terminal boxes - ЗАВОД...
TRANSCRIPT
Terminal boxes1
Terminal boxes
Term
inal
box
es
Increased degree of reliability Exe, Exia, RP, RОKSRV (SA)
series aluminum alloy boxes
p. 9
KSRV-N (KSRV-S, SA/SS) series boxes
of stainless steel
p. 12
KSRV-P (KSRV-KP, SA/P) series explosion-proof
boxes of polyester
p. 15
Order Placement
KSRV X (X X – X X) – X X (X) – X X (X) / X – Specifications (TU) 3400-005-72453807-07
Product nameCode of dimensions Quantity of terminal blocksType of terminal blockQuantity of cable glandsType of cable glandSide of disposition of cable glandOptions, accessories and versions
p. 19
Equipment selection form
p. 21
Exd IIC, RV Exd series explosion-proof boxesSHORV (CCFE)
series aluminum alloy boxes
p. 23
Order Placement
SHORV X – (X X – X X) – X X (X) – X X (X) / X – Specifications (TU) 3400-005-72453807-07
Product nameDimension codeQuantity of terminal blocksType of terminal blockQuantity of cable glandsType of cable glandSide of arrangement of cable glandOptions, accessories and versions
p. 26
SHORVA (CCA) series aluminum alloy boxes
p. 27
Order Placement
SHORVA X – (X X – X X) – X X (X) – X X (X) / X – Specifications (TU) 3400-005-72453807-07
Product nameCode of dimensionQuantity of terminal blocksType of terminal blockQuantity of cable glandsType of cable glandSide of arrangement of cable glandOptions, accessories and versions
p. 29
Equipment selection form
p. 30
KKVA (S) series aluminum alloy boxes
p. 31
AccessoriesCable glands
PlugsAdapters
p. 365
9
KSRV SA
EXE,
EXIA
, RP,
RO
1
• Increased mechanical resistance to impulses and vibration.
• Increased thickness of box walls. • Increased lateral surface for cable glands mounting.• External brackets for convenient mounting.• 10 dimension-types.
MARKING
1Ex e II T6...T4 Gb,
1Ex e [ia] IIC T6... T4 Gb,
0Ex ia IIC T6...T4 Ga,
Ex ia IIIC T85°C...T135°C Da,
Ex tb IIIC T85°C ...T135°C Db
MINING EQUIPMENT MARKING
RO Ex ia I Ma,
RP Ex e I McRN2
CERTIFICATES AND PERMITSGOST R ISO 9001-2015 (ISO 9001:2015)ТС RU С-RU.AA87.В.00244TC RU C-RU.МЛ02.B.00626РОСС RU.МШ06.Н00147Permit of the Federal Environmental, Industrial and Nuclear Supervision Service of Russia No. 12.02246.315Register of Shipping Certificate of Type Approval No. 16.03660.315Specifications (TU) 3400-005-72453807-07НСОПБ.RU.ПР 207.Н.00069PJSC “GAZPROM” No. Г000.RU.1131.H00666
NORMSGOST R IEC 60079-0-2011GOST 14254-96 (IEC 529-89)GOST 12.2.007.0-75GOST 30852.0-2002 (IEC 60079-0:1998)GOST 30852.8-2002GOST 30852.10-2002 (IEC 60079-11:1999)GOST 30852.20-2002 Safety Regulations 05-618-03Safety Regulations 03-553-03GOST IEC 61241-1-1-2011TR CU 012/2011, TR CU 004/2011GOST 24754-2013Ch. 7.3 of Electrical Installation CodeCh. 7.4 of Electrical Installation CodeRegulatory Document 5.2-093-2004
TECHNICAL CHARACTERISTICS
Installation
Class I, mine gas and dust;Class II, subgroups IIA, IIB, IIC, zones 0, 1, 2;Class III by dust, explosive dust atmospheres, which contain volatile solids, non-conducting and conducting dust;Underground mines, non-hazardous with gas (methane) and coal dust;Non-hazardous area of surface buildings and open sites;Facilities supervised by the Russian Maritime Register of Shipping; Hazardous industrial facilities
Maximal voltage, V
~1000 / A250~2200~2800~10 000
Maximal electric current intensity, A
800
Sealing
Silicone rubber (in a groove of lid)
Fastening of enclosure
4 external mounting points
Mounting inside enclosure
2 or 4 mounting poles for mounting plate
Climatic category
NF1 (on request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.13**, W5)
Chemical resistant version
On request C1, C2, C3
66IPHOLOD
10
KSRV SAEX
E, E
XIA
, RP,
RO
1
OPTIONS, ACCESSORIES AND VERSIONS
DESCRIPTION MARKINGLid fixing with hinges /PETLIA
Draining device for condensate draining /DKUV
Ventilation device for moisture removal /VKUV
Climatic category MU1 /MORE
Version for minimum operating temperature –75°С /HOLOD
Version for the tropics with protection against insects /TERMITI
‘Small break’ special version for nuclear power stations /MALAYA TECH
Earthquake-resistant version /MSK-64
Customer acceptance /PRIEMKA
E30 Fire resistance rating (GOST R 53316-2009 “CABLE LINES. CIRCUIT INTEGRITY UNDER FIRE”) /POZHAR
Nameplates with retroreflective coating /SVP
Nameplates with customer caption /NADPIS «_»
Painting of external surface using the colour required by customer (on request) /RAL (code)
DESCRIPTION MARKINGBolt with seal /PLOMBA
Device for joining of cable screens /ECRAN
Neutral bus bar /SHINA N
Internal earthing bus bar /SHINA Z
Bridges among terminals according to cus-tomer’s layout /SHEMA
Marking of terminal blocks according to cus-tomer’s layout /MARK
Special incoming switchgear for pair of heat-ing cables /OKT
Mounting plate of aluminium alloy /ALP
Non-explosion-proof version /PROM
Internal thermal insulation /TEPLOIZOLYATSIYA
Thermal heating for automatic mechanisms /OBOGREV
Mounting plate of stainless steel /NP
Anti-condensation coating /AP
OVERALL AND MOUNTING DIMENSIONS
B
A
C
axb
c
s1
s2
Y
X1ØD X2X
MOUNTING PLATE
11
KSRV SA
EXE,
EXIA
, RP,
RO
1
Dimensions of KSRV enclosures of aluminium alloy
Type of box
Dimensions, mmWeight,
kg
Type of mounting
plate
Dimensions, mm Weight, kg
external internal mounting
A B C a b c s1 s2 X X1 Y ØD A B C D
KSRV111109 112 112 91 102 102 72 5 6 94 — 94 6,3 0,8 K1111A 90 68 87 — 0,05KSRV171109 172 112 91 162 102 72 5 6 154 — 94 6,3 1,1 K1711A 160 68 67 — 0,09KSRV141410 149,5 149,5 107 139,5 139,5 88 5 6 131 — 131 6,3 1,4 K1414A 130 105 124 — 0,1KSRV202012 200 200 120 188 188 101 4 3 180 — 180 6,5 1,9 K2020A 185 142 172 — 0,20 KSRV301410 304,5 149,5 109 294,5 139,5 88 5 6 285 — 131 6,3 2,4 K3014A 285 97 271 84 0,23KSRV302310 305 230 110 293 216 90 4 3 285 — 210 6,5 2,9 K3023A 285 180 271 167 0,41KSRV-U302310 308 232 100 290 216 81 7 3,5 288 — 211 7 3,5KSRV302318 305 230 189 290 216 170 4 3 286 — 210 6,5 3,6 K3023A 285 180 271 167 0,41KSRV-U302318 307 231 180 286 212 161 7 3 286 — 211 7 5,1KSRV513321 511 336 207 479 294 178 8 8 434 — 338 9 15 K5133A 450 254 438 239 0,77KSRV663221 669 329 207 637 287 178 8 8 576 288 332 9 18,7 K6632A 598 250 586 231 1,21KSRV626221 622 622 208 580 580 178 8 8 530 265 616 9 29,5 K6262A 532 532 520 520 2
If you need an enclosure of bigger size, it is possible to produce the unit of several enclosures.
Maximum quantity of cable glands installed on the sides of a box (А – long side, В – short side)*
R, GOST 6211
M, GOST 24705
KSRV111109 KSRV171109 KSRV141410 KSRV202012 KSRV301410 KSRV302310 KSRV302318 KSRV663221A B A B A B A B A B A B A B A B
1/2" M20x1,5 2/1 2/1 5/4 2/1 4/4 4/4 8/8 8/8 12/12 4/4 12/12 8/6 24/24 16/16 48/42 24/243/4" M25x1,5 1/1 1/1 3/3 1/1 3/2 3/2 6/6 6/6 8/5 3/2 8/5 5/4 18/16 14/10 36/36 18/15
1" M32x1,5 1/1 1/1 2/2 1/1 2/1 2/1 3/3 3/3 5/4 2/1 5/4 4/3 12/10 9/8 22/20 12/101 1/4" M40x1,5 1/1 1/1 2/2 1/1 1/1 1/1 2/2 2/2 3/3 1/1 3/3 2/2 8/8 6/5 16/12 8/81 1/2" M50x1,5 — — — — 1/- 1/- 2/2 2/2 3/- 1/- 3/- 2/- 6/5 4/4 10/10 6/5
2" M63x1,5 — — — — — — 1/1 1/1 — — — — 3/3 2/2 6/6 3/32 1/2" M75x1,5 — — — — — — — — — — — — 2/2 1/1 4/4 2/2
3" M90x1,5 — — — — — — — — — — — — 2/2 1/1 4/4 2/2
Recommended cable glandsKNV, КOV, KNVTN, KNVТV, KNE, KNVZ See p. 365
Codes matching tablePrevious international name of product made
by “ZAVOD GORELTEX” CO. LTD. Specifications (TU) 3400-005-72453807-07
Customs union name of product made by “ZAVOD GORELTEX” CO. LTD.
