Construction Details 50 TETRiS insulation components Gap Strip (TGS) - 75 x various widths x 2500mm Vertical Edge Strip (VES) - 75 (high) x 30 x 2500mm T Blocks T300 / T600 - 90, 100, 120, 140, 160 x 300/600 x 2500 150mm (min) Block cut to suit 30 100 150 150mm Beam - Vertical edge detail Technical Advice 08456 71-71-74 www.tetrisfloors.co.uk Fig. 1 Constant 75mm Variable 15 - 85mm 75mm Beam position perpendicular to wall Concrete block used to bridge variable gap between wall and beam 175 150 150mm (min) 175mm Beam - Vertical edge detail Fig. 2 Beam position perpendicular to wall Gap strip can span up to 299mm without the need to be supported with concrete block 50 30 100 150mm (min) 150mm Beam - Vertical edge detail with additional layer of 75mm insulation Constant 75mm Variable 15 - 85mm 75mm Beam position perpendicular to wall 225 75mm 150 100 65 Pre-stressed concrete beams - 150, 175 or 225 high x various lengths Concrete blocks - 100 x 440 x 215mm Concrete closer blocks - 100 x 502 (UW) x 448(LW) x 138mm - 100 x 202 (UW) x 148(LW) x 138mm UW LW Gap strip cut to suit T600 T600 T300 T600 T300 T600 T600 Gap Strip 150 150 150 175 175 175 175 175 175 150 150 150 150 150 150 150 225 Block cut to suit Concrete block used to bridge variable gap between wall and beam Gap Strip 150 Concrete components Fig. 3 7 TETRiS TETRiS R ZERO cold bridging ZERO cold bridging Optional gas membrane (supplied by other) If required, a gas membrane can be easily incorporated as TETRiS produces a smooth, level surface for the membrane to be draped over and built into the course work accordingly. Constant 75mm Variable 15 - 85mm 75mm T300 / T600

Upload: dangquynh

Post on 04-Aug-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TETRiS Construction Details - Cellecta Ltd · Construction Details 50 50 TETRiS insulation components Gap Strip (TGS) - 75 x various widths x 2500mm Vertical Edge Strip (VES) - 75

Construction Details

50 50

TETRiS insulation components

Gap Strip (TGS) - 75 x various widths x 2500mm

Vertical Edge Strip (VES)- 75 (high) x 30 x 2500mm

T Blocks T300 / T600- 90, 100, 120, 140, 160 x 300/600 x 2500

150mm (min)

Block cut to suit

30

100

150

150mm Beam - Vertical edge detail

Technical Advice 08456 71-71-74 www.tetrisfloors.co.uk

Fig. 1

Constant75mm

Variable15 - 85mm

75mm

Beam position perpendicular to wall Concrete block used to bridge variable gap between wall and beam

50

175

150

150mm (min)

175mm Beam - Vertical edge detail

Fig. 2

Beam position perpendicular to wallGap strip can span up to 299mm without the

need to be supported with concrete block

50

30

100

150mm (min)

150mm Beam - Vertical edge detail with additional layer of 75mm insulation

Fig. 3

Constant75mm

Variable15 - 85mm

75mm

Beam position perpendicular to wall

22575mm

150

100

65

Pre-stressed concrete beams- 150, 175 or 225 high x various lengths

Concrete blocks- 100 x 440 x 215mm

Concrete closer blocks- 100 x 502 (UW) x 448(LW) x 138mm- 100 x 202 (UW) x 148(LW) x 138mm

UW

LW

Gap strip cut to suit

T600T600

T300T600 T300

T600 T600 Gap Strip

15

0

15

0

15

0

17

5

17

5

17

5

17

5

17

5

17

5

15

0

15

0

15

0

15

0150

150

150

225

50

Block cut to suit

Concrete block used to bridge variable gap between wall and beam

Gap Strip

15

0

Concrete components

Fig. 3

7

TETRiSTETRiSTETRiSTETRiSR

ZERO cold bridging

ZERO cold bridging

Optional gas membrane (supplied by other) If required, a gas membrane can be easily incorporated as TETRiS produces a smooth, level surface for the membrane to be draped over and built into the course work accordingly.

