow Food Movement San Francisco International Airport – San Francisco, California
In San Francisco’s newly renovated Terminal 2, the Airport will require food and beverage tenants to agree to a 16-point sustainable food policy inspired by the Slow Food movement. Vendors must follow guidelines on portion sizes, sourcing of hormone-free meat and cage-free eggs, and source organic, regional produce wherever possible.
www.moodiereport.com/document.php?c_id=1178&doc_id=21759
CT-140
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
9.0 RESPONSIBLE PROCUREMENT
9.5 Sustainable Foods and Consumer Products
2 to 4 Points – Required for CT-OM Mentor Certification
INTENT
Reduce the environmental impacts associated with food production and distribution.
REQUIREMENTS
Tenants agree to source organic products and sustainable harvested food for both direct sale and in food preparation. This credit pertains only to health and beauty products (i.e. cosmetics and soaps) and whole, non-processed foods (i.e. produce, meats, and cheeses). Sustainable foods and products are defined as meeting any one or more of the following criteria:
Antibiotic free, no added hormones, or non-genetically modified organisms (GMO) animals and animal products
Free-range, cage-free, or grass fed animals or animal products USDA National Organic Program Certified Food Alliance Certified Rainforest Alliance Certified Protected Harvest Certified Fair Trade Marine Stewardship Council’s Blue Eco-Label Blue Ocean Institute Seafood Guide Monterey Bay Aquarium “Green” listed International Organic Standard (IOS) 2008 - Natural & Organic Cosmetic Standard
Points are awarded based on the percentage of the tenant’s total food, health, and cosmetic purchases by cost that meet, in any combination, the definition of sustainable foods and products above using the table below:
SAM Credit Percentage Points
9.5.1 20% 2
9.5.2 40% 4
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the percentage of organic consumer products and organic and sustainably harvested food sources utilized.
CT-141
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Standard Practice
None
Recommended Practice
Offer certified organic or sustainably harvested products
Best Available Practice
None
CASE STUDIES
Angelina’s Metro Market - Organic and Natural Food La Guardia International Airport – New York, New York
Angelina’s Metro Market serves organic, natural food like pasta and salads with over 30 toppings to choose from as well as pastries, bagels, muffins, sandwiches, fruits, veggies, cheese, yogurts, and more. Angelina’s also offers an array of over 120 organic beverages.
www.organicauthority.com/restaurant-buzz/local-and-organic-food-takes-flight-at-la-guardia-airport.html
Organic To Go™ San Diego International Airport – San Diego, California
Organic To Go™ is the nation’s first fast-casual café chain to be certified as an organic retailer by the USDA. Open since 2009 the in the Food Court, the franchise offers ‘clean’ menu options and vegetarian alternatives. Organic To Go™ offers fresh, healthy and delicious food that is free of harmful additives, antibiotics, chemicals, pesticides, growth hormones or genetic modification. Ingredients are certified organic and locally sourced whenever possible.
www.businesswire.com/news/home/20090318005329/en/Organic-Debuts-San-Diego-International-Airport
CT-142
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
10.0 GREEN INTERIORS
10.1 Prerequisite 1 – Minimum Indoor Air Quality (IAQ) Performance
Required
INTENT
Establish minimum indoor air quality (IAQ) performance to enhance indoor air quality within tenant space, thus contributing to the comfort and well-being of the occupants.
REQUIREMENTS
Meet the minimum requirements of Sections 4 through 7 of ASHRAE 62.1-2010, Ventilation for Acceptable Indoor Air Quality. Mechanical ventilation systems shall be designed using the Ventilation Rate Procedure or the applicable local code, whichever is more stringent. Naturally ventilated spaces shall comply with ASHRAE 62.1-2010, paragraph 5.1.
If the project team cannot meet the outside air requirements of ASHRAE 62.1-2010 (with errata but without addenda), document the space and system constraints that make it not possible.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Ventilation systems should meet or exceed the minimum outdoor air ventilation rates as described in the ASHRAE standard. Balance the impacts of ventilation rates on energy use and indoor air quality to optimize for energy efficiency and occupant health. Use the ASHRAE 62 Users Manual for detailed guidance on meeting the referenced requirements.
Standard Practice
Identify potential IAQ conflicts on the site and locate air intakes away from air contaminant source, which might include loading areas, exhaust fans, and cooling towers
Locate air intakes in secure areas for protection from potential security breaches Chicago Building Code uses ASHRAE 62.1-2004
Recommended Practice
Design HVAC systems to meet ventilation requirements of the referenced standard Evaluate carbon or electrostatic filters for use in tenant space Provide a security monitoring system and restrict access to outdoor air intakes for
tenant space
CT-143
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
In cases where conflicts with the City of Chicago ventilation code arise, meet the requirements of the more stringent code.
Best Available Practice
None
CASE STUDY
Green Restaurant Green McDonald’s – Cary, North Carolina An indoor air quality management plan was implemented during construction and a pre-occupancy flush out involving MERV (Minimum Efficiency Reporting Value) 13 air filters was carried out to ensure good air quality prior to occupancy. The ventilation system provides 30 percent more ventilation than the ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers) 2004 standards prescribe and carbon dioxide sensors were installed at various heights throughout the building to monitor indoor air quality.
www.skanska-sustainability-case-studies.com/pdfs/60/60_McDonalds_v001.pdf
CT-144
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
10.0 GREEN INTERIORS
10.2 Prerequisite 2 – Environmental Tobacco Smoke (ETS) Control
Required
INTENT
Prevent or minimize exposure of occupants, indoor surfaces, and ventilation air distribution systems to Environmental Tobacco Smoke (ETS).
REQUIREMENTS
OPTION 1 –
Prohibit smoking in the tenant space Smoking must be prohibited within 25 feet of entryways, outdoor air intakes and
operable windows. Provide signage to allow smoking in designated areas, prohibit smoking in designated areas or prohibit smoking on the entire property.
OR
OPTION 2 –
Prohibit smoking in the tenant space except in designated smoking areas Smoking must be prohibited from within 25 feet from entries, outdoor air intakes and
operable windows. Locate designated smoking rooms to effectively contain, capture and remove ETS from
the tenant space. At a minimum, the smoking room must be directly exhausted to the outdoors with no re-circulation of ETS-containing air to the non-smoking area of the space, and enclosed with impermeable deck-to-deck partitions. With the doors to the smoking room closed, operate exhaust sufficient to create a negative pressure with respect to the adjacent spaces of at least an average of 5 Pa (0.02 inches of water gauge) and with a minimum of 1 Pa (0.004 inches of water gauge).
Performance of the smoking room differential air pressures shall be verified by conducting 15 minutes of measurement, with a minimum of one measurement every 10 seconds, of the differential pressure in the smoking room with respect to each adjacent area and in each adjacent vertical chase with the doors to the smoking room closed. The testing will be conducted with each space configured for worst case conditions of transport of air from the smoking rooms to adjacent spaces with the smoking rooms’ doors closed to the adjacent spaces.
NOTE: It is acceptable to not designate any smoking areas and to provide signage to indicate the prohibition of smoking on the property to satisfy the prerequisite requirements.
SUBMITTALS
CT-145
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Prohibit smoking in tenant space, or effectively control the ventilation air in smoking rooms.
Standard Practice
Chicago Building Code prohibits smoking within 15 feet of entryways which is less stringent than this credit. The distance must be increased to 25 feet to meet this prerequisite.
Recommended Practice
Require all parts of the construction sites to be non-smoking.
Best Available Practice
Where applicable, provide a designated smoking room designed to effectively contain, capture and remove ETS from the tenant space. At a minimum, the smoking room must be directly exhausted to the outdoors with no recirculation of ETS-mixed air to the non-smoking area of the tenant space, enclosed with impermeable deck-to-deck partitions and operated at negative pressure.
Performance of the smoking rooms shall be verified by using tracer gas testing methods as described in the ASHRAE Standard 129-1997. Acceptable exposure in non-smoking areas is defined as less than 1% of the tracer gas concentration in the smoking room detectable in the adjoining non-smoking areas. Smoking room testing as described in ASHRAE Standard 129-1997, Section 8, is required in the contract documents and critical smoking facility systems testing results must be included as a separate document.
CT-146
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
10.0 GREEN INTERIORS
10.3 LEED Certified Design & Construction
1 to 4 Points
INTENT
Promote the incorporation of environmentally sustainable design in building and infrastructure improvements by registering and certifying a project through the LEED certification process and rating system.
REQUIREMENTS
Have achieved or be located within a space that has achieved certification via any LEED process – Certified, Silver, Gold, or Platinum. Up to 4 points are available for this credit:
SAM Credit Certification Level Points
10.3.1 Certified 1
10.3.2 Silver 2
10.3.3 Gold 3
10.3.4 Platinum 4
SUBMITTALS
Include descriptive narrative in the SAM Checklist demonstrating that the project has been registered under LEED during the design process. Provide the LEED submittal documentation and final determination. Indicate what level of LEED certification has been achieved after construction.
TECHNOLOGY/STRATEGY
Tenants should retain the LEED documentation from previous certifications. Many of the credit requirements offer operational and sustainability benefits that can be integrated into everyday tenant operations.
Standard Practice
None
Recommended Practice
Encourage practices that maintain the standards set during the LEED certification process
Best Available Practice
CT-147
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
None 10.0 GREEN INTERIORS
10.4.1 Green Cleaning: High Performance Cleaning
2 points
INTENT
Reduce the exposure of occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, and the environment.
REQUIREMENTS
Have in place during the performance period a high performance cleaning program that addresses the following:
Purchase of cleaning equipment meeting the sustainability criteria outlined in SAM Credit 10.4.2 Green Cleaning: Equipment
Establishment of standard operating procedures (SOPs) addressing how an effective cleaning and hard floor and carpet maintenance system will be consistently utilized, managed, and audited
Development of strategies for promoting and improving hand hygiene, including both hand washing and the use of alcohol-based waterless hand sanitizers
Development of guidelines addressing the safe handling and storage of cleaning chemicals used within the tenant space, including a plan for managing hazardous spills or mishandling incidents
Development of requirements for staffing and training of maintenance personnel appropriate to the needs of the tenant. Specifically address the training of maintenance personnel in the hazards of use, disposal, and recycling of cleaning chemicals, dispensing equipment, and packaging.
Provision for collecting occupant feedback and continuous improvement to evaluate new technologies, procedures, and processes
At a minimum, the policy must cover the green cleaning materials that are within the tenant’s control.
SUBMITTALS
Include descriptive narrative in the SAM Checklist outlining details of a written high performance cleaning program.
CT-148
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Over the performance period, have in place a high performance cleaning program addressing SOPs, sustainable products and equipment, chemical handling and storage, and staff training. Some additional items to consider include:
Employ cleaning techniques that promote the most efficient use of products such as training on the proper amount of product to use and proper wiping motion for certain tasks.
Utilize cleaning techniques that promote the most efficient use of electricity such as working through areas and then turning off the lights in those areas and moving to another section instead of having all the lights on throughout the space for the entire shift.
Provide proper training on supply usage such as when to replace paper products and liners as not to throw away usable product. For example, office trash liners that may need emptying but not replacing when possible.
Standard Practice
None
Recommended Practice
See Appendix AP-A – Green Product Listing for a listing of products Utilize a High Performance Green Cleaning Program
Best Available Practice
None
CASE STUDIES
Green Cleaning XOCO Restaurant – Chicago, Illinois
XOCO uses green housekeeping and sanitizing items. For example, the hand soap is Green Seal certified, as is the window cleaner, counter cleaner, floor cleaner and warewash cleansers.
www.rickbayless.com/restaurants/sustainability.html
Greening of O’Hare and Midway Chicago Department of Aviation – Chicago, Illinois
The Chicago Department of Aviation has implemented a number of sustainable initiatives at O’Hare and Midway airports including the use of Green Seal certified cleaning products and eliminating the use or aerosol sprays to clean and disinfect airport facilities.
www.explorechicago.org/city/en/about_the_city/green_chicago/green_airport.html
CT-149
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
10.0 GREEN INTERIORS
10.4.2 Green Cleaning: Equipment
1 point
INTENT
Reduce the exposure of occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, and the environment.
REQUIREMENTS
Implement a program for the use of janitorial equipment that reduces contaminants and minimizes environmental impact. The cleaning equipment program must require the following:
Vacuum cleaners are certified by the Carpet and Rug Institute “Green Label” Testing Program for vacuum cleaners and operate with a sound level of less than 70dBA
Carpet extraction equipment used for restorative deep cleaning is certified by the Carpet and Rug Institute’s “Seal of Approval” Testing Program for deep-cleaning extractors
Powered floor maintenance equipment, including electric and battery-powered floor buffers and burnishers, is equipped with vacuums, guards and/or other devices for capturing fine particulates and operates with a sound level of less than 70dBA
Propane-powered floor equipment has high-efficiency, low-emissions engines with catalytic converters and mufflers that meet the California Air Resources Board (CARB) or Environmental Protection Agency (EPA) standards for the specific engine size and operate with a sound level of less than 90dBA
Automated scrubbing machines are equipped with variable-speed feed pumps and on-board chemical metering to optimize the use of cleaning fluids. Alternatively, the scrubbing machines use only tap water with no added cleaning products
Powered equipment is ergonomically designed to minimize vibration, noise and user fatigue
Equipment is designed with safeguards, such as rollers or rubber bumpers, to reduce potential damage to building surfaces
Keep a log for all powered cleaning equipment to document the date of equipment purchase and all repair and maintenance activities and include vendor specification sheets for each type of equipment in use
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
CT-150
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Develop, implement and maintain a policy for the use of low-impact powered cleaning equipment. Evaluate the powered cleaning equipment currently being used and make a plan for upgrading to powered cleaning equipment that reduces contaminants within the tenant space and minimizes environmental impact.
Standard Practice
None
Recommended Practice
Utilize cleaning equipment that are designed to have a reduced environmental impact while maintaining performance of cleaning
Best Available Practice
Carpet and Rug Institute approved vacuum and carpet cleaning equipment Electric and battery-powered floor buffers and burnishers that operate at less than
70dBA Low-emissions fossil fuel powered floor cleaning equipment that meets the California Air
Resources Board (CARB) or Environmental Protection Agency (EPA) standards for the specific engine size and operate with a sound level of less than 90dBA’
Automated scrubbing machines are equipped with variable-speed feed pumps and on-board chemical metering to optimize the use of cleaning fluids
Battery-powered equipment is equipped with environmentally preferable gel batteries Ergonomically designed equipment Equipment is designed with safeguards Keep a log for all powered cleaning equipment to document the date of equipment
purchase and all repair and maintenance activities and include vendor specification sheets for each type of equipment in use
CT-151
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
10.0 GREEN INTERIORS
10.4.3 Green Cleaning: Entryway Systems (Non-Terminal Tenants)
1 point
INTENT
Reduce the exposure of occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, and the environment.
REQUIREMENTS
Utilize permanent entryway systems (grilles, grates, mats) at least 10 feet long in the primary direction of travel to reduce the amount of dirt, dust, pollen and other particles entering the tenant space. Public entryways that are not in use or serve only as emergency exits are excluded from the requirement, as are private offices.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Use grills, grates or mats to catch and hold dirt particles and prevent contamination of the tenant’s interior space. Design exterior stone, brick or concrete surfaces to drain away from regularly used entrances.
At entrances, install low-maintenance vegetation consistent with the requirements of SAM Credit 14.3.1 Landscape Management: CDA Specifications and avoid plants, including trees and shrubs that produce fruit, flowers or leaves that are likely to be tracked into the building. Select plants based on an integrated pest management (IPM) approach to eliminate pesticide applications that could be tracked into the building.
Provide a water spigot and electrical outlet at each public building entrance for maintenance and cleaning.
Standard Practice
None
CT-152
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Use grilles, grates, or mats at entryways Install low-maintenance vegetation Eliminate pesticide applications Provide a water spigot and electrical outlet at each entrance
Best Available Practice
None
CT-153
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
10.0 GREEN INTERIORS
10.4.4 Green Cleaning: Integrated Pest Management
1 point
INTENT
Preserve environmental integrity while discouraging the presence of pests/wildlife, in an effort to include methods that maintain and encourage high-performance pest management control.
REQUIREMENTS
Use Integrated Pest Management (IPM) Techniques, such as:
Control dirt, moisture, clutter, foodstuffs, harborage, and building penetrations Use baits and traps rather than pesticide sprays where possible Avoid pesticide applications for prevention of pests Use pesticides only where pests are located Use pesticide specifically formulated for targeted pest
AND/OR
Use wildlife deterrent methods in accordance with United States Department of Agriculture - Wildlife Services.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Over the performance period, have in place a wildlife and pest management plan that addresses overall site management, chemicals, and waste. Include such green landscape management practices such as: applying integrated pest management and deterring wildlife habitat.
Integrated pest management (IPM), defined as managing pests (plants, fungi, insects, and/or animals) in a way that protects human health and the surrounding environment that improves economic returns through the most effective, least-risk option.
The IPM plan includes preferred use of nonchemical methods, definition of emergency conditions, and universal notification providing advance notice of not less than 72 hours under normal conditions, and, 24 hours in emergencies before a pesticide, (other than a least-toxic pesticide) is applied in a building or on surrounding grounds that the building management maintains.
Vegetated roofs must be designed and maintained to not attract wildlife or provide habitat.
CT-154
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
Apply pesticides only during unoccupied hours Ventilate area with significant quantities of outside air during and after applications Completely flush space prior to occupancy Use more than normal outside air ventilation for some period after occupancy Notify occupants prior to occupation If applying outside keep away from air intake
Best Available Practice
None
CT-155
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
10.0 GREEN INTERIORS
10.5 Measurement and Verification
3 Points
INTENT
Provide for the ongoing accountability of energy consumption over time.
REQUIREMENTS
Develop and implement a Measurement and Verification (M&V) Plan consistent with Option D: Calibrated Simulation (Savings Estimation Method 2), or Option B: Energy Conservation Measure Isolation, as specified in the International Performance Measurement & Verification Protocol (IPMVP) Volume III: Concepts and Options for Determining Energy Savings in New Construction, April, 2003.
The M&V period shall cover a period of no less than one year of post-construction occupancy
SUBMITTALS
Include descriptive narrative in the SAM Checklist and M&V Plan.
TECHNOLOGY/STRATEGY
Develop an M&V Plan to evaluate space and/or energy system performance. Characterize the tenant space and/or energy systems through energy simulation or engineering analysis. Install the necessary metering equipment to measure energy use. Track performance by comparing predicted performance to actual performance, broken down by component or system as appropriate. Evaluate energy efficiency by comparing actual performance to baseline performance.
While the IPMVP describes specific actions for verifying savings associated with energy conservation measures (ECMs) and strategies, this Credit expands upon typical IPMVP M&V objectives. M&V activities should not necessarily be confined to energy systems where ECMs or energy conservation strategies have been implemented. The IPMVP provides guidance on M&V strategies and their appropriate applications for various situations. These strategies should be used in conjunction with monitoring and trend logging of significant energy systems to provide for the ongoing accountability of tenant space energy performance.
Standard Practice
None
CT-156
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Install continuous metering equipment for the following end-uses: o Lighting systems and controls o Constant and variable motor loads o Variable frequency drive (VFD) operation o Chiller efficiency at variable loads (kW/ton) o Cooling load o Air and water economizer and heat recovery cycles o Air distribution static pressures and ventilation air volumes o Boiler efficiencies o Indoor water risers and outdoor irrigation
Develop a Measurement and Verification plan that incorporates the monitoring information from the above end-uses and is consistent with Option B, C or D of the 2001 International Performance Measurement & Verification Protocol (IPMVP) Volume I: Concepts and Options for Determining Energy and Water Savings
Consider the recommendations included in the Chicago Climate Action Plan
Best Available Practice
Draft a Measurement & Verification Plan to apply during tenant operation that compares predicted savings to those achieved
CT-157
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
10.0 GREEN INTERIORS
10.6 Tenant Space Automation System
1 point
INTENT
Provide information to support the ongoing accountability and optimization of energy performance and identify opportunities for additional energy-saving investments.
