AHPHX CompactHeat Recovery Air Handling Unit
BIM & REVIT Engineering Solutions
AIR
HA
ND
LER
S LT
D
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
2
The Company…Air Handlers has been trading since May1989, and has just celebrated 25 years inbusiness in 2014. The Company operates fromits 60,000 Sq Ft Factory in Salford Quayswhich was purpose built in year 2000.
Product Development...The Company is continually updating itsproducts to comply with changing energysaving technologies, so the introduction ofthe AHPHX Compact Range of air handlingunits is based on changes in specific Fanpower and heat recovery legislation adoptinghigher energy saving technology.
Compliance...The AHPHX air handling units comply with BSEN 1886 Class L2 Construction Standards. Airhandling unit construction and ErP EuropeanDirective 2018 for energy recovery efficiencies.
Acoustic Performance...Extensive acoustic testing of caseworkconstruction has been carried out at both thecompanies testing facilities, and SalfordUniversity Acoustic Testing Laboratory.Acoustic tests were carried out on twentydouble skin, composite panel/frame systems,eight different triple and quadruple skincomposite panel/frame systems, to BS. ENISO10140-2 (2010) which have all beencertified as UKAS accredited.
1262
Acoustic Testing LaboratoryCollege of Science & Technology
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
3
Location…AHPHX Compact Package Heat Reclaim AirHandling Units are normally located internally inplantrooms, external to the building or on the roof.
Construction… FrameInsulated extruded anodised aluminium pentapostsections with solid die cast mechanical fit cornersare used to build each frame. The frame isacoustically insulated to prevent noise leakage.
PanelsPanels are flush fitted into the frame and air sealedwith neoprene gaskets. A range of acousticallyinsulated panels are available to meet the soundreduction required in the space.
Access PanelsAll access panels will be flush mounted in theframe, and constructed as the fixed panels. Fan andcontrol panel access panels will be lockable. Quickrelease, other access panels will have multidirectional handles.
Heat RecoveryAHPHX Units utilise a diagonal cross flow plateheat exchanger having sealed shaped plates, givingenergy recovery efficiencies of up to 85%.
Standard plate heat exchangers are constructedfrom aluminium, but ant-corrosive coatings areavailable for coastal or aggresive atmospheres.Please contact our sales office for further details.
Face and bypass dampers, actuator operated, offera summer by pass facility.
Plate heat exchangers used in the AHPHX airhandling unit range are eurovent certified,and outperforms Erp 2018 Eco directive 2009/125/EC.
Filters
Filters are fitted to both the fresh air and return airinlets. G4 grade panel filters are used as standard.
Disposable multi pocket bag filters can be offered asan alternative or secondary filter with grades F5, F6,F7 available. Manometers or pressure differentialguages factory fitted are available as an option.
Heating Coil
Low temperature hot water heating coils arecontained within the casework on slide rails for theease of removal. Coils are constructed as standardfrom copper tubes and headers with aluminium fins.
Optional coil construction: • Bare tube (frost coils)
• Wide spaced fins (frost coils)
• Polyester coated fins.
• Blygold coated fins.
• Copper fins.
• HTM – 03 compliant coils.
Cooling Coil Options
Cooling coil options are available to offer mechanicalcooling, direct expansion or chilled water coilsconstructed from copper tubes and headers withaluminium fins as standard.
Optional coil construction: • Polyester coated aluminium fins.
• Blygold coated fins.
• Copper fins.
• Copper fins electro tinned.
• HTM -03 Compliant.
Drain trays are fitted to cooling coils and can befixed or removable, all drain trays have a inbuiltslope.
Bag Filters
Electric Heaters
Manufactured with sheathed elements, and fittedwith a high temperature cut out. Balanced phaseelements are arranged for thyristor or step control.
Cooling Coil
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
4
Fans
AHPHX Compact air handling units have supply andreturn air backward curved centrifugal plug typefans, direct driven by high efficiency EC motors.
This method of scroll free fan produces an optimallow loss flow of air through the impeller so thereare no longer any drastic cross sectional changes.
Fan Inlet Flow grids… By fitting an inlet flow grid to the supply fan it ispossible to achieve significant noise reductionfrom the fan.
The noise reduction is predominantly lowfrequency decay (i.e. 63Hz, 125Hz, 250Hz), whichcan help offer significant sound power loss. Thissound power loss is created by the reduction inturbulence hitting the rotating blades, with tonalfrequency components, known as impellor noise ortonal noise.
Tonal noise consists of the blade – passing noiseand its harmonics. The frequency of the blade –passing noise can be calculated as the sum of thefan speed and the number of blades.
A flow-grid fitted to the inlet of the fans willsignificantly reduce the low frequency noisegenerated disturbance. The vortex is split whenimpacting the grille as it is considerably weakenedwhen it flows through the flowgrid.
Sound pressure is reduced, particularly the lowfrequency. The chart below indicates the powerloss in octave bands.
Freq Hz 63 125 250 500 1K
Powerloss db -6 -10 -7.5 -8 -1
Flowgrids
Dampers
All dampers are constructed from an aerofoilsection double skin aluminium blade profile withedge, blade and side seals to offer low leakage.
The blade rotation is performed by rigid nylon cogswhich operate out of Air Stream. The damperoperating mechanism is connected to an optionalfactory fitted and pre-wired actuator via a squarebrass drive shaft.
Thermal Insulated Dampers
Thermally insulated blades can be provided forfresh air and exhaust air shut off dampers whichadd protection to filters and coil freezing.
Electric Heater
Thermal Insulated Dampers
Fans
Motors operate via a 0-10V DC output from themotor, it provides infinitely variable speed control.
Backward curved scroll free fans are quiet runningwith optimised airflow through the impeller, givingsignificantly reduced tonal noise.
Multi fan wall arrangements are used to achievehigher air flow performance and efficiency.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
5
Baseframes… Formed 2.5mm galvanised steel baseframes arefitted to all AHPHX Compact air handling units, astandard height of 100mm is included, butoptional increased height baseframes are availableon request.
In the case of HTM - 03 and healthcare projects,the baseframe will be as laid down in thespecifications.
All baseframes incorporate lifting points in builtinto the baseframe and designed to suit thespecific lifting weight of the air handling unit.
Lifting instructions and method statement forsecuring lifting equipment are issued with OEMinformation on delivery.
Controls… AHPHX Compact air handling units can be suppliedwith an optional in built controls package withweatherproof options.
Standard Control Package
This option includes for the control panel to be builtinto the air handling unit casework or mounteddirectly onto it.
All internal components will be pre-wired withisolators, actuators, sensors, thermostats, pressureswitches all factory fitted.
The control system will incorporate a controllerwhich contains features to act independent or withBMS. Modbus or BACnet facility. Display features canbe provided on the controller.
The control package includes speed controllers builtinto the controller to speed regulate the E C fans.
Control system options: • Trend, Carel or similar controller.
• Output facility to operate remote condensingunit(s) or heat pump unit(s).
• Output to operate a thyristor controller (additional)for electric heater 0 < 10 Volt temperatureregulation.
Internal Control PanelExternal Weatherproof
Control Panel
Casework Class… AHPHX Compact air handling units have varioustypes of casework available as detailed below.
Standard Casework
Standard Casework is constructed from a 30mmanodised aluminium framework with 25mmdouble skin insulated panels.
Standard Casework Panel Options
30/25FG
OPTION 1 30/25FG0.9mm inner skin galvanised sheet metal1.2 mm outer skin galvanised sheet metal
OPTION 2 30/25FG1.2mm inner skin galvanised sheet metal0.7mm outer skin plastisol plastic coated steel
Sound Reduction Index
Frequency Hz 63 125 250 500 1K 2K 4K 8K
Power Loss db 16.5 16.6 26.6 38.1 39.2 33.4 32.1 39.7
50/50FG
OPTION 1 50/50FG0.9mm inner skin galvanised sheet metal1.2 mm outer skin galvanised sheet metal
OPTION 2 50/50FG1.2mm inner skin galvanised sheet metal0.7mm outer skin plastisol plastic coated steel
Sound Reduction Index
Frequency Hz 63 125 250 500 1K 2K 4K 8K
Power Loss db 15.7 18.4 33.7 36.2 37.5 32.4 35 40.4
Sound Reduction Index 50/50 PB (Double Skin)
Frequency Hz 63 125 250 500 1K 2K 4K 8K
Power Loss db 20 23.5 29.4 36 39 34 34.5 41
Acoustic Enhanced Casework
Various acoustically enhanced panels are availablewith different thickness and acoustic insulationcomposites, frames are constructed from anodisedaluminium and acoustically insulated to preventsound leakage.
All acoustic panel options are listed below withtheir sound reduction index.
30/25AS (Double Skin)
OPTION 1 30/25AS30mm anodised aluminium acoustic insulatedframe with 25mm double skin sound barrierinsulated panels.
Inner Skin0.9mm inner skin galvanised sheet metal
Outer skin1.2mm outer skin galvanised sheet metal
OPTION 2 30/25AS1.2mm inner skin galvanised sheet metal0.7mm outer skin plastisol plastic coated steel
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
6
30/25PB (Double Skin)
OPTION 1 30/25PB30mm anodised aluminium acoustic insulatedframe with 25mm double skin sound barrierinsulated panels.
Inner Skin0.9mm inner skin galvanised sheet metal
Outer skin1.2mm outer skin galvanised sheet metal
OPTION 2 30/25PB1.2mm inner skin galvanised sheet metal0.7mm outer skin plastisol plastic coated steel
Sound Reduction Index
Frequency Hz 63 125 250 500 1K 2K 4K 8K
Power Loss db 20.4 23 23 23.3 33.6 37 37.7 45.5
50/50FG PB (Double Skin)OPTION 1 50/50FG PB50mm anodised aluminium acoustic insulatedframe with 50mm double skin acoustic compositeinsulated panels.
Inner Skin0.9mm inner skin galvanised sheet metal
Outer skin1.2mm outer skin galvanised sheet metal
OPTION 2 50/50FG PB1.2mm inner skin galvanised sheet metal0.7mm outer skin plastisol plastic coated steel
Sound Reduction Index
Frequency Hz 63 125 250 500 1K 2K 4K 8K
Power Loss db 19.6 18.3 33.3 40 38.6 36.1 39.3 46.8
30/25TS PB (Triple Skin)OPTION 1 30/25TS PB30mm anodised aluminium acoustic insulatedframe with 25mm double skin sound barrierinsulated panels.
Inner Skin0.9mm inner skin galvanised sheet metal
Intermediate skin0.9mm inner skin galvanised sheet metal
Outer skin1.2mm outer skin galvanised sheet metal
OPTION 2 30/25TS PB1.2mm inner skin galvanised sheet metal1.2mm intermediate skin galvanised sheet metal0.7mm outer skin plastisol plastic coated steel
Sound Reduction Index
Frequency Hz 63 125 250 500 1K 2K 4K 8K
Power Loss db 22.5 26.2 29.4 30 36.4 35.2 33.6 39.6
50/50FG TS PB (Triple Skin)OPTION 1 30/25FG TS PB50mm anodised aluminium acoustic insulated framewith 50mm triple skin acoustic composite panels.
Inner Skin0.9mm inner skin galvanised sheet metal
Intermediate skin0.9mm inner skin galvanised sheet metal
Outer skin1.2mm outer skin galvanised sheet metal
OPTION 2 50/50FG TS PB1.2mm inner skin galvanised sheet metal1.2mm intermediate skin galvanised sheet metal0.7mm outer skin plastisol plastic coated steel
Sound Reduction Index
Frequency Hz 63 125 250 500 1K 2K 4K 8K
Power Loss db 21.1 21 36.3 39.2 41.7 34.7 32.9 40.2
50/50AS TS PB (Triple Skin)OPTION 1 50/50AS TS PB50mm anodised aluminium acoustic insulated framewith 50mm triple skin acoustic composite panels.
Inner Skin0.9mm inner skin galvanised sheet metal
Intermediate skins0.9mm inner skin galvanised sheet metal
Outer skin1.2mm outer skin galvanised sheet metal
OPTION 2 50/50AS TS PB1.2mm inner skin galvanised sheet metal1.2mm intermediate skin galvanised sheet metal0.7mm outer skin plastisol plastic coated steel
Sound Reduction Index
Frequency Hz 63 125 250 500 1K 2K 4K 8K
Power Loss db 24.1 27.1 34.8 37 37.2 33.5 36.2 39.6
50/50AS QS PB (Quadrouple Skin)OPTION 1 50/50AS QS PB50mm anodised aluminium acoustic insulated framewith 50mm quadruple skin acoustic compositeinsulated panels.
Inner Skin0.9mm inner skin galvanised sheet metal
Intermediate skin2 off 0.9mm intermediate skins galvanised sheet metal
Outer skin1.2mm outer skin galvanised sheet metal
OPTION 2 50/50AS QS PB1.2mm inner skin galvanised sheet metal2 off 1.2mm intermediate skins galvanised sheet metal0.7mm outer skin plastisol plastic coated steel
Sound Reduction Index
Frequency Hz 63 125 250 500 1K 2K 4K 8K
Power Loss db 24.1 36.6 34.7 39.8 40.7 37.8 39.7 43.7
7
Accreditation… In partnership with Salford University acoustictesting laboratory a range of composite acousticpanels have been designed and tested.To obtain the true casework noise breakout, theframe and panel assembly have to be tested with alarge enough area sample to give a truerepresentation of AHPHX Compact casework.In practice the framework can leak sound whichwill flank the panels. Therefore the frame must beacoustically insulated to the same standard as thepanels.
Assembling test frame and panels
Test set up during testing programme
Certification…All acoustic SRI tests arecertified by Salford UniversityTest Laboratories to BS EN ISO10140-2(2010) – Report No’s1429 & 2060.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
8
Type 1Components available for selection with type 1AHPHX Compact Units:
• Inlet attenuators.
• Inlet/ exhaust dampers.
• Mixing box/recirculation section
• Plate exchanger heat recovery device with face andbypass dampers and drain tray.
• Panel filters G3/G4 grade on supply and extract.
• Fan selection containing E.C. backward curved plugfan(s).
• Discharge attenuators.
Type 2Components available for selection with type 2AHPHX Compact Units:
• Inlet attenuators.
• Inlet/exhaust dampers.
• Mixing box/recirculation section
• Plate exchanger heat recovery device with face andbypass dampers and drain tray.
• Panel filters G3/G4 grade on supply and extract.
• Electric heater battery.
• LPHW heating coil.
• Fan section containing E.C. backward curved plug fan(s).
• Discharge attenuators.
