Respond to Alarms for Portable Exhauster POR06 Type REFERENCE Document No. ARP-T-351-00006 Rev/Mod B-1 Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S, Rev. 0 CHANGE HISTORY ( LAST 5 REV-MODS ) Rev-Mod Release Date Justification: Summary of Changes B-1 12/15/2015 Operations request Page 39 & 40 Replaced AOP-003 with AOP-011 B-0 09/24/2015 Reactivation and Periodic Review ADDED: POR06-VTP throughout procedure to the front of instrument and panel identification numbers. Struck out ER311VTPV103 and replace with T111WSTV006 on pages 3,5,8,10,12,14,16,18,20,22,26,28,39,41,49. Page 4 struck out drawing #H-14-107365, Page 37 modified step [5][7] added [5.1]&[5.2] Page 41,45,49 struck out part of NOTE. Page 45 modified step [3], Page 50 modified step [6], Page 54 struck out as required. A-2 10/13/2008 Inconsequential changes to address TFC-MD-061 requirements. Deleted Compliance Officer from reference to Environmental on pages 31 to 36, 53, and 54. Table of Contents Description Page POR06-VTP-FT-184 (INTERLOCK ON/FAN SHUTDOWN) STACK FLOW HI ........................................3 POR06-VTP-FT-184 (INTERLOCK ON/FAN SHUTDOWN) STACK FLOW LO .......................................5 POR06-VTP-PDT-177 HEATER DP HI ...........................................................................................................7 POR06-VTP-LT-195 (INTERLOCK ON/FAN SHUTDOWN) SEAL POT LEVEL HI .................................8 POR06-VTP-LT-195 (INTERLOCK ON/FAN SHUTDOWN) SEAL POT LEVEL LO .............................. 10 POR06-VTP-PDT-180 (INTERLOCK ON/FAN SHUTDOWN) 1 ST HEPA FILTER DP HI HI ..................12 POR06-VTP-PDT-182 (INTERLOCK ON/FAN SHUTDOWN) 2 ND HEPA FILTER DP HI HI ..................14 POR06-VTP-PDT-181 (INTERLOCK ON/FAN SHUTDOWN) 1 ST & 2 ND HEPA FILTERS DP HI HI .....16 POR06-VTP-PDT-180 (INTERLOCK ON TRANSMITTER FAILURE) 1 ST HEPA FILTER DP LO.........18 POR06-VTP-PDT-182 (INTERLOCK ON TRANSMITTER FAILURE) 2 ND HEPA FILTER DP LO ........20 POR06-VTP-PDT-181 (INTERLOCK ON TRANSMITTER FAILURE) 1 ST & 2 ND HEPA FILTERS DP LO22 POR06-VTP-PDT-180 1 ST HEPA FILTER DP HI..........................................................................................24 POR06-VTP-PDT-182 2 ND HEPA FILTER DP HI .........................................................................................25 POR06-VTP-PDT-180 1 ST HEPA FILTER DP ROC......................................................................................26 POR06-VTP-PDT-182 2 ND HEPA FILTER DP ROC .....................................................................................28

Upload: others

Post on 26-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

1 of 54

Tank Farm Plant Operating Procedure Ventilation

USQ # TF-15-2062-S, Rev. 0

CHANGE HISTORY ( LAST 5 REV-MODS )

Rev-Mod Release Date Justification: Summary of Changes

B-1 12/15/2015 Operations request Page 39 & 40 Replaced AOP-003 with AOP-011

B-0 09/24/2015 Reactivation and Periodic

Review

ADDED: POR06-VTP throughout procedure to the front of

instrument and panel identification numbers. Struck out

ER311VTPV103 and replace with T111WSTV006 on pages

3,5,8,10,12,14,16,18,20,22,26,28,39,41,49. Page 4 struck out

drawing #H-14-107365, Page 37 modified step [5][7] added

[5.1]&[5.2] Page 41,45,49 struck out part of NOTE. Page 45

modified step [3], Page 50 modified step [6], Page 54 struck out

as required.

A-2 10/13/2008

Inconsequential changes to

address TFC-MD-061

requirements.

Deleted Compliance Officer from reference to Environmental on

pages 31 to 36, 53, and 54.

Table of Contents

Description Page

POR06-VTP-FT-184 (INTERLOCK ON/FAN SHUTDOWN) STACK FLOW HI ........................................ 3

POR06-VTP-FT-184 (INTERLOCK ON/FAN SHUTDOWN) STACK FLOW LO ....................................... 5

POR06-VTP-PDT-177 HEATER DP HI ........................................................................................................... 7

POR06-VTP-LT-195 (INTERLOCK ON/FAN SHUTDOWN) SEAL POT LEVEL HI ................................. 8

POR06-VTP-LT-195 (INTERLOCK ON/FAN SHUTDOWN) SEAL POT LEVEL LO .............................. 10

POR06-VTP-PDT-180 (INTERLOCK ON/FAN SHUTDOWN) 1ST HEPA FILTER DP HI HI .................. 12

POR06-VTP-PDT-182 (INTERLOCK ON/FAN SHUTDOWN) 2ND HEPA FILTER DP HI HI .................. 14

POR06-VTP-PDT-181 (INTERLOCK ON/FAN SHUTDOWN) 1ST & 2ND HEPA FILTERS DP HI HI ..... 16

POR06-VTP-PDT-180 (INTERLOCK ON TRANSMITTER FAILURE) 1ST HEPA FILTER DP LO ......... 18

POR06-VTP-PDT-182 (INTERLOCK ON TRANSMITTER FAILURE) 2ND HEPA FILTER DP LO ........ 20

POR06-VTP-PDT-181 (INTERLOCK ON TRANSMITTER FAILURE) 1ST & 2ND HEPA FILTERS DP LO22

POR06-VTP-PDT-180 1ST HEPA FILTER DP HI.......................................................................................... 24

POR06-VTP-PDT-182 2ND HEPA FILTER DP HI ......................................................................................... 25

POR06-VTP-PDT-180 1ST HEPA FILTER DP ROC ...................................................................................... 26

POR06-VTP-PDT-182 2ND HEPA FILTER DP ROC ..................................................................................... 28

Page 2: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

2 of 54

POR06-VTP-PDT-178 PRE FILTER DP HI ................................................................................................... 30

POR06-VTP-TE-179 HEATER AIR TEMP LO ............................................................................................. 31

POR06-VTP-TE-179 HEATER AIR TEMP HI .............................................................................................. 33

