total solution catalogue for web - request rejectedtnblnx3.tnb.com/emalbum/albums/emergi-lite...

100
Fire Product Catalogue 2008

Upload: voliem

Post on 08-Mar-2018

214 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Fire Product Catalogue 2008

FirePro

du

ctC

ata

log

ue

2008

UK OFFICE

Thomas & Betts Limited

Emergi-Lite Safety Systems

Bruntcliffe Lane

Leeds

West Yorkshire

LS27 9LL

United Kingdom

Tel +44 (0)113 281 0600

Fax +44 (0)113 281 0601

[email protected]

www.emergi-lite.co.uk

All enquiries to UK office

www.tnb-europe.com

MIDDLE EAST OFFICE

Thomas & Betts Ltd. Br.

Office 107 5EA East Wing

Dubai Airport Free Zone

PO Box 54567

Dubai

United Arab Emirates

Tel +9714 - 6091635

Fax +9714 - 6091636

E-mail: [email protected]

SOUTH EAST ASIA OFFICE

Thomas & Betts Asia (Singapore) Pte Ltd

10 Ang Mo Kio Street 65

#06-07 Techpoint

Singapore 569059

Tel +65 6720 8828

Fax +65 6720 8780

The content of this Thomas & Betts catalogue has been carefully checked for accuracy at the time of print. However, Thomas & Bettsdoesn’t give any warranty of any kind, express or implied, in this respect and shall not be liable for any loss or damage that may resultfrom any use or as a consequence of any inaccuracies in or any omissions from the information which it may contain. E&OE.

Copyright Thomas & Betts 2008. Copyright in these pages is owned by Thomas & Betts except where otherwise indicated. No part of thispublication may be reproduced, copied or transmitted in any form or by any means, without our prior written permission. Images, trademarks, brands, designs and technology are also protected by other intellectual property rights and may not be reproduced orappropriated in any manner without written permission of their respective owners. Thomas & Betts reserves the right to change andimprove any product specifications or other mentions in the catalogue at its own discretion and at any time. These conditions of use aregoverned by the laws of the Netherlands and the courts of Amsterdam shall have exclusive jurisdiction in any dispute.

FPC-PG108

HQ ASSESSED TO BS EN ISO9001: 2000FOR THE MANAGEMENT OF EMERGENCY

LIGHTING AND FIRE DETECTIONEQUIPMENT AND THE MODIFICATION OFMAINS LUMINAIRES FR EMERGENCY

LIGHTING APPLICATIONSCert no: FM09470

A member of theLIGHTING INDUSTRY FEDERATION

Note: The Emergi-Fire range from Emergi-Lite focuses on the specific needs of our customers for firealarm and detection solutions. Products, packaging, documentation, imagery and invoicing may displayeither the Emergi-Fire and/or Emergi-Lite logo.

Fire Product Catalogue Cover 22/4/08 10:05 Page 1

Page 2: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

The Emergi-Lite portfolio from Thomas & Bettsdelivers a highly versatile choice of emergencylighting and fire detection products and systemsfor a wide range of applications. Our aim is toenable customers to achieve the maximumbenefit in investment. This is gained throughproduct design, for quick and simple installationwith inherent energy efficiency and minimummaintenance, whilst keeping the protection andsafety of human life paramount.

Since 1998, the Emergi-Lite brand has been included

in the product portfolio of the Thomas & Betts

Corporation.

In 1898 Thomas & Betts was founded in New York.

The corporate headquarters now reside in Memphis,

Tennessee with the company being listed on the

New York stock exchange. Thomas & Betts has now

over 100 years of experience of successfully supplying

quality products to the market by using innovative

design and manufacturing techniques. A truly global

player having a presence in Europe, North & Central

America, Australia and the Far & Middle East.

Worldwide 13,000 employees are dedicated to

ensuring that Thomas & Betts is fast, flexible and

customer focussed.

Whilst one of our main businesses remains in the

electrical products, among which Emergency Lighting

and Fire Detection Systems, Thomas & Betts

also has leading brands along with significant market

share in Steel Structures, Communications, Electronic

Systems Protection and Earthing & Lightning

Protection.

In recent years, Thomas & Betts has developed a

formidable European safety products division, the

principal products of which are emergency lighting

and fire detection systems. This division serves as a key

knowledge platform. Emergi-Lite being one of the

leading brands within this division, benefits from the

economies of scale in product development and

production, facilitating the efficient further

development of emergency lighting and

fire detection technology.

Home to many well known brands and with over 100 years experience, Thomas & Betts provides a truly world-classlevel of quality, service and support. The electrical division in Europe provides the following key products:

Electrical products

An impressive range of high quality products

to fasten, install, insulate, protect and connect

electrical cables, with the confidence to achieve

a highly professional result.

Premium cable ties for the most demanding

applications, including the Ty-Rap® cable ties with a

steel locking barb and the Ty-Met™ self-locking

stainless steel ties.

A wide variety of multi-purpose heat shrink tubing

for use in insulation, protection, identification and

strain relief.

A broad range of solderless termination systems

for a variety of applications, including power

cables, shielded cables and magnet wire.

A range of liquidtight flexible conduits & fittings

for the protection of electrical cables in industrial

applications, in metallic and non-metallic versions

(including Nylon conduits & fittings).

A new range of cast resin joints for splicing and

branching low voltage cables, in applications like

street, leisure and airfield lighting, utility & home

connections.

A range of spring steel fasteners for quick, easy

and reliable fixing of services to steelwork.

Earthing & Lightningprotection solutions

With Furse, T&B is leading in the design,

manufacture and supply of earthing and

lightning protection systems.

Through its range of products, Furse can provide

complete and innovative solutions for lightning

protection, surge protection and earthing

applications.

Emergency lighting &fire detection systems

Throughout Europe T&B is well represented on

the emergency lighting and fire detection

markets with various leading brands providing

dedicated solutions for safe evacuation of

buildings and sites.

Emergi-Lite Safety Systems is the provider of

advanced emergency lighting and fire detection

systems, with field project support at the design

stage through to commissioning and maintenance.

The emergency lighting engineers, providing

innovation and the latest technology to the OEM

lighting industry.

Kaufel, formerly known as NIFE, is a strong brand

in emergency lighting products and safety power

supply systems, among which product brands are

Sentara, Venter and Twister.

Kaufel supplies a complete range of dedicated

emergency lighting luminaries and central battery

and testing systems with product brands like Brio,

Elitt and Sesam.

VanLien provides a wide range of emergency

Lighting solutions, ranging from luminaries to

central battery systems with product brands like

Optilux, Aqualux and Serenga

Fire Product Catalogue Cover 22/4/08 10:06 Page 2

Page 3: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

1

Introduction 2Introducing Emergi-Lite Safety Systems and our expansive range of fire products and services

Analogue addressable 3 – 34Comprehensive selection of panels forming our ‘Anatec’ analogue addressable range, with appropriate FA95 andDiscovery devices

Conventional 35 – 70Our 2-wire and 4-wire Eurofire and Firetec panels with their associated devices

Wireless systems 71 – 74An introduction to our ‘AnX Wi-free’ wireless fire detection system and devices

Other systems 75 – 88Specific systems and accessories including air aspirating smoke detection, voice evacuation, audio-visual upgrades,Silent-Touch 2, protective call point covers and intrinsically safe devices

Commissioning and maintenance 89 – 90Essential support and after-sales service for fire detection systems

Reference and design 91 – 94A concise reference point to the standards and regulations affecting fire safety

Product index 95

Product reference guide 96

Contents

www.emergi-lite.co.uk Contents

FM09470

Waste Electrical and Electronic Equipment Regulations 2006 (“the WEEE Regulations”)The Government has introduced the Waste Electrical and Electronic Equipment Regulation 2006 (“WEEE”), which has been effective from 1st July 2007.

Producer ResponsibilityIn relation to lighting products, Thomas & Betts Ltd (Emergi-Lite Safety Systems) meets its producer responsibility via membership of the LumicomProducer Compliance Scheme (registration no. WEEE/DH0073UQ). Under this scheme, de-polluted luminaires (i.e. those with the lamps, batteries andliquid filled capacitors removed), which are being replaced by our fittings, will be recycled in an environmentally sound manner.

Recycling CostProducers (or their agents) are required to finance the environmentally sound disposal of non-household luminaires and the gas discharge lampswithin them. Therefore, with effect from 1st July 2007, there will be a recycling charge, which may vary from time to time.

Page 4: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Introduction

2

Products and servicesEmergi-Lite offers a wide range of fire detectionproducts and services to suit your individualrequirements, including:

Analogue addressable fire systems

Conventional 2-wire and 4-wire systems

Wireless fire systems

Air aspirating smoke detection

Voice evacuation

Audio-visual device upgrades

Intrinsically safe systems

Commissioning and ongoing maintenance services

For more specific or tailored requirements, such as fireprotection in marine environments, please contact oursales team for assistance.

Fire panels manufactured by Emergi-Lite are designedto comply with the appropriate parts of the Britishand European standards BS EN54, and are suitable forBS 5839-1:2002. Certain panels can be applied toBS 5839-6:2004 installations.

Emergi-Lite Safety Systems also enjoys partnershipsand close ties with a number of proprietary devicemanufacturers. All devices available are of the highestquality with many having been independentlycertified. For example, Alarmsense (ApolloFire Detectors Ltd) and other fire detectiondevices listed are acceptable forBS 5839-1:2002 and BS 5839-6:2004 systems.

QualityOur manufacturing facilities are certified toBS EN ISO-9001:2000 by BSI, with factory licenceFM09470.

Risk assessment and scheme designThe Regulatory Reform (Fire Safety) Order 2005/Fire (Scotland) Act 2005 is in force. ‘Fire RiskAssessment’ is now the responsibility of buildingowners/users and/or employers (the previous ‘firecertificate’ scheme is superseded).

As part of our project design service we can provideassistance from our trained sales team, with schemedesign to the appropriate emergency lighting or firealarm standards (free service). A ‘Fire AuthoritativeGuide’ is listed in our publications section.

WarrantyProducts manufactured and supplied by Thomas &Betts Ltd: Emergi-Lite Safety Systems (The Company)are covered by warranty subject to the limitations andconditions described in the Company General Termsand Conditions of Sale.

Emergi-Lite Safety Systems is a renowned manufacturer of fire detection & alarm systems, emergencylighting and related safety equipment and has served the safety market in the UK for over 16 years.

Emergi-Fire is the fire safety products brand within Emergi-Lite Safety Systems, part of theThomas & Betts group, which supplies electrical products worldwide.

www.emergi-lite.co.uk

Welcome to Emergi-Lite

PublicationsThe following publications relevant to fire detectionand safety can be purchased from Emergi-Lite.

Authoritative Guide to Advanced Fire AlarmSystem Design Techniques

A detailed technical publication for fire detection andalarm scheme design. It reviews the relevant laws andregulations, fire alarm design to BS 5839-1:2002 andadvanced system design, plus information is providedon radio linked systems, electrical safety andmaintenance.Order code: YFAG-606

Log Book: Fire Detection and Alarm Systems

Provides guidance as a supplement to BS 5839-1:2002.Space is provided for recording component lists,systematic logs, for making weekly test reports andnoting any modifications to the system in place.Order code: YLB-FD0807

Log Book: Emergency Lighting

Handy A4 booklet for recording of periodic emergencyluminaire tests as required by Emergency LightingStandard, BS 5266 part 8.Order code: YLB-EL0807

Page 5: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Analogue addressable

Analogue addressable

Analogue addressableAnatec Pro Series 4 – 7

Anatec-Lite Series 8 – 11

Product selector – Detectors, call points and alarms 12

Analogue addressable FA95 devices 13 – 16

Analogue addressable Discovery devices 17 – 20

Addressable loop powered alarm devices 21 – 26

Alternate addressable loop powered alarm devices 27

Interface modules 28 – 33

Loop isolators 34

www.emergi-lite.co.uk

3

Page 6: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Anatec Pro analogue addressable fire panels

Benefits and featuresOpen protocol:Enables another panel or other devices to be added toan installation to help future maintenance planningand cost control (note: it is not possible to mix withproducts which have a unique or closed protocol).

Digital transmission:Anatec Pro protocol translates device informationdigitally, so is less susceptible to corruption than ananalogue transmission system.

Loop drive capacity:Rated at 500mA (highly stable) to accommodate ahigh number of loop-powered sounders/devices.

Strength of processing power:Up to 126 addresses per loop may be configuredthrough cause and effect programming. Each loop isdriven by a separate processor to prevent completefailure in the unlikely event of a processing devicebreakdown.

Device recognition:Panel ‘Loop learn’ facility automatically identifiesnewly installed devices.

Device sensitivity modes, ’Pro Discovery’:A change to building use may require a change in theoperational function of the detection devices. Fivedifferent operating modes can be set according to thedemands of the premises. For example, it is possible toprogramme a timed changeover between heat andsmoke detection at selected times.

Liquid Crystal Display (LCD) & 32 zone indicators:A 4 line 20 character back lit LCD gives device details;address, zone and type status through to location text.Fire and fault LEDs localize to the zone.

Input – output flexibility:Up to 255 user definable inputs. Relay and two stagealarm outputs options available via expansion boards.

Sounder control programming:Complex patterns can be programmed to suitmodified escape routing or use of the building.Changes can be set from the panel including theisolation or disabling of a zone or an alarm etc.

Panel construction & installation:‘Pro Discovery’ panels have trim options in stainlesssteel or brass. Cabling to the panel is convenientthrough top and bottom access or rear knockouts.

Panel programming:Software tools including ‘cause and effect’ setup canbe applied from a laptop PC. User or Engineers menuis accessible via coded access panel controls.

Anatec Pro System – loop load calculator:Our sales engineers use software to check loadingcalculations, including battery standby capabilities,when preparing a scheme.

Installed system test:One person is able to test system devices includingsilent alarm test. Please refer to the operating manualor contact ‘Fire technical sales’ for further information.

The Anatec Pro family comprises a 1-2 loop basepanel (Anatec Pro Explorer – FADYXP prefix) anda 1, 2 or 4-loop high specification panel (AnatecPro Discovery – FADY prefix).

Anatec Pro Explorer is compatible with AnatecFA95 protocol devices and Anatec Discovery Prowith both Anatec FA95 and Discovery devices.

With Anatec Pro Discovery, devices from both AnatecFA95 and Discovery protocols can be mixed on thesame loop if necessary, enabling the maximum benefitof cost versus functionality. In addition to the featuresof Anatec Pro Explorer, it offers enhanced capabilitiesfor installations where extra intelligence and flexibilityare needed and setup requirements are more complexand involved.

Both Pro Explorer and Pro Discovery panels are fullycompliant with EN54 Parts 2 & 4 and are suitable forBS 5839 Part 1 installations.

4

www.emergi-lite.co.uk

Anatec Pro Series

Analogue addressable panels | Anatec Pro Series

Page 7: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

LCD & Zonal displayThe Anatec Pro series of fire panels all include an easy toreference, back-lit LCD display, allowing a maximum of 80characters, over four lines.

Fully configurable, the display shows details from deviceaddress, zone and type status through to location text. Userfunctionality is set over two levels – level 1 enables viewingof panel status only whereas level 2 offers secure codedaccess for panel and device programming. The panels arefurther enhanced by fire and fault LEDs which localize tothe zone.

Further features include:

One man walk test facility (device or sounder selectable)

Event history log with time and date stamp

Each panel includes a membrane keypad which is enabledeither automatically via lockable front door (FADY panels)or via panel mounted key-switch (FADYXP panels.)

Anatec Pro Discovery with stainless steel trim

To Order

Anatec Pro Explorer Panels

STANDARD ORDER CODE DESCRIPTION

FADYXP1/G Anatec Pro Explorer 1 loop fire panel, grey finish

FADYXP2/G Anatec Pro Explorer 2 loop fire panel, grey finish

OPTIONS

FADYRA Anatec Pro Explorer repeater panel

Suffix P Integral printer

Suffix N Network driver card

Anatec Pro Discovery Panels

STANDARD ORDER CODE DESCRIPTION

FADY1/G Anatec Pro Discovery 1 loop fire panel, grey finish

FADY2/G Anatec Pro Discovery 2 loop fire panel, grey finish

FADY3/G Anatec Pro Discovery 3 loop fire panel, grey finish

FADY4/G Anatec Pro Discovery 4 loop fire panel, grey finish

OPTIONS

FADYRB Anatec Pro Discovery repeater panel

Suffix P Integral printer

Suffix N Network driver card

Suffix A 8 Way programmable alarm

Suffix R 8 Way programmable alarm relay

ANATEC PRO DISCOVERY TRIM OPTIONS

Suffix BR Brass polished finish

Suffix PS Stainless steel finish

Suffix BS Brushed stainless steel finish

Suffix BZ Recessing bezel in trim finish

All trim options are available to special order. To order, replace suffix G (/G) with the preferred trimoption. For example:

Standard panel: FADY1/G (Anatec Pro Discovery 1 loop fire panel, grey finish)

Special order panel :FADY1PN/BSBZ

(Anatec Pro Discovery 1 loop fire panel including integral printerand network driver card, recessed with brushed stainless steelfinish

Anatec Pro Discovery with brass trim

Anatec Pro Discovery with brushedstainless steel trim

Anatec Pro Explorer panel

Anatec Pro Series | Analogue addressable panels

Anatec Pro Series

www.emergi-lite.co.uk

5

Page 8: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

6

www.emergi-lite.co.uk

Anatec Pro Series

Analogue addressable panels | Anatec Pro Series

Connection diagramThe diagram below indicates how the devices should be connected to a FADY panel (1 loop connected).

Sounder circuits

+ -NO P NCA B SCN

Earthfault

detect

BackLoopout

RepeaterNetwork

A B SCN A B SCN CLASS EVAC SILENCE RESET

FAULT FIRE1 FIRE2 ALM1 ALM2

Ou

t1+

Ou

t1-

In1-

In1+

LOOP1

LOOP2 LOOP3 LOOP4

+ - + + + + +- - - - -

Out In Out OutIn In

+ -

Loop card slots

1 2 3 4

28V 0V

Switches for loops &repeater configuration

Earth fault link

FAULT NO P NCNO P NC

I/O

ANATEC-PRO

o o

Auxiliary outputs, fire, fault

Alarm circuit

REPEATER

SCC

PSUo

M D

Loop 2

Loop 1

I/O

Doorretainers

AnX Wi-free fire zone: eachdevice has a loop address

Interface Interface

Conventional sounder circuit

Illustration: Anatec Pro - 2 loop example with networked repeater

Typical wiringBelow is a diagram of a typical analogue addressable loop fitted with a selection of detectors, loop poweredsounders, modules and isolators, all connected to a 2 loop panel. The diagram also illustrates how a series of firepanels can be networked together using the range’s powerful RS485 network.

The diagram is provided for illustration purposes only and you should always refer to the relevant panel/deviceinstructions as appropriate before installation. All devices illustrated are compatible with the Anatec range.

Wireless controller and loopinterface

Wireless detector

Wireless call point

Wireless sounder

o

I/O

SCC

Loop interface

Loop interface

KEY

o

Smoke detector

Manual call point

Loop sounder

Detector with loop beacon/sounder base

Standalone sounder

Standalone beacon

Page 9: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Analogue panelANATEC PRO EXPLORER ANATEC PRO DISCOVERY

SPECIFICATION FADYXP 1 or 2 loop FADY 1 to 4 loop

Loops/device capacity per loop:

No. of loops 1 or 2 1 to 4

Total addresses per loop 126 126

Total addresses per panel 252 504

Panel alarm circuits 2 by 1A per circuit, 2A total 2 by 1A per circuit, 2A total

Loop driver specification:

Loop loading (loop calculator available) 500mA maximum per loop 500mA maximum per loop

Detector & call point compatibility:

Protocols Anatec FA95 protocols Anatec FA95 and Discovery protocols

Power supply:

Mains input voltage 230Vac +10% –6% 230Vac +10% –6%

Internal power supply 24Vdc 24Vdc

Auxiliary output supply 20-28Vdc @ 500mA (max) 20-28Vdc @ 500mA (max)

Battery Standard 2 x 12V 7AH 2 x 12V 12AH

Optional: standby using loop calc Optional 2 x 12V 12AH –

Battery charger output 1.5A(max) 1.5A(max)

Auxiliary outputs 2 independent relays for fire and fault (rated at 1A at 30Vdc)

Auxiliary inputs 4 x fault, evacuate, silence and reset

Panel control & indicators:

Zone indicators 32 fire and fault LEDs 32 fire and fault LEDs

Panel display 4 line 20 character back-lit LCD 4 line 20 character back-lit LCD

Panel construction & wiring:

Construction Steel enclosure with key access to controls Steel enclosure with hinged front door

Colour Cool grey epoxy Cool grey epoxy as standard

Trim options – Brass, brushed or polished stainless steel

Dimensions HWD (mm) 410 x 330 x 130 410 x 555 x 130

Installation Detachable electronics allowing first fix installation Detachable electronics allowing first fix installation

Cable entry Via top and back entry knockouts Via top & back grommets, or bottom entry knockouts

Cabling requirements Complies with BS 5839-1:2002, section 26 for cables, wiring and other interconnections

Networking:

Serial network data Full networking using RS485 link Full networking using RS485 link

Interfaces (Printer/ PC):

Integral printer (parallel) Yes Yes

Options:

Alarm extender Housed in separate enclosure Integral option, 4 or 8 way

Relay extender Housed in separate enclosure Integral option, 4 or 8 way

Analogue repeater panel

SPECIFICATION FADYRA without power supply FADYRB with power supply

Connections DC power supply and network connections fromcontrol panel

Network connections from control panel and230Vac mains input voltage

Display 4 line 20 character back-lit LCD 4 line 20 character back-lit LCD

Battery size N/A 2 x 12V 7AH

Construction Cool grey epoxy steel enclosure Cool grey epoxy steel enclosure

Dimensions hwd (mm) 370 x 325 x 106 370 x 325 x 106

www.emergi-lite.co.uk

Anatec Pro Series

Anatec Pro Series | Analogue addressable panels

7

Technical specification

Networking capabilityWith the addition of a network card, the panels can be used as part of a global system with the facility to controland monitor a large networked site. Network cause/effect may be programmed between Anatec Pro 1-2 loop panels,1-4 loop panels and active repeater panels. The system operates as a global communication system and does notrequire a master panel or computer. This approach reduces the cost and avoids the problem of a total networkfailure associated with master panel configuration. Up to 15 panels or 60 loops may be used to create a network.Each panel can act independently and be programmed to respond selectively to other panels on the network.

The network card uses RS485 data communications, which will transmit up to 2km. Compact network repeaterpanels providing all essential control, and display facilities are available for manned control points.

Page 10: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Sounder control functions:Complex sounder control functions can be set fromthe panel including:

Individual sensitivity settings for each device

A phased evacuation facility

Adjustable contamination levels

Investigation delay period function

Zone dependency/coincidence functions

Day/night (building occupied/unoccupied) function

Panel programming:Particular site requirements can be uploaded/downloaded via an intuitive Windows based PCprogram that allows the system to be programmedquickly and easily. Sophisticated sounder groupmapping and complex cause and effect scenarioscan be easily implemented using the intuitiveupload-download programming software.

