Technical Data Sheet Hilti Firestop Collar CFS-C P European Technical Approval ETA N o 10/0404 Issue 02 / 2014

Upload: hatu

Post on 25-May-2018

280 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P

Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1

Technical Data Sheet

Hilti Firestop CollarCFS-C P

European Technical ApprovalETA No 10/0404

Issue 02 / 2014

Page 2: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 2 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 3

General information

Pipe end configurations Page 03 Pipe end configurations according to intended use Page 04 Insulation configurations Page 05 Hilti Firestop Collar CFS-C P Page 06 Installation instructions Page 07

Fire classification detail tables for walls

Walls Construction and minimum distances Page 08 Flexible and rigid walls minimum wall thickness 100 mm Page 08 Pre-insulated pipes Page 10 Plastic pipes Page 11 Plastic pipes with combustible insulation Page 14 Composite pipes with combustible insulation Page 16 Rigid walls minimum wall thickness 150 mm Page 17 Plastic pipes Page 18

Fire classification detail tables for floors

Floors Construction and minimum distances Page 19 Rigid floors minimum density of 2400 kg/m3 Page 19 Pre-insulated pipes Page 21 Plastic pipes Page 22 Plastic pipes with combustible insulation Page 26 Composite pipes Page 27 Composite pipes with combustible insulation Page 28 Rigid floors minimum density of 550 kg/m3 Page 29 Pre-insulated pipes Page 29 Plastic pipes Page 29 Plastic pipes with combustible insulation Page 32 Composite pipes Page 33 Composite pipes with combustible insulation Page 33

Hilti Firestop Acrylic Sealant CFS-S ACR

Product data sheet Page 35 Installation instructions Page 36

Specification

Additional attributes Page 37

Pipe end configurationsAll pipes tested according to EN 1366-3 have been tested with a specific pipe end configuration. In the fire classification, the first letter of the end configuration refers to the end conditions within the furnace (fire-side), the second letter to the end conditions outside the furnace (non-fire-side).

Test condition Pipe end configurationInside furnace Outside furnace

U / U Uncapped UncappedC / U Capped UncappedU / C Uncapped CappedC / C Capped Capped

As the EN test standard EN 1366-3 states, “it is important to ensure that sealing systems have been tested with appropriate pipe end conditions.” The conditions the pipe and sealing system must endure in a fire situation depend on whether one or both ends of the pipe are sealed in practice, as pressures and the flow of hot gases will vary depending on whether the pipe is ventilated or not.

There are rules that determine which tested end configurations are valid for additional pipe end situations.

For metal pipes:TestedU / C C / U C / C

Cov

ered U / C Y N N

C / U Y Y NC / C Y Y Y

Y = acceptable, N = not acceptable

For plastic pipes:TestedU / U C / U U / C C / C

Cov

ered

U / U Y N N NC / U Y Y N NU / C Y Y Y NC / C Y Y Y Y

Y = acceptable, N = not acceptable

So, for example, a plastic pipe tested with the end configuration U / U will cover all possible end conditions. But a plastic pipe tested U / C will only cover the conditions U / C or C / C.

EI 90 U / U Configuration outside furnace Configuration inside furnace Fire resistance classification in minutes E = integrity, I = insulation

Page 3: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 4 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 5

Pipe end configurations according to intended useAs previously stated, it is important to ensure that the tested pipe configuration corresponds to the intended use of the pipe.

The table below outlines recommended end configurations for various intended pipe uses as per suggestions laid out in EN 1366-3 2009 H.4.2.2. In the event that a national regulation conflicts with this table, the national regulation takes precedence.

Intended use of penetrations (list not exhaustive, other pipes uses possible)Application Penetration

materialManufacturer, product(examples)

Insulation Recommended pipe end classification

Heating Al-Composite Geberit Mepla – U / CCS

KeKelit KELOX KM 110 CS

Rehau Rautitan stabil CS

PE-X Rehau Rautitan flex CS

PP-R Aquatherm blue Aquatherm blue Faserverbundrohr

Potable water Al-Composite Geberit Mepla – U / CCS

KeKelit KELOX KM 110 CS

Rehau Rautitan stabil CSPE EN 12201-2 –PE-HD 100 RC Wavin TS –

CS/LSPE-X Rehau Rautitan flex CSPP EN ISO 15874, DIN 8077/ 8078

(e.g. AquathermGreen, Aquatherm GreenFaserverbundrohr)

CS/LS

PCV-C Friatherm starr CS/LSRefrigeration ABS +GF+ COOL-FIT CS U/CVentilated Waste water  Roof Drainage

PE EN 1519, EN 12666-1 – U / UCI/CS

PE-HD 1000 RC Wavin TS –CS/LS

PE-S2 Geberit Silent db20 –PP EN 1451-1 –

Magnaplast Skolan dB –Pipelife Master 3 –Poloplast Polo Kal NG –Poloplast Polo Kal 3S –Rehau Raupiano Plus –Wavin AS/KeKelit “Phonex AS” –Wavin SiTech –

PVC-C EN 1566-1 –PVC-U EN ISO 1452, EN 1329-1, EN 1453-1 –

Pneumatic Al-composite Geberit Mepla – C/CPP DIN 8077/8078 –

Sprinkler PP-R Aquatherm red – U/CIndustry Al-Composite Various – Varies depending upon appli-

cation, i.e. consider whether pipe is pressurized (U/C), ventilated (U/U) or unventilated (U/C)

PE EN ISO 15494, DIN 8074/8075 –PP DIN 8077/8078 –PVC-U EN ISO 15493, DIN 8061/8062 –

Insulation configurationsWhen sealing pipes, the insulation configuration must be considered. The following configurations are possible:

Insulation over the entire length of the pipe (i.e. thermal insulation)

Continued sustained Continued interrupted

Insulation only required in the area of the penetration seal

Local insulation, Local insulation, sustained sustained

See page 35 for specification of suitable insulation products.

Page 4: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 6 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 7

Installation instructions

Seal the opening: The aperture around the pipe is filled with gypsum plaster (flexible walls) or cementitious mortar (concrete walls/floors) over the full thickness of the wall/floor or alternatively sealed with minimum 25 mm thick Hilti Firestop Acrylic Sealant CFS-S ACR on both sides. Backfilling with stone wool may be omitted in case of small annular gaps and classifications ≤ EI 120.In case of missing sound decoupling means around the pipe it is recommended to use Hilti Firestop Acrylic Sealant CFS-S ACR as annular gap seal. If gypsum plaster or cementitious mortar is intended to be used it is recommended to install a PE foam strip around the pipe over the entire wall or floor thickness for sound de coupling of the pipe.

Clean the plastic pipe. Remove all plaster/mortar or dust from the pipe in the area where the Firestop collar is to be installed.

Attach fastening hooks/tabs: The fastening hooks can be attached to various points of the metal housing. The hooks must be positioned as symmetrically as possible. The required number of fastening hooks is indi-cated below and on the packaging.

Fasten the Hilti Firestop Collar:a) Attach fastening hooks/tabs on the metal housing.b) Mark the fastening points on the wall/floor.c) Fasten the Hilti Firestop Collar, using recommended metal anchors/fasteners, e.g. Hilti HUS for rigid walls and

floors or threaded rod, nuts, washers in flexible walls. These are defined in the respective test reports and approvals.

d) If required by national prescriptions mark the penetration seal with an identification plate containing the re-quired information. In such a case fasten the identification plate in a visible position next to the seal.

Close the Hilti Firestop Collar: Place the Hilti Firestop Collar around the plastic pipe and apply firm pressure by hand until it latches with a "click" sound. No tools, pins or screws are necessary. The Hilti Firestop Collar can be re-opened by pushing down the engaged "tongue" with a screwdriver while pulling the Hilti Firestop Collar apart.

For wall applications: Repeat installation on the other side of the wall.

FS Collar P 50/1,5" – 2FS Collar P 63/2" – 2

FS Collar P 160/6" – 6 FS Collar P 250/10" – 12

FS Collar P 75/2,5" – 3FS Collar P 90/3" – 3

FS Collar P 180/7" – 8FS Collar P 200/8" – 8

FS Collar P 110/4" – 4FS Collar P 125/5" – 4

FS Collar P 225/9" – 10

Collar sizes and number of hooks for suitable pipe diameters

The European Technical Approval (ETA) and the technical data sheet can be obtained via your local Hilti contact.

Hilti Firestop collarCFS-C P

Applications n Sealing flammable pipes from 50 mm to 250 mm in diameter in

penetrations through fire compartment walls and floors n Pipe materials: PVC, PVC-U, PE, PE-HD, PE-X, PP, ABS,

Al-composite n Suitable for use in openings in concrete, aerated concrete,

masonry, drywall, shaft wall and coated board. n Different backfilling and sealing materials are covered

Technical dataCFS-C P

Minimal wall thickness 100mmMinimal ceiling thickness 150mmStorage and transportation temperature - range

-5 °C - 50 °C

Close aperture with Gypsum plaster, cementitious mortar, Hilti Firestop Acrylic Sealant

CFS-S ACRExpansion temperature 210 °C

Firestopping for flammable pipes up to 250 mm in diameter with European Technical Approval.

