Page 1: Technical Data Sheet · Critical Power Modifications reserved Page 3/5 GE_UPS_TDS_TLE_MCE_30K_M18_1GB_V020.docx Technical Data Sheet TLE Modular Series 30 - 180 CE S1 DESCRIPTION

Critical Power

Technical Data Sheet Uninterruptible Power Supply

GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52

www.gecriticalpower.com

imagination at work

TLESM_030-180_UPS front_01

Page 2: Technical Data Sheet · Critical Power Modifications reserved Page 3/5 GE_UPS_TDS_TLE_MCE_30K_M18_1GB_V020.docx Technical Data Sheet TLE Modular Series 30 - 180 CE S1 DESCRIPTION

Critical Power

Modifications reserved Page 2/5

GE_UPS_TDS_TLE_MCE_30K_M18_1GB_V020.docx Technical Data Sheet TLE Modular Series 30 - 180 CE S1

Model: TLE Modular Series 30 - 180 kVA CE S1

Issued by: Product Document Department – Riazzino - CH

Approved by: R & D Department – Riazzino - CH

Date of issue: 13.04.2017

File name: GE_UPS_TDS_TLE_MCE_30K_M18_1GB_V020

Revision: 2.0

Identification No.:

Up-dating

Revision Concern Date

2.0 Connectivity and packaging update 13.04.2017

COPYRIGHT © 2017 by GE Consumer & Industrial SA

All rights reserved.

The information contained in this publication is intended solely for the purposes indicated.

The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE.

The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.

The content of this publication may be subject to modification without prior notice.

Page 3: Technical Data Sheet · Critical Power Modifications reserved Page 3/5 GE_UPS_TDS_TLE_MCE_30K_M18_1GB_V020.docx Technical Data Sheet TLE Modular Series 30 - 180 CE S1 DESCRIPTION

Critical Power

Modifications reserved Page 3/5

GE_UPS_TDS_TLE_MCE_30K_M18_1GB_V020.docx Technical Data Sheet TLE Modular Series 30 - 180 CE S1

DESCRIPTION

The TLE Modular Series UPS provides a compact footprint of less than 2m2 with maximum capacity of 180kVA with best reliability and high performance. TLE Modular Series is considered to be the best power protection solution.

FEATURES

• Modular design with N+X redundancy, on-line and hot-swappable.

• High power density with footprint of less than 2m2 up to 180kVA.

• 30kVA power module with only 3U height.

• Paralleling up to 540kVA (3 cabinets).

• Green and energy saving: ECO mode efficiency 99%, on-line >95%.

• Excellent input performances: power factor >0.99 while THDi <3%.

• Wide accepted input voltage range for maximum compatibility with stressing mains.

• Superior Battery Management enhances battery lifetime resulting in reduced cost of operation.

• Battery cold start: UPS can be powered on from the battery without mains.

• Lifetime monitoring of critical components, such as fans and capacitors.

• Independent LCD display for each power module with self-starting function.

• 9 signalling voltage-free contacts (4 programmable by user).

• User-friendly colour touch screen of 10.4 inches.

Page 4: Technical Data Sheet · Critical Power Modifications reserved Page 3/5 GE_UPS_TDS_TLE_MCE_30K_M18_1GB_V020.docx Technical Data Sheet TLE Modular Series 30 - 180 CE S1 DESCRIPTION

Critical Power

Modifications reserved Page 4/5

GE_UPS_TDS_TLE_MCE_30K_M18_1GB_V020.docx Technical Data Sheet TLE Modular Series 30 - 180 CE S1

SPECIFICATION

Model TLE Modular Series 30 – 180 kVA CE S1 Capacity 30 ÷ 180 kVA, up to 540kVA with 3 parallel cabinets Power Module type 30PM

General data System efficiency Normal mode: >95%, ECO mode: 99%, Battery mode: 95% Cooling air at PF=0.9 (25°C ÷ 30°C, Normal Mode) m3/h 30kVA: 700 60kVA: 1228 90kVA: 1756 120kVA: 2284 150kVA: 2812 180kVA: 3340

Cooling air at PF=0.9 (25°C ÷ 30°C, ECO Mode) m3/h 30kVA: 554 60kVA: 713 90kVA: 871 120kVA: 1030 150kVA: 1188 180kVA: 1346

Display 10.4” LCD colour touch screen IP Class IP20 Interface 9 signalling voltage-free contacts (4 programmable) and SNMP card Operating temperature range UPS: 0°C ÷ 40°C

Storage temperature range UPS: -40°C ÷ 70°C Battery: -20°C ÷ 40°C (higher the temperature, shorter the storage time of the battery)

Relative humidity 0 ÷ 95% (non-condensing) Altitude of operation 1000m / 1500m: -2.5% / 2000m: -5% / 2500m: -7.5% / 3000m: -10% General safety requirements for UPS used in operator access areas IEC/EN 62040-1/A1

Electromagnetic compatibility (EMC) requirements for UPS IEC/EN 62040-2 (C3)

Method of specifying the performance and test requirements of UPS IEC/EN 62040-3

Transport On pallet- Cabinet suitable for handling by forklift External cable connections Top and bottom cable entry Audible noise level 65dB with 100% load / 62dB with 45% load (at 1 meter) Colour RAL 9005 (black) Paralleling Up to 3 cabinets (option) Input Phase 3 Phases + Neutral + Ground Voltage 380V / 400V / 415V (phase - phase) Frequency 50 / 60Hz Power factor >0.99 THDi THDi<3% with 100% linear load