Specifications (TU) 3400-005-72453807-07 Fuse boxes with increased degree of reliability EXE EXIA RP RО
SA, KSRV KSRVSA111108, KSRV111108 KSRV111109SA171108, KSRV171108 KSRV171109SA141410, KSRV141410 KSRV141410SA202012, KSRV202012 KSRV202012SA301410, KSRV301410 KSRV301410SA302310, KSRV302310 KSRV302310
SAG302310, KSRV-U302310 KSRV-U302310SA302318, KSRV302310 KSRV302318
SAG302318, KSRV-U302318 KSRV-U302318SA473018, KSRV473018
KSRV513321SAG473018, KSRV-U473018
SAG623018, KSRV623018 KSRV663221SAG606018, KSRV-U606018 KSRV626221
12
KSRV-N KSRV-S, SA/SSEX
E, E
XIA
, RP,
RO
1
• A possibility of installing a lock on the lid.• A possibility of using replaceable inserts while mounting cable
glands.• Increased area of side surfaces for installation of cable glands.
MARKING
1Ex e II T6...T4 Gb
1Ex e [ia] IIC T6...T4 Gb
0Ex ia IIC T6...T4 Ga
1Ex d e IIB T5 Gb
1Ex d e IIC T5 Gb
1Ex e II T3...T2 Gb X (for /ТЕRМО version)
1Ex e [ia] IIC T3...T2 Gb X (for /ТЕRМО version)
0Ex ia IIC T3...T2 Ga X (for /ТЕRМО version)
Ex ia IIIC T85°С... T135°С Da
Ex tb IIIC T85°С... T135°С Db
MINING EQUIPMENT MARKING
RO Ex ia I Ma
RP Ex e I McRN2
CERTIFICATES AND PERMITSGOST R ISO 9001-2015 (ISO 9001:2015)ТС RU С-RU.AA87.В.00244TC RU C-RU.МЛ02.B.00626 РОСС RU.МШ06.Н00147 НСОПБ.RU.ПР 207.Н.00069 Permit of the Federal Environmental Industrial and Nuclear Supervision Service of Russia No. РРС 00-044017Register of Shipping, Certificate of Type ApprovalNo. 16.03662.315Specifications (TU) 3400-005-72453807-07PJSC “GAZPROM” No. Г000.RU.1131.H00666
NORMSGOST R IEC 60079-0-2011GOST 12.2.007.0-75, GOST 24754-2013GOST 14254-96 (IEC 529-89)GOST 30852.0-2002 (IEC 60079-0:1998)GOST 30852.10-2002 (IEC 60079-11:1999)GOST 30852.8-2002GOST 30852.20-2002TR CU 012/2011, TR CU 004/2011,Safety Regulations 05-618-03,Safety Regulations 03-553-03,GOST IEC 61241-1-1-2011,Ch. 7.3 of Electrical Installation CodeCh. 7.4 of Electrical Installation CodeRegulatory Document 5.2-093-2004
TECHNICAL CHARACTERISTICS
Installation
Class I, mine gas and dust;Class II, subgroups IIA, IIB, IIC, zones 0, 1, 2;Class III by dust, explosive dust atmospheres, which contain volatile solids, non-conducting and conducting dust;Underground mines, non-hazardous with gas (methane) and coal dust;Non-hazardous area of surface buildings and open sites;Facilities supervised by the Russian Maritime Register of Shipping;Hazardous industrial facilities
Maximal voltage, V
10 000~1000 / A250
Maximal electric current intensity, A
800/400
Sealing
Silicone rubber (in a groove of lid)
Fastening of lid
Removable lid with captive stainless steel screws
Mounting inside enclosure
4 mounting poles for mounting plate
Climatic category
NF1 (on request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.13**, W5)
Chemical resistant version
On request C1, C2, C3
66IPTERMO
13
KSRV-N KSRV-S, SA/SS
EXE,
EXIA
, RP,
RO
1
OPTIONS, ACCESSORIES AND VERSIONS
DESCRIPTION MARKINGDraining device for condensate draining /DKUV
Ventilation device for moisture removal /VKUV
Version for high temperature up to +185°С /TERMO
Version for the tropics with protection against insects /TERMITI
‘Small break’ special version for nuclear power stations /MALAYA TECH
Earthquake-resistant version /MSK-64
Customer acceptance /PRIEMKA
Nameplates with customer caption /NADPIS"_"
Mounting plate of stainless steel /NP
Lid fixing with hinges /PETLIYA
Lid lock /ZAMOK
E30 Fire resistance rating for (GOST R 53316-2009 “CABLE LINES. CIRCUIT INTEGRITY UNDER FIRE”) /POZHAR
Bolt with seal /PLOMBA
DESCRIPTION MARKINGNameplates with retroreflective coating /SVP
Device for joining of cable screens /ECRAN
Neutral bus bar /SHINA N
Internal earthing bus bar /SHINA Z
Replaceable inserts for cable glands /SPKV
Bridges among terminals according to customer’s layout /SHEMA
Marking of terminal blocks according to custom-er’s layout /MARK
Special incoming switchgear for pair of heating cables /OKT
Non-explosion-proof version /PROM
Internal thermal insulation /TEPLOIZOLYATSIYA
Thermal heating for automatic mechanisms /OBOGREV
Stainless steel of 03Х17Н13М2 mark according to GOST 5949-75 (316L) /N
OVERALL AND MOUNTING DIMENSIONS
A G1
G2
∅10
H2
H1
B
C
А
B
C
17,5
17,5
H2
H1
∅10
G1
G2
KSRV-N151512, KSRV-N231815, KSRV-N232312, KSRV-N322312, KSRV-N342315, KSRV-N343415,KSRV-N232315, KSRV-N271815, KSRV-N301515 KSRV-N402315, KSRV-N453415, KSRV-N534315
14
KSRV-N KSRV-S, SA/SSEX
E, E
XIA
, RP,
RO
1
Line of KSRV-N…* series explosion-proof boxes*
Type of box External dimension Mounting, mmWeight, kgMethod 1 Method 2
А В С G1 H1 G2 H2KSRV-N151512 150 150 120 120 174 174 120 2,00KSRV-N231815 230 180 150 200 204 254 150 3,39KSRV-N232312 230 230 120 200 254 254 200 3,75KSRV-N232315 230 230 150 200 254 254 200 4,04KSRV-N271815 270 180 150 240 204 294 150 3,83KSRV-N301515 300 150 150 270 174 324 120 3,68KSRV-N322312 320 230 120 260 262 352 170 4,99KSRV-N342315 340 230 150 280 262 372 170 5,60KSRV-N343415 340 340 150 280 372 372 280 7,56KSRV-N402315 400 230 150 340 262 432 170 6,43KSRV-N453415 450 340 150 390 372 482 280 9,56KSRV-N534315 530 430 150 470 462 562 370 13,27
*At customer’s request irregular size can be produced, maximum overall dimensions are 1000x1200x400 mm. It is possible to install hinges and locks on the lid of the enclosure. Minimum orderable quantity of enclosures of irregular sizes is 20 pcs.
Codes matching tablePrevious international name of product made by “ZAVOD GORELTEX” CO. LTD.
Specifications (TU) 3400-005-72453807-07 Customs union name of product made by “ZAVOD GORELTEX” CO. LTD.
Specifications (TU) 3400-005-72453807-07 Terminal boxes with increased degree of reliability EXE EXIA RP RО
KSRV-S KSRV-NKSRV-S151512 KSRV-N151512KSRV-S231815 KSRV-N231815KSRV-S232312 KSRV-N232312KSRV-S232315 KSRV-N232315KSRV-S271815 KSRV-N271815KSRV-S301515 KSRV-N301515KSRV-S322312 KSRV-N322312KSRV-S342315 KSRV-N342315KSRV-S343415 KSRV-N343415KSRV-S402315 KSRV-N402315KSRV-S453415 KSRV-N453415KSRV-S534315 KSRV-N544315
Previous international name of product made by “ZAVOD GORELTEX” CO. LTD. Specifications (TU) 3400-005-72453807-07
Customs union name of product made by “ZAVOD GORELTEX” CO. LTD. Specifications (TU) 3400-005-72453807-07
Equivalent boxesKSRV-N, SA/SS KSRV-N
SA/SS111108, KSRV-N 111108KSRV-N151512SA/SS141410, KSRV-N 141410
SA/SS161610, KSRV-N 161610SA/SS171108, KSRV-N 171108 KSRV-N231815
SA/SS202020,KSRV-N 202020KSRV-N232312KSRV-N232315
SA/SS261210, KSRV-N 261210KSRV-N271815
SA/SS261610, KSRV-N 261610SA/SS301410, KSRV-N 301410
KSRV-N301515SA/SS262614, KSRV-N 262614SA/SS302310, KSRV-N 302310 KSRV-N322312SA/SS302318, KSRV-N 302318
KSRV-N342315SA/SS361614, KSRV-N 361614SA/SS362614, KSRV-N 362614
KSRV-N343415SA/SS303020, KSRV-N 303020SA/SS303030, KSRV-N 303030 KSRV-N402315SA/SS402618, KSRV-N 402618
KSRV-N453415SA/SS403618, KSRV-N 403618SA/SS404020, KSRV-N 404020
KSRV-N534315SA/SS473018, KSRV-N 473018
SA/SS623018, SA/SS601614, KSRV-N 601614, SA/SS1007030, KSRV-N 1007030, SA/SS505020, KSRV-N 505020, SA/SS505030, KSRV-N 505030, SA/SS505040, KSRV-N 505040, SA/SS602618, KSRV-N 602618, SA/SS606020, KSRV-N 606020, SA/SS606030, KSRV-N 606030, SA/SS606040, KSRV-N 606040, SA/SS404040,
KSRV-N 404040, KSRV-N 404030, SA/SS10010030, KSRV-N 10010030
Manufacture according to special order
Recommended cable glandsKNV, КOV, KNVTN, KNVТV, KNE, KNVZ See p. 365
15
KSRV-P KSRV-KP, SA/P
EXE,
EXIA
, RP,
RO
1
• Increased area of side surfaces for installation of cable glands.
• Antistatic shockproof reinforced polyester, UV stabilized and resistant to operation environment.
• 18 dimension-types.
MARKING
1Ex e II T6...T5 Gb
1Ex e [ia] IIC T6...T5 Gb
0Ex ia IIC T6...T5 Ga
Ex ia IIIC T85°С... T100°С Da
Ex tb IIIC T85°С... T100°С Db
MINING EQUIPMENT MARKING
RO Ex ia I MaRN1, RN2
CERTIFICATES AND PERMITSGOST R ISO 9001-2015 (ISO 9001:2015)ТС RU С-RU.AA87.В.00244TC RU C-RU.МЛ02.B.00626РОСС RU.МШ06.Н00147 НСОПБ.RU.ПР 207.Н.00069 Permit of the Federal Environmental, Industrial and Nuclear Supervision Service of Russia No. РРС 00-044017Register of Shipping, Certificate of Type ApprovalNo. 16.03661.315Specifications (TU) 3400-005-72453807-07PJSC “GAZPROM” No. Г000.RU.1131.H00666
NORMSGOST R IEC 60079-0-2011GOST 12.2.007.0-75GOST 30852.0-2002 (IEC 60079-0:1998) GOST 30852.10-2002 (IEC 60079-11:1999)GOST 30852.8-2002GOST 30852.13-2002 (IEC 60079-14:1996)TR CU 012/2011, TR CU 004/2011GOST IEC 61241-1-1-2011GOST 24754-2013Ch. 7.3 of Electrical Installation CodeCh. 7.4 of Electrical Installation CodeRegulatory Document 5.2-093-2004Safety Regulations 05-618-03Safety Regulations 03-553-03GOST 30852.20-2002
TECHNICAL CHARACTERISTICS
Installation
Class I, mine gas and dust;Class II, subgroups IIA, IIB, IIC, zones 0, 1, 2;Class III by dust, explosive dust atmospheres, which contain volatile solids, non-conducting and conducting dust;Underground mines, non-hazardous with gas (methane) and coal dust;Non-hazardous area of surface buildings and open sites;Facilities supervised by the Russian Maritime Register of Shipping; Hazardous industrial facilities
Maximum voltage, V
~1000 / A250
Maximum electric current intensity, A
400
Sealing
Silicone rubber (in a groove of lid)
Fastening of lid
Removable lid with non-falling-out screws made of stainless steel
Mounting inside enclosure
2 or 4 mounting poles for mounting plate
Climatic category
NF1 (on request NF4, NF5, T1, T2, T3, T5, F5, MU1, MU2, MU3, MU4, W5)
Chemical resistant version
On request C1, C2, C3
66IP
16
KSRV-P KSRV-KP, SA/PEX
E, E
XIA
, RP,
RO
1
OPTIONS, ACCESSORIES AND VERSIONS
DESCRIPTION MARKINGLid fixing with hinges /PETLIA
Draining device for condensate draining /DKUV
Ventilation device for moisture removal /VKUV
Climatic category MU1 /MORE
Version for the tropics with protection against insects /TERMITI
Customer acceptance /PRIEMKA
Nameplates with customer caption /NADPIS «_»
Nameplates with retroreflective coating /SVP
Device for joining of cable screens /ECRAN
Bridges among terminals according to customer’s layout /SHEMA
Bolt with seal /PLOMBA
Neutral bus bar /SHINA N
DESCRIPTION MARKINGInternal earthing bus bar /SHINA Z
Marking of terminal blocks according to cus-tomer’s layout /MARK
Special incoming switchgear for pair of heat-ing cables /OKT
Mounting strip with outlets /REYKA
Mounting plate /PLANKA
Non-explosion-proof version /PROM
Internal thermal insulation /TEPLOIZOLYATSIYA
Thermal heating for automatic mechanisms /OBOGREV
Mounting plate of stainless steel /NP
Internal strip for strengthening the fastenersof cable glands and earth circuit continuity /PTSZ
Electric shock protection class II /KZCH2
OVERALL AND MOUNTING DIMENSIONS
∅dDCB
A E
KSRV-P100807, KSRV-P141210, KSRV-P161609, KSRV-P170807KSRV-P221512, KSRV-P221512, KSRV-P221515, KSRV-P261812, KSRV-P302113, KSRV-P332212,
KSRV-P332215, KSRV-P362216, KSRV-P363616, KSRV-P423019
d
DCB
A
EIE
I
KSRV-P723616, KSRV-P723622, KSRV-P723624
17
KSRV-P KSRV-KP, SA/P
EXE,
EXIA
, RP,
RO
1
MOUNTING WITH MOUNTING PLATES /PLANKA
KSRV-P100807, KSRV-P141210, KSRV-P161609 KSRV-P211311, KSRV-P221515, KSRV-P261812, KSRV-P302113, KSRV-P332212, KSRV-P332215, KSRV-P362216, KSRV-P363616, KSRV-P423019
KSRV-P723616, KSRV-P723622, KSRV-P723624
Line of dimension-types of KSRV-P series explosion-proof boxes
Enclosure marking A B C D d E I D1 d1 E1 E2 Weight, kg
KSRV-P100807 105 85 76 73 5 70 — 125 9 — — 0,5KSRV-P141210 148,5 129,5 109 118 8 105,5 — 165 9 — — 1,2KSRV-P161609 160 160 92,5 148 8 19 — 195 9 — — 1,8KSRV-P170807 175 85 76 73 4,8 138 — — 9 205 — 0,6KSRV-P211311 210 129,5 106,5 116 7 166 — — 9 235 — 1,5KSRV-P221512 224,5 149,5 121 135 6,6 182 — 175 9 64 — 1,7KSRV-P221515 224,5 149,5 151 135 6,6 182 — 175 9 64 — 1,8KSRV-P261812 259,5 180 121 163,5 6,6 217 — 211 9 86 — 2KSRV-P302111 299 209 107 195 6,6 254 — 245 9 60 — 2,4KSRV-P302113 299 209 134 195 6,6 254 — 245 9 60 — 2,9KSRV-P332212 329,5 224 123 210 6,6 286 — 245 9 164 — 3,0KSRV-P332215 329,5 224 153 210 6,6 285 — 245 9 164 — 3,1KSRV-P362216 360 220 160,5 203 8,8 300 — 245 9 114 — 4,5KSRV-P363616 360 360 161,5 342 8,8 297 — 385 9 124 — 6,0KSRV-P423019 420 300 187,5 287,5 8,8 362 — 315 9 184 — 6,5KSRV-P723616 720 360 162 335 8,8 311 347 385 9 102 104 12,5KSRV-P723622 720 360 221 331 8,8 311 347 385 9 118 154 13,5KSRV-P723624 720 360 243 332 8,8 311 347 385 9 118 154 13,5
