TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
OASIS ENGINEERING WLL
TECHNICAL SUBMITTAL
GI AND FIRE RATED DUCT MANUFACTURING
Document No: OS/2017/PQ/DF Rev: 00
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
I N D E X
Section 1
Company Profile
Standards & Specification
Fabrication Process
Organization Chart
Quality Management Policy & ISO Certification
List of Manpower& Machinery
Section 2
Material Supplier
Coil Suppler
o Supplier Company Profile
Sample Material Test Certificate
Sample Country of Origin
Flange System Connector
Insulation & Acoustic Liner Supplier
Fire Rated Paint Supplier
o Qatar Civil Defense Approval
Section 3
Compliance Statement
Duct Manufacturing
o SMCNA
SMACNA 2”
SMACNA 4”
SMACNA 6”
Fire Rated Duct Manufacturing
Section 4 Health & Safety Policy
Section 5 List of Major Projects & Previous Approvals
Section 6 Commercial Registration
Section 7 Company Address and Contact Details
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
COMPANY PROFILE
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
STANDARDS & SPECIFICATION
Our world-class methodology ensures that all our ductwork and fittings are pre-programmed in strict compliance with recognized, international construction quality standards. We have the capacity to manufacture low, medium and high pressure systems based on the specific requirements of our clients.Longitudinal seams are typically made with Pittsburgh locks. In addition to economical TDC transverse duct connectors, S & drive slip joints, four-bolt connectors, and TDF connectors are available.
We fully comply with the standards and specifications set by leading HVAC associations:
DW/144: Specification for sheet metal ductwork by HVCA (UK)
SMACNA: Sheet Metal and Air-conditioning contractor's National Association (USA)
NFPA: National Fire Protection Association (USA)
DW/172: Specification for kitchen ventilation system by HVCA (UK)
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
FABRICATION PROCESS
We have state of the art Autoline V production line which can deliver fully folded ducts without any manual
intervention from decoiling to folding. The line can produce both bare ducts and flanged (TDF) ducts.
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
FABRICATION PROCESS
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
ORGANIZATION CHART
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
QUALITY MANAGEMENT POLICY
Quality Management Policy
Oasis Engineering Management is committed to implement and maintain the Quality Management System
and continually improve its effectiveness throughout the organization.
We are committed to Quality and on time Delivery for its products and services. To achieve our commitment,
management will,
Ensure that the fabricated products meets client specifications
Promote a proactive attitude towards quality and consider quality matters in all process
Focusing on client satisfaction by delivering products without fail as per the schedule agreed
Monitor the customer satisfaction levels and delivery performances
Empower the employees and involving them in all levels of Quality Management
Develop quality awareness and skills through training and motivating employees
Communicate the Quality Policy to all staff within the organization and interested parties and review it
periodically to ensure the continuing suitability
All employees of the company are aware about this policy and to contribute their skills and talents to
implement, maintain and continually improve the Quality Management System.
For Oasis Engineering WLL
Kutty Mammad Managing Director
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
ISO QUALITY MANAGEMENT
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
LIST OF MANPOWER
S No Employee Name Designation
1 OS001 Manoj Kumar Sathyadevan Welder
2 OS042 Ramesh Welder
3 OS044 Govind Kumar Bharti Duct Fabricator
4 OS064 Ali Hussain Ansari Duct Fabricator
5 OS069 Ajeet Singh Duct Fabricator
6 OS070 Keshava Ram Duct Fabricator
7 OS072 Shiv Prasad Chaudhary Duct Fabricator
