Page 1: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Rev. 12/2018Id.No. DOK50036

Thermo G 300with control unit 1588

Workshop Manual

HEATING SYSTEMS

Page 2: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G Content

1 Introduction 101

1.1 Content and purpose 1011.2 Meaning of warnings and highlighted content 1011.3 Further documentation to be used 1011.4 Safety information and regulations 1011.4.1 General safety regulations 1011.4.2 Other safety information 1021.5 Suggestions for Improvement and change 102

2 Technical data 201

2.1 Heater 2012.1.1 Altitude capability 2012.2 Gas pressure regulator 2022.3 Fuel 2022.4 Circulating pump 202

3 Description of assemblies and components 301

3.1 Burner head 3023.1.1 Combustion air fan 3023.1.2 Control device 3023.1.3 Mixing chamber 3023.1.4 Heat protection cover 3033.1.5 ZF Module with electronic ignition unit and ionization electrode 3033.1.6 Flame tube 3033.2 Combustion chamber 3033.3 Heat exchanger 3033.4 Temperature sensors with water temperature sensor and integrated overheating protection 3043.5 Gas pressure regulator 3053.5.1 Heating of the gas pressure regulator 3053.6 Circulating pump 305

4 Heater functions 401

4.1 General heater functionality description 4014.2 Operational heater sequence 4024.2.1 Switching on and start 4024.2.2 Heating operation 4024.2.3 Switching off 4034.3 Malfunction interlock and heater interlock 4044.4 Malfunction interlock 4044.4.1 Malfunctions during switching-on and start procedure 4044.4.2 Malfunctions during heater operation 4044.4.3 Malfunctions during purge cycle 4044.4.4 Malfunction interlock release and error clearance 4054.5 Heater interlock 4054.5.1 Heater interlock release 4054.6 Error output 405

5 Troubleshooting 501

5.1 General 5015.2 General error symptoms 5015.3 Malfunction code output via flash code 5035.4 Error symptoms during functional tests with malfunction code output 5055.4.1 Error symptom "No start within safety period" 5055.4.2 Error symptom "Flame interruption" 505

1

Page 3: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G Content

5.4.3 Error symptom "Low voltage" 5075.4.4 Error symptom "Extraneous light detected prior to ignition or during purge cycle" 5085.4.5 Error symptoms "Temperature sensor / overheating protection defective" 5095.4.6 Error symptom "Solenoid valve 1 or 2 defective" 5095.4.7 Error symptom "Overheat protection has triggered" 5105.5 Individual component tests 5115.5.1 General visual inspection 5115.5.2 Heat exchanger visual inspection 5115.5.3 Visual inspection of exhaust outlet and exhaust line 5115.5.4 Combustion chamber visual inspection 5115.5.5 Resistance check of the temperature sensor with integrated overheat protection 5115.5.6 Fan and combustion air intake line visual inspection 5125.5.7 Burner motor inspection 5125.5.8 ZF module inspection 5125.5.9 Ignition electrode inspection 5135.5.10 Heat protection cover inspection 5145.5.11 Gas pressure regulator inspection 514

6 Wiring diagrams 601

6.1 General 601

7 Servicing 701

7.1 General 7017.2 Heater Servicing 7017.3 Vehicle Servicing 7017.4 Heater test run 7017.5 Servicing 7017.6 Measurement and adjustment of the exhaust CO2 content 7027.6.1 Measurement of the exhaust CO2 content 7027.6.2 Adjustment of the exhaust CO2 content 702

8 Removal and installation of components and of the heater 801

8.1 General 8018.2 Removal and installation of the temperature sensor with integrated overheating protection 8018.3 Hood removal and installation 8028.4 Burner head Removal and installation 8028.5 Separating the fan housing from the mixing chamber 8038.6 Control device removal and Installation 8048.7 Fan wheel removal and installation 8048.8 Fan motor removal and installation 8048.9 ZF module removal and installation 8048.10 Combustion chamber removal and installation 8068.11 Heat exchanger removal and installation 8068.12 Heater removal and installation 8078.13 Gas pressure regulator removal and installation 8078.14 Start-up after installation of burner head, heater or heat exchanger 8078.14.1 Bleeding of the coolant circuit 807

9 Modifications and retrofits 901

2

Page 4: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G Content

10 Packing / storage and shipping 1001

10.1 General 1001

Appendix

Scheduled heater maintenance A-1

3

Page 5: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 1 Introduction

1 Introduction

1.1 Content and purpose

This workshop manual is intended for the maintenance and repair of the water heaters (hereinafter heaters) Thermo G300 on the gas low pressure side.

Work on the heater must only be carried out bytrained and / or by Valeo-trained personnel.

Any work on the gas supply line, for example whenremoving or installing the gas regulator, may only becarried out by persons with the appropriate officialauthorization.

1.2 Meaning of warnings and highlighted content

Throughout this manual the emphasized words Warning!, Caution!, ATTENTION: and NOTE: used as follows:

This caption is used to indicate possible severe inju-ries or fatal accidents if instructions or proceduresare carried out incorrectly or entirely disregarded.

This caption is used to indicate possible minor inju-ries if instructions or procedures are carried outincorrectly or entirely disregarded.

ATTENTION:

This caption points to actions which may cause ma-terial damage.

NOTE:This caption is used to draw attention to an important feature.

1.3 Further documentation to be used

In the Thermo G Operating and Service Instructions you will find all the necessary information as well as useful hints relating to the safe operation of the heater.The Thermo G Installation Instructions contain all required information as well as useful hints for the correct installation of the heater.Spare parts required during maintenance and repair, you can order using the Thermo G Spare Parts List at Valeo.If necessary, Valeo will publish Technical Information (TI) for operation, maintenance or repair of the heater.The Heater Accessories Catalog contains useful acces-sories for your heater installation.

All mentioned documents you will find on the Valeo website www.valeo-thermalbus.com/eu_de/Service.

1.4 Safety information and regulations

Basically, general accident pevention provisions and the valid industrial safety directions must be adhered to.

"General Safety Regulations" which exceed the frame-work of these provisions are listed below. The specific safety regulations which affect the present manual are issued in the individual sections or procedures with headings in capital letters.

1.4.1 General safety regulations

Read the Thermo G Operating and Service Instruc-tions before operating the heater for first time.

Familiarize yourself with the Thermo G InstallationInstructions before you make any modifications to theexisting heater installation.

NOTE:

The Thermo G Operating and Service Instructions containsafety instructions and regulations to be followed for safeoperation of the heater.

The Thermo G Installation Instructions contain the statutory regulations and other safety hints and regula-tions for the proper installation of the heater.

Danger to life and health!Warning!

Danger to life and health!Warning!

Hazardous to health!Caution!

Danger to life and health!Warning!

101

Page 6: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 1 Introduction

1.4.2 Other safety information

1.4.2.1 Temperature sensor

ATTENTION:The temperature sensor cable may not be mechani-cally stressed (pull on the cable, carry the heater at the cable etc.).

1.5 Suggestions for Improvement and change

Please direct any complaints, improvement or modifica-tion suggestions regarding this manual to:

[email protected]

STOP!

102

Page 7: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 2 Technical data

2 Technical data

Unless limiting values are defined, the technical data should be understood with tolerances of ±10% common for heaters at an ambient temperature of +20°C, and at nominal voltage.

2.1 Heater

2.1.1 Altitude capability

The heater is adjusted in the factory, and without change of the CO2 adjustment unlimited usable up to an altitude of 1500 m above MSL, above an altitude of 1500 m up to 2000 m an application with splash guard or combustion air intake line must be used.

Table 201 Technical data heater

Heater

ECE type approval number E1 122R-00 0447 / E1 10R-04 7263Kind of design Low-pressure gas burnerHeat output 30 kW ±10%Fuel CNG (natural gas) classes H/LCombustion gas pressure when it enters the heater -2.5 mbarFuel cosumption at CNG class H < 2.95 kg/hRated voltage 24 VoltOperating voltage range 20.5 ... 30 VoltRated power consumption without circulating pump 110 WCurrent in standby mode < 1 mAMax. current at the circulating pump output 12AUsed gas pressure regulator M96-E-SP

Max. ambient temperature for the heater and control deviceStorage temperature -40 ... +120°C

Operating temperature -40 ... +100°CPermissible sucked in combustion air temp. (permanent) -40 ... +60°CPermissible operating overpressure 2.0 barCapacity of the heat exchanger 1.8 lMinimum capacity of the water system 25.00 lMinimum water flow 2400 l/hCO2 in exhaust gas at rated voltage 8.0 ... 9.0 Vol.-%Switch thresholds switches off at 82°C ±1K

switches on at 72°C ±1KHeater dimensions (tolerance ± 3 mm)

L 585 mm W 247 mmH 226 mm

Heater weight 19 kg

201

Page 8: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 2 Technical data

2.2 Gas pressure regulator

Table 202 Technical data gas pressure regulator

2.3 Fuel

ATTENTION:The heater may only be operated using natural gas (CNG).

As fuel natural gas (CNG) with a minimum methane content of 95 % is used.If natural gas with a less methane content is used (natural gas of class L), the CO2 level must be adjusted according to section 7.6.2 in chapter 7.

The max. oil content of the gas is 10 mg/m3.

2.4 Circulating pump

All desired information about the Valeo circulation pumps can be found under www.valeo-thermalbus.com/eu_en/Products/Pumps.

