4301 Wilson Blvd. Arlington, VA 22203-1860 tel: 703.907.5500 www.nreca.coop To: SUNDA Project Cooperatives Dated: November 29, 2016 Re: Reference Block Design for Utility Scale PV Solar System Purpose: Provide a reference PV system block design with simple, convenient features, which is intended to reduce field time and provide for monitoring features. This is a reference design and will need to be adjusted for the particulars of a field site, including electrical string length (based on minimum site temperatures), climatic conditions (such as wind and snow loads), row spacing (based on latitude), land contours, shading, and others. Typical engineering time for such adjustment is intended to be, and historically has been, about 100 hrs for site specific modifications. What’s included: a cover sheet that provides a drawing sheet list, site plans (layouts, trenching and grounding), single line diagrams, schedules, labels, partial plans for inverter pad/mounting, conduit details and stringing plans for arrays. Design Criteria and Attributes used in creating this design: Maximize ground coverage ratio, expandable symmetric block Efficient design, allowing for most of the array construction to be duplicated Combiner box locations optimized to reduce DC conductors, avoiding jumpers or other pull boxes in unusual locations Equipment pad centrally located, driving reduced feeder cost Access roads can be on either side Grounding and Surge Protection: metallic array parts, pad halo grounding, fence grounding, surge arrestors in gear MV switch is used as site AC disconnect, reduces pad footprint Racking system is ETL listed for grounding, reducing significant bonding requirements and on-site labor Racking has integrated wire management Racking design is very modular, fast to install and accessible height good for install AC Switchgear contains the AC bus, the step down transformer for local 120V power and the revenue meter for DAS Electrical equipment pad is conveniently accessible. Designed to provide easy service access, minimize concrete, optimize feeder stub ups Expandability and flexible re-design options to meet site specific issues Monitoring tool needs to be able to: o Provide system overview, historical output and on-site weather data o Public view website to view performance and track environmental offsets online or on any internet device o Assist remote troubleshooting o Optional features: cell-modem, online storage of data, historical data exports, monthly reporting, alarms, curtailment, fault codes and sensors (horizontal/plane of array pyranometers, wind speed/direction, humidity, ambient temp, cell temp, revenue grade meters, load or bus kw meters)

Upload: others

Post on 09-Sep-2019

0 views

Category:

Documents


0 download

TRANSCRIPT

4301 Wilson Blvd. • Arlington, VA 22203-1860 • tel: 703.907.5500 • www.nreca.coop

To: SUNDA Project Cooperatives

Dated: November 29, 2016

Re: Reference Block Design for Utility Scale PV Solar System

Purpose: Provide a reference PV system block design with simple, convenient features, which is intended to reduce field time and provide for monitoring features. This is a reference design and will need to be adjusted for the particulars of a field site, including electrical string length (based on minimum site temperatures), climatic conditions (such as wind and snow loads), row spacing (based on latitude), land contours, shading, and others. Typical engineering time for such adjustment is intended to be, and historically has been, about 100 hrs for site specific modifications.

What’s included: a cover sheet that provides a drawing sheet list, site plans (layouts, trenching and grounding), single line diagrams, schedules, labels, partial plans for inverter pad/mounting, conduit details and stringing plans for arrays.

Design Criteria and Attributes used in creating this design: • Maximize ground coverage ratio, expandable symmetric block • Efficient design, allowing for most of the array construction to be duplicated • Combiner box locations optimized to reduce DC conductors, avoiding jumpers or other pull boxes in

unusual locations • Equipment pad centrally located, driving reduced feeder cost • Access roads can be on either side • Grounding and Surge Protection: metallic array parts, pad halo grounding, fence grounding, surge

arrestors in gear • MV switch is used as site AC disconnect, reduces pad footprint • Racking system is ETL listed for grounding, reducing significant bonding requirements and on-site

labor • Racking has integrated wire management • Racking design is very modular, fast to install and accessible height good for install • AC Switchgear contains the AC bus, the step down transformer for local 120V power and the revenue

meter for DAS • Electrical equipment pad is conveniently accessible. Designed to provide easy service access,

minimize concrete, optimize feeder stub ups • Expandability and flexible re-design options to meet site specific issues • Monitoring tool needs to be able to:

o Provide system overview, historical output and on-site weather data o Public view website to view performance and track environmental offsets online or on any

internet device o Assist remote troubleshooting o Optional features: cell-modem, online storage of data, historical data exports, monthly

reporting, alarms, curtailment, fault codes and sensors (horizontal/plane of array pyranometers, wind speed/direction, humidity, ambient temp, cell temp, revenue grade meters, load or bus kw meters)

DISCLAIMER While significant effort has been made to incorporate all applicable standards and ensure good engineering and correct practice in the development of this design, and this design has been used to develop actual field deployed, utility-scale, solar PV systems, no warranty or guaranty is made on this design for its fitness, suitability, safety or applicability for any purpose. Utilities must employ a trained engineer to interpret and adjust this reference design for the specific requirements of their application.

NRECA intends for the Materials contained in this design to be useful. These Materials may, however, contain technical inaccuracies, typographical errors or other mistakes. NRECA may make corrections or other changes to these Materials at any time. NRECA and its suppliers reserve the right to make corrections, modifications, enhancements, improvements and other changes to its design, programs and services at any time without notice.

THE MATERIALS IN THIS DESIGN ARE PROVIDED "AS IS". NRECA DISCLAIMS ALL WARRANTIES AND CONDITIONS WITH REGARD TO THESE MATERIALS, INCLUDING BUT NOT LIMITED TO, ALL IMPLIED WARRANTIES AND CONDITIONS OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, TITLE AND NONINFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHT.

YOU ACKNOWLEDGE AND AGREE THAT THE APPLICATION NOTES, REFERENCE DESIGNS AND OTHER SUCH DESIGN MATERIALS INCLUDED HEREIN ARE PROVIDED AS AN EXAMPLE ONLY AND THAT YOU WILL EXERCISE YOUR OWN INDEPENDENT ANALYSIS AND JUDGMENT IN YOUR USE OF THESE MATERIALS. NRECA ASSUMES NO LIABILITY FOR YOUR USE OF THESE MATERIALS OR YOUR PRODUCT DESIGNS OR ANY APPLICATION OR APPLICATION ASSISTANCE PROVIDED BY NRECA.

NRECA DOES NOT WARRANT OR REPRESENT THAT ANY LICENSE, EITHER EXPRESS OR IMPLIED, IS GRANTED UNDER ANY PATENT RIGHT, COPYRIGHT, MASK WORK RIGHT, OR OTHER INTELLECTUAL PROPERTY RIGHT OF NRECA COVERING OR RELATING TO THESE MATERIALS OR ANY COMBINATION, MACHINE, OR PROCESS TO WHICH THESE MATERIALS RELATE OR WITH WHICH THESE MATERIALS MAY BE USED.

IN NO EVENT SHALL NRECA BE LIABLE FOR ANY INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR ANY DAMAGES WHATSOEVER, INCLUDING BUT NOT LIMITED TO, DAMAGES RESULTING FROM LOSS OF USE, DATA OR PROFITS, WHETHER IN AN ACTION OF CONTRACT, NEGLIGENCE OR OTHER TORTIOUS ACTION RESULTING FROM USE OF THIS MATERIAL OR ARISING OUT OF THE USE OR PERFORMANCE OF THE DESIGN, REGARDLESS OF WHETHER NRECA OR AN AUTHORIZED NRECA REPRESENTATIVE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.