Advantages n Quick and easy closure without use of a tool n Adjustable position tabs for simple fastening n Sound decoupling strip based on PE (foam) can be used n Low profile for tight installations

Nominal pipe diameter

Number of hooks and fasteners

Order designation Sales Quantity Item Number

50 mm 2 Firestop collar CFS-C P 50/1.5” 1 pc 0043540663 mm 2 Firestop collar CFS-C P 63/2” 1 pc 0043540775 mm 3 Firestop collar CFS-C P 75/2.5” 1 pc 0043540890 mm 3 Firestop collar CFS-C P 90/3” 1 pc 00435409110 mm 4 Firestop collar CFS-C P 110/4” 1 pc 00435410125 mm 4 Firestop collar CFS-C P 125/5” 1 pc 00435411160 mm 6 Firestop collar CFS-C P 160/6” 1 pc 00435412180 mm 8 Firestop collar CFS-C P 180/7” 1 pc 00435413200 mm 8 Firestop collar CFS-C P 200/8” 1 pc 00435414225 mm 10 Firestop collar CFS-C P 225/9” 1 pc 00435415250 mm 12 Firestop collar CFS-C P 250/10” 1 pc 00435416

Page 5: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 8 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 9

1. Flexible and rigid walls, minimum wall thickness 100 mm

The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of:

Flexible walls / drywalls (E) with a minimum thickness of 100 mm (tE), with timber or steel studs lined on both faces with a minimum of two layers of 12.5 mm thick boards. For timber stud walls there must be a minimum distance of 100 mm between the seal and any stud, and the cavity must be filled with a minimum of 100 mm insulation of Class A1 or A2 in accordance with EN 13501-1. Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) over the entire thickness of the wall or Hilti Firestop Acrylic CFS-S ACR Sealant (A2) on both sides with a depth of minimum 25 mm from the surface of the wall.

Rigid walls (E) consisting of comprise concrete, aerated concrete or masonry, minimum density of 450 kg/m3, minimum thick-ness 100 mm. Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) or cementitious mortar over the entire thickness of the wall or Hilti Firestop Acrylic Sealant CFS-S ACR (A2) on both sides with a depth of minimum 15 mm from the surface of the wall. The sealant may be back-filled with mineral wool.

Maximum opening diameter: the opening should not be larger than the collar outside diameter to allow safe fixing of the collar to the wall. Minimum distance between collars (s1): 0 mm. Firestop collar (A1) fastened by hooks (F) (minimum number of hooks: see installation instructions) in flexible wall / drywall and low density rigid wall with M8 threaded rods through the wall secured with nuts on both sides. In high density rigid walls, metal anchors may be used as an alternative (e.g. Hilti HUS). Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the wall. For maximum thickness see tables below.

Annular gap seal(drawings show non-insulated pipes as example)Gypsum plaster (A3)

Gypsum plaster (A3) together with sound decoupling (C1)

Hilti Firestop Acrylic Sealant CFS-S ACR (A2)

Gypsum plaster or cementitious mortar (A3)

Gypsum plaster or cementitious mortar (A3) together with sound decoupling (C1)

Hilti Firestop Acrylic Sealant CFS-S ACR (A2)

Pipe insulation(drawings show mortar as an example for the annular gap seal)Local/Sustained pipe insulation (LS) Continued/Sustained pipe insulation (CS)

Page 6: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 10 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 11

Branded pipes

Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size ClassificationE = integrityI = insulation

ABS/PUR insulation/PE-HD

+GF+ „COOL-FIT“ 90 mm 32 mm CFS-C P 90/3” EI 120-U/C110 mm 40 mm CFS-C P 110/4” EI 120-U/C110 mm 50 mm CFS-C P 110/4” EI 120-U/C160 mm 90 mm CFS-C P 160/6” EI 120-U/C180 mm 110 mm CFS-C P 180/7” EI 120-U/C225 mm 140 mm CFS-C P 225/9” EI 120-U/C250 mm 160 mm CFS-C P 250/10” EI 60-U/C

Normed pipes – Pipe end configuration U/U

Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size ClassificationE = integrityI = insulation

PVC-U (maximum thickness of sound decoupling: 5 mm)

EN ISO 1452-2, EN ISO 15493, DIN 8061/2, EN 1329-1, EN 1453-1

50 mm 2.4–5.6 mm CFS-C P 50/1.5” EI 120-U/U63 mm 3.0–4.7 mm CFS-C P 63/2”75 mm 2.2–3.6 mm CFS-C P 75/2.5”90 mm 2.7–4.3 mm CFS-C P 90/3”110 mm 2.2–8.1 mm CFS-C P 110/4”125 mm 3.7–6.0 mm CFS-C P 125/5”160 mm 2.5–11.8 mm CFS-C P 160/6”

PE (maximum thickness of sound decoupling: 5 mm)

EN 1519, EN 12201-2, EN 12666-1

50 mm 3.0 mm CFS-C P 50/1.5” EI 120-U/U63 mm 3.0 mm CFS-C P 63/2”75 mm 3.0 mm CFS-C P 75/2.5”90 mm 3.5 mm CFS-C P 90/3”110 mm 4.2 mm CFS-C P 110/4”125 mm 4.8 mm CFS-C P 125/5”160 mm 6.2 mm CFS-C P 160/6”

EN ISO 15494, DIN 8074/5

50 mm 2.9–4.6 mm CFS-C P 50/1.5” EI 120-U/U63 mm 1.8–5.8 mm CFS-C P 63/2” EI 90-U/U63 mm 3.6–5.8 mm CFS-C P 63/2” EI 120-U/U75 mm 1.9–6.8 mm CFS-C P 75/2.5” EI 120-U/U90 mm 2.2–8.2 mm CFS-C P 90/3” EI 120-U/U110 mm 2.7–10.0 mm CFS-C P 110/4” EI 120-U/U125 mm 3.1–7.1 mm CFS-C P 125/5” EI 120-U/U160 mm 4.0–9.1 mm CFS-C P 160/6” EI 120-U/U

PP (maximum thickness of sound decoupling: 9 mm)

EN ISO 15874DIN 8077/8078

50 mm 1.8–2.9 mm CFS-C P 50/1.5” EI 90-U/U63 mm 1.8–5.8 mm CFS-C P 63/2” EI 60-U/U75 mm 1.9–6.8 mm CFS-C P 75/2.5” EI 60-U/U75 mm 6.8 mm CFS-C P 75/2.5” EI 120-U/U90 mm 8.2–15.0 mm CFS-C P 90/3” EI 120-U/U110 mm 2.7 mm CFS-C P 110/4” EI 120-U/U

PP (maximum thickness of sound decoupling: 9 mm)

EN 1451-1DIN EN 12056

32 mm 1,8 CFS-C P 50/1.5” EI 120-U/U40 mm 1,8 CFS-C P 50/1.5” EI 120-U/U50 mm 1,8–2,0 CFS-C P 50/1.5” EI 120-U/U70 mm 4,5 CFS-C P 75/2.5” EI 120-U/U75 mm 1.8–3.8 CFS-C P 75/2.5” EI 120-U/U90 mm 2.8–4.5 CFS-C P 90/3” EI 120-U/U110 mm 2.7–5.3 CFS-C P 110/4” EI 120 U/U

Flexible and rigid walls ≥ 100 mm Flexible and rigid walls ≥ 100 mm

1.1. Pre-insulated pipes

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts.

1.2. Plastic Pipes

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts.

Page 7: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 12 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 13

Normed pipes – Pipe end configuration U/CPipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification

E = integrityI = insulation

PP (maximum thickness of sound decoupling: 9 mm)

EN ISO 15874DIN 8077/ 8078

50 mm 4.6–8.3 mm CFS-C P 50/1.5” EI 90-U/C63 mm 5.8–10.5 mm CFS-C P 63/2” EI 60-U/C63 mm 10.5 mm CFS-C P 63/2” EI 120-U/C75 mm 1.9–6.8 mm CFS-C P 75/2.5” EI 60-U/C75 mm 6.8–12.5 mm CFS-C P 75/2.5” EI 120-U/C

Branded pipes – Pipe end configuration U/UPipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification

E = integrityI = insulation

Geberit Silent-db20 (PE-S2)

(maximum thickness of sound decoupling: 9 mm)

Geberit 56 mm 3.2 mm CFS-C P 63/2” EI 120-U/U 63 mm 3.2 mm CFS-C P 63/2” EI 120-U/U75 mm 3.6 mm CFS-C P 75/2.5” EI 120-U/U90 mm 5.6 mm CFS-C P 90/3” EI 120-U/U110 mm 6.0 mm CFS-C P 110/4” EI 120-U/U

Wavin TS (PE-HD 100 RC)

(maximum thickness of sound decoupling: 9 mm)

Wavin 50 mm 4.6 mm CFS-C P 50/1.5” EI 90-U/U75 mm 6.8 mm CFS-C P 75/2.5” EI 120-U/U90 mm 8.2 mm CFS-C P 90/3” EI 120-U/U110 mm 10.0 mm CFS-C P 110/4” EI 120-U/U

PP

(maximum thickness of sound decoupling: 9 mm)

