three phase to five phase

Upload: thriveni-maddineni

Post on 03-Apr-2018

229 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 three phase to five phase

    1/89

    SINGLE-PHASE TO THREE-PHASE DRIVE SYSTEM

    USING TWO PAPALLEL SINGLE PHASE RECTIFIERS

    A Main Project Report submitted in partial fulfilment of the

    Requirements for the award of the degree of

    BACHELORE OF TECHNOLOGY

    IN

    ELECTRICAL & ELECTRONICS ENGINEERING

    By

    M.THRIVENI (09HT1A0225)

    B.RAJU (09HT1A0205)

    P.KARUNAKAR (09HT1A0235)

    B.NAGESWARA RAO (09HT1A0206)

    K.NAVEEN (09HT1A0221)

    Under the guidance of

    Mr.P.PURNA CHANDA RAO M.TechAssistant Professor

    Department of Electrical & Electronics Engineering

    Chalapathi Institute Of Technology(Approved by AICTE, Affiliated to JNTU Kakinada)

    (2009-2013)

  • 7/29/2019 three phase to five phase

    2/89

  • 7/29/2019 three phase to five phase

    3/89

    Acknowledgment

    We would like to express our heartfelt gratitude to my guide Mr. P.PURNA CHANDRA RAO,

    Assistant Professor, Department of Electrical and Electronics Engineering, Chalapathi

    Institute of Technology. He has given us tremendous support in both technical and moral front.

    Without his support and encouragement, we would never have been able to complete the project

    Successfully.

    We are grateful to Mr. N.RAJESH BABU, Head of the Department of Electrical

    And Electronics Engineering, Chalapathi institute of Technology, for presenting us this

    Opportunity and for extending constant support and valuable guidance throughout the project.

    Our profound thanks to Dr.C.Ravi Kanth, principal, chalapathi institute of

    Technology, for his support.

    We would also like to thank all our teaching staff members of EEE for giving us

    Their valuable suggestions. Finally, we are thankful to one and all who contributed for the

    Successful completion of our project work by

    M.THRIVENI (09HT1A0225)

    B.RAJU (09HT1A0205)

    P.KARUNAKAR (09HT1A0235)

    B.NAGESWARA RAO (09HT1A0206)

    K.NAVEEN (09HTIA0221)

  • 7/29/2019 three phase to five phase

    4/89

    DECLARATION

    We hereby declare that the project entitled SINGLE PHASE TO THREE PHASE DRIVE

    SYSTEM USING TWO PARALLEL SINGLE PHASE RECTIFIERS, submitted in the partial

    Fulfillment of the requirements for the award of Bachelor of Technology in Electrical & Electronics

    Engineering, to Chalapathi Institute of Technology, Mothadaka, Guntur, affiliated to JNTU,

    Kakinada is a authentic work and has not been submitted to any other university or institution for

    Award of the degree by

    M.THRIVENI (09HT1A0225)

    B.RAJU (09HT1A0205)

    P.KARUNAKAR (09HTA10235)

    B.NAGESWARA RAO (09HT1A0206)

    K.NAVEEN (09HT1A0221) .

  • 7/29/2019 three phase to five phase

    5/89

  • 7/29/2019 three phase to five phase

    6/89

    ABSTRACT

    Single-phase to three-phase acdcac conversion usually employs a full-bridge

    topology. In these three phases induction motor is operated from single-phase supply

    by using two parallel single-phase rectifiers the topology permits to reduce the rectifier

    switch currents, the harmonic distortion at the input converter side, and presents

    improvements on the fault tolerance characteristics and it is shown by reduction of

    circulating current. . The system is composed of two parallel single-phase rectifiers, a

    three-phase inverter, and an induction motor. The power continuity is a major issue

    solved in this project and is achieved by using parallel converters. The fault in the

    rectifier does not affect the power flow and if a fault in any rectifier is occurred the

    entire power is fed through the other rectifier. The topology was simulated in

    Matlab/simulink software and performance of induction motor by this topology was

    studied.

    1

  • 7/29/2019 three phase to five phase

    7/89

  • 7/29/2019 three phase to five phase

    8/89

    CONTENTS

    ABSTRACT i

    List of Figures iv

    List of Tables vi

    ABSTRACT 1

    LIST OF FIGURES 5

    LIST OF TABLES 8

    Chapter 1: INTRODUCTION 1

    1.1 Introduction: 1

    1.2 Motivation of Work: 2

    1.3 Problem Definition: 2

    1.4 Scope of the project: 2

    1.5 Solution Technique: 2

    1.6 Literature Overview: 3

    Chapter 2:SINGLE PHASE A.C TO THREE PHASE A.C CONVERSION METHODS 8

    2.1 Methods to Convert Single Phase to Three Phase Drive Systems 8

    2.1.1 Rotary phase converter: 8

    2.1.2 Static Phase Converter 9

    2.1.3 Phase Perfect Digital Phase Converter: 9

    2.2 Single-Phase to Three-Phase (1-3) Cycloconverters: 10

    2.2.1 Integral Pulse Modulated (1-3) Cycloconverters: 11

    2.2.2 Phase-Controlled (1-3) Cycloconverter: 11

    2.3 Single-Phase-to-Three-Phase AC/DC/AC PWM Converter: 11

    Chapter 3: CHARACTERISTICS OF INDUCTION MOTOR 13

    3.1 Starting characteristics: 13

    3.2 Running Characteristics: 14

    3.3 Load characteristics: 15

    3.3.1 Constant Torque, Variable Speed Loads: 15

    3.3.2 Variable Torque, Variable Speed Loads: 16

    3.3.3 Constant Power Loads: 16

    3.3.4 Constant Power, Constant Torque Loads: 16

    3.3.5 High Starting/Breakaway Torque followed by Constant Torque 17

    3.4. Induction motor characteristics in the proposed system: 17

    Chapter 4: CONTROL STRATEGIES OF CONVERTERS 19

    4.1 Introduction: 19

    4.2 Sinusoidal Pulse Width Modulation: 21

  • 7/29/2019 three phase to five phase

    9/89

    4.2.1 SPWM Spectra: 24

    4.3 Space Vector PWM: 25

    4.3.1 Principle of Space Vector PWM: 25

    4.4. Vector Control technique: 33

    4.5 control circuits adopted in the system: 34

    4.5.1. Rectifier control circuit: 35

    4.5.2. Inverter control circuit: 35

    4.5.3. pi controller: 36

    Chapter 5: DESIGN METHODOLOGY OF PROPOSED CONVERTER 37

    5.1 Introduction: 37

    5.2 Mathematical Modelling of the proposed system: 39

    5.2.1.Different modes/loops in the proposed system: 39

    5.3 PWM Strategy: 43

    5.4 Control Strategy: 45

    5.5 Harmonic Distortion: 46

    5.6 Ratings of Switches: 49

    5.7 DC-Link Capacitor Design: 50

    5.8 Input Inductors: 51

    5.9 Fault Compensation: 52

    5.10 Losses and Efficiency: 54

    5.11 Costs and Applications of Configuration: 56

    5.12 pulse train of control circuits of rectifier and inverter switches: 56

    Chapter 6: SIMULATION AND RESULT DISCUSSION 58

    6.1 Simulation Results for 110V AC: 58

    6.1.1 Simulation of Conventional Model: 58

    6.1.2 Simulation of Proposed Model: 61

    6.2 Simulation Results for 230V AC: 68

    6.2.1 Simulation of Conventional Model: 68

    6.2.2 Simulation of proposed Model: 70

    Chapter 7: CONCLUSION AND FUTURE SCOPE 75

    Conclusion: 75

    Future Scope: 75

    Chapter 8: BIBLIOGRAPHY 76

  • 7/29/2019 three phase to five phase

    10/89

    LIST OF FIGURES

    Figure no. Description Page no.

    Fig. 2.1: Block diagram for rotary phase converter 9

    Fig 2.2: Block diagram of Phase Perfect Digital Phase Converter 10

    Fig. 2.3(a): Single-phase-to-three-phase ac/dc/ac PWM converter 12

    Fig.2.3(b): wave form of grid voltage & current 12

    Fig. 3.1:Typical torque-speed curve of the three-phase induction

    motor14

    Fig. 3.2: Torque-speed curves of the motor with two different loads 15

    Fig .3.3: Constant Torque, Variable Speed Loads 15

    Fig. 3.4: Variable Torque, Variable Speed Loads 16

    Fig. 3.5: Constant Power Loads 16

    Fig. 3.6: Constant Power, Constant Torque Loads 17

    Fig. 3.7:Relation between the Voltage and Torque versus

    Frequency17

    Fig. 3.8wave forms of three phase voltage, current, speed and

    torque18

    Fig. 4.1 Unipolar and bipolar modulation 22

    Fig. 4.2: Simple Voltage Sourced Inverter 23

    Fig. 4.3: Principal of Pulse Width Modulation 24

    Fig. 4.4: SPWM Harmonic Spectra 25

    Fig. 4.5: Three-phase voltage source PWM Inverter 25

    Fig. 4.6: The eight inverter voltage vectors (V0 to V7) 27

    Fig. 4.7:Locus comparison of maximum linear control voltage in

    Sine PWM and SVPWM27

    Fig. 4.8:The relationship of abc reference frame and stationary dq

    reference frame28

    Fig. 4.9: Basic switching vectors and sectors 29

  • 7/29/2019 three phase to five phase

    11/89

    Fig.4.10:Reference vector as a combination of adjacent vectors at

    sector 131

    Fig. 4.11: Space vector PWM switching patterns at each sector 32

    Fig. 4.12:

    Block diagram for vector control technique using direct

    torque and speed control 34

    Fig. 4.13: Control circuit for rectifier 35

    Fig. 4.14: Control circuit for inverter 36

    Fig 4.15: Block diagram of pi controller 36

    Fig. 5.1 Conventional single-phase to three phase drive system 37

    Fig. 5.2(a) Proposed single-phase to three phase drive system 38

    Fig. 5.2(b)

    Block diagram of proposed single-phase to three phase

    drive system model 38

    Fig: 5.2.1a: Loop1 of the system model 39

    Fig: 5.2.1(b): Loop2 of the system model 40

    Fig: 5.2.1(c): Loop3 of the system model 40

    Fig: 5.2.1(d): Loop4 of the system model 41

    Fig. 5.3 Control Block Diagram for rectifier 45

    Fig. 5.4 WTHD of rectifier voltage (vab for proposed configuration

    and vg for Standard configuration) as a function of 47

    Fig. 5.5 Variables of rectifiers A and B. 48

    Fig. 5.6 Currents ia , ia , and io fordouble-carrier 49

    Fig. 5.7(a)Flow of active power in Conventional acdcac single-

    phase to three phase converter50

    Fig. 5.7(b)Flow of active power in Proposed system with two

    rectifiers

    50

    Fig. 5.8: Inductor specification in terms of THD of ig and 52

    Fig. 5.9(a):Proposed configuration highlighting devices of fault-

    tolerant system.53

    Fig.5.9 (b): Block diagram of the fault diagnosis system 53

    Fig.5.10: Possibilities of configurations in terms of fault occurrence 54

    Fig5.11(a): pulse trainee of rectifier control circuit 56

    Fig.5.11(b): pulse trainee of inverter control circuit 57

    Fig. 6.1: Simulink model of conventional system 58

  • 7/29/2019 three phase to five phase

    12/89

    Fig. 6.2: Wave forms of grid input voltage & current 58

    Fig. 6.3: Wave form of DC-Link capacitor voltage 59

    Fig. 6.4: Wave form of current ia in rectifier A 59

    Fig. 6.5: Wave form of output line voltage 60Fig. 6.6: THD content at input current is 19.36% 60

    Fig. 6.7: Simulink model of proposed system 61

    Fig. 6.8: Simulink model of control circuit for rectifier 61

    Fig. 6.9: Simulink model of control circuit for inverter 62

    Fig. 6.10: Wave forms of grid input voltage & current 62

    Fig. 6.11 : Wave form of DC-Link capacitor voltage 63

    Fig. 6.12: Wave form of circulating current 63

    Fig. 6.13: Wave forms of currents in rectifier A & B 64

    Fig. 6.14: Wave forms of grid voltage & current in fault condition 64

    Fig. 6.15: Wave forms currents in rectifier A & B in fault condition 65

    Fig. 6.16: Wave forms currents in rectifier A in fault condition 65

    Fig. 6.17: THD content at input current using SPWM Technique 66

    Fig. 6.18 : THD content at input current using SVPWM Technique 66

    Fig. 6.19: THD content at output voltage using SPWM Technique 67

    Fig. 6.20 : THD content at output voltage using SVPWM Technique 67Fig.6.21: Wave forms of grid input voltage & current 68

    Fig. 6.22: Wave form of current in rectifier A 69

    Fig. 6.23: Wave form of DC-Link capacitor voltage 69

    Fig. 6.24: Wave forms of currents in rectifier A & B 70

    Fig. 6.25: Wave form of output line voltage 70

    Fig. 6.26: Wave form of circulating current 71

    Fig. 6.27: Wave form of DC-Link capacitor voltage 71

    Fig. 6.28 : THD content at input current using SVPWM Technique 72

    Fig. 6.29: THD content at input current using SPWM technique 72

    Fig. 6.30 : THD content at output voltage with SPWM technique 73

    Fig. 6.31 : THD content at output voltage with SVPWM technique 73

  • 7/29/2019 three phase to five phase

    13/89

    LIST OF TABLES

    Description Pg. No.

    Table 1: ratings of induction motor 19

    Table 2: Switching vectors, phase voltages and output line to line voltages 26

    Table 3: Efficiency of the Proposed System Normalized In Terms Conventional 55

    Table 4: Comparison of conventional and proposed systems for 110V supply 68

    Table 5: Comparison of conventional and proposed systems for 230V 74

    Table 6: Distribution of currents for different values of modulation index 74

  • 7/29/2019 three phase to five phase

    14/89

    Introduction

    1

    Chapter 1

    INTRODUCTION

    1.1 Introduction:

    Many solutions have been proposed when the objective is to supply three-

    phase motors from single-phase ac mains. It is quite common to have only a single

    phase power grid in residential, commercial, manufacturing and mainly in rural areas,

    while the induction motor may require a three-phase power grid. The motor and power

    factor control and reduction of total harmonic distortion have been presented by using a

    single phase to three-phase converter topology, this is a two step conversion which

    involves single phase a.c to d.c by using a rectifier and then d.c to a.c by using three

    phase inverter reduced number of switching devices. The most desirable characteristics

    of ac to ac power converters are:

    Sinusoidal input and output currents Operation with nearly unity power factor for any load Simple and compact power circuit Generation of load voltage with arbitrary amplitude and frequency

    A front end-rectifier followed by a pulse width modulated voltage source

    inverter (VSI-PWM) has been well-established power converter configuration for many

    industrial drives. The increasing costs on the utility usage, due to power quality

    regulations and the need to improve the fault tolerance characteristics and VA capacity

    of systems, have increased the interest in the development of power electronic

    equipment with power factor quality capability. Electrical motors consume a large

    amount of the available electrical energy and this energy tends to increase due to themassive emerging applications of electrical motor drives, in appliances and in industrial

    processes. Therefore, the improvement of the power factor of these low power drive

    systems, usually in the range from fractional horsepower to one horsepower is of

    particular interest. For these power ratings, the system configuration usually comprises

    a single-phase to three-phase type of converter with additional circuitry for power factor

    control and reduction of T.H.D. Single-phase to three-phase acdcac conversion

    usually employs a full-bridge topology. This system composed of two parallel single-

    phase rectifiers and a three-phase inverter and induction motor. The proposed system is

  • 7/29/2019 three phase to five phase

    15/89

  • 7/29/2019 three phase to five phase

    16/89

    Introduction

    3

    1.6 Literature Overview:

    High-Performance Speed-Sensorless Control of an Induction Motor Drive Using a

    Minimalist Single-Phase PWM Converter by Olorunfemi Ojo, Senior Member, IEEE,

    Zhiqiao Wu, Student Member, IEEE, Gan Dong, Student Member, IEEE, and Sheetal

    K. Asuri.

    Summary:

    Home appliances and comfort conditioners are yet to benefit from the recent

    developments in power electronics because of cost constraints. In this paper, a speed-

    sensor less induction motor drive system using converters with reduced device counts

    (minimalist, sparse converters) and actuated from a single-phase system is proposed for

    such low-cost applications. The analysis, control, dynamic, and steady-state

    characteristics of the proposed drive are experimentally illustrated.

    This paper has presented the methodology for the analysis and control of a high-

    performance induction motor drive actuated by two controlled rectifierinverter

    systems with reduced count of switching devices. The general approach for determining

    the modulation signals required for the carrier-based PWM pulse generation for this

    class of minimalist converters has been set forth. The input supply voltage is a single

    phase and the input current is controlled using a natural reference frame controller to

    operate close to unity displacement power factor. The nature of the modulation signals,

    the achievable motor dynamics, and waveforms are clearly layout in simulation results.

    Reduced Switch Count Multiple Three-Phase AC Machine Drive Systems by

    Cursino Brando Jacobina, Senior Member, IEEE, Euzeli Cipriano dos Santos, Jr.,

    Student Member, IEEE, Edison Roberto Cabral da Silva, Fellow, IEEE, Mauricio

    Beltro de Rossiter Correa, Member, IEEE, Antonio Marcus Nigeria Lima, Senior

    Member, IEEE, and Talvanes Meneses Oliveira, Member, IEEE

    Summary:

    In this paper, two three-phase ac drive systems with reduced number of

    components, named configurations and, are investigated. Configuration uses multiple

    two-leg voltage source inverters in which all inverters share an extra-leg. Configuration

    also employs multiple two-leg inverters but in this case the inverters share the midpoint

    of a capacitor bank in the dc-link, instead. These configurations are compared to

    configuration that employs multiple three-leg inverters. The main characteristics of the

  • 7/29/2019 three phase to five phase

    17/89

    Introduction

    4

    machine drive systems are presented together with selected experimental results that

    demonstrate the feasibility of the proposed configurations.

    Two components minimized multiple three-phase ac drive systems have been

    examined in this paper. Configuration uses multiple two-leg converter topologies in

    which all the inverters share an extra-leg. Configuration also uses multiple two-leg

    converter topologies but, instead, they share the midpoint of the capacitor bank of the

    dc-link. Configuration uses 1 legs and configuration uses 2 legs, while configuration

    demands 3 legs, where is the number of drives. The overall performance of

    configuration is superior to that of configuration because: 1) the lower THD; 2) the

    voltage capability that can be split among the inverters; 3) the fact that the machine

    voltages do not depend on the individual capacitor voltages; and 4) there is no ac

    fundamental current flowing through the dc-link capacitors. Configurations and require

    less power devices and consequently a less complex gating control circuitry.

    A Three-Phase Parallel Active Power Filter Operating With PCC Voltage

    Compensation with Consideration for an Unbalanced Load by Woo-Cheol Lee, Taeck-

    Kie Lee, and Dong-Seok Hyun, Senior Member, IEEE

    Summary:

    The performance and dynamic characteristics of a three-phase parallel active

    power filter (APF) with point of the common coupling (PCC) voltage compensation

    with consideration for an unbalanced load is presented and analyzed in this paper. The

    proposed scheme employs a pulse-width modulation (PWM) voltage-source inverter

    and has two operation modes. First, it operates as a conventional active filter with

    reactive power compensation when PCC voltage is within the 15% voltage drop range.

