Duane Meyers AIA Architect Hurst Texas Revisions 560 PR 2422 Uncertain, TX 75661 903.484.4040 [email protected] Revisions 18 Apr 2016 18 Apr 2016 CONTINUOUS BEAD OF FIRESTONE METAL COUNTERFLASHING BY OTHERS ULTRAPLY TPO MEMBRANE ULTRAPLY TPO BONDING ADHESIVE NOTES: 1. REGULAR MAINTENANCE OF COUNTERFLASHING 2. AND SEALANTS REQUIRED. NOT INCLUDED AS PART OF THE FIRESTONE WARRANTY. CONTINUOUS BEAD OF AP SEALANT CONTINUOUS BEAD OF FIRESTONE WATERBLOCK WATERBLOCK APPROPRIATE FIRESTONE FASTENER FIRESTONE TERMINATION BAR REFER TO FIRESTONE WEBSITE FOR MOST CURRENT INFORMATION. 12" (304.8 mm) O.C. MAX. USE APPROPRIATE BASE TIE-IN 3" (76.2 mm) MIN. FACE (SEE NOTES) METAL COUNTERFLASHING SHALL BE 24 GAUGE 3. PRE-FINISHED STEEL OR .032" MIN. ALUMINUM FORMED WITH HEMMED LOWER EDGE. 12" (304.8 mm) O.C. MAX. ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. UltraPly TPO BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM TM MAXIMUM WARRANTY: TERMINATION WITH SURFACE MOUNTED COUNTERFLASHING AND TERMINATION BAR ALL 1/1/2006 UT-T-6 20 YEARS CONTINUOUS BEAD OF AP SEALANT OR HIGH GRADE SEALANT WALL / CURB (MASONRY / CONCRETE SUBSTRATE ONLY) MASONRY AND CONCRETE WALLS / CURBS MUST BE WATERPROOFED AND MAINTAINED IN ORDER FOR ANY SURFACE MOUNTED TERMINATION TO BE EFFECTIVE. OR ULTRAPLY TPO GP SEALANT APPROPRIATE FASTENER 4. INSTALL FIRESTONE TERMINATION BAR WITH 1/4" (6.4 mm) GAP BETWEEN ADJOINING SECTIONS. 5. TERMINATION BAR MUST BE CUT AT INSIDE AND OUTSIDE CORNERS. DO NOT BEND AROUND CORNERS. 6. 7. INSTALL METAL WORK IN ACCORDANCE WITH CURRENT SMACNA RECOMMENDATIONS. TERMINATION BAR MUST BE FASTENED WITHIN 1" (25.4 mm) MAX. OF ALL SECTION ENDS. FIRESTONE INSULATION SUBSTRATE NOTES: 1. INSTALL METAL WORK TO MANUFACTURER'S REQUIREMENTS OR SMACNA RECOMMENDATIONS. GP SEALANT IS REQUIRED ALONG ENTIRE UPSLOPE 3. EDGE OF QUICKSEAM FLASHING WHEN ROOF SLOPE IS 1" (25.4 mm) PER FOOT OR GREATER. ULTRAPLY TPO ULTRAPLY TPO QUICKPRIME DRIP/GRAVEL STOP EDGE METAL (SEE NOTES) CONTINUOUS CLEAT 4. WALL 5.5" TPO QUICKSEAM FLASHING IF SHOP FABRICATED METAL EDGE IS USED IT MUST MEET ANSI/SPRI ES-1 OR AN FM STANDARD. MEMBRANE FLANGE OF METAL MUST BE FULLY SUPPORTED 5. BY WOOD AND TERMINATED AT LEAST 1/2" (12.7 mm) FROM EDGE OF WOOD. WOOD NAILER MUST BE INSTALLED TO MEET APPLICABLE BUILDING CODES OR 200 LBS PER LINEAR FOOT MINIMUM IN ANY GIVEN DIRECTION. ON BALLASTED ROOFS, GRAVEL STOP HEIGHT 6. MUST MEET OR EXCEED BALLAST OR PAVER HEIGHT (2" (50.8 mm) MIN. ABOVE ROOF SURFACE). 1/2" (12.7mm) MIN. 1/2" (12.7mm) MIN. 1/4" (6.35 mm) TO 1/2" (12.7 mm) REFER TO FIRESTONE WEBSITE FOR MOST CURRENT INFORMATION. 2. 1-1/4" HOT DIPPED GALVANIZED ROOF NAILS AT 4" (101.6 mm) O.C. MAX. WOOD NAILER (SEE NOTES) 1-1/4" HOT DIPPED GALVANIZED ROOF NAILS AT 6" (152.4 mm) O.C. MAX. ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. Ul t r aPl y TPO TM BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM MAXIMUM WARRANTY: ROOF EDGE WITH FASCIA METAL BY OTHERS ALL 5/1/2010 UT-RE-20 20 YEARS CONTINUOUS BEAD OF ULTRAPLY TPO GP SEALANT (SEE NOTES) CONTINUOUS BEAD OF ULTRAPLY TPO GP SEALANT (REQUIRED) ULTRAPLY TPO BONDING ADHESIVE (ADHERED SYSTEM ONLY) STOP (SEE NOTES) OPTIONAL GRAVEL IF THE FLANGE OF THE METAL EDGE IS NOT 7. COMPLETELY COVERED WITH QUICKSEAM FLASHING, THEN AN ADDITIONAL PIECE OF QUICKSEAM FLASHING SHALL BE INSTALLED AT ALL METAL SPLICES. REFER TO UT-RE-27. THIS DETAIL IS APPROVED FOR A MAXIMUM OF 20 YEARS. REFER TO DETAIL UT-RE-21 FOR 25 YEAR REQUIREMENTS. ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. UltraPly TPO TM BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM MAXIMUM WARRANTY: PENETRATION WITH TPO PENETRATION POCKET KIT ALL 1/1/2006 UT-P-8 20 YEARS FIRESTONE INSULATION SUBSTRATE FIRESTONE INSULATION NOTES: 1. DO NOT USE OVER EXISTING PENETRATION POCKETS. 4. IF FIELD MEMBRANE IS CUT FOR INSTALLATION, THE MEMBRANE MUST BE REPAIRED WITH TPO MEMBRANE PRIOR TO INSTALLATION OF THE PENETRATION POCKET. MEMBRANE MUST BE INSTALLED WITHIN 1/2" (12.7 mm) 6. OF PENETRATION. PENETRATION PENETRATION 7. FIRESTONE POURABLE SEALER MOUNDED TO SHED WATER (MINIMUM DEPTH OF 2" (50.8 mm), REMAINDER OF POCKET MAY BE FILLED WITH A NON - SHRINKING GROUT. 3. ULTRAPLY TPO QUICKPRIME REQUIRED ON PENETRATIONS AND MEMBRANE INSIDE OF PENETRATION POCKET. PRE-MOLDED ULTRAPLY TPO PENETRATION POCKET 8. 6" (152.4mm) REFER TO FIRESTONE WEBSITE FOR MOST CURRENT INFORMATION. 1" (25.4 mm) MIN. NON-SHRINKING GROUT ULTRAPLY TPO BONDING ADHESIVE REMOVE ALL EXISTING FLASHINGS, LEADS, ETC. PIPE 2. SURFACE MUST BE FREE OF ALL RUST, GREASE, INSULATION, ETC. DO NOT USE WHEN SERVICE LINE TEMP. EXCEEDS 180°F. 5. REFER TO UT-P-6 & 7. (ADHERED SYSTEM ONLY) WELDED SPLICE 2" (50.8 mm) MIN. SUBSTRATE PRECUT PVC PIPE FIRESTONE POURABLE SEALER ULTRAPLY TPO QUICKPRIME (SEE NOTES) ULTRAPLY TPO MEMBRANE 9. REFER TO UT-P-15 OR 16 FOR MAS. SUBSTRATE FIRESTONE INSULATION SUBSTRATE PENETRATION (HOT STACK) ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. UltraPly TPO BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM TM MAXIMUM WARRANTY: PENETRATION (HOT STACK) WITH ULTRAPLY TPO FLASHING (UNSUPPORTED) ALL 1/1/2006 UT-P-6 20 YEARS 1/2" - 1" (12.7 mm - 25.4 mm) WELDED SPLICE 2" (50.8 mm) MIN. 8" (203.2 mm) MIN. ULTRAPLY TPO FLASHING (UNSUPPORTED) ULTRAPLY TPO BONDING ADHESIVE STAINLESS STEEL CLAMPING RING CONTINUOUS BEAD OF ULTRAPLY TPO GP SEALANT INSULATED METAL SLEEVE BY OTHERS ULTRAPLY TPO BONDING ADHESIVE (SEE NOTES) ULTRAPLY TPO MEMBRANE NOTES: 1. REMOVE ALL EXISTING FLASHINGS, LEADS, 2. ETC. PIPE SURFACE MUST BE FREE OF ALL RUST, GREASE, INSULATION, ETC. PIPE MUST BE ANCHORED TO ENSURE 3. NO WRINKLES OR FOLDS UNDER CLAMPING 4. REFER TO FIRESTONE WEBSITE FOR MOST CURRENT INFORMATION. STABILITY. RING. FIELD FABRICATED METAL HOOD BY OTHERS (REQUIRED) FIRESTONE INSULATION MEMBRANE AND INSULATION FOR FULLY ADHERED SYSTEMS. BONDING ADHESIVE REQUIRED BETWEEN 5. FIRESTONE FASTENER AND HD OR HD PLUS SEAM PLATE AT 12" 6. (304.8 mm) O.C. MAX. (SEE NOTES) FIRESTONE FASTENER AND HD SEAM PLATE REQUIRED FOR MAS ONLY. IF FASTENER CANNOT BE INSTALLED AS ILLUSTRATED, REFER TO DETAILS UT-P-15 & 16. CONTINUOUS BEAD OF AP SEALANT OR HIGH GRADE SEALANT 7. (UNSUPPORTED) OR ULTRAPLY TPO MEMBRANE AS FLASHING ULTRAPLY TPO FLASHING WHEN REINFORCEMENT OF TPO MEMBRANE IS EXPOSED, REFER TO UT-LS-14 FOR CUT EDGE SEALANT APPLICATION. ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. UltraPly TPO TM BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM MAXIMUM WARRANTY: LAP SPLICE WITH 2" HAND WELD ALL 1/1/2006 UT-LS-2 20 YEARS SLOPE 2" (50.8mm) MIN. NOTES: 1. REFER TO FIRESTONE WEB SITE FOR MOST CURRENT INFORMATION. WHEN POLYESTER REINFORCEMENT OF TPO IS EXPOSED, APPLY CUT EDGE TREATMENT TO ENTIRE EXPOSED EDGE. REFER TO UT-LS-14. 2" (50.8mm) MIN. 6" (152.4 mm) FIRESTONE FASTENER AND HD OR HD PLUS SEAM PLATE SLOPE 2" (50.8mm) MIN. ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. UltraPly TPO TM BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM MAXIMUM WARRANTY: LAP SPLICE WITH 1-1/2" AUTOMATIC WELDER ALL 1/1/2006 UT-LS-1 20 YEARS SLOPE 1-1/2" (38.1mm) MIN. NOTES: 1. REFER TO FIRESTONE WEB SITE FOR MOST CURRENT INFORMATION. WHEN POLYESTER REINFORCEMENT OF TPO IS EXPOSED, APPLY CUT EDGE TREATMENT TO ENTIRE EXPOSED EDGE. REFER TO UT-LS-14. 2" (50.8mm) MIN. 6" (152.4 mm) FIRESTONE FASTENER AND HD OR HD PLUS SEAM PLATE SLOPE 1-1/2" (38.1mm) MIN. NOTES: 1. 2. USE APPROPRIATE BASE TIE-IN DETAIL REFER TO FIRESTONE WEBSITE FOR MOST CURRENT INFORMATION. WELDED SPLICE (SEE NOTES) ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. UltraPly TPO TM BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM MAXIMUM WARRANTY: INSIDE CORNER ALL 1/1/2006 UT-C-5 20 YEARS REFER TO DETAIL UT-LS-1 OR 2 FOR WELD WIDTH. USE APPROPRIATE TERMINATION DETAIL ULTRAPLY TPO MEMBRANE PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDE CORNER WELDED IN PLACE (SEE NOTES) 3. ULTRAPLY TPO FLASHING (UNSUPPORTED) MAY BE USED IN LIEU OF PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDE CORNER FOR A MAXIMUM WARRANTY OF 15 YEARS . 4. WHEN REINFORCEMENT OF TPO MEMBRANE IS EXPOSED, REFER TO UT-LS-14 FOR CUT EDGE SEALANT APPLICATION. USE APPROP. BASE TIE-IN NOTES: 1. REFER TO FIRESTONE WEBSITE FOR MOST CURRENT INFORMATION. REFER TO DETAIL UT-LS-1 OR 2 FOR WELD WIDTH. 2. ULTRAPLY TPO 18" CURB FLASHING OR MEMBRANE HEAT WELDED TO ULTRAPLY TPO ULTRAPLY TPO MEMBRANE ULTRAPLY TPO T-JOINT COVER WELDED IN PLACE (SEE NOTES) ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. UltraPly TPO TM BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM MAXIMUM WARRANTY: INSIDE CORNER WITH CONTINUOUS WALL FLASHING ALL 1/1/2006 UT-C-4 20 YEARS PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDE CORNER WELDED IN PLACE (SEE NOTES) 3. T-JOINT COVER REQUIRED FOR .060 GAUGE MEMBRANE ONLY. 4. ULTRAPLY TPO FLASHING (UNSUPPORTED) (4"x4" MIN. WITH ROUNDED CORNERS) MAY BE USED IN LIEU OF T-JOINT COVER. DETAIL (FIELD SHEET) USE APPROPRIATE TERMINATION DETAIL 5. ULTRAPLY TPO FLASHING (UNSUPPORTED) MAY BE USED IN LIEU OF PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDE CORNER FOR A MAXIMUM WARRANTY OF 15 YEARS . 6. WHEN REINFORCEMENT OF TPO MEMBRANE IS EXPOSED, REFER TO UT-LS-14 FOR CUT EDGE SEALANT APPLICATION. FIELD SHEET (SEE NOTES) ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. UltraPly TPO TM BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM MAXIMUM WARRANTY: OUTSIDE CORNER ALL 1/1/2006 UT-C-1 20 YEARS USE APPROPRIATE TERMINATION DETAIL USE APPROPRIATE BASE TIE-IN DETAIL PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDE CORNER WELDED IN PLACE (SEE NOTES) NOTES: 1. REFER TO FIRESTONE WEBSITE FOR MOST CURRENT INFORMATION. REFER TO DETAIL UT-LS-1 OR 2 FOR WELD WIDTH. 2. ULTRAPLY TPO 18" CURB FLASHING OR MEMBRANE HEAT WELDED TO ULTRAPLY TPO FIELD SHEET (SEE NOTES) ULTRAPLY TPO MEMBRANE (FIELD SHEET) 3. ULTRAPLY TPO FLASHING (UNSUPPORTED) MAY BE USED IN LIEU OF PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDE CORNER FOR A MAXIMUM WARRANTY OF 15 YEARS . 4. WHEN REINFORCEMENT OF TPO MEMBRANE IS EXPOSED, REFER TO UT-LS-14 FOR CUT EDGE SEALANT APPLICATION. FIRESTONE INSULATION SUBSTRATE WALL / CURB NOTES: 1. 3. WELDED SPLICE (SEE NOTES) ULTRAPLY TPO MEMBRANE ULTRAPLY TPO BONDING ADHESIVE (SEE NOTES) USE APPROPRIATE TERMINATION REFER TO FIRESTONE WEBSITE FOR MOST CURRENT INFORMATION. REFER TO DETAIL UT-LS-1 OR 2 FOR WELD WIDTH. 