TECHNICAL SPECIFICATIONS

DETECTOR TYPE S100 OPTICAL S200 MULTICRITERIA S300 FIXED TEMP. S400 RATE OF RISE

standby current (nominal) 70µA 70µA 35µA 35µA

alarm current (maximum) 50mA 50mA 50mA 50mA

operating voltage 10-30vDC 10-30vDC 10-30vDC 10-30vDC

Max. humidity (non-condensing) 95%RH 95%RH 95%RH 95%RH

operating temperature -30ºC + 70ºC -30ºC + 70ºC -30ºC + 70ºC -30ºC + 70ºC

storage temperature -40ºC + 70ºC -40ºC + 70ºC -40ºC + 70ºC -40ºC + 70ºC

weight including base 130g 130g 130g 130g

diameter 1100mm 1100mm 1100mm 1100mm

height including base 54mm 54mm 54mm 54mm

The Aurora conventional detector range has been designed to satisfy the highest demands of the installer, specifier and owner. Designed to the latest advanced in technology has minimised the number of active com-ponents. A custom ASIC provides superior and reliable detection performance whilst re-ducing the unwanted problems of false alarms. Aurora conventional detectors have been designed with a unique symmetrical chamber. The chamber ensures opti-mum air entry from all directions and offers im-munity to ambient light into the detector. The chamber also in- corporates a patented double dust trap which signifi- cantly reduces the en-try of unwanted airborne contami- nants. This design en-sures optimum performance and increases intervals between ser-vicing. Aurora conventional detector features:

• adaptive signal processing algorithym

• continuous screen providing protection from insects

• central LED providing 360º visibility

• detector magnet test

• symmetrical chamber and patented double dust trap

• unique range of Decorline finishes

The Aurora family is complete with a wide range of detector bases. Both standard and deep bases are available with a wide range of resistors and schotty diode. The BLR100 is a 12-24vDC relay base which can be directly connected to a 12v security sys-tem.

UB100 universal base DBS100 deep base

BLR100 relay base

The CA100 conduit adaptor can be used together with the DBS100 deep base when a surface conduit installation is required.

DC100 dust covers are separately and provide a protective cover to avoid contamination during in-stallation.

CP100 resettable call point

A resettable manual call point designed in accordance with EN54-11. The device can be flush or surface mounted.

A full range of system accessories are available for the Aurora product family.

Argus Security S.r.l. Via Archimede, 42 – Agrate Brianza – 20041 – Milano – Italy Tel +39 039 689 2749 – Fax +39 039 689 5033 – [email protected] – www.argussecurity.it

defining new standards in fire detection technology

All products are supplied with a three year warranty and are CE marked.

ALS100 wall sounder

High output (up to 100dBA) intelligent wall mounted sounder. This sounder has a compact design and is complete with a lockable base.

CBS100 platform sounder

Low current sounder powered via the remote output of the detector.

WCP100 resettable waterproof call point

A resettable waterproof manual call point rated to IP67.

FI100 remote indicator

24vDC low current remote indicator powered via the remote output of the detector.

Smoke Detector Test Kit Set for removing, replacing and testing of smoke detectors up to 6m. Available for both photo and thermal detectors