REQUIREMENTS
Have in place a computer-based tenant space automation system that monitors and controls key systems that include, but are not limited to:
Heating Cooling Ventilation Lighting
Have a preventive maintenance program in place that ensures tenant space automation system components are tested and repaired or replaced according to the manufacturer’s recommended interval. Demonstrate that the tenant space automation system is being used to inform decisions regarding changes in operations and energy-saving investments.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Install and/or maintain a tenant space automation system to automatically control key systems. Ensure that relevant staff is adequately trained to use the system, analyze output, make necessary adjustments, and identify investment opportunities to improve energy performance.
Standard Practice
None
Recommended Practice
Install and utilize a tenant space automation system
Best Available Practice
None
CT-158
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
10.0 GREEN INTERIORS
10.7.1 Occupant Controls: Lighting Comfort
1 Point
INTENT
Provide a high level of lighting system control by individual occupants or by specific groups in multi-occupant spaces (e.g., classrooms and conference areas) to promote the productivity, comfort and well-being of occupants.
REQUIREMENTS
Provide individual lighting controls for 90% (minimum) of the tenant space occupants to enable adjustments to suit individual task needs and preferences.
AND
Provide lighting system controls for all shared multi-occupant spaces to enable lighting adjustment that meets group needs and preferences.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Ensure the tenant space includes occupant controls for lighting. Strategies to consider include lighting controls and task lighting. Integrate lighting systems controllability into the overall lighting design, providing ambient and task lighting while managing the overall energy use of the space.
Standard Practice
None
Recommended Practice
Use motion-activated lighting Design lighting control systems to take advantage of daylight harvesting to reduce
artificial lighting when adequate daylight is available Design areas to provide a variety of levels of light and sound in different areas
simultaneously Provide task lighting or more light switching zones in office areas
CT-159
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
None
CASE STUDY
Occupant Lighting Controls Hertz Corporate – North America and Europe
In 2008, Hertz undertook a number of initiatives to manage and reduce energy usage at its locations in North America and Europe. Initial efforts have focused on Quick Hitters that are energy initiatives that can immediately address interior/exterior lighting, HVAC, and process loads (car wash, vacuum systems). Examples include HVAC Thermostat controls, LED exit signs, lighting occupancy controls, photocells, and time clocks.
https://images.hertz.com/pdfs/green_initiatives_2010.pdf
CT-160
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
10.0 GREEN INTERIORS
10.7.2 Occupant Controls: Thermal Comfort
1 Point
INTENT
Provide a high level of thermal comfort system control by individual occupants or by specific groups in multi-occupant spaces (i.e. classrooms or conference areas) to promote the productivity, comfort and well-being of occupants.
REQUIREMENTS
Provide individual comfort controls for 50% (minimum) of the occupants to enable adjustments to suit individual task needs and preferences. Operable windows can be used in lieu of comfort controls for occupants of areas that are 20 feet inside of and 10 feet to either side of the operable part of the window. The areas of operable window must meet the requirements of ASHRAE 62.1-2010 paragraph 5.1 Natural Ventilation.
AND
Provide comfort system controls for all shared multi-occupant spaces to enable adjustments to suit group needs and preferences.
Conditions for thermal comfort are described in ASHRAE Standard 55-2004 to include the primary factors of air temperature, radiant temperature, air speed and humidity.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Ensure tenant space and systems have comfort controls to allow adjustments to suit individual needs or those of groups in shared spaces. ASHRAE Standard 55-2004 identifies the factors of thermal comfort and a process for developing comfort criteria for tenant spaces that suit the needs of the occupants involved in their daily activities. Control strategies can be developed to expand on the comfort criteria to allow adjustments to suit individual needs and preferences.
These strategies may involve system designs incorporating operable windows, hybrid systems integrating operable windows and mechanical systems, or mechanical systems alone. Individual adjustments may involve individual thermostat controls, local diffusers at floor, desk or overhead levels, or control of individual radiant panels, or other means integrated into the overall space, thermal comfort systems, and energy systems design. In addition, designers should evaluate the closely tied interactions between thermal comfort (as required by ASHRAE Standard 55-2004) and acceptable indoor air quality (as required by ASHRAE Standard 62.1-2010, whether natural or mechanical ventilation).
CT-161
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
Provide individual thermal controls for occupants
Best Available Practice
Provide underfloor air distribution systems with individual diffusers for office spaces
Provide ceiling fans or natural ventilation to increase air movement Provide humidification in HVAC systems serving office For spaces with humidification, install humidistats in addition to thermostats
CT-162
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
10.0 GREEN INTERIORS
10.8 Thermal Comfort: Employee Verification
1 Point
INTENT
Provide for the assessment of thermal comfort over time.
REQUIREMENTS
Agree to implement a thermal comfort survey of employees within a period of 6 to 18 months after occupancy. This survey should collect anonymous responses about thermal comfort in the tenant space including an assessment of overall satisfaction with thermal performance and identification of thermal comfort-related problems. Agree to develop a plan for corrective action if the survey results indicate that more than 20% of occupants are dissatisfied with thermal comfort. This plan should include measurement of relevant environmental variables in problem areas in accordance with ASHRAE Standard 55-2004.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
ASHRAE Standard 55-2004 provides guidance for establishing thermal comfort criteria and the documentation and validation of performance to the criteria. While the standard is not intended for purposes of continuous monitoring and maintenance of the thermal environment, the principles expressed in the standard provide a basis for design of monitoring and corrective action systems.
Standard Practice
None
Recommended Practice
None
Best Available Practice
None
CT-163
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Benchmarking Building Quality University of California – Berkley, California
At the Center for Built Environment at the University of California, Berkeley, they created a standardized environmental quality assessment survey that measures employees’ satisfaction with their workplace environment quickly and at a low price. A standard set of core questions is used to measure satisfaction with environmental factors such as indoor air quality, thermal comfort, and acoustics. The survey has been used to evaluate the performance of 22 buildings in the United States.
www.stanford.edu/group/narratives/classes/08-09/CEE215/ReferenceLibrary/CBE%20Research%20Thermal%20Comfort/A%20Web-Based%20Occupant%20Satisfaction%20Survey.pdf
CT-164
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
11.0 WATER MANAGEMENT
11.1 Utility Meter Data
4 points
INTENT
Increase water efficiency within tenant spaces to reduce the burden on municipal water supply and wastewater systems.
REQUIREMENTS
Provide water meter data (if available). Use water meter data to compile water use and report data on a periodic basis, e.g. annually at a minimum.
SUBMITTALS
Provide numerical data, e.g. annual consumption, for the narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Where possible install water meters to measure a tenant space’s domestic water use.
Meter data will be used to determine water use reduction in SAM Credit 11.3, Option 1. Gather meter data for one full year. This first year reported will act as the baseline for subsequent years.
Standard Practice
Comply with CDA/OMP Specification 15410 – Plumbing Fixtures
Recommended Practice
Track water consumption using metering
Install water meters to track tenant space water use (submetering)
Best Available Practice
Track water consumption using submetering for one or more of the following: o Irrigation o Indoor plumbing fixtures o Cooling towers o Domestic hot water o Process water
CT-165
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
11.0 WATER MANAGEMENT
11.2 Water Management Plan
2 points
INTENT
To reduce the use of water while promoting continuity of information to ensure that water-efficient operating strategies are maintained and provide a foundation for training employees and continuous improvement.
REQUIREMENTS
At a minimum, use the following form to document the following:
Develop a systems narrative that briefly describes current practices, the plumbing systems and equipment in the tenant space. The systems narrative must include all the systems using water, including at a minimum; restroom and kitchen plumbing fixtures, food service equipment (e.g. ice makers), other process related water use systems.
Describe what conservation initiatives have been implemented to reduce the consumption of water.
SUBMITTALS
Include descriptive narrative in the SAM Checklist as well as a copy of the Water Management Plan.
TECHNOLOGY/STRATEGY
For a tenant space to operate successfully, the tenant’s staff must understand the space’s current performance, critical metrics must be established, and steps to improve performance must be developed.
Inspect all existing fittings or fixtures to ensure they are operating properly. Make any repairs needed to bring all fixtures into good working order or permanently turn off water supply to nonfunctional units.
Implement a fixture and fitting replacement and retrofit policy specifying that all newly installed toilets, urinals, private lavatory faucets, and showerheads that are eligible for labeling be WaterSense labeled. For a listing of WaterSense labeled products visit http://www.epa.gov/watersense/product_search.html.
For building water use, confirm that calculations are up to date. Demonstrate that all applicable purchases meet the requirements of the fixture and fitting replacement and retrofit policy.
Standard Practice
None
CT-166
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Develop a Water Management Plan for the tenant space
Best Available Practice
Continuously improve upon and require that all employees are trained on the merits and policies contained within the Water Management Plan.
CASE STUDY
Water Management Planning U.S. Department of Energy Y-12 National Security Complex
A water assessment at the Y-12 National Security Complex in Oak Ridge, Tennessee, provided a comprehensive understanding of current water-consuming equipment and applications while identifying key areas for efficiency improvement.
http://www1.eere.energy.gov/femp/pdfs/y12_lessonslearned.pdf
CT-167
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
WATER MANAGEMENT PLAN TEMPLATE SAM Credit 11.2
Tenant Information
Date
Tenant
Owner
Address/Location
Contact Person
Phone
Water Management Survey
All questions apply to systems under the tenant’s control and/or within the space being evaluated.
1. Does tenant have separately metered water utility? Yes No
2. If yes, what is annual water usage? Gal/yr
From __________/__________ to __________/__________ Month/Year Month/Year
3. Fixture Inventory (input quantity of each unit): Number Flow rate Sensor/Timer
/Aerator
a. Toilets/Water Closet
b. Urinals
c. Lavatories
d. Faucets
e. Water Fountains
3. Fixture Inventory (input quantity of each unit) (cont’d): Number Flow rate Sensor/Timer
/Aerator
CT-168
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
f. Pre-Rinse Spray Valves
g. Other (List)
h. Other (List)
i. Other (List)
4. Water Using Appliances and Equipment (List) Number ENERGY
STAR (Y/N)
a. e.g. Dishwasher, Model ###
b. e.g. Ice Maker, Model ###
c.
d.
5. Conservation Techniques – e.g. rainwater harvesting, gray water reuse
6. Education and Training – If yes, please describe Yes No
a. Water Conservation Signage
b. Employee Training - Water Conservation
c. Customer Education - Water Conservation
7. Please share any additional information you think is pertinent.
(Please use additional pages as necessary to complete)
CT-169
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
11.0 WATER MANAGEMENT
11.3 Water Use Reduction
1 to 10 points
INTENT
Further increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.
REQUIREMENTS
OPTION 1 –
Employ strategies described in CDA/OMP Specification 15410.
AND
Using one year’s worth of meter data, calculate reduction compared to baseline data (data from first review).
Additional water reductions beyond the baseline set by the 1st year data water usage will be awarded credits based on the following table:
SAM Credit Building and Process Water Reduction Points
11.4.1 5% 1
11.4.2 10% 2
11.4.3 15% 3
11.4.4 20% 4
11.4.5 25% 5
11.4.6 30% 6
11.4.7 35% 7
11.4.8 40% 8
11.4.9 45% 9
11.4.10 50% 10
Example: A tenant collected and recorded water meter data from two years ago and designated this period as the baseline water usage. The annual water use for the baseline year was 100,000 gallons. In the subsequent year, due to water efficiency upgrades and improvements, the tenant was able to lower water usage for this period to
CT-170
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
80,000 gallons. This calculates to a 20% improvement over the baseline and therefore 4 points are awarded.
OR
OPTION 2 –
Create an inventory of all the water use improvements and upgrades that tenant has undertaken to improve their water efficiency prior and during the performance review.
A point will be awarded for each of the improvements. Up to 6 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Low-flow toilets (<1.6 gal/flush) 1
Low-flow urinals (<1.0 gal/flush) 1
Waterless toilets and urinals 1
Low-flow kitchen and lavatory faucets (<0.5 gal/min)
1
Low-flow pre-rinse spray valves (<1.6 gal/min) 1
Automatic sensors for faucets and flushing 1
Water meters for submetering 1
Replace potable water for non-potable water applications with collected process water or rainwater (e.g. cisterns, rain barrels)
1
ENERGY STAR dishwasher 1
ENERGY STAR washing machine 1
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
CT-171
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
WaterSense™-certified fixtures and fixture fittings should be used where available. Use high-efficiency fixtures (water dispensers, water closets and urinals) and dry fixtures such as composting toilet systems to reduce the potable water demand. Consider the use of alternate on-site sources of water, such as rainwater, stormwater, or air conditioner condensate, and graywater for non-potable applications such as toilet and urinal flushing, as approved by the manufacturer, and custodial uses.
Standard Practice
None
Recommended Practice
Use high-efficiency fixtures and valves, such as automatic sensors, aerators on lavatories and dual-flush toilets
Best Available Practice
Dry fixtures such as composting toilets and waterless urinals to reduce wastewater volumes
CASE STUDIES
Water Use Reduction Founding Farmers Restaurant – Washington D.C.
Founding Farmers Restaurant in Washington DC utilizes waterless urinals and low-flow valves in their restrooms. They also use an ENERGY STAR dishwasher and spray valve. Their sustainable plumbing and fixture equipment saved at least 193,168 gallons of water compared to a conventional restaurant design in 2009.
http://ddoe.dc.gov/service/case-study-founding-farmers
Water Efficiency XOCO Restaurant – Chicago, Illinois
XOCO uses upwards of 40% less water in its operation in comparison to a comparable standard restaurant of its size. To achieve this, we installed the following water conserving equipment and fixtures:
Low-flow, dual flush toilets. Low flow rinse valve for warewash that uses less than 1.28 gallons per minute (gpm). ENERGY STAR Rated Dishwashing machine High efficiency water heater Low flow water aerators make faucets use less than 1.0 gpm.
www.rickbayless.com/restaurants/sustainability.html
CT-172
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
12.0 ENERGY MANAGEMENT
12.1 Utility Meter Data
4 points
INTENT
Monitor, track and report utility data to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
Provide energy meter data (if available). Use energy meter data to compile energy use and report data on a periodic basis, e.g. annually at a minimum.
SUBMITTALS
Provide numerical data, e.g. annual consumption, for the narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Where possible install electric and/or gas meters to measure a tenant space’s energy consumption.
Meter data will be used to determine energy use reduction in SAM Credit 12.4. Gather meter data for one full year. This first year reported will act as the baseline for subsequent years.
Standard Practice
None
Recommended Practice
Install utility meters where applicable Track and record energy usage
Best Available Practice
Install submeters wherever possible
CT-173
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
12.0 ENERGY MANAGEMENT
12.2 Energy Management Plan
2 points
INTENT
To reduce energy use while promoting continuity of information to ensure that energy-efficient operating strategies are maintained and provide a foundation for training employees and continuous improvement.
REQUIREMENTS
The Energy Management Plan should highlight the tenants’ plan for each of the following:
1. Measure - collecting data and analyzing total consumption for establishing an energy usage baseline.
2. Fix the basics - Fixing the basics typically consists of efforts, such as installing low-energy-consumption devices.
3. Automate - Ongoing energy-efficiency improvements can be achieved by automating and regulating building systems. Measures such as schedule-based lighting control and occupancy sensors automatically turn lights on only when they are needed in commercial buildings, while HVAC control regulates heating and cooling at optimal levels, which can change from day to day. More importantly, however, these measures facilitate an active approach to energy management, because they can be adjusted based on new energy-efficiency opportunities that arise in the future.
a. Timers
b. Sensors
c. Occupancy Controls
d. HVAC
e. Building Information Systems
4. Monitor and control - A strategic energy management plan also helps ensure that initial energy and cost savings don't erode over time. Power meter installations, monitoring services, energy-efficiency analysis, energy bill verification, and implementation of an enterprise energy management (EEM) system can all help achieve this end.
SUBMITTALS
Include descriptive narrative in the SAM Checklist as well as a copy of the Energy Management Plan.
CT-174
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
For a tenant space to operate successfully, the tenant’s staff must understand the space’s current performance, critical metrics must be established, and steps to improve performance must be developed.
Inspect all existing devices or fixtures to ensure they are operating properly. Make any repairs needed to bring all fixtures into good working order or permanently turn off electrical supply to nonfunctional units.
Implement a fixture and fitting replacement and retrofit policy specifying that all newly installed devices, equipment and light bulbs are Energy Star or more energy efficient than those they are replacing.
Demonstrate that all applicable purchases meet the requirements of the fixture and fitting replacement and retrofit policy.
Standard Practice
None
Recommended Practice
Develop an Energy Management Plan for the tenant space
Best Available Practice
Continuously improve upon and require that all employees are trained on the merits and policies contained within the Energy Management Plan.
CASE STUDY
Energy Management Planning One Earth Food Group – Corporate Strategic Energy Management Plan
The One Earth Food Group Continuous Energy Improvement Program focuses on understanding how the company uses energy and developing ways to reduce energy costs. The Energy Management Plan identifies the tasks necessary for the Continuous Energy Improvement Program to maintain consistent progress and achieve its goals.
http://www.energyimprovement.org/tools/2_Plan/2.3/StrategicEnergyManagementPlan-Ex1.pdf
CT-175
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
ENERGY MANAGEMENT PLAN TEMPLATE SAM Credit 12.2
Tenant Information
Date
Tenant
Owner
Address/Location
Contact Person
Phone
Energy Management Survey
All questions apply to systems under the tenant’s control and/or within the space being evaluated.
1. Does tenant have separately metered energy utility? Yes No
2. If yes, what is annual energy usage?
a. Electricity kWh/yr
From __________/__________ to __________/__________ Month/Year Month/Year
b. Gas Btu/yr
From __________/__________ to __________/__________ Month/Year Month/Year
CT-176
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
3. Lighting Fixture Inventory (input quantity of each unit):
Number Wattage Sensor/Timer
a. e.g. T8 fluorescent lamps
b. e.g. CFL recessed lights
c. Other (List)
d. Other (List)
4. Electrical Appliances (List) Number ENERGY
STAR (Y/N)
a. e.g. Dishwasher, Model ###
b. e.g. Ice Maker, Model ###
c. Other (List)
d. Other (List)
5. Office Equipment (List) Number ENERGY
STAR (Y/N)
a. e.g. Printer/Copier, Model ###
b. e.g. Computer, Model ###
c. Other (List)
d. Other (List)
6. Gas Appliances and Equipment (List) Number ENERGY
STAR (Y/N)
a. e.g. Oven/Range, Model ###
b. e.g. Water Heater, Model ###
c. Other (List)
d. Other (List)
7. Mobile Equipment/Vehicle Fuel Usage (input quantity of each unit):
Number Fuel Type Fuel Usage/
Mileage
a. e.g. Lawn Mowers, Model ###
b. e.g. Forklifts, Model ###
c. Other (List)
d. Other (List)
e. Other (List)
CT-177
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
8. Renewable Energy Sources – e.g. solar hot water heating, photovoltaics
9. Largest Energy User (list system, equipment, etc. with the largest consumption of energy – electric and/or gas)
10. Conservation Techniques – e.g. anti-idling, occupancy sensors, etc.
11. Education and Training – If yes, please describe
a. Energy Conservation Signage Yes No
b. Employee Training - Energy Conservation Yes No
c. Customer Education - Energy Conservation Yes No
12. Please share any additional information you think is pertinent.
(Please use additional pages as necessary to complete)
CT-178
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
12.0 ENERGY MANAGEMENT
12.3 Energy Use Reduction
1 to 10 points
INTENT
Further increase energy efficiency within buildings to reduce the burden on local utilities.
REQUIREMENTS
OPTION 1 –
Using one year’s worth of meter data, calculate reduction compared to baseline data (data from first review).
Energy reduction beyond the baseline set by 1st year data energy usage will be awarded credits based on the following table:
SAM Credit Energy Reduction Points
12.4.1 5% 1
12.4.2 10% 2
12.4.3 15% 3
12.4.4 20% 4
12.4.5 25% 5
12.4.6 30% 6
12.4.7 35% 7
12.4.8 40% 8
12.4.9 45% 9
12.4.10 50% 10
Example: A tenant collected and recorded electric meter data from two years ago and designated this period as the baseline electric usage. The annual electric use for the baseline year was 100,000 kWh. In the subsequent year, due to energy efficiency upgrades and improvements, the tenant was able to lower energy usage for this period to 80,000 kWh. This calculates to a 20% improvement over the baseline and therefore 4 points are awarded.
