General Wiring Notes (figures A, B and C) 2 Zone Interlock Wiring (figure 1) 3 Digitrip Alarm Wiring (figure 2) 4 Ground Fault Residual 3-Phase 4-Wire (figure 3) 5 Source Ground Fault (figure 4) 6 Zero Sequence Ground Fault (figure 5) 7 Maintenance Mode Wiring (figure 6) 8 INCOM Communications Module (ICAM) (figure 7) 9 MODBUS Communications Module (MCAM) (figure 8) 10 PROFIBUS DP Communications Module (PCAM) (figure 9) 11 Communications Control (figure 10) 12 Undervoltage Release (figure 11) 13 Circuit Breaker Control - Type NF (figure 12) 14 Circuit Breaker Control - Type RF (figure 13) 15 Series NRX NF Mounted Breaker (with external PT Module) (figure 14) 16 Master Connection NF (figure 15) 17-18 Master Connection RF (figure 16) 19-21 Description Page effective November 2011 Series NRX Technical Data TD01301014E Series NRX Circuit Breaker Wiring Diagrams Contents Instructions Apply To: Series NRX, Type NF Frame ANSI, UL1066, UL489 / IEC, IZMX16, IZM91 Series NRX, Type RF Frame IEC, IZMX40

Upload: others

Post on 07-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

General Wiring Notes (figures A, B and C) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Zone Interlock Wiring (figure 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Digitrip Alarm Wiring (figure 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Ground Fault Residual 3-Phase 4-Wire (figure 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Source Ground Fault (figure 4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Zero Sequence Ground Fault (figure 5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Maintenance Mode Wiring (figure 6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8INCOM Communications Module (ICAM) (figure 7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9MODBUS Communications Module (MCAM) (figure 8) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10PROFIBUS DP Communications Module (PCAM) (figure 9) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Communications Control (figure 10) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Undervoltage Release (figure 11) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Circuit Breaker Control - Type NF (figure 12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Circuit Breaker Control - Type RF (figure 13) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Series NRX NF Mounted Breaker (with external PT Module) (figure 14) . . . . . . . . . . . . . . . . . . . . . . . . . 16Master Connection NF (figure 15) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-18Master Connection RF (figure 16) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-21

Description Page

effective November 2011

Series NRXTechnical Data TD01301014E

Series NRX Circuit Breaker Wiring Diagrams

Contents

Instructions Apply To:

1600 NRX SUB-TITLE IMAGE (12/15/2010)

Series NRX, Type NF Frame ANSI, UL1066, UL489 / IEC, IZMX16, IZM91

Series NRX, Type RF Frame IEC, IZMX40

4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010)

Page 2: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

2 EATON CORPORATION www.eaton.com

General Wiring Notes1 . Each contact block on the Secondary Terminal Block consists of two

contacts (Figure A) . A possible 27 terminal blocks will provide 54 contact points for the type NF frame . A possible 46 terminal blocks will provide 92 contact points for the type RF frame .

FixedTerminal Block

DrawoutTerminal Block

Figure A. Secondary Terminal Blocks

2 . Drawout circuit breakers use Style 66B2508G01 contact blocks that mount onto a metal DIN rail .

3 . Fixed mounted circuit breakers use Style 66B2510G01 contact blocks that mount onto an insulated support frame . The customer tension connectors are at a 45° angle .

4 . Customer wiring is done using a tension clamp termination on each contact .

5 . Contact blocks are individually mounted and hence contact posi-tions may be empty depending on accessories and options ordered .

6 . For drawout configurations, a cross connector can be used to tie adjacent contacts together . It is Weidmuller Style ZQV4 (300V rated only) .

7 . The tension clamp terminals will support solid or flexible conductors, #12/4mm2 through #24/2 .5mm2 AWG wire and are UL/CSA rated for 600V, 10A .

8 . The recommended wire strip length is 10 mm ( .394”) .

9 . The tension clamp terminals also support finely stranded conduc-tors with wire-end ferrules and plastic collars DIN 46228/4, rated connection .

10 . The two-point black plugs house two female crimp contacts (Wei-dmuller crimp Style 73477FCB01), with the odd assigned numbers having the coded rib feature on the black plug (Figure B) . Note that the connector plug must be oriented as shown in Figure B before making the connection.

11 . For secondary contacts, odd numbers should be treated as positive voltage for any accessory . This will not apply for AC ratings .