Type… AHPHX Compact air handling units are doublestacked in configuration, and can contain differentcomponents which are described in their individualtype and make up of components.
The performance charts will relate to the type ofAHPHX Compact unit components make up, whichallows for individual components maximumpressure drops.
Type 3Components available for selection with type 3AHPHX Compact Units:
• Inlet attenuators.
• Inlet dampers.
• Mixing box/recirculation section.
• Plate exchanger heat recovery device with faceand bypass dampers and drain tray.
• Panel filters G3/G4 grades on supply and extract.
• Bag filters grade F5/F6/F7
• Electric heater battery.
• LPHW coil.
• Fan selection containing E.C. backward curvedplug fan(s).
• Cooling coil chilled water or direct expansionheat pump arrangement coil available.
• Discharge attenuators.
Note
The casework class does not affect the performance value in the selection charts but will affect thedimensions of the unit and its acoustic breakout performance.
Type 4Components available for selection with type 4AHPHX Compact Units
• Inlet attenuators.
• Inlet dampers.
• Mixing box/ recirculation section.
• Rotary thermal wheel heat recovery device.
• Panel filters G3/G4 grades on supply and extract.
• Electric heater battery.
• LPHW coil.
• Fan section containing E.C. backward curved plugfan(s).
• Cooling coil chilled water or direct expansionheat pump coil available.
• Bag filters F5/F6/F7 grade.
• Discharge attenuators.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
9
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 2200 2000 1800 1600 1400 1200 1000 700Inlet SWL (db) 69 68 68 67 68 66 67 67Outlet SWL (db) 74 73 72 72 73 71 73 73Absorbed power (Watts) 280 270 262 255 250 244 239 230
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart MODEL AHPHX 800/T1/310-390/1F
Performance TYPICAL TYPE 1 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1
30/25 FG 534 1600 1500 100 750 750 690 690 950 890 220030/25 AS 642 1600 1500 100 750 750 690 690 950 890 220030/25 PB 678 1600 1500 100 750 750 690 690 950 890 220030/25 TS PB 678 1600 1500 100 750 750 690 690 950 890 220050/50 FG 558 1650 1550 100 775 775 675 675 1000 900 224050/50 FG PB 630 1650 1550 100 775 775 675 675 1000 900 224050/50 FG TS PB 750 1650 1550 100 775 775 675 675 1000 900 224050/50 AS TS PB 870 1650 1550 100 775 775 675 675 1000 900 224050/50 AS QS PB 1026 1650 1550 100 775 775 675 675 1000 900 2240
Dimensions and Weight
Airflow (m³/Hr) 2200 2000 1800 1600 1400 1200 1000 700
Dry Efficiency % 75.0 75.5 74.2 72.9 77.6 76.4 76.9 73.0Wet Efficiency % 82.9 83.4 82.6 81.1 86.2 84.9 85.5 81.3Supply Air Lat °C 16.5 16.7 16.5 16.1 17.4 17.1 17.2 16.1Energy Recovered (Kw) 16 15 13 11 10 9 7 5
EQUAL AIRFLOWS ECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan Data
Motor output 390WATTSElectric supply 240V/1/50HzMaximum current rating 2.6AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/1F
Filter Data
G3 or G4 grade panel filters.
Energy Recovery
Plate Heat Exchanger with by pass Model PHX/W800-600/D1175-650
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
10
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 2200 2000 1800 1600 1400 1200 1000 700Inlet SWL (db) 69 68 68 67 68 66 67 67Outlet SWL (db) 74 73 72 72 73 71 73 73Absorbed power (Watts) 280 270 262 255 250 244 239 230
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart MODEL AHPHX 800/T2/310-390/1F
Performance TYPICAL TYPE 2 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 582 1600 1500 100 750 750 690 690 950 890 2200 32030/25 AS 700 1600 1500 100 750 750 690 690 950 890 2200 32030/25 PB 729 1600 1500 100 750 750 690 690 950 890 2200 32030/25 TS PB 729 1600 1500 100 750 750 690 690 950 890 2200 32050/50 FG 605 1650 1550 100 775 775 775 775 1000 900 2240 36050/50 FG PB 682 1650 1550 100 775 775 775 775 1000 900 2240 36050/50 FG TS PB 801 1650 1550 100 775 775 775 775 1000 900 2240 36050/50 AS TS PB 923 1650 1550 100 775 775 775 775 1000 900 2240 36050/50 AS QS PB 1079 1650 1550 100 775 775 775 775 1000 900 2240 360
NOTE Type 2 (T2) AHPHX Units have a single bottom deck section attached to the type 1 (T1), containing an electric orLPHW Heating Coil as illustrated on the above diagram.
Dimensions and Weight
Airflow (m³/Hr) 2200 2000 1800 1600 1400 1200 1000 700
Dry Efficiency % 75.0 75.5 74.2 72.9 77.6 76.4 76.9 73.0Wet Efficiency % 82.9 83.4 82.6 81.1 86.2 84.9 85.5 81.3Supply Air Lat °C 16.5 16.7 16.5 16.1 17.4 17.1 17.2 16.1Energy Recovered (Kw) 16 15 13 11 10 9 7 5
EQUAL AIRFLOWS ECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan Data
Motor output 390WATTSElectric supply 240V/1/50HzMaximum current rating 2.6AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/1F
Filter Data
G3 or G4 grade panel filters.
Energy Recovery
Plate Heat Exchanger withby pass Model PHX/W800-600/D1175-650
Electric Heater Data
Based on minimum airflow9Kw single or three phaseelectric supply.
LPHW Coil Data
Based on maximum airflowand LPHW @ 82/71°C. Maximum heating output10Kw.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
11
Selection Chart MODEL AHPHX 800/T3/310-390/1F
Performance TYPICAL TYPE 3 COMPONENT CONFIGURATION
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 628 1600 1500 100 750 750 690 690 950 890 2200 68030/25 AS 770 1600 1500 100 750 750 690 690 950 890 2200 68030/25 PB 818 1600 1500 100 750 750 690 690 950 890 2200 68030/25 TS PB 818 1600 1500 100 750 750 690 690 950 890 2200 68050/50 FG 656 1650 1550 100 775 775 675 675 1000 900 2240 72050/50 FG PB 755 1650 1550 100 775 775 675 675 1000 900 2240 72050/50 FG TS PB 914 1650 1550 100 775 775 675 675 1000 900 2240 72050/50 AS TS PB 1070 1650 1550 100 775 775 675 675 1000 900 2240 72050/50 AS QS PB 1271 1650 1550 100 775 775 675 675 1000 900 2240 720
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil.
A heat pump coil is also available in this section as an option. All as illustrated on the above diagram.
Dimensions and Weight
Fan DataMotor output 390WATTSElectric supply 240V/1/50HzMaximum current rating 2.6AmpsMaximum Speed @10Volts 2350RPMFan Reference EC 310-390/1F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W800-600/D1175-650
Electric Heater DataBased on maximum airflow 9Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C.Maximum heating output 10Kw.
Cooling/Heat Pump Coil DataChilled water/direct expansion coildata based on maximum airflow &chilled water @ 6/12°C or DXevaporating @ 6°C.
Max cooling output 9Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 2100 1900 1700 1500 1300 1100 900 600Inlet SWL (db) 68 67 68 66 68 65 64 65Outlet SWL (db) 72 72 72 72 73 70 69 70Absorbed power (Watts) 275 270 264 259 255 249 244 240
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 2100 1900 1700 1500 1300 1100 900 600
Dry Efficiency % 75.3 74.1 74.4 77.4 76.1 76.6 73.4 73.5Wet Efficiency % 83.2 82.4 82.7 86.0 84.7 85.2 86.1 81.8Supply Air Lat °C 16.6 16.4 16.5 17.4 17.0 17.1 16.2 16.3Energy Recovered (Kw) 15 14 12 11 10 8 6 4
EQUAL AIRFLOWS ECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
12
Selection Chart MODEL AHPHX 800/T4/310-390/1F
Performance TYPICAL TYPE 4 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 687 1600 1500 100 750 750 690 690 840 780 2200 107030/25 AS 842 1600 1500 100 750 750 690 690 840 780 2200 107030/25 PB 894 1600 1500 100 750 750 690 690 840 780 2200 107030/25 TS PB 894 1600 1500 100 750 750 690 690 840 780 2200 107050/50 FG 717 1650 1550 100 775 775 675 675 900 800 2240 115050/50 FG PB 844 1650 1550 100 775 775 675 675 900 800 2240 115050/50 FG TS PB 989 1650 1550 100 775 775 675 675 900 800 2240 115050/50 AS TS PB 1168 1650 1550 100 775 775 675 675 900 800 2240 115050/50 AS QS PB 1387 1650 1550 100 775 775 675 675 900 800 2240 1150
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil.
A heat pump coil is also available in this section as an option. All as illustrated on the above diagram.
Section includes a F5 to F7 grade Bag Filter arranged for side withdrawal.
Dimensions and Weight
Fan Data
Motor output 390WATTSElectric supply 240V/1/50HzMaximum current rating 2.6AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/1F
Filter Data
G3 or G4 grade panel filters.Secondary F7 grade Bag Filters
Energy Recovery
Plate Heat Exchanger with bypass Model PHX/W700-500/D1175-960
Electric Heater Data
Based on minimum airflow 9Kwsingle or three phase electric supply.
LPHW Coil Data
Based on maximum airflow andLPHW @ 82/71°C. Maximum heating output 10Kw.
Cooling/Heat Pump Coil Data
Chilled water/direct expansion coildata based on maximum airflow &chilled water @ 6/12°C or DXevaporating @ 6°C.Max cooling output 9Kw.
External Pressure Pascals 50 100 150 200 250
Airflow (m³/Hr) 1600 1400 1200 1000 750Inlet SWL (db) 65 63 63 62 64Outlet SWL (db) 68 67 67 67 68Absorbed power (Watts) 195 189 184 178 174
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 1600 1400 1200 1000 750
Dry Efficiency % 75.9 76.5 76.4 77.1 77.7Wet Efficiency % 83.9 84.5 84.4 85.2 86.4Supply Air Lat °C 16.8 17.0 16.9 17.1 17.5Energy Recovered (Kw) 12 10 9 7 6
Plate Heat Exchanger Efficiency %
EQUAL AIRFLOWS ECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
13
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600 650
Airflow (m³/Hr) 3000 2900 2750 2600 2500 2300 2200 2000 1900 1800 1650 1500 1200Inlet SWL (db) 80 80 78 76 79 77 78 74 78 75 74 75 73Outlet SWL (db) 83 83 82 81 82 80 81 77 80 78 78 79 78Absorbed power (Watts) 410 415 420 426 429 436 441 448 454 450 443 439 428
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart MODEL AHPHX 1000/T1/310-680/1F
Performance TYPICAL TYPE 1 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1
30/25 FG 586 1600 1500 100 750 750 690 690 1150 1090 220030/25 AS 712 1600 1500 100 750 750 690 690 1150 1090 220030/25 PB 754 1600 1500 100 750 750 690 690 1150 1090 220030/25 TS PB 754 1600 1500 100 750 750 690 690 1150 1090 220050/50 FG 614 1650 1550 100 775 775 675 675 1200 1100 224050/50 FG PB 698 1650 1550 100 775 775 675 675 1200 1100 224050/50 FG TS PB 838 1650 1550 100 775 775 675 675 1200 1100 224050/50 AS TS PB 978 1650 1550 100 775 775 675 675 1200 1100 224050/50 AS QS PB 1160 1650 1550 100 775 775 675 675 1200 1100 2240
Dimensions and Weight
Airflow (m³/Hr) 3000 2900 2750 2600 2500 2300 2200 2000 1900 1800 1650 1500 1200
Dry Efficiency % 74.6 74.8 75.1 75.4 75.6 76.0 79.2 79.4 77.4 77.6 76.2 73.5 73.2Wet Efficiency % 82.4 82.7 83.0 83.3 83.6 84.0 87.9 88.2 86.0 86.2 84.7 81.8 81.5Supply Air Lat °C 16.4 16.5 16.6 16.7 16.7 16.8 17.9 17.9 17.4 17.4 17.0 16.3 16.2Energy Recovered (Kw) 21 21 20 19 18 17 17 15 14 13 12 11 8
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan Data
Motor output 680WATTSElectric supply 240V/1/50HzMaximum current rating 4.3AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/1F
Filter Data
G3 or G4 grade panel filters.
Energy Recovery
Plate Heat Exchanger with by passModel PHX/W1000/D1175-650
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
14
Selection Chart MODEL AHPHX 1000/T2/310-680/1F
Performance TYPICAL TYPE 2 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 642 1600 1500 100 750 750 690 690 1150 1090 2200 32030/25 AS 780 1600 1500 100 750 750 690 690 1150 1090 2200 32030/25 PB 826 1600 1500 100 750 750 690 690 1150 1090 2200 32030/25 TS PB 826 1600 1500 100 750 750 690 690 1150 1090 2200 32050/50 FG 673 1600 1550 100 775 775 675 675 1200 1100 2240 36050/50 FG PB 765 1600 1550 100 775 775 675 675 1200 1100 2240 36050/50 FG TS PB 918 1600 1550 100 775 775 675 675 1200 1100 2240 36050/50 AS TS PB 1072 1600 1550 100 775 775 675 675 1200 1100 2240 36050/50 AS QS PB 1271 1600 1550 100 775 775 675 675 1200 1100 2240 360
NOTE Type 2 (T2) AHPHX Units have a single bottom deck section attached to the type 1 (T1), containing an electric orLPHW Heating Coil as illustrated on the above diagram.
Dimensions and Weight
Fan DataMotor output 680WATTSElectric supply 240V/1/50HzMaximum current rating 4.3AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/1F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger with bypass ModelPHX/W1000/1175-650
Electric Heater DataBased on maximum airflow 18Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximum heating output 20Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600 650
Airflow (m³/Hr) 3000 2900 2750 2600 2500 2300 2200 2000 1900 1800 1650 1500 1200Inlet SWL (db) 80 81 78 76 79 77 78 74 77 75 74 75 73Outlet SWL (db) 83 83 82 81 82 80 81 77 80 78 78 79 78Absorbed power (Watts) 415 422 430 435 441 448 452 457 450 444 439 433 421
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 3000 2900 2750 2600 2500 2300 2200 2000 1900 1800 1650 1500 1200
Dry Efficiency % 74.6 74.8 75.1 75.4 75.6 76.0 79.2 79.4 77.4 77.6 76.2 73.5 73.2Wet Efficiency % 82.4 82.7 83.0 83.3 83.6 84.0 87.9 88.2 86.0 86.2 84.7 81.8 81.5Supply Air Lat °C 16.4 16.5 16.6 16.7 16.7 16.8 17.9 17.9 17.4 17.4 17.0 16.3 16.2Energy Recovered (Kw) 21 21 20 19 18 17 17 15 14 13 12 11 8
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
15
Selection Chart MODEL AHPHX 1000/T3/310-680/1F
Performance TYPICAL TYPE 3 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 704 1600 1500 100 750 750 690 690 1150 1090 2200 68030/25 AS 850 1600 1500 100 750 750 690 690 1150 1090 2200 68030/25 PB 899 1600 1500 100 750 750 690 690 1150 1090 2200 68030/25 TS PB 899 1600 1500 100 750 750 690 690 1150 1090 2200 68050/50 FG 736 1650 1550 100 775 775 675 675 1200 1100 2240 72050/50 FG PB 833 1650 1550 100 775 775 675 675 1200 1100 2240 72050/50 FG TS PB 993 1650 1550 100 775 775 675 675 1200 1100 2240 72050/50 AS TS PB 1155 1650 1550 100 775 775 675 675 1200 1100 2240 72050/50 AS QS PB 1364 1650 1550 100 775 775 675 675 1200 1100 2240 720
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil.
A heat pump coil is also available in this section as an option. All as illustrated on the above diagram.
Dimensions and Weight
Fan DataMotor output 680WATTSElectric supply 240V/1/50HzMaximum current rating 4.3AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/1F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W900-600/D1175
Cooling/Heat PumpCoil DataChilled water/directexpansion coil data basedon maximum airflow &chilled water @ 6/12°C orDX evaporating @ 6°C.Max cooling output 20Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600
Airflow (m³/Hr) 2750 2650 2500 2400 2275 2150 2000 1850 1700 1550 1350 1200Inlet SWL (db) 78 80 75 76 78 76 75 74 75 73 73 73Outlet SWL (db) 81 82 80 81 81 79 79 77 78 76 76 78Absorbed power (Watts) 418 425 431 438 445 451 456 450 444 440 436 431
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 2750 2650 2500 2400 2275 2150 2000 1850 1700 1550 1350 1200
Dry Efficiency % 75.1 74.7 75.0 75.2 75.5 75.8 75.5 75.9 76.3 76.1 75.9 76.4Wet Efficiency % 82.9 82.5 82.9 83.1 83.4 83.8 83.4 83.9 84.3 84.0 83.8 84.8Supply Air Lat °C 16.6 16.5 16.6 16.6 16.7 16.8 16.7 16.8 16.9 16.8 16.8 16.9Energy Recovered (Kw) 20 19 18 17 16 16 15 13 12 11 10 9
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Electric Heater DataBased on minimum airflow 15Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximum heating output 16Kw.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
16
Selection Chart MODEL AHPHX 1000/T4/310-680/1F
Performance TYPICAL TYPE 4 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1
30/25 FG 768 1600 1500 100 750 750 690 690 1150 1090 220030/25 AS 926 1600 1500 100 750 750 690 690 1150 1090 220030/25 PB 979 1600 1500 100 750 750 690 690 1150 1090 220030/25 TS PB 979 1600 1500 100 750 750 690 690 1150 1090 220050/50 FG 804 1650 1550 100 775 775 675 675 1200 1100 224050/50 FG PB 907 1650 1550 100 775 775 675 675 1200 1100 224050/50 FG TS PB 1082 1650 1550 100 775 775 675 675 1200 1100 224050/50 AS TS PB 1258 1650 1550 100 775 775 675 675 1200 1100 224050/50 AS QS PB 1486 1650 1550 100 775 775 675 675 1200 1100 2240
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil. A heat pump coil is also available in this section as an option. All as illustrated on the above diagram. Section includes a F5 to F7 grade Bag Filter arranged for side withdrawal.
Dimensions and Weight
Fan DataMotor output 680WATTSElectric supply 240V/1/50HzMaximum current rating 4.3AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/1F
Filter DataG3 or G4 grade panel filters.Secondary F7 Bag Filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W900-600/D1175
Cooling/Heat PumpCoil DataChilled water/directexpansion coil data basedon maximum airflow &chilled water @ 6/12°C orDX evaporating @ 6°C.Max cooling output 20Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500
Airflow (m³/Hr) 2500 2300 2150 2000 1900 1800 1650 1500 1350 1200Inlet SWL (db) 76 74 73 73 77 72 73 70 73 72Outlet SWL (db) 79 78 77 78 80 76 77 74 76 75Absorbed power (Watts) 296 303 312 320 327 334 341 338 331 322
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 2500 2300 2150 2000 1900 1800 1650 1500 1350 1200
Dry Efficiency % 75.0 75.5 75.8 75.5 75.8 76.0 75.8 76.2 75.9 76.4Wet Efficiency % 82.9 83.4 83.8 83.4 83.7 84.0 83.7 84.2 83.8 84.4Supply Air Lat °C 16.6 16.7 16.8 16.7 16.8 16.8 16.8 16.9 16.8 16.9Energy Recovered (Kw) 18 17 16 15 14 13 12 11 10 9
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Electric Heater DataBased on maximum airflow 15Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximum heating output 16Kw.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
17
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 4400 4000 3600 3200 2800 2400 2000 1400Inlet SWL (db) 75 74 74 72 74 71 73 72Outlet SWL (db) 80 81 79 77 80 77 79 78Absorbed power (Watts) 498 516 528 539 548 562 555 543
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart MODEL AHPHX 1500/T1/310-390/2F
Performance TYPICAL TYPE 1 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1
30/25 FG 670 1600 1500 100 750 750 690 690 1600 1540 220030/25 AS 805 1600 1500 100 750 750 690 690 1600 1540 220030/25 PB 850 1600 1500 100 750 750 690 690 1600 1540 220030/25 TS PB 850 1600 1500 100 750 750 690 690 1600 1540 220050/50 FG 700 1650 1550 100 775 775 675 675 1650 1550 224050/50 FG PB 790 1650 1550 100 775 775 675 675 1650 1550 224050/50 FG TS PB 941 1650 1550 100 775 775 675 675 1650 1550 224050/50 AS TS PB 1091 1650 1550 100 775 775 675 675 1650 1550 224050/50 AS QS PB 1287 1650 1550 100 775 775 675 675 1650 1550 2240
Dimensions and Weight
Airflow (m³/Hr) 4400 4000 3600 3200 2800 2400 2000 1400
Dry Efficiency % 74.9 75.4 75.9 76.5 76.4 77.6 76.6 77.5Wet Efficiency % 82.7 83.3 83.9 84.5 84.4 86.2 84.7 86.1Supply Air Lat °C 16.5 16.7 16.8 17.0 16.9 17.4 17.0 17.4Energy Recovered (Kw) 32 29 26 23 21 18 15 10
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan DataMotor output 780WATTSElectric supply 240V/1/50HzMaximum current rating 5.2AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/2F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger with by pass Model PHX/W1500-700/D1175-965
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
18
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 4400 4000 3600 3200 2800 2400 2000 1400Inlet SWL (db) 75 74 74 72 74 71 73 72Outlet SWL (db) 80 81 79 77 80 77 79 78Absorbed power (Watts) 498 516 528 539 548 562 555 543
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart MODEL AHPHX 1500/T2/310-390/2F
Performance TYPICAL TYPE 2 COMPONENT CONFIGURATION
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 719 1600 1500 100 750 750 690 690 1600 1540 2200 32030/25 AS 884 1600 1500 100 750 750 690 690 1600 1540 2200 32030/25 PB 920 1600 1500 100 750 750 690 690 1600 1540 2200 32030/25 TS PB 920 1600 1500 100 750 750 690 690 1600 1540 2200 32050/50 FG 764 1650 1550 100 775 775 675 675 1650 1550 2240 36050/50 FG PB 861 1650 1550 100 775 775 675 675 1650 1550 2240 36050/50 FG TS PB 1011 1650 1550 100 775 775 675 675 1650 1550 2240 36050/50 AS TS PB 1165 1650 1550 100 775 775 675 675 1650 1550 2240 36050/50 AS QS PB 1362 1650 1550 100 775 775 675 675 1650 1550 2240 360
NOTE Type 2 (T2) AHPHX Units have a single bottom deck section attached to the type 1 (T1), containing an electric orLPHW Heating Coil as illustrated on the above diagram.
Dimensions and Weight
Airflow (m³/Hr) 4400 4000 3600 3200 2800 2400 2000 1400
Dry Efficiency % 74.9 75.4 75.9 76.5 76.4 77.6 76.6 77.5Wet Efficiency % 82.7 83.3 83.9 84.5 84.4 86.2 84.7 86.1Supply Air Lat °C 16.5 16.7 16.8 17.0 16.9 17.4 17.0 17.4Energy Recovered (Kw) 32 29 26 23 21 18 15 10
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan DataMotor output 780WATTSElectric supply 240V/1/50HzMaximum current rating 5.2AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/2F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W1500-700/D1175-965
Electric Heater DataBased on minimum airflow24Kw single or three phaseelectric supply.
LPHW Coil DataBased on maximum airflowand LPHW @ 82/71°C. Maximum heating output26Kw.
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
19
Selection Chart MODEL AHPHX 1500/T3/310-390/2F
Performance TYPICAL TYPE 3 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 798 1600 1500 100 750 750 690 690 1150 1090 2200 68030/25 AS 978 1600 1500 100 750 750 690 690 1150 1090 2200 68030/25 PB 1039 1600 1500 100 750 750 690 690 1150 1090 2200 68030/25 TS PB 1039 1600 1500 100 750 750 690 690 1150 1090 2200 68050/50 FG 833 1650 1550 100 775 775 675 675 1200 1100 2240 72050/50 FG PB 959 1650 1550 100 775 775 675 675 1200 1100 2240 72050/50 FG TS PB 1161 1650 1550 100 775 775 675 675 1200 1100 2240 72050/50 AS TS PB 1360 1650 1550 100 775 775 675 675 1200 1100 2240 72050/50 AS QS PB 1615 1650 1550 100 775 775 675 675 1200 1100 2240 720
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil.
A heat pump coil is also available in this section as an option. All as illustrated on the above diagram.
Dimensions and Weight
Fan DataMotor output 780WATTSElectric supply 240V/1/50HzMaximum current rating 5.2AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/2F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W1000-400/D1175-960
Electric Heater DataBased on minimum airflow 24Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximum heating output 26Kw.
Cooling/Heat Pump Coil DataChilled water/direct expansion coildata based on maximum airflow &chilled water @ 6/12°C or DXevaporating @ 6°C.Max cooling output 21Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 4200 3800 3400 3000 2600 2200 1800 1200Inlet SWL (db) 62 62 66 68 71 70 72 71Outlet SWL (db) 66 67 72 73 75 75 78 76Absorbed power (Watts) 192 199 216 231 244 248 245 240
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 4200 3800 3400 3000 2600 2200 1800 1200
Dry Efficiency % 72.9 73.1 73.1 73.4 73.6 73.4 72.9 73.5Wet Efficiency % 81.1 81.3 81.5 81.7 81.7 81.9 81.1 81.8Supply Air Lat °C 16.1 16.1 16.2 16.2 16.3 16.2 16.1 16.3Energy Recovered (Kw) 16 15 14 13 13 11 11 10
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
20
Selection Chart MODEL AHPHX 1500/T4/310-390/2F
Performance TYPICAL TYPE 4 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 877 1600 1500 100 750 750 690 690 1350 1290 2200 107030/25 AS 1075 1600 1500 100 750 750 690 690 1350 1290 2200 107030/25 PB 1141 1600 1500 100 750 750 690 690 1350 1290 2200 107030/25 TS PB 1141 1600 1500 100 750 750 690 690 1350 1290 2200 107050/50 FG 915 1650 1550 100 775 775 675 675 1400 1300 2240 115050/50 FG PB 1077 1650 1550 100 775 775 675 675 1400 1300 2240 115050/50 FG TS PB 1263 1650 1550 100 775 775 675 675 1400 1300 2240 115050/50 AS TS PB 1491 1650 1550 100 775 775 675 675 1400 1300 2240 115050/50 AS QS PB 1771 1650 1550 100 775 775 675 675 1400 1300 2240 1150
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil.
A heat pump coil is also available in this section as an option. All as illustrated on the above diagram.
Section includes a F5 to F7 grade Bag Filter arranged for side withdrawal.
Dimensions and Weight
Fan DataMotor output 780WATTSElectric supply 240V/1/50HzMaximum current rating 5.2AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/2F
Filter DataG3 or G4 grade panel filters.Secondary F7 grade Bag Filters
Energy RecoveryPlate Heat Exchanger with bypass Mode PHX/W1200900/D790
Electric Heater DataBased on minimum airflow 24Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximum heating output 26Kw.
Cooling/Heat Pump Coil DataChilled water/direct expansion coildata based on maximum airflow &chilled water @ 6/12°C or DXevaporating @ 6°C.Max cooling output 21Kw.
External Pressure Pascals 50 100 150 200 250
Airflow (m³/Hr) 3200 2800 2400 2000 1440Inlet SWL (db) 62 61 68 67 71Outlet SWL (db) 66 67 73 72 75Absorbed power (Watts) 188 196 213 224 232
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 3200 2800 2400 2000 1440
Dry Efficiency % 74.5 74.4 74.4 74.3 74.2Wet Efficiency % 82.8 82.8 82.7 82.7 82.6Supply Air Lat °C 16.5 16.5 16.5 16.5 16.5Energy Recovered (Kw) 15 14 12 11 9
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
21
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600 650
Airflow (m³/Hr) 6000 5800 5500 5200 5000 4600 4400 4000 3800 3600 3300 3000 2400Inlet SWL (db) 83 83 81 80 82 80 80 78 78 78 78 78 76Outlet SWL (db) 86 86 85 85 85 84 84 81 81 81 80 82 81Absorbed power (Watts) 880 892 896 904 911 916 922 930 937 933 930 924 916
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart MODEL AHPHX 1700/T1/310-680/2F
Performance TYPICAL TYPE 1 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1
30/25 FG 767 1800 1700 100 850 850 790 790 1800 1740 236030/25 AS 932 1800 1700 100 850 850 790 790 1800 1740 236030/25 PB 987 1800 1700 100 850 850 790 790 1800 1740 236030/25 TS PB 987 1800 1700 100 850 850 790 790 1800 1740 236050/50 FG 803 1850 1750 100 875 875 775 775 1850 1750 240050/50 FG PB 913 1850 1750 100 875 875 775 775 1850 1750 240050/50 FG TS PB 1164 1850 1750 100 875 875 775 775 1850 1750 240050/50 AS TS PB 1280 1850 1750 100 875 875 775 775 1850 1750 240050/50 AS QS PB 1518 1850 1750 100 875 875 775 775 1850 1750 2400
Dimensions and Weight
Airflow (m³/Hr) 6000 5800 5500 5200 5000 4600 4400 4000 3800 3600 3300 3000 2400
Dry Efficiency % 75.6 76.0 75.9 76.0 76.0 76.0 76.1 76.2 78.3 78.5 76.3 78.2 78.6Wet Efficiency % 84.0 84.4 84.3 84.4 84.4 84.4 84.5 84.6 87.0 87.2 84.7 86.9 87.3Supply Air Lat °C 16.5 16.9 16.9 17.0 16.9 16.9 17.0 17.0 17.6 17.7 17.0 17.6 17.7Energy Recovered (Kw) 44 43 40 38 37 34 32 29 29 27 24 23 18
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan DataMotor output 1360WATTSElectric supply 240V/1/50HzMaximum current rating 8.6AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/2F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger with by passModel PHX/W1700-1000/D1390
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
22
Selection Chart MODEL AHPHX/1700/T2/310-680/2F
Performance TYPICAL TYPE 2 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 844 1800 1700 100 850 850 790 790 1800 1740 2360 32030/25 AS 1026 1800 1700 100 850 850 790 790 1800 1740 2360 32030/25 PB 1087 1800 1700 100 850 850 790 790 1800 1740 2360 32030/25 TS PB 1087 1800 1700 100 850 850 790 790 1800 1740 2360 32050/50 FG 855 1850 1750 100 875 875 775 775 1850 1750 2400 36050/50 FG PB 1006 1850 1750 100 875 875 775 775 1850 1750 2400 36050/50 FG TS PB 1208 1850 1750 100 875 875 775 775 1850 1750 2400 36050/50 AS TS PB 1410 1850 1750 100 875 875 775 775 1850 1750 2400 36050/50 AS QS PB 1672 1850 1750 100 875 875 775 775 1850 1750 2400 360
NOTE Type 2 (T2) AHPHX Units have a single bottom deck section attached to the type 1 (T1), containing an electric orLPHW Heating Coil as illustrated on the above diagram.
Dimensions and Weight
Fan DataMotor output 1360WATTSElectric supply 240V/1/50HzMaximum current rating 8.6AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/2F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger with bypass Model PHX/W1700-1000/D1390
Electric Heater DataBased on minimum airflow 33Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximum heating output 36Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600 650
Airflow (m³/Hr) 6000 5800 5500 5200 5000 4600 4400 4000 3800 3600 3300 3000 2400Inlet SWL (db) 83 83 81 80 82 80 80 78 78 78 78 78 76Outlet SWL (db) 86 86 85 85 85 84 84 81 81 81 80 82 81Absorbed power (Watts) 880 892 896 904 911 916 922 930 937 933 930 924 916
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 6000 5800 5500 5200 5000 4600 4400 4000 3800 3600 3300 3000 2400
Dry Efficiency % 75.6 76.0 75.9 76.0 76.0 76.0 76.1 76.2 78.3 78.5 76.3 78.2 78.6Wet Efficiency % 84.0 84.4 84.3 84.4 84.4 84.4 84.5 84.6 87.0 87.2 84.7 86.9 87.3Supply Air Lat °C 16.5 16.9 16.9 17.0 16.9 16.9 17.0 17.0 17.6 17.7 17.0 17.6 17.7Energy Recovered (Kw) 44 43 40 38 37 34 32 29 29 27 24 23 18
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
23
Selection Chart MODEL AHPHX 1700/T3/310-680 2F
Performance TYPICAL TYPE 3 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 930 1800 1700 100 850 850 790 790 1700 1640 2340 68030/25 AS 1123 1800 1700 100 850 850 790 790 1700 1640 2340 68030/25 PB 1188 1800 1700 100 850 850 790 790 1700 1640 2340 68030/25 TS PB 1188 1800 1700 100 850 850 790 790 1700 1640 2340 68050/50 FG 973 1850 1750 100 875 875 775 775 1750 1650 2400 72050/50 FG PB 1101 1850 1750 100 875 875 775 775 1750 1650 2400 72050/50 FG TS PB 1312 1850 1750 100 875 875 775 775 1750 1650 2400 72050/50 AS TS PB 1527 1850 1750 100 875 875 775 775 1750 1650 2400 72050/50 AS QS PB 1803 1850 1750 100 875 875 775 775 1750 1650 2400 720
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil. A heat pump coil is alsoavailable in this section as an option. All as illustrated on the above diagram.
Dimensions and Weight
Fan DataMotor output 680WATTSElectric supply 240V/1/50HzMaximum current rating 8.6AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/2F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger with bypass Model PHX/W1600-800/D1390
Cooling/Heat PumpCoil DataChilled water/directexpansion coil data basedon maximum airflow &chilled water @ 6/12°C orDX evaporating @ 6°C.Max cooling output 36Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600
Airflow (m³/Hr) 5500 5300 5000 4800 4500 4300 4000 3700 3400 3100 2700 2400Inlet SWL (db) 82 83 79 79 82 81 79 78 79 77 76 77Outlet SWL (db) 85 86 84 83 85 84 83 82 82 80 80 82Absorbed power (Watts) 841 847 855 862 869 875 879 886 896 883 875 870
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 5500 5300 5000 4800 4500 4300 4000 3700 3400 3100 2700 2400
Dry Efficiency % 75.7 75.8 76.0 76.1 76.2 76.2 76.2 76.4 75.9 75.9 76.0 76.0Wet Efficiency % 84.1 84.2 84.4 84.5 84.7 84.6 84.6 84.9 84.3 84.3 84.4 84.4Supply Air Lat °C 16.9 16.9 16.9 17.0 17.0 17.0 17.0 17.1 16.9 16.9 16.9 16.9Energy Recovered (Kw) 40 39 37 35 33 32 29 27 25 23 20 18
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Electric Heater DataBased on minimum airflow 33Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximum heating output 36Kw.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
24
Selection Chart MODEL AHPHX 1700/T4/310-680/2F
Performance TYPICAL TYPE 4 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1020 1600 1500 100 750 750 690 690 1600 1540 2260 107030/25 AS 1224 1600 1500 100 750 750 690 690 1600 1540 2260 107030/25 PB 1300 1600 1500 100 750 750 690 690 1600 1540 2260 107030/25 TS PB 1300 1600 1500 100 750 750 690 690 1600 1540 2260 107050/50 FG 1067 1650 1550 100 775 775 675 675 1650 1550 2300 115050/50 FG PB 1204 1650 1550 100 775 775 675 675 1650 1550 2300 115050/50 FG TS PB 1436 1650 1550 100 775 775 675 675 1650 1550 2300 115050/50 AS TS PB 1670 1650 1550 100 775 775 675 675 1650 1550 2300 115050/50 AS QS PB 1973 1650 1550 100 775 775 675 675 1650 1550 2300 1150
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil.
A heat pump coil is also available in this section as an option. All as illustrated on the above diagram.
Section includes a F5 to F7 grade Bag Filter arranged for side withdrawal.
Dimensions and Weight
Fan DataMotor output 680WATTSElectric supply 240V/1/50HzMaximum current rating 8.6AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/2F
Filter DataG3 or G4 grade panel filters.Secondary F7 Bag Filters.
Energy RecoveryPlate Heat Exchanger with bypass Model PHX/W1500-1000/D1390
Cooling/Heat PumpCoil DataChilled water/directexpansion coil data basedon maximum airflow &chilled water @ 6/12°C orDX evaporating @ 6°C.Max cooling output 36Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500
Airflow (m³/Hr) 4800 4600 4300 4000 3800 3600 3300 3000 2700 2400Inlet SWL (db) 80 79 78 77 81 77 76 75 77 76Outlet SWL (db) 83 82 80 82 84 80 80 79 80 79Absorbed power (Watts) 792 811 826 834 841 850 862 871 879 870
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 4800 4600 4300 4000 3800 3600 3300 3000 2700 2400
Dry Efficiency % 75.8 76.0 76.0 76.0 76.1 76.0 76.3 78.2 78.6 78.6Wet Efficiency % 84.2 84.4 84.4 84.4 84.5 84.4 84.7 86.9 87.3 87.3Supply Air Lat °C 16.9 16.9 16.9 16.9 17.0 17.0 17.0 17.6 17.7 17.7Energy Recovered (Kw) 37 34 32 29 28 26 24 23 20 18
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Electric Heater DataBased on minimum airflow 33Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximum heating output 33Kw.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
25
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 6600 6000 5400 4800 4200 3600 3000 2100Inlet SWL (db) 85 85 82 80 80 78 76 74Outlet SWL (db) 88 87 86 85 85 80 80 77Absorbed power (Watts) 1044 1030 1011 988 976 955 936 904
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart MODEL AHPHX 1800/T1/310-390/3F
Performance TYPICAL TYPE 1 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1
30/25 FG 990 1960 1860 100 930 930 870 870 1800 1740 227530/25 AS 1190 1960 1860 100 930 930 870 870 1800 1740 227530/25 PB 1257 1960 1860 100 930 930 870 870 1800 1740 227530/25 TS PB 1257 1960 1860 100 930 930 870 870 1800 1740 227550/50 FG 1034 2000 1900 100 1000 1000 900 900 1850 1750 282550/50 FG PB 1168 2000 1900 100 1000 1000 900 900 1850 1750 282550/50 FG TS PB 1390 2000 1900 100 1000 1000 900 900 1850 1750 282550/50 AS TS PB 1613 2000 1900 100 1000 1000 900 900 1850 1750 282550/50 AS QS PB 1902 2000 1900 100 1000 1000 900 900 1850 1750 2825
Dimensions and Weight
Airflow (m³/Hr) 6600 6000 5400 4800 4200 3600 3000 2100
Dry Efficiency % 74.7 74.7 74.7 75.9 76.0 78.5 78.5 73.1Wet Efficiency % 83.1 83.1 83.1 84.3 84.5 87.2 87.2 81.4Supply Air Lat °C 16.6 16.6 16.6 16.9 17.0 17.7 17.7 16.2Energy Recovered (Kw) 48 43 39 35 31 27 23 15
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan DataMotor output 1170WATTSElectric supply 240V/1/50HzMaximum current rating 7.8AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/3F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger with by pass Model PHX/W1700-1200/D1670-790
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
26
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 6300 5700 5100 4500 3900 3300 2700 1800 Inlet SWL (db) 85 85 82 80 80 78 76 74 Outlet SWL (db) 88 87 86 85 85 80 80 77Absorbed power (Watts) 1044 1030 1011 988 976 955 936 904
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart MODEL AHPHX 1800/T2/310-390/3F
Performance TYPICAL TYPE 2 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1083 1960 1860 100 930 930 870 870 1800 1740 2775 32030/25 AS 1303 1960 1860 100 930 930 870 870 1800 1740 2775 32030/25 PB 1357 1960 1860 100 930 930 870 870 1800 1740 2775 32030/25 TS PB 1357 1960 1860 100 930 930 870 870 1800 1740 2775 32050/50 FG 1126 2000 1900 100 1000 1000 900 900 1850 1750 2825 36050/50 FG PB 1270 2000 1900 100 1000 1000 900 900 1850 1750 2825 36050/50 FG TS PB 1491 2000 1900 100 1000 1000 900 900 1850 1750 2825 36050/50 AS TS PB 1718 2000 1900 100 1000 1000 900 900 1850 1750 2825 36050/50 AS QS PB 2009 2000 1900 100 1000 1000 900 900 1850 1750 2825 360
NOTE Type 2 (T2) AHPHX Units have a single bottom deck section attached to the type 1 Unit (T1), containing anelectric or LPHW heating coil as illustrated on the above diagram.
Dimensions and Weight
Airflow (m³/Hr) 6300 5700 5100 4500 3900 3300 2700 1800
Dry Efficiency % 74.7 74.7 74.7 75.9 76.0 78.5 78.5 73.1Wet Efficiency % 83.1 83.1 83.1 84.3 84.5 87.2 87.2 81.4Supply Air Lat °C 16.6 16.6 16.6 16.9 17.0 17.7 17.7 16.2Energy Recovered (Kw) 48 43 39 35 31 27 23 15
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTRotary Thermal Wheel efficiency based on return air entering at 21°C db/50% relative humidity.Supply air entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan DataMotor output 1170WATTSElectric supply 240V/1/50HzMaximum current rating 7.8AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/3F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W1700-1200/D1670-790
Electric Heater DataBased on minimum airflow33Kw single or three phaseelectric supply.
LPHW Coil DataBased on maximum airflowand LPHW @ 82/71°C. Maximum heating output36Kw.
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
27
Selection Chart MODEL AHPHX 1800/T3/310-390/3F
Performance TYPICAL TYPE 3 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1180 1960 1860 100 930 930 870 870 1700 1640 2275 68030/25 AS 1447 1960 1860 100 930 930 870 870 1700 1640 2275 68030/25 PB 1537 1960 1860 100 930 930 870 870 1700 1640 2275 68030/25 TS PB 1537 1960 1860 100 930 930 870 870 1700 1640 2275 68050/50 FG 1233 2000 1900 100 1000 1000 900 900 1750 1650 2825 72050/50 FG PB 1419 2000 1900 100 1000 1000 900 900 1750 1650 2825 72050/50 FG TS PB 1718 2000 1900 100 1000 1000 900 900 1750 1650 2825 72050/50 AS TS PB 2011 2000 1900 100 1000 1000 900 900 1750 1650 2825 72050/50 AS QS PB 2389 2000 1900 100 1000 1000 900 900 1750 1650 2825 720
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil.
A heat pump coil is also available in this section as an option. All as illustrated on the above diagram.
Dimensions and Weight
Fan DataMotor output 1170 WATTSElectric supply 240V/1/50HzMaximum current rating 7.8AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/3F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W1600-1000/D1670-960
Electric Heater DataBased on minimum airflow 33Kwsingle or three phase electric supply.
LPHW Coil Data
Based on maximum airflow andLPHW @ 82/71°C. Maximum heat-ing output 36 Kw.