OR
CT-179
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
OPTION 2 –
Create an inventory of all the energy improvements and upgrades that tenant has undertaken to improve their energy efficiency prior to and during the performance review.
A point will be awarded for each of the improvements. Up to 6 points may be awarded by achieving any of the following measures:
Measure Points
LED lighting 1
CFL lighting 1
Halogen or induction lamps 1
High efficiency T8s and T5s 1
Lighting sensors or timers 1
Organize circuiting of lighting and systems so that individual areas are separately controlled relative to daylight and heating/cooling zones
1
Motion sensors/occupancy sensors in stairs, restrooms, storage rooms, equipment rooms and office space
1
High-efficiency motors and variable-speed pumping systems
1
ENERGY STAR furnaces, exhaust fans, ceiling fans, and air conditioners
1
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Select ENERGY STAR rated equipment, optimize HVAC systems and lighting, and implement an energy management plan that reduces energy consumption. Any strategies that reduce energy consumption should be considered that will impact the results of this credit. Additional points can be obtained using strategies as outlined in the other credits of this section.
Standard Practice
None
CT-180
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Use high-efficiency equipment, fixtures, appliances, and lighting
Maintain an energy management plan that addresses off-hour usage, timers, and/or sensors
Best Available Practice
None
CT-181
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
12.0 ENERGY MANAGEMENT
12.4.1 Optimize Energy Performance: Lighting Power
1 to 5 Points
INTENT
Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
Reduce connected lighting power density below that allowed by ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda) using either the space-by-space method or by applying the tenant’s lighting power allowance to the entire tenant space.
The points awarded for reducing lighting power density below the standard are as follows:
SAM Credit Lighting Power Density Reduction Below the Standard Points
12.4.1.1 15% 1
12.4.1.2 20% 2
12.4.1.3 25% 3
12.4.1.4 30% 4
12.4.1.5 35% 5
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Ensure the connected lighting power maximizes energy performance. If possible, consider a computer simulation model to assess the performance and identify the most cost-effective energy measures.
Standard Practice
None
CT-182
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Consider the following for tenant spaces:
Provide energy efficient lighting systems including LED, fluorescent lighting, solar lighting
Use LED lighting, wherever applicable Use CFL lighting, wherever applicable Utilize energy saving halogen or induction lamps
Utilize high efficiency T8s and T5s Use a computer simulation model to assess energy performance and identify the
most cost effective energy measures
Best Available Practice
None
CASE STUDY
Energy Efficient Burger King Burger King – Waghausel, Germany
The eco-friendly design developed in cooperation with Wirsol Solar AG (Baden-Württemberg) utilizes state-of-the-art technologies and renewable energy to power one-third of the restaurant’s energy consumption, thus reducing energy costs by 45% and the emission of CO2
by more than 120 metric tons every year.
The 20/20 design is complemented with the latest eco-friendly technologies and energy efficient construction elements including:
Interior heat recovery ventilation system that cools and heats the restaurant, saving 73% of energy consumption per year
Long-lasting interior and exterior LED bulbs saving more than 55% of energy consumption annually
Excess heat loss is captured to generate hot water, conserving 50% of energy usage annually
A wind turbine contributing up to 2,500 kWh to the restaurant’s power supply was added to the traditional exterior BK® logo sign
Photovoltaic and wind energy systems that save up to 45% of electricity annually More than 720 solar photovoltaic modules generate over 53,500 kWh of electricity per
year, which equals the annual consumption of five U.S. households A solar-powered electric vehicle charging station for hybrid cars A rainwater reclamation system for outside irrigation
CT-183
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
In addition, the restaurant kitchen features the revolutionary Duke Flexible Batch Broiler, which maximizes cooking flexibility while reducing gas consumption and related costs by 52 percent electricity consumption and costs by 90 percent. All BURGER KING® restaurants in North America have installed this new broiler and the international rollout is expected to be completed by the end of 2012.
www.restaurantnewsresource.com/article46521.html
CT-184
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
12.0 ENERGY MANAGEMENT
12.4.2 Optimize Energy Performance: Lighting Control
1 to 3 Points
INTENT
Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
Up to 3 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Daylight controls for daylight areas: Install daylight responsive controls in all regularly occupied daylit spaces within 15 feet of windows and under skylights. Daylight controls must switch or dim electric lights in response to the presence or absence of daylight illumination in the space.
1
Daylight controls for 50% of the lighting load 1
Install Occupancy Sensors for 75% of the connected lighting load
1
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Ensure the connected lighting power maximizes energy performance.
Standard Practice
None
CT-185
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Provide energy efficient lighting systems including LED, fluorescent lighting, solar lighting and the use of lighting sensors or timers
Organize circuiting of lighting and systems so that individual areas may be separately controlled relative to daylight and heating/cooling zones
Provide motion sensors/occupancy sensors in stairs, restrooms, storage rooms, equipment rooms and office space unless life safety is compromised
Optimize lighting controls for energy savings and function
Best Available Practice
Integrate lighting systems with Tenant Space Automation System (see SAM Credit 10.6)
CT-186
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
12.0 ENERGY MANAGEMENT
12.4.3 Optimize Energy Performance: HVAC
3 to 6 Points
INTENT
Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
OPTION 1 –
Implement one or both of the following strategies: Equipment Efficiency: (3 pts)
Install heating, ventilation and air conditioning (HVAC) systems that comply with the efficiency requirements outlined in the New Buildings Institute’s Advanced Buildings™ Core Performance™ Guide Sections 1.4: Mechanical System Design, 2.9: Mechanical Equipment Efficiency and 3.10: Variable Speed Control, These sections provide guidance on how to design mechanical systems in an energy efficient manner.
Appropriate Zoning and Controls: (3 pts) Zone spaces to meet the following requirements:
o Every solar exposure must have a separate control zone o Interior spaces must be separately zoned o Private offices and special occupancies (conference rooms, kitchens, etc.)
must have active controls capable of sensing space use and modulating the HVAC system in response to demand
OR OPTION 2 –
Reduce design energy cost compared with the energy cost budget for regulated energy components described in the requirements of ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda)
and
OPTION 2: PATH 1 (3 pts)
Demonstrate that HVAC system component performance criteria used for tenant space are 15% better than a system in minimum compliance with ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda).
CT-187
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
or
OPTION 2: PATH 2 (6 pts)
Demonstrate that HVAC system component performance criteria use for tenant space are 30% better than a system that is in minimum compliance with ANSI/ASHRAE/IESNA Standard 90.1-2010 (with errata but without addenda).
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Ensure the HVAC system components maximize energy performance. Review compliance options to determine the most appropriate approach. Option 1 provides a more prescriptive approach to recognizing energy-efficient HVAC design, while Option 2 is performance based.
Standard Practice
None
Recommended Practice
Provide high-efficiency motors and variable-speed pumping systems Utilize ENERGY STAR furnaces, exhaust fans, ceiling fans, and air conditioners
Best Available Practice
Evaluate under floor air distribution systems in office-type spaces Evaluate “green walls” for tenant space Utilize premium efficiency motors where applicable
CASE STUDY
HVAC Initiatives Hertz Corporate – North America and Europe
In 2008, Hertz undertook a number of initiatives to manage and reduce energy usage at its locations in North America and Europe. Initial efforts have focused on Quick Hitters that are energy initiatives that can immediately address interior/exterior lighting, HVAC, and process loads (car wash, vacuum systems). Examples include HVAC Thermostat controls, LED exit signs, lighting occupancy controls, photocells, and time clocks.
https://images.hertz.com/pdfs/green_initiatives_2010.pdf
CT-188
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
12.0 ENERGY MANAGEMENT
12.4.4 Optimize Energy Performance: Equipment & Appliances
1 to 3 Points
INTENT
Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
REQUIREMENTS
For all ENERGY STAR qualified equipment and appliances installed in the tenant space, points will be awarded based on the following percentages by pieces of equipment:
SAM Credit ENERGY STAR Qualified Equipment* Points
12.4.4.1 50% 1
12.4.4.2 75% 2
12.4.4.3 100% 3
*As a percentage of ENERGY STAR eligible equipment Excluded are HVAC, lighting and building envelope products.
This requirement applies to appliance, office equipment, electronics and commercial food service equipment. Excluded are HVAC, lighting and building envelope products.
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Select energy-efficient equipment and appliances, as qualified by the EPA’s ENERGY STAR Program (https://www.energystar.gov).
Standard Practice
None
CT-189
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Consider the following for tenant spaces:
Provide high-efficiency motors and variable-speed pumping systems Provide ENERGY STAR compliant equipment and appliances such as:
o Dishwashers o Water Heaters o Washing machines o Dryers o Refrigerators o Walk-in refrigerators o Freezers o Ranges o Computers o Printers o Copiers o Phones o Televisions o Steamers o Fryers o Hot food holding cabinets o Ice machines o Convection ovens o Combination ovens o Griddles o Broilers
Provide other high efficiency equipment and appliances such as: o Hand Dryers o Food warmers o Charbroilers o Grills o Registers o Power strips
Best Available Practice
None
CT-190
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
12.0 ENERGY MANAGEMENT
12.5 Green Power
2 Points
INTENT
Encourage the development and use of grid-source, renewable energy technologies on a net zero pollution basis.
REQUIREMENTS
Engage in at least a 2-year renewable energy contract to provide at least 35% of the space’s electricity from renewable sources, as defined by the Center for Resource Solutions Green-e Energy product certification requirements.
OPTION 1 – DETERMINE THE BASELINE ELECTRICITY USE
Use the annual electricity consumption from the results of the subparts of SAM Credit 12.1 Utility Meter Data
OR
OPTION 2 – ESTIMATE BASELINE ELECTRICITY USE
Use the U.S. Department of Energy Commercial Buildings Energy Consumption Survey database to determine the estimated electricity use.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Determine the energy needs of the space and investigate opportunities to engage in a green power contract. Green power is derived from solar, wind, geothermal, biomass or low-impact hydro sources. Visit www.green-e.org/energy for details about the Green-e program. The power product purchased to comply with credit requirements need not be Green-e certified. Other sources of green power are eligible if they satisfy the Green-e program’s technical requirements. Renewable energy certificates (RECs), tradable renewable certificates (TRCs), green tags and other forms of green power that comply with Green-e’s technical requirements can be used to document compliance with this section.
CT-191
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
Determine the City of Chicago’s Green Power requirements for the task/project and investigate opportunities to engage in a green power contract with the utility
Visit www.green-e.org for details about the Green-e program
Best Available Practice
None
CASE STUDIES
Energy Efficient Burger King Burger King – Waghausel, Germany
The eco-friendly design developed in cooperation with Wirsol Solar AG (Baden-Württemberg) utilizes state-of-the-art technologies and renewable energy to power one-third of the restaurant’s energy consumption, thus reducing energy costs by 45% and the emission of CO2
by more than 120 metric tons every year.
The 20/20 design is complemented with the latest eco-friendly technologies and energy efficient construction elements including:
Interior heat recovery ventilation system that cools and heats the restaurant, saving 73% of energy consumption per year
Long-lasting interior and exterior LED bulbs saving more than 55% of energy consumption annually
Excess heat loss is captured to generate hot water, conserving 50% of energy usage annually
A wind turbine contributing up to 2,500 kWh to the restaurant’s power supply was added to the traditional exterior BK® logo sign
Photovoltaic and wind energy systems that save up to 45% of electricity annually More than 720 solar photovoltaic modules generate over 53,500 kWh of electricity per
year, which equals the annual consumption of five U.S. household A solar-powered electric vehicle charging station for hybrid cars A rainwater reclamation system for outside irrigation.
CT-192
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
In addition, the restaurant kitchen features the revolutionary Duke Flexible Batch Broiler, which maximizes cooking flexibility while reducing gas consumption and related costs by 52 percent electricity consumption and costs by 90 percent. All BURGER KING® restaurants in North America have installed this new broiler and the international rollout is expected to be completed by the end of 2012.
www.restaurantnewsresource.com/article46521.html
Electricity from Waste Los Angeles World Airports - Los Angeles, California
Over 8,000 tons of food waste produced each year at Los Angeles International Airport is being used to produce methane gas which is then recycled and turned into electricity. This complex process involves food being ground up and mixed with water, creating a slurry, which is then heated up into methane gas and carbon dioxide. Eventually this is transferred offsite to an adjacent power generation plant and converted into electricity.
www.wasteage.com/mag/waste_los_angeles_airport/
CT-193
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.1 Waste Stream Audit
4 points – Required for CT-OM Mentor Certification
INTENT
Determine the overall generation of various wastes produced and reduce ongoing waste and toxins generated by the tenant.
REQUIREMENTS
Conduct a waste stream audit of the tenant’s entire ongoing consumables waste stream for the performance period. Use the initial audit to establish a baseline that identifies the types of waste making up the waste stream and the amounts of each type by weight and volume.
As part of the waste stream audit, tenant will analyze their waste stream to determine weights and volumes of the following categories:
Items for offsite disposal or incineration Items for composting Items for recycling
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist outlining the types of waste and the weight and/or volumes. Refer to the EPA’s website for waste audit worksheets.
http://www.epa.gov/osw/conserve/rrr/rogo/documents/airport-recycling-guide.pdf
TECHNOLOGY/STRATEGY
Understanding waste production patterns is an important first step to waste reduction. Work with your waste hauler or service provider to collect and analyze information on the amounts and types of waste generated by the facility.
Standard Practice
None
CT-194
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Use the results of the waste audit as a baseline for evaluating future recycling efforts. Analyze the results of the audit and identify targets for expanding the tenant’s recycling program. Evaluate the capturing and recycling of specific wastes.
Best Available Practice
Create a Five Year Action Plan outlining waste reduction methods that will be undertaken in the coming years.
CASE STUDIES
Tenant and Contractor Obligations Brisbane International Airport – Brisbane, Australia
The Brisbane Airport Corporation (BAC) uses the activities/nature of business of tenants to determine an overall risk rating for a site. As part of an overall annual or biannual tenant audit, based on the tenant environmental risk category, the BAC inspects; waste minimization practices, segregation of waste and recycling, storage of waste, and Monitoring & Reporting of wastes.
http://www.bne.com.au/sites/all/files/content/files/BAC%20AES%202009_FINAL_March2011.pdf
Waste Research Ben & Jerry’s Ice Cream
The program began when a group of employees dove into the company’s dumpsters to evaluate the amount and type of waste generated by the company. Their “research” gave them three types of trash to focus on: plastic, paper, and cardboard. They began shipping their plastic ingredient buckets to Vermont Republic Industries to be recycled and reused. Ben & Jerry’s production crew purchased a baler which helped in recycling cardboard to be used by paper broker companies. Through these measures, within one year of the inception of the plan, the company had already saved $17,000 in hauling and landfill costs.
www.apus-sustainability.com/2010/04/15/ben-jerry%E2%80%99s-how-one-company-has-integrated-sustainable-practices-into-its-business-model-and-thrived
CT-195
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.2 Waste Management Plan
2 points
INTENT
To reduce the waste generated by the tenant and hauled to and disposed of in landfills and incinerators.
REQUIREMENTS
Maintain a waste reduction and recycling program that reuses, recycles, or composts waste.
SUBMITTALS
Include descriptive narrative in the SAM Checklist as well as a copy of the Waste Management Plan.
TECHNOLOGY/STRATEGY
For a tenant space to operate successfully, the tenant’s staff must understand the space’s current performance, critical metrics must be established, and steps to improve performance must be developed.
Standard Practice
None
Recommended Practice
Develop an Waste Management Plan for the tenant space
Best Available Practice
Continuously improve upon and require that all employees are trained on the merits and policies contained within the Waste Management Plan.
CT-196
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
WASTE MANAGEMENT PLAN TEMPLATE SAM Credit 13.2
Tenant Information
Date
Tenant
Owner
Address/Location
Contact Person
Phone
Waste Management Survey
All questions apply to systems and waste under the tenant’s control and/or within the space being evaluated.
SOLID WASTE
1. Solid Waste Management Company (list all that apply)
2. Do you receive waste generation reports from waste hauler? Yes No
3. If yes, what is annual solid waste generation? lb/yr
From: To:
month/year month/year
4. If yes, what is annual solid waste recycled? lb/yr
From: To:
month/year month/year
5. If yes, what is annual solid waste composted? lb/yr
From: To:
month/year month/year
CT-197
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
6. Indicate with an X in the appropriate column the types of recyclable/compostable solid wastes generated:
Source Separated
Single-Stream
a. Cardboard/cardstock
b. Aluminum
c. Steel
d. Glass
e. Paper
f. Plastics
g. Compostable waste (incl. food waste)
h. Coffee Grounds
i. Other (list)
7. Does tenant have a designated recycling/composting area? Describe location:
LIQUID WASTE
1. Liquid Waste Management Company (list all that apply)
2. Do you receive waste generation reports from waste hauler? Yes No
3. If yes, what is annual liquid waste generation? gal/yr or lb/yr
From: To:
month/year month/year 4. List liquid waste types that are recycled – e.g. grease, motor oil
5. Does tenant have a designated recycling area? Describe location:
CT-198
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
SPECIAL WASTE
1. Does tenant have universal waste management plan for safe disposal of batteries, paints, solvents, electronics, mercury-containing lamps, printer cartridges, etc.
Yes No
2. List all types of universal wastes above and include quantities disposed/recycled, if known:
3. Does tenant have a designated universal waste recycling area? Describe location:
Other Waste Management Questions
1. What is tenant’s largest waste sources/products:
2. Waste Reduction Techniques – e.g. bulk purchasing, manufacturer take-back programs, donation programs, etc.
3. Education and Training – If yes, please describe
Waste Minimizarion/Recycling Signage Yes No
Employee Training – Waste Management Yes No
Customer Education – Waste Management Yes No
CT-199
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
4. Has tenant performed a third-party waste audit? If yes, describe results:
5. Does tenant track waste generation, recycling, and disposal quantities? If yes, indicate if and where results are reported – e.g. website, documents.
6. Describe goals for waste reduction over time – e.g. waste reduction initiatives.
(Please use additional pages as necessary to complete)
CT-200
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.3 Waste Reduction
1 to 10 points
INTENT
Further increase solid waste reduction within buildings to reduce the burden on landfills and minimize emissions due to transport.
REQUIREMENTS
OPTION 1 –
Using one year’s worth of data based on the waste stream audit, calculate reduction compared to baseline data (data from first review, waste audit) of waste sent to landfill.
Waste reduction beyond the baseline set by 1st year data will be awarded credits based on the following table:
SAM Credit Reduction of waste sent to landfill (by percent)
Points
13.3.1 5% 1
13.3.2 10% 2
13.3.3 15% 3
13.3.4 20% 4
13.3.5 25% 5
13.3.6 30% 6
13.3.7 35% 7
13.3.8 40% 8
13.3.9 45% 9
13.3.10 50% 10
Example: A tenant collected and recorded waste disposal data from two years ago and designated this period as the baseline waste disposal. The annual amount of waste that was disposed in landfills for the baseline year was 100 tons. In the subsequent year, due to waste reduction initiatives, the tenant was able to lower waste disposal for this period to 80 tons. This calculates to a 20% improvement over the baseline and therefore 4 points are awarded.
CT-201
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
OR
OPTION 2 –
Create an inventory of all the waste reduction initiatives that tenant has undertaken to reduce solid waste prior to and during the performance review.
A point will be awarded for each of the initiatives. Up to 6 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Recycle glass, paper, plastic, etc. 1
Utilize trash compactors 1
Food waste composting program 1
Repurpose or reuse products or materials program
1
Bulk purchasing, reduced packaging 1
Oil and grease recycling 1
Coffee grounds composting program 1
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
TECHNOLOGY/STRATEGY
Maintain an effective recycling program that at a minimum addresses the traditional recyclables (paper, metal, glass, and plastic) Determine effective strategies for addressing other waste products which might include composting, for organic wastes, or reuse or repurposing for wood or other building materials. Waste reduction strategies including purchasing in bulk to reduce packaging waste or elimination of disposable products should also be considered.
