tm025 rheem 310 series heat pump rev b.pdf

Upload: neiljenkins

Post on 02-Jun-2018

231 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    1/68

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    RRhheeeemmAAuussttrraalliiaaPPttyyLLttdd AABBNN2211009988882233551111

    SERVICE INSTRUCTIONS

    310 Series Heat PumpTM025

    RRReeevvviiisssiiiooonnn:::BBB

    PPPuuubbbllliiissshhheeeddd:::000888///000777

    551310

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    2/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    1

    Contents

    Safety Warning ....................................................................................................................2Introduction..........................................................................................................................2Specifications.......................................................................................................................3Preventative Maintenance ...................................................................................................3Operation.............................................................................................................................4

    Electronic Controller ............................................................................................................5Operating Sequence Flow Charts:.......................................................................................6

    Refrigeration Terms and their Meaning................................................................................8Components and their Function...........................................................................................8Common Faults ...................................................................................................................9Wiring Diagram..................................................................................................................11Refrigeration Sealed System Diagram...............................................................................12LED Indication ...................................................................................................................12Fault Finding ......................................................................................................................14Refrigerant Charge ............................................................................................................45Electrical Insulation Testing ...............................................................................................46

    Component Replacement Procedures Water Heater......................................................47

    Component Replacement Procedures Refrigeration Plant .............................................52Component Replacement Procedures Sealed Refrigeration System .............................57Exploded View - Refrigeration Plant ..................................................................................62

    Replacement Parts List Refrigeration Plant.................................................................63Exploded View - Water Heater...........................................................................................64

    Replacement Parts List Water Heater .........................................................................65Rheem Electric Water Heater Warranty - (Australia Only) .................................................66Document Revision History................................................................................................67

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    3/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    2

    Safety Warning

    The purpose of this Service Manual is to provide sufficient information to allow a personwith the skills as required by the controlling Regulatory Authorities to carry out effectiverepairs to a Rheem 310 series Heat Pump Water Heater in the minimum of time.

    Safety precautions or areas where extra care should be observed when conducting testsoutlined in this manual are indicated by print in bold italics and/or a warning symbol.Take

    care to observe the recommended procedure.

    Certain diagnostic procedures outlined in these service instructions require live testing to be conducted. Wear Personal Protective Equipment (PPE)when conducting these tests to prevent the risk of electric shock. (Refer tothe Rheem Safety Procedure on electr ical testing)

    R134A is a controlled substance under the fair trading act. Personnelqualified and licensed to work with refrigerants may only carry out serviceand repair to the sealed refrigeration system. During repair the refrigerantmust be recovered, not vented to atmosphere.

    Environmental

    At the end of the service li fe o f a Rheem heat pump the refr igerant must berecovered by personnel qualified and licensed to work with refrigerantsprior to the unit being disposed of. Refrigerants must not be vented toatmosphere.

    Introduction

    The information provided in these instructions is based on the water heater being installedin accordance with the Installation Instructions provided with each water heater.

    Should you require further technical advice on a Rheem 310 Series Heat Pump WaterHeater, contact your nearest Rheem Service Department where all genuine replacementparts are also available.

    Heater Model Identification

    All identification numbers are designed to convey detailed information about the waterheater to which it is attached. The model number consists of 8 digits.

    5 X X 310 0 X

    5 Renewable Energy Model

    5 Air Sourced9 Solar Sourced

    0 No Heating Units1 Booster Element

    Storage Capacity in Litres

    No Reference System Requirement

    0 Element Not fitted5 2400 watts7 3600 watts

    Note: Model number, serial number and date of manufacture should be quoted in allcorrespondence.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    4/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    3

    Specifications

    Water Heater

    Model 551310Capacity - Litres 310

    Boost Capacity - Litres 220

    Booster element rating - kW 2.4 or 3.6T&PR valve Rating - kPa 1000

    With ECV 680Maximum inlet pressure - kPa

    Without ECV 800

    Inlet / Outlet RP/20Water Connections

    T&PR RP/15Quantity 1

    AnodeLength 1153

    Control board thermostat setting (fixed) 60C

    Limp mode mechanical thermostat setting 70C

    Mechanical thermostat ECO setting 88C

    Refrigeration System

    Parameter 551310

    Sound rating 51 dBA @1.5mSuperheat setting (Factory) +6C at 10C Evaporator temp.Refrigerant charge R134A 1050 gramsCompressor internal OTC Open 150C. Close 90C (automatic reset)

    Compressor winding resistanceRun winding - Red & Blue: 2.2 ohms at 20C

    Start winding - Red & Black: 3.27 ohms at 20C

    Compressor Capacitor 35F240 VAC 50HZ

    Fan winding resistanceRun winding Black & Brown: 184 ohms at 20CStart winding Black & Blue: 238 ohms at 20C

    Fan Capacitor 2F240 VAC 50HZ

    Circulator winding resistance 75.3 ohms @ 20C

    Preventative Maintenance

    It is suggested for peak performance that the water heater be serviced annually.

    1. Check for discharge from the T&PR valve. When the element or heat pump isoperating a small discharge of water may be evident. Operate the valve-easing lever toensure the valve opens and resets properly. Always open and close the valve gently.The T&PR valve should be replaced at 5 yearly intervals.

    2. Check for leaks at all cylinder fittings.

    3. Check for signs of excessive corrosion on the water heater jacket.

    4. Isolate power to the water heater and check all electrical connections for signs ofoverheating due to poor connection.

    5. Conduct an 'Electrical insulation test' on the water heater (refer to page 46).

    6. Check evaporator fins and fan blade for build up of dust or debris.

    7. Check for sludge build up and if necessary drain and flush tank.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    5/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    4

    Operation

    Operation Water System:

    The heat pump utilises a form of heating called top down heating.The circulator (1)draws cooler water from the bottom of the cylindervia the long dropper tube (2). The water passes through the heatexchanger (condenser) (3)where it is heated by the refrigerant and isthen returned to the top of the cylinder via a short dropper tube (4).

    Operation Heat Pump Mode:

    During normal operation in heat pumpmode the electronic controller(control board) holds a control relay in the energised state and powerfor the compressor is passed to an electronic switch (called a triac) viathe normally open relay contact.

    The operation of the compressor causes a pressure difference withinthe sealed refrigeration system. This pressure difference causes the

    refrigerant to move around the sealed system. The refrigerant entersthe evaporator (5)as a liquid, as the refrigerant absorbs heat from theatmosphere it changes state, at low pressure, from a sub cooled liquidto a super heated vapour or gas (evaporates). The vapour then entersthe compressor (6) and obtains more heat, known as heat ofcompression, and passes into the heat exchanger as a super heatedvapour at high pressure.

    As the refrigerant passes through the heat exchanger it gives offheat which is absorbed by the water flowing through a separatechamber inside the heat exchanger. As the refrigerant gives offheat it cools and changes state back into a liquid (condenses). Therefrigerant then enters the evaporator again and the cycle isrepeated.

    Operation Boost Mode:

    The controller will enter boostmode when atmospheric conditions are unsuitable for heatpump operation or a possible failure of the refrigeration or water circuits has beendetected. The following error conditions will initiate boostmode:

    1. The temperature sensed by the ambient air sensor is below 0C.

    2. The water leaving the heat exchanger is greater than 80C.

    3. The compressor discharge temperature is greater than 110C.

    4. The evaporator temperature is less than -3C.

    5. The failure of sensors S3, S4 or S5.

    6. The compressor is not running based on either of the following conditions:

    a. After 2 minutes in controller sequence 3 the compressor discharge temperature hasnot risen 15C above ambient.

    b. In controller sequence 4 the water temperature rise across the heat exchanger(condenser) is less than 8C.

    Inboost

    mode the electronic controller continues to control the temperature of the water inthe cylinder and the circulator however the control relay is de-energised switching thepower supply from the compressor triac to the element.

    1

    2

    3

    4

    3

    6

    5

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    6/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    5

    Boostmode allows 220 litres of 60C hot water to be provided by electric boosting. Duringthis mode the circulator will cycle on and off periodically allowing for the 220 litre boostcapacity rather than just the amount of water above the element as is the case with aconventional electric boost system.

    Once a heating cycle is completed the error is cleared and normal operation is resumed onthe next call for heat.

    Note: If sensor S4 fails the system will operate on boost mode however the temperaturewill in this case be controlled by the mechanical thermostat and 220 litres of 70C waterwill be available.

    Operation Limp Mode:

    Limpmode will only occur due to the failure of both sensors S1 and S4.

    In limpmode the electronic controller no longer controls the operation of the heat pumpand both heat pump mode and boostmode are rendered inoperable. The control relay isde-energised switching the power supply from the compressor triac to the element.

    Limpmode allows 111 litres of hot water to be provided by electric boosting and the water

    temperature is controlled by the mechanical thermostat which is set to 70C; in thiscondition only the water in the zone above the element is heated as the circulator does notoperate.

    It should be noted that if sensor S1 fails and sensor S4 is operational the system operatesin boost mode however the circulator cannot operate. In this case the end result is anoperation similar to limp mode in which 111 litres of water is heated by the booster and thetemperature controlled to 70C by the Robertshaw thermostat.

    Electronic Controller

    The main features of the electronic controller(control board) are shown on the diagram opposite.The inputs to the software are shown in blue andthe outputs that control the heat pump are shown inred.

    The connection marked relay element energisesor de-energises a relay that switches from heatpump heating to electric element heating when thesystem operates in boost or limp mode.

    The Compressor TRIAC switches the power to the

    compressor on and off.The Communication port can be used inconjunction with a computer to read the inputs andoutputs from the software. This information may belogged using specially designed logging software(Contact Rheem Service for more informationregarding this software).

    The Software loading port is only used for loadingsoftware on to the control board.

    The green and red LEDs indicate the condition ofthe heat pump (refer to the section titled LEDIndication on page 12).

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    7/68

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    8/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    7

    Page 2 of 2:

    NO

    Boost Mode

    220L heated toapprox. 60C

    H

    Relay de-energised

    Red LED Flashing

    Element On

    S1>62C?

    S4>53C?

    YES

    NO

    Element OffYES

    Z

    Circulator On

    NO

    S153C?

    YES Circulator Off

    YES

    NO

    Sequence

    0

    YES

    S4Sensor

    ok?

    Temp atthermostat =

    70C?

    Controller can no longer detect

    lower cylinder temperature.Water temperature will becontrolled by mechanical

    thermostat to 70C

    S1Sensor

    ok?

    NO

    YES

    Controller can no longer detect

    upper cylinder temperature.

    The circulator will not operatepreventing water below theelement level from heating

    Temperature at sensor S4 willnot achieve 53C

    NO

    Heating Cycle

    complete

    Element On

    Limp Mode

    111L heated to

    approx. 70C

    NO

    Element Off

    YES

    Power to controller offY

    S1Sensor

    ok?

    S1>62C?

    YES

    Boost Mode

    220L heated to

    approx. 70C

    Circulator On

    Temp atthermostat =

    70C?

    YES

    S1 2C?

    T4> 2C?

    A

    YES

    NO

    NO Ambient temperature high enoughto resume heat pump operation

    YES

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    9/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    8

    Refrigeration Terms and their Meaning

    Sub Cooled Liquid A substance below its saturation temperature at a given pressure.

    Super Heated VapourA substance above its boiling point at a given pressure.

    Saturated Vapour A substance at its boiling point at a given pressure.

    Latent Heat Hidden (invisible) heat removed or added to a substance that results in achange of state (i.e. liquid to a vapour) without an increase or decrease in temperature.

    Heat of Compression The additional heat added to a substance by the act ofcompressing it.

    Low Side Components and pipe work of a refrigeration system operating at lowpressure, generally considered to be the evaporator, suction line and accumulator.

    High Side Components and pipe work of a refrigeration system operating at highpressure, generally considered to be the condenser, discharge line, liquid receiver/filterdrier and compressor case where a rotary compressor is utilized.

    Boil Off The action of a substance as it absorbs heat and changes state (evaporates)from a liquid to a vapour (gas).

    Give Up Heat The action of a substance as it releases heat and changes state(condenses) from a vapour (gas) to a liquid.

    Components and their Function

    Temperature and Pressure Relief Valve - A valve designed to provide automatic relief bydischarging water in case of excessive temperature, pressure or both.

    Never fit a T&PR Valve with a pressure rating greater than that indicated onthe product-rating label.

    Pressure Limiting Valve (P.L.V.) - A valve that controls its outlet pressure to apredetermined limit.

    Outlet Delivery Tube (Dip Tube) - A plastic tube installed in the hot water outlet of thewater heater cylinder to conduct water from the highest point to the outlet connection. Italso acts as a fitting liner.

    Diffuser- A plastic device installed in the cold water inlet of the water heater cylinder toassist with stratification. It also acts as a fitting liner.

    Fitting Liner - A plastic tube installed in the cold-water inlet of the water heater to provideprotection against corrosion through the life of the water heater.

    Anode (Sacrificial)- A metal alloy electrode installed in the water heater cylinder that bygalvanic action protects the cylinder from corrosion.

    Thermostat - A device responsive to temperature that controls the supply of electricalenergy to the compressor, which results in the stored water being maintained at therequired temperature.

    Evaporator Thermistor - A device responsive to temperature that controls the active

    supply between the compressor circuit and the booster element circuit.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    10/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    9

    Compressor - An electro-mechanical device that adds heats to the refrigerant bycompressing it, known as heat of compression the resulting increase in refrigeranttemperature increases its pressure and causes the refrigerant to circulate through thesystem.

    Evaporator - A finned copper coil mounted on top of the water heater. The refrigerantenters as a liquid, as it passes through the coil it absorbs heat from the surroundingatmosphere and boils off (evaporates) to a gas.

    Condenser - An insulated housing containing stainless steel chambers where heattransfer occurs. The condenser (or heat exchanger) contains three chambers, one forrefrigerant, one for water and a third separating chamber containing air. The refrigerantenters as a gas, as it passes through the condenser it transfers (gives up) the heatabsorbed via the evaporator to the water flowing through the condenser in a separatechamber, during this process the refrigerant cools and changes state (condenses) back toa liquid.

    Receiver Filter Drier- This device, fitted between the condenser and thermal expansion(TX) valve, receives and stores liquid refrigerant from the condenser for delivery to the

    evaporator. The receiver also incorporates a filter and drier to trap impurities and removemoisture from the sealed refrigeration system

    Accumulator- This device, fitted in the suction line prior to the compressor, is designed toaccumulate and prevent liquid refrigerant from entering and damaging the compressor.

    Any liquid refrigerant is evaporated or boiled off and converted to a vapour by theaccumulator.

    Thermal Expansion (TX) Valve - A valve, installed between the condenser andevaporator that controls (meters) the amount of refrigerant delivered to the evaporator.The TX valve has an external temperature sensor fitted to the suction line and increases ordecreases the refrigerant flow to the evaporator depending on the detected suction line

    temperature.

    Thermal Cut Out (Overload) - A manual reset temperature sensitive device thatautomatically cuts off the supply of electrical energy to the control board and/or boostelement.

    Heating Unit (Element)- A tubular device containing an electric resistance element thatconverts electrical energy to heat. Standard element ratings are 2.4 and 3.6kW.

    Common Faults

    When a complaint is lodged about the performance of a hot water system there are anumber of causes that should be checked and eliminated. In an attempt to pinpoint themost likely cause it is important to discuss with the customer their reasons for thecomplaint, the duration of the problem, any change in circumstances or usage and recentweather conditions. This information in conjunction with the following listed commoncomplaints will assist you in locating the most likely cause. All procedures assume there iswater flowing through the water heater.

    Discoloured water- This may be the result of discoloured water entering from the coldwater mains. Check if the cold water is also discoloured.

    Excessive hot water usage- The complaints of insufficient hot water and no hot water

    can on many occasions be attributed to hot water usage exceeding the capacity of thewater heater to provide hot water.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    11/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    10

    When first attending a call of this nature it is essential to establish the probable hot waterusage by querying the usage habits of the household and compare this with the potentialdelivery of the model water heater installed. It can then be established if the usage iswithin or outside the capacity of the model. The areas to look at for excessive usage are:

    1. Automatic washing machines.

    2. Showers exceeding 12 litres/minute for mixed water and 5 minutes in duration.

    3. Two or more showers operating at the same time.

    4. Change of occupancy or number of persons increased.

    5. High water pressure area. (Excessive pressure relief valve discharge)

    6. Plumbing leaks.

    7. Crossed connection.

    Water hammer- A water heater will not cause water hammer, however valves associatedwith the water heater may be the source of the problem i.e. cold-water stopcock, non-return valve or relief valve.

    Most water hammer problems are associated with plumbing, hot and cold or appliancesi.e. solenoid valves, ballcocks, loose pipes, sharp angles in pipe work, faulty or worn valveparts, loose tap washers or neighbouring equipment.

    High water pressure areas will have more complaints of this nature and the use of apressure-limiting valve (PLV) to reduce the household cold-water pressure will usuallysolve most problems.

    Hot water plumbing leaks- If hot water has not been used for a period of time, feelingthe temperature of the hot water line may give an indication of water flow if the pipe iswarm. The method of checking for plumbing leaks is:

    1. Turn off the stopcock on the cold water supply to the water heater.

    2. Open a hot tap to ensure the flow of water stops. This will confirm the stopcock isoperating correctly.

    3. Turn off the hot tap.

    4. Turn on the stopcock to make up the water pressure in the cylinder, and then turn thestopcock off again.

    5. Wait approximately 5 minutes then do either of the following:

    a. With your ear close to the stopcock turn it on slightly and listen for any waterpassing. If there are no leaks, water should not pass.

    b. Open a hot tap while listening for any pressure release. If there is a pressurerelease there will be no leaks in the plumbing system.

    Mixing or crossed connections - If an automatic dishwasher, washing machine, flickmixer tap, tempering valve or thermostatic mixing valve is installed there is always thepossibility that the cold water could mix with the hot water through a faulty or incorrectlyinstalled valve. This is referred to as a cross connection. The complaints of insufficient hotwater, water too cold or excessive discharge from the pressure relief valve may beattributed to a cross connection. The method of checking for a cross connection is:

    1. Turn off the stopcock on the cold water supply to the water heater.

    2. Open a hot tap. If water flow is persistent and cold a cross connection exists.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    12/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    11

    Wiring Diagram

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    13/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    12

    Refrigeration Sealed System Diagram

    LED Indication

    All 310 series Heat Pumps have LED indication. There are two variations of LED indicationdepending upon the version of the controllers software; however all versions utilise a redand green LED to display the operational status and/or fault condition of the appliance.Note: The software version is printed on a label on the control board.

    Controller Software Version HPV 3.1, HPV 3.2 or no HPV identification

    310 Series Heat Pumps with controller version HPV3.1, HPV 3.2 or no HPV identificationhave a green and red LED located internally on the control board in the heat pump(refrigeration) module and utilise the following LED indication:

    LED IndicationLED Status Condition Details

    Green Solid S4 > 53C or S5 > 50CStandby mode (end of heating cycle,cylinder water at required temperature).

    Green Flashing S4 < 44.5C or S3 < 50C Call for heat initiated.

    Red FlashingVarious (refer to operatingsequence flow chart onpage 6 for more details).

    Component fault or ambient conditionstoo cold for heat pump operation.

    No indicationFault or system operatingin limp mode.

    Fault or system in limp mode with call forheat satisfied (water in cylinder @ 70C

    determined by mechanical thermostat).Note: Refer to diagram on page 5 for control board LED location.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    14/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    13

    Controller Software Version HPV 4.0 or higher

    310 series Heat Pumps with controller version HPV 4.0 or higherhave a red and greenLED located externally on the front of the heat pump module or internally on the controlboard in the heat pump (refrigeration) module depending upon date of manufacture.

    LED Flashing Frequency:Different combinations of flashing red and/or green LEDs areutilised to indicate the operational status or fault condition of the Heat Pump. Each flash in

    a series will last 0.5 seconds and is separated by 0.5 seconds between flashes. Eachseries of flashes is separated by 2 sec.

    Example: LED provides 2 flashes: 1) LED on for 0.5 sec.2) LED off for 0.5 sec.3) LED on for 0.5 sec.4) LED off for 2 sec.5) Return to Step 1).

    Operational LED Indication: If no fault is present the green LED will flash as shownbelow to indicate the operational sequence number the Heat Pump is currently operatingin (refer to operating sequence flow chart on page 6 for more details).

    Operational LED Indication

    Sequence Green LED Red LED0 Solid 0

    2 2 flashes 03 3 flashes 0

    4 4 flashes 0

    Fault Indication:If a fault is present the green and/or red LEDs will indicate the faultcondition according to the table below.

    Fault Indication

    Fault Error Green LED Red LEDFaulty power supply or system in limp mode

    with call for heat satisfied (1)N/A 0 0

    T3 (comp dis) > 60C in sequence 0(2) SerrNo 4 1 Flash 0

    T4 (ambient air) < 0C (3) SerrNo 1 0 Solid

    Any Sensor Strip Sensor Fault Any Sflag 0 1 Flash

    Water circ fault T0 (water outlet) > 80C SerrNo 2 0 2 Flashes

    T2 (evaporator) < -3C SerrNo 8 0 3 Flashes

    Comp/refrig fault T3 > T4 + 15C (in seq3) SerrNo 32 0 4 Flashes

    Comp/refrig fault T0 - T1 < 8C (in seq4) SerrNo 32 0 5 Flashes

    Water circ fault T1 > S4 + 7C SerrNo 64 0 6 Flashes

    TRIAC/refrig fault T3 > 110C SerrNo 128 0 7 Flashes

    Thermistor T0 Fault Tflag 1 1 Flash* 1 Flash*

    Thermistor T1 Fault Tflag 2 2 Flashes* 2 Flashes*Thermistor T2 Fault Tflag 4 3 Flashes* 3 Flashes*Thermistor T3 Fault Tflag 8 4 Flashes* 4 Flashes*

    Thermistor T4 Fault Tflag 16 5 Flashes* 5 Flashes*

    Notes:* The green and red LEDs flash simultaneously in these cases.(1) System may be in limp mode with call for heat satisfied (water in cylinder @ 70C

    determined by mechanical thermostat).(2) This condition creates a delay start for the compressor. This is not considered a fault.(3)Ambient temperature too cold for heat pump operation. This is not considered a fault.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    15/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    14

    Fault Finding

    Fault ChartNumber

    Page

    1 161.1 171.2 21

    No Hot Water

    7 43Insufficient hot water 2 23

    3 243.1 25

    3.2 253.3 263.4 27

    3.5 293.6 303.7 30

    8.1 44

    Software versionHPV 3.1, HPV 3.2

    or no HPVidentification

    8.3 444 32

    4.1 334.2 33

    4.3 344.4 35

    4.5 364.6 374.7 38

    4.8 394.9 4.13 40

    4.14 408 44

    System in boost or limp mode

    Software versionHPV 4.0 or higher

    8.2 44Leaking water heater 5 41

    Noisy water heater 6 42Blowing fuse/circuit breaker 7 43

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    16/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    15

    General Fault Finding Chart

    Fault Diagnosis

    No

    hot water?YES 1

    Insufficienthot water?

    NO

    2YES

    System

    in boost or limp

    mode?

    NO

    3

    YES

    NO

    5YES

    6

    NO

    Leaking

    water heater?

    Noisy

    water heater?

    7

    YES

    NO

    Blowing fuse/circuit breaker

    Boost or limp mode will be

    indicated by any of the followingLED conditions:

    Red solid or flashing.

    Red & green flashing together.

    No LEDs (Limp mode with

    Robertshaw thermostat open)

    4

    HPV 3.1, HPV 3.2 or

    no HPV identification

    HPV 4.0 or higher

    What is the

    controller

    software

    version?

    Note: For more information on LED indication refer to pages 12 and 13.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    17/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    16

    Fault Finding Chart 1

    1

    Warning: Terminals may be live.

    Wear Personal Protecti ve

    Equipment to prevent risk of

    electric shock.Is 240

    volts present at

    the terminal

    block? Test 1

    1.1YES

    Is

    the heater

    connected to an

    off peak

    tariff?

    NO

    Off peak connection is unsuitable for Heat

    Pump models. Connect to continuous tariff or

    off peak 2 if available

    YES

    Is the

    isolating switch

    or time clock

    turned off?

    NO

    Restore power and advise customerYES

    Is the

    fuse blown at the

    switchboard?

    NO

    Fault in household electrical wiringNO

    Reset circuit breaker

    or rewire fuse

    YES

    Did

    the fuse or

    circuit breaker blow

    again?

    7YES

    1. Heat pump connected to mixed circuit,

    possible excessive current draw or another

    appliance with a fault

    2. Faulty circuit breaker or fatigued fuse wire

    3. Unit may be short cycling due to faultythermostat

    NO

    No Hot Water

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    18/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    17

    Fault Finding Chart 1.1

    Note: Ensure you

    wait the full five

    minutes before

    progressing from

    this point.

