the ultimate safety breaker - terasaki electric malaysia€¦ · 11/1/2012 · terasaki have an...
TRANSCRIPT
The Ultimate Safety Breaker
page 1 The Ultimate Safety Breaker
OUR CUSTOMER CARE
COMMITMENTS
CUSTOMER SERVICE CONTACT DETAILS
Quality is Guaranteed
All products supplied from this catalogue carry a guarantee against defects in materials andworkmanship for a period of 12 months from date of purchase as standard.
Quality is Accredited
Terasaki has ISO 9001 accreditation for themanufacture, sale and distribution of all productsfeatured in this catalogue.
Ordering is Easy
We have made ordering easy for you by colourcoding the sections of this catalogue and includingorder codes. If you need help with ordering or selection, please call one of the telephone numbers shown below.
Technical Support is Free
We offer free technical support and application software to all customers. This could range fromselecting a product for an unusual applicationthrough to carrying out a protection study. Pleasecall one of the telephone numbers shown below.
Italy: +39 02 92278300
Spain & Latin America: +34 93 8796050
Sweden: +46 8 55628230
Denmark: +45 70 260057
UK and all other
countries in Europe,
Middle East
and Africa: +44 141 9411940
Australia and
New Zealand: +61 3 9429 2999
Brazil: +55 21 33019898
Malaysia: +60 3 55493820
Singapore: +65 6425 4915
China: +86 20 8270 8556
Japan and all
other countries
in Asia: +81 6 67919323
Safety and protection are theprime purposes of Terasakiproducts. You care about safetyand protection. The users ofproducts you specify care aboutsafety and protection.We call TemBreak 2 the UltimateSafety Breaker. Throughout thiscatalogue you will see ourSafety+ mark. This is designedto draw your attention to safetyfeatures which exceedinternational standards.Please read further to discover the benefits of TemBreak 2.
page 3 The Ultimate Safety Breaker
THE TEMBREAK 2PRODUCT LINES
TEMBREAK 2
MOULDED CASE CIRCUIT BREAKERS
Rated current (In) from 20A to 1600A. BreakingCapacity (Icu) from 25kA to 200kA at 415V AC.
SE
CT
ION
1
The Ultimate Safety Breaker page 4
WELCOME TO TEMBREAK 2
TEMBREAK 2 MOULDED CASE CIRCUIT BREAKERS
16A TO 1600A
1. Welcome to TemBreak 2• Easy Selection Guide 5
• 10 Reasons to use TemBreak 2 7
• Safety Plus 9
• Exceeding Standards 11
• Reducing Environmental Impact 12
2. Ratings and Specifications
3. Operating Characteristics
4. Application Data
5. Accessories
6. Installation
7. Dimensions
page 5 The Ultimate Safety Breaker
The TemBreak 2 range of products includes:
- Moulded Case Circuit Breakers (MCCBs)
- Switch-Disconnectors in the same compact mouldedcase frame sizes as MCCBs
- A comprehensive range of accessories which arecommon to MCCBs and Switch-Disconnectors. All internal accessories are common to all frame sizes.
F
J Adjustable thermal, adjustable magnetic
E Electronic protection
N No protection
S 125 G J
E Economical
S Standard
H High
L Limiting*
Frame rating, In (A)
C,S Low breaking capacity
N Medium breaking capacity
G,R High breaking capacity
Fixed thermal, fixed or adjustable magnetic
P Extra High breaking capacity
Type Denoted by
Model Denoted by
Key to Model and Type Designations
EASY SELECTION GUIDE
WELCOME TO TEMBREAK 2
*All TemBreak 2 MCCBs limit short-circuit faults by opening inless than 5ms. Limiting (L) models open particularly quickly.
SE
CT
ION
1
The Ultimate Safety Breaker page 6
E
LH
S
E
Note: All breaking capacities are r.m.s. symmetrical at 415V AC
125 160/250 400/630 800/1000
Model TypeModel Type
S400 NNS630 NN
Frame Rating (A)
In (A)
1250/1600
12516
250
16
630250
1000630
16001250
E400 NJ 25
E630 NE 36
S400 CJ 36
S400 NJ 50
S400 NE 50
S400 GJ 70
S400 GE 70
S400 PJ 85
S400 PE 85
S630 CE 50
S630 GE 70
H400 NE 125
L400 NE 200
Model Type Icu (kA)
S800 CJ 36
S800 NJ 50
S800 NE 50
S800 RJ 70
S800 RE 70
S1000 SE 50
S1000
H800 NE 125
L800 NE 200
Model Type Icu (kA)Model Type Icu (kA) Model Type Icu (kA)
E125 NJ 25
S125 NF 25
S125 NJ 36
S125 GJ 65
H125* NJ 125
L125* NJ 200
E250
S160 NF 25
S160 NJ 36
S160 GJ 65
S250 NJ 36
S250 NE 36
S250 GJ 65
S250 GE 65
S250 PE 70
H160 NJNJ
NJNJ
125
H250 125
NEH250 125
L160 200
L250 200
25NJ
MCCBs
S800 NNS1000 NN
Model Type
NE 70
S1250 SE 50
S1250 NE 70
S1250 GE 85
S1600 SE 50
S1600 NE 85
Model Type Icu (kA)
S1250 NNS1600 NN
Model TypeModel Type
S125 NN S160 NNS250 NN
Switch-Disconnectors
WELCOME TO TEMBREAK 2
EASY SELECTION GUIDE
*250A Frame
page 7 The Ultimate Safety Breaker
• Accessories can be fitted by the switchboard builder or added by theend-user.
• Handles and motor operators can be rapidly fitted using the lockingpegs. It takes less than 10 seconds to secure a handle or motor to the MCCB – a great time saving compared to alternative products.
• All accessories are endurance tested to the same level as the host MCCB.
10 REASONS TO USE TEMBREAK 2
1. FIELD-INSTALLABLE ACCESSORIES
The plug-in MCCB is locked to the base when the toggleis ON. It cannot be removed unless the toggle is OFF or TRIPPED. The safety lock prevents a trip occurring as the MCCB is being removed from the base.
2. SAFETY LOCK FOR PLUG-IN VERSIONS
Door cutout patterns forhandles are symmetrical, even when breakers aremounted in opposite directions.
3. SYMMETRICAL DOOR CUTOUT PATTERNS
Using TemBreak 2 Operating Handles Using other MCCB Operating Handles
All current ratings up to 630Acan be supplied in 2 sizes:the 250A and 630A sizes.
4. MODULAR SIZES
The XOW-1S OCR comes standard with thebacklit LCD display. It can monitor andindicate phase currents, voltages, power,energy, power factor, harmonic currents, andmore. Data communications via Modbus, anopen network, are supported.
5. ADVANCED L.C.D. DISPLAY, OCR
The compact 125A size offers the same features and performance but withreduced dimensions and cost.
LockingPegs
Plug-in MCCB and base Plug-in connection kit, including safety lock
SafetyLock
SE
CT
ION
1
The Ultimate Safety Breaker page 8
10 REASONS TO USE TEMBREAK 2
The mechanical interlock is installed on the front ofthe MCCB, and is compatible with motor operatorsand handles. An automatic changeover system can beassembled very easily by a switchboard builder orend-user.
6. COMPACT CHANGEOVERS
Under the heading “Measures to minimise the risk in the event of failure”,IEC 60204-1 Safety of Machinery-Electrical Equipment of Machineryincludes the following recommendation:
“-the use of switching devices having positive (or direct) opening operation.”
7. DIRECT OPENING
If you require a characteristic which is not available as a preset onour electronic protection unit, send us the details and we willprogram a customised characteristic to suit your application.(Within certain limits - contact us for details).
9. CUSTOMISED TRIPPING TIMES
Overload protection is adjustable between 63% and 100% of the rating.
Short-circuit protection is adjustable on all thermal magnetic models.
Short-circuit protection settings are suitable for motor starting on all models, including the compact 125A frame.
8. UNSURPASSED FLEXIBILITY
10. VISUAL SAFETY
Coloured indicators display the ONor OFF status. The indicators are fullycovered if the breaker trips, and blackis the only visible colour.
Changeover Pair with Link Interlockand Motor Operators
Viewed from Below (250A frame)
ON (I) OFF (O) TRIPPED
WELCOME TO TEMBREAK 2
SAFETY PLUS
Terasaki have an innovative approach to product design. Our goal is to develop products which not only meet, but exceed recognised standards.
We use our knowledge of related applications to improvecircuit breaker designs. For instance, when developing the Direct Opening Action, we applied ideas from a machinery safety standard to the design of theTemBreak 2 switching mechanism.
This proactive development policy confirms our reputation as Innovators in Protection Technology.
Machine Safety
TemBreak 2 MCCBs are marked with IEC symbol indicatingDirect Opening Action.
The robust mechanism ensures that the force you apply to the toggle is transmitted directly to the contacts.
Under the heading “Measures to minimise risk in the event offailure”, IEC 60204-1 Safety of Machinery - ElectricalEquipment of Machines includes the followingrecommendation:
TemBreak 2 MCCBs help you to comply with the world’s moststringent safety standards. It is one of the safest switchingdevices for machinery.
“ - the use of switching devices having positive
(or direct) opening operation.”
page 9 The Ultimate Safety Breaker
Opening force istransmitteddirectly fromthe toggle switch
Contacts separated Maintenance canbe performed onthe load side
The Ultimate Safety Breaker page 10
SE
CT
ION
1
WELCOME TO TEMBREAK 2
You can easily see if a breaker is open, closed or tripped. SAFETY+ colouredindicators boldly display the ON or OFF status. The indicators are fully covered ifa breaker trips, and black is the only visible colour.
This is a unique safety feature. You can identify faulty circuits at a glance.
The toggle position always matches the position of the main contacts.
ON (I) OFF (O) TRIPPED
The risk of touching live parts has been minimised by design. These features reduce the risk of touching live parts:
• There are no exposed metal screws on the front face
• IP20 protection at the terminals
• IP30 protection at the toggle
• If the toggle is broken by accident or misuse, no live part is exposed
• No live parts are exposed when fitting accessories
• Double Insulation
Touch Safety
SAFETY PLUS
Visual Safety
page 11 The Ultimate Safety Breaker
Safety Plus
TemBreak 2 MCCBs exceed the requirements of recognised standards.
International Compliance
• The TemBreak 2 MCCB complies with the internationalstandard IEC 60947-2
• TemBreak 2 Switch Disconnectors comply with IEC 60947-3
• Accessories comply with IEC 60947-5-1 or IEC 61058-1
• The entire range conforms to the IEC general rules for switchgear, IEC 60947-1
• TemBreak 2 MCCBs comply with JIS C 8201-2-1 Ann.1
• The TemBreak 2 range complies with the EC Low Voltage Directive and all models are CE marked
• TemBreak 2 MCCBs carry the IEC symbol indicating Direct Opening Action as defined by IEC 60947-5-1. IEC 60204-1, Safety of Machinery - Electrical Equipment of Machines recommends that switches used for machinery have Direct Opening Action to minimise risk in the event of failure
Independent Tests
TemBreak 2 circuit breakers have been tested at independent laboratories as well as in Terasaki's own laboratory in Osaka, Japan. Copies of independent test reports are availableon request.
Marine Approvals
TemBreak 2 MCCBs are approved by the leading marine approval organisations.
EXCEEDING STANDARDS
WELCOME TO TEMBREAK 2
WELCOME TO TEMBREAK 2
Longer Life Cycle
It makes good environmental sense to install a product with a long life expectancy. If you install a TemBreak 2MCCB, you can expect it to stay in service for at least 30,000 mechanical operations (250A Frame). This is 22,000 more operations than recommended by IEC 60947-2, the international standard for circuit breakers.
If a system must be upgraded in future, we have made the following provisions for recycling:
The modular design of TemBreak 2 allows component parts and accessories to be easily disassembled and separately disposed of. Moulded parts do not contain any embedded metal parts.
Materials are clearly marked to allow future identification for easy recycling.
Uses Eco-friendly Materials
The following materials are used in most TemBreak 2 circuitbreakers:
• Thermoplastic resin not containing PBBs or PBDEs
• Lead-free solder
• Cadmium-free contacts
Lighter and Smaller
Components with low weight and volume make life easy for users, but high performance from smaller products alsomeans less material used and less waste produced.
1
2
REDUCING ENVIRONMENTAL IMPACT
ISO 14001 Terasaki operate an Environmental Management System accredited to ISO 14001:1999. This requires us to monitorand measure the environmental performance of our activities, products and services in order to continually improvesuch performance.
Further information about this standard can be found on the internet at: www.tc207.org
1
2
SE
CT
ION
1
1
• Accessories can be fitted by the switchboard builderor added by the end-user. All internal accessories arecommon for TemBreak 2 MCCBs.
• Handles and motor operators can be rapidly fittedusing the locking pegs. It takes less than 10 secondsto secure a handle or motor to the MCCB – a greattime saving compared to alternative products.
• All accessories are endurance tested to the same levelas the host MCCB.
FIELD-INSTALLABLE ACCESSORIES
LockingPegs
SE
CT
ION
2
The Ultimate Safety Breaker page 14
RATINGS AND SPECIFICATIONS
TEMBREAK 2 MOULDED CASE CIRCUIT BREAKERS
16A TO 1600A
1. Welcome to TemBreak 2
2. Ratings and Specifications
• MCCBs 15
• Switch-Disconnectors 21
3. Operating Characteristics
4. Application Data
5. Accessories
6. Installation
7. Dimensions
page 15 The Ultimate Safety Breaker
Frame Quantity Unit Condition 125
Model E125 S125Number of Poles 3, 4 1Type NJ NF
Nominal current ratings
In (A) 45oC 20,32,50, 16,20,25,63,100,125 32,40,50,
63, 80,100,125
Electrical characteristics
Rated operational voltage Ue (V) AC 50/60 Hz 525 240DC 500 -
Rated insulation voltage Ui (V) 800 800Rated impulse withstand voltage Uimp (kV) 8 8
Ultimate breaking capacity Icu (kA) 690V AC - -(IEC, JIS, AS/NZS) 525V AC 8 -
440V AC 15 -400/415V AC 25 -220/240V AC 35 25250V DC 25 -
Service breaking capacity Ics (kA) 690V AC - -(IEC, JIS, AS/NZS) 525V AC 6 -
440V AC 12 -400/415V AC 19 -220/240V AC 27 13250V DC 19 -
Rated breaking capacity (NEMA) (kA) 480V AC 8 -240VAC 35 25
Protection
Adjustable thermal, adjustable magneticFixed thermal, fixed magneticMicroprocessorUtilisation category A A
Installation
Front connection (FC)Extension bar (FB) • •Cable clamp (FW) • •Rear connection (RC) • -Plug-in (PM) • -Draw- out (DR) - -DIN rail mounting (DA) • •Dimensions h (mm) 155 155
w (mm) 3 pole, (1 pole) 90 (30)4 pole 120
d (mm) 68 68Weight W (kg) 3 pole, (1 pole) 1.1 (0.45)
4 pole 1.4
Operation
Direct Opening ActionToggle operation Door mounted (HS, HP) / Breaker mounted handle (HB) • -Motor operation (MC) • -
Endurance Electrical cycles 440V ACMechanical cycles
MCCB ELECTRICAL CHARACTERISTICS TO IEC 60947-2, EN 60947-2,
JIS C 8201-2-1 ANN.1, AS/NZS 3947-2, NEMA AB-1
RATINGS AND SPECIFICATIONS
Standard • Optional - Not Available
SE
CT
ION
2
*Applies only to 20A and 32A models The Ultimate Safety Breaker page 16
160
S125 S125 H125 L125 S160 S160 S160 H160 L1603, 4 3,4 3, 4 3, 4 1 3, 4 3, 4 3, 4 3, 4NJ GJ NJ NJ NF NJ GJ NJ NJ
20,32,50, 20,32,50, 20,32,50, 20,32,50, 16,20,25,32, 20,32,50,63, 50,63,100, 160 16063,100,125 63,100,125 63,100,125 63,100,125 40,50,63,80, 100,125,160 125,160
100,125,160
690 690 690 690 415 690 690 690 690600 600 600 600 125 600 600 600 600800 800 800 800 800 800 800 800 8008 8 8 8 8 8 8 8 8
6 6 20 25 - 7.5 (5*) 7.5 20 2522 25 45 65 - 25 (18*) 25 45 6525 50 120 180 - 25 (18*) 50 120 18036 65 125 200 - 36 (30*) 65 125 20050 85 150 200 25 65 (42*) 85 150 20025 40 40 40 - 40 (30*) 40 40 40
6 6 15 20 - 7.5 (5*) 7.5 15 2022 22 45 65 - 25 (18*) 25 45 6525 25 80 135 - 25 (18*) 25 80 13536/30 36/33 85 150 - 36 (25*) 36 85 15050 85 150 150 19 65 (35*) 85 150 15019 40 40 40 - 40 (25*) 40 40 40
22 25 45 65 - 22 (18*) 25 45 6550 85 150 200 25 65 (42*) 85 150 200
A A A A A A A A A
• • • • • • • • •• • • • • • • • •• • • • - • • • •• • • • - • • • •- - - - - - - - -
• • - - - - - - -155 155 165 165 165 165 165 165 16590 90 105 105 (35) 105 105 105 105120 120 140 140 - 140 140 140 14068 68 103 103 68 68 68 103 1031.1 1.1 2.4 2.4 (0.5) 1.5 1.5 2.5 2.51.4 1.4 3.2 3.2 1.9 1.9 3.3 3.3
• • • • - • • • •• • • • - • • • •
RATINGS AND SPECIFICATIONS
30,00030,000
20,00030,000
20,00030,000
page 17 The Ultimate Safety Breaker
MCCB ELECTRICAL CHARACTERISTICS TO IEC 60947-2,
EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS 3947-2, NEMA AB-1
RATINGS AND SPECIFICATIONS
Frame Quantity Unit Condition 250
Model E250 S250 S250 S250 S250Number of Poles 3, 4 3, 4 3, 4 3, 4 3, 4Type NJ NJ GJ NE GE
Nominal current ratings
In (A) 45oC 20,32 160 160 40, 40,50,63 200 200 125, 125,100,125 250 250 160 160160,200 250 250
Electrical characteristics 250
Rated operational voltage Ue (V) AC 50/60 Hz 525 690 690 690 690DC 500 600 600 - -
Rated insulation voltage Ui (V) 800 800 800 800 800Rated impulse withstand voltage Uimp (kV) 8 8 8 8 8
Ultimate breaking capacity Icu (kA) 690V AC - 7.5 7.5 7.5 7.5(IEC, JIS, AS/NZS) 525V AC 10 25 25 25 25
440V AC 15 25 50 25 50400/415V AC 25 36 65 36 65220/240V AC 35 65 85 65 85250V DC 25 40 40 - -
Service breaking capacity Ics (kA) 690V AC - 7.5 7.5 7.5 7.5(IEC, JIS, AS/NZS) 525V AC 7.5 25 25 25 25
440V AC 12 25 25 25 25400/415V AC 19 36 36 36 36220/240V AC 27 65 85 65 85250V DC 19 40 40 - -
Rated breaking capacity (NEMA) (kA) 480V AC 10 22 25 25 25240VAC 35 65 85 65 85
Rated short-time withstand current Icw (kA) 0.3 Seconds - - - - -
Protection
Adjustable thermal, adjustable magneticFixed thermal, fixed magneticMicroprocessorUtilisation category A A A A A
Installation
Front connection (FC)Extension bar (FB) • • • • •Cable clamp (FW) • • • • •Rear connection (RC) • • • • •Plug-in (PM) • • • • •Draw- out (DR) - - - - -DIN rail mounting (DA) - - - - -Dimensions h (mm) 165 165 165 165 165
w (mm) 3 pole 105 105 105 105 105(mm) 4 pole 140 140 140 140 140
d (mm) 68 68 68 103 103Weight W (kg) 3 pole 1.5 1.5 1.5 2.3 2.3
4 pole 1.9 1.9 1.9 3.1 3.1
Operation
Direct Opening ActionToggle operation Door mounted (HS, HP) / Breaker mounted handle (HB) • • • • •Motor operation (MC) • • • • •Endurance Electrical cycles 415V AC
Mechanical cycles
Standard • Optional - Not Available
SE
CT
ION
2
*MCCB cannot be used in IT systems at this voltage.**Max. rating 225A for Plug-in.† Refer to Temperature Ratings, Section 6.
Contact us for details.
The Ultimate Safety Breaker page 18
RATINGS AND SPECIFICATIONS
400 630
S250 H250 H250 L250 E400 S400 S400 S400 S400 S400 S400 S400 H400 L400 E630 S630 S6303, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3,4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3,4 3, 4 3, 4PE NJ NE NJ NJ CJ NJ NE GJ GE PJ PE NE NE NE CE GE
40, 160, 40, 160, 250, 250, 250, 250, 250, 250, 250, 250, 250, 250, 630 630 630125, 250** 125, 250** 400 400 400 400 400 400 400 400 400 400160 160250 250
690 690 690 690 525 690 690 690 690 690 690 690 690 690 690* 690* 690*- 600 - 600 500 600 600 - 600 - 600 - - - - - -800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 8008 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8
20 20 20 25 - 15 20 20 20 20 20 20 35 50 10* 20* 20*35 45 45 65 15 22 30 30 30 30 30 30 45 65 15 30 3050 120 120 180 22 30 45 45 65 65 80 80 120 180 25 45 6570 125 125 200 25 36 50 50 70 70 85 85 125 200 36 50 70125 150 150 200 35 50 85 85 100 100 100 100 150 200 50 85 100- 40 - 40 25 40 40 - 40 - 40 - - - - - -
15 15 15 20 - 15 15 15 15 15 15 15 35 50 10* 15* 15*35 45 45 65 15 22 30 30 30 30 30 30 45 65 15 30 3050 80 80 135 22 30 45 45 50 50 80 80 80 135 25 45 5070 85 85 150 25 36 50 50 50 50 85 85 85 150 36 50 50125 150 150 150 35 50 85 85 85 85 85 85 150 150 50 85 85- 40 - 40 19 40 40 - 40 - 40 - - - - - -
35 45 45 65 15 22 25 25 30 30 30 30 45 65 15 25 30125 150 150 200 35 50 85 85 100 100 100 100 150 200 50 85 100
- - - - - - - 5 - 5 - 5 5 5 - - -
A A A A A A A B A B A B B B A A A
• • • • • • • • • • • • • • • • •• • • • • • • • • • • • • • - - -• • • • • • • • • • • • • • • • •- † - † • • • • • • • • • •- - - - • • • • • • • • • • - - -- - - - - - - - - - - - - - - - -165 165 165 165 260 260 260 260 260 260 260 260 260 260 260 260 260105 105 105 105 140 140 140 140 140 140 40 140 140 140 140 140 140140 140 140 140 185 185 185 185 185 185 185 185 185 185 185 185 185103 103 103 103 103 103 103 103 103 103 103 103 140 140 103 103 1032.5 2.4 2.5 2.4 4.2 4.2 4.2 4.3 4.2 4.3 4.2 4.3 7.1 7.1 5.0 5.0 5.03.3 3.2 3.3 3.2 5.6 5.6 5.6 5.7 5.6 5.7 5.6 5.7 9.4 9.4 6.5 6.5 6.5
• • • • • • • • • • • • • • • • •• • • • • • • • • • • • • • • • •
4,50015,000
4,50015,000
10,00030,000
page 19 The Ultimate Safety Breaker
MCCB ELECTRICAL CHARACTERISTICS TO IEC 60947-2, EN 60947-2,
JIS C 8201-2-1 ANN.1, AS/NZS 60947-2, NEMA AB-1
RATINGS AND SPECIFICATIONS
Standard • Optional - Not Available
Frame
ModelNumber of PolesType
Nominal current ratings
Electrical characteristics
Rated operational voltage
Rated insulation voltageRated impulse withstand voltageUltimate breaking capacity(IEC, JIS, AS/NZS)
Service breaking capacity(IEC, JIS, AS/NZS)
Rated breaking capacity (NEMA)
Rated short-time withstand current
Protection
Adjustable thermal, adjustable magnetic (TMD)Fixed thermal, fixed magnetic (TMF)Microprocessor (LSI/LSIG)Utilisation category
Installation
Front connection (FC)Extension bar (FB)Cable clamp (FW)Rear connection (RC)Plug-in (PM)Draw-out (DR)DIN rail mounting (DA)Dimensions
Weight
Operation
Direct Opening ActionToggle operationDoor mounted (HS, HP) / Breaker mounted handle (HB)Motor operation (MC)
Endurance
Quantity
In
Ue
UiUimp
Icu
Ics
Icw
hw
dW
ElectricalMechanical
Unit
(A)
(V)
(V)(kV)(kA)
(kA)
(kA)
(kA)
(mm)(mm)
(mm)(kg)
cyclescycles
Condition
45°C
AC 50/60 HzDC
690V AC525V AC440V AC
400/415V AC220/240V AC
250V DC690V AC525V AC440V AC
400/415V AC220/240V AC
250V DC480V AC240VAC
0.3 Seconds
3 pole4 pole
3 pole4 pole
415V AC
S8003, 4NJ
630800
6906008008
20*304550855020*30455085503085-
■
A
-■
• (3)•••-
2732102801038.511.5
■
■
••
800
S8003, 4CJ
630800
6906008008
10*15*3036505010*15*303650501550-
■
A
-■
• (3)•••-
2732102801038.511.5
■
■
••
4,00010,000
*MCCB cannot be used in IT systems at this voltage.
SE
CT
ION
2
The Ultimate Safety Breaker page 20
RATINGS AND SPECIFICATIONS
S8003, 4RE
630800
690
8008
25*356570100
-20*30505075-
3510010
■
B
-■
• (3)•••-
273210280103(4)(5)
■
■
••
S8003, 4NE
630800
690
8008
20*30455085-
20*30455085-
308510
■
B
-■
• (3)•••-
273210280103(4)(5)
■
■
••
S8003, 4RJ
630800
6906008008
25*4565701005020*345050755045100
-
■
A
-■
• (3)•••-
2732102801038.511.5
■
■
••
H8003, 4NE
630800
690
8008
25*40125125150
-20*349494150
-4015010
■
B
-■
-•••-
273210280140(6)(7)
■
■
••
L8003, 4NE
630800
690
8008
25*45180200200
-20*34135150150
-4520010
■
B
-■
-•••-
273210280140(6)(7)
■
■
••
1000
S10003, 4SE
1000
690
8008
20*30455085-
15*23343865-
3085-
■
A
-■
-•---
27321028010311.014.8
■
■
••
S10003, 4NE
1000
690
8008
25*456570100
-20*34505075-
45100
-
■
A
-■
-•---
27321028010311.014.8
■
■
••
1250
S12503, 4SE
1250
690
8008
20*30455085-
15*23343865-
308515
■
B
-■
-•••-
37021028012019.825.0
■
■
••
S12503, 4NE
1250
690
8008
25*456570100
-20*34505075-
4510015
■
B
-■
-•••-
37021028012019.825.0
■
■
••
S12503, 4GE
1250
690
8008
45*6585
85 (1)125
-34*5065
65 (2)94-
6512515
■
B
-■
-•••-
37021028012019.825.0
■
■
••
1600
S16003, 4SE
1600
690
8008
20*30455085-
15*23343865-
308520
■
B
-•-■
-•-
37021028014027.035.0
■
■
••
S16003, 4NE
1600
690
8008
45*6585
85 (1)125
-34*5065
65 (2)94-
6512520
■
B
-•-■
-•-
37021028014027.035.0
■
■
••
4,00010,000
4,00010,000
2,0005,000
4,0005,000
(1) 100kA at 400V(2) 75kA at 400V(3) 630A only
(4) 8.7kg/630A, 9.1kg/800A(5) 11.9kg/630A, 12.3kg/800A(6) 13.3kg/630A, 14.8kg/800A(7) 16.8kg/630A, 18.8kg/800A
page 21 The Ultimate Safety Breaker
RATINGS AND SPECIFICATIONS
Standard • Optional - Not Available
SWITCH-DISCONNECTOR ELECTRICAL CHARACTERISTICS
TO IEC 60947-3, EN 60947-3, AS/NZS 60947-3Frame
ModelNumber of PolesType
Nominal current ratings
Electrical characteristics
Rated operational voltage
Rated insulation voltageRated impulse withstand voltageRated short-circuit making capacityRated short-time withstand currentUtilisation category to IEC 60947-3
Installation
Front connection (FC)Extension bar (FB)Cable clamp (FW)Rear connection (RC)Plug-in (PM)Draw-out (DR)DIN rail mounting (DA)Dimensions
Weight
Operation
Direct Opening ActionToggle operationDoor mounted (HS, HP) / Breaker mounted handle (HB)Motor operation (MC)Endurance
Quantity
Ie
Ue
UiUimp
IcmIcw
hw
dW
ElectricalMechanical
Unit
(A)
(V)
(V)(kV)
(kA peak)(kA rms)
(mm)(mm)
(mm)(kg)
cyclescycles
Condition
AC 50/60 HzDC
0.3 SecondsACDC
3 pole4 pole
3 pole4 pole
415V AC
160
S1603, 4NN
160
690600800863
AC-23ADC-22A
■
••••--
165105140681.51.9
■
■
••
10,00030,000
125
S1253, 4NN
125
6906008008
3.62
AC-23ADC-22A
■
••••-•
15590120681.11.4
■
■
••
30,00030,000
SE
CT
ION
2
The Ultimate Safety Breaker page 22
RATINGS AND SPECIFICATIONS
Contact us for details.
250
S2503, 4NN
250
690600800863
AC-23ADC-22A
■
••••--
165105140681.51.9
■
■
••
10,00030,000
400
S4003, 4NN
400
690600800895
AC-23ADC-22A
■
••••--
2601401851034.25.6
■
■
••
4,50015,000
630
S6303, 4NN
630
69060080089
5 (3)AC-23ADC-22A
■
•••
--
2601401851034.45.8
■
■
••
4,50015,000
1000
S10003, 4NN
1000
69060080081710
AC-23ADC-22A
-■
-•---
27321028010310.414.0
■
■
••
1250
S12503, 4NN
1250
69060080083215
AC-23ADC-22A
-■
-•••-
37021028012018.223.4
■
■
••
4,0005,000
1600
S16003, 4NN
1600
69060080084520
AC-23ADC-22A
-•-■
-•-
37021028014024.932.9
■
■
••
2,0005,000
800
S8003, 4NN
630800
69060080081710
AC-23ADC-22A
-■
-•••-
273210280103(1)(2)
■
■
••
4,00010,000
(1) 8.0kg/630A, 8.5kg/800A(2) 11.0kg/630A, 11.5kg/800A
(3) 7.6kA/0.1sec.
2
The plug-in MCCB is locked to the basewhen the toggle is ON. It cannot be removedunless the toggle is OFF or TRIPPED. The safety lock prevents a trip occurring asthe MCCB is being removed from the base.
SAFETY LOCK FOR PLUG-IN VERSIONS
Plug-in MCCB and base
Plug-in connection kit, including safety lock
SafetyLock
SE
CT
ION
3
The Ultimate Safety Breaker page 24
OPERATING CHARACTERISTICS
TEMBREAK 2
MOULDED CASE CIRCUIT BREAKERS16A TO 1600A
1. Welcome to TemBreak 2
2. Ratings and Specifications
3. Operating Characteristics
• Thermal Magnetic Protection 25
• Thermal Magnetic Time / Current Characteristics 28
• Electronic Protection
Standard type 36
With LCD 47
• Electronic Time / Current Characteristics
Standard type 40
With LCD 51
• Let-through Peak Current Characteristics 53
• Let-through Energy Characteristics 60
4. Application Data
5. Accessories
6. Installation
7. Dimensions
page 25 The Ultimate Safety Breaker
THERMAL MAGNETIC PROTECTION
TemBreak 2 MCCBs from 125A frame to 800A frame are available with thermal magnetic protectionunits.
3 Pole MCCB with Adjustable Thermal and Adjustable Magnetic Characteristics Single Pole MCCB with Fixed Characteristics
Models with Adjustable Thermal and Adjustable Magnetic Characteristics
All standard 3 pole and 4 pole TemBreak 2 thermal magnetic models have adjustable thermal andadjustable magnetic characteristics.
Traditionally, thermal magnetic MCCBs have had adjustable thermal with fixed magnetic characteristics.The fixed magnetic element can limit the application of the MCCB.
An adjustable magnetic characteristic allows short-circuit protection to be matched to the load and supply characteristics, for example motor inrush currents or generator short-circuit currents.Lowering the short-circuit tripping threshold can allow a higher earth-loop impedance in an installation and provide end-of-cable protection with the correct disconnection times.
Thermal Magnetic trip units are especially suited to the following applications:• Installations where harmonic distortion of current waveforms is likely.
They operate inherently on the root mean square (rms) heating effect of current.• DC circuits. Refer to Section 4, “The Application of MCCBs in DC Systems”
for more information.
OPERATING CHARACTERISTICS
SE
CT
ION
3
The Ultimate Safety Breaker page 26
1. IR is the thermal element adjustment dial and is used to set the rated current tomatch the conductor rating.
IR can be set between 0.63 and 1.0 times In.
2. Ii is the magnetic element adjustment dial and is used to set the short circuittripping threshold to suit the application.
THERMAL MAGNETIC PROTECTION
Adjustment Dials
Models, Types, Rated Currents and Magnetic trip currents of Thermal Elements
OPERATING CHARACTERISTICS
Model Type Rated current In (A) Magnetic trip current Ii (A)
S125 -NF16, 20, 25, 32, 40, 50, 63, 80, 100 13 xIn125 12.4 xIn
E125 -NJ20, 32, 50, 63, 100 6 – 12 xIn125 6 – 10 xIn
S125 -NJ20, 32, 50, 63, 100 6 – 12 xIn125 6 – 10 xIn
S125 -GJ20, 32, 50, 63, 100 6 – 12 xIn125 6 – 10 xIn
H125 -NJ 20, 32, 50, 63, 100, 125 6 - 12 xInL125 -NJ 20, 32, 50, 63, 100, 125 6 – 12 xInS160 -NF 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160 10 xIn
S160 -NJ20, 32, 50, 63, 100, 125 6 – 12 xIn160 6 – 13 xIn
S160 -GJ50, 63, 100, 125 6 – 12 xIn160 6 – 13 xIn
H160 -NJ 160 6 – 13 xInL160 -NJ 160 6 – 13 xIn
E250 -NJ20, 32, 50, 63, 100, 125 6 – 12 xIn160, 200 6 – 13 xIn250 6 – 10 xIn
S250 -NJ160, 200 6 – 13 xIn250 6 – 10 xIn
S250 -GJ160, 200 6 – 13 xIn250 6 – 10 xIn
H250 -NJ160 6 – 13 xIn250 (225A for Plug-in) 6 – 10 xIn
L250 -NJ160 6 – 13 xIn250 (225A for Plug-in) 6 – 10 xIn
E400 -NJ 250, 400 6 – 12 xInS400 -CJ 250, 400 6 – 12 xInS400 -NJ 250, 400 6 – 12 xInS400 -GJ 250, 400 6 – 12 xInS800 -CJ 630, 800 5 – 10 xInS800 -NJ 630, 800 5 – 10 xInS800 -RJ 630, 800 5 – 10 xIn
page 27 The Ultimate Safety Breaker
Neutral Pole Protection
Neutral pole protection is available as an optional extra on four pole thermal magnetic MCCBs.The thermal and magnetic elements in the neutral pole are related to those in the phase poles as follows:
Motor Protection
MCCBs feeding motors are often only required to provide protection from short-circuits. Overloadprotection is provided by a dedicated thermal or electronic overload relay. Tembreak 2 MCCBs withoutthermal protection elements are available for this application. Four pole MCCBs with magnetic trip onlyhave protection on the neutral pole as standard.
Single Pole MCCBs
Single pole models have fixed thermal and fixed magnetic characteristics.
Generator Protection
Generators may need specially modified protection characteristics, based on their short-circuit capability.
If a generator is capable of delivering short-circuit current greater than six times its full load current, a standard TemBreak 2 thermal magnetic MCCB may be used, with I i set at less than the available short-circuit current. (Note that MCCBs, with fixed magnetic characteristics may not be suitable for this application.)
