 SVC for voltage stabilization and harmonic suppression in rolling mill Since 1985, G.T.S Industries – site SOLLAC Dunkerque, France is operating a Static Var Compensator (SVC) delivered by ABB. The SVC, which has a dynamic (thyristor controlled) range of 66 Mvar capacitive is connected to a 90 kV rolling mill bus. Its purpose is to stabilize the bus voltage under vary- ing load conditions which occur during the running of the mill.  This SVC also comp rise s ha rmon ic f ilt ers tune d to the 5 th and 7th harmonics in order to suppress harmonic generated by the thyristor converters in the rolling mill, thereby preventing these harmonics from entering into the surrounding parts of the network. Furthermore, it achieves power factor correction of the rolling mill, thereby relieving the network of reactive power burden and contributing to a considerable decrease of the running costs of the mill. (A saving of about 3 million francs a year on the power billing in 1986 currency). Besides being a source of harmonics, a rolling mill as a load on the network is generally characterized by high and fluctuat- ing consumption of reactive as well as active power. As a con- sequence, the rolling mill will give rise to voltage fluctuations in the feeding network, the severity of which being dependent on the relationship between the size of the rolling mill and the strength of the network.  At the same time, f or safe operati on, the thyristor conv ert - ers which form part of the rolling mill can only tolerate limited fluctuations in the supply voltage. Consequently , the voltage fluctuations, if severe enough, may endanger the reliable operation of the rolling mill, as well as cause nuisance to other equipment connected to the same network. In the present case it was d ecided to invest in the SVC in order to attain dynamic bus voltage stabilization and harmonic suppression, thereby improving the performance of the Mill itself and at the same time fulfil existing obligations towards the grid company by keeping the quality of the voltage at the point of common coupling (220 kV) within specified limits.  The maximiz ing of useful active power transf er while minimizin g system losses was also seen as a valuable feature.  The SVC ensu res t hat the followin g re quire ment s o n vo ltag e control and harmonic filtering are satisfied:  Maxi mum 90 kV (feeding network) bus voltage variations 5 %  Odd harmonics max 1 %  Even har monics max 0.6 %  T otal distor tion max 1.6 %  T echnical da ta SV C Controlled voltage 90 kV Dynamic range 0-66 Mvar (capacitive) Harmonic filters 33 Mvar/5th 16,5 Mvar/5th 16,5 Mvar/7th Control system 3-phase symmetrical closed-loop reactive power control  Thy rist or v alve s Air cooled thyr ist or valves wi th magnetic triggering

Upload: decioh

Post on 14-Jan-2016

1 views

Category:

Documents


0 download

DESCRIPTION

SVC

TRANSCRIPT

Page 1: SVC

7/18/2019 SVC

http://slidepdf.com/reader/full/svc55cf8684550346484b986a04 1/2

SVC for voltage stabilization and harmonic suppression inrolling mill

Since 1985, G.T.S Industries – site SOLLAC Dunkerque,

France is operating a Static Var Compensator (SVC) delivered

by ABB. The SVC, which has a dynamic (thyristor controlled)

range of 66 Mvar capacitive is connected to a 90 kV rolling

mill bus. Its purpose is to stabilize the bus voltage under vary-

ing load conditions which occur during the running of the mill.

 This SVC also comprises harmonic f ilters tuned to the 5th and

7th harmonics in order to suppress harmonic generated by

the thyristor converters in the rolling mill, thereby preventing

these harmonics from entering into the surrounding parts ofthe network.

Furthermore, it achieves power factor correction of the rolling

mill, thereby relieving the network of reactive power burden

and contributing to a considerable decrease of the running

costs of the mill.

(A saving of about 3 million francs a year on the power billing

in 1986 currency).

Besides being a source of harmonics, a rolling mill as a load

on the network is generally characterized by high and fluctuat-ing consumption of reactive as well as active power. As a con-

sequence, the rolling mill will give rise to voltage fluctuations

in the feeding network, the severity of which being dependent

on the relationship between the size of the rolling mill and the

strength of the network.

 At the same time, for safe operation, the thyristor convert-

ers which form part of the rolling mill can only tolerate limited

fluctuations in the supply voltage. Consequently, the voltage

fluctuations, if severe enough, may endanger the reliable

operation of the rolling mill, as well as cause nuisance to other

equipment connected to the same network.

In the present case it was decided to invest in the SVC in

order to attain dynamic bus voltage stabilization and harmonic

suppression, thereby improving the performance of the Mill

itself and at the same time fulfil existing obligations towards

the grid company by keeping the quality of the voltage at the

point of common coupling (220 kV) within specified limits.

 The maximizing of useful active power transfer whi le minimizing

system losses was also seen as a valuable feature.

 The SVC ensures that the following requirements on voltage

control and harmonic filtering are satisfied:

 − Maximum 90 kV(feeding network)

bus voltage variations 5 %

 − Odd harmonics max 1 %

 − Even harmonics max 0.6 %

 − Total distortion max 1.6 %

 Technical data SVC 

Controlled voltage 90 kV 

Dynamic range 0-66 Mvar (capacitive)

Harmonic filters 33 Mvar/5th

16,5 Mvar/5th

16,5 Mvar/7th

Control system 3-phase symmetrical closed-loop

reactive power control

 Thyristor valves Air cooled thyr istor valves wi th

magnetic triggering

Page 2: SVC

7/18/2019 SVC

http://slidepdf.com/reader/full/svc55cf8684550346484b986a04 2/2

   A  p  p   l   i  c  a   t   i  o  n   N

  o   t  e ,

   A   0   2  -   0   1   2   2

   E ,

   2   0   1   1  -   0   9 ,

   E   l  a  n   d  e  r  s   S  v  e  r   i  g  e

   A   B

For more information please contact:

 ABB AB

FACTS

SE-721 64 Västerås,

SWEDEN

Phone: +46 (0)21 32 50 00Fax: +46 (0)21 32 48 10

www.abb.com/FACTS

220/90 kV 

90 kV 

5th

16,5 Mvar

5th33 Mvar

 TCR

66 Mvar

7th

16,5 Mvar

HOT STRIP

MILL

ROUGHING

MILL

Single-line diagram

  Pmax Qmax

  (MW) (Mvar)

HOT STRIP MILL 83 62

ROUGHING MILL 45 86