    1.1

    Are the

    thermostat contacts

    closed?

    NO Replace thermostat.

    Test 2

    No Hot Water

    Is there

    240V at the

    control board &

    relay?

    Test 3 Wiring incorrect.

    Check control board wiring loom

    plug (lower thermostat to control

    board wiring loom).

    NO

    Test 4

    What is the

    status of the

    control boards

    LEDs five

    minutes after

    resetting?

    Replace control board.

    Red solid or Red and

    Green LEDs indicatingsimultaneously

    Green flashing

    Green solid

    No indication

    1.2

    Replace sensor strip.

    Replace control board (system

    should have been operating in

    boost mode after five minutes

    from resetting) then check

    system operation as a second

    fault may be present.

    YES

    Note: To reset heat

    pump switch power off,

    wait for 30 seconds

    then switch back on.

    Reset heat pump &

    wait five minutes

    before progressing

    from this point.

    Is the

    compressor

    running?

    Is the

    sensor strip

    working?

    NO

    YES

    Is the

    refrigeration

    system

    heating?

    YES

    NO

    YES

    NO

    To check if the refrigeration system is

    heating feel the braided flexible hose

    from the heat exchanger water outlet.

    What is the

    controller

    software

    version? HPV 3.1, HPV 3.2 or

    no HPV identification

    HPV 4.0 or higher

    Is

    sensor T3

    working?

    YES

    Replace sensor T3.NO

    Test 5

    System working ok. The element circuit should be

    checked as a temporary condition may have caused the

    appliance to enter boost mode. If in boost mode and the

    element circuit is not operational the cylinder water will

    be cold and the system cannot reset itself automatically.

    Replace control board.

    YES

    Is the

    evaporator fan

    operating?

    YES

    3.6NO

    1.2Red flashing

    Is

    the air flow

    obstructed?

    NO

    Remove obstruction or clean

    evaporator.YES

    Note: For more information on LED indication refer to pages 12 and13.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    19/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    18

    Component Tests 1, 2, 3 & 6

    Tests 1 Test 2

    240

    Warning Live equipment wearPersonal Protective Equipmentwhen conducting th is test.

    Using a multimeter on the AC voltagescale, measure between the terminals ofthe terminal block located behind theelement access cover. The followingmeasurements should be obtained:

    Active & Neutral 240 volts.Active & Earth 240 volts.Neutral & Earth 0 volts.

    Warning - Ensure power isisolated before conducting thistest.

    Using a multimeter on the ohms scale,measure between the terminals of themechanical thermostat. The followingresults should be obtained:

    1L & 2T 0 ohms.3L & 4L 0 ohms.

    Test 3 Test 6

    240

    240

    Warning Live equipment wearPersonal Protective Equipmentwhen conducting this test.

    Using a multimeter on the AC voltagescale, measure between the top 2 terminalsof the heat pump module terminal block.

    Normal voltage is 240 volts.

    Warning Live equipment wearPersonal Protective Equipmentwhen conducting th is test.

    Using a multimeter on the AC voltagescale, measure between the A return andNeutral terminals of the terminal blocklocated behind the element access cover.

    Normal voltage is 240 volts.

    Note:Refer to page 19 for component test 4 and page 20 for component test 5.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    20/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    19

    8.49

    Component Test 4

    Warning Live equipment wear Personal Protective Equipment whenconducting this test.

    Sensor Strip Testing:Unplug the sensor strip plug from the control board and using amultimeter on the kilo-ohms scale, measure between the pins of the sensor strip plug*.There are six individual tests to be performed as there are six individual sensors contained

    along the length of the sensor strip (sensors S0 S5). As the resistance of each sensorwill change according to its temperature, the resistance measurements for each sensor willneed to be checked against the Temperature/Resistance Table shown below. For thisreason it is best to empty the tank of hot water and then measure the cold watertemperature at the T&PR so a known temperature datum can then be applied to allsensors which should then in turn all have similar resistance value when tested.

    Sensor Test Points

    S0 Between Pins 1 and 9

    S1 Between Pins 2 and 9

    S2 Between Pins 4 and 9

    S3 Between Pins 6 and 9

    S4 Between Pins 3 and 8

    S5 Between Pins 3 and 10

    *Note: The sensor strip plug socket test points are quite small, Fine Probe Adapters (partnumber WH0020082) can be utilised as probe extensions. Alternatively small pins may beused however ensure good contact is made when testing.

    Sensor Strip Temperature / Resistance Table

    T (C) R (k) T (C) R (k) T (C) R (k) T (C) R (k) T (C) R (k)-10 37.45 10 15.45 30 7.037 50 3.485 70 1.853

    -9 35.73 11 14.82 31 6.782 51 3.371 71 1.799-8 34.11 12 14.22 32 6.537 52 3.262 72 1.743

    -7 32.56 13 13.65 33 6.302 53 3.157 73 1.695-6 31.10 14 13.10 34 6.076 54 3.055 74 1.646

    -5 29.71 15 12.58 35 5.86 55 2.957 75 1.589-4 28.39 16 12.09 36 5.653 56 2.863 76 1.552

    -3 27.13 17 11.61 37 5.454 57 2.773 77 1.508-2 25.94 18 11.16 38 5.264 58 2.686 78 1.465-1 24.81 19 10.72 39 5.081 59 2.602 79 1.424

    0 23.73 20 10.31 40 4.905 60 2.521 80 1.3841 22.71 21 9.913 41 4.736 61 2.442 81 1.3452 21.73 22 9.535 42 4.574 62 2.367 82 1.3073 20.81 23 9.173 43 4.418 63 2.295 83 1.271

    4 19.92 24 8.826 44 4.269 64 2.225 84 1.2365 19.09 25 8.495 45 4.125 65 2.157 85 1.202

    6 18.29 26 8.177 46 3.987 66 2.092 86 1.1697 17.52 27 7.873 47 3.854 67 2.029 87 1.1378 16.80 28 7.583 48 3.726 68 1.968 88 1.107

    9 16.11 29 7.304 49 3.603 69 1.91 89 1.077

    Sensor strip plugpin configuration

    Testing thesensor strip

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    21/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    20

    Component test 5

    T Sensor Testing:310 Series Heat Pumps have five independent thermistors which areutilised to monitor temperatures at various locations around the system. These thermistorsconnect to and are monitored by the control board and are known as T sensors.

    All five T sensors are identical and each can be tested as follows:

    Warning - Ensure power is isolated before conducting this test.

    Unplug the relevant T sensor from thecontrol board and remove the T sensorfrom its location so its temperature will bethe same as the ambient air temperature(As sensor T4 detects the ambient airtemperature it may remain in position forthis test). Using a multimeter on the kilo-ohms scale, measure between the two pins

    of the T sensor plug*. As the resistance ofeach sensor will change according to itstemperature, the resistance measurementsfor each sensor will need to be checkedagainst the Temperature/Resistance Tableshown below and the value then comparedto the ambient air temperature.

    *Note: The sensor strip plug socket test points are quite small, Fine Probe Adapters (partnumber WH0020082) can be utilised as probe extensions. Alternatively small pins may beused however ensure good contact is made when testing.

    Sensor Monitors Part NumberT0 Water temperature leaving the condenserT1 Water temperature entering the condenser

    T2 Evaporator temperatureT3 Compressor discharge temperatureT4 Ambient air temperature

    056006

    T Sensor Temperature / Resistance Table

    The table below sets out the resistance of the T sensors for a given water or air

    temperature.

    TemperatureDegrees C

    Resistance (All T Sensors)Kilo-ohms

    0 23.7310 15.4520 10.31

    30 7.03740 4.90550 3.485

    60 2.521

    70 1.85380 1.384

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    22/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    21

    Fault Finding - Chart 1.2

    1.2

    Is there

    240V at the

    element?

    NO

    Test 6

    No Hot Water

    Test 8

    YES

    YES

    Is there

    240V at the N/C

    relay contact?

    YES

    Is there

    6VDC at the relaycoil?

    NO

    YES

    NO

    Is the

    element resistancecorrect?

    NO

    Test 7

    Test 9

    Repair faulty wiring.Appliance operation should then

    be checked to determine why thesystem entered boost or limp

    mode as a second fault may bepresent.

    Replace element.Appliance operation should then

    be checked to determine why thesystem entered boost or limp

    mode as a second fault may bepresent.