COVE

R SH

EET

PV0.1

SYSTEM SUMMARY

SHEET LIST

SITE MAP

SUNDA REFERENCE DESIGN1,000KWac, 1,000VdcSINGLE AXIS TRACKER

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

ELECTRICALPV0.1 COVER SHEETPV0.2 GENERAL NOTES AND SYMBOLSPV1.0 SINGLE LINE DIAGRAMPV1.1 PV SCHEDULESPV1.2 PV SCHEDULESPV1.3 PV LABELSPV2.0 SITE PLAN - ARRAY LAYOUTPV2.1 SITE PLAN - FENCE LAYOUTPV2.2 SITE PLAN - MEDIUM VOLTAGE ROUTINGPV2.3 SITE PLAN - INVERTER LAYOUTPV2.4 SITE PLAN - DC FEEDER ROUTINGPV2.5 SITE PLAN - AC FEEDER ROUTINGPV2.6 SITE PLAN - COMMUNICATIONS FEEDER ROUTINGPV2.7 SITE PLAN - GROUNDINGPV3.0 PARTIAL PLAN - STRINGING LAYOUT PV_APV3.1 PARTIAL PLAN - STRINGING LAYOUT PV_BPV3.2 PARTIAL PLAN - STRINGING LAYOUT PV_CPV3.3 PARTIAL PLAN - STRINGING LAYOUT PV_DPV4.0 PARTIAL PLAN - EQUIPMENT PAD DIMENSIONSPV4.1 PARTIAL PLAN - EQUIPMENT PAD AC FEEDER ROUTINGPV4.2 PARTIAL PLAN - EQUIPMENT PAD COMMUNICATIONS FEEDER ROUTINGPV4.3 PARTIAL PLAN - EQUIPMENT PAD - GROUNDINGPV5.0 INVERTER MOUNTING DETAILPV5.1 FENCE GROUNDING DETAIL

AC SYSTEM SIZE: 1,000 KW ACDC SYSTEM SIZE: 1,260 KW DCSTRING SIZE: (20) MODULESSTRING COUNT: (200) STRINGSMODULES: (4,000) REC315PE72INVERTERS: (40) SCHNEIDER_ELECTRIC CL25000NADC VOLTAGE: 1,000VAC VOLTAGE: 480V, 3ɸ, 4 WIREPCC VOLTAGE: 12,470V, 3ɸARRAY AZIMUTH: 180°ARRAY TILT: 0°RACKING: ATI SINGLE AXIS TRACKER

1

PV0.2

A AMPS

AC ALTERNATING CURRENT

AL ALUMINUM

ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING, AND AIR-CONDITIONING

ENGINEERS

C CELSIUS

CT CURRENT TRANSFORMER

CU COPPER

DB DRY BULB

DC DIRECT CURRENT

DIA DIAMETER

DISC DISCONNECT

DWG DRAWING

EGC EQUIPMENT GROUNDING CONDUCTOR

EMT ELECTRICAL METALLIC TUBING

ETL ELECTRICAL TESTING LABS

GALV GALVANIZED

GEC GROUNDING ELECTRODE CONDUCTOR

GFI GROUND FAULT INTERRUPTER

GND GROUND

IMC INTERMEDIATE METALLIC CONDUIT

IMP MAXIMUM POWER CURRENT

INV INVERTER

ISC SHORT CIRCUIT CURRENT

KW KILOWATT

KV KILOVOLT

KA KILOVOLT AMPS

KVM KEYBOARD, VIDEO, MOUSE

LFMC LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT

LFNC LIQUIDTIGHT FLEXIBLE NONMETALLIC CONDUIT

MAX MAXIMUM

MCB MAIN CIRCUIT BREAKER

MIN MINIMUM

MLO MAIN LUG ONLY

MPP MAXIMUM POWER POINT

MV MEDIUM VOLTAGE

NEC NATIONAL ELECTRIC CODE

NEG NEGATIVE

NEU NEUTRAL

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NRTL NATIONALLY RECOGNIZED TESTING LABORATORY

OCPD OVER CURRENT PROTECTION DEVICE

PC PERSONAL COMPUTER

PCC POINT OF COMMON COUPLING

PLC PROGRAMMABLE LOGIC CONTROLLER

POS POSITIVE

PT POTENTIAL TRANSFORMER

PV PHOTOVOLTAIC

PVC POLYVINYL CHLORIDE

RMC RIGID METALLIC CONDUIT

RTU REMOTE TERMINAL UNIT

SCADA SUPERVISORY CONTROL AND DATA ACQUISITION

SCH SCHEDULE

STC STANDARD TEST CONDITIONS

TEMP TEMPERATURE

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLT/VOLTS

VAC VOLTS AC

VDC VOLTS DC

VMP MAXIMUM POWER VOLTAGE

VOC OPEN CIRCUIT VOLTAGE

XFMR TRANSFORMER

1. THE CONTRACTOR IS RESPONSIBLE FOR MEETING ALL OSHA REGULATIONS AND SAFETY PRECAUTIONS ON SITE. THE ENGINEER IS NOT RESPONSIBLE FORSPECIFIC WORKING HAZARDS.

2. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR READING AND UNDERSTANDING ALL EQUIPMENT MANUALS AND DRAWINGS PRIOR TO INSTALLING ANDENERGIZING EQUIPMENT.

3. ALL SYSTEM COMPONENTS SHALL BE LISTED BY A THIRD PARTY TESTING AGENCY (UL, NRTL, ETL, ETC.). ALL EQUIPMENT SHALL HAVE A MINIMUM RATING OFNEMA 3R UNLESS LOCATED INDOORS.

4. ALL ELECTRICAL WORK SHALL BE PERFORMED BY A CERTIFIED ELECTRICIAN AND APPRENTICES UNDER THE SUPERVISION OF A LICENSED ELECTRICALCONTRACTOR.

5. PV STRINGS SHALL BE CONNECTED AND LABELED AS DETAILED IN THE DRAWING SET.

6. THE SYSTEM SHALL BE INSTALLED PER NEC 2014 AND SHALL ADHERE TO ALL LOCAL CODES AND STANDARDS.

7. THE PV SYSTEM SHALL BE GROUNDED AND BONDED PER NEC ARTICLE 690 SECTION V AND ARTICLE 250. ANY DEVIATIONS FROM THE DRAWINGS SET WILLNEED TO BE APPROVED BY THE ENGINEER.

8. SYSTEM SIGNAGE SHALL BE INSTALLED AND LABELED PER NEC ARTICLE 690 SECTION VI.

9. WORKING CLEARANCES AROUND ALL EQUIPMENT SHALL CONFORM TO NEC 110.26.

10. ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH CHAPTER 3 OF THE NEC.

11. CONTRACTOR INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ENGINEER PRIOR TO MAKING ANY CHANGES. APPROVED CHANGES SHALLREQUIRE A DRAWING REVISION TO MAINTAIN VERSION CONTROL.

12. ACTUAL LOCATION OF OVERHEAD AND UNDERGROUND UTILITIES SHALL BE FIELD VERIFIED AND DOCUMENTED PRIOR TO THE EXECUTION OF ANY WORK.THE ENGINEER OF RECORD SHALL BE NOTIFIED OF ANY DISCREPANCIES TO EXISTING CONDITIONS.

13. ALL CONDUCTORS AND EQUIPMENT SHALL BE CONSIDERED "ENERGIZED" UNLESS CHECKED, AND CHECKED AGAIN. LOCKOUT - TAGOUT PROCEDURES SHALLBE EMPLOYED BEFORE ANY WORK IS DONE ON ELECTRICAL EQUIPMENT.

14. THE CONTRACTOR SHALL MAKE AN EFFORT TO CAUSE AS LITTLE DISTURBANCE AS POSSIBLE AND PROTECT THE NATURAL ENVIRONMENT AND RESOURCESOF THE FACILITY DURING THE COURSE OF THE WORK. ALL DISTURBED AREAS SHALL BE RETURNED TO THEIR PRE-CONSTRUCTION STATE OR BETTER. AREASWHICH ARE SEEDED OR SODDED WITH ESTABLISHED GRASS SHALL BE SEEDED AS SOON AS POSSIBLE AFTER COMPLETION OF THE WORK IN THAT AREA.

15. THE CONDUIT LAYOUT DEPICTED IN THE DRAWING SET IS FOR DIAGRAMMATIC PURPOSES ONLY UNLESS OTHERWISE NOTED. CONTRACTOR SHALL ROUTECONDUIT TO BEST SUIT SITE CONDITIONS AND PROVIDE ACCURATE AS-BUILTS.

16. CONNECTORS, TERMINATIONS AND EQUIPMENT HARDWARE SHALL BE TORQUED PER DEVICE LISTING OR INSTALLATION DOCUMENTATION.

17. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS ON THE DRAWINGS INCLUDING EXISTING STRUCTURES. THE ENGINEER SHALL BE NOTIFIED OFANY DISCREPANCIES IN THE DRAWINGS AND/OR EXISTING SITE CONDITIONS.

18. DC VOLTAGE IS ALWAYS PRESENT FROM THE ARRAY DURING DAYLIGHT HOURS. THERE IS A POTENTIAL FOR VOLTAGE TO BE PRESENT AT THE TERMINALS OFTHE DC DISCONNECT, COMBINER BOX AND AT THE DC TERMINALS ON THE INVERTER. ALL PERSONNEL SHOULD BE NOTIFIED OF THIS POTENTIAL HAZARDAND SHOULD TAKE PRECAUTIONS TO PREVENT ACCIDENTAL SHOCK OR INJURY.

19. ALL EQUIPMENT SHALL BE MOUNTED PER MANUFACTURER'S SPECIFICATIONS.

20. THE CONTRACTOR SHALL SUPPLY EQUIPMENT/MATERIAL SUBMITTALS PRIOR TO ORDERING. APPROVAL BY POWERSECURE SOLAR FOR ALL EQUIPMENT ISMANDATORY.

