table 7.5-1 main control room indicators and/or … · ndtt considerations. monitor containment...
TRANSCRIPT
TABLE 7.5-1
MAIN CONTROL ROOM INDICATORS AND/OR RECORDERS AVAILABLE TO THE OPERATOR
Channel Parameter Available
OPERATIONAL OCCURRENCES 1. Tcold or Thot lThot
(measured, wide range lTcold/
2.
3.
4.
5.
Pressurizer water level
system pressure
Containment pressure
Steam line pressure
SGS-UFSAR
Loop
3
2
4
3/loop
Entire distance between taps (528"approx)
0-3000 psig
0-115% of design pressure (-5 to +55 psigl
0-1200 psig
Accuracy
+4% of full range
+4.2% of span level at 2250 psi a
_!5.5% of full range
+5.5% of full scale
.5% of full scale
1 of 4
Indicator/ Recorder
All channels are recorded
All three channels indicated; one channel is selected for recording
Indicated and recorded
All four are indicated; two are also recorded
All channels are indicated
Purpose
Ensure maintenance of proper cooldown rate and to ensure maintenance of proper relation-temperature NDTT considerations.
Ensure maintenance of proper reactor coolant inventory.
Ensure maintenance of proper relationship between system pressure and temperature for NDTT considerations.
Monitor containment conditions to indicate need for potential safeguards actuation.
Monitor steam generator temperature conditions during hot shutdown and cooldown, and for use in recovery from steam generator tube ruptures.
Revision 18 April 26, 2000
Parameter Channel Available
OPERATIONAL OCCURRENCES (Cont.)
6. Steam generator water level (wide range)
7. Stearn generator water level (narrow range)
ACCIDENT CONDITIONS
1. Containment pressure
2. Refueling water storage tank water level
SGS-UfSAR
1/stearn generator
3/steam generator
2
2
0-100%
0-100%
0-115% of design presBUre 1-5 to +55 psi g)
(-15 to +165 psigl
0-100% of ! 48 ft/H Ol
2
TABLE 7.5-1 [Cont'd)
Accuracy
Refer to Applicable Loop Accuracy Calculation
Refer to Applicable Loop Accuracy Calculation
5% of full
+3% of level span
2 of 4
Indicator/ Recorder
All channels recorded
All channels indicated; the channels used for control are recorded
All four are indicated; two are also recorded
Both
Both are indicated and alarmed
Ensure maintenance of reactor heat sink.
tnsure maintenance of reactor heat sink.
Monitor post-LOCA containment conditions.
tnsure that water is flowing to the safety injection system after a LOCA and determine when to shift from injection to recirculation mode.
1. Ste~m gPnerJtor l•nter level {narrow rang<>l
4. Steam rator water 1 (wide range!
5. Steam l1ne pressure
6. Pressurizer water level
7. Conta1nment hydrogen level
B. Conta1nment area monitors (hlgh range)
SGS-UFSA.R
·r !J:;!f' l.s l l l ·1l> 1 p
<i:;t_e.1m 0-100? or>r.Pr~t or
1/st:eam aPr1erator
3/steam I ine
3
2
2
0-100'1.
0-1200 psig
Entire distance between taps ( 528'' Appwx)
0-IO% vol
1 107?/hr
( r:c·nt )
Refer to Applicable Lorlp 1\r:curacy Cal lation
Refer to Applicable Accucac:y at ion
+7.51. of full scale
Indicate the level is some-where between 0 and 100 of span
2% of full scale
3 of 4
Ir1dicator I
All channels indicated; the channels used for control are recorded
All channels are recorded
All channels are indicated
All three indicated and one is for recording
Both channels are recorded
Both channels are recorded
Purpose
Detect steam generator tube rupture; monitor steam generator water level following a steam line break.
Detect steam generator tube rupture; monitor steam generator water level following a steam line break.
Monitor steam line pressures following steam generator tube rupture or steam line break.
Indicate that coolant inventory restored in pressurizer following cooldown after steam generator tube rupture or steam line break.