Geberit “Silent PP”Ostendorf “Skolan-dB”, “Phonex AS”, Pipelife “Master 3”, POLO-PLAST “Polo Kal NG”, POLOPLAST “Polo Kal 3S”, Rehau “Raupiano Plus”, Wavin “AS” /KeKelit “Phonex AS”, Wavin “SiTech”, Cloes “Blue Power”, Cloes “PhoNoFire”, Valsire “Triplus”, Valsire “Silere”, Marley “Silent”

32 mm 1,8 mm CFS-C P 50/1.5” EI 120-U/U40 mm 1,8 mm CFS-C P 50/1.5” EI 120-U/U50 mm 1,8–2,0 mm CFS-C P 50/1.5” EI 120-U/U56 mm 4,0 mm CFS-C P 63/2” EI 90-U/C70 mm 4,5 mm CFS-C P 75/2.5” EI 120-U/U75 mm 1,8–3,8 mm CFS-C P 75/2.5” EI 120-U/U90 mm 2,8–4,5 mm CFS-C P 90/3” EI 120-U/U110 mm 2,7–5,3 mm CFS-C P 110/4” EI 120 U/U

PP

(maximum thickness of sound decoupling: 9 mm

Aquatherm blue, Aquatherm blue Faserverbundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)Aquatherm green Faserverbundrohr, +GF+ PROGEF Stand-ard pipe, +GF+ Deka-prop Industry pipe

50 mm 1,8–2,9 mm CFS-C P 50/1.5” EI 90-U/U63 mm 1,8–5,8 mm CFS-C P 63/2” EI 60-U/U75 mm 1,9–6,8 mm CFS-C P 75/2,5” EI 60-U/U75 mm 6,8–12,5 mm CFS-C P 75/2.5” EI 120 U/U90 mm 8,2–15,0 mm CFS-C P 90/3” EI 120 U/U110 mm 2,7 mm CFS-C P 110/4” EI 120 U/U

Branded pipes – Pipe end configuration U/C

Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size ClassificationE = integrityI = insulation

PP

(maximum thickness of sound decoupling: 9 mm)

Aquatherm blue, Aquatherm blue Faserverbundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)Aquatherm green Faserverbundrohr, +GF+ PROGEF Stand-ard pipe, +GF+ Deka-prop Industry pipe

50 mm 4.6–8.3 mm CFS-C P 50/1.5” EI 90-U/C63 mm 5.8–10.5 mm CFS-C P 63/2” EI 60-U/C63 mm 10.5 mm CFS-C P 63/2” EI 120-U/C75 mm 1.9–6.8 mm CFS-C P 75/2.5” EI 60-U/C75 mm 6.8–12.5 mm CFS-C P 75/2.5” EI 120-U/C50 mm 4.6–8.3 mm CFS-C P 50/1.5” EI 90-U/C

Branded pipes – Pipe end configuration C/UPipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification

E = integrityI = insulation

Geberit Silent-db20 (PE-S2)

(maximum thickness of sound decoupling: 9 mm)

Geberit 135 mm 6.0 mm CFS-C P 160/6” EI 120-C/U160 mm 7.0 mm CFS-C P 160/6” EI 120-C/U

Page 8: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 14 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 15

Normed pipes

Pipe material Pipe norm Pipe diame-ter

Pipe wall thickness

Insulation thickness

Collar size ClassificationE = integrityI = insulation

Insulation configuration

PE EN 1519, EN 12201-2, EN 12666-1

110 mm 4.2 mm 10 mm CFS-C P 125/5” EI 90-U/U ContinuedInterrupted

110 mm 4.2 mm 25 mm CFS-C P 160/6” EI 90-U/U Continued sustained

PP EN ISO 15874DIN 8077/8078

40 mm 3.7–5.5 mm 9 mm CFS-C P 50/1.5” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 4.6–6.9 mm 9 mm CFS-C P 63/2” EI 120-U/C75 mm 6.8–10.3 mm 10 mm CFS-C P 90/3” EI 120-U/C110 mm 10.0–15.1 mm 10 mm CFS-C P 125/5” EI 120-U/C

Branded PipesPipe designation

Pipe manufacturer

Pipe diameter

Pipe wall thickness

Insulation thickness

Collar size ClassificationE = integrityI = insulation

Insulation configuration

PP Aquatherm blue, Aquatherm blue Faserver-bundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faserver-bundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)Aquatherm green Faserver-bundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe

40 mm 3.7 – 5.5 mm 9 mm CFS-C P 50/1.5” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 4.6 – 6.9 mm 9 mm CFS-C P 63/2” EI 120-U/C75 mm 6.8 – 10.3 mm 10 mm CFS-C P 90/3” EI 120-U/C90 mm 10.0 – 15.1

mm22.5 mm CFS-C P 125/5” EI 120-U/C

PP Aquatherm green

40 mm 3.7 mm 9 mm CFS-C P 50/1.5” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 4.6 mm 9 mm CFS-C P 63/2” EI 120-U/C75 mm 6.8 mm 10 mm CFS-C P 90/3” EI 120-U/C110 mm 10.0 mm 10 mm CFS-C P 125/5” EI 120-U/C

PP Aquatherm green Faser-verbund rohr

40 mm 5.5 mm 9 mm CFS-C P 50/1.5” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 6.9 mm 9 mm CFS-C P 63/2” EI 120-U/C75 mm 10.3 mm 10 mm CFS-C P 90/3” EI 120-U/C110 mm 15.1 mm 10 mm CFS-C P 125/5” EI 120-U/C

Wavin TS (PE-HD 100 RC)

Wavin 50 mm 4.6 mm 9 mm CFS-C P 63/2” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

63 mm 5.8 mm 10 mm CFS-C P 75/2.5” EI 120-U/C75 mm 6.8 mm 10 mm CFS-C P 90/3” EI 120-U/C90 mm 8.2 mm 10 mm CFS-C P 110/4” EI 120-U/C110 mm 10.0 mm 10 mm CFS-C P 125/5” EI 120-U/C

Friatherm starr (PVC-C)

Friatec 32 mm 3.6 mm 9 mm CFS-C P 50/1.5” EI 120-U/C Continued sustained or local sustained, length ≥ 200 mm

40 mm 4.5 mm 9 mm CFS-C P 63/2” EI 120-U/C50 mm 5.6 mm 9 mm CFS-C P 75/2.5” EI 120-U/C63 mm 7.1 mm 10 mm CFS-C P 90/3” EI 120-U/C

Rautitan flex (PE-Xa)

Rehau 40 mm 5.5 mm 9 mm CFS-C P 63/2” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 6.9 mm 9 mm CFS-C P 63/2” EI 120-U/C63 mm 8.6 mm 10 mm CFS-C P 75/2.5” EI 120-U/C

Aquatherm Climatherm Faserverbund-rohr (PP)

Aquatherm 40 mm 3.7 mm 9 mm CFS-C P 50/1.5” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 4.6 mm 9 mm CFS-C P 63/2” EI 120-U/C75 mm 6.8 mm 10 mm CFS-C P 90/3” EI 120-U/C110 mm 10.0 mm 10 mm CFS-C P 125/5” EI 120-U/C

Aquatherm Firestop (PP)

Aquatherm 40 mm 5.5 mm 9 mm CFS-C P 50/1.5” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 6.9 mm 9 mm CFS-C P 63/2” EI 120-U/C75 mm 10.3 mm 10 mm CFS-C P 90/3” EI 120-U/C110 mm 15.1 mm 10 mm CFS-C P 125/5” EI 120-U/C

PROGEF Standard pipe (PP)

+GF+ 40 mm 3.7 mm 9 mm CFS-C P 50/1.5” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 4.6 mm 9 mm CFS-C P 63/2” EI 120-U/C75 mm 6.8 mm 10 mm CFS-C P 90/3” EI 120-U/C110 mm 10.0 mm 10 mm CFS-C P 125/5” EI 120-U/C

Flexible and rigid walls ≥ 100 mm

1.3. Plastic pipes with foamed elastomeric insulation

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts.

Page 9: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 16 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 17

Branded pipes

Pipe designation and material

Pipe manufacturer

Pipe diameter

Pipe wall thickness

Insulation thickness

Collar size ClassificationE = integrityI = insulation

Insulation configuration

Geberit Mepla (PE-Xb/Al/ PE-HD)

Geberit 16 mm 2.0 mm 11.5 mm CFS-C P 50/1.5” EI 120-U/C Continued sustained32 mm 3.0 mm 13 mm CFS-C P 63/2” EI 120-U/C

40 mm 3.5 mm 9 mm CFS-C P 63/2” EI 120-U/C50 mm 4.0 mm 9 mm CFS-C P 63/2” EI 120-U/C63 mm 4.5 mm 10 mm CFS-C P 75/2.5” EI 60-U/C75 mm 4.7 mm 10 mm CFS-C P 90/3” EI 90-U/C

Rautitan stabil (PE-Xa/Al/ PE-HD)

Rehau 16 mm 2.6 mm 11.5 mm CFS-C P 50/1.5” EI 120-U/C Continued sustained32 mm 4.7 mm 13 mm CFS-C P 63/2” EI 120-U/C

40 mm 6.0 mm 9 mm CFS-C P 63/2” EI 120-U/CKELOX KM 110 (PE-X/Al/PE)

Ke Kelit 16 mm 2.0 mm 11.5 mm CFS-C P 50/1.5” EI 120-U/C Continued sustained32 mm 3.0 mm 13 mm CFS-C P 63/2” EI 120-U/C

32 mm 3.0 mm 9 mm CFS-C P 50/1.5” EI 90-U/C40 mm 4.0 mm 9 mm CFS-C P 50/1.5” EI 90-U/C50 mm 4.5 mm 9 mm CFS-C P 63/2” EI 90-U/C63 mm 6.0 mm 10 mm CFS-C P 75/2.5” EI 90-U/C

Flexible and rigid walls ≥ 100 mm

1.4. Composite pipes with foamed elastomeric insulation

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts.