8 OS 193 Chandra Singh Tech Helper
9 OS 194 Sandip Kumar Singh Tech Helper
10 OS 200 Ram Kumar Nepali Welder
11 OS 213 Ajit Kumar Yadav Welder
12 OS 214 Kaushal Kishor Sah Ductman
13 OS 215 Man Bahadur Bista Ductman
14 OS 216 Sunil Kumar Purbey Ductman
15 OS 217 Jitender Kumar Chaudhary Ductman
16 OS 218 Murugan Karunanithi Ductman
17 OS 219 Arul Murugan Manivel Ductman
18 OS 220 Sekar Krishnamoorthy Ductman
19 OS 221 Abdulajith Kathar Mytheen Tech Helper
20 OS 222 Sunil Kumar Rawt Tech Helper
21 OS 223 Shiv Shankar Prasad Tech Helper
22 OS224 Raju Sunchiuri Tech Helper
23 OS225 Tilak Gautam Tech Helper
24 OS226 Chitra Bahadur Mijar Tech Helper
S.No. Employee Name Designation
1 OS002 Kutty Mammad Managing Director
2 OS061 Muhammad Arshad Finance Manager
3 OS058 Abilash Gopinath Mechanical Engineer
4 OS015 Vijith Johnson Workshop Supervisor
5 OS059 Mohammed Koya Sales Engineer
6 OS050 Anil Kumar Production Supervisor
7 OS057 Giri Kumar Divakaran Production Supervisor
8 OS052 Babu Daniel Sales Engineer
9 OS055 Nishad T A Design Engineer
10 OS236 Mohammed Hashif Purchaser
11 OS055 Jude Showroom Incharge
12 OS236 Venu Gopal Sr. Admin Officer
13 OS237
Draughtsman
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
LIST OF MACHINERIES
SR NO. NAME OF ITEM BRAND CAPACITY QTY (Nos)
1 Compressor Mac - Turkey 10 Hp 1
2 Sanblasting Machine Euroblast 200 ltr 1
3 Hydraulic Press Mac - Turkey 40 ton 1
4 Lathe Machine Cholchester 1 Mtr 1
5 Bandsaw Machine Beca-Mac 300mm 1
6 Lathe Machine GSP 4 Mtr 1
7 Profile Cutting Machine Tullu 1 Mtr 1
8 Radial Drill Machine Ashqut 50mm Hole 1
9 Bending Machine Sumec 8mm 1
10 Shearing Machine Sumec 8mm 1
11 Autoline V Duct Production Line Falkin 500Sqm/Shift 1
12 CNC Plasma Cutting Machine Hypertherm 4m X 2m X 20mm 2
13 Hydraulic Rolling Machine Falkin 4mm 2
14 Folding Machine Falkin 4mm 1
15 Grooving Machine Falkin 2mm 2
16 Pittsburgh Lock Forming Falkin 2mm 1
17 Hydraulic Cornet Fitting Machine Falkin - 1
18 Seam Locking Machine Trumph - 2
19 Spot Welding Machine Falkin 2mm 2
20 Forklift Komatsu 5 Ton 1
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
RAW MATERIAL SUPPLIERS
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
COIL SUPPLIER
JSW STEEL – INDIA
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
SAMPLE MATERIAL TEST CERTIFICATE
SAMPLE COUNTRY OF ORIGIN
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
DUCTWORK JOINING SYSTEMS SUPPLIER
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
DOBY VERROLEC DUCTWORK JOINING SYSTEMS
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
EXCEL FLANGING SYSTEM
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
FIRE RATED COATING SUPPLIER
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
QATAR CIVIL DEFENCE (QCD) APPROVAL
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
COMPLIANCESTATEMENT
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
COMPLIANCE STATEMENT OF GI DUCT
S. NO Specification Compliance Remarks
1 Duct Thickness and Constructions (GI)
1.1 All ductwork for air distribution shall be fabricated from GI of Grade ASTM A 653
Comply.
1.2 The duct shall be constructed from GI sheet fabrication and for leak proof tightness of seams and joints or angle iron profiles with gasket in between for reinforcement and 6mm bolt, nut and locknut at every 150mm
Comply. The ducts will be fabricated from GI Sheets.
1.3 The longitudinal seams shall be made with Pittsburgh lock and sealed with suitable inorganic sealant. The transverse joints shall be with combination of ‘S’&‘C’ cleats and sealed with inorganic sealant or be of welded type to make it leak prof. The flange joints, where necessitated, shall be of tight fit type with gaskets of inorganic material.
Comply. The proposed ductwork shall be made with Pittsburgh lock. The transverse joints shall be with combination of S& C cleat or Slide on Flange System.
1.4 Full details of the construction and materials along with samples of fabricated ducts and joints shall be submitted to the Engineer for approval before commencement of work.
Comply.