12 . Reference tools for secondary contacts: Crimp tool connector – 1003300000; crimp contact wire release front black housing – 1964560000; release of black housing from secondary structure – 1964550000 .

13 . Reference tool for removing leads from secondary contact connec-tor plug – 65A2818H01 Extraction Tool (Figure C) .

Type of connection Tension clamp connection

Blade size 0.6 x 3.5 mm

Clamping range, rated connection, max. 4 mm2

Conductor cross-section, solid, min 0.5 mm2

Conductor cross-section, flexible, max. 4 mm2

Conductor cross-section, flexible plus plastic collar DIN 46228/1, rated connection, min.

0.5 mm2

Cross-section for connected conductor, finely stranded with wire-end ferrules and plastic collars DIN 46228/4, rated connection, min.

0.5 mm2

Conductor connection cross-section AWG, min. AWG 30

Stripping length 10 mm

Connection direction top

Clamping range, rated connection, min. 0.05 mm2

Gauge to IEC 60947-1 A3

Conductor cross-section, solid, max. 4 mm2

Conductor cross-section, flexible, min. 0.5 mm2

Conductor cross-section, flexible plus plastic collar DIN 46228/1, rated connection, max.

2.5 mm2

Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max.

2.5 mm2

Conductor connection cross-section AWG, max. AWG 12

Table 1. Customer Wiring Details

Figure B. Weidmuller Plug and Crimp Contact

Figure C. Extraction Tool in Use

Series NRX Circuit Breaker Wiring Diagrams Technical Data TD01301014E Effective November 2011

Secondary Lead

Connector Plug

Terminal Extraction Tool

Page 3: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

3EATON CORPORATION www.eaton.com

Technical Data TD01301014E Effective November 2011

Series NRX Circuit Breaker Wiring DiagramsFi

gu

re 1

. Zo

ne

Inte

rlo

ck W

irin

g

No

tes

1 . Tw

iste

d to

geth

er A

WG

#14

to

#20

copp

er w

ire . R

oute

Zon

e in

terlo

ck w

iring

sep

arat

e fr

om p

ower

co

nduc

tors

. DO

NO

T G

RO

UN

D a

ny Z

one

inte

rlock

wiri

ng .

2 . T

he m

axim

um d

ista

nce

betw

een

two

fart

hest

bre

aker

s on

diff

eren

t zo

nes

(fro

m t

he Z

O

dow

nstr

eam

to

the

ZI u

pstr

eam

ter

min

als)

is 2

50 fe

et (7

5m) .

3 . A

max

imum

of

20 b

reak

ers

may

be

cont

aine

d in

par

alle

l in

one

zone

.

4 . P

rovi

de a

sel

f in

terlo

ckin

g ju

mpe

r (o

n Zo

ne 3

), if

coor

dina

tion

is d

esire

d w

ith o

ther

dow

nstr

eam

br

eake

rs n

ot p

rovi

ding

the

zon

e in

terlo

ck fe

atur

e .

Page 4: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

4 EATON CORPORATION www.eaton.com

Series NRX Circuit Breaker Wiring Diagrams Technical Data TD01301014E Effective November 2011

Figure 2. Digitrip Alarm Wiring

Notes

1 . For the Digitrip 520M product, Alarm 1 (ALM1) is for Remote Circuit Breaker Problem Alarm on CAT # N5MLSIG or for Maintenance Mode Active on CAT # N5MRLSIA . Contact rating 1A @ 120 VAC and 1A @ 24VDC .

For the Digitrip 1150 product, Alarm 1 (ALM1) is a programmable contact that can be assigned for a variety of trip or alarm conditions . . Contact rating 1A @ 120 VAC and 1A @ 24VDC .

2 . For the Digitrip 520M product, Alarm 2 (ALM2) is for Hi Load Alarm Function on CAT # N5MLSI or # N5MRLSI, or for use with Ground Alarm CAT # N5MRLSIG . Contact rating 1A @ 240 VAC and 1A @ 24VDC .

For the Digitrip 1150 product, Alarm 2 (ALM2) is a programmable contact that can be assigned for a variety of trip or alarm conditions . . Contact rating 1A @ 120 VAC and 1A @ 24VDC .

3 . If a Communication Module is used, see Figures 7, 8 or 9 for different wiring . A Communication Module will require 24VDC power which in turn provides isolated power to the Digitrip in the circuit breaker . If a Communication Module is not used, and if auxiliary voltage is desired for Alarms or display purposes, the trip unit should be fed from a separate galvanically isolated 24 volt dc supply .