Gas pressure regulator

Test certificate ECE R110, R10.04Kind of gas Natural gas (CNG) class H/LPermissible oil content in gas < 10 mg/m³Input pressure 5 ... 220 barOutput pressure -0.25 ... -2.5 mbarPressure 1st stage 1.8 ... 3.5 barPressure 2nd stage 0.65 ... 0.75 barOperating temperature -40 ... +120°CSorage temperature -40 ... +100°CRated voltage 24 VNominal coil power at rated voltage (2x) 24 WOperating voltage range 20 ... 30 VDimensions(tolerance ± 3 mm)

L 150 mm W 130 mmH 170 mm

Weight 1.7 kg

202

Page 9: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 3 Description of assemblies and components

3 Description of assemblies and components

The water heater Thermo G 300 operates in conjunction with the on-board heating system

– to heat the passenger compartment– to defrost the windscreen, and– to pre-heat the water-cooled enginesin busses.

The water heater operates independently of the vehicle’s engine and is connected to the cooling system, the gas system and the electrical system of the vehicle. It is screw-mounted to the chassis of the vehicle or an addi-tional crossmember.The heat is generated by the combustion of the gas. Via

the heat exchanger of the heater, the heat is dissipated to a coolant circuit. The adaptation to the changing demand of heat is reached by intermittent operation.An integrated control device controls on the basis of the signals of a temperature sensor the on and off switching of the burner.

The heater Thermo G basically consists of:

– the burner head– the combustion chamber– the heat exchanger– temperature sensor system

In addition, a circulating pump and a gas pressure regu-lator for the gas supply to the heater are installed in the vehicle.

1 Combustion air, intake 2 Hood 3 Fan housing 4 Coolant, inlet 5 Temperature sensor with integrated

overheat protection 6 Coolant, outlet

7 Heat exchanger 8 Plug, sensor system 9 Exhaust outlet10 Control device11 Gas port12 Mesh13 Protective grid

1

2

3

45

6

8

9

7

10

11

12

13

301

Page 10: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 3 Description of assemblies and components

3.1 Burner head

The burner head consists of the components

• combustion air fan• control device• mixing chamber• heat protection cover• ZF module with electronic ignition unit and ionization

electrode• flame tube

3.1.1 Combustion air fan

The combustion air fan transports the air required for combustion from the combustion air intake to the combus-tion chamber.By the air fan in addition, the required amount of gas is sucked in through the gas pressure regulator.

The air fan consists of the combustion air motor and the fan wheel. Air is sucked in through a protective grid in the hood and mixed with the gas in the mixing chamber.

If an air intake extension is used the combustion air is sucked in through this extension.

3.1.2 Control device

The control unit 1588 ensures the operating sequence and monitors the burner operation.

3.1.3 Mixing chamber

In the mixing chamber, the gas is mixed with the combus-tion air and then guided into the flame tube.Across the surface of the mixing chamber evenly small bulges are distributed. On the one hand they generate turbulence for mixing of gas and combustion air and on the other hand they increase the flow-around surface of the mixing chamber. So it is cooled more effectively.

Circlip

Fan wheel

Motor

Control device 1588

Socket P

customerconnector

Socket P

Socket T

diagnostic systemSocket D

Socket Vsolenoid valvesand electrical circulating pump

temperature sensor system

regulator heating

302

Page 11: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 3 Description of assemblies and components

3.1.4 Heat protection cover

The heat protection cover is glued to the mixing chamber.

3.1.5 ZF Module with electronic ignition unit and ionization electrode

The electronic ignition unit induces the high voltage required for ignition of the gas-air mixture. Ignition is triggered by a high voltage spark between the two ignition electrodes.The ZF module is used simultaneously for monitoring the flame in the combustion chamber. In principle it is an ionization flame guard.As ionization electrode one of the two ignition electrodes of the ZF module is used. The counter-electrode is the flame tube, which is connected over a ground terminal to the housing with the control device.

The burning flame establishes an electrically conductive connection from the ionization electrode to the flame tube,

and so to the ground potential. This ionization current is measured in the control device. Thereby, the presence or absence of a flame can be clearly detected.The flame monitoring is part of the control.

3.1.6 Flame tube

The flame tube ensures a defined, homogeneous flame ring in the combustion chamber.For that, a plurality of outlet openings for the gas-air mixture across its surface are distributed in a defined pattern. Each opening acts like a nozzle.

3.2 Combustion chamber

In the combustion chamber the gas-air mixture is burned. It ensures that the generated during combustion hot exhaust gases are directed through the fins of the heat exchanger.

3.3 Heat exchanger

In the heat exchanger, the heat produced by the combus-tion is transferred to the coolant circuit.Inside it has circularly arranged fins through which the hot exhaust gases generated during combustion are led.In the outer shell flows the water of the coolant circuit through. There are two welded-on connection pieces, one for the coolant inlet and one for the coolant outlet.

Heat protection cover

Ignition

Ionization electrode

ZF Module

electrodes

Coolant inlet

Coolant outlet

Exhaust outlet

303

Page 12: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 3 Description of assemblies and components

3.4 Temperature sensors with water temperature sensor and integrated overheating protection

The water temperature sensor captures the coolant temperature at the heat exchanger outlet as electrical resistance.This signal is transmitted to the control unit, where it is processed.The overheating protection integrated into the tempera-ture sensor is responsible for temperature limitation.Similar to the water temperature sensor, the coolanttemperature is captured at the heat exchanger outlet as electrical resistance and transmitted to the control unit.Overheating protection prevents inadmissibly high heater operating temperatures.At a temperature greater than 135°C heater deactivation and interlocking is initiated.

It is not necessary to manually reset the overheating protection.

Connector

Temperature sensorincl. overheat protection

304

Page 13: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 3 Description of assemblies and components

3.5 Gas pressure regulator

Gas is supplied by means of the vehicle’s gas supply sy-stem, in which the gas pressure regulator is incorporated.The gas pressure regulator regulates the storage pres-sure (max. 220 / min. 5 bar) downward in 3 steps to the required operating pressure. In the regulator at a pressure below atmospheric pressure the required quantity of gas is released by a diaphragm valve.

The gas pressure regulator has two solenoid valves (see Fig. below).Solenoid 1 (MV1) opens the gas supply from the storage tank to the gas pressure regulator (high pressure branch).Solenoid 2 (MV2) opens the gas supply from the gas pres-sure regulator to the heater (low pressure branch).Both solenoid valves are controlled by the control device. Thus, the gas pressure regulator is integrated into the control concept of the heater..

3.5.1 Heating of the gas pressure regulator

As the expansion of the compressed gas causes conside-rable cooling, the gas pressure regulator must be warmed up. This is accomplished by its integration into the cool water circuit.By means of T-pieces the gas pressure regulator is connected with the water outlet and the water inlet at the heater.Heated water is branched off at the water outlet and flows through the gas regulator. Then it re-enters the heater through the water inlet.

The gas regulator further has an electrical preheating (ERH). The heating cartridge is connected to a dedicated output on the control unit.The ERH is activated at (water) temperatures below -20°C by the control unit. It is switched off again at a water temperature above -10°C. In addition, the initial cycle time from regularly 15 seconds increases to 40 seconds in water temperatures below -20°C.

3.6 Circulating pump

The externally arranged circulating pump ensures coolant transport within the vehicle and/or heater circulation system.Depending on the application, the circulating pump is swit-ched on via the control unit or directly via the vehicle electrical system and operated during the entire heater operation duration.

Further information on installation and operation of the circulating pump contain the Thermo G Installation instructions.

All service information regarding your Valeo circulating pump(s) can be found under www.valeo-thermalbus.com/eu_en/Products/Pumps.

High pressuresolenoid valve

(MV1)

Low pressuresolenoid valve

(MV2)

Gas outlet

Gas inlet

Water outlet

Water inlet

Screw for fixationof the heating cartridge

305

Page 14: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 4 Heater functions

4 Heater functions

4.1 General heater functionality description

The heater function is based on the principle of the low- pressure gas burner and is controlled by a micro processor. At the same time the integrated control unit takes over all monitoring functions.

An electronically controlled motor drives a fan which sucks in combustion air and gas as fuel. Both are mixed in a mixing chamber. The gas-air mixture is then fed into the combustion chamber of the heater and burned there. The hot exhaust gases flow through a heat exchanger and thus provide heat to the water circuit connected to the heater.The heater works intermittently, that means the gas burner is switched on and off according to the heat demand in the water cycle.

The ignition of the gas-air mixture takes place in the combustion chamber by high-voltage ignition sparks.The flame recognition is carried out by an in the ZF-module (electronic ignition unit) integrated flame guard. The principle is based on the measurement of the ionisa-tion current through the flame.

Depending on the equipment, the heater is switched on and off using a• digital timer• switch• or climate control.

During heating operation the burner is automatically swit-ched on and off. For regulation a temperature sensor is installed in the coolant outlet of the heat exchanger. The heater is switched on, when the temperature falls short of a lower temperature threshold (72°C), and is switched off, if the upper temperature threshold is reached (82°C). A distinction between parking heating and auxiliary heating mode does not exists.

For overheating protection of the heater the switching thresholds are modified by the control unit, if specified temperature gradients are exceeded (gradient evalua-tion).

An operating display is available for monitoring the opera-ting status. The operating display is also used to output error messages in flash code.

401

Page 15: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 4 Heater functions

4.2 Operational heater sequence

4.2.1 Switching on and start

When switched on, the operating display is illuminated, the control unit starts controlled operation and checks the coolant temperature.If the coolant temperature is below the upper temperature threshold, the initial cycle starts. This takes approx. 15 seconds, if the coolant temperature is below -20°C approx. 40 seconds.The initial cycle is used to start the combustion air motor and to query the flame monitoring. By the combustion air motor, the heat exchanger is flushed and at the same time a negative pressure to the gas pressure regulator is generated.The solenoid valve 1 at the gas pressure regulator is swit-ched on (open), so that the gas can flow from the gas tank into the gas pressure regulator.Then, during the pre-ignition the electronic ignition unit is turned on to check its function, and to ensure an imme-diate ignition when the gas flows in.Approximately 1 second later the solenoid valve 2 at the gas pressure regulator is turned on (open) and now gas can sucked in.With the opening of the solenoid valve 2, the safety time begins (10 s).When the gas-air mixture the combustion chamber has reached, it is ignited by the activated electronic ignition

unit.When the ignition of the gas-air mixture was successful, the flame guard detects the flame, and the system state will change to flame stabilization.The state flame stabilization is used to stabilize the combustion and ends with the query / decision of the flame guard "flame". If yes, the system changes into the heating mode.