2. POSITION PLATE 1/2" (12.7 mm) MIN. ABOVE FINISHED ROOF ULTRAPLY TPO MEMBRANE MUST EXTEND 1/2" (12.7 mm) BEYOND HD OR HD PLUS SEAM PLATE (SEE NOTES) ULTRAPLY TPO BONDING ADHESIVE ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. UltraPly TPO BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM TM MAXIMUM WARRANTY: BASE TIE-IN WITH HD SEAM PLATES FASTENED TO WALL / CURB ALL 1/1/2006 UT-BT-2 20 YEARS 4. REFER TO UT-BT-16 & 17 FOR MEMBRANE SECUREMENT AT CORNERS. FIRESTONE FASTENER AND HD OR HD PLUS SEAM PLATE AT 12" (304.8 mm) O.C. MAX. (SEE NOTES) ULTRAPLY TPO 18" CURB FLASHING OR MEMBRANE BONDING ADHESIVE REQUIRED BETWEEN MEMBRANE AND INSULATION FOR FULLY ADHERED SYSTEMS. 5. WHEN REINFORCEMENT OF TPO MEMBRANE IS EXPOSED, REFER TO UT-LS-14 FOR CUT EDGE SEALANT APPLICATION. FIRESTONE INSULATION SUBSTRATE WALL / CURB NOTES: 1. MAXIMUM 6" (152.4 mm) LONG FASTENERS. 3. (NOTE: WOOD BLOCKING MAY BE SUBSTITUTED FOR INSULATION TO REDUCE FASTENER LENGTH REQUIREMENT). 4. 6. WELDED SPLICE (SEE NOTES) ULTRAPLY TPO MEMBRANE ULTRAPLY TPO BONDING ADHESIVE (SEE NOTES) USE APPROPRIATE TERMINATION BONDING ADHESIVE REQUIRED BETWEEN MEMBRANE AND INSULATION FOR FULLY ADHERED SYSTEMS. REFER TO FIRESTONE WEBSITE FOR MOST CURRENT INFORMATION. ULTRAPLY TPO BONDING ADHESIVE ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. UltraPly TPO TM BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM MAXIMUM WARRANTY: BASE TIE-IN WITH HD SEAM PLATES FASTENED TO DECK ALL 1/1/2006 UT-BT-1 20 YEARS REFER TO DETAIL UT-LS-1 OR 2 FOR WELD WIDTH. 2. FIRESTONE FASTENER AND HD OR HD PLUS SEAM PLATE AT 12" (304.8 mm) O.C. MAX. (SEE NOTES) ULTRAPLY TPO 18" CURB FLASHING OR MEMBRANE IN CASE OF OBSTRUCTION REFER TO DETAIL UT-BT-5. 5. REFER TO UT-BT-16 & 17 FOR MEMBRANE SECUREMENT AT CORNERS. HD OR HD PLUS SEAM PLATE POSITIONED 1/2" (12.7 mm) BEYOND WALL/CURB 7. WHEN REINFORCEMENT OF TPO MEMBRANE IS EXPOSED, REFER TO UT-LS-14 FOR CUT EDGE SEALANT APPLICATION. NOTES: 1. HOLE IN MEMBRANE SHOULD EXTEND A MINIMUM OF 1/2" 2. INSULATION ADJACENT TO DRAIN TO BE APPROPRIATE 3. FIRESTONE INSULATION WITH APPROPRIATE BONDING FIRESTONE WATERBLOCK MIN. OF 1/2 OF 10 OZ (295 ml) 4. IN REROOF APPLICATIONS: 5. - REMOVE EXISTING FLASHINGS DOWN TO METAL BOWL - REPAIR OR REPLACE BROKEN DRAIN COMPONENTS - DRILL AND TAP BROKEN DRAIN BOLTS AND REPLACE (12.7 mm) BEYOND CLAMPING RING AND SHOULD NOT BE IF NECESSARY. SUBSTRATE FIRESTONE INSULATION ULTRAPLY TPO BONDING ULTRAPLY TPO CONTINUOUS BEAD OF FIRESTONE WATERBLOCK COMPRESSION RING STRAINER BASKET FIRESTONE INSULATION SUBSTRATE SURFACE. TUBE PER 4" DRAIN. USE ADDITIONAL WATERBLOCK SMALLER THAN THE DIAMETER OF THE LEADER PIPE. FOR LARGER DRAINS. 1/2" (12.7mm) MIN. SEE NOTES REFER TO FIRESTONE WEB SITE FOR MOST CURRENT INFORMATION. (SEE NOTES) MEMBRANE 12" (304.8 mm) ADHESIVE (ADHERED ISSUE / REVISION DATE: NOT TO SCALE ACCEPTABLE SYSTEMS: DETAIL NO. UltraPly TPO TM BUILDING PRODUCTS NOBODY COVERS YOU BETTER. www.firestonebpco.com TM MAXIMUM WARRANTY: ROOF DRAIN ALL 1/1/2006 UT-D-1 20 YEARS SYSTEMS ONLY) IF FIELD SEAM EDGE IS WITHIN 9" (228.6 mm) OF DRAIN COMPRESSION RING, TPO TARGET PATCH REQUIRED. IF FIELD SEAM EDGE IS WITHIN 9" (228.6 mm) TO 18" (457.2 mm) OF DRAIN COMPRESSION RING, HEAT WELD A LAYER OF ULTRAPLY TPO FLASHING (UNSUPPORTED) OR ULTRAPLY SUMP AREA FIELD SEAM REQUIREMENTS: A. B. TPO MEMBRANE CENTERED OVER SEAM EDGE. FLASHING MUST EXTEND 3" (76.2 mm) MIN. BEYOND EDGE OF SUMP. 1" MAX. (25.4 mm) A3.1 TPO Roof Details

