productsTR (Temporary Refuge) pressurization unit
1
2 3
4 5
APPLICATION
Our TR-unit basically consists of an explosion proof fan, a filter section that filtrates H2S & SO2 and optionally a heater. The power supply is coming from the vessels Uninterrupted Power Supply (UPS) system or optionally by a battery power pack to ensure operation at all times.Our TR unit provides clean filtered fresh air, free from H2S & SO2 contaminates in an over pressured Temporary Refuge area. Three levels of filtration (G4, F7, and active carbon) is applied to incoming air before being supplied to the TR. The control system constantly compares inside and outside pressures and LEL’s, and should the TR area pressurization or LEL levels fail, provide a visual and/or audible warning.Our TR unit is designed for external installation to TR areas with a supply duct to the TR area interior. The TR unit control panel is designed to be installed internally within the TR area. When the TR unit is operational the unit is designed as a fail-safe system, i.e. should the unit sustain damage or an air seal leaks, then clean air will leak out of the unit rather than contaminated air being drawn in.During normal operation is the TR unit “dead” and closed by gastight dampers. It comes operational for emergency situations.
INTRODUCTION
The Cullen Report into the Piper Alpha disaster (Cullen, 1990) recommended that a temporary refuge (TR) should be provided on all offshore installations. The TR is required to have a defined performance standard related to its survivability when exposed to a major accident that includes, but is not limited to, ingress of smoke, flammable and toxic gas. HVAC forms an essential part of this. As the TR is the last space for the crew before abandoning the vessel, rig or platform, the HVAC system should create and maintain a comfortable and safe indoor condition free of any explosive and/or toxic gas-air mixtures. The air quality and pressure inside the TR-zone is than of top priority. This can be created by our special TR pressurization unit (TR-unit).
KEY FEATURES
• Design according DNV, NMD, NORSOK, HSE. ABS, LR & BV;• Ambient range from -20°C/15%RH to +45°C/80%RH• Casing leakage according to class L1, EN-1886• ATEX Zone II• Reliable• Double walled SS316L• UPS powered (optionally with battery power pack)• Easy service and maintenance access;• Standard H2S concentrations 200 / 400 / 600 ppm• Standard capacity 1000, 4000, 6000 and 7500m³/h. (600ppm)
Information
01 - Inlet grill and motorised control damper (Ex) 03 - Purafil SP Blend, dual hydrocarbon filter, ATEX 05 -
02 - Pre filter, class G4, ATEX, Second filter, class F7, ATEX 04 - Fan motor, 3 x 230V / 50 Hz, Ex-II-2G-d-IICT4
Information
01 - Inlet grill and motorised control damper (Ex) 03 - Purafil SP Blend, dual hydrocarbon filter, ATEX 05 -
02 - Pre filter, class G4, ATEX, Second filter, class F7, ATEX 04 - Fan motor, 3 x 230V / 50 Hz, Ex-II-2G-d-IICT4 06 - Flow switch &
- Fan, anti-sparkling, Ex-e/d + brass lining 07 - Motorised gastight damper, Ex - Fan, anti-sparkling, Ex-e/d + brass lining 07 - Motorised gastight damper, Ex
6 6
7
c
HH
FUNCTIONING
- Flow switch & H2S and CH4 sensors (Ex)
TR 1000
Technical Data TR-1000-3 - 50Hz / 60Hz