    Second, it operates as a voltage compensator when PCC voltage is not within the 15%

    voltage drop range. Both the APF and the voltage compensator compensate

    asymmetries caused by nonlinear loads. Finally, the validity of this scheme is

    investigated through the analysis of simulation and experimental results for a prototype

    APF system rated at 10kVA.

    So it can be conclude that three-phase parallel APF operating with PCC voltage

    compensation with consideration for an unbalanced load, and compared functions of an

    APF and a voltage compensator. The proposed scheme has two operation modes. First,

    it operates as an APF with reactive power compensation when PCC voltage is within

    the 15% voltage drop range. Second, when the PCC voltage is not within the 15%

    voltage drop range, it operates as a voltage compensator. In order to improve APF

  • 7/29/2019 three phase to five phase

    18/89

    Introduction

    5

    performance, a dc voltage control loop was implemented with both the APF and the

    voltage compensator. Both the APF and the voltage compensator compensate

    asymmetries caused by nonlinear loads. This scheme will be used for critical industrial

    equipment like PLCs, HID and adjustable speed drives, and it may fail in situations

    where there are dramatic drops and harmonics in the PCC. To test the validity of the

    proposed scheme, simulation and experimental results were analyzed.

    Control of Circulating Current in Two Parallel Three-Phase Boost Rectifiers by

    Zhihong Ye, Member, IEEE, Dushan Boroyevich, Member, IEEE, Jae-Young Choi,

    Member, IEEE, and Fred C. Lee, Fellow, IEEE

    Summary:

    One unique feature in parallel three-phase converters is a potential zero-

    sequence circulating current. To avoid the circulating current, most present technology

    uses isolation approach, such as transformers or separate power supplies. This paper

    proposes a parallel system where individual converters connect both ac and dc sides

    directly without additional passive components to reduce size and cost of the overall

    parallel system. In this case, the control of the circulating current becomes an important

    objective in the converter design. This paper 1) develops an averaged model of the

    parallel converters based on a phase-leg averaging technique; 2) a zero-sequence model

    is then developed to predict the dynamics of the zero-sequence current; 3) based on the

    zero-sequence model, this paper introduces a new control variable, which is associated

    with space-vector modulation; 4) a strong zero-sequence current control loop is

    designed to suppress the circulating current; 5) simulation and experimental results

    validate the developed model and the proposed control scheme.

    This work has developed an averaged model to predict zero sequence dynamics

    in two parallel three-phase boost rectifiers. To control the zero-sequence current, a new

    control variable associated with space-vector modulation was introduced. Since the

    zero-sequence dynamic is a first-order system, a high bandwidth control loop was

    designed to effectively suppress the circulating current. Both simulation and

    experimental results validated the proposed control scheme. The implementation

    requires only one additional current sensor. The control algorithm can be easily

    programmed in a digital signal processor (DSP).This modelling approach and control

    concept can be generalized for paralleling any two multi-phase converters, such as full

    bridge rectifiers and inverters, three-phase three-leg rectifiers and inverters, and three-

  • 7/29/2019 three phase to five phase

    19/89

    Introduction

    6

    phase four-leg rectifiers and inverters. These converters cover most medium and high

    power applications, such as motor drives, ac power supplies and dc power supplies.

    Study on Ideal Operation Status of Parallel Inverters by Hui Cai, Rongxiang Zhao,

    and Huan Yang, Student Member, IEEE

    Summary:

    In order to keep a parallel inverter system operating stably, it is important to

    restrain the circulating current effectively. Based on the theoretical analysis, the

    limitation of a conventional conclusion about ideal operation status of parallel inverters

    is studied in detail. And then, the ideal operation status of the parallel inverter system is

    well investigated in this paper. A new criterion about ideal operation status of parallel

    inverters is concluded, i.e., there will be no circulating current among parallel inverters

    only when their output voltages have the same frequency, phase, amplitude and are also

    uniformly modulated. The concept of uniform modulation and the corresponding

    conclusion are verified by simulation and experimental results.

    The concept of uniform modulation for a parallel inverter system was

    introduced. A new conclusion about the ideal operation status of a parallel inverter

    system was concluded. Simulation and experimental results verified the theoretical

    analysis result and the proposed conclusion. The new conclusion is more complete to

    analyze the circulating current of a parallel inverter system. It also offers a new point of

    view to restrain the circulating current of the parallel inverter system.

    Shunt Active-Power-Filter Topology Based on Parallel Interleaved Inverters. by

    Lucian Asiminoaei, Member, IEEE, Eddy Aeloiza, Student Member, IEEE, Prasad N.

    Enjeti, Fellow, IEEE, and Frede Blaabjerg, Fellow, IEEE.

    Summary:

    In this paper, an interleaved active-power-filter concept with reduced size of

    passive components is discussed. The topology is composed of two pulse width

    modulation interleaved voltage-source inverters connected together on the ac line and

    sharing the same dc-link capacitor. The advantages of the proposed approach are as

    follows: 1) significant reduction in the linkage inductors size by decreasing the line -

    current ripple due to the interleaving; 2) reduction of the switching stress in the dc-link

    capacitor, due to the shared connection; and 3) more accurate compensation for high-

    power applications, because the power sharing allows one to use a higher switching

    frequency in each inverter. This paper analyzes the design of the passive components

    and gives a practical and low-cost solution for the minimization of the circulation

  • 7/29/2019 three phase to five phase

    20/89

    Introduction

    7

    currents between the inverters, by using common-mode coils. Several simulation results

    are discussed, and experimental results with a three-phase 10-kVA 400-V unit are

    obtained to validate the theoretical analysis.

    This paper discussed the advantages of two inverters connected in parallel and

    sharing the same dc capacitor for reactive power and current-harmonic compensation.

    Design specification analysis shows that the values of the passive components are

    significantly reduced. The intrinsic modularity characteristic of the topology increases

    the reliability and makes it suitable for high-power applications. Simulation results and

    experiments validate the presented analysis. This paper concludes that the usage of

    smaller line inductors and the replacement of the isolation transformer with common

    mode coils gives lower costs and allows a faster response in tracking the harmonic-

    current reference, which makes the topology very attractive for high-power industrial

    APFs.

  • 7/29/2019 three phase to five phase

    21/89

    1-3 AC Conversion Methods

    8

    Chapter 2

    SINGLE PHASE A.C TO THREE PHASE A.C CONVERSION METHODS

    2.1 Methods to Convert Single Phase to Three Phase Drive Systems:

    A wide variety of commercial and industrial electrical equipment requires

    three-phase power. Electric utilities do not install three-phase power as a matter of

    course because it costs significantly more than single-phase installation. As an

    alternative to utility installed three-phase, rotary phase converters, static phase

    converters and phase converting variable frequency drives (VFD) have been used for

    decades to generate three-phase power from a single-phase source. However these

    technologies have serious limitations, which motivated Phase Technologies, LLC to

    develop a new digital phase converter, Phase Perfect. This new patented technology

    overcomes the limitations of earlier phase converters, and is an affordable alternative to

    utility three-phase.

    2.1.1 Rotary phase converter:

    A rotary phase converter, abbreviated RPC, is an electrical machine that

    produces three-phase electric power from single-phase electric power. This allows three

    phase loads to run using generator or utility-supplied single-phase electric power. A

    rotary phase converter may be built as a motor-generator set. These have the advantage

    that in isolating the generated three-phase power from the single phase supply and

    balancing the three-phase output. However, due to weight, cost, and efficiency

    concerns, most RPCs are not built this way. Rotary Phase Converters Provide Reliable,

    Balanced, and Efficient Three Phase Power.

    All converters can be mainly categorized into two groups: one is cascade type

    and another is unified type. In cascade type, the PWM converter for power factor

    correction and the PWM inverter for speed control are connected in series with large

    DC-Link capacitor and two static power converters are operated and controlled in

    separate. In this type, specific number of switches, to compose the converter and

    inverter, are required. Therefore, the required number of switches cannot be reduced

    significantly. On the other hand, in the unified type, conventional concepts of PWM

    converter and inverter are merged together and same converter handles the functions of

  • 7/29/2019 three phase to five phase

    22/89

    1-3 AC Conversion Methods

    9

    PWM converter (power factor correction) and PWM inverter(motor control) at the same

    time. As an added advantage, the input inductor, which is commonly used in the PWM

    converter for power factor correction, can be eliminated and replaced by the existing

    motor inductor. Therefore, this new concept can significantly reduce the number of

    components, compared to any conventional cascade type topologies.

    Fig. 2.1. block diagram for rotary phase converter

    2.1.2 Static Phase Converter:

    Static Phase Convertor allows three phase motors to operate on single phase

    power Static Phase Converters operate by charging and discharging capacitors to

    temporarily produce a 3rd phase of power for only a matter of seconds during start up

    of electric motors, then it will drop out forcing the motor to continue to run on just 1

    phase and only part of its windings. Due to their technology, Static Phase Converters do

    not properly power any class of 3 phase machinery or equipment. They will not in any

    way power 3 phase welders, 3 phase battery chargers, 3 phase lasers, or any type of

    machinery with 3 phase circuitry. Static Phase Converters also will not start delta

    wound 3 phase motors.

    2.1.3 Phase Perfect Digital Phase Converter:

    The Phase Perfect digital phase system is similar to static and rotary phase

    converters in that two of the phase leads to the load come directly from the power line.

