t astm e119-95a fire tests of building r construction and ... · t e s t r e p o r t omega point...

36
TT T T EE E E SS S S TT T T RR R R EE E E PP P P OO O O RR R R TT T T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f) 210-635-8101 800-966-5253 www.opl.com ASTM E119-95a Fire Tests of Building Construction and Materials Sandwich Panel Wall System Project No. 15328-103870 ONE-HOUR FIRE RESISTANCE TEST OF A FOAM-FILLED SANDWICH PANEL WALL ASSEMBLY UNDER NONBEARING CONDITIONS. September 25, 1998 Prepared for: Structall Building Systems 350 Burbank Road Oldsmar, FL 34677

Upload: vunguyet

Post on 12-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

TTTTEEEE

SSSSTTTT

RRRREEEE

PPPPOOOO

RRRRTTTT

OMEGA POINTLABORATORIES, INC.16015 Shady Falls Road

Elmendorf, TX 78112(v) 210-635-8100(f) 210-635-8101

800-966-5253www.opl.com

ASTM E119-95aFire Tests of Building

Construction and Materials

Sandwich Panel Wall SystemProject No. 15328-103870

ONE-HOUR FIRE RESISTANCE TEST OF A FOAM-FILLEDSANDWICH PANEL WALL ASSEMBLY UNDER

NONBEARING CONDITIONS.

September 25, 1998

Prepared for:

Structall Building Systems350 Burbank Road

Oldsmar, FL 34677

Page 2: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

OM

EGA POINT

LA

B

O R A T ORIES

®

Omega Point Laboratories, Inc.16015 Shady Falls Road

Elmendorf, Texas 78112-9784210-635-8100 / FAX: 210-635-8101 / 800-966-5253

www.opl.com / e-mail: [email protected]

ACCREDITED

No. 0689-01

Abstract

Sandwich panels consisting of EPS foam panels (4" thick, 1.0 lb/ft3) clad oneach surface with 26 GA. steel sheet were assembled into a wall and coveredwith two layers of 5/8" Type X gypsum wallboard on each side (over 25 GA.furring channels spaced 16" o.c.). The symmetrical construction, assembledand tested as described herein, successfully met the conditions of acceptanceas outlined in ASTM Method E119-95a FIRE TESTS OF BUILDINGCONSTRUCTION AND MATERIALS for a nonbearing fire endurancerating of 60 min (1 h) from either side.

This report is for the exclusive use of the client named herein. Omega Point Laboratories, Inc. authorizes theclient to reproduce this report only if reproduced in its entirety. The test specimen identification is as providedby the client and Omega Point Laboratories, Inc. accepts no responsibility for any inaccuracies therein. Thedescription of the test procedure, as well as the observations and results obtained, contained herein are true andaccurate within the limits of sound engineering practice. These results are valid only for the specimens testedand may not represent the performance of other specimens from the same or other production lots. This reportdoes not imply certification of the product by Omega Point Laboratories, Inc. Any use of the Omega PointLaboratories name, any abbreviation thereof or any logo, mark, or symbol therefor, for advertising material mustbe approved in writing in advance by Omega Point Laboratories, Inc. The client must have entered into and beactively participating in a Listing & Follow-up Service program. Products must bear labels with the OmegaPoint Laboratories Certification Mark to demonstrate acceptance by Omega Point Laboratories, Inc. into theListing program.

September 25, 1998 Deggary N. Priest DatePresident

Reviewed and approved:

William E. Fitch, P.E. No. 55296 September 25, 1998 Date

Page 3: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems Page iii

LA

BORATOR

IES

OM

EGA POIN

T

TABLE OF CONTENTS

ITEM PAGE

Introduction 1

Test Procedure 3

Test Specimen Construction 7

Test Results and Observations 8

Conclusions 10

Appendices

Appendix A: Construction Drawings 11

Appendix B: Thermocouple Locations 13

Appendix C: Thermocouple Data 21

Appendix D: Construction Photographs 23

Last Page of Report 31

Page 4: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems Page 1

LA

BO R AT ORIE

S

OM

EGA POINT

INTRODUCTION 1

"The performance of walls, columns, floors, and other building members under fireexposure conditions is an item of major importance in securing constructions thatare safe, and that are not a menace to neighboring structures nor to the public.Recognition of this is registered in the codes of many authorities, municipal andother. It is important to secure balance of the many units in a single building, andof buildings of like character and use in a community; and also to promoteuniformity in requirements of various authorities throughout the country. To dothis it is necessary that the fire-resistive properties of materials and assemblies bemeasured and specified according to a common standard expressed in terms thatare applicable alike to a wide variety of materials, situations, and conditions ofexposure.