POR06-VTP-TE-183 (INTERLOCK ON/HEATER OFF) STACK AIR TEMP HI ...................................... 35

POR06-VTP-P-001 GLYCOL PUMP OFF ..................................................................................................... 37

POR06-VTP-RA-301 BETA HI RAD ............................................................................................................. 39

POR06-VTP-RA-301 BETA CAM FAIL ....................................................................................................... 41

POR06-VTP-FCV-301 RECORD SAMPLE FLOW LO ................................................................................ 43

POR06-VTP-FCV-302 CAM SAMPLE FLOW LO ....................................................................................... 45

POR06-VTP-FCV-301 RECORD SAMPLE FLOW HI ................................................................................. 47

POR06-VTP-FCV-302 CAM SAMPLE FLOW HI ........................................................................................ 48

POR06-VTP-PDT-170 (INTERLOCK ON/FAN SHUTDOWN) PLENUM VACUUM HI ......................... 49

POR06-VTP-PDT-170 PLENUM VACUUM LO .......................................................................................... 51

TEMPERATURE RISE ALARM < 20 DEG F ............................................................................................... 53

RECORDS

No records are generated during the performance of this procedure.

Page 3: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

3 of 54

POR06-VTP-FT-184 (INTERLOCK ON/FAN SHUTDOWN) STACK FLOW HI Facility: Portable Exhauster

POR06-VTP-FT-184

(INTERLOCK ON/FAN SHUTDOWN)

STACK FLOW HI

Panel:POR06-VTP-

ENCL-107

Source: FT-184 Setpoint: 475 scfm

Alarm Class: Equipment Status

Alarm Description: High Exhauster Stack Flow

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear rotating beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-FT-184 (INTERLOCK ON/FAN

SHUTDOWN) STACK FLOW HI (K16) AND

PRESS K16.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] INFORM Shift Manager of alarm description and actions taken.

[5] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 4: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

4 of 54

Facility: Portable Exhauster

POR06-VTP-FT-184

(INTERLOCK ON/FAN SHUTDOWN)

STACK FLOW HI

Panel:POR06-VTP- ENCL-107

Source: FT-184 Setpoint: 475

scfm

(Continued) Possible Causes:

1. Transmitter failure.

2. Improper transmitter calibration Programmable Logic Controller program fan speed

controller has been modified or parameters changed.

3. Verabar instrument or tubing has been damaged or plugged.

4. Improper valve line-up.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 5: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

5 of 54

POR06-VTP-FT-184 (INTERLOCK ON/FAN SHUTDOWN) STACK FLOW LO Facility: Portable Exhauster

POR06-VTP-FT-184

(INTERLOCK ON/FAN SHUTDOWN)

STACK FLOW LO

Panel:POR06-VTP-

ENCL-107

Source: FT-184 Setpoint: 225 scfm

Alarm Class: Equipment Status

Alarm Description: Low Exhauster Stack Flow

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear rotating beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-FT-184 (INTERLOCK ON/FAN

SHUTDOWN) STACK FLOW LO (K15) AND

PRESS K15.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view POR06-

VTP- PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] INFORM Shift Manager of alarm description and actions taken.

[5] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 6: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

6 of 54

Facility: Portable Exhauster

POR06-VTP-FT-184

(INTERLOCK ON/FAN SHUTDOWN)

STACK FLOW LO

Panel:POR06-VTP-

ENCL-107

Source: FT-184 Setpoint: 225 scfm

(Continued) Possible Causes:

1. Transmitter failure.

2. Improper transmitter calibration.

3. Programmable Logic Controller program fan speed controller has been modified or

parameters changed.

4. Verabar instrument or tubing has been damaged or plugged.

5. Improper valve line-up.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 7: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

7 of 54

POR06-VTP-PDT-177 HEATER DP HI Facility: Portable Exhauster

POR06-VTP-PDT-177

HEATER DP HI

Panel:POR06-VTP- ENCL-107

Source: PDT-177 Setpoint: 1.4 in WG

Alarm Class: Equipment Status

Alarm Description: Heater alarm (POR06-VTP-PDT-177) indicates high differential pressure

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear rotating beacon XA-101 is illuminated.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-177 HEATER/DEMISTER DP

HI (K3) AND

PRESS K3.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] CHECK ACTIVE ALARMS area of alarm panel view AP-001 to determine if alarm

condition is still active.

[3] NOTIFY Shift Manager of alarm description and actions taken.

[4] HPT TAKE dose rate survey at Heater.

[5] NOTIFY Shift Manager of findings.

Possible Causes:

1. Maintenance work on Pressure Alarm.

2. Failure of Pressure Transmitter.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 8: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

8 of 54

POR06-VTP-LT-195 (INTERLOCK ON/FAN SHUTDOWN) SEAL POT LEVEL HI Facility: Portable Exhauster

POR06-VTP-LT-195

(INTERLOCK ON/FAN SHUTDOWN)

SEAL POT LEVEL HI

Panel: POR06-VTP-

ENCL-107

Source: LT-195 Setpoint: 80% LEVEL

Alarm Class: Equipment Status

Alarm Description: High Seal Pot Liquid Level

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ENSURE automatic actions have taken place.

NOTE - Alarm will only show in ACTIVE ALARMS and alarm beacon will flash as long as

alarm is current. After alarm condition has cleared, alarm will be logged in ALARM

HISTORY. Manual acknowledgement of alarm is not necessary. When alarm

condition is no longer active the alarm will clear and alarm beacon will cease to flash

automatically.

[2] CHECK ACTIVE ALARMS area of alarm panel view POR06-VTP-PV-101 to

determine if alarm condition is still active.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] CONFIRM field reading for POR06-VTP-LG-101 is at or above 80% volume.

[5] INFORM Shift Manager of alarm description.

[6] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 9: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

9 of 54

Facility: Portable Exhauster

POR06-VTP-LT-195

(INTERLOCK ON/FAN SHUTDOWN)

SEAL POT LEVEL HI

Panel: POR06-VTP-

ENCL-107

Source: LT-195 Setpoint: 80%

LEVEL

(Continued) Possible Causes:

1. Transmitter failure.

2. Improper C-Box transmitter calibration.

3. Seal pot reservoir has been overfilled.

4. Seal pot transfer pump has malfunctioned or failed.

5. Improper valve line-up.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 10: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

10 of 54

POR06-VTP-LT-195 (INTERLOCK ON/FAN SHUTDOWN) SEAL POT LEVEL LO Facility: Portable Exhauster

POR06-VTP-LT-195

(INTERLOCK ON/FAN SHUTDOWN)

SEAL POT LEVEL LO

Panel: POR06-VTP-

ENCL-107

Source: LT-195 Setpoint: 30% LEVEL

Alarm Class: Equipment Status

Alarm Description: Low Seal Pot Liquid Level

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ENSURE automatic actions have taken place.