2. Rigid walls

The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of:

Rigid walls (E) consisting of comprise concrete, aerated concrete or masonry, minimum density of 650 kg/m3, minimum thickness 150 mm. Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) or cementitious mortar over the entire thickness of the wall or Hilti Firestop Acrylic Sealant CFS-S ACR (A2) with a depth of minimum 15 mm from the surface of the wall. The sealant may be backfilled with mineral wool.

Maximum opening diameter: the opening should not be larger than the collar outside diameter to allow safe fixing of the collar to the wall. Minimum distance between collars (s1): 0 mm. Firestop collar (A1) fastened by hooks (F) (minimum number of hooks: see installation instructions) in flexible wall / drywall and low density rigid wall with M8 threaded rods through the wall secured with nuts on both sides. In high density rigid walls, metal anchors may be used as an alternative (e.g. Hilti HUS, DBZ, HSA). Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the wall. For maximum thickness see tables below.

Page 10: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 18 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 19

Rigid walls ≥ 150 mm

2.1. Plastic Pipes

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts.

Normed pipes – Pipe end configuration U/U

Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size ClassificationE = integrityI = insulation

PVC-U EN ISO 1452-2, EN ISO 15493, DIN 8061/2, EN 1329-1, EN 1453-1

180 mm 3.6–8.6 mm CFS-C P 180/7” EI 180-U/U200 mm 4.0–9.6 mm CFS-C P 200/8” EI 180-U/U225 mm 4.5–10.8 mm CFS-C P 225/9” EI 180-U/U250 mm 4.9–11.9 mm CFS-C P 250/10” EI 180-U/U

PE

(maximum thickness of sound decoupling: 5 mm)

EN 1519, EN 12201-2, EN 12666-1

200 mm 6.2 mm CFS-C P 200/8“ EI 120-U/U250 mm 7.8 mm CFS-C P 250/10“ EI 120-U/U

EN ISO 15494, DIN 8074/5

180 mm 4.4–16.4 mm CFS-C P 180/7” EI 120-U/U200 mm 4.9–11.4 mm CFS-C P 200/8” EI 120-U/U200 mm 11.4 mm CFS-C P 200/8” EI 180-U/U225 mm 5.5–12.8 mm CFS-C P 225/9” EI 180-U/U250 mm 6.2–14.2 mm CFS-C P 250/10” EI 180-U/U

Normed pipes – Pipe end configuration U/CPipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification

E = integrityI = insulation

PVC-U EN ISO 1452-2, EN ISO 15493, DIN 8061/2, EN 1329-1, EN 1453-1

50 mm 1.8 mm CFS-C P 50/1.5” EI 180-U/C250 mm 4.9–11.9mm CFS-C P 250/10” EI 180-U/C

PE

(maximum thickness of sound decoupling: 5 mm)

EN ISO 15494, DIN 8074/5

50 mm 2.9 mm CFS-C P 50/1.5” EI 180-U/C250 mm 7.8 mm CFS-C P 250/10” EI 180-U/C250 mm 7.8–22.7 mm CFS-C P 250/10” EI 120-U/C

Normed pipes – Pipe end configuration C/UPipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification

E = integrityI = insulation

PP

(maximum thickness of sound decoupling: 9 mm)

EN 1451-1DIN EN 12056

200 mm 6.2–6.8 mm CFS-C P 200/8” EI 120-C/U250 mm 8.6 mm CFS-C P 250/10” EI 120-C/U

Branded pipes – Pipe end configuration C/UPipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification

E = integrityI = insulation

PP

(maximum thickness of sound decoupling: 9 mm)

Geberit “Silent PP”Ostendorf “Skolan-dB”, “Phonex AS”, Pipelife “Master 3”, POLO-PLAST “Polo Kal NG”, POLOPLAST “Polo Kal 3S”, Rehau “Raupiano Plus”, Wavin "AS” / KeKelit “Phonex AS”, Wavin “SiTech”, Cloes “Blue Power”, Cloes “PhoNoFire”, Valsire “Triplus”, Valsire “Silere”,Marley “Silent”

200 mm 6.2–6.8 mm CFS-C P 200/8” EI 120-C/U250 mm 8.6 mm CFS-C P 250/10” EI 120-C/U

3. Rigid floors, minimum density of 2400 kg/m3

The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of:

Rigid floors (E) consisting of concrete with a minimum density of 2400 kg/m3, minimum thickness 150 mm. Penetration seal consists of a single penetration in the floor with Hilti Firestop Collar CFS-C P (A1) on the underside of the floor. Annular gap filled either with gypsum plaster or cementitious mortar (A3) over the entire thickness of the floor or with mineral wool of minimum density 60 kg/m3 covered by Hilti Firestop Acrylic Sealant CFS-S ACR (A2) on top side (or on both sides) with a depth of minimum 10 mm.

Classifications EI 120 and lower (opening diameter up to 300 mm), classification EI 180 (opening diameter up to 260 mm): The opening diameter should not be larger than the collar outside diameter to allow a safe fixing of the collar to the floor. Classifica-tion EI 180 (opening diameter > 260 mm): see in tables below.

Minimum distance between collars/annular gap edge (s1): 0 mm.

Firestop collar (A1) fastened by hooks (minimum number of hooks: see instructions for use) with metal anchors (e.g. Hilti HUS, DBZ, HSA) on the underside of the floor (minimum ∅ 6 mm up to collar size 110/4" and ∅ 10 mm for higher collar sizes).

Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the floor. For maximum thickness see tables below.

Page 11: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 20 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 21

Annular gap seal (drawings show non-insulated pipes as example)Gypsum plaster or cementitious mortar (A3)

Cementitious mortar (A3)together with sound decoupling (C1)

C1A3

Hilti Firestop Acrylic Sealant CFS-S ACR (A2)

Gypsum plaster or cementitious mortar (A3)

Hilti Firestop Acrylic Sealant CFS-S ACR (A2)

Pipe insulation(drawings show mortar as an example for the annular gap seal)Local/Sustained pipe insulation (LS) Continued/Sustained pipe insulation (CS)

3.1. Pre-insulated Pipes

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts.

Branded Pipes

Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size ClassificationE = integrityI = insulation

ABS/PUR insulation/PE-HD

+GF+ „COOL-FIT“ 90 mm 32 mm CFS-C P 90/3” EI 120-U/C110 mm 40 mm CFS-C P 110/4” EI 120-U/C110 mm 50 mm CFS-C P 110/4” EI 120-U/C160 mm 90 mm CFS-C P 160/6” EI 120-U/C180 mm 110 mm CFS-C P 180/7” EI 60-U/C225 mm 140 mm CFS-C P 225/9” EI 120-U/C250 mm 160 mm CFS-C P 250/10” EI 120-U/C

Rigid Floors ≥ 2400 kg/m3

Page 12: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 22 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 23

Normed pipes – Pipe end configuration U/U

Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size ClassificationE = integrityI = insulation

PE EN ISO 15494, DIN 8074/52 Pipes in 1 Collar

20 + 20 mm 1.9 mm CFS-C P 50/1.5” EI 90-U/U

20 + 20 mm 2.8 mm CFS-C P 50/1.5”

PP

(maximum thickness of sound decoupling: 9 mm)

EN ISO 15874DIN 8077/8078

20 mm 1.9–3.4 mm CFS-C P 50/1.5” EI 120-U/U50 mm 1.8–2.9 mm CFS-C P 50/1.5” EI 120-U/U63 mm 1.8–5.8 mm CFS-C P 63/2” EI 180-U/U75 mm 1.9–6.8 mm CFS-C P 75/2.5” EI 180-U/U90 mm 2.2–8.2 mm CFS-C P 90/3” EI 180-U/U110 mm 2.7 mm CFS-C P 110/4” EI 180-U/U125 mm 3.1 mm CFS-C P 125/5” EI 180-U/U

EN 1451-1 32 mm 1,2–1,8 mm CFS-C P 50/1.5” EI 90-U/U40 mm 1,8 mm CFS-C P 50/1.5”50 mm 1,8–2,0 mm CFS-C P 50/1.5”58 mm 4,0 mm CFS-C P 63/2”75 mm 1,9–4,5 mm CFS-C P 75/2.5”78 mm 4,5 mm CFS-C P 75/2.5”90 mm 2,8–4,5 mm CFS-C P 90/3”110 mm 2,7–5,3 mm CFS-C P 110/4”125 mm 3,9–5,3 mm CFS-C P 125/5”135 mm 5,3 mm CFS-C P 160/6”160 mm 4,9–5,3 mm CFS-C P 160/6”