ABBREVIATIONS SYMBOLSGENERAL NOTES

GEN

ERAL

NO

TES

AND

SYM

BOLS

DETAIL TAGXXX-X

#

A

#

R#

EQUIPMENT TAG

FEEDER TAG

KEYED NOTE TAG

REVISION TAG

MODULE

COMBINER

CONTACTOR RECOMBINER

INVERTER

METER

FUSE

CIRCUIT BREAKER

THREE-WINDING TRANSFORMER

TWO-WINDING TRANSFORMER

FUSED DISCONNECT

SWITCH

FUSED SWITCH

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

XXXA

XXXA

X#XXXA

XXXA

XXXA

LA

15A

15A

15A

X#

RATIO

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 242

AutoCAD SHX Text
M

PVMONITORING SYSTEM

PVMETEOROLOGICAL STATION

SPD

1500:5

TRACKER MOTORUNIT_1

TRACKER MOTOR UNIT_2

4X CONTROLLER

UNIT

GPS

WINDSTOW

SWITCH

SITE DATA

PVMONITORING SWITCH

LA

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24SINGLE LINE DIAGRAMSCALE: NONE1

GENERAL NOTES:

1. PROVIDE LABELS TO EACH INCOMING CIRCUIT IN THE INVERTER.

2. PROVIDE IRREVERSIBLE BONDS AT ALL GROUNDING ELECTRODE CONDUCTORS.

3. REFER TO PV SCHEDULES ON PV1.1 FOR EQUIPMENT SPECIFICATIONS AND RACEWAY SIZES.

LINE TYPE LEGEND:

DC FEEDERS

AC FEEDERS

MEDIUM VOLTAGE FEEDER

EQUIPMENT

MODULES

PROVIDED BY MANUFACTURE/ OTHERS

COMMUNICATIONS

SIN

GLE

LIN

E DI

AGRA

M

PV1.0

ARRAY200 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

MODULE, TYP OF 4,000

INVERTERTYP OF 40

1

PV_A400A BUS, MLO480V, 3ɸ, 4WNEMA 3R

PV_B400A BUS, MLO480V, 3ɸ, 4WNEMA 3R

PV_C400A BUS, MLO480V, 3ɸ, 4WNEMA 3R

PV_D400A BUS, MLO480V, 3ɸ, 4WNEMA 3R

PV_MDP1,600A BUS, 1600 MCB480V, 3ɸ, 4WNEMA 3R

SYSTEM SUMMARY

AC SYSTEM SIZE: 1,000.0 KW ACDC SYSTEM SIZE: 1,260.0 KW ACSTRING SIZE: 20STRING COUNT: 200INVERTER: (40) SCHNEIDER_ELECTRIC

CL25000NADC VOLTAGE: 1,000VAC VOLTAGE: 480V, 3ɸ, 4 WIREIC VOLTAGE: 12,470V, 3ɸ, 4 WIREARRAY AZIMUTH: 180°ARRAY TILT: 0°RACKING: ATI RACKING

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

TRANSFORMER1,000KVA12.47KV PRIMARY,480/277V SEC

AUXILIARY DISCONNECT30A FRAME, 15A FUSENEMA 3R

AUX TRANSFORMER5KVA480V PRIMARY208/120V SECONDARY

AUXILIARY POWER PANEL100A BUS, 20A MCB208/120V, 3ɸ,4WIRE, NEMA 3R

23A

3B

3C

3D

4

5

6

7

8

10

11

12

9

14

15

16

MV FUSED SWITCHN.C.

MV SWITCH N.C.CONNECTED TO UTILITY

A

AB

B

B

B

C

D

E

E

F

F

F

G

H

N

1 1

1

1

1

1

KEYED NOTE:

1. TO BE PROVIDED AS PART OF ATI RACKING SYSTEM.

XX

J

K

K

N13 I

ITYP

ITYP

ITYP

ITYP

A1-40A

A2-40A

A3-40A

A5-40A

A4-40A

A6-40A

A7-40A

A8-40A

A9-40A

A10-40A

B1-40A

B2-40A

B3-40A

B5-40A

B4-40A

B6-40A

B7-40A

B8-40A

B9-40A

B10-40A

C1-40A

C2-40A

C3-40A

C5-40A

C4-40A

C6-40A

C7-40A

C8-40A

C9-40A

C10-40A

D1-40A

D2-40A

D3-40A

D5-40A

D4-40A

D6-40A

D7-40A

D8-40A

D9-40A

D10-40A

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

5 STRINGS OF 20 MODULES

A

A

M

N

3

A1

A2

A9

A10

B1

B2

B9

B10

C1

C2

C9

C10

D1

D2

D9

D10

I

I

I

I

I

I

I

I

I

I

PV_A400A

PV_B400A

PV_C400A

PV_D400A

MAIN1,600A

20A

1P 20A

1P 20A

1P 20A

1P 20A

1P 20A

1P 20A

2P 20A

2P 20A

3P

20A

3P

18 18

18

18

18

18

AutoCAD SHX Text
M

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

PV S

CHED

ULE

S

PV1.1

4

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

PV S

CHED

ULE

S

PV1.2

5

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

PV L

ABEL

S

PV1.3

6

INVERTER XX

PV PRODUCTION MONITORING SYSTEM

WHITE LETTERING ON BLACK BACKGROUND. TYPICAL OF 40

WHITE LETTERING ON BLACK BACKGROUND

PV PRODUCTIONMONITORING SWITCH

WHITE LETTERING ON BLACK BACKGROUND.TYPICAL OF 1

TRANSFORMERWHITE LETTERING ON BLACK BACKGROUND. TYPICAL OF 1

PV SERVICE

WHITE LETTERING ON RED BACKGROUND

VOLTAGE: XXX V

AVAILABLE FAULT CURRENT XXX A

CALCULATED: XX/XX/XXXX

OCPD AIC RATING XXX,XXX A

12,470VAC WIREA PHASE BROWNB PHASE ORANGEC PHASE YELLOWGROUND GREEN OR BARE

WHITE LETTERING ON BLACK BACKGROUNDPROVIDE WARNING SIGNAGE AT EACH JUNCTION BOX OR ANY OTHERDEVICE WHERE ENERGIZE THAT CONTAINS 12470VAC WIRE.

AC OUTPUT CURRENT 31 A

NOMINAL AC VOLTAGE 480 V

WARNING

WARNING: ELECTRIC SHOCK HAZARD

APPROPRIATE PPE REQUIRED. FAILURE TO COMPLY MAY RESULT INDEATH OR INJURY. REFER TO NFPA 70E.

DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOADSIDE MAY BE ENERGIZED IN THE OPEN POSITION.

WHITE LETTERING ON RED BACKGROUNDTYPICAL OF 40 INVERTERS (A1-A10, B1-B10, C1-C10, D1-D10)REFER TO DISTRIBUTION PANEL SCHEDULES PV_A TO PV_D FOR LABEL VALUES.

INVERTER AC OUTPUT

WARNINGTHIS EQUIPMENT IS FED BY MULTIPLE SOURCES

(UTILITY AND PHOTOVOLTAIC)

AC OUTPUT CURRENT 31 A

NOMINAL AC VOLTAGE 480 V

WARNING

WARNING: ELECTRIC SHOCK HAZARD

APPROPRIATE PPE REQUIRED. FAILURE TO COMPLY MAY RESULT INDEATH OR INJURY. REFER TO NFPA 70E.

DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOADSIDE MAY BE ENERGIZED IN THE OPEN POSITION.

WHITE LETTERING ON RED BACKGROUNDTYPICAL OF 40 BREAKERS (A1-A10, B1-B10, C1-C10, D1-D10)REFER TO DISTRIBUTION PANEL SCHEDULES PV_A TO PV_D FOR LABEL VALUES.

PHOTOVOLTAIC AC DISCONNECT

WARNINGTHIS EQUIPMENT IS FED BY MULTIPLE SOURCES

(UTILITY AND PHOTOVOLTAIC)

5 STRINGSRATED MPP CURRENT 43.10 A

RATED MPP VOLTAGE 736.0 V

MAX SYSTEM VOLTAGE 988.38 V

MAX CIRCUIT CURRENT 56.81 A

WARNING

WARNING: ELECTRIC SHOCK HAZARD

APPROPRIATE PPE REQUIRED. FAILURE TO COMPLY MAY RESULT INDEATH OR INJURY. REFER TO NFPA 70E.

DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOADSIDE MAY BE ENERGIZED IN THE OPEN POSITION.

WARNING: ELECTRIC SHOCK HAZARDTHE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE

UNGROUNDED AND MAY BE ENERGIZED.