NOTE - Alarm will only show in ACTIVE ALARMS and alarm beacon will flash as long as

alarm is current. After alarm condition has cleared, alarm will be logged in ALARM

HISTORY. Manual acknowledgement of alarm is not necessary. When alarm

condition is no longer active the alarm will clear and alarm beacon will cease to flash

automatically.

[2] CHECK ACTIVE ALARMS area of alarm panel view POR06-VTP-PV-101 to

determine if alarm condition is still active.

[3] ENSURE breather filter isolation valve is T111-WST-V-006 is OPEN.

[4] CONFIRM field reading for POR06-VTP-LG-101 is at or below 30% volume.

[5] INFORM Shift Manager of alarm description.

[6] IF directed by Shift Manager, REFILL seal pot per TO-060-045.

[7] CHECK for leaks.

[8] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 11: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

11 of 54

Facility: Portable Exhauster

POR06-VTP-LT-195

(INTERLOCK ON/FAN SHUTDOWN)

SEAL POT LEVEL LO

Panel: POR06-VTP-

ENCL-107

Source: LT-195 Setpoint: 30% LEVEL

(Continued) Possible Causes:

1. Transmitter failure.

2. Improper C-Box transmitter calibration.

3. Seal pot reservoir has a leak.

4. Seal pot liquid has evaporated

5. Hi Plenum Vacuum drained the seal pot.

6. Improper valve line-up.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 12: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

12 of 54

POR06-VTP-PDT-180 (INTERLOCK ON/FAN SHUTDOWN) 1ST HEPA FILTER DP HI HI Facility: Portable Exhauster

POR06-VTP-PDT-180

(INTERLOCK ON/FAN SHUTDOWN)

1ST HEPA FILTER DP HI HI

Panel: POR06-VTP-

ENCL-107

Source: PDT-180 Setpoint: 5.4 in WG

Alarm Class: Environmental Impact

Alarm Description: First HEPA Filter (FLT-002) High/High Differential Pressure

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-180 (INTERLOCK ON/FAN

SHUTDOWN) 1ST HEPA FILTER DP HI HI (K7) AND

PRESS K7.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] REQUEST HPT perform dose rate survey of HEPA filter housing.

[5] INFORM Shift Manager of alarm description.

[6] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 13: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

13 of 54

Facility: Portable Exhauster

POR06-VTP-PDT-180

(INTERLOCK ON/FAN SHUTDOWN)

1ST HEPA FILTER DP HI HI

Panel: POR06-VTP-

ENCL-107

Source: PDT-180 Setpoint: 5.4 in WG

(Continued) Possible Causes:

1. HEPA filter loaded with particulate.

2. Improper transmitter calibration.

3. Moisture loading on filter.

4. Instrument tubing has been damaged or plugged.

5. Improper instrument valve line-up.

6. Pressure transmitter failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 14: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

14 of 54

POR06-VTP-PDT-182 (INTERLOCK ON/FAN SHUTDOWN) 2ND HEPA FILTER DP HI HI Facility: Portable Exhauster

POR06-VTP-PDT-182

(INTERLOCK ON/FAN SHUTDOWN)

2ND HEPA FILTER DP HI HI

Panel: POR06-VTP-

ENCL-107

Source: PDT-182 Setpoint: 3.7 in WG

Alarm Class: Environmental Impact

Alarm Description: Second HEPA Filter (FLT-003) High/High Differential Pressure

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-182 (INTERLOCK ON/FAN

SHUTDOWN) 2ND HEPA FILTER DP HI HI (K13) AND

PRESS K13.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] REQUEST HPT perform dose rate survey of HEPA filter housing.

[5] INFORM Shift Manager of alarm description.

[6] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 15: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

15 of 54

Facility: Portable Exhauster

POR06-VTP-PDT-182

(INTERLOCK ON/FAN SHUTDOWN)

2ND HEPA FILTER DP HI HI

Panel: POR06-VTP-

ENCL-107

Source: PDT-182 Setpoint: 3.7 in WG

(Continued) Possible Causes:

1. 2nd HEPA filter loaded with particulate.

2. Improper transmitter calibration.

3. Moisture loading on filter.

4. Instrument tubing has been damaged or plugged.

5. Improper instrument valve line-up.

6. Pressure transmitter failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 16: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

16 of 54

POR06-VTP-PDT-181 (INTERLOCK ON/FAN SHUTDOWN) 1ST & 2ND HEPA FILTERS DP

HI HI Facility: Portable Exhauster

POR06-VTP-PDT-181

(INTERLOCK ON/FAN SHUTDOWN)

1ST & 2ND HEPA FILTERS DP HI HI

Panel: POR06-VTP-

ENCL-107

Source: PDT-181 Setpoint: 5.4 in WG

Alarm Class: Environmental Impact

Alarm Description: First and/or Second HEPA Filter (FLT-002/FLT-003) High/High Differential

Pressure

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-181 (INTERLOCK ON/FAN

SHUTDOWN) 1ST & 2ND HEPA FILTER DP HI HI (K10) AND

PRESS K10.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] REQUEST HPT perform dose rate survey of HEPA filter housing.

[5] INFORM Shift Manager of alarm description.

[6] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 17: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

17 of 54

Facility: Portable Exhauster

POR06-VTP-PDT-181

(INTERLOCK ON/FAN SHUTDOWN)

1ST & 2ND HEPA FILTERS DP HI HI

Panel: POR06-VTP-

ENCL-107

Source: PDT-181 Setpoint: 5.4 in WG

(Continued) Possible Causes: (Cont.)

1. 1st or 2nd HEPA filter loaded with particulate.

2. Improper transmitter calibration.

3. Moisture loading on filter.

4. Instrument tubing has been damaged or plugged.

5. Improper instrument valve line-up.

6. Pressure transmitter failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 18: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

18 of 54

POR06-VTP-PDT-180 (INTERLOCK ON TRANSMITTER FAILURE) 1ST HEPA FILTER DP

LO Facility: Portable Exhauster

POR06-VTP-PDT-180

(INTERLOCK ON TRANSMITTER

FAILURE) 1ST HEPA FILTER DP LO

Panel: POR06-VTP-

ENCL-107

Source: PDT-180 Setpoint: 0.2 in WG

Alarm Class: Environmental Impact

Alarm Description: First HEPA Filter (FLT-002) Low Differential Pressure

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-180 (INTERLOCK ON

TRANSMITTER FAILURE) 1ST HEPA FILTER DP LO (K5) AND

PRESS K5.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] ISOLATE tank from exhauster by closing valves POR06-VTP-V-135 and

POR06-VTP-V-136.