Standard Practice
Employ traditional recycling (paper, metal, glass, and plastic)
Recommended Practice
Compost organic wastes such as food scraps and landscaping waste Reuse or repurpose building materials Donate unused inventory to charities
CT-202
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Make waste materials available to other entities through a warehouse or sharing program
Employ purchasing strategies that reduce waste volume, e.g. bulk purchases
Best Available Practice
None
CT-203
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.4 Storage and Collection of Recyclables
1 point – Required for CT-OM Mentor Certification
INTENT
Facilitate the reduction of waste generated by tenant space occupants that is hauled to and disposed of in landfills.
REQUIREMENTS
Provide an easily accessible dedicated area or areas that serve the tenant space for the collection and storage of materials for recycling, including paper, corrugated cardboard, glass, plastics and metals. An area should also be dedicated to collection and storage of compostable food waste.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Ensure that within the tenant space there is an area for recyclable collection and storage that is appropriately sized and located in a convenient area. These areas would likely be designed and sized differently depending on the ultimate use and waste stream of the facility (e.g., office, airlines, concessionaires, etc.) Identify local waste handlers and buyers for glass, plastic, office paper, e-waste, newspaper, cardboard, metals, fluids, fixtures, and organic wastes. Instruct employees, occupants, and contractors on the recycling procedures. Consider employing cardboard balers, aluminum can crushers, recycling chutes and other waste strategies to further enhance the recycling program.
Standard Practice
Designate an area for recyclable collection and storage that is appropriately sized and located in a convenient area
Instruct employees, users and occupants on recycling procedures
Recommended Practice
Investigate and incorporate collection rooms for recycling streams that make sense for each tenant space
Coordinate recyclable waste collection with hauler capability Recycle the following waste, whenever feasible:
o Aluminum o Glass o Paper, newspapers, magazines and cardboard
CT-204
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
o Carpet o Wood (pallets/crates, etc.) o Food waste/grease and compostables o Organic waste and compostables o Gas & oil filters o Motor oil and Anti-freeze o Scrap metal o Batteries o Light bulbs o Toner cartridges o Tires o Electrical wiring o Electronics including monitors
Best Available Practice
Employ cardboard balers, aluminum can crushers, recycling chutes and other technologies to enhance the recycling program
CASE STUDIES
In-Store Recycling Ben & Jerry’s Ice Cream
In each of the stores, there are built-in wooden bins to collect the plastic spoons used by patrons. In fact, some regular customers now bring their plastics from other restaurants in the area to have Ben & Jerry's recycle them.
www.mwcog.org/environment/recycling/hotel/mentor/BEN.HTM
In-Terminal Recycling Oakland International Airport – Oakland, California
On Earth Day 2002 Oakland Airport launched a recycling program to divert discarded newspapers and magazines, and office paper away from landfills. There are currently over 35 recycling stations throughout the terminals. Bins are located adjacent to trash receptacles and encourage greater recycling by identifying the types of acceptable material through visuals on the top and sides of each station. The goal of the Airport is to divert over 50% of the post-consumer trash from landfills.
www.flyoakland.com/noise/environmental_recycle.shtml
CT-205
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recycling on the Ramp Seattle-Tacoma International Airport – Seattle, Washington
Six new sets of large-capacity trash and recycling compactors have been installed on the ramp to handle recyclable and non-recyclable material from aircraft, ground support and other ramp operations. Compactors are monitored through an electronic key system, recording usage by each tenant and reducing pick-up trips by 75 percent. There is a set fee for trash disposal but not for recycling.
CT-206
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.5 Track and Report Recycling Activity
2 points
INTENT
Determine the types and amounts of recyclable waste and determine strategies for reducing and diverting additional waste from landfills.
REQUIREMENTS
Retain periodic recycling reports to be summarized for the performance review period. Types of waste to be tracked include:
Glass – bottles and other containers Metal – aluminum and steel containers, foil Plastic – bottles, containers, packaging, bags Paper – office paper, bags, cup sleeves, cup carriers, non-thermal receipt tape,
customer checks, newspaper, magazines Cardboard – cardstock, display boards, corrugated fiberboard, paperboard Rubber – tires Other (specify what items are recycled)
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist outlining the types of waste and volumes recycled.
TECHNOLOGY/STRATEGY
Standard Practice
Track recycling activity over time. Use the report to identity seasonal swings in recycling rates and program costs and benefits.
Recommended Practice
None
Best Available Practice
Provide the results of the recycling reports to the community and other interested stakeholders
CT-207
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Recycling Activity Delta Air Lines
Delta Air Lines posts monthly recycling statistics through online newsletters, posters and materials displayed in flight attendant lounges.
www.epa.gov/osw/conserve/rrr/rogo/documents/airport-recycling-guide.pdf
CT-208
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.6.1 Organic Byproduct Recycling: Food Waste
4 Points – Required for CT-OM Mentor Certification
INTENT
Facilitate the reduction of waste generated by tenant space occupants that is hauled to and disposed of in landfills.
REQUIREMENTS
Implement a food waste collection program that provides a means of separating food waste that is not fit for human consumption from the rest of the waste stream and finds other uses for the waste (i.e. composting, animal feed stock, anaerobic digestion, etc.).
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the storage, collection and disposal of food waste within the tenant space.
TECHNOLOGY/STRATEGY
With the implementation of increased security at airports, passengers are spending an increased amount of time at the airport and in turn creating more waste. In conjunction with the Airport, tenants should commit to reducing the amount of waste that eventually arrives at the landfills.
Standard Practice
None
Recommended Practice
Collect items such as vegetable trimmings and used paper towels/napkins to be used as high nutrient fertilizer in the production of organic food and fiber
Best Available Practice
Once the food waste has left the Airport it can be taken to a plant where it is then ground up into tiny particles. Through an accelerated process the organic materials are broken down and produce methane gas and carbon dioxide. The methane gas can then be piped to a power generation plant and converted into electricity.
CT-209
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDIES
Waste Recycling Ben & Jerry’s Ice Cream – Washington D.C.
In 1993, the company began giving their out-of-date, mislabeled and unusable product to a local trash-to-energy incineration plant which helps to generate power to people’s homes. In addition, they began to supply some of their waste product to a local composting plant where the waste is used as fertilizer for crops.
www.apus-sustainability.com/2010/04/15/ben-jerry%E2%80%99s-how-one-company-has-integrated-sustainable-practices-into-its-business-model-and-thrived/
Waste Recycling Heathrow International Airport – London, United Kingdom
London’s Heathrow Airport collects the food waste from it on-site cafes and restaurants and sends them to a recycling factory, where the scraps are converted into fertilizer.
www.envirothink.wordpress.com/2010/08/31/heathrow-airport-to-recycle-food-waste-into-fertilizer/
CT-210
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.6.2 Organic Byproduct Recycling: Coffee Grounds
4 Points
INTENT
Facilitate the reduction of waste generated by tenant space occupants that is hauled to and disposed of in landfills.
REQUIREMENTS
Implement a coffee grounds collection program that provides a means of separating grounds from the rest of the waste stream and finding other uses for the waste.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the collection and disposal of coffee grounds from the tenant space.
TECHNOLOGY/STRATEGY
With the implementation of increased security at airports, passengers are spending an increased amount of time at the airport and in turn creating more waste. In conjunction with the Airport, tenants should commit to reducing the amount of waste that eventually arrives at the landfills.
The weight of used coffee grounds can significantly impact the cost of waste removal. Though the use of creative solutions, the coffee grounds can instead be used for composting/fertilizer needs or insect control.
Standard Practice
None
Recommended
Collect the used coffee grounds and sell to a third part as a commodity. Permits and EPA approval may be required depending on the tenant’s location.
Best Available
Re-use coffee grounds onsite as soil additives. Permits and EPA approval may be required depending on the tenant’s location.
CT-211
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDIES
Coffee Grounds for Insect Control HMS Host/Starbucks/Charlotte - Douglas International Airport – Charlotte, North Carolina
In November 2008 Airport staff began pouring used coffee grounds, collected from Airport Tenants, on fire ant mounts to assist with the control. As of March 2009 the grounds were successful in eradicating 15-20 very large fire ant mounds that had been created over airfield lighting and had become a safety concern. The Airport was also working with environmental experts explore the use of coffee grounds for further insect control.
Charlotte – Douglas International Airport, “Recycled Coffee Grounds Snuff Out Airfield Fire Ants” Airport Update March 5, 2009: 2
Coffee Composting Seattle – Tacoma International Airport – Seattle, Washington
The Port of Seattle has implemented a program where a local composting company collects the used recycled coffee grounds from more than 55 specialty coffee shops, restaurants and lounges at the Sea-Tac Airport. The grounds are then mixed with lawn cuttings and yard waste from the home in the City of Seattle. To complete the cycle the Port purchases compost from the composting company for use in airport landscaping, and as grass fertilizer.
http://www.flyingcompass.com/Washington/Seattle/a-142.html
CT-212
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.6.3 Organic Byproduct Recycling: Fats, Oils and Grease
2 Points
INTENT
Facilitate the reduction of waste generated by tenant space occupants that is hauled to and disposed of in landfills.
REQUIREMENTS
Tenant would install and maintain used cooking oil/liquid grease collection equipment and participate in a grease recycling program. Tenants are solely responsible for all costs associated with the interception, collection and appropriate disposal of fats, oils and grease generated by their operations on the premise.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the type, amount and process/company used to convert the fats, oils and grease.
TECHNOLOGY/STRATEGY
With the implementation of increased security at airports, passengers are spending an increased amount of time at the airport and in turn creating more waste. In conjunction with the Airport, tenants should commit to reducing the amount of waste that eventually arrives at the landfills.
New technological advances are now allowing items that previously used to be discarded to now be re-purposed. A prime example is grease from concessionaires and flight kitchens that can be converted into biofuels than can be used by the company or sold to other parties.
Standard Practice
None
Recommended
Collect the used fats, oils and grease and sell to a third part as a commodity
Best Available
None
CT-213
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Grease Trappings Portland International Airport – Portland, Oregon
Airport restaurants are collecting the used cooking oil and grease, 20,000 gallons in 2008, and it is being converted into biodiesel and base products for other industries.
www.flypdx.com/PDFPOP/Pub_Portside_Summer_08.pdf
CT-214
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.7 Surplus Food Sent to Local Organizations
2 Points
INTENT
Increase tenant’s social responsibility by donating surplus food to local hunger relief organizations.
REQUIREMENTS
Unused (wrapped and packaged) food that would otherwise be discarded should be donated to local food banks. Tenants should follow the organization’s guidelines as to the storage, preparation and donation of food.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the amount of unused food that was donated and to which organizations.
TECHNOLOGY/STRATEGY
Efforts need to be undertaken to ensure that waste generated at airports does not all ultimately end up in area landfills. Food scraps and unused food account for a large portion of an airport’s waste stream. Creative waste solutions to minimize contributions to airports are needed, especially for perishable foods.
Tenant should donate unused food products to a local food bank, shelter, etc. The Good Samaritan Food Donation Act offers protection to citizens, businesses and nonprofit organization that proceed in good faith to donate, recover and distribute excess food. It promotes food recovery by limiting liability to acts of gross negligence or intentional misconduct (such as donating food from which others have already become ill) and absent these, donors and others shall not be subject to civil or criminal liability arising from the nature, age, packaging or condition of apparently wholesome food or apparently fit grocery products received as donations.
Standard Practice
None
Recommended Practice
Donate surplus food to a local organization. Below is a sample list of representative organizations but not limited to:
o Feeding America (http://feedingamerica.org/) o Food Donation Connection (www.foodtodonate.com) o Greater Chicago Food Depository (www.chicagosfoodbank.org)
CT-215
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Food Donation Program Seattle – Tacoma Airport – Seattle, Washington
In 2006, Sea-Tac began a food donation program, facilitating food-service concession’s donation of unsold food to local food banks. Donated food is deposited nightly into designated airport coolers, which are check each morning by the food bank. More than 30,000 pounds of food have been donated to local food banks since the program’s inception.
www.recyclescene.com/how-to-recycle/programs-in-action/sea-tac-airport-recycling
CT-216
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.8 Deplaned Waste
1 to 5 Points
INTENT
Facilitate the reduction of waste generated from aircraft that are hauled to and disposed of in landfills.
REQUIREMENTS
Up to 5 points may be awarded by achieving any of the following measures locally:
Technology/Strategy Points
Recycling of Glass, Aluminum, Mixed Paper, Plastics 1
Recycling of Food Waste (including coffee grounds) 1
Repurposing of Goods (including magazines, newspapers, pillows, blankets)
1
Donation of Surplus Food to Local Organizations 2
These points are in addition to points earned in SAM Credits 13.6 Organic Byproduct Recycling and 13.7 Surplus Food Sent to Local Organizations. While the tenant may undertake the above Technologies/Strategies at other airports, for the purposes of this credit activities only apply to operations at CDA Airports.
SUBMITTALS
Include descriptive narrative on the SAM Checklist.
TECHNOLOGY/STRATEGY
Even with an airport-wide recycling program in place, there is the challenge of capturing recyclables from aircraft at the airport. Waste collection is the responsibility of the flight attendants, airline cleaning crew and flight kitchens but it is often a secondary concern to their other duties. Typically there is only limited time to clean the aircraft during turn-arounds and limited space for collection in-flight. A conscious effort by the airline must be taken for an aircraft recycling program to be a success.
CT-217
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Due to the limited amount of time that can be devoted to deplaned waste, the tenant should first identify the types of materials that will be collected. Some examples include, but are not limited to:
Glass bottles Aluminum cans Plastic cups Plastic bottles Paper/newspaper/magazines Pillows Blankets Coffee grounds Surplus meals/snacks
It is best to use a single stream process to minimize the amount of time flight attendants will spend executing the program. By collecting all recyclables and storing them apart from waste that will be sent to the landfill, it allows for service crews to separate the recycled deplaned waste once it is unloaded from the aircraft.
CASE STUDIES
In-Flight Recycling Delta Airlines
Early attempts by Delta to recycle on flights had failed because, among other reasons, the flight attendants were not convinced that the material they collected was actually being recycled on the ground. To educate the flight attendants and assure them that their efforts were worthwhile, Delta created materials to show the recycling process and the goals of the program. They also developed a set of activities to support “continuous education.” Continuous education is provided by materials displayed in flight attendant lounges, as well as through online newsletters and posters with monthly recycling statistics displayed in the break rooms.
In 2009, Delta’s In-Flight Recycling program diverted over 2 million pounds (1,000 tons) of aluminum, mixed paper and plastic from domestic flights serving 29 cities. Delta continues to recycle an average of 1 million individual aluminum cans each month. In-Flight Recycling has fully funded the building of two Habitat for Humanity Homes (Atlanta in 2008 and Cincinnati in 2009) and will have a similar opportunities in 2010.
www.delta.com/about_delta/global_good/environment/index.jsp
CT-218
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
PDX Periodicals Reuse for Education Program Portland International Airport – Portland, Oregon
As part of the PDX Periodicals Reuse for Education Program initiated in 2004, schools receive packages of periodicals during the school year which may include magazines from international flights.
http://www.portofportland.com/PDFPOP/Env_AnnualRpt_2005.pdf
Airline Pillow Recycling Oakland International Airport – Oakland, California
Oakland International Airport is one of the first airports in the nation to participate in a pillow recycling program. Instead of being discarded, the pillows are used as insulation or as material in making furniture.
www.airports.org/aci/aci/file/ACI_Priorities/Environment/TRACKER%20FILE_Airport%20environment%20initiatives.pdf
CT-219
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.9 Repurposing of Goods
2 Points
INTENT
Promote the reuse of materials, equipment and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
REQUIREMENTS
Whenever possible, identify items that can be donated, salvaged, refurbished or reused by a third party. This credit can also be achieved by utilizing donated, salvaged, refurbished or used items from an outside party.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the types of products that were donated and to whom.
TECHNOLOGY/STRATEGY
Salvage and donation are important waste prevention strategies, since they reduce the need for the purchase and manufacture of new products and help keep materials out of landfills. Identify opportunities to incorporate salvaged materials into daily operations. Consider salvaged materials such as cabinetry and furniture, pumps, motors, electrical panels, fixtures and tanks.
The tenant may also identify items that can be sold or donated to other users. Consider items such as appliances, carpet, shelving, displays, non-perishable inventory
Standard Practice
None
Recommended Practice
Tenants should identify items for reuse and donate the goods:
Egg cartons, strawberry baskets, poster board, and other materials can be sent to schools or daycare centers for use in arts and crafts activities
Collect magazines, newspapers, and books from international passengers and donate them to local educational facilities that teach foreign languages, senior centers, and/or united service organizations
Guest hangers no longer suitable for use can be repurposed to local dry cleaners Linens, towels, blankets, soap, shampoo, uniforms, and used furniture can be donated
to a local shelter
CT-220
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Flowers that were used for banquets and celebrations can be sent to a local hospice or hospital
Best Available Practice
None
CASE STUDIES
Donation of Unused Materials Ben & Jerry’s Ice Cream
Plastic tubs/buckets and popsicle sticks are donated to school groups for use in crafts and gardening, and to greenhouses, where popsicle sticks serve as plant markers.
www.mwcog.org/environment/recycling/hotel/mentor/BEN.HTM
PDX Periodicals Reuse for Education Program Portland International Airport – Portland, Oregon
As part of the PDX Periodicals Reuse for Education Program initiated in 2004, schools receive packages of periodicals during the school year which may include magazines from international flights.
http://www.portofportland.com/PDFPOP/Env_AnnualRpt_2005.pdf
CT-221
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.10.1 Reduction of Plastic Waste: Plastic Bottles
2 Points
INTENT
Reduce the amount of plastic that is sold and ultimately disposed within the terminals.
REQUIREMENTS
Tenants should implement the use of reusable mugs, containers or organic material bottles in place of plastic bottles to reduce the amount of waste generated.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the type of containers being sold in place of plastic bottles.
TECHNOLOGY/STRATEGY
At various concessionaire locations there is usually an abundance of plastic bottles being sold, primarily once passengers have cleared the security checkpoints. In an attempt to reduce the amount of plastic bottles that are not recycled by passengers, vendors can offer the sale of beverages in reusable containers or bottles that are made of organic materials.
Standard Practice
None
Recommended Practice
Offer the sale of beverages in reusable containers
Best Available Practice
Various options are available which are made from organic materials in place of plastic. These organic bottles look and feel similar to traditional plastic water bottles but offer a more environmentally friendly option.
CT-222
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.10.2 Reduction of Plastic Waste: Elimination of Petroleum Based Plastic Bags
1 Point
INTENT
Reduce the amount of plastic that are sold and ultimately disposed within the terminals.
REQUIREMENTS
Vendor will do away with the use of petroleum based plastic bags in favor of bags that are more environmentally friendly.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the alternate option given to customers in place of petroleum based plastic bags.
TECHNOLOGY/STRATEGY
Due to the negative environmental effects there have been international movements to discourage the use of petroleum based plastic bags. Plastic bags use up natural resources, consume energy to manufacture, create litter, choke marine life and add to landfill waste.
Standard Practice
Ask the customer if they require a bag instead of automatically giving bags to every customer
Recommended Practice
Implement the use of post-consumer recycled paper bags or reusable bags
Best Available Practice
Offer the use of biodegradable plastic bags
CT-223
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Plastic Shopping Bag Ban San Francisco, California
In 2007 San Francisco’s Board of Supervisors voted to become the first in the United States to prohibit petroleum based plastic checkout bags in large markets and pharmacies. The ban still allows for the use of biodegradable plastic and recycled paper and is aimed to reduce the volume of bags given away by supermarkets. The “supermarket ban” prevented an estimated 100 million plastic bags from ending up in the area landfills. In 2010 San Francisco the city expanded the ban to now include all retailers, from small businesses, retailers and corner stores from using petroleum based plastic bags.
www.treehugger.com/files/2007/03/san_francisco_t_1.php
CT-224
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
13.0 WASTE STREAM MANAGEMENT
13.10.3 Reduction of Plastic Waste: Biodegradable Trash Bags
1 Point
INTENT
Reduce the amount of plastic that are sold and ultimately disposed within the terminals.
REQUIREMENTS
Tenants should use only biodegradable trash bags that once at a landfill break down at a faster rate than traditional trash bags.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing type of biodegradable trash bag used.
