t101d201-01b ana-d eng - a. eberleother e.g. 10 v a92 a93 analogue inputs and outputs with 8 inputs...

8
GB Interface Module Type ANA-D * in wall mounting enclosure * in mounting enclosure * as plug-in module Application The ANA-D interface module can be used if a REGSys™ component has an insufficient number of analogue mA inputs and outputs available. REGSys™ components are identified by the suffix “D” behind the three letter device identification. Example: REG-D™, REG-DA, REG-DP, PQI-D, EOR-D, CPR-D.... The ANA-D interface card functions as an analogue input and output module and can be addressed via the COM 3 (RS 485) interface of any REGSys™ component. The hardware version (mA input or mA output) is specified by feature “E”. E1 refers to an ANA-D with eight analogue inputs, while E2 designates a version with eight analogue outputs. In addition, every interface card has its own intelligence (µP). This makes it possible to implement the connection of signals directly at the module. Programming of the module is carried out at our head- quarters according to customer requirements. Features can be combined with all REGSys™ components 8 freely programmable analogue outputs or 8 freely programmable analogue inputs up to 16 ANA-Ds can be connected per REGSys™ component processing power for connecting the measurement quantities "on board." wide auxiliary voltage ranges all outputs / inputs are galvanically isolated from each other Technical Characteristics Applied norms and standards IEC 1010/ EN61010 (VDE 0411) CAN / CSA - C 22.2 No. 1010.1 - 92 VDE 0110 IEC 255 - 4 EN 55011 : 1991 EN 50082 - 2 : 1995 IEC 688 - 1 IEC 529 EN 50178 / VDE 0160 / 11.94 (draft) VDE0106 part 100 A. Eberle GmbH & Co. KG

Upload: others

Post on 07-Feb-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: T101D201-01b ANA-D eng - A. Eberleother e.g. 10 V A92 A93 Analogue inputs and outputs with 8 inputs with 8 outputs E1 E2 Operating manual German English French Spanish Italian G1 G2

GBT101D201-00 Version 01/2006

Interface ModuleType ANA-D

* in wall mounting enclosure* in mounting enclosure* as plug-in module

Application

The ANA-D interface module can be used if a REGSys™ component has an insuffi cient number of analogue mA inputs and outputs available.REGSys™ components are identifi ed by the suffi x “D” behind the three letter device identifi cation.Example:REG-D™, REG-DA, REG-DP, PQI-D, EOR-D, CPR-D....

The ANA-D interface card functions as an analogue input and output module and can be addressed via the COM 3 (RS 485) interface of any REGSys™ component.

The hardware version (mA input or mA output) is specifi ed by feature “E”.E1 refers to an ANA-D with eight analogue inputs, while E2 designates a version with eight analogue outputs.

In addition, every interface card has its own intelligence (µP). This makes it possible to implement the connection of signals directly at the module.

Programming of the module is carried out at our head-quarters according to customer requirements.

Features

• can be combined with all REGSys™ components

• 8 freely programmable analogue outputs or 8 freely programmable analogue inputs

• up to 16 ANA-Ds can be connected per REGSys™ component

• processing power for connecting the measurement quantities "on board."

• wide auxiliary voltage ranges

• all outputs / inputs are galvanically isolated from each other

Technical CharacteristicsApplied norms and standards

IEC 1010/ EN61010 (VDE 0411)CAN / CSA - C 22.2 No. 1010.1 - 92VDE 0110IEC 255 - 4EN 55011 : 1991EN 50082 - 2 : 1995IEC 688 - 1IEC 529EN 50178 / VDE 0160 / 11.94 (draft)VDE0106 part 100

A. Eberle GmbH & Co. KG

Technical Dataa-eberle

Page 2: T101D201-01b ANA-D eng - A. Eberleother e.g. 10 V A92 A93 Analogue inputs and outputs with 8 inputs with 8 outputs E1 E2 Operating manual German English French Spanish Italian G1 G2

II IIICOM 3analogue inputs & outputs

auxiliary voltage

50 V 230 VCOM 3, analogue inputs, analogue outputs

Auxiliary voltage

Mount. Uh COM3

19" rack. Mount. - 2.2 0.35

Auxiliary voltage Uh 2.2 - 3.7

COM 3 COM3 0.35 3.7 -

Analogue input AI 0.35 3.7 0.5

Analogue output AO 0.35 3.7 0.5

Analogue outputs (feature E2)Outputs E1 ... E8Nominal application range -20 mA…0…20 mAof the output signal Y0…Y2(freely programmable)

