synthetic inertia - supergen wind consortium 6th educational seminar
TRANSCRIPT
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
1/21
SU PE R G E N WIND CONSOR TIU M 6THE D U CA TIONA L SE MINA R
L O U G H B O R O U G H U N I V E R S I T Y 1 2 T H
S E P T E M B E R 2 0 1 1
Synthetic Inertia
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
2/21
Inertia
Inertia can be seen as the resistance to change
Inertia prevents the grid frequency suddenly changing andresults from synchronous machines having large, heavy,rotating generators
Asynchronous machines, such as variable speed windturbines, do not contribute to grid inertia
As the UK aims for 20% renewable electricity supply by 2020,power from wind turbines will make up a larger percentage ofthe produced power. Unless they can produce a syntheticinertia, the inertia of the grid will be reduced
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
3/21
Synthetic Inertia
Inertia can be seen as the conversion of kineticenergy of the rotating mass to electrical energy,causing the frequency to drop.
Synthetic inertia can therefore be produced byincreasing power output during a frequency drop
Luckily, wind turbines have a large store of kineticenergy...
DemSupm
m PP
dt
dJ
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
4/21
How much Energy is Required?
A National Gridinvestigation intosynthetic inertia
concluded that a powerincrease of 5-10% duringa grid frequency drop to49.2Hz in approximately
8 seconds would besufficient
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
5/21
How much energy is available?
A typical measure used forcomparing the inertia ofdifferent generators is known asthe inertia constant,H
An average value for a largegenerator would beapproximately 6s
For the Supergen 5MWExemplar turbine this value
works out to be approximately6s
Hence the wind turbine has thepotential to supply a similarsynthetic inertia response as asynchronous machines inertialresponse.
RatedPower
EH
2
2
1
mJE
DemSup
m
m PPdt
d
J
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
6/21
How do we Access this Kinetic Energy?
Power is rotational speed multiplied by torque
By artificially increasing the torque the power will
also increase in proportion.
This will cause the turbine blades to slow down
Effectively, the kinetic energy in the blades is beingconverted to electrical energy
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
7/21
The Controller A Conundrum
The additional torqueneeds to be demanded bythe controller
The original (inner)controller will detect thereduction in rotationalspeed and decrease torquedemand
This will cancel out whatwe wanted to do!
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
8/21
Controller Solution
In order to fool thecontroller, a dummyspeed input is required
The dummy speed (ad)cancels out the reductionin speed caused by the
additional torque (Tad)
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
9/21
The Torque Controller
The torque controllergenerates a value of Tad,
which is added to the originalcontrollers demanded torqueTdem
Inertia is proportional to thechange in frequency As the turbine slows, more
torque is required tomaintain the same poweroutput
In order to avoid anunrealistic torque demand, amax power limiter is used
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
10/21
The Dummy Speed Controller
The synthetic inertiacontroller must providea dummy speed to foolthe original controller
By looking at the Bodeplot from torquedemand to generatorspeed, a similar, simplertransfer function can bededuced
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
11/21
Hysteresis Loop
The dummy speed controller is only required below rated wind speed
It is undesirable for the controller to turn on or turn off during a frequency dropso a hysteresis loop is put in place
The values of BdLower and BdUpper are set so that the likely hood of the turbinepassing into the other mode of operation is low
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
12/21
Anti-Stall Control
An addition to thecontroller is required toensure that the machinedoes not enter stall
The red line is describedby T=K2
This value is normallyhigher than Ttot
On the line the values areequal and above the linethe Ttot is the higher value
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
13/21
Minimum Generator Speed
It is desirable to preventthe wind turbine operating
below its minimumgenerator speed
This addition to thecontroller graduallyreduces the torquedemand as the generatorapproaches its minimumspeed
Once at the minimumspeed, no additionaltorque is requested
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
14/21
Interaction With the Drive-Train Frequency
This technique requires asudden increase in torque
Interaction with thenatural frequency of thedrive train causes poweroscillation
Techniques to minimisethis cause an unacceptabledelay in producing theincrease in power
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
15/21
Test Simulations
Simulations run usingSimulink software
Frequency dropmodelled as shown.Based on the worst case
detailed in the NationalGrid Report
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
16/21
Graph Displaying Additional Power Generated
Red 13m/s windBlue 10m/s windGreen 7m/s wind
The additional powerpeaks at approximately500kW, 10% of the ratedpower
When below rated speedthere is a recovery periodof 40 60 seconds
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
17/21
Graph Displaying Increase in Total TorqueDemand
Red 13m/s wind
Blue 10m/s wind
Green 7m/s wind
The increase in torque is,
as expected, higher atlower wind speeds
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
18/21
Graph Displaying Increase in Generator Speed
Red 13m/s windBlue 10m/s windGreen 7m/s wind
Due to greater torqueincrease, the generatorspeed dips lower at 7m/sthan at 10m/s
At 13m/s there is an
oscillation caused becausepitch controller is slowerthan the torque demandcontroller
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
19/21
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
20/21
Future Work
Additional work could be done to investigate the impactof this technique on the lifetime of the turbine and/or onthe power electronics
It would be interesting to see how this technique could beapplied over a whole wind farm, maybe some turbinesproducing more extra power than others depending onconditions?
It would also be of interest to investigate if wind turbinescould supply some of the primary response as well as theinertial response especially as they increase in size
-
8/12/2019 Synthetic Inertia - Supergen Wind Consortium 6th Educational Seminar
21/21
Any Questions
Any Questions?