technical specifications for 250/320 kva, 5 cylinder ... · mahindra scania internal combustion...
TRANSCRIPT
TECHNICAL SPECIFICATIONS FOR 250/320 KVA, 5 CYLINDER
MAHINDRA DIESEL GENERATOR SET PACKAGED BY
ENGINE:
Mahindra Scania Internal Combustion (IC) Diesel Engine conforming to BS5514 Standards CPCB Emission Norms, Standard Design, Inline, 4 Stroke, Direct Injection type, Liquid Cooled Turbo charged After-cooled engine rated at 1500 RPM, 24 VOLTS DC Electric Start type.
SCOPE OF SUPPLY FOR DIESEL GENERATING SET PACKAGE
FUEL SYSTEM:
Unit injectors with fuel lift pump Fuel injection pump Electronic Governor integrated in EMS
(Engine Management System) Full ow fuel lter/s
COOLING SYSTEM:
Radiator with set of hose pipes Coolant circulating pump Pusher type fan Thermostat Crank shaft pulley for fan belt Set of fan belts
LUBRICATION SYSTEM:
Wet sump with ller and dipstick Full ow spin-on lube oil lter/s Gear driven lube oil pump with strainer
AIR SYSTEM:
Air Inlet manifold
FLY WHEEL & HOUSING:
Fly wheel SAE 14 Fly wheel housing SAE 1 Starter Ring gear
EXHAUST SYSTEM:
Exhaust manifold Flexible steel exhaust Bellow Residential Silencer Exhaust driven turbo charger EGR (Exhaust Gas Recirculation system)
ELECTRICAL SYSTEM – 24 VOLT DC:
24 Volts Starter Motor and 24 Volts Battery charging alternator with integral regulator for DC output
24 Volts high coolant temperature trip switch
24 Volts low lube oil pressure trip switch 24 Volts fuel shut off solenoid integrated
in EMS Starter Push on GSU
Air lter assembly with dry type lter element
ALTERNATOR: Synchronous Alternator suitable for close coupling with engine, rated for 3 Phase supply at 415 V, 50 Hz, 0.8 Pf (lag) @ 1500 RPM with ±0.5% voltage regulation, Class H insulation conforming to IS 13364 / IS 4722 / BS 4999-5000 standards, Self excited, self regulated, screen protected and drip proof enclosure of IP 23.
ACOUSTIC ENCLOSURE: It is made out of CRCA steel sheet fabricated with the following features: Design to meet CPCB norms of 75 dB (A) at
1 Mtr. Distance in free eld condition as per testing procedure of ISO: 8528 (Part 10) – 1998.
It is made on sophisticated / special purpose CNC machines for consistency in quality and workmanship.
Powder coated with superior nish with UV resistance powder coating.
Insulation materials used are the best in the industry for better sound attenuation.
GENERAL DATA OF THE DIESEL ENGINE
Sl.
No. Description 250/320 KVA
1 No. of cylinders 5
2 KVA/kW 250/200 320/256
3 Engine Model DC 09 071A. 226-289 kW (250-
320 kVA) EU Stage IIIA
4 Bhp 307 / 393
5 Bore x Stroke (in mm) 130 X140
6 Displacement (in ltrs.) 9.3
7 Aspiration Turbo charged Inter Cooled
8 Compression ratio 16 : 01
9 Firing Order 1-2-4-5-3
10 Rotation Anti-clock wise when viewed
from y wheel end
11 Cooling System Liquid Cooled type
12 Lube oil type & grade to be used
ACEA E3, E4, E5 OR E7 type & SAE15W40 grade
13 100% 75% 50%
Fuel injection pump
Make SCANIA
Type GEAR PUMP
PRP – Prime power: For continuous operation at varying load. Max mean load factor of 70% of rated power over 24 hours of operation. 1 hour /12 hours period of accumulated peak overload to 110%.
BATTERY:
12 Volts DC 150 AH x 2 Nos. pre-charged low
maintenance lead acid type battery CANOPY DIMENSION:
DG SET FOUNDATION PLATFORM REQUIRED:
Note: Height of the platform indicated above as 150 mm is minimum. Customer /End user should access the site condition for water ooding situation and increase the height of the platform accordingly.
CONTROL PANEL: Manually operated Standard Running Control Panel located within the Acoustic Enclosure, cubical type; powder coated with hinged doors, undrilled bottom gland plate made out of 18 / 16 gauge CRCA sheet provided with the following:
MCCB (3 Pole) with over load and short circuit protection
Genset Controller Unit, Deep Sea 4520 or equivalent with Multi-data Digital display to read the following parameters:
ALTERNATOR OUTPUT / ELECTRICALS: Voltage, Current, Frequency, power factor, kW, kwh etc
ENGINE GAUGING: Lube oil pressure, coolant temperature, engine speed in rpm, engine run hours, DC voltage, engine service hour etc.