A thermal magnetic MCCB with low instantaneous protection may be used where the generator short-circuit current is less than six times its full load current. These are modified versions of thestandard MCCB.
Four pole MCCBs with low instantaneous protection have protection on the neutral pole as standard.The magnetic characteristic of MCCBs with low instantaneous protection is fixed at the following values:
THERMAL MAGNETIC PROTECTION
OPERATING CHARACTERISTICS
Model Magnetic Trip Current
E125 3xIn
S125 3xIn
S160 3xIn
E250 3xIn
S250 3xIn
E400 3.5xIn
S400 3.5xIn
Phase Trip Threshold Neutral Trip Threshold
Thermal Ir (adjustable) IN (adjustable)= In
Magnetic Ii (adjustable) Ii (adjustable)
The Ultimate Safety Breaker page 28
SE
CT
ION
3
OPERATING CHARACTERISTICS
THERMAL MAGNETIC CHARACTERISTICS
Single Pole MCCBs
Max.
Min.
125A
16~100A
Time/current characteristic curves
S125-NFTime/current characteristic curves
S160-NF
page 29 The Ultimate Safety Breaker
OPERATING CHARACTERISTICS
THERMAL MAGNETIC CHARACTERISTICS
125A Frame
Time/current characteristic curves
E125-NJ, S125-NJ, S125-GJ
50-100A(max)
20-32A(max)
50-100A(min)
20-32A(min)
Adjustable setting rangeof magnetic trip
LO HI
20325063100
240±48384±77600±120756±1511200±240
Time/current characteristic curves
E125-NJ, S125-NJ, S125-GJ
125A(max)
125A(min)
Adjustable setting rangeof magnetic trip
LO HI
125 1250±250
The Ultimate Safety Breaker page 30
SE
CT
ION
3
OPERATING CHARACTERISTICS
THERMAL MAGNETIC CHARACTERISTICS
125A Frame
Time/current characteristic curves
H125-NJ, L125-NJ
page 31 The Ultimate Safety Breaker
OPERATING CHARACTERISTICS
THERMAL MAGNETIC CHARACTERISTICS
160A and 250A Frames
Time/current characteristic curves
S160-NJ, S160-GJ, E250-NJ, S250-NJ, S250-GJ
20-200A(max)
20-200A(min)
Time/current characteristic curves
E250-NJ, S250-NJ, S250-GJ
250A(max)
250A(min)
250 2500±500
SE
CT
ION
3
The Ultimate Safety Breaker page 32
✽ For Plug-in connection,Max. rating 225AIi=2925A±585A
OPERATING CHARACTERISTICS
THERMAL MAGNETIC CHARACTERISTICS
160A and 250A Frames
Time/current characteristic curves
H250-NJ, L250-NJTime/current characteristic curves
H160-NJ, H250-NJ, L160-NJ, L250-NJ
250A(max)
250A(min)
250✽ 2500±500
Magnetic trip currentfor Front connection and Rear connection
page 33 The Ultimate Safety Breaker
THERMAL MAGNETIC CHARACTERISTICS
400A Frame
OPERATING CHARACTERISTICS
Time/current characteristic curves
E400-NJ, S400-CJ, S400-NJ, S400-GJ, S400-PJ
SE
CT
ION
3
The Ultimate Safety Breaker page 34
THERMAL MAGNETIC CHARACTERISTICS
800A Frame
OPERATING CHARACTERISTICS
Time/current characteristic curves
S800-CJ, S800-NJ, S800-RJ
Ambient compensating curves
Percent Rated Current
Trip
ping
Tim
em
inut
ese
cond
hour
10080 90 125
150
250
200
300
400
500
600
700
800
900
1000
1500
2000
2500
3000
4000
5000
6000
7000
8000
0.005
0.010.0080.006
0.02
0.030.040.050.060.080.1
0.2
0.3
0.60.8
0.40.5
1
2
3
54
68
10
20
3040501
2
4
6
10
20
3040
1
2
34
3
5
8
50
Magnetic trip current
In(A)630
Ii(A)
6300±1260
630A(max.)
630A(min.)
Adjustable setting rangeof magnectic trip
LO HI
5
Cal
ibra
ted
Tem
pera
ture
85
95
105
115
125
135
145
15 25 35 45 55
Per
cent
cur
rent
rat
ing
(%)
Ambient Temperature (°C)
Calibrated at 45 °C
I n x 0.63
I n x 0.8
I n x 1.0
Time/current characteristic curves
S800-CJ, S800-NJ, S800-RJ
Ambient compensating curves
Percent Rated Current
Trip
ping
Tim
em
inut
ese
cond
hour
10080 90 125
150
250
200
300
400
500
600
700
800
900
1000
1500
2000
2500
3000
4000
5000
6000
7000
8000
0.005
0.010.0080.006
0.02
0.030.040.050.060.080.1
0.2
0.3
0.60.8
0.40.5
1
2
3
54
68
10
20
3040501
2
4
6
10
20
3040
1
2
34
3
5
8
50
Magnetic trip current
800 8000±1600
800A(max.)
LO HI
800A(min.)
Adjustable setting rangeof magnectic trip
In(A)
Ii(A)
5
Ambient Temperature (°C)
Calibrated at 45 °C
Cal
ibra
ted
Tem
pera
ture
85
95
105
115
125
135
145
15 25 35 45 55
Per
cent
cur
rent
rat
ing
(%)
I n x 0.63
I n x 0.8
I n x 1.0
page 35 The Ultimate Safety Breaker
MEMO
SE
CT
ION
3
The Ultimate Safety Breaker page 36
OPERATING CHARACTERISTICS
TemBreak 2 MCCBs from 250A frame to 1600A frame are available withelectronic protection units. Current ratings, In, of 40A, 125A, 160A, 250A, 400A,630A, 800A, 1000A, 1250A and 1600A are available. These offer great flexibilityas their characteristics can be set to suit a wide range of application conditions.Overload protection can be set between 0.4 and 1.0 times In.
Terasaki offer one of the most adaptable protection units on the market:
If you require a characteristic which is not available as a preset on our standardelectronic protection unit, send us the details and we will program a customisedcharacteristic to your specification.*
ELECTRONIC PROTECTION (STANDARD TYPE)
Every TemBreak 2 electronic protection unit includes overload protection (L),delayed short-circuit protection (S) and instantaneous protection (I) as standard.
*Characteristic is programmable within certain limits.Contact us for details.
Selecting a Preset Characteristic for a 400A TemBreak 2 MCCB with Electronic Protection
Electronic Protection Characteristic
page 37 The Ultimate Safety Breaker
OPERATING CHARACTERISTICS
Three optional functions are available:
Ground Fault Trip (G)
This function trips the MCCB after time delay, tg, if the ground fault current exceeds the presetthreshold, Ig. Ground fault protection can be enabled and disabled by operating a DIP switch onthe electronic protection unit. An external current transformer is available if the ground faulttrip function is required on a 3 pole MCCB, in a 3 phase, 4 wire system. The ground fault trip function is available from 400A to 1600A for In.
Neutral Protection (N)
Neutral protection trips the MCCB after time delay, tN, if current in the neutral conductorexceeds the rated current, In, of the MCCB. The time delay characteristic is identical to that of the overload characteristic (L).
Preferential Trip Alarm (P)
An LED and volt-free output contact are activated after a time delay, tp, if the load currentexceeds the preset threshold, Ip.
An OCR power supply is required for operation of the preferential trip alarm. This is mountedas shown below, either on the side of the breaker (250A and 400 to 1600A – standard), orremotely (400 to 1600A only – on request). Ratings, specifications and wiring arrangements areshown below. Dimensions of the OCR power supply for preferential trip alarm can be found inSection 7. Note that the breaker mounted terminal block is not compatible with the OCR powersupply for Front-Connected and Rear-Connected MCCBs described in Section 5, if the OCRpower supply is mounted on the right side of the breaker.
ELECTRONIC PROTECTION (STANDARD TYPE)Optional Functions
Rated Current of Output Contact
resistive load inductive load
250V AC 2A 2A
220V DC 2A 2A
OCR Power Supply Specifications
Voltage 200-240V AC
Rated Power 2VA
SE
CT
ION
3
The Ultimate Safety Breaker page 38
OPERATING CHARACTERISTICS
ELECTRONIC PROTECTION (STANDARD TYPE)
Available - Not Available
Optional Function
Poles
3
4
3
4
Code
APAPAN
APNAPAG
APGAPAN
APNAGN
APGN
Ground Fault (G)
-
-
-
-
-
-
-
-
Neutral Protection (N)
-
-
-
-
-
-
Preferential Trip Alarm (P)
-
-
-
-
How to Specify Optional Functions
Optional functions must be specified at the time of order. Descriptions for electronic MCCBsinclude a 1-4 digit alphabetic code after the type designation which details the combination ofoptional functions. For example:
S400-GE APG 3P 400A FC - includes preferential trip and ground fault trip.
The table below lists codes for all the optional functions currently available:
In
250
400
630
800
1000
1250
1600
MCCB ProtectionRelay
OCR powersupply for
preferrentislTrip Alarm
ControlPowerSupply
Terminals
OutputContactCables,
Pre-Wired
Connectionsfrom OCR
power supply toProtection Relay,
Pre-Wired
A
B
A. Connection Arrangement for Prefferential Trip Alarm withBreaker Mounted OCR power supply (Standard).
B. Connection Arrangement for Prefferential Trip Alarm withRemotely Mounted OCR power supply (On Request).
page 39 The Ultimate Safety Breaker
ELECTRONIC PROTECTION (STANDARD TYPE)Adjustment Dials
OPERATING CHARACTERISTICS
Tolerances of Characteristics
The left adjustment dial sets the rated current to match the conductor rating. The right adjustmentdial selects one of seven preset characteristics on 400A, 800A, 1250A and 1600A models, and one ofsix preset characteristics on 630A and 1000A models, and one of 5 preset characteristics on 250Amodel. The effects of the left adjustment dial (labelled IR(A)), and the right adjustment dial (labelledCharacteristics) are detailed in the tables shown underneath each time / current graph.
Characteristics Tolerance
Long Time DelayIR Tripping when (IR✕1.05) É load current Ö (IR✕1.25)
tR ± 20%
Short Time DelayIsd ± 15%
tsd Total clearing time +50ms, resettable time –20ms
Instantaneous Ii ± 20%
Preferential Trip AlarmIp ± 10%
tp ± 10%
Ground Fault TripIg ± 15%
tg Total clearing time +50ms, resettable time –20ms
Neutral Protection IN Tripping when (IN✕1.05) É load current Ö (IN✕1.3)
SE
CT
ION
3
The Ultimate Safety Breaker page 40
ELECTRONIC CHARACTERISTICS (STANDARD TYPE)
S250-NE, S250-GE, S250-PE, H250-NE
OPERATING CHARACTERISTICS
In = 250A; 160A; 125A; 40A Note(1)
LT
ST
PTA
NPOption
Standard
IR (A)LTD Pick-up current IR xIn 0.4 0.5 0.63 0.8 0.9 0.95 1.0
1Characteristics
Note(1) For Plug-in (PM), max. setting for IR should be less than 225A. When In=250A, IR should be In✕0.9 or less.(2) Ii max. = 13 x In. (3) Characteristic of neutral protection (tN vs. IN) is identical to characteristic of phase protection (tR vs. IR).
No. 2 4 511
2.5 5 100.20.1
14(Max: 13 x In) Note (2)
0.840
1.0 Note (3)
tN = tRtN
IN
tpIp
Ii
tsd
Isd xIR
xIRxIR
xIR
(s)
(s)
(s)
tR (s)at 200% x IR at 600% x IR
21 21 5 7.5
INST
3
page 41 The Ultimate Safety Breaker
ELECTRONIC CHARACTERISTICS (STANDARD TYPE)
S400-NE, S400-GE, S400-PE, H400-NE, L400-NE
Percent Rated Current IRPercent Rated
Current In
LT
ST
PTA
NP
Option
Standard
IR (A)LTD Pick-up current IR xIn 0.4 0.5 0.63 0.8 0.9 0.95 1.0
1Characteristics
Note(1) GF is not available when In is 250A. (2) Ii max. = 13 x In. (3) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN)is identical to characteristic of phase protection (tR vs. IR). (4) When you specify GF on MCCBs with 3 poles the terminal block is automatically fittedto connect with the external neutral CT for 3 phases 4 wires system. See terminal blocks in section 7. GF is not available for 250A IN.
No. 2 3 4 5 6 711
2.5 5 100.20.1
14(Max: 13 x In) Note (2)0.840
1.0/0.5 Note(3)
tN=tRtN
IN
tpIpIi
tsd
Isd xIR
xIRxIR
xIR
(s)
(s)
GFNote(4)
0.2
0.2tg
Ig xIn(s)
(s)
tR (s)at 200% x IR at 600% x IR
21 21 5 10 19 29
INST
In = 400A; 250A Note(1)
OPERATING CHARACTERISTICS
SE
CT
ION
3
The Ultimate Safety Breaker page 42
0.005
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
1
2
4
6
10
20
30
40
1
2
4
6
10
20
3040
1
2
3
Trip
ping
Tim
e
seco
ndm
inut
eho
ur
100
125
200
300
400
500
600
1000
1500
2000
3000
4000
5000
8000805040302010
Ii
IRIp
Ig Isd
tsd
tp
tg
tR
I
T
Percent Rated Current IRPercent Rated
Current In
ELECTRONIC CHARACTERISTICS (STANDARD TYPE)
E630-NE, S630-CE, S630-GE
In = 630A
LT
ST
PTA
NP
Option
Standard
IR (A)LTD Pick-up current IR xIn 0.4 0.5 0.63 0.8 0.85 0.95 1.0
1Characteristics
Note(1) Ii max. = 10 x In. (2) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN) is identical to characteristic ofphase protection (tR vs. IR). (3) When you specify GF on MCCBs with 3 poles the terminal block is automatically fitted to connect withthe external neutral CT for 3 phases 4 wires system. See terminal blocks in section 7.
No. 2 3 4 5 611
2.5 5 80.20.1
14(Max: 10 x In) Note (1)0.840
1.0/0.5 Note(2)
tN=tRtN
IN
tpIpIi
tsd
Isd xIR
xIRxIR
xIR
(s)
(s)
GFNote(3)
0.2
0.2tg
Ig xIn(s)
(s)
tR (s)at 200% x IR at 600% x IR
21 21 5 10
0.9
16
INST
OPERATING CHARACTERISTICS
page 43 The Ultimate Safety Breakerpage 43 The Ultimate Safety Breaker
ELECTRONIC CHARACTERISTICS (STANDARD TYPE)
S800-NE, S800-RE, H800-NE, L800-NE
Percent Rated Current IRPercent Rated
Current In
LT
ST
PTA
NP
Option
Standard
IR (A)LTD Pick-up current IR xIn 0.4 0.5 0.63 0.8 0.9 0.95 1.0
1Characteristics
Note(1) Ii max. = 12 x In. (2) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN) is identical to characteristic of phaseprotection (tR vs. IR). (3) When you specify GF on MCCBs with 3 poles the terminal block is automatically fitted to connect with the external neutralCT for 3 phases 4 wires system. See terminal blocks in section 7.
No. 2 3 4 5 6 711
2.5 5 100.20.1
14(Max: 12 x In) Note (1)0.840
1.0/0.5 Note(2)
tN=tRtN
IN
tpIpIi
tsd
Isd xIR
xIRxIR
xIR
(s)
(s)
GFNote(3)
0.2
0.2tg
Ig xIn(s)
(s)
tR (s)at 200% x IR at 600% x IR
21 21 5 10 19 29
INST
In = 800A; 630A
OPERATING CHARACTERISTICS
SE
CT
ION
3
The Ultimate Safety Breaker page 44The Ultimate Safety Breaker page 44
0.005
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
1
2
4
6
10
20
30
40
1
2
4
6
10
20
3040
1
2
3
Trip
ping
Tim
e
seco
ndm
inut
eho
ur
100
125
200
300
400
500
600
1000
1500
2000
3000
4000
5000
8000805040302010
Ii
IRIp
Ig Isd
tsd
tp
tg
tR
I
T
Percent Rated Current IRPercent Rated
Current In
ELECTRONIC CHARACTERISTICS (STANDARD TYPE)
S1000-SE, S1000-NE
In = 1000A
LT
ST
PTA
NP
Option
Standard
IR (A)LTD Pick-up current IR xIn 0.4 0.5 0.63 0.8 0.95 1.0
1Characteristics
Note(1) Ii max. = 10 x In. (2) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN) is identical to characteristic ofphase protection (tR vs. IR). (3) When you specify GF on MCCBs with 3 poles the terminal block is automatically fitted to connect withthe external neutral CT for 3 phases 4 wires system. See terminal blocks in section 7.
No. 2 3 4 5 611
2.5 5 80.20.1
14(Max: 10 x In) Note (1)0.840
1.0/0.5 Note(2)
tN=tRtN
IN
tpIpIi
tsd
Isd xIR
xIRxIR
xIR
(s)
(s)
GFNote(3)
0.2
0.2tg
Ig xIn(s)
(s)
tR (s)at 200% x IR at 600% x IR
21 21 5 10
0.9
16
INST
OPERATING CHARACTERISTICS
page 45 The Ultimate Safety Breakerpage 45 The Ultimate Safety Breaker
OPERATING CHARACTERISTICS
ELECTRONIC CHARACTERISTICS (STANDARD TYPE)
S1250-SE, S1250-NE, S1250-GE
Percent Rated Current IRPercent Rated
Current In
LT
ST
PTA
NP
Option
Standard
IR (A)LTD Pick-up current IR xIn
1Characteristics
Note(1) Ii max. = 12 x In. (2) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN) is identical to characteristic of phaseprotection (tR vs. IR). (3) When you specify GF on MCCBs with 3 poles the terminal block is automatically fitted to connect with the external neutralCT for 3 phases 4 wires system. See terminal blocks in section 7.
No. 2 3 4 5 6 711
2.5 5 100.20.1
14(Max: 12 x In) Note (1)0.840
1.0/0.5 Note(2)
tN=tRtN
IN
tpIpIi
tsd
Isd xIR
xIRxIR
xIR
(s)
(s)
GFNote(3)
0.2
0.2tg
Ig xIn(s)
(s)
tR (s)at 200% x IR at 600% x IR
21 21 5 10 19 29
INST
In = 1250A
0.4 0.5 0.63 0.8 0.9 0.95 1.0
SE
CT
ION
3
The Ultimate Safety Breaker page 46The Ultimate Safety Breaker page 46
OPERATING CHARACTERISTICS
Percent Rated Current IRPercent Rated
Current In
Note(1) Ii max. = 12 x In. (2) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN) is identical to characteristic of phaseprotection (tR vs. IR). (3) When you specify GF on MCCBs with 3 poles the terminal block is automatically fitted to connect with the external neutralCT for 3 phases 4 wires system. See terminal blocks in section 7.
In = 1600A
ELECTRONIC CHARACTERISTICS (STANDARD TYPE)
S1600-SE, S1600-NE
LT
ST
PTA
NP
Option
Standard
IR (A)LTD Pick-up current IR xIn
1Characteristics No. 2 3 4 5 6 711
2.5 5 100.20.1
14(Max: 12 x In) Note (1)0.840
1.0/0.5 Note(2)
tN=tRtN
IN
tpIpIi
tsd
Isd xIR
xIRxIR
xIR
(s)
(s)
GFNote(3)
0.2
0.2tg
Ig xIn(s)
(s)
tR (s)at 200% x IR at 600% x IR
21 21 5 10 19 29
INST
0.4 0.5 0.63 0.8 0.9 0.95 1.0
page 47 The Ultimate Safety Breaker
OPERATING CHARACTERISTICS
ELECTRONIC PROTECTION (WITH LCD)
The TemBreak2 enhanced electronic breaker withintegrated VT and CT monitors the current,voltage, instantaneous electrical power, integratedelectrical energy and power factor of a circuit anddisplays their values on the LCD on the front ofthe breaker. This breaker using the Modbusprotocol allows data such as measured values andevent/fault logs to be transmitted to an externaldevice.
¡The LCD window provides the phase currents,line voltages (and their maximum values), powerfactor, electrical power and electrical energy. Itcan also provide the 1st to 19th harmoniccurrents for each phase.
¡When a fault occurs, the cause of the fault andthe fault current are indicated on the LCD. Datain memory is stored even if the power is lost. Youcan view event or fault logs after the power isrestored.
Appearance
Panel cutout
Handle frame
LCD window
The LCD window isequal to the handleframe in width; thepanel cutout can bemade easily.
SE
CT
ION
3
The Ultimate Safety Breaker page 48
OPERATING CHARACTERISTICS
ELECTRONIC PROTECTION (WITH LCD)
¡The breaker is available in three LCD orientations corresponding to the installation orientations of the breaker.
Vertical (move the handle up to ON)(Standard orientation)
Horizontal (move the handle right to ON) Horizontal (move the handle left to ON)
If the breaker is installed in a horizontal orientation, please specify "Horizontal (move the handle right to ON)"or "Horizontal (move the handle left to ON)" when ordering. Otherwise the standard orientation "Vertical (movethe handle up to ON)" will apply.
OCR Power Supply for Electronic Protection with LCDThe XOW OCR, protection relays, requires control power.The OCR power supply is installed on the right side of the breaker as standard. This can also be installedseparately to the breaker. Please specify when ordering.
Note q: When the OCR power supply is installed on the right side of the breaker, the breaker cannot be equipped with a terminal block for connection to theshunt trip device and under voltage trip device.
¡Specifications of OCR power supply
Note w: The permissible range of the control voltage is 85 to 110% of the rated voltage.Please specify the rated voltage when ordering.
Dimensions of the OCR power supply can be found in Section 7.
Control voltage Note w 100 – 120 VAC or 200 – 240 VAC(Rated voltage)Current consumption 2VA
page 49 The Ultimate Safety Breaker
OPERATING CHARACTERISTICS
ELECTRONIC PROTECTION (WITH LCD)
Available types
Type of OCR
Protective function Alarm function Display
Long time-delay trip Short time-delay tripInstantaneous trip
Ground fault trip N-phase protectionPhase rotation
protectionPre-trip alarm LCD window LCD backlight
A GF NP NS PTA
XOW-1L-A ● — — — — ● —
XOW-1L-AGN ● ● ● — — ● —
XOW-1L-AP ● — — — ● ● —
XOW-1L-APGNS ● ● ● ● ● ● —
XOW-1L-APC ● — — — ● ● —
XOW-1L-APGNSC ● ● ● ● ● ● —
XOW-1S-A ● — — — — ● ●
XOW-1S-AGN ● ● ● — — ● ●
XOW-1S-AP ● — — — ● ● ●
XOW-1S-APGNS ● ● ● ● ● ● ●
XOW-1S-APCWH ● — — — ● ● ●
XOW-1S-APGNSCWH ● ● ● ● ● ● ●
● : Standard equipment● : Optional— : Not applicable
Measurement/event indication function specifications
Measurement/event (accuracy)Modbus communication function
● : Yes —: Non Note
Load current(±1.5%)
Present value for each phase ●Ground fault current and negative-phase current can bedisplayed depending on the specifications.
Present max value ●Among L1, L2, L3 phases, the phase having the highestcurrent is subject to measurement and the value of thecurrent is displayed.
Line voltage(±1.0%)
Present value of each line voltage ●
Present max value ●
Present phase voltage value for each phase ● Applies to 4-pole breakers only.
Harmoniccurrent (±2.5%)
Present value of 3rd, 5th, 7th, ...19thharmonic current for each phase
—
Electrical power(±2.5%)
Present value ●
Demand value ●
Max demand value ●
Electrical energy(±2.5%)
Electrical energy ●
Power factor(±5%)
Present value ●
Trip event logFault current (±1.5%) ●
Indication of cause ●
Alarm event log Cause of alarm, Indication of operated value ●
Note: Electrical energy is stored every hour and the fault current and cause of fault are stored every time a fault occurs in a flash memory.
SE
CT
ION
3
The Ultimate Safety Breaker page 50
OPERATING CHARACTERISTICS
ELECTRONIC PROTECTION (WITH LCD)
Measurement/event indication
Communicationfunction
Externalindicator
Test functionIndication viaoutput contact
Control powersupplyCurrent
Voltage,electrical power,electrical energy,power factor,demandelectrical power
Electricalenergy pulse
Harmoniccurrent
Trip event log Alarm event log
W H C I Y
● — — — ● ● — — ● — Required
● — — — ● ● — — ● — Required
● — — — ● ● — — ● ● Required
● — — — ● ● — — ● ● Required
● — — — ● ● ● — ● ● Required
● — — — ● ● ● — ● ● Required
● ● — — ● ● — — ● — Required
● ● — — ● ● — — ● — Required
● ● — — ● ● — — ● ● Required
● ● — — ● ● — — ● ● Required
● ● ● ● ● ● ● ● ● ● Required
● ● ● ● ● ● ● ● ● ● Required
Network interface I/O specificationsItem Modbus line
Communication protocol RS-485
Communication mode 2-wire, half-duplex
Topology Multi-drop bus
Transmission rate 19.2 kbps max
Transmission distance 1.2 km max (at 19.2 kbps)
Data format Modbus-RTU
Max number of nodes 1–31
page 51 The Ultimate Safety Breaker
OPERATING CHARACTERISTICS
ELECTRONIC CHARACTERISTICS (WITH LCD)
Specifications of over-current releaseApplicable MCCB type CT rated primary current ICT
S400-NE, S400-GE, S400-PE,H400-NE, L400-NE
250A400A
E630-NE, S630-CE, S630-GE 630AS800-NE, S800-RE, H800NE, L800-NE
630A800A
S1000-SE, S1000-NE 1000A
Note q: For E630, S630, S1000, (0.5-1.25-2.5-5-10-15-16)sec.w: For E630, S630, S1000, [In] x (1-1.5-2-2.5-3-4-6-8-NON).e: The max. pick-up current is set to 1300% x [ICT] for S400, H400 and L400, 1000% x [ICT] for E630, S630 and S1000,
1200% x [ICT] for S800, H800 and L800.r: When the short time delay trip function has been set to NON, the instantaneous trip function cannot be set to NON. When the instantaneous trip
function has been set to NON, the short time delay trip function cannot be set to NON.t: Selecting "OFF" disables protective functions.
Unless otherwise specified when ordering, the settings will default to those underlined in the table above.
Protective function Symbol Setting range
Rated current (A) In [ICT] x (0.5-0.63-0.8-1.0)
Long time-delay tripLT
Pick-up current (A) IR [In] x (0.8-0.85-0.9-0.95-1.0)• Non tripping at not more than [IR] x 1.05• Tripping at more than [IR] x 1.05 and not more than [IR] x 1.2
Time-delay (s) tR (0.5-1.25-2.5-5-10-15-20-25-30) (sec) at 600% of [IR] qTime-delay setting tolerance: ±20%, +0.13s –0s
COLD/HOT — COLD/HOT
Short time-delay tripST
Pick-up current (A) Isd [In] x (1-1.5-2-2.5-3-4-6-8-10-NON) wCurrent setting tolerance: ±15%
Time-delay (s) tsd I2t OFF: 0.05-0.1-0.2-0.3s (Definite time characteristic)I2t ON: 0.05-0.1-0.2-0.3s (Ramp characteristic at less than 1000% of [In],Definite time characteristic at 1000% or more of [In])
I2t ramp characteristic — OFF/ON
Instantaneous tripINST
Pick-up current (A) Ii [In] x (2-3-4-6-8-10-12-13-14-NON) er
Current setting tolerance: ±20%
Ground fault tripGF
Pick-up current (A) Ig [ICT] x (0.2-0.3-0.4-NON) Current setting tolerance: ±20%
Time-delay (s) tg I2t OFF: 0.1-0.2-0.3-0.4-0.8s (Definite time characteristic)Time-delay setting tolerance: +50ms –20msI2t ON: 0.1-0.2-0.3-0.4-0.8s (Ramp characteristic at less than 40% of [ICT], Definite time characteristic at 40% or more of [ICT])Time-delay setting tolerance: ±15%, +50ms –20ms
I2t ramp characteristic — OFF/ON
Mode — TRIP/OFF t
N-phase protectionNP
Pick-up current (A) IN [ICT] x (0.4-0.5-0.63-0.8-1.0-NON)• Non tripping at not more than [IN] x 1.05• Tripping at more than [IN] x 1.05 and not more than [IN] x 1.2
Time-delay (s) tN Tripping at 600% of [IN] with LT time-delay [tR].
COLD/HOT — COLD/HOT
Phase rotation protectionNS
Pick-up current (A) INS [In] x (0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0)Current setting tolerance: ±10%
Time-delay (s) tNS (0.4-0.8-1.2-1.6-2.0-2.4-2.8-3.2-3.6-4.0) (sec) at 150% of [INS]Time-delay setting tolerance: ±20%, +0.13s –0s
Mode — TRIP/OFF t
Pre-trip alarmPTA
Pick-up current (A) IP [In] x (0.7-0.8-0.9-1.0)Current setting tolerance: ±10%
Time-delay (s) tP 5-10-15-20-40-60-80-120-160-200s more than [IP]Time-delay setting tolerance: ±10%, +0.1s –0s
Mode — AL/OFF t
SE
CT
ION
3
The Ultimate Safety Breaker page 52
OPERATING CHARACTERISTICS
ELECTRONIC CHARACTERISTICS (WITH LCD)
Long time-delay and instantaneous trip3
2
10
1
0.1
0.01
100
150
30
20
10
5
3
2
1
600
1000
1000
0
Trip
ping
tim
e
hour
min
ute
seco
nd
% of rated current [In]
125
COLD start curve
75% HOT start curve
Short time-delay trip3
2
150
30
20
10
5
3
2
1
10
1
0.1
0.01
100010010
Trip
ping
tim
e
hour
min
ute
seco
nd
% of rated current [In]
I2t OFF
I2t ON
N-phase protection and ground fault trip
10
1
0.1
0.01
3
2
150
30
20
10
5
3
2
1
100010010
Trip
ping
tim
e
hour
min
ute
seco
nd
% of CT rated primary current [ICT]
125
I2t ON
I2t OFF
COLD start curve
75% HOT start curve
Phase rotation protection and pre-trip alarm3
2
150
30
20
10
5
3
2
1
10
1
0.1
0.01
100010010
Trip
ping
tim
e
hour
min
ute
seco
nd
% of rated current [In]
page 53 The Ultimate Safety Breaker
LET-THROUGH PEAK CURRENT CHARACTERISTICS
S125-NF. 240V AC S160-NF. 240V AC.
E125-NJ, S125-NJ, S125-GJ. 440V AC. S125-NJ, S125-GJ. 690V AC.
OPERATING CHARACTERISTICS
SE
CT
ION
3
The Ultimate Safety Breaker page 54
LET-THROUGH PEAK CURRENT CHARACTERISTICS
H125-NJ, L125-NJ. 690V ACH125-NJ, L125-NJ. 440V AC.
S160-NJ, S160-GJ, E250-NJ, S250-NJ, S250-GJ. 440V AC. S160-NJ, S160-GJ, S250-NJ, S250-GJ. 690V AC.
OPERATING CHARACTERISTICS
page 55 The Ultimate Safety Breaker
LET-THROUGH PEAK CURRENT CHARACTERISTICS
c
S250-NE…up to 36kA/380-415V, 25kA/440V
S250-GE…up to 65kA/380-415V, 50kA/440V
S250-NE, S250-GE(250A)
S250-PE, H250-NE(250A)
3 380V AC, 415V AC, 440V AC
S250-NE, S250-GE…up to 7.5kA
S250-NE, S250-GE(250A)
S250-PE, H250-NE(250A)
70S400-PJ, S400-PE --- up to 85kAS400-GJ, S400-GE --- up to 70kA
S400-CJ...up to 15kAS400-NJ, S400-NE, S400-GJ, S400-GE, S400-PJ, S400-PE...up to 20kA
H160-NJ, L160-NJ, S250-NE, S250-GE, S250-PE, H250-NJ, H250-NE, L250-NJ. 690V AC.
H160-NJ, L160-NJ, S250-NE, S250-GE, S250-PE, H250-NJ, H250-NE, L250-NJ. 440V AC.
E400-NJ, S400-CJ, S400-NJ, S400-NE, S400-GJ, S400-GE, S400-PJ, S400-PE. 415V AC.
S400-CJ, S400-NJ, S400-NE, S400-GJ, S400-GE, S400-PJ, S400-PE. 690V AC.
OPERATING CHARACTERISTICS
SE
CT
ION
3
The Ultimate Safety Breaker page 56
LET-THROUGH PEAK CURRENT CHARACTERISTICS
H400-NE, L400-NE. 415V AC.
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
50
30
20
10
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
50
30
20
10
E630-NE, S630-CE, S630-GE. 415V AC.
E630-NE, S630-CE, S630-GE. 690V AC.
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through peak currentM5261
S800-CJ ... up to 36kA
S800-NJ ... up to 50kA
S800-RJ ... up to 70kA
S800-CJ, S800-NJ, S800-RJ. 415V AC.
OPERATING CHARACTERISTICS
page 57 The Ultimate Safety Breaker
LET-THROUGH PEAK CURRENT CHARACTERISTICS
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through peak currentM5262
S800-NE ... up to 20kA
S800-RE ... up to 25kA
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through peak currentM5253
H800-NE ... up to 125kA
L800-NE ... up to 200kA
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through peak currentM5262
S800-NJ ... up to 20kA
S800-RJ ... up to 25kA
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through peak currentM5261
S800-NE ... up to 50kA
S800-RE ... up to 70kA
S800-NE, S800-RE. 415V AC.
S800-NE, S800-RE. 690V AC. H800-NE, L800-NE. 415V AC.
OPERATING CHARACTERISTICS
S800-NJ, S800-RJ. 690V AC.
SE
CT
ION
3
The Ultimate Safety Breaker page 58
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through peak currentM5262
S1000-SE ... up to 20kA
S1000-NE ... up to 25kA
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through peak currentM5251
S1250-SE ... up to 50kA
S1250-NE ... up to 70kA
S1250-GE ... up to 85kA
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through peak currentM5254
H800-NE, L800-NE ... up to 25kA
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through peak currentM5261
S1000-SE ... up to 50kA
S1000-NE ... up to 70kA
LET-THROUGH PEAK CURRENT CHARACTERISTICS
S1000-SE, S1000-NE. 415V AC.
S1000-SE, S1000-NE. 690V AC. S1250-SE, S1250-NE, S1250-GE. 415V AC.
OPERATING CHARACTERISTICS
H800-NE, L800-NE. 690V AC.
LET-THROUGH PEAK CURRENT CHARACTERISTICS
S1600-SE, S1600-NE. 415V AC.S1250-SE, S1250-NE, S1250-GE. 690V AC.
S1600-SE, S1600-NE. 690V AC.
OPERATING CHARACTERISTICS
page 59 The Ultimate Safety Breaker
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through peak currentM5252
S1250-SE ... up to 20kA
S1250-NE ... up to 25kA
S1250-GE ... up to 45kA
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through peak currentM5251
S1600-SE ... up to 50kA
S1600-NE ... up to 85kA
300
200
100
5
3
2
1
0.5
Max
. Let
-th
rou
gh
pea
k cu
rren
t(kA
)
0.3
0.2
2 3 5 10 20 30 50 100 200 300
50
30
20
10
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through peak currentM5252
S1600-SE ... up to 20kA
S1600-NE ... up to 45kA
SE
CT
ION
3
The Ultimate Safety Breaker page 60
LET-THROUGH ENERGY CHARACTERISTICS
1 240VAC
S160-NF. 240V ACS125-NF. 240V AC
E125-NJ, S125-NJ, S125-GJ. 440V AC. S125-NJ, S125-GJ. 690V AC.
OPERATING CHARACTERISTICS
page 61 The Ultimate Safety Breaker
LET-THROUGH ENERGY CHARACTERISTICS
H125-NJ, L125-NJ. 690V ACH125-NJ, L125-NJ. 440V AC.
S160-NJ, S160-GJ, E250-NJ, S250-NJ, S250-GJ. 440V AC.
S160-NJ, S160-GJ, S250-NJ, S250-GJ. 690V AC.