TECHNOLOGY/STRATEGY
Even given other initiatives to reduce the amount of waste, there inevitably will be waste generated that ends up in the area landfills. The combination of reducing the amount of waste sent to landfills and using trash bags that break down in the landfills will help decrease the massive amounts of garbage that are created.
The process behind the biodegradation occurs in two parts. First the plastic is oxidized, then microorganisms consume the plastic leaving behind "refuse" which is a reusable biomass which is both environmentally friendly and does not contain harmful toxins. All products then biodegrade and find their way into the waterways and the soil.
Biodegradable bags can be purchased at prices similar to the traditional trash bags used by many. However not all biodegradable bags break down in landfill conditions; some bags require oxygen to decompose.
Plastics are certified as biodegradable if they comply with ASTM D6954.
Standard Practice
None
Recommended Practice
o Eliminate the use of traditional plastic bags. Biodegradable bags will break down into CO2 and water when it is exposed to UV light, moisture, heat and microorganisms
Best Available Practice
None
CT-225
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.1 Heat Island Reduction
1 point
INTENT
Minimize impacts of the existing roofs and pavements that cause the heat island effect (thermal gradient differences between developed and underdeveloped areas).
REQUIREMENTS
Use any combination of the following strategies:
Convert 50% of the site’s hardscape area (including roads, sidewalks, courtyards, and parking lots)
o Provide shade through an existing tree canopy or within five (5) years of landscape installation - landscaping (trees) must be in place at the time of review
o Have paving materials with a Solar Reflective Index (SRI) of at least 29 and implement a maintenance program that ensures these surfaces are cleaned at least every two years to maintain good reflectance and minimums
o Have an open-grid pavement system (that consists of at least 50 percent open area)
AND/OR
Convert 50% of the roof area using roofing materials that have one of the following characteristics
o Use roofing materials having a Solar Reflectance Index (SRI) equal to or greater than the values in the table below for a minimum of 75% of the roof area. Implement a maintenance program that ensures all SRI surfaces are cleaned at least every two years to maintain good reflectance.
Roof Type SRI
Low-Sloped Roof 78
Steep-Sloped Roof 29
o Vegetated green roof
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist.
CT-226
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Employ strategies, materials and landscaping techniques that reduce heat absorption of exterior materials. Use shade (calculated at 10 a.m., 12 noon, and 3 p.m. on the summer solstice [June 21] that will be used as the effective shaded area) from native or adapted trees and large shrubs, vegetated trellises or other exterior structures supporting vegetation. Consider the use of new coatings and integral colorants for asphalt to achieve light-colored surfaces instead of blacktop. Position photovoltaic cells to shade impervious surfaces.
Consider installing high-albedo roofs to reduce heat absorption. SRI is calculated according to ASTM E 1980. Reflectance is measured according to ASTM E 903, ASTM E 1918 or ASTM C 1549. Emittance is measured according to ASTM E 408 or ASTM C 1371. Product information is available from the Cool Roof Rating Council website, at www.coolroofs.org. Also, visit the ENERGY STAR website, www.energystar.gov, to research compliant products.
Unless the reflectance is determined directly through in-situ testing, the following default SRI values are to be used:
MATERIAL SRI
New Conventional “gray” concrete 35
Old (weathered) “gray” concrete 19
New “white” concrete 86
Old (weathered) “white” concrete 45
New Asphalt 0
Old Asphalt 6
Standard Practice
White roofs are currently the standard for new construction on airport property. These are acceptable; however, SRI decreases with the age of the roof. Unless a cleaning program is in place, the benefits of white roofs diminish over time. For this reason, along with the benefits of stormwater management, the construction of vegetated green roofs is encouraged.
Recommended Practice
Maximize light colored/high albedo pavement, such as Portland Concrete Cement (PCC), for roadways, parking lots, sidewalks and plaza areas. Reflectance must be a minimum of 0.3 (‘White’ portland cement – 0.7 to 0.8, typical PCC – 0.35 to 0.5, typical asphalt pavement – 0.05 (new) to 0.15 (over 5 years)). On an annual basis, test the pervious areas to verify the SRI standard is met as well as to depict improvement.
Install a vegetated green roof
CT-227
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Evaluate and utilize an ENERGY STAR compliant roofing system, such as aluminum coating and light-colored coatings. Thermoplastic and white Poly(vinyl chloride) (PVC) roofing systems meet these standards.
Best Available Practice
Install trees consistent with CDA/OMP Specification 02905 – Sustainable Airport Landscaping, and for any proposed plant species not listed, consult an FAA certified airport biologist to ensure the plants will not attract wildlife.
Implement a creative combination of the above strategies to reach this goal. For example, a task/project can provide five (5) percent shading of dark colored impervious surfaces and 25 percent light colored/high albedo pavement to achieve this goal.
Install open grid pavement for surface lots and site pavement Install light-colored permeable pavers and concrete Install “green walls” for building façade
CASE STUDY
FedEx Cargo Facility Green Roof O’Hare International Airport – Chicago, IL
The new FedEx Cargo Facility green roof at the O'Hare International Airport in Chicago is the largest free-standing building vegetated roof in the central United States at 170,000 square feet. This project required utilization and coordination of an uplift-resistant and rapidly executed green roof design due to the active runway status of the O'Hare facility.
www.greenroofs.com/projects/pview.php?id=1166
CT-228
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.2 Stormwater Management
4 points
INTENT
Limit disruption of natural water hydrology by reducing impervious cover, increasing on-site infiltration, reducing or eliminating pollution from stormwater runoff, and eliminating contaminants by enhancing the current operating system.
REQUIREMENTS
Reduce impervious surfaces totaling at least 5% of your total site area by converting to permeable surfaces. Those surfaces can include, but are not limited to:
Permeable asphalt / concrete Permeable pavers Aggregate materials Turf or landscaped areas
OR
Nonstructural techniques such as, but not limited to:
Rain gardens Vegetated swales Disconnection of imperviousness Rainwater recycling
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist. Up to 4 points can be achieved by accomplishing the strategies above in a significant manner.
TECHNOLOGY/STRATEGY
Maintain natural stormwater flows by promoting infiltration. Maintain procedures that include ongoing monitoring of any installed features that assist in stormwater irrigation, pervious paving, and other measures to minimize impervious surfaces. Any strategies used should discourage wildlife habitat. Reuse stormwater volumes generated for non-potable uses such as landscape irrigation, vehicle washing or building exterior washing.
CT-229
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
Follow Chicago Department of Aviation’s Best Management Practices.
Recommended Practice
Install rain gardens, vegetated swales, disconnection of imperviousness, and rainwater recycling
Evaluate curb breaks and drainage ditches, and/or bioswales Install landscape to reduce runoff (See SAM Credit 14.3.1 Landscape Management:
CDA Standards) Install cisterns or rain barrels
Best Available Practice
Encourage use of permeable pavement, where applicable
Where potential for contamination exists, the use of these technologies must be weighed carefully to prevent larger contaminant issues, such as infiltration of ground water
CT-230
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.3.1 Landscape Management: CDA Specifications
1 point
INTENT
Preserve ecological integrity, enhance natural diversity and aesthetics, while supporting high-performance spaces and integration into the surrounding landscape.
REQUIREMENTS
Currently follow the requirements of the CDA 02905 “Sustainable Airport Landscaping” specifications.
AND
Reuse or compost landscape waste, as applicable.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Maintain landscape that is aesthetically pleasing and at the same time, low maintenance, ecologically and financially sustainable yet does not compromise airport security and aircraft safety. Over the performance period, have in place a low-impact plan that addresses overall site management, chemicals, fertilizers, and landscape waste. Include such green landscape management practices such as, but not limited to:
Providing proper training methods to current employees Discouraging wildlife habitat Removing or not installing invasive plants Using drought tolerant plants
Standard Practice
None
CT-231
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Avoid clustering shrubs and trees Avoid fruit and palatable seed producing plants Use native and low maintenance plants with special consideration for vegetated green
roofs Minimize use of high maintenance grass areas, lawns and annual plants Establish areas of high and low landscape maintenance areas. Group plants with similar
water-use needs by determining which areas of the site should receive a higher level of care than others and, during drought periods, more irrigation. Coordinate these areas with the irrigation plan in SAM Credit 14.3.5 Landscape Management: Irrigation.
Do not apply chemicals within 25-feet (at a minimum) of a body of water
Best Available Practice
Conduct soil testing as necessary to determine the amount of nutrients needed for a healthy landscape
CT-232
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.3.2 Landscape Management: Landscape Equipment
1 point
INTENT
Preserve ecological integrity, enhance natural diversity and aesthetics, while supporting high-performance spaces and integration into the surrounding landscape.
REQUIREMENTS
Use non-gasoline powered landscape equipment.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
By eliminating the use of gasoline or other fossil fuels, the tenant is able to reduce the air pollution impacts and greenhouse gas emissions. Depending on the technology, noise pollution can also be reduced.
Standard Practice
None
Recommended Practice
Use electric mulching and/or electric mowers
Best Available Practice
Use solar or propane powered mowers
CT-233
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.3.3 Landscape Management: Fertilizer Use
1 point
INTENT
Preserve ecological integrity; enhance natural diversity and aesthetics, while supporting high-performance spaces and integration into the surrounding landscape.
REQUIREMENTS
Ban the use of phosphorus fertilizers.
AND
Use non–synthetic fertilizer only as needed for establishment of new vegetation. For established vegetation, minimize use of fertilizer to only those cases where absolutely necessary.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Due to the over usage and nature of phosphates in synthetic fertilizers and detergents, increasing amounts have been entering into waterways. In an effort to reduce the degradation of local waterways, phosphorus use should be banned.
For established vegetation, fertilizer use should be eliminated. However, if the soil lacks the nutrients to produce healthy vegetation, the tenant may need to supplement the nutrients with the appropriate non-synthetic fertilizer, only as needed.
Standard Practice
None
Recommended Practice
Conduct soil testing as necessary to determine the amount of nutrients needed for a healthy landscape
Use organic and natural products such as, but not limited to: o Grass clippings/mulch o Compost o Coffee grounds o Commercial organic fertilizers o Seaweed o Animal manure
CT-234
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Use non-potable hot water for weed control to eliminate vegetation in pavement cracks in place of herbicides
Do not apply pesticides or fertilizers before an expected rainfall (unless specified within the manufactures recommendations)
Do not apply chemicals within 25-feet (at a minimum) of a body of water
Best Available Practice
Eliminate fertilizer and herbicide use altogether
CT-235
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.3.4 Landscape Management: Landscape Waste
1 point
INTENT
Preserve ecological integrity, enhance natural diversity and aesthetics, while supporting high-performance spaces and integration into the surrounding landscape.
REQUIREMENTS
Reuse or compost all landscape waste on-site.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Over the performance period, prevent the removal of landscape waste from the airport to off-site (off-airport) disposal locations. Use mulching and composting to provide material for other landscape uses within the tenant space.
Any onsite composting of landscape waste must address wildlife concerns and not promote wildlife activity.
Standard Practice
None
Recommended Practice
Utilize mulching mowers to significantly reduce landscape waste generation, fertilizer needs, and water consumption through retention of organic matter
Best Available Practice
Establish a centralized landscaping composting facility Use compost for tenant landscaping needs
CT-236
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.3.5 Landscape Management: Irrigation
1 to 3 points
INTENT
Preserve ecological integrity, enhance natural diversity and aesthetics, while supporting high-performance spaces and integration into the surrounding landscape.
REQUIREMENTS
Reduce potable water or other natural surface or subsurface resource consumption for irrigation compared with current conventional means. If the building does not have separate water metering for irrigation systems, the water-use reduction achievements can be demonstrated through calculations.
Up to 3 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Irrigation controls (e.g., soil moisture sensors, weather data-based controller)
1
Rain water harvesting and graywater (e.g., rain barrels and cisterns)
2
No irrigation (through plant selection/landscape xeriscaping) 3
Potable water: Water suitable for drinking that meets or exceeds EPA drinking water standards; it is supplied from wells or municipal water systems.
SUBMITTALS
Include descriptive narrative in the SAM Checklist.
TECHNOLOGY/STRATEGY
Specify water-efficient, climate-tolerant native or adapted plantings. Implement or maintain high-efficiency irrigation technologies, such as micro-irrigation, moisture sensors, or weather data-based controllers. Feed irrigation systems with captured rainwater, graywater (on-site or municipal), municipally reclaimed water, or on-site treated wastewater. Consider not operating an irrigation system. Consider use of xeriscaping principles in arid climates.
CT-237
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
No irrigation system Drought tolerant plants Utilize vegetation which may be acceptable for site use (native and/or low-maintenance),
with special consideration for vegetated green roofs Minimized use of high maintenance grass areas, lawns and annual plants Established areas of high and low landscape maintenance areas. Group plants with
similar water-use needs by determining which areas of the site should receive a higher level of care than others and, during drought periods, more irrigation. Higher maintenance areas should be located around the major building entries and high traffic areas. Lower maintenance areas should be located on low traffic areas, buffer zones and service areas.
Best Available Practice
Have a soil and climate analysis to determine the appropriate landscape strategy Evaluation of stormwater and/or graywater cisterns for capturing rainwater from all new
roofs for irrigation If irrigation system is installed, a soil moisture monitoring system is present to reduce
reliance on manual control and timed devices, as well as for detecting leaks Have incorporated the use of recycled and treated wastewater for the use of irrigation
CT-238
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.4 Rainwater Harvesting
2-12 Points
INTENT
Further increase water efficiency within tenant space to reduce the burden on municipal water supply and wastewater systems.
REQUIREMENTS
Tenant should collect rainwater and implement a harvesting system with intended use(s) for the rainwater.
Between 2-12 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Meter and log your rainwater harvesting system 1
Use harvested rainwater for any portion of your total irrigation needs
2
Use harvested rainwater for a significant portion or all of your irrigation needs
3
Use harvested rainwater in place of other potable water uses, such as, but not limited to flushing of water closets and urinals, exterior building cleaning, and vehicle washing
6
Potable water: Water suitable for drinking that meets or exceeds EPA drinking water standards; it is supplied from wells or municipal water systems.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the system used.
TECHNOLOGY/STRATEGY
Rainwater harvesting systems can vary in complexity and sophistication, but in every system must utilize some basic common elements. A catchment area will intercept the rainfall and a barrel, cistern or other vessel will store the collected rainwater.
Rooftops provide an ideal environment for the catchment and a downspout running can be used for conveyance between the catchment area and the cistern.
Water collected from rain harvesting can be used to irrigate landscaping, in the cleaning of building exteriors and for vehicle washing.
CT-239
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
Use rainwater collected to irrigate landscaping or wash down building exteriors
Best Available Practice
Make use of the collected rainwater by incorporating into vehicle washing or flushing water closets and urinals
CASE STUDY
Consolidated Rental Car Facility Nashville International Airport – Nashville, Tennessee
A new Consolidated Rental Car Facility expected to be completed in November 2011 will feature housing for rental cars, “quick turnaround” facility providing refueling and car was services, and covered access to the terminal. The facility will incorporate sustainable features including the use of recycled water for washing rental cars.
http://www.nashintl.com/renovation/pdfs/CONRAC2010-ConstructionAreaL.pdf
CT-240
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.5 Water Efficient Vehicle Washing
1 to 8 Points
INTENT
Limit or eliminate the use of potable water or other natural surface or subsurface resources available on or near the project site for vehicle washing.
REQUIREMENTS
Up to 8 points may be awarded by achieving any of the following measures:
Technology/Strategy Points
Install low volume, high pressure sprayer nozzles on water hoses
1
Log vehicle washing and meter vehicle wash systems separately to measure water
1
Recycle more than 50% of wash water during vehicle washing 3
Recycle all wash water during vehicle washing 3
Potable water: Water suitable for drinking that meets or exceeds EPA drinking water standards; it is supplied from wells or municipal water systems.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the system in place to reuse the water.
TECHNOLOGY/STRATEGY
Reduce potable water or other natural surface or subsurface resource consumption for vehicle washing compared with current conventional means. If the tenant does not have separate water metering for vehicle washing systems, the water-use reduction achievements can be demonstrated through calculations.
Tenants are encouraged to implement systems where water is recycled on-site or sent to water treatment facility where it is treated and sent back to the tenant’s facility. Tenant, through a reclaim system, can collect and reuse water from carwash operations.
CT-241
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Standard Practice
None
Recommended Practice
Low volume, high pressure sprayer nozzles on water hoses Keep a log of vehicle washing water use Capture wash water for re-use (cistern) Practice indoor vehicle washing
Best Available Practice
Treat wash water for re-use
CT-242
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.6 Clean Fuel Vehicles
1 to 4 Points
INTENT
Reduce emissions from airport vehicles to improve the local air quality. For the installation of alternative fuel infrastructure see SAM Credit 14.7.
REQUIREMENTS
As part of their day-to-day business operations, tenant should operate clean fuel vehicles in place of gas powered vehicles used to support the business (not personal vehicles). Points will be awarded as follows:
SAM Credit Percentage of Fleet Points
14.6.1 30% 1
14.6.2 60% 2
14.6.3 90% 3
14.6.4 100% 4
Clean fuel vehicles include electric, compressed natural gas (CNG), biodiesel (B20 and higher), propane, hybrid (fuel/electric),etc. Flex fuel and E-85 fueled vehicles do not qualify for this credit.
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the clean fuel vehicles used.
TECHNOLOGY/STRATEGY
Airport-related activities result in the emission of a host of air pollutants that adversely affect public health and the environment. While emissions from the largest source pollutant, aircraft, are declining due to the implementation of stringent regulations, emissions from other airport sources, still contribute to the total air pollution burden associated with airports.
Standard Practice
None
Recommended Practice
Tenants are encouraged to identify and incorporate any other measures that may assist in reducing air quality emissions. For example, many clean vehicle options now exist including, electric, compressed natural gas (CNG), hybrid (fuel/electric), etc.
CT-243
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Best Available Practice
None
CASE STUDY
Compressed Natural Gas Vehicles Baltimore – Washington International Airport – Baltimore, Maryland
Currently, low-floor 40 ft. Neoplan, buses operate daily, ferrying passengers from the airport terminal to the consolidated rental car facility. The airport reports that the buses have operated successfully with no major CNG-fuel related problems and with a good reception by the public. As of 2006, the total project expenditure of $1.125 million represents the incremental costs for the CNG buses ($45,000 per vehicle).
www.faa.gov/airports/environmental/vale/media/ileav_report_final_2005.pdf
CT-244
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.7 Alternative Fuel Infrastructure
3 to 6 Points
INTENT
Reduce emissions from airport vehicles to improve the local air quality.
REQUIREMENTS
Tenant should provide infrastructure to power alternative fuel vehicles used in place of gasoline powered vehicles. The infrastructure should be available for employees’ personal vehicles used for commuting and/or vehicles used for day-to-day business operations.
Infrastructure includes electric vehicle charging stations, or access to other alternative fuels, including but not limited to propane, CNG, etc. Points will be awarded as follows:
Technology/Strategy Points
Provide infrastructure for use by employees for personal vehicles
3
Provide infrastructure for business vehicles
3
SUBMITTALS
Include descriptive narrative on SAM Checklist detailing the infrastructure provided.
TECHNOLOGY/STRATEGY
Increasing oil prices, depletion of natural resources, and the accumulation of greenhouse gas emissions have led individuals to look into alternative means of fueling vehicles. As alternative fuels become more prevalent, it is important to provide alternative fueling stations delivering fueling options to the consumer.
With the popularity of alternative fuel vehicles, especially CNG powered taxis and buses, an airport environment provides an ideal location for fueling infrastructure due to the large number of vehicles accessing the site. Although CNG and electric are two common alternatives, others such as biofuels, LPG, hydrogen, etc. should also be encouraged to help drive the market where feasible. Fleet vehicles which are prevalent at airports are well suited to providing at least a startup market for these alternative fuels.
Standard Practice
None
CT-245
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Tenants are encouraged to provide infrastructure to power alternative fuel vehicles used in place of gasoline powered vehicles.
Best Available Practice
None
CT-246
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
14.0 VENUE SPECIFIC CONSIDERATIONS
14.8 Green Restaurant Certification
5 Points
INTENT
Encourage the green efforts of concessions and tenants.