    At that point the similarity ends. Power to generate the voltage for the third lead flows

  • 7/29/2019 three phase to five phase

    23/89

    1-3 AC Conversion Methods

    10

    into the digital phase converter through an inductor and a set of semiconductor switches

    which feed a DC (constant voltage) link capacitor. The switches on the input can

    control the waveform of the input current and insure that it is sinusoidal, so as not to

    create harmonic distortion on the power grid. The DC link capacitor is connected to a

    second set of semiconductor switches which feed a second inductor and a filter

    capacitor to smooth out the high-frequency pulses created by the switches.

    The system is controlled by a small microcontroller, specifically a digital signal

    processor (DSP) which can measure voltages and feed controlled pulses into the

    switches, in addition to performing high-speed calculations. The DSP is constantly

    monitoring the system voltages and current to insure that the input current is sinusoidal,

    and the output voltage is also sinusoidal. The output voltage can be made equal in

    magnitude to the input voltage to an accuracy that is primarily determined by the

    measurement accuracy of the DSP. Typically, the line-line output voltages of Phase

    Perfect are balanced to within 1-2%. As the load on the system changes, the DSP senses

    any drop in the voltage and adjusts the pulses to the semiconductor switches to maintain

    this accuracy from no load up to full load. Any motor load or any combination of

    motors up to the maximum rating of the digital phase converter can be connected

    without creating unbalanced voltages. This is the first product to apply modern

    technology to the problem of phase conversion.

    Fig 2.2. Block diagram of Phase Perfect Digital Phase Converter

    2.2 Single-Phase to Three-Phase (1-3) Cycloconverters:

    Recently, with the decrease in the size and the price of power electronics

    switches, single-phase to three-phase cycloconverters started drawing more research

    interest. Usually, an H bridge inverter produces a high frequency single-phase voltage

    waveform, which is fed to the cycloconverter either through a high frequency

    transformer or not. If a transformer is used, it isolates the inverter from the

    cycloconverter. In addition to this, additional taps from the transformer can be used to

  • 7/29/2019 three phase to five phase

    24/89

    1-3 AC Conversion Methods

    11

    power other converters producing a high frequency ac link. The single-phase high

    frequency ac (HFAC) voltage can be either sinusoidal or trapezoidal. There might be

    zero voltage intervals for control purposes or zero voltage commutation.

    2.2.1 Integral Pulse Modulated (1-3) Cycloconverters:

    The input to these cycloconverters is single-phase high frequency sinusoidal or

    square waveforms with or without zero voltage gaps. Every half-cycle of the input

    signal, the control for each phase decides if it needs a positive pulse or a negative pulse

    using integral pulse modulation. For integral pulse modulation, the command signal and

    the output phase voltage are integrated and the latter result is subtracted from the

    former. For a positive difference, a negative pulse is required, and vice versa for the

    negative difference. For the positive (negative) input half-cycle, if a positive pulse isrequired, the upper (lower) switch is turned on; otherwise, the lower (upper) switch is

    turned on.

    Therefore, the three-phase output voltage consists of positive and negative half-

    cycle pulses of the input voltage. Note that this converter can only work at output

    frequencies which are multiples of the input frequency.

    2.2.2 Phase-Controlled(1-3) Cycloconverter:This cycloconverter converts the single-phase high frequency sinusoidal or square

    wave voltage into three-phase voltages using the previously explained phase control

    principles. The voltage command is compared to a saw tooth waveform to find the

    firing instant of the switches. Depending on the polarity of the current and the input

    voltage, the next switch to be turned on is determined. Compared to the previous one,

    this converter has more complex control but it can work at any frequency.

    2.3 Single-Phase-to-Three-Phase AC/DC/AC PWM Converter:

    Single phase to three-phase pulse width-modulation (PWM) converters for low-

    power three-phase induction motor drives, where a single- phase half-bridge PWM

    rectifier and a two-leg inverter are used. The simplest circuit of an ac/dc/ac converter

    topology converting from a single-phase supply to a three-phase variable-voltage

    system is a single-phase full-bridge rectifier and a three-leg PWM inverter system. This

    converter gives excellent performance such as sinusoidal control of source current,unity power-factor control of the source side, constant dc voltage control, and

  • 7/29/2019 three phase to five phase

    25/89

    1-3 AC Conversion Methods

    12

    bidirectional power flow. However, it requires ten active switching devices, so that it is

    more expensive than other circuits.

    Fig. 2.3(a). Single-phase-to-three-phase ac/dc/ac PWM converter

    Fig.2.3 (b) wave form of grid voltage & current

  • 7/29/2019 three phase to five phase

    26/89

    Control Strategies of Converters

    13

    Chapter 3

    CHARACTERISTICS OF INDUCTION MOTOR

    Three-phase AC induction motors are widely used in industrial and commercial

    applications. They are classified either as squirrel cage or wound-rotor motors. These

    motors are self-starting and use no capacitor, start winding, centrifugal switch or other

    starting device. Almost 90% of the three-phase AC Induction motors are of Squirrel-

    cage type.

    3.1 Starting characteristics:

    Induction motors, at rest, appear just like a short circuited transformer and if

    connected to the full supply voltage, draw a very high current known as the Locked

    Rotor Current. They also produce torque which is known as the Locked Rotor

    Torque. The Locked Rotor Torque (LRT) and the Locked Rotor Current (LRC) are a

    function of the terminal voltage of the motor and the motor design. As the motor

    accelerates, both the torque and the current will tend to alter with rotor speed if the

    voltage is maintained constant. The starting current of a motor with a fixed voltage will

    drop very slowly as the motor accelerates and will only begin to fall significantly when

    the motor has reached at least 80% of the full speed. The actual curves for the induction

    motors can vary considerably between designs but the general trend is for a high current

    until the motor has almost reached full speed. The LRC of a motor can range from

    500% of Full-Load Current (FLC) to as high as 1400% of FLC. Typically, good motors

    fall in the range of 550% to 750% of FLC.

    The starting torque of an induction motor starting with a fixed voltage will drop

    a little to the minimum torque, known as the pull-up torque, as the motor accelerates

    and then rises to a maximum torque, known as the breakdown or pull-out torque, at

    almost full speed and then drop to zero at the synchronous speed. The curve of the start

    torque against the rotor speed is dependent on the terminal voltage and the rotor design .

    The LRT of an induction motor can vary from as low as 60% of FLT to as high as

    350% of FLT. The pull-up torque can be as low as 40% of FLT and the breakdown

    torque can be as high as 350% of FLT. Typically, LRTs for medium to large motors are

    in the order of 120% of FLT to 280% of FLT. The PF of the motor at start is typically

  • 7/29/2019 three phase to five phase

    27/89

    Control Strategies of Converters

    14

    0.1-0.25, rising to a maximum as the motor accelerates and then falling again as the

    motor approaches full speed.

    Fig. 3.1 Typical torque-speed curve of the three-phase induction motor

    3.2 Running Characteristics:

    Once the motor is up to speed, it operates at a low slip, at a speed determined by

    the number of the stator poles. Typically, the full-load slip for the squirrel cage

    induction motor is less than 5%. The actual full-load slip of a particular motor is

    dependent on the motor design. The typical base speed of the four pole induction motor

    varies between 1420 and 1480 RPM at 50 Hz, while the synchronous speed is 1500

    RPM at 50 Hz. The current drawn by the induction motor has two components: reactive

    component (magnetizing current) and active component (working current). The

    magnetizing current is independent of the load but is dependent on the design of the

    stator and the stator voltage. The actual magnetizing current of the induction motor can

    vary, from as low as 20% of FLC for the large two pole machine, to as high as 60% for

    the small eight pole machine.

    The working current of the motor is directly proportional to the load. The

    tendency for the large machines and high-speed machines is to exhibit a low

    magnetizing current, while for the low-speed machines and small machines the

    tendency is to exhibit a high magnetizing current. A typical medium sized four pole

    machine has a magnetizing current of about 33% of FLC. A low magnetizing current

  • 7/29/2019 three phase to five phase

    28/89

    Control Strategies of Converters

    15

    indicates a low iron loss, while a high magnetizing current indicates an increase in iron

    loss and a resultant reduction in the operating efficiency.

    3.3 Load characteristics:

    In real applications, various kinds of loads exist with different torque-speed

    curves. For example, Constant Torque, Variable Speed Load (screw compressors,

    conveyors, feeders), Variable Torque, Variable Speed Load (fan, pump), Constant

    Power Load (traction drives), Constant Power, Constant Torque Load (coiler drive) and

    High Starting/Breakaway Torque followed by Constant Torque Load (extruders, screw

    pumps). The motor load system is said to be stable when the developed motor torque is

    equal to the load torque requirement. The motor will operate in a steady state at a fixed

    speed. The response of the motor to any disturbance gives us an idea about the stability

    of the motor load system. This concept helps us in quickly evaluating the selection of a

    motor for driving a particular load.

    Fig. 3.2Torque-speed curves of the motor with two different loads

    3.3.1 Constant Torque, Variable Speed Loads:

    The torque required by this type of load is constant regardless of the speed. In

    contrast, the power is linearly proportional to the speed. Equipment, such as screw

    compressors, conveyors and feeders, has this type of characteristic.

  • 7/29/2019 three phase to five phase

    29/89

    Control Strategies of Converters

    16

    Fig 3.3. Constant Torque, Variable Speed Loads

    3.3.2 Variable Torque, Variable Speed Loads:

    This is most commonly found in the industry and sometimes is known as aquadratic torque load. The torque is the square of the speed, while the power is the cube

    of the speed. This is the typical torque-speed characteristic of a fan or a pump.

    Fig 3.4. Variable Torque, Variable Speed Loads

    3.3.3 Constant Power Loads:

    This type of load is rare but is sometimes found in the industry. The power

    remains constant while the torque varies. The torque is inversely proportional to the

    speed, which theoretically means infinite torque at zero speed and zero torque at infinite

    speed. In practice, there is always a finite value to the breakaway torque required. This

    type of load is characteristic of the traction drives, which require high torque at low

    speeds for the initial acceleration and then a much reduced torque when at running

    speed.