NUREG 0737
NUREG 0737
Revision 18 Apri 1 2 6, 2000
I
Channels Parameter
ACCIDENT CONDITIONS (Cent)
9. Reactor vessel level 2
10. Containment liquid level
11. Neutron flux
12. Core Exit
4
2
2
2 (29 TC's
Hot leg-
top of RV
Bottom -top of RV
ro-a amps -120% wide range log power
32"F Thermocouples (11 each channel) 2300"F
13. Margin to 2 ± 999"F Saturation 0-250"F
0-25"F
TABLE 7.5-1 {Cont)
Accuracy
6% without RCPs
running
±10.5% of full span
(2) (3)
(4)
Indicator/ Recorder
One channel
recorded
One set recorded
Both channels are recorded
Both are indicated and alarmed
Both channels are indicated
Both Channels recorded and indicated
Purpose
Detect cooling.
inadequate
Indication of neutron flux
during and following an accident
NUREG 0737
Detect inadequate core cooling
core
(1) The CET subsystem which is part of the In-Core Instrumentation System, has been upgraded to EQ to ensure availability post accident. However, since the balance of the In-Core Instrumentation is non-safety related, the FSAR text on the CET subsystem remains under Section 7.7 of the FSAR.
(2) Accuracy of the representative core exit T/C temperature (instrument and rack error) ±6°F/random + 3°F (bias) . (3) Process measurement accuracy:
Core Condition Error Covered core ~o -ll°F bias Core uncovered and CET at 700"F -85°F bias Core uncovered and CET at 1200°F -140~F bias
(4) The indicated margin to saturation is automatically adjusted by the subcooling margin monitor computer for errors that could cause indication to be higher than actual. This provides the operator with reasonable confidence that the RCS fluid will be subcooled at the core exit whenever a positive margin to saturation is indicated on the display units.
4 of 4 SGS-UFSAR Revision 23
October 17, 2007
I
Parameter
NUCLEAR INSTRUMENTATION
1. Source Range a. Count rate
b. Startup rate
SGS-UFSAR
TABLE 7.5-2
MAIN CONTROL ROOM INDICATORS AND/OR RECORDERS AVAILABLE TO THE OPERATOR TO MONITOR SIGNIFICANT PLANT PARAMETERS DURING NORMAL OPERATION
No. of Channels Available
2
2
1 to 10 6 counts/ sec
-1.0 to 5.0 decades/min
Accuracy
±7% of the linear full scale analog voltage
±7% of the linear full scale analog voltage
1 of 11
Indicator/ Recorder
Both channels indicated. Either may be selected for recording.
Both channels indicated.
Notes
One two-pen recorder is used to record any of the 8 nuclear channels (2 source range, 2 intermediate range and 4 power range).
Revision 6 February 15, 1987
Parameter
NUCLEAR INSTRUMENTATION
2. Intermediate Range a. Flux level
No. of Channels Available
2
b. Startup rate 2
3 . Power Range a. Uncalibrated
ion chamber current (top and bottom uncompensated ion chambers)
SGS-UFSAR
decades/min
4
TABLE 7.5-2 (Cont)
-1.0 to 5.0 full scale analog
0 to 120% of full power current
Accuracy
±7% of the linear full scale analog voltage and ±3% of the linear full scale voltage in the range of 10-4 to 10-3
amps
±7% of the linear indicated.
±1% of full power
2 of 11
Indicator/ Recorder
Both channels indicated. Either may be selected for recording using the recorder in Item 1 above.
Both channels
All 8 current signals indicated
Notes
Revision 6 February 15, 1987
NUCLEAR
b. Calibrated ion chamber current (top and bottom uncompensated ion chambers)
c. Not used
d. flux of the top and bottom ion chambers
SGS-UFSAR
No. of Channels
4
4
TABLE 7.5-2 (Cont.)
0-120% of full power
0 to 120% of full power
±2% of full power
±3% of full power for indication ±2% for recording
3 of 11
Indicator/
All 8 current recorded (four recorders) Recorder 1 - upper
and lower currents for Channel 1
Recorder 2 - upper And lower currents for Channel 2
Recorder 3 - upper and lower currents for Channel 1
Recorder 4 upper and lower currents for Channel 1
All 4 channels indicated. 2 of the 4
channels may be recorded using recorder in Item 1 above.
Revision 25 October 26, 2010
No. of Channels
Parameter Available
NUClEAR INSTRUMENTATION (Cont.)
e. Average ftux of 4 the top and bottom ion chambers
f. Flux 4 difference of the top and bottom ion chambers
REACTOR COOLANT SYSTEM
1. Taverage 1/loop (measured)
2. AT( measured) 1/loop
a. Tcold or 1·Thot and Thot 1·Tcold per (measured, loop wide range)
SGS·UFSAR
TABlE 7.5·2 (Cont.)
