The main challenges for Batteries
3 Outperforming Solutions
Exposure Typical Problems Solutions
Battery Performance Low cost batteries have extremely low performance at high temperature and/or in cycling conditions. (typically ¼)
Select right batteries depending on temperature and grid conditions .
High Ambient Temperature Both Battery design life and Cycle life are reduced (Typ 50% at 30-35C)
Temp Controlled Storage and Installation in Cooling Cabinet
Repeated Power Outages Battery does not have time to recharge due to Repeated Cycles.State of Charge will decline and Batteries will dry out and fail.
Use New Battery can fast recharge or operate in partial state of charge
OverCharge Incorrect rectifer settings (ie Boost) can significantly shorten battery life.Battery is overheated (risk of Thermal runaway/ leaking) Design life reduced to 1/5.
Review Rectifier settings or use Float Voltage recharge
Why are Batteries failing so early in many countries ?
Electric AC Grids drive needs for different batteries
Stable AC Grids
Float Battery
Source: NASA GSFC
No AC Grid
Deep Cycling Battery
Very Unstable Grids
PSOC Cycling Battery
40% of the worlds population lives with no electricity or with unstable electric grids
10 years Design float LifeHigh Cyclic performance
Range : 13Ah – 170Ah
Telecom Products Range
AGM
Silver Technology
PSOC Cyclic PerformanceSpecially Designed for Unstable GridRange 84Ah-142Ah
AGM
Blue Technology
OPZV
Solar Technology
Deep Cycle PerformanceDesigned for Off grid
Range : 200Ah-2000Ah
Stable Grid
Unstable Grid
Off Grid
AGM
Red Technology
15 years Design float LifePure Lead TechnologySpecially design for Stable gridRange from 50Ah to 180Ah
Thin-plates = more plates per cell = increased surface area Minimal spacing between plates, typically <1mm Very low internal resistance, hence:
High volumetric power density High gravimetric power density Rapid recharge capability (no current limit) Superior Low Temperature Performance
Very high pack compression High Cycling Capability
Premium Plastic Standard Plastics
NorthStar PPO PC/ABS ABS PP
Halogen free V0 Yes Yes No No
High temp (65°C) sustainability Yes No No Yes
Ability to be left beyond end-of-life without degrading Yes No No Yes
Ability to maintain high pack compression with minimum deflection ***** **** *** *
Material cost * ** ** ***
NorthStar PPO Plastic Technology Designed for long and reliable life in any condition
NorthStar Superior Technology
NSB Red Technology
NSB Red Star TechnologyTM using Pure Lead has been developed to provide exceptionally long float life for telecommunication applications under stable AC grid conditions.
Design float life of 15-years @ 20°C and @ 2.27VPC
High energy density
Non-halogenated V0 plastic container and lid
Stable up to 65°C
Twin venting port
Available Q4 2010
DimensionsCapacity /Ah
Height /mm Width /mm Depth /mmNSB60 Red 263 108 287 60NSB92 Red 264 108 396 92NSB100 Red 287 108 396 100NSB100X Red
264 110 520 100
NSB150 Red 320 125 283 150NSB180 Red 320 125 560 180
NSB Silver Technology
70
80
90
100
110
0% 20% 40% 60% 80% 100% 120% 140% 160% 180% 200%
Design Float Life
Cap
acit
y
NSB Silver Alloy
Calcium alloy
Patented Silver Alloy• Increased Life under Float conditions• Higher Temperature Performance +65C • Higher Cycling Capabilities• Reduced grid corrosion rate 10 years Design float Life
Superior Cycling Performance
12V Front Terminal 12V Top Terminal• NSB 40 FT . NSB13• NSB 60 FT . NSB40• NSB 90 FT . NSB 75• NSB 100 FT . NSB90• NSB 110 FT . NSB125• NSB 155 FT• NSB 170 FT
• Easy and Safe Set up
- No Boost Voltage required
- No Full recharge required after each cycle - PSOC Capable
• Faster recharge
• High cyclic capabilities - Up to 2500 cycles at 25% DOD
NSB Blue Technology – Designed for Unstable Grid
NSB 100 BLUE and NSB170 BLUE now available Up 2 to 3 Times more cycles than NSB Standard .
0%
20%
40%
60%
80%
100%
0 4 8 12 16 20 24
Sta
te O
f C
har
ge
Recharge Time /hours
Standard AGM22-hour recharge
NBS Blue2-hour recharge
NSB Blue Technology – Designed for Unstable Grid
Fastest Float Recharge
• Blue Technology can repeatedly cycle in lower State of charge window utilizing full rectifier power
• Standard AGM needs to be recharged to >103%
Unstable Grid Field Trial - Bangladesh
0 250 500 750 1000 1250 1500 1750 2000 2250
10
10.5
11
11.5
12 SE Asia Cycle
Number of Cycles
On-
load
vol
tage
/V
Blue Battery
Standard AGM
In these conditions, Standard AGM will fail after few months. The Blue Battery has completed over 1800 cycles in 1 year of operation and is still working
21
22
23
24
25
26
27
28
29
0 30 60 90
Days
Volta
ge
February March April
Increase in battery life
Unstable AC Grid Outages
Simulated laboratory cycling confirms the large increase in cycle life with the Blue Battery
NSB Solar – OPZV Technology
Designed to DIN 40742 IEC 61427 Solar tested 20 years life time @ 20°C Horizontal and Vertical operation Maintenance Free High Capacity Density and Cyclic Capabilities Halogen free VO container material Operational temperature -40°C - +55°C Panzerpole touch protected DIN 40050 Degassing system Free of leakage Low self discharge Recyclable
• Extra step for horizontal cells during manufacturing
• 100% quality control:
• Pressure tightness test for each single cell
Where and when to use the NSB Technology
10
100
Silver Blue Solar
AC G
rid o
utag
es(h
ours
per
mon
th)
300
720 Off Grid
Unstable Grid
Stable Grid
PSOC Cyclic
High Cyclic
Standby
NorthStar.More than just a battery company.