    Fig 3.5. Constant Power Loads

    3.3.4 Constant Power, Constant Torque Loads:

  • 7/29/2019 three phase to five phase

    30/89

    Control Strategies of Converters

    17

    This is common in the paper industry. In this type of load, as speed increases,

    the torque is constant with the power linearly increasing. When the torque starts to

    decrease, the power then remains constant.

    Fig 3.6 Constant Power, Constant Torque Loads

    3.3.5 High Starting/Breakaway Torque followed by Constant Torque:

    This type of load is characterized by very high torque at relatively low

    frequencies. Typical applications include extruders and screw pumps.

    Fig. 3.7. Relation between the Voltage and Torque versus Frequency

    3.4. Induction motor characteristics in the proposed system:

  • 7/29/2019 three phase to five phase

    31/89

    Control Strategies of Converters

    18

    Fig 3.8(a) line-line voltage(V)

    The above figure shows line-line voltage of three phase induction motor of a given

    input of 230V a.c to three phase inverter. It can be noticed that due to presence of

    harmonic content there exists a distortion in the wave form.

    Fig 3.8(b) Three phase currents (A)

    The above figure shows three phase currents obtained from given input current of 23A.

    Here in the induction motor the induced e.m.f in the rotor is very large, as a result a

    very high starting current is seen.

    Fig 3.8(c) Rotor speed of induction motor in rad/sec

    The above figure shows rotor speed obtained as 120 rad/sec for applied voltage of 230

    a.c, the reference speed set for this induction motor is 120 rad/sec, it can be clearly

    observed that speed is maintained constant even though the input voltage is varied.

    Fig 3.8(d) electromagnetic torque in N/m

  • 7/29/2019 three phase to five phase

    32/89

    Control Strategies of Converters

    19

    The above figure shows electromagnetic in newton/metre, it can be observed that the

    starting torque is very much high in the interval t=0 to t=0.1 and it has come to steady

    state after t=0.1. The high starting torque is because it has to run high inertia load at

    starting time.

    Power 2 hp, 230v

    Frequency 50hz

    Speed 1425rpm

    Rotor Type Squirrel cage

    Voltage(Line To

    Line)

    230v

    Stator

    Resistance(Rs)

    0.64ohms

    Stator

    Inductance(Lls)

    0.21e-3h

    Rotor

    Resistance(Rr)

    0.26ohms

    Rotor

    Inductance(Llr)

    0.48e-3h

    Mutual

    Inductance(Lm)

    4e-3h

    Inertia(J) 0.0226kg.m^2

    Reference

    Frame

    Rotor

    Table 1: Ratings of Induction Motor

    The above table shows ratings of three phase induction motor for different

    parameters.

    Chapter 4

    CONTROL STRATEGIES OF CONVERTERS

    4.1 Introduction:

    At present, voltage source converters are mostly used in electrical drives. These

    converters utilize capacitors in the DC-link to store temporarily electrical energy.

  • 7/29/2019 three phase to five phase

    33/89

    Control Strategies of Converters

    20

    Switching the power electronic devices allows the DC voltage to be modulated which

    can result in a variable voltage and frequency waveform. The purpose of the modulator

    is to generate the required switching signals for these switching devices on the basis of

    user defined inputs. For this purpose, the voltagetime integral was introduced, which

    in turn is tied to the average voltage per sample U(tk) that may be written as

    (4.1)

    Where Ts is a given sample interval and u(t) represents the instantaneous voltage across

    a single-phase of a load. The introduction of the variable Ts assumes the use of a fixed

    sampling frequency which is normally judicially chosen higher than the fundamental

    frequency range required to control electrical machines. The upper sampling frequency

    limit is constrained by the need to limit the switching losses of the converter

    semiconductor devices. The ability to control the converter devices in such a manner

    that the load is provided with a user defined mean reference voltage per sample U(tk)

    is instrumental to control current accurately. This statement can be made plausible by

    considering the incremental flux linkage for one sample interval of a load in the form of

    a coil with inductance L and resistance R which may be written as

    (4.2)

    The corresponding incremental change of load current (over a sample interval Ts) may

    be written as in

    (4.3)

    the event that magnetic saturation effects may be ignored. This expression can, with the

    aid of (4.3), be expressed as

    (4.4)

    This may be reduced to

    (4.5)

  • 7/29/2019 three phase to five phase

    34/89

    Control Strategies of Converters

    21

    When the time constant = L/R of the load is deemed to be relatively large compared to

    Ts, as is normally the case for electrical machines. Central to the issue of controlling the

    incremental current is therefore, according to (4.5), the ability of the modulator to

    realize (within the constraint of this unit) the condition

    (4.6)

    For each sampling instance. Note that (4.6) simply states that the switching states of the

    converter must be controlled by the modulator to ensure that the average voltage (per

    sample) equals the user defined average reference value to ensure that the actual and

    reference incremental current change (per sample interval) are equal.

    How this may be achieved will be outlined in subsequent sections for variousconverter topologies using an approach taken by Svensson. In effect, this approach

    considers how the average voltage per sample U (tk) varies as function of the converter

    switch on/off time within a sample interval. Once this relation is known for the

    converter under consideration, the function in question is compared with the user

    defined reference value to determine the converter switch state within each sample.

    Initially, a single-phase half-bridge converter will be considered followed by an

    analysis of a single-phase full-bridge converter and three-phase converter.

    4.2 Sinusoidal Pulse Width Modulation:

    This is a method in which fixed dc input voltage is given to an inverter and the

    output is a controlled ac voltage. This is done by adjusting the on and off periods of the

    inverter components.

    The advantages of PWM control are:

    1. No additional components are required with this method.

    2. Lower order harmonics are eliminated or minimised along with its output voltage

    control. Hence, the filtering requirements are minimised since higher order harmonics

    can be filtered easily.

    If the half-cycle sine wave modulation, the triangular carrier only in a positive

    or negative polarity range of changes, the resulting SPWM wave only in a polar Range,

    called unipolar control mode. Figure 4.1(a) shows the unipolar and bipolar modulation

    of PWM pulses. If the half-cycle sine wave modulation, triangular carrier in continuous

  • 7/29/2019 three phase to five phase

    35/89

    Control Strategies of Converters

    22

    change between positive and negative polarity, the SPWM wave is between positive

    and negative changes, known as bipolar control.

    Fig. 4.1: Unipolar and bipolar modulation

    The switches in the voltage source inverter (See Fig. 4.1(b)) can be turned on

    and off as required. In the simplest approach, the top switch is turned on If turned on

    and off only once in each cycle, a square wave waveform results. However, if turned on

    several times in a cycle an improved harmonic profile may be achieved.

    In the most straightforward implementation, generation of the desired output

    voltage is achieved by comparing the desired reference waveform (modulating signal)

    with a high-frequency triangular carrier wave as depicted schematically in Fig.4.2.

    Depending on whether the signal voltage is larger or smaller than the carrier waveform,

    either the positive or negative dc bus voltage is applied at the output. Note that over the

    period of one triangle wave, the average voltage applied to the load is proportional to

    the amplitude of the signal (assumed constant) during this period. The resulting

    chopped square waveform contains a replica of the desired waveform in its low

    frequency components, with the higher frequency components being at frequencies of

    an close to the carrier frequency.

    Fig. 4.2: Simple Voltage Sourced Inverter

  • 7/29/2019 three phase to five phase

    36/89

    Control Strategies of Converters

    23

    Notice that the root mean square value of the ac voltage waveform is still equal

    to the dc bus voltage, and hence the total harmonic distortion is not affected by the

    PWM process. The harmonic components are merely shifted into the higher frequency

    range and are automatically filtered due to inductances in the ac system. When the

    modulating signal is a sinusoid of amplitude Am, and the amplitude of the triangular

    carrier is Ac, the ratio m=Am/Ac is known as the modulation index. Note that

    controlling the modulation index therefor controls the amplitude of the applied output

    voltage. With a sufficiently high carrier frequency (see Fig. 4.3 drawn for fc/fm = 21

    and t = L/R = T/3; T = period of fundamental), the high frequency components do not

    propagate significantly in the ac network (or load) due the presence of the inductive

    elements. However, a higher carrier frequency does result in a larger number of

    switchings per cycle and hence in an increased power loss. Typically switching

    frequencies in the 2-15 kHz range are considered adequate for power systems

    applications. Also in three-phase systems it is advisable to use so that all three

    waveforms are symmetric.

    (4.7)

    Note that the process works well for m1, there are periods of thetriangle wave in which there is no intersection of the carrier and the signal as in Fig.4.4.

    However, a certain amount of this over modulation is often allowed in the interest of

    obtaining a larger ac voltage magnitude even though the spectral content of the voltage

    is rendered somewhat poorer.

  • 7/29/2019 three phase to five phase

    37/89

    Control Strategies of Converters

    24

    Fig. 4.3: Principal of Pulse Width Modulation

    Note that with an odd ratio for fc/fm, the waveform is anti-symmetric over a 360 degree

    cycle. With an even number, there are harmonics of even order, but in particular also a

    small dc component. Hence an even number is not recommended for single phase

    inverters, particularly for small ratios of fc/fm.

    4.2.1 SPWM Spectra:

    Although the SPWM waveform has harmonics of several orders in the phase

    voltage waveform, the dominant ones other than the fundamental are of order n and n2

    where n = fc/fm. This is evident for the spectrum for n=15 and m = 0.8 shown in

    Fig.4.5. Note that if the other two phases are identically generated but 120 o apart in

    phase, the line-line voltage will not have any triple n harmonics. Hence it is advisable to

    choose, as then the dominant harmonic will be eliminated. It is evident from Fig 4.5b,

    that the dominant 15th harmonic in Fig. 4.5 is effectively eliminated in the line voltage.