Cooling/Heat Pump Coil DataChilled water/direct expansion coildata based on maximum airflow &chilled water @ 6/12°C or DXevaporating @ 6°C.Max cooling output 36Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 6300 5700 5100 4500 3900 3300 2700 1800Inlet SWL (db) 85 84 80 79 82 79 77 75 Outlet SWL (db) 88 86 84 83 85 80 80 78Absorbed power (Watts) 1012 983 960 941 922 900 876 852
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 6300 5700 5100 4500 3900 3300 2700 1800
Dry Efficiency % 74.6 74.7 74.8 75.9 76.0 78.7 74.5 77.8Wet Efficiency % 83.0 83.1 83.2 84.3 84.5 87.4 82.9 86.5Supply Air Lat °C 16.6 16.6 16.6 16.9 17.0 17.7 16.6 17.5Energy Recovered (Kw) 45 41 37 33 29 25 19 14
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
28
Selection Chart MODEL AHPHX 1800/T4/310-390/3F
Performance TYPICAL TYPE 4 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1346 1800 1700 100 850 850 790 790 1800 1740 2360 107030/25 AS 1650 1800 1700 100 850 850 790 790 1800 1740 2360 107030/25 PB 1752 1800 1700 100 850 850 790 790 1800 1740 2360 107030/25 TS PB 1752 1800 1700 100 850 850 790 790 1800 1740 2360 107050/50 FG 1405 1850 1750 100 875 875 775 775 1850 1750 2400 107050/50 FG PB 1654 1850 1750 100 875 875 775 775 1850 1750 2400 115050/50 FG TS PB 1938 1850 1750 100 875 875 775 775 1850 1750 2400 115050/50 AS TS PB 2089 1850 1750 100 875 875 775 775 1850 1750 2400 115050/50 AS QS PB 2718 1850 1750 100 875 875 775 775 1850 1750 2400 1150
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil.
A heat pump coil is also available in this section as an option. All as illustrated on the above diagram.
Section includes a F5 to F7 grade Bag Filter arranged for side withdrawal.
Dimensions and Weight
Fan DataMotor output 1170WATTSElectric supply 240V/1/50HzMaximum current rating 7.8AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/3F
Filter DataG3 or G4 grade panel filters.Secondary F7 grade Bag Filters
Energy RecoveryPlate Heat Exchanger with bypass Model PHX/W1700-1100/D1390-965
Electric Heater DataBased on minimum airflow 21Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximum heating output 25Kw.
Cooling/Heat Pump Coil DataChilled water/direct expansion coildata based on maximum airflow &chilled water @ 6/12°C or DXevaporating @ 6°C.Max cooling output 24Kw.
External Pressure Pascals 50 100 150 200 250
Airflow (m³/Hr) 4800 4200 3600 3000 2200Inlet SWL (db) 80 79 77 75 74Outlet SWL (db) 83 82 80 79 78Absorbed power (Watts) 733 720 694 648 612
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 4800 4200 3600 3000 2200
Dry Efficiency % 78.2 78.4 78.8 76.1 73.0Wet Efficiency % 86.9 87.1 87.4 84.1 81.3Supply Air Lat °C 17.6 17.7 17.7 16.9 16.1Energy Recovered (Kw) 36 32 27 22 16
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
29
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600 650
Airflow (m³/Hr) 9000 8700 8250 7800 7500 6900 6600 6000 5700 5400 4900 4500 3500Inlet SWL (db) 77 77 78 76 76 74 74 75 74 74 76 75 75Outlet SWL (db) 81 81 82 80 82 79 80 80 80 80 80 80 80Absorbed power (Watts) 1320 1308 1296 1284 1277 1260 1252 1244 1237 1220 1210 1198 1187
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart MODEL AHPHX 2000/T1/310-680/3F
Performance TYPICAL TYPE 1 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1
30/25 FG 1159 1960 1860 100 930 930 870 870 2100 2040 294030/25 AS 1408 1960 1860 100 930 930 870 870 2100 2040 294030/25 PB 1491 1960 1860 100 930 930 870 870 2100 2040 294030/25 TS PB 1491 1960 1860 100 930 930 870 870 2100 2040 294050/50 FG 1214 2000 1900 100 1000 1000 900 900 2150 2050 300050/50 FG PB 1380 2000 1900 100 1000 1000 900 900 2150 2050 300050/50 FG TS PB 1657 2000 1900 100 1000 1000 900 900 2150 2050 300050/50 AS TS PB 1934 2000 1900 100 1000 1000 900 900 2150 2050 300050/50 AS QS PB 2294 2000 1900 100 1000 1000 900 900 2150 2050 3000
Dimensions and Weight
Airflow (m³/Hr) 9000 8700 8250 7800 7500 6900 6600 6000 5700 5400 4900 4500 3500
Dry Efficiency % 74.2 74.3 74.3 74.3 74.4 74.4 74.5 74.3 74.5 74.4 75.8 76.1 78.5Wet Efficiency % 82.6 82.7 84.7 82.7 82.8 82.0 82.8 82.7 82.8 82.8 84.2 84.5 87.3Supply Air Lat °C 16.5 16.5 16.5 16.5 16.5 16.3 16.5 16.5 16.5 16.5 16.9 17.0 17.7Energy Recovered (Kw) 65 63 59 56 54 49 48 43 41 39 36 33 27
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan DataMotor output 2040WATTSElectric supply 240V/1/50HzMaximum current rating 12.9AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/3F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger with by pass Model PHX/W2000-1400/D1650-1390
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
30
Selection Chart MODEL AHPHX 2000/T2/310-680/3F
Performance TYPICAL TYPE 2 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1347 1960 1860 100 930 930 870 870 2100 2040 2940 32030/25 AS 1636 1960 1860 100 930 930 870 870 2100 2040 2940 32030/25 PB 1733 1960 1860 100 930 930 870 870 2100 2040 2940 32030/25 TS PB 1733 1960 1860 100 930 930 870 870 2100 2040 2940 32050/50 FG 1412 2000 1900 100 1000 1000 900 900 2150 2050 3000 36050/50 FG PB 1605 2000 1900 100 1000 1000 900 900 2150 2050 3000 36050/50 FG TS PB 1926 2000 1900 100 1000 1000 900 900 2150 2050 3000 36050/50 AS TS PB 2249 2000 1900 100 1000 1000 900 900 2150 2050 3000 36050/50 AS QS PB 2666 2000 1900 100 1000 1000 900 900 2150 2050 3000 360
NOTE Type 2 (T2) AHPHX Units have a single bottom deck section attached to the type 1 (T1), containing an electric orLPHW Heating Coil as illustrated on the above diagram.
Dimensions and Weight
Fan DataMotor output 2040WATTSElectric supply 240V/1/50HzMaximum current rating 12.9AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/3F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W2000-1400/D1670-1390
Electric Heater DataBased on minimum airflow 54Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximum heating output 60Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600 650
Airflow (m³/Hr) 9000 8700 8250 7800 7500 6900 6600 6000 5700 5400 4900 4500 3500Inlet SWL (db) 77 77 78 76 76 74 74 75 74 74 76 75 75Outlet SWL (db) 81 81 82 80 82 79 80 80 80 80 80 80 80Absorbed power (Watts) 1320 1308 1296 1284 1277 1260 1252 1244 1237 1220 1210 1198 1187
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 9000 8700 8250 7800 7500 6900 6600 6000 5700 5400 4900 4500 3500
Dry Efficiency % 74.2 74.3 74.3 74.3 74.4 74.4 74.5 74.3 74.5 74.4 75.8 76.1 78.5Wet Efficiency % 82.6 82.7 84.7 87.7 82.8 82.0 82.8 82.7 82.8 82.8 84.2 84.5 87.3Supply Air Lat °C 16.5 16.5 16.5 16.5 16.5 16.3 16.5 16.5 16.5 16.5 16.9 17.0 17.7Energy Recovered (Kw) 65 63 59 56 54 49 48 43 41 39 36 33 27
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
31
Selection Chart MODEL AHPHX 2000/T3/310-680/3F
Performance TYPICAL TYPE 3 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1548 1960 1860 100 930 930 870 870 2000 1940 2940 68030/25 AS 1870 1960 1860 100 930 930 870 870 2000 1940 2940 68030/25 PB 1977 1960 1860 100 930 930 870 870 2000 1940 2940 68030/25 TS PB 1977 1960 1860 100 930 930 870 870 2000 1940 2940 68050/50 FG 1619 2000 1900 100 1000 1000 900 900 2050 1950 3000 72050/50 FG PB 1832 2000 1900 100 1000 1000 900 900 2050 1950 3000 72050/50 FG TS PB 2184 2000 1900 100 1000 1000 900 900 2050 1950 3000 72050/50 AS TS PB 2541 2000 1900 100 1000 1000 900 900 2050 1950 3000 72050/50 AS QS PB 3000 2000 1900 100 1000 1000 900 900 2050 1950 3000 720
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil.
A heat pump coil is also available in this section as an option. All as illustrated on the above diagram.
Dimensions and Weight
Fan DataMotor output 2040WATTSElectric supply 240V/1/50HzMaximum current rating 12.9AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/3F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W1900-1300/D1670-1390
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600
Airflow (m³/Hr) 8200 7900 7500 7200 6700 6400 6000 5500 5100 4600 4000 3600Inlet SWL (db) 77 76 77 75 76 75 75 74 74 74 74 75Outlet SWL (db) 82 81 81 80 81 80 80 79 80 81 80 81Absorbed power (Watts) 1190 1181 1176 1165 1150 1142 1130 1122 1110 1096 1080 1071
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 8200 7900 7500 7200 6700 6400 6000 5500 5100 4100 4000 3600
Dry Efficiency % 74.4 74.5 74.4 74.6 74.6 74.5 74.9 75.9 76.1 78.4 78.4 78.7Wet Efficiency % 82.7 82.8 82.8 82.9 83.0 82.9 83.3 84.3 84.5 87.1 87.1 87.7Supply Air Lat °C 16.5 16.5 16.5 16.6 16.6 16.6 16.7 16.9 17.0 17.7 17.6 17.7Energy Recovered (Kw) 59 57 54 52 48 46 43 40 37 35 30 27
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Electric Heater DataBased on maximum airflow 51Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C.Maximum heating output 55Kw.
Cooling/Heat PumpCoil DataChilled water/directexpansion coil data basedon maximum airflow &chilled water @ 6/12°C orDX evaporating @ 6°C.Max cooling output 55Kw.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
32
Selection Chart MODEL AHPHX 2000/T4/310-680/3F
Performance TYPICAL TYPE 4 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1758 1960 1860 100 930 930 870 870 1900 1840 2940 107030/25 AS 2120 1960 1860 100 930 930 870 870 1900 1840 2940 107030/25 PB 2242 1960 1860 100 930 930 870 870 1900 1840 2940 107030/25 TS PB 2242 1960 1860 100 930 930 870 870 1900 1840 2940 107050/50 FG 1841 2000 1900 100 1000 1000 900 900 1950 1850 3000 115050/50 FG PB 2077 2000 1900 100 1000 1000 900 900 1950 1850 3000 115050/50 FG TS PB 2477 2000 1900 100 1000 1000 900 900 1950 1850 3000 115050/50 AS TS PB 2880 2000 1900 100 1000 1000 900 900 1950 1850 3000 115050/50 AS QS PB 3403 2000 1900 100 1000 1000 900 900 1950 1850 3000 1150
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil.
A heat pump coil is also available in this section as an option. All as illustrated on the above diagram.
Section includes a F5 to F7 grade Bag Filter arranged for side withdrawal.
Dimensions and Weight
Fan DataMotor output 2040WATTSElectric supply 240V/1/50HzMaximum current rating 12.9AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/3F
Filter DataG3 or G4 grade panel filters.Secondary F7 Bag Filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W1800-1300/D1670-1390
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500
Airflow (m³/Hr) 7500 6900 6400 6000 5700 5400 4900 4500 4000 3600Inlet SWL (db) 76 75 76 75 76 75 77 76 76 75Outlet SWL (db) 80 79 80 79 80 78 82 80 79 78Absorbed power (Watts) 990 977 962 950 938 925 912 898 877 856
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 7500 6900 6400 6000 5700 5400 4900 4500 4000 3600
Dry Efficiency % 74.4 74.5 74.5 74.7 74.7 76.2 76.0 76.1 76.2 76.2Wet Efficiency % 82.8 82.9 82.9 83.3 83.1 84.6 84.4 84.5 84.6 84.7Supply Air Lat °C 16.5 16.5 16.6 16.6 16.6 17.0 16.9 17.0 17.0 17.0Energy Recovered (Kw) 54 50 46 43 41 40 36 33 29 26
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Electric Heater DataBased on minimum airflow 42Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximum heating output 46Kw.
Cooling/Heat PumpCoil DataChilled water/directexpansion coil data basedon maximum airflow &chilled water @ 6/12°C orDX evaporating @ 6°C.Max cooling output 45Kw.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
33
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 8800 8000 7200 6400 5600 4800 4000 2800Inlet SWL (db) 78 77 80 76 75 74 75 75Outlet SWL (db) 82 81 83 80 80 78 80 80Absorbed power (Watts) 896 928 950 970 986 1011 999 977
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart MODEL AHPHX 2100/T1/310-390/4F
Performance TYPICAL TYPE 1 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1
30/25 FG 1228 1960 1860 100 930 930 870 870 2000 1940 294030/25 AS 1476 1960 1860 100 930 930 870 870 2000 1940 294030/25 PB 1559 1960 1860 100 930 930 870 870 2000 1940 294030/25 TS PB 1559 1960 1860 100 930 930 870 870 2000 1940 294050/50 FG 1283 2000 1900 100 1000 1000 900 900 2050 1950 300050/50 FG PB 1449 2000 1900 100 1000 1000 900 900 2050 1950 300050/50 FG TS PB 1725 2000 1900 100 1000 1000 900 900 2050 1950 300050/50 AS TS PB 2001 2000 1900 100 1000 1000 900 900 2050 1950 300050/50 AS QS PB 2360 2000 1900 100 1000 1000 900 900 2050 1950 3000
Dimensions and Weight
Airflow (m³/Hr) 8800 8000 7200 6400 5600 4800 4000 2800
Dry Efficiency % 74.2 74.4 74.2 74.7 75.8 76.1 76.4 73.1Wet Efficiency % 82.5 82.8 82.9 83.1 84.2 84.5 84.8 81.3 Supply Air Lat °C 16.4 16.5 16.6 16.6 16.9 17.0 17.0 16.1Energy Recovered (Kw) 63 58 52 46 41 35 29 20
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan DataMotor output 1560WATTSElectric supply 240V/1/50HzMaximum current rating 10.4AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/4F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger with by pass Model PHX/W1900-1400/D1670-960
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
34
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 8800 8000 7200 6400 5600 4800 4000 2800Inlet SWL (db) 78 77 80 76 75 74 75 75Outlet SWL (db) 82 81 83 80 80 78 80 80Absorbed power (Watts) 896 928 950 970 986 1011 999 977
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart AHPHX 2100/T2/310-390/4F
Performance TYPICAL TYPE 2 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1396 1960 1860 100 930 930 870 870 2000 1940 2940 32030/25 AS 1680 1960 1860 100 930 930 870 870 2000 1940 2940 32030/25 PB 1749 1960 1860 100 930 930 870 870 2000 1940 2940 32030/25 TS PB 1749 1960 1860 100 930 930 870 870 2000 1940 2940 32050/50 FG 1452 2000 1900 100 1000 1000 900 900 2050 1950 3000 36050/50 FG PB 1636 2000 1900 100 1000 1000 900 900 2050 1950 3000 36050/50 FG TS PB 1922 2000 1900 100 1000 1000 900 900 2050 1950 3000 36050/50 AS TS PB 2215 2000 1900 100 1000 1000 900 900 2050 1950 3000 36050/50 AS QS PB 2589 2000 1900 100 1000 1000 900 900 2050 1950 3000 360
NOTE Type 2 (T2) AHPHX Units have a single bottom deck section attached to the type 1 (T1), containing an electric orLPHW Heating Coil as illustrated on the above diagram.
