Important Safety Notice It is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to. All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation. All connections should be checked periodically to ensure correct tightness. DO NOT USE POWER TOOLS ON THESE PRODUCTS
Technical Data: ECLC03 1 or 2 Level Control Relay
Data ECLC03
Function 1 or 2 level control
Supply terminals A1-A2
Voltage range AC/DC 24-240V(50-60Hz)
Input Maximum 2VA
Supply voltage tolerance -15%;+10%
Sensitivity (input resistance) Adjustable in range 5 kΩ -100 kΩ
Voltage in electrodes Maximum AC 5 V
Current in probe AC <0.1 mA
Time response Maximum 400 ms
Maximum capacity length 800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ)
Maximum capacity of probe cable 400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ)
Time delay (t) Adjustable, 0.5 -10 s
Time delay after power on 1.5 s
Accuracy in setting (mechanical) ± 5 %
Temperature coecient 0.05%oC/,at=20oC(0.05%oF, at=68oF)
Output 1×SPDT
Current rating 10A/ AC1
Switching voltage 250VAC/24VDC
Minimum breaking capacity DC 500mW
Output indication Red LED
Mechanical life 1×107
Electrical life(AC1) 1×106
Reset time Maximum 200ms
Operating temperature -20oC to +55oC (-4oF to 131oF)
Storage temperature -35oC to +75oC (-22oF to 158oF)
Mounting/DIN rail Din rail EN/IEC 60715
Protection degree IP40 for front panel/IP20 terminals
Operating position Any
Overvoltage category III.
Maximum cable size (mm2) solid wire max.1×2.5 or 2×1.5/with sleeve max.1×2.5(AWG 12)
Dimensions 90 x 18 x 64mm
Weight 81g
Standards IEC/EN 62055-1,IEC/EN61010-1
Page 1 of 2 EDS1211-001Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440 / Fax: 01582 692 450 e-mail: [email protected] / website: http://www.europacomponents.com
Technical Data: ECLC03 1 or 2 Level Control Relay
Panel Diagram:
-1-
Instruction Manual
Level control relay GRL8
Panel Diagram
GEYA ELECTRICAL CO.,LTDAdd:Wenzhou Brige Industrial Zone,Beibaixiang Town,Yueqing,Zhejiang,China 325603
Tel:0086-577-62711079Fax:0086-577-62711751Mobile:0086-13567770207E-mail:[email protected]:www.geya.net
General
■Model and connotation
Wiring Diagram
■Applications -Designed for monitoring level in wellss, basins, reservoirs, tanks.....■Function Features -In one device you can choose the following configurations: - 2 level control mode - 1 level control mode -Choice of function PUMP UP, PUMP DOWN. -Adjustable time delay on the output (0.1 - 10s). -Sensitivity adjustable by a potentiometer (5-100kΩ). -Galvanically separated supply voltage AC/DC 24-240V. - Relay status is indicated by LED. - 1-MODULE,DIN rail mounting.
01
GRL8 Series
GRL8
Design number
Function
Supply terminals
AC/DC 24-240V(50-60Hz)
A1-A2
Voltage range
Input max.2VA
-15%;+10%Supply voltage tolerance
Sensitivity ( input resistance) adjustable in range 5 kΩ -100 kΩ
0.05%/℃,at=20℃(0.05%℉,at=68℉)
1×SPDT
10A/AC1
250VAC/24VDC
Temperature coecient
Output
500mW
red LED
1×10
1×10
max.200ms
Min.breaking capacity DC
Switching voltage
Current rating
Output indication
Mechanical life
Electrical life(AC1)
Reset time
-20℃ to +55℃(-4℉ to 131℉)
-35℃ to +75℃(-22℉ to 158℉)
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
90×18×64mm
61g
IEC/EN 62055-1,IEC/EN61010-1
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
Standards
2 or 1 level contorl mode
GRL8-01
Technical parameters
max. AC 5 VVoltage in electrodes
AC <0.1 mACurrent in probe
max. 400 msTime response
adjustable, 0.5 -10 sTime delay (t)
1.5 sTime delay after power on
± 5 %Accuracy in setting (mechanical)
400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ)Max. capacity of probe cable
GRL8-02
2 level contorl mode
81g
Max. capacity length 800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ)
GRL8-01
Un R
Sensitivity
GRL8-02
Un R
5 100(k )Ω
0.1 10s
2
4 6
8Tt
2
1ton PUMP
UP DOWN
1toff 1toff
1ton
2
Sensitivity20
40 60
80
5 100(k )Ω
20
40 60
80
LevelLevelC
MaxMin
A1 A2
Max
12 C
1114
Un2 level control
A1 A2
12 C
1114
Un
1 level control
Min Max Min
Dimensions:
-2-
http://www.geya.net
Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.
CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.