Networking capabilityThe ability to interconnect up to eight main panelsplus an additional four repeaters per main panel ontotwo-wire RS485 networks.

www.emergi-lite.co.ukAnalogue addressable panels | Anatec-Lite Series

Anatec-Lite Series

8

To OrderSTANDARD ORDER CODE DESCRIPTION

FANP116 Single loop 16 zone panel (FA95/Discovery),plastic enclosure

FANP132 Single loop 32 zone panel (FA95/Discovery),metal enclosure

FANP232 Two loop 32 zone panel (FA95/Discovery),metal enclosure

OPTIONS

FANP/RP16 16 zone repeater panel

FANP/RP32 32 zone repeater panel

Suffix N Network card

FANP1BAT1 Battery for FANP116 panel

FANP2BAT2 Battery for FANP132 & 232 panels

Anatec-Lite EN54 fire panels

Benefits and featuresDevice compatibility:Anatec-Lite is fully compatible with both Anatec FA95and Discovery protocol devices.

Digital transmission:The Anatec Pro protocol translates device informationdigitally. This type of signaling is less susceptible tocorruption than an analogue transmission system.

Loop drive capacity:Powerful short circuit protected loop drivers, capableof supporting up to 40-loop powered 10mA soundersper loop.

Input – output flexibility:

Two programmable inputs

A fault output relay and three programmablerelay outputs with voltage free changeovercontacts

Two independently programmable conventionalsounder circuits

Security control:secure push-button or keyswitch entry:Push button access code or keyswitch entry to AccessLevels 2 and 3 (depending on model purchased.)

The Anatec-Lite panel range is fully compliantwith EN54 parts 2 & 4 and offers the basis tobuild a powerful analogue addressable firesystem.

The range comprises a robust 1 or 2-loop 32-zoneversion in a metal enclosure complemented by a singleloop 16-zone version in a plastic enclosure. Togetherthey offer an array of user and installer-friendlyfeatures, including panel networking.

Anatec-Lite panels are compatible with Anatec FA95and Discovery devices, offering enhanced capabilitiesfor installations where extra intelligence and flexibilityare required.

Page 11: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk Anatec-Lite Series | Analogue addressable panels

Anatec-Lite Series

9

LCD & Zonal displayAn easy to read, 80-character back-lit display is fitted to show details from device address, zone and type statusthrough to location text. The panel is enhanced with features including:

40 characters of custom text programmable per device

999 event monitoring

Comprehensive test, maintenance &commissioning functions (including auto-learnloops, monitor a point, test outputs, one manwalk test and loop continuity test)

Earth fault monitoring

An alarm counter that records the number oftimes the panel has been in an alarm state (tomeet clause 7.13 of EN 54-2)

FunctionsAnatec-Lite panels have extensive programmablefunctions including:

Zone programming – to confirm a true state of fireZones can be programmed for three sets ofcircumstances to control sounding of fire alarms.

A zone: No action on the first detected alarm,unless there is a signal from another zoneconfirming a fire

B zone: The first detected alarm will be indicated,but a full fire condition will be flagged only whena detector signal from the same zone givesconfirmation

C zone: The panel enters a fire condition on thefirst detected alarm, but certain outputs areinhibited until the fire is confirmed from a secondsource

Day/night (building occupied/unoccupied) functionAllows the panel’s operational characteristics to bechanged at a pre-determined time. For example, fromthe engineers menu changes can be made to detectorsensitivity (high/low) & zone dependency settings.

Delay period function – to allow system investigationProgramable for time period, the zone(s) it applies toand whether or not it operates in day or night mode.

SoftwareSophisticated sounder group mapping andcomplex cause and effect scenarios can be easilyimplemented using the intuitive upload-download programming software.

Networking capabilityThe system can support eight interconnected panelsover a two-wire RS485 network. Single loop 16 zonepanels and 1 & 2 loop 32 zone panels may benetworked together. Any main panel can connect upto four repeaters. Up to 1 km of cable may be fittedto a network system.

Each networked panel can be programmed to:

Accept Faults from other panels

Accept Fires from other panels

Accept Control actions such as silence controlsounder, silence alarm sounders and reset fromother panels

Accept Disablement commands for zones,sounders and output sets from other panels

(Each of these four functions may be individuallyselected.)

All panels monitor all other panels for network wiringfaults. Fires on remote panels are displayed in detailon a local panel including the point description of theorigin of the alarm. Faults on remote panels aredisplayed in detail on a local panel including the pointdescription in the case of a detector.

Cause and effect can be programmed into a localpanel dependent on which remote panel is in alarm.The network supports programming of siteinformation into remote panels from a PC connectedat a local panel. Time and date is common to allpanels throughout the network.

All panels connected to the network need a networkdriver card.

Page 12: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.ukAnalogue addressable panels | Anatec-Lite Series

Anatec-Lite Series

10

Sounder circuits+ 1 -

LoopEarthfault

detect

FaultNC C NO

Relay 1 Relay 2 Relay 3NC C NO NC C NONC C NO

Auxiliary+24v i/p1 i/p2 0v + 2 - + B -+ A -

BackLoopout

ANATEC-L ANATEC-L REPEATER

SCC SMU

Air samplingdetector

o o

SMU

o

Auxiliary outputs, fire, fault

Alarm circuit

Optical beam detector& controller

InterfaceInterfaceInterface

PSU

Illustration: Anatec-Lite, 1 loop example with networked repeater

Connection diagramThe diagram below indicates how the devices should be connected to the panel.

Typical wiringBelow is a diagram of a typical analogue addressable loop fitted with a selection of detectors, loop poweredsounders, modules and isolators, all connected to a single loop panel. The diagram also illustrates how a series of firepanels can be networked together using the range’s powerful RS485 network.

The diagram is provided for illustration purposes only and you should always refer to the relevant panel/deviceinstructions as appropriate before installation. All devices illustrated are compatible with the Anatec range.

o

Smoke detector

Manual call point

Loop sounder

Detector with loop beacon/sounder base

Standalone sounder

Standalone beacon

Airsamplingdetector

SCC

SMU

Interface: Sounder circuitcontroller

Interface: Switch monitor unit

Beam detector controller

Aspirating smoke detectionsystem

Beam detector

KEY

Page 13: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

Anatec-Lite Series

Anatec-Lite Series | Analogue addressable panels

Technical specificationAnatec-Lite analogue addressable panel

1 loop, 16 zone 1/2 loop, 32 zoneProduct order code FANP116 FANP132/FANP232Loops/device capacity per loop:No. of loops 1 1 or 2Total addresses per panel 126 126/ 252Panel alarm circuits 2 2Loop driver specification:Number of loop drivers 1 FANP132: 1 / FANP232: 2Line monitored for open and short circuit faults Yes YesOnboard loop isolators with LED indication when active Yes YesAuto-polling from each loop end Yes YesLoop output current (max) 500mA 500mALoop powered sounders per loop, max @ 10mA 40 40No. of programmable sounder groups 15 15No. of programmable output sets 16 16Conventional sounder circuits:Number of programmable circuits 2 2End of line resistor value 6,800Ω 5% tolerance, 0.25 W 6,800Ω 5% tolerance, 0.25 WOpen & short circuit line monitoring Yes YesOutputs fused at 400mA 500mAMaximum number of sounders @ 20mA 40 50Detector & call point compatibility:Protocols Anatec FA95 and Discovery protocolsPower supply:Mains input voltage 230Vac ± 10% 50/60Hz 230Vac ± 10% 50/60HzInternal power supply 27Vdc Nominal 27Vdc NominalTotal output current limited to 1.4A @ 230Vac 3A @ 230VacSupply and battery charger monitored for failure Yes YesBatteries monitored for disconnection and failure Yes YesBatteries protected against deep discharge Yes YesBattery [separate product code] 3.2AH VRLA 7.0AH VRLAQuiescent current drain (1 loop unloaded) <50mA <80mAQuiescent current drain (2 loop unloaded) - <100mAFuses (to IEC EN 60127 pt 2):Mains fuse 1A HRC Ceramic 20mm 1A HRC Ceramic 20mmBattery fuse 3A F 20mm 3A F 20mmEarth fault monitoring Yes (any conductor) Yes (any conductor)Temperature compensated charging Yes YesAuxiliary outputs:Type Relay voltage free single pole changeoverMaximum switching current 1A 1AMaximum switching voltage 30Vdc 30VdcRelay 1 Programmed from cause and effectFault Active when no faults are present24V Aux power output 100mA. Protected by resettable overload circuitAuxiliary inputs:Input 1 and 2 Connect to 0V to trigger. Maximum input voltage 27Vdc (non-latching)Panel control & indicators:Control buttons Silence, Reset, Resound, Investigate; More information; MenuEvent scrolling and menu access buttons Up (1); Down (2); Accept (3); Abort (4)Zone indicators 16 32Panel display Two lines x 40 characters, back-lit Two lines x 40 characters, back-litOther LED indicators General Fire, System Energized; Pre-Alarm; Remote Output Activated; Menus Accessed; Disablement;

Test; Remote Output Disabled; Silenced; General Fault; System FaultPanel construction & wiring:Construction Plastic body and lid Metal body and lidColour Grey GreyDimensions, body hwd (mm) 380 x 235 x 77mm (plastic), includes ‘lip’ 410 x 250 x 80mm (metal)Dimensions, lid hwd (mm) 380 x 235 x 16mm (plastic) 439 x 274 x 7mm (metal)Weight kg (without batteries) 1.9 4.5Type of cable Fire resistant screened cable, minimum size 1mm2

Maximum cable length per loop 1km 1kmConnector blocks Plug-on type, maximum conductor size 1.5mm2

Networking:Connection Via CFP761 network driver card fitted at main panelMaximum number of main panels per network 8 8Maximum number of repeaters per main panel 4 4Maximum cable length per network 1km (daisy chain configuration) 1km (daisy chain configuration)Interfaces: Printer/ PCIntegral printer – Via main panel RS232 connector blockPC connection Via main panel RS232 Molex connector (lead supplied in XFP507 upload/download software kit)

11

Page 14: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

PRODUCT CODE DESCRIPTION

FA95 DETECTORSFA95-ACB Detector mounting base W 13FA95-ABB Detector mounting base B 13FA95-OPT Optical smoke detector W 14FA95-OPTB Optical smoke detector B 14FA95-MUS Multi-sensor detector W 14FA95-HDS Heat detector, grade A2S W 53 15FA95-HTT Heat detector, grade CS W 53 15FA95-300RS-ISO Manual call point R 16DISCOVERY DETECTORSFA95-ACB Detector mounting base W 17FA95-ABB Detector mounting base B 17FADY-OPT Optical smoke detector W 43 18FADY-TEM Heat detector W 53 18FADY-MUS Multi-sensor detector W 43 19FADY-CO Carbon monoxide detector W 43 19FADY-300-RS-ISO Manual call point R 53 20

FA95 LOOP ALARMSFA95-LPS-ISO Sounder base W 21FA95-BSNDR Local area sounder base W 22FA95-IBS-ISO Sounder base, integrated W 22FA95-LBB-ISO Beacon base W C 23FA95-LPSB-ISO Sounder beacon base W C 23FA95-LS100R Horn sounder R 24FA95-LS100R-WP Horn sounder R 65 24FA95-LS100W Horn sounder W 24FA95-LS100W-WP Horn sounder W 65 24FA95-LSBOR-ISO Horn sounder-beacon R 24FA95-LSBOW-ISO Horn sounder-beacon W 24FA95-LSBR65-ISO Horn sounder-beacon R 65 24FA95-LSBW65-ISO Horn sounder-beacon W 65 24FA95-KLSR Dome sounder R 65* 25FA95-KLSW Dome sounder W 65* 25FA95-KLBR Dome beacon R 65* R 25FA95-KLBW Dome beacon W 65* C 25FA95-KLSBR Dome sounder-beacon R 65* R 26FA95-KLSBW Dome sounder-beacon W 65* C 26FA95-LPBEA Beacon for base mount W R 26FA95-LPBEA-A Beacon for base mount W A 26

FAC95 ALTERNATIVE LOOP ALARM DEVICES (VISUAL & AUDIBLE)An alternate suite of analogue addressable sounders, suitable for where tone compatibility with other types of sounder is not an issue.FAC95-LS-5 Sounder base W 27FAC95-LBRDB Beacon R 65 C 27FAC95-LSR Sounder R 27FAC95-LSRDB Sounder R 65 27FAC95-LSW Sounder W 27FAC95-LSWDB Sounder W 65 27FAC95-LSBR Sounder-beacon R R 27FAC95-LSBRDB Sounder-beacon R 65 R 27FAC95-LSBW Sounder-beacon W R 27FAC95-LSBWDB Sounder-beacon W 65 R 27

* These devices are IP65 rated when used with deep base and gasket provided.

Anatec FA95 & Discovery devicesThe following pages highlight the range of detectors, call points, ancillary devices and alarms for bothAnatec FA95 and Discovery protocols. The table below offers an overview of device features andcapabilities to assist with planning and selection.

Feat

ure

s:

Body

Col

our:

R=

Red;

W=

Whi

te;

B=

Blac

k

IPra

ting:

Wea

ther

proo

f

Self-

test

faul

tm

onito

ring

Red

alar

mLE

D

Soun

der

Beac

on

Lens

colo

ur:

A=

Am

ber;

C=

Cle

ar;

R=

Red

Built

inis

olat

or

HTM

82lo

wvo

lum

ese

ttin

g

Apo

lloA

lert

/Ev

acto

ne

Con

stan

tto

ne

DIN

tone

100

dB(A

)

1H

zfla

shra

te

Inte

grat

edba

se

Loop

addr

essa

ble

Gro

upad

dres

sing

Mas

ter

/sl

ave

func

tion

Can

besy

nchr

onis

ed

Dis

cove

ry

Page

refe

renc

e

Analogue addressable panels | Product selector

Product selector – Analogue addressable devices

www.emergi-lite.co.uk

12

Page 15: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

With cutting edge design and improved performance, Anatec FA95 analogue addressable fire detectorsoffer many benefits to installers and users alike. The low profile device package employs a zeroinsertion force base, a user-friendly addressing methodology and extended data and alarm features.

Key features of Anatec FA95: Address Confirmation

Automatic Type Identification

Interrupt warning – for call-point speed of response

Analogue value reporting

Input bits reporting

Address card for simple user friendly and accurateidentification of detector location

Anatec FA95 Device Flag

Detector optionsThe detector range includes optical smoke and temperature sensors, and a multi-sensor device combining elementsof both.

Optical sensor operation:Smoke particles entering the chamber will scatter light from an internal LED onto a photo diode. Internal electronicsmeasures the voltage level from the photo diode and translates this into a digital signal which is sent to the CIE atthe next interrogation. The detector is calibrated using a digital count (equivalent to an analogue voltage) for cleanair and will flag an alarm when the count value exceeds 55 (the equivalent level at which smoke particles are presentabove a given threshold).

Heat sensor operation:A thermistor is used to measure temperature. The electronic network in the device generates a voltage levelproportional to the air temperature adjacent.

A standard manual call point is available. Other essential loop devices comprise isolators (including isolator base),loop powered sounders & sounder beacons and beam detectors. For connecting external devices a range ofcompatible interface units are available: input/output, zone monitors, sounder circuit controllers etc. Many devicesand interfaces are available with in-built isolators providing excellent loop integrity.

Detector mounting base FA95-ACB (white)

A common mounting base for Anatec FA95 and Discovery detectors.Features:

Stainless steel terminals

Fitted with a universal address card (FA95-XPC)

Grub screw for locking the detector

SPECIFICATION

Termination Terminals can take up to 2.5mm2 diameter wire

Construction White moulded polycarbonate

OPTION

FA95-ABB Detector mounting base (black body)

FA95-ACB

FA95-ABB

Analogue addressable detectors | Analogue addressable devices

Analogue addressabledetectors

www.emergi-lite.co.uk

13

Page 16: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.ukAnalogue addressable devices | Analogue addressable detectors

14

Optical smoke detector (white) FA95-OPT

Smoke particles entering the chamber will scatter light from an internalLED onto a photo diode. Internal electronics measure the voltage level andtranslate this into an analogue value which will be sent to the panel, whenit next interrogates the device.

Recommended for general purpose use to give early warning of fire.

Analogue addressabledetectors

Multi-sensor detector FA95-MUS

The unit combines both optical and temperature sensor processes to giveindication of a fire. It is sensitive to both smouldering and flaming fires(i.e. can be used where an ionisation type might have been usedpreviously.)

SPECIFICATION

Voltage range 17 – 28Vdc

Average quiescent current at 24V 500µA

Alarm level analogue value 55

Alarm indicator 2 clear LEDs, red light on alarm

Operating temperature –20 to +60ºC

Wiring & polarity 2 wire supply, polarity insensitive

Construction White moulded polycarbonate

Ingress rating IP23D

Dimensions ø d (mm) 100 x 50 (58 with base)

Weight g 105 (160 with base)

FA95-OPT

FA95-MUS

FA95-OPTB

SPECIFICATION

Voltage range 17 – 28Vdc

Average quiescent current at 24V 340µA

Alarm level analogue value 55

Alarm indicator Clear LED, red light on alarm

Operating temperature –20 to +60ºC

Wiring & polarity 2 wire supply, polarity insensitive

Construction Moulded polycarbonate

Ingress rating IP23D

Dimensions ø d (mm) 100 x 42 (50 with base)

Weight g 105 (157 with base)

Standards EN54-7: 2000

OPTION

FA95-OPTB Optical smoke detector (black body)

Page 17: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

15

www.emergi-lite.co.uk Analogue addressable detectors | Analogue addressable devices

Analogue addressabledetectors

Heat detector FA95-HTT

High temperature (CS)

The high temperature HTT model will register a fire at 90ºC, making itsuitable for boiler rooms, as well as other areas where the ambienttemperature is considered to be higher than normal room temperature(kitchens and factory hot work areas etc.)

SPECIFICATION

Voltage range 17 – 28Vdc

Average quiescent current at 24V 250µA

Alarm level analogue value 55

Alarm indicator Red light LED on alarm

Operating temperature –20 to + 70ºC

Wiring & polarity 2 wire supply, polarity insensitive

Construction White moulded polycarbonate

Ingress rating IP53

Dimensions ø d (mm) 100 x 42 (50 with base)

Weight g 105 (157 with base)

Standards EN54-5: 2000

FA95-HTT

Heat detector FA95-HDS

Fixed temperature (A2S)

The standard HDS heat detector responds to increasing air temperature andtriggers an alarm at 55ºC. This device is suitable for areas where theambient temperature is considered to be higher than normal roomtemperature, such as kitchens and factory hot work areas.

SPECIFICATION

Voltage range 17 – 28Vdc

Average quiescent current at 24V 250µA

Alarm level analogue value 55

Alarm indicator Red light LED on alarm

Operating temperature –20 to + 70ºC

Wiring & polarity 2 wire supply, polarity insensitive

Construction White moulded polycarbonate

Ingress rating IP53

Dimensions ø d (mm) 100 x 42 (50 with base)

Weight g 105 (157 with base)

Standards EN54-5: 2000

FA95-HDS

Page 18: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Analogue addressable devices | Call points/ancillary devices

Analogue addressablecall points/ancillary devices

Manual call point with isolator FA95-300RS-ISO

Fitted with frangible element. A key test facility is situated underside,which is fully reset when the key is removed.

Remote indicator unit FAP6-P10

A remote indicator is used to help an investigator quickly identify thelocation where a device has registered a fire, without having to gain entryto every room or inaccessible space.

SPECIFICATION

LED indicator Red

Termination Terminal block

Dimensions ø d (mm) 85 x 85 x 5

Weight g 38.2

www.emergi-lite.co.uk

16

SPECIFICATION

Voltage range 17 – 28Vdc

Average quiescent current at 24V 100µA

Alarm level analogue value 64

Alarm indicator Red LED on alarm

Operating temperature –20 to +60ºC

Wiring & polarity 2 wire supply, polarity insensitive

Construction Moulded polycarbonate

Ingress rating IP24

Dimensions hwd (mm) 89 x 93 x 26.5

Standards EN54-17: 2005

ACCESSORIES

FA95-3RS-COV Clear polycarbonate hinged call point cover

FA95-3RS-KEY10 Spare call point key (pack of 10)

RSL800 Fire call point notice sticker

FA95-300-RS-ISO

FAP6-P10

RSL800

o o

Remote indicator

Closed roomspace

Normaldetection:

Indicator visible

Corridor

Vision panel in doorSolid door

Page 19: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Discovery analogue addressable detectors | Analogue addressable devices

Discovery analogueaddressable detectors

www.emergi-lite.co.uk

17

Discovery is a powerful, intelligent, digital communication protocol, developed specifically to cater formodern day application requirements. Three different modes of operation are available: Normal, Readand Write. This enables an extensive exchange of information between the loop devices and the panel.

NORMAL MODE: is identical to Anatec FA95 but with somepowerful extensions for mode selection and detectorsensitivity drift warning.

READ MODE: allows loop device information, such asinstallation and servicing data, to be read by the controlpanel.

WRITE MODE: enables the control panel to writeinformation to the loop device, such as detector responsemode.

Detector optionsThe detector range includes optical smoke andtemperature sensors, a multi-sensor device with aprogrammable combination of optical and heatdetection, and a carbon monoxide detector.

A standard surface mounted call point is available.Other essential loop devices comprise isolators(including isolator base), loop powered sounders &sounder beacons. For connecting external devices arange of compatible interface units are available:input/output, zone monitors, sounder circuitcontrollers etc. Many devices and interfaces areavailable with in-built isolators providing excellentloop integrity.

Detector features and benefitsDrift compensation – smoke detectorAs the sensor output changes in time owing tocontamination such as dust, the signal processor willcompensate for this to retain sensitivity.

Heat detectionFull rate of rise (R-o-R) processing for heat detector.

Transient rejectionLow sensitivity to very rapid changes in sensor outputminimizing false alarms.

Response modesOne of five settings can be programmed from thepanel. A smoke detector can be set for a particularsmoke threshold while a heat detector the fixed leveland rate of rise sensitivity can adjusted.

Non volatile memoryThis can store site and date (last service) information.

Detector mounting base FA95-ACB (white)

A common mounting base for Anatec FA95 and Discovery detectors.Features:

Stainless steel terminals

Fitted with a universal address card (FA95-XPC)

Grub screw for locking the detector

SPECIFICATION

Termination Terminals can take up to 2.5mm2 diameter wire

Construction White moulded polycarbonate

OPTION

FA95-ABB Detector mounting base (black body)

FA95-ACB

FA95-ABB

Page 20: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Analogue addressable devices | Discovery analogue addressable detectors

Optical smoke detector FADY-OPT

Smoke particles entering the chamber will scatter light from an internalLED onto a photo diode. Internal electronics measure the voltage level andtranslate this into an analogue value which will be sent to the panel, whenit next interrogates the device.

Recommended for general purpose use to give early warning of fire.

SPECIFICATION

Voltage range 17 – 28Vdc

Average quiescent current at 24V 400µA

Alarm level analogue value 55

Alarm indicator 2 Clear cover LEDs, red light on alarm

Operating temperature –20 to +60ºC

Wiring & polarity 2 wire supply, polarity insensitive

Construction Moulded polycarbonate

Ingress rating IP43

Dimensions ø d (mm) 100 x 42 (50 with base)

Weight g 105 (160 with base)

Standards EN54-7: 2000

Heat detector FADY-TEM

The Discovery device can be used in different areas through adjustment ofits sensitivity from the panel. One device for 5 classes of response asdefined by EN54-5:2000. Linear response from 10 to 80 degrees C.