WHITE LETTERING ON RED BACKGROUNDTYPICAL OF 40:A1-A10, B1-B10, C1-C10, D1-D10

INVERTER DC INPUT

XX

XX

XX

AC OUTPUT CURRENT 310 A

NOMINAL AC VOLTAGE 480 V

WARNING

WARNING: ELECTRIC SHOCK HAZARD

APPROPRIATE PPE REQUIRED. FAILURE TO COMPLY MAY RESULT INDEATH OR INJURY. REFER TO NFPA 70E.

DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOADSIDE MAY BE ENERGIZED IN THE OPEN POSITION.

WHITE LETTERING ON RED BACKGROUNDTYPICAL OF 4:PV_A, PV_B, PV_C AND PV_D BREAKERS OF PV_MDP.

WARNINGTHIS EQUIPMENT IS FED BY MULTIPLE SOURCES

(UTILITY AND PHOTOVOLTAIC)

PHOTOVOLTAIC SYSTEM AC DISCONNECT

PV-X

WARNING:ELECTRIC SHOCK HAZARD. THE DC

CONDUCTORS OF THIS PHOTOVOLTAICSYSTEM ARE UNGROUNDED AND MAY

BE ENERGIZED.WHITE LETTERING ON RED BACKGROUNDTHIS LABEL IS REQUIRED ON EXPOSED RACEWAY, CABLE TRAY, ENCLOSURESAND CONDUIT BODIES CONTAINING PHOTOVOLTAIC SOURCE CIRCUITS.SPACING AND LOCATION OF LABEL AS SPECIFIED PER NEC 690.35(F).

AC OUTPUT CURRENT 1,240 A

NOMINAL AC VOLTAGE 480 V

WARNING

WARNING: ELECTRIC SHOCK HAZARD

APPROPRIATE PPE REQUIRED. FAILURE TO COMPLY MAY RESULT INDEATH OR INJURY. REFER TO NFPA 70E.

DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOADSIDE MAY BE ENERGIZED IN THE OPEN POSITION.

WHITE LETTERING ON RED BACKGROUND

WARNINGTHIS EQUIPMENT IS FED BY MULTIPLE SOURCES

(UTILITY AND PHOTOVOLTAIC)

PHOTOVOLTAIC SYSTEM AC DISCONNECT

PV-MDP

WHITE LETTERING ON BLACK BACKGROUNDTYPICAL OF 4 PANEL BOARDS: PV_A, PV_B, PV_C AND PV_D

PV_X DISTRIBUTION PANEL480V, 3φ, 4W

400A BUS, MLO

WHITE LETTERING ON BLACK BACKGROUND

PV_MDP480V, 3φ, 4W

1,600A BUS, 1,600 MCB

5.0KVA AUXILIARYPOWER TRANSFORMER

480:208/120V, 3φWHITE LETTERING ON BLACK BACKGROUND

AUXILIARY POWER PANEL208/120V, 3φ

100A BUS, 20A MCBWHITE LETTERING ON BLACK BACKGROUND

PHOTOVOLTAIC POWER SOURCEMAX 1,000V

WHITE LETTERING ON BLACK BACKGROUNDTHIS LABEL IS REQUIRED ON EXPOSED RACEWAY, CABLE TRAY, ENCLOSURESAND CONDUIT BODIES CONTAINING PHOTOVOLTAIC CIRCUITS. SPACINGAND LOCATION OF LABEL AS SPECIFIED PER NEC 690.31(E)(4).

1000VDC WIRE

WHITE LETTERING ON BLACK BACKGROUNDPROVIDE WARNING SIGNAGE AT EACH JUNCTION BOX, COMBINER BOX,DISCONNECT, AND ANY OTHER DEVICE WHERE ENERGIZE THAT CONTAINS1000VDC WIRE.

POSITIVE RED OR YELLOWNEGATIVE BLACKGROUND GREEN OR BARE

120/208VAC WIREL1 BLACKL2 REDNEUTRAL WHITE OR GRAYGROUND GREEN OR BARE

WHITE LETTERING ON BLACK BACKGROUNDPROVIDE WARNING SIGNAGE AT EACH JUNCTION BOX OR ANY OTHERDEVICE WHERE ENERGIZE THAT CONTAINS 120/240VAC WIRE.

480VAC WIREA PHASE BROWNB PHASE ORANGEC PHASE YELLOWGROUND GREEN OR BARE

WHITE LETTERING ON BLACK BACKGROUNDPROVIDE WARNING SIGNAGE AT EACH JUNCTION BOX OR ANY OTHERDEVICE WHERE ENERGIZE THAT CONTAINS 360VAC WIRE.

WHITE LETTERING ON BLACK BACKGROUND.

AUXILIARY POWER DISCONNECT

MV FUSEDSWITCH

WHITE LETTERING ON BLACK BACKGROUND. TYPICAL OF 1

PV PRODUCTIONMETEOROLOGICAL STATION

WHITE LETTERING ON BLACK BACKGROUND. TYPICAL OF 2

TRACKER MOTOR UNITWHITE LETTERING ON BLACK BACKGROUND. TYPICAL OF 2

4X CONTROL UNITWHITE LETTERING ON BLACK BACKGROUND. TYPICAL OF 1

SITE DATA

WHITE LETTERING ON BLACK BACKGROUND. TYPICAL OF 1

GPSWHITE LETTERING ON BLACK BACKGROUND. TYPICAL OF 1

WIND STOW SWITCHWHITE LETTERING ON BLACK BACKGROUND. TYPICAL OF 1

PV PRODUCTIONMETER

WHITE LETTERING ON BLACK BACKGROUND. TYPICAL OF 1

VOLTAGE XX

WORKING DISTANCE (INCHES) XX

INCIDENT ENERGY (CAL/CM2) XX

FLASH BOUNDARY (INCHES) XX

LIMITED APPROACH (INCHES) XX

RESTRICTED APPROACH (INCHES) XX

GLOVE CLASS XX

WARNINGARC FLASH AND SHOCK HAZARD

APPROPRIATE PPE REQUIREDXXX

STUDY PERFORMED BY POWERSECURE SOLAR ON XX/XX/XXXX

BLACK LETTERING ON WHITE BACKGROUND WITH ORANGE HEADER.ARC FLASH VALUES TO BE DETERMINED BY ENGINEER OF RECORD BEFORESYSTEM COMMISSIONING.

VOLTAGE XX

WORKING DISTANCE (INCHES) XX

INCIDENT ENERGY (CAL/CM2) XX

FLASH BOUNDARY (INCHES) XX

LIMITED APPROACH (INCHES) XX

RESTRICTED APPROACH (INCHES) XX

GLOVE CLASS XX

DANGERARC FLASH AND SHOCK HAZARD

NO SAFE PPE EXISTSXXX

STUDY PERFORMED BY POWERSECURE SOLAR ON XX/XX/XXXX

BLACK LETTERING ON WHITE BACKGROUND WITH RED HEADER.ARC FLASH VALUES TO BE DETERMINED BY ENGINEER OF RECORD BEFORESYSTEM COMMISSIONING.

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SITE

PLA

N -

ARRA

Y LA

YOU

T

PV2.0

1PV4.0

1PV4.1

1PV4.2

SCALE: 1"=40'-0"SITE PLAN - ARRAY LAYOUT1

INVERTER (TYPICAL OF 40)

PV MODULE (TYPICAL OF 4,000)

SECURITY FENCE

EQUIPMENT PAD

TRANSFORMER

POLE MOUNTED COORDINATED SWITCH

BACK OF MODULE TEMPERATURE SENSOR

24' VEHICLE ACCESS GATE

4' PEDESTRIAN ACCESS GATE

CONSTRUCTION LAY DOWN AREA

GENERAL NOTES:

1. REFER TO SINGLE LINE DIAGRAM ON PV1.0 FOR SPECIFICATIONS.

2. REFER TO EQUIPMENT AND FEEDER SCHEDULES ON PV1.1 FOR SPECIFICATIONS.

3. PROVIDE ATI SINGLE AXIS TRACKER. RACKING SYSTEM SHALL BE A PIER DRIVEN SYSTEM. EACH ROW SECTIONSHALL CONTAIN 80 MODULES HIGH IN PORTRAIT. HORIZONTAL DISTANCE BETWEEN RACK SECTION SHALL BESPECIFIED BY MANUFACTURER. THE RACKING SYSTEM SHALL BE UL LISTED FOR GROUNDING CONTINUITY.COMPONENTS WITHIN THE RACKING SYSTEM SHALL FORM AN ELECTRICALLY BONDED UNIT AND WILL REQUIREADDITIONAL BONDING FROM ONE INDIVIDUAL RACK SECTION TO ADJACENT SECTIONS. REFER TOMANUFACTURER PROVIDED DOCUMENTATION AND SEALED STRUCTURAL DOCUMENTATION.