    Choosing a multiple of 3 is also convenient as then the same triangular waveform can

    be used as the carrier in all three phases, leading to some simplification in hardware. It

    is readily seen that as the where E is the dc bus voltage, that the rms value of the output

    voltage signal is unaffected by the PWM process.. However, the problematic harmonics

  • 7/29/2019 three phase to five phase

    38/89

    Control Strategies of Converters

    25

    are shifted to higher orders, thereby making filtering much easier. Often, the filtering is

    carried out via the natural high-impedance characteristic of the load.

    Fig. 4.4:SPWM Harmonic Spectra: n =15, m =0.8

    4.3 Space Vector PWM:

    4.3.1 Principle of Space Vector PWM:

    The circuit model of a typical three-phase voltage source PWM inverter is

    shown in Fig. 4.9. S1 to S6 are the six power switches that shape the output, which are

    controlled by the switching variables a, a, b, b, c and c. When an upper transistor is

    switched on, i.e., when a, b or c is 1, the corresponding lower transistor is switched off,

    i.e., the corresponding a, b or c is 0. Therefore, the on and off states of the upper

    transistors S1, S3 and S5 can be used to determine the output voltage.

  • 7/29/2019 three phase to five phase

    39/89

    Control Strategies of Converters

    26

    Fig. 4.5: Three-phase voltage source PWM Inverter

    The relationship between the switching variable vector [a, b, c] t and the line-to-

    line voltage vector [Vab Vbc Vca]t is given by (2.1) in the following:

    (4.8)

    Also, the relationship between the switching variable vector [a, b, c]t and the phase

    voltage vector [Va Vb Vc]t can be expressed below.

    (4.9)

    there are eight possible combinations of on and off patterns for the three upper

    power switches. The on and off states of the lower power devices are opposite to the

    upper one and so are easily determined once the states of the upper power transistors

    are determined. According to equations (4.8) and (4.9), the eight switching vectors,

    output line to neutral voltage (phase voltage), and output line-to-line voltages in terms

    of DC-link Vdc, are given in Table below which shows the eight inverter voltage vectors

    (V0 to V7).

  • 7/29/2019 three phase to five phase

    40/89

    Control Strategies of Converters

    27

    Table 2: Switching vectors, phase voltages and output line to line voltages

    Fig. 4.6: The eight inverter voltage vectors (V0 to V7)

    Space Vector PWM (SVPWM) refers to a special switching sequence of the

    upper three power transistors of a three-phase power inverter. It has been shown togenerate less harmonic distortion in the output voltages and or currents applied to the

    phases of an AC motor and to provide more efficient use of supply voltage compared

    with sinusoidal modulation technique as shown in Fig. 4.11.

  • 7/29/2019 three phase to five phase

    41/89

    Control Strategies of Converters

    28

    Fig. 4.7: Locus comparison of maximum linear control voltage in Sine PWM and SVPWM.

    To implement the space vector PWM, the voltage equations in the abc reference

    frame can be transformed into the stationary dq reference frame that consists of the

    horizontal (d) and vertical (q) axes as depicted in below Figure.

    Fig. 4.8: The relationship of abc reference frame and stationary dq reference frame.

    From this figure, the relation between these two reference frames is below

    fdq0 = Ksfabc

    where,

    (4.10)

    f denotes either a voltage or a current variable.

    As described in above figure, the transformation is equivalent to an orthogonal

    projection of [a, b, c]t

    onto the two-dimensional perpendicular to the vector [1, 1, 1]t

    (the equivalent d-q plane) in a three-dimensional coordinate system. As a result, six

    non-zero vectors and two zero vectors are possible. Six nonzero vectors (V1 - V6) shape

    the axes of a hexagonal as depicted and feed electric power to the load.

  • 7/29/2019 three phase to five phase

    42/89

    Control Strategies of Converters

    29

    The angle between any adjacent two non-zero vectors is 60 degrees.

    Meanwhile, two zero vectors (V0 and V7) are at the origin and apply zero voltage to the

    load. The eight vectors are called the basic space vectors and are denoted by V 0, V1, V2,

    V3, V4, V5, V6, and V7. The same transformation can be applied to the desired output

    voltage to get the desired reference voltage vector Vrefin the d-q plane.

    The objective of space vector PWM technique is to approximate the reference

    voltage vector Vref using the eight switching patterns. One simple method of

    approximation is to generate the average output of the inverter in a small period, T to be

    the same as that of Vrefin the same period.

    Fig. 4.9: Basic switching vectors and sectors.

    Therefore, space vector PWM can be implemented by the following steps:

    Step 1. Determine Vd, Vq, Vref, and angle ()

    Step 2. Determine time duration T1, T2, T0

    Step 3. Determine the switching time of each transistor (S1 to S6)

    Step 1: Determine Vd, Vq, Vref, and angle ():

    From Fig. 4.14, the Vd, Vq, Vref, and angle () can be determined as follows:

  • 7/29/2019 three phase to five phase

    43/89

    Control Strategies of Converters

    30

    (4.11)

    (4.12)

    (4.13)

    Where f = fundamental frequency

    Step 2: Determine time duration T1, T2, T0:

    From Fig. 4.15, the switching time duration can be calculated as follows:

    Switching time duration at Sector 1

    (4.14)

  • 7/29/2019 three phase to five phase

    44/89

    Control Strategies of Converters

    31

    (4.15)

    (4.16)

    (4.17)

    Switching time duration at any Sector

    (4.18)

    Fig. 4.10: Reference vector as a combination of adjacent vectors at sector 1.

  • 7/29/2019 three phase to five phase

    45/89

    Control Strategies of Converters

    32

    Step 3: Determine the switching time of each transistor (S1 to S6):

    (a) Sector 1. (b) Sector 2.

    (c) Sector 3. (d) Sector 4.

    (e) Sector 5. (f) Sector 6.

    Fig. 4.11: Space vector PWM switching patterns at each sector.

  • 7/29/2019 three phase to five phase

    46/89

    Control Strategies of Converters

    33

    Table 3: Switching Time Calculation at Each Sector

    4.4. Vector Control technique:

    This control is also known as the field oriented control, flux oriented

    control or indirect torque control. Using field orientation (Clarke-Park

    transformation), three-phase current vectors are converted to a two-dimensional rotating

    reference frame (d-q) from a three-dimensional stationary reference frame. The d

    component represents the flux producing component of the stator current and the q

    component represents the torque producing component. These two decoupled

    components can be independently controlled by passing though separate PI controllers.

    The outputs of the PI controllers are transformed back to the three-dimensional

    stationary reference plane using the inverse of the Clarke-Park transformation. The

    corresponding switching pattern is pulse width modulated and implemented using the

    SVM. This control simulates a separately exited DC motor model, which provides an

    excellent torque-speed curve. The transformation from the stationary reference frame to

    the rotating reference frame is done and controlled with reference to a specific flux

    linkage space vector (stator flux linkage, rotor flux linkage or magnetizing flux

  • 7/29/2019 three phase to five phase

    47/89

    Control Strategies of Converters

    34

    linkage). In general, there exists three possibilities for such selection and hence, three

    different vector controls.

    They are:

    Stator flux oriented control

    Rotor flux oriented control

    Magnetizing flux oriented control

    The most challenging and ultimately, the limiting feature of the field orientation,

    is the method whereby the flux angle is measured or estimated. Depending on the

    method of measurement, the vector control is divided into two subcategories: direct and

    indirect vector control. In direct vector control, the flux measurement is done by using

    the flux sensing coils or the Hall devices. This adds to additional hardware cost and in

    addition, measurement is not highly accurate. Therefore, this method is not a very good

    control technique. The more common method is indirect vector control. In this method,

    the flux angle is not measured directly, but is estimated from the equivalent circuit

    model and from measurements of the rotor speed, the stator current and the voltage.

    Fig. 4.12: block diagram for vector control technique using direct torque and speed control

    4.5 control circuits adopted in the system:

    Two control circuits has been used, one for rectifier circuit using pwm technique

    and other for inverter using vector control technique, the details are as follows .

  • 7/29/2019 three phase to five phase

    48/89

    Control Strategies of Converters

    35

    4.5.1. Rectifier control circuit:

    The dc-link voltage vc is adjusted to its reference value v*c using the controller

    Rc, which is a standard PI type controller. This controller provides the amplitude of the

    reference grid current Ig . To control power factor and harmonics in the grid side, the

    instantaneous reference current ig must be synchronized with voltage eg, as given in the

    voltage oriented control (VOC) for three-phase system. This is obtained via blocks Ge-

    Ig, based on a PLL scheme. The reference currents i*a and i*b are obtained by making

    ia = ib = ig /2, which means that each rectifier receives half of the grid current. The

    control of the rectifier currents is implemented using the controllers indicated by blocks

    Ra and Rb. These controllers can be implemented using linear or nonlinear techniques.

    In this paper, the current control law is the same as that used in the two sequences

    synchronous controller described.

    Fig. 4.13: control circuit for rectifier

    4.5.2. Inverter control circuit:

    In these control circuit speed reference has been taken from induction motor to

    generate the gating pulses across the inverter switches. To implement vector control the

    induction motor parameters must be known and values put into complex set of

    mathematical equations developed from generalized machine theory. Here speed

    controller generates a signal representing the demanded speed, and to drive a motor at

    that speed also voltage signal is generated by using three phase sequence analyzer

  • 7/29/2019 three phase to five phase

    49/89

    Control Strategies of Converters

    36

    where the magnitude of the voltage is generated, in order to generate pulses this two

    phase transformation is changed to three phase transformation by using d-q axis of

    trigonometric functions i.e., 2 sint (where t= 0, 145, 270 degrees), thus three gating

    pulses are generated.