[5] REQUEST HPT perform dose rate and contamination surveys of HEPA filter housing

and general area.

[6] INFORM Shift Manager of alarm description.

[7] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 19: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

19 of 54

Facility: Portable Exhauster

POR06-VTP-PDT-180

(INTERLOCK ON TRANSMITTER

FAILURE) 1ST HEPA FILTER DP LO

Panel: POR06-VTP-

ENCL-107

Source: PDT-180 Setpoint: 0.2 in WG

(Continued) Possible Causes:

1. Transmitter failure.

2. Improper transmitter calibration.

3. Loss of power supply.

4. Signal wire failure.

5. Instrument tubing has been damaged or plugged.

6. Improper instrument valve line-up.

7. Failed filter.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 20: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

20 of 54

POR06-VTP-PDT-182 (INTERLOCK ON TRANSMITTER FAILURE) 2ND HEPA FILTER

DP LO Facility: Portable Exhauster

POR06-VTP-PDT-182

(INTERLOCK ON TRANSMITTER

FAILURE) 2ND HEPA FILTER DP LO

Panel: POR06-VTP-

ENCL-107

Source: PDT-182 Setpoint: 0.2 in WG

Alarm Class: Environmental Impact

Alarm Description: Second HEPA Filter (FLT-003) Low Differential Pressure

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-182 (INTERLOCK ON

TRANSMITTER FAILURE) 2ND HEPA FILTER DP LO (K11) AND

PRESS K11.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] ISOLATE tank from exhauster by closing valves POR06-VTP-V-135 and

POR06-VTP-V-136.

[5] REQUEST HPT perform dose rate and contamination surveys of HEPA filter housing

and general area.

[6] INFORM Shift Manager of alarm description.

[7] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 21: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

21 of 54

Facility: Portable Exhauster

POR06-VTP-PDT-182

(INTERLOCK ON TRANSMITTER

FAILURE) 2ND HEPA FILTER DP LO

Panel: POR06-VTP-

ENCL-107

Source: PDT-182 Setpoint: 0.2 in WG

(Continued) Possible Causes:

1. Transmitter failure.

2. Improper transmitter calibration.

3. Loss of power supply.

4. Signal wire failure.

5. Instrument tubing has been damaged or plugged.

6. Improper instrument valve line-up.

7. Failed filter.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 22: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

22 of 54

POR06-VTP-PDT-181 (INTERLOCK ON TRANSMITTER FAILURE) 1ST & 2ND HEPA

FILTERS DP LO Facility: Portable Exhauster

POR06-VTP-PDT-181

(INTERLOCK ON TRANSMITTER

FAILURE) 1ST & 2ND HEPA FILTERS

DP LO

Panel: POR06-VTP-

ENCL-107

Source: PDT-181 Setpoint: 0.2 in WG

Alarm Class: Environmental Impact

Alarm Description: First and/or Second HEPA Filter (FLT-002/FLT-003) Low Differential Pressure

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-181 (INTERLOCK ON

TRANSMITTER FAILURE) 1ST & 2ND HEPA FILTERS DP LO (K9) AND

PRESS K9.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] ISOLATE tank from exhauster by closing valves POR06-VTP-V-135 and

POR06-VTP-V-136.

[5] REQUEST HPT perform dose rate and contamination surveys of HEPA filter housing

and general area.

[6] INFORM Shift Manager of alarm description.

[7] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 23: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

23 of 54

Facility: Portable Exhauster

POR06-VTP-PDT-181

(INTERLOCK ON TRANSMITTER

FAILURE) 1ST & 2ND HEPA FILTERS

DP LO

Panel: POR06-VTP-

ENCL-107

Source: PDT-181 Setpoint: 0.2 in WG

(Continued) Possible Causes:

1. Transmitter failure.

2. Improper transmitter calibration.

3. Loss of power supply.

4. Signal wire failure.

5. Instrument tubing has been damaged or plugged.

6. Improper instrument valve line-up.

7. Failed filter.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 24: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

24 of 54

POR06-VTP-PDT-180 1ST HEPA FILTER DP HI Facility: Portable Exhauster

POR06-VTP-PDT-180

1ST HEPA FILTER DP HI

Panel: POR06-VTP-ENCL-107

Source: PDT-180 Setpoint: 4.5 in WG

Alarm Class: Environmental Impact

Alarm Description: First HEPA Filter (FLT 002) High Differential Pressure

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-180 1ST HEPA FILTER DP HI

(K6) AND

PRESS K6.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] REQUEST HPT perform dose rate survey of HEPA filter housing.

[3] INFORM Shift Manager of alarm description.

Possible Causes:

1. 1st HEPA filter loaded with particulate.

2. Improper transmitter calibration.

3. Moisture loading on filter.

4. Instrument tubing has been damaged or plugged.

5. Improper instrument valve line-up.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 25: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

25 of 54

POR06-VTP-PDT-182 2ND HEPA FILTER DP HI Facility: Portable Exhauster

POR06-VTP-PDT-182

2ND HEPA FILTER DP HI

Panel: POR06-VTP-ENCL-107

Source: PDT-182 Setpoint: 3.2 in WG

Alarm Class: Equipment Status

Alarm Description: Second HEPA Filter (FLT 003) High Differential Pressure

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-182 2ND HEPA FILTER DP

HI (K12) AND

PRESS K12.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] REQUEST HPT perform dose rate survey of HEPA filter housing.

[3] INFORM Shift Manager of alarm description.

Possible Causes:

1. 2nd HEPA filter loaded with particulate.

2. Improper transmitter calibration.

3. Moisture loading on filter.

4. Instrument tubing has been damaged or plugged.

5. Improper instrument valve line-up.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 26: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

26 of 54

POR06-VTP-PDT-180 1ST HEPA FILTER DP ROC Facility: Portable Exhauster

POR06-VTP-PDT-180

1ST HEPA FILTER DP ROC

Panel: POR06-

VTP-

ENCL-10

7

Source: PDT-180 Setpoint: 0.5 in WG/minute

Alarm Class: Equipment Status

Alarm Description: First HEPA Filter (FLT-002) Differential Pressure Rate of Change (ROC)

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-180 1ST HEPA FILTER DP

ROC (K8) AND

PRESS K8.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] REQUEST HPT perform dose rate survey of HEPA filter housing.

[5] INFORM Shift Manager of alarm description.

[6] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 27: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

27 of 54

Facility: Portable Exhauster

POR06-VTP-PDT-180

1ST HEPA FILTER DP ROC

Panel: POR06-

VTP-

ENCL-10

7

Source: PDT-180 Setpoint: 0.5 in WG/minute

(Continued) Possible Causes:

1. Transmitter failure.

2. Improper transmitter calibration.

3. 1st HEPA filter failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 28: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

28 of 54

POR06-VTP-PDT-182 2ND HEPA FILTER DP ROC Facility: Portable Exhauster

POR06-VTP-PDT-182

2ND HEPA FILTER DP ROC

Panel: POR06-

VTP-

ENCL-107

Source: PDT-182 Setpoint: 0.5 in WG/minute

Alarm Class: Equipment Status

Alarm Description: Second HEPA Filter (FLT-003) Differential Pressure Rate of Change (ROC)

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Exhauster shuts down.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-182 2ND HEPA FILTER DP

ROC (K14) AND

PRESS K14.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] REQUEST HPT perform dose rate survey of HEPA filter housing.

[5] INFORM Shift Manager of alarm description.

[6] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 29: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

29 of 54

Facility: Portable Exhauster

POR06-VTP-PDT-182

2ND HEPA FILTER DP ROC

Panel: POR06-

VTP-

ENCL-107

Source: PDT-182 Setpoint: 0.5 in WG/minute

(Continued) Possible Causes:

1. Transmitter failure.

2. Improper transmitter calibration.

3. 2nd HEPA filter failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 30: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

30 of 54

POR06-VTP-PDT-178 PRE FILTER DP HI Facility: Portable Exhauster

POR06-VTP-PDT-178

PRE FILTER DP HI

Panel: POR06-VTP-ENCL-107

Source: PDT-178 Setpoint: 1.4 in WG

Alarm Class: Equipment Status

Alarm Description: Pre-Filter High (FLT-001) High Differential Pressure

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-178 PRE FILTER DP HI (K4)

AND

PRESS K4.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] REQUEST HPT perform dose rate survey of HEPA filter housing.

[4] INFORM Shift Manager of alarm description.

Possible Causes:

1. Pre-Filter loaded with particulate.

2. Improper transmitter calibration.

3. Instrument tubing has been damaged or plugged.

4. Improper instrument valve line-up.

5. Moisture loading on filter.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 31: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

31 of 54

POR06-VTP-TE-179 HEATER AIR TEMP LO Facility: Portable Exhauster

POR06-VTP-TE-179

HEATER AIR TEMP LO

Panel: POR06-VTP-ENCL-107

Source: TE-179 Setpoint: <40 F

Alarm Class: Equipment Status

Alarm Description: First HEPA Filter Inlet Temperature LO

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

Immediate Actions:

[1] ENSURE automatic actions have taken place.

NOTE - Alarm will only show in ACTIVE ALARMS and alarm beacon will flash as long as

alarm is current. After alarm condition has cleared, alarm will be logged in ALARM

HISTORY. Manual acknowledgement of alarm is not necessary. When alarm

condition is no longer active the alarm will clear and alarm beacon will cease to flash

automatically.

[2] CHECK ACTIVE ALARMS area of alarm panel view POR06-VTP-PV-101 to

determine if alarm condition is still active.

[3] REQUEST Shift Manger to notify Environmental.

[4] STOP all waste disturbing retrieval activities in the tank(s) being ventilated by this

exhauster, until air stream temperature is within specified range.

NOTE – Glycol heater adjustments respond slowly, it is recommended to adjust heater in steps

of a few degrees (or as directed by Shift Manager). It may be necessary to repeat the

following three steps several times to achieve the desired air stream temperature.

[5] ADJUST glycol heater thermostat as needed to restore air stream temperature to desired

operating conditions.

[6] MONITOR temperature values periodically for one hour.

[7] IF air stream temperature is not within specified range, REPEAT step [5] and [6] until

desired temperature is achieved.

(Continued on Next Page)

Page 32: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

32 of 54

Facility: Portable Exhauster

POR06-VTP-TE-179

HEATER AIR TEMP LO

Panel: POR06-VTP-ENCL-107

Source: TE-179 Setpoint: <40 F

(Continued) Immediate Actions: (Cont.)

[8] IF the desired air stream temperature rise is not achievable within 2 shifts, NOTIFY

Shift Manager AND

SHUT DOWN exhauster per TO-060-045.

[9] REQUEST Shift Manager to notify Environmental.

Possible Causes:

1. Thermocouple failure.

2. Pump failure.

3. Glycol level low.

4. Temperature switch TS-206 failed closed.

5. Loss of power supply.

6. Programmable Logic Controller failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 33: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

33 of 54

POR06-VTP-TE-179 HEATER AIR TEMP HI Facility: Portable Exhauster

POR06-VTP-TE-179

HEATER AIR TEMP HI

Panel: POR06-VTP-ENCL-107

Source: TE-179 Setpoint: 130 F

Alarm Class: Equipment Status

Alarm Description: First HEPA Filter Inlet Temperature High

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Glycol heater shuts down.

Immediate Actions:

[1] ENSURE automatic actions have taken place.

NOTE - Alarm will only show in ACTIVE ALARMS and alarm beacon will flash as long as

alarm is current. After alarm condition has cleared, alarm will be logged in ALARM

HISTORY. Manual acknowledgement of alarm is not necessary. When alarm

condition is no longer active the alarm will clear and alarm beacon will cease to flash

automatically.

[2] CHECK ACTIVE ALARMS area of alarm panel view POR06-VTP-PV-101 to

determine if alarm condition is still active.

[3] REQUEST Shift Manger to notify Environmental.

[4] STOP all waste disturbing retrieval activities in the tank(s) being ventilated by this

exhauster, until air stream temperature is within specified range.

NOTE – Glycol heater adjustments respond slowly, it is recommended to adjust heater in steps

of a few degrees (or as directed by Shift Manager). It may be necessary to repeat the

following three steps several times to achieve the desired air stream temperature.

[5] ADJUST glycol heater thermostat as needed to restore air stream temperature to desired

operating conditions.

[6] MONITOR temperature values periodically for one hour.

[7] IF air stream temperature is not within specified range, REPEAT steps [5] and [6] until

desired temperature is achieved.

(Continued on Next Page)

Page 34: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

34 of 54

Facility: Portable Exhauster

POR06-VTP-TE-179

HEATER AIR TEMP HI

Panel: POR06-VTP-ENCL-107

Source: TE-179 Setpoint: 130 F

(Continued) Immediate Actions: (Cont.)

[8] IF the desired air stream temperature rise is not achievable within 2 shifts, NOTIFY

Shift Manager AND

SHUT DOWN exhauster per TO-060-045.

[9] REQUEST Shift Manager to notify Environmental.

Possible Causes:

1. Thermocouple failure.

2. Temperature switch TS-206 failed closed.

3. Loss of power supply.

4. Programmable Logic Controller failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 35: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

35 of 54

POR06-VTP-TE-183 (INTERLOCK ON/HEATER OFF) STACK AIR TEMP HI Facility: Portable Exhauster

POR06-VTP-TE-183

(INTERLOCK ON/HEATER OFF)

STACK AIR TEMP HI

Panel: POR06-VTP-ENCL-107

Source: TE-183 Setpoint: 120 F

Alarm Class: Equipment Status

Alarm Description: Stack Air Temperature High

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

2. Glycol heater shuts down.

Immediate Actions:

[1] ENSURE automatic actions have taken place.

NOTE - Alarm will only show in ACTIVE ALARMS and alarm beacon will flash as long as

alarm is current. After alarm condition has cleared alarm will be logged in ALARM

HISTORY. Manual acknowledgement of alarm is not necessary. When alarm

condition is no longer active the alarm will clear and alarm beacon will cease to flash

automatically.

[2] CHECK ACTIVE ALARMS area of alarm panel view POR06-VTP-PV-101 to

determine if alarm condition is still active.

[3] REQUEST Shift Manger to notify Environmental.

[4] STOP all waste disturbing retrieval activities in the tank(s) being ventilated by this

exhauster, until air stream temperature is within specified range.

NOTE - Glycol heater adjustments respond slowly, it is recommended to adjust the heater in

steps of a few degrees (or as directed by Shift Manager). It may be necessary to repeat

the following three steps several times to achieve the desired air stream temperature.

- The glycol hearer will automatically reset at 115F stack temperature and restart the

glycol heater.

- When stack temperature is less than 115F the clear rotating beacon will automatically

clear with no operator action.

[5] ADJUST glycol heater thermostat as needed to restore air stream temperature to desired

operating conditions.

(Continued on Next Page)

Page 36: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

36 of 54

Facility: Portable Exhauster

POR06-VTP-TE-183

(INTERLOCK ON/HEATER OFF)

STACK AIR TEMP HI

Panel: POR06-VTP-ENCL-107

Source: TE-183 Setpoint: 120 F

(Continued) Immediate Actions: (Cont.)

[6] MONITOR temperature values periodically for one hour.

[7] IF air stream temperature is not within specified range, REPEAT step [5] and [6] until

desired temperature is achieved.

[8] IF the desired air stream temperature rise is not achievable within 2 shifts, NOTIFY

Shift Manager AND

SHUT DOWN exhauster per TO-060-045.

[9] REQUEST Shift Manager to notify Environmental.

Possible Causes:

1. Thermocouple failure.

2. Temperature switch TS-206 failed closed or set too high.

3. Loss of power supply.

4. Programmable Logic Controller failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 37: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

37 of 54

POR06-VTP-P-001 GLYCOL PUMP OFF Facility: Portable Exhauster

POR06-VTP-P-001

GLYCOL PUMP OFF

Panel: POR06-VTP-ENCL-107

Source: P-001 Setpoint: N/A

Alarm Class: Equipment Status

Alarm Description: Glycol pump indicates pump is off

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Heater shuts down.

2. Clear rotating beacon (XA-101) is illuminated.

Immediate Actions:

[1] ENSURE automatic actions have taken place.

NOTE - Alarm will only show in ACTIVE ALARMS and alarm beacon will flash as long as

alarm is current. After alarm condition has cleared, alarm will be logged in ALARM

HISTORY. Manual acknowledgement of alarm is not necessary. When alarm

condition is no longer active the alarm will clear and alarm beacon will cease to flash

automatically.

[2] CHECK ACTIVE ALARMS area of alarm panel view POR06-VTP-PV-101 to

determine if alarm condition is still active.

[3] ENSURE glycol pump switch POR06-VTP-HS-102 is in ON position.

[4] NOTIFY Shift Manager of findings.

[5] IF directed by Shift Manager, ATTEMPT to restart glycol pump

[5.1] POSITION POR06-VTP-HS-102 on POR06-VTP-CP-105 EXHAUSTER

CONTROL PANEL to OFF.

[5.2] POSITION POR06-VTP-HS-102 on POR06-VTP-CP-105 EXHAUSTER

CONTROL PANEL to ON.

[6] IF directed by Shift Manager, SHUT DOWN exhauster per TO-060-045.

[7] IF repair is needed, REQUEST initiation of Work Package to troubleshoot and repair

glycol pump.

(Continued on Next Page)

Page 38: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

38 of 54

Facility: Portable Exhauster

POR06-VTP-P-001

GLYCOL PUMP OFF

Panel: POR06-VTP-ENCL-107

Source: P-001 Setpoint: N/A

(Continued) Possible Causes:

1. Glycol pump switch POR06-VTP-HS-102 is in OFF position.

2. Glycol level low.

3. Glycol pump failure.

4. Heater core or piping leaks.

5. Power failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 39: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

39 of 54

POR06-VTP-RA-301 BETA HI RAD Facility: Portable Exhauster

Panel: POR06-VTP-ENCL-107

POR06-VTP-RA-301

BETA HI RAD

Source: RA-301 Setpoint: 3,000 cpm

Alarm Class: Environmental Impact

Alarm Description: High beta count

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Exhauster fan shuts down.

2. Warning bell sounds.

3. Clear rotating beacon XA-101 illuminates.

4. Red rotating beacon XA-301 illuminates.

5. Vacuum pumps POR06-VTP-P-301 or POR06-VTP-P-302 shut down.

Immediate Actions:

[1] IMMEDIATELY EVACUATE personnel from work area.

[2] ENSURE automatic actions have taken place.

[3] INFORM Shift Manager of alarm description.

[4] NOTIFY HPT.

[5] IF HPT reports the spread of contamination, REQUEST Shift Manager RESPOND per

TF-AOP-011.