Electrical isolation Optocoupler

Load range 0 ≤ R ≤ 8 V/ Y2

Alternating component ≤ 0.5 % of Y2

Measuring accuracy ≤ 0.5 % compared to the end value of the input signal

Overload range 1.2 times the value

Maximum value for R → ∞ 15 V

Electrical safetySafety class IDegree of pollution 2Overvoltage category II, III

Interference emissions Group 1 class A according to EN 55011:1991

Analogue inputs (feature E1)Inputs E1 ... E8Input range X0…X2 -20 mA…0…20 mA(freely programmable)

Electrical isolation Optocoupler

Input resistance 1.5 V / X2

Overload range 1.4 times value

Measuring accuracy ≤ 0.5 % compared to the end value of the input signal

Common mode rejection > 100 dB at 0…120 Hz Asymmetry of the source resistance 1.5 kΩ

Auxiliary voltages

Note:All test voltages are AC voltages in kV, which may be applied for 1 minute.

Test voltages

Immunity Electrostatic discharges according to interference to EN 61000-4-2:1995 Air discharge: 8 kV Contact discharge: 8 kV Electromagnetic fi elds according to ENV 50140:1993 and/or ENV 50204:1995 80 - 1000 MHz: 10 V/m 900 ± 5 MHz: 10 V/m pulse modulated Fast transient interferences (bursts) according to EN 61000-4- 4:1995 Supply voltage: 230 V AC: 2 kV; Data cables: 1 kV Conducted interferences according to ENV 50141:1993 0.15 - 80 MHz: 10 Veff 50 Hz magnetic fi elds according to EN 61000-4-8:1993 30 A/m

Power supply

For all feature:Voltage dips ≤ 80 ms cause neither loss of data nor devicemalfunction.

Temperature range Function (housing) -10 °C...+50 °C Function (plug-in module) -10 °C...+60 °C Transport und storage -25 °C...+65° C

Climatic stability

Feature H1 H2

AC (internal) - -

AC 85 V...264 V -

DC 88 V...280 V 18 V...72 V

Power consumption ≤15 VA ≤10 Watt

Frequency 45 Hz to 400 Hz -

Microfuse T2 250 V T2 250 V

Technical Data ANA-D

A. Eberle GmbH & Co. KG 2

Page 3: T101D201-01b ANA-D eng - A. Eberleother e.g. 10 V A92 A93 Analogue inputs and outputs with 8 inputs with 8 outputs E1 E2 Operating manual German English French Spanish Italian G1 G2

5 TE

2

16

20

24

28

32

22

26

30

d b z d b z

2 1

2

32

7.6225.4

CB

1

CB

2

Socket connector 1Auxiliary voltage, COM 3

Auxiliary voltageL(+) 28 L(-) 30

GND 32

COM 3Rx + d2 Rx - b2

Tx + d4 Tx - b4

Mechanical designPlug-in moduleFront plate Aluminium, RAL 7035 greyHeight 3 U (132.5 mm)Width 8 T (40.6 mm)Circuit board 160 mm x 100 mmWeight ≤ 0.5 kgDegree of protection Plug-in module IP 00 Socket connector IP 00Mounting Acc. to DIN 41494 part 5Plug-in connectors DIN 41612

Figure 1 Position of the socket connectors

Figure 2 Position of the blade connectors

ANA-D contact assignment

Installation in the mounting rackEach mounting rack is provided with space for 84 modules and thus for 84 place numbers “n”. A specifi c place number is the reference point for the installation of the guide and the connection elements on the rear of the mounting rack.

Place numbers

Socket connector 1 2

Guide n -

Screws n n+5

Technical Data ANA-D

3 A. Eberle GmbH & Co. KG

Page 4: T101D201-01b ANA-D eng - A. Eberleother e.g. 10 V A92 A93 Analogue inputs and outputs with 8 inputs with 8 outputs E1 E2 Operating manual German English French Spanish Italian G1 G2

3 H

E

84 TE

245 mm

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

a-eberle

ANA-D

a-eberle a-eberle

BIN-D

a-eberle

K1 K2 K3 K4 K5 K6 K7 K8

22b

2 6 6 10 10 18 18 22 22 26 26 30 30z b z b z b z b z b z b z b z

14 14

+ - + - + - + - + - + - + - + -

prog

.

prog

.

prog

.

prog

.

prog

.

prog

.

prog

.

prog

.Pin assignment

Socket connecter no.

