SERVICE MANUAL
FILE NO. DAS-SM-00-003
AIR-CONDITIONER
SUPP M NT
SPLIT WALL TYPE
RAS-07YKH-E/RAS-07YAH-E
RAS-10YKH-E
/
RAS-10YAH-ERAS-13YKH-E/RAS-13YAH-E
RAS-07YKH-ES/RAS-07YAH-ES
RAS-10YKH-ES/RAS-10YAH-ES
RAS-13YKH-ES/RAS-13YAH-ES
-
8/10/2019 Toshiba conditioner.PDF
2/73 2
CONTENTS
1. SPECIFICATIONS.................................................................................... 3
2. CONSTRUCTION VIEWS ....................................................................... 7
3. WIRING DIAGRAM ................................................................................ 10
4. SPECIFICATIONS OF ELECTRICAL PARTS ..................................... 12
5. REFRIGERANT CYCLE DIAGRAM ..................................................... 15
6. CONTROL BLOCK DIAGRAM ............................................................. 21
7. OPERATION DESCRIPTIONS................................................................ 22
8. INSTALLATION PROCEDURE .............................................................. 30
9. TROUBLESHOOTING CHART.............................................................. 44
10. PART REPLACEMENT.......................................................................... 60
11. EXPLODED VIEWS AND PARTS LIST .............................................. 65
-
8/10/2019 Toshiba conditioner.PDF
3/73 3
RAS-10YKH-E/10YAH-E RAS-13YKH-E/13YAH-EMODEL
ITEM Cooling Heating Cooling Heating
220V240V 220V240V 220V240V 220V240VCapacity kW *1 2,652,70 3,003,10 3,453,50 4,004,10
Phase Single
V 220240Power source
Hz 50
Power consumption kW 0,981,02 0,890,91 1,261,30 1,191,27
Power factor % 9590 9588 9892 9593
V 220V240V 220V240V 220V240V 220V240VRunning current
Indoor/Outdoor A 0,11/4,58 - 0,11/4,61 0,11/4,17 - 0,11/4,22 0,15/5,70 - 0,15/5,75 0,15/5,54 - 0,15/5,44
Starting current A 19 14 25 25
Moisture removal lit/h 1,2 2,0
Indoor (H/M/L) dB (A) 41 / 36 / 29 41 / 36 / 29 44 / 39 / 34 44 / 39 / 34Noise(SPL at 1 meter) Outdoor (220240V) dB (A) 4749 4749 49 / 51 49 / 51
Name of refrigerant R-22Refrigerant
Rated volume kg 0,74 0,88
Refrigerant control Capillary tubeGas side size mm 9,52 12,7
Connection type Flare connection
Liquid side size mm 6,35
Connection type Flare connection
Maximum length (of one way) m *2 10 15Interconnection pipe
Maximum height difference
Indoor unit
Outdoor unitm
5 6
Condensate drain pipe Outer diameter mm 16
INDOOR UNIT RAS-10YKH-E RAS-13YKH-E
Height mm 265
Width mm 790Dimensions
Depth mm 189Net weight kg 8
Evaporator type Finned tube
Indoor fan type Cross flow fan
High fan m/h 600 650
Medium fan m/h 500 560Air flow rate
Low fan m/h 400 510
Fan motor output W 20
Air filter Polypropylene net filter (Washable)
OUTDOOR UNIT RAS-10YAH-E RAS-13YAH-E
Height mm 530 538
Width mm 770 780Dimensions
Depth mm 200 300
Net weight kg 31 42
Condenser type Finned tube
Outdoor fan type Propeller
Air flow rate (220240V) m/h 15001700 16901730
Fan motor output W 18 28
Model PH120T1-4C PH170T2-4L2Compressor
Output W 750 1100
Safety device Fuse, Overload relay
Auto louver Yes
Usable outdoor temperature range C 2143 -521 2143 -521
1. SPECIFICATIONS
RAS-10YKH-E / RAS-10YAH-E, RAS-13YKH-E / RAS-13YAH-E
Specifications are subject to change without notice.