4. STRINGING FEEDERS SHALL BE ROUTED ALONG RACKING SYSTEM IN RACKING MANUFACTURERS PROVIDEDINTEGRATED WIRE MANAGEMENT TRAY OR BELOW GRADE.

UTILITY PROVIDED POLE, POINT OF DEMARCATION

MEDIUM VOLTAGE SWITCH

PV DISTRIBUTION PANEL BOARD (TYPICAL OF 4)

20'-0"MINIMUM

19'-0" 12'-6 1/2"

20'-0"ACCESS PATH

TRACKER MOTOR UNIT

1PV4.3

1PV5.0

7

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SITE

PLA

N -

FEN

CE L

AYO

UT

PV2.1

SCALE: 1"=40'-0"SITE PLAN - FENCE LAYOUT1

SECURITY FENCE

24' VEHICLE ACCESS GATE 4' PEDESTRIAN ACCESS GATE

GENERAL NOTES:

1. TOTAL FENCE LENGTH IS APPROXIMATELY 2,620 FEET.

2. FENCE SHALL BE 6'-0" TALL TOPPED WITH 3 STRING BARBED WIRE NO LESS THAN 12" IN HEIGHT. OVERALLHEIGHT OF 7'-0" MINIMUM PER NEC110.31.

3. ONE PERMANENT VEHICLE ENTRANCE GATE, 24' MINIMUM IN WIDTH, LOCATED AS SHOWN.

4. ONE PERMANENT PEDESTRIAN ENTRANCE GATE,4' MINIMUM IN WIDTH, LOCATED AS SHOWN.

5. REFER TO FENCE GROUNDING DETAIL ON PV5.1.

1003'-11"

306'-7"306'-7"

439'-7 3/4"8'-0" 4'-0"

528'-3 1/4"

100'-0"

100'-0"

8

24'-0"

Aɸ, PV OUTPUT

Bɸ, PV OUTPUT

Cɸ, PV OUTPUT

Aɸ, MEDIUM VOLTAGE

Bɸ, MEDIUM VOLTAGE

Cɸ, MEDIUM VOLTAGE

NEU, PV OUTPUTNEU, MEDIUM VOLTAGEHo Xo

STRAP TO TANK ANDCONNECTION TO PAD

NEUTRAL

STRAP TO TANK ANDCONNECTION TO PADNEUTRAL

GROUND PAD GROUND PAD

TO EQUIPMENT PADGROUND RING

GROUND ROD, PER NEC250.24(A)(2)

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SITE

PLA

N -

MED

IUM

VO

LTAG

E RO

UTI

NG

PV2.2SCALE: 1"=40'-0"SITE PLAN - MEDIUM VOLTAGE ROUTING1

GROUND MOUNTED MEDIUM VOLTAGE SWITCH

CONTRACTOR PROVIDED POLE MOUNTED SWITCH

MEDIUM VOLTAGE TRANSFORMER

LINE TYPE LEGEND:

MV FEEDERS

FEEDERS/EQUIPMENTPROVIDED BY OTHERS

UTILITY NEUTRAL

NEW EQUIPMENT

GROUNDING CONDUCTOR

SCALE: NTSMEDIUM VOLTAGE INERCONNECTION DETAIL3

SCALE: NTSMEDIUM VOLTAGE TRANSFORMER DETAIL2

E E

O

UTILITY OWNEDMETER

UTILITY OWNEDCT AND PT

UTILITY OWNED POLE,POINT OF INTERCONNECTION

E

E

MEDIUM VOLTAGE TRANSFORMER

GROUND MOUNTED MEDIUM VOLTAGE SWITCH

CONTRACTOR PROVIDED POLE MOUNTED SWITCH

UTILITY OWNED POLE, POINT OF INTERCONNECTION

ALL MEDIUM VOLTAGE SHALL BE ROUTED BELOW GRADE TO POLE

GENERAL NOTES:

1. REFER TO SINGLE LINE DIAGRAM ON PV1.0 FOR SPECIFICATIONS.

2. REFER TO EQUIPMENT AND FEEDER SCHEDULES ON PV1.1 FOR SPECIFICATIONS.

O

O

O

9

FROM EACH CONCENTRIC NEUTRAL

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SITE

PLA

N -

INVE

RTER

LAY

OU

T

PV2.3

SCALE: 1"=40'-0"SITE PLAN - INVERTER LAYOUT1

LEGEND:

AREA OF INVERTERS FEEDINGDISTRIBUTION PANEL A (PV_A)

AREA OF INVERTERS FEEDINGDISTRIBUTION PANEL B (PV_B)

AREA OF INVERTERS FEEDINGDISTRIBUTION PANEL C (PV_C)

AREA OF INVERTERS FEEDINGDISTRIBUTION PANEL D (PV_D)

GENERAL NOTES:

1. REFER TO EQUIPMENT SCHEDULE AND SINGLE LINE DIAGRAM FOR SPECIFICATIONS.

PV_A PV_B PV_C PV_DINVERTERS A1-A10 INVERTERS B1-B10 INVERTERS C1-C10 INVERTERS D1-D10

AREA

OF

INVE

RTER

A1 AR

EA O

F IN

VERT

ER A

2 AREA

OF

INVE

RTER

A3 AR

EA O

F IN

VERT

ER A

4

AREA

OF

INVE

RTER

A5 AR

EA O

F IN

VERT

ER A

6 AREA

OF

INVE

RTER

A7 AR

EA O

F IN

VERT

ER A

8

AREA

OF

INVE

RTER

A9 AR

EA O

F IN

VERT

ER A

10 AREA

OF

INVE

RTER

B1 AR

EA O

F IN

VERT

ER B

2

AREA

OF

INVE

RTER

B3 AR

EA O

F IN

VERT

ER B

4 AREA

OF

INVE

RTER

B5

AREA

OF

INVE

RTER

B6

AREA

OF

INVE

RTER

B7 AR

EA O

F IN

VERT

ER B

8

AREA

OF

INVE

RTER

B9 AR

EA O

F IN

VERT

ER B

10

AREA

OF

INVE

RTER

C1 AR

EA O

F IN

VERT

ER C

2 AREA

OF

INVE

RTER

C3 AR

EA O

F IN

VERT

ER C

4

AREA

OF

INVE

RTER

C5 AR

EA O

F IN

VERT

ER C

6 AREA

OF

INVE

RTER

C7 AR

EA O

F IN

VERT

ER C

8

AREA

OF

INVE

RTER

C9 AR

EA O

F IN

VERT

ER C

10 AREA

OF

INVE

RTER

D1 AR

EA O

F IN

VERT

ER D

2

AREA

OF

INVE

RTER

D3 AR

EA O

F IN

VERT

ER D

4 AREA

OF

INVE

RTER

D5

AREA

OF

INVE

RTER

D6

AREA

OF

INVE

RTER

D7 AR

EA O

F IN

VERT

ER D

8 AREA

OF

INVE

RTER

D9 AR

EA O

F IN

VERT

ER D

10

10

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SITE

PLA

N -

DC F

EEDE

R RO

UTI

NG

PV2.4

SCALE: 1"=40'-0"SITE PLAN - DC ROUTING1

GENERAL NOTES:

1. REFER TO EQUIPMENT SCHEDULE AND SINGLE LINE DIAGRAM FOR SPECIFICATIONS

2. ALL UNDERGROUND RACEWAY SHALL BE SCHEDULE 40 PVC. TRANSITIONS BELOW TO ABOVE GRADE SHALL BEPER CONDUIT STUB UP DETAIL.

3. FOR TRENCHES 24" WIDE AND LESS, ONLY ONE RUN OF MAGNETIC ELECTRICAL WARNING TAPE SHALL BEREQUIRED PER DETAIL 3.

4. FOR TRENCHES WIDER THAN 24" ONE PIECE OF TAPE SHALL BE LOCATED AT EACH SIDE OF THE TRENCH WITHADDITIONAL RUNS PROVIDED AS NECESSARY. THE MAXIMUM DISTANCE BETWEEN TAPE RUNS SHALL BE 24" ONCENTER.

5. TRENCH BOTTOMS: EXCAVATE TRENCHES 3" DEEPER THAN BOTTOM OF PIPE ELEVATION TO ALLOW FORBEDDING COURSE. HAND EXCAVATE FOR BELL OF PIPE. EXCAVATE TRENCHES 3" DEEPER THAN ELEVATIONREQUIRED IN ROCK OR OTHER UNYIELDING BEARING MATERIAL TO ALLOW BEDDING COURSE.