� �

Series NRX Circuit Breaker

�±10%

Page 5: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

5EATON CORPORATION www.eaton.com

Technical Data TD01301014EEffective November 2011

Series NRX Circuit Breaker Wiring Diagrams

Figure 3. Ground Fault Residual 3-Phase 4-Wire

Notes

1 . Sensor NFNCTKIT (IZMX-CT16-N) is customer wired to sense Neutral currents . This is required for 3 phase, 4 wire Residual Ground Fault (applicable for Trip Units having G protection) .

2 . Required Sensor Series NRX Frame (IZMX Type Coding) NF NFNCTKIT (IZMX-CT16-N) RF RFNCTKIT (IZMX-CT40-N) NF or RF NFGFSKIT (IZMX-EFS)

Digitrip

Series NRX Circuit Breaker

� �

Page 6: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

6 EATON CORPORATION www.eaton.com

Series NRX Circuit Breaker Wiring Diagrams Technical Data TD01301014E Effective November 2011

Figure 4. Source Ground Fault Sensing

Notes

1 . Sensor NFGFSKIT (IZMX-EFS) is used to sense and detect Ground Fault Currents .

2 . Apply jumper for this mode of sensing for trip units having Ground or Ground Alarm Functionality .

Digitrip

Series NRX Circuit Breaker

�ExternalSensor

Page 7: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

7EATON CORPORATION www.eaton.com

Technical Data TD01301014E Effective November 2011

Series NRX Circuit Breaker Wiring Diagrams

Figure 5. Zero Sequence Ground Fault Sensing

Notes

1 . Sensor NFGFSKIT (IZMX-EFS) is used to sense and detect Ground Fault Currents of 3-wire or 4-wire .

2 . Apply jumper for this mode of sensing for trip units having Ground or Ground Alarm Functionality .

Series NRX Circuit Breaker

Digitrip

Page 8: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

8 EATON CORPORATION www.eaton.com

Series NRX Circuit Breaker Wiring Diagrams Technical Data TD01301014E Effective November 2011

Fig

ure

6. M

ain

ten

ance

Mo

de

Wir

ing

No

tes

1 . T

he D

igitr

ip 5

20M

Cat

# N

5MR

LSI(G

) can

loca

lly b

e pl

aced

in M

aint

enan

ce M

ode

via

a tw

o po

sitio

n sw

itch

loca

ted

on t

he Tr

ip U

nit .

The

Dig

itrip

115

0 C

at #

N11

RLS

I(G) c

an b

e lo

cally

pro

gram

med

to

plac

e th

e D

igitr

ip in

Mai

nten

ance

Mod

e . T

he f

unct

ion

can

be a

rmed

via

a r

emot

e sw

itch

as s

how

n . In

ad

ditio

n, t

he f

unct

ion

can

be a

ctiv

ated

via

Com

mun

icat

ions

Mod

ules

. A b

lue

LED

on

the

Dig

itrip

ver

ifies

the

Dig

itrip

is in

Mai

nten

ance

Mod

e . 2 .

The

rec

omm

ende

d se

lect

or s

witc

h fo

r th

is lo

w v

olta

ge a

pplic

atio

n is

Eat

on p

art

num

ber

1025

0T13

3-2E

whi

ch in

clud

es a

con

tact

blo

ck r

ated

for

logi

c le

vel a

nd c

orro

sive

use

.

3 . T

he m

axim

um le

ngth

of

this

wiri

ng t

o re

mot

e A

rm S

witc

h (o

r al

tern

ate

rela

y co

ntac

t) is

3 m

eter

s (9

.78

feet

) . U

se #

20

AW

G w

ire o

r la

rger

.

4 . A

rem

ote

Sta

ck L

ight

Ann

unci

ator

Pan

el o

r ot

her

rem

ote

indi

catio

n de

vice

can

be

conn

ecte

d to

ver

ify t

hat

Dig

itrip

is in

Mai

nten

ance

Mod

e .

5 . R

elay

in D

igitr

ip m

akes

whe

n in

Mai

nten

ance

Mod

e . C

onta

ct is

rat

ed 1

A @

120

VAC

.