Upload: dangnga

Post on 03-Apr-2018

214 views

Category:

Documents


1 download

TRANSCRIPT

Dua

ne M

eyer

s AIA

A

rchi

tect

HurstTexas

Revisions

560

PR 2

422

Unc

erta

in, T

X 75

661

903.

484.

4040

drm

eyer

s@m

ac.c

om

Revisions

18 Apr 2016

18 Apr 2016

CONTINUOUS BEAD OF FIRESTONE

METAL COUNTERFLASHING BY OTHERS

ULTRAPLY TPO MEMBRANE

ULTRAPLY TPO BONDING ADHESIVE

NOTES:1.

REGULAR MAINTENANCE OF COUNTERFLASHING2.AND SEALANTS REQUIRED. NOT INCLUDED ASPART OF THE FIRESTONE WARRANTY.

CONTINUOUS BEAD OF AP SEALANT

CONTINUOUS BEAD OF FIRESTONE WATERBLOCK

WATERBLOCK

APPROPRIATE FIRESTONE FASTENER

FIRESTONE TERMINATION BAR

REFER TO FIRESTONE WEBSITE FOR MOSTCURRENT INFORMATION.

12" (304.8 mm) O.C. MAX.

USE APPROPRIATE BASE TIE-IN

3" (76.2 mm) MIN. FACE (SEE NOTES)

METAL COUNTERFLASHING SHALL BE 24 GAUGE3.PRE-FINISHED STEEL OR .032" MIN. ALUMINUMFORMED WITH HEMMED LOWER EDGE.

12" (304.8 mm) O.C. MAX.

ISSUE / REVISION

DATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

UltraPly TPO

BUILDING PRODUCTSNOBODY COVERS YOU BETTER.

www.firestonebpco.com

TM

TM

MAXIMUM WARRANTY:

TERMINATION WITH SURFACE MOUNTEDCOUNTERFLASHING AND TERMINATION BAR

ALL

1/1/2006UT-T-6

20 YEARS

CONTINUOUS BEAD OF AP SEALANTOR HIGH GRADE SEALANT

WALL / CURB(MASONRY /CONCRETESUBSTRATE

ONLY)

MASONRY AND CONCRETEWALLS / CURBS MUST BE

WATERPROOFED ANDMAINTAINED IN ORDER

FOR ANY SURFACEMOUNTED TERMINATION

TO BE EFFECTIVE.

OR ULTRAPLY TPO GP SEALANT

APPROPRIATE FASTENER

4. INSTALL FIRESTONE TERMINATION BARWITH 1/4" (6.4 mm) GAP BETWEEN ADJOININGSECTIONS.

5. TERMINATION BAR MUST BE CUT AT INSIDE AND OUTSIDE CORNERS. DO NOT BEND

AROUND CORNERS.

6.

7. INSTALL METAL WORK IN ACCORDANCE WITHCURRENT SMACNA RECOMMENDATIONS.

TERMINATION BAR MUST BE FASTENED WITHIN1" (25.4 mm) MAX. OF ALL SECTION ENDS.

FIRESTONE INSULATION

SUBSTRATE

NOTES:1.

INSTALL METAL WORK TO MANUFACTURER'SREQUIREMENTS OR SMACNA RECOMMENDATIONS.

GP SEALANT IS REQUIRED ALONG ENTIRE UPSLOPE3.EDGE OF QUICKSEAM FLASHING WHEN ROOFSLOPE IS 1" (25.4 mm) PER FOOT OR GREATER.

ULTRAPLY TPO

ULTRAPLY TPO QUICKPRIME

DRIP/GRAVEL STOP EDGEMETAL (SEE NOTES)

CONTINUOUS CLEAT

4.

WALL

5.5" TPO QUICKSEAM FLASHING IF SHOP FABRICATED METAL EDGE IS USED ITMUST MEET ANSI/SPRI ES-1 OR AN FM STANDARD.

MEMBRANE

FLANGE OF METAL MUST BE FULLY SUPPORTED5.BY WOOD AND TERMINATED AT LEAST 1/2"(12.7 mm) FROM EDGE OF WOOD.

WOOD NAILER MUST BE INSTALLED TO MEETAPPLICABLE BUILDING CODES OR 200 LBS PERLINEAR FOOT MINIMUM IN ANY GIVEN DIRECTION.

ON BALLASTED ROOFS, GRAVEL STOP HEIGHT6.MUST MEET OR EXCEED BALLAST OR PAVERHEIGHT (2" (50.8 mm) MIN. ABOVE ROOF SURFACE).

1/2" (12.7mm) MIN.

1/2" (12.7mm) MIN.

1/4" (6.35 mm) TO1/2" (12.7 mm)

REFER TO FIRESTONE WEBSITE FOR MOSTCURRENT INFORMATION.

2.1-1/4" HOT DIPPED GALVANIZED ROOFNAILS AT 4" (101.6 mm) O.C. MAX.

WOOD NAILER (SEE NOTES)

1-1/4" HOT DIPPEDGALVANIZED ROOF NAILSAT 6" (152.4 mm) O.C. MAX.

ISSUE / REVISIONDATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

Ul t r aPl y TPOTM

BUI LDING PRODUCTSNOBODY COVERS YOU BETTER.

www.firestonebpco.comTM

MAXIMUM WARRANTY:

ROOF EDGE WITH FASCIA METAL BY OTHERS

ALL5/1/2010 UT-RE-20

20 YEARS

CONTINUOUS BEAD OFULTRAPLY TPO GPSEALANT (SEE NOTES)

CONTINUOUS BEAD OFULTRAPLY TPO GP

SEALANT (REQUIRED)

ULTRAPLY TPO BONDINGADHESIVE (ADHEREDSYSTEM ONLY)STOP (SEE NOTES)

OPTIONAL GRAVEL

IF THE FLANGE OF THE METAL EDGE IS NOT7.COMPLETELY COVERED WITH QUICKSEAMFLASHING, THEN AN ADDITIONAL PIECE OFQUICKSEAM FLASHING SHALL BE INSTALLEDAT ALL METAL SPLICES. REFER TO UT-RE-27.

THIS DETAIL IS APPROVED FOR A MAXIMUMOF 20 YEARS. REFER TO DETAIL UT-RE-21

FOR 25 YEAR REQUIREMENTS.

ISSUE / REVISION

DATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

UltraPly TPOTM

BUILDING PRODUCTSNOBODY COVERS YOU BETTER.

www.firestonebpco.com

TM

MAXIMUM WARRANTY:

PENETRATION WITH TPO PENETRATION POCKET KIT

ALL

1/1/2006UT-P-8

20 YEARS

FIRESTONE INSULATION

SUBSTRATE

FIRESTONE INSULATION

NOTES:1.

DO NOT USE OVER EXISTING PENETRATION POCKETS.4.

