synchrounous machine
TRANSCRIPT
-
8/8/2019 Synchrounous Machine
1/22
Chapter 5 Synchronous Machines
Main features of synchronous machines:
A synchronous machine is an ac machine whose speed under steady-state conditions is
proportional to the frequency of the current in its armature.
The rotor, along with the magnetic field created by the dc field current on the rotor,rotates at the same speed as, or in synchronism with, the rotating magnetic field produced
by the armature currents, and a steady torque results.
Figure 4.12 Schematic views of three-phase generators: (a) two-pole, (b) four-pole, and
(c) Yconnection of the windings.
5.1 Introduction to Polyphase Synchronous Machines
Synchronous machines: Armature winding: on the stator, alternating current.
Field winding: on the rotor, dc power supplied by the excitation system.
Cylindrical rotor: for two- and four-pole turbine generators.
Salient-pole rotor: for multipolar, slow-speed, hydroelectric generators and for most
synchronous motors.
Acting as a voltage source:
Frequency determined by the speed of its mechanical drive (or prime mover).
The amplitude of the generated voltage is proportional to the frequency and the field
current.
tNk
tNk
mepphw
mpphwa
cos
2
poles
cos
=
= (4.45)
1
-
8/8/2019 Synchrounous Machine
2/22
mme2
poles
= (4.46)
tNktdt
dNk
dt
de mepphwmeme
p
phw
a
a
sincos
== (4.47)
tNke mepphwmea sin= (4.48)
pphwmepphwmemax 2 == NkfNkE (4.49)
pphwmepphwmerms 22
2== NkfNkfE
(4.50)
Synchronous generators can be readily operated in parallel: interconnected power
systems.
When a synchronous generator is connected to a large interconnected system containing
many other synchronous generators, the voltage and frequency at its armature terminals
are substantially fixed by the system.
It is often useful, when studying the behavior of an individual generator or group of
generators, to represent the remainder of the system as a constant-frequency,constant-voltage source, commonly referred to as an infinite bus.
Analysis of a synchronous machine connected to an infinite bus.
Torque equation:
RFfR
2
sin2
poles
2
FT
= (5.1)
where
= resultant air-gap flux per poleR
fF = mmf of the dc field winding
RF = electric phase angle between magnetic axes of R and fF
The minus sign indicates that the electromechanical torque acts in the direction to
bring the interacting fields into alignment.
In a generator, the prime-mover torque acts in the direction of rotation of the rotor,
and the electromechanical torque opposes rotation. The rotor mmf wave leads the
resultant air-gap flux.
In a motor, the electromechanical torque is in the direction of rotation, in opposition
to the retarding torque of the mechanical load on the shaft.
Torque-angle curve: Fig. 5.1.
Figure 5.1 Torque-angle characteristics.
2
-
8/8/2019 Synchrounous Machine
3/22
An increase in prime-mover torque will result in a corresponding increase in the
torque angle.
: pull-out torque at . Any further increase in prime-mover
torque cannot be balanced by a corresponding increase in synchronous
electromechanical torque, with the result that synchronism will no longer be
maintained and the rotor will speed up. loss of synchronism, pulling out of step.
maxTT =o90RF =
5.2 Synchronous-Machine Inductances; Equivalent Circuits
Figure 5.2 Schematic diagram of a two-pole,
three-phase cylindrical-rotor synchronous machine.
5.2.1 Rotor Self-Inductance
5.2.2 Stator-to-Rotor Mutual Inductances
5.2.3 Stator Inductances; Synchronous Inductance
5.2.4 Equivalent Circuit Equivalent circuit for the synchronous machine:
Single-phase, line-to-neutral equivalent circuits for a three-phase machine operating under
balanced, three-phase conditions.
sL = effective inductance seen by phase a under steady-state, balanced three-phase
machine operating conditions.
ses LX = : synchronous reactance
aR = armature winding resistance
afe = voltage induced by the field winding flux (generated voltage, internal voltage)
aI = armature current
av = terminal voltage
Motor reference direction:
faasaaa EIjXIRV ++= (5.23)
Generator reference direction:
faasaaa EIjXIRV += (5.24)
3
-
8/8/2019 Synchrounous Machine
4/22
Figure 5.3 Synchronous-machine equivalent circuits:
(a) motor reference direction and (b) generator reference direction.
XXX += als (5.25)
alX = armature leakage reactance
X = magnetizing reactance of the armature winding
RE = air-gap voltage or the voltage behind leakage reactance
Figure 5.4 Synchronous-machine equivalent circuit showing air-gap and
leakage components of synchronous reactance and air-gap voltage.
4
-
8/8/2019 Synchrounous Machine
5/22
5.4 Steady-State Power-Angle Characteristics
The maximum power a synchronous machine can deliver is determined by the maximum
torque that can be applied without loss of synchronism with the external system to which it is
connected. Both the external system and the machine itself can be represented as an impedance in
series with a voltage source.
Figure 5.11 (a) Impedance interconnecting two voltages; (b) phasor diagram.