6 . T

he D

igitr

ip c

an a

lso

be p

lace

d re

mot

ely

in it

s M

aint

enan

ce M

ode

via

a G

ener

al P

urpo

se R

elay

(ice

cub

e ty

pe w

ith lo

gic

leve

l con

tact

s), a

ctiv

ated

by

a re

mot

e co

ntro

l sw

itch .

A r

ecom

men

ded

type

is ID

EC

Rel

ay R

Y22

. Cho

ose

volta

ge a

s de

sire

d .

7 . I

f C

omm

unic

atio

n M

odul

e is

use

d, s

ee F

igur

es 7

or

8 fo

r di

ffere

nt w

iring

. Th

e C

omm

unic

atio

n M

odul

e w

ill r

equi

re 2

4VD

C p

ower

and

will

pro

vide

is

olat

ed p

ower

to

the

Dig

itrip

in t

he c

ircui

t br

eake

r . If

a C

omm

unic

atio

n M

odul

e is

not

use

d, t

he D

igitr

ip t

hat

requ

ires

auxi

liary

vol

tage

for A

larm

s sh

ould

be

fed

from

a g

alva

nica

lly is

olat

ed 2

4 vo

lt dc

sup

ply .

� ��

Ser

ies

NR

X C

ircu

it B

reak

erS

erie

s N

RX

Cir

cuit

Bre

aker

Alt

ern

ate

Cu

sto

mer

Wir

ing

(p

arti

al)

Mai

nte

nan

ce M

od

e W

irin

g

Page 9: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

9EATON CORPORATION www.eaton.com

Technical Data TD01301014EEffective November 2011

Series NRX Circuit Breaker Wiring Diagrams

Figure 7. INCOM Communications Module (ICAM)

Notes

1 . The Series NRX Communication Module is a separate device that snaps into the Din Rail starting at locations 19 through 26 . (Removal of the four contact blocks is required .)

2 . The Communications Module voltage requirement is 24VDC ±10% and should be sourced from a high quality supply (6 watts is the burden of the CAM) .

3 . INCOM communication cable is a two conductor with shield type wire in “daisy chain” configuration . The recommended cable (Belden “Blue Hose” # 9643 or equivalent) has a twisted-pair of wires (# 20 AWG stranded 7 x 28 conductors with PVC insulation) having an aluminum/mylar foil shield with drain wire . The Maximum system capacity is 10,000 feet of communications cable and 1000 devices on the INCOM network . Make sure that the twisted-pair wire is recommended for INCOM network use . Use shielded twisted-pair wire to connect each slave to the INCOM network, daisy-chain style . The polarity of the twisted-pair is not important . Ground the shield at the host computer (device) .

4 . Set the jumper on the module to enable or disable the communications control as desired .

5 . When the Communications Module is employed and Source Ground or Zero Sequence Ground Sensing method is required, the Ground Fault function is enabled by this jumper .

6 . Connectors are UL/CSA rated 300V, VDE rated 250V . The recommended connector is Weidmuller # BL 3 .5/90/5 BK, oriented for 90° lead exit, however other lead orientations are possible . Wire guage # 18 AWG/0 .82mm2 .

7 . The final device in the daisy-chain configuration must have a 100 ohm termination resistor installed across terminals #1 and #2 on TB2 .

���

Digitrip 520M/1150

Page 10: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

10 EATON CORPORATION www.eaton.com

Series NRX Circuit Breaker Wiring Diagrams Technical Data TD01301014E Effective November 2011

Figure 8. MODBUS Communications Module (MCAM)

Notes

1 . The Series NRX Communication Module is a separate device that snaps into the Din Rail starting at locations 19 through 26 . (Removal of the four contact blocks is required .)

2 . The Communications Module voltage requirement is 24VDC ±10% and should be sourced from a high quality supply (6 watts is the burden of the CAM) .

3 . Modbus communication cable is a three conductor with shield type wire in “daisy chain” configuration . The recommended cable has a twisted-pair of wires (# 24 AWG stranded 7 x 32 conductors with PVC insulation) having an aluminum/mylar foil shield with drain wire . The Maximum system capacity is 4,000 feet of communications cable and 32 unit loads on the Modbus RTU network . Make sure that the twisted-pair wire is recommended for Modbus RTU network use . Use shielded twisted-pair wire to connect each slave to the Modbus RTU network, daisy-chain style . The polarity of the twisted-pair is not important . Ground the shield at the host computer (device) .