Range Accuracy
0 to 2001 of t2X of full full power power to 120
:t6X of full power to 200%
·30 to +30X :1:4%
540 • 615°F :1.:4°F
0 to 150% of :1:4% of fulL full power 4T power AT
0 • 700°F t4%
4 of 11
Indicator/ Recorder
All 4 channels recorded.
All 4 channels indicated.
All channels indicated.
All channels indicated. One channel is selected for recording.
Both channels recorded.
Notes
Revision 15 June 12, 1996
REACTU'" CC'OLAtlT SYSTEI·l ICont . l
3. OverpowPr .\T Set point
4. Overtemperature T Setpoint
5. Pressurizer Pressure
6. Pressurizer Level
7. Primary Coolant Flow
8. System Pressure
SGS-OFSAR
ll '· . 1 (h.:;nriP 1 S {I'Jc<l l dbl, - - - -
1: l " f'
3/l 00p
2
0-?',"F
1700 to ~500 psig
Ent1re distance between taps o-1oo•
0 to 120~ of rated fl0w
0 )f100 psig
±41 of full power :\T
±4' of full power .\T
±'il.O psi
±4.2% span level at 2250 psia
Repeatability of iH of full flow
±5.5%
5 of 11
Indicator/ ~~£Or de~
All channels One channel
indicated. is selected
for recording.
All channels indicated. One channel is selected for recording.
All channels indicated One channel is selected for recording.
All channels indicated. One channel is selected for recording.
All channels indicated.
All channels indicated and recorded.
Two-pen recorder used, second pen records reference level signal
Revision 18 April 26, 2000
I l
Parameter
REACTOR CONTROL SYSTEM
No. of Channels Available
1. Demanded rod speed 1
2. Auctioneered T
3.
average
T reference
4. Control rod Position
SGS-UFSAR
1
1
0 to 100% of rated speed
540° to 615°F
TABLE 7.5-2 (Cont)
Accuracy
±2%
6 of 11
Indicator/ Recorder
The one channel is indicated.
The one channel is recorded.
The one channel is recorded.
Notes
Any one of the T channels avg into the auctioneer may be bypassed.
If system not available, borate and sample accordingly.
Revision 6 February 15, 1987
No. of Channels
Parameter Available
REACTOR CONTROL SYSTEM
a. Number of 1/group steps of demanded rod withdrawal
b. Demanded 1 position of the part length rod bank.
SGS-UFSAR
TABLE 7.5-2 (Cont)
Indicator/ Range Accuracy Recorder
0 to 230 steps ::!: 1 step Each group is indicated during rod motion.
0 to 230 steps ::!: 1 step The bank is indicated during rod motion.
7 of 11
Notes
These signals are used in conjunction with the measured position signals (4c) to detect deviation of any individual rod from the demanded position. A deviation will actuate an alarm and annunciator.
Revision 6 February 15, 1987
Parameter
REACTOR CONTROL SYSTEM (Cont.!
5.
c. Full length rod measured position
Control rod bank demanded position
SGS-UFSAR
No. of Channels Available
1 for each rod
4
0 to 230 steps
0 to 230 step!!
TABLE 7.5-2 (Cont.)
Accuracy
Unit 1, +12 steps (100\::_RT~~O\)
Unit 2, +12 steps 1RTP>B5\l +18 step!! 1RTP::_85%!
:1:2.5\ of total travel
a of 11
Indicator/ Recorder
Each rod position is indicated.
All 4 control rod bank positions are recorded along with the low-low limit alarm for each bank.
Rod position indicators are required to be calibrated within !12 steps.
1. One channel for each control bank.
2 • An alarm and annunciator is actuated when the last rod control bank to be withdrawn reaches the withdrawal limit, when any rod control bank reaches the low insertion limit, and when any rod control bank reaches the low-law insertion limit.
Revision 16 January 31, 1998
Parameter
CONTAINMENT SYSTEM
Containment pressure
FEEDWATER AND STEAM SYSTEMS
1.
2.
3.
Auxiliary feedwater flow
Steam generator level (narro;.! range)
Steam generator level (wide range)
SGS-UFSAR
No. of Channels Available
1/stearn line
3/steam generator
1/steam generator
0 - 115 of design pressure (-5 to +55 psigl
0-250000 PPH
0-100%
0-100%
TABLE 1.5-2 (Cant.)
Accuracy
+5. 5% of full span
Refer to Applicable Loop Accuracy Calculation
Refer to Applicable Loop Accuracy Calculation
9 of 11
lndicatm:/ Recorder
All 4 channels indicated and 2 are also recorded.