Heat detector response mode:

SPECIFICATION

Voltage range 17 – 28Vdc

Average quiescent current at 24V 500µA

Alarm level analogue value 55

Alarm indicator 2 clear LEDs, red light on alarm

Operating temperature Minimum –20ºC

Wiring & polarity 2 wire supply, polarity insensitive

Construction White moulded polycarbonate

Ingress rating IP53

Dimensions ø d (mm) 100 x 42 (50 with base)

Weight g 105 (160 with base)

Standards EN54-5: 2000

Discovery analogueaddressable detectors

MODE CLASS APPLICATION TEMPERATURE RESPONSETEMPERATUREMIN MAX

1 A1R 25 50 57

2 A2 25 50 61

3 A2S 25 50 61

4 CR 55 80 90

5 CS 55 80 90

www.emergi-lite.co.uk

18

FADY-OPT

FADY-TEM

Page 21: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Discovery analogue addressable detectors | Analogue addressable devices

Discovery analogueaddressable detectors

www.emergi-lite.co.uk

19

Multi-sensor detector FADY-MUS

The unit combines both optical and temperature sensor processes to giveindication of a fire. It is sensitive to both smouldering and flaming fires(i.e. can be used where an ionisation type might have been usedpreviously). Features:

Optical and heat thermistor sensors

Five response modes, for smoke and heat sensitivity

Response mode selectable from the panel

Drift compensation

SPECIFICATION

Voltage range 17 – 28Vdc

Average quiescent current at 24V 500µA

Alarm level analogue value 55

Alarm indicator 2 clear LEDs, red light on alarm

Operating temperature –20 to +60ºC

Wiring & polarity 2 wire supply, polarity insensitive

Construction White moulded polycarbonate

Ingress rating IP43

Dimensions ø d (mm) 100 x 50 (58 with base)

Weight g 105 (160 with base)

Standards EN54-7: 2000 & EN54-5: 2000

Carbon monoxide detector FADY-CO

A supplementary detector for use in areas where there might be smokestratification or smouldering fire risk. For spaces less than 50m² in area. Canbe used where optical detectors are likely to give false alarms – forexample, where aerosol contaminents, such as steam, cooking fumes,plumbing solder fumes, are present.

SPECIFICATION

Voltage range 17 – 28Vdc

Average quiescent current at 24V 500µA

Alarm level analogue value 55

Alarm indicator 2 clear LEDs, red light on alarm

Operating temperature 0 to +50ºC

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Ingress rating IP43

Dimensions ø d (mm) 100 x 42 (50 with base)

Weight g 105 (160 with base)

Standards EN54-7: 2000

Caution: Should not be used on an escape route or other specific cases.Susceptible to false alarms from fumes containing CO, such as from openhearth fires and gas appliances

FADY-MUS

FADY-CO

Page 22: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Analogue addressable devices | Discovery call points/ancillary devices

Discovery analogue addressablecall points/ancillary devices

Manual call point with isolator FADY-300-RS-ISO

Fitted with frangible element. A key test facility is situated underside,which is fully reset when the key is removed.

Protective covers for manual call pointsA tough protective cover is available to help prevent accidental operationof call points, or prevent unauthorised use by those with malicious intent.The cover is suitable for use in educational buildings, hospitals, nursinghomes or places where the threat of false alarm is prevalent.

SPECIFICATION

Voltage range 17 – 28Vdc

Average quiescent current at 24V 350µA

Alarm level analogue value 64

Operating temperature –20 to +60ºC

Wiring & polarity 2 wire supply, polarity insensitive

Construction Moulded polycarbonate

Ingress rating IP53

Dimensions hwd (mm) 87 x 87 x 52

Standards EN54-11

ACCESSORY

RSL800 Fire call point notice sticker

STANDARD ORDER CODE DESCRIPTION

FMC-ST30 Surface mount protective cover, with 30mm spacer

FMC-ST50WP Surface mount weatherproof cover, with 50mm spacer

For further options, please contact technical sales.

www.emergi-lite.co.uk

20

FADY-300-RS-ISO

RSL800

FMC-ST30

Ceiling tile mounting box FAP-MBCT

The fixture is used to fit a detector or sounder into a false ceiling matrix.The devices can be pre-wired and tested before the ceiling is fitted. Withthe ceiling tiles in place, the MBCT assemblies can be slotted into place.

FAP-MBCT-FD

STANDARD ORDER CODE DESCRIPTION

FAP-MBCT-FD Ceiling tile mounting box for detectors

FAP-MBCT-SO Ceiling tile mounting box for sounders

Page 23: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Loop powered alarms | Analogue addressable devices

Loop powered alarms

www.emergi-lite.co.uk

21

Analogue addressable loop powered alarmsEmergi-Lite offers a high quality range of addressable loop powered sounders, beacons and basessuitable for both Anatec FA95 and Discovery protocols. These devices complement our Anatec series ofanalogue addressable fire panels, featured on pages 4 to 11.

All devices in this range are fitted with a bi-directional short circuit isolator which is unaffected by a short circuit oneither loop input or output.

Tone compatibility chart

The chart below highlights the tone compatibility between sounder bases, sounders and beacons within the range,to assist installers and scheme designers with appropriate selection of devices.

Sounder base with isolator FA95-LPS-ISO

A loop powered sounder above an integral mounting base for either aDiscovery or FA95 sensor head, to sound a warning on fire detection.Features:

Suitable for both Anatec FA95 and Discovery protocols

Two volume ranges, a lower one for sensitive areas (warning hospitalstaff)

Sounder tones are synchronised

Group addressing alerting specific sections of a building

Snap fit cover available in white or red to be ordered separately.

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Maximum sound output, normal to the face 91dBA

Maximum sound output to EN54 83dBA

Isolation Short circuit isolator fitted

Current consumption at 24V (max) 8.25mA

Quiescent current 300µA

Addressing set by DIL switch

Construction Polycarbonate

Wiring Connectors accept up to 2.5mm² cables

IP rating 21C, indoor use only

Dimensions hwd (mm) 115 x 38

Weight g 160

OPTIONS

FA95-LWC White snap fit cover

FA95-LRC Red snap fit cover

FA95-LPS-ISO

FA95-LWC

Key:

Full compatibility with synchronised evacuation and alert tones Similar evacuate tone but not synchronised. Cannot be used together for staged evacuation Beacons are synchronised Beacons are synchronised but can drift (after 10 mins)

PRODUCT CODE DESCRIPTION FA95-LPS-ISO

FA95-BSNDR

FA95-IBS-ISO

FA95-LPSB-ISO

FA95-LS100R

FA95-LS100W

FA95-LS100R-

WP

FA95-LS100W-

WP

FA95-LPBEA

FA95-LPS-ISO Sounder base

FA95-BSNDR Sounder base

FA95-IBS-ISO Sounder base,integrated

FA95-LPSB-ISO Sounder beacon base

FA95-LS100R Horn sounder

FA95-LS100W Horn sounder

FA95-LS100R-WP Horn sounder

FA95-LS100W-WP Horn sounder

FA95-LPBEA Beacon

Page 24: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Analogue addressable devices | Loop powered alarms

Loop powered alarms

www.emergi-lite.co.uk

22

Integrated sounder base with isolator FA95-IBS-ISO

The IBS-ISO is a loop powered sounder with an integral mounting base foreither a Discovery or FA95 sensor head, to sound the alarm on firedetection. An integral isolator is fitted. Features:

Suitable for both Anatec FA95 and Discovery protocols

Selectable volume ranges: high range for normal use and low range forsensitive areas (to alert hospital staff)

Tone synchronisation

Group addressing to alert particular areas or rooms

Acoustic self-test. This produces a fault signal if there is no sound at theunit when it is switched on

Sounder caps must be ordered separately.

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Maximum sound output, normal to the face 91dBA

Maximum sound output to EN54 83dBA

Isolation Short circuit isolator fitted

Current consumption at 24V (max) 5mA

Quiescent current 200µA

Addressing set by DIL switch

Construction Polycarbonate

Wiring Connectors accept up to 2.5mm² cables

IP rating 21D, indoor use only

Dimensions hwd (mm) 115 x 38

Weight g 140

Standards EN54-3 when used in the high range

OPTIONS

FA95-LWC-IBS White cap

FA95-LRC-IBS Red cap

FA95-IBS-ISO

FA95-LWC-IBS

Local area sounder base FA95-BSNDR

A loop powered sounder with an integral mounting base for either aDiscovery or FA95 sensor head. Features:

Suitable for both Anatec FA95 and Discovery protocols

Adjustable volume control, from 70 to 85dBA

Low current consumption

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Sound output dBA 85dBA

Current consumption at 24V (max) 3mA

Quiescent current <100µA

Addressing Not addressable – reacts to signal from mounted detector

Construction Polycarbonate

Wiring Connectors accept up to 2.5mm² cables

IP rating 23D

Dimensions hwd (mm) 115 x 38

Weight g 140

Standards EN54-3

FA95-BSNDR

Page 25: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Beacon base with isolator FA95-LBB-ISO

A loop powered flashing beacon with integral mounting base for either aDiscovery or FA95 sensor head, to flash a warning on fire detection.Features:

Suitable for both Anatec FA95 and Discovery protocols

LEDs are synchronised to flash once a second

Single or group addressing

Beacon self-test through LED monitoring

Built-in isolator helps reduce cost an installation time

Snap fit cover available in white or red to be ordered separately.

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Isolation Short circuit isolator fitted

Current consumption at 24V (max) 3.1mA

Quiescent current 300µA

Addressing set by DIL switch

Construction Polycarbonate

Wiring Connectors accept up to 2.5mm2 cables

IP rating 21D, indoor use only

Dimensions hwd (mm) 115 x 31

Weight g 109

Standards EN54-17 (isolating circuit)

OPTIONS

FA95-LWC-IBS White snap fit cover

FA95-LRC-IBS Red snap fit cover

Loop powered alarms | Analogue addressable devices

Loop powered alarms

www.emergi-lite.co.uk

23

Sounder beacon base with isolator FA95-LPSB-ISO

A loop powered sounder together with a flashing beacon above an integralmounting base for either a Discovery or FA95 sensor head, to sound andflash a warning on fire detection. Features:

Suitable for both Anatec FA95 and Discovery protocols

Two volume ranges, a lower one for sensitive areas (warning hospitalstaff)

Sounder tones are synchronised

Group addressing alerting specific sections of a building

Acoustic and beacon self test with fault notification at the panel

Snap fit cover available in white or red to be ordered separately.

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Maximum sound output, normal to the face 91dBA

Maximum sound output to EN54 83dBA

Isolation Short circuit isolator fitted

Current consumption at 24V (max) 8mA

Quiescent current 300µA

Addressing set by DIL switch

Construction Polycarbonate

Wiring Connectors accept up to 2.5mm² cables

IP rating 21D, indoor use only

Dimensions hwd (mm) 115 x 38

Weight g 160

Standards EN54-3: higher sound range only, isolating circuit toEN54-17

OPTIONS

FA95-LWC-IBS White snap fit cover

FA95-LRC-IBS Red snap fit cover

FA95-LBB-ISO

FA95-LWC-IBS

FA95-LPSB-ISO

FA95-LWC-IBS

Page 26: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Loop powered alarms

100dB Loop powered horn FA95-LSBOR-ISO

sounder beacon FA95-LSBR65-ISO

(Weatherproof IP66)

The LSB sounder-beacon series is designed for open area use, providing ahigher level of sound with a visual flash. Features:

Suitable for both Anatec FA95 and Discovery protocols

Can be addressed and synchronised from the panel through the loop

Group addressing to alert particular areas or rooms

Acoustic self-test – produces a fault signal if there is no sound at theunit when switched on

Enables DDA compliance

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Sound output dBA 100

Beacon LED red flash

Current consumption at 24V (max) 8-9mA

Quiescent current 333µA

Addressing Set by DIL switch or by pulsed mode synchronisation addressing

Construction Moulded ABS in red (white – weatherproof version), withremovable back box

Wiring Connectors accept up to 2.5mm² cables

IP rating IP21C indoor use only, IP66 weatherproof version

Dimensions hwd (mm) 105 x 105 x 50 (standard version),110 x 110 x 113 (weatherproof version)

Weight g 209, 294 (weatherproof version)

Standards EN54-34: 2001, EN54 pt 3:2001 (weatherproof version)

OPTIONS

FA95-LSBOW-ISO Loop powered horn sounder beacon, white

FA95-LSBW65-ISO Weatherproof loop powered horn sounder beacon, white

100dB Loop powered FA95-LS100R

horn sounder FA95-LS100R-WP (weatherproof IP66)

Loop powered horn sounder designed for open area use, where a higherlevel of warning sound is needed. The 100dBA sound level is produced withonly a 5mA current consumption. The level can be adjusted to 92dBA (+/-3dBA) as required. The sounder has onboard electronics which enables it tobe addressed and synchronised from the panel through the loop. Features:

Group addressing to alert particular areas or rooms

Acoustic self-test – produces a fault signal if there is no sound at theunit when switched on

Suitable for both Anatec FA95 and Discovery protocols

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Sound output dBA 100

Current consumption at 24V (max) 5mA

Quiescent current <1.2mA

Addressing Set by DIL switch or by pulsed mode synchronization addressing

Construction Moulded ABS in red, with removable back box

Wiring Connectors accept up to 2.5mm² cables

IP rating IP21C indoor use only, IP66 weatherproof version

Dimensions hwd (mm) 105 x 105 x 50110 x 110 x 113 (weatherproof version)

Weight g 215, 340 (weatherproof version)

Standards EN54-34: 2001, EN54 pt 3:2001 (weatherproof version)

OPTIONS

FA95-LS100W Loop powered horn sounder, white

FA95-LS100W-WP Weatherproof loop powered horn sounder, white

Analogue addressable devices | Loop powered alarms www.emergi-lite.co.uk

24

FA95-LS100R

FA95-LS100R-WP

FA95-LSBOR-ISO

Page 27: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Open area sounder FA95-KLSR

A sounder for general use, with a fitted isolator as standard. The soundtone is selectable from a set of 32 options. Features:

Can be addressed and synchronised from the panel

Self-test

Suitable for both Anatec FA95 and Discovery protocols

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Sound output dBA 100

Current consumption at 24V (max) 5mA

Construction Flame retardant polycarbonate in red

Wiring Connectors accept up to 2.5mm2 cables

IP rating IP65, with deep base

Dimensions ø h (mm) 97.5 x 104

Weight g 250

Standards EN54-3

OPTIONS

FA95-KLSW Open area sounder, white

Loop powered alarms

Loop powered alarms | Analogue addressable deviceswww.emergi-lite.co.uk

25

Open area beacon FA95-KLBR

An LED beacon device with a red flash, suitable for general fire use inconjunction with sounder devices. An IP65 rating is achieved with the deepbase version. Features:

Can be addressed and synchronised from the panel

Self-test

Isolator fitted

Choice of 32 tones of sound

Suitable for both Anatec FA95 and Discovery protocols

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Current consumption at 24V (max) 5mA

Construction Flame retardant polycarbonate in red, translucent cover

Wiring Connectors accept up to 2.5mm2 cables

IP rating IP65, with deep base

Dimensions ø h (mm) 97.5 x 104

Weight g 250

OPTION

FA95-KLBW Open area beacon, white

FA95-KLSR

FA95-KLBR

Page 28: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

26

www.emergi-lite.co.ukAnalogue addressable devices | Loop powered alarms

Loop powered alarms

Open area sounder beacon FA95-KLSBR

A combined sounder-beacon for general open space use. The beacon flashfunction is useful for compliance with projects needing to comply with DDArequirements.

Can be addressed and synchronised from the panel

Self-test

Isolator fitted

Choice of 32 tones of sound

Suitable for both Anatec FA95 and Discovery protocols

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Sound output dBA 100

Current consumption at 24V (max) 8 – 9mA

Construction Flame retardant polycarbonate in red

Wiring Connectors accept up to 2.5mm2 cables

IP rating IP65, with deep base

Dimensions ø h (mm) 97.5 x 104

Weight g 250

Standards EN54-3

OPTION

FA95-KLSBW Open area sounder beacon, white

FA95-KLSBR

Beacon FA95-LPBEA

A local area indoor beacon, to be used in conjunction with sounders inexisting or new installations where the sound output may not be loudenough over the ambient noise level, for example a machine shop. Thedevice is also relevant for DDA applications, where the hard of hearingneed an alternate means of warning. The beacon also provides a suitablestaff alarm in hospitals or care homes. Features:

High intensity LED source flashing once a second. Lens colour options

Low current consumption from the loop

Beacon self-test through LED monitoring

Lockable once fitted

Suitable for both Anatec FA95 and Discovery protocols

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Loop loading Up to 20 beacons between standard isolators

Current consumption at 24V (max) 3mA

Quiescent current 150µA

Construction Polycarbonate, white base with red translucent diffuser

IP rating 21D, indoor use only

Dimensions hwd (mm) 115 x 38

Weight g 140

OPTION

FA95-LPBEA-A Amber lens model

FA95-LPBEA

Page 29: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Sound output at 1m 94/100dBA

Current consumption at 24V (max) 7.5mA

Quiescent current 800µA

Construction Flame retardant polycarbonate

Wiring Connectors accept up to 2.5mm2 cables

IP rating IP43(IP65, with deep base)

Sounder dimensions ø h (mm) 93.6 (DB-93) x 84.3 (DB-101.6)

Sounder beacon dimensions ø h (mm) 93.6 (DB-93) x 89.6 (DB-106.9)

OPTIONS

FAC95-LSRDB Open area sounder, red, deep base

FAC95-LSW Open area sounder, white, shallow base

FAC95-LSWDB Open area sounder, white, deep base

FAC95-LSBRDB Open area sounder beacon, red, deep base

FAC95-LSBW Open area sounder beacon, white, shallow base

FAC95-LSBWDB Open area sounder beacon, white, deep base

www.emergi-lite.co.uk Alternate loop powered alarms | Analogue addressable devices

Alternate loop poweredalarms

27

A range of alarm devices compatible with Anatec analogue addressable fire panels. Loop addressing isset on a DIL switch and any sounder can be set as a master with others as slaves. These devices need aseparate isolator.

Loop powered base sounder FAC95-LS-5

With integral mounting base suitable for an FA95 sensor head, to soundthe alarm on fire detection.

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Sound output at 1m 91dBA

Current consumption at 24V (max) 7mA

Quiescent current 800µA

Construction Polycarbonate

Wiring Connectors accept up to 2.5mm2 cables

IP rating IP42

Dimensions hwd (mm) 106 x 25 (35 with cover)

OPTIONS

FA95-LWC-IBS White cap

FA95-LRC-IBS Red cap

Loop powered LED beacon FAC95-LSBRDB

Addressable bright flash LED beacon with red flash rate of 1Hz and red body.

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Current consumption at 24V (max) 7mA

Quiescent current 800µA

Construction Flame retardant polycarbonate

IP rating IP65, with deep base

Dimensions ø h (mm) 93.6 x 77 (deep base)

Open area sounder FAC95-LSR

Multi tone, for open area use, operating across a range of frequencies.

Open area sounder-beacon FAC95-LSBR

FAC95-LS-5

FAC95-LSBRDB

FAC95-LSR

Page 30: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Interface modules

www.emergi-lite.co.ukInterface modules | Zone monitor

28

Interface modules for intelligent fire detection and alarm systemsAn analogue fire system is usually designed with a number of loops, each beginning and ending at thefire panel. The integrity of loop wiring is vital for data transmission, where a short circuit between loopwires would be very serious. Hence it is necessary to have isolating circuits positioned in the loop inorder to isolate any section containing a short circuit, until the fault is rectified.

The isolator detailed here is polarity sensitive and will normally switch out the negative arm of the loop, when ashort circuit is sensed.

Normally the isolator allows current flow in both directions. If the loop voltage falls beneath a preset threshold theisolator will switch open to isolate the incoming and outgoing lines. The device will test the isolated sectionregularly and will reconnect when the fault is cleared.

Isolating devices are provided either as standalone products or integral within many interfaces, detection or sounderunits. Interfaces with integral isolators and detectors fitted to isolating bases will stay operational when the adjacentsection of loop is isolated. The isolating unit, when isolating, will display a yellow fault indication LED.

It is good practice for devices wired between two isolators to be located in the same zone.

Zone monitor with isolator FA95-ZMU

Powers a zone of up to 20 conventional detectors (Orbis or FAP6) from theloop. The device sends a high analogue value to the panel, only when adetector on the monitored circuit changes to an alarm state. Features:

Suitable for both Anatec FA95 and Discovery protocols

Surface mounting with entry points for cut out on sides and rear

Connections for loop in & out wiring and detector zone + & – inputs

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Indicators Red LED for alarm, yellow LEDs for a short circuit loop-wiring fault

Output to panel Signal on detector alarm

Isolation Short circuit isolator fitted

Current consumption at 24V (max) 11mA in alarm

Quiescent current 4mA

Construction Polycarbonate box, indoor use

Dimensions hwd (mm) 150 x 90 x 48

Weight g 230

EOL

Illustration:Zone monitor unit [FA95-ZMU]

Loop outLoop in

Application:A ZMU is used to connect asystem of conventionaldevices to an analogueaddressable fire system.

Zone monitor unit [ZMU]

o

o

o

o

Conventional detectorsEmergi-Lite OrbisFAP6

PSU

FA95-ZMU

Key:

Manual call point

Analogue detector

Conventional detector

Conventional sounder

o

o

CIE CanteenOfficeOfficeOffice

Reception

AL-1

AL-2

o o o o

oo o o

H

o

PSU

o o o o

Separate building - annex

A building previously protected by a conventional fire system:-The conventional panel is replaced by a zone monitor unit [ZMU] and a sounder circuit controller

[SCC]. This system can now be connected to the main analogue panel in another building (theconventional devices and wiring remain unaltered).

ZMU SCC

Page 31: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk Switch monitors | Interface modules

Interface modules

29

Switch monitor with isolator FA95-SMU

Monitors one or more volt-free contacts connected on a single pair ofwires. Open or short circuit faults are reported. Features:

Suitable for both Anatec FA95 and Discovery protocols

Surface mounting with entry points for cut out on sides and rear

Connections for loop in & out wiring and external monitor

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Indicators Red LED for alarm, 2 yellow LEDs for wiring faults

Output to panel Normal, fault, pre-alarm, alarm

Isolation Short circuit isolator fitted

Current consumption at 24V (max) 3.6mA

Quiescent current 1.25mA

Max. switching current 3A

Construction ABS plastic box, indoor use

IP rating IP54

Dimensions hwd (mm) 150 x 90 x 48

Weight g 240

Mini switch monitor FA95-SMUM

Monitors one or more volt-free contacts connected on a single pair ofwires. Small unit, ideal for fitting into equipment with limited space.Features:

Suitable for both Anatec FA95 and Discovery protocols

Locate with double sided tape in seat area

Connect flying leads to user provided connector block. Red & black forloop, yellow & green to remote LED, violet & white to monitored circuit

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Indicators Red LED for alarm with connection for a remote LED (triggeredsimultaneously)

Output to panel Normal, fault, pre-alarm, alarm

Current consumption at 24V (max) 3.5mA on alarm

Quiescent current 1mA

Construction Polycarbonate moulding with six flying leads

Dimensions hwd (mm) 76 x 47 x 14

Weight g 46

CIE

Warehouse

CanteenOfficeOfficeOffice

Reception

o o o o

oo o o

H

o

Beamdetector

Beamreflector

SMU

AL-1

AL- 2

A switch monitor unit [FA95-SMU]is used to input a ‘fire’ signal downthe loop within 10 seconds fromthe activation of devices such as:• Sprinkler switch activated• Beam detector activated• Plant alarm

Loop in

Switch monitor unit [SMU]

Loop out

Device to bemonitored

FA95-SMU

FA95-SMUM

Key: analogue devices

Manual call point

Detectoro

Sounder

Page 32: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

30

Interface modules

Interface modules | Switch monitor

Switch monitor PLUS with isolator FA95-SMUPLUS

Monitors one or more volt-free contacts connected on a single pair ofwires. An opto coupled output is fitted for resetting a remote detector anda selectable delay. Applicable for flow switch monitoring. Features:

Suitable for both Anatec FA95 and Discovery protocols

Surface mounting with entry points for cut out on sides and rear

Connections for loop in & out wiring and external monitor

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Indicators Red LED for alarm, 2 yellow LEDs for wiring faults

Output to panel Normal, fault, pre-alarm, alarm

Isolation Short circuit isolator fitted

Current consumption at 24V (max) 3.6mA

Quiescent current 1.25mA

Max. switching current 3A

Construction ABS plastic box, indoor use

IP rating IP54

Dimensions hwd (mm) 150 x 90 x 48

Weight g 240

Mini switch monitor with interrupt FA95-SMUM-INT

Monitors one or more open switches connected on a single pair of wiresand gives a priority response in the event of a fire. For example: to signalwhen a conventional manual call point (singly or in a zone) is activated.Features:

Suitable for both Anatec FA95 and Discovery protocols

Locate with double sided tape in seat area

Connect flying leads to user provided connector block. Red & black forloop, yellow & green to remote LED, violet & white to monitored circuit

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Indicators Red LED for alarm with connection for a remote LED (triggeredsimultaneously)

Output to panel Normal, fault, alarm

Current consumption at 24V (max) 4mA

Quiescent current 870µA

Construction Polycarbonate moulding with six flying leads

Dimensions hwd (mm) 76 x 47 x 14

Weight g 46

CIE CanteenOfficeOfficeOffice

Reception

o o o o

oo o o

H

o

SMUM-INT

AL-1

AL-2

Switch monitor interrupt unit [SMUM-INT]

EOL

Loop outLoop in

MCP

A switch monitor interrupt unit [FA95-SMUM-INT]signals back to the CIE within 3 seconds ofactivation, so that it can be used for priority devicessuch as:-o Supervisory call pointso Secure area key operated call points

FA95-SMUM-INT

FA95-SMUPLUS

Key:

Manual call point

Analogue detector

Conventional detector

Conventional sounder

o

o

Page 33: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

31

www.emergi-lite.co.uk Sounder circuit controller | Interface modules

Interface modules

Sounder circuit controller FA95-SCC

Operates and controls a zone of externally powered sounders. Status reportsignals are sent to the panel. Sounders are able to work continuously orpulsed, individually or in groups (sounders can be synchronised in pulsedoperation.) External power supply is monitored. Features:

Suitable for both Anatec FA95 and Discovery protocols

Surface mount unit with entry points for cut out on sides and rear

Connections for loop in & out wiring, sounder circuit, fault inputs &local power supply

SPECIFICATION

Min/max loop operating voltage SCC is loop powered:17Vdc, 28Vdc.An external supply is required for the alarm load

Indicators Red LED for alarm, yellow LED for a short circuit loopwiring fault & another yellow LED for fault detection

Output to panel Signal on short or open circuit fault, or externalpower supply fault

Isolation Short circuit isolator fitted

Current consumption, loop, at 24V (max) 3.6mA

Quiescent current 1.95mA

Current consumption, external supply (max) 47mA at 32Vdc plus sounder load

Maximum sounder circuit current 1A at 30Vdc

Construction ABS plastic box, indoor use

Dimensions hwd (mm) 150 x 90 x 48

Weight g 240

CIE

PSU

Warehouse – noisy environment

CanteenOfficeOfficeOffice

Reception

AL-1

AL-2

o o o o

oo o o

H

o

SCC

PSU

Sounder circuit controller, FA95-SCCcontrolling conventional 24 voltsounders, when a signal is receivedfrom the loop.

Application examples:• When loop sounders do not provide

a high enough sound outputrequired for the premises

• When more than 2 conventionalalarm outputs are required on thesystem

Loop in

EOL

SCC

Loop out

FA95-SCC

Key:

Manual call point

Analogue detector

Conventional detector

Conventional sounder

o

o

Page 34: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Interface modules

Interface modules | Input/output units

Input/Output unit with isolator FA95-1CI/O

A two channel I/O interface device for interfacing external equipment andthe fire detection system together. Two outputs, with volt-free contacts, areprovided from a loop powered relay which is activated by a control signalfrom the panel. Two inputs (one monitored and one opto-coupledunmonitored) enable open or closed switch positions to be reported alongwith fault. Features:

Suitable for both Anatec FA95 and Discovery protocols

Surface mount unit with entry points for cut out on sides and rear

Connections for loop in & out wiring, relay contacts and externalmonitoring

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Indicators 2 red LEDs for relay and switch position, 2 yellow LEDs forwiring faults

Isolation Short circuit isolator fitted

Current consumption at 24V (max) 3.5mA

Quiescent current 1.25mA

Max switching current 3A

Construction ABS plastic box, indoor use

IP rating IP54

Dimensions hwd (mm) 150 x 90 x 48

Weight g 240

CIE

o

oo o

o o o

o o o o

PSU

GA

SB

OIL

ER

Fire door

Fire door

Door retainer

Door retainer

GS

GS - gas solenoid

I/O

I/O

www.emergi-lite.co.uk

32

FA95-ICI/O Input/output interface unitTwo single pole volt free relay outputs forcontrolling various pieces of equipment in theevent of a fire, for example:• Plant shutdown• Fire dampers• Door magnets• Security doors• Moving a lift to ground floor

An HVac (heating, ventilation or air-conditioning)control is illustrated

Loop in

HVac

NO C NC NO C NC

Input/output unit[I/O] Loop out

FA95-1CI/O

Key:

Manual call point

Analogue detector

Conventional detector

Conventional sounder

o

o

Page 35: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Input/output units | Interface modules

Interface modules

Output unit with isolator FA95-1CO

A two channel output device for interfacing external equipment and thefire detection system together. Two outputs, with volt-free contacts, areprovided from a loop powered relay which is activated by a control signalfrom the panel. Features:

Suitable for both Anatec FA95 and Discovery protocols

Surface mount unit with entry points for cut out on sides and rear

Connections for loop in & out wiring and relay contacts

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Indicators 1 red LED for relay and switch position, 1 yellow LED for wiringfaults

Isolation Short circuit isolator fitted

Current consumption at 24V (max) 3mA

Quiescent current 400µA

Max switching current 3A

Construction ABS plastic box, indoor use

IP rating IP54

Dimensions hwd (mm) 150 x 90 x 48

Weight g 240

Mains switching input/output unit FA95-1CO-240

Designed to switch equipment operating at 230V/50Hz, such as mainspowered magnetic door holders or other mains powered machinery.Features:

Suitable for both Anatec FA95 and Discovery protocols

Volt-free single pole changeover relay output

Monitored switch input

Surface mount unit with entry points for cut out on sides and rear

Connections for loop in & out wiring, mains and relay

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Indicators 1 red LED for relay set, 1 red LED for switch input closed,1 yellow LED for wiring faults

Isolation Short circuit isolator fitted

Current consumption at 24V (max) 3.5mA

Quiescent current 1.25mA

Max switching capacity 1.25kVA

Construction ABS plastic box, indoor use

IP rating IP54

Dimensions hwd (mm) 150 x 90 x 48

Weight g 240

www.emergi-lite.co.uk

33

FA95-1CO

FA95-1CO-240

Page 36: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Loop isolators | Standard/Isolating base www.emergi-lite.co.uk

34

Loop isolators

Standard loop isolator FA95-LIU (unit)

FA95-LLB (base)

A standalone isolating unit with separate base, to be fitted in the loopbetween detectors and other loop devices.

Suitable for Anatec FA95 protocol

Unit and base are to be ordered separately

SPECIFICATION

Min/max loop operating voltage 17Vdc, 28Vdc

Indicators Yellow LED illuminated when in the ‘isolated condition’

Current consumption at 18V, 28V 23µA (4mA with adjacent loop section isolated), 43µA

Operating temperature –20 to + 70ºC

Dimensions ø d (mm) 100 x 24

Weight g 100

FA95-LIU

FA95-LIU-B20D

Isolating base FA95-LIU-B20D

An isolating unit with integral base seat for a detector, which will isolate ashort circuit fault in the loop section, while allowing the mounted detectorto operate.

For applications where it is not necessary to fit an isolator with eachdetection device, up to 20 devices can be fitted in between the isolatingbase and the next on the loop, provided the switch on surge current isbelow 20mA. Features:

Addressing card fitted

Suitable for Anatec FA95 protocol

Page 37: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk Conventional

Conventional

35

Emergi-Fire Sensa with Alarmsense 36 – 37

Eurofire Sensa panels 38 – 41

Firetec Sensa panels 42 – 44

AlarmSense devices 45 – 49

Eurofire 4-wire panels 50 – 53

Firetec 4-wire panels 54 – 56

FAP6 4-wire detectors 60 – 62

FAP6 4-wire call points/ancillary 63 – 65

Conventional 4-wire alarms 66 – 70

Conventional

Page 38: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

The Emergi-Fire Sensa control panel operatingwith Apollo Alarmsense devices is an advancedand cost-effective 2-wire fire system for small tomedium-sized buildings. System flexibilityenables use in applications such as ‘dwellingsand in houses of multiple occupation’ (HMO)and distributed buildings using a proven andextensive networking capability.

In summary this is a flexible, reliable and costeffective fire detection system that is easy to installand extend.

Eurofire Sensa panelsEurofire Sensa panels are designed to comply with theEuropean Standard EN54 Parts 2 and 4 and aresuitable for BS 5839-1:2002 and BS 5839-6:2004installations.

Panels are available in 4, 8, 12 or 16 zones of firedetection cover, with powerful and flexible setup,control and display capabilities.

AlarmSense devicesAlarmSense devices (detectors, manual call points,sounders, sounder beacons and alarm relays) aredesigned to operate normally on the same pair ofzone wires from the panel. A key feature is that alarmsounders can be programmed to operate as so-called‘priority’ or ‘non-priority’ devices.

The principle of priority andnon-priority responseIn a Sensa system, the nominal operating voltage is12 volts, which enables AlarmSense detectors andmanual call points (MCPs) to operate. Sounders andbeacons operate at 24 volts, so remain dormant at thisstage. When a detector or MCP is activated, the panelwill register a change and will take the zone voltageup to 24 volts, which will switch the sounders on.

A ‘priority’ set device reacts as a normal sounder instandard use and sounds a full alarm. A ‘non-priority’set device will give an initial local alert prior to goinginto full alarm.

AlarmSense sounder and sounder beacon bases arechangeable between ‘priority’ and ‘non-priority’ modes.

‘Non-priority’ devices are intended for use in HMOtype applications where there are a number ofindividual dwellings. The operating method isintended to help reduce the instances of unwantedalarms and give a local warning before the fullalarm/evacuation.

A sounder-beacon base (with a detector on the baseseat) when set to ‘non-priority’, will sound a local alertfor 2 minutes at that locality. People in the vicinity oroccupants in the dwelling will be the first warned of apossible fire situation or false alarm. They will have2 minutes to investigate and rectify a false alarm,

(i.e. heat or fumes from cooking). After 2 minutes, ifthe detector is still activated, the Eurofire panel willgo into a full fire situation. At any time during thealert period, if another device is activated, the systemgoes into a full fire situation.

Eurofire can be programmed to react to ‘non-priority’signals in one of two ways:

The panel sends out a ‘non-priority’ pattern to thezone, which causes only the sounder on theactivated detector to sound, or

The panel sends out a ‘non-priority’ pattern to allzones, which have been set to include ‘non-priority’ devices. This will cause any local response(LR) devices set as ‘non-priority’ to also sound –no other ‘non-priority’ devices will sound.

If another device of any type or a ‘priority/non-priority’ is activated during the alert period, thesystem goes into a full fire alarm condition.

A ‘non-priority’ alert cannot be generated if thesystem is already in a fire alarm condition.

When a heat detector is attached on a sounder orsounder beacon base, we recommend that thesounder be set as a ‘priority’ device.

www.emergi-lite.co.uk

Emergi-Fire Sensa with Alarmsense

Conventional | Emergi-Fire Sensa with Alarmsense

36

Page 39: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Programming non-priority detectorsfor local alarm operationThe diagram below illustrates a 2-storey block containing3 flats and an entrance lobby. A Eurofire panel controlsthe fire alarm system for all 3 flats. Manual call points aresituated in the lobby and along the corridors. Sounderdetector bases are situated throughout with a separatesounder adjacent to the fire panel.

Scenario 1 – ‘Non-priority’ detector in Flat 1activates owing to fumes from cooking

The base sounder above the detector will sound for 2minutes (alerting the occupants in flat 1).

The sounder beacon (Zone 8) next to the panelactivates, if it is programmed for local response (LR).The occupant has time to expel the smoke from thedetector vicinity.

During this period, the panel indicates ‘Zone 1 LocalAlert’, and sounds the buzzer in the control panel. Theresponsible person has time to investigate the alertand act accordingly. If any detector or MCP activatesduring the alert, the system goes into a full firesituation and sounds the alarm.

After the alert period, with fumes dispersed, the panelwill return to the quiescent state. If the detectorremains activated after the alert period, the panel willgo into a full fire alarm condition.

Scenario 2 – Non-priority detector in Flat 1 isactivated as a real fire condition

The sequence is the same as in the first scenario, untilthe 2-minute alert period is over. After the alertperiod, with a real fire, the detector remains activatedand the panel will go into a full fire alarm condition.

Scenario 3 – Detector or MCP is activated as a fire

The panel goes into a full fire situation. If a ‘non-priority’ detector is activated afterwards – the paneltreats this as a normal detector being activated in afire situation.

www.emergi-lite.co.uk

37

Emergi-Fire Sensa with Alarmsense | Conventional

CIE

Up

Up

Zn3Zn2

Zn1Zn8

Zn4

Zn5

Zn6Zn7

Zone 7

Zone 5

Zone 3Zone 2

Zone 1

# = Set as non-priority detector

#

##

Flat 2

Flat 1

Flat 3

Apartment building with a floor plan of 2 floors: Illustration ofdetector programming for local alarm operation

Floor 1

Floor 2

Zone 6

Zone 4

Key:

Manual call point

Combined sounder-detectorbase (priority set)

Combined sounder-detectorbase (non-priority set)

Sounder-beacon base

Standalone smoke alarm

Page 40: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Conventional | Eurofire Sensa 2-wire panels

Eurofire Sensa 2-wire panels

www.emergi-lite.co.uk

38

Eurofire Sensa 2-wire fire panels Benefits and featuresComprehensive zone coverage:Available in 4, 8, 12 or 16 zonemodels.

Zone capacity:Nominally 30 devices per zone.

Soft select:Non-latching or latching zones:The non-latching zone featureallows a better integrityconnection to existing systems(other manufacture). This preventslockout and allows panels to bereset more readily (the panelbeing connected to must have aspare zone and auxiliary contactswith a volt-free pair). Short circuitfire or fault for older systems.

Output wiring:2-wire configuration to the zones,giving reduced wiring cost.

Outputs:4 alarm outputs and auxiliary volt-free contacts, which areprogrammable for continuous,pulsing or delayed operation.Fault volt-free relay contacts.

Sounder delay activation:Eurofire includes a sounder ‘delay-on’ facility. This allows the user toprogramme chosen sounders orbeacons to activate at a latermoment. This is suited toapplications where it is beneficialnot to have undue panic, such asin bars or Soft Play centres.

2-wire and 4-wire systemintegration:The Eurofire system has the abilityto recognise and operate a 4-wirezone, which can potentially save onwiring when a refurbishment isundertaken. For example in a smallhotel or guesthouse where nosounders or sounder-beacons arefitted in bedrooms, a bedroom zonecan be the 2-wire format, withdetectors and alarms wired on thesame pair. Other existing 4-wirezones in the building can remain ifdesired (it will be necessary to checkfor sounder tone compatibility).

Networking capability:Coverage in larger buildingcomplexes can be achieved bylinking Eurofire EN54 panels andrepeaters together via a ‘CANConnect’ link. It is also possible tomake more power available forsounder circuits, or save on fieldwiring.

Eurofire Sensa is a range of conventional (non-addressable) firedetection panels with extensive safety, technical and practicalfeatures for the installer and user. Eurofire Sensa panels aredesigned to comply with the European Standard EN54 Parts 2 and 4and are suitable for BS 5839-1:2002 and BS 5839-6:2004installations.

Panels are available in 4, 8, 12 or 16 zones of fire detection cover, withpowerful and flexible setup, control and display capabilities and areconfigured to operate with Apollo AlarmSense devices.

The 2-wire convention uses one pair of wires for the connection of Sensa-compatible devices (detectors, manual call points and alarm sounders). Thisgives the scheme designer a greater flexibility of choice, whilst retainingcompliance with the relevant standards. Benefits can be seen in havingreduced field wiring costs and time saving with ease of installation.

Panels are supplied as a complete package, with all end of line devices,batteries and a logbook included.

Page 41: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Eurofire Sensa 2-wire panels | Conventional

Panel DisplayThe Eurofire Sensa panel includes an easy to reference display with LCD screen allowing for up to four lines of text,with text programmable for each zone. 6 buttons are included on the front of the panel which can be used to accessthe following functions:

Lamp test, silence alarms, silence buzzer

User zone, sounder and 2-wire sounder isolation

Walk and alarm test facility with mute option

99-event history log that stores any events withtime and date stamp, for the user to scroll

Configurable system message for the user withnormal time and date displayed

The panel also features indicator LEDs which advisethe current state of the fire detection system, and givea clear signal of fire or fault in any particular zone.

Further functionality includes the facility to reviewevent logs, to override any pre-set alarm delays, andto enable sounding the evacuation to all zones.

Eurofire Sensa 2-wire panels

www.emergi-lite.co.uk

39

Networking capabilityFire detection coverage in a larger building complex can be achieved by linking Eurofire EN54 panels and repeaterstogether via a ‘CAN Connect’ link. (‘CAN Connect’ is a readily available communications protocol.) It is also possibleto make more power available for sounder circuits (additional 4), or save on field wiring:

Indicator detailsThe panel includes indicators for information, fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.

Scenario: In abuilding, one panelmight be sited in theoffice area and onein the warehousearea. The zones foreach area are wiredto their respectivepanels. Network thepanels and theoffice unit has fullvisibility of thebuilding. It may benecessary to use ahigher rated cableand the Emergi-Litenetwork card (pleasecontact Technicalsales for furtherguidance).

CAN network

IsolatedCAN

network

CA

NN

ETC

AR

D

CAN network

IsolatedCAN

network

CA

NN

ETC

AR

D

To nextpanel

Illustration: Network of Eurofire panels, in star format[wired to the CAN network facility]

Eurofire c-net

Eurofire c-net Eurofire c-net

Page 42: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Eurofire Sensa 2-wire panels

Conventional | Eurofire Sensa 2-wire panels www.emergi-lite.co.uk

40

Connection diagramThe diagram below illustrates a Eurofire panel connected to detectors, sounders, and call points, with settings forboth ‘priority’ and non-priority’.

Eurofire 2-wirezonal layoutThe illustration belowshows a potential schemelayout for a Eurofire panel,over 5 active zones, with1 additional alarm circuit.

Additonal alarmcircuits

Auxiliary relaycontacts

NC C NO +AL2-+AL1-

Aux 1 Aux 2

+Z1- +Z2-

Cla

ssch

ang

e

TTL

fau

lt

GN

D

- 24v +

+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-NC C NONC C NO NC C NO

Co

mm

on

fau

lt

Pro

gi/p

Bo

mb

aler

t+AL3- +AL4-

Isolated CAN network

HI LO SCR HI LO SCRHI LO SCR HI LO SCR

CAN network

- 24v +- 12v +

Auxoutputs

Auxi/p

- +AC AC

Batt

+Z10-+Z9- +Z11- +Z12- +Z13- +Z14- +Z15- +Z16-

Eurofire Sensa 2 wire: Illustration of zonal wiring

Fault 1 Fault 2

2- wire zones; 2 & 4 to 8,wired as priority or non-

priority EOL diode to unused zones [cathode to zone,+ve end]

EOLresistor inunused

alarm ccts

No spurs

EOL diode on last detector[cathode to zone +ve end]

No spurs

o

o

o o

o

Call point -2wKey:

Optical 2wdetector

Priority 2wsounder

2w Sounder, setas non-priority

Standardsounder

o

o

Z1: Priority zone

Z3: Non-priority zone

Key:

o

EOL

Call point

Optical smoke detector

Heat detector

Beamdetector set

End of line device-detector circuit

Sounder (priority)

Sounder-beacon (priority)

Zone: detection circuitwiring

Alarm circuit wiring

SEOLEnd of line device -alarm circuit

RA1

Programmablesounder circuitsfrom the panel

Zone circuits toEurofire 2wSensa panel

Kitchen

Fire exit

Fire exit

Fire exit

Apex roof

o

A1R

o o

oo

o

o

o

o

o

A1R

o

o

o

ROOFWINDOWCONTROL

o

Auxiliarycircuits

Motorisedwindowvents

EOL

EOL

EOL

EO

L

EO

L

SEOL

A1R

Page 43: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Detectors per zone 30 per zone, maximum

Sounders per zone [1] 30 per zone, maximum

Sounder-Beacons per zone [2] 15 per zone, maximum

Zone Sounder Current (panel total) 1.25A max (see notes 1 & 2)

Sounder current 5mA at either low (70dBA) or high (87dBA) output

Sounders per panel 250

Sounder-Beacon Current 9mA at either low (70dBA) or high (87dBA) output

Sounder-Beacons per panel 135

Inputs Class change, Bomb Alert, Programmable

Display 4 x 20 character LCD + zone fire & fault LEDs and system LEDs

Mains input voltage 230Vac +10% –6% 50Hz

Output auxiliary voltage, DC 24Vdc @ 250mA 12Vdc @ 250mA

Battery size 12V 7AH x 2 (connected in series)

Battery standby Minimum 24 hours (please contact technical sales for further information.)

Construction: Metal back box with moulded polycarbonate front panel in cool grey

Panel dimensions hwd (mm) 469 x 373 x 103

Detector & call point compatibility Sensa – Alarmsense detectors, call points and alarm devices.

Programmable features Extensive via buttons and LCD display

CAN Network Panel and repeater combinations via CAN 2.0b link

Outputs:

Alarm Lines 4

Alarm current total 1.25A- zone sounder current, see note 3

Auxiliary outputs 2 sets of volt free contacts, rated @ 2A 30Vdc

Fault outputs 2 sets of volt free contacts, rated @ 2A 30Vdc

Notes:[1] – Version 2 sounders only[2] – Using version 2 sounder-beacons only[3] – Total Panel Alarm Current is 1.25A. The total zone sounder current must be taken into account when deciding how much load is available for alarm lines

AL1 – 4For example: a maximum of 250 sounders (5mA each) or 135 sounder beacons (9mA each) can be loaded onto the system.

Warning: do not use FAP6 detectors on Alarmsense systems. Although they would appear to work initially, using them could cause severe system malfunction in the longer term. Also beaware that if used with the Sounder/Sounder Beacon Bases the non-priority function will not operate correctly.