Possibility of KSRV-P series boxes batching with mounting plates and mounting stripes
Marking of enclosure Mounting plate Mounting stripe /REYKAName of component Quantity per a box, pcs
KSRV-P100807 KP1008A — —KSRV-P141210 — — —KSRV-P161609 — — —KSRV-P170807 KP1708A A0154-01 2KSRV-P221512 KP2215A A0154-02 2KSRV-P221515 KP2215A A0154-02 2
18
KSRV-P KSRV-KP, SA/PEX
E, E
XIA
, RP,
RO
1
Marking of enclosure Mounting plate Mounting stripe /REYKAName of component Quantity per a box, pcs
KSRV-P261812 KP2618A A0154-03 2KSRV-P302113 KP3021A A0154-04 2KSRV-P332212 KP3322A A0154-05 2KSRV-P332215 KP3322A A0154-05 2KSRV-P362216 KP3622A A0154-06 2KSRV-P363616 KP3636A A0154-07 2KSRV-P423019 KP4230A A0154-08 2KSRV-P723616 KP7236A A0154-08 2KSRV-P723622 KP7236A A0154-08 2KSRV-P723624 KP7236A A0154-08 2
Codes matching tablePrevious international name of product made by “ZAVOD GORELTEX”
CO. LTD. Specifications (TU) 3400-005-72453807-07 Customs union name of product made by “ZAVOD GORELTEX”
CO. LTD. Specifications (TU) 3400-005-72453807-07 Terminal boxes with increased degree of reliability EXE EXIA RO
KSRV-KP KSRV-PKSRV-KP 100807 KSRV-P100807KSRV-KP 141210 KSRV-P141210KSRV-KP 161609 KSRV-P161609KSRV-KP 170807 KSRV-P170807KSRV-KP 211311 KSRV-P211311KSRV-KP 221512 KSRV-P221512KSRV-KP 221515 KSRV-P221515KSRV-KP 261812 KSRV-P261812KSRV-KP 302111 KSRV-P302111KSRV-KP 302113 KSRV-P302113KSRV-KP 332212 KSRV-P332212KSRV-KP 332215 KSRV-P332215KSRV-KP 362216 KSRV-P362216KSRV-KP 363616 KSRV-P363616KSRV-KP 423019 KSRV-P423019KSRV-KP 723616 KSRV-P723616KSRV-KP 723622 KSRV-P723622KSRV-KP 723624 KSRV-P723624
Previous international name of product made by “ZAVOD GORELTEX” CO. LTD. Specifications (TU) 3400-005-72453807-07
Customs union name of product made by “ZAVOD GORELTEX” CO. LTD. Specifications (TU) 3400-005-72453807-07
Equivalent boxes of plastic SA/P KSRV-P
SA/P090907 KSRV-P100807SA/P111108 KSRV-P141210SA/P171108 KSRV-P221512SA/P141410 KSRV-P221515SA/P301410 KSRV-P302113SA/P302310 KSRV-P332212SA/P302318 KSRV-P362216SA/P473018 KSRV-P423019SA/P623018 KSRV-P723616
Recommended cable glandsKNV, КOV, KNVTN, KNVТV, KNE, KNVZ See p. 365
19
Marking formation
Term
inal
box
es
1
TERMINAL BLOCKS SELECTION ALGORITHM For products with Exe protection terminal blocks should be Exe version, for Exia products – Exia version.Terminal block should conform to wire cross-section (for spring terminals terminal block should conform to type of terminal).Consideration must be given to maximum voltage and amperage of connected conductor.Consideration should be given to the type of DIN-rail (specially when it is needed to install different terminal blocks next to eachother).For boxes with Exe and Exiaprotection classes, it is recommended to use terminal blocks with conductor of cooper and zinc alloy,
since they have minimal dissipated power.
In case of contact loss or increase of terminal resistance, due to incorrect installation or corrosion over operating of “e” protection class equipment, terminal blocks become HAZARDOUS for using. It is necessary to check electrical connections in Exe-equipment regularly and maintain them in proper working order.
Terminal blocks (low resistance conductors of cooper and zinc alloy)*Type Description RN1 Screw terminal block 0,2-2,5 sq. mm I=15A V=600V C2 Screw terminal block 0,5-4 sq.mm I=24A V=800V (abbreviated marking С)
RN2 Screw terminal block 0,2–4 sq. mm I = 24А V = 400VC4 Screw terminal block 0,5–6 sq. mm I = 32А V = 800V (abbreviated marking С)
RN4 Screw terminal block 0,2–6 sq. mm I = 32А V = 630VC6 Screw terminal block 0,5–10sq. mm I = 41А V = 800V (abbreviated marking С)
C10 Screw terminal block 0,5–16 sq. mm I = 57А V = 800V (abbreviated marking С) C16 Screw terminal block 0,5–25 sq. mm I = 76А V = 800V (abbreviated marking С) C35 Screw terminal block 0,5–35/50 sq. mm I = 125А V = 800V C50 Screw terminal block 1,5–50/70 sq. mm I = 150А V = 800V (abbreviated marking С) C70 Screw terminal block 1,5–95 sq. mm I = 192А V = 800V (abbreviated marking С)
CDА120 Screw terminal block 4–150/185 sq. mm I = 269А V = 800V (abbreviated marking С) CDA185 Screw terminal block 4–240 sq. mm I = 353А V = 800V (abbreviated marking С)
UT2 Screw terminal block 0,5–4 sq. mm I = 24А V = 1000VUT4 Screw terminal block 0,5–6 sq. mm I = 32А V = 1000VUT6 Screw terminal block 0,5–10 sq. mm I = 41А V = 1000V
UT10 Screw terminal block 0,5–16 sq. mm I = 57А V = 1000VHMM1 Spring terminal block 0,2–2,5 sq. mm I = 17,5А V = 500VHMM2 Spring terminal block 0,2–4 sq. mm I = 24А V = 800VHMM4 Spring terminal block 0,2–6 sq. mm I = 32А V = 800VHMM6 Spring terminal block 0,2–10 sq. mm I = 41А V = 800V
ТE2 Screw terminal block 0,5–4 sq. mm earth ТE4 Screw terminal block 0,5–6 sq. mm earth ТE6 Screw terminal block 0,5–10 sq. mm earth
ТE10 Screw terminal block 0,5–16 sq. mm earth ТE16 Screw terminal block 0,5–25 sq. mm earth ТE50 Screw terminal block 1,5–50/70 sq. mm earth ТE70 Screw terminal block 1,5–95 sq. mm earth
Maximum quantity of terminals depending on section of cable coresType of terminal
blockSection of cable
cores, mmAmpere rating, A
Quantity of terminal rows
KSRV111109
KSRV141410
KSRV171109
KSRV202012
KSRV301410
KSRV302310
KSRV302318
KSRV513321
KSRV663221
KSRV626221
RN1 0,2–2,5 17,51 14 23 28 32 57 64 64 99 140 1202 — — — 72 — 118 118 198 270 180
C2, TE2 0,5–4 241 10 17 22 24 42 48 48 72 104 902 — — — 56 — 90 90 144 206 240
C4, TE4 0,5–6 321 9 14 18 21 33 38 38 64 88 782 — — — 48 — 76 76 128 174 156
C6, TE6 0,5–10 411 7 12 15 17 27 32 32 52 72 622 — — — 40 — 62 62 104 140 124
C10, TE10 0,5–16 571 — 10 12 14 21 24 24 44 58 502 — — — 32 — 48 48 86 112 100
C16, TE16 0,5–25 761 — 8 10 11 18 20 20 36 48 422 — — — — — 40 40 68 94 84
C35, TE35 0,5–50 125 1 — 5 — 8 13 16 16 26 36 31C50, TE50 1–70 150 1 — — 6 7 11 14 14 22 30 27C70, TE70 1–95 192 1 — — — 6 10 12 12 20 26 24
UT2,5 0,14–1,5 201 11 18 23 24 43 48 48 80 110 962 — — — 56 — 96 96 160 218 192
UT4 0,25–4 301 9 15 19 21 34 38 38 70 92 802 — — — 48 — 80 80 134 182 160
UT6 0,25–6 501 7 12 14 17 26 30 30 54 70 612 — — — 40 — 60 60 102 138 122
20
Marking formationTe
rmin
al b
oxes
1
If you need to place terminal blocks for cable with different cross-sections into the box, then the following formula should be used for checking when calculating their possible quantity:
where
X, Y… — quantity of terminal blocks of appropriate cross-section;A, B… — maximum possible quantity of terminal blocks of this cross-section.In case if the inequality is valid, then this way of disposal of terminal blocks in the box is possible.
Otherwise it is necessary to choose bigger size of the box, in case of exceeding of maximum size, a module construction should be used.
Cable glands section See p. 365
MARKING FORMATION
KSRV X (X X – X X) – X X (X) – X X (X) / X – Specifications (TU) 3400-005-72453807-07
Product nameCode of dimensions Quantity of terminal blocksType of terminal blockQuantity of cable glandsType of cable glandSide of disposition of cable glandOptions, accessories and versions
Order example: KSRV301410 (20S2-4S10-1RE10)-2KNV1N(B)-1KOV3N(A)-2KOV3N(C)/AP – SPECIFICATIONS (TU) 3400-005-72453807-07KSRV301410 box, complete with:– 20 terminal blocks, cross-section 2,5 sq. mm– 4 terminal blocks for cable, cross-section 10 sq.mm– 1 “earth” terminal, cross-section 10 sq.mm – 1 cable gland for KOV3 series armored cable on A side– 2 cable glands for KNV1 series not armored cable on B side– 2 cable glands for KOV3 series for armored cable on C side– the box has internal anticondensation coating AP
If you find it difficult to select dimensions of the box according to the required feature, then put the letters X instead of numbers after the name of the box:
Example: KSRV X (20S2-4S10-1RE10)-2KNV1N(B)-1KOVZN(V)/AP- Specifications (TU) 3400-005-72453807-07If you need to order an analogue of KZPM, KZP, KP, KSV series boxes, you can use the following mode of order:KSRV analogue of KZPM 3.1-16/24-12x4-25x2KSRV analogue of KZP 4.2-25/48-12x4-25x8KSRV analogue of KP48-1624KSRV analogue of KSV-4-9-01
Minimum distance between outlets in KSRV series boxes, mmМ90х1,5 3” 130М75х1,5 2½” 105 120М63х1,5 2” 80 100 110М50х1,5 1½” 75 80 95 110М40х1,5 1¼” 65 70 75 90 100М32х1,5 1” 55 60 65 70 85 95М25х1,5 ¾” 45 50 55 60 65 80 90М20х1,5 ½” 40 40 45 50 55 60 75 85
Pipe thread (GOST 6211 – GOST 6357) ½” ¾” 1” 1¼” 1½” 2” 2½” 3”Metricthread (GOST 24705) М20х1,5 М25х1,5 М32х1,5 М40х1,5 М50х1,5 М63х1,5 М75х1,5 М90х1,5
Gland dimension-type 1 2 3 4 5 6 7 8
21
Equipment Selection Form
Term
inal
box
es
1
KSRV (SA) Exe, Exia, RO, RP SERIES TYPICAL EXPLOSION-PROOF TERMINAL BOXES EQUIPMENT SELECTION FORM
Mounting zone Zone 0 Zone 1 Zone 2 RP version RO version RN version
Required type of explosion safety ___________________________
Group and subgroups of gas/air mixtures IIA IIB IIC IIIC
Temperature class Т4 Т5 Т6Operating
temperature Tambient from _____ to _____
IP protection IP66 (on default) IP65 IP67 IP68
Material of enclosure Corrosion-resistant aluminum-silicon alloy 08X18H10 (AISI304) grade of stainless steel
Shock-proof antistatic polyester Low carbon steel with powder coating
Terminal blocks
Current rating Section, mm2 Quantity, pcsType of terminals
screw spring
16 0,2-2,5
25 0,2-4
32 0,2-6
40 0,6-10
63 0,5-16
75 0,5-25
125 0,5-50
150 1,5-70
200 1,5-95
250 4-185
350 4-240
Terminal N
Tire N
Terminal PE
Tire PE
Cable glands
Side of arrangement Quantity ofglands for a side
Diameter of external jacket of cable, mm
Diameter of internal jacket of cable, mm
(only for armored cable)
Type of cable gland Type of cable
A B C D
Options and accessories
Anti-condensation coating /AP Bolt with seal /PLOMBA
Earthquake-resistant version /MSK-64 Painting of external surface using the colour required by
customer (on request) /RAL (_____) Nameplates with retroreflective coating /SVP
Nameplates with customer caption /NADPIS “__”
Quantity of terminal boxes, pcs pcs
Customer’s notes (op-tional information)
Overall dimensions restrictions (if there are such), mm _______Х_______ Х_______length height deepness
Place of mounting
Other
Contact detailsCompany: Tel./fax:Mailing address:Contact person: E-mail:
B
C
D
22
Equipment Selection Form Te
rmin
al b
oxes
1
KSRV (SA) EXE, EXIA, RO, RP SERIES NOT TYPICAL EXPLOSION-PROOF TERMINAL BOXES EQUIPMENT SELECTION FORM
Mounting zone Zone 0 Zone 1 Zone 2 RO version RP version
RN version Required type of explosion safety ________ Operating temperature Tambient from _____ to _____
Group and subgroups of for gas/air mixtures IIA IIB IIC IIICTemperature
class Т4 Т5 T6 Temperature class for /TERMO version Т2 T3
IP protection IP66 (on default) IP65 IP67 IP68
Overall dimensions restrictions (if there are such), mm _______Х_______ Х_______
length height deepness
Arrangement of terminals (optional information)
Terminals
Section, mm² Quan-tity, pcs
Type of terminal (screw on default)
Earth PE
Cable glandsB
C
D
ОТКР
ЫВА
ТЬ
ОТКЛ
ЮЧИ
В ОТ
СЕТ
И
А
Marking of sides of enclosures
Marking of sides of enclosures
Quan-tity of
glands, pcs
Diameter of external jacket of cable, mm
Diameter of internal jacket of cable, mm (only for armored cable) or diam-
eter of cable in metal hose, mm
Type of cable gland (KNV, on default)
Type of cable
A B C D
Options and accessories
Material of enclosure
Corrosion-resistant
aluminum-silicon alloy
Low carbon
steel with powder coating
08X18H10
(AISI304) grade of stainless
steel
Shock-proof
antistatic polyester
Lid fixing with hinges PETLIA NO
Version for high temperature up to +185°C TERMO NO NO NO
Climatic category MU1 MORE NO NOVersion for minimum operating temperature –75°С HOLOD NO NO NO‘Small break’ special version for nuclear power stations MALAYA TECH NO
E30 Fire resistance rating POZHAR NOLid lock ZAMOK NO NOPainting of external surface using the colour required by customer RAL (code) RAL NO NO NO
Replaceable inserts for cable glands SPKV NO NOMounting plate of aluminum alloy ALP NO NOInternal strip for cable glans fixing support and earth continuity PTSZ NO NO NO
Anti-condensation coating AP NO NO NO
Draining device for condensate draining /DKUV Nameplates with retroreflective coating /SVP
Marking of terminal blocks according to cus-tomer’s layout /MARK
Ventilation device for moisture removal /VKUV Bolt with seal /PLOMBA Mounting plate of stainless steel /NP
Version for the tropics with protection against insects /TERMITI
Device for joining of cable screens /EKRAN Non-explosion-proof version /PROM
Earthquake-resistant version /MSK-64 Neutral bus bar /SHINA N Internal thermal insulation /TEPLOIZOLYATSIYA
Customer acceptance /PRIEMKA Internal earthing bus bar /SHINA Z Thermal heating for automatic mechanisms /OBOGREV
Nameplates with customer caption /NADPIS “___”
Special incoming switchgear for pair of heating cables /OKT
Bridges among terminals according to customer’s layout /SHEMA
Quantity of boxes, pcs pcs
Customer’s notes (optional information) Place of installation Other
Contact detailsCompany: Tel./Fax:Mailing address:Contact person: E-mail:
А
B
C
D AUTOMATIC EQUIPMENT
SIDE OF ARRANGMENT __
WIN
DOW
23
SHORV CCFE
EXD, R
V E
XD
1
• Service life of flameproof joint is more than 25 years.
• High resistance of SHORV series boxes of aluminum alloy to effect of hydrogen sulphide.
• 26 dimension types of boxes.• The boxes are tested under conditions of –60˚C
(special version –75˚C).• Unpainted internal surface of the box guarantees
increased heat conductivity.• It is possible to make the box with window.• The boxes can be made of highly corrosion-proof
stainless chrome-nickel casting steel.
MARKING
1Ex d IIС T6...T4 Gb X
1Ex d IIB+H2 T6...T4 Gb
1Ex d [ia] IIB+H2 T6...T4 Gb
1Ex d [ib] IIB+H2 T6...T4 Gb
1Ex d [ia] IIC T6...T4 Gb X
1Ex d [ib] IIC T6...T4 Gb X
Ex tb IIIC T70°С...T135°С Db
MINING EQUIPMENT MARKING
RV Ex d I Mb
RV Ex d [ib] I MbRN2
CERTIFICATES AND PERMITSGOST ISO 9001-2015 (ISO 9001:2015)РОСС RU.МШ06.Н00147ТС RU С-RU.AA87.В.00244Permit of the Federal Environmental, Industrial and Nuclear Supervision Service of Russia No. РРС 00-044017НСОПБ.RU.ПР 014.Н.00042Register of Shipping , Certificate of Type ApprovalNo. 16.03660.315Specifications (TU) 3400-005-72453807-07PJSC “GAZPROM” No. Г000.RU.1131.H00666
NORMSGOST R IEC 60079-0-2011GOST IEC 60079-1-2011GOST IEC 61241-1-1-2011GOST 14254-96 (IEC 529-89)GOST 12.2.007.0-75GOST 30852.0-2002GOST 30852.10-2002 (IEC 60079-11:1999)GOST 30852.20-2002, TR CU 012/2011Safety Regulations 05-618-03Safety Regulations 03-553-03GOST 24754-2013Ch. 7.3 of Electrical Installation CodeCh. 7.4 of Electrical Installation CodeRegulatory Document 5.2-093-2004
TECHNICAL CHARACTERISTICS
Installation
Class I, mine gas and dust;Class II, subgroups IIA, IIB+H2, IIC (except acetylene), zones 1, 2;Class III by dust, explosive dust atmospheres, which contain volatile solids, non-conducting and conducting dust;Underground mines, non-hazardous with gas (methane) and coal dust;Facilities supervised by the Russian Maritime Register of Shipping; Hazardous industrial facilities
Maximal voltage, V
~1000, A250, ~3300 (for SHORV423229 and higher), ~10000 (от SHORV654533)
Maximal electric current intensity, A
650, 1500 (for ~1000, A250)
Sealing
Silicone rubber (in a groove of lid) for IP67, flanged sealant PG-FLANETS for IP68, silicone sealant PG-SMAZKA
Mounting inside enclosure
4 mounting poles for mounting plate
Climatic category
NF1 (on request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.13**, W5)
Chemical resistant version
On request C1, C2, C3
IP 6667 68
HOLOD
24
SHORV CCFEEX
D, R
V E
XD
1
OPTIONS, ACCESSORIES AND VERSIONS
DESCRIPTION MARKINGLid fixing with hinges (for SHORV281811, for other dimension-types of SHORV series boxes, hinges are mounted on default)
/PETLIA
Draining device for condensate draining /DKUV
Ventilation device for moisture removal /VKUV
Climatic category MU1 /MORE
Version for minimum operating temperature –75°С /HOLOD
Version for the tropics with protection against insects /TERMITI
‘Small break’ special version for nuclear power stations /MALAYA TECH
Earthquake-resistant version /MSK-64
Customer acceptance /PRIEMKA
Nameplates with customer caption /NADPIS «_»
E30 Fire resistance rating (GOST R 53316-2009 “CABLE LINES. CIRCUIT INTEGRITY UNDER FIRE”) /POZHAR
Mounting plate of stainless steel /NP
Nameplates with retroreflective coating /SVP
DESCRIPTION MARKINGPainting of external surface using the colour required by customer (on request) /RAL (code)
Bolt with seal /PLOMBA
Device for joining of cable screens /ECRAN
Neutral bus bar /SHINA N
Internal earthling bus bar /SHINA Z
Phase bus bar /SHINA F
Bridges among terminals according to customer’s layout /SHEMA
Marking of terminal blocks according to cus-tomer’s layout /MARK
Mounting plate of aluminum alloy /ALP
Internal thermal insulation /TEPLOIZOLYATSIYA
Thermal heating for automatic equipment /OBOGREV
Anti-condensation coating /AP
Ingress protection IP67 /IP67
Non-falling-out screws for fastening of lid /NBK
Radiator cooling system /RADIATOR
Centering pin /SHTIFT
OVERALL AND MOUNTING DIMENSIONS
Overall dimensions SHORV series boxes
Typical size ofenclosureDimensions, mm
Weight, kgExternal Internal Standard fastening Fastening using crampsA B C a b c S S1 d e f D E F
SHORV281811 282 182 118 212 112 74 14 14 160 124 м6 160 155 9 6,3SHORV302021 304 204 211 240 140 163 14 14 230 130 М8 230 210 9 8,6SHORV422221 424 224 213 359 159 165 15 14 350 150 М8 350 230 9 13,6SHORV362827 364 284 275 300 220 217 20 14 290 210 М8 290 290 9 17,25SHORV362821 364 284 215 300 220 157 20 14 290 210 М8 290 290 9 14.97SHORV423229 425 325 297 361 261 233 24 14 350 250 M10 350 330 11 25,3SHORV423222 425 325 226 361 261 163 24 14 350 250 M10 350 330 11 20,7SHORV573931 576 396 318 506 326 247 26 20 360 236 М10 360 376 11 48.1SHORV573926 576 396 268 506 326 197 26 20 360 236 M10 360 376 11 44.4SHORV654533 650 450 337 570 370 222 16 17,5 550 350 10 550 446 11 59.5SHORV654526 650 450 265 570 370 150 16 16 550 350 10 550 446 11 51.6SHORV725235 723 523 359 639 439 246 23 18,5 600 400 10 600 505 11 83.8
25
SHORV CCFE
EXD, R
V E
XD
1
Typical size ofenclosureDimensions, mm
Weight, kgExternal Internal Standard fastening Fastening using crampsA B C a b c S S1 d e f D E F
SHORV725224 723 523 249 639 439 136 23 17 600 400 10 600 505 11 71.2SHORV896745 891 671 455 776 556 374 23 29 680 480 М16 680 640 14 173,9SHORV896735 891 671 355 776 556 274 23 28 680 480 М16 680 640 14 150
Mounting plate
Overall dimensions of mounting plates for SHORV series boxes
Name Dimensions, mm Type of box Weight, kgА В a bSH2818X 210 110 193 53 SHORV281811 —SH3020X 220 120 180 80 SHORV302021 —SH4222X 340 140 300 100 SHORV422221 —
SH3628X 280 200 240 160 SHORV362827SHORV362821 0,435
SH4232X 340 240 300 200 SHORV423229SHORV423222 0,660
SH5739X 460 280 440 260 SHORV573931SHORV573926 0,700
SH6545X 540 340 500 300 SHORV654533SHORV654526 0,750
SH7252X 605 405 590 388 SHORV725235SHORV725224 —
SH8967X 720 500 680 460 SHORV896745SHORV896735 0,800
Where X – code of material, А — aluminum, N – stainless steel.
Maximum recommended quantity of cable glands on the sides of SHORV series boxes
Dimension-type of enclosure
Side A Side BType of thread of cable gland Type of thread of cable gland
½" 20x1,5
¾" 25x1,5
1" 32x1,5
1 ¼" 40x1,5
1 ½" 50x1,5
2" 63x1,5
2 ½" 75x1,5
3" 85x2 4" ½"
20x1,5¾"
25x1,51"
32x1,51 ¼"
40x1,51 ½"
50x1,52"
63x1,52 ½"
75x1,53"
85x2 4"
SHORV281811 4 4 3 — — — — — — 2 2 2 — — — — — —SHORV302021 11 8 6 5 3 2 2 1 — 6 5 3 2 1 1 1 1 —SHORV362827 21 18 13 9 6 5 3 2 1 14 12 8 6 5 4 2 1 1SHORV362821 15 10 8 6 4 3 2 2 - 10 8 6 4 3 2 1 1 —SHORV423229 30 22 15 12 8 6 5 3 2 23 16 12 8 6 5 4 2 1SHORV423222 21 15 10 8 6 4 3 2 — 14 11 6 6 4 3 2 1 —SHORV573931 39 32 21 18 11 10 6 4 3 25 20 13 11 7 6 4 2 2SHORV573926 28 24 14 12 10 6 4 3 3 18 15 9 8 6 4 3 2 2SHORV654533 46 38 24 20 14 10 8 4 3 28 22 15 12 8 6 5 3 2SHORV654526 32 22 16 14 7 6 5 4 — 20 14 10 8 5 4 3 2 —SHORV725235 58 42 36 24 20 14 10 6 4 38 28 22 15 14 8 6 4 2SHORV725224 28 22 18 10 7 6 5 — — 18 14 11 6 5 4 3 — —
Codes matching tablePrevious international name of product made by “ZAVOD GORELTEX” CO. LTD.
Specifications (TU) 3400-005-72453807-07 Customs union name of product made by “ZAVOD GORELTEX” CO. LTD.
Specifications (TU) 3400-005-72453807-07 Terminal boxes EXD, RV
CCFE SHORVCCFE-01R SHORV281811CCFE-1R SHORV302021CCFE-2R SHORV422221CCFE-3R SHORV362827
CCFE-3VR SHORV362821CCFE-4R SHORV423229
CCFE-4VR SHORV423222CCFE-45 SHORV573931
CCFE-45V SHORV573926CCFE-5 SHORV654533
CCFE-5V SHORV654526CCFE-55 SHORV725235
CCFE-55V SHORV725224CCFE-6 SHORV896745
CCFE-6V SHORV896735
Recommended cable glandsKNV, КOV, KNVTN, KNVТV, KNE, KNVZ See p. 365
26
Order placementTe
rmin
al b
oxes
1
Terminal blocks Type of terminal block RN1 C2 C4 C6 C10 C16 C35 C50 C70 С120 С185 С240
Cross-section of cable cores, mm 0,2–2,5 0,5–4 0,5–6 0,5–10 0,5–16 0,5–25 0,5–50 1–70 1–95 6–150 6–240 70–240 Ampere rating, A 17,5 24 32 41 57 76 125 150 192 269 353 400
Maximum quantity of terminal blocks installed in SHORV* series boxes, pcs
Type of box Dimensions, mmC2 C4 C6 C10 C16 C35 С50 С70
SHORV281811 32 27 10 7 6 0 0 0SHORV302021 28 23 21 9 7 0 0 0SHORV362827 90 76 42 34 28 10 0 0SHORV423229 122 95 78 60 34 16 8 0SHORV573931 226 192 124 100 72 30 28 12SHORV654533 336 285 190 150 100 57 34 15SHORV725235 469 398 280 185 138 70 40 25
*Table values are similar to values of SHORVA with window and SHORVA-N..
MARKING FORMATION
SHORV X – (X X – X X) – X X (X) – X X (X) / X – Specifications (TU) 3400-005-72453807-07
Product nameDimension codeQuantity of terminal blocksType of terminal blockQuantity of cable glandsType of cable glandSide of arrangement of cable glandOptions, accessories and versions
Order example: SHORV362821 (40C2 – 10C16) – 5KNV1N(B) – 2KNV4N(D) – Specifications (TU) 3400-005-72453807-07
If you find it difficult to select dimension of the box according to the required response, then put the letters X instead of num-bers after the name of the box:Example: SHORV Х (40C2 – 10C16) – 5KNV1N(B) – 2KNV4N(D) – Specifications (TU) 3400-005-72453807-07.
27
SHORVA CCA
EXD, R
V E
XD
1
• Due to threaded joint, which connect a lid with enclosure, the boxes give protection in explosive mixtures, which refer to subgroup IIC.
• 10 dimension types of enclosures (including enclosures with window).
• SHORVA series enclosures were tested under -60˚C conditions.
• Service life of flameproof joint is more than 25 years.
• High resistance of SHORVA series enclosures to of aluminum alloy to effect of hydrogen sulphide.
• Unpainted internal surface of the box guarantees increased heat conductivity.
MARKING
1Ex d IIC T6...T4 Gb
1Ex d [ia] IIC T6...T4 Gb
1Ex d [ib] IIC T6...T4 Gb
Ex tb IIIC T85°С...T135°С Db
1Ex d e mb IIC T6...T4 Gb
MINING EQUIPMENT MARKING
RV Ex d I Mb X
RV Ex d [ib] I Mb XRN2
CERTIFICATES AND PERMITSGOST ISO 9001-2015 (ISO 9001:2015)РОСС RU.МШ06.Н00147ТС RU С-RU.AA87.В.00244Permit of the Federal Environmental, Industrial and Nuclear Supervision Service of Russia No. РРС 00-044017НСОПБ.RU.ПР 014.Н.00042Register of Shipping, Certificate of Type ApprovalNo. 16.03657.315Specifications (TU) 3400-005-72453807-07PJSC “GAZPROM” No. Г000.RU.1131.H00666
NORMSGOST R IEC 60079-0-2011GOST 14254-96 (IEC 529-89)GOST 30852.0-2002 (IEC 60079-0:1998)GOST 30852.1-2002 (IEC 60079-1:1998)GOST 30852.10-2002 (IEC 60079-11:1999)GOST 30852.20-2002, TR CU 012/2011GOST IEC 61241-1-1-2011GOST 24754-2013 Ch. 7.3 of Electrical Installation CodeCh. 7.4 of Electrical Installation CodeRegulatory Document 5.2-093-2004Safety Regulations 05-618-03Safety Regulations 03-553-03GOST 12.2.007.0-75
TECHNICAL CHARACTERISTICS
Installation
Class I, mine gas and dust;Class II, subgroups IIA, IIB, IIC, zones 1, 2;Class III by dust, explosive dust atmospheres, which contain volatile solids, non-conducting and conducting dust;Facilities supervised by the Russian Maritime Register of Shipping; Hazardous industrial facilities
Maximal voltage, V
~1000 / A250
Maximal electric current intensity, A
400
Sealing
Silicone sealant
Mounting inside enclosure
2 or 4 mounting poles for mounting plate
Climatic category
NF1 (on request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.1з**, W5)
Chemical resistant version
On request C1, C2, C3
IP 6667 68
28
SHORVA CCAEX
D, R
V E
XD
1
OVERALL AND MOUNTING DIMENSIONS
Overall dimensions of SHORVA series boxes
Type of boxDimensions, mm
Weight, kgExternal Internal, mm FasteningA B C a b c Ød Ød1 s E F ØG
SHORVA121211 120 120 115 94 94 74 82 M95x2 13 100 145 10 1,9SHORVA151512 151 151 125 124 124 84 116 M130x2 13 126 174 11 2,8SHORVA171712 175 175 129,5 146 146 89 137 M150х2 14 150 195 11 3,6SHORVA232316 235 235 164 203 203 117 185 M200х2 14 196 267 14 7,4SHORVA272721 276.5 276.5 218 248 248 152 232 M250x3 14 236 316 14 11,4SHORVA424229 429,5 429,5 291 395,5 395,5 216 330 M390x4 16,5 390 480 14 35,6
If you need an enclosure of bigger size, it is possible to produce the unit of several enclosures.
Maximum allowed quantity of cable glands installed on one side of SHORVA series box depending on the dimension size of cable gland, pcs
Dimension-type of a cable gland
Type of boxSHORVA121211 SHORVA151512 SHORVA171712 SHORVA232316 SHORVA272721 SHORVA424229
1 2 3 5 8 15 232 2 2 3 6 11 173 1 2 2 4 8 124 1 1 2 3 6 95 1 1 2 2 4 66 2 2 47 1 2 38 1 2
10 1 2
Codes matching table
Previous international name of product made by “ZAVOD GORELTEX” CO. LTD. Specifications (TU) 3400-005-72453807-07
Customs union name of product made by “ZAVOD GORELTEX” CO. LTD. Specifications (TU) 3400-005-72453807-07
Terminal boxes EXD, RVССА SHORVA
CCA/M1 SHORVA121211CCA-0/M1 SHORVA151512
CCA-01/M1 SHORVA171712CCA-02/M1 SHORVA232316CCA-03/M1 SHORVA272721CCA-04/M1 SHORVA424229
Recommended cable glandsKNV, КOV, KNVTN, KNVТV, KNE, KNVZ See p. 365
OPTIONS, ACCESSORIES AND VERSIONS
DESCRIPTION MARKINGDraining device for condensate draining /DKUV
Ventilation device for moisture removal /VKUV
Climatic category MU1 /MORE
Version for the tropics with protection against insects /TERMITI
‘Small break’ special version for nuclear power stations /MALAYA TECH
Customer acceptance /PRIEMKA
Nameplates with customer caption /NADPIS «_»
E30 Fire resistance rating (GOST R 53316-2009 “CABLE LINES. CIRCUIT INTEGRITY UNDER FIRE”) /POZHAR
Mounting plate of stainless steel /NP
Painting of external surface using the colour required by customer (on request) /RAL (code)
Nameplates with retroreflective coating /SVP
DESCRIPTION MARKINGDevice for joining of cable screens /ECRAN
Neutral bus bar /SHINA N
Internal earthling bus bar /SHINA Z
Phase bus bar /SHINA F
Bridges among terminals according to customer’s layout /SHEMA
Marking of terminal blocks according to cus-tomer’s layout /MARK
Mounting plate of aluminum alloy /ALP
Internal thermal insulation /TEPLOIZOLYATSIYA
Thermal heating for automatic equipment /OBOGREV
Anti-condensation coating /AP
Ingress protection IP68 /IP68
Radiator cooling system /RADIATOR
29
Order placement
Term
inal
box
es
1
SELECTION OF TYPE OF SHORVA BOX AND FORMATION OF MARKING FOR MOUNTING PLATEOverall dimensions of mounting plates
Name of a mounting plates Type of a box
Dimensions, mmA B a b
SHA1212X SHORVA121211 80 80 60 48SHA1515X SHORVA151512 100 100 80 60SHA1717X SHORVA171712 113 113 90 90SHA2323X SHORVA232316 150 150 130 130SHA2727X SHORVA272721 200 200 158 158SHA4242X SHORVA424229 315 315 230 230
Where X – code of material, А — aluminum, N – stainless steel.
