sysnchronous generator transient analysis2
TRANSCRIPT
-
8/8/2019 Sysnchronous Generator Transient Analysis2
1/12
SYSNCHRONOUS GENERATOR
TRANSIENT ANALYSIS
NAME: - M. S. NakandalaINDEX NO: - 080314MFIELD: - EEDATE OF PER: -25.10.2010DATE OF SUB: - 06.12.2010
OBSERVATION SHEET
NAME: - M. S. NakandalaINDEX NO: - 080314MFIELD: - EEDATE OF PER: - 25.10.2010INSTRUCTED BY: -
-
8/8/2019 Sysnchronous Generator Transient Analysis2
2/12
a) Obtaining of short circuit armature current oscillogram
Pre-short circuit line voltage = 35 VSteady short circuit current = 2.3 AGenerator speed = 1507 rpmNumber of generator pole pairs = 2
b) Obtaining of field current oscillogram
Steady state field current = 0.1A
-
8/8/2019 Sysnchronous Generator Transient Analysis2
3/12
d) Slip test
Minimum Phase current = 1.7AMaximum phase current = 1.85AMinimum line voltage = 20 VMaximum line voltage = 21 VGenerator speed = 1470 rpm
-
8/8/2019 Sysnchronous Generator Transient Analysis2
4/12
CALCULATION
a. Obtaining of short circuit armature current oscillogram
T(ms) Armature (A)
0 13.5
10 10.5
20 8.25
30 7.75
40 7
50 6.75
-
8/8/2019 Sysnchronous Generator Transient Analysis2
5/12
60 6.25
70 5.75
80 5.5
90 5.25
100 5110 4.75
120 4.5
130 4.25
140 4.25
150 4.25
160 4.25
170 4
180 4
190 4
200 4
210 4
220 4
230 3.75
240 3.5
250 3.75
260 3.75
270 3.75
280 3.63
290 3.63
300 3.5
310 3.5
320 3.5
330 3.5
340 3.5
350 3.5
From the Graph, From theory,
A = 12.69A
B =3.5A== 17.8/2 BVX
Sd
-
8/8/2019 Sysnchronous Generator Transient Analysis2
6/12
21.203/35 ==SV
== 252.2/2'' AVX Sd
T(ms) )(
0 9.13
5 8.178769
10 7.280297
15 6.427746
20 5.714704
25 4.995176
30 4.443571
35 3.83469340 3.423728
45 2.906233
50 2.618125
55 2.175670
60 1.995472
65 1.614460
70 1.529879
75 1.199277
80 1.200496
85 0.911657
90 0.991153
95 0.737635
100 0.89
105 0.667384
-
8/8/2019 Sysnchronous Generator Transient Analysis2
7/12
msT
msD
d 75.58'
75.58
=
=
=
=
263.2'
129.9
dX
C
Td''= 3.16 ms
The open circuit transient and sub transient time constants can also be obtained,
Tdo'= Td' XdXd'
Tdo'= 58.75 8.172.63 = 182.50 ms
Tdo''= Td'' Xd'Xd''
Tdo''= 3.16 2.2632.252 = 3.18 ms
T(ms) Armature (A)
0 27.510 21
20 16.5
30 15.5
40 14
50 13.5
60 13.5
T(ms) )( Y
0 6.711
5 5.825462
10 4.962770
15 4.136171
20 3.350680
25 2.605238
30 1.894530
35 1.210465
40 0.543320
-
8/8/2019 Sysnchronous Generator Transient Analysis2
8/12
70 11.5
80 11
90 10.5
100 10
110 9.5
120 9130 8.5
140 8.5
150 8.5
160 8.5
170 8
Ta = 7.1994 ms
Field current variation following a short circuit
+= te
T
Te
T
Te
X
XXIII Tat
d
kddTt
d
kddTt
d
ddfff cos
'')
''1(
'
)'( /''/'/00
Assume no dampers. ThereforeTkd = 0
If=0.1+ 0.1 8.17-2.2632.263[ e-t58.75 -1-0e-t3.16- 0]
If=0.1+ 0.261[ e-t58.75 -e-t3.16]
Time (ms) If0 0.110 0.30912720 0.28522830 0.25661040 0.23211450 0.21143760 0.193995
-
8/8/2019 Sysnchronous Generator Transient Analysis2
9/12
70 0.17928480 0.16687590 0.156408100 0.147580110 0.140132120 0.133851
130 0.128553140 0.124084150 0.120314160 0.117135170 0.114453180 0.112191190 0.110283200 0.110283
Armature voltage on sudden open circuit from a steady short circuit,
Va=2Vscost+0- 2VsXd-X'dX''de-tTdo cost+0-2VsXd-X''dXde-tT'do cost+0
Lets assume o = 0 and w = 314.16
Va=2Vscost- 2VsXd-X'dX''de-tTdo' cost-2VsX'd-X''dXde-tT''do cost
Va=28.58cos314.16t- 74.96 e-t182.5 cos314.16t+ 0.038 e-t3.18cos (314.16t)
Time (ms) Va (V)0 -46.34210 6.19121820 36.9518330 -14.90964240 -26.34220
-
8/8/2019 Sysnchronous Generator Transient Analysis2
10/12
50 19.01405160 16.17591170 -19.24569480 -7.66366190 16.657707100 1.542538
110 -12.435448120 1.922312130 7.732483140 -2.885151150 -3.536619160 1.829280170 0.575103180 0.546291190 0.736901200 -3.448195210 -0.305235
220 6.104372230 -1.672241240 -7.862695250 4.764766260 8.264291270 -8.388188280 -7.086703290 11.894220300 4.355570310 -14.659071320 -0.326669330 16.162164340 -4.557087350 -16.047549360 9.727125370 14.162948380 -14.561356390 -10.573992400 18.458777410 5.553778420 -20.908704430 0.449740440 21.547857450 -6.864051460 -20.200138470 13.054196480 16.895844490 -18.389985500 -11.869240
-
8/8/2019 Sysnchronous Generator Transient Analysis2
11/12
Slip test parameters
Xd= Va,pk-pkmaxIa,pk-pk min
Xd= 211.7*3 = 7.13
XQ= Va,pk-pkminIa,pk-pk max
XQ= 201.85*3 = 6.24
-
8/8/2019 Sysnchronous Generator Transient Analysis2
12/12
DISCUSSION
When comparing Xd value obtained from the slip test and the short circuit armaturecurrent oscillogram there is a huge difference between them.
When we compare the theoretical and practical graph of the variation of field current atshort circuit test, it seems both are having same shape. But the practical curve takes more time toacquire the steady state, compare with theoretical curve. This may occur due to the effect ofdamping effect in real situation. Also theoretical oscillograms are very smooth. But in practicalcase they are not like that, because they have been affected to noise introduced by the externaldevices.
In short circuit oscillogram there are 4 components in the transient behavior. Transient component Sub transient component DC offset component Steady state component
Transient and sub transient components rapidly vary with the time, but transient componenttakes much time to decay than sub transient component. Generally sub transient period lasts for3-4 cycles of current. However transient period is long and lasts for some hundreds of cycles.DC offset current is caused due to the armature reaction.
It is important to know whether the generator can withstand against transient behaviors and itis having correct damping. The parameters we calculated by using the observations of short
circuit study are important when designing protection schemes to the synchronous generator.Therefore short circuit study is very important.