6. ALL BACKFILL SHOULD BE FREE OF MATERIALS THAT MAY DAMAGE THE CONDUIT OR CABLE SYSTEM. BACKFILLWITHIN 150 MM (6 IN) OF THE CONDUIT OR CABLE SHOULD BE FREE OF SOLID MATERIAL GREATER THAN 100MM (2 IN) IN MAXIMUM DIMENSION OR WITH SHARP EDGES LIKELY TO DAMAGE IT. THE BALANCE OF BACKFILLSHOULD BE FREE OF SOLID MATERIAL GREATER THAN 200 MM (8 IN) IN MAXIMUM DIMENSION. BACKFILLMATERIAL SHOULD BE ADEQUATELY COMPACTED.

7. REFER TO ARRAY GROUNDING DETAIL FOR BARE COPPER GROUND TRENCH ROUTING.

8. FEEDER ROUTING SHOWN DIAGRAMMATICALLY, COORDINATION WITH SITE CONDITIONS REQUIRED.

2'-0"MINIMUM

1'-0"MINIMUM

1-0"MINIMUM

BACKFILL, REFER TO GENERALNOTE 5

MAGNETIC WARNING TAPE,REFER TO GENERAL NOTE 2 & 3

2'-0"MINIMUM

1'-0"MINIMUM

1-0"MINIMUM

BARE COPPER GROUND SIZEDAS SPECIFIED, REFER TO ARRAYGROUNDING PLAN

3" MINIMUM TRENCH EDGETO BARE COPPER GROUND

3" MINIMUM TRENCH EDGETO BARE COPPER GROUND

3" MINIMUMTRENCH EDGE TO

CONDUIT

4" MINIMUMBETWEEN CONDUITS

3" MINIMUMTRENCH EDGE TO

CONDUIT4" MINIMUM

BETWEEN CONDUITS

SCALE: NONETYPICAL SINGLE CONDUIT TRENCH2

SCALE: NONETYPICAL MULTIPLE CONDUIT TRENCH3

PV_A PV_B PV_C PV_D

TYP.A

A

A

A

TYP.

TYP.

TYP.

ATYP.

ATYP.

ATYP.

ATYP.

11

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SITE

PLA

N -

AC F

EEDE

R RO

UTI

NG

PV2.5

SCALE: 1"=40'-0"SITE PLAN - AC ROUTING1

GENERAL NOTES:

1. REFER TO EQUIPMENT SCHEDULE AND SINGLE LINE DIAGRAM FOR SPECIFICATIONS.

2. ALL UNDERGROUND RACEWAY SHALL BE SCHEDULE 40 PVC. TRANSITIONS BELOW TO ABOVE GRADE SHALL BEPER CONDUIT STUB UP DETAIL.

3. FOR TRENCHES 24" WIDE AND LESS, ONLY ONE RUN OF MAGNETIC ELECTRICAL WARNING TAPE SHALL BEREQUIRED PER DETAIL 3.

4. FOR TRENCHES WIDER THAN 24" ONE PIECE OF TAPE SHALL BE LOCATED AT EACH SIDE OF THE TRENCH WITHADDITIONAL RUNS PROVIDED AS NECESSARY. THE MAXIMUM DISTANCE BETWEEN TAPE RUNS SHALL BE 24" ONCENTER.

5. TRENCH BOTTOMS: EXCAVATE TRENCHES 3" DEEPER THAN BOTTOM OF PIPE ELEVATION TO ALLOW FORBEDDING COURSE. HAND EXCAVATE FOR BELL OF PIPE. EXCAVATE TRENCHES 3" DEEPER THAN ELEVATIONREQUIRED IN ROCK OR OTHER UNYIELDING BEARING MATERIAL TO ALLOW BEDDING COURSE.

6. ALL BACKFILL SHOULD BE FREE OF MATERIALS THAT MAY DAMAGE THE CONDUIT OR CABLE SYSTEM. BACKFILLWITHIN 150 MM (6 IN) OF THE CONDUIT OR CABLE SHOULD BE FREE OF SOLID MATERIAL GREATER THAN 100MM (2 IN) IN MAXIMUM DIMENSION OR WITH SHARP EDGES LIKELY TO DAMAGE IT. THE BALANCE OF BACKFILLSHOULD BE FREE OF SOLID MATERIAL GREATER THAN 200 MM (8 IN) IN MAXIMUM DIMENSION. BACKFILLMATERIAL SHOULD BE ADEQUATELY COMPACTED.

7. REFER TO ARRAY GROUNDING DETAIL FOR BARE COPPER GROUND TRENCH ROUTING.

8. FEEDER ROUTING SHOWN DIAGRAMMATICALLY, COORDINATION WITH SITE CONDITIONS REQUIRED.

2'-0"MINIMUM

1'-0"MINIMUM

1-0"MINIMUM

BACKFILL, REFER TO GENERALNOTE 5

MAGNETIC WARNING TAPE,REFER TO GENERAL NOTE 2 & 3

2'-0"MINIMUM

1'-0"MINIMUM

1-0"MINIMUM

BARE COPPER GROUND SIZEDAS SPECIFIED, REFER TO ARRAYGROUNDING PLAN

3" MINIMUM TRENCH EDGETO BARE COPPER GROUND

3" MINIMUM TRENCH EDGETO BARE COPPER GROUND

3" MINIMUMTRENCH EDGE TO

CONDUIT

4" MINIMUMBETWEEN CONDUITS

3" MINIMUMTRENCH EDGE TO

CONDUIT4" MINIMUM

BETWEEN CONDUITS

SCALE: NONETYPICAL SINGLE CONDUIT TRENCH2

SCALE: NONETYPICAL MULTIPLE CONDUIT TRENCH3

PV_A PV_BPV_C

PV_D

1PV4.1B

C

(10) B BB

H

EC

12

(10) (10) (10)

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SITE

PLA

N -

COM

MU

NIC

ATIO

NS

FEED

ER R

OU

TIN

G

PV2.6

SCALE: 1"=40'-0"SITE PLAN - COMMUNICATONS ROUTING1

GENERAL NOTES:

1. REFER TO EQUIPMENT SCHEDULE AND SINGLE LINE DIAGRAM FOR SPECIFICATIONS.

2. ALL UNDERGROUND RACEWAY SHALL BE SCHEDULE 40 PVC. TRANSITIONS BELOW TO ABOVE GRADE SHALL BEPER CONDUIT STUB UP DETAIL.

3. FOR TRENCHES 24" WIDE AND LESS, ONLY ONE RUN OF MAGNETIC ELECTRICAL WARNING TAPE SHALL BEREQUIRED PER DETAIL 3.

4. FOR TRENCHES WIDER THAN 24" ONE PIECE OF TAPE SHALL BE LOCATED AT EACH SIDE OF THE TRENCH WITHADDITIONAL RUNS PROVIDED AS NECESSARY. THE MAXIMUM DISTANCE BETWEEN TAPE RUNS SHALL BE 24" ONCENTER.

5. TRENCH BOTTOMS: EXCAVATE TRENCHES 3" DEEPER THAN BOTTOM OF PIPE ELEVATION TO ALLOW FORBEDDING COURSE. HAND EXCAVATE FOR BELL OF PIPE. EXCAVATE TRENCHES 3" DEEPER THAN ELEVATIONREQUIRED IN ROCK OR OTHER UNYIELDING BEARING MATERIAL TO ALLOW BEDDING COURSE.

6. ALL BACKFILL SHOULD BE FREE OF MATERIALS THAT MAY DAMAGE THE CONDUIT OR CABLE SYSTEM. BACKFILLWITHIN 150 MM (6 IN) OF THE CONDUIT OR CABLE SHOULD BE FREE OF SOLID MATERIAL GREATER THAN 100MM (2 IN) IN MAXIMUM DIMENSION OR WITH SHARP EDGES LIKELY TO DAMAGE IT. THE BALANCE OF BACKFILLSHOULD BE FREE OF SOLID MATERIAL GREATER THAN 200 MM (8 IN) IN MAXIMUM DIMENSION. BACKFILLMATERIAL SHOULD BE ADEQUATELY COMPACTED.

7. REFER TO ARRAY GROUNDING DETAIL FOR BARE COPPER GROUND TRENCH ROUTING.

8. FEEDER ROUTING SHOWN DIAGRAMMATICALLY, COORDINATION WITH SITE CONDITIONS REQUIRED.

2'-0"MINIMUM

1'-0"MINIMUM

1-0"MINIMUM

BACKFILL, REFER TO GENERALNOTE 5

MAGNETIC WARNING TAPE,REFER TO GENERAL NOTE 2 & 3

2'-0"MINIMUM

1'-0"MINIMUM

1-0"MINIMUM

BARE COPPER GROUND SIZEDAS SPECIFIED, REFER TO ARRAYGROUNDING PLAN

3" MINIMUM TRENCH EDGETO BARE COPPER GROUND

3" MINIMUM TRENCH EDGETO BARE COPPER GROUND

3" MINIMUMTRENCH EDGE TO

CONDUIT

4" MINIMUMBETWEEN CONDUITS

3" MINIMUMTRENCH EDGE TO

CONDUIT4" MINIMUM

BETWEEN CONDUITS

SCALE: NONETYPICAL SINGLE CONDUIT TRENCH2

SCALE: NONETYPICAL MULTIPLE CONDUIT TRENCH3

PV_A PV_B PV_CPV_D

1PV4.2

IITYP.

K

13

INVERTER DIST.PANELBOARD

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SCALE: 1"=40'-0"SITE PLAN - ARRAY GROUNDING1

SITE

PLA

N -

GRO

UN

DIN

G

PV2.7

O

O

O

1PV4.3

GENERAL NOTES:

1. THE RACKING SYSTEM SHALL BE UL LISTED FOR GROUNDING CONTINUITY. COMPONENTS WITHIN THE RACKINGSYSTEM SHALL FORM AN ELECTRICALLY BONDED UNIT AND REQUIRE ADDITIONAL BONDING FROM ONEINDIVIDUAL RACK SECTION TO ADJACENT SECTIONS.

2. REFER TO SINGLE LINE DIAGRAM AND SCHEDULES FOR SPECIFICATIONS.

3. ARRAY EQUIPMENT GROUND CONDUCTOR SHALL BE RUN IN TRENCH WITH INVERTERS FEEDERS WHEREPOSSIBLE.

4. GROUND FEEDER ROUTING SHOWN DIAGRAMMATICALLY, COORDINATION WITH SITE CONDITIONS REQUIRED.

5. PROVIDE AT LEAST 6'-1/2" OF WORKING CLEARANCE FOR INVERTERS AS PER NEC 110.26(A)(3) OR TO THE HEIGHTOF THE EQUIPMENT, WHICHEVER IS GREATER.

KEYED NOTES:

1. PROVIDE #10 COPPER (FEEDER A) EQUIPMENT GROUND CONDUCTOR (EGC) FROM THE INVERTER GROUND BARTO RACK ON ADJOINING ROW. EGC SHALL BE RUN WITH ASSOCIATED STRING FEEDERS.

2. PROVIDE #8 COPPER (FEEDER B) EQUIPMENT GROUND CONDUCTOR (EGC) FROM INVERTER GROUND BUS BARTO ASSOCIATED DISTRIBUTION PANEL BOARD. EGC SHALL BE RUN IN CONDUIT WITH ASSOCIATED AC OUTPUTCONDUCTORS.

3. PROVIDE #1 ALUMINIUM (FEEDER C) EQUIPMENT GROUND CONDUCTOR (EGC) FROM PV DISTRIBUTION PANELINVERTER TO PV MAIN DISTRIBUTION PANEL BOARD. EGC SHALL BE RUN IN CONDUIT WITH ASSOCIATED ACOUTPUT CONDUCTORS.

4. PROVIDE ARRAY GROUNDING ELECTRODE THE LENGTH OF ARRAY.

5. PROVIDE #6 BARE COPPER (FEEDER L) BONDING JUMPER VIA IRREVERSIBLE CRIMP FROM ARRAY SUPPLEMENTALGROUNDING CONDUCTOR IN TRENCH TO POST OF RACKING. IRREVERSIBLE CRIMP SHALL BE UL LISTED FORGROUNDING AND BONDING. ENSURE ALL CONNECTIONS ARE TORQUED TO MANUFACTURER'S SPECIFICATIONS.

6. PROVIDE #6 BARE COPPER (FEEDER L) BONDING JUMPER VIA IRREVERSIBLE CRIMP FROM ARRAY SUPPLEMENTALGROUNDING CONDUCTOR IN TRENCH TO THE INVERTER AND DISTRIBUTION PANEL BOARD MOUNTINGSTRUCTURE. IRREVERSIBLE CRIMP SHALL BE UL LISTED FOR GROUNDING AND BONDING.

7. GROUNDING STRAP FROM THE GEAR RACK TO THE POST PROVIDED BY RACKING MANUFACTURER.

8. THE GEAR BOX COUPLES TO THE TORQUE TUBE THROUGH MECHANICAL MEANS WHICH CREATES A PROPERGROUNDING CONNECTION. THE SOLAR MODULES AND THE TORQUE TUBE ARE GROUNDED BY MEANS OFINTEGRATED GROUNDING CLIPS ON THE MODULE CLAMP.

9. BOND ARRAY GROUNDING ELECTRODE VIA IRREVERSIBLE CRIMP.

#

1PV5.1

SCALE: NTSSIDE ELEVATION - RACK GROUNDING2

14

9 9 9

9999

O O O O

9

1

7

A 2 B

4 O

5L 6 L 3 C

8

9

9

A1-4

A1-3

A1-2

A1-1

A2-3

A2-2

A2-1

A1-5

A3-2

A3-1

A2-5

A2-4

A4-1

A3-5

A3-4

A3-3

A4-5

A4-4

A4-3

A4-2

A5-4

A5-3

A5-2

A5-1

A6-3

A6-2

A6-1

A5-5

A7-2

A7-1

A6-5

A6-4

A8-1

A7-5

A7-4

A7-3

A8-5

A8-4

A8-3

A8-2

A9-4

A9-3

A9-2

A9-1

A10-3

A10-2

A10-1

A9-5

A10-5

A10-4

B1-2

B1-1

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SCALE: 1/16"=1'-0"PARTIAL PLAN - STRINGING LAOUT PV_A1

GENERAL NOTES:

1. EACH STRING SHALL BE LABELED AS DESIGNATED WITH SHRINK TUBE.

2. LABELS SHALL BE LOCATED AT CONNECTOR ON BOTH POSITIVE AND NEGATIVE SIDES, AND AT THE CONNECTOR BOX.

PART

IAL

PLAN

- ST

RIN

G LA

YOU

T PV

_A

PV3.0

A#-##

SCALE: NONETYPICAL ONE STRING DETAIL2

NEGATIVE END OF PV SOURCE CIRCUIT

POSITIVE END OFPV SOURCE CIRCUIT

SOURCE CIRCUIT NUMBER

INVERTER DESIGNATION

15

A10-5

A10-4

B1-2

B1-1

B2-1

B1-5

B1-4

B1-3

B2-5

B2-4

B2-3

B2-2

B3-4

B3-3

B3-2

B3-1

B4-3

B4-2

B4-1

B3-5

B4-5

B4-4

B5-2

B5-1

B6-1

B5-5

B5-4

B5-3

B6-5

B6-4

B6-3

B6-2

B7-4

B7-3

B7-2

B7-1

B8-3

B8-2

B8-1

B7-5

B8-5

B9-1

B9-2

B9-4 B10-2

B10-1

B9-5

B10-4

B10-3

B10-5

B9-3

B8-4

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SCALE: 1/16"=1'-0"PARTIAL PLAN - STRINGING LAOUT PV_B1

PART

IAL

PLAN

- ST

RIN

G LA

YOU

T PV

_B

PV3.1

GENERAL NOTES:

1. EACH STRING SHALL BE LABELED AS DESIGNATED WITH SHRINK TUBE.

2. LABELS SHALL BE LOCATED AT CONNECTOR ON BOTH POSITIVE AND NEGATIVE SIDES, AND AT THE CONNECTOR BOX.

A#-##

SCALE: NONETYPICAL ONE STRING DETAIL2

NEGATIVE END OF PV SOURCE CIRCUIT

POSITIVE END OFPV SOURCE CIRCUIT

SOURCE CIRCUIT NUMBER

INVERTER DESIGNATION

16

C1-4

C1-3

C1-2

C1-1

C2-3

C2-2

C2-1

C1-5

C3-2

C3-1

C2-5

C2-4

C4-1

C3-5

C3-4

C3-3

C4-5

C4-4

C4-3

C4-2

C5-4

C5-3

C5-2

C5-1

C6-3

C6-2

C6-1

C5-5

C7-2

C7-1

C6-5

C6-4

C8-1

C7-5

C7-4

C7-3

C8-5

C8-4

C8-3

C8-2

C9-4

C9-3

C9-2

C9-1

C10-3

C10-2

C10-1

C9-5

C10-5

C10-4

D1-2

D1-1

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SCALE: 1/16"=1'-0"PARTIAL PLAN - STRINGING LAOUT PV_C1

PART

IAL

PLAN

- ST

RIN

G LA

YOU

T PV

_C

PV3.2

GENERAL NOTES:

1. EACH STRING SHALL BE LABELED AS DESIGNATED WITH SHRINK TUBE.

2. LABELS SHALL BE LOCATED AT CONNECTOR ON BOTH POSITIVE AND NEGATIVE SIDES, AND AT THE CONNECTOR BOX.

A#-##

SCALE: NONETYPICAL ONE STRING DETAIL2

NEGATIVE END OF PV SOURCE CIRCUIT

POSITIVE END OFPV SOURCE CIRCUIT

SOURCE CIRCUIT NUMBER

INVERTER DESIGNATION

17

C10-5

C10-4

D1-2

D1-1

D2-1

D1-5

D1-4

D1-3

D2-5

D2-4

D2-3

D2-2

D3-4

D3-3

D3-2

D3-1

D4-3

D4-2

D4-1

D3-5

D4-5

D4-4

D5-2

D5-1

D6-1

D5-5

D5-4

D5-3

D6-5

D6-4

D6-3

D6-2

D7-4

D7-3

D7-2

D7-1

D8-3

D8-2

D8-1

D7-5

D10-5

D8-5

D8-4

D9-1

D9-4

D9-3

D9-5 D10-4

D10-3

D10-2

D9-2 D10-1

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

N

KEY PLAN - OVERALL ARRAY

SCALE: 1/16"=1'-0"PARTIAL PLAN - STRINGING LAOUT PV_D1

PART

IAL

PLAN

- ST

RIN

G LA

YOU

T PV

_D

PV3.3

GENERAL NOTES:

1. EACH STRING SHALL BE LABELED AS DESIGNATED WITH SHRINK TUBE.

2. LABELS SHALL BE LOCATED AT CONNECTOR ON BOTH POSITIVE AND NEGATIVE SIDES, AND AT THE CONNECTOR BOX.

A#-##

SCALE: NONETYPICAL ONE STRING DETAIL2

NEGATIVE END OF PV SOURCE CIRCUIT

POSITIVE END OFPV SOURCE CIRCUIT

SOURCE CIRCUIT NUMBER

INVERTER DESIGNATION

18

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

PART

IAL

PLAN

-EQ

UIP

MEN

T PA

D DI

MEN

SIO

NS

PV4.0

SCALE: 1/2"=1'-0"PARTIAL PLAN - EQUIPMENT PAD DIMENSIONS1

LINE TYPE LEGEND:

CONCRETE PAD

EQUIPMENT

PROVIDED BY MANUFACTURER/ OTHERS

CONDUIT WINDOW

20'-6"

6'-0"

4'-6"

1'-6" 1'-6"1'-8" 1'-4"

2'-0"

6" 6"

6"6"

1'-0" 9"

4

5

81112 7

14 610

18 10"

KEYED NOTES:

1. REPRESENTS GPS, WIND STOW SWITCH, SITE DATA AND 4XCONTROLLER LEFT TO RIGHT.

8'-6"

10'-0"

8'-6"

9'-4"

1

7'-8"

6'-0" 2'-6"

2'-8"

2'-9"

3"

2'-0"

2'-0"

2'-0"

2'-0" 2'-0"

10"

13

6"

19

XX

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

PART

IAL

PLAN

-EQ

UIP

MEN

T PA

D AC

FEE

DER

ROU

TIN

G

PV4.1

SCALE: 1/2"=1'-0"PARTIAL PLAN - EQUIPMENT PAD AC FEEDER ROUTING1

LINE TYPE LEGEND:

CONCRETE PAD

EQUIPMENT

PROVIDED BY MANUFACTURER/ OTHERS

CONDUIT WINDOW

AC FEEDERS

MEDIUM VOLTAGE FEEDERS

4

5

81112 7

146

10

18113

TO PV DISTRIBUTIONPANELS

TO MV FUSED SWITCH

TO TRACKERMOTOR UNITS

C

D

H

G

F

E

M

KEYED NOTES:

1. REPRESENTS GPS, WIND STOW SWITCH, SITE DATA AND 4XCONTROLLER LEFT TO RIGHT.

20

XX

F

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

PART

IAL

PLAN

-EQ

UIP

MEN

T PA

D CO

MM

UN

ICAT

ION

S FE

EDER

RO

UTI

NG

PV4.2SCALE: 1/2"=1'-0"PARTIAL PLAN - EQUIPMENT PAD COMMUNICATIONS FEEDER ROUTING1

LINE TYPE LEGEND:

CONCRETE PAD

EQUIPMENT

PROVIDED BY MANUFACTURER/ OTHERS

CONDUIT WINDOW

COMMUNICATIONS

4

5

81112 7

146

10

18113

TO INVERTERS

TO TRACKERMOTOR UNITS

I

N

K

N

KEYED NOTES:

1. REPRESENTS GPS, WIND STOW SWITCH, SITE DATA AND 4XCONTROLLER LEFT TO RIGHT.

J K

21

XX

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

PART

IAL

PLAN

-EQ

UIP

MEN

T PA

D GR

OU

NDI

NG

PV4.3

SCALE: 1/4"=1'-0"PARTIAL PLAN - EQUIPMENT PAD GROUNDING1

LINE TYPE LEGEND:

CONCRETE PAD

EQUIPMENT

PROVIDED BY MANUFACTURER/ OTHERS

CONDUIT WINDOW

GROUND FEEDERS

4

57

18 2

13

TO ARRAY

TO MV FUSED SWITCH AND FENCE

O

KEYED NOTES:

1. PROVIDE IRREVERSIBLE BOND TO GROUND RING.

2. REPRESENTS GPS, WIND STOW SWITCH, SITE DATA AND 4XCONTROLLER LEFT TO RIGHT.

1

1 1

1

1

1 1

O

O O

O

O O

O

17 17

17 1717

O

L

1 1

O

22

XX

81112

1014

17

6

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

INVE

RTER

MO

UN

TIN

G DE

TAIL

PV5.0

23

SCALE: NTS TYPICAL (10) INVERTERS AND (1) PV DISTRIBUTION PANEL ELEVATION1

GENERAL NOTES:

1. TYPICAL (10) INVERTERS AND (1) PV DISTRIBUTION PANEL ELEVATION APPLIES IN 4 UNIQUE LOCATIONS:INVERTERS A1-A10 & PV_A INVERTERS B1-B10 & PV_B INVERTERS C1-C10 & PV_C AND INVERTERS D1-D10 & PV_D .

3'-6 5/8"TYP.

2'-2 1/2"TYP.

3'-0"TYP.

2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0"1'-8"

4'-2"

6'-6 5/8"

43'-9"

INVERTER INVERTER INVERTER INVERTER INVERTER

DISTRIBUTIONPANEL

INVERTER INVERTER INVERTER INVERTER INVERTER

REV

DATE

DESC

RIPT

ION

NRE

CASU

NDA

REF

EREN

CE D

ESIG

N1,

000K

Wac

, 1,0

00Vd

c, S

INGL

E AX

IS T

RACK

ER

TITL

E:

PRO

JECT

:

1609

HER

ITAG

E CO

MM

ERCE

CT

WAK

E FO

REST

, NC

2758

7PO

WER

SECU

RESO

LAR.

COM

THIS

LIN

E SH

OU

LDM

EASU

RE O

NE

INCH

DATE:

SHEET:10.21.2016

CON

FIDE

NTI

AL&

PRO

PRIE

TARY

PREL

IMIN

ARY

NO

T FO

RCO

NST

RUCT

ION

OF 24

FEN

CE G

ROU

NDI

NG

DETA

IL

PV5.1

24

SCALE: NTSFENCE GROUNDING DETAIL1

GENERAL NOTES:

1. ALL FENCE GROUNDING POINTS SHALL BE LOCATED WITHIN FENCE PERIMETER.

2. GROUND CORNER POSTS AND ADDITIONAL POSTS AT 500' INTERVAL.

3. GROUND ALL GATE POSTS.

KEYED NOTES:

1. PROVIDE EXOTHERMIC WELD TO TOP RAIL.

2. #6 BARE COPPER WIRE, TYPICAL UNLESS NOTED OTHERWISE.

3. PROVIDE SPLIT BOLT TO CONNECT WIRE TO FENCE FABRIC.

4. PROVIDE EXOTHERMIC WELD TO FENCE POST.

5. 3/4" X 10' COPPER CLAD GROUND ROD BONDED TO BARE COPPER.

6. FLEXIBLE GROUND BRAID SECURED TO GATE.

7. GATES SHALL BE BONDED TOGETHER.

FINISHED GRADE

1

2

3

4

5 5 5

4 46 6

3

1

3

1

7