Voltage range 304Vac ÷ 478Vac (phase - phase), full load 228Vac ÷ 478Vac (phase - phase), 75% load

Frequency range 40Hz ÷ 70Hz

Output Voltage 380V / 400V / 415V (programmable) THDu THD <1% with linear load / THD <5% with non-linear load Power factor 0.9 Crest factor 3:1 Overload Capability 110% for 1 hour / 125% for 10 minutes / 150% for 1 minute / >150% for 200ms Short-circuit characteristic 2.7 times for 200ms between phase/phase and phase/N/PE

Bypass Input connection Separate for rectifier and bypass input or common to the rectifier input

Primary components Static switch (SCR) on bypass Electromechanic contactor (backfeed protection) on bypass

Overload on bypass 110% Long term operation / 110% ÷ 125% for 5min. / 125% ÷ 150% for 1min. / 150% ÷ 400% for 1sec. / >400%, less than 200ms

ICC (short circuit current capability) Static bypass: 40kA Maintenance bypass: 10kA

Output UPS power versus power factor for: Inductive loads Resistive loads Capacitive loads

Page 5: Technical Data Sheet · Critical Power Modifications reserved Page 3/5 GE_UPS_TDS_TLE_MCE_30K_M18_1GB_V020.docx Technical Data Sheet TLE Modular Series 30 - 180 CE S1 DESCRIPTION

Critical Power

Modifications reserved Page 5/5

GE_UPS_TDS_TLE_MCE_30K_M18_1GB_V020.docx Technical Data Sheet TLE Modular Series 30 - 180 CE S1

Battery Battery type Valve regulated lead-acid (VRLA), NiCd and Li-ion on request Float voltage at 20°C 436V ÷ 545V (dependent on the number of cells) Number of cells VRLA at 2.27V/cell: 192 ÷ 240 cells Min. discharge voltage (programmable) 320V ÷ 400V (dependent on the number of cells) Recharge current Up to 20% of the rated output power of PM (kW), programmable

Recharge time <5 hours up to 80% of battery capacity Longer recharge time for long autonomy time / high load conditions

Automatic and manual battery test Standard Common battery in parallel system Up to 3 cabinets (with same output power rating) Battery power data kVA 30 60 90 120 150 180 DC power at full load & PF=0.8 lag. / PF=0.9 lag. kW 25.3/28.4 50.5/56.8 75.8/85.3 101.0/113.7 126.3/142.1 151.6/170.5 Maximum discharge current (1.65V/cell) Amps 80/90 159/179 239/269 319/359 399/448 478/538

EXTERNAL BATTERY TABLE Battery autonomy (0.8 PF full load) *) 10 year design life batteries

UPS (kVA) 1x33Ah *) 2x33Ah *) 3x33Ah *) 30 20 min. 42 min. 66 min. 60 8 min. 20 min. 31 min. 90 4 min. 12 min. 20 min.

120 - 8 min. 14 min. 150 - 5 min. 10 min. 180 - 4 min. 8 min.

Battery cabinet

Dimensions 790 x 1100 x 1600 mm (W x D x H) Weight 725 kg 1135 kg 1550 kg Floor loading 835 kg/m2 1306 kg/m2 1785 kg/m2

Dimensions and weights

Net weight Cabinet 170Kg

Power module 30 kVA 34Kg

Dimension (W x D x H)

Cabinet 600 x 1100 x 1600mm

Power module 30 kVA 460 x 790 x 134mm

Protections

Protections for mains voltages (3 x 380V / 400V / 415 Vac) UPS model Mains Input Bypass Input Common Input Mains External Battery

TLE Modular Series 180/30 3 x 50A 3 x 50A 3 x 50A 3 x 80A TLE Modular Series 180/60 3 x 100A 3 x 100A 3 x 100A 3 x 160A TLE Modular Series 180/90 3 x 160A 3 x 160A 3 x 160A 3 x 250A TLE Modular Series 180/120 3 x 200A 3 x 200A 3 x 200A 3 x 300A TLE Modular Series 180/150 3 x 250A 3 x 250A 3 x 250A 3 x 355A TLE Modular Series 180/180 3 x 315A 3 x 315A 3 x 315A 3 x 400A

Cable sections

Cables section (mm2) / IEC 60950-1 Local Standard and cables installation disposal shall be applied

UPS model Mains Input Bypass Input Common Input Mains Mains Output External Battery TLE Modular Series 180/30 3 x 10 + 10 4 x 10 4 x 10 + 10 4 x 10 + 10 3 x 16 + 16 TLE Modular Series 180/60 3 x 25 + 16 4 x 25 4 x 25 + 16 4 x 25 + 16 3 x 50 + 25 TLE Modular Series 180/90 3 x 50 + 25 4 x 50 4 x 50 + 25 4 x 50 + 25 3 x 120 + 70 TLE Modular Series 180/120 3 x 70 + 35 4 x 70 4 x 70 + 35 4 x 70 + 35 3 x 150 + 95 TLE Modular Series 180/150 3 x 120 + 70 4 x 120 4 x 120 + 70 4 x 120 + 70 3 x 185 + 95 TLE Modular Series 180/180 3 x 150 + 95 4 x 150 4 x 150 + 95 4 x 150 + 95 3 x 240 + 120

600mm

1600

mm