OPERATING CHARACTERISTICS
SE
CT
ION
3
The Ultimate Safety Breaker page 62
OPERATING CHARACTERISTICS
S250-PE...up to 70kA/380-415V, 50kA/440V
S250-NE…up to 36kA/380-415V, 25kA/440V
S250-GE…up to 65kA/380-415V, 50kA/440V
S250-NE, S250-GE(250A)
S250-PE, H250-NE(250A)
S250-NE, S250-GE…up to 7.5kA
S250-NE, S250-GE(250A)
S250-PE, H250-NE(250A)
S400-GJ, S400-GE ...up to 70kAS400-PJ, S400-PE ...up to 85kA
H160-NJ, L160-NJ,S250-NE, S250-GE, S250-PE, H250-NE, H250-NJ, L250-NJ. 690V AC.
H160-NJ, L160-NJ, S250-NE, S250-GE, S250-PE, H250-NE, H250-NJ, L250-NJ. 440V AC.
E400-NJ, S400-CJ, S400-NJ, S400-NE, S400-GJ, S400-GE, S400-PJ, S400-PE. 415V AC.
S400-CJ...up to 15kAS400-NJ, S400-NE, S400-GJ, S400-GE, S400-PJ, S400-PE...up to 20kA
S400-CJ, S400-NJ, S400-NE, S400-GJ, S400-GE, S400-PJ, S400-PE. 690V AC.
LET-THROUGH ENERGY CHARACTERISTICS
page 63 The Ultimate Safety Breaker
OPERATING CHARACTERISTICS
LET-THROUGH ENERGY CHARACTERISTICS
E630-NE, S630-CE, S630-GE. 415V AC.H400-NE, L400-NE. 415V AC.
E630-NE, S630-CE, S630-GE. 690V AC.
30
20
10
0.5
0.3
0.2
0.1
0.05
Max
. Let
-th
rou
gh
En
erg
y (I2 t
) (✕
106 A
2 sec
)
0.03
0.02
2 3 5 10 20 30 50 100 200 300
5
3
2
1
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through energy (I2t)M5263
S800-CJ ... up to 36kA
S800-NJ ... up to 50kA
S800-RJ ... up to 70kA
S800-CJ, S800-NJ, S800-RJ. 415V AC.
SE
CT
ION
3
The Ultimate Safety Breaker page 64
LET-THROUGH ENERGY CHARACTERISTICS
OPERATING CHARACTERISTICS
30
20
10
0.5
0.3
0.2
0.1
0.05
Max
. Let
-th
rou
gh
En
erg
y (I2 t
) (✕
106 A
2 sec
)
0.03
0.02
2 3 5 10 20 30 50 100 200 300
5
3
2
1
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through energy (I2t)M5264
S800-NE ... up to 20kA
S800-RE ... up to 25kA
30
20
10
0.5
0.3
0.2
0.1
0.05
Max
. Let
-th
rou
gh
En
erg
y (I2 t
) (✕
106 A
2 sec
)
0.03
0.02
2 3 5 10 20 30 50 100 200 300
5
3
2
1
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through energy (I2t)M5255
H800-NE ... up to 125kA
L800-NE ... up to 200kA
30
20
10
0.5
0.3
0.2
0.1
0.05
Max
. Let
-th
rou
gh
En
erg
y (I2 t
) (✕
106 A
2 sec
)
0.03
0.02
2 3 5 10 20 30 50 100 200 300
5
3
2
1
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through energy (I2t)M5264
S800-NJ ... up to 20kA
S800-RJ ... up to 25kA
30
20
10
0.5
0.3
0.2
0.1
0.05
Max
. Let
-th
rou
gh
En
erg
y (I2 t
) (✕
106 A
2 sec
)
0.03
0.02
2 3 5 10 20 30 50 100 200 300
5
3
2
1
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through energy (I2t)M5263
S800-NE ... up to 50kA
S800-RE ... up to 70kA
S800-NE, S800-RE. 415V AC.
S800-NE, S800-RE. 690V AC. H800-NE, L800-NE. 415V AC.
S800-NJ, S800-RJ. 690V AC.
page 65 The Ultimate Safety Breaker
LET-THROUGH ENERGY CHARACTERISTICS
S1000-SE, S1000-NE. 415V AC.
S1000-SE, S1000-NE. 690V AC. S1250-SE, S1250-NE, S1250-GE. 415V AC.
OPERATING CHARACTERISTICS
H800-NE, L800-NE. 690V AC.
30
20
10
0.5
0.3
0.2
0.1
0.05
Max
. Let
-th
rou
gh
En
erg
y (I2 t
) (✕
106 A
2 sec
)
0.03
0.02
2 3 5 10 20 30 50 100 200 300
5
3
2
1
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through energy (I2t)M5256
H800-NE, L800-NE ... up to 25kA
30
20
10
0.5
0.3
0.2
0.1
0.05
Max
. Let
-th
rou
gh
En
erg
y (I2 t
) (✕
106 A
2 sec
)
0.03
0.02
2 3 5 10 20 30 50 100 200 300
5
3
2
1
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through energy (I2t)M5263
S1000-SE ... up to 50kA
S1000-NE ... up to 70kA
30
20
10
0.5
0.3
0.2
0.1
0.05
Max
. Let
-th
rou
gh
En
erg
y (I2 t
) (✕
106 A
2 sec
)
0.03
0.02
2 3 5 10 20 30 50 100 200 300
5
3
2
1
Prospective short circuit current in RMS sym. (kA)
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through energy (I2t)M5264
S1000-SE ... up to 20kA
S1000-NE ... up to 25kA
Max
. Let
-th
rou
gh
En
erg
y (I2 t
) (✕
106 A
2 sec
)
2 3 5 10 20 30 50 100 200 300
Prospective short circuit current in RMS sym. (kA)
300
200
100
5
3
2
1
0.5
0.3
0.2
50
30
20
10
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through energy (I2t)M5249
S1250-SE ... up to 50kA
S1250-NE ... up to 70kA
S1250-GE ... up to 85kA
SE
CT
ION
3
The Ultimate Safety Breaker page 66
S1600-SE, S1600-NE. 690V AC.
OPERATING CHARACTERISTICS
LET-THROUGH ENERGY CHARACTERISTICS
S1600-SE, S1600-NE. 415V AC.S1250-SE, S1250-NE, S1250-GE. 690V AC.
Max
. Let
-th
rou
gh
En
erg
y (I2 t
) (✕
106 A
2 sec
)
2 3 5 10 20 30 50 100 200 300
Prospective short circuit current in RMS sym. (kA)
300
200
100
5
3
2
1
0.5
0.3
0.2
50
30
20
10
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through energy (I2t)M5250
S1250-SE ... up to 20kA
S1250-NE ... up to 25kA
S1250-GE ... up to 45kAM
ax. L
et-t
hro
ug
h E
ner
gy
(I2 t) (
✕10
6 A2 s
ec)
2 3 5 10 20 30 50 100 200 300
Prospective short circuit current in RMS sym. (kA)
300
200
100
5
3
2
1
0.5
0.3
0.2
50
30
20
10
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø415VACMax.Let-through energy (I2t)M5249
S1600-SE ... up to 50kA
S1600-NE ... up to 85kA
Max
. Let
-th
rou
gh
En
erg
y (I2 t
) (✕
106 A
2 sec
)
2 3 5 10 20 30 50 100 200 300
Prospective short circuit current in RMS sym. (kA)
300
200
100
5
3
2
1
0.5
0.3
0.2
50
30
20
10
Range:Voltage:Curve Type:Drawing N0:
Tembreak 23ø690VACMax.Let-through energy (I2t)M5250
S1600-SE ... up to 20kA
S1600-NE ... up to 45kA
3
Door cutout patterns for handles are symmetrical, even when breakersare mounted in opposite directions.
SYMMETRICAL DOOR CUTOUTPATTERNS
Using TemBreak 2 Operating Handles Using other MCCB Operating Handles
SE
CT
ION
4
The Ultimate Safety Breaker page 68
APPLICATION DATA
TEMBREAK 2 MOULDED CASE CIRCUIT BREAKERS
16A TO 1600A
1. Welcome to TemBreak 2
2. Ratings and Specifications
3. Operating Characteristics
4. Application Data
• What is Discrimination? 69
• How to Read the Discrimination Tables 70
• Discrimination Tables 71
• What is Cascading? 74
• How to Read the Cascade Tables 75
• Cascade Tables 76
5. Accessories
6. Installation
7. Dimensions
page 69 The Ultimate Safety Breaker
APPLICATION DATA
WHAT IS DISCRIMINATION?Discrimination, also called selectivity, is the co-ordination of protective devices such that a fault is cleared by the protective device installed immediately upstream of the fault, and by that device alone.
Total discrimination
Discrimination is said to be total if the downstream circuit breaker opens and the upstream circuit breaker remains closed. This ensures maximumavailability of the system.
Partial discrimination
Discrimination is partial if the above condition is not fulfiled up to theprospective short-circuit current, but to a lesser value, termed the selectivity limit current (Is).
Above this value both circuit breakers could open, resulting in loss of selectivity.
HOW TO READ THE DISCRIMINATION TABLES
Boxes containing the letter “T” indicate total discrimination between therelevant upstream and downstream circuit-breakers. Total discrimination applies for all fault levels up to the breaking capacity of the upstream or the downstream circuit breaker, whichever is the lesser.
For the other boxes, discrimination is either partial or there is no discrimination.
If discrimination is partial then the value of the selectivity limit current, Is, is shown in the box.
Worked Examples
Q (1) A main switchboard requires a 1600A ACB feeding a 400A MCCB.The fault level is 70kA. What combination of protective devices would provide total discrimination?
A (1) A TemPower2 ACB AR216S feeding a TemBreak2 S400-GJ would provide total discrimination up to 70kA. See page 71
Note: Discrimination would be total whether the TemPower 2 ACB had an integral or external protection relay because Icw (1s) = Ics.
Most other ACBs have Icw (1s) <Ics.
DISCRIMINATION
upstreamcircuitbreaker
downstreamcircuitbreaker
faultcurrent
X
X
SE
CT
ION
4
The Ultimate Safety Breaker page 70
APPLICATION DATA
HOW TO READ THE DISCRIMINATION TABLES
Q (2) A Sub distribution board requires a 630A MCCB feeding a 250A MCCB.The fault level is 65kA. What combination of protective devices wouldprovide total discrimination?
A (2) Using a TemBreak 2 S630-GE MCCB feeding a TemBreak 2 S250-GJwould provide total discrimination up to 65kA. See page 73
Q (3) A final distribution board contains a 125A MCCB incomer feeding a 32A Type B MCB. Is discrimination between these devices possible?
A (3) A TemBreak 2 MCCB type S160-NJ/125A feeding a TD3 DIN type MCB would provide total discrimination. See page 72
Alternatively ANY OTHER MCB can be used provided it has energy limitingability of class 3 in accordance with EN 60898.
page 71 The Ultimate Safety Breaker
APPLICATION DATA
Upstream: TemPower 2 ACB with or without Integral Protection Relay.
Downstream: TemBreak 2 MCCB.
DISCRIMINATION TABLES
Frame
Model
800A 1250A 1600A 2000A 2500A 3200A 4000A 5000A 6300A
AR
208S
AR
212S
AR
212H
AR
216S
AR
216H
AR
316H
AR
220S
AR
220H
AR
320H
AR
325S
AR
325H
AR
332S
AR
332H
AR
440S
B
AR
650S
AR
663S
AR
663H
Notes: 1. All ACB’s have Ii set at NON, MCR ON.2. Assuming ACB time settings are greater than MCCB.3. The above table is in accordance with IEC 60947-2, Annex A.
4. External relay can be used - Contact Terasaki for further details.5. All values shown at 400V AC.
T= Total Selectivity
Upstream ACB
Do
wn
str
eam
MC
CB
65kA 65kA 80kA 65kA 80kA 100kA 65kA 80kA 100A 85kA 100kA 85kA 100kA 100kA 120kA 120kA 135kABreakingCapacity
125A E125NJ 25kA T T T T T T T T T T T T T T T T T
S125NJ 36kA T T T T T T T T T T T T T T T T T
S125GJ 65kA T T T T T T T T T T T T T T T T T
H125NJ 125kA T T T T T T T T T T T T T T T T T
L125NJ 200kA T T T T T T T T T T T T T T T T T
160A/ S160NJ 36kA T T T T T T T T T T T T T T T T T
250A S160GJ 65kA T T T T T T T T T T T T T T T T T
E250NJ 25kA T T T T T T T T T T T T T T T T T
S250NJ 36kA T T T T T T T T T T T T T T T T T
S250GJ 65kA T T T T T T T T T T T T T T T T T
S250PE 70kA T T T T T T T T T T T T T T T T T
H250NJ 125kA T T T T T T T T T T T T T T T T T
L250NJ 200KA T T T T T T T T T T T T T T T T T
400A/ E400NJ 25kA T T T T T T T T T T T T T T T T T
630A S400CJ 36kA T T T T T T T T T T T T T T T T T
S400NJ 50kA T T T T T T T T T T T T T T T T T
S400NE 50kA T T T T T T T T T T T T T T T T T
S400GJ 70kA T T T T T T T T T T T T T T T T T
S400GE 70kA T T T T T T T T T T T T T T T T T
S400PJ 85kA T T T T T T T T T T T T T T T T T
S400PE 85kA T T T T T T T T T T T T T T T T T
H400NJ 125kA T T T T T T T T T T T T T T T T T
H400NE 125kA T T T T T T T T T T T T T T T T T
E630NE 36kA T T T T T T T T T T T T T T T T T
S630CE 50kA T T T T T T T T T T T T T T T T T
S630GE 70kA T T T T T T T T T T T T T T T T T
800A S800-CJ 36kA T T T T T T T T T T T T T T T T T
S800-NJ 50kA T T T T T T T T T T T T T T T T T
S800-RJ 70kA T T T T T T T T T T T T T T T T T
S800-NE 50kA T T T T T T T T T T T T T T T T T
S800-RE 70kA T T T T T T T T T T T T T T T T T
H800-NE 125kA T T T T T T T T T T T T T T T T T
L800-NE 200kA T T T T T T T T T T T T T T T T T
1000A S1000-SE 50kA - T T T T T T T T T T T T T T T T
S1000-NE 70kA - T T T T T T T T T T T T T T T T
1250A S1250-SE 50kA - T T T T T T T T T T T T T T T T
S1250-NE 70kA - T T T T T T T T T T T T T T T T
S1250-GE 100kA - T T T T T T T T T T T T T T T T
1600A S1600-SE 50kA - - - T T T T T T T T T T T T T T
S1600-NE 100kA - - - T T T T T T T T T T T T T T
SE
CT
ION
4
The Ultimate Safety Breaker page 72
APPLICATION DATA
In 20A 32A 50A 63A 100A 125A 20A 32A 50A 63A 100A 125A 160A 20A 32A 50A 63A 100A 125A 160A 200A 250A 250A 400A
6A 260 T T T T T 260 T T T T T T 260 T T T T T T T T T T
10A 260 420 T T T T 260 420 T T T T T 260 420 T T T T T T T T T
16A 260 420 650 T T T 260 420 650 T T T T 260 420 650 T T T T T T T T
20A 260 420 650 1000 T T 260 420 650 1000 T T T 260 420 650 1000 T T T T T T T
25A 260 420 650 1000 T T 260 420 650 1000 T T T 260 420 650 1000 T T T T T T T
32A 260 420 650 1000 1500 T 260 420 650 1000 1500 T T 260 420 650 1000 1500 T T T T T T
40A 260 420 650 1000 1500 2000 260 420 650 1000 1500 2000 T 260 420 650 1000 1500 2000 T T T T T
50A 260 420 650 1000 1500 2000 260 420 650 1000 1500 2000 3000 260 420 650 1000 1500 2000 3000 T T T T
63A 260 420 650 1000 1500 2000 260 420 650 1000 1500 2000 3000 260 420 650 1000 1500 2000 3000 2600 T T T
Notes: 1. MCBs can be of any manufacture provided they are Energy class three as defined in EN 60898.
2. Table based on type B MCBs3. MCBs can be 6kA or 10kA at 400V
4. The above table is in accordance with IEC 60947-2, Annex A.5. All values shown at 400V AC.6. Is expressed in A.
T= Total Selectivity
Upstream MCCB
Do
wn
str
eam
MC
B
S125NJ (36kA) S160NJ (36kA) S250NJ (36kA) S400NJ
E125NJ (25kA) E250NJ (25kA)
Upstream: TemBreak 2 MCCB (thermal-magnetic)
Downstream: MCB
DISCRIMINATION TABLES
page 73 The Ultimate Safety Breaker
APPLICATION DATA
Upstream: TemBreak 2 MCCB (electronic).
Downstream: TemBreak 2 MCCB.
DISCRIMINATION TABLES
Notes: 1. All pick-up current and time delay settings are to be set at maximum for upstream MCCBs.2. The above table is in accordance with IEC 60947-2, Annex A.3. All values shown at 400V AC.4. Is expressed in kA.
T= Total Selectivity
Upstream MCCB
Do
wn
str
eam
MC
CB
Frame 250A 400A 630A 800A 1000A 1250A 1600A
Model
BreakingCapacity
36kA
65kA
70kA
125kA
50kA
70kA
85kA
125kA
200kA
36kA
50kA
70kA
50kA
70kA
125kA
200kA
50kA
70kA
50kA
70kA
100kA
50kA
100kA
50A
100A
S50-NF
E100-NF
10kA
10kA
T T T T T T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T T T T T T
125A
E125-NJ
S125-NJ
S125-GJ
H125-NJ
25kA
36kA
65kA
125kA
T T T T T T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T 50 T T T T T T T T T
T T T T T T T T T T T T T 50 T T T T T T 70 T 85
160A/
250A
S160-NJ
S160-GJ
H160-NJ
E250-NJ
S250-NJ
S250-GJ
S250-NE
S250-GE
H250-NJ
S250-PE
H250-NE
36kA
65kA
125kA
25kA
36kA
65kA
36kA
65kA
125kA
70kA
125kA
- - - - T T T T T T T T T T T T T T T T T T T
- - - - T T T T T T T T 36 36 T T T 50 T T T T T
- - - - - - - T T T T T T 50 T T T T T T 70 T 85
- - - - T T T T T T T T T T T T T T T T T T T
- - - - T T T T T T T T T T T T T T T T T T T
- - - - T T T T T T T T 36 36 T T T 50 T T T T T
- - - - - - - T T T T T T T T T T T T T T T T
- - - - - - - T T T T T 36 36 T T T 50 T T T T T
- - - - - - - T T T T T T 50 T T T T T T 70 T 85
- - - - - - - T T T T T 36 36 T T T 50 T T 70 T T
- - - - - - - T T T T T 36 36 T T T 50 T T 70 T 85
400A/
630A
E400-NJ
S400-CJ
S400-NJ
S400-NE
S400-GJ
S400-GE
S400-PJ
S400-PE
H400-NE
E630-NE
S630-CE
S630-GE
25kA
36kA
50kA
50kA
70kA
70kA
85kA
85kA
125kA
36kA
50kA
70kA
- - - - - - - - - 10 10 10 T T T T T T T T T T T
- - - - - - - - - 10 10 10 25 25 25 25 30 30 T T T T T
- - - - - - - - - 10 10 10 25 25 25 25 30 30 36 36 36 T T
- - - - - - - - - 10 10 10 25 25 25 25 30 30 36 36 36 T T
- - - - - - - - - 10 10 10 25 25 25 25 30 30 36 36 36 T 50
- - - - - - - - - 10 10 10 25 25 25 25 30 30 36 36 36 T 50
- - - - - - - - - 10 10 10 25 25 25 25 30 30 36 36 36 T 50
- - - - - - - - - 10 10 10 25 25 25 25 30 30 36 36 36 T 50
- - - - - - - - - 10 10 10 36 36 25 25 T 50 T T 70 T 70
- - - - - - - - - - - - - - - - - - T T T T T
- - - - - - - - - - - - - - - - - - 36 36 36 T T
- - - - - - - - - - - - - - - - - - 36 36 36 T 50
800A S800-CJ
S800-NJ
S800-RJ
S800-NE
S800-RE
36kA
50kA
70kA
50kA
70kA
- - - - - - - - - - - - - - - - - - - - - 20 20
- - - - - - - - - - - - - - - - - - - - - 20 20
- - - - - - - - - - - - - - - - - - - - - 20 20
- - - - - - - - - - - - - - - - - - - - - 20 20
- - - - - - - - - - - - - - - - - - - - - 20 20
S25
0-N
E
S25
0-G
E
S25
0-P
E
H25
0-N
E
S40
0-N
E
S40
0-G
E
S40
0-P
E
H40
0-N
E
L40
0-N
E
E63
0-N
E
S63
0-C
E
S63
0-G
E
S80
0-N
E
S80
0-R
E
H80
0-N
E
L80
0-N
E
S10
00-S
E
S10
00-N
E
S12
50-S
E
S12
50-N
E
S12
50-G
E
S16
00-S
E
S16
00-N
E
SE
CT
ION
4
The Ultimate Safety Breaker page 74
APPLICATION DATA
Cascading is a technique where the current limiting capability of upstream circuitbreakers is used to permit the installation of lower rated and therefore lower costcircuit breakers downstream.
The upstream TemBreak 2 circuit breaker acts as a resistance against short-circuitcurrents. With this assistance, downstream circuit breakers with breaking capacitieslower than the prospective short-circuit at their point of installation can interruptthe reduced short-circuit current.
Since the current is limited downstream of the limiting circuit breaker, cascadingapplies to all switchgear in the downstream circuit. It is not restricted to twoconsecutive devices.
Cascading is recognised by the following standards related to electrical installations:
IEC 60364
BS 7671
AS/NZS 3000
The Advantages
Installation of a single limiting circuit-breaker results in considerablesimplifications and savings for the entire downstream installation:
• Simplification of selection of devices using the cascading tables
• Savings on downstream devices. Cascading allows circuit-breakers with lower ratings to be used.
In addition the application of cascading will reduce both electrodynamic and thermal stress within the installation.
WHAT IS CASCADING?
page 75 The Ultimate Safety Breaker
APPLICATION DATA
HOW TO READ THE CASCADE TABLES
The value shown in the table is the increased breaking capacity, expressed in kA, that can be achieved if the downstream MCCB is backed up by the appropriate upstream MCCB.
Worked Examples:
Q (1) A 36kA panelboard is required with a 400A incomer and 125A outgoing MCCBs. Can cascading be applied?
A (1) A cost effective solution would be to use an S400-CJ incomer rated at 36kA and E125-NJ MCCBs rated at 25kA downstream.
The upstream S400-CJ MCCB would back up the downstream E125-NJ to 36kA. If this was an 8 Way panelboard you have managed to save cost by installing eight 25kA MCCBs rather than eight 36kA MCCBs.
Q (2) If the same 8 way panelboard was to be used in an 80kA installation, what MCCBs could be used?
A (2) You could still use the E125-NJ provided it was backed up by an L400-NE. The Current limiting capacity of the 400A MCCBwould back up the E125A from 25kA to 85kA.
SE
CT
ION
4
The Ultimate Safety Breaker page 76
APPLICATION DATA
Upstream: TemBreak 2 MCCB.
Downstream: Din type MCB.
CASCADE TABLES
In 125A 125A 125A 160A 160A 250A 250A 250A
TD3
M06
(6kA)
6A 14 14 14 12 12 12 12 12
10A 14 14 14 12 12 12 12 12
16A 14 14 14 12 12 12 12 12
20A 14 14 14 12 12 12 12 12
25A 14 14 14 12 12 12 12 12
32A 14 14 14 12 12 12 12 12
40A 12 12 12 10 10 10 10 10
50A 12 12 12 10 10 10 10 10
63A 12 12 12 10 10 10 10 10
Model
Notes: 1. All values shown at 400V AC.2. Cascade fault level limit is expressed in kA.
Upstream MCCB
Do
wn
str
eam
MC
B
In 125A 125A 125A 160A 160A 250A 250A 250A
TD3
M10
(10kA)
6A 25 30 30 25 25 25 25 25
10A 25 30 30 25 25 25 25 25
16A 25 30 30 25 25 25 25 25
20A 25 30 30 25 25 25 25 25
25A 25 30 30 25 25 25 25 25
32A 25 30 30 25 25 25 25 25
40A 25 30 30 23 23 23 20 23
50A 25 30 30 23 23 23 23 23
63A 25 30 30 23 23 23 23 23
Model
Notes: 1. All values shown at 400V AC.2. Cascade fault level limit is expressed in kA.
Upstream MCCB
Do
wn
str
eam
MC
B
E125NJ (25kA) S125NJ (36kA) S125GJ (65kA) S160NJ (36kA) S160GJ (65kA) E250NJ (25kA) S250NJ (36kA) S250GJ (65kA)
E125NJ (25kA) S125NJ (36kA) S125GJ (65kA) S160NJ (36kA) S160GJ (65kA) E250NJ (25kA) S250NJ (36kA) S250GJ (65kA)
CASCADE TABLES
page 77 The Ultimate Safety Breaker
APPLICATION DATA
Upstream: TemBreak 2 MCCB.
Downstream: TemBreak 2 MCCB.
Frame
Model
Breaking Capacity 25kA 36kA 65kA 125kA 200kA 36kA 65kA 125kA 200kA 25kA 36kA 65kA 70kA 125kA 200kA
125A 160A/250A
50A S50NF 10kA 25 25 25 25 25 15 15 25 25 15 15 15 15 25 25
E100NF 10kA 25 25 25 25 25 15 15 25 25 15 15 15 15 25 25
125A E125NJ 25kA - 36 50 65 85 36 50 65 85 - 36 50 50 65 85
S125NJ 36kA - - 65 85 125 - 65 85 125 - - 65 65 85 125
S125GJ 65kA - - - 125 150 - - 125 150 - - - 70 125 150
H125NJ 125kA - - - - 200 - - - 200 - - - - - 200
160A/ S160NJ 36kA - - - - - - 65 85 125 - - 65 65 85 125
250A S160GJ 65kA - - - - - - - 125 150 - - - 70 125 150
H160NJ 125kA - - - - - - - - 200 - - - - - 200
E250NJ 25kA - - - - - - - - - - 36 50 50 65 85
S250NJ 36kA - - - - - - - - - - - 65 65 85 125
S250GJ 65kA - - - - - - - - - - - - 70 125 150
S250PE 70kA - - - - - - - - - - - - - 125 150
H250NJ 125kA - - - - - - - - - - - - - - 200
E125N
J
S125N
J
S125G
J
H125N
J
L125N
J
S160N
J
S160G
J
H160N
J
L160N
J
E250N
J
S250N
J
S250G
J
S250P
E
H250N
J
H250N
E
L250N
J
Upstream MCCB
Do
wn
str
eam
MC
CB
Frame
Model
400A 630A 800A/1000A 1250A/1600A
125A E125NJ 25kA 36 36 50 50 65 85 36 36 50 30 36 36 - - - - - - - - -
S125NJ 36kA - 50 65 65 85 125 - 50 65 - 50 50 - - - - - - - - -
S125GJ 65kA - - 70 85 125 150 - - 70 - - 70 - - - - - - - - -
H125NJ 125kA - - - - - 200 - - - - - - - - - - - - - - -
160A/ S160NJ 36kA - 50 65 65 85 125 - 50 65 - 50 70 50 50 50 70 - - - - -
250A S160GJ 65kA - - 70 85 125 150 - - 70 - - 70 70 70 - 70 - - - - -
H160NJ 125kA - - - - - 200 - - - - - - - - - - - - - - -
E250NJ 25kA 36 36 50 50 65 85 36 36 50 30 36 50 36 36 36 50 - - - - -
S250NJ 36kA - 50 65 65 85 125 - 50 65 - 50 70 50 50 50 70 - - - - -
S250GJ 65kA - - 70 85 125 150 - - 70 - - 70 70 70 - 70 - - - - -
S250PE 70kA - - - - 125 150 - - - - - - 85 85 - - - - - - -
H250NJ 125kA - - - - - 200 - - - - - - - 150 - - - - - - -
400A E400NJ 25kA 36 36 50 50 65 85 36 36 50 30 36 50 36 36 36 36 36 36 36 36 36
S400CJ 36kA - 50 65 65 70 100 - 50 65 - 50 70 50 50 50 50 50 50 50 50 50
S400NJ 50kA - - 70 70 85 125 - - 70 - - 70 70 70 - 70 - 70 70 - 70
S400GJ 70kA - - - 85 125 150 - - - - - - 85 85 - - - - - - 85
S400PJ 85kA - - - - 125 150 - - - - - - - - - - - - - - -
S400C
J
S400N
JS
400N
E
S400G
JS
400G
E
S400P
JS
400P
E
H400N
E
L400N
E
E630N
E
S630C
E
S630G
E
S800C
J
S800N
JS
800N
E
S800R
JS
800R
E
H800N
E
L800N
E
S1000S
E
S1000N
E
S1250S
E
S1250N
E
S1250G
E
S1600S
E
S1600N
E
Upstream MCCB
Do
wn
str
eam
MC
CB
Notes: 1. All values shown at 400V AC.2. Cascade fault level limit is expressed in kA.
Notes: 1. All values shown at 400V AC.2. Cascade fault level limit is expressed in kA.
Breaking Capacity
36kA 50kA 70kA 85kA 125kA 200kA 36kA 50kA 70kA 36kA 50kA 70kA 125kA 200kA 50kA 70kA 50kA 70kA 85kA 50kA 85kA
SE
CT
ION
4
The Ultimate Safety Breaker page 78
APPLICATION DATA
The Application of MCCBs in DC Systems
Terasaki’s MCCBs provide an excellent range of protection for DC installations. We offer MCCBs of up to 1000A with DC overload protection and up to 2500A with DC short-circuit protection.
Protection Method
Current transformers require alternating current to generate magnetic flux thereby inducing current toflow in the secondary winding. Any device which relies on current transformers for measurement ordetection of current is therefore unsuitable for protection of DC systems. Most electronic MCCBs fallinto this category.
The most common method of detecting DC overloads is by the use of a thermal element. Short-circuit protection in DC circuits is provided by electromagnetic tripping elements.
Tripping Characteristics
The time-current characteristics of a thermal element, such as those published in Section 3, areunaffected by the frequency of current applied. They hold good for both AC and DC currents.
A magnetic element operates on the instantaneous value of the current waveform. This means that inpractice in an AC circuit, it will operate at the peak value of the sinusoidal waveform. Trippingcharacteristics are published in AC root mean square (rms) Amperes (A). This means that the value ofAC instantaneous current, Ip, which will operate the element is equal to the rms current multiplied by√–2. Similarly, the value of DC instantaneous current which will operate the element is equal to the AC
rms current multiplied by √–2.
Time Constant
Time constants associated with DC circuits prevent the voltage of the circuit from reactingimmediately when a load current is suddenly interrupted.
The time constant, τ, of a circuit indicates how quickly voltage across capacitors and current throughinductors react to transient conditions.
DC operating current of magnetic element = √–2 ✕ AC rms operating current of magnetic element.
The time constant of a capacitive circuit is the product of capacitance and resistance: τ = RC (s).The time constant of an inductive circuit is given by: τ = L/R (s).
page 79 The Ultimate Safety Breaker
APPLICATION DATA
The Application of MCCBs in DC Systems
Time Constant
Transient voltages and currents, including those produced by switching, donot approximate their steady state values until 5 time constants have elapsed.
Fault currents occurring in circuits with high time constants are extremelydifficult to interrupt due to the lagging voltage. All DC breaking capacitiesin this section are shown with the assumption that the time constant of thecircuit is restricted to the values shown below.
Breaking Capacity
The short-circuit ratings of MCCBs suitable for DC installations are shownin the table below. In some cases, two or more poles must be connected inseries to achieve the given rating, this is also indicated in the table. Please refer to catalogue I73E for further details.
Fault Level τNear the rated current, In, of the circuit breaker <2.0ms
<2.5 x In <2.5ms
<10kA <7ms
>10kA <15ms
DC Breaking Capacity, Icu (kA), Protection and Reference
Voltage 250V DC 350V DC 500V DC 600V DC Protection
Poles in Series 2 3 3 4 3 4 Overload Short Circuit
E125-NJ 25 – – – – – Thermal, adjustable Magnetic, adjustable
S125-ND – 10 – 7.5 – 5 Thermal, adjustable Magnetic, fixed
S125-GJ 40 – – – – – Thermal, adjustable Magnetic, adjustable
S160-ND – 10 – 7.5 – 5 Thermal, adjustable Magnetic, fixed
E250-NJ 25 – – – – – Thermal, adjustable Magnetic, adjustable
S250-ND – 10 – 7.5 – 5 Thermal, adjustable Magnetic, fixed
E400-NJ 25 – – – – – Thermal, adjustable Magnetic, adjustable
S400-CJ – – – – – – Thermal, adjustable Magnetic, adjustable
S400-ND – 20 15 – 15 – Thermal, adjustable Magnetic, fixed
S800-CJ 50 – – – – – Thermal, adjustable Magnetic, adjustable
S800-ND – 30 20 – 20 – Thermal, adjustable Magnetic, fixed
XS1000ND 50 30 20 20 20 20 Thermal, fixed Magnetic, adjustable
XS1250ND 50 50 50 50 20 20 – Magnetic, adjustable
XS1600ND 50 50 50 50 20 20 – Magnetic, adjustable
XS2000ND 50 50 50 50 20 20 – Magnetic, adjustable
XS2500ND 50 50 50 50 20 20 – Magnetic, adjustable
SE
CT
ION
5
The Ultimate Safety Breaker page 80
ACCESSORIES
TEMBREAK 2
MOULDED CASE CIRCUIT BREAKERS16A TO 1600A
1. Welcome to TemBreak 2
2. Ratings and Specifications
3. Operating Characteristics
4. Application Data
5. Accessories
• Electrical Control (Internal Accessories) 81
• Termination of Control Wiring 86
• Electrical Control (Motorised Operation) 87
• Operating Handles & Locking Devices 92
• Insulation Accessories 95
• Dual Supply Changeover Systems 98
6. Installation
7. Dimensions
page 81 The Ultimate Safety Breaker
Electrical control accessories for TemBreak 2 aredesigned with the installer in mind. Status andalarm contacts, remote tripping coils andundervoltage protection coils are of modular design andconvenient to use.
• Every accessory fits every MCCB and Switch-Disconnector in the range.
• All accessories are endurance tested to the same level as MCCBs.
• TemBreak 2 internal accessories are easily field-installable.
• All accessories are individually packaged and are supplied with fitting instructions.
• Control wiring is terminated on the accessoryscrew terminal. Alternatively a terminal blockwhich clips to the side of the MCCB is available.
1) Heavy-duty auxiliary switch2) Heavy-duty alarm switch3) General-purpose auxiliary switch4) General-purpose alarm switch5) Shunt trip6) Undervoltage trip
(1) (2) (3) (4) (5) (6)
ELECTRICAL CONTROL USING INTERNALLY
MOUNTED ACCESSORIES
ACCESSORIES
Installing Accessories in a 4 pole S400 model
1 2 3
5
7 8
6
The internal accessories can be easily installed in the field without special tools or product training.
4
Easy field-Installation of Accessories
• Internal accessory can be simply plugged into position
• No tools are required for this,except a screwdriver to lift theMCCB front cover clips.
• Accessories fit with a firm clickwhen installed correctly.
• Colour coding of accessories helps identification and installation
Click
SE
CT
ION
5
The Ultimate Safety Breaker page 82
ELECTRICAL CONTROL USING INTERNALLY
MOUNTED ACCESSORIES
Valid Maximum Accessory Combinations
ACCESSORIES
E250E125 E400E630
S125 S160S250
S400S630
H125H160H250
H400
L
H
S
E
125Frame size (A) 160 and 250 400 and 630 800 and 1000 1250 and 1600
L125L160L250
L400
H800
L800
S800S1000
S1250S1600
Shunt Trip
General Purpose Alarm Switch
General Purpose Auxiliary Switch
Undervoltage Trip
General Purpose Alarm Switch
General Purpose Auxiliary Switch
Shunt Trip
Heavy Duty Alarm Switch
Heavy Duty Auxiliary Switch
Undervoltage Trip
Auxiliary Switch
Alarm Switch
Shunt Trip
Undervoltage Trip
Heavy Duty Alarm Switch
Heavy Duty Auxiliary Switch
• General purpose and heavy duty status indication switches cannot bemixed in the same MCCB.