Normed pipes – Pipe end configuration U/CPipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification

E = integrityI = insulation

PVC-U

(maximum thickness of sound decoupling: 5 mm)

EN ISO 1452-2, EN ISO 15493, DIN 8061/2, EN 1329-1, EN 1453-1

50 mm 1.8 mm CFS-C P 50/1.5” EI 180-U/C250 mm 4.0–11.9 mm CFS-C P 250/10”

PE

(maximum thickness of sound decoupling: 5 mm)

EN ISO 15494, DIN 8074/5

50 mm 2.9 mm CFS-C P 50/1.5” EI 180-U/C180 mm 4.4–16.4 mm CFS-C P 180/7” EI 120-U/C200 mm 4.9–11.4 mm CFS-C P 200/8” EI 120-U/C225 m 5.5–12.8 mm CFS-C P 225/9” EI 120-U/C250 mm 6.2–22.7 mm CFS-C P 250/10” EI 120-U/C250 mm 7.8 mm CFS-C P 250/10” EI 180-U/C

PP

(maximum thickness of sound decoupling: 9 mm)

EN ISO 15874DIN 8077/8078

40 mm 3.7–5.5 mm CFS-C P 50/1.5” EI 120-U/C50 mm 4.6–8.3 mm CFS-C P 50/1.5” EI 180-U/C63 mm 5.8–10.5 mm CFS-C P 63/2” EI 180-U/C75 mm 6.8 mm CFS-C P 75/2.5” EI 180-U/C75 mm 6.8–12.5 mm CFS-C P 75/2.5” EI 120-U/C90 mm 8.2 mm CFS-C P 90/3” EI 180-U/C90 mm 8.2–15.0 mm CFS-C P 90/3” EI 120-U/C110 mm 10.0–15.1 mm CFS-C P 110/4” EI 120-U/C

3.2. Plastic Pipes

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts.

Normed pipes – Pipe end configuration U/U

Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size ClassificationE = integrityI = insulation

PVC-U

(maximum thickness of sound decoupling: 5 mm)

EN ISO 1452-2, EN ISO 15493, DIN 8061/2, EN 1329-1, EN 1453-1

20 mm 1.5–2.2 mm CFS-C P 50/1.5” EI 120-U/U50 mm 2.4–5.6 mm CFS-C P 50/1.5”63 mm 3.0–4.7 mm CFS-C P 63/2”75 mm 2.2–3.6 mm CFS-C P 75/2.5”90 mm 2.7–4.3 mm CFS-C P 90/3”110 mm 1.8–8.1 mm CFS-C P 110/4”125 mm 3.7–6.0 mm CFS-C P 125/5”160 mm 2.5–11.8 mm CFS-C P 160/6”180 mm 3.6–8.6 mm CFS-C P 180/7”200 mm 4.0–9.6 mm CFS-C P 200/8”225 mm 4.5–10.8 mm CFS-C P 225/9”250 mm 4.9–11.9 mm CFS-C P 250/10”

PVC-C

(maximum thickness of sound decoupling: 5 mm)

EN 1566-1 20 mm 1.5 – 2.2 mm CFS-C P 50/1.5” EI 120-U/U50 mm 2.4 – 5.6 mm CFS-C P 50/1.5”63 mm 3.0 – 4.7 mm CFS-C P 63/2”75 mm 2.2 – 3.6 mm CFS-C P 75/2.5”90 mm 2.7 – 4.3 mm CFS-C P 90/3”110 mm 1.8 – 8.1 mm CFS-C P 110/4”125 mm 3.7 – 6.0 mm CFS-C P 125/5”160 mm 2.5 – 11.8 mm CFS-C P 160/6”180 mm 3.6 – 8.6 mm CFS-C P 180/7”200 mm 4.0 – 9.6 mm CFS-C P 200/8”225 mm 4.5 – 10.8 mm CFS-C P 225/9”250 mm 4.9 – 11.9 mm CFS-C P 250/10”

PE

(maximum thickness of sound decoupling: 5 mm)

EN 1519, EN 12201-2, EN 12666-1

50 mm 3.0 mm CFS-C P 50/1.5” EI 120-U/U63 mm 3.0 mm CFS-C P 63/2”75 mm 3.0 mm CFS-C P 75/2.5”90 mm 3.5 mm CFS-C P 90/3”110 mm 4.2 mm CFS-C P 110/4”125 mm 4.8 mm CFS-C P 125/5”160 mm 6.2 mm CFS-C P 160/6”200 mm 6.2 mm CFS-C P 200/8”250 mm 7.7 mm CFS-C P 250/10”

EN ISO 15494, DIN 8074/5

20 mm 1.9–2.8 mm CFS-C P 50/1.5” EI 90-U/U50 mm 2.9–4.6 mm CFS-C P 50/1.5” EI 120-U/U63 mm 1.8–5.8 mm CFS-C P 63/2” EI 120-U/U75 mm 1.9–6.8 mm CFS-C P 75/2.5” EI 120-U/U90 mm 2.2–8.2 mm CFS-C P 90/3” EI 120-U/U110 mm 2.7–10.0 mm CFS-C P 110/4” EI 120-U/U125 mm 3.1–7.1 mm CFS-C P 125/5” EI 120-U/U160 mm 4.0–9.1 mm CFS-C P 160/6” EI 120-U/U

Rigid Floors ≥ 2400 kg/m3

Page 13: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 24 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 25

Branded pipes – Pipe end configuration U/U

Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size ClassificationE = integrityI = insulation

Geberit Silent-db20 (PE-S2)

(maximum thickness of sound decoupling: 9 mm)

Geberit 75 mm 3.6 mm CFS-C P 75/2.5” EI 180-U/U90 mm 5.6 mm CFS-C P 90/3” EI 180-U/U110 mm 6.0 mm CFS-C P 110/4” EI 180-U/U135 mm 6.0 mm CFS-C P 160/6” EI 120-U/U160 mm 7.0 mm CFS-C P 160/6” EI 180-U/U

Wavin TS (PE-HD 100 RC)

(maximum thickness of sound decoupling: 9 mm)

Wavin 50 mm 4.6 mm CFS-C P 50/1.5” EI 90-U/U63 mm 5.8 mm CFS-C P 63/2” EI 120-U/U75 mm 6.8 mm CFS-C P 75/2.5” EI 120-U/U90 mm 8.2 mm CFS-C P 90/3” EI 120-U/U110 mm 10.0 mm CFS-C P 110/4” EI 120-U/U

PP

(maximum thickness of sound decoupling: 9 mm)

Geberit “Silent PP”Ostendorf “Skolan-dB”, “Phonex AS”, Pipelife “Master 3”, POLO-PLAST “Polo Kal NG”, POLOPLAST “Polo Kal 3S”, Rehau “Raupiano Plus”, Wavin “AS” /KeKelit “Phonex AS”, Wavin “SiTech”, Cloes “Blue Power”, Cloes “PhoNoFire”, Valsire “Triplus”, Valsire “Silere”, Marley “Silent”

32 mm 1,2–1,8 mm CFS-C P 50/1.5” EI 180-U/U40 mm 1,8 mm CFS-C P 50/1.5” EI 180-U/U50 mm 1,8–2,0 mm CFS-C P 50/1.5” EI 180-U/U58 mm 4,0 mm CFS-C P 63/2” EI 180-U/U75 mm 1,9–4,5 mm CFS-C P 75/2.5” EI 180-U/U78 mm 4,5 mm CFS-C P 75/2.5” EI 180-U/U90 mm 2,8–4,5 mm CFS-C P 90/3” EI 90-U/U110 mm 2,7–5,3 mm CFS-C P 110/4” EI 180-U/U125 mm 3,9–5,3 mm CFS-C P 125/5” EI 180-U/U135 mm 5,3 mm CFS-C P 160/6” EI 180-U/U160 mm 4,9–5,3 mm CFS-C P 160/6” EI 90-U/U

Magnaplast “Skolan-dB” pipes

(maximum thickness of sound decoupling: 9 mm)

Magnaplast 58 mm 4,0 mm CFS-C P 90/3” EI 180-U/U78 mm 4,5 mm CFS-C P 75/2.5”90 mm 4,5 mm CFS-C P 90/3”110 mm 5,3 mm CFS-C P 110/4”135 mm 5,3 mm CFS-C P 160/6”160 mm 5,3 mm CFS-C P 160/6”

Rehau “Raupiano Plus” pipes (PP/PP-MV/PP)

(maximum thickness of sound decoupling: 9 mm)

Rehau 50 mm 1,8 mm CFS-C P 50/1.5” EI 180-U/U75 mm 1,9 mm CFS-C P 75/2.5” EI 180-U/U110 mm 2,7 mm CFS-C P 110/4” EI 180-U/U

Wavin “AS” / KeKelit “Phonex AS” pipes

(maximum thickness of sound decoupling: 9 mm)

Wavin 70 mm 4,5 mm CFS-C P 75/2.5” EI 180-U/U90 mm 4,5 mm CFS-C P 90/3” EI 180-U/U125 mm 5,3 mm CFS-C P 125/5” EI 180-U/U160 mm 5,3 mm CFS-C P 160/6” EI 180-U/U