4 . Set the jumper on the module to enable or disable the communications control as desired .

5 . When the Communications Module is employed and Source Ground or Zero Sequence Ground Sensing method is required, the Ground Fault function is enabled by this jumper .

6 . Connectors are UL/CSA rated 300V, VDE rated 250V . The recommended connector is Weidmuller # BL 3 .5/90/5 BK, oriented for 90° lead exit, however other lead orientations are possible . Wire gauge # 18 AWG/0 .82mm2 .

7 . The final device in the daisy-chain configuration must have a 121 ohm termination resistor installed across terminals #1 and #2 on TB2 .

Digitrip 520M/1150

Series NRX Circuit Breaker

��

Page 11: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

Figure 9. PROFIBUS Communication Module (PCAM)

Notes

1 . The Series NRX Communication Module is a separate device that snaps into Din Rail starting at location 19 through 26 . (Removal of the four contact blocks is required .)2 . Communication Module voltage requirement is 24 VDC ± 10% and should be sourced from reliable service (6 watts is

the burden of the CAM) .3 . Profibus DP communication cable uses a five conductor flexible cable with shield type wire in “daisy chain”

configuration . The maximum cable lenght depends on Baud rate and can link up to 32 unit loads on the network . See Profibus guide line Order number 2 .142 .

Ground the shield at host computer (device)4 . Set jumper on the module to enable or disable communications control as desired .5 . When the Communications Module is employed and Source Ground or Zero Sequence Ground Sensing method is

required, this Ground Fault function is enabled by this jumper .6 Connector TB1 is UL/CSA rated 300V, VDE rated 250V . Recommended: Weidmuller (BL 3 .5/90/5 BK) Orientation: 90°

lead exit, but other lead orientations are possible . Wire gauge: #18 AWG / 0 .82mm2 .7 . The final device on each end of the network in the daisy chain configuration must have termination resistors installed as

shown on TB2 .

Series NRXCircuitBreaker

CommunicationsModule

PROFIBUS Communications Module

Digitrip 520M/1150

1

5

3

7

4

2

6

TB2-6 TB2-3 TB2-8

390 ohm

7

390 ohm

7

220 ohm

TB2-5TB 29 pinD Sub

Female

53 4 68

Dat

a B

Dat

a A D

GN

D

CN

TR-P

/RTS VP

SHIE

LD(S

HEL

L)SC

REW

11EATON CORPORATION www.eaton.com

Technical Data TD01301014EEffective November 2011

Series NRX Circuit Breaker Wiring Diagrams

Page 12: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

Figure 10. Communications Control (SR and ST Wiring)

Notes

1 . Spring Release and Shunt Trip wiring as shown for optional communication close or open capability .

2 . Choose Spring Release coil voltage rating as desired if communications is required .

3 . Choose Shunt Trip rating to be the same as Spring Release rating if communication is required .

4 . Control Power rating must match ST and SR coil rating .

5 . Close duration is two seconds on communication activation .

6 . Communication control jumper must be in the enable position for communications opening or closing .

7 . Spring Release terminals are 35 & 36 for NF Frame only . For RF Frame breakers, the terminals are 49 & 50 .

Series NRX Circuit BreakerCommunicationsModule

����

5

6

12 EATON CORPORATION www.eaton.com

Series NRX Circuit Breaker Wiring Diagrams Technical Data TD01301014E Effective November 2011

Page 13: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

Figure 11. Undervoltage Release

Notes

1 . Treated as the positive voltage for DC ratings .

Series NRX Circuit Breaker

13EATON CORPORATION www.eaton.com

Technical Data TD01301014EEffective November 2011

Series NRX Circuit Breaker Wiring Diagrams

Page 14: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

Figure 12. Circuit Breaker Control - Type NF Frame

Legend:MOT – Motor Operator for Charging Closing SpringST – Shunt TripSR – Spring ReleaseDescription of Operation

1 . Motor is energized and runs, charges closing spring, and is cut off by switch .

2 . When spring is charged, SC closes and Green indicating light will light (if applicable) .

3 . Closing CS-C contact energizes Spring Release Coil and closes circuit breaker . Spring Release internal electronics pulse the SR coil and then provides a high impedance circuit . This provides anti-pumping .

4 . When the spring discharges its energy, the motor switch will re-energize the charging motor until the spring is charged again .

