tds-4core

2
POWER CABLES CU/XLPE/SWA/PVC, BS 5467 TECHNICAL PARTICULARS 4 CORE CABLES Srl Description Unit New Baan code FX244SPSK FX244TPSK 1.00 General 1.01 Item 4 x 185 4 x 240 1.02 Voltage grade kV 0.6/1.0 0.6/1.0 1.03 Ref. standard BS 5467 BS 5467 1.04 No. of cores 4 4 1.05 Max.operating temp. ° C 90 90 1.06 Max.short circuit temp. ° C 250 250 2.00 CONDUCTOR 2.01 Material Cu Cu 2.02 Nominal area mm² 185 240 2.03 Minimum no. of wires 30 34 2.04 Shape Shaped Shaped 2.05 Compaction Yes Yes 2.06 Conductor diameter - Approx. mm N. A. N. A. 3.00 INSULATION 3.01 Material XLPE XLPE 3.02 Thickness- Average mm 1.6 1.7 3.03 Thickness- Min at any point mm 1.34 1.43 3.04 Core diameter - Approximate mm N. A. N. A. 3 05 Core Identification By Colour By Colour 3.05 Core Identification By Colour~ By Colour~ ~Colour: Red, Yellow, Blue & Black. 4.00 BEDDING 4.01 Material PVC PVC 4.02 Thickness- Nominal mm 1.4 1.6 4.03 Thickness- Min at any point mm 0.92 1.08 4.04 Dia over bedding- Approximate mm 45.6 51.3 4.05 Colour of bedding Black Black 5.00 ARMOUR 5.01 Material SWA SWA 5.02 Dia of wire- Nominal mm 2.5 2.5 5.03 Number of wires- Approximate mm 52 58 5.04 Dia over armour- Approximate mm 50.6 56.3 * In case of non availablity of 0.9 mm size armour wires we may use 1.25 mm size armour wires and in that case the number of armour wires will change. 6.00 OUTERSHEATH 6.01 Material PVC-Type 9 PVC-Type 9 6.02 Thickness- Nominal mm 2.6 2.7 6.03 Thickness- Min at any point mm 1.88 1.96 6.04 Overall dia- Approx. mm 56.0 62.0 6.05 Colour of sheath Black Black 7.00 PACKAGING (approx) 7.01 Standard Drum length (± 5%) mtr 500 250 7.02 Packing material Wooden / Steel drums with Lamiflex lagging Wooden / Steel drums with Lamiflex lagging 7.03 Approx. Size of drum (H x W) mm 2000 x 1320 1800 x 1140 Page 1 of 2

Upload: mohammed-shukkur

Post on 18-Nov-2015

8 views

Category:

Documents


1 download

DESCRIPTION

Cable Details

TRANSCRIPT

  • POWER CABLESCU/XLPE/SWA/PVC, BS 5467

    TECHNICAL PARTICULARS4 CORE CABLES

    Srl Description UnitNew Baan code FX244SPSK FX244TPSK

    1.00 General1.01 Item 4 x 185 4 x 2401.02 Voltage grade kV 0.6/1.0 0.6/1.01.03 Ref. standard BS 5467 BS 54671.04 No. of cores 4 41.05 Max.operating temp. C 90 901.06 Max.short circuit temp. C 250 2502.00 CONDUCTOR2.01 Material Cu Cu2.02 Nominal area mm 185 2402.03 Minimum no. of wires 30 342.04 Shape Shaped Shaped2.05 Compaction Yes Yes2.06 Conductor diameter - Approx. mm N. A. N. A.3.00 INSULATION3.01 Material XLPE XLPE3.02 Thickness- Average mm 1.6 1.73.03 Thickness- Min at any point mm 1.34 1.433.04 Core diameter - Approximate mm N. A. N. A.3 05 Core Identification By Colour By Colour3.05 Core Identification By Colour~ By Colour~

    ~Colour: Red, Yellow, Blue & Black.4.00 BEDDING4.01 Material PVC PVC4.02 Thickness- Nominal mm 1.4 1.64.03 Thickness- Min at any point mm 0.92 1.084.04 Dia over bedding- Approximate mm 45.6 51.34.05 Colour of bedding Black Black5.00 ARMOUR5.01 Material SWA SWA5.02 Dia of wire- Nominal mm 2.5 2.55.03 Number of wires- Approximate mm 52 585.04 Dia over armour- Approximate mm 50.6 56.3

    * In case of non availablity of 0.9 mm size armour wires we may use 1.25 mm size armour wires and in that case the number of armour wires will change.

    6.00 OUTERSHEATH6.01 Material PVC-Type 9 PVC-Type 96.02 Thickness- Nominal mm 2.6 2.76.03 Thickness- Min at any point mm 1.88 1.966.04 Overall dia- Approx. mm 56.0 62.06.05 Colour of sheath Black Black7.00 PACKAGING (approx)7.01 Standard Drum length ( 5%) mtr 500 2507.02 Packing material Wooden / Steel

    drums with Lamiflex lagging

    Wooden / Steel drums with Lamiflex lagging

    7.03 Approx. Size of drum (H x W) mm 2000 x 1320 1800 x 1140

    Page 1 of 2

  • POWER CABLESCU/XLPE/SWA/PVC, BS 5467

    Srl Description UnitNew Baan code FX244SPSK FX244TPSK

    1.00 General1.01 Item 4 x 185 4 x 2408.00 WEIGHTS (approx) 201011 1810098.01 Finished cable/km kg 9980 125408.02 Net weight kg 4990 31358.03 Gross weight of drum kg 5270 33959.00 ELECTRICAL PARAMETERS9.01 Max. DC resistance of cond.@ 20 C /km 0.0991 0.07549.02 Approx. AC resistance of cond.@ 90 C /km 0.128 0.09899.03 Approx. Reactance @ 50 Hz /km 0.072 0.0719.04 Approx. Impedance @ 50 Hz /km 0.147 0.1229.05 Approx. Voltage drop @ 90C (considering 3 phase circuit) mV/m/A 0.25 0.219.06 Min. Insulation resistance constant at 90 C km 3.67 3.679.07 Short circuit current rating of conductor for 1 Second kA 26.46 34.329.08 Current Rating

    9.08.01 Current rating- in ground at 35 C A 394 4559.08.02 Current rating- in duct at 35 C A 329 3809.08.03 Current rating- in air at 50 C A 386 4569.08.04 Basic Assumptions

    Ambient temp. - 50 CGround temp. 35 CDepth of laying in ground - 0.5 Mtr.Thermal resistivity of soil -1.2 K. m/W

    9.09 ELECTRICAL PARAMETERS - Armour9 09 01 Approx D C resistance at 20 deg C ohm/km 0 61 0 549.09.01 Approx. D.C. resistance at 20 deg C ohm/km 0.61 0.549.09.02 Armour short ckt capacity for 1sec (Approx.) kA 11.84 13.21

    10.00 MISC10.01 Max pulling tension when pulled by pulling eye kg 3700 480010.02 Min. Bending radius mm 8 x OD 8 x OD

    Note:1) Embossing on outer sheath of cable shall be as per example given below for 4 x 16 mm2 size cable:

    "ELECTRIC CABLE 600/1000 V BS 5467 OMAN CABLES 4 X 16 YEAR"

    Apart from the above sequential length marking shall also be provided on outer sheath of cable at every one meter by printing/Indenting/embossing.

    Page 2 of 2