Dimensions and Weight
Airflow (m³/Hr) 8800 8000 7200 6400 5600 4800 4000 2800
Dry Efficiency % 74.2 74.4 74.2 74.7 75.8 76.1 76.4 73.1Wet Efficiency % 82.5 82.8 82.9 83.1 84.2 84.5 84.8 81.3Supply Air Lat °C 16.4 16.5 16.6 16.6 16.9 17.0 17.0 16.1Energy Recovered (Kw) 63 58 52 46 41 35 29 20
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan DataMotor output 1560WATTSElectric supply 240V/1/50HzMaximum current rating 10.4AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/4F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W1900-1400/D1670-960
Electric Heater DataBased on maximum airflow45Kw single or three phaseelectric supply.
LPHW Coil DataBased on maximum airflowand LPHW @ 82/71°C.Maximum heating output50Kw.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
35
Selection Chart MODEL AHPHX 2100/T3/310-390/4F
Performance TYPICAL TYPE 3 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1601 1960 1860 100 930 930 870 870 2000 1940 2940 68030/25 AS 1963 1960 1860 100 930 930 870 870 2000 1940 2940 68030/25 PB 2086 1960 1860 100 930 930 870 870 2000 1940 2940 68030/25 TS PB 2086 1960 1860 100 930 930 870 870 2000 1940 2940 68050/50 FG 1672 2000 1900 100 1000 1000 900 900 2050 1950 3000 72050/50 FG PB 1925 2000 1900 100 1000 1000 900 900 2050 1950 3000 72050/50 FG TS PB 2193 2000 1900 100 1000 1000 900 900 2050 1950 3000 72050/50 AS TS PB 2728 2000 1900 100 1000 1000 900 900 2050 1950 3000 72050/50 AS QS PB 3241 2000 1900 100 1000 1000 900 900 2050 1950 3000 720
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil.
A heat pump coil is also available in this section as an option. All as illustrated on the above diagram.
Dimensions and Weight
Fan DataMotor output 1560WATTSElectric supply 240V/1/50HzMaximum current rating 10.4AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/4F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W1900-1200/D1670-1175
Electric Heater DataBased on maximum airflow 42Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C. Maximumheating output 46Kw.
Cooling/Heat Pump Coil DataChilled water/direct expansion coildata based on maximum airflow &chilled water @ 6/12°C or DXevaporating @ 6°C. Max coolingoutput 45Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400
Airflow (m³/Hr) 8400 7600 6800 6000 5200 4400 3600 2400Inlet SWL (db) 64 64 68 70 73 72 74 73Outlet SWL (db) 68 69 74 75 77 77 80 78 Absorbed power (Watts) 384 398 432 462 488 496 490 480
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 8400 7600 6800 6000 5200 4400 3600 2400
Dry Efficiency % 74.3 74.7 74.7 74.7 75.8 75.9 76.2 74.7Wet Efficiency % 82.6 83.1 83.1 83.1 84.2 84.3 84.7 83.0Supply Air Lat °C 16.5 16.6 16.6 16.6 16.9 16.9 17.0 16.6Energy Recovered (Kw) 60 55 49 43 38 32 26 17
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
36
Selection Chart MODEL AHPHX 2100/T4/310-390/4F
Performance TYPICAL TYPE 4 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1827 1960 1860 100 930 930 870 870 1800 1740 2775 107030/25 AS 2240 1960 1860 100 930 930 870 870 1800 1740 2775 107030/25 PB 2378 1960 1860 100 930 930 870 870 1800 1740 2775 107030/25 TS PB 2378 1960 1860 100 930 930 870 870 1800 1740 2775 107050/50 FG 1907 2000 1900 100 1000 1000 900 900 1850 1750 1825 115050/50 FG PB 2245 2000 1900 100 1000 1000 900 900 1850 1750 1825 115050/50 FG TS PB 2630 2000 1900 100 1000 1000 900 900 1850 1750 1825 115050/50 AS TS PB 3106 2000 1900 100 1000 1000 900 900 1850 1750 1825 115050/50 AS QS PB 3689 2000 1900 100 1000 1000 900 900 1850 1750 1825 1150
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil. A heat pump coil is also available in this section as an option. All as illustrated on the above diagram. Section includes a F5 to F7 grade Bag Filter arranged for side withdrawal.
Dimensions and Weight
Fan DataMotor output 1560WATTSElectric supply 240V/1/50HzMaximum current rating 10.4AmpsMaximum Speed @10Volts 2350RPMFan Reference EC310/390/4F
Filter DataG3 or G4 grade panel filters.Secondary F7 grade Bag Filters
Energy RecoveryPlate Heat Exchanger with bypass Model PHX/W1700-1300/D1670-1175
Electric Heater DataBased on maximum airflow 30Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C.Maximum heating output 36Kw.
Cooling/Heat Pump Coil DataChilled water/direct expansion coildata based on maximum airflow &chilled water @ 6/12°C or DXevaporating @ 6°C.Max cooling output 35Kw.
External Pressure Pascals 50 100 150 200 250
Airflow (m³/Hr) 6400 5600 4800 4000 3000Inlet SWL (db) 66 65 70 69 73Outlet SWL (db) 70 71 75 74 77Absorbed power (Watts) 376 392 426 448 464
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 6400 5600 4800 4000 3000
Dry Efficiency % 74.7 74.7 75.9 76.2 76.1Wet Efficiency % 83.1 83.1 84.3 84.6 84.1Supply Air Lat °C 16.6 16.6 16.9 17.0 16.9Energy Recovered (Kw) 46 40 35 29 22
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
37
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600 650
Airflow (m³/Hr) 12000 11600 11000 10400 10000 9200 8800 8000 7600 7200 6600 6000 4800Inlet SWL (db) 85 85 86 85 86 84 85 83 85 83 82 83 81Outlet SWL (db) 90 89 91 89 90 88 89 87 88 86 85 86 85Absorbed power (Watts) 1760 1770 1780 1804 1817 1828 1840 1857 1850 1840 1826 1810 1793
Airflow performance based on maximum speed @ 10 Volts.
Selection Chart MODEL AHPHX 2300/T1/310-680/4F
Performance TYPICAL TYPE 1 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Air Flow Performance
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1
30/25 FG 1494 1960 1860 100 930 930 870 870 2840 2780 325030/25 AS 1815 1960 1860 100 930 930 870 870 2840 2780 325030/25 PB 1922 1960 1860 100 930 930 870 870 2840 2780 325030/25 TS PB 1922 1960 1860 100 930 930 870 870 2840 2780 325050/50 FG 1565 2000 1900 100 1000 1000 900 900 2900 2800 350050/50 FG PB 1780 2000 1900 100 1000 1000 900 900 2900 2800 350050/50 FG TS PB 2137 2000 1900 100 1000 1000 900 900 2900 2800 350050/50 AS TS PB 2494 2000 1900 100 1000 1000 900 900 2900 2800 350050/50 AS QS PB 2958 2000 1900 100 1000 1000 900 900 2900 2800 3500
Dimensions and Weight
Airflow (m³/Hr) 12000 11600 11000 10400 10000 9200 8800 8000 7600 7200 6600 6000 4800
Dry Efficiency % 74.3 74.3 74.3 74.4 74.5 74.6 74.7 74.6 74.6 74.6 74.7 74.7 76.1Wet Efficiency % 82.6 82.6 82.7 82.7 82.8 82.9 83.1 82.9 82.9 82.9 83.1 83.1 84.5Supply Air Lat °C 16.5 16.5 16.5 16.5 16.5 16.6 16.6 16.6 16.6 16.6 16.6 16.6 17.0Energy Recovered (Kw) 86 83 79 75 72 66 64 58 55 52 48 43 35
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Fan DataMotor output 2720WATTSElectric supply 240V/1/50HzMaximum current rating 17.2AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/4F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger with by pass Model PHX/W1500-700/D1175-965
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
38
Selection Chart MODEL AHPHX 2300/T2/310-680/4F
Performance TYPICAL TYPE 2 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1695 1960 1860 100 930 930 870 870 2840 2780 3250 32030/25 AS 2059 1960 1860 100 930 930 870 870 2840 2780 3250 32030/25 PB 2180 1960 1860 100 930 930 870 870 2840 2780 3250 32030/25 TS PB 2180 1960 1860 100 930 930 870 870 2840 2780 3250 32050/50 FG 1776 2000 1900 100 1000 1000 900 900 2900 2800 3500 36050/50 FG PB 2019 2000 1900 100 1000 1000 900 900 2900 2800 3500 36050/50 FG TS PB 2423 2000 1900 100 1000 1000 900 900 2900 2800 3500 36050/50 AS TS PB 2830 2000 1900 100 1000 1000 900 900 2900 2800 3500 36050/50 AS QS PB 3355 2000 1900 100 1000 1000 900 900 2900 2800 3500 360
NOTE Type 2 (T2) AHPHX Units have a single bottom deck section attached to the type 1 (T1), containing an electric orLPHW Heating Coil as illustrated on the above diagram.
Dimensions and Weight
Fan DataMotor output 2720WATTSElectric supply 240V/1/50HzMaximum current rating 17.2AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/4F
Filter DataG3 or G4 grade panel filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W2700-1600/D1670-1390
Electric Heater DataBased on maximum airflow 75Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C.Maximum heating output 85Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600 650
Airflow (m³/Hr) 12000 11600 11000 10400 10000 9200 8800 8000 7600 7200 6600 6000 4800Inlet SWL (db) 85 85 86 85 86 84 85 83 85 83 82 83 81Outlet SWL (db) 90 89 91 89 90 88 89 87 88 86 85 86 85Absorbed power (Watts) 1760 1770 1780 1804 1817 1828 1840 1857 1850 1840 1826 1810 1793
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 12000 11600 11000 10400 10000 9200 8800 8000 7600 7200 6600 6000 4800
Dry Efficiency % 74.3 74.3 74.3 74.4 74.5 74.6 74.7 74.6 74.6 74.6 74.7 74.7 76.1Wet Efficiency % 82.6 82.6 82.7 82.7 82.8 82.9 83.1 82.9 82.9 82.9 83.1 83.1 84.5Supply Air Lat °C 16.5 16.5 16.5 16.5 16.5 16.6 16.6 16.6 16.6 16.6 16.6 16.6 17.0Energy Recovered (Kw) 86 83 79 75 72 66 64 58 55 52 48 43 35
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
39
Selection Chart MODEL AHPHX 2300/T3/310-680/4F
Performance TYPICAL TYPE 3 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 1950 1960 1860 100 930 930 870 870 2650 2590 3250 68030/25 AS 2354 1960 1860 100 930 930 870 870 2650 2590 3250 68030/25 PB 2490 1960 1860 100 930 930 870 870 2650 2590 3250 68030/25 TS PB 2490 1960 1860 100 930 930 870 870 2650 2590 3250 68050/50 FG 2038 2000 1900 100 1000 1000 900 900 2700 2600 3500 72050/50 FG PB 2307 2000 1900 100 1000 1000 900 900 2700 2600 3500 72050/50 FG TS PB 2750 2000 1900 100 1000 1000 900 900 2700 2600 3500 72050/50 AS TS PB 3199 2000 1900 100 1000 1000 900 900 2700 2600 3500 72050/50 AS QS PB 3778 2000 1900 100 1000 1000 900 900 2700 2600 3500 720
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil. A heat pump coil is also available in this section as an option. All as illustrated on the above diagram. Section includes a F5 to F7 grade Bag Filter arranged for side withdrawal.
Dimensions and Weight
Fan DataMotor output 2720WATTSElectric supply 240V/1/50HzMaximum current rating 17.2AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/4F
Filter DataG3 or G4 grade panel filters.Secondary F7 grade Bag Filters.
Energy RecoveryPlate Heat Exchanger with bypass Model PHX/W2500-1600/D1670-1390
Cooling/Heat PumpCoil DataChilled water/directexpansion coil data basedon maximum airflow &chilled water @ 6/12°C orDX evaporating @ 6°C.Max cooling output 65Kw.
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500 550 600
Airflow (m³/Hr) 11000 10600 10000 9600 9100 8600 8000 7400 6800 6200 5400 4800Inlet SWL (db) 84 86 83 83 86 85 83 82 83 82 83 83Outlet SWL (db) 88 89 87 86 88 87 86 85 85 84 85 86Absorbed power (Watts) 1810 1790 1795 1810 1790 1771 1760 1748 1731 1722 1711 1696
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 11000 10600 10000 9600 9100 8600 8000 7400 6800 6200 5400 4800
Dry Efficiency % 74.3 74.3 74.3 74.3 74.3 74.4 74.4 74.7 74.7 74.6 75.9 76.1Wet Efficiency % 82.7 82.7 82.7 82.7 82.7 82.7 82.8 83.1 83.1 82.3 84.3 84.5Supply Air Lat °C 16.5 16.5 16.5 16.5 16.5 16.5 16.5 16.6 16.6 16.4 16.9 17.0Energy Recovered (Kw) 79 76 72 69 65 62 58 53 49 44 40 35
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Electric Heater DataBased on maximum airflow 66Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C.Maximum heating output 70Kw.