5 . To detect presence of voltage (Health Light), use Omron Red indicator LED Port # C22-L-R-120 for 120VAC application . For 230VAC application, use C22-L-R-230 . For 24VDC application, use C22-L-R-24 . Remove White (22mm diameter pilot light) Light Diffuser from assembly to give better indication of voltage present . Activate Pushbutton to trip circuit breaker . See Eaton for other voltages .

6 . For secondary contacts, odd numbers should be treated as positive for any accessory . This will not apply to AC ratings .

7 . The secondary contacts for drawout circuit breakers have been so arranged to allow for jumper stab connectors to tie common voltage together wherever possible . (For example: Terminals 36 to 38 could employ this jumper stab) .

8 . Reference Figure 15 for internal circuit breaker wiring .

��

Series NRX Circuit Breaker

14 EATON CORPORATION www.eaton.com

Series NRX Circuit Breaker Wiring Diagrams Technical Data TD01301014E Effective November 2011

Page 15: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

Figure 13. Circuit Breaker Control - Type RF Frame

Legend:MOT – Motor Operator for Charging Closing SpringST – Shunt TripSR – Spring ReleaseDescription of Operation

1 . Motor is energized and runs, charges closing spring, and is cut off by switch .

2 . When spring is charged, SC closes and Green indicating light will light (if applicable) .

3 . Closing CS-C contact energizes Spring Release Coil and closes circuit breaker . Spring Release internal electronics pulse the SR coil and then provides a high impedance circuit . This provides anti-pumping .

4 . When the spring discharges its energy, the motor switch will re-energize the charging motor until the spring is charged again .

5 . To detect presence of voltage (Health Light), use Omron Red indicator LED Port # C22-L-R-120 for 120VAC application . For 230VAC application, use C22-L-R-230 . For 24VDC application, use C22-R-24 . Remove White (22mm diameter pilot light) Light Diffuser from assembly to give better indication of voltage present . Activate Pushbutton to trip circuit breaker . See Eaton for other voltages .

6 . For secondary contacts, odd numbers should be treated as positive for any accessory . This will not apply to AC ratings .

7 . The secondary contacts for drawout circuit breakers have been so arranged to allow for jumper stab connectors to tie common voltage together wherever possible . (For example: Terminals 50 to 52 could employ this jumper stab) .

8 . Reference Figure 16 for internal circuit breaker wiring .

��

Series NRX Circuit Breaker

49 51 53

50 52

15EATON CORPORATION www.eaton.com

Technical Data TD01301014EEffective November 2011

Series NRX Circuit Breaker Wiring Diagrams

Page 16: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

Figure 14. Series NRX NF Mounted Breaker (with external PT Module)

16 EATON CORPORATION www.eaton.com

Series NRX Circuit Breaker Wiring Diagrams Technical Data TD01301014EEffective November 2011

Series NRX NF Mounted Breakers – 3 pole – 3 wireSeries NRX RF Mounted Breakers without internal PT module

LA

LB

LC

PTMODULE

BREAKER

A

0-600 L-L INPUT

B C

To additionalbreakers

SecondaryContacts

{

1 3 5

31 VB30 VA

32 VC

TP2

14

Series NRX NF Mounted Breakers – 3 pole or 4 pole – 4 wire

LA

LB

LC

PTMODULE

BREAKER

A0-600 L-L INPUT

B C

To additionalbreakers

SecondaryContacts1

N

3 5

31 VB30 VA

32 VC

TP2

14 VN

LN

(16 max)

(16 max)

Page 17: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

17EATON CORPORATION www.eaton.com

Technical Data TD01301014EEffective November 2011

Series NRX Circuit Breaker Wiring Diagrams

Figure 15. Typical breaker master connection diagram - NF

Fig

ure

15.

Ser

ies

NR

X-N

F Fr

ame

Bre

aker

Mas

ter

Co

nn

ecti

on

Dia

gra

m D

raw

ing

Nu

mb

er 6

D32

389

(co

nti

nu

ed n

ext

pag

e)

Page 18: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

18 EATON CORPORATION www.eaton.com

Series NRX Circuit Breaker Wiring Diagrams Technical Data TD01301014E Effective November 2011

Figure 15 Notes for previous page Number 6D32389 - NF Frame

ote:N :