Ambient H2S concentration 600ppm
TR H2S concentration 10ppm (60min)
Air quantity 1.000m3/h
Pst 1.350Pa
Execution SS316L, ATEX Zone II
Primary filter G4
Secondary filter F7
Tertiary filter Activated Carbon + Alumina
Power supply fan3x380V-50Hz / 3x440V-60HZ
Rated power 1.1kW / 1.3kW
Power supply heater3x380V-50Hz / 3x440V-60Hz
Capacity (custom designed) kW
Power supply valves 1x230V-50Hz / 60Hz
Weight (excl. heater) 1225 kg
Control panel (separate delivery
Safe Area
Technical Data TR-1000-3 - 50Hz / 60Hz Technical Data TR-4000-12 - 50Hz / 60Hz
Ambient H2S concentration 600ppm
TR H2S concentration 10ppm (60min)
Air quantity 4.000m3/h
Pst 1.350Pa
Execution SS316L, ATEX Zone II
Primary filter G4
Secondary filter F7
Tertiary filter Activated Carbon + Alumina
Power supply fan3x380V-50Hz / 3x440V-60HZ
Rated power 3.2kW / 3.7kW
Power supply heater3x380V-50Hz / 3x440V-60Hz
Capacity (custom designed) kW
Power supply valves 1x230V-50Hz / 60Hz
Weight (excl. heater) 2640 kg
Control panel (separate delivery
Safe Area
TR 4000
TR 6000
Technical Data TR-6000-3 - 50Hz / 60Hz
Ambient H2S concentration 600ppm
TR H2S concentration 10ppm (60min)
Air quantity 6.000m3/h
Pst 1.350Pa
Execution SS316L, ATEX Zone II
Primary filter G4
Secondary filter F7
Tertiary filter Activated Carbon + Alumina
Power supply fan3x380V-50Hz / 3x440V-60HZ
Rated power 4.0kW / 4.6kW
Power supply heater3x380V-50Hz / 3x440V-60Hz
Capacity (custom designed) kW
Power supply valves 1x230V-50Hz / 60Hz
Weight (excl. heater) 3350 kg
Control panel (separate delivery
Safe Area
Technical Data TR-6000-3 - 50Hz / 60Hz
Alternatives available on request.Due to continuous product development Heinen Hopman reserves the right to introduce alterations without prior notice.
Technical Data TR-7500-12 - 50Hz / 60Hz
Ambient H2S concentration 600ppm
TR H2S concentration 10ppm (60min)
Air quantity 7.500m3/h
Pst 1.350Pa
Execution SS316L, ATEX Zone II
Primary filter G4
Secondary filter F7
Tertiary filter Activated Carbon + Alumina
Power supply fan3x380V-50Hz / 3x440V-60HZ
Rated power 5.5kW / 6.4kW
Power supply heater3x380V-50Hz / 3x440V-60Hz
Capacity (custom designed) kW
Power supply valves 1x230V-50Hz / 60Hz
Weight (excl. heater) 3785 kg
Control panel (separate delivery
Safe Area
TR 7500
PROjECTS wITh h&h’S TR UNIT INSTALLEDjB-114ClientJack-Up BargesGeneration1st Type of platform/vesselHeavy Liftworking areaNorth Sea
workfoxClientWorkfoxGeneration1st Type of platform/vesselMulti purposeworking areaNorth Sea
jB-115ClientJack-Up BargesGeneration2nd Type of platform/vesselHeavy Liftworking areaNorth Sea
EnQuestClientEnQuestGeneration2nd Type of platform/vesselFPSOworking areaNorth Sea
jB-118ClientJack-Up BargesGeneration3rd Type of platform/vesselHeavy Liftworking areaAbu Dhabi
PROjECTS wITh TR PRESSURE TESTS PERFORmED Ensco 72ClientEnscoheliportDen Helder Type of vesselOilrigLocationOffshore Northsea
Seafox 2ClientWorkfoxheliportDen Helder Type of vesselAccommodation bargeLocationOffshore Northsea
Seafox 4ClientWorkfoxheliportDen Helder Type of vesselAccommodation bargeLocationOffshore Northsea
Seafox 5ClientWorkfoxheliportDen Helder Type of vesselAccommodation bargeLocationOffshore Northsea
