(tis246)

Upload: syslo

Post on 03-Apr-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 (TIS246)

    1/4

    Technical Information SheetPage 1 of 4

    741-F Mille r Drive , Leesburg, Virginia 20175 T +1 703 443-0000 F +1 703 669-1300 www.eurotherm.com

    Action Instruments Barber-Colman Continental Industries Eurotherm Chessell Eurotherm Controls

    TIS#: 246, Issue 1

    Date: 11/15/03

    Issued By: Mark Demick

    Subject

    This document describes the Minimum Pulse Time setting and its affect on Cycle Time in the

    3116 and 3216 Series PID controllers.

    Controllers

    3116, 3216 Controllers

    Introduction

    All PID controllers having a logic, triac or relay output to interface to an AC voltage load

    through a mercury contactor, solid state relay (SSR), or other On/Off AC actuator modulate

    the output using a Time Proportioning Output (TPO) algorithm to control the average

    power to the load.

    This is done by switching the output ON for a period of time (TON) and OFF for a period of

    time (TOFF) and repeating this cycle indefinitely. During one (1) cycle the average power

    supplied to the load is:

    )( CycleTimeTrHeaterPoweerAveragePow ON= ; where Cycle Time OFFONCYC TT)T +=( .

    The Duty Cycle is the factor CycleTimeTON and is normally expressed as a percentage.

    Duty cycle represents the proportion of maximum available heater power. The average

    power (duty cycle) is varied by changing the ratio of TON to TOFF. Over longer periods of

    time the average power may be expressed as:

    )( TimeTotalCycleTotalTrHeaterPoweerAveragePow ON= ;

    Note that HeaterPowerhere is the actual power transferred by the heater and may not be

    the same as the heaters power rating.

    The PID controller calculates the Duty Cycle (the PID output control signal from 0 to 100

    percent) and provides settings in the controller such as Cycle Time and Minimum On Time.

  • 7/28/2019 (TIS246)

    2/4

    Technical Information SheetTIS#: 246 Page 2 of 4

    741-F Mille r Drive , Leesburg, Virginia 20175 T +1 703 443-0000 F +1 703 669-1300 www.eurotherm.com

    Action Instruments Barber-Colman Continental Industries Eurotherm Chessell Eurotherm Controls

    The Cycle Time setting typically varies from 100 milliseconds to over 100 seconds. The reasons

    for a settable Cycle Time have to do with the type of power control device and the type of load

    being driven and the effect on the life and precision of temperature control required.

    The minimum possible TON or TOFF is one-half cycle of the supply frequency (8.33ms @ 60Hz)

    and often is one whole cycle (16.67ms @ 60Hz) to minimize the effects of DC.

    50% 75% 90%25%

    Off Off Off Off Off On On On OnTime

    Average

    Power

    Duty Cycle =T

    ON/ T

    CYC

    100%

    10%

    On

    0%

    Figure 1

    3116, 3216 Controllers

    The control outputs in the 3116 and 3216 controllers may be either logic or relay output and

    are typically used to drive Solid State Relays (SSR) or other AC voltage actuators. There is a

    single setting in these controllers for Minimum Pulse Time 1.PLS, 2.PLS and 4.PLS. No setting

    for cycle time is offered and is instead calculated from TON and TOFF. TON and TOFF are calculated

    using the following formulas:

    )1(. ndOutputDemaFractionalPLSnTON =

    ndOutputDemaFractionalPLSnT FFO = .

    Where FractionalOutputDemand = Controller Working Output (WRK.OP) in % / 100.

  • 7/28/2019 (TIS246)

    3/4

    Technical Information SheetTIS#: 246 Page 3 of 4

    741-F Mille r Drive , Leesburg, Virginia 20175 T +1 703 443-0000 F +1 703 669-1300 www.eurotherm.com

    Action Instruments Barber-Colman Continental Industries Eurotherm Chessell Eurotherm Controls

    For example, with 1.PLS set to 250 ms, Table 1 shows TON, TOFF and TCYC. Zero (0) and one-

    hundred (100) are not shown as the power would be fully Off and On respectively.

    % Output TON (ms) TOFF (ms) Cycle Time (ms)

    1 252.5 25000.0 25252.5

    5 263.2 5000.0 5263.2

    10 277.8 2500.0 2777.8

    15 294.1 1666.7 1960.8

    20 312.5 1250.0 1562.5

    25 333.3 1000.0 1333.3

    30 357.1 833.3 1190.5

    35 384.6 714.3 1098.9

    40 416.7 625.0 1041.7

    45 454.5 555.6 1010.1

    50 500.0 500.0 1000.055 555.6 454.5 1010.1

    60 625.0 416.7 1041.7

    65 714.3 384.6 1098.9

    70 833.3 357.1 1190.5

    75 1000.0 333.3 1333.3

    80 1250.0 312.5 1562.5

    85 1666.7 294.1 1960.8

    90 2500.0 277.8 2777.8

    95 5000.0 263.2 5263.2

    99 25000.0 252.5 25252.5

    Table 1

    It can be seen from Table 1 that there is but one output percentage where TON or TOFF are

    equal fifty (50) percent, as expected. Further note that at 50 percent output, both TON or TOFF

    are twice the Minimum Pulse Time so that at 50 percent output and only at 50 percent

    output we can say:

    seTimeMimimumPulTCYC = 4 @ Duty Cycle = 50%

    For a decreasing controller output towards 0 from 50 percent, TON approaches the MinimumPulse Time asymptotically while TOFF increases to maintain the correct Duty Cycle ratio. The

    same holds true for an increasing output towards 100 from 50 percent, TOFF approaches the

    Minimum Pulse Time asymptotically while TON increases to maintain the correct Duty Cycle

    ratio. This is clearly seen in Figure 1 and Table 1.

  • 7/28/2019 (TIS246)

    4/4

    Technical Information SheetTIS#: 246 Page 4 of 4

    741-F Mille r Drive , Leesburg, Virginia 20175 T +1 703 443-0000 F +1 703 669-1300 www.eurotherm.com

    Action Instruments Barber-Colman Continental Industries Eurotherm Chessell Eurotherm Controls

    For logic outputs, the Minimum Pulse Time may be set to Auto (default) which is 110 milli-

    seconds, or between 100ms and 150 seconds. Relay outputs do not have an Auto setting but

    can be adjusted between 1 and 150 seconds, 5 seconds being the default.

    The Time Proportioning Output (TPO) algorithm is designed so that it never has to put small

    duration pulses onto the switching device. This means that for mercury contactors the wear is

    reduced for longer life. For Solid State Relays (SSR) or Silicon Controlled Rectifier (SCR) power

    controllers, the minimum period is usually long enough to ensure that the zero voltage

    switching restriction does not prevent a good approximation to the power requirement. Figure

    2 shows the TPO algorithm in chart form.

    3116, 3216 Time Propor tioning Output

    0

    300

    600

    900

    1200

    1500

    1800

    2100

    2400

    2700

    3000

    0 10 20 30 40 50 60 70 80 90 100

    Output Power Demand in Percent

    Timeinmillis

    econds

    TON (ms) TOFF (ms) Cycle Time (ms)

    Figure 2