-
8/10/2019 Toshiba conditioner.PDF
4/73 4
RAS-10YKH-ES / RAS-10YAH-ES, RAS-13YKH-ES / RAS-13YAH-ES
RAS-10YKH-ES/10YAH-ES RAS-13YKH-ES/13YAH-ESMODEL
ITEM Cooling Heating Cooling Heating
220V240VCapacity kW *1 2,652,70 3,003,10 3,453,50 4,004,10
Phase Single
V 220240Power source
Hz 50
Power consumption kW 0,981,02 0,890,91 1,261,30 1,191,27
Power factor % 9590 9588 9894 9793
V 220V240VRunning current
Indoor/Outdoor A 0,11/4,44 - 0,11/4,46 0,11/4,15 - 0,11/4,10 0,15/5,70 - 0,15/5,61 0,15/5,43 - 0,15/5,54
Starting current A 19 14 25 25
Moisture removal lit/h 1,2 2,0
Indoor (H/M/L) dB (A) 41 / 36 / 29 41 / 36 / 29 44 / 39 / 34 44 / 39 / 34Noise(SPL at 1 meter) Outdoor (220240V) dB (A) 4749 4749 49 / 51 49 / 51
Name of refrigerant R-410ARefrigerant
Rated volume kg 0,69 0,80
Refrigerant control Capillary tube
Gas side size mm 9,52
Connection type Flare connection
Liquid side size mm 6,35
Connection type Flare connection
Maximum length (of one way) m *2 10 15Interconnection pipe
Maximum height difference
Indoor unit
Outdoor unitm
5 6
Condensate drain pipe Outer diameter mm 16
INDOOR UNIT RAS-10YKH-ES RAS-13YKH-ES
Height mm 265
Width mm 790Dimensions
Depth mm 189
Net weight kg 8Evaporator type Finned tube
Indoor fan type Cross flow fan
High fan m/h 600 650
Medium fan m/h 500 560Air flow rate
Low fan m/h 400 510
Fan motor output W 20
Air filter Polypropylene net filter (Washable)
OUTDOOR UNIT RAS-13YAH-E RAS-13YAH-ES
Height mm 530 538
Width mm 770 780Dimensions
Depth mm 200 300
Net weight kg 31 42
Condenser type Finned tubeOutdoor fan type Propeller
Air flow rate (220240V) m/h 15001700 16901730
Fan motor output W 18 28
Model PA118X1T-4FZ PA160X2T-4FMCompressor
Output W 750 1100
Safety device Fuse, Overload relay
Auto louver Yes
Usable outdoor temperature range C 2143 -521 2143 -521
Specifications are subject to change without notice.
-
8/10/2019 Toshiba conditioner.PDF
5/73
-
8/10/2019 Toshiba conditioner.PDF
6/73 6
Note : *1 Capacity is based on the following temperature conditions.
CONDITION COOLING HEATINGTEMPERATURE
Indoor unit inlet air temperature
(DB) 27 C 20 C
(WB) 19 C 12 C
Outdoor unit inlet air temperature
(DB) 35 C 7 C
(WB) 24 C 6 C
Notes : *2 CHARGELESSRAS-07YKH-E, RAS-07YKH-ES, RAS-10YKH-E, RAS-10YKH-ES
No additional refrigerant required.
This air conditioner accepts a connection piping length of up to 10m and a head of up to 5m.
There is no need to add the refrigerant as long as the total length of the connection piping is up to 10m.
RAS-13YKH-E, RAS-13YKH-ES
No additional refrigerant required.
This air conditioner accepts a connection piping length of up to 15m and a head of up to 6m.
There is no need to add the refrigerant as long as the total length of the connection piping is up to 15m.
-
8/10/2019 Toshiba conditioner.PDF
7/73 7
2. CONSTRUCTION VIEWS
2-1. Indoor Unit
Air filter
790
Heat exchangerAir inlet
265
Air outlet47 1
0
50
189
4710
50
Knock out system
790
232 326 232
Hanger
321Drain hose (0,54m)
Connecting pipe (0,39m)
(Flare 6,35)(Flare 9,52)(Flare 12,7 for 13YKH-E only)
Hanger
65965,5
326
450
65,5
For stud bolt
(8~10)
For stud bolt
(6)
Hanger
Minimumdistanceto wall
Minimumdistanceto ceiling
265
178,
5
Knock out system
Front panel
Back body
20
20
37
40,
5
60,5
790
12626931976
Center line Installationplate outline
HangerHanger40,
5
3,
5
Hanger
Minimumdistanceto wall1
7
20
46
120 or more 120 or more
66 or more
2,
5
Connecting pipe (0,49m)
-
8/10/2019 Toshiba conditioner.PDF
8/73 8
2-2. Outdoor Unit
RAS-07YKH-E, RAS-07YKH-ES, RAS-10YKH-E, RAS-10YKH-ES
600 85
36 11125 Drain hole
50
302
16
230
8-6 Holes(For fixing the outdoor unit)
4-11x14 Long holes
(For anchor bolt 8-10)
Gas side (flare 9,52)
Liquid side (flare 6,35)
111
A600
R105036
252
16
230
11x14 Hole 6 Hole
Handle
11
525
530
5
268
Fan guard
420 TOSHIBA
770 59
89
200
11
12
Electricparts cover
Z
54 62
Serviceport
250
Z View600
45ormor
e
Inlet port
600 or more
(Minimum distanceof the wall)
4-11x14 Long holes
(For anchor bolt 8-10)
400ormore Outlet
port
Centerport
230
100 or more
Inlet port
Visible outlineof the product
A Detail Drawing
Mounting dimension of anchor bolt
268
77059
89
-
8/10/2019 Toshiba conditioner.PDF
9/73 9
RAS-13YAH-E, RAS-13YAH-ES
538
325
325
52,
5
23
301
325
300
Handle
25 Drain outlet
Electric parts cover
Serviceport
6154
325 (pitch) (8,5)(8,5)
342
100 or more
100 or more 600 or more
600 or more
Installation dimension
600
Air inlet
Air outlet
8-6 hole(for fixing outdoor unit)
Liquid side (Flare 6,35)
Gas side(Flare 12,7 for 13YAH-E,
Flare
9,52 for 13YAH-ES)
120
11x14 hole
6 hole
R10
600
Detail Drawing
5036
A
A
6-11x14 hole (for 8-10 anchor bolt)
600
100
130
780
90
59
27
Fan guard
420 Z
ViewZ
4x11x14 Long holes (for 8-10 anchor bolt)
-
8/10/2019 Toshiba conditioner.PDF
10/73
-
8/10/2019 Toshiba conditioner.PDF
11/73 11
RAS-13YKH-E / RAS-13YAH-ERAS-13YKH-ES / RAS-13YAH-ES
1 2 3 4 5 61 2 3 4 5 6
5 3 1 1 21 2
1 21 2
LN
FANMOTOR
WHI
WHI
PNK
BLK BLUBLU
RED
RED
RED
SOLENOIDCOIL
BLK
CAPACITOR
CAPACITOR
GRN & YELCHASSIS
INDOOR
OUTDOOR
RED
BLU
BLK
WHI
GRN&YEL
GRN&YEL
P04BLK
BRW
BLU
ORN
ORN
CN04 CN13
CN25
CN03CN10
C58 MCC-798
CN11 CN01
BLK
BLK
BLK
BLK
POWERSUPPLYCIRCUIT
C02
DC 12V
DB01R01C01
L01C15
R22
F01
6,3A
250V
R21
RY01RY02
WHI
CR01
CR02
RY04RY03
BLK
T02C.T
3
4
3
4
220V-240V50Hz
POWERTERMINALBLOCK
INDOORTERMINAL
BLOCK
THERMOSENSOR
(TA)
AC FAN MOTOR
HEATEXCHANGER
SENSOR(TC)
::::::::::
BROWNREDWHITEYELLOWBLUEBLACKGRAYPINKORANGEGREEN &YELLOW
BRWREDWHIYELBLUBLK
GRYPNKORN
GRN&YEL
COLOR IDENTIFICATION
VARISTOR
1987654321
98765
98765
4
4
3
3
2
2
1
1
221
SG01
DSA
1 2 35 3 11 2 3
YEL
BLK B
LK
BRW
PNK
WHI1
3
321 4
321 4
COMPRESSOR
BLU
PNK
BLK
WHI
BLU
BLU
BLU
BLU
BLU
OUTDOORTERMINAL
BLOCK
THERMALFUSE77C x 2
LOUVER MOTOR
12346 5PNK
YEL
ORN
RED
BRW
BLU
CN07 12346 5
DC 5VCR03 IC 03
INFRARED RAYS RECEIVEAND INDICATION PARTS
BLK
BLK
OVER LOADRELAY
THERMOSTATFOR
COMPRESSORSame as
figure.