Such a standard is found in the methods that follow. They prescribe a standardexposing fire of controlled extent and severity. Performance is defined as the periodof resistance to standard exposure elapsing before the first critical point in behavioris observed. Results are reported in units in which field exposures can be judgedand expressed.

The methods may be cited as the "Standard Fire Tests," and the performance orexposure shall be expressed as "2-h," "6-h," "1/2-h," etc.

When a factor of safety exceeding that inherent in the test conditions is desired, aproportional increase should be made in the specified time-classification period."

The ASTM E119 test procedure is identical or very similar to the following standardtest methods:

UL 263UBC 7-1

NFPA 251ANSI A2.1

"1. Scope1.1 The test methods described in this fire-test-response standard are applicableto assemblies of masonry units and to composite assemblies of structural materialsfor buildings, including bearing and other walls and partitions, columns, girders,beams, slabs, and composite slab and beam assemblies for floors and roofs. Theyare also applicable to other assemblies and structural units that constitute

1 American Society for Testing and Materials, 1996 Annual Book of Standards, ASTM E119-95aStandard Methods of FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS.

Page 5: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems Page 2

LA

BO R AT ORIE

S

OM

EGA POINT

permanent integral parts of a finished building.1.2 It is the intent that classifications shall register performance during theperiod of exposure and shall not be construed as having determined suitability foruse after fire exposure.1.3 This standard should be used to measure and describe the properties ofmaterials, products, or assemblies in response to heat and flame under controlledlaboratory conditions and should not be used to describe or appraise the fire hazardor fire risk of materials, products, or assemblies under actual fire conditions.However, results of this test may be used as elements of a fire risk assessment whichtakes into account all of the factors which are pertinent to an assessment of the firehazard of a particular end use.

Note 1 - A method of fire hazard classification based on rate of flame spread iscovered in ASTM Method E84, Test for Surface Burning Characteristics ofBuilding Materials.

1.4 The results of these tests are one factor in assessing fire performance ofbuilding construction and assemblies. These methods prescribe a standard fireexposure for comparing the performance of building construction assemblies.Application of these test results to predict the performance of actual buildingconstruction requires careful evaluation of test conditions.

1.5 The values stated in inch-pound units are to be regarded as the standard.The values given in parentheses are for information only.

1.6 This standard does not purport to address all of the safety concerns if any,associated with its use. It is the responsibility of the user of this standard toestablish appropriate safety and health practices and determine the applicability ofregulatory limitation prior to use."

"4. Significance and Use4.1 This test method is intended to evaluate the duration for which the types ofassemblies noted in 1.1 will contain a fire, or retain their structural integrity orexhibit both properties dependent upon the type of assembly involved during apredetermined test exposure.4.2 The test exposes a specimen to a standard fire exposure controlled to achievespecified temperatures throughout a specified time period. In some instances, thefire exposure may be followed by the application of a specified standard fire hosestream. The exposure, however, may not be representative of all fire conditionswhich may vary with changes in the amount, nature and distribution of fireloading, ventilation, compartment size and configuration, and heat sinkcharacteristics of the compartment. It does, however, provide a relative measure offire performance of comparable assemblies under these specified fire exposure

Page 6: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems Page 3

LA

BO R AT ORIE

S

OM

EGA POINT

conditions. Any variation from the construction or conditions (that is, size, methodof assembly, and materials) that are tested may substantially change theperformance characteristics of the assembly.4.3 The test standard provides for the following:4.3.1 In walls, partitions and floor or roof assemblies:4.3.1.1 Measurement of the transmission of heat.4.3.1.2 Measurement of the transmission of hot gases through the assembly,sufficient to ignite cotton waste.4.3.1.3 For load bearing elements, measurement of the load carrying ability ofthe test specimen during the test exposure.

4.3.2 For individual load bearing assemblies such as beams and columns:Measurement of the load carrying ability under the test exposure with someconsideration for the end support conditions (that is, restrained or not restrained).

4.4 The test standard does not provide the following:4.4.1 Full information as to performance of assemblies constructed withcomponents or lengths other than those tested.4.4.2 Evaluation of the degree by which the assembly contributes to the firehazard by generation of smoke, toxic gases, or other products of combustion.4.4.3 Measurement of the degree of control or limitation of the passage of smokeor products of combustion through the assembly.4.4.4 Simulation of the fire behavior of joints between building elements such asfloor-wall or wall-wall, etc., connections.4.4.5 Measurement of flame spread over surface of tested element.4.4.6 The effect of fire endurance of conventional openings in the assembly, thatis electrical receptacle outlets, plumbing pipe, etc., unless specifically provided forin the construction tested."