All channels indicated
All channels indicated. The channels used for control are recorded.
All channels recorded.
Notes
One channel to measure the flow to each steam generator
Revision 17 October 16, 1998
Parameter
FEEDWATER AND STEAM SYSTEMS
4. Progra.m:med steam generator level signal
5. Main feedwater flow
6. Magnitude of signal
control valves
SGS-UFSAR
No. of Channels Available
1/steam generator
2/steam generator
1/main 1/bypass
TABLE 7.5-2 (Cont.)
Range
0-100%
0 to 120% of maximum calculated flow
0 to 100% of valve opening
Accuracy
±5%
±1.5%
10 of 11
Indicator/ Recorder
lUI channels indicated.
All channels indicated. The channels used for control are recorded.
All channels indicated
Notes
l. One channel for each main and bypass feedwater control valve
2. OPEN/SHUT indication is provided in the control room for each main and bypass feedwater control valve.
Revision 25 October 26, 2010
I
Parameter
FEEDWATER AND STEAM SYSTEMS
7. Steam flow
8. Steam line pressure
9. Steam dump modulated signal
10. Turbine steamline inlet pressure
SGS-UFSAR
No. of Channels Available
2/steam generator
3/loop
1
2
TABLE 7.5-2 (Cont.)
0 to 120% of maximum calculated flow
0 to 1200 psig
0 - 85% max calculated steam flow
0 to 120% to max calculated turbine load
Accuracy
±10%
±5.5%
±1.5%
±3.5%
11 of 11
:Cndicator/ Recorder
All channels indicated. The channels used for control are recorded.
All channels indicated and 1 is recorded.
The one channel is indicated
Both cha:mels indicated.
OPEN/SHUT indication is provided in the control roo:n for each steam dump valve.
OPEN/SHUT indication is provided in control room for each turbine stop valve.
Revision 25 October 26, 2010
I
TABLE 7.5-3
INDEX TYPE "A" VARIABLES
Variable Description Variable Reference Reactor Coolant System Hot Leg 5 Water Temperature
Reactor Coolant Pressure 6
Degrees of Subcooling 9 Containment Pressure 11 Refueling Water Storage Tank Level 27 Pressurizer Level 30 Steam Generator Pressure 36 Auxiliary Feedwater Flow 39 Auxiliary Feedwater Storage Tank 40 Level {Condensate Storage Tank)
steam Generator Water Level - Narrow Range 35a
1 of 1 SGS-UFSAR
No.
Revision 16 January 31, 1998
Variable Ref. No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
SGS-UFSAR
TABLE 7.5-4
SUMMARY OF INSTRUMENTATION COMPLIANCE WITH REGULATORY GUIDE 1.97
Variable
Neutron Flux (Source Range, Intermediate range, Power range) - Monitors
Control Rod Position
RCS Soluble Boron Concentration
RCS Cold Water
- Indication
RCS Hot Leg Water Temperature RTDs
- Indication
RCS Pressure Transmitters
Core Exit Temperature - Thermocouples
Coolant Level in Reactor
of Subcooling - Display (inputs - See variable Ref. No. 6 and 7)
Containment Sump Water Level -Transmitters and Level Switches
Containment Pressure (narrow and wide range) - Transmitters
Containment Isolation Valve Position (excluding check valves) - Limit Switches
Concentration or Radiation Level in Circulating Primary Coolant
Analysis of Primary Coolant (Gamma
Containment Area Radiation - Monitors
Effluent Noble Gas Effluent from Condenser Air Removal System Exhaust - Monitors
1 of 5
Level
Unit 1-2 Unit 2-1
1
1
Unit 1-3a Unit 2-1 Unit 1-3b Unit 2-1
3a Unit 1-3b Unit 2-1
Unit 1-3a Unit 2-1
1
1
1
3a
Unit 1-3a Unit 2-1
1
5
5
3a
1
Revision 25 October 26, 2010
Variable
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
SGS-UFSAR
TABLE 7.5-4 (Cont)
Variable
Containment 3ydrogen Concentration -
Containment Effluent Radioactivity Noble Gases from Identified Release Points - Monitors
Radiation Exposure Rate (Electrical Penetration Area) - Monitors
RHR Sys~em Flow - Transmitters
RHR Hea-: Exchanger Outlet Temperature -
Accumulator Tank Level and Pressure -- Transmitters - Transmitter
Accumulator Isolation Valve Position
Boric Acid Flow Transmitters
Flow in HPI Transmitters
Flow in LPI System - Transmitters
Water Tank Level and Low Level Alarm - Transmitters
Transmitter Range
Reactor Coolant Pump Status
Primary Relief Valve Positions (including PORV and code valves) or Flow through or Pressure in Relief Valve Lines
Pressurizer Level - Transmitters
- Transmitter
Pressurizer Heater Status (Current) - Heaters
2 of 5
3a
3b
3b
3a
4b
1
Unit 1-3a Unit 2-1
3a
3a
Unit 1-3a Unit 2-1 Unit 1-4c Unit 2-1
1
1
Unit -3a Unit -1 Unit -4c Unit -1
2
Revision 25 October 26, 2010
•
•
•
Variable Ref. No.