COMPRESSOR
Detail B
Detail A
RAS-13YAH-ES RAS-13YAH-E
Same asfigure. BLK
A
B
RAS-13YAH-ES RAS-13YAH-E
-
8/10/2019 Toshiba conditioner.PDF
12/73
-
8/10/2019 Toshiba conditioner.PDF
13/73 13
4-2. Outdoor Unit
RAS-10YAH-E, RAS-10YAH-ES
RAS-13YAH-E, RAS-13YAH-ES
No. PARTS NAME MODELS TYPE SPECIFICATIONS
Output (Rated) 750W, 2poles, 1phase, 220240V, 50Hz
C-R C-SRAS-10YAH-E PH120T1-4C Winding resistance ()
(at 20C) 4,53 8,73
Output (Rated) 1100W, 2poles, 1phase, 220240V, 50Hz
C-R C-SRAS-13YAH-E PH170T2-4L2 Winding resistance ()
(at 20C) 2,22 3,04
Output (Rated) 750W, 2poles, 1phase, 220240V, 50Hz
C-R C-SRAS-10YAH-ES PA118X1T-4FZ Winding resistance ()
(at 20C) 3,17 5,18
Output (Rated) 1100W, 2poles, 1phase, 220240V, 50Hz
C-R C-S
1 Compressor
RAS-13YAH-ES PA160X2T-4FM Winding resistance ()(at 20C) 2,26 3,53
Output (Rated) 18W, 6poles, 1phase, 220240V, 50Hz
Red-Black White-BlackRAS-10YAH-E
RAS-10YAH-ESUE6-21SJ5P Winding resistance ()
(at 20C) 370 370
Output (Rated) 28W, 6poles, 1phase, 220240V, 50Hz
Red-Black White-Black
2Fan motor
(for outdoor)
RAS-13YAH-E
RAS-13YAH-ESAF-230-28P Winding resistance ()
(at 20C) 198 160
RAS-10YAH-E
RAS-10YAH-ESSK-50FMP1,5U1 AC 500V, 1,5F
3
Running
capacitor(for fan motor) RAS-13YAH-E
RAS-13YAH-ESSK-50FMP1,5U2 AC 500V, 1,5F
RAS-10YAH-E
RAS-10YAH-ESSK-40CMP25U1 AC 400V, 25F
4
Running
capacitor
(for compressor) RAS-13YAH-E
RAS-13YAH-ESSK-40CMP35U1 AC 400V, 35F
RAS-10YAH-E JMRA99269-9200 U/T : 6,8A (90C), OPEN 135 5C, CLOSE : 69 11C5 Overload relay
RAS-13YAH-E JMRA99257-9200 U/T : 8,0A (80C), OPEN 145 5C, CLOSE : 75 11C
6Thermostat
(for compressor)RAS-10YAH-E CS-7 OFF : 130C, ON : 70C
RAS-10YAH-ERAS-13YAH-E LB60012 AC 200 / 240V
7Solenoid coil
(for 4-way valve) RAS-10YAH-ES
RAS-13YAH-ESVHV-01A1501A1 AC 200 / 240V
-
8/10/2019 Toshiba conditioner.PDF
14/73
-
8/10/2019 Toshiba conditioner.PDF
15/73 15
5. REFRIGERANT CYCLE DIAGRAM
RAS-10YKH-E / RAS-10YAH-E
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
Evaporator
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating CoolingCompressor
Accumulator
Condenser
Propeller fan
Outdoor unit
Dryer
Capillary tube1,5x500
PH120T1-4C
CoolingHeating
Mark( )means check points of Gas Leak
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
Packed valve(9,52)
Packed valve(6,35)
0,39m(Connecting pipe)9,52
0,49m(Connecting pipe)6,35
T
P
RefrigerantR-22 0,74kg
Ambient temp.conditions DB/WB (C)50Hz
Standardpressure P(kg/cmG)
Surface temp. of heatexchanger interchanging
pipe T (C)
Fan speed(indoor)
Indoor Outdoor
Standard 15,0 40,0 High 21/ - 7/6High temperature *1 1923 52,059,0 Low 27/ - 21/15HeatingLow temperature 12,5 35,0 High 21/ - -10/-10
Standard 6,0 12,0 High 27/19 35/24
High temperature 6,5 15,0 High 32/23 43/26Cooling
Low temperature 4,0 2,0 Low 21/15 21/15
-
8/10/2019 Toshiba conditioner.PDF
16/73 16
RAS-13YKH-E / RAS-13YAH-E
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
Heat exchanger
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Gas container connection (Reinstall etc.)
Heating CoolingCompressor
Accumulator
Condenser
Propeller fan
Outdoor unit
Capillary tube1,2x400
PH170T2-4L2
CoolingHeating
Mark( )means check points of Gas Leak
O.D.:12,7mm O.D.:6,35mm
Cooling
Heating
Packed valve(12,7)
Packed valve(6,35)
0,49m(Connecting pipe)12,7
0,39m(Connecting pipe)6,35
T
P
RefrigerantR-22 0,88kg
Capillary tube1,7x400
Capillary tube0,6x1500
Ambient temp.conditions DB/WB (C)50Hz
Standardpressure P(kg/cmG)
Surface temp. of heatexchanger interchanging
pipe T (C)
Fan speed(indoor)
Indoor Outdoor
Standard 15,0 43,0 High 21/ - 7/6High temperature *1 1923 52,059,0 Low 27/ - 21/15HeatingLow temperature 12,5 35,0 High 21/ - -10/-10
Standard 5,0 10,0 High 27/19 35/24
High temperature 6,0 14,0 High 32/23 43/26Cooling
Low temperature 4,0 2,0 Low 21/15 21/15
-
8/10/2019 Toshiba conditioner.PDF
17/73 17
RAS-07YKH-E / RAS-07YAH-E
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
Ambient temp.conditions DB/WB (C)50Hz
Standardpressure P(kg/cmG)
Surface temp. of heatexchanger interchanging
pipe T (C)
Fan speed(indoor)
Indoor Outdoor
Standard 15,0 40,0 High 21/ - 7/6High temperature *1 1923 52,059,0 Low 27/ - 21/15HeatingLow temperature 12,5 35,0 High 21/ - -10/-10
Standard 6,0 12,0 High 27/19 35/24
High temperature 6,5 15,0 High 32/23 43/26Cooling
Low temperature 4,0 2,0 Low 21/15 21/15
Evaporator
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating CoolingCompressor
Accumulator
Outdoor unit
Dryer
Capillary tube1,5x1400
PH80T1-4C
CoolingHeating
Mark( )means check points of Gas Leak
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
Packed valve(9,52)
Packed valve(6,35)
0,39m(Connecting pipe)9,52
0,49m(Connecting pipe)6,35
T
P
RefrigerantR-22 0,63kg
Condenser
Propeller fan
-
8/10/2019 Toshiba conditioner.PDF
18/73 18
RAS-10YKH-ES / RAS-10YAH-ES
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
Evaporator
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating CoolingCompressor
Accumulator
Condenser
Propeller fan
Outdoor unit
Dryer
Capillary tube0,8x400
PA118X1T-4FZ
CoolingHeating
Mark( )means check points of Gas Leak
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
Packed valve(9,52)
Packed valve(6,35)
0,39m(Connecting pipe)9,52
0,49m(Connecting pipe)6,35
T
P
RefrigerantR-410A 0,69kg
Capillary tube1,2x400
MufflerMuffler