TEST PROCEDUREVertical Test Furnace

The test furnace is designed to allow the specimen to be uniformly exposed to thespecified time-temperature conditions. It is fitted with 39 symmetrically-locatedpropane gas burners designed to allow an even heat flux distribution across the faceof a test specimen. Furnace pressures may be maintained at any value from +0.04"W.C. to -0.20" W.C. It must be realized that any full-size vertical fire test furnacewill have a pressure difference between the bottom and top of approximately 0.10in. W.C. after operating temperatures are reached. For this reason, the furnace is

Page 7: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems Page 4

LA

BO R AT ORIE

S

OM

EGA POINT

operated by controlling the pressure within the furnace (with respect to thelaboratory ambient pressure) by regulating the pressure at a specific horizontalplane in the furnace. Many times the furnace pressure will be adjusted so that the"neutral pressure plane" (that where the pressure difference between the furnaceinterior and the laboratory is zero) is at a desired location: for instance; at the top,at a point 1/3 of the way down from the top, or at the bottom of the specimen.

The temperature within the furnace is determined to be the mathematical averageof thermocouples located symmetrically within the furnace and positioned twelveinches away from the exposed face of the test specimen. The materials used in theconstruction of these thermocouples are those suggested in the test standard.During the performance of a fire exposure test, the furnace temperatures aremonitored at least every 15 seconds and displayed for the furnace operator to allowcontrol along the specified temperature curve. A paper printout of the data isproduced every 30 seconds, and all data is saved to hard disk at intervals of onceper minute unless more often is requested.

The fire exposure is controlled to conform with the standard time-temperaturecurve shown in Figure 1, as determined by the table below:

3603002401801206 0000

250

500

750

1000

1250

1500

1750

2000

2250

2500

Time (min)

Tem

pera

ture

(°F)

Time(min)

05

1020306090

120180240300360420480

Temperature(°F)

681000130014621550170017921850192520002075215022252300

Figure 1

The furnace interior temperature during a test is controlled such that the areaunder the time•temperature curve is within 10% of the corresponding area underthe standard time•temperature curve for 1 hour or less tests, 7.5% for those less

Page 8: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems Page 5

LA

BO R AT ORIE

S

OM

EGA POINT

than 2 hours and 5% for those tests of 2 hours or more duration.

Temperatures of Unexposed Surfaces

Temperatures of unexposed surfaces are monitored using 24 gauge, Type Kthermocouples placed under 6 in. x 6 in. x 0.4 in. thick dry, felted pads as describedin the standard. Temperature readings are taken at not less than nine points onthe surface, at intervals not exceeding 1.0 minute. The temperature on theunexposed surface of a test specimen during the test is taken to be the averagevalue of all thermocouples.

Applied Load

If required, this test method may be used to expose a horizontal or vertical assemblyto fire while maintaining a live load on test specimen. This is accomplished byapplying a uniform load hydraulically, with actuators designed for that purpose.

Fire Endurance Test

The fire exposure is continued on the specimen with its applied load if applicable,until failure occurs, or until the specimen has withstood the test conditions for thedesired fire endurance rating.

Hose Stream Test

"11.1 Where required by the conditions of acceptance, subject a duplicate specimento a fire exposure test for a period equal to one half of that indicated as theresistance period in the fire endurance test, but not for more than 1 h, immediatelyafter which subject the specimen to the impact, erosion, and cooling effects of a hosestream directed first at the middle and then at all parts of the exposed face, changesin direction being made slowly.

11.2 Exemption - The hose stream test shall not be required in the case ofconstructions having a resistance period, indicated in the fire endurance test, of lessthan 1 h.

11.3 Optional Program - The submitter may elect, with the advice and consent ofthe testing body, to have the hose stream test made on the specimen subjected tothe fire endurance test and immediately following the expiration of the fireendurance test.

11.4 Stream Equipment and Details - The stream shall be delivered through a21/2-in. (64-mm) hose discharging through a National Standard Playpipe ofcorresponding size equipped with a 11/8-in. (28.5-mm) discharge tip of the standard-

Page 9: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems Page 6

LA

BO R AT ORIE

S

OM

EGA POINT

taper smooth-bore pattern without shoulder at the orifice. The water pressure andduration of the application shall be as prescribed in Table 1.

TABLE 1 Conditions For Hose Stream TestWater Pressure Duration of

at Base of Application,Resistance Period Nozzle, psi min/100 ft2 (9 m2)

(kPa) exposed area8 h and over45 (310) 64 h and over if less than 8 h 45 (310) 52 h and over if less than 4 h 30 (207) 21/211/2 h and over if less than 2 h 30 (207) 11/21 h and over if less than 11/2 h 30 (207) 1Less than 1 h, if desired 30 (207) 1

11.5 Nozzle Distance - The nozzle orifice shall be 20 ft (6-m) from the center of theexposed surface of the test specimen if the nozzle is so located that when directed atthe center its axis is normal to the surface of the test specimen. If otherwiselocated, its distance from the center shall be less than 20 ft by an amount equal to 1ft (305-mm) for each 10 deg of deviation from the normal."