32
33
34
35
35A
36
37
38
39
40
41 41A
42
43
44
45
46
47
48
49
SGS-UFSAR
TABLE 7.5-4 (Cont)
Variable Description
Compliance Level
Quench Tank Level (Pressurizer Relief Tank) - Transmitters
.Range
Quench Tank Temperature (Pressurizer Relief Tank)
Quench Tank Pressure (Pressurizer Relief Tank)
Transmitters Range
Steam Generator Level - Transmitters
steam Generator Level - Narrow Range
Steam Generator Pressure - Transmitters
Safety/Relief Valve Positions or Main Steam Flow - Transmitters
Main Feedwater Flow
Auxiliary Feedwater Flow - Transmitters
condensate Storage Tank Water Level (Auxiliary Feedwater Storage Tank) - Transmitters
COntainment Spray Flow Containment Spray Flow Additive Rate - Transmitters
Beat Removal by the Containment Fan Beat Removal System - Transmitters
containment Atmosphere Temperature
Containment Sump Water Temperature
CVCS Makeup Flow-in - Transmitters
Letdown Flow - Transmitters
Volume Control Tank Level - Transmitters
Component Cooling Water Temperature to ESF System - Transmitters
Component Cooling Water Flow to ESF System - Transmitters
3 of 5
4c
3b
l
Unit 1-3a Unit 2-1
Unit 2-1
Unit 1-3a Unit 2-1
3a
1
Unit l-3a Unit 2-1
Unit 1-4a Unit 2-1
5
3a
3a
4b
5
3a
Unit 1-3b Unit 2-1
4a
Unit 1-4a Unit 2-1
4b
Revision 15 June 12, 1996
Variable Ref. No.
50
51
52
52 A
528
53
53 A
54
55
56
57
58
59
60A
608
61
62
63
SGS-UFSAR
TABLE 7.5-4 (Cont.)
Variable Compliance Description Level
High-Level Radioactive Liquid Tank Level - Indication 3b
Radioactive Gas Holdup Tank Pressure-Indication 3b
Emergency Ventilation Damper Position -control Room Damper Limit Switches 4a
Emergency Ventilation Damper Position -Auxiliary Bldg. Damper Limit Switches 4a
Emergency Ventilation Damper Position -Fuel Handling Bldg. 4a
Status of Standby Power 5
status of Control Air 5
Containment or Purge Effluent N/A
Reactor Shield Building Annulus Effluent N/A
Auxiliary Building Effluent N/A
condenser Air Removal System Exhaust N/A
Common Plant Vent or Multi-Purpose Vent Discharging any of above releases -Monitors 3a
Vent from Steam Generator Safety Relief Valves or Atmospheric Dump Valves -Monitors s All other identified Release Points (Decontamination Bldg.) -Monitors 3b
All other identified Release Points (Auxiliary Feed Pump Turbine Exhaust} -Monitors 5
All Identified Plant Release Points -Monitors (Particulates and Halogens) 3a
Radiation Exposure Meters 5
Airborne radiohalogens and particulates (portable sampling with onsite analysis capability) 1
4 of 5 Revision 16 January 31, 1998
Variable Ref. No.
64
65
66
67
68
69
70
71
72
TABLE 7.5-4 {Cont.)
Variable Description
Plant and Environs Radiation -Instrument Range
Plant and Environs Radioactivity
Wind Direction
Wind Speed
Estimation of Atmospheric Stability
Primary Coolant (Grab Sample)
Containment Air (Grab sample}
Containment Sump (Grab sample)
Effluent Radioactivity - Noble Gases -Monitors
73 DELETED*
Compliance Level
4c
1
1
1
1
5
5
5
3a
*ijOTE This variable is replaced by variable 35a as primary indication of SGTR
5 of 5 SGS-UFSAR Revision 20
May 6, 2003
TABLE 7.5-5
JUSTIFICATION FOR NONCONFORMANCE TO REGULATORY GUIDE 1.97
Variable Reference No.