    Replace relay.

    Appliance operation should thenbe checked to determine why thesystem entered boost or limp

    mode as a second fault may be

    present.

    Replace control board.

    Appliance operation should thenbe checked to determine why the

    system entered boost or limpmode as a second fault may be

    present.

    Repair faulty wiring between heatpump module electrical

    connection plug and element.Appliance operation should thenbe checked to determine why the

    system entered boost or limp

    mode as a second fault may bepresent.

    Note: all faults in this chart are in the boost or limp mode (element)

    circuit. After determining the fault in the element circuit the applianceoperation should then be checked to determine why the system

    entered boost or limp mode as a second fault may be present.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    23/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    22

    Component Tests 7, 8 & 9

    Tests 7 Test 8

    240

    Warning Live equipment wearPersonal Protective Equipment

    when conducting this test.Using a multimeter on the AC voltagescale, measure between the white wire onthe heat pump module electricalconnection plug and the top terminal of theheat pump module terminal block(Neutral).

    Normal voltage is 240 volts.

    Warning - Ensure power isisolated before conducting this

    test.Disconnect the element wires from thethermostat and terminal block, and using amultimeter on the ohms scale, measurebetween the two element wires. Thefollowing results should be obtained:

    2.4kW element: 22 26 ohms.3.6kW element: 15 17 ohms.

    Test 9

    Warning Live equipment wear Personal Protective Equipment whenconducting this test.

    Using a multimeter on the DC voltage scale, measure between the two wires on thecontrol board relay plug.

    Normal voltage is 6 Volts DC.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    24/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    23

    Fault Finding - Chart 2

    2

    YESRecommend a water heater ofsufficient capacity to meet the

    customers needs.

    Insufficient Hot Water

    NO

    Has the

    supply of hot water

    recently been

    depleted?

    Boost or limp mode may beindicated by any of the following

    LED conditions:Red solid or flashing.

    Red & green flashing together.

    No LED indication.Has the

    usage pattern

    changed

    recently? i.e. additional appliances

    or people using hot water

    Depending on the ambient

    temperature the water heater may

    take 3 to 5 hours to recover.

    Is theheater of sufficient

    size?

    NO

    Recommend a hot water usage

    pattern that will suit the water

    heater and the customers needs.

    YES

    Is the

    water supply pressuremore than 80% of the

    T&PR rating?

    Fit pressure limiting valve if not

    already installed.

    Existing pressure limiting valve

    faulty - replace.

    YESYES

    Is thecorrect T&PR

    valve fitted?

    NO

    NO

    YES

    Check for crossed water

    connection.

    Replace T&PR valve.

    Replace T&PR valve with one ofcorrect pressure rating.

    Do not use reconditioned T&PR

    valves.

    Are there

    any plumbing leaks,

    crossed connections or

    dripping taps?

    NO

    Repair any leaks.

    Isolate crossed connections.

    YES

    Is theheater operating

    in boost or limp

    mode?

    NO

    What is the

    controller

    software

    version?

    YES

    3

    4

    HPV 3.1, HPV 3.2 or

    no HPV identification

    HPV 4.0 or higher

    Is the

    T&PR valve

    continuously

    discharging

    water?

    YES

    NO

    Is theheater outlet water

    temperature> 58C

    Is atempering valve

    fitted?

    Arethe filtersblocked?

    NO

    Clean or replace filtersYES YES

    Is thetempering valve outlet

    water temperatureapprox 48C?

    NO

    NO

    Replace tempering valveNO

    YES

    System workingYES

    NO

    Is the

    sensor strip

    working?

    NO

    YES

    Replace sensor strip

    Test 4

    The heater outletwater temperature

    can be measured at

    the T&PR.

    Is the heater

    connected to anoff peak tariff?NO

    Off peak connection is unsuitablefor Heat Pump models. Connect

    to continuous tariff or off peak 2 ifavailable.

    YES

    Note: This assumes thatthe hot water to the

    tempering valve is above52C.

    Note: For more information on LED indication refer to pages 12 and 13.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    25/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    24

    Fault Finding - Chart 3

    3

    System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV

    identification

    What is the

    status of thecontrol boards

    LEDs?

    Replace control board.

    Red solid or Red and Green LEDs

    indicating simultaneously

    Red flashing

    Green solid

    Green flashing

    Test 4

    System working. Check operation.

    No LED Indication 3.1

    NO

    YES NO

    Are therelay, circulator,

    fan, sensor strip & Tsensors all firmly plugged

    into the correctsockets?

    YES

    Ensure plugs are firmly plugged

    into correct sockets on control

    board and that plug pins on

    control board are clean and free

    from conformal coating.

    NO

    Test 5

    Is the

    sensor stripworking?

    Replace sensor strip.

    Are all

    T sensors

    working?

    Replace faulty T sensor(s).

    Ensure water in heatpump is below 60C&

    reset heat pump. Toreset heat pump switchoff, wait for 30 seconds

    then switch back on.

    Does

    compressor

    successfully start

    after delay?

    Note: The compressor

    starts 30 seconds after

    the circulator.

    NO

    NO

    Is

    circulatoroperating?

    Does

    compressor try

    to start after

    delay?

    NO

    3.3

    3.4

    Circulator operation can be

    checked by feeling circulator

    brass body for vibration.

    Let heat pumprun for ten

    minutes or untilred LED flashes.

    Does

    red LED

    flash?

    YES

    Red LED will flash if

    system enters boost

    mode.

    8.3

    Has

    compressor

    recently beenoperating?

    YES

    Compressor internal OTCmay have opened.

    Switch off power to heatpump, wait for ten

    minutes then switchpower back on.

    YES

    NO

    3.5YES

    System working. Ambient air

    temperature may have been too high or

    low for normal operation. Heat pump

    may have been too hot after operating

    for an extended period due to large

    volumes and/or frequent water usage.

    NO

    YES

    YES

    LED

    Status

    after5

    seconds

    Green - flashing

    Red solid or flashing / Red and Green

    indicating simultaneously / Green solidReplace control board.

    3.2Red - flashing

    3.8

    Note: Refer to page 5 for T sensor plug socket location on control board.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    26/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    25

    Fault Finding Chart 3.1

    3.1

    Are the

    thermostat contactsclosed?

    YESRepair faulty wiring.

    Replace control board.

    Test 2

    System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV

    identification

    NO

    System has operated in limp mode

    due to a faulty sensor strip (S1 & S4

    faults) and has completed a heatingcycle. Water was heated by the

    electric element and controlled bythe Robertshaw thermostat to 70C.

    Replace sensor strip.

    Is the

    sensor strip

    working?

    NO

    Replace control board.

    YES

    Test 4

    Are thesensor strip plug

    pins clean?

    Ensure sensor strip plug pins andcontrol board socket are clean

    and free from conformal coating.

    NO

    YES

    Fault Finding Chart 3.2

    3.2

    T0 is monitoring

    water out of the

    heat exchanger

    Switch off heat pump &allow sensor T0 to cool

    below 80C. Whensufficiently cool switchheat pump back on.

    Is redLED flashing after

    5 seconds?

    Replace control board

    YES

    Is

    Green LEDflashing?

    NO

    YES

    Circulator operation can bechecked by feeling circulator

    brass body for vibration.

    NO

    Hassensor T0 cooled

    to below80C?

    YES

    NO

    Is circulator

    operating?3.3NO

    3.8YES

    Replace control board

    System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV

    identification

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    27/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    26

    Fault Finding Chart 3.3

    3.3

    Ensure circulator is firmly plugged

    into correct socket on control

    board and that plug pins on

    control board are clean and free

    from conformal coating.

    NO

    YES

    Is the

    circulator motor

    resistance

    correct?

    Is 240V

    present at the

    circulator?

    Test 10 Is the

    circulator plug firmly

    plugged into correctsocket?

    NO

    Check circulator impellor for

    restriction or siezure.

    YES

    Replace circulator

    YES

    NO

    Test 11

    Replace control board

    System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV

    identification

    Component Tests 10 & 11

    Test 10 Test 11

    Warning Live equipment wear

    Personal Protective Equipmentwhen conducting this test.

    Using a multimeter on the AC voltagescale, measure between the circulatorplug terminals at the control board.

    Normal voltage is 240 volts.

    Note: As the control board controls thespeed of the circulator by pulsing theelectrical supply to the circulator ananalogue multimeter may indicatebetween 180 240V.

    Warning - Ensure power is

    isolated before conducting thistest.

