sysnchronous generator transient analysis2

Upload: mnsatyani

Post on 09-Apr-2018

243 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    1/12

    SYSNCHRONOUS GENERATOR

    TRANSIENT ANALYSIS

    NAME: - M. S. NakandalaINDEX NO: - 080314MFIELD: - EEDATE OF PER: -25.10.2010DATE OF SUB: - 06.12.2010

    OBSERVATION SHEET

    NAME: - M. S. NakandalaINDEX NO: - 080314MFIELD: - EEDATE OF PER: - 25.10.2010INSTRUCTED BY: -

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    2/12

    a) Obtaining of short circuit armature current oscillogram

    Pre-short circuit line voltage = 35 VSteady short circuit current = 2.3 AGenerator speed = 1507 rpmNumber of generator pole pairs = 2

    b) Obtaining of field current oscillogram

    Steady state field current = 0.1A

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    3/12

    d) Slip test

    Minimum Phase current = 1.7AMaximum phase current = 1.85AMinimum line voltage = 20 VMaximum line voltage = 21 VGenerator speed = 1470 rpm

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    4/12

    CALCULATION

    a. Obtaining of short circuit armature current oscillogram

    T(ms) Armature (A)

    0 13.5

    10 10.5

    20 8.25

    30 7.75

    40 7

    50 6.75

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    5/12

    60 6.25

    70 5.75

    80 5.5

    90 5.25

    100 5110 4.75

    120 4.5

    130 4.25

    140 4.25

    150 4.25

    160 4.25

    170 4

    180 4

    190 4

    200 4

    210 4

    220 4

    230 3.75

    240 3.5

    250 3.75

    260 3.75

    270 3.75

    280 3.63

    290 3.63

    300 3.5

    310 3.5

    320 3.5

    330 3.5

    340 3.5

    350 3.5

    From the Graph, From theory,

    A = 12.69A

    B =3.5A== 17.8/2 BVX

    Sd

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    6/12

    21.203/35 ==SV

    == 252.2/2'' AVX Sd

    T(ms) )(

    0 9.13

    5 8.178769

    10 7.280297

    15 6.427746

    20 5.714704

    25 4.995176

    30 4.443571

    35 3.83469340 3.423728

    45 2.906233

    50 2.618125

    55 2.175670

    60 1.995472

    65 1.614460

    70 1.529879

    75 1.199277

    80 1.200496

    85 0.911657

    90 0.991153

    95 0.737635

    100 0.89

    105 0.667384

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    7/12

    msT

    msD

    d 75.58'

    75.58

    =

    =

    =

    =

    263.2'

    129.9

    dX

    C

    Td''= 3.16 ms

    The open circuit transient and sub transient time constants can also be obtained,

    Tdo'= Td' XdXd'

    Tdo'= 58.75 8.172.63 = 182.50 ms

    Tdo''= Td'' Xd'Xd''

    Tdo''= 3.16 2.2632.252 = 3.18 ms

    T(ms) Armature (A)

    0 27.510 21

    20 16.5

    30 15.5

    40 14

    50 13.5

    60 13.5

    T(ms) )( Y

    0 6.711

    5 5.825462

    10 4.962770

    15 4.136171

    20 3.350680

    25 2.605238

    30 1.894530

    35 1.210465

    40 0.543320

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    8/12

    70 11.5

    80 11

    90 10.5

    100 10

    110 9.5

    120 9130 8.5

    140 8.5

    150 8.5

    160 8.5

    170 8

    Ta = 7.1994 ms

    Field current variation following a short circuit

    += te

    T

    Te

    T

    Te

    X

    XXIII Tat

    d

    kddTt

    d

    kddTt

    d

    ddfff cos

    '')

    ''1(

    '

    )'( /''/'/00

    Assume no dampers. ThereforeTkd = 0

    If=0.1+ 0.1 8.17-2.2632.263[ e-t58.75 -1-0e-t3.16- 0]

    If=0.1+ 0.261[ e-t58.75 -e-t3.16]

    Time (ms) If0 0.110 0.30912720 0.28522830 0.25661040 0.23211450 0.21143760 0.193995

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    9/12

    70 0.17928480 0.16687590 0.156408100 0.147580110 0.140132120 0.133851

    130 0.128553140 0.124084150 0.120314160 0.117135170 0.114453180 0.112191190 0.110283200 0.110283

    Armature voltage on sudden open circuit from a steady short circuit,

    Va=2Vscost+0- 2VsXd-X'dX''de-tTdo cost+0-2VsXd-X''dXde-tT'do cost+0

    Lets assume o = 0 and w = 314.16

    Va=2Vscost- 2VsXd-X'dX''de-tTdo' cost-2VsX'd-X''dXde-tT''do cost

    Va=28.58cos314.16t- 74.96 e-t182.5 cos314.16t+ 0.038 e-t3.18cos (314.16t)

    Time (ms) Va (V)0 -46.34210 6.19121820 36.9518330 -14.90964240 -26.34220

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    10/12

    50 19.01405160 16.17591170 -19.24569480 -7.66366190 16.657707100 1.542538

    110 -12.435448120 1.922312130 7.732483140 -2.885151150 -3.536619160 1.829280170 0.575103180 0.546291190 0.736901200 -3.448195210 -0.305235

    220 6.104372230 -1.672241240 -7.862695250 4.764766260 8.264291270 -8.388188280 -7.086703290 11.894220300 4.355570310 -14.659071320 -0.326669330 16.162164340 -4.557087350 -16.047549360 9.727125370 14.162948380 -14.561356390 -10.573992400 18.458777410 5.553778420 -20.908704430 0.449740440 21.547857450 -6.864051460 -20.200138470 13.054196480 16.895844490 -18.389985500 -11.869240

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    11/12

    Slip test parameters

    Xd= Va,pk-pkmaxIa,pk-pk min

    Xd= 211.7*3 = 7.13

    XQ= Va,pk-pkminIa,pk-pk max

    XQ= 201.85*3 = 6.24

  • 8/8/2019 Sysnchronous Generator Transient Analysis2

    12/12

    DISCUSSION

    When comparing Xd value obtained from the slip test and the short circuit armaturecurrent oscillogram there is a huge difference between them.

    When we compare the theoretical and practical graph of the variation of field current atshort circuit test, it seems both are having same shape. But the practical curve takes more time toacquire the steady state, compare with theoretical curve. This may occur due to the effect ofdamping effect in real situation. Also theoretical oscillograms are very smooth. But in practicalcase they are not like that, because they have been affected to noise introduced by the externaldevices.

    In short circuit oscillogram there are 4 components in the transient behavior. Transient component Sub transient component DC offset component Steady state component

    Transient and sub transient components rapidly vary with the time, but transient componenttakes much time to decay than sub transient component. Generally sub transient period lasts for3-4 cycles of current. However transient period is long and lasts for some hundreds of cycles.DC offset current is caused due to the armature reaction.

    It is important to know whether the generator can withstand against transient behaviors and itis having correct damping. The parameters we calculated by using the observations of short

    circuit study are important when designing protection schemes to the synchronous generator.Therefore short circuit study is very important.