technical comparison of cahors vs conventional trfo_final
TRANSCRIPT
-
7/25/2019 Technical Comparison of Cahors vs Conventional Trfo_final
1/2
Release no. 001 / Rev 0
Medium Voltage Division
Sr.NoCLASSIFI
CATIONPARAMETER
CONVENTIONAL OIL FILLED
TRANSFORMERS
CAHORS - HERMETIC
TECHNOLOGY MAINTENANCE
FREE OIL FILLED TRANSFORMER
BENEFITS / REMARKS
1 ConventionalHermetic Technology with non- gas
cushion
2 With Breathers & Conservators Without Breathers & Conservator Compact
3Possiblilty of Oil
Contamination with Air
YES. High Exposure to Oxydation
phenomenon due to Breathing
Technology
NO. Totally Airtight
Oil BDV get maintained @ required value & all
oil properties remains unchanged for entire
life of Transformer. Hence No maintenance.
4Oil filtration during pre-
commissioning & chargingRequired Not Required
Saving of MAN-HOURS, Cost & free from any
contamination. Ready to charge product.
5Oil Filtration & Oil TOP up
for preventive maintenanceRequired Not Required
Since no preventive maintenance required,
hence no need of any shut down, DG
operation. Hence cost saving & interruption
free operation of transformer.
6 Radiators Corrugated Fins
Compact. No need of any accessories fitting at
site i.e. conservator & detachable radiator
fitting. Further no need of Oil top up from
Spare oil of 10% which is suppplied in case of
conventional design.
7In Radiator, oil flow for cooling through
inlet & outlet nozzle only
Corrugated fins are attached directly to
main tank where cooling is faster &
better
Provides higher surface area for cooling with
effective faster cooling. i.e. Better Heat
dissipation. This enhances the efficiency of
Transformer.
8Oil need to undergo flow process for
achieving the cooling
Oil undergo emerge process for
achieving the coolingSuperior
9 Chemical Ageing Yes. Faster Extremely Slow
No adverse effect of external environment.
Hence Transformer gets Healthy working
operational condition.
10 Noise Level
High. Approx. > 60 dB as a operational
noise. (As per NEMA standard, its max
value is 65 dB)
Low. Approx.between 45 dB to 57 dB as
a operational noise. (As per NEMA
standard, its max value is 65 dB)
Low Noise & hence no disturbances by
transformer to external faculties.
11 Spare Requirement of oil Required for Preventive maintenance Not RequiredSpace saving of storage of Oil barrels & saving
on cost of spare oil.
12OIL BDV level with ageing
effectReduces faster Reduces very slow
Enhance the life of transformer from 20 years
to 30 years without any maintenance
13 Insulating Material Craft PaperEpoxy Diamond dotted paper for winding
& Polymide material forcoils.
It donot allow to produce any sluges in OIL &
donot give any agening effect. Hence provide
better & reliable insulation to inter turn
winding.
14 Gasket Rubber Cork Nitrile Gaskets i.e.NBR
It donot get cracks on high temprature &
hence survive with even continuous high temp
as well. It has longer life of 30 years compare
to Rubber cork gasket of 1 or 2 years.
15 Oil Leakage Possibility
YES, due to conventional design of
Detachable radiators, welded Tank &
gasketing structure.
Thanks to hermetically Sealed design, No
possibility of Oi leakage
Hence no need of spare oil, no need of any
shut down for atttending the oil leakage
complaint & saving of man, material & money.
16 Partial Dischare it is not partial discharge free Partial discharge free
Losses maintains to the actual designed values
for the complete life, unlike to increase the
losses after few years of service. This will give
Error free & maintenance free operation as
well.
17On higher side (conventional losses &
conventional designed)
Onlower side for standard Design &
available with STAR 3 rating, certified by
BEE
Reduces Electricity bill values & provides
higher efficiency to the product.
18Losses get increased with its operational
life
Losses remain steady with its operational
lifeUniform operation throughtoout the life.