Eurofire Repeater panel

PRODUCT ORDER CODE FEUN-RP

Connections 2-core for data from the main panel and 2-core for 24 Vdc power

Display 4 x 20 character LCD with Zone, Fire and Fault LEDs

Inputs Data and DC supply inputs from the main panel (repeater loading must be included when calculating load at the main panel)

Outputs 4 programmable alarm outputs (load to be included in main panel alarm load)

Construction Metal back box with moulded polycarbonate front panel in cool grey

Dimensions hwd (mm) 469 x 373 x 103

Eurofire Sensa 2-wire panels | Conventional

Eurofire Sensa 2-wire panels

www.emergi-lite.co.uk

41

STANDARD ORDER CODE DESCRIPTION

FEWN-4 Eurofire 4 Zone Panel

FEWN-8 Eurofire 8 Zone Panel

FEWN-12 Eurofire 12 Zone Panel

FEWN-16 Eurofire 16 Zone Panel

OPTIONS

Suffix LD Lockable door option for Eurofire Panel

FEUN-RP Eurofire Repeater Panel

ACCESSORIES

F4ALMB 4 way Alarm Extender

F4COB Relay Unit, 4 pole

FEUN-EOL-KIT End of Line Component Kit

FEUN-NETCAN CAN Isolator Assembly

FEUR-BG Semi-recessing bezel grey

FEUN-SPARES Eurofire Spares Pack

To Order

PRODUCT ORDER CODE FEWN-4 FEWN-8 FEWN-12 FEWN-16

No. of zones 4 Zone 8 Zone 12 Zone 16 Zone

Eurofire Sensa, 2-wire panel technical specification

Page 44: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Conventional | Firetec Sensa 2-wire panels

Firetec Sensa 2-wire panels

www.emergi-lite.co.uk

42

Firetec Sensa 2-wire fire panels Benefits and featuresThe panel is easy to install andcomes with a wide range offeatures for the user andmaintenance engineer.

The panel enclosure is shapedwith gentle curves and clean linesto fit in with surrounding décor.

Comprehensive zone coverage:Available in 2, 4 or 8 zone models.

Zone capacity:Nominally 25 devices per zone.

Output wiring:2-wire, giving reduced wiring cost.

Standby duration:48 hours

Walk test:1 man operation

Security coded push button entry:Status can be checked via level 1.Subsequent levels are passwordprotected for the authorised userand engineer respectively

Programmability:Several features such as ‘priority –non priority setting’, ‘delays toalarms’, ‘day mode’ are availableto tailor the function of the panelto local requirements.

Details are listed in thespecification table.

Outputs:Output facilities for Alarm,Volt-free alarm and TTL Fault.

Note: Firetec Sensa 2-wire panelavailable soon. Please contactEmergi-Lite Sales Team for furtherdetails.

STANDARD DESCRIPTIONORDER CODE

FTEW2 Firetec 2 Zone Panel

FTEW4 Firetec 4 Zone Panel

FTEW8 Firetec 8 Zone Panel

Firetec Sensa is a range of conventional (non-addressable) firedetection panels offering a practical, cost effective fire safetysolution for smaller to medium sized premises. Firetec Sensa panelsare designed to comply with the European Standard EN54 Parts 2and 4 and are suitable for BS 5839-1:2002 and BS 5839-6:2004installations.

Firetec Sensa is now more versatile than ever with the ability of handlingdetection and alarm in up to 8 separate zones. Panels are available in2, 4 and 8 zones of fire cover, with flexible setup, control and displaycapabilities, and are configured to operate with ‘2-wire’ Sensa: Alarmsensedetection and alarm devices.

The 2-wire convention uses one pair of wires for the connection of Sensa-compatible devices (detectors, manual call points and alarm sounders). Thisgives the scheme designer a greater flexibility of choice, whilst retainingcompliance with the relevant standards. Benefits can be seen in havingreduced field wiring costs and time saving with ease of installation.

Panels are supplied as a complete package, with all end of line devices,batteries and a logbook included.

Secure panel operation:Key switch activation optionFor installations where it is necessary to secure the panel from interference,a key switch option is available, which enables or disables the controlbuttons on the front fascia. To order this option a suffix KS should beadded to the standard product code.

OPTION

Suffix KS Optional security keyswitch for Firetec panels

Page 45: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Firetec Sensa 2-wire panels | Conventional

Firetec Sensa 2-wire panels

www.emergi-lite.co.uk

43

Connection diagramThe diagram below illustrates an 8 zone Firetec panel connected to detectors, alarms, and call points.

Display & user interfaceThe Firetec Sensa panel includes a clear, easy toreference push button and LED display capable ofproviding the user with all the necessary informationto determine fire, fault or ‘fire and fault’ within aparticular zone. 5 buttons are included on the front ofthe panel which can be used to access the followingfunctions:

Silence alarms or enable/disable zones

Silence buzzer

User zone and 2-wire sounder isolation

Lamp test

Walk and alarm test facility

Reset function

Alarm circuits

NC C NO

Auxiliary relaycontacts

NC C NO+AL2- +AL1- Aux 1 Aux 2+Z1- +Z2-

Ena

ble

dela

y

Cla

ssch

ange

Mon

inpu

t

TT

Lfa

ult

GN

D

C - Classchange switch

End of line resistor10K, on last

sounder

Enable alarmdelay switch

+Aux-24v

Lo Hi+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-

Zones 2,4,5 wired butnot shown

EOL diode to unusedzones [cathode to

zone, +ve end]EOL

resistor inunused

alarm cct

No spurs

Call point

Detector Standard alarm device

C

EOL diode on lastdetector [cathodeto zone +ve end]

No spurs

o

o

o

o

Z1: Priority zoneo

o

Z3: Non-priority zone

o

Priority alarm device

Non-prioity alarm device

Indicator detailsThe panel includes an LED system to indicate fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.

The panel also features indicator LEDs which advise the current state of the fire detection system, to highlightsystem, earth, or supply faults, system disabled or test status, and alarm silenced mode.

Page 46: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Conventional | Firetec Sensa 2-wire panels

Firetec Sensa 2-wire panels

www.emergi-lite.co.uk

44

Notes:

1 Total panel alarm current, is total zone alarm current + total sounder current on AL1 & AL2. Total should not exceed 1A.

2 Ensure that maximum number of sounders/sounder-beacon devices does not exceed total current allowed for zones.30 sounders on a zone = 5mA * 30 = 0.15A. Zone supplying maximum current, no more sounders/sounder-beacons should be placed on zone.16 sounder-beacons on a zone = 9mA * 16 = 0.144A. Zone supplying maximum current, no more sounders/sounder-beacons should be placed on the zone.Sounders and sounder-beacon devices can be used together on a zone but should not exceed the maximum alarm current per zone.

3 Current available for alarm lines AL1 & AL2 = 1A - Total zone alarm current being used.

Detection Circuits Compatible with Emergi-Lite Sensa sounders, manual call points, smoke and heat detectors, Emergi-Lite Sensa zonesounders & zone sounder-beacon bases, Emergi-Lite Sensa priority/non priority devices

Detectors per Zone 25 Detectors per zone

Total Alarm Current (panel total) 1A, see note 1

Maximum Alarm Current Per Zone 0.15A

Sounders Per Zone(Low70dB(A) 5mAHigh87dB(A) 5mA)

25

Sounder-Beacons Per Zone(Low70dB(A) 9mAHigh87dB(A) 9mA)

16

Alarm Lines [AL1 & AL2] 2 Alarm circuits per panel each rated @ 24Vdc 0.5A max, panel total is 1A. Each sounder circuit protected by a resettablefuse - resets when fault is removed. Expandable to 8 circuits in groups of 4 with 4 way alarm extender board

Auxiliary Relay Contacts 2 Sets of volt-free contacts rated 30Vdc @2A - activated during a fire condition when the alarm circuits are activated

Auxiliary Output 24Vdc rated 250mA protected by resettable fuse - resets when fault is removed.

Class Change Connect CC to Gnd terminal to activate sounders.

Fault Monitoring Zone: Short circuit & open circuit/detector removed monitoring using end of line device

Alarm: Short circuit & open circuit using end of line resistor

Mains Input Voltage 230Vac +10% -6%, 50Hz (mains fuse: 20mm, 240Vac 1A High rupture capacity)

Battery 1 x 12V 7AH VRLA (valve regulated lead acid) battery. Temperature compensated charger. Deep discharge protected withcut off at approx. 10.5V. Protected by a resettable fuse - resets when fault is removed.

Battery Standby 48 hours. For more details refer to technical sales for standby calculations.

Supply Fault Monitoring Mains missing - battery missing - battery charger fault

Controls 5 push buttons with coded entry access

Construction Moulded polycarbonate plastic fascia and back box in cool grey

Dimensions hwd (mm) 263 x 337 x 90

Fault Output TTL fault output: Active (5Vdc) when no faults are present - fail safe to off

Programmability Zones individually programmed as latching or unlatching fire conditionsZones individually programmed as Priority or Non Priority

Class change can be programmed to illuminate 'general fire' led when activated.Delay of 1-10 mins to alarms activating in a fire condition - this works in conjunction with

Enable delay' input. 'Enable delay' can also be used as a 'day switch/input.'

PRODUCT ORDER CODE FTEW2 FTEW4 FTEW8

No. of Zones 2 Zone 4 Zone 8 Zone

Firetec Sensa, 2-wire panel technical specification

Page 47: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

AlarmSense devices | Conventional

AlarmSense devices

AlarmSense devices (detectors, manual call points, sounders, sounder beacons and alarm relays) aredesigned to operate normally on the same pair of zone wires from the panel. A key feature is thatalarm sounders can be programmed to operate as so-called ‘priority’ or ‘non-priority’ devices.

A ‘priority’ set device reacts as a normal sounder instandard use and sounds a full alarm. A ‘non-priority’set device will give an initial local alert prior to goinginto full alarm.

‘Non-priority’ devices are intended for use in HMO typeapplications where there are a number of individualdwellings. The operating method is intended to helpreduce the instances of unwanted alarms and give alocal warning before the full alarm/evacuation.

When a heat detector is attached on a sounder orsounder beacon base, we recommend that the sounderbe set as a ‘priority’ device.

For more information about priority/non-prioritydevices, please refer to pages 36 – 37.

Detector base FAPW2-ASB

The Sensa detector base is specific for the Sensa detector range. Electroniccircuitry is included, which monitors the presence of the detector and willsignal a fault if a device is removed.

SPECIFICATION

Quiescent current at 15V <30µA

Load shown to the zone withhead removed

47Ω for 10ms every 4 seconds

Wiring & polarity 2 wire supply, polarity insensitive

Termination Connectors accept up to 2.5mm2 cables

Construction White moulded polycarbonate

Dimensions ø d (mm) 100

Weight g 55

www.emergi-lite.co.uk

45

FAPW2-ASB

Device benefits and featuresThe table below highlights the key features of the sounder bases and sounder-beacon bases available as part of ourconventional 2-wire range.

PRODUCT CODE DESCRIPTION

FAPW2-BS24W Sounder base W

FAPW2-BSB24W Sounder base beacon C W

FAPW2-CBSW Sounder base cap W

FAPW2-CBSR Sounder base cap R

Feat

ure

s:

Beac

on

Soun

der

Am

ber,

Cle

aror

Red

lens

Red

orW

hite

body

Apo

lloA

lert

/Ev

acto

ne

Inte

grat

edba

se

Con

vent

iona

l

Acc

esso

ries

Page 48: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

46

Sounder base unit FAPW2-BS24W

A compact low profile device fitted with a base seat for fitting compatiblesmoke or heat detectors. For standalone use, optional caps in red or whiteare available. The sounder has a volume control (DIL switch selection forhigh or low output) and can operate within the ‘priority/non-priority’signalling regime.

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 12V <20µA

Sounder active current @ 24V 5mA

Sound output dBA, high volume 87

Low volume dBA 70 nominal

Operating temperature –20 to +60ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Connectors accept up to 2.5mm2 cables

Construction Polycarbonate/ABS

Dimensions ø d (mm) 115 x 40

Weight g 150

Standards EN54-3

OPTIONS

FAPW2-CBSW White cap

FAPW2-CBSR Red cap

Conventional | AlarmSense devices

AlarmSense devices

Sounder beacon base FAPW2-BSB24W

A compact low profile device with visual and sound warning indication.The unit is fitted with an integral base seat for fitting compatible smoke orheat detectors. For standalone use, optional caps in red or white areavailable. The sounder has a volume control (DIL switch selection for highor low output) and can operate within the ‘priority/non-priority’ signallingregime.

Suited to premises where visual warning indication is needed for the hardof hearing.

Enables the user to comply with the Disability Discrimination Act (DDA).

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 12V <20µA

Sounder active current @ 24V 9mA

Sound output dBA, high volume 87

Low volume dBA 70 nominal

Operating temperature –20 to +60ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Connectors accept up to 2.5mm2 cables

Construction Polycarbonate

Dimensions ø d (mm) 115 x 40

Weight g 150

Standards EN54-3

OPTIONS

FAPW2-CBSW White cap

FAPW2-CBSR Red cap

FAPW2-BS24W

FAPW2-BSB24W

Application

Owing the level of sound these devices can produce; they are effective forlocal use. For example, in situations where there is a corridor with anumber of adjoining rooms, closed doors can reduce the sound levelsomewhat. Consequently, it is recommended that this type of soundershould be placed in both the room and the corridor.

Page 49: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

47

AlarmSense devices | Conventional

AlarmSense devices

Optical smoke detector FAPW2-OP

The optical detector measures the level of smoke particles using lightscatter, then going to alarm at a pre-set threshold.

Integrating optical smoke detector FAPW2-OP-INT

This detector is available for spaces in buildings where smoke particles(cigarette smoke for example) might be present normally, to help avoidfalse alarms.

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 15V <50µA

Alarm current at 2 – 8.5V10.5 – 15V

<1.5mA25 +/- 2mA

Wiring & polarity 2 wire supply, polarity insensitive

Construction Polycarbonate

Dimensions ø d (mm) 100 x 42

Weight g 100

Standards EN54-7: 2000

Rate of rise device, grade A1R FAPW2-R6

The detector monitors the rate of temperature rise in the vicinity and willalso trigger when a fixed upper threshold of 50°C is reached.

Fixed temperature detector, grade CS FAPW2-F84

The static heat detector will signify fire, when a preset temperature isreached. The CS device will trigger at 80°C.

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 15V <50µA

Alarm current at 12V24V

<1.5mA25 +/- 2mA

Grades A1R & CS

Wiring & polarity 2 wire supply, polarity insensitive

Construction Polycarbonate

Dimensions ø d (mm) 100 x 42

Weight g 100

Standards EN54-5: 2000

FAPW2-OP

FAPW2-R6

FAPW2-F84

Page 50: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Surface mount unit FMFW2-800

The Sensa call point is fitted with frangible element. A key test facility issituated underside, which is fully reset when the key is removed. The deviceis detected as an operated call point by the Sensa system.

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 15V <50µA

Alarm current at 2 – 8.5V10.5 – 15V

<1.5mA25 +/- 2mA

Wiring & polarity 2 wire supply, polarity insensitive

Reset time 1 second

LED indicator Red

Construction Polycarbonate/ABS

Dimensions ø d (mm) 87 x 87 x 52

Weight g 170

Standards EN54-11: 2000

ACCESSORY

RSL800 Fire call point notice sticker

Conventional | AlarmSense devices

AlarmSense devices

www.emergi-lite.co.uk

48

FMFW2-800

Protective covers for manual call pointsA tough protective cover is available to help prevent accidental operationof call points, or prevent unauthorised use by those with malicious intent.The cover is suitable for use in educational buildings, hospitals, nursinghomes or places where the threat of false alarm is prevalent.

STANDARD ORDER CODE DESCRIPTION

FMC-ST30 Surface mount protective cover, with 30mm spacer

FMC-ST50WP Surface mount weatherproof cover, with 50mm spacer

For further options, please contact technical sales.

FMC-ST30

FMC-ST50WP

RSL800

Page 51: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

AlarmSense devices | Conventional

AlarmSense devices

Standard remote indicator unit FAP6-P10

(standard base)A remote indicator is used to help an investigator quickly identify thelocation where a device has registered a fire, without having to gain entryto every room or inaccessible space.

Remote indicator unit FMFW2-PBD20

(sounder base or sounder beacon base)The PBD version is designed to show indication from a detector fitted to asounder base or sounder beacon base in premises such as an HMO.

SPECIFICATION

LED indicator Red

Construction Polycarbonate/ABS

Termination Terminal block

Dimensions ø d (mm) 85 x 85 x 5

Weight g 38.2

Alarm relay FAPW2-ALR

This ancillary unit allows external items, including paging devices andmagnetic door closers to be connected to the 2-wire fire detection system.The relay can be configured to provide two sets of volt-free contacts foruse by external devices.

Selectable DIL switch features:

A relay-reset delay of 2 seconds is selectable by DIL switch.

Non-priority signals from the fire panel can be recognised at the relayaccording to a DIL switch setting, which could enable the relay to beused as a stand-alone alarm indicator or activate an external functionlike a staff alarm.

SPECIFICATION

Voltage range 9 – 33Vdc

Relay operating voltage >18V

Quiescent current at 12V <20µA

Surge current at relay set voltage 15mA for 20ms

Relay contact ratings 1A at 30Vdc

Wiring & polarity 2 wire supply, polarity sensitive

Termination Connectors accept up to 2.5mm2 cables

Dimensions ø d (mm) 65 x 45 x 25

Weight g 35

Standards EN54

Commissioning note: At commissioning the relay should be reset prior touse. During operation the relay will reset if there is a power loss on the firealarm circuit.

www.emergi-lite.co.uk

49

FAP6-P10

FAPW2-ALR

o o

Remote indicator

Closed roomspace

Normaldetection:

Indicator visible

Corridor

Vision panel in doorSolid door

-ve+

ve-R

Zone

Zone

Zone inZone out

L1 zone +ve

L2 zone -ve

Rem

oteLE

Dboard

R5

Connection of remote LED unit to Sensasounder or sounder-beacon bases

Page 52: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Eurofire 4-wire panels

Conventional | Eurofire 4-wire panels www.emergi-lite.co.uk

50

Eurofire 4-wire fire panels

Traditionally, conventional fire systems have been wired as ‘4-wire’installations, where the detection and alarm devices are wiredseparately from the panel. This does give some integral protectionwhere the alarm circuit would not be affected by a fault on thedetection side.

Eurofire EN54 is a conventional (non-addressable) fire detection systemwith enhanced safety, technical and practical features for the installer anduser. Eurofire EN54 panels are designed to comply with the EuropeanStandard EN54 Parts 2 and 4 and are suitable for BS 5839-1:2002 andBS 5839-6:2004 installations.

Panels are configured to operate with ‘4-wire’ detection and alarm devicesand are available as a standalone panel for 4, 8, 12 or 16 zones of firecover, ideal for medium sized premises. Alternatively, for larger installationsEurofire can be networked with sister Eurofire panels and repeaters forcomplete cover over the site.

Panels are supplied as a complete package, with all end of line devices,batteries and a logbook included.

Benefits and featuresThe panel has an extensive arrayof useful tools and featuresdesigned to help both the installerto set up the system easily and theuser to manage the systemeffectively.

Standby duration:48 hours

Zone capacity:Up to 30 devices per zone.

Soft select:Non-latching or latching on fire:The non-latching zone featureallows a better integrityconnection to existing systems(other manufacture). This methodwill monitor the interconnectionbetween panels and allow panelsto be reset more readily (thepanel being connected to, musthave a spare zone and alarm lineor auxiliary contacts with avolt-free pair). Short circuit fire orfault for older systems.

Security control:Coded push button entry:The status viewer has quick entry atlevel 1. Levels 2 and 3 are passwordprotected for the authorised userand Engineer respectively.

Outputs:4 Programmable Alarm outputs.Fire auxiliary volt-free relaycontacts, which are programmablefor continuous, pulsing anddelayed operation. Fault volt-freerelay contacts.

Output wiring:Conventional 4-wire to the zones.

2-wire zone selection:In instances, where it is desired torun a zone of 2-wire devices, thepanel can be programmed toachieve this by a trainedcommissioning engineer.

Sounder delay activation:A sounder ‘delay-on’ facilityallows the user to programmechosen sounders or beacons toactivate at a later moment. Idealwhere it is beneficial not to haveundue panic, such as in bars orSoft Play centres.

Networking capability:Coverage in larger buildingcomplexes can be achieved bylinking Eurofire EN54 panels andrepeaters together via a ‘CANConnect’ link. It is also possible tomake more power available forsounder circuits or save on fieldwiring.

Page 53: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Eurofire 4-wire panels

Eurofire 4-wire panels | Conventionalwww.emergi-lite.co.uk

51

Panel DisplayThe Eurofire panel includes an easy to reference display with LCD screen allowing for up to four lines of text, withtext programmable for each zone. 6 buttons are included on the front of the panel which can be used to access thefollowing functions:

Lamp test, silence alarms, silence buzzer

User zone and sounder isolation

Walk and alarm test facility with mute option

99-event history log that stores any events withtime and date stamp, for the user to scroll

Configurable system message for the user withnormal time and date displayed

The panel also features indicator LEDs which advisethe current state of the fire detection system, and givea clear signal of fire or fault in any particular zone.

Further functionality includes the facility to reviewevent logs, to override any pre-set alarm delays, andto enable sounding the evacuation to all zones.

Networking capabilityFire detection coverage in a larger building complex can be achieved by linking Eurofire EN54 panels and repeaterstogether via a ‘CAN Connect’ link. (‘CAN Connect’ is a readily available communications protocol.) It is also possibleto make more power available for sounder circuits (additional 4), or save on field wiring:

Indicator detailsThe panel includes indicators for information, fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.

Scenario: In abuilding, one panelmight be sited in theoffice area and onein the warehousearea. The zones foreach area are wiredto their respectivepanels. Network thepanels and theoffice unit has fullvisibility of thebuilding. It may benecessary to use ahigher rated cableand the Emergi-Litenetwork card (pleasecontact Technicalsales for furtherguidance).

A1 R

c s

o

o

oo

o EO

L

o

EO

L

o

o

EOL

SEOL

SEOL

Network

Zone 8

Eurofire c-net

Zone 1

Zone 7

Zone 2

Illustration: 8 zone Eurofirewith network panel connected

4 sounder circuits, 2shown connected

EO

L

Page 54: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

52

Eurofire 4-wire panels

Conventional | Eurofire 4-wire panels

Connection diagramThe diagram below illustrates a Eurofire panel connected to detectors, sounders, and call points.

Eurofire 4-wire zonal layoutThe illustration below shows a potential scheme layout for a Eurofire panel, over 5 active zones, with 4 alarm circuits.

Alarm circuits

Auxiliary relaycontacts

NC C NO +AL2-+AL1-

Aux 1 Aux 2

+Z1- +Z2-

Cla

ssch

ang

e

TTL

fau

lt

GN

D

- 24v +

+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-NC C NONC C NO NC C NO

Co

mm

on

fau

lt

Pro

gi/p

Bo

mb

aler

t+AL3- +AL4-

Isolated CAN network

HI LO SCR HI LO SCRHI LO SCR HI LO SCR

CAN network

- 24v +- 12v +

Auxoutputs

Auxi/p

- +AC AC

Batt

+Z10-+Z9- +Z11- +Z12- +Z13- +Z14- +Z15- +Z16-

o

o

o

Fault 1 Fault 2

Zones 2-8 wired as Z1

EOL diode to unusedzones [cathode to

zone, +ve end]

EOLresistor in

unusedalarm ccts

No spurs

EOL diode on lastdetector [cathodeto zone +ve end]

o

No spurs

o

c s

o

o

o

o o

oo

o

o

o

o

o

o

o

o

EO

L

EOL

EOL

Programmablesounder circuits from

the panel

Zone circuits toEurofire 4wpanel

Illustration:Scheme layout using aEurofire panel [5 zones active,with four alarm circuits]

EOL

Kitchen

Fire exit

Fire exit

Fireexit

Apex roof

SEOL

SEO

L

SEOL

SEOL

EOL

Key:

o

c s

EOL

Call point

Opticalsmokedetector

Heat detector

Beam detector set

End of line device -detector circuit

Sounder

Sounder-beacon

Zone: detection circuitwiring

Alarm circuit wiring

SEOL End of line device -alarm circuit

Page 55: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

53

www.emergi-lite.co.uk

PRODUCT ORDER CODE FEUN-4 FEUN-8 FEUN-12 FEUN-16

No. of zones 4 Zone 8 Zone 12 Zone 16 Zone

Detectors per zone 30 per zone maximum

No. of alarm lines 4 (expandable to 16 programmed in groups of 4, with card extenders)

Maximum alarm load Total = 1.25A. Maximum per line or circuit = 1A

Inputs Class change. Bomb Alert and Programmable input

Display 4 x 20 character LCD, plus zone fire and fault LEDs

Mains input voltage 230Vac +10%, –6% 50Hz

Output auxiliary voltage, DC 24Vdc & 12Vdc @ 250mA

Battery size 12V 7AH x 2 (connected in series)

Battery standby 24 hours minimum (please contact technical sales for further information.)