• It is not possible to install a shunt trip and an undervoltage trip inan MCCB as they occupy the same location. Undervoltage tripscan provide remote tripping if necessary by wiring a normallyclosed contact or pushbutton in series with the protected supply.
• Undervoltage trips with time delays require an external time delaycontroller which clips to the side of the MCCB.
page 83 The Ultimate Safety Breaker
.4
OFF,Trip
.1
.2
ELECTRICAL CONTROL USING INTERNALLY
MOUNTED ACCESSORIES
ACCESSORIES
Status Indication Switches
General Purpose Auxiliary Switch
Terminal Designations andFunction of General PurposeAuxiliary Switch
.4
.1
.2
General Purpose Alarm Switch
Terminal Designations andFunction of General PurposeAlarm Switch
General Purpose Auxiliary Switch (AX)
An auxiliary switch electrically indicatesthe ON or OFF status of the MCCB. The general purpose type is a changeoverswitch with 3 terminals.
A microcurrent version is available forswitching currents as low as 1mA.
Auxiliary switches are colour coded grey.The cable capacity of the terminals is 0.5to 1.25mm2.
The general purpose auxiliary switchmeets the requirements of IEC 61058-1.
General Purpose Alarm Switch (AL)
An alarm switch electrically indicates theTRIP status of the MCCB. The generalpurpose type is a changeover switch with3 terminals.
A microcurrent version is available forswitching currents as low as 1mA.
Alarm switches are colour coded grey andblack. The cable capacity of the terminalsis 0.5 to 1.25mm2.
The general purpose alarm switch meetsthe requirements of IEC 61058-1.
General purpose auxiliaries and alarm switch ratings Microcurrent versions
AC
Volts (V)
DC
ResistiveLoad
ResistiveLoad
InductiveLoad
InductiveLoad
Volts (V) Amperes (A)Amperes (A)
DC
Minimum Load
Minimum Load
Volts Amperes (A)(V)
ResistiveLoad
1mA at 5V
30 0.1 DC and 30V
DC.
440 - - 250 - - 100mA at
240 3 2 125 0.4 0.05 15V DC.
110 3 2 30 3 2
Trip
SE
CT
ION
5
The Ultimate Safety Breaker page 84
.4
.3
ELECTRICAL CONTROL USING INTERNALLY
MOUNTED ACCESSORIES
ACCESSORIES
Status Indication Switches
Heavy Duty Auxiliary Switch
Terminal Designationsand Function of Heavy DutyAuxiliary Switch, a contact
.2
.1 Terminal Designationsand Function of Heavy DutyAuxiliary Switch, b contact
.4
.3 Terminal Designationsand Function of Heavy DutyAlarm Switch, a contact
.2
.1 Terminal Designationsand Function of Heavy Duty Alarm Switch, b contact
Heavy Duty Alarm Switch
Heavy Duty Auxiliary Switch (AX)
The heavy duty auxiliary switch has animpulse withstand voltage (Uimp) of 6kV and is suitable for isolating safetycircuits. The auxiliary switch electricallyindicates the ON or OFF status of theMCCB. The heavy duty type is a bridgeswitch with two terminals. It is availablein either normally open or normallyclosed configurations.
Heavy duty auxiliary switches are colourcoded grey. The cable capacity of the terminals is 1.25 to 2.5mm2.
The heavy duty auxiliary switch meetsthe requirements of IEC 60947-5-1.
It has direct opening action,recommended by IEC 60204-1 Safety of Machinery - ElectricalEquipment for Machines.
Heavy Duty Alarm Switch (AL)
The heavy duty alarm switch has animpulse withstand voltage (Uimp) of 6kV and is suitable for isolating controlcircuits. The alarm switch electricallyindicates the TRIP status of the MCCB.The heavy duty type is a bridge switchwith two terminals. It is available ineither normally open or normally closedconfigurations.
Heavy duty auxiliary switches are colourcoded grey and black. The cable capacityof the terminals is 1.25 to 2.5mm2.
The heavy duty alarm switch meets therequirements of IEC 60947-5-1.
It has direct opening action,recommended by IEC 60204-1 Safety of Machinery - ElectricalEquipment for Machines.
Ratings of Heavy Duty Auxiliary and Alarm Switches
AC
Volts (V)
DC
ResistiveLoad
ResistiveLoad
InductiveLoad
InductiveLoad
Volts (V) Amperes (A)Amperes (A)
500 1 1 -
440 3 3 250 0.5 0.5
240 4 4 125 1 1
110 5 5 48 3 2.5
48 6 6 24 6 2.5
OFF,Trip
OFF,Trip
Trip
Trip
100-120 200-240 380-450 24 48 100-120 200-240
0.014 0.014 0.0065 0.03 0.03 0.011 0.011
page 85 The Ultimate Safety Breaker
ELECTRICAL CONTROL USING INTERNALLY
MOUNTED ACCESSORIES
ACCESSORIES
Remote Tripping Devices
Shunt Trip (SHT)
A shunt trip allows an MCCB to be trippedremotely on the application of the rated coil voltageacross the shunt trip terminals. TemBreak 2 shunttrips have continuously rated coils and are suitablefor use in electrical interlocking applications.
The MCCB contacts and toggle will move to thetripped position when the shunt trip is operated.
The permissible voltage range is 85% to 110% forAC or 75% to 125% for DC.
The cable capacity of the terminals is 0.5 to1.25mm2. Shunt trips are colour coded grey.
Under Voltage Trip (UVT)
An undervoltage trip will trip the breakerautomatically when the voltage applied to theterminals of the undervoltage coil drops to between70% and 35% of its voltage rating. Theundervoltage trip prevents the circuit breaker beingclosed unless a voltage corresponding to at least85% of its voltage rating is applied across theterminals of the undervoltage coil.
The MCCB contacts and toggle will move to thetripped position when the under-voltage tripoperates.
Undervoltage trips with AC operating voltages areavailable with 500ms time delays. Time-delay unitsare fitted to the outside of MCCBs.
The cable capacity of the terminals is 0.5 to1.25mm2. Undervoltage trips are colour coded greyand black.
RatedVoltage
ExcitationCurrent(A)
Voltage DCVoltage AC
Terminal Designations of Shunt Trips
Shunt Trips
Undervoltage Trips Terminal Designations of Undervoltage Trips
Ratings of Shunt Trips
Controller
C1 C2~ ~
(–) (+)
Controller
D1 D2~ ~
(–) (+)
Ratings of Undervoltage TripsPower supply capacity (VA) Excitation current (mA)
MCCB ModelRatedVoltage
Voltage AC Voltage DC100-120 200-240 380-450 24 100-120 200-240
E125, S125, H125, L125, S160,H160, L160, E250, S250, H250,L250, E400, S400, H400, L400,E630, S630
1.4 2.8 2.3 23 10 10
MCCB ModelRatedVoltage
Voltage AC Voltage DC100-110 115-120 200-220 230-240 380-415 440-450 24 100-120 200-240
S800, H800, L800, S1000,S1250, S1600 1.5 1.6 2.4 2.9 2.1 2.3 29 13 11
SE
CT
ION
5
The Ultimate Safety Breaker page 86
ACCESSORIES
Terminal Block for Front-Connected and Rear-Connected MCCBs (TF)
A terminal block facilitates convenient and accessiblecontrol wiring to internally mounted accessoriesespecially the accessories with lead wire. It allows the use of control wiring cables with largercross-sectional area than permitted by the internalaccessories themselves.
This terminal block can be clipped to either side of theMCCB. If mounted on the left incoming wiring will be fed vertically up to the terminals. If mounted on theright, the incoming wiring will be fed vertically down to the terminals.
The maximum incoming cable size to the terminal blockis 2.0mm2. 11terminals or 6 terminals can be specified.See page 153.
TERMINATION OF CONTROL WIRING
Terminal blocks are for optional use with all types of internallymounted accessory.
Terminal Block for Front-Connected and Rear-Connected MCCBs
Terminal Block for Plug-in MCCBs
Terminal Block for Plug-in MCCBs
The terminal block for a plug-in MCCBconsists of:
• a male section pre-fitted with 3 cables with which clips easily to the back of the MCCB
• a female section with 3 user terminals which clips easily into the plug-in base.
Up to 4 terminal blocks can be installedon a 125A, 160A or 250A frame MCCB.Up to 5 terminal blocks can be installedon a 400A to 800A frame MCCB.
page 87 The Ultimate Safety Breaker
ACCESSORIES
ELECTRICAL CONTROL USING MOTORISED OPERATION
Overview – Motor Operators (MC)
Motor operators provide the possibility ofopening and closing an MCCB onapplication of electrical control signals.TemBreak 2 motor operators areextremely reliable, having been designedto endure the same switching duty as thehost MCCB.
• Easy field-installation.
• Fast operation ( 100ms).
• Positive contact indication.
• Padlocking facility as standard(Maximum 3, hasp diameter 8mm).
• Optional keylock.
• Versions available with automatic reset function.
• Voltage presence indication.
Motor operators for 125A and250A frame are mounted on thefront of the breaker. They can berapidly fitted by locating the roundpegs and square pegs on the motorinto corresponding round andsquare holes on the breaker. It takesless than 10 seconds to secure themotor to the MCCB.Two levers securely lock the motor intoposition. No tools are needed to fit the motor operator.
400A frame to 1000A frame motoroperators are held in place withmounting screws. They can beinstalled easily in the field.
Mountingscrews
Round Peg
Padlockingfacility
ON / OFFTRIPPED
IndicatorOperating
Handle
Voltage presence
ON / OFFpush buttons
ManualCharging
PointSpring status
Manualcharging
lever
Optionalkey lock
ON / OFF+TRIPPED indicator
Optionalkey lock
Select Lever
Motor Operator for 125A and 250A Frame MCCB’s
Motor Operator for 400A and 630A Frame MCCB’s
Motor Operator for 125A and 250A frame MCCB’s
Motor Operator for 400A and 630A frame MCCB’s
Square Peg
SE
CT
ION
5
The Ultimate Safety Breaker page 88
ELECTRICAL CONTROL USING MOTORISED OPERATION
Indication of ON, OFF or TRIPPED Status
Ratings and Specifications
MCCB on MCCB off MCCB tripped
The handle of 125A and 250A frame motor operators has dual functions:
1. Indication of ON, OFF or TRIPPED status as shown in the photographs below;
2. Manual operation when handle is pulled out. The supply to electrical control circuits inside the motor operator is cut when the handle is pulled out.
Motor operators for400A to 1000A frameMCCBs incorporate amechanical flag whichindicates the ON, OFFand TRIPPED status of the MCCB. They can be manuallycharged using the lever provided.
■ = AvailableNote: Operating times shown in the above table apply only when the rated operational voltage is supplied to the motor operator.The voltage supplied to the motor operator must be within the range of 85% and 110% of the rated operating voltage.
ACCESSORIES
Type of Motor Operators T2MC12 T2MC25 T2MC40 T2MC80
Applicable MCCB E125 E250 E400 S800, S1000S125 S160, S250 S400 H800
H125, H160, H250 E630 L800L125, L160, L250 S630
Rated operatingvoltage
100-110 V AC ■ ■ ■
200-220 V AC ■ ■ ■
230-240 V AC ■ ■ ■
24 V DC ■ ■ ■
48 V DC ■ ■ ■
100-110 V DC ■ ■ ■
200-220 V DC ■ NA NAOperating current/Starting currentPeak value (A)
100-110 V AC 4.5/8 ON ---/2.3 OFF, RESET 1.4/3.7 ON ---/2.2 OFF, RESET 1.7/3.5200-220 V AC 4/8 ON ---/2.3 OFF, RESET 1.1/3.5 ON ---/2.2 OFF, RESET 1.3/3.5230-240 V AC 3.5/7 ON ---/2.3 OFF, RESET 1.1/3.5 ON ---/2.2 OFF, RESET 1.3/3.524 V DC 18/26 ON ---/7.2 OFF, RESET 3.9/8.1 ON ---/12 OFF, RESET 6.0/11.548 V DC 12/18 ON ---/7.2 OFF/RESET 2.0/5.1 ON ---/7 OFF, RESET 3.2/6.5100-110 V DC 2.2/6 ON ---/2.4 OFF/RESET 1.2/3.8 ON ---/2.2 OFF, RESET 1.3/3.5200-220 V DC 2.2/5.5 — —
Operating method Direct drive Spring charging Spring chargingOperating time (s) ON 0.1 0.1 0.1
OFF 0.1 1.5 1.5RESET 0.1 1.5 1.5
Operating switch rating 100V, 0.1 A, Opening voltage44V, current 4mA
100V, 0.1 A, Opening voltage 48V, current 1mA
Power supply required 300 VA minimum 300VA minimum 300VA minimumDielectric properties (1 min) 1500 V AC (1000V AC for 24V DC and 48V DC motors)Weight 1.4 kg 3.5kg 3.5kg
page 89 The Ultimate Safety Breaker
ACCESSORIES
ELECTRICAL CONTROL USING MOTORISED OPERATION
Motor Operator Control Circuits
Operation
The motor operator incorporates a self-holdcircuit for the closing and opening signals.Therefore a momentary (over 50msec.) open orclose signal will ensure a complete operation.
When the breaker trips, the breaker is reset by applying a signal to the OFF terminals of the motor.
When a UVT is used with a motor operator,design the control circuit so that the UVT isenergised before a reset or close signal is sent to the motor operator. A 40ms time delay in the reset and close signals is sufficient to allow the UVT to energise.
When a shunt trip is used with a motor operator,design the control circuit so that the shunt trip is de-energised before a reset or close signal is sent to the motor operator.
When a mechanical interlock is used with motoroperators, design the control circuit to provideelectrical interlocking between the motoroperators. The electrical interlocking shouldprevent a close signal being sent to a motoroperator unless the other motor operator andcircuit breaker are in the OFF position.
Auto- reset
Two types of motor operator are available: motor operators without auto-reset and motoroperators with auto-reset. The correct type of motor operator should be selected for theapplication. MCCB auxiliary and alarm switchesdo not have to be used in the control circuits for motor operators whether they have auto-reset or not, saving cost and space.
MCCB and Motor Operator Showing ControlWiring Socket
The Control circuits for MotorOperators are connected using a simple plug and socket system.
Control circuit for Motor Operators
Control Wiring Plug
SE
CT
ION
5
The Ultimate Safety Breaker page 90
ACCESSORIES
ELECTRICAL CONTROL USING MOTORISED OPERATION
Manualoperatinghandle
Indicator
Lock plate
Control circuitterminals
Trip button
Positive contact indication
Colour coding indicates the true position ofthe contacts clearly: ON (red), OFF (green),TRIP (white).
Easy maintenance
Manual ON/OFF operationwith one stroke
Breaker mounting, removal, and even settingchanges can be done without removing themotor operator.
Fast closing operation
Closing in 60ms or less. The closing timeremains constant over repeated operations.
NOTE1 : Maximum values at AC115V, 50Hz2 : Maximum values at AC230V, 50Hz3 : Maximum values at DC110V4 : Maximum values at the rated operating voltages
■ = Available✽ Trip button on breaker to be used (accessible with motor fitted)
Ratings and SpecificationsType of Motor Operators T2MCX6
Applicable MCCB S1250
S1600
Rated OperatingVoltage (V)
AC 100-115V 50/60Hz ■
200-230V 50/60Hz ■
DC 100-110V ■
24V ■
Lock in “OFF” position (standard) ■
Manual Trip Button ✽
Steady-state r.m.s.Amp/inrush Amp (A)
AC100-115V ON1 –/3.1
OFF, RESET1 1.8/6.0
AC200-230V ON2 –/1.2
OFF, RESET2 1.0/3.2
DC100-110V ON3 –/0.8
OFF, RESET3 1.1/4.2
DC24V ON –/4.5
OFF, RESET 4.0/12.0
Type of operation Spring Charged
Operating Time(s) ON (Maximium values) 0.06
OFF, RESET4 3
Control Switch Ratings 250V, 5A
Power Source Capacity (VA) 300VA
Dielectric withstand voltage The value in brackets fot 24V DC
AC1500V(AC500V)
Weight (kg) 6.4
Type T2MCX6
page 91 The Ultimate Safety Breaker
ACCESSORIES
ELECTRICAL CONTROL USING MOTORISED OPERATION
SE
CT
ION
5
The Ultimate Safety Breaker page 92The Ultimate Safety Breaker page 92
OPERATING HANDLES & LOCKING DEVICES
TemBreak 2 external operating handles are extremely reliable, having been designed to endure the sameswitching duty as the host MCCB.It is easy to fit the operating unit to the MCCBs up to 250A frame. Fitting involves three easy steps:1. Align breaker toggle with operating mechanism2. Push external operating handle into position (the handle’s round pegs locate securely in the breaker’s
round holes and the external operating handle’s* square pegs in the breaker’s square holes).3. Twist locking screws through 45 degrees.*
Safety Features• Door interlock mechanism with override facility included as standard• IP55 as standard (HS), IP54 as standard (HP), IP3X as standard (HB)• IP65 optional (HS, HP), IP5X optional (HB)• Locks OFF with up to 3 padlocks (8mm hasps)• Optional Key fitting facility is available for Castell FS1 (HS)
Contact us for the details of mounting dimension.• Optional keylock in OFF postion (HP, HB)• Available Gray handle with Black base or Red handle with Yellow base (HS)• Available in black or red and yellow (HP, HB)• A trip test can be performed with the external operating handle fitted to the MCCB
Orientation
To switch the breaker from OFF to ON the externaloperating handle is rotated through 90 degrees in aclockwise direction.
The ON (I) and OFF (O) indication of the externaloperating handle can be re-oriented in steps of 90 degreeswith respect to the operating mechanism. This allows the indication position to remain the same whether thebreaker is mounted vertically (right side up or upside down) or horizontally (on its left side or on its right side). The hole cut-out dimensions for a panel or door will remain unchanged if the external operatinghandle is re-oriented. The external operating handle’s axis of rotation is on the intersection of thecentre lines of a 3P MCCB. This means that the positioning of the door cutouts is symmetrical forbreakers mounted horizontally on either side of a vertical busbar system.
*external operating handles for 400A and 1600A Framemodels are secured with four screws.
ACCESSORIES
MCCB ONMCCB ON
Using TemBreak 2 Operating Handles Using other MCCB Operating Handles
Cubicle Door Cutouts
The door mounted handles allow breakers installed in control centers orswitchboards to be manually operated from outside and complies withIEC 60204-1.It consists of an operating mechanism that is mounted on the breaker,an operating handle that is mounted on the door, and a shaft thattransmits the turning force from the handle to the operating unit.The shaft can be cut to the required length.The shaft support makes easy to insert to the operating handle whenthe panel door is being closed.
The external operating handle keeps the panel doorlocked when in the ‘ON’ position. There is OFFopen type only.
OFF open typeThe handle is turned to the OFF position to open thepanel door.
• Door interlock release buttonThe release button enables the panel door to beopened with the handle in the ‘ON’position. To release: push the release button onthe side of the operating handlewith a flat-bladedscrewdriver.
Door interlock mechanism
• Padlock (Standard)This mechanism allows the breaker to be padlocked inthe OFF position.Padlocks are not supplied. Up to three padlocks can be installed.
Toggle lock mechanism
ACCESSORIES
OPERATING HANDLES & LOCKING DEVICES
Door Mounted Handle (HS) standard type
page 93 The Ultimate Safety Breaker
Handle cover
Operating handle
Gasket for IP65(optional)
Shaft support(optional)
Square shaft
Operating unit
Pad locking leverPlastic lever or Metal leveravailable.
The Ultimate Safety Breaker page 94
SE
CT
ION
5
ACCESSORIES
The door mounted handle is used tooperate a circuit breaker mountedinside a cubicle from outside thedoor. It consists of an operatingmechanism that is mounted on the breaker, an operating handle that is mounted on the door, and a shaft that transmits the turningforce from the handle to theoperating unit. The shaft can be cut to the required length.
Handle unit
Optionalkey lock
Operatingunit
Locking Devices
Toggle locking devices allow MCCBs tobe locked ON or OFF using up to threepadlocks. Locking devices for 125A, 160Aand 250A frame models accept padlockswith 5mm hasp diameter. Locking devicesfor 400A to 1600A frame models acceptpadlocks with 8mm hasp diameter.
Fittings for Castell and Fortress locks are available. They are suitable for use on door mountedhandles (HP) for MCCBs.
Breaker Mounted Handle (HB)
OPERATING HANDLES & LOCKING DEVICES
Door Mounted Handle (HP) ordinal type
This external operating handle is used tooperate a circuit breaker mounted justbehind a compartment door with thedoor closed. The operating unit and thehandle itself are mounted directly ontothe circuit breaker. The handle protrudesthrough a cutout in the door. A mouldeddoor flange is supplied with the externaloperating handle which covers the cutoutfrom the front.
Padlocking and keylocking is possible in the OFF position.
Cutoutflange
OFFPadlocked
lever
Door interlockingmechanism
Door Mounted Handle with Optional Keylock
Breaker Mounted Handle Padlocked in the OFF Position
S250 Locked OFF S400 Locked OFF
Anti-tampersleeved
extensions
page 95 The Ultimate Safety Breaker
INSULATION ACCESSORIES
Terminal Covers
Terminal Cover Lock with Lead Seal
Terminal covers are used to prevent directcontact with live MCCB terminations.They also provide additional insulationto reduce the possibility of a short circuit between phases or to earth whenlarge conductors are used.
General features
• Terminal covers for 125A to 630Aframe models require no tools forinstallation
• Terminal covers for 125A to 630Aframe models have an IP20 ingressprotection rating
• Terminal covers are orderedindividually. Two terminal covers arerequired to cover both the line andload terminals of an MCCB. Eachcover can either be fitted to the top orbottom of the MCCB
• Terminal covers have a meggermeasurement hole of 4mm diameteron each phase.
Meggermeasurement
holes
Earth Barrier Fitted to Rear of Terminal Cover
Options
• A terminal cover for 125A to 630Aframe models lock allows an anti-tampering seal to be added.
• An earth barrier for 125A and 250Aframe models can be added toterminal covers for front connection.The earth barrier provides insulationat the rear of the terminations.
ACCESSORIES
The Ultimate Safety Breaker page 96
SE
CT
ION
5
ACCESSORIES
INSULATION ACCESSORIES
Terminal Covers for Front Connection (CF)
Terminal covers for front connection are suitable for coveringthe exposed live parts of conductors terminated on the MCCB.
Flush Terminal Covers (CS)
Flush terminal covers are available for 125A to 630A frame models and are useful for increasing theingress protection rating at the terminals without increasing the overall length. They can be used withbusbar and for direct entry of stranded cable (with cable clamp terminals (FW), refer to Section 6,Installation).Flush terminal covers are identical to rear terminal covers for 400A and 630A frame models. The user can remove a section of the rear terminal cover using a tool to allow entry of the conductor.
Terminal Covers for Front Connection Flush Terminal Covers
Terminal covers for Rear Connection (CR)
Terminal covers for rear connection are available for125A to 1000A frame models and may be used onMCCBs fitted with rear connections (RC) or plug-inconnections (PM). They prevent access to theterminals from the front and top.
Terminal Covers for Rear Connection
page 97 The Ultimate Safety Breaker
INSULATION ACCESSORIES
Interpole Barriers (BA)
MCCB Fitted with Interpole Barriers on Both Ends Interpole Barriers between Adjacent MCCBs
Interpole barriers provide maximum insulation between phases at the terminals of the MCCB. They cannot be fitted at the same time as any of the terminal covers. Interpole barriers for use on one end of the MCCB are supplied as standard. Additional interpole barriers can beordered individually. All interpole barriers can easily be fitted to either end of an MCCB.
MCCB moulds have been designed to accept an additionalinterpole barrier between two adjacent MCCBs.
ACCESSORIES
The Ultimate Safety Breaker page 98
SE
CT
ION
5
ACCESSORIES FOR DUAL SUPPLY CHANGEOVER SYSTEMS
ACCESSORIES
Viewed from Below
Where more than one AC voltage source is available to a distribution system it isoften necessary to prevent multiple sources supplying the system at one time.Interlocking accessories are used together with two MCCBs to prevent both being inthe ON state simultaneously. This provides a secure mechanical means of preventingthe connection of two supply sources.
An automatic changeover controller can monitor the status of two supplies andcontrol the switching of two MCCBs according to pre-programmed parameters.When an automatic changeover controller is interfaced to a pair of interlockedMCCBs fitted with remote control accessories, a secure, fully automatic changeoversystem is achieved.
Link Interlock (ML)
Link interlocks are available for 125A to1000A frame models and consist of amechanism mounted to each MCCB in anadjacently mounted pair. The linkbetween each mechanism inhibits theclosure of one MCCB unless the other isin the OFF position.
Link interlocks can be used on a mixture of 3 and 4 pole breakers of the same frame size.
The TemBreak 2 link interlock is aninnovative design breakthrough which will save space, time and money forswitchboard builders in that:
• Installation is extremely simple.Link interlocks are field-installable and only require a screwdriver to fit.For 400A to 1000A frame models, Link interlocks are factory-fitted andavailable with motor operators oroperating handles.
• Link interlocks replace the accessorycover on the front of the breaker
• Motor operators and operating handles are compatible with link interlocks
• The interlock is installed on the frontof the MCCB and does not thereforeinterfere with copperwork or cables
• No need to buy factory-built backplates with MCCBs and interlocks pre-fitted
Link Interlock
Changeover Pair with LinkInterlock and Motor Operators
page 99 The Ultimate Safety Breaker
The TemBreak 2 wire interlock is an innovative designbreakthrough which will save space, time and money forswitchboard builders in that:
• Installation is extremely simple. Wire interlocks are field-installable.For 400A to 1000A frame models, Wire interlocks arefactory-fitted and available with motor operators oroperating handles.
• Wire interlocks replace the accessory cover on the front ofthe breaker
• Motor operators and operating handles are compatiblewith wire interlocks
• Interlocking of MCCBs mounted in differentcompartments is possible
• No need to buy factory-built backplates with MCCBs andinterlocks pre-fitted
Wire interlocks are available also for 1250A and 1600Aframe models. The mechanisms are mounted on the back oftwo MCCBs. MCCBs cannot be mounted directly to a flatplate, but are installed on a frame to ensure space for theinterlock mechanism.
Slide Interlock (MS)
Slide interlocks are manually operated toggle lockingdevices which can be installed between two adjacentMCCBs. Depending on the position of the slide, one or other of the MCCBs on either side of a slideinterlock is inhibited from being in the ON position.Slide interlocks can be used between MCCBs of thesame number of poles and of the same frame size.Slide interlocks can be installed in the field and are padlockable in both positions.
ACCESSORIES FOR DUAL SUPPLY CHANGEOVER SYSTEMS
ACCESSORIES
Wire Interlock (MW)
Wire interlocks are available for 125A to 1000A frame models and consist of two mechanismsconnected by a cable. The mechanisms are mounted on two MCCBs located at a distance from eachother which is limited by the length and bend radius of the cable. The mechanisms and cable inhibitthe closure of one MCCB unless the other is in the OFF position. Each mechanism is orderedseparately. Cables of 1.0m or 1.5m length are also ordered as separate items.
Wire interlocks can be used on a mixture of 3 and 4 pole MCCBs of different frame sizes. This allows potential cost savings by using lower rated MCCBs for the alternative power supply. MCCBs can be mounted in different switchboard compartment or on different planes.
Slide Interlock Installed Between two MCCBs
Changeover Pair with Wire Interlock and Motor Operators
View from above
The Ultimate Safety Breaker page 100
SE
CT
ION
5
ACCESSORIES FOR DUAL SUPPLY CHANGEOVER SYSTEMS
ACCESSORIES
TemTransfer Automatic Changeover Controller
The TemTransfer is a fully configurable Automatic Changeover Controller (ACC). It is designed to monitor the incoming AC mains supply (1 or 3 phases) for under/over voltage and under/over frequency. Should these fall out of limits, the module will issue a startcommand to the generating set controller. Once the set isavailable and producing an output within limits the ACCwill control the transfer devices and switch the load fromthe mains to the generating set. Should the mains supplyreturn to within limits the module will command a returnto the mains supply and shut down the generator after a suitable cooling run. Various timing sequences are used to prevent nuisance starting and supply breaks.
TemTransfer is compatible with TemPower 2 ACBs,TemBreak 2 MCCBs and TemContact contactors.
When TemTransfer is used with a pair of TemBreak 2MCCBs, additional control wiring and components may benecessary for some control schemes. Contact us for details.
Terasaki can supply TemTransfer pre-configured tospecification, or unconfigured with an optional interface kit.
Configuration is by PC based software and the interface kit using an FCC68 socket on the rear of the module. This allows rapid and secure configuration of the module.The FCC68 socket also provides full real-time diagnosticson the status of the ACC, its inputs and outputs.
Configuration and connection options allow for a widerange of higher functions such as ‘Auto start inhibit’,‘Manual restore to mains’, ‘Load inhibit’ (both mains and gen-set), ‘Lamp test’, Push-button transfer control,External mains or Gen-set failure inputs, etc.
The four position key-switch allows for mode selection:-
• Auto Mode
• Auto mode with manual return to Mains
• Run generator off load
• Run generator on load
A clear mimic diagram with‘International’ symbols and LEDsprovide clear indication of supplyavailability and load switching status.Further LED indication is provided for ‘Start delay in progress’ and ‘Mains return timer active’. Two userconfigurable LED’s are provided toallow the user to display specific states(defaulted to indicate that the closingprocedure of the Mains or Generatorcircuit breaker has been started).
Five user configurable relaysare provided to allow control of contactors, different circuit breaker types and engine controlmodules and alarm systems.
The controller features a self seekingpower supply which will utilise powerfrom the Mains AC supply or theGenerator AC supply. A DC supply to the module is not essential for basicoperation, though some ‘higher’functions require it (such as systemdiagnostics).
The module is mounted in a robustplastic case, connection to the module is via plug and socket connectors.
TemTransfer Automatic Changeover Controller
page 101 The Ultimate Safety Breaker
ACCESSORIES FOR DUAL SUPPLY CHANGEOVER SYSTEMS
ACCESSORIES
ON/OFFSTATUS
Specifications
DC Supply
The TemTransfer is normally powered from the AC sensing supplies. It will only draw power from the DC supply if both AC suppliesare not present.
DC power should be supplied from a low voltagesupply between 8 to 35V continuous. It is able to operate at 0V for 50ms during cranking,providing supply was at least 10V before dropoutand supply recovers to 5V. This is achievedwithout the need for internal batteries.
Maximum operating current:150mA @ 12V, 95mA @ 24V.
Maximum standby current (AC powered supply)34.7 mA @ 115V. 16.1mA @ 230V.
3 Low voltage auxiliary relay contacts: 8Amp DC rated 1 each: NO+NC C/O (a and b C/O contacts)
2 Mains rated relay contacts: 8Amp RMS rated 1 each NO+NC. (a and b contacts)
Dimensions: 96 x 144 x 155 DIN STANDARD.
Operating temperature range:-15 to +55oC
Indication LED’s:Mains Available/On Load, GeneratorAvailable/On load, Start Delay, Mains ReturnDelay and 2 User Configurable.
Operating voltage: - Specify on ordering.
AC Voltage Input Range (for AC PoweredOperation): 115V Version:- 88 - 160 V ac RMS230V Version:- 176 - 305 V ac RMS
AC Voltage Input/Adjustment Range (Sensing Operation):115V Version:- 55 - 152 V ac RMS230V Version:- 110 - 304 V ac RMSAC Frequency Input/Adjustment Range:10 - 75 Hz
Schematic Diagram:Automatic ChangeoverSystem with TemTransferand TemBreak 2Interlocked MCCBs
STATUS
STATUSGenerator Mains
START
SE
CT
ION
6
The Ultimate Safety Breaker page 102
INSTALLATION
TEMBREAK 2
MOULDED CASE CIRCUIT BREAKERS16A TO 1600A
1. Welcome to TemBreak 2
2. Ratings and Specifications
3. Operating Characteristics
4. Application Data
5. Accessories
6. Installation
• Connection and Mounting Options and Accessories 103
• Insulation Distances 108
• Mounting Angle 110
• Direction of Power Supply 110
• Standard Installation Environment and Special Treatments 111
• Temperature Ratings 112
7. Dimensions
page 103 The Ultimate Safety Breaker
TemBreak 2 MCCBs connection andmounting accessories facilitate easy installationin any arrangement. Breakers and accessoriesare easy to fit. They are designed to providesafe and secure termination and mountingpoints. 125A and 160A/250A frame modelshave a choice of 45mm front cutout patterns
Overview of Connection and Mounting Accessories
Please refer to Section 2, Ratings and Specifications, for details of the connection and mountingoptions which are available for each model.
Please refer to Section 7, Dimensions, for detailed dimensions of connection and mounting optionsand accessories.
Note that one set of mounting screws is supplied as standard with every circuit breaker or switchdisconnector purchased.
Connection and mounting options overview diagram
CONNECTION AND MOUNTING OPTIONS AND ACCESSORIES
INSTALLATION
Optional 45mm Cutout Patterns
45mm
SE
CT
ION
6
The Ultimate Safety Breaker page 104
This connection method is standard for all front connected (FC) MCCB models. Solid conductors or cables terminated with crimp lug terminals can be used.
Serrated Terminal Surface
Each terminal on 160A and 250A models has aserrated surface. This provides excellent grip forheavy cables terminated with crimp lug terminals,thereby preventing sideways rotation of the lug.
Connection of Large Conductors and Multiple Conductors
Extension bars (FB) are terminal extensions which can be fitted to lineor load side terminals and are used to connect large conductors andmultiple conductors. Available for field fitting in sets of 3 or 4 bars.
*H125 and L125 are 250A frame size
INSTALLATION
CONNECTION AND MOUNTING OPTIONS AND ACCESSORIESConnection of Busbars and Terminated Cables
Maximum Dimensions of Compression Terminals
Frame Size (A) 125* 160 & 250 400 & 630
Width, W (mm) 17 25 25
Diameter, d (mm) 9 9 11
Maximum from centre to tip, e(mm) 8.5 10 12
page 105 The Ultimate Safety Breaker
Cable clamp terminals (FW) can be used to secure stranded cable directly to the MCCB. Availablefor field fitting in sets of 3 or 4.
CONNECTION AND MOUNTING OPTIONS AND ACCESSORIESDirect Entry of Stranded Cable
Rear connections (RC) allow termination of conductors in a different switchboardcompartment to the MCCB body.
The stud can be rotated in steps of 45 degrees on a 125A to 630A frame MCCBs and 90degrees on a 800A frame MCCBs in the field.
Termination in Separate Compartment
INSTALLATION
MCCB Model Cable Capacity (mm2)
E125, S125, S125-NF 1.5 to 50 (1 cable)
H125, L125, S160-NF 1.5 to 70 (1 cable)
S160, E250, S250, H250, L250 35 to 120 (1 cable)
E400, S400, H400, L400 80 to 240 (1 cable)
60 to 120 (2 cables)
SE
CT
ION
6
The Ultimate Safety Breaker page 106
The plug in mounting system allows fast replacement of the MCCB body without the need to disturbthe terminations. Solid conductors or cables terminated with compression terminals can be used.
Plug-In Safety Lock
The plug-in MCCB body is automatically locked to the base when the contacts are closed (toggle ON). It cannot be removed unless the contacts are in the isolated position (toggle OFF or TRIPPED). This system ensures safe removal of the MCCB from the base. Plug-in safety lock is available from125A to 800A frame models.
The connection bars for plug-in bases are optional and can be configured in the field either for frontor rear access. The illustrations below show possible mounting and connection options for plug inbases. These mounting and connection options are available from 125A to 800A frame models.
1. Mounted on base plate withconnection bars mounted forfront access.Insulation plates are suppliedas standard and must be fitted.
2. Terminations in separate compartment. Connection barsare mounted for top access at thetop and rear access at the bottom.
3. Mounted on angle bars.Connection bars aremounted for rear access.
INSTALLATION
CONNECTION AND MOUNTING OPTIONS AND ACCESSORIESPlug-in Mounting
Plug-in connections and safety lock are fittedto the back of the MCCB
Plug-in MCCB and base
Safety Lock
IP2X
InsulationPlates
Note: Plug-in mounting for 1250A frame model is availablefor only “Mounted on angle bars”, and safety trip canbe specified as option.
page 107 The Ultimate Safety Breaker
The DIN rail adaptor is easily fitted to the rear of 3 pole E125 and S125 models to allow clipmounting of the MCCB to 35mm DIN rail.