Correction Factor

When the indicated resistance period is 1/2 h or over, determined by the failurecriteria of the standard, a correction shall be applied for variation of the furnaceexposure from that prescribed, where it will affect the classification. This is to bedone by multiplying the indicated period by two thirds of the difference in areabetween the curve of average furnace temperature and the standard curve for thefirst three fourths of the period and dividing the product by the area between thestandard curve and a base line of 68°F (20°C) for the same part of the indicatedperiod, the latter area increased by 3240°F•min to compensate for the thermal lagof the furnace thermocouples during the first part of the test. For a fire exposure inthe test higher than standard, the indicated resistance period shall be increased bythe amount of the correction. For a fire exposure in the test lower than standard,the indicated resistance period shall be similarly decreased for fire exposure belowstandard. The correction is accomplished by mathematically adding the correctionfactor, C, to the indicated resistance period.

Page 10: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems Page 7

LA

BO R AT ORIE

S

OM

EGA POINT

The correction can be expressed by the following equation:

C =2 I (A – As)3 (As + L)

where:

C = correction in the same units as I,I = indicated fire-resistance period,

A = area under the curve of indicated average furnace temperature for thefirst three fourths of the indicated period,

As = area under the standard furnace curve for the same part of theindicated period, and

L = lag correction in the same units as A and As (54°F•h or 30°C•h(3240°F•min or 1800°C•min))

TEST SPECIMEN CONSTRUCTION

Pre-manufactured steel faced, polystyrene foam filled sandwich panels weredelivered to the laboratory by the client, bearing the inspection mark of PFSCorporation (NERQA-251). The manufacturer supplied the following information:

Steel Skins: 26 GA. (0.019 min ± 0.0030 inches) hot dip galvanized. SD50 G90,with a minimum yield stress of 50 ksi.

EPS Foam: 1.0 pcf nominal density, furnished by Carpenter (NER-QA 204).

Adhesive: Mor-Ad M-640 & 642, manufactured by Morton Chemical, classifiedas Type II, Class 2.

The panels were three feet wide, ten feet long and nominally four inches thick. Theedges were designed to snap into each other (see drawing, Appendix A) and lock intoplace. The test wall was constructed by snapping together three 36" wide panelsand cutting a fourth panel to 12" wide, so that the finished wall was 120" tall and120" wide. The assembly was then placed into a 120" x 120" masonry-linedrestraining frame and screwed into 2" x 2" x 1/8" steel angle to secure it along theperimeter on both faces.

25 GA. galvanized steel furring channels (23/8" wide at the base, 11/8" wide at thecrown and 1" high) were screwed to both sides of the panel wall, spaced vertically at16" o.c. and attached with #8 x 9/16" Tek screws spaced 6" o.c.

Page 11: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems Page 8

LA

BO R AT ORIE

S

OM

EGA POINT

An inner layer of 5/8" Type X fire resistant drywall (48" x 120" x 5/8" Firecode, USGypsum Co.) was attached over the furring strips on each side, installedhorizontally, with joints offset 24" from one side of the wall to the other. Thegypsum was attached using #6 x 11/4" self drilling screws, spaced 12" o.c.

An outer layer of 5/8" Type X fire resistant drywall (48" x 120" x 5/8" Firecode, USGypsum Co.) was attached over the inner layers on each side, installed horizontally,with joints offset 24" from one side of the wall to the other. The gypsum wasattached using #6 x 17/8" self drilling screws, spaced 8" o.c. All joints and screwheads on both sides of the wall were then covered with paper and/or gypsum jointcompound in the normal manner. The unexposed surface of the wall was theninstrumented with eleven thermocouples as indicated in Appendix B.

TEST RESULTS AND OBSERVATIONS

The wall assembly was placed in front of the Laboratory’s test furnace onSeptember 16, 1998. The ambient temperature at the start of the test was 72°F,with a relative humidity of 90%. Throughout the fire test, the pressure differentialbetween the inside of the furnace (measured at a point 1/3 of the way down from thetop center of the wall specimen) and the laboratory ambient air was maintained at -0.03 inches of water column, which resulted in a neutral pressure at the top of thetest article.

Observations made during the test are as follows:

Time ( min:sec ) Observation

0:00 Furnace fired at 8:52 a.m.0:32 Gypsum paper turning brown.1:22 Gypsum paper ignited.1:55 Gypsum paper fully consumed.3:57 Paper tape flaking and falling from the joints.

