1 of 10 ES E118-D AU1804 TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK GENERAL Climate Wizard coolers operate with a high ratio of energy efficiency and deliver cool fresh air at extremely low energy cost. The CW-80 is characterized by having no additional moisture added to the supply air stream (indirect cooling) , whilst the CW-80S can be operated in “Supercool” mode producing even colder supply air with added moisture (direct cooling). These coolers comprise two supply air fans, four exhaust air fans, sixteen indirect heat exchanger core packs, water reservoir, pump, and chlorinator system. The CW-80S has an additional pump and Chillcel ® pads. CABINET AND BASE FRAME The cabinet is constructed from 304 stainless steel incorporating the motor / fan assemblies, non-corrodible heat exchange cores and other ancillary equipment all supported by a heavy gauge galvanized base frame for structural stability. Fork lift tine channels are provided within the base frame to facilitate transport and lifting. Lifting chains / straps could also be used through these channels with appropriate lifting equipment onto elevated structures (e.g. roof of a building). Components are effectively treated to ensure corrosion resistance and mechanical fasteners are zinc coated steel and stainless steel as appropriate. Connection interface surfaces are provided for the outlet ductwork to the customer ductwork to enable fitment using established industry practices. FANS The fans are a multi blade, centrifugal type with backward curved blades and single inlet. They have black coated rotors and aluminium impellers and are individually statically and dynamically balanced. The fans are directly mounted to the electric motors. The electric motors are high efficiency, electronically commutated and speed controlled to optimise efficiency particularly at low speeds. HEAT EXCHANGE CORES The heat exchange cores are designed to facilitate heat exchange between the wet and dry air passages such that high efficiency heat transfer takes place without the addition of any moisture. They are designed to provide long life and long term high efficiency. The CW-80S Supercool is also fitted with Chillcel ® fabricated, honeycomb cooling pads. RESERVOIR The reservoir is constructed from polymer to ensure durability and corrosion resistance. The reservoir is designed to house the water pump(s) and accommodate the level control, chlorinator system and salinity monitoring water management system. The design of the reservoir and watering system ensures that no water remains after draining. ELECTRICAL CABINET AND CONTROLS Control equipment including motor control hardware, PLC control system, touch screen and other electrical equipment is pre-wired and factory mounted within a robust IP66 enclosure suitable for outdoor conditions. WATER DISTRIBUTION SYSTEM The water supply connection is a 316 stainless steel ½” BSPT fitting that connects to the internally mounted electrically operated water solenoid. Heat exchange cores saturation and Chillcel ® pads (for CW-80S only) saturation is achieved through internally mounted pump(s) delivering water to a specially designed non-clog water distribution system providing continuous uniform flow. The wet components of each pump are manufactured from stainless steel and the pumps are driven by a 3 phase industrial, fully enclosed fan cooled electric motor with thermal overload protection. Easily cleanable in line strainers are provided for both the incoming water supply and the water distribution system. WATER MANAGEMENT SYSTEM The cooler includes an electronic water management system that controls the maximum salinity level of the reservoir water through continuous monitoring, draining and automatic replenishment as determined by the control system. AIR FILTER Intake air is filtered through easily accessible, washable and replaceable pleated filters. BMS INTERFACE A BACnet module (optional) provides full BACnet interface for control and monitoring of the cooler. Remote control of the cooler is possible via dedicated BMS terminals provided within the electrical cabinet. ILL2060-A

Upload: others

Post on 31-Oct-2021

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN

1 of 10 ES E118-D AU1804

TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

GENERALClimate Wizard coolers operate with a high ratio of energy efficiency and deliver cool fresh air at extremely low energy cost.The CW-80 is characterized by having no additional moisture added to the supply air stream (indirect cooling) , whilst the CW-80S can be operated in “Supercool” mode producing even colder supply air with added moisture (direct cooling).These coolers comprise two supply air fans, four exhaust air fans, sixteen indirect heat exchanger core packs, water reservoir, pump, and chlorinator system. The CW-80S has an additional pump and Chillcel® pads.