The 45mm cutout of TemBreak 2 devices makes them suitable for mounting alongside modulardevices in distribution boards.
CONNECTION AND MOUNTING OPTIONS AND ACCESSORIESMounting on 35mm DIN Rail
INSTALLATION
45mm
A range of flanges which improves the appearance of door cutouts is available. These aresuitable for toggle-operated and motor-operated MCCBs and switch-disconnectors.
Door Flanges
SE
CT
ION
6
The Ultimate Safety Breaker page 108
The insulation distances between the MCCB and earthed metal parts and insulators shown in this section must be maintained to prevent arcing faults occurring due to conductive ionised gas. In cases where other specifications require different insulation distances to those shown here, the greater distance must be maintained. In cases where two different models are installed one above the other, the insulation distance between the two models should be as for the lower model.
INSTALLATION
INSULATION DISTANCES
1. Insulation plate
2. Top plate (earthed metal)
3. Insulation tube or tape
4. Front-connected type
5. Front-connected type with extension bar
6. Rear-connected type, plug-in type
7. Side panel
8. A. Distance from lower breaker to exposed live part of upper breaker terminal (front-connected type) or distance from lower breaker to end face of upper breaker (rear-connected type or plug-in type)
B1. Distance from end face of breaker to top plate
B2. Distance from end face of breaker to insulation plate
C. Gap between breakers
D. Distance from side of breaker to side panel (earthed metal)
E. Dimensions of insulation over exposed conductors
Exposed conductors must be insulated up to the breaker terminals. Interpole barriers or optional terminalcovers are recommended. If optional terminal covers are used, insulate the exposed conductor until it overlapsthe terminal cover.
ATTENTION
page 109 The Ultimate Safety Breaker
INSULATION DISTANCE IN mm (AT 690V AC MAXIMUM)
INSTALLATION
Model Type A B1 B2 C D E
E125 NJ 50 40(2) 10 0 25 *(1)
S125 NF 50 40(2) 10 0 25 *(1)
S125 NJ 50 40(2) 10 0 25 *(1)
S125 GJ 75 45 25 0 25 *(1)
H125 NJ 100 80 60 0 50 *(1)
L125 NJ 100 80 60 0 50 *(1)
S160 NF 50 40 30 0 25 *(1)
S160 NJ 50 40 30 0 25 *(1)
S160 GJ 100 80 60 0 50 *(1)
H160 NJ 100 80 60 0 50 *(1)
L160 NJ 100 80 60 0 50 *(1)
E250 NJ 50 40 30 0 25 *(1)
S250 NJ 50 40 30 0 25 *(1)
S250 NE 50 40 30 0 25 *(1)
S250 GJ 100 80 30 0 25 *(1)
S250 GE 100 80 30 0 25 *(1)
S250 PE 100 80 60 0 50 *(1)
H250 NJ 100 80 60 0 50 *(1)
H250 NE 100 80 60 0 50 *(1)
L250 NJ 100 80 60 0 50 *(1)
E400 NJ 100 80 40 0 30 *(1)
S400 CJ 100 80 40 0 30 *(1)
S400 NJ 100 80 40 0 30 *(1)
S400 GJ 100 80 40 0 30 *(1)
S400 GE 100 80 40 0 30 *(1)
S400 PJ 100 80 40 0 30 *(1)
S400 PE 100 80 40 0 30 *(1)
H400 NE 120 120 80 0 80 *(1)
L400 NE 120 120 80 0 80 *(1)
E630 NE 120 100 80 0 80 *(1)
S630 CE 120 100 80 0 80 *(1)
S630 GE 120 100 80 0 80 *(1)
S800 CJ 120 100 80 0 80 *(1)
S800 NJ 120 100 80 0 80 *(1)
S800 NE 120 100 80 0 80 *(1)
S800 RJ 150 120 80 0 80 *(1)
S800 RE 150 120 80 0 80 *(1)
H800 NE 120(3) 120 80 0 80 *(1)
L800 NE 120(3) 120 80 0 80 *(1)
S1000 SE 150 120 80 0 80 *(1)
S1000 NE 150 120 80 0 80 *(1)
S1250 SE 150 120 80 0 80 *(1)
S1250 NE 150 120 80 0 80 *(1)
S1250 GE 150 150 100 0 100 *(1)
S1600 SE 150 150 100 0 100 *(1)
S1600 NE 150 150 100 0 100 *(1)
*Note: (1) Insulate the exposed conductor until it overlaps the moulded case at the terminal, or the terminal cover.(2) 10mm at 440V AC Maximum.(3) Take care that arc gases are emitted to both line and load sides.
SE
CT
ION
6
The Ultimate Safety Breaker page 110
TemBreak 2 MCCBs may be mounted at any angle without affecting performance.
Power can be supplied through TemBreak 2 MCCBs in either direction without loss of performance.
INSTALLATION
MOUNTING ANGLE
DIRECTION OF POWER SUPPLY
Mounting angle does not affect performance.
page 111 The Ultimate Safety Breaker
TemBreak 2 MCCBs are intended for installation in the following conditions as standard:
• Operating ambient temperature -5 degrees C to 45 degrees C. Refer to page 112 for thermalderating information above this temperature.
• Relative humidity of up to 85%.
• Altitude up to 2000m.
• Atmospheres free from dust, smoke, corrosive gases, inflammable gases, moisture and salt.
For installation in conditions more onerous than those described above, contact Terasaki for details.
The following special treatments have been developed for installation in specific environmental conditions:
• Low temperature treatment.For installation attemperatures down to -40degrees C for storage and -20 degrees C for operation. The environment must be free from rapid changes intemperature that result in theformation of condensation.
• Fungus-moisture proofing.For installation attemperatures up to 65degrees C and relative humidity of up to 95%. The environment must befree from rapid changes intemperature.
• Anti-corrosion treatment.MCCB is surface treated to increase resistance tocorrosion. If the MCCB is to be installedin atmosphere that containsexcessive volumes of corrosive gases or moisture, it should behouse in an airtight enclosure.
STANDARD INSTALLATION ENVIRONMENT
AND SPECIAL TREATMENTS
INSTALLATION
The Ultimate Safety Breaker page 112
SE
CT
ION
6
The Ultimate Safety Breaker page 112
INSTALLATION
TEMPERATURE RATINGS
Rated Current (A)
E125-NJ Front 20A 19 18.5 18 17.5S125-NJ Rear 32A 31 30.5 30 29S125-GJ Plug-in 50A 48 45 43 41
63A 60 57 55 52100A 97 94 90 87125A 121 117 113 109
H125-NJ Front 20A 19 18.5 18 17.5L125-NJ Rear 32A 31 30 29 28
Plug-in 50A 48 47 45 4463A 61 59 57 55100A 97 95 92 89125A 121 118 114 111
S160-NJ Front 20A 19 18.5 18 17.5Rear 32A 31 30 29 28
S160-MJ Plug-in 50A 48 46 44 42S160-GJ 63A 61 59 57 55
100A 97 94 91 88125A 121 117 113 109160A 156 151 146 141
H160-NJ FrontL160-NJ Rear 160A 156 151 147 143
Plug-inE250-NJ Front 20A 19 18.5 18 17.5
Rear 32A 31 30 29 28Plug-in 50A 48 46 44 42
63A 61 59 57 55100A 97 94 91 88125A 121 117 113 109
E250-NJ Front 160A 156 151 146 141S250-NJ Rear 250A 243 235 227 219S250-GJ Plug-inH250-NJ FrontL250-NJ Rear 160A 156 151 147 143
Plug-inFront
250A 244 237 230 223Rear
E400-NJ Front 250A 244 237 230 223S400-CJ Rear 400A 390 380 369 358S400-NJ Plug-inS400-GJS400-PJS800-CJ Front 630A 615.2A 600.1A 584.7A 569.4AS800-NJ Rear 800A 779.7A 758.9A 737.9A 716.9AS800-RJ Plug-in
Calibration Temperature: 45°C
Calibration Temperature: 30°C
MCCB Type Connection Rating at calibrationType temperature (45°C) 50°C 55°C 60°C 65°C
Rated Current (A)MCCB Type Connection Rating at calibrationType temperature (30°C) 35°C 40°C 45°C 50°C 55°C 60°C 65°C
H250-NJ Plug-in Conn. 250A 244 236 225 219 209 200 190L250-NJ
*Contact us for details of plug-in versions
page 113 The Ultimate Safety Breaker
Rated Current (A)MCCB Type Connection RatingType 30°C 35°C 40°C 45°C 50°C 55°C 60°C 65°C
S250-NE Front 250A 250 250 250 250 237.5 225 200 200S250-GE Rear
Plug-in 250A 250 237.5 225 225 200 200 157.5 157.5S250-PE Front 250A 250 250 250 250 237.5 225 200 200H250-NE RearS400-NE Front 250A 250 250 250 250 250 250 225 200S400-GE Rear 400A 400 400 400 400 400 380 360 320S400-PE Plug-inH400-NE Front 250A 250 250 250 250 250 250 225 200L400-NE Rear 400A 400 400 400 400 400 380 360 320
Plug-in 250A 250 250 250 250 250 250 225 200400A 400 400 400 400 400 380 360 320
E630-NE Front 630A 630 630 630 630 630 598.5 567 504S630-CE Rear*S630-GES800-NE Front 630A 630A 630A 630A 630A 630A 598.5A 567A 504AS800-RE Rear 800A 800A 800A 800A 800A 760A 720A 640A 504A
Plug-inH800-NE Front 630A 630A 630A 630A 630A 630A 598.5A 567A 504AL800-NE Rear 800A 800A 800A 800A 800A 720A 640A 504A 504A
Plug-inS1000-SE Front 1000A 1000A 1000A 1000A 1000A 900A 800A 630A 630AS1000-NE RearS1250-SE Front 1250A 1250A 1250A 1250A 1250A 1125A 1000A 787.5A 787.5AS1250-NE RearS1250-GE Plug-inS1600-SE Front 1600A 1600A 1600A 1600A 1600A 1520A 1440A 1280A 1008AS1600-NE Rear
INSTALLATION
TEMPERATURE RATINGS
The Ultimate Safety Breaker page 114
SE
CT
ION
7
DIMENSIONS
TEMBREAK 2
MOULDED CASE CIRCUIT BREAKERS 16A TO 1600A
1. Welcome to TemBreak 2
2. Ratings and Specifications
3. Operating Characteristics
4. Application Data
5. Accessories
6. Installation
7. Dimensions• S125-NF, S160-NF 115
• E125-NJ, S125-NJ, S125-GJ, S125-NN 116
• S160-NJ, S160-GJ, E250-NJ, S250-NJ, S250-GJ, S250-NN 118
• H125-NJ, L125-NJ, H160-NJ, L160-NJ, S250-NE, S250-GE, S250-PE, H250-NJ, H250-NE, L250-NJ 120
• E400-NJ, S400-CJ, S400-NJ, S400-GJ, S400-PJ, S400-NE, S400-GE, S400-PE, S400-NN 122
• H400-NE, L400-NE 124
• E630-NE, S630-CE, S630-GE, S630-NN 126
• S800-CJ, S800-NJ, S800-RJ, S800-NE, S800-RE, S800-NN 128
• H800-NE, L800-NE 130
• S1000-SE, S1000-NE, S1000-NN 132
• S1250-SE, S1250-NE, S1250-GE, S1250-NN 133
• S1600-SE, S1600-NE, S1600-NN 135
• Operating Handles 137
• Terminal Covers 149
• Interpole Barriers 152
• Terminal Blocks for Front-Connected and Rear-Connected MCCBs 153
• OCR Power Supply for Electronic Protection
Standard type 155
With LCD 157
• Slide Interlocks 158
• Link Interlocks 163
• Wire Interlocks 169
• Position of Trip Button 176
• External Neutral CT/Door Flanges 177
page 115 The Ultimate Safety Breaker
DIMENSIONS
S125-NF, S160-NF
SE
CT
ION
7
The Ultimate Safety Breaker page 116
DIMENSIONS
With extension bars (optional)
Panel hinge position (hatching area)bottom view
HL
154±
1
8.5
100
17
200150
100
200150
15
M4x0.7Tapped hole
30
132
ø9
8.5(
max
.)
30
17(max.)max.t5
3P
L
Drilling plan
4P
LH H
Preparation of conductor
30 303060 M4X0.7
Tapped hole
ø18ø8.5
16
132
15
5
3030
3030
8
M4X0.7Mountingscrew
134
134
52102
15 30
L L
H
H
L
3P
H
Drilling plan
4P
Stud can beturned 45˚or 90˚
Conductoroverlap max.
Mounting plate(max. t3.2)
Panel cutout(Front view)
Panel cutout dimensions showngive an allowance of 1.5mmaround the handle escutcheon.
HL
6110
3.5
4P3P
6090
4561
24
134
8
155
47
90 10645
164.55.5
154
10
28(max.)
30 30 30
45 75
Interpole barrier(removable) Mounting hole
Connector plug
Front panel t2
M8 screw
M4x0.7Mounting screw
Operating knob
HLHL
CL
CLCL
6110645
164.55.5
154
28(max.)
Connector plug
Front panel t2Operating knob
CL
90
155
45
4P3P
R1
21.514.5
155
148
Pad lock
8690
Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.
48
E125-NJ, S125-NJ, S125-GJ, S125-NN
page 117 The Ultimate Safety Breakerpage 117 The Ultimate Safety Breaker
DIMENSIONS
8.5
8.5
3.2t
3.2t
14.2 14.2
22.2 22.2
Detail of connecting partOriented for rear access
8.5
8.5
3.2t
3.2t
14.2 14.2
22.2 22.2
Detail of connecting partOriented for rear access
Detail of connecting part
8.5
3.2t
812
5
Oriented for front access
21.8
Note that the insulation plate (supplied as standard) must be fitted between the base and the backplate.
6.5
5 (max.)
10 (max.)
Preperation of conductor
15 (max.)
8.5
2- 6 4- 6
2- 6 4- 6
(rear view) Drilling plan(front view)
(rear view) Drilling plan(front view)
3P
Mounting Plate
Mounting Plate
4P
3P
1715 15
30 30 30 30 30
30 60
185
152
88
17
4P 3P 4P
3P 4P
30
17 17 1530 30 30 30 30
94 12460
180
102
113
155
3.2t
3.2t
12110197
60.268.2
Support or rail
Support or rail
Mounting screwM6x14 max.
Mounting on a support or rails (shown with optional connection bars oriented for rear access)
Termination of Busbar
Mounting through the backplate (shown with optional connection bars oriented for rear access)
Mounting on the backplate (optional connection bars must be oriented for front access)
Mounting Plate
Mounting Screw M5x20a
27 22.24
(61)
(61)
45
168
(rear view)
3P 4P
Drilling plan(front view)
4- 64- 6
3P
17.5 22.5
37.5 75
35 70
15 15
50
4P
max
105
45
4
102
155
155
3.2t
3.2t
21.8
168
148144
21.81
Insulating plate
Mounting plate
Insulating plateMounting screw M5 NUT
E125-NJ, S125-NJ, S125-GJ, S125-NN Plug-in Versions
The Ultimate Safety Breaker page 118
SE
CT
ION
7
The Ultimate Safety Breaker page 118
DIMENSIONS
With extension bars (optional)
Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.
48
S160-NJ, S160-GJ, E250-NJ, S250-NJ, S250-GJ, S250-NN
page 119 The Ultimate Safety Breakerpage 119 The Ultimate Safety Breaker
S160-NJ, S160-GJ, E250-NJ, S250-NJ, S250-GJ, S250-NN
Plug-in Versions
9
6 (max.)
15.5 (max.)
Preperation of conductor
22 (max.)
Mounting on a support or rails (shown with optional connection bars oriented for rear access)
Mounting through the backplate (shown with optional connection bars oriented for rear access)
Mounting on the backplate (optional connection bars must be oriented for front access)
Mounting screwM8x18 max.
Support or rail
Support or rail
45
4
27
102
42
88
116
172
4t4t
165
97
(61)
101
121
76.5
M5x20Mounting screw
Mounting plate
45
(61)
102
22
160
4t
2020
165
144
168
1484
122
Insulating plate
Mounting screw M5 NUT
Insulating plate
Mounting plate
Termination of Busbar
DIMENSIONS
The Ultimate Safety Breaker page 120
SE
CT
ION
7
The Ultimate Safety Breaker page 120
With extension bars (optional)
Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.
48
H125-NJ, L125-NJ, H160-NJ, L160-NJ, S250-NE, S250-GE,
S250-PE, H250-NJ, H250-NE, L250-NJ
DIMENSIONS
page 121 The Ultimate Safety Breakerpage 121 The Ultimate Safety Breaker
H125-NJ, L125-NJ, H160-NJ, L160-NJ, S250-NE, S250-GE,
H250-NJ, L250-NJ. Plug-in Versions
9
6 (max.)
15.5 (max.)
Preperation of conductor
22 (max.)
Mounting on a support or rails (shown with optional connection bars oriented for rear access)
Mounting through the backplate (shown with optional connection bars oriented for rear access)
Mounting on the backplate (optional connection bars must be oriented for front access)
Mounting screwM8x18 max.
45
4
27
102
42
88
116
172
4t4t
165
132
96
136
156
76.5
M5x20Mounting screw
Mounting plate
45
96
102
22
160
4t
2020
165
179
203
1834
122
Insulating plate
Mounting screw M5 NUT
Insulating plate
Mounting plate
Support or rail
Support or rail
Termination of Busbar
DIMENSIONS
The Ultimate Safety Breaker page 122
SE
CT
ION
7
The Ultimate Safety Breaker page 122
With extension bars (optional)
With extension bars (optional)
30
30
E400-NJ, S400-CJ, S400-NJ, S400-NE, S400-GJ, S400-GE,
S400-PJ, S400-PE, S400-NN
DIMENSIONS
page 123 The Ultimate Safety Breakerpage 123 The Ultimate Safety Breaker
E400-NJ, S400-CJ, S400-NJ, S400-NE, S400-GJ, S400-GE,
S400-PJ, S400-PE, S400-NN Plug-in Versions
11
8 (max.)
20 (max.)
Preperation of conductor
30 (max.)
Support or rail
Support or rail
Mounting screwM10x30 max.
Mounting screw M5 x 20
Mounting plate
90102
260
97
4
102113
48
138142
180
6t
6t19
825
8
65
276
90102
260
971
4
32
6t
32
204208
246
12
1
Insulating plate
Mounting plate
Mounting M6 NUT
Insulating plate
Mounting screw M6x70
Mounting on a support or rails (shown with optional connection bars oriented for rear access)
Mounting through the backplate (shown with optional connection bars oriented for rear access)
Mounting on the backplate (optional connection bars must be oriented for front access)
Termination of Busbar
DIMENSIONS
The Ultimate Safety Breaker page 124
SE
CT
ION
7
The Ultimate Safety Breaker page 124
With extension bars (optional)
With extension bars (optional)
H400-NE, L400-NE
DIMENSIONS
page 125 The Ultimate Safety Breakerpage 125 The Ultimate Safety Breaker
H400-NE, L400-NE. Plug-in Versions
11
8 (max.)
20 (max.)
Preperation of conductor
30 (max.)
Support or rail
Support or rail
188
188
Mounting screwM10x30 max.
Mounting on a support or rails (shown with optional connection bars oriented for rear access)
Mounting through the backplate (shown with optional connection bars oriented for rear access)
Mounting on the backplate (optional connection bars must be oriented for front access)
Mounting screw M5 x 20
Mounting plate
90102
260
134
4
102113
48
175179
217
6t
6t19
825
8
65
276
90102
260
1341
4
32
6t
32
241245
283
12
133
Insulating plate
Mounting plate
Insulating plate
Mounting screw M6x70
Termination of Busbar
DIMENSIONS
The Ultimate Safety Breaker page 126
SE
CT
ION
7
The Ultimate Safety Breaker page 126
With extension bars (optional)
30
E630-NE, S630-CE, S630-GE, S630-NN
DIMENSIONS
page 127 The Ultimate Safety Breakerpage 127 The Ultimate Safety Breaker
E630-NE, S630-CE, S630-GE, S630-NN with Motor Operators
With extension bars (optional)
30
DIMENSIONS
The Ultimate Safety Breaker page 128
SE
CT
ION
7
The Ultimate Safety Breaker page 128
3PHL
4PHL
HLHL
HL 3PHL
4PHL
ø48
ø15
8
(15.
5)
263
126
117
243
160 15
610
1.9
26
55
2532
20
103
122
4210
137.516
140
(19.8)
(18)
200.512.5
213
99.5 43434343 7070707070
13
707070
1328
70 70
(15.
5)
(19.8)
(18)
ø13
101.
9
101.
9
126
117
160
160 15
6
110
25832
15
8027
380
140
16 137.5
13
12.5 200.5
213
99.5
1328
70
W
L1t1
L2t2
280175105
707070
210140
136
ASL ASL ASL ASL
ASL ASL ASL
ASL
HL
8 16
200.
5
100100
200200150150
ASLASL
4P3P
ASL
3P 4P
3P 4P
ASL ASL ASL
ASL
HL HL
HL HL
HL HLHL
HL
Drilling plan (front view) Panel cutout (front view)
Drilling plan (front view)
Conductor overlap, max
Conductor overlap, max
M8Tapped hole
M8Tapped hole
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Interpole barrier (removable) Mounting hole
M8Mounting screw
M8Mounting screw
Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.
Trip button (red)
Toggle extension (removable)
Toggle extension(removable)
Stud can be turned 90° ø15 for accessory wiring
when necessary
Groove for dissipating heat generated by overcurrent
Drilling plan (front view)
Connector plug
Front Panel
Front Panel
Interpole barrier(removable)
M8Mounting screw
Panel cutout dimensions shown give an allowance of 1.5mm around motor operator.
M8Tapped hole
M8Tapped hole
Mounting hole
Drilling plan (front view)
Panel cutout (front view)
Con
duct
or
over
lap,
max
Con
duct
or
over
lap,
max
Stud can be turned 90°
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Manual operating handle (removable)
Manual operating handle (removable)
M8 Mounting screw
Pad lock
Pad lock
Connector plug
ø15 for accessory wiring when necessary
Panel hinge position (hatching area)(bottom view)
3P4P
172
92
R6
70 70 70
13
70 70 70 70 70 43 43 43 43
117
1
26
122
1
03
20
32
25
136
5
1
27
5
30.
5 3P
4P
ø13
8
ø48
ø13
70 70 103
28 13
145
10
80.5
117
126
127.5
42
8
140
210
70 70 70
105 175
280
70
W
13
70
80
273
8
0
15
32 8
25
55.
5 4
6.5
110
117
1
26
141
1
32
170
51
90
103
145
28 13
127.5 80.5
51
170
t1 L1
t2 L2
Front connected
Rear connected
Front connected with Motor Operator
Rear connected with Motor Operator
8
S800-CJ, S800-NJ, S800-RJ, S800-NE, S800-RE, S800-NN
DIMENSIONS
Breaker type Rated current t1 t2 L1 L2 WS800-CJ, S800-NJ,S800-RJ, S800-NN
630A 8 8 32 34 40800A 10 10 32 35 40
S800-NE, S800-RE630A 8 8 32 36 40800A 10 10 32 36 40
Breaker type Rated current t1 t2 L1 L2 WS800-CJ, S800-NJ, S800-RJ,S800-NN
630A 8 8 32 34 40800A 10 10 32 35 40
S800-NE, S800-RE630A 8 8 32 36 40800A 10 10 32 36 40
page 129 The Ultimate Safety Breakerpage 129 The Ultimate Safety Breaker
S800-CJ, S800-NJ, S800-RJ, S800-NE, S800-RE. Plug-in Versions
DIMENSIONS
ø13
10 (max.)
25 (max.)
17
Preperation of conductor
40 (max.) Mounting screw M12✕25 max. Hex. sec. head bolt.
Mounting on a support or rails
Outline Dimensions
Mounting through the backplate (shown with optional connection bars oriented for rear access)
Mounting on the backplate (optional connection bars must be oriented for front access)
Termination of Busbar
HL HL
HL HL
HL HL
HL HL
HL HL
HL HL
ASL
3P 4P
ASL
ASL
ASL
ASL
3P 4P
ASL
3P 4P
ASL
3P 4P
3P 4P
ASL
3P 4P
ASL
3P 4P
ASL
HL HL
ASL
ASL
105 280
103
145
127.5 210 51.6
116
175
158
.5
46.
5
126
308
3
50
117
80.5
103
145
127.5 51.6
116
126
308
3
50
117
80.5
55.5
132
141
149.
5
90
70 70 70 70 70
170
40.5
182
6
3 6
3 2
1 2
1 7
9.5
70.
5
70 70 70 70 70
70 70 70
40.5
65 81
193
293
308
273
102
90
18
112148163
10t
10t
6630
8144
ø13 R6.52140
10t
13
25
R6.5
21
40
13
1725
169.
516
0.5
330
160.
515
1.5
70 70 70 70 70 40
284
177107
1053570
214
312
105
140
ø1366
30
8144
5317
68
4-ø9
R6.52140
10t
1317
25
ø13
10t
ø13
280 210 105 175
100 170
50
79.
5 7
0.5
15
15
ø9
279
279
53
272
102
90
44
10t
10t
1
1715
44 1
137
179
8
8 220
262
ø13
25
6630
8144
ø13 R6.521
4010
t
13
25
1725
ø1366
30
8144
R6.521
4010
t
1317
25
ø13
ø13
25
144
135
8
8
ø13
Detail of connecting part Oriented for rear access
Detail of connecting part Oriented for front access
Terminal bars should be connected alternatelyon adjacent poles.
Detail of connecting part Oriented for rear access
Terminal bars should be connected alternatelyon adjacent poles.
Drilling plan (front view)(rear view)
Drilling plan (front view)(rear view)
Mounting hole
M8Mounting screw
Trip button (red)
Toggle extension (removable)
M8Mounting screw
Mounting plate
Mounting plate
Pan head screw M8✕16
Mounting plate
Toggle extension (removable)
Mounting base (rear view)
Toggle extension (removable)
Drilling plan (front view)
M8✕80
Insulating plate
Mounting plate
Insulating plate
Toggle extension (removable)
51
170
100
51
170
The Ultimate Safety Breaker page 130
SE
CT
ION
7
The Ultimate Safety Breaker page 130
H800-NE, L800-NE
DIMENSIONS
HL
L2
630A
Rated current
800A
73
74
L2
630A
Rated current
800A
73
74
Panel cutout (front view)
Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.
Panel cutout dimensions shown give an allowance of 1.5mm around motor operator.
Panel cutout (front view)
Drilling plan (front view)
Drilling plan (front view)
Conductor overlap, max
Conductor overlap, max
M8Tapped hole
M8Tapped hole
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Interpole barrier (removable)
Mounting hole
M8Mounting screw
M8Mounting screw
Trip button (red)
Toggle extension (removable)
Toggle extension(removable)
Stud can be turned 90° ø15 for accessory wiring
when necessary
Groove for dissipating heat generated by overcurrent
Drilling plan (front view)
Front Panel
Interpole barrier(removable)
M8Mounting screw
M8Tapped hole
Mounting hole
Con
duct
or
over
lap,
max
Manual operating handle (removable)
Pad lock
Connector plug
Connector plug
Front Panel
M8Tapped hole
Drilling plan (front view)
Con
duct
or
over
lap,
max
Stud can be turned 90°
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Manual operating handle (removable)
M8 Mounting screw
Pad lock
ø15 for accessory wiring when necessary
Groove for dissipating heat generated by overcurrent
Panel hinge position (hatching area)(bottom view)
3P4P
172
92
R6
Front connected
Rear connected
Front connected with Motor Operator
Rear connected with Motor Operator
HL
101.
916
0
140
ASL
HL HL
HL HL
HLHL HL
ASL ASL ASL
4P
4P
ASL
3P
3P
4P
ASL ASL
3P
70140 105
70
7070
15
164.5175
13
140
182
10 L2
10 69
210 280
40 70
65 117
126
1546
.5
110
8055
.525 8
32
273
80
140
65 15
70 70 70
13
70 70 70 70 7043 43 43 43
117
126
10
42
2032
25
136
512
75
30.5
126
117
3P4P
ø13
ø13
ø48
8
8
8
122
164.518280.5
80.5
90
51
7070
51
170170
3PHL
4PHL
HL
(19.8)
(18)
ø13
101.
9
126
117
160 15
6
110
25832
15
8027
380
16 174.5
13
237.5
250
136.5
70
40
280175105
707070
210140
ASL ASL ASL ASL
15
10 L2
10 69
65
12.5
(15.
5)
HL
8(15.
5)
160 15
610
1.9
2532
20
140
122
174.516
140
(19.8)
(18)
237.512.5
250
136.5
13
707070
136
ASL
HL HL4P
ASL
3P
70 70 70 70 7043 43 43 43
117
126
136
512
75
30.5
ø48
7070
65 15
10
4212
611
7
HL
8 16
237.
5
100100
200200150150
ASL
page 131 The Ultimate Safety Breakerpage 131 The Ultimate Safety Breaker
H800-NE, L800-NE. Plug-in Versions
DIMENSIONS
ø13
10 (max.)
25 (max.)
17
Preperation of conductor
40 (max.) Mounting screw M12✕25 max. Hex. sec. head bolt.
Mounting on a support or rails
Outline Dimensions
Mounting through the backplate (shown with optional connection bars oriented for rear access)
Mounting on the backplate (optional connection bars must be oriented for front access)
Termination of Busbar
HL HL
HL HL
HL HL
HL HL
HL HL
HL HL
ASL
3P 4P
ASL
ASL
3P 4P
ASL
3P 4P
ASL
3P 4P
3P 4P
ASL
3P 4P
3P 4P
ASL
HL HL
ASL
105 280
210
116
175
158
.5
46.
5
126
308
3
50
117
126
308
3
50
117
55.5
132
141
149.
5
90
70 70 70 70 70
170
40.5
182
6
3 6
3 2
1 2
1 7
9.5
70.
5
70 70 70 70 70
70 70 70
40.5
65 81
193
293
308
273
102
90
112148163
10t
10t
6630
8144
ø13 R6.52140
10t
13
25
R6.5
21
40
13
1725
169.
516
0.5
330
70 70 70 70 70 40
284
177107
1053570
214
312
105
140
ø1366
30
8144
5317
68
4-ø9
R6.52140
10t
1317
25
ø13
10t
ø13
280 210 105 175
100 170
50
79.
5 7
0.5
15
15
ø9
279
279
53
272
102
90
44
10t
10t
1
1715
44 1
174
216
8
8 257
299
ø13
25
6630
8144
ø13 R6.521
4010
t
13
25
1725
ø1366
30
8144
R6.521
4010
t
1317
25
ø13
ø13
25
144
135
51.6
51.6 116
160.
515
1.5
ø13
18
Detail of connecting part Oriented for rear access
Detail of connecting part Oriented for front access
Terminal bars should be connected alternatelyon adjacent poles.
Detail of connecting part Oriented for rear access
Terminal bars should be connected alternatelyon adjacent poles.
Drilling plan (front view)(rear view)
Drilling plan (front view)(rear view)
Mounting hole
M8Mounting screw
Trip button (red)
Toggle extension (removable)
M8Mounting screw
Mounting plate
Mounting plate
Pan head screw M8✕16
Mounting plate
Toggle extension (removable)
Mounting base (rear view)
Toggle extension (removable)
Drilling plan (front view)
Insulating plate
Mounting plate
Insulating plate
Toggle extension (removable) M8✕80
51
170
100
51
170
ASL
182164.5
1408
80.5
ASL
182164.5
1408
80.5
ASL
ASL
The Ultimate Safety Breaker page 132
SE
CT
ION
7
The Ultimate Safety Breaker page 132
HLHL HL
HL HL
HL HL
HL
8
ASL
117
127.5
ø13
45
103
28 13
145
25 8
32 20 126
13
80.5
ø13
45
25 8
32 20 126
13
117
3PHL
4PHL
HLHL
HL 3PHL
4PHL
ø48
ø15
(15.
5)
263
126
117
160 15
610
1.9
26
55
103
122
137.516
140
(19.8)
(18)
200.512.5
213
99.5 43434343 7070707070
1328
70 70
(15.
5)
(19.8)
(18)
ø13
101.
9
101.
9
126
117
160
160 15
6
110
25832
15
8027
380
140
16 137.5
13
12.5 200.5
213
99.5
1328
70
45
3214
3714
280175105
707070
210140
136
ASL ASL ASL ASL
ASL ASL ASL
ASL
HL
8 16
200.
5
100100
200200150150
ASLASL
4P3P
ASL
3P 4P
3P 4P
ASL ASL ASL
Drilling plan (front view) Panel cutout (front view)
Drilling plan (front view)
Conductor overlap, max
M8Tapped hole
M8Tapped hole
Interpole barrier (removable) Mounting hole
M8Mounting screw
M8Mounting screw
Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.
Trip button (red)
Toggle extension (removable)
Toggle extension(removable)
Vertical direction only
ø15 for accessory wiring when necessary
Groove for dissipating heat generated by overcurrent
Drilling plan (front view)
Connector plug
Front Panel
Front Panel
Interpole barrier(removable)
M8Mounting screw
Panel cutout dimensions shown give an allowance of 1.5mm around motor operator.
M8Tapped hole
M8Tapped hole
Mounting hole
Drilling plan (front view)
Panel cutout (front view)
Con
duct
or
over
lap,
max
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Manual operating handle (removable)
Manual operating handle (removable)
M8 Mounting screw
Pad lock
Pad lock
Connector plug
ø15 for accessory wiring when necessary
Panel hinge position (hatching area)(bottom view)
Conductor overlap, max
Vertical direction only
Conductor overlap, max
3P4P
172
92
R6
70 70 70 70 70 43 43 43 43
117
1
26
136
5
1
27
5
30.
5
ø48
ø13
70 70
3P4P
140
210
70 70 70
105 175
280
70
45
13
70
80
273
8
0
15
32 8
25
55.
5 4
6.5
110
117
1
26
141
1
32
170
51
90
103
145
28 13
127.5 80.5
51
170
14 32
14 37
Front connected
Rear connected
Front connected with Motor Operator
Rear connected with Motor Operator
8
103
1
22
1270 70 70
1270 70 70
S1000-SE, S1000-NE, S1000-NN
DIMENSIONS
page 133 The Ultimate Safety Breakerpage 133 The Ultimate Safety Breaker
S1250-SE, S1250-NE, S1250-GE, S1250-NN
DIMENSIONS
Drilling plan (front view)
Drilling plan (front view)
Interpole barrier (removable)
Mounting hole
M8Mounting screw
M8Mounting screw
Panel cutout (front view)
Panel cutout dimensions shown give an allowance of 1.5mm around the handle escutcheon.
Soft plastic tubing ø50 to be provided on center pole and neutral pole of vertical terminal type for insulation.
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Conductor overlap, max
Conductor overlap, max
Trip button (red)
Toggle extension (removable)
Toggle extension (removable)
ø15 for accessory wiring when necessary
Insulating plate
Mounting plate
Drilling plan (front view)
M8Mounting screw
Pad lock
Conductor overlap, max
Control circuit terminal
Soft plastic tubing ø50 to be provided on center pole and neutral pole of vertical terminal type for insulation.
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Insulating plate
Drilling plan (front view) Panel cutout (front view)
ø15 for accessory wiring when necessaryConductor overlap, max
Mounting plateM8Mounting screw
Panel cutout dimensions shown give an allowance of 1.0mm around motor operator.
HLHLHL
HL
HL HL
ASLASL
4P3P
ASL
4P
ASLASL
3P
ø13
ø13
ø9
45
4P3P
ø9
20
19
7310
171
73
120
1118
3215
184
154
13
45
296
113226
300230
7070707070
4P
3P
110
25
8
32
9547.5
184
154
200
170
15
8037
080
78
13
70
190
78
190
105 175
707070140
280210
ASL
170
140
14
80 171
1828
120
112
3114
29
17
HL
ASL 98
193
4P
3P
ASL
80 171
17
144
114
258
12
21 140
1828
120
ø9
ø13
140
184
154
79
40
173.