Construction: Metal back box with moulded polycarbonate front panel in cool grey

Dimensions hwd (mm) 469 x 373 x 103

Detector & call point compatibility ‘Emergi-Lite Orbis’ and FAP6 smoke and heat with diode base. Manual call points with 220-680 ohm resistor

Outputs:

Auxiliary outputs Two sets of volt-free aux. programmable contacts (rated 2A @ 30Vdc)

Fault outputs Two sets of volt-free fault contacts (rated 2A @ 30Vdc)

Additional options:

FEUN-BG Semi-recessing trim bezel finished in grey

Networking Panels networked using ‘CAN’ Network terminals. An ‘isolated CAN network driver’ is available for isolated networks.Please contact technical sales for particular need

Zone upgrade Where a user expects to expand coverage in the future a special upgradeable version can be supplied.Please specify the requirement when requesting a quotation

Eurofire Repeater panel

PRODUCT ORDER CODE FEUN-RP

Connections 2-core for data from the main panel and 2-core for 24Vdc power

Display 4 x 20 character LCD with Zone, Fire and Fault LEDs

Inputs Data and DC supply inputs from the main panel (repeater loading must be included when calculating load at the main panel)

Outputs 4 programmable alarm outputs (load to be included in main panel alarm load)

Battery size 12V 7AH x 2 (connected in series)

Construction Metal back box with moulded polycarbonate front panel in cool qrey

Dimensions hwd (mm) 469 x 373 x 103

Eurofire 4-wire panels

Eurofire 4-wire panels | Conventional

STANDARD ORDER CODE DESCRIPTION

FEUN-4 Eurofire 4 Zone Panel

FEUN-8 Eurofire 8 Zone Panel

FEUN-12 Eurofire 12 Zone Panel

FEUN-16 Eurofire 16 Zone Panel

OPTIONS

Suffix LD Lockable door option for Eurofire Panels

FEUN-RP Eurofire Repeater Panel

ACCESSORIES

F4ALMB 4 way Alarm Extender

F4COB Relay Unit, 4 pole

FEUN-EOL-KIT End of Line Component Kit

FEUN-NETCAN CAN Isolator Assembly

FEUR-BG Semi-recessing bezel grey

FEUN-SPARES Eurofire Spares Pack

To Order

Eurofire conventional, 4-wire panel technical specification

Page 56: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Firetec 4-wire panels

Conventional | Firetec 4-wire panels

STANDARD ORDER CODE DESCRIPTION

FTEP1 Firetec 1 Zone Panel

FTEP2 Firetec 2 Zone Panel

FTEP4 Firetec 4 Zone Panel

FTEP8 Firetec 8 Zone Panel

ACCESSORIES

FTE-EOL-KIT End of Line Component Kit

FTE-BG Semi-recessing bezel grey

FTE-SPARES Firetec Spares Pack

www.emergi-lite.co.uk

54

Firetec 4-wire fire panels Benefits and featuresThe panel is easy to install and comes with a widerange of features for the user and maintenanceengineer.

The panel enclosure is shaped with gentle curves andclean lines to fit in with surrounding décor.

Comprehensive zone coverage:Available in 1, 2, 4 or 8 zone models.

Zone capacity:Nominally 25 devices per zone.

Standby duration:48 hours

Walk test:1 man operation

Display and user interface:Indicators for information, fire, fault and ‘fire & fault’

Security coded push button entry:Status can be checked via level 1. Subsequent levelsare password protected for the authorised user andengineer respectively

Programmability:A number of features are available including‘latching/unlatching zones’, ‘delays to alarmactivation’, ‘monitored input’ (which can be on or off).Programmability is detailed in the specification table.

Outputs:A set of output facilities for Alarm, Volt-free alarmand TTL fault

Traditionally, conventional fire systems havebeen wired as ‘4-wire’ installations, where thedetection and alarm devices are wiredseparately from the panel. This does give someintegral protection where the alarm circuitwould not be affected by a fault on thedetection side.

Firetec is a conventional (non-addressable) firedetection panel that is suited for fire detectioncoverage in smaller premises, such as offices andshops. The panel is configured to operate with ‘4-wire’detection and alarm devices and is available as astandalone panel for 1, 2, 4 or 8 zones of fire cover.

Firetec panels are designed to comply with theEuropean Standard EN54 Parts 2 and 4 and aresuitable for BS 5839-1:2002 and BS 5839-6:2004installations.

Panels are supplied as a complete package, with allend of line devices, batteries and a logbook included.

Secure panel operation:Key switch activation optionFor installations where it is necessary to secure the panel from interference,a key switch option is available, which enables or disables the controlbuttons on the front fascia. To order this option a suffix KS should beadded to the standard product code.

OPTION

Suffix KS Optional security keyswitch for Firetec panels

Page 57: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Firetec 4-wire panels

Firetec 4-wire panels | Conventionalwww.emergi-lite.co.uk

55

Connection diagramThe diagram below illustrates an 8 zone Firetec panel connected to detectors, alarms, and call points.

Display & user interfaceThe Firetec 4-wire panel includes a clear, easy toreference push button and LED display capable ofproviding the user with all the necessary informationto determine fire, fault or ‘fire and fault’ within aparticular zone. 5 buttons are included on the front ofthe panel which can be used to access the followingfunctions:

Silence alarms or enable/disable zones

Silence buzzer

User zone and sounder isolation

Lamp test

Walk and alarm test facility

Reset function

Alarm circuits

NC C NO

Auxiliary relaycontacts

NC C NO+AL2- +AL1- Aux 1 Aux 2+Z1- +Z2-

o

o

o

Enab

led

elay

Cla

ssch

ang

e

Mo

nin

pu

t

TTL

fau

lt

GN

D

C - Classchange switch

End of line resistor10K, on last

sounder

Enable alarmdelay switch

+Aux-24v

Lo Hi+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-

Zones 2-5 wired as Z1 EOL diode to unusedzones [cathode to

zone, +ve end]

Firetec 8 zone: wiring illustration -zones & alarms

EOL diode on lastdetector [cathodeto zone +ve end]

EOLresistor –unused

alarm cct

No spurs

o

No spurs

o

Call point

Detector

Alarm device

C

Indicator detailsThe panel includes an LED system to indicate fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.

The panel also features indicator LEDs which advise the current state of the fire detection system, to highlightsystem, earth, or supply faults, system disabled or test status, and alarm silenced mode.

Page 58: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

56

Auxiliary output 24Vdc rated 250mA protected by resettable fuse – resets when fault is removed

Auxiliary relay 2 Sets of volt-free contacts rated 30Vdc @2A – activated during a fire condition when the alarm circuits are activated

Panel controls & indicators:

Controls 5 push buttons (with coded entry access)

Indicators 27 LED indicators for fire, fault or fire and fault

Construction: Moulded polycarbonate plastic fascia and back box in cool grey

Dimensions hwd (mm) 263 x 337 x 90

Weight (Kg), without battery 2.55

Cable requirements To comply with the recommendations of BS 5839-1:2002, section 26 for cables, wiring and other interconnections

Detector & call point compatibility * Compatible with Emergi-Lite Orbis smoke and heat detectors with diode base.* Compatible with FAP6 smoke and heat detectors with diode base.

* Compatible with 220 – 680 Ohm Manual Call Points (MCP).

Programmability Zones individually programmed as latching or unlatching fire conditionsZones individually programmed as 470 Ohm or short circuit fire detection

Class change can be programmed to illuminate ‘general fire’ led when activated.Delay of 1-10 mins to alarms activating in a fire condition – this works in congunction with

Enable delay’ input. ‘Enable delay’ can also be used as a ‘day switch/input.’

Class Change Connect CC to Gnd terminal to activate sounders

Fault Monitoring Zone: Short circuit & open circuit/detector removed monitoring using end of line deviceAlarm: Short circuit & open circuit using end of line resistor

Fault Output TTL fault output: Active (5Vdc) when no faults are present – fail safe to off

Additional options:

FTEP-BG Recessing bezel kit

Alarm Lines 2 Alarm circuits per panel each rated @ 24Vdc 0.5A max. 2 Alarm circuits per panel each rated @ 24Vdc 1A max.

Panel total is 0.5A Panel total is 1A

Each sounder circuit protected by a resettable fuse – resets when fault is removed

Expandable to 8 circuits in groups of 4 with 4 way alarm extender board

Power supply:

Supply Fault Monitoring 230Vac +10% -6%, 50Hz (mains fuse: 20mm, 240Vac 1A High rupture capacity)

Supply Fault Monitoring Mains missing – battery missing – battery charger fault

Battery 1 x 12V 7AH VRLA (valve regulated lead acid) battery

Battery charger Battery charger is temperature compensated

Battery deep discharge protection Battery is deep discharge protected (cut off at approx. 10.5V)

Battery fuse protection Battery protected by resettable fuse – resets when fault is removed

Battery Standby [up to 4z, then 8z] 72 hours with 20 detectors per zone and 30 mins of0.75A alarm load

48 hours with 20 detectorsper zone and 30 mins of

1A alarm

For more details refer to technical sales for standby calculations

Firetec 4-wire panels

Conventional | Firetec 4-wire panels

PRODUCT ORDER CODE FTEP1 FTEP2 FTEP4 FTEP8

Zones of Fire Protection 1 2 4 8

Detectors per zone 25

Firetec conventional, 4-wire panel technical specification

Page 59: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk Emergi-Lite Orbis detectors | Conventional

Emergi-Lite Orbis detectors

Emergi-Lite Orbis brings the latest in fire detector microprocessor technology to the Firetec and Eurofiresystems. Non-addressable (conventional) smoke and heat sensors respond to fire situations within agiven zone, sending a signal to the fire panel, which will indicate a fire condition and sound the alarm.

Orbis provides valuable core features, with high reliability, a marked reduction in unwanted false alarms,complemented by operational and maintenance enhancements.

Features:

StartUp: Correct installation – a flashing red LED

Continuity link: Zone wiring can be voltagetested before commissioning

Wide-angle optics: Responsive to fires with blackor white smoke

Drift Compensation: Calibrated sensitivity levelsare maintained despite contamination

DustDefy: Dust ingress prevented while airflow isunimpeded

Transient Rejection: Abnormal readings arefiltered out to reduce false alarms

DirtAlert: A flashing yellow LED will indicatewhen the drift compensation limit has beenreached

SensAlert: A flashing yellow LED indicatesincorrect sensor operation

Fast Test: A 4 second test confirms correct detector operation

E-Z Fit slots: Remove and refit the base without dismounting the fixing screws

Detector base with diode FAPO-TDB

The standard detector base has a diode fitted beneath the connectors. Alink feature enables voltage testing of zone wiring before commissioning.

The base is a five terminal unit – positive IN, positive OUT, Negative IN &OUT, remote LED negative and functional earth (screen) wire. Two fixingcentre positions are provided at 51 and 60mm.

SPECIFICATION

Construction White moulded polycarbonate

Termination Connectors accept up to 2.5mm2 cables

Dimensions ø d (mm) 100 x 15

Weight g 60

Detector relay base FAPO-TRB

The relay base has a single pole voltage free changeover contact for use toswitch ancillary equipment. When the detector goes to alarm the relay isenergised and changes state.

Contacts rated at 30Vdc, 1A.

SPECIFICATION

Termination Connectors accept up to 2.5mm2 cables

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 15

Weight g 60

FAPO-TDB

FAPO-TRB

57

Page 60: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.ukConventional | Emergi-Lite Orbis detectors

58

Optical smoke detector FAPO-OPT

The optical detector measures the level of smoke particles using lightscatter, going to alarm at a pre-set threshold. New optics help reduce falsealarms while stability is strengthened by using internal software control.

Recommended for general purpose use to give early warning of fire.

SPECIFICATION

Voltage range 8.5 – 33Vdc

Average quiescent current at 24V 65µA

Alarm current at 12V24V

20mA40mA

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 97 x 31 (100 x 46 inc base)

Weight g 75, 135 with base

Standards EN54-7: 2000

Optical smoke and thermally FAPO-MUS

enhanced detectorThe detector uses optical and heat sensing technology in deciding when totrigger an alarm condition. The unit is designed as a smoke detector andcannot be switched from smoke to heat detection.

This detector is more sensitive to fast burning, flaming fires than theoptical model. Ideal for where heat is prevalent at an early stage inthe fire.

SPECIFICATION

Voltage range 8.5 – 33Vdc

Average quiescent current at 24V 65µA

Alarm current at 12V24V

20mA40mA

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 97 x 42 (100 x 57 inc base)

Weight g 80, 140 with base

Standards EN54-7: 2000

Emergi-Lite Orbis detectors

FAPO-OPT

FAPO-MUS

Page 61: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

59

www.emergi-lite.co.uk Emergi-Lite Orbis detectors | Conventional

Emergi-Lite Orbis detectors

Heat detectors – FAPO-HR1, FAPO-HR2, FAPO-HR3

Fixed temperatureThe fixed (static) heat detector will trigger when a pre-set uppertemperature threshold is exceeded at the sensor.

Classification – maximum application temperature: HR1 = 50ºC, HR2 = 65ºC,HR3 = 80ºC

SPECIFICATION

Voltage range 8.5 – 33Vdc

Average quiescent current at 24V 65µA

Alarm current at 12V24V

20mA40mA

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 42

Weight g 100

Standards EN54-5: 2000

STANDARD ORDER CODE DESCRIPTION

FAPO-HR1 Heat detector – Fixed upper threshold 50ºC, A2S

FAPO-HR2 Heat detector – Fixed upper threshold 65ºC, BS

FAPO-HR3 Heat detector – Fixed upper threshold 80ºC, CS

Heat detectors – FAPO-RR1, FAPO-RR2 , FAPO-RR3

Rate of riseThe heat detector will monitor the rate of temperature increase in thevicinity and will also be triggered when a fixed upper thresholdtemperature level is exceeded.

Readings are taken every 2 seconds, the stored values are compared againsta preset value to decide if an alarm level has been reached.

Classification – maximum application temperature: RR1= 50ºC, RR2 = 65ºC,RR3 = 80ºC

SPECIFICATION

Voltage range 8.5 – 33Vdc

Average quiescent current at 24V 65µA

Alarm current at 12V24V

20mA40mA

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 97 x 36 (100 x 51 inc base)

Weight g 70, 130 with base

Standards EN54-7: 2000

STANDARD ORDER CODE DESCRIPTION

FAPO-RR1 Heat detector -Rate of rise with fixed upper threshold 50ºC, A1R

FAPO-RR2 Heat detector -Rate of rise with fixed upper threshold 65ºC, BR

FAPO-RR3 Heat detector -Rate of rise with fixed upper threshold 80ºC, CR

FAPO-HR1

FAPO-RR1

Page 62: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Conventional 4-wire detectors

www.emergi-lite.co.ukConventional | Conventional 4-wire detectors

60

Detector base with diode FAP6-STB

The standard detector base has a diode fitted beneath the connectors.

SPECIFICATION

Termination Connectors accept up to 2.5mm2 cables

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 15

Weight g 60

Relay base FAP6-RLB

The relay base incorporates a set of volt-free changeover contacts, whichwill latch when the detector registers an alarm.

FAP6-STB

FAP6-RLB

Conventional 4-wire detection: The FAP6 rangeIntroducing the FAP6 range of detectors, for use with the Firetec and Eurofire 4-wire panels. FAP6provides proven technology in a slim package, the concise range comprises optical and heat detectors(fixed and rate of rise temperature). In conjunction with Firetec the range is suited to small to mediumsized buildings.

FAP6 is based on series 65technology from Apollo FireDetectors Ltd

SPECIFICATION

Voltage range 9 – 33Vdc

Relay base alarm current at 24V 17mA

Modes Latching

Operating temperature -20 to +70ºC

Termination Connectors accept up to 2.5mm2 cables

Construction White moulded polycarbonate

Dimensions ø d (mm) 100, 25

Weight g 100

Page 63: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

61

www.emergi-lite.co.uk Conventional 4-wire detectors | Conventional

Conventional 4-wire detectors

Relay base, 12 volt FAP6-RLB12

The low voltage relay base incorporates a set of volt-free changeovercontacts that can be used for either latching or non-latching (securitysystem) purposes. To enable control of an automatic door closer,for example.

SPECIFICATION

Voltage range 9 – 15Vdc

Average quiescent current at 12V <10µA

Relay base alarm current, at 12V 20mA

Modes Latching or non-latching

Operating temperature –20 to +70ºC

Termination Connectors accept up to 2.5mm2 cables

Construction White moulded polycarbonate

Dimensions ø d (mm) 100, 25

Weight g 100

Optical smoke detector FAP6-OPT

The optical detector measures the level of smoke particles using lightscatter, going to alarm at a pre-set threshold. New optics help reduce falsealarms while stability is strengthened by using internal software control.

Recommended for general purpose use to give early warning of fire.

SPECIFICATION

Voltage range 8.5 – 33Vdc

Average quiescent current at 24V 65µA

Alarm current at 12V24V

20mA40mA

Alarm indication Clear LED, red on alarm

Operating temperature -20 to +60ºC

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)

Weight g 99, 150 with base

Standards EN54-7: 2000

FAP6-RLB12

FAP6-OPT

Page 64: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

62

Conventional 4-wire detectors

Conventional | Conventional 4-wire detectors

Heat detector – FAP6-RR6, FAP6-RR75, FAP6-RR90

Rate of riseThe heat detector will monitor the rate of temperature increase in thevicinity and will also be triggered when a fixed upper thresholdtemperature level is exceeded.

Classification – maximum application temperature: RR6= 50ºC, RR75 = 65ºC,RR90 = 80ºC

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 24V <50µA

Alarm current at 9V24V

17mA52mA

Alarm indication Red LED

Operating temperature –20 to +90ºC

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)

Weight g 80, 131 with base

Standards EN54-7: 2000

STANDARD ORDER CODE DESCRIPTION

FAP6-RR6 Heat detector – Rate of rise with fixed upper threshold 50ºC, A1R

FAP6-RR75 Heat detector – Rate of rise with fixed upper threshold 65ºC, BR

FAP6-RR90 Heat detector – Rate of rise with fixed upper threshold 80ºC, CR

FAP6-RR6

Heat detector – FAP6-FT8

fixed temperatureThe fixed (static) heat detector will trigger when a pre-set uppertemperature threshold is exceeded at the sensor.

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 24V <50µA

Alarm current at 9V24V

17mA52mA

Alarm indication Red LED

Operating temperature –20 to +90ºC

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)

Weight g 80, 131 with base

Standards EN54-5: 2000

FAP6-FT8

Page 65: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

63

www.emergi-lite.co.uk Conventional 4-wire call points | Conventional

Conventional 4-wire call points

Call point FMC-200R

Surface mounted manually operated call point with LED indicator,providing a switch closure to the panel when operated. Features:

Secure clip-fix front cover

A single key for test, reset and removal of cover

SPECIFICATION

Voltage range 24Vdc

Impedance 470R series resistor

Alarm indication Red LED

Operating temperature -25 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Construction ABS plastic in red

Ingress rating IP42

Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)

Weight g 190

Standards EN54-11

OPTIONS

FMC-200RS Call point with re-settable plastic element

FMC-10G Spare glass (pack of 10)

FMC-10GRS Spare re-settable element (pack of 10)

Weatherproof call point FMC-200RWP

Surface mounted manually operated call point with LED indicator,providing a switch closure to the panel when operated. Features:

Secure clip-fix front cover

One key for test, reset and removal of cover

Weatherproof to IP67

SPECIFICATION

Voltage range 24Vdc

Impedance 470R series resistor

Alarm indication Red LED

Operating temperature –25 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Construction ABS plastic in red

Ingress rating IP67

Dimensions lwd (mm) 110 x 110 x 65

Weight g 290

Standards EN54-11

OPTION

FMC-200RSWP Weatherproof call point with re-settable plastic element

ACCESSORIES FOR FMC CALL POINTS

FMC-KEY Spare test key (pack of 10)

FMC-10G Spare glass (pack of 10)

FMC-10GRS Spare re-settable element (pack of 10)

FMC-PC Polycarbonate cover

FMC-PCS Polycarbonate cover with security tie

RSL800 Fire call point notice sticker

SPARES FOR FMC INDOOR CALL POINTS

FMC-BBR Back box in red

FMC-BBW Back box in green

FMC-200R

FMC-200RWP

For standard and weatherproofprotective call point covers, seepage 88.

RSL800

Page 66: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

64

Conventional 4-wire call points

Conventional | Conventional 4-wire call points

Call point FMC-800R

Surface mounted manually operated call point, providing a switch closureto the panel when operated. Features:

Secure clip-fix front cover

A single key for test, reset and removal of cover

SPECIFICATION

Voltage range 24Vdc

Impedance 470R series resistor

Operating temperature –25 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Construction ABS plastic in red

Ingress rating IP42

Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)

Weight g 190

Standards EN54-11

OPTION

FMC-800RS Call point with re-settable plastic element

Weather resistant call point FMC-800RWP

Surface mounted manually operated call point, providing a switch closureto the panel when operated. Features:

Secure clip-fix front cover

One key for test, reset and removal of cover

Weatherproof to IP67

SPECIFICATION

Voltage range 24Vdc

Impedance 470R series resistor

Operating temperature –25 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Construction ABS plastic in red

Ingress rating IP67

Dimensions lwd (mm) 110 x 110 x 65

Weight g 290

Standards EN54-11

OPTION

FMC-800RSWP Weatherproof call point with re-settable plastic element

ACCESSORIES FOR FMC CALL POINTS

FMC-KEY Spare test key (pack of 10)

FMC-10G Spare glass (pack of 10)

FMC-10GRS Spare re-settable element (pack of 10)

FMC-PC Polycarbonate cover

FMC-PCS Polycarbonate cover with security tie

RSL800 Fire call point notice sticker

SPARES FOR FMC INDOOR CALL POINTS

FMC-BBR Back box in red

FMC-BBW Back box in green

FMC-800R

FMC-800RWP

For standard and weatherproofprotective call point covers, seepage 88.

RSL800

Page 67: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

65

www.emergi-lite.co.uk Conventional 4-wire call points/ancillary | Conventional

Conventional 4-wirecall points/ancillary

Key-switch operated call point FMC-2KSW

A key-switch operated call point for use in secure premises where restrictedaccess is needed.

Suitable for use with 230Vac systems

SPECIFICATION

Voltage range 24Vdc

Operation 2 position keyswitch with 1 NO contact and 1 NC contact

Switch rating 10A, 24Vdc 2A, 230Vac

Operating temperature –25 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Flying lead connections

Construction ABS plastic in red

Ingress rating IP42, when fitted to a standard back box

Dimensions lwd (mm) 87 x 87 x 20

Weight g 190

Standards EN54-11

Fitting The 2KSW can be used with either a standard or a weatherresistant back box.