AHPH
X Com
pact H
eat Re
cove
ry Air H
andling Unit
40
Selection Chart MODEL AHPHX 2300/T4/310-680/4F
Performance TYPICAL TYPE 4 COMPONENT CONFIGURATION
SIDE ELEVATION FRONT ELEVATION END ELEVATION
RETURN
AIR
EXHAUST
DISCHARGE
FRESH
AIR
SUPPLY
AIR
Casework Class Weight (kg) H1 H2 H3 H4 H5 H6 H7 W1 W2 L1 L2
30/25 FG 2196 2200 2100 100 1050 1050 990 990 2450 2390 3000 107030/25 AS 2648 2200 2100 100 1050 1050 990 990 2450 2390 3000 107030/25 PB 2799 2200 2100 100 1050 1050 990 990 2450 2390 3000 107030/25 TS PB 2799 2200 2100 100 1050 1050 990 990 2450 2390 3000 107050/50 FG 2299 2250 2150 100 1050 1050 950 950 2500 2400 3050 115050/50 FG PB 2594 2250 2150 100 1050 1050 950 950 2500 2400 3050 115050/50 FG TS PB 3094 2250 2150 100 1050 1050 950 950 2500 2400 3050 115050/50 AS TS PB 3597 2250 2150 100 1050 1050 950 950 2500 2400 3050 115050/50 AS QS PB 4249 2250 2150 100 1050 1050 950 950 2500 2400 3050 1150
NOTE Type 3 (T3) AHPHX Units have a single bottom deck section attached to the type 1 (T1) unit, containing anelectric or LPHW heating coil, together with a chilled water or direct expansion cooling coil. A heat pump coil is also available in this section as an option. All as illustrated on the above diagram. Section includes a F5 to F7 grade Bag Filter arranged for side withdrawal.
Dimensions and Weight
Fan DataMotor output 2720WATTSElectric supply 240V/1/50HzMaximum current rating 17.2AmpsMaximum Speed @10Volts 3000RPMFan Reference EC310/680/4F
Filter DataG3 or G4 grade panel filters.Secondary F7 Bag Filters.
Energy RecoveryPlate Heat Exchanger withby pass Model PHX/W2300-1500/D1940-1390
External Pressure Pascals 50 100 150 200 250 300 350 400 450 500
Airflow (m³/Hr) 10000 9200 8600 8000 7600 7200 6600 6000 5400 4800Inlet SWL (db) 83 83 85 83 82 83 82 82 83 83Outlet SWL (db) 87 86 87 86 85 85 84 84 85 86Absorbed power (Watts) 1800 1826 1837 1804 1770 1748 1720 1702 1670 1652
Airflow performance based on maximum speed @ 10 Volts.
Air Flow Performance
Airflow (m³/Hr) 10000 9200 8600 8000 7600 7200 6600 6000 5400 4800
Dry Efficiency % 74.2 74.5 74.5 74.6 74.7 74.6 74.8 74.7 74.7 75.9Wet Efficiency % 81.8 82.8 82.9 82.9 83.1 82.9 83.2 83.1 83.1 84.3Supply Air Lat °C 16.3 16.5 16.5 16.6 16.6 16.6 16.6 16.6 16.6 16.9Energy Recovered (Kw) 71 66 62 58 55 52 48 43 39 35
EQUAL AIRFLOWSECO DIRECTIVE ErP 2016/2018 COMPLIANTPlate Exchanger efficiency based on return air temperature entering at 21°C db/50% relative humidity.Supply air temperature entering at -5°C db/95% relative humidity.
Plate Heat Exchanger Efficiency %
Electric Heater DataBased on maximum airflow 57Kwsingle or three phase electric supply.
LPHW Coil DataBased on maximum airflow andLPHW @ 82/71°C.Maximum heating output 65Kw.
Cooling/Heat PumpCoil DataChilled water/directexpansion coil data basedon maximum airflow &chilled water @ 6/12°C orDX evaporating @ 6°C.Max cooling output 60Kw.
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
41
Performance Graphs…
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 800/310-390/T1&2/1F
500 1000 1500 2000 2500 3000
600
700
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1000/310-680/T1&2/1F
500 1000 1500 2000 2500 3000
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 800/310-390/T3/1F
500 1000 1500 2000 2500 3000
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 800/310-390/T4/1F
500 1000 1500 2000 2500 3000
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1000/310-680/T4/1F
500 1000 1500 2000 2500 3000
600
700
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1000/T1&2/310-680/1F
500 1000 1500 2000 2500 3000
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
42
Performance Graphs…
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1500/310-680/T1&2/2F
1000 2000 3000 4000 5000 6000 7000
600
700
500
400
300
200
100
Airflow (M3/Hr)Ex
tern
al R
esis
tan
ce (P
A)
AHPHX 1700/T1&2/310-680/2F
1000 2000 3000 4000 5000 6000 7000
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1500/T3/310-390/2F
500 1000 1500 2000 2500 3000
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1500/310-390/T4/1F
500 1000 1500 2000 2500 3000
600
700
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1700/T4/310-680/2F
1000 2000 3000 4000 5000 6000 7000
600
700
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1700/T3/310-680/2F
1000 2000 3000 4000 5000 6000 7000
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
43
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1700/310-390/T1&2/2F
1000 2000 3000 4000 5000 6000 7000
600
700
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 2000/310-390/T1&T2/2F
3000 4000 5000 6000 7000 8000 9000
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1700/310-390/T3 3F
1000 2000 3000 4000 5000 6000 7000
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1700/310-390/T4 3F
1000 2000 3000 4000 5000 6000 7000
600
700
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 2000/310-680/T4 3F
3000 4000 5000 6000 7000 8000 9000
600
700
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 2000/310-680/T3 3F
3000 4000 5000 6000 7000 8000 900
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
44
Performance Graphs…
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1900/310-390/T1 & T2 4F
2000 3000 4000 5000 6000 7000 8000 9000
600
700
500
400
300
200
100
Airflow (M3/Hr)
AHPHX 1900/310-680/T1 & T2 4F
4000 5000 6000 7000 8000 9000 10000 11000 12000
600
500
400
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1900/310-390/T3 4F
2000 3000 4000 5000 6000 7000 8000 9000
300
200
100
Airflow (M3/Hr)
Exte
rnal
Res
ista
nce
(PA
)
AHPHX 1900/310-390/T4 4F
2000 3000 4000 5000 6000 7000
600
700
500
400
300
200
100
Airflow (M3/Hr)
AHPHX 1900/310-680/T4 4F
4000 5000 6000 7000 8000 9000 10000 11000 12000
600
700
500
400
300
200
100
Airflow (M3/Hr)
AHPHX 1900/310-680/T3 4F
3000 4000 5000 6000 7000 8000 9000 10000 11000
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
45
Weatherproofing - External Model…For externally mounted AHPHX Compact Units, fullyweatherproof construction options are provided,incorporating a pent style roof with directional gradientslopes to protect against rain ingress as illustrated below.
SIDE ELEVATION FRONT ELEVATION END ELEVATION
AIR
SUPPLY
AIR
FRESHAIR
RETURN
DISCHARGEEXHAUST
+-
Type 1
Type 2
Type 3
Type 4
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
46
AHPHX REF WEIGHT KG W D H
AHPHX 800/390/1F/30-25 12.8 890 200 690AHPHX 800/390/1F/50-50 12.6 900 200 675AHPHX 1000/680/1F/30-25 15.7 1090 200 690AHPHX 1000/680/1F/50-50 15.6 1100 200 675AHPHX 1500/390/2F/30-25 33.1 1540 300 690AHPHX 1500/390/2F/50-50 32.6 1550 300 675AHPHX 1700/680/2F/30-25 42.8 1740 300 790AHPHX 1700/680/2F/50-50 42.4 1750 300 775AHPHX 1800/390/3F/30-25 47.3 1740 300 870AHPHX 1800/390/3F/50-50 49.1 1750 300 900AHPHX 2000/680/3F/30-25 64.6 2040 350 870AHPHX 2000/680/3F/50-50 67.1 2050 350 900AHPHX 2100/390/4F/30-25 61.4 1940 400 870AHPHX 2100/390/4F/50-50 72.9 1950 400 900AHPHX 2300/680/4F/30-25 100.4 2780 400 870AHPHX 2300/680/4F/50-50 104.9 2800 400 900
AHPHX REF WEIGHT KG W D H
AHPHX 800/390/1F/30-25 11.2 890 80 690AHPHX 800/390/1F/50-50 11.4 900 80 675AHPHX 1000/680/1F/30-25 15.2 1090 80 690AHPHX 1000/680/1F/50-50 15.2 1100 80 675AHPHX 1500/390/2F/30-25 17.5 1540 100 690AHPHX 1500/390/2F/50-50 16.8 1550 100 675AHPHX 1700/680/2F/30-25 22.8 1740 100 790AHPHX 1700/680/2F/50-50 22.8 1750 100 775AHPHX 1800/390/3F/30-25 26.9 1740 100 870AHPHX 1800/390/3F/50-50 28.3 1750 100 900AHPHX 2000/680/3F/30-25 29.4 2040 100 870AHPHX 2000/680/3F/50-50 29.9 2050 100 900AHPHX 2100/390/4F/30-25 27.3 1940 100 870AHPHX 2100/390/4F/50-50 27.9 1950 100 900AHPHX 2300/680/4F/30-25 39.3 2780 100 870AHPHX 2300/680/4F/50-50 40 2800 100 900
D
H
W
H
D
W
Standard Weather CowlStandard weather cowls containlouvre blades to give addedweather protection. The cowlsare constructed from plastisolplastic coated sheet steel.
Standard LouvreDeep seal weather louvres areprovided as standard on fresh airintakes and exhaust air outlets,constructed from anodisedaluminium with plastisol plasticcoated steel frame.
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
47
Attenuator Performance…Insertion losses for different attenuatorlengths serving atmospheric and systemside, for both integral or bolt on style.
Attenuation… All attenuators are provided to match theAHPHX Compact unit and can be supplied as anintegral or bolt on arrangement. This isrecommended to prevent noise flanking theattenuators, or the need to acoustic lag theductwork.
If the attenuators are positioned away from thenoise source (i.e. AHPHX Compact), then ductnoise breakout will occur, unless the duct isacoustically lagged to the same high standard,as the AHPHX Casework.
Option 1
Splitter absorbers inbuilt into the AHPHX Compactunit Casework which provides a uniform caseworkappearance, as shown on Figures 2 and 3 on page 47.
Option 2
Duct style attenuators with bolt on arrangement asshown below. The splitter absorbers are containedwithin a galvanized flanged sheet steel duct. Purposedesigned bolt on type attenuators have mezz ordolby flanges to match the air handling unit frames,and can have optional inlet/outlet fairings.
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
48
Attenuator Performance 600mm long
Model Insertion Loss db
Frequency Hz 63 125 250 500 1K 2K 4K 8K
AHPHX 800/1F/390 -6 -12 -22 -31 -40 -40 -40 -38
AHPHX 1000/1F/680 -6 -13 -24 -33 -42 -42 -42 -40
AHPHX 1500/2F/390 -7 -13 -24 -33 -42 -42 -42 -32
AHPHX 1700/2F/680 -6 -12 -22 -31 -40 -40 -40 -38
AHPHX 1800/3F/390 -6 -12 -24 -33 -42 -42 -42 -30
AHPHX 2000/3F/680 -7 -13 -24 -33 -42 -42 -42 -32
AHPHX 2100/4F/390 -7 -12 -24 -32 -40 -40 -40 -30
AHPHX 2300/4F/680 -7 -12 -24 -32 -40 -40 -40 -30
Attenuator Performance 900mm long
Model Insertion Loss db
Frequency Hz 63 125 250 500 1K 2K 4K 8K
AHPHX 800/1F/390 -8 -15 -26 -44 -48 -47 -47 -45
AHPHX 1000/1F/680 -8 -16 -27 -45 -49 -49 -48 -47
AHPHX 1500/2F/390 -8 -17 -28 -46 -49 -49 -49 -48
AHPHX 1700/2F/680 -8 -15 -26 -45 -49 -48 -48 -47
AHPHX 1800/3F/390 -8 -16 -27 -45 -49 -49 -48 -47
AHPHX 2000/3F/680 -9 -18 -29 -48 -52 -51 -51 -49
AHPHX 2100/4F/390 -9 -18 -30 -48 -52 -52 -52 -50
AHPHX 2300/4F/680 -9 -18 -30 -48 -52 -52 -52 -50
Attenuator Performance 1200mm long
Model Insertion Loss db
Frequency Hz 63 125 250 500 1K 2K 4K 8K
AHPHX 800/1F/390 -10 -20 -35 -50 -50 -51 -51 -50
AHPHX 1000/1F/680 -10 -19 -34 -49 -48 -50 -50 -49
AHPHX 1500/2F/390 -10 -20 -35 -50 -50 -51 -51 -50
AHPHX 1700/2F/680 -9 -18 -33 -48 -48 -49 -49 -48
AHPHX 2000/3F/390 -10 -19 -34 -49 -48 -50 -50 -49
AHPHX 1900/3F/680 -10 -20 -35 -50 -50 -51 -51 -50
AHPHX 2100/4F/390 -10 -21 -35 -51 -52 -52 -51 -50
AHPHX 2300/4F/680 -10 -21 -35 -51 -52 -52 -51 -50
Attenuator Performance 1500mm long
Model Insertion Loss db
Frequency Hz 63 125 250 500 1K 2K 4K 8K
AHPHX 800/1F/390 -14 -26 -44 -53 -53 -53 -53 -50
AHPHX 1000/1F/680 -14 -25 -42 -51 -51 -51 -51 -48
AHPHX 1500/2F/390 -14 -26 -44 -53 -53 -53 -53 -50
AHPHX 1700/2F/680 -14 -23 -40 -50 -50 -50 -50 -47
AHPHX 1800/3F/390 -14 -26 -43 -52 -52 -52 -52 -49
AHPHX 2000/3F/680 -14 -26 -43 -52 -52 -52 -52 -49
AHPHX 2100/4F/390 -14 -26 -44 -53 -53 -53 -53 -50
AHPHX 2300/4F/680 -14 -26 -44 -53 -53 -53 -53 -50
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
49
Attenuator Performance 1800mm long
Model Insertion Loss db
Frequency Hz 63 125 250 500 1K 2K 4K 8K
AHPHX 800/1F/390 -16 -30 -52 -53 -53 -54 -54 -52
AHPHX 1000/1F/680 -16 -29 -49 -50 -50 -51 -51 -49
AHPHX 1500/2F/390 -16 -30 -52 -53 -53 -54 -54 -52
AHPHX 1700/2F/680 -16 -28 -48 -49 -49 -49 -49 -48
AHPHX 1800/3F/390 -16 -30 -52 -53 -53 -54 -54 -52
AHPHX 2000/3F/680 -16 -30 -52 -52 -53 -54 -54 -52
AHPHX 2100/4F/390 -16 -31 -53 -53 -53 -54 -54 -52
AHPHX 2300/4F/680 -16 -31 -53 -53 -53 -54 -54 -52
AHPHX REF W H L WEIGHT (Kg)
AHPHX 800/1F/390 890mm 675mm 600mm 44AHPHX 1000/1F/680 1090mm 675mm 600mm 53AHPHX 1500/2F/690 1540mm 675mm 600mm 70AHPHX 1700/2F/680 1740mm 790mm 600mm 97AHPHX 1800/3F/390 1740mm 870mm 600mm 85AHPHX 2000/3F/680 2040mm 870mm 600mm 108AHPHX 2100/4F/390 2040mm 870mm 600mm 108AHPHX 2300/4F/680 2780mm 870mm 600mm 144
AHPHX 800/1F/390 890mm 675mm 900mm 66AHPHX 1000/1F/680 1090mm 675mm 900mm 80AHPHX 1500/2F/690 1540mm 675mm 900mm 105AHPHX 1700/2F/680 1740mm 790mm 900mm 145AHPHX 1800/3F/390 1740mm 870mm 900mm 127AHPHX 2000/3F/680 2040mm 870mm 900mm 162AHPHX 2100/4F/390 2040mm 870mm 900mm 162AHPHX 2300/4F/680 2780mm 870mm 900mm 216
AHPHX 800/1F/390 890mm 675mm 1200mm 88AHPHX 1000/1F/680 1090mm 675mm 1200mm 106AHPHX 1500/2F/690 1540mm 675mm 1200mm 140AHPHX 1700/2F/680 1740mm 790mm 1200mm 194AHPHX 1800/3F/390 1740mm 870mm 1200mm 170AHPHX 2000/3F/680 2040mm 870mm 1200mm 216AHPHX 2100/4F/390 2040mm 870mm 1200mm 216AHPHX 2300/4F/680 2780mm 870mm 1200mm 288
AHPHX 800/1F/390 890mm 675mm 1500mm 110AHPHX 1000/1F/680 1090mm 675mm 1500mm 132AHPHX 1500/2F/690 1540mm 675mm 1500mm 175AHPHX 1700/2F/680 1740mm 790mm 1500mm 242AHPHX 1800/3F/390 1740mm 870mm 1500mm 212AHPHX 2000/3F/680 2040mm 870mm 1500mm 270AHPHX 2100/4F/390 2040mm 870mm 1500mm 270AHPHX 2300/4F/680 2780mm 870mm 1500mm 360
AHPHX 800/1F/390 890mm 675mm 1800mm 132AHPHX 1000/1F/680 1090mm 675mm 1800mm 159AHPHX 1500/2F/690 1540mm 675mm 1800mm 210AHPHX 1700/2F/680 1740mm 790mm 1800mm 291AHPHX 1800/3F/390 1740mm 870mm 1800mm 255AHPHX 2000/3F/680 2040mm 870mm 1800mm 324AHPHX 2100/4F/390 2040mm 870mm 1800mm 324AHPHX 2300/4F/680 2780mm 870mm 1800mm 432
Attenuator Dimensions and Weights...