CABINET AND BASE FRAMEThe cabinet is constructed from 304 stainless steel incorporating the motor / fan assemblies, non-corrodible heat exchange cores and other ancillary equipment all supported by a heavy gauge galvanized base frame for structural stability. Fork lift tine channels are provided within the base frame to facilitate transport and lifting. Lifting chains / straps could also be used through these channels with appropriate lifting equipment onto elevated structures (e.g. roof of a building).Components are effectively treated to ensure corrosion resistance and mechanical fasteners are zinc coated steel and stainless steel as appropriate. Connection interface surfaces are provided for the outlet ductwork to the customer ductwork to enable fitment using established industry practices.

FANSThe fans are a multi blade, centrifugal type with backward curved blades and single inlet. They have black coated rotors and aluminium impellers and are individually statically and dynamically balanced. The fans are directly mounted to the electric motors. The electric motors are high efficiency, electronically commutated and speed controlled to optimise efficiency particularly at low speeds.

HEAT EXCHANGE CORESThe heat exchange cores are designed to facilitate heat exchange between the wet and dry air passages such that high efficiency heat transfer takes place without the addition of any moisture. They are designed to provide long life and long term high efficiency.The CW-80S Supercool is also fitted with Chillcel® fabricated, honeycomb cooling pads.

RESERVOIRThe reservoir is constructed from polymer to ensure durability and corrosion resistance. The reservoir is designed to house the water pump(s) and accommodate the level control, chlorinator system and salinity monitoring water management system. The design of the reservoir and watering system ensures that no water remains after draining.

ELECTRICAL CABINET AND CONTROLSControl equipment including motor control hardware, PLC control system, touch screen and other electrical equipment is pre-wired and factory mounted within a robust IP66 enclosure suitable for outdoor conditions.

WATER DISTRIBUTION SYSTEMThe water supply connection is a 316 stainless steel ½” BSPT fitting that connects to the internally mounted electrically operated water solenoid. Heat exchange cores saturation and Chillcel® pads (for CW-80S only) saturation is achieved through internally mounted pump(s) delivering water to a specially designed non-clog water distribution system providing continuous uniform flow.The wet components of each pump are manufactured from stainless steel and the pumps are driven by a 3 phase industrial, fully enclosed fan cooled electric motor with thermal overload protection.Easily cleanable in line strainers are provided for both the incoming water supply and the water distribution system.

WATER MANAGEMENT SYSTEM The cooler includes an electronic water management system that controls the maximum salinity level of the reservoir water through continuous monitoring, draining and automatic replenishment as determined by the control system.

AIR FILTERIntake air is filtered through easily accessible, washable and replaceable pleated filters.

BMS INTERFACEA BACnet module (optional) provides full BACnet interface for control and monitoring of the cooler.Remote control of the cooler is possible via dedicated BMS terminals provided within the electrical cabinet.

ILL2060-A

Page 2: TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN

2 of 10 ES E118-D AU1804

TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

ILL2345-A

ELECTRICAL SYSTEM OVERVIEW

ILL2345-A

WATER CONNECTION1/2” BSPT Male thread (compatible with 1/2” NPT) connection on cooler. Water Supply Temperature: Max. 40°C

In areas subject to freezing, the water line needs a drain down facility.If the water pressure exceeds the maximum specification then a pressure reducing valve is required and must be supplied and fitted by the installer.

DRAIN CONNECTIONA built-in Drain Valve is controlled by the Water Management System. Drain water and tank overflow water must be carried away to a suitable discharge point in accordance with local regulations. The drain outlet provided will accept an NPS 2 inch (DN50) PVC pipe. Direct water into an open drain.