Minimum distance between the holes in SHORVA series boxes, mm 4” 175
М90х1,5 3” 140 155М75х1,5 2 1/2” 115 130 145М63х1,5 2” 95 110 120 135М50х1,5 1 1/2” 85 90 105 115 130М40х1,5 1 1/4” 75 80 85 100 110 125М32х1,5 1” 65 70 75 80 95 105 120М25х1,5 3/4” 55 60 65 70 75 90 100 115М20х1,5 1/2” 50 50 55 60 65 70 85 95 110
Pipe (GOST 6211-81) 1/2” 3/4” 1” 1 1/4” 1 1/2” 2” 2 1/2” 3” 4”Metric (GOST 24705-81) М20х1,5 М25х1,5 М32х1,5 М40х1,5 М50х1,5 М63х1,5 М75х1,5 М90х1,5
Dimension-type of cable gland 1 2 3 4 5 6 7 8 10
Terminal blocks Type of terminal block RN1 C2 C4 C6 C10 C16 C35 C50 C70 С120 С185 С240
Cross-section of cable cores, mm 0,2–2,5 0,5–4 0,5–6 0,5–10 0,5–16 0,5–25 0,5–50 1–70 1–95 6–150 6–240 70–240 Ampere rating, A 17,5 24 32 41 57 76 125 150 192 269 353 400
Maximum quantity of terminals installed in SHORVA series boxes, pcs
Type of box Dimensions, mmC2 C4 C6 C10 C16 C35 С50 С70 C120 C185
SHORVA121211 8 6 5 4 — — — — — —SHORVA151512 11 9 8 6 5 4 3 — — —SHORVA171712 14 12 9 7 6 4 4 3 — —SHORVA232316 2х20 2х17 2х14 2х11 2х9 7 6 5 3 —SHORVA272721 2х29 2х25 2х20 2х16 2х13 10 8 8 5 4SHORVA424229 3х42 3х36 2х29 2х23 2х19 11 7 6
MARKING FORMATION
SHORVA X – (X X – X X) – X X (X) – X X (X) / X – Specifications (TU) 3400-005-72453807-07
Product nameCode of dimensionQuantity of terminal blocksType of terminal blockQuantity of cable glandsType of cable glandSide of arrangement of cable glandOptions, accessories and versions
Order example: SHORVA171712 (40S2 – 10S16) – 3KNV1N(B) – 2KNV4N(D) – Specifications (TU) 3400-005-72453807-07.
If you find it difficult to select dimension of the box according to the required response, then put the letters X instead of numbers after the name of the box:
Example: SHORVA X (40S2 – 10S16) – 3KNV1N(B) – 2KNV4N(D) – Specifications (TU) 3400-005-72453807-07.
30
Equipment Selection Form Te
rmin
al b
oxes
1
SHORV (CCFE), SHORVA (CCA) Exd, RV SERIES NON TYPICAL EXPLOSION-PROOF TERMINAL BOXES EQUIPMENT SELECTION FORM
Mounting zone Zone 1 RV version RN version Required type of explosion safety __________Group and subgroups
of gas/air mixtures I IIB+H2 IICX IIC IIIC IP protection IP66 (on default))
Temperature class Т4 Т5 T6Operating
temperature Tambient from _____ to _____
Overall dimensions restrictions (if there are such), mm _______Х_______ Х_______
length height deepness
Arrangment of terminals (optional information)
Terminals
Section, mm² Quantity, pcs Type of terminal (screw on defaut)
Earth PE
Cable glands
Designation sides of enclosure Quantity of glands Side of arrangment
Diameter of external jacket
of cable, mm
Diameter of internal jacket of cable, mm (only for armoured cable) or diameter of cable in metal
hose, mm
Type of cable gland Type of cable
Options and accessories
Material of enclosureCorrosion-resistant
aluminum-silicon alloy
Stainless chrome-nickel
steel
SHORVA (IIC) SHORV (IICХ) SHORV-N
Anticondensation coating АP NO
Painting of external surface using the colour required by customer RAL (code) RAL RAL NO
Version for minimum operating temperature –75°С HOLOD NO
Bolt with seal PLOMBA NO
Non-falling-out screws for fastening of lid NBK NO
Centering pin (for SHORV896745 and bigger sizes) SHTIFT NO
Draining device for condensate draining /DKUV Customer acceptance /PRIEMKA
Ventilation device for moisture removal /VKUV Nameplates with customer caption /NADPIS “___”
Climatic category MU1 /MORE E30 Fire resistance rating /POZHAR
Version for the tropics with protection against insects /TERMITI Bridges among terminals according to customer’s layout /SHEMA
‘Small break’ special version for nuclear power stations /MALAYA TECH Nameplates with retroreflective coating /SVP
Earthquake-resistant version /MSK-64 Device for joining of cable screens /EKRAN
Neutral bus bar /SHINA N Internal earthing bus bar /SHINA Z
Phase bus bar /SHINA F Mounting plate of stainless steel /NP
Thermal heating for automatic equipment /OBOGREV Mounting plate of aluminum alloy /ALP
Internal thermal insulation /TEPLOIZOLYATSIYA Marking of terminal blocks according to customer’s layout /MARK
Radiator cooling system /RADIATOR
Quantity of boxes, pcs pcs Climatic category – NF1 (on default)
Contact detailsCompany: Tel./Fax:Mailing address:Contact person: E-mail:
B
CА
D
А
B
C
D Automatic equipment
SIDE OF ARRANGMENT __
31
KKVA S
EXD, R
V E
XD
1
• High IP66/67 rating.• KKVA series boxes can be equipped with terminal
blocks for cables, which cross-section is up to 6 mm2.• From 1 to 4 holes in enclosure. • Different ways of fastening to vertical and hori-
zontal surfaces. • N (NPT) inchtapered thread is set as a default.
Other types of threads can be reached by using adap-tors.
MARKING
1Ex d IIC T6..T4 Gb
0Ex ia IIC T6..T4 Ga
1Ex s IIC T6..T4 Gb
1Ex e II T6..T4 Gb
Ex tb IIIC T85°С...T135°С Db
Ex ia IIIC T85°С..T135°С Da
MINING EQUIPMENT MARKING
RV Ex d I Mb XRN2
CERTIFICATES AND PERMITSGOST R ISO 9001-2015 (ISO 9001:2015)ТС RU С-RU.AA87.В.00244TC RU C-RU.МЛ02.В.00626РОСС RU.МШ06.Н00147Permit of the Federal Environmental, Industrial and Nuclear Supervision Service of Russia No. РРС 00-044017НСОПБ.RU.ПР 014.Н.00042Register of Shipping (on request) Specifications (TU) 3400-005-72453807-07PJSC “GAZPROM” No. Г000.RU.1131.H00666
NORMSGOST 14254-96 (IEC 529-89)GOST R IEC 60079-0-2011GOST 30852.0-2002 (IEC 60079-0:1998)GOST 30852.1-2002 (IEC 60079-1:1998)GOST 30852.8-2002GOST 30852.20-2002GOST 22782.3-77GOST 30852.10-2002 (IEC 60079-11:1999)GOST IEC 61241-1-1-2011TR CU 012/2011, TR CU 004/2011Ch. 7.3 of Electrical Installation CodeCh. 7.4 of Electrical Installation CodeRegulatory Document 5.2-093-2004 Safety Regulations 05-618-03Safety Regulations 03-553-03GOST 12.2.007.0-75GOST 24754-2013
TECHNICAL CHARACTERISTICS
Installation
Class I, mine gas and dust;Class II, subgroups IIA, IIB, IIC, zones 0, 1, 2;Class III by dust, explosive dust atmospheres, which contain volatile solids, non-conducting and conducting dust;Underground mines, non-hazardous with gas (methane) and coal dust;Non-hazardous area of surface buildings and open sites;Hazardous industrial facilities
Maximal voltage, V
750
Maximal electric current intensity, A
40
Sealing
Silicone sealant
Climatic category
NF1 (on request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.1з**, W5)
Chemical resistant version
On request C1, C2, C3
IP 6667
32
KKVA SEX
D, R
V E
XD
1
OPTIONS, ACCESSORIES AND VERSIONS
DESCRIPTION MARKINGVersion of stainless steel /N
Anticondensation coating /AP
Chain of stainless steel for a lid /TSEPOCHKA
Polymeric-and-epoxy panting /RAL (code)
E30 Fire resistance rating (GOST R 53316-2009 “CABLE LINES. CIRCUIT INTEGRITY UNDER FIRE”) /POZHAR
Non explosion-proof version (fireproof) /PROM
Major characteristics of installed terminal blocks
Type of terminal
Nominal cross-section, mm2
Cross-section of cable cores, mm2
Ampere rating, A
Maximal voltage, V
Overall dimensions, mm Maximum quantity of installed
terminalsA В СRР.4 4 0,2–6 32 275 35 31 6 4RN1 1,5 0,2–2,5 17,5 500 32 27 4,2 5RN2 2,5 0,2–4 24 400 32 27 5 5
Взрывозащищенные распределительные и протяжные коробки ККVА
Type Dimension-type of thread Drawing Lid diameter,
mm H A B C X Weight, kg
KKVA-К90N1 4 x 1/2"
90 75,5 106 — 0,50
KKVA-К90N2 4 x 3/4"
KKVA-К90N3 4 x 1"
KKVA-КС90N1 4 x 1/2"
90 75,5 106 130 — 110 0,60
KKVA-КС90N2 4 x 3/4"
KKVA-КС90N3 4 x 1"
KKVA-TSG90N1 3 х 1/2"
90 75,5 106 125 75 111 0,60
KKVA-TSG90N2 3 х 3/4"
KKVA-TSG90N3 3 х 1"
*Maximum quantity of holes – 4.
MARKING FORMATION
ККVА – X X X–X (X) / X – Specifications (TU) 3400-005-72453807-07Product nameArrangement of holesCode of dimension-typeCode and dimension-type of threadType of cable glandSide of arrangement of glandOptions, accessories and versions
A
B
C
D
Recommended cable glandsKNV, КOV, KNVTN, KNVТV, KNE, KNVZ See p. 365