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
50
Acoustic Louvre…As an option to attenuators or attenuator cowls onthe air intake and discharge of external AHPHX airhandling units, acoustic louvres can be used as analternative method of reducing the atmosphericside air noise. Four different depths are availablewith the noise reduction, dimensions and weightsas shown on pages 51 and 52.
Acoustic louvres have four depths, offering adifferent insertion loss for each depth. The chart onpage 51 gives the noise reduction for each depth300mm, 400mm, 500mm, 600mm.
External AHPHX compact with inlet and exhaust acoustic louvres on a Type 4 configuration unit (Fig 1).
External AHPHX compact with inlet and exhaust acoustic louvres. Also supply and return air integralattenuators on a Type 1 configuration unit (Fig 2).
External AHPHX compact with inlet and exhaust acoustic louvres. Also supply and return air integralattenuators on a Type 3 configuration unit (Fig 3).
Figure 1
Figure 2
Figure 3
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
51
AHPHX REF WEIGHT (Kg) W D H
AHPHX 800/390/1F/30-25 20.1 890 690 300mmAHPHX 800/390/1F/30-25 26.9 890 690 400mmAHPHX 800/390/1F/30-25 33.5 890 690 500mmAHPHX 800/390/1F/30-25 40.2 890 690 600mmAHPHX 800/390/1F/50-50 20 900 675 300mmAHPHX 800/390/1F/50-50 26.6 900 675 400mmAHPHX 800/390/1F/50-50 33.3 900 675 500mmAHPHX 800/390/1F/50-50 40 900 675 600mm
Dimensions & Weights
HE
IGH
T
SIDE VIEW
WID
TH
PLAN VIEW
WIDTH
AIRWAY
AIRWAY
DEPTH
FRONT VIEW
Frequency Hz 63 125 250 500 1K 2K 4K 8K
Insertion Loss db 300mm -4 -5 -7 -10 -16 -20 -20 -14
Insertion Loss db 400mm -4 -6 -8 -12 -18 -21 -21 -15
Insertion Loss db 500mm -5 -8 -10 -14 -21 -23 -23 -16
Insertion Loss db 600mm -5 -9 -11 -16 -24 -26 -26 -18
Acoustic Louvre Performance
Acoustic Louvre Performance, Dimensions and Weights...
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
52
AHPHX REF WEIGHT (Kg) W D H
AHPHX 1000/680/1F/30-25 24.8 1090 690 300mmAHPHX 1000/680/1F/30-25 33 1090 690 400mmAHPHX 1000/680/1F/30-25 41.3 1090 690 500mmAHPHX 1000/680/1F/30-25 49.6 1090 690 600mmAHPHX 1000/680/1F/50-50 24.7 1100 675 300mmAHPHX 1000/680/1F/50-50 32.9 1100 675 400mmAHPHX 1000/680/1F/50-50 41.2 1100 675 500mmAHPHX 1000/680/1F/50-50 49.4 1100 675 600mm
AHPHX 1500/390/2F/30-25 38.1 1540 690 300mmAHPHX 1500/390/2F/30-25 50.8 1540 690 400mmAHPHX 1500/390/2F/30-25 63.5 1540 690 500mmAHPHX 1500/390/2F/30-25 76.2 1540 690 600mmAHPHX 1500/390/2F/50-50 38.2 1550 675 300mmAHPHX 1500/390/2F/50-50 50.9 1550 675 400mmAHPHX 1500/390/2F/50-50 63.6 1550 675 500mmAHPHX 1500/390/2F/50-50 76.4 1550 675 600mm
AHPHX 1700/680/2F/30-25 51.7 1740 790 300mmAHPHX 1700/680/2F/30-25 68.9 1740 790 400mmAHPHX 1700/680/2F/30-25 86.1 1740 790 500mmAHPHX 1700/680/2F/30-25 103.4 1740 790 600mmAHPHX 1700/680/2F/50-50 49.80 1750 775 300mmAHPHX 1700/680/2F/50-50 66.4 1750 775 400mmAHPHX 1700/680/2F/50-50 83.0 1750 775 500mmAHPHX 1700/680/2F/50-50 99.6 1750 775 600mm
AHPHX 1800/390/3F/30-25 54 1740 870 300mmAHPHX 1800/390/3F/30-25 72 1740 870 400mmAHPHX 1800/390/3F/30-25 90 1740 870 500mmAHPHX 1800/390/3F/30-25 1080 1740 870 600mmAHPHX 1800/390/3F/50-50 56.5 1750 900 300mmAHPHX 1800/390/3F/50-50 75.3 1750 900 400mmAHPHX 1800/390/3F/50-50 94.1 1750 900 500mmAHPHX 1800/390/3F/50-50 113 1750 900 600mm
AHPHX 2000/680/3F/30-25 63.6 2040 870 300mmAHPHX 2000/680/3F/30-25 84.8 2040 870 400mmAHPHX 2000/680/3F/30-25 106 2040 870 500mmAHPHX 2000/680/3F/30-25 127.2 2040 870 600mmAHPHX 2000/680/3F/50-50 66.5 2050 900 300mmAHPHX 2000/680/3F/50-50 88.7 2050 900 400mmAHPHX 2000/680/3F/50-50 110.8 2050 900 500mmAHPHX 2000/680/3F/50-50 133 2050 900 600mm
AHPHX 2100/390/4F/30-25 60.5 1940 870 300mmAHPHX 2100/390/4F/30-25 80.7 1940 870 400mmAHPHX 2100/390/4F/30-25 100.8 1940 870 500mmAHPHX 2100/390/4F/30-25 121 1940 870 600mmAHPHX 2100/390/4F/50-50 62.8 1950 900 300mmAHPHX 2100/390/4F/50-50 83.7 1950 900 400mmAHPHX 2100/390/4F/50-50 104.6 1950 900 500mmAHPHX 2100/390/4F/50-50 125.6 1950 900 600mm
AHPHX 2300/680/4F/30-25 138.4 2780 870 300mmAHPHX 2300/680/4F/30-25 185.5 2780 870 400mmAHPHX 2300/680/4F/30-25 230.6 2780 870 500mmAHPHX 2300/680/4F/30-25 276.8 2780 870 600mmAHPHX 2300/680/4F/50-50 144.2 2800 900 300mmAHPHX 2300/680/4F/50-50 192.2 2800 900 400mmAHPHX 2300/680/4F/50-50 240.3 2800 900 500mmAHPHX 2300/680/4F/50-50 288.4 2800 900 600mm
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
53
1262
Acoustic Testing LaboratoryCollege of Science & Technology
AHTWCompactHeat Recovery Air Handling Unit
BIM & REVIT Engineering Solutions
AIR
HA
ND
LER
S LT
D
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
54
PVHRU Max QuietPackaged Void HeatReclaim Unit
Envirofresh 73 Quiet
Benefits
• Meets TM52 for Schools• Meets BB93 Feb 2015• Renewable Energy Source• BMS Controls Installed in Unit• Factory Pre-Commissioned• Heating and Cooling from One Source• 50% Less CO2 Production than a Gas Boiler• Low Energy Consumption• Reduced Site Installation Cost• No External Condensing Units, Pipework or wiring• Low Noise Emissions with Silenced Compressors• High Specification UKAS Certified Low Breakout Casework• No Loss of Heating Capacity at Low Temperatures• Room Heating and Cooling available at Reduced Air Volumes• Tempered Air Supply without Defrosting• No Increase in Footprint over Standard AHUs• More Pleasant External Appearance than Condensing Unit or Chiller Installations
Low Energy, Air Source Heat Pump System,Silenced with Acoustic Treatment asused in Hundreds of Projects
Envirofresh 73 Quiet
OutPerforms
Benefits• Low profile from 300mm deep.
• Up to 90% Heat Recovery efficiency.
• Outperforms ErP 2018.
• Heating Coil options. LPHW or electric.
• Cooling coil options chilled water or DX.
• Heat pump coil options.
• TM52 compliant.
• On board controls available.
• Filtration to F7.
• Summer by pass facility.
• High sound reduction casework tested to BS EN ISO 10140-2(2010) UKAS certified.
• High performance backward curved centrifugal fans with lowspecific fan power.
• Meets BB101 and BB93 Feb 2015.
• Bottom access.
From
300
mm Deep
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
55
Benefits• Low SFP• Tonal noise control• Matching attenuators• Weatherproof options• Low noise breakout• Meets BB 93 Feb 2015• High sound reduction casework tested to BS EN ISO 10140-2 (2010)• Backward curved, low speed, EC fans• Attenuators/cowls and acoustic louvre options• Auto change over control system for duty and stand by operation on VTI units• Suspension brackets with vibration control available• Fan motor isolators fitted as standard• Variable volume control system - Vari Vol• Speed regulation 0>10 Volts• Bottom and side access
Series VSI/VTI Single & Twin LowProfile Quiet ExtractFan Units
Single Fan Series VSI
Twin Fan Series VTI
PVU QuietPackaged Void Unit
low Profile Unit
Benefits• Ultra low profile from 300mm• Option bag filters to F7 grade• Optional mixing box• Matching attenuators• Tonal noise control• Speed regulation 0>10 Volts• Heating coils - LPHW and electric• Bottom and side access• Fully integrated packaged controls• Fan motor isolator fitted as standard• High airflow / pressure performance• Low specific fan power E.C. fans backward curved• Constant pressure ‘Vari-Vol’ variable volume system available• High sound reduction casework tested to BS EN ISO 10140-2(2010)• Suspension brackets with vibration control available• Cooling coils chilled water/DX/heatpump available
Acoustic Testing LaboratoryCollege of Science & Technology
Acoustic Testing LaboratoryCollege of Science & Technology
AHPH
XCo
mpa
ct H
eat Re
cove
ry Air H
andling Unit
Air Handlers Northern Ltd.Alfred Procter HouseBute Street, SalfordManchester M50 1DU
Tel: 0161 745 8888Fax: 0161 743 9190Email: [email protected]: www.airhandlers.net
The company reserves the right to make any variation in technical specification to the equipment described, or to withdraw or replace productswithout prior notification or public announcement. Air Handlers Northern Ltd is continually developing and improving its products. All description,illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are
subject to the company’s General Conditions of Sale, a copy is available on request.
• Single Cased Extract Unit VSI• Twin Fan Extract Units VTI and ITU• Classvent Units• Packaged Void Units PVU• Vertical Air Handling Units• AH Series Modular AHU’s• IDG Series Indirect Gas Fired AHU’s• DG Series Direct Gas Fired AHU’s• HOSP Health Care Specification Hygiene AHU’s• AHW Welded Frame and Stainless Units• TWHR Heat Reclaim AHU’s containing Thermal Wheels• AHR Heat Recovery AHU’s containing Recuperators• Freshcool Cooling only Packaged Units• Envirofresh Packaged Heat Pump Units• Attenuators and Anti-vibration Mounts• Acoustic Enclosures and Screens• Flat Pack Build and Refurbishment• Planned Maintenance and Site Repairs• Airflow/Acoustic/Leakage Performance Testing Facility• Skidpak Fully Packaged Units• Auto Cad, BIM and REVIT
Product Range... Other AssociatedLiterature...
• Sound Advice for VentilationPlant in Schools.By David Pinchbeck
• Air Handling Units AcousticInsulation Performance testReport
• BSRIA EnvirofreshPerformance Test Report
• EcoDesign Directive 2016/18
• AUTO CAD 3D
• BIM
• REVIT