SPECIFICATION PRODUCT: GI DUCT
GI COIL SUPPLIER: JSW (ASTM A 653 Grade With Z275-G90 Coating)
ACCESSOIES SUPPLIER: DOBY VERROLEC / EXCEL UAE
DUCT CONSTRUCTION STANDARD: SMACNA
LOCAL CONSTURCTION STANDARD: QCS 2010
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
DUCT CONSRUCTION SPECIFICATION: SMACNA
SMACNA 2"
S No Material
Thickness Max Duct Size
in MM Transverse Joint
Max Spacing in MM
Longitudinal Joint
Intermediate Reinforcement
1 24 (0.6mm) Up to 300 S & C Cleat 1220 Pittsburg Lock Nil
2 24 (0.6mm) 301 - 550 S & C Cleat 1220 Pittsburg Lock Nil
3 24 (0.6mm) 551 - 700 S & C Cleat 1220 Pittsburg Lock Nil
4 24 (0.6mm) 701 - 900 Slide on Flange
20mm 1220 Pittsburg Lock Nil
5 22 (0.8mm) 901 - 1200 Slide on Flange
30mm 1220 Pittsburg Lock Nil
6 20 (1.0mm) 1201 - 1500 Slide on Flange
30mm 1220 Pittsburg Lock Nil
7 20 (1.0mm) 1501 - 2100 Slide on Flange
40mm 1220 Pittsburg Lock
GI Angle 50x50x5mm @600mm
8 18 (1.2mm) 2101 - 2700 Slide on Flange
40mm 1220 Pittsburg Lock
GI Angle 50x50x5mm @600mm
9 18 (1.2mm) 2701 - Max Slide on Flange
40mm 1220 Pittsburg Lock
GI Angle 50x50x5mm @600mm
SMACNA 4"
S No Material
Thickness Max Duct Size
in MM Transverse Joint
Max Spacing in MM
Longitudinal Joint
Intermediate Reinforcement
1 24 (0.6mm) Up to 250 S & C Cleat 1200 Pittsburg Lock NOT REQUIRED
2 24 (0.6mm) 251 - 400 S & C Cleat 1200 Pittsburg Lock NOT REQUIRED
3 24 (0.6mm) 401 - 650 Slide on Flange
20mm 1200 Pittsburg Lock NOT REQUIRED
4 22 (0.8mm) 651 - 900 Slide on Flange
30mm 1200 Pittsburg Lock NOT REQUIRED
5 20 (1.0mm) 901- 1000 Slide on Flange
30mm 1200 Pittsburg Lock NOT REQUIRED
6 18 (1.2mm) 1001 - 1500 Slide on Flange
40mm 1200 Pittsburg Lock NOT REQUIRED
7 18 (1.2mm) 1501 - 2100 Slide on Flange
40mm 1200 Pittsburg Lock
GI Angle 50x50x5mm @600mm
8 18 (1.2mm) 2101 - 2400 Slide on Flange
40mm 1200 Pittsburg Lock
GI Angle 50x50x5mm @600mm
9 18 (1.2mm) 2401 - > Slide on Flange
40mm 1200 Pittsburg Lock
GI Angle 50x50x5mm @600mm
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
SMACNA 6"
S No
Material Thickness
Max Duct Size in MM
Transverse Joint Max Spacing
in MM Longitudinal
Joint Intermediate
Reinforcement
1 22 (0.8mm) Up to 550 Slide on Flange
20mm 1220 Pittsburg Lock Nil
2 20 (1.0mm) 551 - 900 Slide on Flange
30mm 1220 Pittsburg Lock
GI Angle 50x50x5mm @600mm
3 18 (1.2mm) 901 - 1200 Slide on Flange
30mm 1220 Pittsburg Lock
GI Angle 50x50x5mm @600mm
4 18 (1.2mm) 1201 - 1500 Slide on Flange
30mm 1220 Pittsburg Lock
GI Angle 50x50x5mm @600mm
5 18 (1.2mm) 1501 - 2000 Slide on Flange
40mm 1220 Pittsburg Lock
GI Angle 50x50x5mm @600mm
6 18 (1.2mm) 2001 -> Slide on Flange
40mm 1220 Pittsburg Lock
GI Angle 50x50x5mm @600mm
Stiffened Sheet along the duct at 300mm pitch will be using for All the Sizes of the duct
Reference:
SMACNA HVAC Duct Construction Standards.
Doby Verrolec / Excel Duct Work joint System
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
COMPLIANCE STATEMENT OF GI FIRE RATED DUCT
GENERAL SPECIFICATION
The fire rated ductwork specified are tested in compliance to B.S. 476 Part 24 (Duct A & Duct B) and
Australia Standard A.S. 1530.4 (Duct A & Duct B) as mentioned in UBBL 1984 and A.S. 1668.1998 for
120 minutes (2-Hours) stability, integrity and insulation respectively.
The duct manufactured shall be single skin in construction having total thickness not more than 2mm
thick including intumescent coating as tested.
The construction of ductwork shall be rectangular, flat oval or round in shape to reduce the limited
height and weight of the duct.