5
102
31.5
117.
5
8
80
200
370
170
25
80
1532
13
210
45
280
175
70
338(max.)
4.52914
4P
3P
18
242.570
3114
105
7070
28
166
4P3P
ASLASL ASL ASL
11(max.)
R3
ø13
ø9
ASLASL
70 70
73
13
15
114
144
12
184
154
101
7173
19 90.5
13.5
328
20
111
242.
5
168
140
70
300230
3P
4P3P
242.5 45
4.570
296
4P
113226
70
3P 4P
ASL
18
11(max.)
HL HL
HL
HL HL
HL
HL
Front connected
Rear connected
Front connected with Motor Operator
Rear connected with Motor Operator
The Ultimate Safety Breaker page 134
SE
CT
ION
7
The Ultimate Safety Breaker page 134
S1250-SE, S1250-NE, S1250-GE, S1250-NN. Plug-in Versions
DIMENSIONS
Plug-in with Motor Operator
Plug-in
HLHL
HLHL
ASLASL
4P3P
ASL ASL
145
40
4P
3P
ø13
40
4P3P
ø11
15
147
30 832
15
144
114
1515
199
169
2658
2194
6421
5826
9464
18980
13
7021
280
7070
45
8562
90
90 90
210
140
105175
707070
11(max.)
ø11
70
144
9421
64M
ax.1
5
1511
4
26
30
40
1532
8 147 M
ax.1
5
199
64
169
5826
58
94
21
260.5
21
6245
280
90
210
4P
3P
85
4P
3P
9070140
40
4.5
70 70
13
18
90
7070
105175
ø13
ASL
HL
3P 4P
ASL ASLASL
R3
ASL
90.5
13.5
168
4P
3P
HL
HL HL
HL
Drilling plan (front view)
M10 Mounting screw
Mounting base (rear view)
Conductor overlap, max
Toggle extension (removable)
Auxiliary circuit terminals
Mounting angle
Drilling plan (front view)Mounting base (rear view)
Conductor overlap, max
M10Mounting screw
Auxiliary circuit terminals
Mounting angle
Mounting angle
Panel cutout (front view)
Panel cutout dimensions shown give an allowance of 1.0mm around motor operator.
page 135 The Ultimate Safety Breakerpage 135 The Ultimate Safety Breaker
S1600-SE, S1600-NE, S1600-NN
DIMENSIONS
Front connected
Rear connected
Front connected with Motor Operator
Rear connected with Motor Operator
Conductor overlap, max
Conductor overlap, max
Trip button (red)
Mounting angle
Mounting angle
( )ON side Center pole and Neutral poleOFF side All poles
Insulation tube
Panel cutout dimensions shown give an allowance of 1.5mm around the handle escutcheon.
Interpole barrier(removable)
Toggle extension(removable)
Toggle extension(removable)
Panel cutout (front view)
Drilling plan (front view)
Drilling plan (front view)
M8Mounting screw
M8Mounting screw
Mounting hole
Insulating plate
ø12
Mounting angleL40✕40✕5
Conductor overlap, max
Drilling plan (front view)
M8Mounting screw
Insulating plate
Control circuit terminal
Pad lock
Conductor overlap, max
Mounting angle
( )ON side Center pole and Neutral poleOFF side All poles
Insulation tube
Panel cutout (front view)Drilling plan (front view)
M8Mounting screw
Panel cutout dimensions shown give an allowance of 1.0mm around motor operator.
3P
ASL ASL
4PHL
HL
HL
HL
ASL
ASL
HL
4P3P
184
154
139(
min
)
70
4P3P
4P3P
85 3015 30
15
707070
ø9
ø13
139(
min
.)15
(max
)
184
154
110
95
47.5
200
170
15
100
370
100
140
70
78
190
78
190
105 17570707045
280210
ø9
3220
ASL
30
170
140
20
80 191
1828
140132
1120
46
17
LH
ASL
4P
R3
98
193
3P
ASL
6010
0
6530
130
1511585
1570
80 191
17 140
ø13
ø9
1525
154
184
30
4010
231
.5
117.
517
3.5
79
2032
15
100
100
370
170
200
28
70
4P
3P
11(max.) 4.5
262.5
18
358(max.)
20 46
1120
280
175105
707070
210
14045
166
4P3P
ASL ASL ASL ASL
R3
ø9
ø12
ASL
139(
min
.)15
184
154
153015
3085
130
262.
5
100
60
6530
13.5
90.5
11(max.) 4.5
262.5 70
4P
3P
707070
15
4P
3P
168
4P
3P
HL
ASL
HL
HL
HL
HL HL
The Ultimate Safety Breaker page 136
SE
CT
ION
7
The Ultimate Safety Breaker page 136
S1600-SE, S1600-NE, S1600-NN. Draw-out Versions
DIMENSIONS
Draw-out with Motor Operator
Draw-out
HLHL
HLHL
ASL
2-ø12
HL
HL
ASLASL
3PHL
4PHL
ASL
ø12
112.5
4P3P
200
225
90°
60
220
3017
019
030
100
7550
Max
.45
Max
.45
2020
12070
525
105
200
220
170
190
272282
316
182.5
170100
21520
15
707070220150
2828 370(max.)28300(max.)28
190190
80
7878
4P
3P
4P3P
ASLASL
ø12
ASLASLASL
4P3P
ø12
100
(4P)112.5
100(4P)
60
90°
3030
190
170
120
2025
202570
50 75
525
220
200
105
52.5
121
452.
540
20
166
220
11(max.) 4.5
215
170(4P)200(3P)
4P3P
(4P)182.5
225(3P)
70707015
4P3P210
70
265¶300(max.)¶370(max.)
220150
R3
13.5
90.5
168
4P
3P
HL
ASL
Drilling plan (front view)Breaker fixing screw
ø12 Mounting hole ø12
Mounting hole2✕2-ø12 Mounting hole
Mounting angleL50✕50✕6526(draw-out)
396(connected)
395(draw-out)325(disconnected)
295(test)265(connected)
Toggle extension(removable)
Draw-out handle(removable)
Auxiliary circuit terminals (self-engaging)
Auxiliary circuit terminals (self-engaging) Auxiliary circuit terminals
(self-engaging)
Auxiliary circuit terminals (Automatic connection)
Conductor overlap, max
Conductor overlap, max
Trip button (red)
Drilling plan (front view)
Breaker fixing screwø12 Mounting hole
ø12 Mounting hole
Mounting angleL50✕50✕6
Draw-out handle(removable)
28-M3.5Auxiliary circuit terminals (Automatic connection)
Conductor overlap, max
Conductor overlap, max
417.5 (test)447.5 (disconnected)517.5 (draw-out)
387.5 (connected)
¶Contact TERASAKI if manual connection is required.
Panel cutout (front view)
Panel cutout dimensions shown give an allowance of 1.0mm around motor operator.
page 137 The Ultimate Safety Breakerpage 137 The Ultimate Safety Breaker
Applicable MCCB A
S160-NJ, E250-NJ,S250-NJ, S250-GJ, 106±2S250-NN
H125, L125, H160, L160,S250-NE, S250-GE, 141±2S250-PE, H250, L250
Applicable MCCBE125, S125
106±2
Breaker Mounted Handle
DIMENSIONS
The Ultimate Safety Breaker page 138
SE
CT
ION
7
The Ultimate Safety Breaker page 138
Breaker Mounted Handle
1.2-3.2
B
Handleescutcheon
Hook lever(Defeatmechanism)
Door defeatrelease button
130
18 12922 5
5
130 10 24 50 A 105
105CL CL CL
HL
HL
HL 4-ø10
ø110
200 200
14090
Applicable MCCB A BE400 S400 E630 S630 150±2 97
H400 L400 187±2 134
Applicable MCCB AS800 S1000 150±2
H800 L800 187±2
Handle escutcheon
Panel cutout Indicator
Positions of the hinge and handle as seen from the load side of the breaker.
Door defeatrelease button
Hook lever(Defeatmechanism)
DIMENSIONS
page 139 The Ultimate Safety Breakerpage 139 The Ultimate Safety Breaker
Door Mounted Handle standard type
358453 max. 144E125S125
ASL: Arrangement Standard LineHL: Handle Frame Centre LineCL: Handle Centre Line
Padlock dimensions (mm)
Applicable MCCB A✱✱1 B C
✽1: Max. means the maximum length fot A without cutting the shaft.+ The shaft can be cut to the required length.
A: Distance from the panel surface to the breaker mounting surfaceB: Length of the square shaft used
HL
LC
LC
ø78
70
LC
44
C
Panel thickness1.2–3.2
A19.5±2
B
Max. ø8Min.ø5 Min. 13
HL
28
4-ø7
ø31-ø37
40
HL
250
150 150
200 200
250
7.9
15.8
7.9
15.8
9° 9°Positional relationship between the hinge and handle as viewed from the load side of the breaker.The hinge must be inside the hatched area.
Panel cutout
DIMENSIONS
The Ultimate Safety Breaker page 140
SE
CT
ION
7
The Ultimate Safety Breaker page 140
Door Mounted Handle standard type
ASL: Arrangement Standard LineHL: Handle Frame Centre LineCL: Handle Centre Line
Padlock dimensions (mm)
Applicable MCCB A✽1 B C
S160-NJ, E250-NJ,
S250-NJ, S250-GJ 453 max. 358 144
S250-NN
H125, L125, H160, L160,
S250-NE, S250-GE, S250-PE, 488 max. 358 179
H250, L250
✽1: Max. means the maximum length fot A without cutting the shaft.+ The shaft can be cut to the required length.
A: Distance from the panel surface to the breaker mounting surfaceB: Length of the square shaft used
HL
LC
LC
ø78
70
LC
44
C
Panel thickness1.2–3.2
A19.5±2
B
Max. ø8Min.ø5 Min. 13
HL
28
4-ø7
ø31-ø37
40
HL
250
150 150
200 200
250
7.9
15.8
7.9
15.8
9° 9°Positional relationship between the hinge and handle as viewed from the load side of the breaker.The hinge must be inside the hatched area.
Panel cutout
DIMENSIONS
page 141 The Ultimate Safety Breakerpage 141 The Ultimate Safety Breaker
Door Mounted Handle standard type
E400 E630S400 S630
220 min.456 max.257 min.493 max.
8632286
322
188.5188.5225.5225.5
H400L400
Applicable MCCB A✽1 B C
Panel cutout
Positional relationship between the hinge and handle as viewed from the load side of the breaker.The hinge must be inside the hatched area.
LC
LC
LC
HL
HL HL
125
19.5±2
150 150
200 200
250 250
28
B
45
A
C
Panel thickness1.2–3.2
Max. ø8Min. ø5 Min. 13
9° 9°
15.8
7.9
7.9
15.8
40
ø31-ø37
ø78
4-ø7
✽1: Min. means the minimum length for A by cutting the shaft. Max. means the maximum length fot A without cutting the shaft.+ The shaft can be cut to the required length.
A: Distance from the panel surface to the breaker mounting surfaceB: Length of the square shaft used
ASL: Arrangement Standard LineHL: Handle Frame Centre LineCL: Handle Centre Line
Padlock dimensions (mm)
DIMENSIONS
The Ultimate Safety Breaker page 142
SE
CT
ION
7
The Ultimate Safety Breaker page 142
Door Mounted Handle standard type
DIMENSIONS
✽1: Min. means the minimum length for A by cutting the shaft. Max. means the maximum length fot A without cutting the shaft.+ The shaft can be cut to the required length.
A: Distance from the panel surface to the breaker mounting surfaceB: Length of the square shaft used
Applicable MCCB A✱✱1 B C
H800, L800 257 min. 86
493 max. 322
S800, S1000 220 min. 86
456 max. 322
225.5
225.5
188.5
188.5
Panel cutout
Positional relationship between the hinge and handle as viewed from the load side of the breaker.The hinge must be inside the hatched area.
LCLC
LC
HL
HLHL
19.5±2
B
A
C
ø78
125
15.8
7.9
7.9
15.8
40
150
200
150
200
250 250
28
45
Panel thickness1.2–3.2
9° 9°
ø31-ø37
4-ø7
Max. ø8Min. ø5 Min. 13
ASL: Arrangement Standard LineHL: Handle Frame Centre LineCL: Handle Centre Line
Padlock dimensions (mm)
page 143 The Ultimate Safety Breakerpage 143 The Ultimate Safety Breaker
Door Mounted Handle standard type
DIMENSIONS
✽1: Min. means the minimum length for A by cutting the shaft. Max. means the maximum length fot A without cutting the shaft.+ The shaft can be cut to the required length.
A: Distance from the panel surface to the breaker mounting surfaceB: Length of the square shaft used
Applicable MCCB A✱✱1 B C
512.5max. 322 245
S1250 276.5min. 86 245
S1600 296.5min. 86 265
532.5max. 322 265
Positional relationship between the hinge and handle as viewed from the load side of the breaker.The hinge must be inside the hatched area.
Max. ø8Min. ø5 Min. 13
150 150
200 200
250 250
7.9
15.8
15.8
7.9
9°
9°
28
40
LH
LH
125
ø78
LCLC
LC
45
B
C
A
Panel thickness1.2–3.2
19.5±2
LH
ø31-ø37
4-ø7
ASL: Arrangement Standard LineHL: Handle Frame Centre LineCL: Handle Centre Line
Padlock dimensions (mm)
The Ultimate Safety Breaker page 144
SE
CT
ION
7
Door Mounted Handle ordinal type
ø5.5~ø8
370543 max. 421 With +E125S125
Applicable MCCB A✱✱1 B C Shaft support
✽1: Max. means the maximum length fot A without cutting the shaft.+ The shaft can be cut to the required length. If it is necessary to cut the shaft so short that it does not protrude beyond the shaft support, the shaft support may be removed.
DIMENSIONS
page 145 The Ultimate Safety Breaker
Door Mounted Handle ordinal type
ø5.5~ø8
Applicable MCCB A✽1 B C D Shaft support
S160-NJ, E250-NJ,
S250-NJ, S250-GJ 543 max. 370 421 186 With +
S250-NN
H125, L125, H160, L160,
S250-NE, S250-GE, S250-PE, 578 max. 370 421 221 With +
H250, L250
✽1: Max. means the maximum length fot A without cutting the shaft.+ The shaft can be cut to the required length. If it is necessary to cut the shaft so short that it does not protrude beyond the shaft support, the shaft support may be removed.
DIMENSIONS
The Ultimate Safety Breaker page 146
SE
CT
ION
7
Door Mounted Handle ordinal type
Applicable MCCB A✽1 B C D Shaft support
ø5.5~ø8
✽
DIMENSIONS
page 147 The Ultimate Safety Breaker
Door Mounted Handle ordinal type
DIMENSIONS
✽1: Min. means the minimum length for A by cutting the shaft. Max. means the maximum length fot A without cutting the shaft.+ The shaft can be cut to the required length. If it is necessary to cut the shaft so short that it does not protrude beyond the shaft support, the shaft support may be removed.
A: Distance from the panel surface to the breaker mounting surfaceB: Length of the tube used to cover the square shaftC: Length of the square shaft usedD: Distance from the tip of the shaft support to the breaker mounting surface
Applicable MCCB A✱✱1 B C Shaft support
H800, L800 307 min. 12 107.5 Without
647 max. 280 447.5
S800, S1000 270 min. 12 107.5 Without
610 max. 280 447.5
D
—
261
—
298
With +
With +
Key for key lock(optional)
M6 (Nominal size of Allen key applicable: 3)
Shaft support
Panel cutout Positions of the hinge and handle as seen from the load side of the breaker.
Indicator
105
105
B
C
34
1.2-3.2 D
24 51
A
100
105
28 20
12
105
4-ø10
ø110 12
20 28
200
150
100 100
150
200
CLCL
CL
HL
HLHL
Handle escutcheon
Panel lock release
The Ultimate Safety Breaker page 148
SE
CT
ION
7
Door Mounted Handle ordinal type
DIMENSIONS
✽1: Min. means the minimum length for A by cutting the shaft. Max. means the maximum length fot A without cutting the shaft.+ The shaft can be cut to the required length. If it is necessary to cut the shaft so short that it does not protrude beyond the shaft support, the shaft support may be removed.
A: Distance from the panel surface to the breaker mounting surface B: Length of the tube used to cover the square shaftC: Length of the square shaft used D: Distance from the tip of the shaft support to the breaker mounting surface
Applicable MCCB A ✽1 B C D Shaft support
667max. 280 447.5 317
S1250 367min. 52 147.5 317 Without
S1600 387min. 52 147.5 337 Without
687max. 280 447.5 337
With +
With +
1.2-3.2
ø110
24
C
18
D
B
A
51 34
HL
105
4P
3P
LC
105 15
Panel lock release
100 100
150 150
200 200
12
12
20
28
20
28
Handle escutcheon
Panel cutout
LC
ASL
4-ø10
M6 (Nominal size of Allen key applicable: 3)Key for key lock(optional)
Positions of the hinge and handle as seen from the load side of the breaker.
M8 mounting screw
130
3P
4P
130
100
CL
HL
Shaft support
page 149 The Ultimate Safety Breaker
Terminal Covers
DIMENSIONS
Plug-in mounted versionThis version can be mountedsimply by being plugged in thebreaker body.
Screw-mounted versionThe terminal covers for 630 to800AF are mounted to thebreakers using tapping screws.The terminal cover for 1250AFis mounted to insert nuts of thebreaker cover using screws. Theinsert nuts do not come standardwith the breaker. Please be sureto state “with terminal cover(CF)” when ordering the breaker.
Terminal covers for Front connected MCCB’s (CF)
Megger measurement hole ø4(Above each terminal)
A
B
C
D
A C
D
B
Megger measurement hole ø4(Above each terminal)
Mounting screw
The Ultimate Safety Breaker page 150
SE
CT
ION
7
Terminal Covers
DIMENSIONS
Terminal covers for Cable clamp terminal type MCCB’s (CS)
Notes:(1) Not applicable when extension bars (FB) are fitted.(2) There will be an approx. 40 mm gap between the bottom of the terminal cover and the breaker mounting surface.(3) Values in parentheses indicate the distance to the head of terminal cover mounting screws.
MCCB type ConnectionA B B’ C D Mounting version
1P 3P 4P 1P 3P 4P 3P, 4P 1P 3P 4P 1P 3P 4PPlug-in
mountedScrew-
mounted
E125,S125 Front conn. 30 90 120 40 40 40 o 48 48 48 46 46 46 õ —
Cable clamp 30 90 120 2.5 2.5 2.5 6 62.5 61 61 60 59.5 59.5 õ —
S160,-NJ, S160NNE250-NJ, S250-NJ,S250-GJ, S250-NN
Front conn. (1) 35 105 140 55 55 55 o 54 54 54 52 52 52 õ —
Cable clamp 35 105 140 2.5 2.5 2.5 6 63 61 61 49.5 59.5 59.5 õ —
H125, L125, H160, L160,S250-NE, S250-GE, S250-PEH250, L250
Front conn. (1) o 105 140 o 55 55 o o 89 89 o 87 87 õ —
Cable clamp o 105 140 o 2.5 2.5 4.5 o 96 96 o 59.5 59.5 õ —
E400, S400E630, S630
Front conn. Wide type o 180 240 o 110 114 o o 97 98 o 96 98 õ —
Front conn. Straight type o 140 185 o 85 85 o o 97 97 o 94.5 94.5 õ —
Cable clamp o 140 185 o 3 3 4.5 o 97 97 o 93 93 õ —
H400, L400 Front conn. Wide type o 180 240 o 110 114 o o 134 135 o 96 98 õ —
Front conn. Straight type o 140 185 o 85 85 o o 134 134 o 94.5 94.5 õ —
Cable clamp — 140 185 o 3 3 4.5 o 134 134 o 93 93 õ —
S800, S1000 Front conn. (3) — 215 285 — 130 130 — — 99.5(102)
99.5(102)
— 99(101.5)
99(101.5)
— õ
H800, L800 Front conn. (2) (3) — 215 285 — 130 130 — — 99.5(139)
99.5(139)
— 99(101.5)
99(101.5)
— õ
S1250 Front conn. (3) — 215 285 — 130 130 — — 115 115 — 99(102.5)
99(102.5)
— õ
page 151 The Ultimate Safety Breaker
Terminal Covers
Megger measurement hole ø4 (Above each terminal)
DIMENSIONS
Terminal covers for Rear connected and Plug-in MCCB’s (CR)
Notes:(1): There will be an approx. 40 mm gap between the bottom of the terminal cover and the breaker mounting surface.(2): Values in parentheses indicate the distance to the head of terminal cover mounting screws.
MCCB typeA B
B'C D Mounting version
3 poles 4 poles 3 poles 4 poles 3 poles 4 poles 3 poles 4 polesPlug-in
mountedScrew-
mounted
E125, S125 90 120 2 2 6 41.5 41.5 40.5 40.5 õ —
S160, E250, S250-NJ, S250-GJ, S250-NN
105 140 2 2 6 42.5 42.5 39.5 39.5 õ —
H125, L125, H160, L160, S250-NE,S250-GE, S250-PE, H250, L250
105 140 2 2 6 77.5 77.5 39.5 39.5 õ —
E400, S400, E630, S630 140 185 3 3 5 97 97 93 93 õ —
H400, L400, (1) 140 185 3 3 5 134 134 93 93 õ —
S800, S1000 (2) 206 280 14 18 —101
(103.5)99
(101.5)100.5(103)
98(100.5)
— õ
H800, L800 (2) 206 280 14 18 —138
(140.5)136
(138.5)137.5(140)
135(137.5)
— õ
Plug-in mounted versionThis version can be mountedsimply by being plugged in thebreaker body.
Screw-mounted versionThe terminal covers for 630 to800AF are mounted to thebreakers using tapping screws.
A
B
C3.5
D
Megger measurement hole ø4 (Above each terminal)
Mounting screw
ø4Hole for Megger measurement
The Ultimate Safety Breaker page 152
SE
CT
ION
7
Interpole Barriers
MCCB type A B
E125, S125 47 53
S160, E250, S250-NJ, 100 53
S250-GJ, S250-NN
H125, L125, H160, L160, 100 88
S250-NE, S250-GE, S250-PE,
H250, L250
E400, S400, E630, S630 110 95
H400, L400 110 95
S800, H800, L800, 110 95
S1000
DIMENSIONS
page 153 The Ultimate Safety Breaker
Terminal Blocks for Front-Connected and Rear-Connected MCCBs
kkll
8
8
8 8
MCCB type A A’ B C Fig
E125, S125 — 3 0.5 40 2
S160, E250, S250-NJ,S250-GJ, S250-NN 2 — 0.5 40 1H125, L125, H160, L160,S250-NE, S250-GE, S250-PE, 2 — 35.5 75 1H250, L250
MCCB type A B C
E400, S400, E630, S630 39.5 30.5 70H400, L400 39.5 67.5 107S800, S1000 31 30.5 70H800, L800 31 67.5 107
Comments:1. The tightening torque for the M3.5 terminal screws is 0.9 to 1.2 N.m.2. Connection wire size is 2.5mm2 (max).
Comments:1. The tightening torque for the M3.5 terminal screws is 0.9 to 1.2 N.m.2. Connection wire size is 2.5mm2 (max).3. When you specify Ground Fault Trip on electronic MCCBs with
3 poles the terminal block is automatically fitted to connect with the external neutral CT for 3 phases 4 wires system.
DIMENSIONS
11 terminals
11 terminals
The Ultimate Safety Breaker page 154
SE
CT
ION
7
DIMENSIONS
Terminal Blocks for Front-Connected and Rear-Connected MCCBs
6 terminals
Comments:1. The tightening torque for the M3.5 terminal screws is 0.9 to 1.2 N.m.2. Connection wire size is 1.25mm2 (max).
Comments:1. Values in parentheses applies to 4-pole breakers.2. Tightening torque of M3.5 terminal screws: 0.9 – 1.2 N.m.3. Connection wire size: 2.0mm2 max x 2.
PALcPALa
kRC1C2
PALcPALa
kRD1D2
AXc1AXb1AXa1AXc2AXb2AXa2
AXc1AXb1AXa1ALc1ALb1ALa1
ON
OFF
L CL
14.5 C
2440
A
B
D
8
14.5
14.5
14.5
14.5
11.5
Left terminal designationsExample
Right terminal designationsExample
M3.5 screw
With SHT
With UVT
Wire Lead Direction
Wire Lead Direction
Terminal cover (see through)
3/4 poles
MCCB Type A B C D
E125, S125 42.5 27 53 53
S160, E250, S250-NJ, S250-GJ, S250-NN
42.5 27 53 53
H125, L125, H160, L160,S250-NE, S250-GE, S250-PE,H250, L250
77.5 62 53 53
E400, S400, E630, S630 72.5 57 43 63
H400, L400 109.5 94 43 63
S800, S1000 72.5 57 23.5 82.5
H800, L800 109.5 94 23.5 82.5
MCCB Type A B C D
S1250 51114
(124)57 72
S1600 51114
(124)77 92
6 terminals
ON
OFF
AXc1
AXb1
AXa1
AXc2
AXb2
AXa2
AXc3
AXb3
AXc4
AXb4
D1
D2
AXc1
AXb1
AXa1
AXc2
AXb2
AXa2
AXc3
AXb3
AXc4
AXb4
C1
C2
ALc1
ALb1
ALa1
PALc
PALa
ALc1
ALb1
ALa1
ALc2
ALb2
ALa2
A
21
9.6✕
5
12
6262
1
B62
21
27.5C
12.5D
7.8
M3.5✕0.7 screw
Left terminal designationsExample
Right terminal designationsExample
page 155 The Ultimate Safety Breaker
OCR Power Supply for Electronic Protection (Standard type)
DIMENSIONS
MCCB Type
S250-NE, S250-GE,S250-PE, H250-NE
PTAoutput 1a
Control power
ONOP1OP2PALcPALa
OFF
Notes: Separate installation of the OCR power supply is not available.
Terminal screw M3.5
ON
PALc
16.2
3480
1616
1518
15
25.2 79
PALa
OP1OP2
OFF
Notes: 1. Tightening torque of terminal screws: 0.9 – 1.2 N.m2. Applicable wire size: 2.0 mm2 max
Connection diagram Mounting dimensions
The Ultimate Safety Breaker page 156
SE
CT
ION
7
OCR Power Supply for Electronic Protection (Standard type)
OCR power supply installed on the breaker OCR power supply installed separately to the breaker
ON
OS1
Factory wired
Lead wire (450 mm long) Lead wire (450 mm long)
OS2
OP1OP2
PALc PTAoutput 1a
PTAoutput 1aPALa
PALc
PALa
WhiteRed
Control power
Control power
OS1OS2
OP1OP2
White Red
OFF
ON
OFF
Lead wire (600 mm long)
Terminal screw M3.5
ON
OS1
D
A80
1616
1518
15
C B
OS2
OP1OP2
OFF
Notes: 1. Tightening torque of terminal screws: 0.9 – 1.2 N.m2. Applicable lead wire size: 2.0 mm2 max
16
16
108088
66
59
45 57.5
6 22
25
9
100
10
167.8
1515
18
Mounting hole ø4.5
Terminal screw M3.5
Support
Connection diagram
Mounting dimensions
OCR power supply installed on the breaker
OCR power supply installed separately to the breaker
DIMENSIONS
MCCB Type A B C D
S400-NE, S400-GE, S400-PE,E630-NE, S630-CE, S630-GE
71 74 25.2 16.2
H400-NE, L400-NE 71 111 25.2 16.2
S800, S1000 62.5 74 25.2 16.2
H800, L800 62.5 111 25.2 16.2
S12503P 33 72 21 12
4P 43 72 21 12
S16003P 33 92 21 12
4P 43 92 21 12
page 157 The Ultimate Safety Breaker
OCR Power Supply for Electronic Protection (with LCD)
MCCB Type A B C D
S400-NE, S400-GE, S400-PE,E630-NE, S630-CE, S630-GE
71 74 25.2 16.2
H400-NE, L400-NE 71 111 25.2 16.2
S800, S1000 62.5 74 25.2 16.2
H800, L800 62.5 111 25.2 16.2
OCR power supply installed on the breaker OCR power supply installed separately to the breaker
ON
OS1
Factory wired
OS2
OP1OP2
WhiteRed
Control power
Control power
OS1OS2
OP1OP2
White Red
OFF
ON
OFF
Lead wire (600 mm long)
Terminal screw M3.5
ON
OS1
D
A80
1616
1518
15
C B
OS2
OP1OP2
OFF
Notes: 1. Tightening torque of terminal screws: 0.9 – 1.2 N.m2. Applicable lead wire size: 2.0 mm2 max
16 Mounting hole ø4.5
16
108088
66
83
69
81.5
6 22
25
9
100
10
167.8
1515
18
Terminal screwM3.5
Support
OP1
OP2
Controlpower supply
OS1 (red)
OS2 (white)
Connect the red and white lead wires from the breaker to OS1 and OS2 respectively. (Max lead wire length : 600 mm)
Connection diagram
Mounting dimensions
OCR power supply installed on the breaker
OCR power supply installed separately to the breaker
DIMENSIONS
The Ultimate Safety Breaker page 158
SE
CT
ION
7
Slide Interlocks
T2MS123SF T2MS124SF
DIMENSIONS
MCCB Type Poles Conn. Parts No. A
E125, S1253 FC, RC T2MS123SF 91.7
4 FC, RC T2MS124SF 91.7
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
page 159 The Ultimate Safety Breaker
Slide Interlocks
T2MS253SF/T2MS253LF T2MS254SF/T2MS254LF
DIMENSIONS
MCCB Type Poles Conn. Parts No. A
S160, E250, S250-NJ, S250GJ, S250-NN
3 FC, RC T2MS253SF91.7
4 FC, RC T2MS254SF
H125, L125, H160, L160, S250-NE, S250-GE, S250-PE,H250, L250
3 FC, RC T2MS253LF126.7
4 FC, RC T2MS254LF
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
The Ultimate Safety Breaker page 160
SE
CT
ION
7
Slide Interlocks
T2MS403SF/T2MS403LF T2MS404SF/T2MS404LFPanel Cutout
Drilling plan
Panel cutout dimensions shown give an allowance of 1.0 mm around the handle escutcheon.
Panel Cutout
Mechanical Interlocks slide type (MS)
For 400A, 630A frame size
DIMENSIONS
MCCB Type Poles Conn. Parts No. A
E400, S400, E630, S6303 FC, RC T2MS403SF
135.54 FC, RC T2MS404SF
H400, L4003 FC, RC T2MS403LF
172.54 FC, RC T2MS404LF
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
page 161 The Ultimate Safety Breaker
Mechanical Interlocks slide type (MS)
For 800A, 1000A frame size
T2MS803SF/T2MS803LF T2MS804SF/T2MS804LF
Drilling plan
Panel cutout dimensions shown give an allowance of 1.0 mm around the handle escutcheon.
ASL
HL HL LH HL
LH LH LH LH
ASL ASL
ASL ASL
HL HL HL HL
ASL
LH LH LH LH
M8 Tapped hole
3P 4P
M6 Tapped hole M8 Tapped hole M6 Tapped hole
ASL
107
107
92
R6R6
273
223
6.5
105175
6.5
10520
105
8686 320
422
8686
107
107
117
126
92
107
70
320195
70125
250
7070
250
492
600
A
460
107
20 2020
Panel Cutout
Slide Interlocks
DIMENSIONS
MCCB Type Poles Conn. Parts No. A
S800, S10003 FC, RC T2MS803SF
135.54 FC, RC T2MS804SF
H800, L8003 FC, RC T2MS803LF
172.54 FC, RC T2MS804LF
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
Notes:(1) The interlock cannot be applied to breakers equipped with front extension bars due to the
shortage of the insulating distance.
The Ultimate Safety Breaker page 162
SE
CT
ION
7
Slide Interlocks
DIMENSIONS
Notes:1 : Please order with the breakers.(1) The interlock cannot be applied to breakers equipped with a terminal block, UVT controller or OCR controller.(2) See the outline dimensions of the breaker for the drilling plan.
Slide knob stroke Slide knob stroke
HL HL
d
ASLh
gf
a
e
d
R
HL
HL HL
HL
ASLC
a
m
b
k
r
HL HL
m
r
R
HL HL
ASLC
a
b
k
R
HL HL
d
ASLh
gf
a
e
d
R
3P 4P
MCCB Type Parts No. Poles a b c d e f g h k m R R
S1250(S1250-ND isexcluded)
T2MSX63SF 3 220 340 135 61.5 343 64 74 138 430 160.5 30 8.5
T2MSX64SF 4 290 410 135 61.5 413 64 74 138 570 160.5 30 8.5
TL-1250NE XLF9 13 220 340 129 61.5 343 58 74 132 430 179.6 30 8.5
4 290 410 129 61.5 413 58 74 132 570 179.6 30 8.5
S1250-NDS1600
T2MSX63SF 3 220 340 135 61.5 343 64 74 138 430 180.5 30 8.5
T2MSX64SF 4 290 410 135 61.5 413 64 74 138 570 180.5 30 8.5
page 163 The Ultimate Safety Breaker
Link Interlocks
T2ML12RAT2ML12L3A T2ML12RAT2ML12L4A
T2ML12RAT2ML12L3A T2ML12RAT2ML12L4A
DIMENSIONS
MCCB Type Poles Position Parts No. A
E125, S125
3Right T2ML12RA
81.74
3Left
T2ML12L3A
4 T2ML12L4A
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
The Ultimate Safety Breaker page 164
SE
CT
ION
7
Link Interlocks
DIMENSIONS
Link Interlocks
T2ML25RA T2ML25RAT2ML25L3A T2ML25L4A
T2ML25RA T2ML25RAT2ML25L3A T2ML25L4A
MCCB Type Poles Position Parts No. A
S160, E250, S250-NJ, S250-GJ, S250-NN
3Right T2ML25RA
81.74
3Left
T2ML25L3A
4 T2ML25L4A
H125, L125, H160, L160,S250-NE, S250-GE, S250-PE,H250, L250
3Right T2ML25RA
116.74
3Left
T2ML25L3A
4 T2ML25L4A
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
page 165 The Ultimate Safety Breaker
DIMENSIONS
Link Interlocks with motor operators
Mounting hole(For pan head screw M6)
Mounting hole(For pan head screw M6)
CL
CL CL
CL
HL HL HL HL
HL HL
HL
HL
HL
HL
HL HL
140 14040
214
45 45 45 45
4545 45 4518
160
5770 70
214
260
214
260
214
1857070
40140
185 40115 70
185
14070115
40185
140
156
136
140
19.8 A
136
T2ML40RAT2ML40L3A T2ML40RAT2ML40L4A
T2ML40RAT2ML40L3A T2ML40RAT2ML40L4A
MCCB Type Poles Position Parts No. A
E400, S400E630, S630
3Right T2ML40RA
2134
3Left
T2ML40L3A
4 T2ML40L4A
H400, L400
3Right T2ML40RA
2504
3Left
T2ML40L3A
4 T2ML40L4A
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
For 400A and 630A frame, the link mechanical interlocks can not be used without motor operators. Please specify also the motor operatorswhen ordering. Furthermore, please request the additional labels for the breakers to TERASAKI and put the labels on the side of the breakers.
The Ultimate Safety Breaker page 166
SE
CT
ION
7
DIMENSIONS
Link Interlocks with breaker mounted handles
140 14040
214
45 45 45 45
4545 45 45
70 70
1857070
40140
185 40115 70
185
14070115
40185
260
260
214
260
260
24 50 B
A
76
76
1.2~3.2
214
214
Key lock(option)
Mounting hole(For pan head screw M6)
Mounting hole(For pan head screw M6)
CL
CL
CL
CL
HL HL HL HL
HL HL HL HL
HL HL HL HL
T2ML40RAT2ML40L3A T2ML40RAT2ML40L4A
T2ML40RAT2ML40L3A T2ML40RAT2ML40L4A
MCCB Type Poles Position Parts No. A B
E400, S400E630, S630
3Right T2ML40RA
200 150±24
3Left
T2ML40L3A
4 T2ML40L4A
H400, L400
3Right T2ML40RA
237 187±24
3Left
T2ML40L3A
4 T2ML40L4A
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
For 400A and 630A frame, the link mechanical interlocks can not be used without breaker mounted handles. Please specify also the breakermounted handles when ordering. Furthermore, please request the additional labels for the breakers to TERASAKI and put the labels on theside of the breakers.