NOTE:If during the start the main switch is turned off, or the water temperature rises above the upper temperature threshold, or a fault is detected, the system switches into the purge cycle.

4.2.2 Heating operation

After the flame is stabilized, the heater is in controlled operation.The operation indication, the circulating pump, the combustion air motor, the solenoid valves 1 and 2 at the gas pressure regulator and the flame guard are active.Once the upper switching threshold is exceeded, the heating operation is terminated and the purge cycle is initiated. The solenoid valves at the gas pressure regu-lator are closed, the flame extinguishes, but the combus-tion air fan and the circulating pump continue running.

Fig. 401 Operational sequence

* Coolant temperature below -20°C 40 seconds, otherwise 15 seconds, plus 0.3 seconds delayed switching of the combustion air motor and circulating pump** On/Off depending on T

Process

Signals

Main switch off on off

Coolant temperature T > T_min T < T_min T >= T_max T < T_min T >= T_max T < T_min

Fla

me

gen

era

tio

n

Fla

me

gen

era

tio

n

Fla

me

gen

era

tio

n

Actuators

Operating display

Combustion air motor

Circulating pump

Electronic ignition unit

Solenoid valve 1

Solenoid valve 2

ERH **

Time in s 3 37/12* 1 9 1 ... 5 115 3 37/12* 1 9 1 ... 5 115 12 37/12* 1 9 1 ... 5 115

State

Rea

dy to

sta

rt

Initi

al c

ycle

with

lig

ht c

heck

Pre

-ign

ition

Igni

tion

Sta

bili

zatio

n

Pur

ge c

ycle

1 w

ith s

afe

ty p

erio

d

Pur

ge c

ycle

2

Initi

al c

ycle

with

lig

ht c

heck

Pre

-ign

ition

Igni

tion

Sta

bili

zatio

n

Pur

ge c

ycle

1 w

ith s

afe

ty p

erio

d

Pur

ge c

ycle

2

Initi

al c

ycle

with

lig

ht c

heck

Pre

-ign

ition

Igni

tion

Sta

bili

zatio

n

Pur

ge c

ycle

1 w

ith s

afe

ty p

erio

d

Pur

ge c

ycle

2

Off Standby Start HeatingPurge cycle Standby Start Heating

Purge cycle Standby Start Heating

Purge cycle Off

402

Page 16: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 4 Heater functions

After a safety period of 5 seconds the purge cycle 2 starts. The flame monitoring is evaluated.The purge cycle ends approx. after 115 seconds. The combustion air fan is switched off. The heater is in a controlled break. The operation indication, the flame guard and the circula-ting pump continue their operation.

NOTE:If during the purge cycle 2 a “flame“ is recognized, the combustion air motor is switched off and an appropriate error message is given.The operation indication, the flame guard and the circula-ting pump continue to run until the purge cycle 2 is terminated (after 115 seconds).

Once the temperature falls short of the lower switching threshold, the heater restarts burner operation. It runs through the same sequence as the switching-on sequence.

4.2.2.1 Gradient evaluation

In case of low coolant flow or poor coolant circuit venting the temperature quickly increases in heating operation.The control unit recognises the quick temperature increase and automatically sets the upper switching thres-hold to a lower value. The quicker the temperature increases, the lower the swit-ching threshold for starting the controlled break is set.In addition, the burner is also switched back on again after the controlled break at a lower switching threshold.

This prevents residual heat triggering the overheating protection.

If the temperature rise (temperature gradient) is again within permissible limits, the thresholds are reset to normal values immediately (lower threshold 72°C, upper threshold 82°C).

4.2.3 Switching off

Switching the heater off ends the combustion process. The operation indication goes off and the purge cycle is initiated.The purge cycle cools down the components. This prevents that the residual heat in the heat exchanger, which is still present, overheats the components.The solenoid valves 1 and 2 at the gas pressure regulator are closed, the flame extinguishes, combustion air fan and the circulating pump continue running.After a safety period of 5 seconds the purge cycle 2 starts. The flame monitoring is evaluated.The purge cycle ends approx. after 115 seconds. The combustion air fan, the flame guard and the circulating pump are switched off.

403

Page 17: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 4 Heater functions

4.3 Malfunction interlock and heater interlock

Malfunction interlocks and heater interlocks are distin-guished.The interlocks protect the heater and the surrounding vehicle assemblies against sequence errors after failure or malfunction of individual heater components.In a heater interlock safety-related components are affected by the failure or malfunction. It may only be released by Valeo-trained personnel after eliminating the cause.

4.4 Malfunction interlock

If one of the malfunctions listed below occurs, the heater will initiate a fault shut-down, followed by malfunction interlock.In the process a purge cycle up to 115 seconds duration can be executed.An error code is outputted by means of flash impulses via the operating display.In case of several sequential malfunction interlocks a heater interlock is initiated (see 4.5).

4.4.1 Malfunctions during switching-on and start procedure

Malfunction causes:• Short circuit and/or interruption of electrical compo-

nents (temperature sensor, combustion air motor, circulating pump, solenoid valves 1 and 2, electronic ignition unit of the ZF module, electrical regulator heating)

• Flame detection during intial cycle• No start: No flame detection within 10 seconds after

opening of the solenoid valve 2• Heater operation outside the permissible operation

temperature range.• Voltage falling short of the low voltage threshold of

approx. 20.5 V within a duration of 20 seconds after a heating request.

• Voltage exceeding the high voltage threshold of approx. 30 V within a duration of 6 seconds after a heating request (purge cycle only and after that the heater goes into the standby mode, no malfunction interlock).

NOTE:As soon as the overvoltage is eliminated (6 seconds conti-nuously), the heater restarts operation automatically according to functional sequence.

4.4.2 Malfunctions during heater operation

Malfunction causes:• Short circuit and/or interruption of electrical compo-

nents (temperature sensor, combustion air motor, circulating pump, solenoid valves 1 and 2, electronic ignition unit of the ZF module, electrical regulator heating)

• Heater operation outside the permissible operation temperature range.

• Flame interruption (more than 5 consecutive combus-tion faults by a flameout)

NOTE:After a combustion fault by a flameout the heater is swit-ched into the state „flushing“.In this case, the gas supply is interrupted by the solenoid valve 2 at the gas pressure regulator, the combustion air motor continues to run.If a component test has shown no errors and no flame is detected by the flame guard, after 10 seconds the pre-ignition is performed for the resumption of the combustion operation as during the normal start.

• Voltage falling short of the low voltage threshold of approx. 20.5 V within a duration of 20 seconds

• Voltage exceeding the high voltage threshold of approx. 30 V within a duration of 6 seconds (it takes place a purge cycle only, and after that the heater goes into the standby mode, no malfunction interlock)

NOTE:As soon as the overvoltage is eliminated (6 seconds conti-nuously), the heater restarts operation automatically according to functional sequence.

4.4.3 Malfunctions during purge cycle

Malfunction causes:• Short circuit and/or interruption of electrical compo-

nents (temperature sensor, combustion air motor, circulating pump, solenoid valves 1 and 2, electronic ignition unit of the ZF module, electrical regulator heating)

• Heater operation outside the permissible operation temperature range.

• Voltage falling short of the low voltage threshold of approx. 20.5 V within a duration of 20 seconds

• Voltage exceeding the high voltage threshold of approx. 30 V within a duration of 6 seconds (it takes place a purge cycle only, and after that the heater goes into the standby mode, no malfunction interlock)

NOTE:As soon as the overvoltage is eliminated (6 seconds conti-nuously), the heater restarts operation automatically according to functional sequence.

404

Page 18: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 4 Heater functions

4.4.4 Malfunction interlock release and error clearance

The malfunction interlock is released when the heater is switched off.After that it will be immediately ready for operation.

Resetting a malfunction interlock leads to:• Clear the lock of the outputs with errors, that means

the outputs are activated again, an error can be detected again.

• The blink code output is reset, it will return to the output of the main switch state via the operation display.

• The fault counter status for the / fault is reset, that means, the fault counter can be increased for any errors again.

4.5 Heater interlock

The heater interlock overrides the standard malfunc-tion interlock.

If the heater interlock is active, neither start nor purge cycle are executed after the heater is switched on again.Prior to restarting the heater, cause investigation and trou-bleshooting must be performed by Valeo-trained personnel.After that the heater interlock can be released (see 4.5.1).

Heater interlock causes:• Short circuit and/or interruption of the temperature

sensor, overheat protection, solenoid valve 2• Flame guard defective • Overheat protection triggered• Flame detection after „flushing“• Flame detection during the purge cycle 2• Control device fault or programming error • Repeated malfunctions (8)• Repeated flame interruptions (5)

4.5.1 Heater interlock release

ATTENTION:Prior to releasing the heater interlock the cause of the fault must be eliminated!The heater interlock release is permitted by Valeo- trained personnel only.

To release the heater interlock, the heater must be disconnected from the vehicle electrical system when it is on.The heater interlock release is performed using the follo-wing sequence:

1. Correct the cause of the heater interlock.2. Switch interlocked heater on.3. Disconnect the switched on heater for > 10 seconds

from the vehicle electrical system.4. Reconnect the switched on heater to the vehicle

electrical system.