Seafox 7ClientWorkfoxheliportDen Helder Type of vesselAccommodation bargeLocationOffshore Northsea
Switf-1ClientSwitf - Switf 1heliportDen Helder Type of vesselAccommodation bargeLocationOffshore Northsea
L10-AClientEngie (GDF Suez)heliportDen Helder Type of vesselOilrigLocationOffshore Northsea
G17-AClientEngie (GDF Suez)heliportDen Helder Type of vesselOilrigLocationOffshore Northsea
G5-AClientEngie (GDF Suez)heliportDen Helder Type of vesselOilrigLocationOffshore Northsea
L15-AClientEngie (GDF Suez)heliportDen Helder Type of vesselOilrigLocationOffshore Northsea
PROjECTS wITh TR PRESSURE TESTS PERFORmED F17-AClientEngie (GDF Suez)heliportDen Helder Type of vesselOilrigLocationOffshore Northsea
EndeavourClientGMSheliportDen Helder Type of vesselAccommodation bargeLocationOffshore Northsea
EnduranceClientGMSheliportNowitch Type of vesselAccommodation bargeLocationOffshore Northsea
jB-114ClientJack-up BargeheliportDen Helder Type of vesselAccommodation bargeLocationOffshore Northsea
jB-115ClientJack-up BargeheliportDen Helder Type of vesselAccommodation bargeLocationOffshore Northsea
jB-117ClientJack-up BargeheliportDen Helder Type of vessel-LocationOffshore Northsea
jB-118ClientJack-up BargeheliportDen Helder Type of vesselAcommodation bargeLocationOffshore Northsea
Enquest ProducerClientEnquestheliportAberdeen Type of vesselFPSOLocationOffshore Northsea
BargeClientContour GlobalheliportRwanda Type of vesselMethane gas bargeLocationLake Kiva - Rwanda
Eirrik RaudeClientOceanrigheliportPort Stanly Type of vesselOilrigLocationOffshore Falkland Islands
hermodClientHeeremaheliportDen Helder Type of vesselSemi submersible rigLocationOffshore Northsea
Oleg StrashnovClientSHLheliportDen Helder Type of vesselSemi submersible vesselLocationOffshore Northsea
www.heinenhopman.com
Heinen & Hopman encourages a more
sustainable world. By providing eco-friendly solutions and serviceswe offer our clients
the option of reducing energy consumption
and thus co2 emissions. Visit
greenmanifest.info for more information.
BrazilT: +55 213 587 4241/4244E: [email protected]
France - La CiotatT: +33 4 4204 8685E: [email protected]
France - AntibesT: +33 6 3090 7786 E: [email protected]
GermanyT:+49 4073 1680E: [email protected]
GermanyT:+49 471 9869 300E: [email protected]
IndiaT: +91 336 499 1293E: [email protected]
ItalyT: +39 018 745 7970E: [email protected]
The Netherlands (hQ)T: +31 33 299 2500E: [email protected]
The Netherlands (Rotterdam)T: +31 78 890 8050E: [email protected]
NorwayT: +47 6919 0900E: [email protected]
Peoples Republic of ChinaT: +86 213 253 2896E: [email protected]
Peoples Republic of ChinaT: +86 510 8528 1763E: [email protected]
PolandT: +48 914 331 800E: [email protected]
RomaniaT: +40 236 448 222E: [email protected]
RussiaT: +7 (4012) 308 801E: [email protected]
SingaporeT: +65 6897 7879E: [email protected]
South KoreaT: +82 704 901 0000E: [email protected]
SpainT: +34 932 259 668E: [email protected]
SwedenT: +46 3121 7500E: [email protected]
TurkeyT: +90 216 493 8118E: [email protected]
UAE (Abu Dhabi) T:+971 2550 4147E: [email protected]
UAE (Dubai)T: +971 4263 5453E: [email protected]
USA - Fort Lauderdale, FloridaT: +1 954 463 0110E: [email protected]
USA - houma, Louisiana T: +1 985 876 7982E: [email protected]