15:00 Horizontal cracks visible at the joints.20:00 Most joint coverings have fallen from the joints.30:00 Joints open approximately 1/2".60:00 The furnace was extinguished and the test article removed from

the furnace and positioned for the hose stream test. At the endof the fire test, all gypsum pieces remained in place, with ~3/4"open joints and very few cracks present in the outer layer ofgypsum. The inner layer appeared to be completely intact.

Page 12: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems Page 9

LA

BO R AT ORIE

S

OM

EGA POINT

The test article was then exposed to the standard hose stream test at a nozzlepressure of 30 psi, from a perpendicular distance of 20 feet, for 60 seconds. The twolayers of gypsum wallboard on the exposed side of the panel were removed by thewater stream. The steel facer on the exposed side was scorched, but still containedthe surface coating and was not wrinkled by the heat. The water did not penetratethe wall, so the hose stream test was successful.

A table showing the maximum temperatures reached on each of the unexposed sidethermocouples during the 60 minute fire exposure is presented below:

TC No. Max. Temp (°F) TC No. Max. Temp (°F)

1 80 7 802 81 8 803 84 9 804 80 10 855 80 11 786 81 Average 81

None of the unexposed face thermocouples exceeded an increase in temperature of325°F and their average did not exceed an increase of 250°F.

During the fire test, the wall was measured for deflection at three points along ahorizontal line at mid-height: at 30" (position #1), 60" (position #2) and 90" (position#3) from the left side of the wall. Measurements were made from a taught string tothe wall surface at each location.

TIME Position Position Position (min) #1 (in.) #2 (in.) #3 (in.)

0 3-5/8 3-5/8 3-5/810 3-3/4 3-3/4 3-3/430 3-3/4 3-3/4 3-3/445 4 4 460 4 4 4

Calculation of Time Correction

The E119 standard requires that a correction factor be applied for variation of thefurnace exposure from that prescribed, where it will affect the classification. Thiscalculation has been determined, as indicated below, to be less than 30 seconds, and

Page 13: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems Page 10

LA

BO R AT ORIE

S

OM

EGA POINT

so will not affect the sixty minute classification, which is reported to the nearestintegral minute.

Correction to indicated time:

Where:

-0.40-24

minutesseconds

Indicated fire resistance: 60 minutesArea under first 3/4 of test curve: 57660 (°F•min)Area under first 3/4 E119 curve: 58269 (°F•min)

Lag correction: 3240 (°F•min)

Listings and plots of the furnace control temperatures and specimen unexposedsurface temperatures may be found in Appendix C. A photographic documentationof the test has been included in Appendix D.

CONCLUSIONS

The wall assembly constructed and tested as described herein, achieved a fireresistance rating of 60 minutes from both sides when tested in accordance withASTM Method E119-95a FIRE TESTS OF BUILDING CONSTRUCTION ANDMATERIALS as a restrained, nonbearing wall assembly.

Page 14: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

APPENDIX A

CONSTRUCTION DRAWINGS

11

Page 15: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

12

Page 16: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

APPENDIX B

THERMOCOUPLE LOCATIONS

13

Page 17: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

60504030201000

250

500

750

1000

1250

1500

1750

E119 Std

Furnace Avg

Project No. 15328-103870Structall Building Systems, Inc.Furnace Interior Temperature

Time (min)

14

Page 18: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

60504030201000

25

50

75

100

125

150

175

200

Project No. 15328-103870Structall Building Systems, Inc.Unexposed Surface Average Temperature

Time (min)

15

Page 19: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Structall Building System Project No. 15328-103870 September 17, 1998

Integration Integration AverageFurnace of Furnace of E119 Std Cold Side TC # TC # TC # TC #

Time E119 Std Average Average Average Error Temp 1 2 3 4(min) (°F) (°F) (°F•min) (°F•min) (%) (°F) (°F) (°F) (°F) (°F)

0 68 77 0 0 0.00% 77 77 77 77 771 254 130 36 93 -61.7% 77 77 77 77 772 441 320 193 372 -48.2% 77 77 77 77 773 627 683 626 838 -25.3% 77 77 77 77 774 814 826 1312 1490 -11.9% 77 77 77 77 775 1000 854 2084 2328 -10.5% 77 77 77 77 776 1060 951 2918 3290 -11.3% 77 77 77 77 777 1120 1084 3868 4312 -10.3% 77 76 77 77 778 1180 1136 4910 5394 -8.97% 77 76 77 77 779 1240 1173 5996 6536 -8.26% 77 77 77 77 77