Mechanical Interlocks link type (ML)
For 400A, 630A frame size
page 167 The Ultimate Safety Breaker
For 800A and 1000A frame, the link mechanical interlocks can not be used without motor operators. Please specify also the motor operatorswhen ordering. Furthermore, please request the additional labels for the breakers to TERASAKI and put the labels on the side of the breakers.
DIMENSIONS
Link Interlocks with motor operators
MCCB Type Poles Position Parts No. A
S800, S1000
3Right T2ML80RA
2134
3Left
T2ML80L3A
4 T2ML80L4A
H800, L800
3Right T2ML80RA
2504
3Left
T2ML80L3A
4 T2ML80L4A
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
Mechanical Interlocks link type (ML)
For 800A, 1000A frame size
Notes:(1) The interlock cannot be applied to breakers equipped with terminal block.
105
M8Mounting hole
M8Mounting hole
LC
136140
HL
18
210280105175105
280210
243
273
243
LC
105175280280
105105
70707070
70707070
243
273
243
LH
5815
6
19.8
136140
21040
40
160
A40
40210
LC
LC
LHLHLHLH
LHLHLHLH
LH
HL
LC
T2ML80L3A T2ML80RA T2ML80L4A T2ML80RA
T2ML80L3A T2ML80RA T2ML80L4A T2ML80RA
The Ultimate Safety Breaker page 168
SE
CT
ION
7
DIMENSIONS
Link Interlocks with breaker mounted handles
Key lock(option)
M8 Mounting hole
M8 Mounting hole
273
243
273
243
LC
LC
210280105175
280210105105
40 40
LH
LC
LC
LHLHLHLH
LHLHLHLH
LHLHHL
273
243
273
243
280280175105175105105105
70707070
70707070
21040 40210
24 50 BA
1.2–3.2
T2ML80RAT2ML80L3A T2ML80RAT2ML80L4A
T2ML80RAT2ML80L3A T2ML80RAT2ML80L4A
MCCB Type Poles Position Parts No. A B
S800, S1000
3Right T2ML80RA
200 1504
3Left
T2ML80L3A
4 T2ML80L4A
H800, L800
3Right T2ML80RA
237 1874
3Left
T2ML80L3A
4 T2ML80L4A
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
For 800A and 1000A frame, the link mechanical interlocks can not be used without breaker mounted handles. Please specify also the breakermounted handles when ordering. Furthermore, please request the additional labels for the breakers to TERASAKI and put the labels on theside of the breakers.
Mechanical Interlocks link type (ML)
For 800A, 1000A frame size
Notes:(1) The interlock cannot be applied to breakers equipped with terminal block.
page 169 The Ultimate Safety Breaker
DIMENSIONS
Wire Interlocks
B C
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
MCCB Type Parts No. A
E125, S125 T2MW12CA 81.7
Cable length Parts No. B C
1.0m T2MW00SA 130min. – 480max. 160min. – 480max.
1.5m T2MW00LA 130min. – 980max. 160min. – 980max.
Mechanical Interlocks wire type (MW)
For 125A frame size
The Ultimate Safety Breaker page 170
SE
CT
ION
7
DIMENSIONS
Wire Interlocks
C D
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
Cable length Parts No. B C
1.0m T2MW00SA 155min. – 480max. 180min. – 480max.
1.5m T2MW00LA 155min. – 980max. 180min. – 980max.
MCCB Type Parts No. A B
S160, E250, S250-NJS250-GJ, S250-NN
T2MW25CA 81.7 64
H125, L125, H160,L160, S250-NE, S250-GE, S250-PE,H250, L250
T2MW25CA 116.7 99
page 171 The Ultimate Safety Breaker
DIMENSIONS
Wire Interlocks with motor operators
CL CL
HL HL HL HL
CL CL
HL HL HL HL
HL
HL
HL
HL
45 45 45 45
45 45 45 45
70140
70140 185
70185
115
19.8 A
18
156
160
57
18570
14070
14070
185115
136
140
136
140
214
214
214
260
214
260
ø9
C D
19B B
19
Min.
R100
Min.
R100
Min.
R100
Min.
R100
27.5 27.5
27.5 27.5
Mounting hole(For pan head screw M6)
Mounting hole(For pan head screw M6)
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
MCCB Type Parts No. A B
E400, S400, E630, S630
T2MW40CA 213 105.4
H400, L400 T2MW40CA 250 142.4
Cable length Parts No. B C
1.0m T2MW00SA 180min. – 480max. 225min. – 480max.
1.5m T2MW00LA 180min. – 930max. 225min. – 930max.
For 400A and 630A frame, the wire mechanical interlocks can not be used without motor operators. Please specify also the motor operatorswhen ordering. Furthermore, please request the additional labels for the breakers to TERASAKI and put the labels on the side of the breakers.
The Ultimate Safety Breaker page 172
SE
CT
ION
7
DIMENSIONS
Wire Interlocks with breaker mounted handles
140 140
214
214
214
214
45 45 45 45
4545 45 45
70 70
1857070
140
185115 70
185
14070.1115
185
260
260
260
260
24 50 BA
27.5 27.5
27.5 27.5
DC
76
27.576
C D
1.2~3.2
Key lock(option)
Mounting hole(For pan head screw M6)
Mounting hole(For pan head screw M6)
CL CL
HL HL HL HL
CL CL
HL HL HL HL
HL HL HL HL
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
MCCB Type Parts No. A B
E400, S400, E630, S630
T2MW40CA 200 150±2
H400, L400 T2MW40CA 237 187±2
Cable length Parts No. B C
1.0m T2MW00SA 180min. – 430max. 225min. – 430max.
1.5m T2MW00LA 180min. – 930max. 225min. – 930max.
For 400A and 630A frame, the wire mechanical interlocks can not be used without breaker mounted handles. Please specify also the breakermounted handles when ordering. Furthermore, please request the additional labels for the breakers to TERASAKI and put the labels on theside of the breakers.
Mechanical Interlocks wire type (MW)
For 400A, 630A frame size
page 173 The Ultimate Safety Breaker
CL CL
LH
HL
HL
HL HLHL
HL
HLHL
HLHL
CL
CL
HL
Mounting hole
Electrical Interlock cable ø5length 2m
Mechanical Interlock cable ø5length 1m or 1.5m
Min.R100
Min.R100 Min.R100
Min.R100
160
105
243
A
C
140
136
D
19.8
210 210
210175105
175280
58
428
MC
CB
O
N16
MC
CB
O
FF
8
Min
.200
1515
273
17.5
124.
5
70 70 70
70707070
70
210
105 105
105
18
140
136
17.5
124.
5
280
280 280105
ø9
ø9
156
MCCB Type Parts No. A
S800, S1000 T2MW80CA 213
H800, L800 T2MW80CA 250
Cable length Parts No. C D
1.0m T2MW00S 250min. – 430max. 320min. – 430max.
1.5m T2MW00L 250min. – 930max. 320min. – 930max.
DIMENSIONS
Wire Interlocks with motor operators
For 800A and 1000A frame, the wire mechanical interlocks can not be used without motor operators. Please specify also the motor operatorswhen ordering. Furthermore, please request the additional labels for the breakers to TERASAKI and put the labels on the side of the breakers.
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
Mechanical Interlocks wire type (MW)
For 800A, 1000A frame size
The Ultimate Safety Breaker page 174
SE
CT
ION
7
DIMENSIONS
Wire Interlocks with breaker mounted handles
For 800A and 1000A frame, the wire mechanical interlocks can not be used without breaker mounted handles. Please specify also the breakermounted handles when ordering. Furthermore, please request the additional labels for the breakers to TERASAKI and put the labels on theside of the breakers.
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
MCCB Type Parts No. A B
S800, S1000 T2MW80CA 200 150±2
H800, L800 T2MW80CA 237 187±2
Cable length Parts No. C D
1.0m T2MW00S 250min. – 430max. 320min. – 430max.
1.5m T2MW00L 250min. – 930max. 320min. – 930max.
Mechanical Interlocks wire type (MW)
For 800A, 100A frame size
CL
LH HL HL
HL HLHL HL
HLHL HL HL
CL CL
CL CL
HL
243
243
105 105
DC
210 210 175 175
210 175105 105 175 210
428
MC
CB
O
FF
8M
CC
B
ON
16M
in.2
00
130
124.
517
.5
1515
273
1515
273
70 70 70 70
70 70 70 70
DC
50
24 A
B
1.2-3.2
Min.100
ø9
Mounting hole
Mechanical Interlock cable ø5length 1m or 1.5m
Key lock(option)
page 175 The Ultimate Safety Breaker
DIMENSIONS
Wire Interlocks rear type
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
MCCB Type Parts No. A
S1250 (S1250-ND is excluded)
Factory fitted120
S1250-ND, S1600 140
Cable length Parts No. P L
1.0m T2MW00S 650–500–350 450–500–530 ±30
1.5m T2MW00L 1000–900–750 550–600–700 ±30
Mechanical Interlocks wire type (MW)
For 1250A, 1600A frame size
210
280A
70 70
17105 175
17180
5.5 90 40.5
25.5
60
25.5
60
P220220
6 6
370
154
184
A
6016.5
3568
4073
P
L
ø9
ASL
ASL
HL
ASL ASL ASL
ASL ASL
ø13
Min.R50
HL
HL HL
HL HL
3P 4P Mounting hole
Cable fitting screw
Partition
Toggle extension(removable)
Drilling plan (front view)
Vertical installation
Horizontal installation
The Ultimate Safety Breaker page 176
SE
CT
ION
7
DIMENSIONS
Position of Trip Button
Positions of Trip Button
B
D
C
A Trip button
HL
LC
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
MCCB Type Poles A B C D
E125, S125 3, 4 13.8 20.4 3.3 4.3
S160, E250, S250-NJ, S250-GJ, S250-NN,
3, 4 17.2 20.4 3.3 4.3
H125, L125, H160, L160, S250-NE, S250-GE, S250-PE,H250, L250
3, 4 17.2 20.4 3.3 4.3
E400, S400H400, L400, E630, S630
3, 4 21.6 37.2 5.3 6.6
S800, S1000H800, L800
3, 4 21.6 33 5.3 6.6
MCCB Type Poles A B A2 B2 C D E
S1250S1600
3, 4 30 37.5 31 70.5 6 6 8
HL
BE
D
B2
A2
A
Trip button
øC Trip button
ASL
DIMENSIONS
External Neutral CT
Door Flanges
80
85
2-M4
35 145
85110
4-ø10
4-M6
k
50
l
k l
75
140
4-M6
75100
50105
4-ø8
2-M4 4011
02050
57
Door flanges are recommended to be used to cover the cutout of a switchboard panel.
HL
HL
D
HL
HL
DK
H
FG
E
AB
C
Ht
t
C
A
FG
E
B
CL CL CL
ASL
CLASLASLASL
ASL
CLASL2
1
2
1
2
1 CL2
1
2
1
2
1
Breaker outline
Fig. 1 Fig. 2
M3✕0.5Flat head screw Panel
d tapped hole
Panel drilling plan Breaker outlineM3✕0.5 Flat head screwM4✕0.7 Flat head screw Panel Panel drilling plan
d tapped hole
Door Flange for toggle-operated MCCBs (mm)
Notes:1 : CL Handle centre line is applied.2 : ASL Arrangement standard line is applied.
MCCB Type Parts No. Fig. A B C D EF G H
K d tMin Max Min Max Min Max
E125, S125
T2DF25 1 1 77.5 77.5 105 50 92 37 42 37 42 32 45 — M3✕0.5 2
H125, L125, H160, L160, S250-NE, S250-GE, S250-PE,H250, L250
T2DF25 1 1 82.5 82.5 105 50 92 37 42 37 42 32 45 — M3✕0.5 2
S160, E250, S250-NJ, S250-GJ, S250-NN
T2DF25 1 1 82.5 82.5 105 50 92 37 42 37 42 32 45 — M3✕0.5 2
E400, S400, E630, S630
T2DF40 2 1 130 130 135 95 120 48 56 48 56 57 90 80 M3✕0.5 2
H400, L400
T2DF40 2 1 130 130 135 95 120 48 56 48 56 57 90 80 M3✕0.5 2
S800, S1000
T2DF40 2 2 132 141 135 95 120 48 56 48 56 57 90 80 M3✕0.5 2
H800, L800
T2DF40 2 2 132 141 135 95 120 48 56 48 56 57 90 80 M3✕0.5 2
S1250 T2DFX6 2 2 170 200 150 120 135 51 63.5 51 63.5 85 115 80 M3✕0.5 2
S1600 T2DFX6 2 2 170 200 150 120 135 51 63.5 51 63.5 85 115 80 M3✕0.5 2
page 177 The Ultimate Safety Breaker
Type of CT Rated primary current (A) Rated secondary current (mA)T2GB40N04 400 100T2GB40N06 630 100T2GB40N08 800 100
Type of CT Rated primary current (A) Rated secondary current (mA)T2GBX6N10 1000 100T2GBX6N12 1250 100T2GBX6N16 1600 100
The Ultimate Safety Breaker page 178
SE
CT
ION
7
DIMENSIONS
Door Flange for motor-operated MCCBs (mm)
MCCB Type Parts No. A B C D EF G H
K d tMin Max Min Max Min Max
E125S125
T2DM25 77.5 77.5 200 130 151 80 90 80 90 94 98 106 4 3.5
H125, L125, H160, L160S250-NE, S250-GE, S250-PEH250, L250
T2DM25 77.5 77.5 200 130 151 80 90 80 90 94 98 106 4 3.5
S160, E250, S250-NJ, S250-GJ, S250-NN
T2DM25 77.5 77.5 200 130 151 80 90 80 90 94 98 106 4 3.5
E400, S400E630, S630
T2DM40 57 103 200 180 150 59 69 105 115 144 148 156 4 3.5
H400, L400
T2DM40 57 103 200 180 150 59 69 105 115 144 148 156 4 3.5
S800,S1000
T2DM40 58 102 200 180 150 60 70 104 114 144 148 156 4 3.5
H800, L800
T2DM40 58 102 200 180 150 60 70 104 114 144 148 156 4 3.5
Panel drilling plan
d tapped hole
B
EC
F
H
K
G
A
Dt
Panel
Motor outline
CL CLCL
HL HL
7
DIRECT OPENING
Under the heading “Measures to minimise therisk in the event of failure”, IEC 60204-1 Safetyof Machinery-Electrical Equipment Machineryincludes the following recommendation:
“-the use of switching devices having positive(or direct) opening operation.”
180
SE
CT
ION
8
180
TEMBREAK 2 FIXED THERMAL MOULDED CASECIRCUIT BREAKERS
TEMBREAK 2
MOULDED CASE CIRCUIT BREAKERS 16A TO 1600A
1. Welcome to TemBreak 2
2. Ratings and Specifications
3. Operating Characteristics
4. Application Data
5. Accessories
6. Installation
7. Dimensions
TEMBREAK 2
FIXED THERMAL MOULDED CASE CIRCUIT BREAKERS 15A TO 800A
8. Characteristics and Outline Dimensions
• S100-NF, S100-GF 181
• S125-NF, S125-GF 183
• S225-NF, S225-GF 185
• S250-NF, S250-GF 187
• H100-NF, L100-NF 189
• H125-NF, L125-NF 191
• H225-NF, L225-NF 193
• H250-NF, L250-NF 195
• E400-NF 197
• S400-CF, S400-NF, S400-GF, S400-PF 199
• S800-CF, S800-NF, S800-RF 201
181
Time/Current characteristic curves
Ambient Compensating Curves
Characteristics and Outline Dimensions
Ratings and Specifications
Molded Case Circuit Breakers8 S100-NF, S100-GF(100A Frame)
seco
ndm
inut
eho
ur
100
125
200
300
400
500
700
1000
1500
2000
3000
4000
5000
8000
0.005
0.01
0.02
0.040.06
0.1
0.2
0.40.6
1
2
46
10
203040
1
2
46
10
203040
1
23
Percent Rated Current
Tri
pp
ing
Tim
e
Magnetic trip setting960%–1440%
Max.(40–50A)
Max.(60–100A)
Max.(15–30A)
Min.(40–100A)
Min.(15–30A)
140
130
120
110
100
90
0 10 20 30 40 50
15A
50A
100A,60A
75A,40A
20A
30A
Calibratedtemperature
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
Type Number of poles■RatingsRated current, ACalibrated at 40°C
Rated insulation voltage〔Ui〕 V ACRated impulse withstand voltage 〔U imp〕 kV■Rated breaking capacity, kAIEC60947-2 AC 690VIcu/Ics(sym) 500V
440V415V380V240V
q DC 250V125V
■Rated short time withstand current, kAWeight (' marked standard type) kg■Connections and MountingsFront-connected (FC) Terminal screws
With extension barsRear-connected (RC) Bolt studs
Flat bar studsPlug-in (PM)Draw-out type (DR)DIN rail mountClip-in chassis mount■Accessories (optional) Symbol
Motor operator MCExternal operating Breaker-mounted HBhandle Door-mounted (variable depth) HPToggle extension HAMechanical interlock Slide type MS
Link type MLWire type MW
Toggle holder HHToggle lock HLTerminal cover For front-connected CF
For rear-connected and plug-in CRInterpole barrier BATerminal block for lead TFDoor flange DF
■Standard specificationsOvercurrent trip mechanismTrip button (color)Handle position indication (ON: Red, OFF: Green)Suitability for isolation
Ext
erna
llym
ount
ed
S100-NF2 3 4
15 5020 6030 7540 100
6908
6/622/2225/2530/3030/3050/5025/1940/30―0.7 1.1 1.4
'
○(BAR)―○○―― ○⑪―
― ●― ●― ●―― ●― ●― ●●●●●●③●●
Thermal-magneticYes (Red)YesYes
S100-GF2 3 4
15 6020 7530 1004050
6908
6/625/2250/2565/3365/3385/8540/4040/40―0.7 1.1 1.4
'
○(BAR)―○○―― ○⑪―
― ●― ●― ●―― ●― ●― ●●●●●●e
●●
Thermal-magneticYes (Red)YesYes
Combinations of Internally Mounted Accessories(Optional)
SH UV AX AL
2
3・4
AL
SH
AL
UV
AX
UV
AX
AL
AX
SH
AX
UV
AL
AX
SH
AL
Pole
s
ToggleLeft poleRight pole
Auxiliary switch Alarm switchUnder
voltage trip Shunt trip
NOTE: 2-pole type breaker may incorporate only one combination of AX (max.2C) , AL , SH , UV , AX (max.2C) AL into the right pole.
Notes:' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”. 1 : DC rating available on request. 3 : Line side interpole barriers aresupplied as standard. (Front connection only) !1 : Provided with DIN rail adaptor.
Outline dimensions (mm) S100-NF, S100-GF
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
182
SE
CT
ION
8
5.2 2024.2
10(m
ax.)
15(max.)
ø6.5
ø8.5
ø9
8.5(
max
.)
17(max.)max.t5
134
155
30 60 3090
60 90 120
35 47.5 22.5
2P
LH
3P
HL
4P
LH
LC
M660 4.5 90 120
22
55 84 84
190
2P
L
3P
LH H
4P
HL
LC
CL
30
92
16
6830
8
52102
30
155
170
116
108
40
27 43
160
27
CL
60
55
15
84
90 90
22
30 60 30
120
84
47
3P
L
2P
LL H
C
H
4P
CLH
L
2P
4P3P
15HL
513
4
LC
92
61845
688
2P
L LHLH C
3P
L H
4P
102
2416
30 3.227.2
30
8 20.5
LC
30
132
30
3P3P
4P
C
L
L
4P
CLC
LL
2P
HLH H
303060
132
3030 30
30
134CL
3P 4P2P
15 15 10 14 14
35
50
21 14
70
37.5 75
ø6
22.5
134
75
15
3.227.2
30
CLHL HL HL
CL
R1
3P
52
28.586
45
2P4P
4357
30 LC HL
CL
50
16
13.5
3 13.5
8.5
11.5
3 13.5
Front-connected
Rear-connected
Plug-in
Mounting hole
Interpole barrier (removable)
M4✕0.7Tapped hole
M8screw 8.5(
max
.)
17(max.)max.t5
M4✕0.7Mounting screw
M4✕0.7Tapped hole
M4✕0.7Mounting screwStud can be
turned 45° or 90°
Mounting plate(max. t3.2)
Mounting hole
Mounting plateM5✕0.8Mounting screw
Note: Studs are factory installed in horizontal direction both on the line and load sides.Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.
Conductor
M6screw
Drilling plan (front view)With extension bars (optional)Preparation of conductor
Detail of connecting part
Conductor overlap, maxDrilling plan (front view) Panel cutout (front view)
Preparation of conductorDetail of connecting part
Drilling plan (front view)Mounting base (rear view)
ø18 for accessory wiring when necessary
2P only
ø18
183
Time/Current characteristic curves
Ambient Compensating Curves
Characteristics and Outline Dimensions
Ratings and Specifications
Molded Case Circuit Breakers8 S125-NF, S125-GF(125A Frame)
100
125
200
300
400
500
700
1000
1500
2000
3000
4000
5000
8000
0.005
0.01
0.02
0.040.060.1
0.2
0.40.6
1
2
46
10
2030401
2
46
10
2030401
23
hour
min
ute
seco
nd
Min.
Max.
Magnetic trip setting800%–1200%
Percent Rated Current
Tri
pp
ing
Tim
e140
130
120
110
100
90
0 10 20 30 40 50
Calibratedtemperature
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
Type Number of poles■RatingsRated current, ACalibrated at 40°C
Rated insulation voltage〔Ui〕 V ACRated impulse withstand voltage 〔U imp〕 kV■Rated breaking capacity, kAIEC60947-2 AC 690VIcu/Ics(sym) 500V
440V415V380V240V
q DC 250V125V
■Rated short time withstand current, kAWeight (' marked standard type) kg■Connections and MountingsFront-connected (FC) Terminal screws
With extension barsRear-connected (RC) Bolt studs
Flat bar studsPlug-in (PM)Draw-out type (DR)DIN rail mountClip-in chassis mount■Accessories (optional) Symbol
Motor operator MCExternal operating Breaker-mounted HBhandle Door-mounted (variable depth) HPToggle extension HAMechanical interlock Slide type MS
Link type MLWire type MW
Toggle holder HHToggle lock HLTerminal cover For front-connected CF
For rear-connected and plug-in CRInterpole barrier BATerminal block for lead TFDoor flange DF
■Standard specificationsOvercurrent trip mechanismTrip button (color)Handle position indication (ON: Red, OFF: Green)Suitability for isolation
Ext
erna
llym
ount
ed
S125-NF2 3 4
125
6908
6/622/2225/2530/3030/3050/5025/1940/30-0.7 1.1 1.4
'
○(BAR)―○○―― ○⑪-
― ●― ●― ●-― ●― ●― ●●●●●●③●●
Thermal-magneticYes (Red)YesYes
S125-GF2 3 4
125
6908
6/625/2250/2565/3365/3385/8540/4040/40-0.7 1.1 1.4
'
○(BAR)―○○―― ○⑪―
― ●― ●― ●―― ●― ●― ●●●●●●e
●●
Thermal-magneticYes (Red)YesYes
Combinations of Internally Mounted Accessories(Optional)
SH UV AX AL
2
3・4
AL
SH
AL
UV
AX
UV
AX
AL
AX
SH
AX
UV
AL
AX
SH
AL
Pole
s
ToggleLeft poleRight pole
Auxiliary switch Alarm switchUnder
voltage trip Shunt trip
NOTE: 2-pole type breaker may incorporate only one combination of AX (max.2C) , AL , SH , UV , AX (max.2C) AL into the right pole.
Notes:' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”. 1 : DC rating available on request. 3 : Line side interpole barriers aresupplied as standard. (Front connection only) !1 : Provided with DIN rail adaptor.
Outline dimensions (mm) S125-NF, S125-GF
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
184
SE
CT
ION
8
5.2 2024.2
10(m
ax.)
15(max.)
ø6.5
ø8.5
ø9
8.5(
max
.)
17(max.)max.t5
134
155
30 60 3090
60 90 120
35 47.5 22.5
2P
LH
3P
HL
4P
LH
LC
M660 4.5 90 120
22
55 84 84
190
2P
L
3P
LH H
4P
HL
LC
CL
30
92
16
6830
8
52102
30
155
170
116
108
40
27 43
160
27
CL
60
55
15
84
90 90
22
30 60 30
120
84
47
3P
L
2P
LL H
C
H
4P
CLH
L
2P
4P3P
15HL
513
4
LC
92
61845
688
2P
L LHLH C
3P
L H
4P
102
2416
30 3.227.2
30
8 20.5
LC
30
132
30
3P3P
4P
C
L
L
4P
CLC
LL
2P
HLH H
303060
132
3030 30
30
134CL
3P 4P2P
15 15 10 14 14
35
50
21 14
70
37.5 75
ø6
22.5
134
75
15
3.227.2
30
CLHL HL HL
CL
R1
3P
52
28.586
45
2P4P
4357
30 LC HL
CL
50
16
13.5
3 13.5
8.5
11.5
3 13.5
Front-connected
Rear-connected
Plug-in
Mounting hole
Interpole barrier (removable)
M4✕0.7Tapped hole
M8screw 8.5(
max
.)
17(max.)max.t5
M4✕0.7Mounting screw
M4✕0.7Tapped hole
M4✕0.7Mounting screwStud can be
turned 45° or 90°
Mounting plate(max. t3.2)
Mounting hole
Mounting plateM5✕0.8Mounting screw
Note: Studs are factory installed in horizontal direction both on the line and load sides.Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.
Conductor
M6screw
Drilling plan (front view)With extension bars (optional)Preparation of conductor
Detail of connecting part
Conductor overlap, maxDrilling plan (front view) Panel cutout (front view)
Preparation of conductorDetail of connecting part
Drilling plan (front view)Mounting base (rear view)
ø18 for accessory wiring when necessary
2P only
ø18
185
Time/Current characteristic curves
Ambient Compensating Curves
Characteristics and Outline Dimensions
Ratings and Specifications
Molded Case Circuit Breakers8 S225-NF, S225-GF(225A Frame)
seco
ndm
inut
eho
ur
100
125
200
300
400
500
700
1000
1500
2000
3000
4000
5000
8000
0.005
0.01
0.02
0.040.06
0.1
0.2
0.40.6
1
2
46
10
2030401
2
46
10
2030401
23
Max.
Min. Magnetic trip setting1040%–1560%
Percent Rated Current
Tri
pp
ing
Tim
e140
130
120
110
100
90
0 10 20 30 40 50
225A,125A
175A
200A
150A
Calibratedtemperature
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
Type Number of poles■RatingsRated current, ACalibrated at 40°C
Rated insulation voltage〔Ui〕 V ACRated impulse withstand voltage 〔U imp〕 kV■Rated breaking capacity, kAIEC60947-2 AC 690VIcu/Ics(sym) 500V
440V415V380V240V
q DC 250V125V
■Rated short time withstand current, kAWeight (' marked standard type) kg■Connections and MountingsFront-connected (FC) Terminal screws
With extension barsRear-connected (RC) Bolt studs
Flat bar studsPlug-in (PM)Draw-out type (DR)DIN rail mountClip-in chassis mount■Accessories (optional) Symbol
Motor operator MCExternal operating Breaker-mounted HBhandle Door-mounted (variable depth) HPToggle extension HAMechanical interlock Slide type MS
Link type MLWire type MW
Toggle holder HHToggle lock HLTerminal cover For front-connected CF
For rear-connected and plug-in CRInterpole barrier BATerminal block for lead TFDoor flange DF
■Standard specificationsOvercurrent trip mechanismTrip button (color)Handle position indication (ON: Red, OFF: Green)Suitability for isolation
Ext
erna
llym
ount
ed
S225-NF2* 3 4
125 200150 225175
6908
7.5/7.525/2525/2535/3535/3565/6540/4040/40―1.5 1.5 1.9
'
○(BAR)―○○―――
●●●―●●●●●●●●3
●●
Thermal-magneticYes (Red)YesYes
S225-GF2* 3 4
125150175200225
6908
7.5/7.525/2550/2565/3565/3585/8540/4040/40―1.5 1.5 1.9
'
○(BAR)―○○―――
●●●―●●●●●●●●3
●●
Thermal-magneticYes (Red)YesYes
Combinations of Internally Mounted Accessories(Optional)
SH UV AX AL
3・4
AL
SH
AL
UV
AX
UV
AX
AL
AX
SH
AX
UV
AL
AX
SH
AL
Pole
s
ToggleLeft poleRight pole
Auxiliary switch Alarm switchUnder
voltage trip Shunt trip
Notes:' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”. 1 : DC rating available on request. 3 : Line side interpole barriers aresupplied as standard. (Front connection only)
Outline dimensions (mm) S225-NF, S225-GF
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
186
SE
CT
ION
8
15.5
(max
.)
ø9
22(max.) 3P 4P
LC
HLHL
105 140
165
116
108
180
180
200
27
3P 4PLHLH
22
9898
M8
144
52.5 17.535
105 140
7010535
75
HL HL
3P 4P
35 35
C
4PH HL
L
3P
L
ø11 35 3523
35
CL
428
428
LC
30.5
11.5
19
11.5
30.523
ø11
HL
24
92
100
70 835
140
102
4561
688105 105
H
L
3P
L L
CL C
4P
H
9898
22
126
35
126
ø24
3535
144
35 3535
35
H
4P3P
LHL3P
8
4P
3535 35
HL
22
614
4
106
20
15 1571
ø9
68
CLCL
CL CL CL
22
97120
23 23
3517.5
70
37.5 75
ø6
15 15
50
1515
15.5
(m
ax.)
24
527
R1
3P
52.5
52
100
4P
50
HL
CL
50165
144
Drilling plan (front view) Panel cutout (front view)
Mounting base (rear view)
Drilling plan (front view)
Detail of connecting part
Preparation of conductor With extension bars (optional) Drilling plan (front view)Front-connected
Rear-connected
Plug-in
Conductor overlap, max
M8screw
Conductor overlap, max
Stud can be turned 45°or 90°
M4✕0.7Tapped hole
10(m
ax.)ø9
25(max.)max.t7
M4✕0.7Mounting screw
M4✕0.7Tapped hole
Mounting plate(max. t3.2)
M5✕0.8Mounting screw
Mounting hole
Interpole barrier (removable)
Mounting hole
M4✕0.7Mounting screw
Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.
Preparation of conductor
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Mounting plate
M8 screw
Conductor width, max.22
187
Time/Current characteristic curves
Ambient Compensating Curves
Characteristics and Outline Dimensions
Ratings and Specifications
Molded Case Circuit Breakers
Type Number of poles■RatingsRated current, ACalibrated at 40°C
Rated insulation voltage〔Ui〕 V ACRated impulse withstand voltage 〔U imp〕 kV■Rated breaking capacity, kAIEC60947-2 AC 690VIcu/Ics(sym) 500V
440V415V380V240V
q DC 250V125V
■Rated short time withstand current, kAWeight (' marked standard type) kg■Connections and MountingsFront-connected (FC) Terminal screws
With extension barsRear-connected (RC) Bolt studs
Flat bar studsPlug-in (PM)Draw-out type (DR)DIN rail mountClip-in chassis mount■Accessories (optional) Symbol
Motor operator MCExternal operating Breaker-mounted HBhandle Door-mounted (variable depth) HPToggle extension HAMechanical interlock Slide type MS
Link type MLWire type MW
Toggle holder HHToggle lock HLTerminal cover For front-connected CF
For rear-connected and plug-in CRInterpole barrier BATerminal block for lead TFDoor flange DF
■Standard specificationsOvercurrent trip mechanismTrip button (color)Handle position indication (ON: Red, OFF: Green)Suitability for isolation
Ext
erna
llym
ount
ed
8 S250-NF, S250-GF(250A Frame)
100
125
200
300
400
500
700
1000
1500
2000
3000
4000
5000
8000
0.005
0.01
0.02
0.040.060.1
0.2
0.40.6
1
2
46
10
2030401
2
46
10
2030401
23
hour
min
ute
seco
nd
Magnetic trip setting800%–1200%
Percent Rated Current
Tri
pp
ing
Tim
e
Min.
Max.
140
130
120
110
100
90
0 10 20 30 40 50
Calibratedtemperature
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
Combinations of Internally Mounted Accessories(Optional)
SH UV AX AL
3・4
AL
SH
AL
UV
AX
UV
AX
AL
AX
SH
AX
UV
AL
AX
SH
AL
Pole
s
ToggleLeft poleRight pole
Auxiliary switch Alarm switchUnder
voltage trip Shunt trip
S250-NF2* 3 4
250
6908
7.5/7.525/2525/2535/3535/3565/6540/4040/40-1.5 1.5 1.9
'
○(BAR)―○○―――
●●●―●●●●●●●●③●●
Thermal-magneticYes (Red)YesYes
S250-GF2* 3 4
250
6908
7.5/7.525/2550/2565/3565/3585/8540/4040/40―1.5 1.5 1.9
'
○(BAR)―○○―――
●●●―●●●●●●●●e
●●
Thermal-magneticYes (Red)YesYes
Notes:' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”. 1 : DC rating available on request. 3 : Line side interpole barriers aresupplied as standard. (Front connection only)
Outline dimensions (mm) S250-NF, S250-GF
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
188
SE
CT
ION
8
15.5
(max
.)
ø9
22(max.) 3P 4P
LC
HLHL
105 140
165
116
108
180
180
200
27
3P 4PLHLH
22
9898
M8
144
52.5 17.535
105 140
7010535
75
HL HL
3P 4P
35 35
C
4PH HL
L
3P
L
ø11 35 3523
35
CL
428
428
LC
30.5
11.5
19
11.5
30.523
ø11
HL
24
92
100
70 835
140
102
4561
688105 105
H
L
3P
L L
CL C
4P
H
9898
22
126
35
126
ø24
3535
144
35 3535
35
H
4P3P
LHL3P
8
4P
3535 35
HL
22
614
4
106
20
15 1571
ø9
68
CLCL
CL CL CL
22
97120
23 23
3517.5
70
37.5 75
ø6
15 15
50
1515
15.5
(m
ax.)
24
527
R1
3P
52.5
52
100
4P
50
HL
CL
50165
144
Drilling plan (front view) Panel cutout (front view)
Mounting base (rear view)
Drilling plan (front view)
Detail of connecting part
Preparation of conductor With extension bars (optional) Drilling plan (front view)Front-connected
Rear-connected
Plug-in
Conductor overlap, max
M8screw
Conductor overlap, max
Stud can be turned 45°or 90°
M4✕0.7Tapped hole
10(m
ax.)ø9
25(max.)max.t7
M4✕0.7Mounting screw
M4✕0.7Tapped hole
Mounting plate(max. t3.2)
M5✕0.8Mounting screw
Mounting hole
Interpole barrier (removable)
Mounting hole
M4✕0.7Mounting screw
Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.