[6] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[7] IF directed by Shift Manager, START exhauster per TO-060-045.

[8] ACKNOWLEDGE alarm in the following order:

[8.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F8] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[8.2] IDENTIFY BLINKING alarm POR06-VTP-RA-301 BETA HI RAD (K6) AND

PRESS K6.

[9] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

(Continued on Next Page)

Page 40: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

40 of 54

Facility: Portable Exhauster

Panel: POR06-VTP-ENCL-107 POR06-VTP-RA-301

BETA HI RAD

Source: RA-301 Setpoint: 3,000 cpm

(Continued) Possible Causes:

1. CAM failure.

2. HEPA filter failure.

3. CAM false alarm.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

TF-AOP-011, Response to Elevated Airborne Radioactivity

Page 41: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

41 of 54

POR06-VTP-RA-301 BETA CAM FAIL Facility: Portable Exhauster

POR06-VTP-RA-301

BETA CAM FAIL

Panel: POR06-VTP-ENCL-107

Source: RA-301 Setpoint: N/A

Alarm Class: Equipment Status

Alarm Description: Continuous Air Monitor failure

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Exhauster fan shuts down.

2. Clear rotating beacon XA-101 illuminates.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE GEMS ALARMS [F8] from ACTIVE ALARMS

area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-RA-301 BETA CAM FAIL (K5)

AND

PRESS K5.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view POR06-

VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] INFORM Shift Manager of alarm description.

[5] NOTIFY HPT.

[6] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 42: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

42 of 54

Facility: Portable Exhauster

POR06-VTP-RA-301

BETA CAM FAIL

Panel: POR06-VTP-ENCL-107

Source: RA-301 Setpoint: N/A

(Continued) Possible Causes:

1. CAM failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 43: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

43 of 54

POR06-VTP-FCV-301 RECORD SAMPLE FLOW LO Facility: Portable Exhauster

POR06-VTP-FCV-301

RECORD SAMPLE FLOW LO

Panel: POR06-VTP-ENCL-107

Source: FCV-301 Setpoint: 0.85 cfm

Alarm Class: Environmental Impact

Alarm Description: Record sample flow low

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance, or testing procedures.

Automatic Actions:

1. Running vacuum pump POR06-VTP-P-301 or POR06-VTP-P-302 switches to standby

pump after 20 seconds.

2. Clear Rotating Beacon XA-101 is illuminated.

3. Exhauster shuts down if flow is not restored within 20 seconds after pumps switch.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE GEMS ALARMS [F8] from ACTIVE ALARMS

area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-FCV-301 RECORD SAMPLE

FLOW LO (K1) AND

PRESS K1.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] IF exhauster shuts down, ENSURE breather filter isolation valve T111-WST-V-006 is

OPEN.

[4] INFORM Shift Manager of alarm description.

[5] NOTIFY HPT of alarm.

[6] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 44: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

44 of 54

Facility: Portable Exhauster

POR06-VTP-FCV-301

RECORD SAMPLE FLOW LO

Panel: POR06-VTP-ENCL-107

Source: FCV-301 Setpoint: 0.85 cfm

(Continued) Possible Causes:

1. Vacuum pump failure.

2. Flow control valve failure.

3. Loose/disconnected fitting on sample tubing.

4. Instrument tubing has been damaged or plugged.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 45: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

45 of 54

POR06-VTP-FCV-302 CAM SAMPLE FLOW LO Facility: Portable Exhauster

POR06-VTP-FCV-302

CAM SAMPLE FLOW LO

Panel: POR06-VTP-ENCL-107

Source: FCV-302 Setpoint: 0.85 cfm

Alarm Class: Equipment Status

Alarm Description: Continuous Air Monitor sample flow low

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Running vacuum pump POR06-VTP-P-301 or POR06-VTP-P-302 switches to standby

pump after 20 seconds.

2. Clear rotating beacon XA-101 illuminates.

3. Exhauster shuts down if flow is not restored within 20 seconds after pumps switch.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE GEMS ALARMS [F8] from ACTIVE ALARMS

area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-FCV-302 CAM SAMPLE FLOW

LO (K4) AND

PRESS K4.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] IF exhauster shuts down, ENSURE breather filter isolation valve is OPEN.

[4] INFORM Shift Manager of alarm description.

[5] NOTIFY HPT of alarm.

[6] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 46: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

46 of 54

Facility: Portable Exhauster

POR06-VTP-FCV-302

CAM SAMPLE FLOW LO

Panel: POR06-VTP-ENCL-107

Source: FCV-302 Setpoint: 0.85 cfm

(Continued) Possible Causes:

1. Vacuum pump failure.

2. Flow control valve failure.

3. Loose/disconnected fitting on sample tubing.

4. Obstructed sample tubing.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 47: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

47 of 54

POR06-VTP-FCV-301 RECORD SAMPLE FLOW HI Facility: Portable Exhauster

POR06-VTP-FCV-301

RECORD SAMPLE FLOW HI

Panel: POR06-VTP-ENCL-107

Source: FCV-301 Setpoint: 1.15 cfm

Alarm Class: Equipment Status

Alarm Description: Record sample flow high

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE GEMS ALARMS [F8] from ACTIVE ALARMS

area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-FCV-301 RECORD SAMPLE

FLOW HI (K2) AND

PRESS K2.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] INFORM Shift Manager of alarm description.

Possible Causes:

1. Vacuum pump failure.

2. Flow control valve failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 48: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

48 of 54

POR06-VTP-FCV-302 CAM SAMPLE FLOW HI Facility: Portable Exhauster

POR06-VTP-FCV-302

CAM SAMPLE FLOW HI

Panel: POR06-VTP-ENCL-107

Source: FCV-302 Setpoint: 1.15 cfm

Alarm Class: Equipment Status

Alarm Description: CAM sample flow high

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear Rotating Beacon XA-101 is illuminated.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE GEMS ALARMS [F8] from ACTIVE ALARMS

area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-FCV-302 CAM SAMPLE FLOW

HI (K3) AND

PRESS K3.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] INFORM Shift Manager of alarm description.

Possible Causes:

1. Vacuum pump failure.

2. Flow control valve failure.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 49: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

49 of 54

POR06-VTP-PDT-170 (INTERLOCK ON/FAN SHUTDOWN) PLENUM VACUUM HI Facility: Portable Exhauster

POR06-VTP-PDT-170

(INTERLOCK ON/FAN

SHUTDOWN)

PLENUM VACUUM HI

Panel: POR06-VTP-ENCL-107

Source: PDT-170 Setpoint: - in WG

Alarm Class: Equipment Status

Alarm Description: Interlock On/Fan shutdown/Plenum vacuum HI

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Exhauster shuts down.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-170 (INTERLOCK ON/FAN

SHUTDOWN) PLENUM VACUUM HI (K2) AND

PRESS K2.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view

POR06-VTP-PV-101.