NOTE:The heater automatically starts after connecting it to the vehicle electrical system.The heater can be switched off during the initial cycle.

The heater interlock release additionally leads to:• Reset of the fault counter to 0• Reset of the flame interruption counter to 0• Reset of the start interruption counter to 0

The heater interlock is recorded by the control device.

4.6 Error output

If the heater is equipped with the standard timer, an error code is displayed on the digital timer after a malfunction occurs, otherwise via flash code given by the operating indicator light.

405

Page 19: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

5 Troubleshooting

5.1 General

This section describes the troubleshooting at the heater Thermo G 300.

ATTENTION:Troubleshooting may only be performed by briefed and competent trained personnel.

In case of doubt functional relations can be obtained in chapters 3 and 4.

Error recognition is usually limited to localizing the faulty component.The following malfunction causes are not taken into consi-deration and should basically always be verified and/or a malfunction due to these reasons should be excluded:

• Corrosion on plugs• Loose plug connections• Crimp failures on plugs and/or pins• Corrosion on cable and fuses• Corrosion on battery terminals• Cable insulation damage

ATTENTION:Prior to replacing a fuse troubleshooting needs to be performed. The heater must be disconnected from the vehicle electrical system and the fuse is to be replaced when the heater is in currentless state.A properly dimensioned fuse must be inserted (see chapter 6 Schematic diagrams).After each error correction a functional test must be performed in the vehicle.

5.2 General error symptoms

The following table lists the possible, general error symp-toms.

Table 503 General error symptoms

Error symptom Possible cause

Error in the electrics

Operating indication is not illuminated and the heater does not function.

• No voltage supply• Fuse(s) defective• Cable to the pins of plug C of the control device

Fuse F1 triggered Short circuit or overload of cables and/or heater components Check cables, connectors and components and replace as required.

Fuse F2 triggered. Short circuit or overload of cables or of the circulating pump Check cables, connectors and components and replace as required.

Fuse F3 triggered Short circuit in the supply cable to the main switch or, if installed, in the digital timer

Heater is functional, however the operating display is not illuminated

Operating indication defective or cables leading to the operating indication interrupted or shorted

501

Page 20: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

Fehler im Wassersystem

Circulating pump failure ( Aquavent 6000S and Aquavent 6000SC only).

• Error mode activated

In case of malfunctions the motor is switched off via the error mode

Reactivation of the circulating pump motorFor this purpose disconnect the power supply for > 2 min.After the power supply is reconnected the motor performs a soft start.

Heater stops as the connected heat exchanger provides insufficient heat.

Flow rate too small, because• Air in the heater, heat exchanger or in system

sections• Taps/valves (flow controllers) throttled,

contaminated, closed.• Contaminations in the system, e.g. filters or at bottle

necks• Circulating pump delivery rate insufficient(air in

pump housing)• insufficient frost protection (antifreeze)• System resistance too high (especially high in cold

weather)• Circulating pump defective

Heat exchanger provides not enough heat, because• Air in the heat exchangers and/or system sections• Contaminated heat exchangers• Insufficient air entry or air exit• Fan: Insufficient delivery rate / incorrect direction of

rotation / resistance too high• Antifreeze content too high

Approximate flow rate determination:

Heat flow [kW] according to type plateFlow rate in in [l/h] = x 860

Temperature difference ∆t in [K]measured on the heater between water inlet and water outlet(e.g. using contact thermometer)

Table 503 General error symptoms

Error symptom Possible cause

502

Page 21: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

5.3 Malfunction code output via flash code

The kind of malfunction is indicated from the operating indication light through a flash code, and if a standard timer is used, on the display (operating indication) respec-tively.The flash code is immediately generated after detection of the malfunction and will be kept while the heater is powered on until the heater is freed.The flash code comprises of a burst (sequence) of 5 short flashes depicting the break and a defined number of long pulses corresponding to the malfunction number, which are to be counted. After that the cycle starts with 5 short flashes again and so on.The meaning of the number of long pulses is shown in the table below.

Error in the fuel supply

No fuel supply to the heater • empty gas tank• bent, closed, clogged or leaky lines• frozen water inlets in the gas regulator or in the gas

line• closed gas supply valve• solenoid valve 1 or 2 don‘t open• defective gas pressure regulator

Faults in combustion

combustion irregularly • the speed of the combustion air fan is too low• defective combustion air fan• restricted combustion air supply• restricted gas supply• the methane content of the gas doesn’t match requi-

rements (min. 95% by volume)• contaminated combustion air intake grille

Table 503 General error symptoms

Error symptom Possible cause

Burst Break flashimpuls

nthflashimpuls

Break Burst

Flash code output

503

Page 22: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

Table 504 : Flash code

No. of impulses

Error Error description

0 Control device error (is not indicated at timer 1531) Control device error

1 No start within safety period No start within safety period (10 sec.)

2 Flame interruptionFlame interruption during burner operation, repeated starts unsuccessful

3 Low Voltage / high voltageHigh voltage (> 30V, at least 6 seconds)

Low voltage (< 20.5V, at least 20 seconds)

4 Extraneous light in initial or purge cycleExtraneous light in purge cycle 2

Extraneous light prior to ignition

5 not used

6Temperature sensor / overheat protection defective

Temperature sensor short circuit

Temperature sensor interruption

Temperature sensor / overheat protection non-plausible

Overheat protection short circuit

Overheat protection interruption

7 Solenoid valve 1 or 2 defective

Solenoid valve short circuit

Solenoid valve interruption

Solenoid valve doesn‘t close

8 Combustion air fan motor defective Combustion air fan motor short circuit

9 Circulating pump defective Circulating pump short circuit

10 Overheat protection triggered Overheating T>135°C

11 ZF module (ignition unit) defectiveElectronic ignition unit short circuit

Electronic ignition unit interruption

12 Heater interlock

Flame interruption counter threshold exceeded (5)

Heater interlock - release required

Malfunction counter threshold exceeded (8)

13 Electrical pressure regulator heating defective short circuit/interruption

504

Page 23: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

5.4 Error symptoms during functional tests with malfunction code output

5.4.1 Error symptom "No start within safety period"

If due to a malfunction the heater unsuccessfully has attempted to start eight times in a row, it will be interlo-cked.No further start attempts will be tried.The heater interlock overrides the standard malfunc-tion interlock.

The procedure for releasing the heater interlock can be found in point 4.5.1.

The "No start within safety period" error symptom does not always indicate that no ignition took place.This symptom occurs as well, if the heater fails to enter heating operation after a successful ignition, e.g. in case the fuel supply is interrupted.

5.4.2 Error symptom "Flame interruption"

If due to a malfunction flame interruption occurs during heating operation five times in a row, the heater will be in-terlocked.No further start attempts will be tried.The heater interlock overrides the standard malfunction interlock.

NOTE:After above mentioned error symptoms occur, trou-bleshooting according to page 506 is recommended.

The procedure for a heater interlock release is outlined in point 4.5.1.

505

Page 24: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

Are the combustion air intake opening and line and the exhaust line clean and securely mounted?

Clean and securely mount the combustion air intake opening and line and the exhaust line.

Is sufficient fresh air intake ensured and are no exhaust fumes drawn in?

Secure fresh air supply. Prevent exhaust intake.

Is the fan wheel properly secured?Are all screw connections tightened and ensured that no air escapes?

Secure the fan wheel properly. Make sure that all screw connections are tightened and that no air escapes (see also 8.5).

Is the distance of the ignition electrodes OK? Adjust ignition electrodes properly (see 5.5.9) respectively check the correct installation of the ZF module.

NO

JES

Switch heater on: Does the combustion air motor start?

Are all electrical connection plugged in and undamaged?

Check combustion air motor (see 5.5.7)

Connect electrical connections or replace

damaged parts.

Do the solenoid valves at the gas

pressure regulator open?

Are the solenoid valves at the gas

regulator controlled correctly?

Replace gas pressure regulator.

Remove the control device, check it

and replace if required (see 8.6).

Does the ZF module work?

(Ignition noise?)

Is the ZF module controlled

correctly?

Replace ZF module.

Remove the control device, check it

and replace if required (see 8.6).

Remove the control device, check it

and replace if required (see 8.6).

506

Page 25: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

5.4.3 Error symptom "Low voltage"

A value is stored in the control unit as smallest "permis-sible low voltage".It must be noted that the voltage may be lowered during heater start, and that the "low voltage" threshold may be violated.Among others this depends on the vehicle electrical system, the temperature of optional components, such as the circulating pumps or the electrical regulator heating.

NO

JES

Is the battery charge condition permanently

greater than 20.5V (measured at heater)?

Ensure permanent battery voltage greater

than 20.5V.

Disconnect the C plug from the control unit.

Is the voltage between pin 1 and pin 2 of plug

C at least 20.5V?

Is the electrical connection to the heater

OK? (fuse, wiring harnesses, plug connec-

tions, pins, etc.)

Repair or replace the

electrical connection to

the heater.

Start heater: Is the voltage permanently applied to the heater during heater start

or during heating operation 20.5V?

Ensure higher voltage during heater

start and/or heating operation.

Control unit defective, replace it.

507

Page 26: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

5.4.4 Error symptom "Extraneous light detected prior to ignition or during purge cycle"

NO

JES

Did overheating occur due to impaired

coolant flow?

Open valves, refill coolant, bleed coolant circuit. Verify

the circulating pump is correct controlled.

Is the burner properly screwed onto the

heat exchanger?Properly screw burner onto the heat ex-

changer.

Did the heater burn longer before?

Was the heater stopped or the voltage

disconnected before or during purge

cycle?

Is the combustion air intake clean/free?

Is the motor OK and can rotate freely?

Is the exhaust outlet clean/free?

Is the flame pipe OK (not coked,

contaminated or damaged)?