Preparation of conductor
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Mounting plate
M8 screw
Conductor width, max.22
Ext
erna
llym
ount
ed
189
Time/Current characteristic curves
Ambient Compensating Curves
Characteristics and Outline Dimensions
Ratings and Specifications
Molded Case Circuit Breakers8 H100-NF, L100-NF(100A Frame)
seco
ndm
inut
eho
ur
100
125
200
300
400
500
700
1000
1500
2000
3000
4000
5000
8000
0.005
0.01
0.02
0.040.06
0.1
0.2
0.40.6
1
2
46
10
2030401
2
46
10
2030401
23
Percent Rated Current
Tri
pp
ing
Tim
e
Max.(40–100A)
Max.(15–30A)
Min.(40–100A)
Min.(15–30A)Magnetic trip setting960%–1440%
140
130
120
110
100
90
0 10 20 30 40 50
75A
40A 60A,100A
20A
30A
15A,50A
Calibratedtemperature
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
Type Number of poles■RatingsRated current, ACalibrated at 40°C
Rated insulation voltage〔Ui〕 V ACRated impulse withstand voltage 〔U imp〕 kV■Rated breaking capacity, kAIEC60947-2 AC 690VIcu/Ics(sym) 500V
440V415V380V240V
q DC 250V125V
■Rated short time withstand current, kAWeight (' marked standard type) kg■Connections and MountingsFront-connected (FC) Terminal screws
With extension barsRear-connected (RC) Bolt studs
Flat bar studsPlug-in (PM)Draw-out type (DR)DIN rail mountClip-in chassis mount■Accessories (optional) Symbol
Motor operator MCExternal operating Breaker-mounted HBhandle Door-mounted (variable depth) HPToggle extension HAMechanical interlock Slide type MS
Link type MLWire type MW
Toggle holder HHToggle lock HLTerminal cover For front-connected CF
For rear-connected and plug-in CRInterpole barrier BATerminal block for lead TFDoor flange DF
■Standard specificationsOvercurrent trip mechanismTrip button (color)Handle position indication (ON: Red, OFF: Green)Suitability for isolation
H100-NF3 4
15 5020 6030 7540 100
6908
20/1545/45120/80125/85125/85150/15040/4040/40―2.4 3.2
'
○(BAR)―○○―――
●●●―●●●●●●●●e
●●
Thermal-magneticYes (Red)YesYes
L100-NF3 4
15 5020 6030 7540 100
6908
25/2065/65180/135200/150200/150200/15040/4040/40―2.4 3.2
'
○(BAR)―○○―――
●●●―●●●●●●●●e
●●
Thermal-magneticYes (Red)YesYes
Combinations of Internally Mounted Accessories(Optional)
SH UV AX AL
3・4
AL
SH
AL
UV
AX
UV
AX
AL
AX
SH
AX
UV
AL
AX
SH
AL
Pole
s
ToggleLeft poleRight pole
Auxiliary switch Alarm switchUnder
voltage trip Shunt trip
Notes:' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ▲ : Semi-standard. ● : “yes” or “available”. ― : “no” or “not available”. 1 : DC rating available on request. 3 : Line side interpole barriers are supplied as standard. (Front connection only)
Outline dimensions (mm) H100-NF, L100-NF
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
190
SE
CT
ION
8
4P3PHL HL
CL CL CL
3P 4P
3P 4P 3P 4P
LC
3P 4P
HL
HL
HL
HLHLHL HL HL HL
CL
CL CL CL
CL
HL
15.5
(max
.)
ø9
22(max.)
CL
3P 4P
CL
HL
CL
35
126
3P4P
620
144
22
ø24
3535 35 35 35 35
144
35 35 35ø971106
102
961038
127
8
15 15
8096
1074
45
35 35
127
126
103
102
8
463
98
2335 35 35
140ø11 11
.530
.5
1209723
2311
.5
30.5
22
9898
105 140
165
144
52.5 17.535
3517.5
70
37.5 75
1515
ø6
50102
8 151175
108
180
105 140
7010535
180
200
75
M827 15 15
50
8096
1038
59ø9
25(max.)
10(m
ax.)
127
8
max.t7
102
70105
22
35105140
9898
144
165
100
HL HL
15.5
(m
ax.)
24
527
3P4P
R1
52.5
52
50100
50
50
Tapped hole
Mounting plate(max. t3.2)
Stud can be turned 45° or 90°
Conductor overlap, max
M4✕0.7Mounting screw M4✕0.7
M4✕0.7Mounting screw M4✕0.7
Tapped hole
Mounting hole
Mounting screw
Mounting plate
M5✕0.8
With extension bars (optional) Drilling plan (front view)
Drilling plan (front view) Panel cutout (front view)
Mounting base (rear view)
Drilling plan (front view)
3PHL
Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Preparation of conductor
Mounting hole
Front-connected
Rear-connected
Plug-in
M8 screw
M4✕0.7Mounting screw
Preparation of conductorMounting hole
Interpole barrier (removable)
Detail of connecting part
M8 screw
Conductor width, max.22
3PHL
Type Number of poles■RatingsRated current, ACalibrated at 40°C
Rated insulation voltage〔Ui〕 V ACRated impulse withstand voltage 〔U imp〕 kV■Rated breaking capacity, kAIEC60947-2 AC 690VIcu/Ics(sym) 500V
440V415V380V240V
q DC 250V125V
■Rated short time withstand current, kAWeight (' marked standard type) kg■Connections and MountingsFront-connected (FC) Terminal screws
With extension barsRear-connected (RC) Bolt studs
Flat bar studsPlug-in (PM)Draw-out type (DR)DIN rail mountClip-in chassis mount■Accessories (optional) Symbol
Motor operator MCExternal operating Breaker-mounted HBhandle Door-mounted (variable depth) HPToggle extension HAMechanical interlock Slide type MS
Link type MLWire type MW
Toggle holder HHToggle lock HLTerminal cover For front-connected CF
For rear-connected and plug-in CRInterpole barrier BATerminal block for lead TFDoor flange DF
■Standard specificationsOvercurrent trip mechanismTrip button (color)Handle position indication (ON: Red, OFF: Green)Suitability for isolation
H125-NF,L125-NF8 (125A Frame)
Combinations of Internally Mounted Accessories(Optional)
SH UV AX AL
3・4
AL
SH
AL
UV
AX
UV
AX
AL
AX
SH
AX
UV
AL
AX
SH
AL
Pole
s
ToggleLeft poleRight pole
Auxiliary switch Alarm switchUnder
voltage trip Shunt trip
191
Characteristics and Outline Dimensions
Ratings and Specifications
Molded Case Circuit Breakers
Time/Current characteristic curves
Ambient Compensating Curves
100
125
200
300
400
500
700
1000
1500
2000
3000
4000
5000
8000
0.005
0.01
0.02
0.040.06
0.1
0.2
0.40.6
1
2
46
10
2030401
2
46
10
2030401
23
hour
min
ute
seco
nd
Max.
Min.
Percent Rated Current
Tri
pp
ing
Tim
e
Magnetic trip setting960%–1440%
140
130
120
110
100
90
0 10 20 30 40 50
Calibratedtemperature
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
H125-NF3 4
125
6908
20/1545/45120/80125/85125/85150/15040/4040/40―2.4 3.2
'
○(BAR)-○○-――
●●●―●●●●●●●●e
●●
Thermal-magneticYes (Red)YesYes
L125-NF3 4
125
6908
25/2065/65180/135200/150200/150200/15040/4040/40―2.4 3.2
'
○(BAR)-○○―――
●●●―●●●●●●●●e
●●
Thermal-magneticYes (Red)YesYes
Ext
erna
llym
ount
ed
Notes:' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ▲ : Semi-standard. ● : “yes” or “available”. ― : “no” or “not available”. 1 : DC rating available on request. 3 : Line side interpole barriers are supplied as standard. (Front connection only)
Outline dimensions (mm) H125-NF,L125-NF
4P3PHL HL
CL CL CL
3P 4P
3P 4P 3P 4P
LC
3P 4P
HL
HL
HL
HLHLHL HL HL HL
CL
CL CL CL
CL
HL
15.5
(max
.)
ø9
22(max.)
CL
3P 4P
CL
HL
CL
35
126
3P4P
620
144
22
ø24
3535 35 35 35 35
144
35 35 35ø971106
102
961038
127
8
15 15
8096
1074
45
35 35
127
126
103
102
8
463
98
2335 35 35
140ø11 11
.530
.5
1209723
2311
.5
30.5
22
9898
105 140
165
144
52.5 17.535
3517.5
70
37.5 75
1515
ø6
50102
8 151175
108
180
105 140
7010535
180
200
75
M827 15 15
50
8096
1038
59ø9
25(max.)
10(m
ax.)
127
8
max.t7
102
70105
22
35105140
9898
144
165
100
HL HL
15.5
(m
ax.)
24
527
3P4P
R1
52.5
52
50100
50
50
Tapped hole
Mounting plate(max. t3.2)
Stud can be turned 45° or 90°
Conductor overlap, max
M4✕0.7Mounting screw M4✕0.7
M4✕0.7Mounting screw M4✕0.7
Tapped hole
Mounting hole
Mounting screw
Mounting plate
M5✕0.8
With extension bars (optional) Drilling plan (front view)
Drilling plan (front view) Panel cutout (front view)
Mounting base (rear view)
Drilling plan (front view)
3PHL
Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Preparation of conductor
Mounting hole
Front-connected
Rear-connected
Plug-in
M8 screw
M4✕0.7Mounting screw
Preparation of conductorMounting hole
Interpole barrier (removable)
Detail of connecting part
M8 screw
Conductor width, max.22
3PHL
SE
CT
ION
8
192
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
193
Time/Current characteristic curves
Ambient Compensating Curves
Characteristics and Outline Dimensions
Ratings and Specifications
Molded Case Circuit Breakers
Type Number of poles■RatingsRated current, ACalibrated at 40°C
Rated insulation voltage〔Ui〕 V ACRated impulse withstand voltage 〔U imp〕 kV■Rated breaking capacity, kAIEC60947-2 AC 690VIcu/Ics(sym) 500V
440V415V380V240V
q DC 250V125V
■Rated short time withstand current, kAWeight (' marked standard type) kg■Connections and MountingsFront-connected (FC) Terminal screws
With extension barsRear-connected (RC) Bolt studs
Flat bar studsPlug-in (PM)Draw-out type (DR)DIN rail mountClip-in chassis mount■Accessories (optional) Symbol
Motor operator MCExternal operating Breaker-mounted HBhandle Door-mounted (variable depth) HPToggle extension HAMechanical interlock Slide type MS
Link type MLWire type MW
Toggle holder HHToggle lock HLTerminal cover For front-connected CF
For rear-connected and plug-in CRInterpole barrier BATerminal block for lead TFDoor flange DF
■Standard specificationsOvercurrent trip mechanismTrip button (color)Handle position indication (ON: Red, OFF: Green)Suitability for isolation
8 H225-NF, L225-NF(225A Frame)
seco
ndm
inut
eho
ur
100
125
200
300
400
500
700
1000
1500
2000
3000
4000
5000
8000
0.005
0.01
0.02
0.040.06
0.1
0.2
0.40.6
1
2
46
10
203040
1
2
46
10
203040
1
23
Percent Rated Current
Tri
pp
ing
Tim
e
Max.
Min.
Magnetic trip setting1040%–1560%
140
130
120
110
100
90
0 10 20 30 40 50
125A
175A
200A
150A
225A
Calibratedtemperature
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
H225-NF3 4
125150175200225
6908
20/1545/45120/80125/85125/85150/15040/4040/40―2.4 3.2
'
○(BAR)―○○―――
●●●―●●●●●●●●e
●●
Thermal-magneticYes (Red)YesYes
L225-NF3 4
125150175200225
6908
25/2065/65180/135200/150200/150200/15040/4040/40―2.4 3.2
'
○(BAR)―○○―――
●●●―●●●●●●●●e
●●
Thermal-magneticYes (Red)YesYes
Combinations of Internally Mounted Accessories(Optional)
SH UV AX AL
3・4
AL
SH
AL
UV
AX
UV
AX
AL
AX
SH
AX
UV
AL
AX
SH
AL
Pole
s
ToggleLeft poleRight pole
Auxiliary switch Alarm switchUnder
voltage trip Shunt trip
Ext
erna
llym
ount
ed
Notes:' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ▲ : Semi-standard. ● : “yes” or “available”. ― : “no” or “not available”. 1 : DC rating available on request. 3 : Line side interpole barriers are supplied as standard. (Front connection only)
Outline dimensions (mm) H225-NF, L225-NF
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
194
SE
CT
ION
8
4P3PHL HL
CL CL CL
3P 4P
3P 4P 3P 4P
LC
3P 4P
HL
HL
HL
HLHLHL HL HL HL
CL
CL CL CL
CL
HL
15.5
(max
.)
ø9
22(max.)
CL
3P 4P
CL
HL
CL
35
126
3P4P
620
144
22
ø24
3535 35 35 35 35
144
35 35 35ø971106
102
961038
127
8
15 15
8096
1074
45
35 35
127
126
103
102
8
463
98
2335 35 35
140ø11 11
.530
.5
1209723
2311
.5
30.5
22
9898
105 140
165
144
52.5 17.535
3517.5
70
37.5 75
1515
ø6
50102
8 151175
108
180
105 140
7010535
180
200
75
M827 15 15
50
8096
1038
59ø9
25(max.)
10(m
ax.)
127
8
max.t7
102
70105
22
35105140
9898
144
165
100
HL HL
15.5
(m
ax.)
24
527
3P4P
R1
52.5
52
50100
50
50
Tapped hole
Mounting plate(max. t3.2)
Stud can be turned 45° or 90°
Conductor overlap, max
M4✕0.7Mounting screw M4✕0.7
M4✕0.7Mounting screw M4✕0.7
Tapped hole
Mounting hole
Mounting screw
Mounting plate
M5✕0.8
With extension bars (optional) Drilling plan (front view)
Drilling plan (front view) Panel cutout (front view)
Mounting base (rear view)
Drilling plan (front view)
3PHL
Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Preparation of conductor
Mounting hole
Front-connected
Rear-connected
Plug-in
M8 screw
M4✕0.7Mounting screw
Preparation of conductorMounting hole
Interpole barrier (removable)
Detail of connecting part
M8 screw
Conductor width, max.22
3PHL
H250-NF, L250-NF8 (250A Frame)
195
Characteristics and Outline Dimensions
Ratings and Specifications
Molded Case Circuit Breakers
Time/Current characteristic curves
Ambient Compensating Curves
Type Number of poles■RatingsRated current, ACalibrated at 40°C
Rated insulation voltage〔Ui〕 V ACRated impulse withstand voltage 〔U imp〕 kV■Rated breaking capacity, kAIEC60947-2 AC 690VIcu/Ics(sym) 500V
440V415V380V240V
q DC 250V125V
■Rated short time withstand current, kAWeight (' marked standard type) kg■Connections and MountingsFront-connected (FC) Terminal screws
With extension barsRear-connected (RC) Bolt studs
Flat bar studsPlug-in (PM)Draw-out type (DR)DIN rail mountClip-in chassis mount■Accessories (optional) Symbol
Motor operator MCExternal operating Breaker-mounted HBhandle Door-mounted (variable depth) HPToggle extension HAMechanical interlock Slide type MS
Link type MLWire type MW
Toggle holder HHToggle lock HLTerminal cover For front-connected CF
For rear-connected and plug-in CRInterpole barrier BATerminal block for lead TFDoor flange DF
■Standard specificationsOvercurrent trip mechanismTrip button (color)Handle position indication (ON: Red, OFF: Green)Suitability for isolation
100
125
200
300
400
500
700
1000
1500
2000
3000
4000
5000
8000
0.005
0.01
0.02
0.040.060.1
0.2
0.40.6
1
2
46
10
2030401
2
46
10
2030401
23
hour
min
ute
seco
nd
Min.
Max.
Percent Rated Current
Tri
pp
ing
Tim
e
Magnetic trip setting800%–1200%
140
130
120
110
100
90
0 10 20 30 40 50
Calibratedtemperature
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
H250-NF3 4
250
6908
20/1545/45120/80125/85125/85150/15040/4040/40―2.4 3.2
'
○(BAR)―○――――
●●●―●●●●●●●●e
●●
Thermal-magneticYes (Red)YesYes
L250-NF3 4
250
6908
25/2065/65180/135200/150200/150200/15040/4040/40―2.4 3.2
'
○(BAR)―○――――
●●●―●●●●●●●●e
●●
Thermal-magneticYes (Red)YesYes
Combinations of Internally Mounted Accessories(Optional)
SH UV AX AL
3・4
AL
SH
AL
UV
AX
UV
AX
AL
AX
SH
AX
UV
AL
AX
SH
AL
Pole
s
ToggleLeft poleRight pole
Auxiliary switch Alarm switchUnder
voltage trip Shunt trip
Ext
erna
llym
ount
ed
Notes:' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ▲ : Semi-standard. ● : “yes” or “available”. ― : “no” or “not available”. 1 : DC rating available on request. 3 : Line side interpole barriers are supplied as standard. (Front connection only)
Outline dimensions (mm) H250-NF, L250-NF
4P3PHL HL
CL CL CL
3P 4PHL
HL
HL
CL CL
HL
CL
3P 4P
CL
HL
CL
35
126
3P4P
620
144
22
ø24
3535 35 35 35 35
144
35 35 35ø971106
102
961038
127
8
15 15
8096
1074
45
35 35
127
126
103
102
8
463
98
2335 35 35
140ø11 11
.530
.5
1209723
2311
.5
30.5
8096
1038
59ø9
25(max.)
10(m
ax.)
127
8
max.t7
102
70105
22
35105140
9898
144
165
100
HL HL
3P4P
R1
52.5
52
50100
50
50
Tapped hole
Mounting plate(max. t3.2)
Stud can be turned 45° or 90°
Conductor overlap, max
M4✕0.7Mounting screw M4✕0.7
M4✕0.7Mounting screw M4✕0.7
Tapped hole
Mounting hole
With extension bars (optional) Drilling plan (front view)
Drilling plan (front view) Panel cutout (front view)
3PHL
Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Front-connected
Rear-connected
M8 screw
M4✕0.7Mounting screw
Preparation of conductorMounting hole
Interpole barrier (removable) 3P
HL
SE
CT
ION
8
196
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
197
Time/Current characteristic curves
Ambient Compensating Curves
Characteristics and Outline Dimensions
Ratings and Specifications
Molded Case Circuit Breakers
Type Number of poles■RatingsRated current, ACalibrated at 40°C
Rated insulation voltage〔Ui〕 V ACRated impulse withstand voltage 〔U imp〕 kV■Rated breaking capacity, kAIEC60947-2 AC 690VIcu/Ics(sym) 500V
440V415V380V240V
q DC 250V125V
■Rated short time withstand current, kAWeight (' marked standard type) kg■Connections and MountingsFront-connected (FC) Terminal screws
With extension barsRear-connected (RC) Bolt studs
Flat bar studsPlug-in (PM)Draw-out type (DR)DIN rail mountClip-in chassis mount■Accessories (optional) Symbol
Motor operator MCExternal operating Breaker-mounted HBhandle Door-mounted (variable depth) HPToggle extension HAMechanical interlock Slide type MS
Link type MLWire type MW
Toggle holder HHToggle lock HLTerminal cover For front-connected CF
For rear-connected and plug-in CRInterpole barrier BATerminal block for lead TFDoor flange DF
■Standard specificationsOvercurrent trip mechanismTrip button (color)Handle position indication (ON: Red, OFF: Green)Suitability for isolation
8 E400-NF(400A Frame)
100
125
200
300
400
500
700
1000
1500
2000
3000
4000
5000
8000
0.005
0.01
0.02
0.040.06
0.1
0.2
0.40.6
1
2
46
10
2030401
2
46
10
2030401
23
Max.(300–400A)
Min.(300–400A)
Min.(250A)
Max.(250A)
seco
ndm
inut
eho
ur
Percent Rated Current
Tri
pp
ing
Tim
e
Magnetic trip setting900%–1100%
140
130
120
110
100
90
0 10 20 30 40 50
300A
350A
400,250A
Calibratedtemperature
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
Magnetic trip pickup current
E400-NF3
250300350400
6908
—15/1522/2225/2525/2535/3525/1940/30―4.2
'
○(BAR)―○――――
●●●―●●●
●
●●●③●●
Thermal-magneticYes (Red)YesYes
Combinations of Internally Mounted Accessories(Optional)
SH UV AX AL
3
AL
SH
AL
UV
AX
UV
AX
AL
AX
SH
AX
UV
AL
AX
SH
AL
Pole
s
ToggleLeft poleRight pole
Auxiliary switch Alarm switchUnder
voltage trip Shunt trip
Rated current (A) Magnetic trip pickup current (A)In× 10
250 2500300 3000350 3500400 4000Notes:1. Setting tolerance: ±10%.
Ext
erna
llym
ount
ed
Notes:' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ▲ : Semi-standard. ● : “yes” or “available”. ― : “no” or “not available”. 1 : DC rating available on request. 3 : Line side interpole barriers are supplied as standard. (Front connection only)
Outline dimensions (mm) E400-NF
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
198
SE
CT
ION
8
H
CL
CL CL
CL
CL CL CL CL
L
L
HL
HL
HL
H
145
260
85.397
8
214
103
228
90102
116
14.7
110
12028
14.5
30 44.5
368
45
51
127.5145
90140
3014
.544
.525(max.)12
ø14
148
44.5
349
358
ø11
260
118
92
R6
97
1074
90102
103
228
260
830
ø13
127.5
30 45 45
103
11070
1539 21
4
45
228
90
88ø36
ø13
(max
.)
Front-connected
Rear-connected
Interpole barrier (removable)
M6Mounting screw
M6Tapped hole
Groove for dissipating heat generated by overcurrent
M10 screw
Mounting hole
Mounting plate
Cond
ucto
r ov
erlap
, max
M6Tapped hole
ON side:36OFF side:35
Preparation of conductor With extension bars (optional) Drilling plan (front view)
Drilling plan (front view) Panel cutout (front view)
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.
Stud can be turned 45° or 90°
Trip button (red)
199
Time/Current characteristic curves
Ambient Compensating Curves
Characteristics and Outline Dimensions
Ratings and Specifications
Molded Case Circuit Breakers
Type Number of poles■RatingsRated current, ACalibrated at 40°C
Rated insulation voltage〔Ui〕 V ACRated impulse withstand voltage 〔U imp〕 kV■Rated breaking capacity, kAIEC60947-2 AC 690VIcu/Ics(sym) 500V
440V415V380V240V
q DC 250V125V
■Rated short time withstand current, kAWeight (' marked standard type) kg■Connections and MountingsFront-connected (FC) Terminal screws
With extension barsRear-connected (RC) Bolt studs
Flat bar studsPlug-in (PM)Draw-out type (DR)DIN rail mountClip-in chassis mount■Accessories (optional) Symbol
Motor operator MCExternal operating Breaker-mounted HBhandle Door-mounted (variable depth) HPToggle extension HAMechanical interlock9 Slide type MS
Link type MLWire type MW
Toggle holder HHToggle lock HLTerminal cover For front-connected CF
For rear-connected and plug-in CRInterpole barrier BATerminal block for lead TFDoor flange DF
■Standard specificationsOvercurrent trip mechanismTrip button (color)Handle position indication (ON: Red, OFF: Green)Suitability for isolation
8 S400-CF, S400-NF, S400-GF, S400-PF(400A Frame)
seco
ndm
inut
eho
ur
100
125
200
300
400
500
700
1000
1500
2000
3000
4000
5000
8000
0.005
0.01
0.02
0.040.06
0.1
0.2
0.40.6
1
2
46
10
203040
1
2
46
10
203040
1
23
Percent Rated Current
Tri
pp
ing
Tim
e
Setting tolerance(X6) Setting tolerance(X12)
X6X12
Min.(300–400A)
Min.(125–250A)
Max.(300–400A)
Max.(125–250A)
Adjustable setting range of magnetic trip(Notes:2.)
140
130
120
110
100
90
0 10 20 30 40 50
175A 125A
300A 200A
350A
225A
400,250,150A
Calibratedtemperature
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
Magnetic trip pickup current
S400-CF3 4
125 250150 300175 350200 400225
6908
15/1522/2230/3036/3636/3650/5040/4040/40―4.2 5.6
'
○(BAR)―○○▲――
●●●―●●●
●
●●●③●●
Thermal-magneticYes (Red)YesYes
S400-NF3 4
125 250150 300175 350200 400225
6908
20/1530/3045/4550/5050/5085/8540/4040/40―4.2 5.6
'
○(BAR)―○○▲――
●●●―●●●
●
●●●e
●●
Thermal-magneticYes (Red)YesYes
S400-GF3 4
125 250150 300175 350200 400225
6908
20/1530/3065/5070/5070/50100/8540/4040/40―4.2 5.6
'
○(BAR)―○○▲――
●●●―●●●
●
●●●e
●●
Thermal-magneticYes (Red)YesYes
S400-PF3 4
250300350400
6908
20/1530/3080/8085/8585/85100/8540/4040/40―4.2 5.6
'
○(BAR)―○○▲――
●●●―●●●
●
●●●e
●●
Thermal-magneticYes (Red)YesYes
Combinations of Internally Mounted Accessories(Optional)
SH UV AX AL
3・4
AL
SH
AL
UV
AX
UV
AX
AL
AX
SH
AX
UV
AL
AX
SH
AL
Pole
s
ToggleLeft poleRight pole
Auxiliary switch Alarm switchUnder
voltage trip Shunt trip
Rated current Magnetic trip pickup current(A) Adjustable range (A)
In× 12 11 10 9 8 7 6125 1500 1375 1250 1125 1000 875 750150 1800 1650 1500 1350 1200 1050 900175 2100 1925 1750 1575 1400 1225 1050200 2400 2200 2000 1800 1600 1400 1200225 2700 2475 2250 2025 1800 1575 1350250 3000 2750 2500 2250 2000 1750 1500300 3600 3300 3000 2700 2400 2100 1800350 4200 3850 3500 3150 2800 2450 2100400 4800 4400 4000 3600 3200 2800 2400Notes:1. Setting tolerance: ±20%. 2. The protection characteristic curves assume that the magnetic
trip current is adjustable. 3. Unless otherwise stated when ordering, the selector dial is
factory set to position “12”. 4. The trip pickup current of DC models is not adjustable; the dial
position corresponding to the trip pickup current is marked with awhite point.
Ext
erna
llym
ount
ed
Notes:' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ▲ : Semi-standard. ● : “yes” or “available”. ― : “no” or “not available”. 1 : DC rating available on request. 3 : Line side interpole barriers are supplied as standard. (Front connection only) 9 : The mechanical interlock is not applicable to the draw-out type (DR).
Outline dimensions (mm) S400-CF, S400-NF, S400-GF, S400-PF
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
200
SE
CT
ION
8
H
CL
CL
CLCL CL CL
L HL
L
HLHL
HL
HL HL
CL CL CL CL CL
HL HL HL HL HL HL
H 4P3P
20(m
ax.)ø11
30(max.)
CL
CL
CL
2✕2-
ø6
20(m
ax.)
260
85.397
1038
21422
8
90102
116 116
14.7
110 120
28 14.5
30 44.5
368
454545 45
70 115
5151
127.5145
90 45140
185
3014
.544
.5
25(max.)12
ø14 148
44.5
349
358
ø11
60 60 60126.581.5
260
971038
90102
228
260
830
ø13
127.5
30 45 45 45
103
11070
153915
39 214
4545
228
90 45 45 45
88
ø36
ø13
51
116 116
51
315
286
260
140 18570 115
20 3643
16
151 52 4
228
276
315
90 45 45 45
70 1070
2014
020
4848
2020
30.5 30.5
9025
2514
0
70 7010
40
40
5
5
(max
.)
52.5
145
118
92
R6
3P
4P
36.5
4P3P
3P 4P 4P3P 3P 4P
Front-connected
Rear-connected
Plug-in
Interpole barrier (removable)
M6Mounting screw
M6Tapped hole
Groove for dissipating heat generated by overcurrent
M10 screwMounting hole
Mounting plate
Cond
ucto
r ov
erlap
, max
Cond
ucto
r ov
erlap
, max
M6Tapped hole
ON side:36OFF side:35
Preparation of conductor With extension bars (optional) Drilling plan (front view)
Drilling plan (front view) Panel cutout (front view)
M10screw
M5Mounting screw
Conductor width, max. 30
Mounting angle
Mounting base (rear view)
Detail of connecting part
Drilling plan (front view)
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.
Stud can be turned 45° or 90°
Preparation of conductor
Trip button (red)
S800-CF, S800-NF, S800-RF8 (800A Frame)
Combinations of Internally Mounted Accessories(Optional)
SH UVAX AL
3・4
AL
SH
AL
UV
AX
UV
AX
AL
AX
SH
AX
UV
AL
AX
SH
AL
Pole
s
ToggleLeft poleRight pole
Auxiliary switch Alarm switchUnder
voltage trip Shunt trip
201
Characteristics and Outline Dimensions
Ratings and Specifications
Molded Case Circuit Breakers
Time/Current characteristic curves
Ambient Compensating Curves
hour
min
ute
seco
nd
100
125
200
300
400
500
700
1000
1500
2000
3000
4000
5000
8000
0.005
0.01
0.02
0.040.06
0.1
0.2
0.40.6
1
2
46
10
203040
1
2
46
10
203040
1
23
X10X5
Percent Rated Current
Tri
pp
ing
Tim
e
Adjustable setting range of magnetic trip
Max.
Min.
Setting tolerance(X5) Setting tolerance(X10)
Magnetic trip pickup currentRated current Magnetic trip pickup current
(A) Adjustable range (A)In× 10 9 8 7 6 5
500 5000 4500 4000 3500 3000 2500600 6000 5400 4800 4200 3600 3000630 6300 5670 5040 4410 3780 3150700 7000 6300 5600 4900 4200 3500800 8000 7200 6400 5600 4800 4000
Notes:1. Setting tolerance: ±20%.
2. Unless otherwise stated when ordering, the selector dial is
factory set to position “10”.3. The trip pickup current of DC models is not adjustable; the dial
position corresponding to the trip pickup current is marked with awhite point.
140
130
120
110
100
90
0 10 20 30 40 50
700A
800A
500A
600A
630A
Calibratedtemperature
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
Type Number of poles■RatingsRated current, ACalibrated at 40°C
Rated insulation voltage〔Ui〕 V ACRated impulse withstand voltage 〔U imp〕 kV■Rated breaking capacity, kAIEC60947-2 AC 690VIcu/Ics(sym) 500V
440V415V380V240V
q DC 250V125V
■Rated short time withstand current, kAWeight (' marked standard type) kg■Connections and MountingsFront-connected (FC) Terminal screws
With extension barsRear-connected (RC) Bolt studs
Flat bar studsPlug-in (PM)Draw-out type (DR)DIN rail mountClip-in chassis mount■Accessories (optional) Symbol
Motor operator MCExternal operating Breaker-mounted HBhandle Door-mounted (variable depth) HPToggle extension HAMechanical interlock9 Slide type MS
Link type MLWire type MW
Toggle holder HHToggle lock HLTerminal cover For front-connected CF
For rear-connected and plug-in CRInterpole barrier BATerminal block for lead TFDoor flange DF
■Standard specificationsOvercurrent trip mechanismTrip button (color)Handle position indication (ON: Red, OFF: Green)Suitability for isolation
S800-CF3 4
500600630700800
6908
10/1015/1530/3036/3636/3650/5050/5050/50―8.5 11.5
―'
―○○▲――
●●●●●●●
●
●●●e
●●
Thermal-magnetic(adjustable)Yes (Red)YesYes
S800-NF3 4
500600630700800
6908
20/2030/3045/4550/5050/5085/8550/5050/50―8.5 11.5
―'
―○○▲――
●●●●●●●
●
●●●e
●●
Thermal-magnetic(adjustable)Yes (Red)YesYes
S800-RF3 4
500600630700800
6908
25/2045/3465/5070/5070/50100/7550/5050/50―8.5 11.5
―'
―○○▲――
●●●●●●●
●
●●●e
●●
Thermal-magnetic(adjustable)Yes (Red)YesYes
Ext
erna
llym
ount
ed
Notes:' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ▲ : Semi-standard. ● : “yes” or “available”. ― : “no” or “not available”. 1 : DC rating available on request. 3 : Line side interpole barriers are supplied as standard. (Front connection only) 9 : The mechanical interlock is notapplicable to the draw-out type (DR).
Outline dimensions (mm) S800-CF, S800-NF, S800-RF
HLHL HL
HL HLHL HL
HL HL
HL HL
HL
ASL ASL
4P3P
ASL
3P 4P
ASL
[max
.]
ASL
3P 4P
ASL
3P 4P
3P 4P
ASL ASL ASL
ASL
3P 4P
ASL
HL HL
ASL
t1 L1
t2 L2
1038
1038
28 13
145
70 70 70
13
70 70 70 70 70 43 43 43 43
117
1
26
10
122
1
03
20
32
25
136
5
1
27
5
30.
5
80.5
105 280 145
127.5 210 51.6
116 70 70 70 70 70
170
40.5
23
71.5 43.5
40
175
158
.5
46.
5 182
6
3 6
3 2
1 2
1
26.
5
79.
5 7
0.5
126
1
17
80.5
117
126
3P4P
ø13
8
ø48
55.5
132
141
149.
5
ø13
127.5
27
ø13
100 170
50
79.
5 7
0.5
15
15
ø9
70 70
42
3P4P
172
92
R6
1038
Drilling plan (front view) Panel cutout (front view)
Mounting base (rear view)
Drilling plan (front view)
Detail of connecting part and Preparation of conductor
Drilling plan (front view)Front-connected
Rear-connected
Plug-in
Conductor overlap, max
Conductor overlap, max
M8Tapped hole
M8Tapped hole
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Interpole barrier (removable) Mounting hole
Mounting hole
M8Mounting screw
M8Mounting screw
M8Mounting screw
Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.
Trip button (red)
Trip button (red)
Toggle extension (removable)
Toggle extension(removable)
Toggle extension (removable)
M12 screw
Stud can be turned 90° ø15 for accessory wiring
when necessary
Groove for dissipating heat generated by overcurrent
140
210
70 70 70
105 175
280
70
51
170
40
13
145
70
28 13
127.5
80
273
8
0
15
32 8
25
55.
5 4
6.5
110
117
1
26
141
1
32
80.5
170
51
90
51
170
51
170
90
273
100
SE
CT
ION
8
202
ASL : Arrangement Standard Line HL : Handle Frame Centre Line CL : Handle Centre Line
Rated current t1 t2 L1 L2630A 8 8 32 34800A 10 10 32 35
TERASAKI ELECTRIC CO., LTD.
Head Office: 7-2-10 Hannancho, AbenokuOsaka, Japan
Circuit Breaker Division: 7-2-10 Kamihigashi, Hiranoku Osaka, Japan
Telephone: 81-6-6791-9323Fax: 81-6-6791-9274Email: [email protected]
http://www.terasaki.co.jp/
TERASAKI ELECTRIC (EUROPE) LTD.
79 Beardmore Way, Clydebank Industrial EstateClydebank, Glasgow, G81 4HT, Scotland (UK)
Telephone: 44-141-941-1940Fax: 44-141-952-9246Email: [email protected]
http://www.terasaki.com/
TERASAKI ITALIA s.r.l.
Via Ambrosoli, 4A-20090 Rodano, Milano, Italy
Telephone: 39-02-92278300Fax: 39-02-92278320Email: [email protected]
http://www.terasaki.it/
TERASAKI ELECTRIC (EUROPE) LTD.
BRANCH IN SPAIN
Cal Ros Dels Ocells 5-7, Granollers 08403, Barcelona, Spain
Telephone: 34-93-879-60-50Fax: 34-93-870-39-05Email: [email protected]
http://www.terasaki.es/
TERASAKI SKANDINAVISKA AB
Box 2082 SE-128 22 Skarpnäk Sweden
Telephone: 46-8-556-282-30Fax: 46-8-556-282-39Email: [email protected]
http://www.terasaki.se/
TERASAKI CIRCUIT BREAKERS (S) PTE. LTD.
9 Toh Guan Road East 03-01 Alliance BuildingSingapore 608604
Telephone: 65-6425-4915Fax: 65-6425-4351Email: [email protected]
TERASAKI ELECTRIC (M) SDN, BHD.
Lot 3, Jalan 16/13D, 40000 Shah Alam, Selangor DarulEhsan, Malaysia
Telephone: 60-3-5549-3820Fax: 60-3-5549-3960Email: [email protected]
TERASAKI DO BRASIL LTDA.
Rua Cordovil, 259-Parada De Lucas, 21250-450Rio De Janeiro-R.J., Brazil
Telephone: 55-21-3301-9898Fax: 55-21-3301-9861Email: [email protected]
http://www.terasaki.com.br
TERASAKI ELECTRIC (CHINA) LTD.
72 Pacific Industrial Park, Xin Tang Zengcheng,Guangzhou 511340, China
Telephone: 86-20-8270-8556Fax: 86-20-8270-8586Email: [email protected]
TERASAKI ELECTRIC GROUP SHANGHAI
REPRESENTATIVE OFFICE
Room No. 1405-6, Tomson Commercial Building710 Dong Fang Road, Pudong, Shanghai, 200122, China
Telephone: 86-21-58201611Fax: 86-21-58201621Email: [email protected] and specifications are subject to change without notice.
CAT REF. ’11-I61E