    Unplug the circulator connection plug fromthe control board and using a multimeter onthe ohms scale, measure between the twocirculator connection plug terminals.

    A reading of approximately 75.3 ohmsshould be obtained.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    28/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    27

    Fault Finding Chart 3.4

    3.4

    Is 240V

    present at the

    compressor

    terminals?

    NO Faulty compressor wiring.

    YES

    Are

    the compressor

    winding resistances

    correct?

    Test 12

    Replace compressor

    NO

    Faulty compressor and/orcompressor capacitor wiring.

    YES

    Note: Tests 12 & 13 must be

    performed after waiting for the 30second delay after starting of the

    circulator and cannot be performed

    whilst the red LED is flashing.

    Test 14

    Is the

    compressor

    capacitor

    working?

    Replace compressor capacitorNO

    YES

    Is 240V

    present at the control

    board compressor

    terminals?

    YES

    Test 15

    Test 13

    Replace control boardNO

    Is there

    6VDC at the relay

    coil?

    Is the

    relay plug pluggedinto the control

    board?

    NO

    YES

    Plug in relay plug at control board.NO

    Ensure plug pins are clean of

    conformal coating and are making

    contact. If plug & pins are ok

    replace the control board.

    YES

    Test 9

    System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV

    identification

    Are

    the compressor

    winding resistancescorrect?

    Compressor internal ECOmay have tripped open

    circuiting the compressor

    windings. Wait ten

    minutes for ECO to cool

    and auto reset.

    NO

    Is the

    compressortemperature 150C

    or hotter?

    Reset heat pump and run

    system until compressor

    ECO trips again.

    YES

    Test 14

    8.3YES

    NO

    Note: To reset heat

    pump switch power off,

    wait for 30 seconds

    then switch back on.

    Note: Compressor internalECO is auto trip & auto

    reset & is not a replaceable

    component.

    ECO Opens @ 150C

    ECO Closes @ 90C

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    29/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    28

    Component Tests 12 15

    Tests 12 Test 13

    Warning Live equipment wearPersonal Protective Equipment

    when conducting th is test.

    Remove the compressor electrical accesscover and using a multimeter on the ACvoltage scale, measure between the redand blue wires.

    Normal voltage is 240 volts.

    Warning Live equipment wearPersonal Protective Equipment

    when conducting this test.

    Using a multimeter on the AC voltagescale, measure between the control boardcompressor output terminal and the topterminal of the heat pump module terminalblock (Neutral).

    Normal voltage is 240 volts.

    Test 14 Test 15

    Warning - Ensure power isisolated before conducting thistest.

    Remove the compressor electrical accesscover and mark and disconnect terminalwiring. Using a multimeter on the ohmsscale, measure between the compressorterminals. The following run and startwinding results should be obtained.

    (Run) Red & Blue terminals 2.2 ohms(Start) Red & Black terminals 3.2 ohms

    Warning - Ensure power isisolated before conducting thistest.

    Disconnect the wiring to the compressorcapacitor and using a multimeter on thecapacitance (F) scale measure betweenthe two capacitor terminals.

    Normal capacitance is 35 micro Farads(35F).

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    30/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    29

    Fault Finding Chart 3.5

    3.5

    Is the

    temperature atsensor T4< 2C?

    System functioning correctly andshould operate in boost mode

    until temperature at T4 risesabove 2C at which time the heat

    pump will reset and start back at

    sequence 0.

    YES

    T4 is ambientair sensor

    Is thetemperature at

    sensor T2< 2C?

    NO

    3.6YES

    T2 is evaporator

    sensor Is theambient air

    temperature 60C in seq 0)Green 2 flash - Heat pump operating in sequence 2

    Green 3 flash - Heat pump operating in sequence 3

    Green 4 flash - Heat pump operating in sequence 4

    Other LED indication:If no fault is present the Green LED

    will flash to indicate the following:

    4.1Red solidRed solid or flashing.

    Red & Green flashing simultaneously.

    No LED indication.

    For other LED indication refer to notes

    below.

    For more information on LED indication refer to pages 12 and13.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    34/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    33

    Fault Finding Chart 4.1

    4.1

    Is

    sensor T4firmly plugged

    into correctsocket?

    NO

    Ensure sensor T4 is firmly

    plugged into correct socket oncontrol board and that plug pins

    on control board are clean andfree from conformal coating.

    Red solid

    T4 < 0C

    YES

    Is thetemperature atsensor T4

    < 2C?

    NO

    YES

    Issensor T4

    working?

    Test 5

    Replace sensor T4NO

    Replace control boardYES

    T4 is ambient

    air sensor

    Note: When T4 < -0C the system will enter boost mode. When in boost mode dueto this operation the system will reset and start at sequence 0 when T4 > 2C

    System functioning correctly and

    should operate in boost modeuntil temperature at T4 rises

    above 2C at which time the heatpump will reset and start back at

    sequence 0.

    Note: Refer to page 5 for T sensor plug socket location on control board.

    Fault Finding Chart 4.2

    4.2

    Is thesensor strip

    working?

    NO

    Red 1 flash

    sensor strip fault

    Is thesensor strip

    firmly pluggedinto the correct

    socket?

    YES

    NO

    Test 4

    Replace control boardYES

    Ensure sensor strip is firmly

    plugged into correct socket oncontrol board and that plug pinson control board are clean and

    free from conformal coating.

    Replace sensor strip

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    35/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    34

    Fault Finding Chart 4.3

    4.3

    NO

    Red 2 flashT0 >80C

    YES

    YES

    NO

    Test 5

    T0 is monitoring

    water out of the

    heat exchangerIs

    sensor T0

    firmly pluggedinto correct

    socket?

    Is

    sensor T0

    working?

    Replace sensor T0

    Switch off heat pump &allow sensor T0 to cool

    below 80C. Whensufficiently cool switchheat pump back on.

    Does red

    LED immediately

    go to 2 flash?

    Replace control board

    YES

    Is circulator

    operating?

    NO

    Blockage of water system atcirculator, heat exchanger,

    dropper tubes or flexible hoses.

    Loose, damaged or jammed

    circulator impellor.

    YES

    Circulator operation can be

    checked by feeling circulatorbrass body for vibration.

    NO

    Ensure circulator is firmly pluggedinto correct socket on control

    board and that plug pins on

    control board are clean and free

    from conformal coating.

    NO

    YES

    Is the

    circulator motor

    resistance

    correct?

    Is 240V

    present at the

    circulator?

    Test 10 Is the

    circulator plug firmly

    plugged into correct

    socket?

    NO

    Check for loose, damaged or

    jammed circulator impellor.

    YES

    Replace circulator

    YES

    NO

    Test 11

    Hassensor T0 cooled

    to below80C?

    YES

    NO

    Replace control board

    Ensure sensor T0 is firmly

    plugged into correct socket on

    control board and that plug pinson control board are clean and

    free from conformal coating.

    Is there

    an air lock in the

    water system?

    NO

    Bleed air from water outlet at

    flexible hose union.YES

    Warning! Ensure water escaping

    from flexible hose is caught in a

    container and does not escape or

    sensor strip damage may occur.

    Note: Refer to page 5 for T sensor plug socket location on control board.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    36/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    35

    Fault Finding Chart 4.4

    4.4

    Is

    sensor T2firmly plugged

    into correctsocket?

    NO

    Ensure sensor T2 is firmly

    plugged into correct socket oncontrol board and that plug pins

    on control board are clean andfree from conformal coating.

    Red 3 flash

    T2 < -3C

    Is thetemperature atsensor T2

    < 2C?

    NO

    Issensor T2

    working?

    Test 5

    Replace sensor T2NO

    Replace control boardYES

    T2 is evaporatorsensor

    System functioning correctly andshould operate in boost mode

    until evaporator temperature rises

    above 2C at which time the heatpump will reset and start back at

    sequence 0.

    Did the

    system reset &operate in normal

    heat pumpmode?

    Is theambient air

    temperature 2C

    Is

    the air flowobstructed?

    NO

    Remove obstruction.YES

    YES

    Clean dirty evaporator.

    Appliance installed in enclosedroom contrary to installation

    instructions. Appliance is suitablefor outdoor installation only.

    Raise temperature of sensor T2 to

    above 2C by removing fromevaporator and holding probe between

    thumb & fingers. Heat pump shouldauto reset to sequence 0 when T2raises above 2C. Ensure sensor

    probe is reinserted into evaporator on

    completion of testing procedure.

