tgm 5, tgm 5-ex transmitter for angular position · tgm 5, tgm 5-ex transmitter for angular...
TRANSCRIPT
TGM 5, TGM 5-Ex Transmitter for angular position
Operating instruction 42/1434 EN Rev. 02
42/14-34 EN
A112.5
∅15
8∅
110j
6∅
60
B
D
32
35
61.511.5200
AC
Z-14961/1
E
Z-14961/2
PG 13.5 od./orM 18 x 1.5
55°
9.5
130±
0.2
8
Fig. 3 Dimensional drawing of TGM 5 (-Ex) with flange mounting(dimensions in mm)
42/14-34 EN
Z-14961/3
E
E
9
Cable entry Plug connection
Pg13.5 M 18 x 1.5 angled straight
E 71.5 90.5 ≈ 143 ≈ 157
TGM 5
friction bearing ball bearing
A ∅ 19f8 ∅ 10f8
B 1 × 45° 0.5 × 45°
C 3 ± 0.1 –
D 3.5 ± 0.1 –
View AVersion with plugconnection
to Fig. 3
11
42/14-34 EN
Output and power supply
Catalog No.optional model4th position
Electricalisolation
Powersupply Us
Max. powersupply con-sumption
Max.load
1 without 12...20 V DC 24 mA
without 12...36 V DC 24 mA
2 without 13.2...36 V DC 24 mA
without 13.2...26.4 V AC 24 mA
3 with 13.2...36 V DC 100 mA 600 Ω
with 13.2...26.4 V AC 100 mA 600 Ω
US 12V–( )IA
----------------------------
US 12V–( )IA
----------------------------
US 13 2V,( )–IA
----------------------------------
US 13 2V,( )–IA
---------------------------------- 1 4,×
36
42/14-34 EN
2) only with output 4...20 mA, 4-wire circuit (Catalog No. 14436-xx7xxx0)
Catalog No.optional model4th position
2-wirecircuit
3-wirecircuit
4-wirecircuit
JumperBr3
1 4...20 mA open
–––4...20 mA
0... 5 mA0...10 mA0...20 mA–
0... 5 mA0...10 mA0...20 mA4...20 mA2)
closedclosedclosedopen
2 –––4...20 mA
0... 5 mA0...10 mA0...20 mA–
0... 5 mA0...10 mA0...20 mA4...20 mA2)
closedclosedclosedopen
0... 5 mA0...10 mA0...20 mA4...20 mA2)
closedclosedclosedopen
3 0... 5 mA0...10 mA0...20 mA4...20 mA2)
closedclosedclosedopen
0... 5 mA0...10 mA0...20 mA4...20 mA2)
closedclosedclosedopen
37
42/14-34 EN
Explosion protection
Certificate of conformityPTB 03 ATEX 2118
DesignationII 2 G EEx ib IIC T6 orII 2 G EEx ib IIC T4
Temperature classT6 for max. 40 °C ambient temperatureT4 for max. 70 °C ambient temperature
Mounting of the unitWithin hazardous areas of Zone 1 or Zone 2
Supply and signal current circuitFor connection to a certified intrinsically safe current circuitwith the following maximum valuesU = 20 V, I = 35 mA, P = 700 mW
Effective internal inductance LiNegligibly low
Effective internal capacitance Ci between the connectionsNegligibly low
Effective internal capacitance Ci between the connections and case (ground)
≤ 6 nF
42
ABB Automation Products GmbHBorsigstr. 2, 63755 Alzenau, GermanyPhone +49 551 905534Fax. +49 551 [email protected]
© Copyright 2003 by ABB Automation Products GmbHWe reserve the right to technical amendments
This document is protected by copyright. Information in this doc-ument is intended only to assist the user in safe and efficient op-eration of the equipment. Its contents are not to be reproducedin full or part without prior approval of legal owner.
Subject to technical changesPrinted in the Fed. Rep. of Germany
42/1434 EN Rev. 02Edition 10.03