thermal and lifetime behavior of innovative insulation systems for rotating machines

Upload: greg-rabulan

Post on 09-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 Thermal and Lifetime Behavior of Innovative Insulation Systems for Rotating Machines

    1/4

  • 8/8/2019 Thermal and Lifetime Behavior of Innovative Insulation Systems for Rotating Machines

    2/4

    Proceedings of the 2008 International Conference on Electrical Machines

    2

    III. APPLIED TESTS

    Following tests were applied to the generator bars:

    Measurement of dielectric properties and materialconsistency: The dielectric constant was determined bymeasurement and the resin content by burning out in afurnace.

    Thermal observation of the warming of the voltagegrading end corona protection tape. This test was done by means of a wireless temperature measurement(Infra-red camera) at different rated voltages.

    Lifetime of generator bars. The generator bars weretested with high voltage stress: 2.2 and 3.0 times ratedvoltage. The residual time until breakdown wasrecorded.

    IV. DIELECTRIC CONSTANT MEASUREMENT AND RESINCONTENT DETERMINATION

    For the determination of the dielectric behaviour an

    unbalanced dissipation factor bridge was used [3]. The

    capacitance of the model bars was measured at several

    points on both sides and an average value of the dielectric

    constant r was calculated. The test setup of the electrode

    configuration is shown in Fig. 2.

    Fig. 2: Test setup for capacitance and rmeasurement

    The result of these measurements showed a variance of

    the capacitances and r values of 5 %, which is caused by

    deviations of the dimensions due to production of the bars.

    The average

    rof the VPI bars was between 4.0 and 4.5 andthe RR bars showed a r of 4.9 up to 5.2. A significant

    difference between the standard material and the new

    material could not be found out.

    By the means of incinerating the resin content of the bars

    was determined with a high-temperature furnace. The bars

    were heated until the resin burned out and only mica and

    glass was left in the insulation. By weighing with a

    chemical balance the resin content could be calculated.

    Typical values for the resin content are 27 % for VPI STD,

    22 % for VPI FAB, 34 % for RR STD and 30 % for RRFAB insulations.

    V. THERMAL BEHAVIOUR OBSERVATION

    For the observation of the thermal behaviour of the

    different model bars and the performance of the end corona

    protection a test setup as shown in Fig. 3 was used.

    The bars were clamped on a bracket and the temperature

    was measured with an IR-camera [4].

    Fig. 3: Test setup for observation of thermal behaviour

    The generator bars were loaded with following electrical

    stress ratings: nominal voltage UN, 2xUN+1kV, 3xUN. A

    test cycle took a duration of 10 minutes and the starting

    temperature for each cycle had to be the same (room

    temperature). The special interest of these tests was the

    temperature rise, the location of hotspots and the

    determination of absolute temperatures. The results showed

    a similar behaviour of bars with same production

    technology and used materials. Hot spots could be observedat the point with the highest electrical field strength such as

    at the corners and at the beginning of the stress grading

    area. Fig. 4 is an example of an IR picture.

  • 8/8/2019 Thermal and Lifetime Behavior of Innovative Insulation Systems for Rotating Machines

    3/4

    Proceedings of the 2008 International Conference on Electrical Machines

    3

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    110

    120

    1.0 2.0 3.0

    Voltage U/UN

    Temperature[C]

    STD VPI after 1 min (3.0 kV/mm)STD VPI after 10 min (3.0 kV/mm)FAB VPI after 1 min (4.0 kV/mm)

    FAB VPI after 10 min (4.0 kV/mm)STD RR after 1 min (2.75 kV/mm)STD RR after 10 min (2.75 kV/mm)FAB RR after 1 min (3.5 kV/mm)FAB RR after 10 min (3.5 kV/mm)

    Fig. 4: Thermal performance of voltage grading tape

    Hotspots at the points of highest electrical field strengths

    can be easily recognized as well as at the edges of the bars.

    Fig. 5: Warming-up of voltage grading tape

    The results showed that VPI bars with new FAB

    technology had the highest temperatures as to be expected

    due to testing at very high field strength of 4.0 kV/mm.

    The maximum temperature of the end corona protection

    after 10 min at 3 times the nominal voltage reached almost

    120 C

    In this test the temperature of RR STD and FAB

    generator bars was significantly lower compared to VPI

    bars as they were operating at a lower electric stress.

    VI. LIFE TIME TESTS

    The life time behaviour of six different insulation

    systems for generator bars was tested.