ILL2255-A

ILL2355-A

ILL2356-A

ILL2356-A

Page 3: TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN

3 of 10 ES E118-D AU1804

TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

BACnet is currently offered as an option on all CW-80 Series coolers. The popular protocols BACnet/IP and BACnet MS/TP can be provided as well as BACnet Ethernet.Communication items (referred to as “objects”) form the key to the BACnet system. Seeley International have developed a full set of 108 objects for the CW-80 Series range of coolers. This set of objects (referred to as an “objects list”) is detailed in the cooler Installation and Operation Manual “BACnet Object List CW-80 Series” and is available to assist customers in design-ing their building management control systems. This objects list can be divided into two groups - 17 objects that can be both read and modified by the customer and the balance of 91 objects that can be read only.The first group of 17 modifiable objects are associated with controlling and operating the CW-80 Series cooler as summa-rized in the following table: -

Item Objects Detailsbasic control 6 control of BACnet active, run,

cool, direct cool (supercool only), fan speed, water tank drain

master error reset 2 ability to reset errors

clock 8 provision for adjusting clock - daylight saving

BACnet integrity 1 used to confirm BACnet signal integrity (selectable feature)

The second group of 91 read only objects are associated with the status of the CW-80 Series cooler as summarized in the following table: -

Item Objects Detailsbasic 19 software number, version and

date, control mode, current operating status, watering sequence control, commission-ing mode

BMS 7 status of standard hard wired BMS signals

air temperatures and humdity

8 air temperatures in both deg C and deg F for ambient, inter-mediate (supercool only) and supply airhumidity in RH% for ambient and supply air

pressures 4 differential pressure across the supply and exhaust parts of the core in both Pa and inches of water

fans 10 supply and exhaust fan speeds, enable signals, normal signals

tank 9 status of tank water level sensors, inlet solenoid, drain valve, chlorinator enable and adequate voltage output, aver-age tank refill time, drain delay elapsed period

watering system 2 operating status of indirect pump and direct (supercool only) pump

Item Objects Detailssalinity 2 status of high salinity signal

and timed drain in progress

hours 6 accumulated running time in hours for overall cooler, supply fans, exhaust fans, indirect pump, direct pump (supercool only), chlorinator

errors 24 water supply poor or inad-equate at various stages of the tank fill or refill, indirect pump overload, direct pump (supercool only) overload, supply fan errors, exhaust fan errors, chlorinator warning and critical errors, high inlet air filter differential pressure error, low exhaust pressure error, unit operating in forced vent mode or has shut down due to combination of errors

With the BACnet option installed, the standard BMS interface is still available should this be required. In this scenario the customer would control the cooler using the standard BMS interface but at the same time utilise the BACnet system only to monitor the detailed status of the cooler. A specific BACnet object is provided so that the customer can freely select either this style of control or normal full BACnet control.

BACnet field wiring is simple as only a single pair of shielded wires is required to be connected to two terminals. Further, in multiple cooler installations this wiring can be looped from one cooler to the next up to a maximum of 127 coolers whilst still maintaining individual control and status monitoring.

BACNET INTERFACE OPTIONS FOR CW-80 SERIES

Page 4: TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN

4 of 10 ES E118-D AU1804

TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

ILL2354-BILL2353-B

ILL2351-B

ILL2351-B

3980

4469

2310

2547

ILL2352-B

2523

3513

ILL2352-B

ILL2354-B

WATER INLET DRAIN

39556

861 1063

ILL2353-B

1200

720

1200

TOP

SIDE

REAR (CONTROL PANEL)

FRONT (SUPPLY AIR OUTLET)

ILL2357-A

FRONT (CW-80S ADDITIONAL

COMPONENTS)

ILL2357-A

PLUMBING DOOR SWING

ILL2536-A

ILL2309-A

ILL2309-B

Option: Attenuator Ready Exhaust Ducts replacing

Weatherseals

Page 5: TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN

5 of 10 ES E118-D AU1804

TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

* Cooling capacity measured to Australian Standard AS2913-2000, ambient of 38°C dry bulb & 21°C wet bulb, with room exit temperature of 27.4°C.