1 . All contacts shown with circuit breaker open and discharged and control power de-energized . The OTS are shown in reset position .2 . All trip unit wires are #22 AWG—0 .34 mm2—300V .3 . All accessory wires are #18 AWG—0 .82 mm2—600V .4 . 54 contacts maximum .5 . PT module inputs for Digitrip 1150 only .6 . Connectors K15 and K16 are not always present .7 . On three-pole circuit breakers only, connector K4—1 .2 wires only are wired out to secondary contacts .8 . Odd number contacts have guide rib on black housing .9 . Zone interlock wiring shown dotted—optional jumper is standard .10 . Latch check switch can be wired either externally (option) or internally (option) to a spring release accessory . Wiring LCS internally ensures the one-shot pulse provided by the SR circuitry is made active only after the mechanism spring is charged and the latch is in its proper state .11 . For accessories having a DC rating, the odd numbers will be treated as positive voltage .12 . Reserved for spring charge SC input contact .13 . For Digitrip 520M ALM2 is an alarm used for GF (Ground fault style trip unit) . ALM1 is used for diagnostic alarm or maintenance mode active . For Digitrip 1150, these contracts can be programmed as desired .

Page 19: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

19EATON CORPORATION www.eaton.com

Technical Data TD01301014EEffective November 2011

Series NRX Circuit Breaker Wiring Diagrams

Figure 16. Typical breaker master connection diagram - RF

Fig

ure

16.

Ser

ies

NR

X-R

F Fr

ame

Bre

aker

Mas

ter

Co

nn

ecti

on

Dia

gra

m D

raw

ing

Nu

mb

er 6

D32

424

(co

nti

nu

ed n

ext

pag

e)

Page 20: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

20 EATON CORPORATION www.eaton.com

Series NRX Circuit Breaker Wiring Diagrams Technical Data TD01301014E Effective November 2011

Fig

ure

17.

Ser

ies

NR

X-R

F Fr

ame

3M

aste

r C

on

nec

tio

n D

iag

ram

Dra

win

g N

um

ber

6D

3242

4 (c

on

tin

ued

fro

m p

revi

ou

s p

age

and

no

tes

on

nex

t p

age)

Figure 17. Typical breaker master connection diagram (Cont.) - RF.

Page 21: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

21EATON CORPORATION www.eaton.com

Technical Data TD01301014EEffective November 2011

Series NRX Circuit Breaker Wiring Diagrams

Figure 16 and 17. Notes for two previous pages Number 6D32424 - RF Frame

1 . All contacts shown with circuit breaker open and discharged and control power de-energized . The OTS are shown in reset position .2 . All trip unit wires are #22 AWG—0 .34 mm2—300V .3 . All accessory wires are #18 AWG—0 .82 mm2—600V .4 . 92 contacts maximum .5 . Contacts 47 and 48 are not used on this breaker . If an internal PT Module is not provided, an external PT Module may be connected at terminals 14, 30, 31, and 32 .6 . Connectors K15 and K16 are not always present .7 . On three-pole circuit breakers only, connector K4—1 .2 wires only are wired out to secondary contacts .8 . Odd number contacts have guide rib on black housing .9 . Zone interlock wiring shown dotted—optional jumper is standard .10 . Latch check switch can be wired either externally (option) or internally (option) to a spring release accessory . Wiring LCS internally ensures the one-shot pulse provided by the SR circuitry is made active only after the mechanism spring is charged and the latch is in its proper state .11 . For accessories having a DC rating, the odd numbers will be treated as positive voltage .12 . Reserved for spring charge SC input contact .13 . For Digitrip 520M ALM2 is used for GF (ground fault style trip unit) or high load alarm (non-ground fault style trip unit) . ALM1 is used for diagnostic alarm or maintenance mode active . For Digitrip 1150, these contacts can be programed as desired .

Page 22: TD01301014E Series NRX Circuit Breaker Wiring Diagrams · 2.5 mm2 Conductor cross-section, flexible AEH plus plastic collar DIN 46228/4, rated connection, max. 2.5 mm2 Conductor connection

Eaton CorporationElectrical Group1000 Cherrington ParkwayMoon Township, PA 15108United States877-ETN-CARE (877-386-2273)Eaton .com

© 2010 Eaton CorporationAll Rights ReservedPrinted in USAPublication No . TD01301014EH05November 2011

PowerChain Management is a registered trademark of Eaton Corporation .

All other trademarks are property of their respective owners .

Series NRX Circuit Breaker Wiring Diagrams

Technical Data TD01301014E Effective November 2011