    Fig.4.14: control circuit for inverter

    4.5.3. pi controller:

    Pi controller consists of two components 1) kp which is proportional to the

    error, it increases the loop gain of the system 2) ki which is proportional to the integral

    of the error, it increases the order of the system and reduces the steady state error.

    Fig 4.15: block diagram of pi controller

    In the simulink circuit KP & Ki values chosen based on trial and error method.

  • 7/29/2019 three phase to five phase

    50/89

    Design Methodology of Proposed Converter

    37

    Chapter 5

    DESIGN METHODOLOGY OF PROPOSED CONVERTER

    5.1 Introduction:

    In this chapter the conventional and proposed system is design and analysed.

    The circuit of conventional system ac-dc-ac is shown below in Fig. 5.1, which consists

    of rectifier, a three phase inverter and induction motor. The conventional system

    consists of total ten switches, a input inductor (Lg) and two capacitor banks.

    Fig. 5.1: Conventional single-phase to three phase drive system

    In the proposed system two parallel rectifiers, an inverter and induction motor

    has been used. The system consists of total fourteen switches i.e., qa1, qa1 , qa2 , and

    qa2 , and qb1, qb1, qb2 and qb2 of rectifier A & B, . The inverter is constituted of

    switches qs1, qs1, qs2, qs2, qs3 and qs3. The system is composed of grid, input

    inductors (La, La, Lb, and Lb), capacitor bank at the dc link. The conduction state of

    the switches is represented by variable sqa1 to sqs3, where sq = 1 indicates a closed

    switch while sq = 0 an open one.

    Four gating pulses has been given across to each two anti parallel switches in

    rectifier circuit by using pwm technique and three pulses have generated by using

    vector control across inverter where only one switch is on at upper leg lower leg at a

    instant.

  • 7/29/2019 three phase to five phase

    51/89

    Design Methodology of Proposed Converter

    38

    Fig. 5.2(a): Proposed single-phase to three phase drive system

    The below figure shows the block diagram of proposed system where single

    phase a.c supply is converted to d.c by using a rectifier and by using a three phase

    inverter d.c is converted to three phase a.c to operate a three phase induction motor and

    also control circuits are designed in order to generate gating pulses across rectifier and

    inverter switches.

    Fig. 5.2(b): Block diagram of proposed single-phase to three phase drive system model

    1ph

    ac

    Rectifier

    A

    3PH

    VSIIM

    Parallel converters

    Control

    circuit

    Rectifier

    B

    Speed Ref

    Vdc

  • 7/29/2019 three phase to five phase

    52/89

    Design Methodology of Proposed Converter

    39

    5.2 Mathematical Modelling of the proposed system:

    From Fig. 2, the following equations can be derived for the front-end rectifier,

    the below equations (5.1), (5.2), (5.3), (5.4), has been derived by applying kvl across

    four loops in proposed circuit. Here resistance is also taken in to consideration in the

    system.

    5.2.1.Different modes/loops in the proposed system:

    Here four different loops are considered for the designing of mathematical

    modelling of the proposed system.

    Fig: 5.2.1(a): loop1 of the system model

    By applying the kirchoff voltage law in the above loop,

    we get

    (5.1)

    Where Va10 , va20 are pole voltages across switches qa1 and qa2 respectively,

    eg is the grid voltage ra, ra, la, la are the resistances and inductances across input side,

    Also ia, ia are currents across rectifier A.

  • 7/29/2019 three phase to five phase

    53/89

    Design Methodology of Proposed Converter

    40

    Fig: 5.2.1(b): loop2 of the system model

    Similarly from the loop 2 we can get,

    (5.2)

    Where Vb10, vb20 are pole voltages across switches qb1 and qb2 respectively,

    eg is the grid voltage Rb, rb, lb, lb are the resistances and inductances across input

    side, ib and ib are currents in rectifier B.

    Fig: 5.2.1(c): loop3 of the system model

    (5.3)

  • 7/29/2019 three phase to five phase

    54/89

    Design Methodology of Proposed Converter

    41

    Where Va10 , Vb10 are pole voltages across switches qa1 and qb1 respectively,

    ra, rb, la, lb are the resistances and inductances across input side, ia and ib are currents

    in rectifier A and B respectively.

    Fig: 5.2.1(d): loop4 of the system model

    (5.4)

    Where Va20, Vb20 are pole voltages across switches qa2 and qb2 respectively

    ra, rb, la, lb are the resistances and inductances across input side, , ia and ib are

    currents in rectifier A and B respectively.

    Where p = d/dt and symbols like r and l represent the resistances and

    inductances of the input inductors La, La, Lb, and Lb.

    The grid current can be derived as,

    (5.5)

    The circulating current io can be defined from ia and ia or ib and ib , i.e.,

    (5.6)

    Introducing io and adding (5.3) and (5.4), relations (5.1)(5.4) become

    (5.7)

    (5.8)

  • 7/29/2019 three phase to five phase

    55/89

    Design Methodology of Proposed Converter

    42

    (5.9)

    Where

    (5.10)

    (5.11)

    (5.12)

    Relations (5.7)(5.9) and (5.5) constitute the front-end rectifier dynamic model.

    Therefore, va (rectifier A), vb (rectifier B), and vo (rectifiers A and B) are used to

    regulate currents ia, ib, and io, respectively. Reference currents ia and ib are chosen

    equal to ig /2 and the reference circulating current io is chosen equal to 0.

    In order to both facilitate the control and share equally current, voltage, and

    power between the rectifiers, the four inductors should be equal, i.e., rg = ra = ra = rb

    = rb and lg = la =la = lb = lb. In this case, the model (5.7)(5.9) can be simplified to

    the model given by

    (5.13)

    (5.14)

    (5.15)

    Additionally, the equations for ig , ia , and ib can be written as

    (5.16)

    (5.17)

    (5.18)

    In this ideal case (four identical inductors), the circulating current can be reduced tozero imposing

  • 7/29/2019 three phase to five phase

    56/89

    Design Methodology of Proposed Converter

    43

    (5.19)

    When Io = 0 (ia = ia, ib = ib) the system model (5.7)(5.9) is reduced to

    (5.20)

    (5.21)

    Then, the model of the proposed system becomes similar to that of a system composed

    of two conventional independent rectifiers

    5.3 PWM Strategy:

    The inverter can be commanded by using an adequate pulse width modulation

    (PWM) strategy for three-phase voltage source inverter (VSI), so that it will not be

    discussed here. In this section, the PWM strategy for the rectifier will be presented.

    The rectifier pole voltages va10, va20, vb10, and vb20 depend on the

    conduction states of the power switches, i.e.,

    (5.22)

    Where vc is the total dc-link voltage.

    Considering that va, vb, and vo denote the reference voltages determined by

    the current controllers, we found

    (5.23)

    (5.24)

    (5.25)

    The gating signals are directly calculated from the reference pole voltages

    va10, va20, vb10, and vb20. However, (5.23)(5.25) are not sufficient to determine

    the four pole voltages uniquely from va, vb and vo. Introducing an auxiliary

    variable vx = va20, that equation plus the three equations (5.23)(5.25) constitute a

    four independent equations system with four variables (va10, va20, vb10, and

    vb20). Solving this system of equations, we obtain

    (5.26)

  • 7/29/2019 three phase to five phase

    57/89

    Design Methodology of Proposed Converter

    44

    (5.27)

    (5.28)

    (5.29)

    From these equations, it can be seen that, besides va, vb and vo, the pole

    voltages depend on also of vx. The limit values of the variable vx can be calculated

    by taking into account the maximum vc /2 and minimum vc /2 value of the pole

    voltages

    (5.30)

    (5.31)

    Where vc is the reference dc-link voltages, vmax = max and vmin = min with

    = {va , 0, va/2 + vb /2 vo/2, va/2 vb /2 vo/2}

    Introducing a parameter (0 1), the variable vx can be written as

    (5.32)

    When = 0, = 0.5, and = 1 the auxiliary variable vx has the following

    values vx = vxmin, vx = vx have = (vxmin +vxmax)/2, and vx = vxmax,

    respectively. When vx = vxmin or vx = vxmax a converter leg operates with zero

    switching frequency.

    Once vx is chosen, pole voltages va10, va20, vb10, and vb20are defined

    from (5.26) to (5.29). The gating signals are obtained by comparing pole voltages with

    one (vt1), two (vt1 and vt2) or more high frequency triangular carrier signals. In the

    case of double-carrier approach, the phase shift of the two triangular carrier signals (vt1

    and vt2) is 180 .

    The parameter changes the place of the voltage pulses related to va and vb .

    When vx = vxmin ( = 0) or vx = vxmax ( = 1) are selected, the pulses are placed

    in the begin or in the end of the half period (Ts) of the triangular carrier signal. On the

    other hand, when vx =vx have the pulses are centred in the half period of the carrier

    signal. The change of the position of the voltage pulses leads also to the change in the

  • 7/29/2019 three phase to five phase

    58/89

    Design Methodology of Proposed Converter

    45

    distribution of the zero instantaneous voltages (i.e., va = 0 and vb = 0).With = 0 or

    = 1 the zero instantaneous voltages are placed at the beginning or at the end of the

    switching period, respectively, while with = 0.5, they are distributed equally at the

    beginning and at the end of the half period. This is similar to the distribution of the

    zero-voltage vector in the three-phase inverter. Consequently, influences the

    harmonic distortion of the voltages generated by the rectifier.