Current Transformers: Aluminium busbar of suitable capacity
with incoming and outgoing termination Indicating lamp for ‘DG Set ON’ & ‘LOAD ON’
Set of instruments, fuses / MCBs duly wired and ferruled
FUEL TANK: Integral / Sub-base fuel tank for 8 hours operation
FUEL TANK CAPACITY
KVA No. of Ltrs.
250 / 320 500
Note to the End-User: At the DG set installation site, following to be made available: Minimum 60% ventilation for free ow of
fresh air has to be made available. Adequate ventilation for fresh air entry
and hot air exit for the D. G. set has to be made available.
All around space of 3 feet should be maintained.
DG SET Rating in KVA
Length x Width x Height L X W X H (IN mm)
250 / 320 4800 X 1600 X 2325
DG SET Rating in KVA
Length x Width x Height L X W X H (IN mm)
250/320 5800 X 2500 X 150
MCCB RATING
KVA Amps
250 / 320 400 / 630
Mob: +91 7829901033 / 9886754337
Mail: [email protected] Website: www.innovadiesel.co.in
SFC @ g/kW-h
14
211/204 216/214 219/217
SCANIA POWER GENERATION ENGINEs
Standard equipment
Dc09 071A, 226-289 kW (250-320 kVA)
EU Stage IIIA, CPCB II
Technical Specification Engine speed 1500 rpm (50 Hz)
250 kVA 320 kVA
PRP PRP
Gross power (kW/bhp)
Gross power (kVA/kW)
Heat rejection to coolant (kW)
Spec Fuel consumption (SFC) @ full
load
Spec Fuel consumption (SFC) @ 3/4
load
Spec Fuel consumption (SFC) @ 1/2
load
226 / 307
250 / 200
107
289 / 393
320 / 256
128
PRP – Prime power: For continuous operation at varying load, Max mean load factor
of 70% of rated power over 24 h of operation. 1 hour /12 hours period of accumulated
peak overload to 110%
• Scania Engine Management System, EMS
• Unit injectors, PDE
• Turbocharger
• Fuel filter and extra pre-filter with water separator
• Oil filter, full flow
• Centrifugal oil cleaner
• Oil cooler, integrated in block
• Oil filler, in valve cover
• Deep front oil sump
• Oil dipstick, in block
• Magnetic drain plug for oil draining
• Starter, 1-pole 6.0 kW
• Alternator, 1-pole 100A
• Flywheel, SAE 14
• Silumin flywheel housing, SAE 1 flange
• Front-mounted engine brackets
• EGR system
• Open crankcase ventilation
• Operator's manual
This specification may be revised without notice.
TM
Authorised Generators Original Equipment Manufacturer
AN ISO 9001 : 2008 CERTIFIED COMPANY
Packaged by:
#161/1, 12th Cross,
Mahalakshmi Layout,
Bangalore – 560086.
Mob: +91 7829901033 / 9886754337Mail: [email protected]: www.innovadiesel.co.in
promotes reparability and fuel economy.
The engines for power generation from Scania are based on a robust designwith a strength optimised cylinder block containing wet cylinder liners thatcan easily be exchanged. Individual cylinder heads with 4 valves per cylinder
performance.
The engine is equipped with a Scania developed Engine ManagementSystem, EMS, in order to ensure the control of all aspects related to engine
in order to suit a variety of installations.
The injection system is based on electronically controlled unit injectors thatgive low exhaust emissions with good fuel economy and a high torque. Forfurther reduction of NO emissions the engines are also equipped with anx
exhaust gas recirculation, EGR, system developed by Scania. The enginecan be fitted with many accessories such as air cleaners, radiators and PTOs
Spec Fuel consumption (SFC) : g/kW-h
204
214
217
211
216
219
SCANIA POWER GENERATION ENGINEs
Engine description
1:6
97
4
1242
1:6
97
5
473 433
848
437
All dimensions in mm
Dc09 071A, 226-289 kW (250-320 kVA)
EU Stage IIIA, CPCB II
No of cylinders
Working principle
Firing order
Displacement
Bore x stroke
Compression ratio
Weight
Piston speed at 1500 rpm
Piston speed at 1800 rpm
Camshaft
Pistons
Connection rods
Crankshaft
Oil capacity
Electrical system
5 in-line
4-stroke
1-2-4-5-3
9.3 litres
130 x 140 mm
16:01
950 kg (excl oil and coolant)
7.0 m/s
8.4 m/s
High position alloy steel
Aluminium pistons
I-section press forgings of alloy steel
Alloy steel with hardened and
polished bearing surfaces
332-38 dm
1-pole 24V
TM
Authorised Generators Original Equipment Manufacturer
AN ISO 9001 : 2008 CERTIFIED COMPANY
Packaged by:
#161/1, 12th Cross,
Mahalakshmi Layout,
Bangalore – 560086.
Mob: +91 7829901033 / 9886754337Mail: [email protected]: www.innovadiesel.co.in