01-02-2017 Skymax ® CE Smoke and Heat Extraction system for staircases CE approved according to EN 12101-2 and in conformity with NBN S21-208 TECHNICAL FILE SKYLIGHTS

Upload: others

Post on 24-Mar-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TECHNICAL FILE Skymax CE - Optilite · 2019. 7. 19. · 01-02-2017 3/4 E_TD_TECHNICAL_FILE_SKYLUX_SKYMAX_CE CE specifications according to EN 12101-2 for Skymax® CE * always ask

01-02-2017

Skymax® CESmoke and Heat Extraction systemfor staircasesCE approved according to EN 12101-2

and in conformity with NBN S21-208

TECHNICAL FILE

SKYLIGHTS

Page 2: TECHNICAL FILE Skymax CE - Optilite · 2019. 7. 19. · 01-02-2017 3/4 E_TD_TECHNICAL_FILE_SKYLUX_SKYMAX_CE CE specifications according to EN 12101-2 for Skymax® CE * always ask

E_TD_TECHNICAL_FILE_SKYLUX_SKYMAX_CE 01-02-20172/4

General product descriptionThe Skymax® CE dome exists of:- An acrylic or polycarbonate Skylux® dome* in conformity with EN, composed according to the Skylux®

specifications- A curb in PVC (type 16/00 or 30/20) or metal, which is part of the CE agreement of the SHEV system (see

pictures below)- A PVC frame (standard, EP or EP25) or with a Skylux® Window with glass (exceptional low U value), which is part

of the CE certification- External support sheets with accessories for PVC curbs- Two opening system with 24 Volt actuators

Complementary:- One central detection unit type Skycom® Skymax CE (installation on top in the staircase)- A priority switch- Inner spoilers (optional to improve the aerodynamic coefficient Cv)- The positive safety can be disconnected

Advantages

* Skylux® domes have a CE agreement according to EN 1873:2014+A1:2016** Ut: U (transparant) or insulation value of the Skylux® dome according to EN 1873:2014+A1:2016, determined in accordance with EN 673

Skymax® CE

- Free access to the roof- Exceptional insulation (Ut** value up to 0.50 W/m².K)- Air permeability class 2 according to EN 1873:2014+A1:2016- RW value up to 40 dB- 100 % thermal break- Skylux® quick-mount concept- Easy installation- CE approved according to EN 12101-2

Page 3: TECHNICAL FILE Skymax CE - Optilite · 2019. 7. 19. · 01-02-2017 3/4 E_TD_TECHNICAL_FILE_SKYLUX_SKYMAX_CE CE specifications according to EN 12101-2 for Skymax® CE * always ask

01-02-20173/4

E_TD_TECHNICAL_FILE_SKYLUX_SKYMAX_CE

CE specifications according to EN 12101-2 for Skymax® CE

* always ask for the aerodynamic coefficient determined by lateral wind

Product description actuatorThe Skymax® CE is a dome for smoke and heat extraction equipped with a daily ventilation function. On alarm, the dome fully opens diagonally away from the upstand. The opening of the dome in open position is 900 mm horizontally and 570 mm vertically. The two actuators are equipped with an electric final course, which states the maximum course of the actuator on opening and closing.

Specific characteristics opening mechanism

Product description central detection unit

The Skymax® CE is operated by a Skycom® Skymax CE central detection unit and a heat detector. This detection unit is equipped with several connection possibilities. The detection unit has an autonomy of at least 72h with tension due the incorporated batteries. The central detection unit must be equipped with a priority switch to operate the SHE systemin case of emergency.

Time until full opening ....................................................... < 60 secMin. functioning temperature (°C)....................... -15 °C Heat resistance (°C) ............................................................. B300 Snow load (N/m²) ..................................................................... SL 300 to SL 900Wind load (N/m²) ..................................................................... WL 1500Reliability class SHE.............................................................. Re 1000Durability ......................................................................................... Re 10.000 Aerodynamic coefficient* ............................................. 0.60 - 0.77Maximum slope ......................................................................... 10°

Tension ............................................................................................... 24 V DC - 48 V DCCurrent .............................................................................................. nominal 5 A (per system) at 24 VOpening angle ............................................................................ entirely (180°)Final course ................................................................................... electronicDensity ............................................................................................... IP 54Certification ................................................................................ CE volgens EN 12101-2Execution mechanism ........................................................ galvanisedExecution housing .................................................................. powder-coated white

Page 4: TECHNICAL FILE Skymax CE - Optilite · 2019. 7. 19. · 01-02-2017 3/4 E_TD_TECHNICAL_FILE_SKYLUX_SKYMAX_CE CE specifications according to EN 12101-2 for Skymax® CE * always ask