    5.4 Control Strategy:

    Fig. 5.3 presents the control block diagram of the system in Fig. 5.2,

    highlighting the control of the rectifier. The rectifier circuit of the proposed system has

    the same objectives of that in Fig. 5.1, i.e., to control the dc-link voltage and to

    guarantee the grid power factor close to one. Additionally, the circulating current io in

    the rectifier of the proposed system needs to be controlled. In this way, the dc-link

    voltage VC is adjusted to its reference value VC using the controller RC, which is a

    standard PI type controller. This controller provides the amplitude of the reference grid

    current Ig. To control power factor and harmonics in the grid side, the instantaneous

    reference current ig must be synchronized with voltage eg, as given in the voltage

    oriented control (VOC) for three-phase system. This is obtained via blocks Ge-Ig, based

    on a PLL scheme. The reference currents i*a and i*b are obtained by making ia = ib

    = ig /2, which means that each rectifier receives half of the grid current. The control of

    the rectifier currents is implemented using the controllers indicated by blocks Ra and

    Rb . These controllers can be implemented using linear or nonlinear techniques. In this

    paper, the current control law is the same as that used in the two sequences synchronous

    controller described.

    Fig. 5.3: Control Block Diagram for rectifier

  • 7/29/2019 three phase to five phase

    59/89

    Design Methodology of Proposed Converter

    46

    These current controllers define the input reference voltages va and vb .The

    homopolar current is measured (io ) and compared to its reference (io = 0). The error

    is the input of PI controller Ro , that determines the voltage vo . The calculation of

    voltage vx is given from (5.30) to (5.32) as a function of , selected as shown in the

    Section V. The motor there-phase voltages are supplied from the inverter (VSI). Block

    VSI-Ctr indicates the inverter and its control. The control system is composed of the

    PWM command and a torque/flux control strategy (e.g., field-oriented control or

    volts/hertz control).

    5.5 Harmonic Distortion:The harmonic distortion of the converter voltages has been evaluated by using

    the weighted THD (WTHD). It is computed by using

    (5.33)

    where a1 is the amplitude of the fundamental voltage, ai is the amplitude of ith

    harmonic and p is the number of harmonics taken into consideration Fig. 4 shows theWTHD of voltages generated by rectifiers [vab = (va + vb )/2 for the proposed

    configuration and vg =vg10 vg20 for the conventional one] at rated grid voltage as a

    function of . Note that the parameter determines vx from (5.30) to (5.32). The

    resultant voltage vab generated by rectifier is responsible to control ig, which means

    that this voltage is used to regulate the harmonic distortion of the utility grid.

    When the single-carrier PWM is used, the behaviour of WTHD of the proposed

    system is similar to that of conventional one for all , as observed in Fig. 5.4. When the

    double-carrier PWM is used with = 0.5, the WTHD is also the same for both

    configurations. However, for the other values of the WTHD of the proposed system is

    lower than that of the conventional one. The WTHD of the proposed topology (double-

    carrier with = 0 or = 1) is close to 63% of that of the conventional topology (with

    = 0.5). The study has also shown that it is possible to reduce the switching frequency of

    the proposed system in 60% and still have the same WTHD of the standard

    configuration.

  • 7/29/2019 three phase to five phase

    60/89

    Design Methodology of Proposed Converter

    47

    Fig. 5.4: WTHD of rectifier voltage (vab for proposed configuration and vg for

    standard configuration) as a function of.

    The WTHD behaviour in Fig. 5.4 can be explained from Fig. 5.5. That figure

    depicts the pole voltages (va10, va20, vb10, vb20) and their references (va10, va20,

    vb10, vb20), the triangular carrier signals (vt1 , vt2 ), the resultant rectifier voltage

    (vab ) and the circulating voltage (vo ). Fig. 5.5(a) and (c) shows these variables with

    single-carrier (with = 1) and double-carrier (with =1), respectively. For the double-

    carrier the voltage vab has smaller amplitude and better distribution along the half

    switching period than that of single-carrier, which means a lower WTHD (as observed

    in Fig. 5.4 for = 1). On the other hand, for = 0.5 the distribution of voltage vab

    along the switching period is the same for both cases, i.e., single-carrier and double-

    carrier have the same WTHD (as observed in Fig. 4 for = 0.5).

    Besides the total harmonic distortion (THD) of the grid current ig , associated to

    the WTHD of the voltage vab , the harmonic distortion analysis must also consider the

    currents in the rectifiers. This is an important issue due to losses of the converter. The

    harmonic distortion of the rectifier currents (ia , ia , ib , and ib ) with double-carrier is

    higher than that of the grid current ig . When the parallel rectifier with double-carrier is

    used, the THD of all these currents are reduced for = 0 or = 1 and increased for =

    0.5. On the other hand, the THD of the circulating current is also smaller with = 0 or

    = 1. Fig. 5.6 shows currents ia , ia , and io for double-carrier with = 1 and = 0.5.

  • 7/29/2019 three phase to five phase

    61/89

    Design Methodology of Proposed Converter

    48

    It can be seen that the mean values of the ripples of all currents are smaller when = 1

    is selected.

    In conclusion the optimal rectifier operation is obtained with double-carrier

    making = 0 or = 1. A four-carrier approach may also be used. Compared with the

    two-carrier strategy, the four-carrier strategy permits to reduce the harmonic distortion

    of the grid current, but increases the rectifier losses.

    Fig. 5.5: Variables of rectifiers A and B.

    (a) Single-carrier with = 1.

    (b) Single-carrier with = 0.5.

    (c) Double-carrier with = 1.

    (d) Double carrier with = 0.5.

  • 7/29/2019 three phase to five phase

    62/89

    Design Methodology of Proposed Converter

    49

    Fig. 5.6: Currents ia , i_a , and io for double-carrier with = 1 and = 0.5.

    5.6 Ratings of Switches:

    Assuming same rms voltages at both grid and machine sides, a machine power

    factor of 0.85 and neglecting the converter losses, currents of the rectifier switches

    normalized in terms of currents of the inverter switches are 2.55 and 1.27 for the

    conventional and the proposed single-phase to three-phase converter, respectively. Fig.

    5.7(a) and (b) shows the flow of active power in the conventional and in the proposed

    single-phase to three-phase converter, respectively. For balanced system (Lg =La = La

    = Lb = Lb ), voltage vo is close to zero, so that the dc-link voltage is equal to that

    required by the conventional system. Since the parallel connection scheme permits to

    reduce the switch currents and preserve the dc-link voltage, the rating of each power

    switch in the rectifier side is reduced.

  • 7/29/2019 three phase to five phase

    63/89

    Design Methodology of Proposed Converter

    50

    Fig. 5.7(a): Flow of active power in Conventional acdcac single-phase to three phase converter

    Fig. 5.7(b): Flow of active power in proposed system with two rectifiers

    5.7 DC-Link Capacitor Design:

    The dc-link capacitor design and calculation carried out in this section. The

    voltage ripple over the dc capacitor is limited to an imposed maximum value ofvmax.

    some simplified assumptions are considered such that the integration time interval (t1,

    t2) is half of the switching period Tsw and the dc current (Idc) is half of the peak value

    of the nominal line current.

    Then the minimum required dc capacitor is given by

  • 7/29/2019 three phase to five phase

    64/89

    Design Methodology of Proposed Converter

    51

    Where idc anddc are current and voltage of the dc capacitor, respectively, Tsw

    is the switching period, and dc is the voltage ripple.

    C=4.7mF

    5.8 Input Inductors:

    The design of input inductors is carried out in this section .

    Where Vdc is the voltage on the dc capacitor and i is the amplitude of the

    cross-current developed during the interval t0, the Vdc obtained is 230V

    LF=

    L= 5mH

    The THD of the grid current as a function of for different values of ln [the

    inductances of rectifiers A and B (lg ) referred to that of the conventional configuration

    (lg ), i.e., ln = lg /lg ]. For ln > 0.4 (lg > 0.4lg) the THD of the grid current of the

    proposed topology is smaller than that of the conventional topology.

  • 7/29/2019 three phase to five phase

    65/89

    Design Methodology of Proposed Converter

    52

    Fig. 5.8: Inductor specification in terms of THD of ig and.

    5.9 Fault Compensation:

    The proposed system presents redundancy of the rectifier converter, which can

    be useful in fault-tolerant systems. The proposed system can provide compensation for

    open-circuit and short-circuit failures occurring in the rectifier or inverter converter

    devices.

    The fault compensation is achieved by reconfiguring the power converter

    topology with the help of isolating devices (fast active fusesFj , j = 1, . . . , 7) and

    connecting devices (back-to-back connected SCRst1 , t2 , t3 ), as observed in Fig.

    5.10(a). These devices are used to redefine the post-fault converter topology, which

    allows continuous operation of the drive after isolation of the faulty power switches in

    the converter. Fig. 5.10(b) presents the block diagram of the fault diagnosis system. In

    this figure, the block fault identification system (FIS) detects and locates the faulty

    switches, defining the leg to be isolated. This control system is based on the analysis of

    the pole voltage error.

    The fault detection and identification is carried out in four steps:

    1) Measurement of pole voltages (vj0).

    2) Computation of the voltage error j0 by comparison of reference voltages and

    measurements affected in Step 1).

    3) Determination as to whether these errors correspond or not to a faulty condition; this

    can be implemented by the hysteresis detector shown in Fig. 5.10(b).

  • 7/29/2019 three phase to five phase

    66/89

    Design Methodology of Proposed Converter

    53

    4) Identification of the faulty switches by using j0.

    Fig. 5.9(a): Proposed configuration highlighting devices of fault-tolerant system.

    Fig.5.9 (b): Block diagram of the fault diagnosis system.

    This way, four possibilities of configurations have been considered in terms of faults

    1) Pre-fault (healthy) operation.

    2) Post-fault operation with fault at the rectifier B

    3) Post-fault operation with fault at the rectifier A.