IF FIELD MEMBRANE IS CUT FOR INSTALLATION, THEMEMBRANE MUST BE REPAIRED WITH TPO MEMBRANEPRIOR TO INSTALLATION OF THE PENETRATION POCKET.MEMBRANE MUST BE INSTALLED WITHIN 1/2" (12.7 mm)

6.

OF PENETRATION.

PENE

TRAT

ION

PENE

TRAT

ION

7.

FIRESTONE POURABLE SEALER MOUNDED TO SHEDWATER (MINIMUM DEPTH OF 2" (50.8 mm), REMAINDER OFPOCKET MAY BE FILLED WITH A NON - SHRINKING GROUT.

3.

ULTRAPLY TPO QUICKPRIME REQUIRED ON PENETRATIONSAND MEMBRANE INSIDE OF PENETRATION POCKET.

PRE-MOLDED ULTRAPLY TPO PENETRATION POCKET

8.

6" (152.4mm)

REFER TO FIRESTONE WEBSITE FOR MOST CURRENTINFORMATION.

1" (25.4 mm) MIN.

NON-

SHRI

NKIN

G GR

OUT

ULTRAPLY TPO BONDING ADHESIVE

REMOVE ALL EXISTING FLASHINGS, LEADS, ETC. PIPE2.SURFACE MUST BE FREE OF ALL RUST, GREASE, INSULATION, ETC.

DO NOT USE WHEN SERVICE LINE TEMP. EXCEEDS 180°F.5.REFER TO UT-P-6 & 7.

(ADHERED SYSTEM ONLY)

WELDED SPLICE 2" (50.8 mm) MIN.

SUBSTRATE

PRECUT PVC PIPE

FIRESTONE POURABLE SEALER

ULTRAPLY TPO QUICKPRIME (SEE NOTES)

ULTRAPLY TPO MEMBRANE

9. REFER TO UT-P-15 OR 16 FOR MAS.

SUBSTRATE

FIRESTONE INSULATION

SUBSTRATE

PENE

TRAT

ION

(HOT

STA

CK)

ISSUE / REVISION

DATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

UltraPly TPO

BUILDING PRODUCTSNOBODY COVERS YOU BETTER.

www.firestonebpco.com

TM

TM

MAXIMUM WARRANTY:

PENETRATION (HOT STACK) WITH ULTRAPLY TPOFLASHING (UNSUPPORTED)

ALL

1/1/2006UT-P-6

20 YEARS

1/2" -

1" (1

2.7 m

m - 2

5.4 m

m)

WELDED SPLICE2" (50.8 mm) MIN.

8" (2

03.2

mm) M

IN.

ULTRAPLY TPO FLASHING(UNSUPPORTED)

ULTRAPLY TPO BONDING ADHESIVE

STAINLESS STEELCLAMPING RING

CONTINUOUS BEADOF ULTRAPLY TPOGP SEALANT

INSULATED METALSLEEVE BY OTHERS

ULTRAPLY TPO BONDING ADHESIVE(SEE NOTES)

ULTRAPLY TPO MEMBRANE

NOTES:1.

REMOVE ALL EXISTING FLASHINGS, LEADS,2.ETC. PIPE SURFACE MUST BE FREE OF ALLRUST, GREASE, INSULATION, ETC.PIPE MUST BE ANCHORED TO ENSURE3.

NO WRINKLES OR FOLDS UNDER CLAMPING4.

REFER TO FIRESTONE WEBSITE FOR MOSTCURRENT INFORMATION.

STABILITY.

RING.

FIELD FABRICATED METALHOOD BY OTHERS (REQUIRED)

FIRESTONE INSULATION

MEMBRANE AND INSULATION FOR FULLYADHERED SYSTEMS.

BONDING ADHESIVE REQUIRED BETWEEN5.

FIRESTONE FASTENER AND HD ORHD PLUS SEAM PLATE AT 12"

6.

(304.8 mm) O.C. MAX. (SEE NOTES)

FIRESTONE FASTENER AND HD SEAM PLATEREQUIRED FOR MAS ONLY. IF FASTENERCANNOT BE INSTALLED AS ILLUSTRATED,REFER TO DETAILS UT-P-15 & 16.

CONTINUOUS BEAD OFAP SEALANT OR HIGH

GRADE SEALANT

7.

(UNSUPPORTED) OR ULTRAPLYTPO MEMBRANE AS FLASHING

ULTRAPLY TPO FLASHING

WHEN REINFORCEMENT OF TPO MEMBRANEIS EXPOSED, REFER TO UT-LS-14 FOR CUTEDGE SEALANT APPLICATION.

ISSUE / REVISION

DATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

UltraPly TPOTM

BUILDING PRODUCTSNOBODY COVERS YOU BETTER.

www.firestonebpco.com

TM

MAXIMUM WARRANTY:

LAP SPLICE WITH 2" HAND WELD

ALL

1/1/2006UT-LS-2

20 YEARS

SLOPE

2" (50.8mm) MIN.

NOTES:1. REFER TO FIRESTONE WEB SITE FOR MOST

CURRENT INFORMATION.

WHEN POLYESTER REINFORCEMENT OF TPOIS EXPOSED, APPLY CUT EDGE TREATMENT TOENTIRE EXPOSED EDGE. REFER TO UT-LS-14.

2" (50.8mm) MIN.

6" (152.4 mm)

FIRESTONE FASTENER ANDHD OR HD PLUS SEAM PLATE

SLOPE 2" (50.8mm) MIN.

ISSUE / REVISION

DATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

UltraPly TPOTM

BUILDING PRODUCTSNOBODY COVERS YOU BETTER.

www.firestonebpco.com

TM

MAXIMUM WARRANTY:

LAP SPLICE WITH 1-1/2" AUTOMATIC WELDER

ALL

1/1/2006UT-LS-1

20 YEARS

SLOPE

1-1/2" (38.1mm) MIN.