REQUIREMENTS
Acquire certification from the Green Restaurant Association.
SUBMITTALS
Include documentation from the Green Restaurant Association on tenant’s certification.
TECHNOLOGY/STRATEGY
In order to attain certification tenants must undertake an assessment by the Green Restaurant Association and meet minimum points in each category. Each year the Certified Green Restaurant™ is expected to increase their point value by 10 points from the following year to demonstrate their commitment.
Categories of examination include:
Water Efficiency Waste Reduction and Recycling Sustainable Furnishings and Materials Sustainable Food Energy Disposables Chemical and Pollution Reduction
In order to qualify as a Certified Green Restaurant™ tenants must also:
Have a full-scale recycling program Prohibit the use of Polystyrene Foam (aka Styrofoam) Undergo Yearly Education
Depending on the number of points met, a restaurant can qualify for 2 to 4 stars.
Standard Practice
None
CT-247
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Recommended Practice
Undergo Green Restaurant Association’s assessment and achieve certification
Best Available Practice
None
CASE STUDY
Certified Green Restaurant Frontera Grill and Tolpolobampo – Chicago, Illinois
Both restaurants were recognized for their efforts to reduce waste, energy and water use, improve recycling, and support organic farming. A 3 star rating was given to each restaurant after they accumulated 175 points on the rating scale.
www.rickbayless.com/news/view?articleID=141
CT-248
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
15.0 INNOVATION FOR CONCESSIONS & TENANTS – Operations & Maintenance
15.1 – 15.3 Innovation for Concessions & Tenants
1 to 3 Points
INTENT
Provide tenants the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
REQUIREMENTS
In writing, identify the intent of the proposed innovation credit, the proposed requirement for compliance, and the proposed submittals to demonstrate compliance, and the approach (strategies) that might be used to meet the requirements.
Up to three points are available for this credit:
SAM Credit Points
15.1 1
15.2 1
15.3 1
SUBMITTALS
Include descriptive narrative in the SAM Checklist following the criteria in the Requirements section above.
TECHNOLOGY/STRATEGY
Substantially exceed a SAM performance credit such as energy performance or water efficiency and/or apply strategies or measures that demonstrate a comprehensive approach and quantifiable environment and/or health benefits.
Refer to LEED Credit Interpretation Results (CIRs) or the Innovation in the LEED Design Credit Catalog5 for potential strategies that may be considered for innovation. The SRP will review proposed innovations by the concessionaire or tenant on a case by case basis.
5 Available at www.usgbc.org.
CT-249
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
15.0 INNOVATION FOR CONCESSIONS & TENANTS
15.4 Community/Cultural Responsibility
1 to 3 Points
INTENT
Promote specific social and cultural initiatives considered to be important to the sustainability of the airport environment and surrounding community.
REQUIREMENTS
A point will be awarded for each of the initiatives listed below that are promoted and organized by the tenant up to a maximum of 3 points:
Industry Award – Tenant has received an industry award for their sustainability initiatives.
Green Certification – Tenant has achieved a green certification from an industry organization, e.g. Green Restaurant Association, SAM Green Airplane Rating, LEED certified project, ISO 14001, etc.
Employee Wellness Program – Have in place a program that encourages good health. Programs that maintain good health include but are not limited to health club memberships, incentivized programs for weight loss or to quit smoking, access to yoga, meditation, tai chi, zen gardens, bicycles for employees at work, etc.
Employee Training and Education Programs – Have in place programs that promote employee opportunities for any type of continued education.
Carpooling Incentives – Provide incentives to employees for carpooling. Community Outreach and Volunteerism Programs Cultural Programs – Promote and organize programs that display or present local art,
performers, and culture and make accessible to the travelling public and/or airport community regarding culture, art, community connectivity, etc.
Other Community/Cultural Programs
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist. Indicate in the narrative which of the above technologies and strategies are being included in the project and, where applicable, indicate where these items are shown in the drawings or specifications.
TECHNOLOGY/STRATEGY
Organize and implement initiatives or programs not listed above that have a social or cultural impact on the travelling public, employees, and/or surrounding communities.
CT-250
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
CASE STUDY
Outreach & Involvement Alaska Airlines In addition to their corporate giving programs, Alaska Airlines and Horizon Air encourage their employees to be involved in their communities and offer multiple programs. Under the Dollars for Doers program, employees are acknowledged for their hard work for making a difference in the communities they serve. Employees are given $10 for every hour they volunteer (up to $1,000 per year) to be donated to the organization for which they volunteer. In addition, their Matching Gift Program, Alaska and Horizon will match their employees contributions to nonprofit institutions or organizations which meet their corporate giving guidelines. http://www.alaskaair.com/content/about-us/social-responsibility/outreach-and-involvement.aspx Plane Pull HMS Host – Chicago, Illinois
In September 2012, HMS Host competed in and helped sponsor the 4th Annual Law Enforcement Torch Run Plane Pull, to benefit the Special Olympics of Illinois. The contest featured 34 teams of up to 20 members playing tug of war with a UPS A300 aircraft (weighing more than 190,000 lbs.). This fun and competitive event raised both money and awareness for the Special Olympics of Illinois and their sports training and competition programs.
CT-251
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
15.0 INNOVATION FOR CONCESSIONS & TENANTS
15.5 Menu Items (Green Walls, Alternative Water Heating, Advanced Wastewater Treatment, Kinetic Energy Systems/Power Regeneration, Waste-to-Energy Systems, Net Zero Energy/Water/Waste, Biological Systems, or Exemplary Performance)
1 to 3 Points
INTENT
Promote specific technologies and strategies considered to be important to the sustainability of the airport environment.
REQUIREMENTS
A point will be awarded for each of the strategies or technologies listed below that are utilized by the tenant up to a maximum of 3 points:
Green Walls – Use green, vegetated wall systems, interior or exterior, if applicable. Green walls used for interior spaces must be designed for the improvement of indoor air quality as well as aesthetics.
Alternative Water Heating – Use demand, tankless, instantaneous or solar water heating technology
Advanced Wastewater Treatment – Utilize on-site wastewater treatment systems to treat sanitary sewage waste. Treated waste may be reused for irrigation, process water, or toilet flushing in accordance with relevant regulations and technologies.
Kinetic Energy Systems/Power Regeneration Systems – Use kinetic energy systems for the generation of electricity. Point is achieved for any system that converts a portion of electricity from kinetic or mechanical energy.
Waste to Energy Systems – Use solid or liquid wastes to generate electricity. Examples may include but are not limited to anaerobic digestion, refuse derived fuel for power generation, methane capture, etc.
Net Zero Programs, such as energy use, waste reduction, etc. Biological systems, such as the use of vermiculture (worms), raising bees for honey,
algae for fuel, etc. Exemplary Performance – Significantly exceed the requirements of any credit. Other
SUBMITTALS
Include descriptive narrative and calculations in the SAM Checklist. Indicate in the narrative which of the above technologies and strategies are being included in the project and, where applicable, indicate where these items are shown in the drawings or specifications.
CT-252
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
TECHNOLOGY/STRATEGY
Organize and implement initiatives or programs not listed above that have a social or cultural impact on the travelling public, employees, and/or surrounding communities.
Green Walls – Vegetated green wall systems can result in significant air conditioning savings. Vegetated green wall systems on exterior of building envelope can reduce wall surface temperatures by as much as 18°F (depending on which direction it is facing), which also results in significant air conditioning savings, while reducing the heat island effect. In interior applications, green or living walls can help regulate indoor temperatures, humidity, and air quality. Green walls fall into two categories:
o Green facades (outside): Made up of climbing plants growing directly on a wall o Living walls (inside): Modular panels often made of steel containers, geotextiles,
irrigation systems, growing medium and vegetation Alternative Water Heating – Alternative water heating for the purposes of this credit
includes two types of technologies – instantaneous and solar thermal: o Instantaneous hot water heating technology uses include demand,
instantaneous, or tankless water heaters. Demand water heaters heat water directly without the use of a storage tank thus avoiding the standby heat losses associated with conventional storage tank water heaters. When a hot water tap is turned on, cold water is heated directly by a gas burner or an electric element as it passes through the unit. As a result, demand water heaters deliver a constant supply of hot water not limited by the volume of a storage tank.
o Water heating – Solar thermal hot water heating technology uses a solar collector which is simply a heat exchanger designed to convert the sun’s radiant light energy into thermal energy to be stored for later use. This collector uses optics and parabolic concentration technology to heat the fluid media passing through the selectively coated tubing manifold. The fluid media is circulated, via a pump, through the collector and into a storage tank located within the home/building.
Advanced Wastewater Treatment – Onsite wastewater treatment is the collection, treatment and disposal or reuse of wastewater at or near the location in which the waste is generated. Onsite wastewater treatment systems provide preliminary, primary, secondary and tertiary treatment. The methods of treatment can vary but generally accomplish the same task. Systems are designed to be reliable and self-sufficient, however, the labor required to operate the system may be the largest expense. This, of course, is often integrated into standard facilities operation and management. Health, safety, and liability issues must be addressed early in the design process. Costs associated with the installation of these systems are generally offset by decrease in water demand, utility fees, or governmental grants.
CT-253
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
Kinetic Energy/Power Regeneration Systems – This class of systems converts kinetic energy or mechanical energy into electricity. There are a number of systems that accomplish this, the most common application being regenerative braking common in many hybrid vehicles. In this case, braking energy that would normally be lost as heat friction is instead converted to electricity and stored in a battery. Other systems include piezoelectric systems that convert pressure or vibration from, for example, footsteps or vehicle traffic to electricity.
Waste-to-Energy (WTE) Systems – These systems create energy in the form of electricity or heat from the incineration of a waste product. Most WTE systems produce electricity directly through combustion of a waste product, or produce a combustible fuel through the decomposition of a waste product. In the latter case, the typical systems are anaerobic decomposition of organic wastes, such as in landfills or sewage treatment digesters. Other direct combustion waste products may be derived from a nearby manufacturing industry, such as a saw mill (wood waste) or other flammable solid. In either case, the pollutants emitted must be addressed for this system to be effective.
Net Zero Programs – These may include water, energy, or waste. In essence, the loop is closed – there are no inputs or outputs of a given operation for a given stream, be it water, waste, or energy.
o Water reuse is achievable depending on demand and regulatory environment and may employ such technologies as graywater reuse, rainwater harvesting.
o Net zero energy has been proven for buildings where energy demand is produced onsite typically through photovoltaics of wind turbines and through energy conservation techniques.
o Net zero waste systems are more typical of a manufacturing process but there may be potential applications in construction materials for example.
Biological Systems – This category is a catch-all for systems that use living organisms to produce a beneficial commodity. The commodity is considered beneficial if it provides a use that has environmental, financial, or social benefits. This can include apiaries for the production of honey or vermiculture for the disposal of organic wastes.
Exemplary Performance – When achieving a high level of compliance with any of the previous credits, the SRP will evaluate any claims that go significantly above and beyond the requirements of any SAM credit. For example, for SAM Credit 9.5 – Sustainable Food and Consumer Products, the highest threshold achievable is 40%, however if the sustainable food and consumer products of a given tenant exceed 80%, an exemplary performance point may be claimed.
Other innovative technologies can be presented and will be evaluated by the SRP for final approval.
CT-254
Rahm Emanuel Mayor
Rosemarie S. Andolino Commissioner
© 2012 City of Chicago
November 5, 2012
16.0 MONITORING & REPORTING
16.1 Documenting Sustainable Measures
5 Points
INTENT
Track, document, report and promote the CDA’s Green Commitment and encourage tenants airport-wide to join the movement.
REQUIREMENTS
Identify a primary contact person for all sustainability-related tracking and communications.
AND
Complete the SAM Checklist in accordance with chapter guidelines.
SUBMITTALS
Complete the SAM Checklist. Include and submit the completed checklist, and submit any progress reports/annual reports that support this credit.
TECHNOLOGY/STRATEGY
Track operating costs to identify any positive impacts related to the sustainable performance improvements to the building and its operations. At a minimum include water, electricity and waste management data to document operating costs on an ongoing basis. Use this data to optimize consumption and waste from operations and identify potential areas of improvement in future checklist and performance periods.
Standard Practice
None
Recommended Practice
None
Best Available Practice
Document overall operating costs (i.e., water/electricity/recycle) for the previous five years (or length of occupancy, whichever is shorter) and track changes in overall operating costs over the performance period. Document operating costs and financial impacts of all aspects of SAM CT implementation on an ongoing basis.
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
APPENDIX CT-A
GREEN AIRPLANE RATING SYSTEM for
CONCESSIONS & TENANTS
The Sustainable Airport Manual Green Airplane Rating System consists of all the points available for each credit, by project category, for each checklist. The tables show each of the credit categories for the C&T Design & Construction section and the C&T Daily Operations section of the SAM, their titles and available points. The points that can be achieved vary based on each tenant. The total points achieved can be used to determine the SAM Green Airplane Rating.
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
_________
SUSTAINABLE AIRPORT MANUAL GREEN AIRPLANE RATING SYSTEM
____________
Terminal Food
Service Tenant
Terminal Non-Food
Service Tenant
Non-Terminal Tenant
AP Administrative Procedures 8 8 8 8AP.1 Prerequisite 1 Green Meetings Required Required Required RequiredAP.2 Prerequisite 2 Document Reduction and Recycling Initiative (DRRI) Required Required Required RequiredAP.3 Corporate Sustainability Policy 1 1 1 1AP.4 Green Procurement Policy 4 4 4 4
AP.5.1 Recycled Content Paper, 30% 1 1 1 1AP.5.2 Recycled Content Paper, 50% 1 1 1 1AP.5.3 Recycled Content Paper, 100% 1 1 1 1
1.0 Sustainable Sites 1 1 1 11.1 Prerequisite 1 - Adopt CDA Best Management Practices Required Required Required Required1.2 Light Pollution Reduction 1 1 1 12.0 Water Efficiency 6 6 0 62.1 Prerequisite 1 Water Use Reduction Required Required Required
2.2.1 Water Use - Additional Reduction, 30% 2 2 22.2.2 Water Use - Additional Reduction, 35% 2 2 22.2.3 Water Use - Additional Reduction, 40% 2 2 23.0 Energy & Atmosphere 26 7 7 263.1 Prerequisite 1 Fundamental Systems Commissioning Required Required3.2 Prerequisite 2 Minimum Energy Performance Required Required
3.3.1 Optimize Energy Performance, 8% OR Option 2 - Prescriptive Compliance Path (Terminal Tenants) 1 5 5 13.3.2 Optimize Energy Performance, 10% 1 13.3.3 Optimize Energy Performance, 12% 1 13.3.4 Optimize Energy Performance, 14% 1 13.3.5 Optimize Energy Performance, 16% 1 13.3.6 Optimize Energy Performance, 18% 1 13.3.7 Optimize Energy Performance, 20% 1 13.3.8 Optimize Energy Performance, 22% 1 13.3.9 Optimize Energy Performance, 24% 1 1
3.3.10 Optimize Energy Performance, 26% 1 13.3.11 Optimize Energy Performance, 28% 1 13.3.12 Optimize Energy Performance, 30% 1 13.3.13 Optimize Energy Performance, 32% 1 13.3.14 Optimize Energy Performance, 34% 1 13.3.15 Optimize Energy Performance, 36% 1 13.3.16 Optimize Energy Performance, 38% 1 13.3.17 Optimize Energy Performance, 40% 1 13.3.18 Optimize Energy Performance, 42% 1 13.3.19 Optimize Energy Performance, 44% 1 1
3.4 Enhanced Commissioning 2 23.5 Measurement and Verification 3 33.6 Green Power 2 2 2 24.0 Materials & Resources 14 14 14 144.1 Prerequisite 1 Storage and Collection of Recyclables Required Required Required Required
4.2.1 Construction Waste Management, 50% 1 1 1 14.2.2 Construction Waste Management, 75% 1 1 1 14.2.3 Construction Waste Management, 100% 1 1 1 14.3.1 Material Reuse, 5% 1 1 1 14.3.2 Material Reuse, 10% 1 1 1 14.4.1 Recycled Content,10% 1 1 1 14.4.2 Recycled Content, 20% 1 1 1 14.5.1 Local/Regional Materials, 10% Extracted, Harvested or Manufactured Regionally 1 1 1 14.5.2 Local/Regional Materials, 20% Extracted, Harvested or Manufactured Regionally 1 1 1 14.5.3 Local/Regional Materials, 50% Extracted, Harvested or Manufactured Locally (within 250 miles) 1 1 1 1
4.6 Rapidly Renewable Materials 1 1 1 14.7 Certified Wood 1 1 1 14.8 Furniture and Equipment 1 1 1 14.9 Equipment Salvage and Reuse 1 1 1 15.0 Indoor Environmental Quality 12 6 6 125.1 Prerequisite 1 Minimum Indoor Air Quality (IAQ) Performance Required Required Required Required5.2 Prerequisite 2 Environmental Tobacco Smoke (ETS) Control Required Required Required Required
5.3.1 Construction IAQ Management Plan: During Construction 1 15.3.2 Construction IAQ Management Plan: Before Occupancy 1 15.4.1 Low-Emitting Materials: Adhesives and Sealants 1 1 1 15.4.2 Low-Emitting Materials: Paints and Coatings 1 1 1 15.4.3 Low-Emitting Materials: Flooring Systems 1 1 1 15.4.4 Low-Emitting Materials: Composite Wood and Agrifiber Products 1 1 1 1
5.5 Indoor Chemical and Pollutant Source Control 1 15.6.1 Controllability of Systems: Lighting 1 1 1 15.6.2 Controllability of Systems: Thermal Comfort 1 15.7.1 Thermal Comfort: Design 1 15.7.2 Thermal Comfort: Employee Verification 1 1
5.8 Noise Transmission 1 1 1 16.0 Construction Practices 5 4 4 5