10 1300 1212 7121 7738 -7.98% 77 77 77 77 7711 1328 1260 8289 8984 -7.74% 77 77 77 77 7712 1347 1319 9510 10252 -7.24% 77 77 77 77 7713 1364 1362 10782 11539 -6.56% 77 77 77 77 7714 1381 1385 12087 12843 -5.88% 77 77 77 77 7715 1396 1400 13412 14163 -5.30% 77 76 77 77 7716 1410 1411 14749 15497 -4.83% 77 77 77 77 7717 1424 1421 16097 16846 -4.44% 77 77 77 77 7718 1436 1428 17454 18207 -4.14% 77 77 77 77 7719 1448 1442 18821 19581 -3.88% 77 77 77 77 7720 1459 1462 20205 20967 -3.63% 77 77 77 77 7721 1470 1479 21607 22363 -3.38% 77 77 77 77 7722 1480 1493 23025 23770 -3.13% 77 77 77 77 7723 1490 1503 24455 25187 -2.91% 77 77 77 77 7724 1499 1514 25895 26614 -2.70% 77 77 77 77 7725 1508 1524 27346 28049 -2.51% 77 77 77 77 7726 1517 1531 28806 29494 -2.33% 77 77 77 77 7727 1525 1542 30274 30947 -2.17% 77 77 77 78 7728 1533 1551 31752 32408 -2.02% 77 77 78 78 7729 1541 1556 33237 33877 -1.89% 77 77 78 78 7830 1549 1560 34727 35353 -1.77% 77 77 78 78 7731 1556 1563 36221 36837 -1.67% 77 77 78 78 7832 1563 1565 37717 38327 -1.59% 77 77 78 78 7733 1570 1569 39217 39825 -1.53% 77 77 78 78 7834 1576 1576 40721 41329 -1.47% 78 77 78 79 7835 1583 1586 42233 42840 -1.42% 78 77 78 79 7836 1589 1593 43755 44357 -1.36% 78 77 78 79 7837 1595 1599 45282 45880 -1.30% 78 78 78 79 7838 1601 1604 46816 47409 -1.25% 78 78 78 79 7839 1606 1607 48353 48944 -1.21% 78 78 78 79 7840 1612 1608 49892 50485 -1.17% 78 78 79 80 7841 1617 1612 51434 52032 -1.15% 78 78 79 80 7842 1623 1616 52980 53583 -1.13% 78 78 79 80 7843 1628 1623 54532 55140 -1.10% 78 78 78 80 7844 1633 1633 56092 56702 -1.08% 79 78 79 81 7845 1638 1641 57660 58269 -1.04% 79 78 79 81 7846 1643 1646 59236 59841 -1.01% 79 78 79 81 7947 1648 1652 60817 61418 -0.98% 79 78 79 81 78

16

Page 20: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Structall Building System Project No. 15328-103870 September 17, 1998

Integration Integration AverageFurnace of Furnace of E119 Std Cold Side TC # TC # TC # TC #

Time E119 Std Average Average Average Error Temp 1 2 3 4(min) (°F) (°F) (°F•min) (°F•min) (%) (°F) (°F) (°F) (°F) (°F)

48 1652 1655 62403 62999 -0.95% 79 79 79 81 7949 1657 1658 63991 64585 -0.92% 79 79 79 82 7950 1661 1665 65585 66176 -0.89% 79 79 79 82 7951 1666 1674 67186 67771 -0.86% 80 79 79 82 7952 1670 1680 68795 69370 -0.83% 80 79 80 82 7953 1674 1682 70408 70973 -0.80% 80 79 79 82 7954 1678 1684 72023 72581 -0.77% 80 79 80 83 7955 1682 1689 73641 74193 -0.74% 80 79 80 83 7956 1686 1691 75264 75809 -0.72% 80 79 80 83 8057 1690 1695 76888 77429 -0.70% 80 79 80 84 8058 1694 1699 78517 79053 -0.68% 80 79 80 84 7959 1698 1710 80154 80680 -0.65% 80 79 80 83 8060 1701 1707 81794 82311 -0.63% 81 80 81 84 80

Max Temp: 81 80 81 84 80Max Allowed: 327 402 402 402 402

17

Page 21: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Structall Building System Project No. 15328-103870 September 17, 1998

Time(min)

0123456789

1011121314151617181920212223242526272829303132333435363738394041424344454647

Furnace Furnace FurnaceTC # TC # TC # TC # TC # TC # TC # Probe # Probe # Probe #

5 6 7 8 9 10 11 Ambient 1 2 3(°F) (°F) (°F) (°F) (°F) (°F) (°F) (°F) (°F) (°F) (°F)

