the ventilation of the future.. what is ec? ac – asynchronous motor
TRANSCRIPT
The ventilation of the future.
What is EC?
AC – Asynchronous motor
EC – Electronically commutated motor
EC motor-driven fans
The use of energy efficient, EC-motor driven, fans results in higher efficiencies.
Easy control: CO2
Humidity
Temperature
Pressure
Constant air volume
Stepless speed control
EC on average uses 30% less power than AC
In some applications in excess of 50%
Energy consumption
Speed control
Efficiency
Legislation
EU adopts The Kyoto Protocol
Aim:
• Reduce emissions by 20% by 2020
Directive:
• Mandatory for all 27 EU countries
• All fans sold or imported in Europe
EuP/ErP
Lot 6 Lot 10 Lot 11
Roof and box fans
Fans < 125 W
Fans125 W to 500 kW
EuP / ErP
Motors0.75 kW to 500 kW
2010 2011 2012 2013 2014 2015 2016 2017
EuP/ErP – Lot 11
Lot 6 Lot 10 Lot 11
Roof and box fans Ventilatoren< 125 W
Fans125 W to 500 kW
EuP / ErP
2010 2011 2012 2013 2014 2015 2016 2017
IE2
Motors0.75 kW to 500 kW
IE3IE3
Lot 11 - Motors
How does Lot 11 impact motors?
2010 2011 2012 2013 2014 2015 2016 2017
IE3 > 7.5 KW
IE2 IE3 > 0.75 KW
Legislation – Motors
• Implemented 16th June 2011- IE2
• IEC - International Electrotechnical Commission
• IEC 60034-2-1: 2007
• IEC 60034-2: 1996 (EFF) EXP Nov 1st 2010
Motor efficiencies
High Efficiency
Low Efficiency
EFF 1
EFF 2
IE4 Super Premium (Proposed)
IE3 Premium Efficiency
IE2 High Efficiency
IE1 Standard Efficiency
Exceptions
Exceptions
Lot 11 - Fans
Lot 6 Lot 10 Lot 11
Roof and box fans Fans< 125 W
Fans125 W to 500 kW
EuP / ErP
2010 2011 2012 2013 2014 2015 2016 2017
? ?
Efficiency requriement 1
Efficiency requirement 2
EuP directive – Lot 11
Between 0.125KW and 500KW input
Applies to:
• Fans integrated in a unit
• Stand alone units
What fans are affected?
All fan typesAll fan types
• Axial fans
• Forward curved centrifugal/radial bladed
• Backward curved centrifugal without housing
• Backward curved centrifugal with housing
• Cross flow
• Mixed flow
Exceptions
• Atex fans
• Emergency smoke extract
• Railways (Transportation)
• Kitchen hoods - Less than 280W
• Laundry dryers - Less than 3KW
• Box fans
ExceptionsBrussels, XXX
C(2010) YYY finalArticle 1Subject matter and scope1. This Regulation establishes ecodesign requirements for the placing on the market or putting into service of fans, including those integrated in other energy-related products as covered by Directive 2009/125/EC.2. The Regulation shall not apply to fans integrated in:(i) products with a sole electric motor of 3 kW or less where the fan is fixed on the same shaft used for driving the main functionality;(ii) laundry and washer dryers ≤ 3 kW maximum electrical input power;(iii) kitchen hoods < 280 W total maximum electrical input power attributable to the fan(s).3. This Regulation shall not apply to fans which are:(a) designed specifically to operate in potentially explosive atmospheres as defined in Directive 94/9/EC(b) designed for emergency use only, at short-time duty, with regard to fire safety requirements set out in Directive 89/106/EC(c) designed specifically to operate:(i) a. where operating temperatures of the gas being moved exceed 100ºC;
b. where operating ambient temperature for the motor, if located outside the gas stream, driving the fan exceeds 65°C;(ii) where the annual average temperature of the gas being moved and/or the operating ambient temperature for the motor, if located outside the gas stream, are lower than -40ºC;(iii) with a supply voltage >1 000 V AC or >1 500 V DC;(iv) in toxic, highly corrosive or flammable environments or in environments with abrasive substances.
Existing systems
• Do not have to replace or modify before the ErP start date.
• ErP non-compliant fans can be retrofitted up to 31st Dec 2014.
• After 1st Jan 2015 these fans will also have to comply with the then current ErP directive.
What now?
• Fans will have to adhere to the minimum efficiency levels.
• Defined at the best operating point based on electrical power input.
• Efficiency of the complete fan is assessed.
Fan types Measurement category
Efficiency category
Power range P in kW
Target energy efficiency Efficiency grade
(N) ab 01.01.2013
Efficiency grade
(N) ab 01.01.2015
Axial fan A, C static 0.125 ≤ P ≤ 10 ηtarget = 2.74 ∙ ln(P) – 6.33 + N 36 40
10 < P ≤ 500 ηtarget = 0.78 ∙ ln(P) – 1.88 + N
B, D total 0.125 ≤ P ≤ 10 ηtarget = 2.74 ∙ ln(P) – 6.33 + N 50 58
10 < P ≤ 500 ηtarget = 0.78 ∙ ln(P) – 1.88 + N
Centrifugal forward curved fan and centrifugal radial bladed fan
A, C static 0.125 ≤ P ≤ 10 ηtarget = 2.74 ∙ ln(P) – 6.33 + N 37 44
10 < P ≤ 500 ηtarget = 0.78 ∙ ln(P) – 1.88 + N
B, D total 0.125 ≤ P ≤ 10 ηtarget = 2.74 ∙ ln(P) – 6.33 + N 42 49
10 < P ≤ 500 ηtarget = 0.78 ∙ ln(P) – 1.88 + N
Centrifugal backward curved fan without housing
A, C static 0.125 ≤ P ≤ 10 ηtarget = 4.56 ∙ ln(P) – 10.5 + N 58 62
10 < P ≤ 500 ηtarget = 1.1 ∙ ln(P) – 2.6 + N
Centrifugal backward curved fan with housing
A, C static 0.125 ≤ P ≤ 10 ηtarget = 4.56 ∙ ln(P) – 10.5 + N 58 61
10 < P ≤ 500 ηtarget = 1.1 ∙ ln(P) – 2.6 + N
B, D total 0.125 ≤ P ≤ 10 ηtarget = 4.56 ∙ ln(P) – 10.5 + N 61 64
10 < P ≤ 500 ηtarget = 1.1 ∙ ln(P) – 2.6 + N
Mixed flow fan A, C static 0.125 ≤ P ≤ 10 ηtarget = 4.56 ∙ ln(P) – 10.5 + N 47 50
10 < P ≤ 500 ηtarget = 1.1 ∙ ln(P) – 2.6 + N
B, D total 0.125 ≤ P ≤ 10 ηtarget = 4.56 ∙ ln(P) – 10.5 + N 58 62
10 < P ≤ 500 ηtarget = 1.1 ∙ ln(P) – 2.6 + N
Cross flow fan B, D total 0.125 ≤ P ≤ 10 ηtarget = 1.14 ∙ ln(P) – 2.6 + N 13 21
10 < P ≤ 500 ηtarget = N
Regulation enforcement
• UK Market Surveillance Authority (MSA)
• Eco-design directive
• National Measurement Office
For more information: www.rohs.gov.uk/EUP/
End of presentationEnd of presentation