Wavin “SiTech” pipes

(maximum thickness of sound decoupling: 9 mm)

Wavin 75 mm 2,3 mm CFS-C P 75/2.5” EI 180-U/U90 mm 2,8 mm CFS-C P 90/3” EI 180-U/U125 mm 3,9 mm CFS-C P 125/5” EI 180-U/U160 mm 4,9mm CFS-C P 160/6” EI 180-U/U

PP

(maximum thickness of sound decoupling: 9 mm)

Aquatherm blue, Aqua-therm blue Faserver-bundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faser verbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe) Aquatherm green Faserverbundrohr, +GF+ PROGEF Stand-ard pipe, +GF+ Deka-prop Industry pipe

20 mm 1.9–3.4 mm CFS-C P 50/1.5” EI 120-U/U50 mm 1.8–2.9 mm CFS-C P 50/1.5” EI 180-U/U63 mm 1.8–5.8 mm CFS-C P 63/2” EI 180-U/U75 mm 1.9–6.8 mm CFS-C P 75/2.5” EI 180-U/U90 mm 2.2–8.2 mm CFS-C P 90/3” EI 180-U/U110 mm 2.7 mm CFS-C P 110/4” EI 180-U/U125 mm 3.1 mm CFS-C P 125/5” EI 180-U/U

Branded pipes – Pipe end configuration U/C

Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size ClassificationE = integrityI = insulation

PP

(maximum thickness of sound decoupling: 9 mm)

Aquatherm blue, Aquatherm blue Faserverbundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)Aquatherm green Faserverbundrohr, +GF+ PROGEF Stand-ard pipe, +GF+ Deka-prop Industry pipe

40 mm 3.7–5.5 mm CFS-C P 50/1.5” EI 120-U/C50 mm 4.6–8.3 mm CFS-C P 50/1.5” EI 180-U/C63 mm 5.8–10.5 mm CFS-C P 63/2” EI 180-U/C75 mm 6.8 mm CFS-C P 75/2.5” EI 180-U/C75 mm 6.8–12.5 mm CFS-C P 75/2.5” EI 120-U/C90 mm 8.2 mm CFS-C P 90/3” EI 180-U/C90 mm 8.2–15.0 mm CFS-C P 90/3” EI 120-U/C110 mm 10.0–15.1 mm CFS-C P 110/4” EI 120-U/C

Page 14: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 26 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 27

3.3. Plastic pipes with foamed elastomeric insulation

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts.

Normed pipes

Pipe material Pipe norm Pipe diameter

Pipe wall thickness

Insulation thickness

Collar size ClassificationE = integrityI = insulation

Insulation configuration

PP EN ISO 15874DIN 8077/8078

40 mm 3.7–5.5 mm 9 mm CFS-C P 63/2”” EI 180-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 4.6–6.9 mm 9 mm CFS-C P 75/2.5” EI 180-U/C75 mm 6.8–10.3 mm 10 mm CFS-C P 90/3” EI 180-U/C90 mm 12.3 mm 22.5 mm CFS-C P 160/6” EI 120-U/C110 mm 10.0–15.1 mm 10 mm CFS-C P 125/5” EI 180-U/C

Branded pipes Pipe designation

Pipe manufacturer

Pipe diameter

Pipe wall thickness

Insulation thickness

Collar size ClassificationE = integrityI = insulation

Insulation configuration

Wavin TS (PE-HD-100 RC)

WavinSupllier

50 mm 4.6 mm 9 mm CFS-C P 63/2” EI 180-U/C Continued sustained or local sustained, length ≥ 250 mm

63 mm 5.8 mm 10 mm CFS-C P 75/2.5”75 mm 6.8 mm 10 mm CFS-C P 90/3”90 mm 8.2 mm 9.5 mm CFS-C P 110/4”110 mm 10.0 mm 9.5 mm CFS-C P 125/5”

Friatherm starr (PVC-C)

Friatec 32 mm 3.6 mm 9 mm CFS-C P 50/1.5” EI 180-U/C Continued sustained or local sustained, length ≥ 200 mm

40 mm 4.5 mm 9 mm CFS-C P 63/2”50 mm 5.6 mm 9 mm CFS-C P 75/2.5”63 mm 7.1 mm 10 mm CFS-C P 90/3”

Rautitan flex (PE-Xa)

Rehau 40 mm 6.0 mm 9 mm CFS-C P 63/2” EI 180-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 6.9 mm 9 mm CFS-C P 75/2.5” EI 180-U/C63 mm 8.6 mm 9 mm CFS-C P 90/3” EI 180-U/C40 mm 6.0 mm 9–20.5 mm CFS-C P 63/2”–

75/2.5”EI 120-U/C

50 mm 6.9 mm 9–21 mm CFS-C P 75/2.5”–90/3”

EI 120-U/C

63 mm 8.6 mm 9–21.5 mm CFS-C P 90/3”–110/4“

EI 120-U/C

PP Aquatherm blue, Aquatherm blue Faserver-bundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faserver-bundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)Aquatherm green Faserver-bundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe

40 mm 3.7–5.5 mm 9 mm CFS-C P 63/2” EI 180-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 4.6–6.9 mm 9 mm CFS-C P 75/2.5” EI 180-U/C75 mm 6.8–10.3 mm 10 mm CFS-C P 90/3” EI 180-U/C90 mm 12.3 mm 22.5 mm CFS-C P 160/6” EI 120-U/C110 10.0–15.1 mm 10 mm CFS-C P 125/5” EI 180-U/C

Rigid Floors ≥ 2400 kg/m3

3.4. Composite pipes

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts.

Branded pipes

Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size ClassificationE = integrityI = insulation

Geberit Mepla (PE-Xb/Al/PE-HD)

(maximum thickness of sound decoupling: 9 mm)

Geberit 40 mm 3.5 mm CFS-C P 50/1.5” EI 90-U/C50 mm 4.0 mm CFS-C P 50/1.5” EI 120-U/C63 mm 4.5 mm CFS-C P 63/2” EI 60-U/C75 mm 4.7 mm CFS-C P 75/2.5” EI 30-U/C110 mm 6.0 mm CFS-C P 110/4” EI 180-U/U

Rigid Floors ≥ 2400 kg/m3

Page 15: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 28 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 29

Branded Pipes Pipe designation

Pipe manufacturer

Pipe diameter

Pipe wall thickness

Insulation thickness

Collar size ClassificationE = integrityI = insulation

Insulation configuration

Geberit Mepla (PE-Xb/Al/ PE-HD)

Geberit 40 mm 3.5 mm 9 mm CFS-C P 63/2” EI 180-U/C Continued sustained or local sustained, length ≥ 250 mm

50 mm 4.0 mm 9 mm CFS-C P 63/2”63 mm 4.5 mm 9 mm CFS-C P 75/2.5”75 mm 4.7 mm 10 mm CFS-C P 90/3”

Geberit Mepla (PE-Xb/Al/ PE-HD)

Geberit 40 mm 3.5 mm 9 – 20.5 mm CFS-C P 63/2”–75/2.5”

EI 120-U/C

50 mm 4.0 mm 9 – 21 mm CFS-C P 63/2”–90/3”

63 mm 4.5 mm 9 – 21.5 mm CFS-C P 75/2.5”–110/4”

75 mm 4.7 mm 10 – 22 mm CFS-C P 90/3”–125/5”

KELOX KM 110” (PE-X/Al/PE-X)

KeKelit 32 mm 3.0 mm 9 mm CFS-C P 50/1.5” EI 180-U/C Continuated Sustained40 mm 4.0 mm 9 mm CFS-C P 50/1.5” EI 180-U/C

50 mm 4.5 mm 9 mm CFS-C P 63/1.5” EI 180-U/C63 mm 6.0 mm 10 mm CFS-C P 75/2.5” EI 120-U/C

KELOX KM 110” (PE-X/Al/PE-X)

KeKelit 32 mm 3.0 mm 9 – 19.5 mm CFS-C P 50/1.5”– 75/2.5”

EI 120-U/C Continuated Sustained

40 mm 4.0 mm 9 – 20.5 mm CFS-C P 50/1.5”– 75/2.5”

50 mm 4.5 mm 9 – 21 mm CFS-C P 63/2”–90/3”

63 mm 6.0 mm 10 – 21.5 mm

CFS-C P 75/2.5”–110/4”

KELOX KM 110” (PE-X/Al/PE-X)

KeKelit 32 mm 3.0 mm 19.5 mm CFS-C P 75/2.5” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

40 mm 4.0 mm 20.5 mm CFS-C P 75/2.5”50 mm 4.5 mm 21 mm CFS-C P 90/3”63 mm 6.0 mm 21.5 mm CFS-C P 110/4”

Rautitan stabil (PE-Xa//Al/PE-HD)

Rehau 40 mm 6.0 mm 9 mm CFS-C P 63/2” EI 180-U/C Continued sustained or local sustained, length ≥ 250 mm

40 mm 6.0 mm 9-20.5 mm CFS-C P 63/2”–75/2.5”

EI 120-U/C

3.5. Composite pipes with foamed elastomeric insulation

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts.

Rigid floors ≥ 2400 kg/m3 4. Rigid floors, minimum density of 550 kg/m3

The floor must have a minimum thickness of 150 mm and comprise concrete or aerated concrete with a minimum density of 550 kg/m3.