NOTES:1. REFER TO FIRESTONE WEB SITE FOR MOST

CURRENT INFORMATION.

WHEN POLYESTER REINFORCEMENT OF TPOIS EXPOSED, APPLY CUT EDGE TREATMENT TOENTIRE EXPOSED EDGE. REFER TO UT-LS-14.

2" (50.8mm) MIN.

6" (152.4 mm)

FIRESTONE FASTENER ANDHD OR HD PLUS SEAM PLATE

SLOPE 1-1/2" (38.1mm) MIN.

NOTES:1.

2.

USE APPROPRIATE

BASE TIE-IN DETAIL

REFER TO FIRESTONE WEBSITE FOR MOSTCURRENT INFORMATION.WELDED SPLICE (SEE NOTES)

ISSUE / REVISION

DATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

UltraPly TPOTM

BUILDING PRODUCTS

NOBODY COVERS YOU BETTER.www.firestonebpco.com

TM

MAXIMUM WARRANTY:

INSIDE CORNER

ALL

1/1/2006UT-C-5

20 YEARS

REFER TO DETAIL UT-LS-1 OR 2 FOR WELDWIDTH.

USE APPROPRIATE TERMINATION DETAIL

ULTRAPLY TPO MEMBRANE

PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDECORNER WELDED IN PLACE (SEE NOTES)

3. ULTRAPLY TPO FLASHING (UNSUPPORTED) MAY BE USED IN LIEU OF PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDE CORNER FOR A MAXIMUM WARRANTY OF 15 YEARS .

4. WHEN REINFORCEMENT OF TPO MEMBRANEIS EXPOSED, REFER TO UT-LS-14 FOR CUTEDGE SEALANT APPLICATION.

USE APPROP.BASE TIE-IN

NOTES:1. REFER TO FIRESTONE WEBSITE FOR MOST CURRENT INFORMATION.

REFER TO DETAIL UT-LS-1 OR 2 FOR WELD WIDTH.2.

ULTRAPLY TPO 18" CURBFLASHING OR MEMBRANE HEAT

WELDED TO ULTRAPLY TPO

ULTRAPLY TPO MEMBRANE

ULTRAPLY TPO T-JOINT COVERWELDED IN PLACE (SEE NOTES)

ISSUE / REVISION

DATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

UltraPly TPOTM

BUILDING PRODUCTSNOBODY COVERS YOU BETTER.

www.firestonebpco.com

TM

MAXIMUM WARRANTY:

INSIDE CORNER WITH CONTINUOUS WALL FLASHING

ALL

1/1/2006UT-C-4

20 YEARS

PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDECORNER WELDED IN PLACE (SEE NOTES)

3. T-JOINT COVER REQUIRED FOR .060 GAUGE MEMBRANE ONLY.4. ULTRAPLY TPO FLASHING (UNSUPPORTED) (4"x4" MIN. WITH

ROUNDED CORNERS) MAY BE USED IN LIEU OF T-JOINT COVER.

DETAIL

(FIELD SHEET)

USE APPROPRIATE TERMINATION DETAIL

5. ULTRAPLY TPO FLASHING (UNSUPPORTED) MAY BE USED IN LIEU OF PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDE CORNER FOR A

MAXIMUM WARRANTY OF 15 YEARS .6. WHEN REINFORCEMENT OF TPO MEMBRANE IS EXPOSED, REFER

TO UT-LS-14 FOR CUT EDGE SEALANT APPLICATION.FIELD SHEET (SEE NOTES)

ISSUE / REVISION

DATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

UltraPly TPOTM

BUILDING PRODUCTS

NOBODY COVERS YOU BETTER.www.firestonebpco.com

TM

MAXIMUM WARRANTY:

OUTSIDE CORNER

ALL

1/1/2006UT-C-1

20 YEARS

USE APPROPRIATE

TERMINATION DETAIL

USE APPROPRIATE

BASE TIE-IN DETAIL

PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDECORNER WELDED IN PLACE (SEE NOTES)

NOTES:1. REFER TO FIRESTONE WEBSITE FOR MOST CURRENT

INFORMATION.REFER TO DETAIL UT-LS-1 OR 2 FOR WELD WIDTH.2.

ULTRAPLY TPO 18" CURB FLASHINGOR MEMBRANE HEAT WELDED TOULTRAPLY TPO FIELD SHEET (SEE NOTES)

ULTRAPLY TPO MEMBRANE (FIELD SHEET)

3. ULTRAPLY TPO FLASHING (UNSUPPORTED) MAY BE USED IN LIEU OF PRE-MOLDED ULTRAPLY TPO INSIDE/OUTSIDE CORNER FOR A MAXIMUM WARRANTY OF 15 YEARS .

4. WHEN REINFORCEMENT OF TPO MEMBRANE ISEXPOSED, REFER TO UT-LS-14 FOR CUT EDGESEALANT APPLICATION.

FIRESTONE INSULATION

SUBSTRATE

WALL / CURB

NOTES:1.

3.

WELDED SPLICE (SEE NOTES)

ULTRAPLY TPO MEMBRANE

ULTRAPLY TPO BONDING ADHESIVE (SEE NOTES)

USE APPROPRIATETERMINATION

REFER TO FIRESTONE WEBSITE FOR MOSTCURRENT INFORMATION.REFER TO DETAIL UT-LS-1 OR 2 FOR WELD WIDTH.2.

POSI

TION

PLA

TE 1/

2" (1

2.7 m

m)

MIN.

ABO

VE F

INIS

HED

ROOF

ULTRAPLY TPO MEMBRANE MUST EXTEND1/2" (12.7 mm) BEYOND HD OR HD PLUS SEAM PLATE (SEE NOTES)

ULTRAPLY TPO BONDING ADHESIVE

ISSUE / REVISION

DATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

UltraPly TPO

BUILDING PRODUCTSNOBODY COVERS YOU BETTER.

www.firestonebpco.com

TM

TM

MAXIMUM WARRANTY:

BASE TIE-IN WITH HD SEAM PLATES FASTENEDTO WALL / CURB

ALL

1/1/2006UT-BT-2

20 YEARS

4.