77 77 77 77 77 76 76 77 76 77 7777 77 77 77 77 76 76 77 148 104 15077 77 77 77 77 76 76 77 360 212 45477 77 77 77 77 76 76 77 886 452 94277 77 77 77 77 76 76 77 1007 653 103377 77 77 77 77 76 76 77 998 745 101677 77 77 77 77 75 76 78 1080 856 110977 77 77 77 77 76 76 78 1197 986 122477 77 77 77 77 76 76 78 1229 1072 124977 77 77 77 77 76 76 78 1253 1123 127177 77 77 77 77 76 76 78 1280 1170 130377 77 77 77 77 76 76 78 1317 1220 134677 77 77 77 77 76 76 78 1362 1274 139477 77 77 77 77 76 76 78 1397 1315 143677 77 77 77 77 76 76 78 1414 1342 145677 77 77 77 77 76 76 79 1427 1361 146877 77 77 77 77 76 76 78 1437 1376 147877 77 77 77 77 75 76 78 1450 1386 148677 77 77 77 77 76 76 79 1454 1394 148977 77 77 77 77 76 76 79 1465 1411 150177 77 77 77 77 76 76 79 1480 1432 151577 77 77 77 77 76 76 79 1495 1444 152877 77 77 77 77 76 76 79 1508 1457 154177 77 77 77 77 76 76 79 1516 1465 154777 77 77 77 77 76 76 79 1526 1475 155977 77 77 77 77 76 76 79 1538 1482 156777 77 77 77 77 76 76 79 1546 1490 157177 77 77 77 77 76 76 79 1557 1502 158378 78 77 77 77 77 76 79 1563 1513 159078 78 77 78 77 77 76 79 1568 1520 159177 77 77 77 77 77 76 79 1570 1526 159278 78 77 77 77 77 76 80 1571 1531 159578 77 77 77 77 77 77 80 1576 1539 159878 78 77 77 77 77 77 80 1579 1545 159778 78 77 78 77 78 77 80 1584 1551 160378 78 78 78 78 78 77 80 1594 1564 161578 78 78 78 78 78 77 79 1600 1577 161978 78 78 78 78 79 77 80 1609 1585 162578 78 78 78 78 79 77 80 1610 1594 162978 78 78 78 78 79 77 80 1612 1600 163278 78 78 78 78 80 77 80 1616 1602 163678 78 78 78 78 80 77 80 1622 1603 164178 79 78 78 78 80 77 80 1619 1611 164078 78 78 78 78 80 77 80 1626 1619 164979 79 78 78 79 81 77 81 1635 1630 165779 79 78 78 78 81 78 81 1642 1639 166479 79 78 78 78 81 77 80 1649 1641 166979 79 78 78 78 82 77 80 1651 1642 1674

18

Page 22: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Structall Building System Project No. 15328-103870 September 17, 1998

Time(min)

48495051525354555657585960

Max Temp:Max Allowed:

Furnace Furnace FurnaceTC # TC # TC # TC # TC # TC # TC # Probe # Probe # Probe #

5 6 7 8 9 10 11 Ambient 1 2 3(°F) (°F) (°F) (°F) (°F) (°F) (°F) (°F) (°F) (°F) (°F)

79 79 78 79 79 82 78 81 1656 1646 167779 79 79 79 79 82 78 80 1658 1652 167879 79 79 79 79 82 78 81 1662 1663 168779 80 79 79 79 83 78 81 1671 1670 169579 79 79 79 79 83 78 81 1677 1673 169979 80 79 79 79 83 78 82 1677 1677 170080 80 79 79 79 84 78 81 1682 1675 170480 80 79 79 79 84 78 82 1684 1683 170780 80 79 79 79 84 78 81 1686 1684 170680 80 79 80 79 85 78 81 1689 1686 171280 80 79 79 79 84 78 80 1695 1688 171580 80 79 79 80 84 78 81 1706 1698 172780 81 80 80 80 85 78 81 1704 1699 1723

80 81 80 80 80 85 78402 402 402 402 402 401 401

19

Page 23: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Structall Building System Project No. 15328-103870 September 17, 1998

Time(min)

0123456789

1011121314151617181920212223242526272829303132333435363738394041424344454647

Furnace Furnace Furnace Furnace Furnace Furnace FurnaceProbe # Probe # Probe # Probe # Probe # Probe # Probe #

4 5 6 7 8 9 10(°F) (°F) (°F) (°F) (°F) (°F) (°F)

76 77 77 77 77 77 77118 135 184 112 142 121 90289 371 515 268 346 216 164577 839 878 678 741 493 342733 952 938 878 893 663 506801 949 924 902 905 699 599904 1032 1036 975 1012 804 706