Is the heat exchanger clean (no resi-

dues, soot)?

Clean/clear combustion air intake.

Correct motor problem.

Clean/clear exhaust outlet.

Clean / replace flame pipe.

Clean heat exchanger.

Did the error return?

Let heater cool down for approx. 2

minutes and restart it again.

Did the error return?

Replace the gas pressure regulator if required.

Did the error return?

Control unit defective, replace it.

508

Page 27: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

5.4.5 Error symptoms "Temperature sensor / overheating protection defective"

5.4.6 Error symptom "Solenoid valve 1 or 2 defective"

The solenoid valves 1 and 2 are at the gas pressure regulator (see Chapter 3, Section 3.5).

Is the plug “T“ of the temperature

sensor system plugged in correct-

ly? Is the plug, the pins and the

cables of the temperature sensor

system OK? Is the temperature

sensor incl. overheating protection

installed correctly?

Replace control unit.

Correct error and/or replace the

component.

Replace temperature sensor system.

NO

JES

Remove and check the temperature

sensor system (see 5.5.5).

Without complaints?

509

Page 28: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

5.4.7 Error symptom "Overheat protection has triggered"

Is the plug “V“ of the gas regulator

harness plugged in correctly?

Is the plug, the pins and the cables

of the gas regulator harness OK?

Are the solenoid valves at the gas

regulator installed correctly?

Replace control unit.

Correct error and/or replace the

component.

NO

JES

Replace gas regulator.

NOTE:

Replacement of the solenoid valves

is not permitted.

Is it ensured that sufficient cooling

and coolant flow are available?

Are all shut-off valves open?

Is the cooling system proof, comple-

tely filled and bled?

Is a circulating pump connected and

the direction of rotation of the circula-

tion pump correctly?

Is the cold resistance of the coolant

given?

Remove the control unit, check it

and replace if required.

Correct error and/or replace the

component.

NO

JES

510

Page 29: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

5.5 Individual component tests

Individual components can basically be tested using visual inspection or manual electrical testing.

The general safety regulations according to Chapter 1must be observed.

ATTENTION:Prior to disconnecting the temperature sensor plug connection, disconnect the heater from the vehicle electrical system.

5.5.1 General visual inspection

1. Inspect components for damages (cracks, deforma-tion, leaks, discolourations, etc.) and replace as needed.

2. Inspect plugs and cables for corrosion, contact and crimp errors and repair as needed.

3. Check plug contacts for corrosion and tight fit. Repair as needed.

5.5.2 Heat exchanger visual inspection

1. Inspect heat exchanger interior for damage, corro-sion, sooting and deposits.

2. Inspect heat exchanger for outer damage, corrosion, moisture, deformations, deposits, discolourations, etc.

ATTENTION:Soot and deposits in the heat exchanger must be removed, as they impact the heat transfer to the coolant.Severe outer deformations may impact coolant flow.

5.5.3 Visual inspection of exhaust outlet and exhaust line

Inspect exhaust outlet and possibly available exhaust line for conditions, tight fit, contamination and deposits.

5.5.4 Combustion chamber visual inspection

1. Remove combustion chamber (see 8.10).

2. Check combustion chamber for scaling and coke deposits and remove them if necessary.

3. Inspect combustion chamber for deformation and moisture.

4. Inspect combustion chamber for cracks.

NOTE:Cracks in longitudinal direction at the end of the welding seam shorter than 80 mm are permissible.

5. After the inspection is completed, reinstall the com-bustion chamber (see 8.10).

5.5.5 Resistance check of the temperature sensor with integrated overheat protection

Prior to removing the temperature sensor, the over-pressure in the cooling system must be released (i.e.by opening the radiator cap). Observe the risk of inju-ries due to increased coolant temperature. Possiblylet heater additionally cool down and have collectingcontainer ready for discharged coolant.

Inspection

1. Inspect temperature sensor, plug and cable for damage and proper fit.

2. Remove temperature sensor (see 8.2).

3. Perform the electrical test using a measuring device suitable for resistance measurements.The electrical resistance between pin 1 and pin 3 (see Fig. 502) is at 0°C 500 Ohm, between pin 2 and pin 3 2000 Ohm. Both resistances change depending on temperature. The ratio should be at tempered through sensor 1:4.

4. Install temperature sensor (see 8.2).

Danger to life and health!Warning!

Fig. 501

Risk of scalds!Caution!

511

Page 30: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

5.5.6 Fan and combustion air intake line visual inspection

1. Inspect a possibly available combustion air intake line for contamination, condition and deposits.

2. Remove burner head (see 8.4).

3. Separate mixing chamber and fan housing (see 8.5).

4. Remove fan wheel (see 8.8).

5. Inspect fan wheel for damages, the channels of the fan wheel for contamination and deposits.

6. Install fan wheel (see 8.7).In the course of this check circlip for proper fit.

7. Check the combustion air fan for smoothness.

8. Install mixing chamber to the fan housing (see 8.5).

9. Install burner head (see 8.4).

5.5.7 Burner motor inspection

The motor can be checked by applying 24V DC voltage. During that the electrical connection to the control unit must be disconnected.

1. Remove burner head (see 8.4).

2. Separate mixing chamber and fan housing (see 8.5).

3. Inspect the motor for bearing conditions (stiffness).

4. Disconnect motor plug from the control unit.

5. Check motor with 24VDC (Pin 1 to 24V+).

6. Reconnect motor plug to the control unit.

7. Install mixing chamber to the fan housing (see 8.5).

8. Install burner head (see 8.4).

5.5.8 ZF module inspection

NOTE:It can only be verified by visual inspection of the igni-tion electrode, whether the ignition spark jumps over to the ignition electrode.

High voltage: The voltage received by the ignition electrode is >13,000 Volt.

During operation or testing of the electronic ignitionunit, the ignition electrode may not be contacted bypersons or items.

Check with STT diagnosis adapter1. Remove burner head (see 8.4).

2. Connect the test plug instead of the temperature sensor plug to the control unit.

3. Reconnect the heater to the vehicle electrical system.

4. Connect the SST diagnosis adapter to the heater and a PC via the interface on the control unit.

5. Start SST diagnosis, establish connection to the heater and open the Component Test menu.

6. Select the ZF module in the Component Test menu, enter a runtime and start the component test.

7. Nominal condition: Ignition sparks at the ignition electrode jump over with a rate of 6Hz.

8. After the test is completed, exit SST diagnosis as needed.

Fig. 502

Pin 1 & 3

Pin 2 & 3Overheat protection

Water temperaturesensor

Risc of electric shock!Warning!

512

Page 31: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

9. Disconnect the heater from the vehicle electrical system.

10. Disconnect the test plug.

11. Install burner head (see 8.4).

5.5.9 Ignition electrode inspection

NOTE:The ignition electrode insulation body may not be damaged.Ignition electrodes not functioning properly must be replaced.

1. Remove burner head (see 8.4)

2. Check distance of the electrode tips to the flame pipe (see Fig. 504).

3. Check the distance between the electrodes (see Fig. 505).

4. Inspect the ignition electrode insulation body for damage.

Functionality is verified while inspecting the ZF module.

Fig. 503 Burner head - ZF module

Ignition electrode

Flame pipe

Insulation bodyignition electrode

513

Page 32: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

5.5.10 Heat protection cover inspection

Check the heat protection cover visually. For that remove the burner head (see 8.4).

NOTE:Cracks and small outbreaks in heat protection cover are permitted and do not constitute a impairment.

The area of the heat protection cover in which outbreaks are permitted is gray marked in Fig. 506.

5.5.11 Gas pressure regulator inspection

ATTENTION:

The gas pressure regulator must not be disas-sembled.

NOTE:The check is performed when the gas pressure regulator is installed.

5.5.11.1 General tests

– Check the plug pins for corrosion and tight fit.– Was the gas pressure regulator replaced after 4 years

of operation?– When the heater is switched off, no gas may escape

through the outlet to the heater, even when solenoids are open.

– The supply line connection must be checked for im-permeability.

5.5.11.2 Examination of the solenoid valves at the gas pressure regulator

During heater operation disconnect plug connection to the gas pressure regulator.The combustion must stop immediately. If the combustion

Fig. 504 Distance of the ignition electrodes to the flame pipe

Fig. 505 Distance between ignition electrodes

Fig. 506 Outbreaks at the heat protection cover

Heat protectioncover

Area of the heat protection coverare permittedin which outbreaks

514

Page 33: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 5 Troubleshooting

does not stop immediately, the gas regulator must be replaced.

5.5.11.3 Test of the electrical functionality of the solenoid valves at the gas pressure regulator

ATENTION:

The replacement of one or both solenoid valves at thegas pressure regulator is not permitted.If one or both solenoid valves on the gas regulatordoes not function correctly, the gas regulator must bereplaced.

The electrical function of the solenoid valves can be tested manually.

Manual test:1. Disconnect the heater from the vehicle electrical

system.

2. Shut-off gas supply to the gas pressure regulator.

3. Disconnect plug „V“ from the control unit.

4. Check electrical function by applying 24VDC:– Opening voltage: as of 17,0 Volt– Power consumption at

24V and 20°C: 24 Watt

– Rated current at 24V: 1,0 Ampere

The solenoid valve must open audibly when applying the DC voltage.

5. Reconnect the plug „V“ to the control unit.

5.5.11.4 Testing the safety valve on the gas pressure regulator

If the intake valve is open (MV1) no gas must escape at the safety valve’s hose connection. If gas escapes, the gas pressure regulator must be replaced.

5.5.11.5 Checking for accumulations of oil and condensation in the gas pressure regulator

Possible accumulations of oil and condensate must be drained by unscrewing the drain plug on the gas pressure regulator. If larger amounts have accumulated, testing must be done to establish whether the quarterly draining interval was adhered to. If the result is positive, the interval must be shortened.