Sound Power Level(without High Ca-pacity option)

Radiated Power in horizontal direction with supply duct connected (dB re 1pw) Octave Band Centre Frequency (HZ)

Total Sound Power Level (dBA re 1pw)63 125 250 500 1k 2k 4k 8k

CW-80, CW-80S 95 101 98 94 95 91 86 81 99

SPECIFICATION CW-80 CW-80S

Services

Electrical Supply

Standard 3 phase N+E, 380-415V 50Hz 22A 3 phase N+E, 380-415V 50Hz 22AHigh Capacity option 3 phase N+E, 380-415V 50Hz 27A 3 phase N+E, 380-415V 50Hz 27A

Water Supply

1/2” male BSPT connection.Recommended pressure range

200 to 500 Kpa. Maximum pressure (static) 800 Kpa

Minimum flow rate through 10.0mm test orifice: 45 L/min

Or Minimum pressure measured at con-nection point whilst simultaneously

delivering 45 L/min: 85 Kpa

1/2” male BSPT connection.Recommended pressure range

200 to 500 Kpa. Maximum pressure (static) 800 Kpa

Minimum flow rate through 10.0mm test orifice: 45 L/min

Or Minimum pressure measured at con-nection point whilst simultaneously

delivering 45 L/min: 85 Kpa

Environment Max. Operating Temp 55 deg C ambient (measured in shade)

55 deg C ambient (measured in shade)

Performance

Airflows @ High Speed

StandardSupply - 6,400 l/sec (23,040 m3/hr)

@ 100PaExhaust - 5,240 l/sec (18,860 m3/hr)

Supply - 6,400 l/sec (23,040 m3/hr) @ 100Pa

Exhaust - 5,240 l/sec (18,860 m3/hr)

High Capacity optionSupply - 6,400 l/sec (23,040 m3/hr)

@ 430PaExhaust - 5,240 l/sec (18,860 m3/hr)

Supply - 6,400 l/sec (23,040 m3/hr) @ 430Pa

Exhaust - 5,240 l/sec (18,860 m3/hr)

Nominal Cooling Capacity* kW

60.1kW @ 19.8 deg C supply temp, stand-alone cooling

143.4kW pre-cooling outside air

82.3kW @ 17.0 deg C supply temp, stand-alone cooling

166.4kW pre-cooling outside air

Supply Motors/Fans

Diecast aluminium housing. Inverter drive with 0-10V control and overload protection.

380 - 480V 50 / 60Hz 2 fans / motors, 560mm dia

380 - 480V 50 / 60Hz 2 fans / motors, 560mm dia

Exhaust Motors/Fans

Diecast aluminium housing. Inverter drive with 0 - 10 V control and overload

protection.

380 - 480V 50 / 60Hz 4 fans / motors, 355mm dia

380 - 480V 50 / 60Hz 4 fans / motors, 355mm dia

Supply Air Outlet

End discharge, horizontal duct. 1,200 x 1,200mm 1,200 x 1,200mm

Pump (Indirect)

IP55 304/316 Stainless Steel wet end construction. 0.75kW 3 phase 50 / 60 Hz 0.75kW 3 phase 50 / 60 Hz

Pump (Direct)

IP55 304/316 Stainless Steel wet end construction. nil 0.25kW 3 phase 50 / 60 Hz

Chlorinator Controller and Cells. 240V 50Hz 240V 50Hz

Salinity Management

Seeley International P/Ltd. Salinity Water Manager 866015 Water Probe 833842

Salinity Water Manager 866015 Water Probe 833842

Drain Valve Seeley International P/Ltd low voltage, vertical, electric servo motor drive. 24VAC, P/No 117317 24VAC, P/No 117317

Drain Connection

Supplied horizontal outlet accepts 60.35mm OD (DN50) PVC pressure water pipe. NPS 2 inch PVC NPS 2 inch PVC

Water Reservoir

Seeley International P/Ltd moulded polymer. 180 litre capacity 180 litre capacity