FMC-2KSW

Remote Indicator unit FAP6-P10

A remote indicator is used to help an investigator quickly identify thelocation where a device has registered a fire, without having to gain entryto every room or inaccessible space. Features:

Fire detector operated text

SPECIFICATION

LED indicator Red

Termination Terminal block

IP rating IP42

Dimensions lwd (mm) 86.5 x 86.5 x 9

Weight g 38

Ceiling tile mounting box FAP-MBCT

The fixture is used to fit a detector or sounder into a false ceiling matrix.The devices can be pre-wired and tested before the ceiling is fitted. Withthe ceiling tiles in place, the MBCT assemblies can be slotted into place.

FAP6-P10

FAP-MBCT-FD

STANDARD ORDER CODE DESCRIPTION

FAP-MBCT-FD Ceiling tile mounting box for detectors

FAP-MBCT-SO Ceiling tile mounting box for sounders

o o

Remote indicator

Closed roomspace

Normaldetection:

Indicator visible

Illustration: Use of remote indicatorin conventional fire system

Corridor

Vision panel in doorSolid door

L1 in

L1 out

- RZone+

Zone -

End of linedevice

Example: Connecting a remote indicator to anFAP6 detector base (shown common across

two detectors) in a zone

L2Earth

L1 in

L1 out

L2

- R

Note: A diode is normallyfitted between L1 in & L1 out

LED-

COM-

IN+

OUT+LED-

COM-

IN+

OUT+

Connection of remote LED unitto FAPO Orbis detector

EO

L

Zone

Zone -ve

Zone +ve

Note: A diode is normallyfitted between IN+ & OUT-

Remote LEDindicator

Page 68: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

66

www.emergi-lite.co.uk

Conventional 4-wire alarms

Conventional | Conventional 4-wire alarms

FACS Conventional 4-wire sounders,beacons and alarm bellsEmergi-Lite Safety Systems offers a range of sounderand alarm options, for use with Firetec and Eurofire4-wire panels.

The table below highlights the key features ofindividual alarms to assist with planning and selection,when preparing a fire detection and evacuationsystem.

PRODUCT CODE DESCRIPTION

FACS-5W Sounder base W 67

FACS-5TPR Sounder base cap R 67

FACS-5TPW Sounder base cap W 67

FACS-1R Sounder R 67

FACS-1RL Sounder R 67

FACS-1W Sounder W 67

FACS-1WL Sounder W 67

FACS-BBR Back box for FACS1R R 67

FACS-BBW Back box for FACS1W W 67

FACS-4R Sounder R 68

FACS-4RDB Sounder R 65 68

FACS-4W Sounder W 68

FACS-4WDB Sounder W 65 68

FACS-8R Sounder-beacon R R 68

FACS-8RDB Sounder-beacon R R 65 68

FACS-8RDB-A Sounder-beacon A R 65 68

FACS-8W Sounder-beacon R W 68

FACS-8WDB Sounder-beacon R W 65 68

FACS-BEA-R Beacon R R 69

FACS-BEA-RDB Beacon R R 65 69

FACB-624 Bell R 69

FACB-624-G Bell G 69

FAAB-624-WP Bell R 55 70

Feat

ure

s:

Bell

6in

diam

Beac

on

Soun

der

Soun

der:

room

/be

dhea

d

Soun

der

beac

on

Am

ber,

Cle

aror

Red

lens

Red.

Whi

teor

Gre

ybo

dy

Vis

ualL

ED

IPra

ting

100

dB(A

)

Inte

grat

edba

se

Acc

esso

ries

32To

nera

nge

Page

refe

renc

e

Page 69: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

67

www.emergi-lite.co.uk

Conventional 4-wire alarms

Conventional 4-wire alarms | Conventional

Low profile sounder FACS-5W

A low height sounder that can be used standalone with an optional coveror as a platform for a smoke/heat detector with a detector base. Features:

Four selectable tones including warble, pips and sweep

SPECIFICATION

Voltage range 8 – 35Vdc

Current draw @ 24Vdc 11mA

Sound output, at 1m (dBA) 91 (94 with cover plate)

No. of tones 4

Operating frequency 800Hz to 1Khz

Operating temperature –20 to +70ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Terminal block

Cable entry Rear

Construction ABS plastic

Ingress rating IP43 (DB version - IP65)

Dimensions ø h (mm) 106 x 25 (35 with cover)

Weight g 121

OPTIONS

FACS-5TPW White cover

FACS-5TPR Red cover

Room sounder FACS-1R

A room sounder, suitable for bedroom and passageway use. Features:

Low profile with a small footprint

Audio/visual version with flashing LEDs on alarm

Four selectable tones including warble, pips and sweep

SPECIFICATION

Voltage range 8 – 35Vdc

Current draw @ 24Vdc 11mA

Sound output, at 1m (dBA) 97

No. of tones 4

Volume control -50dBA

Operating frequency 800Hz to 1Khz

Operating temperature -20 to +70ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Terminal block

Cable entry Rear (or side entry with surface box)

Construction ABS plastic

Ingress rating IP43

Dimensions lwd (mm) 86.5 x 86.5 x 9 (+25.2 back box or recessed)

Weight g 103

OPTIONS

FACS-1RL Room sounder, red, with two flashing hi-intensity LEDs

FACS-1W Room sounder, white

FACS-1WL Room sounder, white, with two flashing hi-intensity LEDs

FACS-BBR Back box for FACS-1R

FACS-BBW Back fox for FACS-1W

FACS-5W

FACS-5TPW

FACS-1R

Page 70: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

68

Conventional 4-wire alarms

Conventional | Conventional 4-wire alarms

Open area sounder FACS-4R

A multi-tone sounder for open area use, operating across a range offrequencies. Features:

Quick fit installation

32 tones, selectable by DIL switch

High, medium and low outputs can be selected to fit in with a localsound pattern requirement

Side grub screw for security locking

SPECIFICATION

Voltage range 15 – 35Vdc

Sound level Low Med Hi

Current draw @ 24Vdc <9mA <18mA <36mA

Sound output, at 1m, 1st tone (dBA) 91 106 111

No. of tones 32

Operating frequency 440 to 2900Hz

Operating temperature –20 to +70ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Terminal block

Cable entry Rear (DB rear or side entry [with cover plate])

Construction ABS plastic

Ingress rating IP43 (DB version - IP65)

Dimensions ø h (mm) 93.6 (DB-93) x 84.3 (DB-101.6)

Weight g 220 (DB-250)

OPTIONS

FACS-4RDB Open area sounder, red, deep base

FACS-4W Open area sounder, white, shallow base

FACS-4WDB Open area sounder, white, deep base

Open area sounder beacon FACS-8R

A multi tone sounder-beacon, for open area use. Features:

LED cluster beacon light

32 tones, selectable by DIL switch

Enables compliance with the Disability Discrimination Act (DDA)

Side grub screw for security locking

SPECIFICATION

Voltage range 15 – 35Vdc

Sound level Low Med Hi

Current draw @ 24Vdc <14mA <20mA <41mA

Sound output, at 1m, 1st tone (dBA) 88 103 109

No. of tones 32

Operating frequency 440 to 2900Hz

Operating temperature –20 to +70ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Terminal block

Cable entry Rear (DB rear or side entry [with cover plate])

Construction ABS plastic, with red lens

Ingress rating IP43 (DB version – IP65)

Dimensions ø h (mm) 93.6 (DB-93) x 89.6 (DB-106.9)

Weight g 233 (DB-258)

OPTIONS

FACS-8RDB Open area sounder, red, deep base

FACS-8W Open area sounder, white, shallow base

FACS-8WDB Open area sounder, white, deep base

FACS-8RDB-A Open area sounder, red, deep base with amber cover

FACS-4R

FACS-4RDB

FACS-8R

FACS-8RDB

Page 71: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

69

www.emergi-lite.co.uk Conventional 4-wire alarms | Conventional

Conventional 4-wire alarms

Alarm beacon FACS-BEA-R

A bright output flashing beacon to augment sounders, particularly in areasof higher ambient noise. LED light source with low power requirement.

SPECIFICATION

Voltage range 20 – 35Vdc

Set up Standard Low

Current draw @ 24Vdc 5mA 3mA

Light output (equiv) @24Vdc 0.7w 0.4w

Operating frequency 1Hz

Operating temperature –20 to +70ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 6 way angled terminal block

Cable entry Rear (DB - rear or side entry)

Construction ABS plastic in red

Ingress rating IP43 (DB version - IP65)

Dimensions ø h (mm) 93.6 (DB-93) x 60.2 (DB-77.1)

Weight g 145

OPTION

FACS-BEA-RDB Alarm beacon, deep base

FACS-BEA-R

FACS-BEA-RDB

Alarm fire bell FACB-624

A wall mountable motorised fire bell for fire alarm or class change.The gong is secured by a tamper resistant bolt.

SPECIFICATION

Voltage range 18 – 28Vdc

Current draw @ 24Vdc 25mA

Sound output, at 1m (dBA) 96

Operating temperature –10 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Cable entry Rear (or side entry with surface box)

Construction Metal gong in red

Ingress rating IP42

Dimensions ø h (mm) 150 x 54

Weight g 527

OPTION

FACB-624-G Alarm fire bell with grey gong

FACB-624

Page 72: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

70

Conventional 4-wire alarms

Conventional | Conventional 4-wire alarms

Alarm fire bell FAAB-624-WP

A wall mountable fire bell for fire alarm or class change applications.Weather resistant rating achieved with a rubber gasket.

SPECIFICATION

Voltage range 18 – 30Vdc

Current draw @ 24Vdc 30mA

Sound output, at 1m (dBA) 93 – 95

Operating temperature –10 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Cable entry Rear (or side entry with surface box)

Construction Metal gong in red, base in polycarbonate

Ingress rating IP55

Dimensions ø h (mm) 150 x 85

Weight g 1,100

FAAB-624-WP

Page 73: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

71

www.emergi-lite.co.uk Wireless systems

Wireless systems

Wireless systemsSystem overview 72

Wireless detectors 73

Wireless ancillary devices and call points 74

Page 74: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

AnX Wi-free fire

www.emergi-lite.co.ukWireless systems | AnX Wi-free fire

72

AnX Wi-free fireOverviewEmergi-Lite Safety Systems offers a wireless fire detection andalarm system package that links into a wired analogue loop.

For a project where a ‘wire-free’ solution is needed, a stagedapproach is employed. Firstly, it is essential to carry out a radiosurvey to understand the radio profile of the building and planwhere devices need to be fitted. Secondly, a proposal listing thetype of equipment will be offered. Prior to the fitting process adetailed scheme layout will be provided with the equipment list toaid the installer. On completion, commissioning of the system is astandard part of the package.

ApplicationsThe system is suited to parts of buildings, which have sensitive structuresand decoration, or which cannot be disturbed for historic or preservationreasons. Wire free equipment is also useful to extend an existing system(temporarily or permanently), such as in portable buildings in aneducational complex.

o

A1R

o

Loop outLoop in

Illustration: Radio fire section integrated into an Anatecloop via an interface module FAR-INTM-ISO

Radio detector battery fit

FAR-SVT Survey tool

Features Design capacity: Five

interfaces per analogue loop

Loading per interface: Up to15 devices

Operating radio frequencyband: 868mHz

Integrity: the devices are self-monitoring

Addressing: Devices areaddressed individually via anonboard mechanical cardfacility

The ‘detection and alarm set’is an annex to an analogueloop system, without the needfor a costly dedicated controlpanel

Ease of installation:Installation and setup can beaccomplished withoutcomplicated procedures A1 R

o

Key:

Optical detector

Heat detector, A1R

Sounder-beacon

Manual call point

Sounder

Loop interface module

Page 75: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

73

www.emergi-lite.co.uk Wireless devices | Wireless systems

Wireless devices

AnX Wi-free fire detection devicesThe Anx Wi-free system comprises a set of detection and alarm devices equipped with radio basesections. These communicate with an interface unit mounted according to the radio survey. Theinterface unit is wired into an Anatec analogue addressable system. A fire condition or fault iscommunicated from the radio devices to the interface for relay to the analogue panel, where it isregistered. The radio device address is recognised by the panel as if it were a device wired on the loop.

If there is a fire condition, the panel will issue an alarm signal, which is relayed by radio from the interface to soundthe radio fire alarms.

The dimensions and body construction of the field devices listed below are similar to those of the FA95 devicesshown on pages 13 – 26 of this catalogue.

Battery packsEach radio field device is fitted with two sets of three AA alkaline batteries (for redundancy). The batteries have a 3-year design life for the application.

Optical smoke detector FAR-OPT-M

Complete with address module and battery. Ideal todetect slow burning fires.

Multi-sensor detector FAR-MUS-M

Complete with address module and battery. Suitablefor all types of fire.

Heat detector, A1R rating FAR-HDA-M

Complete with address module and battery. Suited tosmoky areas (kitchens).

Fixed temperature heat detector,CS rating FAR-HDC-M

Complete with address module and battery. Suitablefor use in compartments where central heating boilersfunction.

Page 76: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Wireless devices

www.emergi-lite.co.ukWireless systems | Wireless devices

74

Dome sounder, red FAR-SR-BR

Complete with address module and battery.

Dome sounder beacon, redFAR-SBR-BR

Complete with address module and battery.

Manual call point FAR-MCP-M

Complete with address module and battery.

Survey tool FAR-SVT

A handy survey tool to determine wireless signalstrength in the building and to help select positions tomount devices and antennae.

Antenna FAR-ANT

A standard antenna to be used in between the fielddevices and the INTM interface, where an increase insignal strength might be needed.

Directional antenna FAR-ANTD

A directional antenna for sites where there might beexternal buildings incorporated in the plan.

Wireless communication moduleFAR-INTM-ISO

A wireless communication module, which acts as aradio field device controller and a wired interfaceconnected into an FA95 supported analogueaddressable loop. The unit is fitted with a loop isolatorand when wired to the loop is polarity sensitive.

OPTIONS

FAR-SW-BW Base unit, white

OPTIONS

FAR-SBA-BW Dome sounder beacon, white base, amber beacon

FAR-SBC-BW Dome sounder beacon, white base with clear lens, redflashing beacon

Page 77: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

75

www.emergi-lite.co.uk Other systems

Other systems

Other systemsEmergency voice communication system 76 – 77

Voice enhanced sounders 78

Audio visual upgrades 79

Beam detectors 80 – 81

Air sampling 82 – 83

Air duct detection devices 84

Silent-Touch 2 85

Door retainers 86

Intrinsic safety 87

Lone-ALERT 88

Protective covers for call points 88

Page 78: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Emergency voicecommunication system

www.emergi-lite.co.ukOther systems | Emergency voice communication system

76

Emergi-Voice CommunicationThe Emergi-Voice product range extends from firetelephone and disabled refuge wired communicationsystem to standalone voice alarm sounders.

Telephone communicationThe Emergi-Voice specialist telephone communicationsystem is designed for ‘fire telephone’ or ‘disabledrefuge’ use with a particular application to assist thefire-fighting service in conditions where normal radiocommunication might be impaired.

The system is compliant with BS 5839-9:2003. Underthe code, fire telephone and disabled refuge systemswill form a single system if both are to be fitted in abuilding.

Emergi-Voice is a fixed full duplex (bi-directional)secure communications system.

Disabled refugeA disabled refuge is a secure location designated forpeople who have impaired mobility, who would beexpected to need help to leave the building or whomay impede the general flow of evacuation from thebuilding. This applies to anyone who cannot walk200m without stopping, typically wheelchair users andthe walking infirm.

Telephone system features andbenefits BS 5839-9:2003 compliant

Wired as a network

Wired with CWZ category fire cables

Up to 300 lines per system

8 lines per exchange

Up to 32 exchanges per network

1 outstations handset per line for new systems forcompliance

Up to 8 master handsets

Full fault monitoring on all critical paths with a99-event fault log in memory

Battery maintained

Maximum distance to outstation handsets on spurs– 500m

Maximum distance between exchanges – 500m(e.g.: For a 3 exchange system the total networkcable length = 1500m)

The system comprises a master handset controller, an8-line exchange and a set of outstation handsets(either type A or type B).

Master handset controllerA wall or desk mounted unit with operational andcontrol features including fault monitoring, menudriven navigation and an LCD display.

Telephone exchangeA wall mounted unit with 8 lines to outstations.

Outstations (Section 11 of BS 5839Pt 9:2003)Type A is a telephone handset in a hinged enclosure,for evacuation or fire fighting use (sec 11.1.2a).

Alternate type A is an IP66 rated enclosure. Type B is ahands free set in a vandal resistant enclosure, fordisabled refuge (sec 11.1.2b).

Master handset controller

Outstation type BOutstation type A

Page 79: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Emergi-Voice product selection

www.emergi-lite.co.uk Emergency voice communication system | Other systems

Emergency voicecommunication system

STANDARD ORDER CODE DESCRIPTION

FEVC-MHC Monitored master handset

FEVC-X8 Exchange unit: 8 line

FEVC-OA1 Type A outstation handset, flush with push door

FEVC-OA2 Type A outstation handset, flush with locking door

FEVC-OA3 Type A outstation handset, flush with push door in stainless steel

FEVC-OAS1 Type A outstation handset, surface with push door

FEVC-OAS2 Type A outstation handset, surface with locking door

FEVC-OAS3 Type A outstation handset, surface with push door in stainless steel

FEVC-OAS66 Type A outstation handset, surface, IP66 enclosure

FEVC-OB1 Type B outstation, hands-free

AC mains

AC mains

Phone lines:2 core FP200 (1mm2)

Equipment:-Controller handsets – up to 8Exchanges – up to 328 phone lines per exchange

Exchange network cabling:2 x 4 core FP200 (500m length)or MICC (200m length)

For a particular project schemedesign please contact ourTechnical sales department.

Typical layoutThe diagram below illustrates the typical layout of a fire telephone system with two handset controllers networkedtogether.

77

Page 80: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Voice enhanced sounders

www.emergi-lite.co.ukOther systems | Voice enhanced sounders

78

The Emergi-Voice range includes sounders and sounder beacons for use with fire panels.

Two types of voiced enhanced sounders are avaliable. One for general use and an industrial unit to meet therequirements of gas extinguishing systems.

Sounders are suitable for ‘first fix’ installations or retrofitting into existing systems.

Voice enhanced sounder FAKV-4R

An open area type alarm, for industrial and general use, which gives a firealarm tone (selectable), prior to a message. Features:

Single evacuation message selectable from three pre-programmed options

Voice enhanced sounder FAKV-9SR

A heavy duty alarm device specifically for use with gas extinguishingsystems. Three stages of alarm are provided with a warning message ateach stage. The beacon option can be configured to operate with one or allstages of alarm.

SPECIFICATION

Voltage range 24Vdc

Sound level Sounder Sounder beacon

Current draw @ 24Vdc (tone dependent) 26mA 32mA

Sound output at 1m (dBA) 106 106

No. of tones 32

Operating frequency 400 to 2850Hz

Operating temperature –20 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Cable entry 2 x 20mm

Construction Flame retardant polycarbonate

Ingress rating IP65

Dimensions ø h (mm) 100 x 81 (97.5 x 104 deep base)

Weight g 250

Standards EN60950

STANDARD ORDER CODE DESCRIPTION

FAKV-4R Sounder, red shallow base

FAKV-4RDB Sounder, red deep base

FAKV-4W Sounder, white shallow base

FAKV-4WDB Sounder, white deep base

FAKV-8R Sounder beacon red base, red lens

FAKV-8RDB Sounder beacon red deep base, red lens

FAKV-8R Sounder beacon white base, clear lens, red LED

FAKV-8RDB Sounder beacon white deep base, clear lens, red LED

SPECIFICATION

Voltage range 24Vdc

Sound level Sounder Sounder beacon

Current draw @ 24Vdc (tone dependent) 30mA 48mA

Sound output at 1m (dBA) 110 110

No. of tones 64

Operating frequency Tone table

Operating temperature -20 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Cable entry 5

Construction Flame retardant polycarbonate

Ingress rating IP66

Dimensions hwd (mm) 166.5 x 166.5 x 149.5 (213.5 depth - sounder beacon)

Weight g 700 (sounder beacon 800)

Standards

STANDARD ORDER CODE DESCRIPTION

FAKV-9SR Sounder, red

FAKV-9SBR Sounder beacon, red base, red lens, LED beacon

Multi-message option

In larger premises, where stagedevacuation might be needed amulti-message option is availableto give alert and evacuationmessages. Up to four messagescan be sent via an interface unitwhich monitors the fire panelsounder circuit outputs.

Features:

Multi-message alarm giving 3gas release warning messages

USB connection, that enablesuser defined messages to bedownloaded (WAV format)from a PC

Can be interfaced with otherunits to permit warningmessages to be triggered insequence

FAKV-4R

FAKV-9SR

Page 81: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

79

www.emergi-lite.co.uk Audio visual upgrades | Other systems

Audio visual upgrades

Easy AV™ – Audio Visual upgrade productsThe new V4 Easy AV™ product supplied by Emergi-Lite provides a unique method of upgrading existingfire alarm signalling products to combined audio visual use. The addition of the retrofit unit to anexisting Roshni sounder is achieved at minimal cost with no waste and in compliance with DDArequirements. The Easy AV™ product converts the existing Roshni sounder to a combined audiovisualalarm simply by removing the existing sounder from the base, connecting the Easy AV™ unit and re-fittingit. Easy AV™ features:

High output LED technology

Easy and low cost upgrade for compliance with the Disability Discrimination Act (DDA)

No additional cabling or power supply

Fully synchronised and monitored

Uses existing audible device (No waste)

Retrofit beacon ring kit for FAAS-EAVR-424

FAAS-4 series soundersRetrofit kit supplied by Emergi-Lite providing a unique method ofupgrading existing FAAS-4 series sounders to combined audio visual use.Conversion is achieved easily in a matter of minutes, at minimal cost, and incompliance with DDA requirements.

SPECIFICATION ALARM DEVICE

Voltage range 9 – 30Vdc

Current Consumption 2.5mA to 5.6mA at 24Vdc

Flash output adjustment Low power / High output, selectable

Flash output level 1w/2w, approx equivalent Xenon output

Flash frequency 1Hz or 1.5Hz, selectable

Flash colour Red

IP rating IP 43 to IP65 (deep base body)

Construction V0 Thermo plastic, polycarbonate

Colour Translucent Red

Dimensions note Additional height when fitted: 20mmDiameter at lens: 124mm, body: 93mm

6” Bell retrofit kit for FAAB-EAVR-424

FAAB-6 series soundersThe new Easy AV 6 inch bell retrofit kit supplied by Emergi-Lite provides aunique method of upgrading existing fire bells to combined audio visualuse. The addition of the unit to an existing 6” motorised bell is achievedeasily in a matter of minutes, at minimal cost, and in compliance withDDA requirements.

SPECIFICATION ALARM DEVICE

Voltage range 9 – 30Vdc (24Vdc nominal)

Current Consumption 3 to 6mA max, 3.5mA nominal

Flash output High or Low level

Flash output level 1w standard, 2w hi, red Xenon

Flash colour Red

IP rating According to IP rating of bell

Construction V0 Thermo plastic, polycarbonate

Colour Translucent Red

Cable monitoring Normal loop through wiring provides open and s/c monitoring

Terminals To suit 2.5mm2 conductor

Dimensions note Additional height when fitted: 27.5mm.Diameter at lens: 156 mm

Easy AV™ is a trademark of FircroftTechnologies. Roshni is a Fulleon tradename.