Functions Diagram
Dimensions(mm)
GRL8-01
Un
Max
Min
2 level control
11-14
11-12
Un
Max
Min
11-14
2 level control(pump up/down)
PUMP UP
11-14PUMP DOWN
2
1ton
UP DOWN
1toff 1toff
1ton
2
2
1ton
UP DOWN
1toff 1toff
1ton
2
GRL8-02
GRL8-02
Un R
A1 A2
12
14 11
5 100(k )Ω
0.1 10s
2
4 6
8Tt
Min
C
2
1ton
PUMPUP DOWN
Max
1toff 1toff
1ton
2
Sensitivity20
40 60
80
95
4.2
1 level control(pump up t on)
Un
Level
11-14
2
1ton
UP DOWN
1toff 1toff
1ton
2
Tt Tt Tt
t <Tt
1 level control(pump up t off )
Un
Level
11-14
2
1ton
UP DOWN
1toff 1toff
1ton
2
Tt
t <Tt
Tt Tt
1 level control(pump down t on)
Un
Level
11-14
2
1ton
UP DOWN
1toff 1toff
1ton
2
Tt Tt Tt
t <Tt
1 level control(pump down t off )
Un
Level
11-14
2
1ton
UP DOWN
1toff 1toff
1ton
2
Tt
t <Tt
Tt Tt
Functions Diagram:
-2-
http://www.geya.net
Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.
CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.
Functions Diagram
Dimensions(mm)
GRL8-01
Un
Max
Min
2 level control
11-14
11-12
Un
Max
Min
11-14
2 level control(pump up/down)
PUMP UP
11-14PUMP DOWN
2
1ton
UP DOWN
1toff 1toff
1ton
2
2
1ton
UP DOWN
1toff 1toff
1ton
2
GRL8-02
GRL8-02
Un R
A1 A2
12
14 11
5 100(k )Ω
0.1 10s
2
4 6
8Tt
Min
C
2
1ton
PUMPUP DOWN
Max
1toff 1toff
1ton
2
Sensitivity20
40 60
80
95
4.2
1 level control(pump up t on)
Un
Level
11-14
2
1ton
UP DOWN
1toff 1toff
1ton
2
Tt Tt Tt
t <Tt
1 level control(pump up t off )
Un
Level
11-14
2
1ton
UP DOWN
1toff 1toff
1ton
2
Tt
t <Tt
Tt Tt
1 level control(pump down t on)
Un
Level
11-14
2
1ton
UP DOWN
1toff 1toff
1ton
2
Tt Tt Tt
t <Tt
1 level control(pump down t off )
Un
Level
11-14
2
1ton
UP DOWN
1toff 1toff
1ton
2
Tt
t <Tt
Tt Tt
Wiring Diagram:
-1-
Instruction Manual
Level control relay GRL8
Panel Diagram
GEYA ELECTRICAL CO.,LTDAdd:Wenzhou Brige Industrial Zone,Beibaixiang Town,Yueqing,Zhejiang,China 325603
Tel:0086-577-62711079Fax:0086-577-62711751Mobile:0086-13567770207E-mail:[email protected]:www.geya.net
General
■Model and connotation
Wiring Diagram
■Applications -Designed for monitoring level in wellss, basins, reservoirs, tanks.....■Function Features -In one device you can choose the following configurations: - 2 level control mode - 1 level control mode -Choice of function PUMP UP, PUMP DOWN. -Adjustable time delay on the output (0.1 - 10s). -Sensitivity adjustable by a potentiometer (5-100kΩ). -Galvanically separated supply voltage AC/DC 24-240V. - Relay status is indicated by LED. - 1-MODULE,DIN rail mounting.
01
GRL8 Series
GRL8
Design number
Function
Supply terminals
AC/DC 24-240V(50-60Hz)
A1-A2
Voltage range
Input max.2VA
-15%;+10%Supply voltage tolerance
Sensitivity ( input resistance) adjustable in range 5 kΩ -100 kΩ
0.05%/℃,at=20℃(0.05%℉,at=68℉)
1×SPDT
10A/AC1
250VAC/24VDC
Temperature coecient
Output
500mW
red LED
1×10
1×10
max.200ms
Min.breaking capacity DC
Switching voltage
Current rating
Output indication
Mechanical life
Electrical life(AC1)
Reset time
-20℃ to +55℃(-4℉ to 131℉)
-35℃ to +75℃(-22℉ to 158℉)
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
90×18×64mm
61g
IEC/EN 62055-1,IEC/EN61010-1
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
Standards
2 or 1 level contorl mode
GRL8-01
Technical parameters
max. AC 5 VVoltage in electrodes
AC <0.1 mACurrent in probe
max. 400 msTime response
adjustable, 0.5 -10 sTime delay (t)
1.5 sTime delay after power on
± 5 %Accuracy in setting (mechanical)
400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ)Max. capacity of probe cable
GRL8-02
2 level contorl mode
81g
Max. capacity length 800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ)
GRL8-01
Un R
Sensitivity
GRL8-02
Un R
5 100(k )Ω
0.1 10s
2
4 6
8Tt
2
1ton PUMP
UP DOWN
1toff 1toff
1ton
2
Sensitivity20
40 60
80
5 100(k )Ω
20
40 60
80
LevelLevelC
MaxMin
A1 A2
Max
12 C
1114
Un2 level control
A1 A2
12 C
1114
Un
1 level control
Min Max Min
Wiring Diagram: