XV EUROPEAN CONFERENCE MILANO 7 th -8 th JUNE 2013 CSG Latest Technology in Refrigeration and Air Conditioning Under the Auspices of the PRESIDENCY OF THE COUNCIL OF MINISTERS Optimization of combined heating and cooling in Supermarkets Torben Funder-Kristensen Head of Public Industry Affairs [email protected]

Upload: centro-studi-galileo

Post on 20-Jan-2015

160 views

Category:

Business


1 download

DESCRIPTION

 

TRANSCRIPT

XV EUROPEAN CONFERENCE MILANO 7th-8th JUNE 2013 CSG

Latest Technology in Refrigeration and Air Conditioning Under the Auspices of the PRESIDENCY OF THE COUNCIL OF MINISTERS

Optimization of combined heating and cooling in Supermarkets

Torben Funder-Kristensen

Head of Public Industry [email protected]

Content

Introduction

Balancing demands

The heat recovery concept

Why CO2 ?

CO2 compared to R404A

The Case of Heat Recovery

Heat balanceCOSP and COPTEWICOST

Conclusion

SubcriticalCO2

Transcritical & SubcriticalCO2

Transcritical& Subcritical CO2

SubcriticalCO2

Efficiency Limits of Transcritical CO2

SubcriticalCO2

Transcritical & SubcriticalCO2

Transcritical& Subcritical CO2

SubcriticalCO2

SubcriticalCO2

Transcritical & SubcriticalCO2

Transcritical& Subcritical CO2

SubcriticalCO2

EfficiencyLimits of Transcritical CO2

Balancing the triangle of demands

• Ensure safe solutions

• Ensure energy efficient solutions

• Ensure low direct emission

• Ensure affordable solutions

• The good thing is that it is possible with CO2 as refrigerant

TEWI Safety

Affordabillity

Leak tight Toxicity

COP

GWP

Flammabillity

Cost

Service

Hot water for sanitary purposesHot water for sanitary purposes Cooling for conservation of perishable foods

Cooling for conservation of perishable foods

Heating for comfortHeating for comfort

Introduction - a Super Market Needs

the scene is set for heat recovery…………..

The Heat Recovery Concept

Utilise the fact that cooling creates heat!

Design a system where the discharge gas is utilised to serve heating needs

Select the most suitable refrigerant

Ensure Cooling obligations

Optimise COSP

Heat lost to ambient

Heat used for heating

Cooling of products is a Heat source

COSP : Coefficient of System Performance

Why CO2?

Mature status as refrigerant for refrigeration – more than 2000 systems running in the EU

Temperature regulation within large temperature band of discharge gas

Efficiency less dependent on discharge temperature

Efficiency most dependent on return water temperature

Transcritical phase invites for high efficient counter flow heat exchangers

CO2 compared to R404A

• Many refrigerants are good at low Heat Recovery rates• CO2 is significantly superior at high temperatures

Heat Reclaim Case

Southern Denmark

Area: 1000 m2 from 2010

Compressors: 5 MT (1 VS), 4 LT

Cooling Capacity: 160 kW

Online COP calculation

Heating : Sanitary water (1800 l tank (65 oC )

Floor heating/low temp coils (35 oC )

Heating investments (add on) is less than 7000 €

MT Pack LT Pack

Performance of refrigeration system (COP)

The Heat Balance

The Heat recovery factor shows the potential for heat recovery

In this case during winter condition HRF = 2.6 at the sufficient cooling capacity

If the full Cooling capacity were utilised i.e. by utilising external evaporators the heating factor could be increased even more

COP : Coefficient of Cooling Performance

• Numbers are in kW• COP is set to average during day• Ventilation loss (Qvent ) is net zero due to

dehumidification

System set up in the case from Southern Denmark

Case results

COP is nearly constant

COSP fluctuates with the heating demand and increases with decreasing temperature – howver strongly influenced by other heating sources in the store

More than sufficient Heat available.

Case : TEWI comparison between systems

Heat recovery will increase compressor power consumption by close to 10 % due to temporary peak heating tasks

TEWI decreases significantly using CO2 and heat recovery. More than 30 % improvements was achieved compared to a conventional system with high direct emission

Minor TEWI decrease based on heat recovery alone

R404A system

CO2 Booster

CO2 Booster with heat recovery

Electricity : ½ kg CO2/kWHGas: 2 kg CO2 / M3Leakage rate 10%Charge: 200kg R404A (GWP =3922)

372 Tons CO2 per Year

-27%-34%

Case : Energy running cost comparison between systems

The CO2 booster system with heat recovery decreases overall energy cost with more than 20 %

Savings in running costs for topping up on refrigerants leaks are not considered

The CO2 system with Heat recovery increases Electricity cost up to 10% compared to systems without heat recovery.

Electricity : 0,14 € / kWhGas : 1,40 € / m3

R404A system

CO2 Booster

CO2 Booster with heat recovery

95.000 € per Year

-7%

-28%

Conclusion

• Supermarket applications are very suitable for improving overall system performance of CO2 systems using heat recovery

• The traditional CO2 weaknesses as high temperatures and pressures is turned into advantages using heat recovery

• TEWI can be reduced by 5-10 % using heat recovery

• Running cost can be reduced by more than 20% by introducing heat recovery and removing conventional heating sources

• Pay back has been proven to be very short on excess investments