5
-
8/8/2019 Synchrounous Machine
6/22
cos22 IEP = (5.34)
Z
EEI 21
= (5.35)
jeEE 11
= (5.36)
22 EE = (5.37)
ZjeZXjRZ =+= (5.38)
( ) ZZZ
jj
j
j
je
Z
Ee
Z
E
eZ
EeEIeI
=
== 2121 (5.39)
( ) ( ZZZ
E
Z
EI = coscoscos 21 ) (5.40)
( )2
2
2212 cos
Z
RE
Z
EEP Z = (5.41)
( ) 22
221
2 sin Z
RE
Z
EE
P Z += (5.42)
where
==
X
RZZ
1tan90 o (5.43)
( )2
2
1211 sin
Z
RE
Z
EEP Z = (5.44)
Frequently, 0and, , leads and power flows from source to .1E 2
E 1E 2
E
When 0
-
8/8/2019 Synchrounous Machine
7/22
Figure 5.12 Equivalent-circuit representation of
a synchronous machine connected to an external system.
Note that ,21EEP 1 XP , 21max EEP , and .
1
max
XP
In general, stability considerations dictate that a synchronous machine achieve
steady-state operation for a power angle considerably less than .o90
7
-
8/8/2019 Synchrounous Machine
8/22
Figure 5.14 Equivalent circuits and phasor diagrams for Example 5.7.
8
-
8/8/2019 Synchrounous Machine
9/22
9
-
8/8/2019 Synchrounous Machine
10/22
10
-
8/8/2019 Synchrounous Machine
11/22
5.3 Open- and Short-Circuit Characteristics5.3.1 Open-Circuit Saturation Characteristic and No-Load Rotational
Losses
Figure 5.5 Open-circuit characteristic of a synchronous machine.
5.3.2 Short-Circuit Characteristic and Load Loss
11
-
8/8/2019 Synchrounous Machine
12/22
Figure 5.6 Typical form of an open-circuit core-loss curve.
( )saafa jXRIE += (5.26)
Figure 5.7 Open- and short-circuit characteristics of a synchronous machine.
Figure 5.8 Phasor diagram for short-circuit conditions.
( )laaaR jXRIE += (5.27)
aca
aga
usI
VX
,
,
, = (5.28)
a
ratedas
I
VX
=, (5.29)
12
-
8/8/2019 Synchrounous Machine
13/22
Figure 5.9 Open- and short-circuit characteristics showing
equivalent magnetization line for saturated operating conditions.
fOfO
=SCR (5.30)
AFSC
AFNLSCR = (5.31)
13
-
8/8/2019 Synchrounous Machine
14/22
Figure 5.10 Typical form of short-circuit load loss and stray load-loss curves.
t
T
R
R
t
T
+
+=
5.234
5.234(5.32)
( )2eff,
ntaturecurrecircuitarmshort
lossloadcircuitshort
=aR (5.33)
14
-
8/8/2019 Synchrounous Machine
15/22
5.5 Steady-State Operating Characteristics
Figure 5.15 Characteristic form of synchronous-generator compounding curves.
15
-
8/8/2019 Synchrounous Machine
16/22
Figure 5.16 Capability curves of an 0.85 power factor, 0.80 short-circuit ratio,
hydrogen-cooled turbine generator. Base MVA is rated MVA at 0.5 psig hydrogen.
aaIVQP =+=22powerApparent (5.48)
Figure 5.17 Construction used for the derivation of a synchronous generator capability curve.
asa IjXVQjP += (5.49)
asafa IjXVE += (5.50)
222
2
=
++
s
faa
s
a
X
EV
X
VQP (5.51)
Figure 5.18 Typical form of synchronous-generator V curves.
16
-
8/8/2019 Synchrounous Machine
17/22
Figure 5.19 Losses in a three-phase, 45-kVA, Y-connected,
220-V, 60-Hz, six-pole synchronous machine.
17
-
8/8/2019 Synchrounous Machine
18/22
5.6 Effects of Salient Poles; Introduction to Direct-And
Quadrature-Axis Theory5.6.1 Flux and MMF Waves
18
-
8/8/2019 Synchrounous Machine
19/22
Figure 5.20 Direct-axis air-gap fluxes in a salient-pole synchronous machine.
( )33,3 3cos2 += tVE ea (5.52)
( )( ) ( )3333,3 3cos21203cos2 +=+= tVtVE eeb o (5.53)
( )( ) ( )3333,3 3cos21203cos2 +=+= tVtVE eeco
(5.54)
Figure 5.21 Quadrature-axis air-gap fluxes in a salient-pole synchronous machine.
Figure 5.22 Phasor diagram of a salient-pole synchronous generator.
5.3.2 Phasor Diagrams for Salient-Pole Machines
19
-
8/8/2019 Synchrounous Machine
20/22
Figure 5.23 Phasor diagram for a synchronous generator showing
the relationship between the voltages and the currents.
dlad XXX += (5.55)
qlaq XXX += (5.56)
Figure 5.24 Relationships between component voltages in a phasor diagram.
ba
ab
oa
ao =
(5.57)
aqa
q
qq
IXII
XI
oaba
abao ==
= (5.58)
qqddaaafa IjXIjXIRVE +++= (5.59)
20
-
8/8/2019 Synchrounous Machine
21/22
Figure 5.25 Generator phasor diagram for Example 5.9.
21
-
8/8/2019 Synchrounous Machine
22/22
22