6.1.1 Alternative Transportation During Construction: Staging Area 1 16.1.2 Alternative Transportation During Construction: Low-Emitting & Fuel-Efficient Vehicles, 10% 1 1 1 16.1.3 Alternative Transportation During Construction: Low-Emitting & Fuel-Efficient Vehicles, 50% 1 1 1 1
6.2 Construction Noise and Acoustical Quality 1 1 1 16.3 Sustainable Temporary Construction Materials 1 1 1 17.0 Innovation for Concessions & Tenants - Design & Construction 11 1 1 17.1 Innovation for Concessions & Tenants - Design & Construction 17.2 Innovation for Concessions & Tenants - Design & Construction 17.3 Innovation for Concessions & Tenants - Design & Construction 17.4
37.5 LEED Accredited Professional 1 1 1 1
7.6.1 LEED Certified Project - Certified 17.6.2 LEED Certified Project - Silver 17.6.3 LEED Certified Project - Gold 17.6.4 LEED Certified Project - Platinum 116.0 Monitoring & Reporting 5 5 5 516.1 Documenting Sustainable Measures 5 5 5 5
TOTAL POINTS POSSIBLE 88 52 46 78
Prerequisites 7 6 9
6 6 6
21 18 31
26 23 39
31 28 47
42 37 62
Menu Items (Green Walls, LED lights, Recycled Content Finishes, Rapidly Renewable Finishes, Instantaneous Hot Water Heating, Non-Terminal Tenant Options)
Sustainable Airport Manual Credits
Po
ten
tial
Po
ints Points by Tenant Type
Concessions & Tenants - Design & Construction
Rahm EmanuelMayor
November 5, 2012© 2012 City of ChicagoRosemarie S. Andolino
Commissioner
CT-A-1
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
______________
SUSTAINABLE AIRPORT MANUAL GREEN AIRPLANE RATING SYSTEM
_______________
Full ServiceCounter Service
To-Go, Kiosk BuildoutFree-
Standing, Kiosk
AP Administrative Procedures 0 8 8 8 8 8 8 8 8AP.1 Prerequisite 1 Green Meetings Required Required Required Required Required Required Required RequiredAP.2 Prerequisite 2 Document Reduction and Recycling Initiative (DRRI) Required Required Required Required Required Required Required Required
AP.3* Corporate Sustainability Policy* 1 1 1 1 1 1 1 1AP.4 Green Procurement Policy 4 4 4 4 4 4 4 4
AP.5.1 Recycled Content Paper, 30% 1 1 1 1 1 1 1 1AP.5.2 Recycled Content Paper, 50% 1 1 1 1 1 1 1 1AP.5.3 Recycled Content Paper, 100% 1 1 1 1 1 1 1 1
8.0 Company Policy 19 17 17 17 17 17 19 198.1 Prerequisite 1 Tenant Environmental Liaison Required Required Required Required Required Required Required Required
8.2* Establish and Implement Employee Sustainability Training Program* 2 2 2 2 2 2 2 28.3.1.1 Alternative Transportation: Public Transportation Access, 25% 3 3 3 3 3 3 3 38.3.1.2 Alternative Transportation: Public Transportation Access, 50% 1 1 1 1 1 1 1 18.3.1.3 Alternative Transportation: Public Transportation Access, 75% 1 1 1 1 1 1 1 18.3.1.4 Alternative Transportation: Public Transportation Access, 100% 1 1 1 1 1 1 1 1
8.3.2 Alternative Transportation: Bicycle-Access, Storage and Changing Rooms 2 2 28.3.3.1 Alternative Transportation: Low-Emitting and Fuel-Efficient Vehicles, 5% 1 1 1 1 1 1 1 18.3.3.2 Alternative Transportation: Low-Emitting and Fuel-Efficient Vehicles, 25% 1 1 1 1 1 1 1 18.3.3.3 Alternative Transportation: Low-Emitting and Fuel-Efficient Vehicles, 50% 1 1 1 1 1 1 1 18.3.3.4 Alternative Transportation: Low-Emitting and Fuel-Efficient Vehicles, 100% 1 1 1 1 1 1 1 18.3.4.1 Alternative Transportation: Carpooling, 5% 1 1 1 1 1 1 1 18.3.4.2 Alternative Transportation: Carpooling, 25% 1 1 1 1 1 1 1 18.3.4.3 Alternative Transportation: Carpooling, 50% 1 1 1 1 1 1 1 18.3.4.4 Alternative Transportation: Carpooling, 100% 1 1 1 1 1 1 1 1
8.4 Community Education 1 1 1 1 1 1 1 19.0 Responsible Procurement 27 23 23 23 12 12 23 129.1 Sustainable Furniture 1 1 1 1 1 1 1 1
9.2* Eliminate Use of Polystyrene Foam* 1 1 1 1 1 1 1 19.3.1 Consumer Disposable Products: Eliminate Use of Disposables 3 3 3 3 3
9.3.2.1* Consumer Disposable Products: Bio-Based Content, 25%* 2 2 2 2 2 2 2 29.3.2.2 Consumer Disposable Products: Bio-Based Content, 50% 2 2 2 2 2 2 2 29.3.3.1 Consumer Disposable Products: Post-Consumer Recycled Plastic, 30% 1 1 1 1 1 1 1 19.3.3.2 Consumer Disposable Products: Post-Consumer Recycled Plastic, 60% 1 1 1 1 1 1 1 19.3.3.3 Consumer Disposable Products: Post-Consumer Recycled Plastic, 100% 1 1 1 1 1 1 1 1
9.3.4.1* Consumer Disposable Products: Post-Consumer Recycled Paper, 30%* 1 1 1 1 1 1 1 19.3.4.2 Consumer Disposable Products: Post-Consumer Recycled Paper, 60% 1 1 1 1 1 1 1 19.3.4.3 Consumer Disposable Products: Post-Consumer Recycled Paper, 100% 1 1 1 1 1 1 1 19.4.1* Local/Regional Food Sources, Within 250 miles, 25%* 2 2 2 2 29.4.2 Local/Regional Food Sources, Within 250 miles, 50% 2 2 2 2 29.4.3 Local/Regional Food Sources, Within 100 miles, 25% 29.4.4 Local/Regional Food Sources, Within 100 miles, 50% 2
9.5.1* Sustainable Food and Consumer Products, 20%* 2 2 2 2 29.5.2 Sustainable Food and Consumer Products, 40% 2 2 2 2 210.0 Green Interiors 16 4 0 0 4 0 12 1210.1 Prerequisite 1 Minimum Indoor Air Quality (IAQ) Performance Required Required Required10.2 Prerequisite 2 Environmental Tobacco Smoke (ETS) Control Required Required Required Required Required Required Required Required
10.3.1 LEED Certified - Design & Construction - Certified 110.3.2 LEED Certified Project - Design & Construction - Silver 110.3.3 LEED Certified Project - Design & Construction - Gold 110.3.4 LEED Certified Project - Design & Construction - Platinum 110.4.1 Green Cleaning: High Performance Cleaning 2 2 2 2 210.4.2 Green Cleaning: Equipment 1 1 1 1 110.4.3 Green Cleaning: Entryway Systems (Non-Terminal Tenants) 1 1 110.4.4 Green Cleaning: Integrated Pest Management 1 1 1 1 1
10.5 Measurement and Verification 3 3 310.6 Tenant Space Automation System 1 1 1
10.7.1 Occupant Controls: Lighting Comfort 1 1 110.7.2 Occupant Controls: Thermal Comfort 1 1 1
10.8 Thermal Comfort: Employee Verification 1 1 111.0 Water Management 16 0 0 0 0 0 12 1211.1 Utility Meter Data 4 4 4
11.2 Water Management Plan 2 2 211.3.1 Water Use Reduction, 5% OR Option 2 - Menu Items 1 6 611.3.2 Water Use Reduction, 10% 111.3.3 Water Use Reduction, 15% 111.3.4 Water Use Reduction, 20% 111.3.5 Water Use Reduction: 25% 111.3.6 Water Use Reduction: 30% 111.3.7 Water Use Reduction: 35% 111.3.8 Water Use Reduction: 40% 111.3.9 Water Use Reduction: 45% 1
11.3.10 Water Use Reduction: 50% 112.0 Energy Management 33 14 12 0 14 0 14 1412.1 Utility Meter Data 4 4 4 4 4 412.2 Energy Management Plan 2 2 2 2 2 2
12.3.1 Energy Use Reduction, 5% OR Option 2 - Menu Items 1 6 6 6 6 612.3.2 Energy Use Reduction, 10% 112.3.3 Energy Use Reduction, 15% 112.3.4 Energy Use Reduction, 20% 112.3.5 Energy Use Reduction, 25% 112.3.6 Energy Use Reduction, 30% 112.3.7 Energy Use Reduction, 35% 112.3.8 Energy Use Reduction, 40% 112.3.9 Energy Use Reduction, 45% 1
12.3.10 Energy Use Reduction, 50% 112.4.1.1 Optimize Energy Performance: Lighting Power, 15% 112.4.1.2 Optimize Energy Performance: Lighting Power, 20% 112.4.1.3 Optimize Energy Performance: Lighting Power, 25% 112.4.1.4 Optimize Energy Performance: Lighting Power, 30% 112.4.1.5 Optimize Energy Performance: Lighting Power, 35% 1
12.4.2 Optimize Energy Performance: Lighting Control 312.4.3 Optimize Energy Performance: HVAC 6
12.4.4.1 Optimize Energy Performance: Equipment & Appliances, 50% 112.4.4.2 Optimize Energy Performance: Equipment & Appliances, 75% 112.4.4.3 Optimize Energy Performance: Equipment & Appliances, 100% 1
12.5 Green Power 2 2 2 2 213.0 Waste Stream Management 42 17 17 2 13 2 17 1313.1* Waste Stream Audit* 4 4 4 4 4 413.2 Waste Management Plan 2 2 2 2 2 2 2 2
13.3.1 Waste Reduction, 5% OR Option 2 - Menu Items 1 6 6 6 6 613.3.2 Waste Reduction, 10% 113.3.3 Waste Reduction, 15% 113.3.4 Waste Reduction, 20% 113.3.5 Waste Reduction, 25% 113.3.6 Waste Reduction, 30% 113.3.7 Waste Reduction, 35% 113.3.8 Waste Reduction, 40% 1
Concessions & Tenants - Operations & Maintenance
Sustainable Airport Manual Credits
Po
ten
tial
Po
ints Points by Tenant Type
Terminal Tenants Non-Terminal TenantsFood Service Tenant * Non-Food Service Tenant
Food Service Tenant *
Non-Food Service Tenant
CT-A-2
______________
SUSTAINABLE AIRPORT MANUAL GREEN AIRPLANE RATING SYSTEM
_______________
Full ServiceCounter Service
To-Go, Kiosk BuildoutFree-
Standing, Kiosk
Concessions & Tenants - Operations & Maintenance
Sustainable Airport Manual Credits
Po
ten
tial
Po
ints Points by Tenant Type
Terminal Tenants Non-Terminal TenantsFood Service Tenant * Non-Food Service Tenant
Food Service Tenant *
Non-Food Service Tenant
13.3.9 Waste Reduction, 45% 113.3.10 Waste Reduction, 50% 1
13.4* Storage and Collection of Recyclables* 1 1 1 1 1 113.5 Track and Report Recycling Activity 2
13.6.1* Organic Byproduct Recycling: Food Waste* 4 4 4 413.6.2 Organic Byproduct Recycling: Coffee Grounds 413.6.3 Organic Byproduct Recycling: Fats, Oils and Grease 2
13.7 Surplus Food Sent to Local Organizations 213.8 Deplaned Waste 513.9 Repurposing of Goods 2
13.10.1 Reduction of Plastic Waste: Plastic Bottles 213.10.2 Reduction of Plastic Waste: Elimination of Petroleum Based Plastic Bags 113.10.3 Reduction of Plastic Waste: Biodegradable Trash Bags 1
14.0 Venue Specific Considerations 44 0 0 0 0 0 0 014.1 Heat Island Reduction 114.2 Stormwater Management 1
14.3.1 Landscape Management: CDA Specifications 114.3.2 Landscape Management: Landscape Equipment 114.3.3 Landscape Management: Fertilizer Use 114.3.4 Landscape Management: Landscape Waste 114.3.5 Landscape Management: Irrigation 3
14.4 Rainwater Harvesting 1214.5 Water Efficient Vehicle Washing 8
14.6.1 Clean Fuel Vehicles, 30% 114.6.2 Clean Fuel Vehicles, 60% 114.6.3 Clean Fuel Vehicles, 90% 114.6.4 Clean Fuel Vehicles, 100% 1
14.7 Alternative Fuel Infrastructure 614.8 Green Restaurant Certification 5
15.0 Innovation for Concessions & Tenants 9 0 0 0 0 0 0 015.1 Innovation for Concessions & Tenants - Operations & Maintenance 115.2 Innovation for Concessions & Tenants - Operations & Maintenance 115.3 Innovation for Concessions & Tenants - Operations & Maintenance 115.4 Community/Cultural Responsibility 315.5 3
16.0 Monitoring & Reporting 5 5 5 5 5 5 5 516.1 Documenting Sustainable Measures 5 5 5 5 5 5 5 5
TOTAL APPLICABLE POINTS POSSIBLE 219 88 82 55 73 44 110 95
Prerequisites 4 4 4 4 4 5 5
Achiever 6 6 6 6 6 6 6
Leader 44 41 28 37 22 55 48
Mentor 70 66 44 58 35 88 76
Menu Items (Green Walls, Alternative Water Heating, Advanced Wastewater Treatment, Kinetic Energy Systems/Power Regeneration, Waste-to-Energy Systems, Net Zero Energy/Water/Waste, Biological Systems, or Exemplary Performance)
* In addition to the points above, Food Service Tenants must also meet the following credits, where applicable, to achieve a Mentor rating: AP.3, 8.2, 9.2, 9.3.2.1, 9.3.4.1, 9.4.1, 9.5.1, 13.1, 13.4, and 13.6.1.
Rahm EmanuelMayor
November 5, 2012 © 2012 City of ChicagoRosemarie S. Andolino
Commissioner
CT-A-2
Rahm Emanuel Mayor
© 2012 City of Chicago
November 5, 2012
Rosemarie S. Andolino Commissioner
APPENDIX CT-B
CONCESSIONS & TENANTS CHECKLISTS
Instructions for completing SAM Checklists:- see also the Sustainable Airport Manual (SAM) for more information
NOTE: Only blue text and unshaded cells may be changed by the user.
Instructions Example1 Determine based on the Applicability section of the CT chapter whether this is a Design &
Construction (DC) evaluation or a Operations & Maintenance (OM) evaluation. Pick from the appropriate worksheet tabs: "CT-DC Checklist " or "CT-OM Checklist ".
2 Fill out title information in blue at the top: Tenant name, additional descriptions, date submitted.
Joe's EateryCDA No. xxxx-xx Terminal 3 Build-OutRevised: 8/12/2012
3 From the drop-down menu, select the appropriate tenant type: Terminal, Food Service, Full Service; Terminal, Food Service, Counter Service; Terminal, Food Service, To-Go/Kiosk, etc. The "Goal by Tenant Type" and "Points by Tenant Type" columns will populate based on your selection.
4 For those credits that were achieved, indicate this by putting the appropriate point in the “Points Obtained” column. Note that for “Prerequisite” credits, no point is achieved as theseare the minimum performance requirements for sustainability under the SAM. For prerequisites, insert a "Yes" for those that are applicable (some prerequisites may not apply for all tenants).
If the credit requirements for 6.2 – Construction Noise and Acoustical Quality are met, then insert a “1” under the “Points Obtained” column. For 4.1 - Prerequisite 1 Storage and Collection of Recyclables, insert a "Y" or "Yes" in the "Points Obtained" column to indicate compliance with the prerequisite.
5 In the "Narrative" column, describe the scope of work for the project relevant to this credit by replacing the ”Fill in scope of work” phrase with the appropriate description. ORFor credits that were not achieved, leave the "Points Obtained" column blank and describe the reasons for this in the "Narrative". Include any additional information such as estimated quantities and/or locations.
NOTE: Only blue text and unshaded cells may be changed by the user.
Under 12.4.4 - Optimize Energy Performance: Equipment and Appliances, fill in scope of work: "A total of 89% of all ENERGY STAR eligible equipment are ENERGY STAR qualified. This includes all computers and printers, kitchen appliances, and most copiers." Input 2 points in the "Points Obtained" column.ORUnder 12.4.4 - Optimize Energy Performance: Equipment and Appliances, fill in scope of work: "Due to the specialized nature of the computing equipment and peripheral equipment, only the kitchen appliances and copiers were ENERGY STAR qualified. The overall percentage of ENERGY STAR qualified equipment was only 25%. Therefore, the point was not achieved." Leave "Points Obtained" column blank in this case.
6 For some credits, supporting documentation, typically some form of calculations, will also need to be included, if applicable. See SAM for supporting documentation templates. In some cases, the SRP may require additional supporting documentation for the other credits during review process for clarification.
NOTE: Points cannot be awarded for those credits that require supporting documentation without the appropriate documentation.
For 11.1 - Utility Meter Data, submit, with this checklist, water meter data (if available) .
7 SUBMIT THE ENTIRE CHECKLIST, INCLUDING SUPPORTING DOCUMENTATION, FOR EVERY MILESTONE SUBMITTAL OR PERFORMANCE PERIOD FOR REVIEW BY THE SRP.
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
Template Sustainable Airport Manual (SAM) Concessions & Tenants - Design & Construction Checklist11/5/12
[Tenant Name][CDA Project Number, Concessionaire, Checklist Description, Additional Information]Revised: [Revision Date] Tenant Type: [choose from drop-down menu]
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
AP Administrative Procedures 8
AP.1
Prerequisite 1 - Green Meetings Guide meeting hosts, planners and attendees toward more eco-friendly meetings and incorporate environmental considerations into planning and conducting meetings in order to minimize the negative impact on the environment.
Prereq Fill in scope of work
AP.2Prerequisite 2 - Document Reduction and Recycling Initiative (DRRI) Reduce the volume paper used and facilitate the recycling of documents.
Prereq Fill in scope of work
AP.3
Corporate Sustainability Policy Keeping with the spirit and intent of this Manual, it is strongly encouraged that companies working in support of CDA on any project establish and adopt their own corporate policy on sustainable practices.
1 Fill in scope of work
AP.4Green Procurement Policy Reduce the environmental impact of products and services by developing a Green Purchasing Program.
4 Fill in scope of work
AP.5Recycled Content PaperReduce the need for virgin materials, energy, and waste associated with the production of paper by promoting the use of recycled content paper.
3 Fill in scope of work
POINTS OBTAINED
APPLICABLE POINTS BY
TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
1
1.1Prerequisite 1- Adopt CDA Best Management PracticesMinimize the environmental impacts of facility operations.
Prereq Fill in scope of work
1.2
Light Pollution Reduction Minimize light trespass from the tenant space, reduce sky-glow to increase night sky access, improve nighttime visibility through glare reduction, and reduce development impact on nocturnal environments
1 Fill in scope of work
POINTS OBTAINED
APPLICABLE POINTS BY
TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
2.0 Water Efficiency 6
2.1Prerequisite 1 - Water Use Reduction Increase water efficiency within tenant spaces to reduce the burden on municipal water supply and wastewater systems.
Prereq Fill in scope of work
2.2Water Use - Additional ReductionFurther increase water efficiency within tenant space to reduce the burden on municipal water supply and wastewater systems.
6 Fill in scope of work
POINTS OBTAINED
APPLICABLE POINTS BY
TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
3.0 Energy & Atmosphere 26
3.1
Prerequisite 1 - Fundamental Systems Commissioning Verify that the project’s energy related systems are installed, calibrated and perform according to the owner’s project requirements, basis of design, and construction documents.
Prereq Fill in scope of work
3.2
Prerequisite 2 - Minimum Energy Performance Establish the minimum level of energy efficiency for the tenant space systems to reduce environmental and economic impacts associated with excessive energy use.
Prereq Fill in scope of work
3.3
Optimize Energy PerformanceAchieve increasing levels of energy performance beyond the prerequisite standard to reduce environmental and economic impacts associated with excessive energy use.
19 Fill in scope of work
3.4Enhanced Commissioning Begin the commissioning process early in the design process and execute additional activities after systems performance verification is completed.
2 Fill in scope of work
3.5Measurement and Verification Provide for the ongoing accountability of tenant energy consumption over time.
3 Fill in scope of work
3.6Green PowerEncourage the development and use of grid-source, renewable energy technologies on a net zero pollution basis.
2 Fill in scope of work
POINTS OBTAINED
APPLICABLE POINTS BY
TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
4.0 Materials & Resources 14
4.1Prerequisite 1 - Storage and Collection of Recyclables Facilitate the reduction of waste generated by tenant space occupants that is hauled to and disposed of in landfills.
Prereq Fill in scope of work
4.2
Construction Waste Management Divert construction and demolition debris from disposal in landfills and incineration facilities. Redirect recyclable recovered resources back to the manufacturing process and reusable materials to appropriate sites.
3 Fill in scope of work
4.3
Material ReuseReuse building materials and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
2 Fill in scope of work
4.4
Recycled ContentIncrease demand for building products that incorporate recycled content materials, thereby reducing impacts resulting from extraction and processing of virgin materials.
2 Fill in scope of work
1.0 Sustainable Sites
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
16 and 17 - CDA SAM Appendix CT-A and CT-B v3.0 - FINAL.xls CT-B-3 11/2/2012
Template Sustainable Airport Manual (SAM) Concessions & Tenants - Design & Construction Checklist11/5/12
[Tenant Name][CDA Project Number, Concessionaire, Checklist Description, Additional Information]Revised: [Revision Date] Tenant Type: [choose from drop-down menu]
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
4.5
Local/Regional MaterialsIncrease demand for building and all other materials and products that are extracted, harvested or recovered, as well as manufactured within the region, thereby supporting the use of indigenous resources and reducing the environmental impacts resulting from transportation.
3 Fill in scope of work
4.6Rapidly Renewable Materials Reduce the use and depletion of finite raw materials and long-cycle renewable materials by replacing them with rapidly renewable materials.
1 Fill in scope of work
4.7Certified WoodEncourage environmentally responsible forest management.
1 Fill in scope of work
4.8Furniture and Equipment Reduce the environmental and indoor air quality impacts of the furniture and equipment acquired for use in tenant space.