Constant75mm

Variable15 - 85mm

75mm

T300 / T600

Page 2: TETRiS Construction Details - Cellecta Ltd · Construction Details 50 50 TETRiS insulation components Gap Strip (TGS) - 75 x various widths x 2500mm Vertical Edge Strip (VES) - 75

50 T600

15

0

15

0

Vertical edge options - Timber frame buildings

50

150m

m (

min

)

Concrete finish flows into void to producelevel wall for sole plate to be fixed to

Strip of Cellecta XFLOOR 250 extrudedpolystyrene placed in cavity to act as a retainingwall and eliminate cold bridging.

Timber sole plate fixed to retaining wall

Block cut to suit

50 50

150mm (min)

Block cut to suit 100

150

225mm Beam - Vertical edge detail

Constant75mm

Variable15 - 85mm

75mm

Beam position perpendicular to wall Concrete block used to bridge variable gap between wall and beam

T600 T600

100

150

T600T600

15

0

15

0

Fig. 6

30

100

150

T600 50

15

0

15

0

Timber sole plate fixed to retaining wall

30

100

150Constant

75mm

Variable15 - 85mm

75mm

140mm Timber Frame

90mm Timber Frame

Fig. 5

Technical Advice 08456 71-71-74 www.tetrisfloors.co.uk8

140100

Construction DetailsTETRiSTETRiSTETRiSTETRiS

R

TETRiSThe eco-friendly block & beam

ON SITE?

Download the or FREE Cellecta appwatch the installa�on video on YouTube

T600

T600Gap Strip

22

5

Fig. 4

100

22

5

Gap Strip

22

5

22

5

T300

TETRiS Gap Strip cutting

½ beam - TETRiS Gap Strip (TGS) supplied pre-cut to suit specific beam used

Fig. 7

T60050

15

0

Double beams - TETRiS Gap Strip (TGS) supplied pre-cut to suit specific beam used

Triple beams - TETRiS Gap Strip (TGS) supplied pre-cut to suit specific beam used

Block cut to suit - 440mm (max)

Gap Strip

15

0

T300T300

Covering concrete blocks -TETRiS Gap Strip (TGS)supplied 600mm wide, cut to size on site

Irregular beam spacing - TETRiS Gap Strip (TGS) supplied 600mm wide, cut to size on site

No concrete block required (up to 299mm)

Page 3: TETRiS Construction Details - Cellecta Ltd · Construction Details 50 50 TETRiS insulation components Gap Strip (TGS) - 75 x various widths x 2500mm Vertical Edge Strip (VES) - 75

9

Underfloor heating systems (supplied by other) An underfloor heating system can easily be integrated into the floor prior to applying the structural concrete floor finish.

Option 2Cover the TETRiS blocks with a D49 steel mesh, cable-tie the underfloor heating pipes to the mesh at the desired centres and cover with the structural concrete. Install the heating manifold at a later stage.

Lightweight partition walls not exceeding2 0.75kNm can be built anywhere off the

finished floor.

75mm

Lightweight non-load bearing concrete (1)blockpartition walls can be positioned

anywhere when built perpendicular to the beams.

Non-load bearing partitions

Fig. 8

TETRiSTETRiSTETRiSTETRiSR

Technical Advice 08456 71-71-74 www.tetrisfloors.co.uk

Fig. 15

Fig. 14

Option 1Secure the underfloor heating pipes to the TETRiS blocks with ‘U’ anchors at the desired centres and cover with the structural concrete topping. Install the heating manifold at a later stage.

Lightweight non-load bearing concrete block(1)partition walls built parallel to the beams

MUST be constructed within a 75mm (each side on the centre line of the beam) zone directly above the floor beam(s).

100mm(max)

100mm(max)

Construction Details

Fig. 9

T600T600 T600T600

T600 T600 T600

75mm

T300/600 T300/600 T300/600 T300/600 T300/600

Fig. 10 Fig. 11

Beams laid staggeredon 100mm sleeper wall

Fig. 13Fig. 12

Load bearing partitions

Beam ends butted on 200mm sleeper wall

T300/600 T300/600 T300/600 T300/600

200mm DPC100mm DPC