In the event that solid particulate matter is found in the oil/condensate, the gas pressure regulator must be replaced.After the test, the drain plug must be screwed in with a tightening torque of 8 ±1 Nm.

Fig. 507 Solenoid valves at the gas pressure regulator

High pressure

Low pressure solenoid valve(MV2)

solenoid valve (MV1)

Fig. 508 Oil drain screw at the gas pressure regulator

Oil drain screw

515

Page 34: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 6 Wiring diagrams

6 Wiring diagrams

6.1 General

The following figures represent heater connection options to the vehicle electrical system.

The in the table below shown cable cross-sections are to be used.

Cable length <7.5m Cable length 7.5 - 15m

0.75 mm² 1.5 mm²

2.5 mm² 4.0 mm²

601

Page 35: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 6 Wiring diagrams

Abb. 601 System wiring diagram for water heaters Thermo G with timer, for legend see page 603

Abb. 602 System wiring diagram for water heaters Thermo G with switch, for legend see page 603

ERH

MV2

MV1

UP

BMSG 1588

Thermo G

1 10 4 12 11 8

2

HS

ERH +

ERH -

MV2 +

MV2 -

MV1 +rt

sw

bl

br

MV1 -

UP +

BM+

BM-

ZF+

ZF-

ION-

ION+

UP -

+

S-Bus

PT500

PT2000

UPFA

BA+

1

8

7

6

4

5

1

1

2

2

1

1

2

2

3

3

4

4

2

1

3

1

2

3

4

5

6

2

F5

5A

F4

5A

F3

5A

F2

20A

F1

20A

UPFA

BA

HS

0.75mm2

0.75mm2

2.5mm2

2.5mm2

2.5mm2

2.5mm2

2.5mm2

2.5mm2

0.75mm2

0.7

5m

m2

0.7

5m

m2

0.7

5m

m2

0.7

5m

m2

C

BM

I

P

D

T

V

1

2

Terminal. 58

Terminal 15

Terminal 30 (permanent plus)

Terminal 31 (ground)

T. 31 HG

T. 30 HG

T. 31 UP

T. 30 UP

Ground

Electronic

Gas

free

OverheatingProtection

CoolantTemperature

Sensor

Diagnostic

RegulatorPressure

IgnitionModule

ERH

MV2

MV1

UP

BMSG 1588

Thermo G

2

HS

BM+

BM-

ZF+

ZF-

ION-

ION+

+

S-Bus

PT500

PT2000

UPFA

BA+

1

8

7

6

4

5

1

1

2

2

1

1

2

2

3

3

4

4

2

1

3

1

2

3

4

5

6

F3

5A

F2

20A

F1

20A

UPFA

HS

BA

0.75mm2

0.75mm2

2.5mm2

2.5mm2

2.5mm2

2.5mm2

2.5mm2

2.5mm2

0.75mm2

C

BM

I

P

D

T

V

ERH +

ERH -

MV2 +

MV2 -

MV1 +rt

sw

bl

br

MV1 -

UP +

UP -

Terminal 30 (permanent plus)

Terminal 31 (ground)

T. 31 HG

T. 30 HG

T. 31 UP

T. 30 UP

Ground

Electronic

Gas

free

OverheatingProtection

CoolantTemperature

Sensor

Diagnostic

PressureRegulator

IgnitionModule

602

Page 36: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 6 Wiring diagrams

Position Designation

BA Operation indicator max. 1x5W or 2x2W BM Combustion air motor (in the heater)ERH Electrical regulator heating (gas press. regulator)F1 Car flat-type fuse 20A acc. DIN 72581 part 3F2 Car flat-type fuse 20A acc. DIN 72581 part 3F3 Car flat-type fuse 5A acc. DIN 72581 part 3F4 Car flat-type fuse 5A acc. DIN 72581 part 3F5 Car flat-type fuse 5A acc. DIN 72581 part 3HS Main switchMV1 High-press. solen. valve, 1st stage (gas regulator)MV2 Low-press. solen. valve, 2nd stage (gas regula-

tor)UP Circulating pumpUPFA Circulating pump external controlZF-Modul Electronic ignition module (in the heater)

Legend for the wiring diagrams

Connector Description

C To vehicle (Power)C1 Terminal 30 (+)C2 Terminal 31 (–)C3 --C4 UPFAC5 Operation indicator +C6 Main switchC7 Terminal 30 UPC8 Terminal 31 UPP Circulating pumpP1 Circulating pump +P2 Circulating pump –

D DiagnosticD1 Diagnostic+D2 Diagnostic-D3 S-BusD4 --V Solenoid valves and electr.

gas regulator heatingV1 ERH+V2 ERH -V3 MV2+V4 MV2 -V5 MV1+V6 MV1 -

Connector pin assignment

Cable colors

blbrgegngrorrtswviws

bluebrownyellowgreengrayorangeredblackvioletwhite

2

4

8

753

1

6

1 2

1

2

3

4

5

6

3

1

42

603

Page 37: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 7 Servicing

7 Servicing

7.1 General

This section describes the work which is permitted to be performed on the heater when it is installed.

Work on the heater must only be carried out bytrained and / or by Valeo-trained personnel.

Any work on the gas supply line, for example whenremoving or installing the gas regulator, may only becarried out by persons with the appropriate officialauthorization.

The heater must be protected against being switched on unintentionally.

NOTE:When checking for leaks in the gas path it is recommen-ded to use a suitable for gas leak detection spray or a gas detector.Often into the gas an odorant (fragrance) is mixed, by which a leakage can also be perceived by a distinct odor.

7.2 Heater Servicing

Due to the risk of overheating, the battery main supply may not be disconnected, as long as the heater is opera-ting or in purge cycle.Make sure that the circulating pump is running while the heater is switched on for tests/inspections.

When comprehensive repair work is being carried out on the heater, it is advisable to remove it from the vehicle.

After work has been carried out at the heat circuit, a coo-lant mixture of water and antifreeze must be replenished in accordance with the vehicle manufacturer’s instructions and the heating circuit must be bleeded.

7.3 Vehicle Servicing

ATTENTION:

In the vicinity of the heater a temperature of 110 °Cmust under no circumstances be exceeded (e.g.during paint work on the vehicle).

7.4 Heater test run

The heater must not be operated, not even with thetimer, in enclosed areas like garages or workshopsnot equipped with exhaust ventilation facilities.

7.5 Servicing

In order to ensure long-term functional reliability, the follo-wing maintenance activities should be performed :

– The openings of the combustion air intake grid and the exhaust outlet must be checked for contamination and cleaned as needed.

– Outside the heating season the heater should be operated with the vehicle engine cold approximately every four weeks for 10 minutes setting the heating system to "warm". In this way, starting problems at the beginning of the heating season will be avoided.

– Every three months accumulated oil and condensate must be drained in accordance with 5.5.11.5 at the oil drain plug of the gas pressure regulator.

ATTENTION:

If solid particulate matter is found in the oil/condensate, the gas pressure regulator must bereplaced.

– The gas presure regulator must be replaced every 4 years for safety reasons (ageing of the seals).

– When renewing the coolant for the vehicle’s engine, care must be taken to bleed the heater, after the ve-hicle’s cooling system has been bled. Turn on the circulating pump (if there is a separate switch) or turn on the heater for approx. 5 seconds and operate the circulating pump in the purge cycle. This procedure may have to be repeated. Insufficient coolant must be replenished in accordance with the manufacturer’s instructions.

NOTE:The Aquavent 6000C circulating pump has a dry running protection which deactivates the motor in a dry run after approx.10 seconds. The Aquavent 4800SC and 6000SC are shutting down in a dry run only after 45 minutes.The system is reactivated by disconnecting it from the power supply for approx. 2 minutes.

– At the latest at the beginning of the heating season, the heater and the gas pressure regulator must be tested by a professional.

Danger to life and health!Warning!

Risk of Suffocation!Warning!

701

Page 38: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 7 Servicing

– Measuring and adjustment of the exhaust CO2 content as required (see 7.6).

7.6 Measurement and adjustment of the exhaust CO2 content

The exhaust CO2 content is to be measured and adjusted as required according to the level given in the technical data under the following circumstances:

– as part of a function check– in case of combustion irregularities– after repairs at the burner– after gas pressure regulator replacement– after an application customization– if the heater is operated with CNG (natural gas) which

methane content is less than 95 Vol%– after installation of a replacement burner– for long-term use at high altitudes

NOTE:The CO2 level of the Thermo G 300 replacement burner is adjusted by the manufacturer for use with CNG of class H.

7.6.1 Measurement of the exhaust CO2 content

The exhaust should not be measured directly at the exhaust outlet of the heat exchanger, as this may cause inaccuracies.Exhaust fumes should be sampled from the exhaust pipe in a distance of 350 mm after the heat exchanger. In the case no exhaust pipe is connected, for the measu-

rement a flexible pipe of 500 mm length (see accessory catalog) can be used.At this point also the measurement of the exhaust gas temperature should be performed.An increased exhaust gas temperature can e.g. indicate a sooted heat exchanger.

1. After a combustion period of approx. 3 min. measure the CO2 content in the exhaust and compare it to the target value in the Table 201 „Technical data heater“ in Chapter 2.

7.6.2 Adjustment of the exhaust CO2 content

The exhaust CO2 content adjustment is performed using an adjustment screw, accessible at the heater above the gas port (see Fig. 701).By the screw the gas flow rate at the gas inlet and thus the ratio of the gas-air mixture is changed at a given vacuum.

Adjust the exhaust CO2 content as follows:

1. Check input voltage at the heater.

2. Let the heater run approx. 3 minutes.

3. Measure the CO2 content in the exhaust and compare it to the target value in the Table 201 „Technical data heater“ in Chapter 2.