E_TD_TECHNICAL_FILE_SKYLUX_SKYMAX_CE 01-02-20174/4

SKYLUX IS A REGISTERED BRAND OF AG.PLASTICSSPINNERIJSTRAAT 100 - B-8530 STASEGEMT +32 (0)56 20 00 00 - F +32 (0)56 21 95 [email protected]

Curb combinations

Sizes and opening direction

UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN MILLIMETERS

ANGLES ±X.X° 2 PL ±X.XX 3 PL ±X.XXX

2/04/2014

TITLE:

A2 1

FILE NAME: Skymax 3020 open Skylux dome.dft

SCALE: SHEET 1 OF 1

Designer

Material

Mass

VolumeSurfaceIxx

Datetods0,000000 kg.mm^2

0,00 dm^30,000 kg

Density

23/06/2014Last modification on

REV

REVISION HISTORYDESCRIPTION DATE APPROVED

A A

SECTION A-A

SKYMAX CE ELECTRIC 30-20 OPENSkylux dome

843

590

860140

front view side view

top view

cross section

perspective

B

C

EF

G B'

C'

D

1000

1200

1000

1200

300

D

3

1

3

4 5

100

PVC 30-20 B B' C C' D E F G100 x 100 1000 1000 1200 1200 300 860 140 59080 x 130 800 1300 1000 1500 300 860 -60 59090 x 120 900 1200 1100 1400 300 860 40 590120 x 120 1200 1200 1400 1400 300 860 340 590

2

6 6

1 dome2 curb3 frame4 actuator right5 actuator left6 supporting plate

UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN MILLIMETERS

ANGLES ±X.X° 2 PL ±X.XX 3 PL ±X.XXX

2/04/2014

TITLE:

A2 1

FILE NAME: Skymax M30 open Skylux dome.dft

SCALE: SHEET 1 OF 1

Designer

Material

Mass

VolumeSurfaceIxx

Datetods0,000000 kg.mm^2

0,00 dm^30,000 kg

Density

19/06/2014Last modification on

REV

REVISION HISTORYDESCRIPTION DATE APPROVED

A A

SECTION A-A

SKYMAX CE ELECTRIC M30 OPENSkylux dome

1000 1000

1000 1000

front view side view

top view

cross section

perspective

B

C

EF

G B'

C'

860140

590

843

D300

6

12345

domecurbframe actuator rightactuator left

1

2

3

4 5

100

M30 B B' C C' D E F G100 x 100 1000 1000 1000 1000 300 860 140 59080 x 130 800 1300 800 1300 300 860 -60 59090 x 120 900 1200 900 1200 300 860 40 590120 x 120 1200 1200 1200 1200 300 860 340 590

with PVC curb 16/00min 300 mm total height

with PVC curb 30/20 with metal curb M30 or higher

UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN MILLIMETERS

ANGLES ±X.X° 2 PL ±X.XX 3 PL ±X.XXX

2/04/2014

TITLE:

A2 1

FILE NAME: Skymax 1600 open Skylux dome.dft

SCALE: SHEET 1 OF 1

Designer

Material

Mass

VolumeSurfaceIxx

Datetods0,000000 kg.mm^2

0,00 dm^30,000 kg

Density

23/06/2014Last modification on

REV

REVISION HISTORYDESCRIPTION DATE APPROVED

A A

SECTION A-A

SKYMAX CE ELECTRIC 16-00 OPENSkylux dome

front view side view

top view

cross section

B

EF

G B'

C'

1000

1000 1000

1000

C

300

D

860140

590

840

1

1

2

3

4

5

100

PVC 16-00 B B' C C' D E F G100 x 100 1000 1000 1000 1000 300 860 140 59080 x 130 800 1300 800 1300 300 860 -60 59090 x 120 900 1200 900 1200 300 860 40 590120 x 120 1200 1200 1200 1200 300 860 340 590

1 dome2 curb3 frame4 actuator right5 actuator left6 supporting plate

6 6

raccordement câblage(�n de course)

opening directionmax.

875 mm650 mm

cable connection(�nal course)

900 mm

Attestations, certificates and documentation• Positive safety in conformity with NBN S21-208-1&3• CE of the Skylux® dome according to EN 1873:2014+A1:2016• CE of the SHE system according to EN 12.101-2• Attestation 1200 Joule fall through protection for armoured

dome with polycarbonate shell• Attestation for 72h autonomy with Skycom® Skymax CE

central detection unit• DoP via www.skylux.be

Fire classification• Fire classification Skylux® domes Acrylic dome : Euroclass E (EN 13501-1) Polycarbonate dome : Euroclass B-s1, d0 (EN 13501-1)• Fire classification PVC curbs : Euroclass E (EN 13501-1)

Attention: the CE certification is only valid if the composition, execution and the installation regulations are respected. AG.Plastics guarantees the CE conformity as described in the documentation and according the plant regulations of the appliances. Every variance, cancels the CE conformity.