4
5
13
14
24
27
35
39
40
41
42
44
SGS-UFSAR
Justification
Isolation devices are not provided for these variables. However, these variables will be on the safety parameter display system and Class lE multiplexors will have qualified isolation devices.
Same as 4
There is radiation monitoring on the letdown line; however, during an accident this line is isolated. The back-up or alternate means of measuring this variable is the Sampling System.
The Sampling System obviates the need for this variable.
Same as 4
Same as 4
Same as 4
Same as 4
Same as 4
An alternate means of determining the containment spray flow is the spray additive tank flow rate, which is available (refer to Variable Code No. 41a). The spray additive tank flow rate is the flow of liquid which is educted to the suction of the containment spray pumps. The eduction is accomplished by recirculating the containment spray liquid from the discharge to the suction of the containment spray pumps. Indication of the spray additive flow provides confirmation of containment spray pumps operation.
Same as 4
The containment sump temperature indication is not required in Safety Guide 1, "Net Positive Suction Head for Emergency Core Cooling and
1 of 3 Revision 20 May 6, 2003
I
Variable
45
46
47
49
53
53A
SGS-UFSAR
TABLE 7.5-5 (Cont)
Containment Heat Removal System Pumps". PSE&G' s Emergency Core Cooling and Containment Heat Removal pumps,
suction storage
Same as
Same as
Same as
Same as
from tank
Guide
4
4
4
4
the residual heat removal pumps which take the containment sump when the refueling water
is empty, were designed to meet the criteria in 1.
1) The vi tal instrument bus parameters current, watts) aYe not adjustable by the
(voltage, frequency, operator. The vital
instru.ment inverter bus and automatically switches to the backup action.
supply without operator
2) Vi tal Instrument Bus Inverter failure annunciated on the overhead annunciator, Failure of all Channel Indications, and auxiliary alarm typewriter 115 VAC Instrument Bus Loss of
in alarm conditions for Loss of Vital Instrument Bus These lead the operator through actions required due to the loss of a vita: instrument bus to maintain the plant in a safe condition and to maintain
with the Technical The alarms are expected to be available during accident conditions.
3) The inverter and
on every shift. abnormalities are
volts, inverter output frequency, line are moni tared
must be taken if inverters are located in an
accessible mild environment area.
1) The PORV accumulators are normally supplied air by the control air header which is monitored by RG 1.97 instruments. In the event the air header containment isolation valves are closed the PORVs, the minimum of 100
can
control air from air to accumulators are designed to supply for a close/ open cycles. There are no actions the
with to the PORV accumulators air pressure actions to restore the control air. The operator is directed to procedures for loss of control air that contains steps necessary to restore control air pressure.
2) The accumulators are provided with low air pressure alarms to indicate that the air supply available to opera~e the PORVs is low. The alarm response directs the operator to for loss of control a'r that contains steps necessary to restore control air pressure. The alarms are expec~ed to be available during accident conditions.
2 of 3 Revision 25 October 26, 2010
TABLE 7.5-5 (Cont)
Variable Reference No. Justification
59
60B
62
69, 70, 71
73
The steam generator safety relief valves and the atmospheric dump valves are located on the main steam line, upstream of the MSIV. A radiation monitor is installed on the main steam line of each steam generator also upstream of the MSIV. This monitor will therefore give an indication of the level of radiation in the steam from the vents if the steam generator safety relief valves or the atmospheric dump valves should open.
The steam supply to the auxiliary feed pump is taken from the main steam line of No. 11 (21) and No. 13 (23) steam generators, upstream of the MSIVs. A radiation monitor is installed on the main steam line of each steam generator also upstream of the MSIV. If the auxiliary feed pump is in operation, this monitor will therefore give an indication of the level of radiation in the exhaust.
This variable was deleted in Revision 3 of Regulatory Guide 1.97.
These variables were changed to level 5 as a result of Technical Specification Amendments 254/235, which allows the use of contingency sampling capability in lieu of PASS.
DELETED*
*NOTE This variable is replaced by variable 35a as primary indication of SGTR.
3 of 3 SGS-UFSAR Revision 20
May 6, 2003