    Note: Refer to page 5 for T sensor plug socket location on control board.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    37/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    36

    Fault Finding Chart 4.5

    4.5

    Is 240V

    present at the

    compressor

    terminals?

    NO Faulty compressor wiring.

    Red 4 flash

    T3 is not > T4 +

    15C in sequence 3

    YES

    Does

    compressor start

    or try to start after

    delay?

    YES

    Are

    the compressor

    winding resistances

    correct?

    Test 12

    Replace compressorNO

    Faulty compressor and/or

    compressor capacitor wiring.

    YES

    Note: T3 is compressor discharge sensor. T4 is ambient air sensor. This check is performed in sequence 3 to

    ensure that the sealed refrigerant system is operating (heating).

    8

    Are

    sensors T3 & T4

    firmly plugged into

    the correct

    sockets?

    Ensure sensors T3 & T4 are firmly

    plugged into correct sockets on

    control board and that plug pins

    on control board are clean and

    free from conformal coating.

    NO

    Note: Tests 12 & 13 must be

    performed after waiting for the 30

    second delay after starting of the

    circulator and cannot be performed

    whilst the red LED is flashing.

    Test 14

    NO

    Is the

    compressor

    capacitor

    working?

    Replace compressor capacitorNO

    Note: The compressor starts 30

    seconds after the circulator.

    YES

    Are

    sensors T3 & T4

    working?

    Replace faulty sensor(s)NO

    Ensure water in heatpump is below 60C &reset heat pump. Toreset heat pump switch

    off, wait for 30 secondsthen switch back on.

    YES

    Does red

    LED immediately

    go to 4 flash?

    NO

    YES

    Is 240V

    present at the control

    board compressor

    terminals?

    YES

    Test 15

    Test 13

    Test 5

    Replace control boardNO

    Replace control board

    Is there

    6VDC at the relay

    coil?

    Is the

    relay plug plugged

    in to the control

    board?

    NO

    YES

    Plug in relay plug at control board.NO

    Ensure plug pins are clean of

    conformal coating and are makingcontact. If plug & pins are ok

    replace the control board.

    YES

    Test 9

    YES

    Note: Refer to page 5 for T sensor plug socket location on control board.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    38/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    37

    Fault Finding Chart 4.6

    4.6

    Is 240V

    present at the

    compressor

    terminals?

    NO Faulty compressor wiring.

    YES

    Does

    compressor start

    or try to start after

    delay?

    NO

    YES

    Are

    the compressor

    winding resistancescorrect?

    Test 12

    Replace compressorNO

    Faulty compressor and/or

    compressor capacitor wiring.

    YES

    8

    Are

    sensors T0 & T1

    firmly plugged into

    the correct

    sockets?

    Ensure sensors T0 & T1 are

    plugged into correct sockets on

    control board and that plug pins

    on control board are clean and

    free from conformal coating.

    NO

    Note: Tests 12 & 13 must be

    performed after waiting for the 30

    second delay after starting of the

    circulator and cannot be performed

    whilst the red LED is flashing.

    Test 14

    Is the

    compressor

    capacitor

    working?

    Replace compressor capacitorNO

    Note: The

    compressor starts 30

    seconds after the

    circulator.

    YES

    Are

    sensors T0 & T1

    working?

    YES

    Replace faulty sensor(s)NO

    Ensure water in heatpump is below 60C &reset heat pump. Toreset heat pump switch

    off, wait for 30 secondsthen switch back on.

    YES

    Does red

    LED immediately

    go to 5 flash?

    NO

    YES

    Is 240V

    present at the control

    board compressor

    terminals?

    YES

    Test 15

    Test 13

    Test 5

    Replace control boardNO

    Replace control board

    Red 5 flashT0 - T1 < 8Cin

    sequence 4

    Note: T0 is heat exchanger water outlet sensor. T1

    is heat exchanger water inlet sensor. This check is

    performed in sequence 4 to ensure that the sealed

    refrigerant system is operating (heating).

    Note: Refer to page 5 for T sensor plug socket location on control board.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    39/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    38

    Fault Finding Chart 4.7

    4.7

    Is thesensor strip & sensor

    T1 firmly plugged intothe correct

    sockets?

    Ensure sensor strip & sensor T1

    are both firmly plugged into the

    correct sockets on control boardand that plug pins on control

    board are clean and free from

    conformal coating.

    NO

    YES

    Is

    sensor T1working?

    Replace sensor T1NO

    YES

    Test 5

    Replace cold water dropper tube.

    Red 6 flashT1 > S4 + 7Cinsequence 3 or 4

    Note: T1 is heat exchanger water inlet sensor. S4 is thermistor sensor strip sensor.

    This check is performed in sequence 3 or 4 to ensure that the circulator is operating.

    Is

    sensor stripworking?

    YES

    Replace sensor stripNO

    Is thecirculator water

    flow directioncorrect?

    YES

    NOReinstall circulator so as flow is

    directed towards heat exchanger.

    Has thecold water dropper

    tube fallen off?

    YES

    Replace control board.NO

    Test 4

    Is there

    an air lock

    in the watersystem?

    Bleed air from water system at

    water outlet flexible hose union.YES

    NO

    Warning! Ensure water escaping

    from flexible hose is caught in a

    container and does not escape or

    sensor strip damage may occur.

    Note: Refer to page 5 for T sensor plug socket location on control board.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    40/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    39

    Fault Finding Chart 4.8

    4.8

    NO

    YES

    System working ok. Ambient air

    temperature too hot for normal

    heat pump operation.

    YES

    Test 5

    Appliance may have been

    operating for an extended period

    due to large volume and/or

    frequent water usage.

    Red 7 flashT3 > 110Cin

    sequence 3 or 4

    Note: T3 is compressor

    discharge sensor.

    NO

    YES

    Is

    sensor T3firmly plugged

    into correct

    socket?

    YES

    NO

    NO

    Test 19

    Ensure sensor T3 is firmly

    plugged into the correct socket oncontrol board and that plug pins

    on control board are clean and

    free from conformal coating.

    Replace sensor T3

    Is

    sensor T3

    working?

    Isthe ambient air

    temperature above50C?

    8.2

    Fit pressure gauge to

    high side of

    refrigerant system

    Is the

    head pressure

    excessive?

    Hassensor T3 cooled

    to below60C?

    Switch off heat pump &allow sensor T3 to cool

    below 60C. Whensufficiently cool switchheat pump back on.

    NO

    YES

    Note: Refer to page 5 for T sensor plug socket location on control board.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    41/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    40

    Fault Finding Charts 4.9 to 4.13

    4.9

    NO

    T sensor fault

    YES

    NO

    Test 5

    Is

    T sensorfirmly plugged

    into correct

    socket?

    Replace T sensor.

    Ensure T sensor is firmly plugged

    into correct socket on controlboard and that plug pins on

    control board are clean and free

    from conformal coating.

    4.10 4.11 4.12 4.13

    Replace control board.

    IsT sensor

    working?

    T0 fault.

    T0 is monitoringwater out of the

    heat exchanger.

    T1 fault.

    T1 is monitoringwater into the

    heat exchanger.

    T2 fault.

    T2 is monitoringthe evaporator

    temperature.

    T3 fault.

    T3 is monitoringthe compressor

    discharge temp.

    T4 fault.

    T4 is monitoringthe ambient air

    temperature.

    YES

    Note: Refer to page 5 for T sensor plug socket location on control board.

    Fault Finding Chart 4.14

    4.14

    Are the

    thermostat contactsclosed?

    YESRepair faulty wiring.

    Replace control board.

    Test 2

    System in boost or limp mode - Software version 4.0 or higher

    NO

    System has operated in limp modedue to a faulty sensor strip (S1 & S4

    faults) and has completed a heatingcycle. Water was heated by the

    electric element and controlled by

    the Robertshaw thermostat to 70C.

    Replace sensor strip.Is the

    sensor strip

    working?

    NO

    Replace control board.

    YES

    Test 4

    Are thesensor strip plug

    pins clean?

    Ensure sensor strip plug pins andcontrol board socket are clean

    and free from conformal coating.

    NO

    YES

    Is there

    240V at thecontrol board &

    relay?

    YES

    Wiring incorrect.

    Check control board wiring loomplug (lower thermostat to control

    board wiring loom).

    NO

    Test 3

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    42/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    41

    Fault Finding Chart 5

    5

    Isthe T&PR

    valve continuouslydischarging

    water?