Heat Exchange Core

Seeley International P/Ltd synthetic plate type, super efficient. 16 cores

16 cores + 2 cooling pads Seeley International Chillcel®

honeycomb

ShippingDimensions 4,469 L * 2,310 W * 2,547mm H 4,469 L * 2,310 W * 2,547mm H

Weight 2,000 kg 2,100 kg

Operating Weight

Weight including reservoir water, system water, supply and exhaust stator ducts. 2,700 kg 2,850 kg

Air Filtration MERV 7 (G4) washable filters (standard). 622 x 622 x 45mm deep (nominal 25” x 25” x 2” deep)

622 x 622 x 45mm deep (nominal 25” x 25” x 2” deep)

Standards Compliance

AS / IEC / EN 60204 CE Marking

AS / IEC / EN 60204 CE Marking

Page 6: TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN

6 of 10 ES E118-D AU1804

TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

ILL2334-A

ILL2333-A

STATIC PRESSURE (Pa) 0 40 120 200 280

Airflow (l/sec) @ 80% De-rate 6,830 6,640 6,270 5,930 5,600

Airflow (l/sec) @ 90% De-rate 7,150 7,060 6,850 6,590 6,330

STATIC PRESSURE (Pa) 0 40 120 200 280

Airflow (m3/hr) @ 80% De-rate 24,590 23,900 22,570 21,350 20,160

Airflow (m3/hr) @ 90% De-rate 25,740 25,420 24,660 23,720 22,790

CW-80 STANDARD AUSTRALIA, EUROPE, SOUTH AFRICA & UK

CW-80 STANDARD AUSTRALIA, EUROPE, SOUTH AFRICA & UK

Page 7: TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN

7 of 10 ES E118-D AU1804

TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

ILL2337-A

ILL2336-A

STATIC PRESSURE (Pa) 0 40 120 200 280

Airflow (l/sec) @ 80% De-rate 6,500 6,320 5,980 5,660 5,330

Airflow (l/sec) @ 90% De-rate 6,970 6,840 6,590 6,320 6,050

STATIC PRESSURE (Pa) 0 40 120 200 280

Airflow (m3/hr) @ 80% De-rate 23,400 22,750 21,530 20,380 19,190

Airflow (m3/hr) @ 90% De-rate 25,090 24,620 23,720 22,750 21,780

CW-80S STANDARD AUSTRALIA, EUROPE, SOUTH AFRICA & UK

CW-80S STANDARD AUSTRALIA, EUROPE, SOUTH AFRICA & UK

Page 8: TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN

8 of 10 ES E118-D AU1804

TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

ILL2523-A

STATIC PRESSURE (Pa) 300 400 500 600

Airflow (l/sec) @ 85% De-rate 7,400 6,870 6,430 5,960

STATIC PRESSURE (Pa) 300 400 500 600

Airflow (m3/hr) @ 85% De-rate 26,640 24,730 23,150 21,460

ILL2524-A

CW-80 HICAP AUSTRALIA, EUROPE, SOUTH AFRICA & UK

CW-80 HICAP AUSTRALIA, EUROPE, SOUTH AFRICA & UK

Page 9: TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN

9 of 10 ES E118-D AU1804

TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

ILL2526-A

STATIC PRESSURE (Pa) 200 300 400 500

Airflow (m3/hr) @ 85% De-rate 26,500 24,980 23,440 21,850

ILL2527-A

STATIC PRESSURE (Pa) 200 300 400 500

Airflow (l/sec) @ 85% De-rate 7,360 6,940 6,510 6,070

CW-80S HICAP AUSTRALIA, EUROPE, SOUTH AFRICA & UK

CW-80S HICAP AUSTRALIA, EUROPE, SOUTH AFRICA & UK

Page 10: TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN

10 of 10 ES E118-D AU1804

TECHNICAL SPECIFICATIONS - CW-80 & CW-80S AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

NOTES: THIS PAGE LEFT INTENTIONALLY BLANK