For details of the penetration seal design see 3.

Pipes shall be supported at maximum 200 mm at maximum 250 mm away from the upper face of the floor construction.

4.1. Pre-insulated Pipes

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts.

4.2. Plastic Pipes

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts

Branded pipes

Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size ClassificationE = integrityI = insulation

ABS/PUR insulation/PE-HD

+GF+ „COOL-FIT“ 90 mm 32 mm CFS-C P 90/3” EI 120-U/C110 mm 40 mm CFS-C P 110/4” EI 120-U/C110 mm 50 mm CFS-C P 110/4” EI 120-U/C160 mm 90 mm CFS-C P 160/6” EI 120-U/C180 mm 110 mm CFS-C P 180/7” EI 60-U/C225 mm 140 mm CFS-C P 225/9” EI 120-U/C250 mm 160 mm CFS-C P 250/10” EI 120-U/C

Normed pipes – Pipe end configuration U/U

Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size ClassificationE = integrityI = insulation

PVC-U EN ISO 1452-2, EN ISO 15493, DIN 8061/2, EN 1329-1, EN 1453-1Pipe End Configuration U/U

20 mm 1.5–2.2 mm CFS-C P 50/1.5” EI 120-U/U

50 mm 2.4–5.6 mm CFS-C P 50/1.5” EI 120-U/U

PE EN ISO 15494, DIN 8074/5Pipe End Configuration U/U

20 mm 1.9–2.8 mm CFS-C P 50/1.5” EI 90-U/U

50 mm 2.9–4.6 mm CFS-C P 50/1.5” EI 90-U/U

EN ISO 15494, DIN 8074/52 Pipes in 1 Collar

20+20 mm 1.9 mm CFS-C P 50/1.5” EI 90-U/U

20+20 mm 2.8 mm CFS-C P 50/1.5” EI 90-U/U

PP

(maximum thickness of sound decoupling: 9 mm)

EN ISO 15874DIN 8077/8078

20 mm 1.9–3.4 mm CFS-C P 50/1.5” EI 120-U/U

Rigid Floors ≥ 550 kg/m3

Rigid Floors ≥ 550 kg/m3

Page 16: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 30 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 31

Normed pipes – Pipe end configuration U/C

Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size ClassificationE = integrityI = insulation

PP

(maximum thickness of sound decoupling: 9 mm)

EN ISO 15874DIN 8077/8078

40 mm 3.7–5.5 mm CFS-C P 50/1.5” EI 120-U/C50 mm 4.6–6.9 mm CFS-C P 50/1.5”75 mm 6.8 mm CFS-C P 75/2.5”90 mm 12.3 mm CFS-C P 90/3”110 mm 10.0–15.1 mm CFS-C P 110/4”

Branded pipes – Pipe end configuration U/UPipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification

E = integrityI = insulation

Geberit Silent-db20 (PE-S2)

(maximum thickness of sound decoupling: 9 mm)

56 3.2 CFS-C P 63/2” – 75/2.5”

EI 180-U/U

63 3.2 CFS-C P 63/2” – 75/2.5”

110 6.0 CFS-C P 110/4”

Wavin TS (PE-HD-100 RC)

(maximum thickness of sound decoupling: 9 mm)

Wavin 50 mm 4.6 mm CFS-C P 50/1.5” EI 90-U/U63 mm 5.8 mm CFS-C P 63/2” –

75/2.5”EI 120-U/U

75 mm 6.8 mm CFS-C P 75/2.5” EI 120-U/U90 mm 8.2 mm CFS-C P 90/3” EI 120-U/U110 mm 10.0 mm CFS-C P 110/4” EI 120-U/U

Master 3 (PP-CO/PP-MV/PP-CO)

(maximum thickness of sound decoupling: 9 mm)

Pipelife 32 mm 1.2 mm CFS-C P 50/1.5” EI 90-U/U40 mm 1.8 mm CFS-C P 50/1.5”50 mm 1.8 mm CFS-C P 50/1.5”75 mm 1.8 mm CFS-C P 75/2.5”110 mm 1.8 mm CFS-C P 110/4”

Polo Kal 3S (PP/PP-MV/PP)

(maximum thickness of sound decoupling: 9 mm)

POLOPLAST 75 mm 3.8 mm CFS-C P 75/2.5” EI 90-U/U90 mm 4.5 mm CFS-C P 90/3”110 mm 4.8 mm CFS-C P 110/4”

Polo Kal NG (PP-CO/PP-MV/PP-CO)

(maximum thickness of sound decoupling: 9 mm)

POLOPLAST 32 mm 1.8 mm CFS-C P 50/1.5” EI 90-U/U40 mm 1.8 mm CFS-C P 50/1.5”50 mm 2.0 mm CFS-C P 50/1.5”75 mm 2.6 mm CFS-C P 75/2.5”90 mm 3.0 mm CFS-C P 90/3”110 mm 3.6 mm CFS-C P 110/4”

PP

(maximum thickness of sound decoupling: 9 mm)

Aquatherm blue, Aquatherm blue Faserverbundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)Aquatherm green Faserverbundrohr, +GF+ PROGEF Stand-ard pipe, +GF+ Deka-prop Industry pipe

20 mm 1.9 – 3.4 mm CFS-C P 50/1.5” EI 120-U/U

Branded pipes – Pipe end configuration U/C

Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size ClassificationE = integrityI = insulation

PP

(maximum thickness of sound decoupling: 9 mm

Aquatherm blue, Aquatherm blue Faserverbundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)Aquatherm green Faserverbundrohr, +GF+ PROGEF Stand-ard pipe, +GF+ Deka-prop Industry pipe

40 mm 3.7–5.5 mm CFS-C P 50/1.5” EI 120-U/C50 mm 4.6–6.9 mm CFS-C P 50/1.5”75 mm 6.8 mm CFS-C P 75/2.5”90 mm 12.3 mm CFS-C P 90/3”110 mm 10.0–15.1 mm CFS-C P 110/4”

Branded pipes – Pipe end configuration U/CPipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification

E = integrityI = insulation

Polo Kal NG (PP-CO/PP-MV/PP-CO)

(maximum thickness of sound decoupling: 9 mm)

POLOPLAST 200 mm 6.8 mm CFS-C P 200/8” EI 180-U/CEI 180-U/C250 mm 8.6 mm CFS-C P 250/10”

Page 17: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 32 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 33

Normed pipes – Pipe end configuration U/CPipe material Pipe norm Pipe

diameter Pipe wall thickness

Insulation thickness

Collar size ClassificationE = integrityI = insulation

Insulation configuration

PP EN ISO 15874DIN 8077/8078

90 mm 12.3 mm 22.5 mm CFS-C P 160/6” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

110 mm 15.1 mm 10 mm CFS-C P 125/5” EI 120-U/C

Branded pipes – Pipe end configuration U/CPipe designation

Pipe manufacturer

Pipe diameter

Pipe wall thickness

Insulation thickness

Collar size ClassificationE = integrityI = insulation

Insulation configuration

Rautitan flex (PE-Xa)

Rehau 40 mm 6.0 mm 20.5 mm CFS-C P 63/2”–75/2.5”

EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm50 mm 6.9 mm 21 mm CFS-C P 75/2.5–

90/3”EI 120-U/C

63 mm 8.6 mm 21.5 mm CFS-C P 110/4” EI 120-U/CAquatherm ClimathermFaserverbund-rohr

Aquatherm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6” EI 120-U/C

110 mm 15.1 mm 10 mm CFS-C P 125/5” EI 120-U/C

Aquatherm FusiothermFaserverbund-rohr

Aquatherm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6” EI 120-U/C

110 mm 15.1 mm 10 mm CFS-C P 125/5” EI 120-U/C

Aquatherm Firestop

Aquatherm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6” EI 120-U/C110 mm 15.1 mm 10 mm CFS-C P 125/5” EI 120-U/C

4.3. Plastic Pipes with foamed elastomeric insulation

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts.

Rigid Floors ≥ 550 kg/m3

4.4. Composite pipes

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts.

Branded pipes – Pipe end configuration U/C

Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size ClassificationE = integrityI = insulation

Geberit Mepla (PE-Xb/Al/PE-HD)

Geberit 40 mm 3.5 mm CFS-C P 50/1.5” EI 90-U/C50 mm 4.0 mm CFS-C P 50/1.5” EI 120-U/C63 mm 4.5 mm CFS-C P 63/2” EI 60-U/C75 mm 4.7 mm CFS-C P 75/2.5” EI 30-U/C

Branded pipes – Pipe end configuration U/CPipe designation

Pipe manufacturer

Pipe diameter

Pipe wall thickness

Insulation thickness

Collar size ClassificationE = integrityI = insulation

Insulation configuration

Geberit Mepla (PE-Xb/Al/ PE-HD)

Geberit 40 mm 3.5 mm 20.5 mm CFS-C P 63/2”–75/2.5”

EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm50 mm 4.0 mm 21 mm CFS-C P 63/2”–

90/3”EI 120-U/C

63 mm 4.5 mm 21.5 mm CFS-C P 75/2.5”–110/4”

EI 120-U/C

75 mm 4.7 mm 22 mm CFS-C P 90/3”–125/5”

EI 120-U/C

KELOX KM 110” (PE-X/Al/PE-X)

KeKelit 32 mm 3.0 mm 19.5 mm CFS-C P 75/2.5” EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

40 mm 4.0 mm 20.5 mm CFS-C P 75/2.5” EI 120-U/C50 mm 4.5 mm 21 mm CFS-C P 90/3” EI 120-U/C63 mm 6.0 mm 21.5 mm CFS-C P 110/4” EI 120-U/C

Rautitan stabil (PE-Xa/Al/ PE-HD)

Rehau 40 mm 6.0 mm 20.5 mm CFS-C P 63/2”–75/2.5”

EI 120-U/C Continued sustained or local sustained, length ≥ 250 mm

4.5. Composite pipes with foamed elastomeric insulation

Minimum distance between pipe closure devices: 0 mm.