    The superior electrical properties of the Resin Rich and

    VPI FAB insulation system have been described in detail

    earlier in [1], [2]. In this voltage endurance test the

    influence of different types of mica, grain sizes of mica and

    production technologies according to table II was

    examined.

    For each system a number of four similar bars wereproduced and two voltage levels (2.2 and 3.0 times nominal

    voltage) were applied for the voltage endurance tests. The

    tests were stopped after a maximum of 1000 h when no

    breakdown of the insulation system has occurred.

    The test setup as shown in Fig. 6 was designed to

    simulate realistic conditions; according to this request a

    conducting tape was applied to reproduce the grounded

    stator slot.

    Fig. 6: Test setup for voltage endurance tests

    In addition a dissection of the generator bars and

    microscopic inspection of the breakdown channel was

    done. The bars were cut to thin slices that a microscope for

    transmitted light could be used. Good results can be

    achieved by polishing the surface of conductor and

    insulation system. An example of a prepared bar can be

    found in Fig. 7.

  • 8/8/2019 Thermal and Lifetime Behavior of Innovative Insulation Systems for Rotating Machines

    4/4

    Proceedings of the 2008 International Conference on Electrical Machines

    4

    11,5

    8

    25,9

    1

    0,1

    0,

    06

    1100

    15,

    07

    38,

    19

    2,

    5

    2,

    04

    488,

    61

    27,

    41

    27,

    85

    1260

    258,

    66

    178,

    07

    1100

    1100

    515,

    3

    417,

    96

    1100

    1100

    71,

    90

    155,

    57

    114,

    84

    1,00

    10,00

    100,00

    0,01 0,1 1 10 100 1000 10000

    Lifetime [h]

    ElectricFieldStrength[kV/mm]

    LD VPI FAB

    LD RR STD

    LD VPI STD

    Fig. 7: Preparation of bars for optical investigation

    VII.LIFE TIME DIAGRAM

    The test results of the voltage endurance tests were

    evaluated by application of a life time diagram with

    doubled logarithmic scale according to the inverse power

    law for electrical ageing processes [5]. The statistical

    parameters for this diagram were determined by the median

    of the breakdown times. Normally a Weibull distribution

    [6] is applied for life time investigations of electric

    equipment, but due to a statistically low number of test

    specimen its use was not appropriate.

    The endurance points of the test specimens according to

    table II are displayed in the following diagram.

    Fig. 8: Life time points of VPI and RR bars producedwith different mica types

    Uncalcined mica as well as muscovite with big grain size

    show a tendency to have slightly increased life times.

    To obtain statistically significant results further

    evaluations with more specimens have to be performed.

    VIII. SUMMARY

    The dielectric, thermal and lifetime behaviour of

    different motor and generator insulation systems were

    investigated. The test objects were produced in RR and VPI

    technology comparing a standard (STD) and innovative

    (FAB) glass cloth carrier. Also different types of mica

    paper and grain sizes were used.

    The measurement of the dielectric constant showed a

    deviation of 5 % due to production variances. The influence

    due to the variation of the material was in the same range.

    For this reason the resin content was determined by using a

    high-temperature furnace to glow out the resin.

    The observation of the thermal behaviour was done with

    warm-up test. The evaluation of the results showed that the

    highest temperatures were recorded at the VPI FAB

    material having the highest electrical load.

    The best results concerning voltage endurance was also

    recorded at the VPI bars, the FAB bars showed better

    lifetime behaviour with respect to the applied field strength.

    ACKNOWLEDGMENT

    The authors gratefully acknowledge the manufacturer of

    the mica insulation system, Isovolta, System Development

    High Voltage, for the support and production of the model

    generator bars.

    REFERENCES

    [1] Ladsttter W., Marek P., Grubelnik W., Senn F.: New InsulationTechnology impacts Generator Design, Power-Gen InternationalConference 2006 Orlando

    [2] Senn F., Ladsttter W., Grubelnik W., Marek P.: Improved Mica Insulation System for HV Rotating Machines, DISEE 2006,International Conference, Slovakia

    [3] LDV-6, www.ldic.de[4] www.FLIR.com[5] Sumereder C., Weiers T., Significance of Defects Inside In-Service

    Aged Winding Insulations, IEEE Trans. On Energy Conversion, Vol.23, No. 1, March 2008, p. 9-14

    [6] Sumereder C., Statistical Lifetime of Hydro Generators and FailureAnalysis, IEEE Trans. DEI, Vol.15, No.3, June 2008