All duct work construction should be constructed in accordance to SMACNA Duct Construction
Standard from Galvanized sheet meet coated with a layer of intumescent coating of not less than 600
microns similar to WinDuct or equivalent.
All Ductwork shall comply with QCS 2010 Standards
All Winduct WiinCoat Solution comply with Qatar Civil Defense Approval for GI Ductwork to provide fire
protection for 2 hours stability and integrity for both horizontal and vertical ductwork
SPECIFICATION PRODUCT: GI DUCT FIRE RATED (2 HOURS)
GI COIL SUPPLIER: JSW (ASTM A 653 Grade With Z275-G90 Coating)
FIRE COATING SUPPLIER: WINDUCT
ACCESSOIES SUPPLIER: DOBY VERROLEC / EXCEL
DUCT CONSTRUCTION STANDARD: SMACNA
LOCAL CONSTURCTION STANDARD: QCS 2010
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
S No Item Description
1 Fire resistant Period (Stability / Integrity / Insulation)
120 minutes (2 hours)
2 Test Standard A.S. 1530.4 (Australian Standard) and B.S. 476 Part 24 (British Standard)
3 Material of ductwork Galvanised iron sheet constructed to SMACNA Duct thickness gauge Construction Standard.
4 Weight of Duct Not more than 12 kg/m2
5 Method of application Roller or brush or spray
The ductwork should be fabricated / constructed based on SMACNA Duct Construction Standard (static of 250pa – 1000pa).
Any transformation or reducer shall be use the thickness of the larger dimension of the duct section, in the event that the duct works are accessible after the installation, the ductwork shall be immediate apply intumescent fire rated coating.
All surface of the fabricated ductwork shall be clean from all stain, oil and glue etc before applying the coating by hand brusher or roller to the required minimum thickness of fire rated coating as recommended by the manufacturer.
All finished ductwork shall be checked visually to ensure that they are fully completed together with all TDC joint and clip in place and coated.
All coating shall be verified and checked by the system manufacture representative with "Elcometer - Digital Gauge" to ensure the thickness as recommended are met or within the recommended thickness as specified in their test reports.
S. NO Specification Compliance Remarks
1 Duct Thickness and Constructions (GI)
1.1 All ductwork for air distribution shall be fabricated from GI of Grade ASTM A 653
Comply.
1.2 The duct shall be constructed from GI sheet fabrication and for leak proof tightness of seams and joints or angle iron profiles with gasket in between for reinforcement and 6mm bolt, nut and locknut at every 150mm
Comply. The ducts will be fabricated from GI Sheets.
1.3 The longitudinal seams shall be made with Pittsburgh lock and sealed with suitable inorganic sealant. The transverse joints shall be flange joints, and shall be of tight fit type with fire rated gaskets.
Comply. The proposed ductwork shall be made with Pittsburgh lock. The transverse joints shall be with Slide on Flange System.
1.4 Full details of the construction and materials along with samples of fabricated ducts and joints shall be submitted to the Engineer for approval before commencement of work.
Comply.
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
DUCT CONSTRUCTION TABLE
FIRE RATED DUCTS
S No Material
Thickness Max Duct
Size in MM Transverse Joint
Max Spacing in MM
Longitudinal Joint Intermediate
Reinforcement
1
18 (1.2MM) Up to 400 Slide on Flange 20mm 1220 Pittsburg Lock Nil
2 18 (1.2MM) 401 - 600 Slide on Flange 20mm 1220 Pittsburg Lock Nil
3 18 (1.2MM) 601 - 800 Slide on Flange 20mm 1220 Pittsburg Lock Nil
4 18 (1.2MM) 801 - 1250 Slide on Flange 30mm 1220 Pittsburg Lock GI Angle 50x50x5mm
@600mm
5 18 (1.2MM) 1251 - 2000 Slide on Flange 40mm 1220 Pittsburg Lock GI Angle 50x50x5mm
@600mm
6 18 (1.2MM) 2001 - > Slide on Flange 40mm 1220 Pittsburg Lock GI Angle 50x50x5mm
@600mm
Stiffened Sheet along the duct at 300mm pitch will be using for all the sizes of the duct
Reference:
SMACNA HVAC Duct Construction Standards. Doby Verrolec / Excel Duct Work joint System
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
HSE POLICY
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
HSE Policy The long-term business success of Oasis Engineering depends on our ability to continuallyimprove the quality
of our services and products while protecting people and the environment.Emphasis must be placed on
ensuring human health, operational safety, environmental protection,quality enhancement, and community
goodwill. This commitment is in the best interests of ourcustomers, our employees and contractors, our
stockholders, and the communities in which welive and work.