REFER TO UT-BT-16 & 17 FOR MEMBRANESECUREMENT AT CORNERS.

FIRESTONE FASTENER AND HD OR HD PLUS SEAMPLATE AT 12" (304.8 mm) O.C. MAX. (SEE NOTES)

ULTRAPLY TPO 18" CURB FLASHING OR MEMBRANE

BONDING ADHESIVE REQUIRED BETWEEN MEMBRANEAND INSULATION FOR FULLY ADHERED SYSTEMS.

5. WHEN REINFORCEMENT OF TPO MEMBRANE ISEXPOSED, REFER TO UT-LS-14 FOR CUT EDGESEALANT APPLICATION.

FIRESTONE INSULATION

SUBSTRATE

WALL / CURB

NOTES:1.

MAXIMUM 6" (152.4 mm) LONG FASTENERS.3.(NOTE: WOOD BLOCKING MAY BE SUBSTITUTEDFOR INSULATION TO REDUCE FASTENER LENGTH REQUIREMENT).

4.

6.

WELDED SPLICE (SEE NOTES)

ULTRAPLY TPO MEMBRANE

ULTRAPLY TPO BONDING ADHESIVE (SEE NOTES)

USE APPROPRIATETERMINATION

BONDING ADHESIVE REQUIRED BETWEEN MEMBRANEAND INSULATION FOR FULLY ADHERED SYSTEMS.

REFER TO FIRESTONE WEBSITE FOR MOSTCURRENT INFORMATION.

ULTRAPLY TPO BONDING ADHESIVE

ISSUE / REVISION

DATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

UltraPly TPOTM

BUILDING PRODUCTSNOBODY COVERS YOU BETTER.

www.firestonebpco.com

TM

MAXIMUM WARRANTY:

BASE TIE-IN WITH HD SEAM PLATES FASTENED TO DECK

ALL

1/1/2006UT-BT-1

20 YEARS

REFER TO DETAIL UT-LS-1 OR 2 FOR WELD WIDTH.2.

FIRESTONE FASTENER AND HD OR HD PLUS SEAMPLATE AT 12" (304.8 mm) O.C. MAX. (SEE NOTES)

ULTRAPLY TPO 18" CURB FLASHING OR MEMBRANEIN CASE OF OBSTRUCTION REFER TO DETAIL UT-BT-5.

5. REFER TO UT-BT-16 & 17 FOR MEMBRANESECUREMENT AT CORNERS.HD OR HD PLUS SEAM PLATE POSITIONED

1/2" (12.7 mm) BEYOND WALL/CURB

7. WHEN REINFORCEMENT OF TPO MEMBRANE ISEXPOSED, REFER TO UT-LS-14 FOR CUT EDGESEALANT APPLICATION.

NOTES:1.

HOLE IN MEMBRANE SHOULD EXTEND A MINIMUM OF 1/2"2.

INSULATION ADJACENT TO DRAIN TO BE APPROPRIATE3.FIRESTONE INSULATION WITH APPROPRIATE BONDING

FIRESTONE WATERBLOCK MIN. OF 1/2 OF 10 OZ (295 ml)4.

IN REROOF APPLICATIONS:5.- REMOVE EXISTING FLASHINGS DOWN TO METAL BOWL- REPAIR OR REPLACE BROKEN DRAIN COMPONENTS- DRILL AND TAP BROKEN DRAIN BOLTS AND REPLACE

(12.7 mm) BEYOND CLAMPING RING AND SHOULD NOT BE

IF NECESSARY.

SUBSTRATE

FIRESTONE INSULATION

ULTRAPLY TPO BONDING

ULTRAPLY TPO

CONTINUOUS BEAD OFFIRESTONE WATERBLOCK

COMPRESSION RINGSTRAINER BASKET

FIRESTONE INSULATION

SUBSTRATE

SURFACE.

TUBE PER 4" DRAIN. USE ADDITIONAL WATERBLOCK

SMALLER THAN THE DIAMETER OF THE LEADER PIPE.

FOR LARGER DRAINS.

1/2" (12.7mm) MIN.SEE NOTES

REFER TO FIRESTONE WEB SITE FOR MOST CURRENTINFORMATION.

(SEE NOTES)

MEMBRANE

12" (304.8 mm)

ADHESIVE (ADHERED

ISSUE / REVISION

DATE:

NOT TO SCALEACCEPTABLE SYSTEMS:

DETAIL NO.

UltraPly TPOTM

BUILDING PRODUCTS

NOBODY COVERS YOU BETTER.www.firestonebpco.com

TM

MAXIMUM WARRANTY:

ROOF DRAIN

ALL

1/1/2006UT-D-1

20 YEARS

SYSTEMS ONLY)

IF FIELD SEAM EDGE IS WITHIN 9" (228.6 mm) OF DRAIN COMPRESSION RING, TPOTARGET PATCH REQUIRED.IF FIELD SEAM EDGE IS WITHIN 9" (228.6 mm) TO 18" (457.2 mm) OF DRAIN COMPRESSIONRING, HEAT WELD A LAYER OF ULTRAPLY TPO FLASHING (UNSUPPORTED) OR ULTRAPLY

SUMP AREA FIELD SEAM REQUIREMENTS:

A.

B.

TPO MEMBRANE CENTERED OVER SEAM EDGE. FLASHING MUST EXTEND 3" (76.2 mm) MIN.BEYOND EDGE OF SUMP.

1" MAX.(25.4 mm)

A3.1

TPO Roof Details