Hilti Firestop Collar CFS-C P (A3) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts.

Rigid Floors ≥ 550 kg/m3

Rigid Floors ≥ 550 kg/m3

Page 18: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 34 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 35

Loose mineral wool products suitable for being used as backfilling material of CFS-S ACR Firestop Acrylic Sealant:

Product Manufacturer

Heralan LSIsover loose wool SLIsover Universal-StopfwolleRockwool RLParoc Pro Loose Wool

Knauf InsulationSaint-Gobain IsoverSaint-Gobain IsoverRockwoolParoc OY AB

Suitable insulation products; Combustible insulation (closed cell flexible elastomeric foam, e.g. AF/Armaflex). Reaction to fire minimum B-s3, d0 (acc. to EN 13501-1) Combustible insulation for sound decoupling ( elastomeric foam, e.g. PE). Reaction to fire minimum E (acc. to EN 13501-1)

Hilti Firestop acrylic sealant CFS-S ACR

Applications n Within or between flexible wall constructions n Vertical joints in / between wall constructions n Horizontal joints in a wall abutting a floor, ceiling or roof n Joints in floor construction n Penetration seals (steel and copper pipes)

An acrylic based firestop sealant that provides movement capability in fire rated linear joint seals and penetration seals

Advantages n Easy to dispense, apply and tool n Strong adhesion to various base materials n Low shrinkage after curing n Excellent airborne sound insulation property n Broad application temperature range

* The European Technical Approval (ETA) can be obtained via your local Hilti contact or www.hilti.com

Packaging Volume Color Order designation Sales Quantity Item Number

Cartridge 310 ml White Firestop acrylic sealant CFS-S ACR 1 pc 00435859Cartridge 310 ml White Firestop acrylic sealant CFS-S ACR 1 pc 00435860Cartridge 310 ml Grey Firestop acrylic sealant CFS-S ACR 1 pc 00435862Foil pack 580 ml White Firestop acrylic sealant CFS-S ACR 20 pc 00435863Pail 5 l White Firestop acrylic sealant CFS-S ACR 1 pc 00435864Pail 10 l White Firestop acrylic sealant CFS-S ACR 1 pc 02046766

Technical dataCFS-S ACR

Chemical basis Water-based acrylic dispersionVolume shrinkage < 20 %Movement 12.5 % (ISO 11600)Cure Time (at 23° C / 50 % r.H.) ~ 3 mm / 72 hApplication temperature range 5° C – 40° CStorage and transportation temperature - range

5° C – 25° C

Shelf life (@73° F / 23° C and 50 % relative humidity)

24 month(s)

Reaction to fire class D-s1d0 (EN13501-1)Approvals* ETA 10 / 0292, ETA 10 / 0389

Page 19: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P

page 36 Hilti Firestop Collar CFS-C P | Issue 02/2015 Hilti Firestop Collar CFS-C P | Issue 02/2015 page 37

Installation instructions

Clean opening. Surfaces to which CFS-S ACR will be applied should be dry, cleaned of loose debris, dirt, oil, wax and grease. Use wire brushing for cleaning.

Notes on Cleaning:

• Surfaces with cured acrylic sealant can only be cleaned mechanically e.g. using a knife, but not with a solvent.

• Remove uncured sealant first mechanically then clean with water.

• CFS-S ACR cannot be completely cleaned off porous surfaces – joints may be taped off to avoid staining.

• Dispenser equipment and tools have to be cleaned if a work break lasts longer than approximately 20 minutes.

Insert backing material if required. Make sure proper backing material is used and compressed according European Technical Approval (see ETA Annex)

Apply CFS-S ACR using a dispenser.

CFS-S ACR adheres to most substrates (concrete, masonry, drywall, plaster, etc.) without using a primer. For best adhesion on porous substrates, use CFS-S ACR diluted with water as primer. Other primers are not necessary.

Smooth joint with water using a narrow spatula or finger.

Joint Penetration

Charecteristics Assessment of charecteristics Norm, standard, test

Health and the environmentAir permeability(gas thightness)Water permeability

Air tightness / smoke tightness and water tightness for a single penetration of a plastic pipe firestopped with Hilti Firestop Collar CFS-C P can be achieved when the annular gap is sealed with Hilti Firestop Acrylic Seal-ant CFS-S ACR (10 mm thickness).q/A [m3/(h x m2)] at Δ p 50 Pa / Δ p 250 PaAir: 1.9 x 10-6 / 9.7 x 10-6

Nitrogen: 1.1 x 10-6 / 5.5 x 10-6

CO2: 6.4 x 10-5 / 3.2 x 10-4

Methane: 4.3 x 10-5 / 2.1 x 10-4

EN 1026

Watertight to 1m head of water or 9806 Pa ETAG 026-2

Dangerous substances CFS-C P is in compliance concerning the registration, evaluation, authorization and re-striction of Chemicals (REACH).The product does not contain any constitu-ents contained in the list of dangerous sub-stances of the European Commission above the acceptable limits.

Material safety data sheet

Protection against noise(Air borne sound insulation)

The following airborne sound insulation for a single penetration of plastic pipe firestopped with Hilti Firestop Collar CFS-C can be achieved when the annular gap is sealed: with Hilti Firestop Acrylic Sealant CFS-S ACR:Flexible wall Rw = 53 dB Dn,w = 60 dB Rigid wall Rw = 51 dB Dn,w = 58 dB

with cementitious mortar: Rigid wall Rw = 52 dB Dn,w = 59 dB

EN ISO 140-3EN ISO 20140-10EN ISO 717-1

Durability and serviceability Category Z2 (suitable for penetration seals intended for use in dry indoor conditions excluding temperatures below 0° C).

ETAG 026-2 and 3

Reaction to fire Class E EN 13501-1

Characteristics of CFS-C PAdditional Attributes

Hilti firestop products are comprehensively tested and individually matched to the technical requirements of a building’s mechanical installations. In addition to their superior passive fire protection behavior, Hilti firestop products also meet increasingly significant requirements in building technology and also help designers and installers to meet these additional requirements. The assessment of fitness for use has been made in accordance with EOTA ETAG No 026 – Part 2.

Service

With more than 20 years of experience worldwide, Hilti is one of the leading suppliers of firestop systems. We actively help you manage your firestop projects better by providing:• Quick engineering judgements• Extensive technical literature• On-site training and demonstration• Sophisticated jobsite logistics• Assurance of conformity with specific application requirements• International network of Hilti firestop specialists

Our network of experienced sales representatives, field engineers, firestop specialists and customer service representatives is just a phone call away (use the local toll-free Hilti number).

Bauchemie Piktos_neu.ai05.11.2007

SchallschutzRauch- und Gasdichtigkeit

Wasserbeständigkeit Elektische

30years

30Jahre

45%

Dampfdichtigkeit Wärmedämmend

Air-seal/Luftdichtheit

dBritish StandarBS 476

C US

FMAPPROVED

FMFactory Mutual

Bauchemie Piktos_neu.ai05.11.2007

SchallschutzRauch- und Gasdichtigkeit

Wasserbeständigkeit Elektische

30years

30Jahre

45%

Dampfdichtigkeit Wärmedämmend

Air-seal/Luftdichtheit

dBritish StandarBS 476

C US

FMAPPROVED

FMFactory Mutual

Bauchemie Piktos_neu.ai05.11.2007

SchallschutzRauch- und Gasdichtigkeit

Wasserbeständigkeit Elektische

30years

30Jahre

45%

Dampfdichtigkeit Wärmedämmend

Air-seal/Luftdichtheit

dBritish StandarBS 476

C US

FMAPPROVED

FMFactory Mutual

Page 20: Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti ... · Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P | Issue 02/2015 page 1 Technical Data Sheet Hilti Firestop

Hilti Firestop Collar CFS-C P

page 38 Hilti Firestop Collar CFS-C P | Issue 02/2015Hilti Corporation | 9494 Schaan | Liechtenstein | P +423-234 2111 | F +423-234 2965 | www.hilti.com

Hilti. Outperform. Outlast.

Hilti

= re

gist

ered

trad

emar

k of

Hilt

i Cor

p., S

chaa

n I 

W 4

303

021

5 0

-en 

I 2

Prin

ted

in L

iech

tens

tein

 I ©

201

3 I 

Righ

t of t

echn

ical

and

pro

gram

me

chan

ges

rese

rved

S. E

. & O

.