1023 1165 1159 1109 1151 949 8751102 1198 1184 1154 1193 1010 9731147 1228 1210 1185 1220 1055 10331191 1262 1245 1221 1257 1105 10861238 1305 1294 1266 1305 1163 11451288 1366 1359 1328 1360 1240 12181325 1409 1395 1371 1396 1292 12801351 1423 1414 1395 1420 1317 13131370 1435 1423 1413 1436 1333 13351384 1446 1431 1425 1444 1340 13491391 1459 1438 1435 1451 1349 13631398 1466 1442 1448 1458 1360 13731413 1476 1458 1462 1475 1373 13881434 1496 1477 1485 1494 1395 14071446 1522 1495 1506 1511 1420 14241459 1531 1508 1521 1525 1444 14401467 1539 1514 1528 1533 1465 14521477 1546 1528 1537 1544 1485 14611484 1561 1531 1549 1548 1512 14701492 1564 1538 1552 1557 1518 14791502 1571 1552 1561 1573 1526 14891515 1579 1564 1568 1587 1531 14971520 1588 1562 1574 1590 1538 15061526 1596 1566 1580 1593 1544 15091532 1598 1571 1582 1598 1543 15131536 1597 1572 1578 1600 1544 15131539 1606 1576 1578 1606 1547 15171542 1612 1579 1592 1610 1557 15251550 1622 1590 1602 1620 1565 15361558 1622 1593 1607 1627 1574 15481565 1629 1597 1612 1631 1579 15571572 1629 1603 1618 1638 1583 15631580 1627 1606 1615 1642 1584 15691584 1625 1609 1614 1644 1582 15691585 1631 1612 1618 1646 1585 15741592 1629 1617 1629 1654 1590 15801599 1636 1628 1629 1665 1591 15891608 1650 1635 1637 1676 1599 15991617 1660 1641 1649 1682 1609 16081620 1667 1646 1653 1685 1616 16161622 1677 1654 1662 1689 1627 1619

20

Page 24: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Structall Building System Project No. 15328-103870 September 17, 1998

Time(min)

48495051525354555657585960

Max Temp:Max Allowed:

Furnace Furnace Furnace Furnace Furnace Furnace FurnaceProbe # Probe # Probe # Probe # Probe # Probe # Probe #

4 5 6 7 8 9 10(°F) (°F) (°F) (°F) (°F) (°F) (°F)

1626 1680 1655 1666 1692 1630 16251631 1682 1659 1667 1696 1632 16271641 1681 1670 1668 1707 1634 16321649 1690 1677 1680 1715 1644 16461652 1700 1681 1688 1717 1654 16621656 1699 1680 1688 1718 1657 16671656 1702 1685 1689 1719 1659 16701663 1701 1691 1694 1728 1665 16741665 1713 1688 1700 1725 1671 16741668 1709 1697 1702 1733 1673 16781669 1720 1696 1705 1735 1683 16841677 1730 1708 1720 1746 1697 16951680 1725 1702 1711 1747 1684 1690

21

Page 25: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

APPENDIX C

THERMOCOUPLE DATA

21

Page 26: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Mas

onry

Fra

me

ELEVATION VIEW FROM UNEXPOSED SIDE

OMEGA POINT LABORATORIES, INC.Project No. 15328-103870

Structall Building Systems

Thermocouple Placement

Scale:1/2"=1'

120"

120"

30" 30" 30" 30"

30"

30"

30"

30"

11

10

987

654

321

Note:24 GA. Type K thermocouples were placed on the surface of the wall at the locations indicated and covered with the standard 6" x 6" x 3/8" mineral fiber pads, held in place with silicone adhesive at all four corners.

22

Page 27: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

APPENDIX D

PHOTOGRAPHS

23

Page 28: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

#1: Panels as received, showing PFS inspection mark.

#2: Attaching joined panels to the test frame.

24

Page 29: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

#3: Screwing the furring strips to the panel surface (done on each side).

#4: Installing the 5/8" Type X drywall (first layer).

25

Page 30: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

#5: Installing the second layer of drywall.

#6: Exposed face immediately prior to placing up to the furnace.

26

Page 31: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

#7: Unexposed surface at start of test.

#8: Gypsum face with furnace flames.

26

Page 32: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

#9: Unexposed surface after 26 minutes of fire exposure.

#10: Gypsum joints open slightly.

27

Page 33: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

#11: Unexposed surface at the end of the 60 minute fire exposure.

#12: Exposed face immediately after removal from the furnace.

28

Page 34: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

#13: Positioning the test article for the hose stream test.

#14: Hose stream test was performed for 60 seconds.

29

Page 35: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

#15: Hose stream test.

#16: Exposed face after the hose stream test.

30

Page 36: T ASTM E119-95a Fire Tests of Building R Construction and ... · T E S T R E P O R T OMEGA POINT LABORATORIES, INC. 16015 Shady Falls Road Elmendorf, TX 78112 (v) 210-635-8100 (f)

Project No. 15328-103870 September 25, 1998Structall Building Systems APPENDICES

LA

BORATOR

IES

OM

EGA POIN

T

#17: Unexposed face after the hose stream test.

31