Oceanic requires the active commitment to, and accountability for, QHSE from all employees andcontractors.
Line management has a leadership role in the communication and implementation of,and ensuring compliance
with, QHSE policies and standards. We are committed to:
Protect, and strive for improvement of, the health, safety and security of our people at all times;
Eliminate Quality non-conformances and HSE accidents;
Meet specified customer requirements and ensure continuous customer satisfaction;
Set Quality & HSE performance objectives, measure results, assess and continually improve
processes, services and product quality, through the use of an effective management system; Plan for,
respond to and recover from any emergency, crisis and business disruption; Minimize our impact on the
environment through pollution prevention, reduction of natural resource consumption and emissions,
and the reduction and recycling of waste;
Apply our technical skills to all HSE aspects in the design and engineering of our services and
products;
Communicate openly with stakeholders and ensure an understanding of our QHSE policies, standards,
programs and performance. Reward outstanding QHSE performance;
Improve our performance on issues relevant to our stakeholders that are of global concern and on
which we can have an impact, and share with them our knowledge of successful
QHSE programs and initiatives.
This Policy shall be regularly reviewed to ensure ongoing suitability. The commitments listed are in addition to
our basic obligation to comply with Oceanic Standards, as well as all applicable laws and regulations where we
operate. This is critical to our business success because it allows us to systematically minimize all losses and
adds value for all our stakeholders.
For Oasis Engineering WLL
Kutty Mammad
Managing Director
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
RECENT PROJECT LIST& PREVIOUS APPROVAL
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
LIST OF MAJOR PROJECTS EXECUTED
S.NO. CLIENT PROJECT / DESCRIPTION SCOPE
1 Sogelec Iskan for Electrical Engineering Co.
VOX Cinema, Doha Festival City Supply of Rectangular GI and Fire Rated Ducts
2 Laffan Refrigeration & Air-conditioning
Doha Festival City – Phase 2 Supply of Rectangular GI Ducts
3 TEA for Electrical and Contracting WLL
Buzwair G+6 Tower Supply of SS Duct
4 Bin Thani Electro Mechanical WLL
Qatar Airways Crew City Supply of Rectangular GI Ducts and Fittings
5 Shapoorji Pallonji Qatar South East Car Park Supply of Rectangular GI Ducts
6 Radis Engineering Co WLL Fox Hills, Lusial Supply of GI Ducts
7 HOW United WLL QSTP - QF Supply of SS 316L Rectangular Ducts
8 Jubail MEP Qatar WLL Gulf Mall – GOSlia Showroom Supply of Rectangular GI Ducts& Fittings
9 Dutco McConnel Dowell Qatar LLC
Qatalum – Inline Tube Cleaning Machine Building
Supply of GI & MS Rectangular Ducts
10 Security & Safety Trading Center
Basement + Kitchen Supply of Fire Rated Ducts + SS 304 Ducts
11 PAT Engineering Enterprises Co WLL
6 Villa Project – Al Rayyan Supply of Rectangular GI Ducts& Fittings
12 Powermech Engineering Co WLL
Union Residential Tower Supply of Rectangular SS Ducts
13 Precise Contracting Co WLL QP District Supply of GI Rectangular Ducts
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
PREVIOUS APPROVALS
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
COMMERCIAL REGISTRATION
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
COMPANY ADDRESS & CONTACT DETAILS
TECHNICAL SUBMITTAL
Format No: OE-2012-26 Issue Date : 15-10-2012 Revision No: 00 Revision Date:
ADDRESS:
Office Address
OASIS Engineering WLL,
Near Midmac Round About,
P.O.Box: 31843
Doha, Qatar.
Tel: +974 4476 3993, 4476 3994
Fax: +974 4476 3388
Email: [email protected]
Workshop
Street 20
Sihiliya Industrial Area
Doha, Qatar
KEY CONTACT PERSONS:
1. Kutty Mammad Mob: +974 5580 8549 Managing Director Email: [email protected] 2. Mohammed Koya Mob: +974 7446 2746 Sales Engineer Email: [email protected] 3. Vijith Johnson Mob: +974 7446 2745 Workshop Supervisor Email: [email protected] 4. Arshad Tel: +974 4476 3993 Finance Manager Email: [email protected]