    Existing pressure limiting valve

    faulty.Fit pressure limiting valve if not

    already fitted.

    Replace T&PR valve if required.

    Is theleak from the

    electrical accesscover?

    NO

    YES

    NO

    Is theleak from

    the element barrelfitting?

    YESCheck for loose element bolts.Remove element and replace

    gasket.

    YES

    NO

    Remove anode and repair leakusing Teflon thread tape.YES

    Is the

    correct T&PR valvefitted?

    Replace T&PR valve with one ofthe correct pressure rating.

    Do NOT use reconditioned

    T&PR valves.

    NO

    Check for crossed waterconnection.

    Replace T&PR valve.

    YES

    Is thewater supply

    pressure above800kPa?

    YES

    NO

    Isthe water leak

    intermittent?

    NO

    Leak is probably condensatedraining from the evaporatorcondensate tray.

    Normal Operation.

    YES

    Arethe anode/s

    leaking?

    Inner Cylinder leakingCheck for hot spots on the jacket

    Replace water heater.

    NO

    Isthe leak from theheat pump water

    system?

    NO

    Tighten or remake flexible hose

    connection(s).

    Repair or replace leaking heatexchanger.

    Replace leaking circulator.

    Remake or replace dropper tubeconnections.

    YES

    Leaking water heater

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    43/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    42

    Fault Finding Chart 6

    6

    Fan loose on motor shaft, remove

    assembly and tighten.Fan motor faulty - Replace.

    Is the

    noise water

    hammer?

    NO

    NO

    Is thenoise only evident

    when water is flowing

    through the

    heater?

    YES

    Cylinder contracting due to pressure

    release when hot tap opened.

    This can also be accompanied by a

    creaking or cracking sound.

    Normal Operation.

    NO

    Check for restrictions in pipe work, faulty

    valves, loose plumbing or other

    appliances i.e. washing machine or

    dishwasher.

    Fit 600kPa pressure limiting valve.

    YES

    Is

    the noise

    mechanical or air

    related?

    Normal noise level during operation is

    approximately 52dB at 1.5 metres.

    If this level is affecting neighbors a timer

    should be fitted to prevent operation

    during the affected hours or to comply

    with local council regulations

    AIR

    Is the

    noise from the

    evaporator

    fan?

    Is the

    noise only evident

    during the heating

    cycle?

    Check for loose fittings or pipe work in

    the refrigeration system.

    Check for possible mechanical failure in

    compressor

    YES

    Is the

    water pressuremore than 80% of the

    T&PR valve

    rating?

    Check all other appliances or valves that

    can generate noise i.e. washing

    machines, dishwashers, ball valves etc.

    NO

    YES

    Mechanical

    Refer to water hammer causes in the

    Common Complaints section.

    Check for a faulty stop cock, non-return

    valve or T&PR valve.NO

    Is the

    noise a

    metallic popping

    sound?

    YES

    NO

    YES

    Noisy water heater

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    44/68

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    45/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    44

    Fault Finding Chart 8 - 8.3

    8.3

    Replace compressor.

    Test 19

    Refrigeration system fault finding

    Is the

    head pressure

    excessive?

    Test 21

    NO

    Fit pressure gauge

    to high side of

    refrigerant system.

    Allow time for the

    system to equalise.

    Did

    the system

    equalise?

    Is the system

    taking too long to

    equalise?

    Possible restriction in system,

    Locate and repair.

    Possible system overcharge,

    adjust refrigerant charge.

    TX valve metering incorrectly,

    adjust or replace TX valve.

    NO

    YES

    Is theTX valve

    operating?

    NO

    Locate blockage in refrigerant

    system and repair.

    YES

    Adjust TX valve (refer to

    component replacement

    procedure 23 TX valve

    adjustment) or replace if faulty.

    NO

    System overcharged, adjust

    refrigerant charge.YES

    YES

    8.28

    Fit pressure gauges

    to high and low side

    of refrigerant system.

    Is the

    Suction pressure

    low/vacuum or

    excessively

    high?

    Test 20Locate and repair leak in

    refrigerant system.

    High side head pressure excessive (Test 18)

    YES

    High

    Low

    NO

    8.1

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    46/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    45

    Component Test 19

    Warning Live equipment. Wear Personal Protective Equipment whenconducting this test.

    1800 kPa

    Fit gauges to the high side access pipeand observe the discharge pressure.

    Typical high pressure range is 1400-2100 kPa depending on cylinder watertemperature. The high pressure rangeshould be within 1700-1800 kPa whenheating from cold.

    Component Test 20

    Warning Live equipment. Wear Personal Protective Equipment whenconducting this test.

    400 kPa

    Check for persistent air bubbles throughsight glass of receiver/filter drier. Fitgauges to the low side access pipe and

    observe the suction pressure.

    The suction (low side) pressure is verydependent on ambient conditionshowever the low pressure range istypically between 200-600 kPa.

    200 kPa @ 10C ambient.600 kPa @ 45C ambient.

    A suction pressure of less than 200kPamay indicate a refrigerant leak or a

    malfunctioning TX valve.

    Note: Refer to the following section formore information on refrigerant chargeand refrigerant charge fault indications.

    Refrigerant Charge

    Indication of correct refrigerant chargeThe receiver/filter dryer sight glass should show clear liquid, a few small bubbles might bevisible during initial start up of the system or when the TX valve opens quickly, howeverclear liquid should return shortly after. Compressor current draw should be between 5 6

    Amps and system pressures should be within normal ranges (refer to component test 19(above) and component test 20 (above) for typical system pressures).

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    47/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    46

    Indication of undercharged systemBubbles persist for a significant amount of time or repeat often. Compressor current drawis low (6 Amps) and compressor noisy. Note:Unusual currentdraw or high head pressure can be a sign of other problems such as a blockage ormalfunctioning TX valve.

    Component Test 21

    Warning Live equipment. Wear Personal Protective Equipment whenconducting this test.

    Fit gauges to low side access pipe.

    Remove the insulation from the TX valvesensor on the suction line.

    Hold the sensor by hand to increase theheat detected by the sensor. The TXvalve should open with the followingresults:

    1. Flow of refrigerant through sight glassof receiver/filter dryer should increase.

    2. Evaporator pressure should increase.3. Suction line should become cooler.

    Remove hand and replace insulation, theTX valve should close, resulting in thereversal of the above results.

    Electrical Insulation Testing

    There are three basic test procedures that should be carried out when the operation andfunction of a heat pump water heaters electrical system is in doubt.

    Wear Personal Protective Equipment when conducting step 1 of thisprocedure to reduce the risk of electric shock. Refer to Rheem safety

    procedure on electrical testing.Insulation resistance of the water heater Neutral Circuit. (Reading not to be below0.66 Mega ohm).

    1. Isolate power to the water heater at the isolation swi tch. Confirm with multi-meter across terminal block Active and Neutral, then Active and Earth , thenNeutral and Earth that vol tage is not present.

    2. Once satisfied, disconnect the Active and Neutral wires from the water heater terminalblock.

    3. Connect megger leads to the Neutral of the water heater wiring and Earth.

    4. Operate megger. A reading above 0.66 Mega ohm should be obtained.

    5. If a reading below 0.66 Mega ohm is indicated, all component parts will need to beindividually tested to locate the fault. Refer to Fault Finding Chart 7 on page 43.

  • 8/10/2019 TM025 Rheem 310 Series Heat Pump REV B.pdf

    48/68

    TM025 Rheem Heat Pump Service Instructions REV: BDate of Issue: 02/08/07

    This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed uncontrolled.

    47

    Insulation resistance of the water heater Active Circuit (reading not to be below 0.66mega-ohm).

    6. Connect megger leads to the Active of the water heater wiring and Earth.

    7. Operate megger. A reading above 0.66 Mega ohm should be obtained.

    8. If a reading below 0.66 Mega ohm is indicated, all component parts will need to be

    individually tested to locate the fault. Refer to Fault Finding Chart 7 on page 43.

    To check Continuity of the Heat Pump electrical circuit.

    9. Set megger to resistance scale or multimeter to x1 resistance scale.

    10. Measure between the Active and Neutral terminals on the power supply terminal blocklocated behind the electrical/element access cover. The resistance should beapproximately 24 ohms. If a reading outside this resistance is measured all electricalcomponent parts will need to be individually tested to locate the fault. Refer toSpecifications table on page 3 for indicative resistance values of components.

    11. Reconnect active cable