4. Insert a hex screw driver into the hole above the gas port (see Fig. 701) and turn the adjustment screw until the target value is reached.

Fig. 701 Adjustment of the exhaust CO2 content

CO2–

CO2+

702

Page 39: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 8 Repair

8 Removal and installation of components and of the heater

8.1 General

The general safety regulations according to Chapter 1must be observed.

Prior to removing components, disconnect the heaterfrom the vehicle electrical system.

ATTENTION:Sealing elements between disassembled compo-nents must always be replaced.This does not apply for the gasket ring of the temperature sensor because it is firmly attached.Screws with thread coating (screw locking) must be replaced.

NOTE:If components are disassembled to a degree not covered in this workshop manual, any warranty claim shall be voided.Only genuine Valeo spare parts should be used.

Basically, the access to the individual components of the heater is for the purposes of testing or replacement as follows:

After the removal of the hood, the control device and the fan motor (electric test) are accessible.

By removal of the burner head access to the following components is possible:

• combustion chamber• flame pipe• heat exchanger• ignition electrodes

The separation of the fan housing from the mixing chamber is necessary for the examination or replacement of the following components:

• fan motor• fan wheel• ZF-module

8.2 Removal and installation of the temperature sensor with integrated overheating protection

Prior to removing the temperature sensor, the over-pressure in the cooling system must be released (i.e.by opening the radiator cap). Observe the risk of inju-ries due to increased coolant temperature. Possiblylet heater additionally cool down and have collectingcontainer ready for discharged coolant.

Removal1. Disconnect the heater from the vehicle electrical

system and from the circulating pump as needed.2. Disconnect the temperature sensor plug (5, Fig. 802).

ATTENTION:The temperature sensor is positioned directly in the coolant circuit. To prevent coolant from escaping as far as possible, the coolant hoses are to be closed with pinch-off pliers (331457).

3. Unscrew and remove temperature sensor (1, Fig. 801). Collect the escaping coolant.

Installation1. Manually screw temperature sensor (1, Fig. 801) into

the coolant outlet (2).2. Tighten temperature sensor (1) with 8 Nm ± 0.5 Nm.3. Connect temperature sensor plug (5, Fig. 802).4. Connect the heater with the vehicle electrical system

and the circulating pump as needed.

Danger to life and health!Warning!

Risc of electric shock!Warnung!

Fig. 801 temperature sensor removal and installation

Risk of scalds!CAUTION!

1

2

1 Temperature sensor2 Coolant outlet

801

Page 40: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 8 Repair

8.3 Hood removal and installation

Removal1. Disconnect the heater from the vehicle electrical

system.2. Loosen screws (3, Fig. 802).3. Remove hood (4).

Installation1. Place hood (4, Fig. 802) into installation position.

Ensure center alignment and proper fit. 2. Insert screws (3) and tighten with 2 Nm + 0.5 Nm.3. Connect the heater to the vehicle electrical system.

8.4 Burner head Removal and installation

Burner head removal 1. Disconnect the heater from the vehicle electrical

system and from the circulating pump as needed.2. Disconnect the temperature sensor plug (5, Fig. 802).

3. If necessary, disconnect the combustion air intake line from the heater.

4. Disconnect gas supply hose and seal it with a blank plug.

5. Unscrew nuts (2).6. Remove burner head (1).

Burner head installation1. Bring burner head (1, Fig. 802) together with a new

gasket ring (6) into assembly position. Ensure center alignment and correct fit of the gasket.

2. Place nuts (2) and alternately tighten them slightly.3. Tighten nuts (2) with 7.5 + 1 Nm and apply screw

locking paint.4. Remove blank plug from gas supply hose and

reconnect gas supply hose to the heater.5. If necessary, reconnect the combustion air intake line

to the heater.6. Reconnect the temperature sensor plug (5).7. Connect the heater with the vehicle electrical system

and the circulating pump as needed.

Fig. 802 Burner head / hood removal and installation

1 Burner head2 Nuts (2)3 Screws (2)4 Hood5 Temperature sensor plug6 Gasket heat exchanger7 Heat exchanger with

combustion chamber

1

234

5

6

7

802

Page 41: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 8 Repair

8.5 Separating the fan housing from the mixing chamber

Separating1. Remove burner head (see 8.4).2. Remove hood (see 8.3).3. Disconnect ZF-module connector (8, Fig. 804) from

control device (5).4. Remove 4 screws securing the fan housing (2, Fig.

803) to the mixing chamber and remove fan housing (2) carefully together with the with the control device, the fan motor and the fan wheel. During this, the ZF module plug (8, Fig. 804) must be stuck through the hole in the housing.

Assembling1. Remove any residuals of the mixing chamber seal (5,

Fig. 803) from fan housing and/or from the mixing

chamber.2. Bring the the fan housing (2) in assembly position with

the mixing chamber (6). During this, ensure the new mixing chamber gasket ring (5) and the ZF module grommet are in the correct position.

ATTENTION:Before screwing on the fan housing, ensure that the wires of the ZF module and the rubber grommet have the proper position.

3. Attach fan housing (2) to the mixing chamber (6) using 4 screws.

4. Plug the ZF module plug into the control device.5. Install hood (see 8.3).6. Install burner head (siee 8.4).

Fig. 803 Separating the fan housing from the mixing chamber

1

2

3

4

5

1 Hood2 Fan housing with combustion air motor3 Fan wheel4 Circlip5 Gasket ring

6

803

Page 42: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 8 Repair

8.6 Control device removal and Installation

Removal1. Disconnect the heater from the vehicle electrical

system. Disconnect the plug “C“.2. Disconnect the circulating pump plug “P“.3. Disconnect the gas pressure regulator plug “V“.4. Disconnect the temperature sensor plug “T“ (5, Fig.

802). 5. Remove hood (see 8.3).6. Disconnect the plug of the ZF module (8, Fig. 804) and

the fan motor (2) plug from the control device (5).7. Remove the control device attaching screw (5).8. Remove the control device (5).

Installation1. Position control device (5, Fig. 804) to fan housing (3).2. Screw in the attaching screw of the control device and

tighten it (2 +0.5 Nm).3. Plug the ZF module plug (8) and the fan motor plug (2)

into the control device (5).4. Install hood (see 8.3).5. Plug in the temperature sensor plug „T“ (5, Fig. 802).6. Plug in the gas pressure regulator plug „V“.7. Plug in the circulating pump plug „P“.8. Plug in „C“ plug.

8.7 Fan wheel removal and installation

Removal1. Separate the fan housing from the mixing chamber

(see 8.5).

ATTENTION:Do not overstretch the circlip.

2. Remove the fan wheel (4, Fig. 804). For that first remove the shaft circlip (7) using suitable pliers. Then remove the fan wheel.

Installation1. Remove any residuals of the mixing chamber seal (9,

Fig. 804) from fan housing and/or from the mixing chamber.

2. Slide fan wheel (4) onto the motor shaft. Install shaft circlip (7) with suitable pliers.

ATTENTION:Do not use an overstretched shaft circlip! Ensure secure engagement of the circlip in the groove!

Verify the fan wheel is freely rotatable.3. Attach fan housing to the mixing chamber (see 8.5).

8.8 Fan motor removal and installation

Removal1. Separate the fan housing from mixing chamber (see

8.5).

ATTENTION:Do not overstretch the circlip.

2. Remove the fan wheel (4, Fig. 804). For that first remove the shaft circlip (7) using suitable pliers. Then remove the fan wheel.

3. Remove 3 countersunk screws securing the fan motor (2) to the fan housing (3) and remove the fan motor from fan housing (2).

Installation1. Position fan motor (2, Fig. 804) onto the fan housing

(3) and secure the fan motor (2) using 3 countersunk screws M5x35 (5 +1 Nm).

2. Slide fan wheel (4) onto the motor shaft. Install shaft circlip (7) with suitable pliers.

ATTENTION:Do not use an overstretched shaft circlip! Ensure secure engagement of the circlip in the groove!

Verify the fan wheel is freely rotatable.3. Attach fan housing to the mixing chamber (see 8.5).

8.9 ZF module removal and installation

Removal1. Separate the fan housing from the mixing chamber

(see 8.5).2. Remove screw and serrated lock washer, securing

the ground cable of the ZF module (8, Fig. 804) to the mixing chamber.

3. Remove screws, securing the ZF module to the mixing chamber and remove the ZF module along with the gasket and the ignition electrodes from the mixing chamber.

Installation1. Position ZF module (8, Fig. 804) along with the

ignition electrodes and gasket into the mixing chamber.

2. Secure ZF module to the mixing chamber using 2 screws.

3. Attach ground cable of the ZF module to the mixing chamber with a screw and a serrated lock washer.

4. Attach fan housing to the mixing chamber (see 8.5).

804

Page 43: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 8 Repair

Fig. 804 Removal and Installation of components

1

2

3

4

5

6

7

8

9

10

11

12

13

1 - Hood2 - Fan motor3 - Fan housing4 - Fan wheel5 - Control device6 - Gas port7 - circlip

8 - ZF module9 - Gasket ring, Mixing chamber10 - Mixing chamber11 - Heat protection cover12 - Gasket, flame pipe13 - Flame pipe

805

Page 44: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 8 Repair

8.10 Combustion chamber removal and installation

Removal

Combustion chamber and heat exchanger can bevery hot. If necessary, let them cool down.

1. Remove burner head (see 8.4).2. Pull combustion chamber (1, Fig. 805) out of the heat

exchanger (2).

Installation1. Slide combustion chamber (1, Fig. 805) until stop into

the heat exchanger (2).