Ambient temp.conditions DB/WB (C)50Hz
Standardpressure P
(MPaG)
Surface temp. of heatexchanger interchanging
pipe T (C)
Fan speed(indoor)
Indoor Outdoor
Standard 2,5 43,0 High 20/ - 7/6High temperature *1 3,13,6 51,058,0 Low 27/ - 21/15HeatingLow temperature 2,2 36,0 High 20/ - -10/-10
Standard 0,9 10,0 High 27/19 35/24
High temperature 1,1 16,0 High 32/23 43/26Cooling
Low temperature 0,6 2,0 Low 21/15 21/15
-
8/10/2019 Toshiba conditioner.PDF
19/73 19
RAS-13YKH-ES / RAS-13YAH-ES
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
Heat exchanger
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating CoolingCompressor
Condenser
Propeller fan
Outdoor unit
Dryer
Capillary tube1,5x500
PA160X2T-4FM
CoolingHeating
Mark( )means check points of Gas Leak
O.D.:9,52mm O.D.:6,35mm
Cooling
Gas container connection (Reinstall etc.)
Packed valve(9,52)
Packed valve(6,35)
(Note)Maximum pipe length is 15mMaximum pipe head is 6m
0,49m(Connecting pipe)9,52
0,39m(Connecting pipe)6,35
T
P
RefrigerantR-410A 0,80kg
Capillary tube1,2x1200
Muffler
Ambient temp.conditions DB/WB (C)50Hz
Standardpressure P
(MPaG)
Surface temp. of heatexchanger interchanging
pipe T (C)
Fan speed(indoor)
Indoor Outdoor
Standard 2,7 43,0 High 20/ - 7/6High temperature *1 3,23,6 52,057,0 Low 27/ - 21/15HeatingLow temperature 2,0 30,0 High 20/ - -10/-10
Standard 0,9 11,0 High 27/19 35/24
High temperature 1,0 14,0 High 32/23 43/26Cooling
Low temperature 0,6 2,0 Low 21/15 21/15
-
8/10/2019 Toshiba conditioner.PDF
20/73 20
RAS-07YKH-ES / RAS-07YAH-ES
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
Ambient temp.conditions DB/WB (C)50Hz
Standardpressure P(kg/cmG)
Surface temp. of heatexchanger interchanging
pipe T (C)
Fan speed(indoor)
Indoor Outdoor
Standard 2,5 43,0 High 20/ - 7/6High temperature *1 3,1-3,6 51,058,0 Low 27/ - 21/15Heating
Low temperature 2,2 36,0 High 20/ - -10/-10
Standard 0,9 10,0 High 27/19 35/24
High temperature 1,1 16,0 High 32/23 43/26Cooling
Low temperature 0,6 2,0 Low 21/15 21/15
Evaporator
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating CoolingCompressor
Accumulator
Outdoor unit
Dryer
Capillary tube1,2x900
PA79X1T-4FZ5
CoolingHeating
Mark( )means check points of Gas Leak
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
Packed valve(9,52)
Packed valve(6,35)
0,39m(Connecting pipe)9,52
0,49m(Connecting pipe)6,35
T
P
RefrigerantR-410A 0,73kg
Condenser
Propeller fan
-
8/10/2019 Toshiba conditioner.PDF
21/73
21
Infrared Rays Signal Receiver
Current Sensor
Thermo. Sensor
Functions
Louver Control
3-minutes Delay at Restart for Compressor
Motor Revolution Control
Processing (Temperature Processing)
Timer
ECONO.