Row

Description Function Pin Comments

K1 mA input or output +-

b2z2

Freely programmable

K2 mA input or output +-

b6z6

Freely programmable

K3 mA input or output +-

b10z10

Freely programmable

K4 mA input or output +-

b14z14

Freely programmable

K5 mA input or output +-

b18z18

Freely programmable

K6 mA input or output +-

b22z22

Freely programmable

K7 mA input or output +-

b26z26

Freely programmable

K8 mA input or output +-

b30z30

Freely programmable

Socket connector 2Analogue inputs (feature E1)Analogue outputs (feature E2)

Analogue inputs or outputs

Figure 3 ANA-D as 19” plug-in module, feature B1

Housing

Material PlasticDegree of protection IP 65 Weight ≤ 1.0 kgDimensions See fi gures 4 and 5Connection elements Screw terminals

The ANA-D interface module is also very fl exible with regard to the type of housing used. The following are just some of the housing option available.

ANA-D as a plug-in module (8 TE) in a 19” mounting rack

Wall mounting and panel mounting housing (features B2, B3)

Note:Additional equippingof mounting rack /application-specifi c pinassignment on request

Technical Data ANA-D

A. Eberle GmbH & Co. KG 4

Page 5: T101D201-01b ANA-D eng - A. Eberleother e.g. 10 V A92 A93 Analogue inputs and outputs with 8 inputs with 8 outputs E1 E2 Operating manual German English French Spanish Italian G1 G2

Figure 5 ANA-D in panel mounting housing, 12 TE, feature B3

Figure 4 ANA-D in wall mounting housing, 20 TE, feature B2

Bottom view

Side view

Wall mountingCutout 68+07 x 138 +1 mm

Technical Data ANA-D

5 A. Eberle GmbH & Co. KG

Page 6: T101D201-01b ANA-D eng - A. Eberleother e.g. 10 V A92 A93 Analogue inputs and outputs with 8 inputs with 8 outputs E1 E2 Operating manual German English French Spanish Italian G1 G2

L(+)

L(-)

Tx+

Tx-

Rx+

Rx-

CO

M 3

Input 1

Input 2

Input 3

Input 4

Input 5

Input 6

Input 7

Input 8

Uh

µP

L(+)

L(-)

Tx+

Tx-

Rx+

Rx-

CO

M 3

Output 1

Output 2

Output 3

Output 4

Output 5

Output 6

Output 7

Output 8

Uh

µP

Figure 6 REGSys™ - system overviewFigure 6 REGSys™ - system overviewFigure 6

Figure 7 Block diagram for feature E1Figure 7 Block diagram for feature E1Figure 7 Figure 8 Block diagram for feature E2

Block diagrams

Technical Data ANA-D

A. Eberle GmbH & Co. KG 6

Page 7: T101D201-01b ANA-D eng - A. Eberleother e.g. 10 V A92 A93 Analogue inputs and outputs with 8 inputs with 8 outputs E1 E2 Operating manual German English French Spanish Italian G1 G2

FEATURE CODE

Analogue interface (8TE, 3HE)with 8 freely programmable analogue channels as well as COM 3 (RS485)for communication with a CPU from the XXX-DX series

ANA-D

Design 19” plug-in module (8 TE)Wall mounting housing with wiring (20 TE)

Panel mounting housing (12 TE)

B1B2B3

Auxiliary voltage 85 V ... 110 V ... 264 V AC / 88 V ... 110 V ... 264 V AC / 88 V ... 110 V 220 V ... 280 V DC220 V ... 280 V DC220 V18 V ... 60 V ... 72 V DC60 V ... 72 V DC60 V

H1H2

Output quantity (Start/end values freely programmable)Current -20...0...20 mA

other e.g. 10 VA92A93

Analogue inputs and outputs with 8 inputswith 8 outputs

E1E2

Operating manual GermanEnglishFrench

SpanishItalian

G1G2G3G4G5

Ordering information

When ordering please note:

• Only one code with the same capital letter is possible

• If the capital letter is followed by the number 9, additional details in plain text are required

• If capital letters are followed by 0, the code can be omitted.

Technical Data ANA-D

7 A. Eberle GmbH & Co. KG

Page 8: T101D201-01b ANA-D eng - A. Eberleother e.g. 10 V A92 A93 Analogue inputs and outputs with 8 inputs with 8 outputs E1 E2 Operating manual German English French Spanish Italian G1 G2

A. Eberle GmbH & Co. KGAalener Str. 30/32 * D-90441 Nürnberg * Phone: +49 (0)911 / 62 81 08-0 * Fax: +49 (0)911 / 62 81 08 96e-mail: [email protected] http://www.a-eberle.deA. Eberle GmbH & Co. KGe-mail: [email protected] http://www.a-eberle.deA. Eberle GmbH & Co. KG

Technical Data ANA-D

A. Eberle GmbH & Co. KG 8