HINWEIS:– The combustion chamber should be inserted into

the heat exchanger in such a way that its welding seam is positioned between 2 and 10 o clock (not upwards!). A position change during mainte-nance is permissible and affects the expected service life of the combustion chamber positively.

2. Install burner head (see 8.4).

8.11 Heat exchanger removal and installation

Combustion chamber and heat exchanger can bevery hot. If necessary, let them cool down.

Removal1. Remove burner head (see 8.4).2. If necessary, remove temperature sensor (see 8.2).3. Pull combustion chamber (1, Fig. 805) out of the heat

exchanger (2) (see 8.10).4. If necessary, loosen the exhaust line clamp on the

exhaust outlet (3).5. If available, close water taps.

Prior to disconnecting the coolant houses, the over-pressure in the cooling system must be released (i.e.by opening the radiator cap). Observe the risk of inju-ries due to increased coolant temperature. Possiblylet heater additionally cool down and have collectingcontainer ready for discharged coolant.

6. Loosen hose clamps on the coolant hoses, pull coolant hoses from the coolant inlet (5) and the coolant outlet (6) and seal with blank plugs.

7. Remove screws and washers at the heat exchanger stand (4).

8. Remove heat exchanger from the vehicle.

Installation1. Bring the heat exchanger (2, Fig. 805) into installation

Fig. 805 Combustion chamber removal and installation

Risk of burns!Caution!

2

1

1 Combustion chamber2 Heat exchanger3 Exhaust outlet4 Stand5 Coolant inlet6 Coolant outlet

5 6

4

4

3

Fig. 806 Combustion chamber welding seam position

permissible

not permissible

Risk of burns!Caution!

Risk of scalds!Caution!

806

Page 45: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 8 Repair

position and mount the stand (4) to the vehicle using screws, nuts and washers according to the mounting points used.

2. If necessary, secure the exhaust line using a clamp to the exhaust outlet (3).

3. Fit coolant the hoses onto the coolant inlet (5) and the coolant outlet (6) and secure them with hose clamps applying a tightening torque of 6 ± 0.6 Nm.

4. If available, open the water taps.5. Install the burner head (see 8.4).6. Bleed the coolant circuit (see 8.14.1).

8.12 Heater removal and installation

NOTE:The fuel supply system must be subsequently bleeded (see 8.14.1).

Removal1. Remove burner head (see 8.4).2. Remove heat exchanger (see 8.11).

Installation1. Install heat exchanger (see 8.11) 2. Install burner head (siehe 8.4)3. Bleed coolant circuit (see 8.14.1).

8.13 Gas pressure regulator removal and installation

Work on the gas supply pipe and the gas pressureregulator may only be performed by personnel withan official authorization.

ATTENTION:

Before removing the gas pressure regulator, makesure that the gas supply from the gas reservoir to thegas pressure regulator is shut-off.

Removal1. Unplug electrical connectors at the gas pressure

regulator.2. Close coolant hoses using pinch-off pliers.

NOTE:Optionally mark coolant hoses for proper installation.

3. Loosen the hose clamps securing the coolant hoses and remove the hoses.

4. Remove the gas intake line.5. Loosen the hose clamps securing the gas outlet line

and remove the line.6. Remove the hose from the safety valve.7. Loosen the nut at the threaded attachment pin and

remove the gas pressure regulator together with the washer and spring washer.

Installation1. Place gas pressure regulator together with the washer

and spring washer into installation position and attach it using the nut (tightening torque 20 ±2Nm).

2. Reconnect the hose to the safety valve.3. Reconnect the gas outlet line and secure it using a

hose clamp (tightening torque 5 +0.5Nm). 4. Mount gas intake line (tightening torque 25 Nm). 5. Reconnect coolant hoses and secure them using

hose clamps (tightening torque 1.2 Nm).6. Remove the pinch-off pliers from the coolant hoses. 7. Restore electrical plug connections.

ATTENTION:

After installation of the gas pressure regulator andbefore starting the heater the gas intake line connec-tion should be checked for tightness by authorizedpersonnel.

8.14 Start-up after installation of burner head, heater or heat exchanger

During the test run the coolant and fuel connections must be checked for leak-tightness and tight fit.If the heater goes while operating in an error mode, perform a troubleshooting (see Chapter 5).

8.14.1 Bleeding of the coolant circuit

NOTE:The coolant circuit must be principally bleeded according to manufacturer‘s specification.

Risk of scalds at coolant with increased temperature.

The Aquavent 5000 (U4814) and Aquavent 6000S (U4855) circulating pumps may only be switched on for bleeding, after dry operation can be excluded.

The Aquavent 5000S (U4854) and Aquavent 6000SC (U4856) circulating pumps may even in dry operation be switched on for bleeding.Adjust the vehicle heating system to "warm" and refill coolant.As soon as it is confirmed that the vehicle engine is filled with coolant, run vehicle engine with increased idle speed.Once the cooler thermostat opens, switch the vehicle

Danger to life and health!Warning!

Risk of scalds!Caution!

807

Page 46: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G 8 Repair

engine off and check the coolant level.Refill coolant as needed.

While the vehicle engine is switched off, switch on the heater with the circulating pump and the vehicle heating fan.After the engine motor cooled down, the heater must automatically start and stop as soon as the upper swit-ching threshold is reached.

If the heater does not start automatically, it must be verified, whether the heater overheating protection is triggered and the heater is interlocked.

Release the heater (see 4.5) and repeat the bleeding process.

808

Page 47: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

901

Thermo G 9 Modifications and retrofits

9 Modifications and retrofits

For further optimization the heaters are continuously improved. Units in the field can usually be upgraded or retrofitted. For this purpose respective modification kits will be available. For Information, refer to the category ’’Service“ of the Valeo homepage.

Page 48: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

1001

Thermo G 10 Packing / storage / shipping

10 Packing / storage and shipping

10.1 General

The heater or its components, which are sent to Valeo for inspection or repair, must be cleaned and packaged to ensure that handling, transport and storage will not damage them.

ATTENTION:If a complete heater is sent back, it must be completely drained. Packaging and/or shipping must ensure that no coolant can leak.

Coolant inlet and outlet fittings must be plugged and sealed using blank plugs.

The temperatures described in Chapter 2 may not be exceeded during storage.

Page 49: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G Maintenance plan

Scheduled heater maintenance

The heater should be inspected in scheduled time inter-vals, latest at the beginning of the heating period (time of increased heater usage due to present weather condi-tions).In principle the regulations of the vehicle manufacturers

must be adhered. If there no such regulations, Valeo prescribes the here shown maintenance intervals for common applications.If heaters should be used in other vehicles and/or applica-tions, the maintenance intervals may be shortened or extended. In such cases please contact your dedicated Valeo partner for further information.

Check / Maintenance Important notes Check result Measured values,

accomplished repairsOK. not OK

1. Electrical connections

a) Examine electrical plug connections and the wiring harness for visible damages, replace as required.

2. Heat exchanger

a) Check for external damage, discoloration caused by over-heating and leaks.

b) Clean the heat exchanger inside, remove soot and debris.

Determine overheating cause as needed (e.g. water circulation sys-tem); check overheat protection.

3. Fuel system

a) Inspect fuel lines and connections for leakage.

b) Gas pressure regulator:

- quaterly drain oil at the oil drain plug

c) Check solenoid valves for correct function. For that, during heater operation, disconnect plug connection to the gas pres-sure regulator. The combustion must stop immediately.

Ensure tight connection of the gas lines!Tighten fittings and hose clamps.

After 4 years operation, the gas pressure regu-lator must be replaced.

Address of the operator Date of the maintenance

Vehicle data

Heater data

Type of heater: Operating/ control device data

Fuel natural gas (CNG) Class H

Date of commission

Class L

Ident. no.:

Serial no.:

acc. diagnosis (SST)

1

Page 50: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Thermo G Maintenance plan

Check / Maintenance Important notes Check result Measured values,

accomplished repairsOK. not OK

4. Burner Head

a) Inspect combustion air intake opening for clear passage.

b) Inspect hood for damage.

c) Inspect ignition electrodes for damage and correct distance and readjust if required.

Replace damged parts.

5. Exhaust system

a) Inspect exhaust line for clear passage, clean or replace it as needed.

b) Remove combustion chamber from heat exchanger, inspect both parts for damage and contamination, clean and replace as needed.

c) Insert combustion chamber and mount burner head. Ensure proper fit and tight connection to the heat exchanger.

d) Combined nuts (M8) for burner head attachment, tightening torque 7.5 +1 Nm, secure them.

e) Measurements

Target values and procedures are outlined in the workshop manual

Ambient temperature (° C)

Exhaust temperature (° C)

CO2 (Vol.%)

Secure them with locking compound

Limits acc. to Regu-lation ECE-R 122

see technical data heater

8,0 ... 9,0 Vol.% at 24V

6. Water system

a) If available, inspect, clean as needed or replace filter insert.

7. Functional check

a) Check fault memory, clear it as needed using the diagnosis tool (STT).

b) Check heater functionality.

Attention:

During the maintenance, check all screw connections for tight-ness (for corresponding torque values see Workshop Manual).

after at least 10 min. heater operation

2

Page 51: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

memos

Page 52: Thermo G 300 · 1.5 Suggestions for Improvement and change 102 2 Technical data 201 2.1 Heater 201 2.1.1 Altitude capability 201 2.2 Gas pressure regulator 202 2.3 Fuel 202 2.4 Circulating

Valeo Thermal Commercial Vehicles Germany GmbH

Friedrichshafener Str. 7 - Tel. +49 (0)8105 7721-0 - Fax +49 (0)8105 7721-88982205 Gilching - Germany -

www.valeo-thermalbus.com - [email protected]

© V

ale

o T

herm

al

Com

merc

ial Veh

icle

s G

erm

any

Gm

bH

2019