Louver Direction Setting
Louver AUTO Swing
OFF TIMER Setting
ON TIMER Setting
Fan Speed Selection
Thermo. Setting
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Operation (START/STOP)
Relay Driver, Louver Driver
Clock FrequencyOscillator Circuit
Heat Exchanger Sensor
Infrared
RaysInitializing Circuit
C. P. UMain Unit Control Panel
AC 220/230/240V ~
50Hz
Remote Control
Lo
ON/O
4-Way Valve
ON/OFF Signal
Outdoor Fan
ON/OFF Signal
Compressor
ON/OFF Signal
RelayRelayRelay
4-Way VOutdoor Fan MotorCompressor
(Compressor Current)
Relay
RY02
RY01 RY03
Noise Filter
Power Supply
Circuit
-
8/10/2019 Toshiba conditioner.PDF
22/73 22
7. OPERATION DESCRIPTIONS
7-1. FAN ONLY Operation
(MODE of the remote control : FAN ONLY)
(1) During this mode, the relay RY01 is alwaysturned off so that only the indoor fan is operated.
RY02 is always turnd on.1) When the FAN is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-1-1.
2) When the FAN is set to LOW, MED, or HIGH,
the indoor fan motor operates with a constantin volume as listed in Table 7-1-1.
7-2. COOL Operation
(MODE of the remote control : COOL)
(1) Compressor, 4-way valve, outdoor fan andoperation display are controlled as shown in Fig.
7-2-1.
Fig. 7-2-2
(3) Once the setting is made, the operation mode ismemorized in the microcomputer so that the
same operation can be effected thereafter simplyby pushing the START/STOP button.
Fig. 7-2-1
(2) Relays RY01 and RY02 are turned on to ener-
gize the outdoor unit, and a cool operation iscarried out.
1) When the FAN is set to AUTO, the indoor fanmotor operates as shown in Fig. 7-2-2.
2) When the FAN is set to LOW, MED, or HIGH,
the indoor fan motor operates with a constantin volume as listed in Table 7-1-1.
(Roomt
emp.
Settemp.)
MED
*For model : RAS-07YKH-E, RAS-07YKH-ES LOW(+)
LOW
LOW(continuous)
+4
+3
+2
+1
0
RY01
OFF
Settemp.
Manual
FAN
Accordingto the setposition
HIGH
AUTO
HIGH
MED
LOW(+)
LOW
LOW
28
27
26
25
24
(Roomtemp.
Settemp.)
Settemp.
Fig. 7-1-1 Auto setting of air volume
Table 7-1-1 Manual setting of FAN SPEED
Indication of
FAN SPEED
LOW
MED
HIGH
HIGH Air volume (m3/hr)
RAS-10YKH-E RAS13-YKH-ERAS-10YKH-ES RAS13-YKH-ES
400(430)* 510
500(490)* 560
600(550)* 650
(Roomt
emp.
Settemp.)
+1
0Settemp.
ON
OFF
4-way
valve
(RY
04)
Outdo
orfan
(RY
03)
OPER
ATION
display
ON
OFF
OFFON ON
Comp
ressor
(RY
01)
Commonrelay
(RY
02)
(2) Once the setting is made, the operation mode is
memorized in the microcomputer so that thesame operation can be effected thereafter simply
by pushing the START/STOP button.
-
8/10/2019 Toshiba conditioner.PDF
23/73 23
7-2-1. Louver Control
(1) By pushing the SET button of the remote controlduring the operation, the louver can be set to the
desired position.
And the louver position is stored in the micro-computer, the louvers will be set to the positionautomatically at the next operation.