19 Size Bulky due to conservator & RadiatorCompact by almost 30% as compared to
others thanks to corrugated FinsSaving of space at site.
20 Product expectedLife 15-20 Yrs 25-30 yrs Enhances the life of product
CONFIDENTIAL COPY
TRANSFIX INDIA Pvt Ltd
Technical Comparison Document(Conventional Oil filled Transformer Vs. CAHORS Hermetic TYPE Oil filled Transformer)
Technology
Cooling
Losses
TEC
HNOLOGY
PRODUCT
-
7/25/2019 Technical Comparison of Cahors vs Conventional Trfo_final
2/2
Medium Voltage Division
Sr.NoCLASSIFI
CATIONPARAMETER
CONVENTIONAL OIL FILLED
TRANSFORMERS
CAHORS - HERMETIC
TECHNOLOGY MAINTENANCE
FREE OIL FILLED TRANSFORMER
BENEFITS / REMARKS
21 Accessories for protection
Separate mounting Arrangement
required for OTI, PRV, Bukhlolz, etc for
protection.
Integrated in single instrument i.e. DGPT
2 -Protection device
Limit the no. of cut out to Tank & provides
smoother function though one device instead
of group of device.
22 SafetyLack of safety due to oil leakages &
further chances of fire explosion due to
low fire point
100% safety as no contact of oil with
external wheatherconditions & No
leakages. Also available with high flash
point of 135 Deg C. We can also supply
oil with higherflash point upto 370 Deg
C instead of standard oil at anextra cost.
Provides Safe & Reliable operation
23Short Circuit Withstand
CapacityLow dueto circular coil shape
High. Thanksto Oblong shape of
Winding to have better axial & radial
forces sustainability
Provides Rigid design to withstand different
abnormal supply & load conditions.
24 DESIGN Compliance IS 2026 IS 2026
25 Theft Possibility Theft of Oil, copper & core is possible
Not easily possible due to Hermetic
Technology where, many safety
interlocks are available in our
technology, which can be shown during
factory visit
Not easily accessible for theft of Oil & copper
in case of small ratings of transformer upto
400 KVA
26 MaintenanceEvery 3 years Maintenance + Oil
Replacement for entire lifeMaintenance free for entire l ife Saving of Man, Material & Money
27 Failure Rate failure rate < 5.6 % as per utility High reliability ( failure rate < 0.1 % ) Highly reliable & trusted by our customers
28Adds cost on MSEB bills due to high
lossesSaves over other transformers
29 Adds cost on Frequent Maintenance Saves 100% on this parameter
30Adds Oil Replacement & oil filtration
Cost Saves 100% on this parameter
31 Adds Overhead Cost Saves 100% on this parameter
32 Aesthetic LookConventional look with a Bulky size with
poor Paint finish likely to rust
Modern, compact & aesthetically sound,
Paint with mini 1000hrs SaltSpray
resistance
Long lasting paint shade which servives 30
years of rust proof services.
33 Handling & Installation
Difficult since detachable radiators, Oil
Barrel & their assembly at site which
lead to time & money involvement
Easy, as its a ready to charge product
without any detachable parts & loose oil
Ready to charge product without any site
activities i.e. Fitting, Oil top up etc. Hence
reduction of installation cost as well.
34 Return on investment (ROI) NIL
High. The cost of transformer gets
recovered thanks to all above mentioned
economical benefits (savings).
Competitive intial cost & negligible running
cost. Hence completely economical & ROI
product.
CONFIDENTIAL COPY
Product Photo
TRANSFIX INDIA Pvt Ltd
Saving of Man, Material & Money
Astethically Sound to deliver modernization &
technology upgradation.
Note: This document is mainlyfor general comparison and knowledge sharing purpose
only . To know more about any point can be shared in details separately.
35
Economical Benefit
Technical Comparison Document(Conventional Oil filled Transformer Vs. CAHORS Hermetic TYPE Oil filled Transformer)
GENERAL
PROTECTION