[2] ENSURE automatic actions have taken place.

[3] ENSURE breather filter isolation valve T111-WST-V-006 is OPEN.

[4] INFORM Shift Manager of alarm description.

[5] IF directed by Shift Manager, START exhauster per TO-060-045.

(Continued on Next Page)

Page 50: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

50 of 54

Facility: Portable Exhauster

POR06-VTP-PDT-170

(INTERLOCK ON/FAN

SHUTDOWN)

PLENUM VACUUM HI

Panel: POR06-VTP-ENCL-107

Source: PDT-170 Setpoint: -in WG(vacuum)

(Continued) Possible Causes:

1. Upstream isolation valve partially closed.

2. Blockage in inlet air upstream of valve POR06-VTP-V-135.

3. Improper transmitter calibration.

4. Instrument tubing has been damaged or plugged.

5. Improper instrument valve line-up.

6. Tank inlet HEPA filter plugged.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 51: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

51 of 54

POR06-VTP-PDT-170 PLENUM VACUUM LO Facility: Portable Exhauster

Panel: POR06-VTP-ENCL-107 POR06-VTP-PDT-170

PLENUM VACUUM LO

Source: PDT-170 Setpoints: -0.3 in. wg

Alarm Class: Equipment Status

Alarm Description: Interlock On/Fan shutdown/Plenum vacuum LO

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Automatic Actions:

1. Clear rotating beacon (XA-101) is illuminated.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm POR06-VTP-PDT-170) PLENUM VACUUM LO

(K1) AND

PRESS K1.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view AP-001.

[2] CHECK ACTIVE ALARMS area of alarm panel view POR06-VTP-PV-101 to

determine if alarm condition is still active.

[3] CHECK indicating transmitter POR06-VTP-PDT-170.

[4] NOTIFY Shift Manager of findings.

[5] REQUEST Shift Manager to evaluate.

Supplemental Actions:

[6] MONITOR POR06-VTP-PDT-170 and exhauster current alarms until they return to

baseline values and clear.

[7] NOTIFY the Shift Manager of all actions and findings.

(Continued on Next Page)

Page 52: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

52 of 54

Facility: Portable Exhauster

Panel: POR06-VTP-ENCL-107 POR06-VTP-PDT-170

PLENUM VACUUM LO

Source: PDT-170 Setpoints: -0.3 in. wg

(Continued) Possible Causes:

1. Portable exhauster has shut down.

2. Maintenance work on Pressure Alarm.

3. Dome intrusive work.

4. Open Risers, open pit drains and or missing sealing media on pit cover block(s), cracks,

seams or penetrations that admit too much air to the Pit(s).

5. Failure of Pressure Transmitter.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster

Page 53: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

53 of 54

TEMPERATURE RISE ALARM < 20 DEG F Facility: Portable Exhauster

Panel: POR06-VTP-ENCL-107 TEMPERATURE RISE

ALARM 20 DEG F

Source: TE-179 Setpoints: dT 20 F

Alarm Class: Equipment Status

Alarm Description: Heater alarm (TE-179) indicates low differential temperature

Automatic Actions:

1. Clear rotating beacon (XA-101) is illuminated.

NOTE - Alarm Response Procedures are not designed for, nor intended to be applied to, expected

alarms generated by approved operating, maintenance or testing procedures.

Immediate Actions:

[1] ACKNOWLEDGE alarm in the following order:

[1.1] SELECT ACKNOWLEDGE ACTIVE ALARMS/BEACON [F7] from ACTIVE

ALARMS area of alarm panel view POR06-VTP-PV-101.

[1.2] IDENTIFY BLINKING alarm TEMPERATURE RISE ALARM 20 DEG F

(F2) AND

PRESS F2.

[1.3] PRESS F1 to return to ACTIVE ALARMS area of alarm panel view AP-001.

[2] CHECK CURRENT ALARMS area of alarm panel view POR06-VTP-PV-101 to

determine if alarm condition is still active.

[3] IF CURRENT ALARMS area of alarm panel view POR06-VTP-PV-101 displays

POR06-VTP-TE-179 HEATER AIR TEMP LO, RESPOND per alarm

POR06-VTP-TE-179 HEATER TEMP LO, page 31.

[4] REQUEST Shift Manger to notify Environmental.

[5] STOP all waste disturbing retrieval activities in the tank(s) being ventilated by this

exhauster, until air stream temperature is within specified range.

(Continued on Next Page)

Page 54: Tank Farm Plant Operating Procedure Ventilation USQ # TF ... Library/… · Release Date 12/15/2015 Page 1 of 54 Tank Farm Plant Operating Procedure Ventilation USQ # TF-15-2062-S,

Respond to Alarms for Portable Exhauster POR06

Type

REFERENCE Document No.

ARP-T-351-00006 Rev/Mod

B-1 Release Date

12/15/2015 Page

54 of 54

Facility: Portable Exhauster

Panel: POR06-VTP-ENCL-107

TEMPERATURE RISE

ALARM 20 DEG F

Source: TE-179 Setpoints: dT 20 °F

(Continued) Immediate Actions: (Cont.)

NOTE – Glycol heater adjustments respond slowly, it is recommended to adjust the heater in

steps of a few degrees (or as directed by Shift Manager). It may be necessary to repeat

the following three steps several times to achieve the desired air stream temperature.

[6] ADJUST glycol heater thermostat as needed to restore air stream temperature to desired

operating conditions.

[7] MONITOR temperature values periodically for one hour.

[8] IF air stream temperature is not within specified range, REPEAT steps [6] and [7] until

desired temperature is achieved.

[9] IF the desired air stream temperature rise is not achievable within 2 shifts, NOTIFY

Shift Manager AND

SHUT DOWN exhauster per TO-060-045.

[10] REQUEST Shift Manager to notify Environmental.

Supplemental Actions:

[11] REQUEST initiation of Work Package to troubleshoot and repair heater system.

Possible Causes:

1. Thermostat is set too low.

2. Glycol level low.

3. Glycol pump off.

References:

Drawings: H-2-829116, 500 CFM Portable Exhauster Piping & Instrument Diagram

Documents: TO-060-045, Operate POR06 Exhauster