(2) When the AUTO button is pushed, the louververtically swings within range of 25deg.
7-3. DRY Operation
(MODE of the remote control : DRY)
(1) Compressor 4-way valve, outdoor fan and
operation display are controlled as shown in Fig.7-3-1.
(Roomtemp.S
ettemp.)
Settemp.
OFF ON
+3
+2
+1
0
OFF
4-wayvalve
(RY04)
Outdoorfan
(RY03)
OPERATION
display
Compressor
(RY01)
Commonrelay
(RY02)
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
ON
Fig. 7-3-1
The microprocessor turns the compressor onand off at regular intervals (4 to 6 minutes onand/or off). During the compressor off, the
indoor fan will operate in the super lowposition.
The indoor fan will operate in the AUTOposition.
(2) The pattern of operation depending on therelation between room temperature and set
temperature is shown below:
Room temp.
Set temp.+1
Set temp.
Compressor
Outdoor fan
Indoor fan L. *S.L. S.L.L. L. S.L. L.
ON ON ON ON
OFF OFF OFF
*Super Low
Fig. 7-3-2
7-4. HEAT Operation
(MODE of the remote control : HEAT)
(1) Relays compressor 4-way valve, outdoor fan andoperation display are controlled as shown in Fig.7-4-1.
Fig. 7-4-2
(3) Once the setting is made, the operation mode ismemorized in the microcomputer so that the
same operation can be effected thereafter simplyby pushing the START/STOP button.
Fig. 7-4-1
(2) Relays RY01 and RY02 are turned on to ener-gize the outdoor unit, and a heat operation is
carried out. The indoor fan motor operates asshown in Fig. 7-4-2, when the FAN is set to
AUTO.
The motor operates with a constant air volume
as listed in Table 7-1-1, when the FAN is set toLOW, MED, or HIGH.
0
1
ON
OFF
ON
OFFONON ON
(Roomtemp.
Settemp.)
4-wayvalve
(RY04)
Outdoorfan
(RY03)
OPER
ATION
dis
play
Comp
ressor
(RY01)
Comm
onrelay
(RY02)
(Roomt
emp
.Settemp.)
0
-1
-2
-3
-4
Settemp.
MED
RY01 OFF
MED(-)
LOW(+)
LOW
FAN
ManualAUTO
Accordingto the setposition
-
8/10/2019 Toshiba conditioner.PDF
24/73
-
8/10/2019 Toshiba conditioner.PDF
25/73
-
8/10/2019 Toshiba conditioner.PDF
26/73 26
7-8. High-Temperature Limit Control
(Heating Operation)
The microprocessor detects the indoor heat ex-changer temperature so as to prevent exceeding thecondensate pressure.
Control is performed as shown in Fig. 7-8-1.
60
53
52
(C)Compressor,Outdoor fan
OFF
ON
*1 Only outdoor fan is turned off.
*1
Heat exchangertemperature
Fig. 7-9-1
RAS-13YKH-E, RAS-13YKH-ES
Compressor
Less than 2C continuesfor 5 minutes
OFF
ON
Outdoor fan
6
Heat exchangertemperature
2
(C)
Fig. 7-8-1
7-9. Low-Temperature Limit Control(Cooling Operation)
The microprocessor detects the indoor heat ex-changer temperature so as to prevent freezing up theindoor heat exchanger.
Control is performed as shown in Fig. 7-9-1 and 7-9-2.
RAS-07YKH-E, RAS-07YKH-ES, RAS-10YKH-E, RAS-10YKH-ES
Compressor
Less than 5C continuesfor 5 minutes
OFF
ON
Outdoor fan
7
Heat exchangertemperature
5
(C)
Fig. 7-9-2
According to theset position
Indoor fan speed
35
32
30
20
Heat exchangertemperature
(C)
U.L. (Ultra Low)
Room temp.
Set temp.S.L (Super Low)
Room temp.
Set temp.OFF
>