1 Fill in scope of work
4.9
Equipment Salvage and ReusePromote the reuse of equipment and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
1 Fill in scope of work
POINTS OBTAINED
APPLICABLE POINTS BY
TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
5.0 Indoor Environmental Quality 12
5.1
Prerequisite 1 - Minimum Indoor Air Quality (IAQ) PerformanceEstablish minimum indoor air quality (IAQ) performance to enhance indoor air quality in tenant space, thus contributing to the comfort and well-being of the occupants.
Prereq Fill in scope of work
5.2Prerequisite 2 - Environmental Tobacco Smoke (ETS) ControlPrevent or minimize exposure of occupants, indoor surfaces, and ventilation air distribution systems to Environmental Tobacco Smoke (ETS).
Prereq Fill in scope of work
5.3.1
Construction IAQ Management Plan: During Construction Reduce indoor air quality problems resulting from the construction/renovation process in order to help sustain the comfort and well-being of construction workers and tenant space occupants.
1 Fill in scope of work
5.3.2
Construction IAQ Management Plan: Before Occupancy Reduce indoor air quality problems resulting from the construction/renovation process in order to help sustain the comfort and well-being of construction workers and tenant space occupants.
1 Fill in scope of work
5.4.1Low-Emitting Materials: Adhesives and SealantsReduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
1 Fill in scope of work
5.4.2Low-Emitting Materials: Paints and CoatingsReduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
1 Fill in scope of work
5.4.3Low-Emitting Materials: Flooring SystemsReduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
1 Fill in scope of work
5.4.4Low-Emitting Materials: Composite Wood and Agrifiber ProductsReduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well-being of installers and occupants.
1 Fill in scope of work
5.5Indoor Chemical and Pollutant Source ControlMinimize exposure of occupants to potentially hazardous particulates and chemical pollutants.
1 Fill in scope of work
5.6.1
Controllability of Systems: LightingProvide a high level of lighting system control by individual occupants or by specific groups in multi-occupant spaces (e.g. classrooms and conference areas) to promote the productivity, comfort and well-being of occupants.
1 Fill in scope of work
5.6.2
Controllability of Systems: Thermal Comfort Provide a high level of thermal comfort system control by individual occupants or by specific groups in multi-occupant spaces (i.e. classrooms or conference areas) to promote the productivity, comfort and well-being of occupants.
1 Fill in scope of work
5.7.1Thermal Comfort: DesignProvide a comfortable thermal environment that supports the productivity and well-being of occupants.
1 Fill in scope of work
5.7.2Thermal Comfort: Employee Verification Provide for the assessment of tenant space thermal comfort over time.
1 Fill in scope of work
5.8Noise TransmissionLimit noise levels in noise-sensitive, occupied spaces such as terminals and offices to increase employee productivity and passenger comfort.
1 Fill in scope of work
POINTS OBTAINED
APPLICABLE POINTS BY
TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
6.0 Construction Practices 5
6.1.1Alternative Transportation During Construction: Staging AreaReduce emissions due to construction vehicles by minimizing the amount of traffic to the construction site.
1 Fill in scope of work
6.1.2
Alternative Transportation During Construction: Low-Emitting and Fuel-Efficient Vehicles, 10% Reduce emissions from on-road construction vehicles (examples include foreman pickups or shuttle buses).
1 Fill in scope of work
16 and 17 - CDA SAM Appendix CT-A and CT-B v3.0 - FINAL.xls CT-B-4 11/2/2012
Template Sustainable Airport Manual (SAM) Concessions & Tenants - Design & Construction Checklist11/5/12
[Tenant Name][CDA Project Number, Concessionaire, Checklist Description, Additional Information]Revised: [Revision Date] Tenant Type: [choose from drop-down menu]
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
6.1.3Alternative Transportation During Construction: Low-Emitting and Fuel-Efficient Vehicles, 50% Reduce emissions from on-road construction vehicles.
1 Fill in scope of work
6.2.Construction Noise and Acoustical QualityImprove the exterior noise quality during construction affecting residential areas or other noise sensitive areas.
1 Fill in scope of work
6.3
Sustainable Temporary Construction MaterialsReduce the use and depletion of finite raw materials and long-cycle renewable materials by replacing them with high recycled content, rapidly renewable materials and FSC certified wood products for temporary uses during construction.
1 Fill in scope of work
POINTS OBTAINED
APPLICABLE POINTS BY
TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
7.0 Innovation in Design/Construction 11
7.1
Innovation in Design/Construction Provide design teams and projects the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
1 Fill in scope of work
7.2
Innovation in Design/Construction Provide design teams and projects the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
1 Fill in scope of work
7.3
Innovation in Design/Construction Provide design teams and projects the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
1 Fill in scope of work
7.4Menu ItemsTo promote specific technologies and additional strategies considered to be important to the sustainability of the airport environment.
3 Fill in scope of work
7.5LEED Accredited ProfessionalTo support and encourage the design integration required by LEED to streamline the application and certification process.
1 Fill in scope of work
7.6.1 to 7.6.4
LEED Certified Project Promote the incorporation of environmentally sustainable design in building and infrastructure improvements by registering and certifying a project through the LEED certification process and rating system.
4 Fill in scope of work
POINTS OBTAINED
APPLICABLE POINTS BY
TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
16.0 Monitoring & Reporting 5
16.1Documenting Sustainable MeasuresTrack, document, report and promote the CDA’s Green Commitment and encourage tenants airport-wide to join the movement.
5 Fill in scope of work
TOTAL POINTS OBTAINED
TOTAL POSSIBLE
POINTS
88
16 and 17 - CDA SAM Appendix CT-A and CT-B v3.0 - FINAL.xls CT-B-5 11/2/2012
airports going green.org
Project Submittal Forms,
Comments, Case Studies, Lessons-Learned, New Technologies
Please email:
Template Sustainable Airport Manual (SAM) Concessions & Tenants - Operations & Maintenance Checklist11/5/12
[Tenant Name][CDA Project Number, Concessionaire, Checklist Description, Additional Information]Revised: [Revision Date] Tenant Type: [choose from drop-down menu]
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
AP Administrative Procedures 8
AP.1
Prerequisite 1 - Green Meetings Guide meeting hosts, planners and attendees toward more eco-friendly meetings and incorporate environmental considerations into planning and conducting meetings in order to minimize the negative impact on the environment.
Prereq Fill in scope of work
AP.2Prerequisite 2 - Document Reduction and Recycling Initiative (DRRI) Reduce the volume paper used and facilitate the recycling of documents.
Prereq Fill in scope of work
AP.3
Corporate Sustainability Policy Keeping with the spirit and intent of this Manual, it is strongly encouraged that companies working in support of CDA on any project establish and adopt their own corporate policy on sustainable practices.
1 Fill in scope of work
AP.4Green Procurement Policy Reduce the environmental impact of products and services by developing a Green Purchasing Program.
4 Fill in scope of work
AP.5Recycled Content PaperReduce the need for virgin materials, energy, and waste associated with the production of paper by promoting the use of recycled content paper.
3 Fill in scope of work
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
8.0 Company Policy 19
8.1Prerequisite 1 - Tenant Environmental LiaisonFacilitate the dissemination of environmental information within the workplace and create a link with CDA staff for environmental issues.
Prereq Fill in scope of work
8.2
Establish and Implement Employee Sustainability Training Program In keeping with the spirit and intent of this Manual, it is strongly encouraged that companies working in support of CDA on any project establish and adopt their own employee training program.
2 Fill in scope of work
8.3.1Alternative Transportation: Public Transportation Access Reduce pollution and land development impacts from automobile use.
6 Fill in scope of work
8.3.2Alternative Transportation: Bicycle Access, Storage and Changing RoomsReduce pollution and land development impacts from automobile use.
2 Fill in scope of work
8.3.3Alternative Transportation: Low-Emitting and Fuel-Efficient Vehicles (Non-Construction)Reduce pollution and land development impacts from automobile use.
4 Fill in scope of work
8.3.4Alternative Transportation: CarpoolingReduce pollution and land development impacts from single occupancy vehicle use for employees.
4 Fill in scope of work
8.4Community Education Promote awareness of tenant environmental and sustainability initiatives.
1 Fill in scope of work
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
9.0 Responsible Procurement 27
9.1Sustainable FurnitureReduce the environmental and indoor air quality impacts of the furniture acquired for use in the tenant space.
1 Fill in scope of work
9.2Eliminate Use of Polystyrene Foam Reduce the environmental impact of polystyrene production and disposal.
1 Fill in scope of work
9.3.1Consumer Disposable Products: Eliminate Use of Disposables Reduce the need for virgin materials and reduce the volume of solid waste generated by tenant activities.
3 Fill in scope of work
9.3.2Consumer Disposable Products: Bio-Based Content Reduce the need for virgin materials and reduce the volume of solid waste generated by tenant activities.
4 Fill in scope of work
9.3.3Consumer Disposable Products: Post-Consumer Recycled Plastic Reduce the need for virgin materials and reduce the volume of solid waste generated by tenant activities.
3 Fill in scope of work
9.3.4Consumer Disposable Products: Post-Consumer Recycled Paper Reduce the need for virgin materials and reduce the volume of solid waste generated by tenant activities.
3 Fill in scope of work
9.4Local and Regional Food SourcesReduce the environmental and transportation impacts associated with food production and distribution.
8 Fill in scope of work
9.5Sustainable Food and Consumer Products Reduce the environmental impacts associated with food and consumer product production and distribution.
4 Fill in scope of work
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
10.0 Green Buildings 16
10.1
Prerequisite 1 - Minimum Indoor Air Quality (IAQ) PerformanceEstablish minimum indoor air quality (IAQ) performance to enhance indoor air quality within tenant space, thus contributing to the comfort and well-being of the occupants.
Prereq Fill in scope of work
10.2Prerequisite 2 - Environmental Tobacco Smoke (ETS) ControlPrevent or minimize exposure of occupants, indoor surfaces, and ventilation air distribution systems to Environmental Tobacco Smoke (ETS).
Prereq Fill in scope of work
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
16 and 17 - CDA SAM Appendix CT-A and CT-B v3.0 - FINAL.xls CT-B-3 11/2/2012
Template Sustainable Airport Manual (SAM) Concessions & Tenants - Operations & Maintenance Checklist11/5/12
[Tenant Name][CDA Project Number, Concessionaire, Checklist Description, Additional Information]Revised: [Revision Date] Tenant Type: [choose from drop-down menu]
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
10.3
LEED Certified Design and Construction Promote the incorporation of environmentally sustainable design in building and infrastructure improvements by registering and certifying a project through the LEED certification process and rating system.
4 Fill in scope of work
10.4.1
High Performance CleaningReduce the exposure of occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, and the environment.
2 Fill in scope of work
10.4.2
Green Cleaning: Equipment Reduce the exposure of occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, and the environment.
1 Fill in scope of work
10.4.3
Green Cleaning: Entryway Systems (Non-Terminal Tenants) Reduce the exposure of occupants and maintenance personnel to potentially hazardous chemical, biological, and particulate contaminants, which adversely affect air quality, human health, and the environment.
1 Fill in scope of work
10.4.4
Integrated Pest Management Plan Preserve environmental integrity while discouraging the presence of pests/wildlife, in an effort to include methods that maintain and encourage high-performance pest management control.
1 Fill in scope of work
10.5Measurement and Verification Provide for the ongoing accountability of energy consumption over time.
3 Fill in scope of work
10.6
Tenant Space Automation SystemProvide information to support the ongoing accountability and optimization of energy performance and identify opportunities for additional energy-saving investments.
1 Fill in scope of work
10.7.1
Occupant Controls: Lighting Comfort Provide a high level of lighting system control by individual occupants or by specific groups in multi-occupant spaces (e.g. classrooms and conference areas) to promote the productivity, comfort and well-being of occupants.
1 Fill in scope of work
10.7.2
Occupant Controls: Thermal Comfort Provide a high level of thermal comfort system control by individual occupants or by specific groups in multi-occupant spaces (i.e. classrooms or conference areas) to promote the productivity, comfort and well-being of occupants.
1 Fill in scope of work
10.8Thermal Comfort: Employee VerificationProvide for the assessment of thermal comfort over time.
1 Fill in scope of work
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
11.0 Water Management 16
11.1Utility Meter DataMonitor, track and report utility data to reduce environmental and economic impacts associated with excessive water use.
4 Fill in scope of work
11.2
Water Management Plan Promote continuity of information to ensure that water-efficient operating strategies are maintained and provide a foundation for training and system analysis.
2 Fill in scope of work
11.3Water Use Reduction Recognize previous tenant improvements and upgrades that had a positive impact on water efficiency.
10 Fill in scope of work
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
12.0 Energy Management 33
12.1Utility Meter DataMonitor, track and report utility data to reduce environmental and economic impacts associated with excessive energy use.
4 Fill in scope of work
12.2
Energy Management Plan Promote continuity of information to ensure that energy-efficient operating strategies are maintained and provide a foundation for training and system analysis.
2 Fill in scope of work
12.3Energy Use Reduction Recognize previous tenant improvements and upgrades that had a positive impact on energy efficiency.
10 Fill in scope of work
12.4.1
Optimize Energy Performance: Lighting Power Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
5 Fill in scope of work
12.4.2
Optimize Energy Performance: Lighting Control Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
3 Fill in scope of work
12.4.3
Optimize Energy Performance: HVACAchieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
6 Fill in scope of work
12.4.4
Optimize Energy Performance: Equipment and Appliances Achieve increasing levels of energy conservation beyond the referenced standard to reduce environmental and economic impacts associated with excessive energy use.
3 Fill in scope of work
12.5Green Power Encourage the development and use of grid-source, renewable energy technologies on a net zero pollution basis
2 Fill in scope of work
16 and 17 - CDA SAM Appendix CT-A and CT-B v3.0 - FINAL.xls CT-B-4 11/2/2012
Template Sustainable Airport Manual (SAM) Concessions & Tenants - Operations & Maintenance Checklist11/5/12
[Tenant Name][CDA Project Number, Concessionaire, Checklist Description, Additional Information]Revised: [Revision Date] Tenant Type: [choose from drop-down menu]
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
13.0 Waste Stream Management 42
13.1Waste Stream AuditDetermine the overall generation of various wastes produced and reduce ongoing waste and toxins generated by the tenant.
4 Fill in scope of work
13.2Waste Management PlanPromote continuity of information to ensure that waste reduction strategies are maintained and provide a foundation for training and system analysis.
2
13.3Energy Use Reduction Recognize previous tenant improvements and upgrades that had a positive impact on waste reduction.
10
13.4Storage and Collection of RecyclablesFacilitate the reduction of waste generated by tenant space occupants that is hauled to and disposed of in landfills.
1 Fill in scope of work
13.5Track and Report Recycling ActivityDetermine the types and amounts of recyclable waste and determine strategies for reducing and diverting additional waste from landfills.
2 Fill in scope of work
13.6.1Organic Byproduct Recycling: Food Waste Facilitate the reduction of waste generated by tenant space occupants that is hauled to and disposed of in landfills.
4 Fill in scope of work
13.6.2Organic Byproduct Recycling: Coffee GroundsFacilitate the reduction of waste generated by tenant space occupants that is hauled to and disposed of in landfills.
4 Fill in scope of work
13.6.3Organic Byproduct Recycling: Fats, Oils and Grease Facilitate the reduction of waste generated by tenant space occupants that is hauled to and disposed of in landfills.
2 Fill in scope of work
13.7Surplus Food Sent to Local OrganizationsIncrease tenant’s social responsibility by donating surplus food to local hunger relief organizations.
2 Fill in scope of work
13.8Deplaned WasteFacilitate the reduction of waste generated from aircraft that are hauled to and disposed of in landfills.
5 Fill in scope of work
13.9
Repurposing of GoodsPromote the reuse of materials, equipment and products to reduce demand for virgin materials and reduce waste, thereby lessening impacts associated with the extraction and processing of virgin resources.
2 Fill in scope of work
13.10.1Reduction of Plastic Waste: Plastic BottlesReduce the amount of plastic that is sold and ultimately disposed within the terminals.
2 Fill in scope of work
13.10.2Reduction of Plastic Waste: Elimination of Petroleum Based Plastic BagsReduce the amount of plastic that is sold and ultimately disposed within the terminals.
1 Fill in scope of work
13.10.3Reduction of Plastic Waste: Biodegradable Trash Bags Reduce the amount of plastic that is sold and ultimately disposed within the terminals.
1 Fill in scope of work
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
14.0 Venue Specific Considerations 44
14.1
Heat Island ReductionMinimize impacts of the existing roofs and pavements that cause the heat island effect (thermal gradient differences between developed and underdeveloped areas).
1 Fill in scope of work
14.2
Stormwater Management Limit disruption of natural water hydrology by reducing impervious cover, increasing on-site infiltration, reducing or eliminating pollution from stormwater runoff, and eliminating contaminants by enhancing the current operating system.
1 Fill in scope of work
14.3.1
Landscape Management: CDA Specifications Preserve ecological integrity, enhance natural diversity and aesthetics, while supporting high-performance spaces and integration into the surrounding landscape.
1 Fill in scope of work
14.3.2
Landscape Management: Landscape Equipment Preserve ecological integrity, enhance natural diversity and aesthetics, while supporting high-performance spaces and integration into the surrounding landscape.
1 Fill in scope of work
14.3.3
Landscape Management: Fertilizer Use Preserve ecological integrity, enhance natural diversity and aesthetics, while supporting high-performance spaces and integration into the surrounding landscape..
1 Fill in scope of work
14.3.4
Landscape Management: Landscape Waste Preserve ecological integrity, enhance natural diversity and aesthetics, while supporting high-performance spaces and integration into the surrounding landscape..
1 Fill in scope of work
14.3.5
Landscape Management: Irrigation Preserve ecological integrity, enhance natural diversity and aesthetics, while supporting high-performance spaces and integration into the surrounding landscape..
3 Fill in scope of work
14.4Rainwater Harvesting Further increase water efficiency within tenant space to reduce the burden on municipal water supply and wastewater systems.
12 Fill in scope of work
16 and 17 - CDA SAM Appendix CT-A and CT-B v3.0 - FINAL.xls CT-B-5 11/2/2012
Template Sustainable Airport Manual (SAM) Concessions & Tenants - Operations & Maintenance Checklist11/5/12
[Tenant Name][CDA Project Number, Concessionaire, Checklist Description, Additional Information]Revised: [Revision Date] Tenant Type: [choose from drop-down menu]
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
Rahm EmanuelMayor
Rosemarie S. AndolinoCommissioner
November 5, 2012© 2012 City of Chicago
14.5Water Efficient Vehicle WashingLimit or eliminate the use of potable water or other natural surface or subsurface resources available on or near the project site for vehicle washing.
8 Fill in scope of work
14.6Clean Fuel VehiclesReduce emissions from airport vehicles to improve the local air quality.
4 Fill in scope of work
14.7Alternative Fuel InfrastructureReduce emissions from airport vehicles to improve the local air quality.
6
14.8Green Restaurant Certification Encourage the green efforts of concessions and tenants.
5 Fill in scope of work
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
15.0 Innovation for Concessions & Tenants 9
15.1
Innovation for Concessions & TenantsTo provide tenants the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
1 Fill in scope of work
15.2
Innovation for Concessions & TenantsTo provide tenants the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
1 Fill in scope of work
15.3
Innovation for Concessions & TenantsTo provide tenants the opportunity to achieve exceptional performance above the requirements set by the Sustainable Airport Manual Green Airplane Rating System and/or innovative performance not specifically addressed by the Sustainable Airport Manual.
1 Fill in scope of work
15.4
Community/Cultural ResponsibilityPromote specific technologies and additional strategies social and cultural initiatives considered to be important to the sustainability of the airport environment and surrounding community.
3
15.5Menu ItemsPromote specific technologies and additional strategies considered to be important to the sustainability of the airport environment.
3 Fill in scope of work
POINTS OBTAINED
POINTS BY TENANT TYPE
GOAL BY TENANT TYPE
CREDIT CREDIT DESCRIPTION POINTS NARRATIVE
16.0 Monitoring & Reporting 5
16.1Documenting Sustainable MeasuresTrack, document, report and promote the CDA’s Green Commitment and encourage tenants airport-wide to join the movement.
5 Fill in scope of work
TOTAL POINTS OBTAINED
TOTAL POSSIBLE
POINTS
219