INSTALLER SELECTABLE FUNCTIONS

Link 1 Link 2 FlashHz

Flasho/p

Av currmA

1 L 3.5

1.5 L 4

1 H 4.8

1.5 H 6

FAAS-EAVR-424

FAAB-EAVR-424

Page 82: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

80

Beam detectors

Conventional | Beam detectors

Fire beam detector FBEAM40 PLUS

The beam detector is designed for detection at higher levels, particularly inbuildings with an apex roof, where it is impracticable to fit point detectors.

The set is designed for use typically in factories, warehouses and shoppingmalls and can be sited up to 40m above floor level.

Features

Standard range of 5 to 40m. Extendable to 40 to 80m or 80 to 100mwith reflector sets

Low power consumption

Self aligning beam between motorised detector head and reflector

Maintains alignment over time, through constant monitoring andcorrection

Separate controller unit mounted at operator level

Can be configured for use an analogue addressable system through aFA95-SMU switch monitor interface. Also it can be connected for soleuse on a conventional zone. On a 2-wire zone (Eurofire only) the panelshould have a zone configured for 4-wire operation

Easy to fit in comparison to other beam detectors. Provided thedetector head and reflector plate are wall mounted in reasonable lineof sight on walls normal to each other an auto-alignment can beachieved from the controller unit in a reasonable time

Compensation feature for dust contamination

Change latching mode: The detector relay can be programmed to latchon alarm or set to reset

Kits are supplied complete with detector, reflector, test filter, allen keyand manual

SPECIFICATION

Supply 12 – 24Vdc

Quiescent current 3mA

Time to alarm Adjustable from 2 to 30 seconds

Time to fault Adjustable from 1 to 60 seconds

Construction ABS plastic in white

Operating temperature –15˚C to +55˚C

Ingress rating IP65

Dimensions whd (mm) 155 x 180 x 125

Weight kg 1 (head), 0.5 (controller)

Standards Designed to comply with EN54 part 12

FBEAM40 PLUS Detector head andcontrol unit

FBEAM40 PLUS Detector head withreflector base plate

Page 83: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

STANDARD ORDER CODE DESCRIPTION

FBEAM-RFL80 Reflector set 40-80m range

FBEAM-RFL100 Reflector set 80-100m range

OPTIONS

FBEAM-PLATE Reflector base plate

81

www.emergi-lite.co.uk Beam detectors | Conventional

Beam detectors

STANDARD ORDER CODE DESCRIPTION

FBEAM40 Beam detector, 5-40m rangeKit comprises; detector, controller, test filter, allen key and manual

Note: Conventional systemMore than one detector can be included so long as separate power suppliesare provided.

Please contact Technical sales for further assistance.FBEAM-RFL80 Reflector set

Fire beam detector

Fire beam detector wiring

Controller atoperator

level

Zone -sole use

Illustration: FBEAM40 wired to a) A conventional zone, b) Interface to an analogue addressable loop

Detector head(max height 40m)

AC mains

Detector head(max height 40m)

CIE

Eurofire 4w or 2wFiretec 4w

+ -

EOL

Loop in

Loopout

SMU

AC mains

Reflector sets

Page 84: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Air sampling

www.emergi-lite.co.ukOther systems | Air sampling

82

Aspirating ‘air sampling’ smokedetectionThe methods and technology used in anaspirating smoke detection system is generallymore sensitive than that used in alternativeones, which better serves applications requiringvery high reliability and an immediate response.

Aspiration equipment and technology is highlysensitive to smoke particle detection (detectioncapability as described in the appendix of BS 6266).Such a system is ideal for larger buildings or placeswhich have a need for sensitive and reliable coverage.

ApplicationsThe pipe work detection points can be located veryclose to critical areas and in many instances be siteddiscretely.

Typical applications include:

The protection of clean environments such ascomputer suites, pharmaceutical facilities or othercritical areas

The protection of areas where the building fabricis a concern or where the building contents havehigh value or where the building has a critical use

Museums, Stately homes, art galleries orwarehouses for artefact storage

Telephone exchanges

The system can be used in dusty areas or where theprevailing conditions are more extreme:

Areas with hot or cold temperatures – buildingatriums

Dusty areas – paper mills or grain storagewarehouses for example

Prison establishments

Areas with higher levels of radio energy present

Detector Fire panel loop

Sampling pipes located near air-conditioningextractor– computer suite

System and detector operationThe system is built up from a single detector unitconnected to a matrix of pipework with strategicallyplaced sampling holes along the pipes length. Air isdrawn from the pipe network by an impeller to besampled in a measuring chamber in the detector. Thedetector, which works on the light scattering principle,is at least 10 times more sensitive than a standardpoint detector, such that smoke from a fire will bedetected at a very early stage despite the distance thesampled air might have to travel down the pipe. Theinherent reliability and stability of the system means itwill accurately detect a fire early and not give a falsealarm.

The detector construction, which works on the‘forward light scattering principle’, includes filteringand electronics that enables it to discriminate betweensmoke and dust particles. Other variables such assensor electrical noise are taken into account byalgorithms in the software to determine the level ofsmoke content in the air and hence when to issue analarm signal.

Different detector models are available depending onthe area of detection and the pipe length required.

Page 85: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

CIE

o o

o

H o o

Air sampling detector integrated to an analogueaddressable system – single loop illustration

Analogue panel

Airsamplingdetector

SMU

o

83

www.emergi-lite.co.uk Air sampling | Other systems

Air sampling

Typical area of coverageOne detector and one air pump might sample from upto 100 sampling holes over an area of 1000m2 (ceilingheight 12m). The pipe arrangement could be arrangedas for lengths of 100m or other combination providedthe permitted response time set by the designrequirement is met.

Alarm compatibilityFor alarm provision the aspirating system can belinked into an analogue addressable fire networkthrough a compatible interface or to a conventionalsystem via one of the zones. The system is compatiblewith Anatec FA95 and Discovery protocols.

How to orderIf you have a specific project where an aspiratingsmoke detection system would provide the solutionfor fire cover, then please contact our Technical Salesdepartment for assistance in design and productselection.

Stratos is a tradename of Airsense Technology Ltd.

H

o

Manual call point

Analogue smokedetector (optical)

Analogue heatdetector

SMULoop interface unit

Key:

Page 86: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

www.emergi-lite.co.uk

84

Duct detectors

Other systems | Duct detectors

Smoke detection inair ductsIn premises with extensive ductedventilation systems it is advisableto be able to detect the presenceof smoke, so that the airflow canbe closed down before smokecontaminated air is vented intoother areas. The system describedhere should be used tosupplement detection methods inareas where a fire may originate.

STANDARD ORDER CODE DESCRIPTION

FAP6-ASU Duct detector housing, with an FAPO conventional detector base

FA95-ASU Duct detector housing, with an FA95 analogue addressable detectorbase

OPTIONS

Longer tubes for wider air ducts

FAP6-AST75 Air sampling tube, (length 15-75cm)

FAP6-AST150 Air sampling tube, (length 75-150cm)

FAP6-AST300 Air sampling tube, (length 150-300cm)

Smoke Detectors

FAPO-OPT Conventional detector for FAP6-ASU housing

FA95-OPT Anatec analogue detector for FA95-ASU housing

FADY-OPT Anatec Discovery detector for FA95-ASU housing

FA95-ASU

ApplicationThe duct detector is a supplementary smoke detection system that issuitable for medium to large buildings with ventilation/air heating systems(HVAC). Typical sites include manufacturing and food processing plants,shopping malls, sports arenas and hotels.

The duct detector comprises an air sampling housing, available in twomodels for different conventions. One type will accept an FAPO Orbisdetector (conventional system) and the other includes a base for an AnatecFA95 (or FADY Discovery) smoke detector (analogue addressable).

The housing can be fitted to the wall of the ventilation duct. An inletsampling and an exhaust pipe from the detector housing are fitted throughholes made in the duct wall, to cycle duct air through the chamber and pastthe smoke detector.

The exhaust pipe must be fitted downstream from the inlet to create apressure differential that sucks air through the sample pipe.

When the detector senses smoke an alarm would be registered at the firepanel. Visual indication is shown by the detector LED or via a remote LEDunit that can be connected to the terminal block in the duct devicehousing.

FAP6-ASU

Page 87: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

85

www.emergi-lite.co.uk Silent-Touch 2 | Other systems

Silent-Touch 2

SILENT-TOUCH 2‘Silent-Touch 2’ (ST2) is a local alarm controldevice designed to help reduce unwantedalarms (where people might have burnt toastfor example) in buildings with dwellings having‘multiple occupation’ (HMO).

ApplicationsThe unit has been produced for use in premises suchas university accommodation, buildings with self-contained flats or apartments.

FunctionIf the fire alarm system were to activate from a localdetection:

The ST2 interface is wired to the addressable loop asan interface. It then feeds a conventional circuit wiredin 2 x 2 core fire resistant cable to the local dwelling.When a detector is activated in the dwelling thefollowing can take place:-

Scenario 1 (BS 5839-6/12.2b): If the ST2 is pressed afteractivation, the local alarms will not sound for a 2-minute period. They will stay off if the fire zonereturns to normal within that period.

Scenario 2 (BS 5839-6/12.2a): If the ST2 is pressedbefore the fire system activates, the quiet period is 15minutes and power is removed to the local zone. Pressthe HB a second time and the power will be restored.

The occupier will hear a beep 15 seconds before thenormal state is resumed in each case.

Features Compliant with BS 5389-6

Can be integrated into an analogue addressableloop to the main panel

FA95 and Discovery compatible

Fully monitored for open and short circuits

Failsafe: A general fire condition from the mainpanel overrides all other states

HMO level of protection status would be grade Aor B (mains/battery powered detectors –grade D)

Up to 20 control units per loop

SPECIFICATION

Operating voltage 17Vdc to 40Vdc

Quiescent current 5mA

Construction ABS plastic in white

Dimensions whd (mm) 144 x 84 x 36

Standards Designed to comply with EN54 part 12

STANDARD ORDER CODE DESCRIPTION

FST-2AP HMO alarm delay controller

CIE

ST2

o

c s

o

o

ST2

o

o

EOL

EOL

Flat 1 Flat 2

Conventionaldevices

2x2 core cable

Loop -2 core

Illustration: ‘Silent-Touch’ controlling conventional devices in twoseparate flats , interfaced from an analogue addressable loop

Hush button is a tradename ofC-Tec (Computronics Ltd.)

Page 88: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

86

www.emergi-lite.co.uk

Door retainers

Other systems | Door retainers

Electromagnetic door retainer FDMW-024, FDMW-240

During normal operation the door is held open by electromagneticforce. When the power is cut a spring loaded release pin pushes thedoor from the magnet to close. Includes integral release pin and manualrelease switch.

SPECIFICATION

Operating voltage 24Vdc (230Vac: mains version)

Current consumption 45mA (12mA: mains version)

Min/max rated holding force 112N/200N

Release switch Yes

Wiring & termination Wiring to 4mm terminals

Cable entry Knockouts

Construction & fixing Flame retardant ABS plastic in grey. Wall mountable

Ingress rating IP51

Dimensions hwd (mm) 95 x 87 x 45.5

Weight g 400

Door closer power size 3 - 5

Standards EN61000-3-2, EN50081-1, EN6090, EN1155

STANDARD ORDER CODE DESCRIPTION

FDMW-024 Door retainer, 24Vdc

FDMW-240 Door retainer, 230Vac mains

OPTION

FDMFB Floor mounting bracket

Electromagnetic pole mounted FDMP-024

door retainerThe pole mounted series is available for different door retaining situationswith potential for floor, ceiling or wall mounting (wall mount throughturning the magnet 90º). Two standard lengths are available – 0.5m and 1m.

SPECIFICATION

Operating voltage 24Vdc

Current consumption 47mA (5C), 76mA (1K)

Min/max rated holding force 500N/750N (5C)1000N/1300N (1K)

Release switch Yes

Construction & fixing Steel fabrication

Ingress rating IP51

Dimensions; height & depth from wall (mm) H283/D350: 5CL & 1KL

Dimensions; height & depth from wall (mm) H183/D250: 5CS & 1KS

Weight kg 1.6 (5C), 2 (1K)

Door closer power size 3 - 6

Standards EN61000-3-2, EN50081-1, EN6090, EN1155

STANDARD ORDER CODE DESCRIPTION

FDMP-024-5CL 750N door retainer, 283mm height

FDMP-024-5CS 750N door retainer, 183mm height

FDMP-024-1KL 1300N door retainer, 283mm height

FDMP-024-1KS 1300N door retainer, 183mm height

FDMW-024

FDMP-024

Page 89: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Device isolationA high degree of isolation is required when connecting IS devices within the hazardous area to control equipmentoutside it.

o

IS

Hazardous area Safe area

CIE

IS barrierinterface

IS fire detectiondevice Control panel

Intrinsically safe firedetection and alarmequipment Ex iAn intrinsically safe circuit is onewhere no spark or an effectfrom a rise in temperature orother increase in energy withinthe circuit will cause ignition toa mixture in a potentiallycombustible atmosphere.

Plants and facilities where paint,solvent or other volatilesubstances are held are classifiedas hazardous areas because anexplosive air/gas mixture may bepresent part or all of the time.

Intrinsically safe fire detection andalarm devices meet the criteria byoperating at such low energy levelsas to be incapable of sparking sucha flammable or combustiblemixture in a hazardous area.

Earthing is required for of all partsof intrinsically safe devices, includingenclosures, cables and conduits aswell as the devices themselves.

Illustration: Intrinsically safe (IS) detector linked via an IS barrier to a control panel

87

www.emergi-lite.co.uk

Intrinsic safety

Intrinsic safety | Other systems

Intrinsically safe barriersOperation of intrinsically safe fire detection and alarm devicesThe operating sensing characteristics of IS detection devices for detectingsmoke or heat are the same as standard versions.

Use of field detection and alarm devices with IS barriersOnly one sounder device should be connected per barrier. No more than 5detector devices should be connected per barrier.

Design of schemeQualified experts should undertake the design of a scheme for a siteneeding intrinsically safe equipment.

Equipment supplyEmergi-Lite Safety Systems is able to provide intrinsically safe detectors, callpoints and sounders. Please contact our technical sales department withyour specific requirements.

Active isolationIsolation is normally achieved with galvanic isolation.

A galvanic isolator is an active piece of equipmentthat limits the energy transfer to a hazardous areaunder fault conditions. The term ‘transformer isolatedbarrier’ is sometimes used to describe such a device,alluding to a physical separation in the device itself.

On a cautionary note, a galvanic isolator does notcater for polarity reversal in the signal wires to a firepanel in the safe area. Hence, for some panels itwould not be possible to monitor for an open circuitor end of line faults (zone or alarm) in the normalmanner.

Passive isolationA zener diode barrier is a passive type of unit, againdesigned to keep the flow of energy, across theinterface, to such a low level that it could not igniteany combustible gas mixture in the hazardous domain.

The zener device protects against faults in wireconnections to the hazardous side of the barrier.Faults include: - Short circuits, poor earth connection,a power supply failure or incorrect connection

A zener barrier must be connected to a sure equi-potential earth point (at the same potential as theincoming earth to the intrinsically safe area). As thistype of earth connection will cause most fire panels toregister an earth fault, we recommend that the panelmanufacturer be consulted first.

Page 90: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Self-contained alarms/protective call points

www.emergi-lite.co.uk

88

Protective covers for manual call pointsA tough protective cover is available to help prevent accidental operationof call points, or prevent unauthorised use by those with malicious intent.The cover is suitable for use in educational buildings, hospitals, nursinghomes or places where the threat of false alarm is prevalent.

STANDARD ORDER CODE DESCRIPTION

FMC-ST30 Surface mount protective cover, with 30mm spacer

FMC-ST50WP Surface mount weatherproof cover, with 50mm spacer

For further options, please contact technical sales.

FMC-ST30

FMC-ST50WP

Other systems | Self-contained alarms/protective call points

Lone-ALERT FAKR-840

A stand-alone, self-contained fire alarm designed for use in smallretail, industrial or temporary buildings as well as constructionsites, camp sites or marquees where a full BS 5839 alarm system isnot required.

The unit can also be used as a temporary alarm when the main fire alarmsystem is under maintenance. When fitted with LR14 batteries, these unitswill operate in standby mode for over 12 months.

Each unit has the facility to be interlinked with other units to provideadditional coverage so that when one call point is activated, all of theother units sound.

Features

Battery operated unit with low battery warning function

Electronic sounder

Rugged metal construction

Simple to install and operate

Units can be linked to form a complete system

SPECIFICATION

Power supply LR14 battery

Sound output at 1m Up to 97dB(A)

No. of tones 3

Operating Temperature –15ºC to +45ºC

Construction Steel case

Weight (kg) 1.5

Lone-ALERT

Page 91: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Commissioning & maintenance

Commissioning & maintenance

Commissioning & maintenanceCommissioning/Redcare 90For commissioning, maintenance and service enquiries please contact our service team, either by telephone on0113 281 0600 or via email: [email protected] for assistance.

www.emergi-lite.co.uk

89

Page 92: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

90

www.emergi-lite.co.uk

Commissioning, maintenance and service

Commissioning & maintenance | Commissioning/Redcare

The Thomas & Betts Services Group is an organisation, based in Leeds that provides a highly skilledsupport service, from experienced and trained engineers, for commissioning and maintaininginstalled systems. This applies to both fire detection & alarm systems and emergency lightingcentral battery systems.

CommissioningAll project quotations, for fire detection and alarm systems, will include a section for commissioning as part ofpackage. British Standard BS 5839-1:2002 Section 5 recommends that a fire alarm installation should be fullycommissioned to ensure satisfactory operation. As the manufacturer’s commissioning team, we can offer to the useran in-depth knowledge of the product and a wide experience of its applications that would ensure compliance withthe code, together with a service that is both cost effective and reliable.

Remote Monitoring of installed fire detection & alarm systems – Redcare or Standard Digicom

We offer a particular service in relation to Remote Monitoring:

We can supply the monitoring equipment.

We do offer set-up and a 12-month monitoring service via an Alarm Receiving Centre (ARC)

We do offer installation and commissioning.

We do not supply, install or maintain the Telecoms line since this is the responsibility of others.

Maintenance, refurbishment & equipmentassessmentWe are pleased to offer term maintenance contracts for:

Fire Detection Systems

Central Battery Systems

Further, we offer expertise in the assessment with report on the conditionof existing fire detection or central battery equipment installations. Afterreporting we will be able to make recommendations for maintenance &testing, repair, upgrade or a replacement programme.

Emergency Lighting with Testing SystemsIf you have a need to upgrade a standard system or need assistance with a testing system call us, we have a range ofproducts to suit different needs.

The commissioning of emergency lighting systems is carried out to BS 5266 part 1 as standard.

QualificationsOur service engineers are fully trained both internally and externally, including by BFPSA. Individuals are certified forsite working (health & safety) under the Electrotechnical Certification Scheme.

For further information or to discuss a commissioning or a maintenance requirement for a particular project or site,please get in touch with a member of the field service staff at Leeds:

Field service coordinator

Fire detection & alarm systems

Central battery systems

Fire panel maintenance

Page 93: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

91

www.emergi-lite.co.uk Reference & Design

Reference & Design

Reference & Design

Reference & Design 92 – 94

Product index 95

Product selection chart 96

Fire detection systems are vital to ensure the ongoing safety of personnel in any organization. Carefuldesign, proper installation and effective management of the fire detection system are key to promotingsafety and as such are enforced by law, and bound by industry codes of practice.

This section serves as a broad overview of the regulations and standards relevant to fire safety. Wheremore in-depth information is required, please contact our sales team to discuss individual requirementsor request our separate brochure ‘An Authoritative Guide to Advance Fire System Design Techniques.’

Emergi-Lite offers expert assistance in Fire Alarm and Emergency Lighting scheme design to the lateststandards, as a supplementary service to that provided by qualified consulting engineers and local fireauthorities. Our technical team can provide specialist advice, plans and specifications for all types of firesafety systems detailed in this catalogue, including analogue addressable, conventional, voice enhancedand wireless systems.

Page 94: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

This section aims to provide a brief overview of the regulations, codes of practice and product standardsrelevant to fire safety.

A more detailed guide ‘An Authoritative Guide to Advanced Fire System Design Techniques’ is available,please contact Emergi-Lite for more details. This authoritative guide covers all aspects of design fromlaws & regulations, through design to comply with BS 5839-1:2002 and associated advanced practices, tocommissioning, maintenance and notes on documentation.

It is recommended that BS 5839:2002 should be read in detail by the user who will be involved withdesign of fire detection systems.

Regulations and standardsThe Regulatory Reform (Fire Safety) Order 2005/Fire(Scotland) Act 2005 is in force today. Some of the keypoints are:

The Fire Safety Order applies to all workplaces andother non-domestic premises.

The control regime is fire risk assessment based,with responsibility for fire safety resting with theperson responsible for the premises (buildingowner/user and employer).

Protection should be provided to all persons insidea building and those who might be affected by afire.

There should be a duty to maintain those fireprecautions required under Building Regulations,which are for the use and protection of the firebrigade.

There will be a new statutory duty on a FireAuthority to promote community fire safety, forpowers of entry for the investigation of fires, andfor a power to take away samples for testing.

Fire protection products and related servicesshould be ‘fit for purpose’, correctly installed andmaintained in accordance with relevant BritishStandards and the instructions of themanufacturer.

In addition the Disability Discrimination Act (DDA) hasa significant bearing on the operation of firedetection systems. The type of equipment used inpremises or areas used by the less able must cater fortheir needs, especially knowing that the evacuationtime might be longer. Factors for considerationinclude:

The provision and positioning of manual callpoints for ease of use.

Alarm devices that are both audible and visible inapplicable areas.

The control of fire doors along escape-routes.

Codes of practiceThe British standard code of practice BS 5839-1:2002 isthe code for fire detection and alarm systems forbuildings, systems design, installation and servicing.This code is referred to in ‘Approved document B’(the guide to building regulations) and the guide‘Fire Safety – an employers guide’, which gives itstrength in law.

Other important sections of BS 5839:2002 are:

6: Dwellings

8: Voice alarm systems

Product standardsThe BS EN54 set of standards govern the standard ofdesign and manufacture of products used in firedetection and alarm systems.

Fire system design to comply with BS 5839-1:2002

Documentation and CertificationThe fire alarm system designer should a havedocument record for:

Design

Installation

Commissioning

Categories of systemBefore a designer can start on a fire scheme, thecategory of protection needed should be agreed aseither being P – Property, L – life or M – manual.

Each of these is sub-divided for specific situations andrequirements, as identified below:

Categories (automatic fire detection and alarm [AF] intypes P and L):

Type P: Property protectionP1: AF installed throughout the protected building.P2: AF installed in defined parts only.

Type L: Protection of lifeL1: AF installed throughout the protected building.L2: AF installed in defined parts (a type L2 system

should include the coverage required by a type L3system).

L3: AF to protect escape routes and rooms that openonto escape routes.

L4: AF to protect escape routes in circulation areas,stairways and corridors.

L5: AF to address a specific fire risk situation.

Type M: Manual alarm systems.

BS EN54 part Section

1 Fire detection and fire alarm systems

2 Control and indicating equipment

3 Fire alarm devices / sounders

4 Power supply equipment.

5 Heat detectors

7 Smoke detectors

11 Manual call-points

13 Compatibility assessment of system components forfire detection and alarm systems

14 Guidelines for planning, design, installation,commissioning, use and maintenance

Reference & Design

Reference and design

www.emergi-lite.co.uk

92

Page 95: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Reference & Design

Reference and design

www.emergi-lite.co.uk

93

Positioning of detection and alarm devices

Detectors, 10-point guide

A summary designed to help the user decide where to fit smoke or heat detectors, when planning a scheme.

1. Siting a detector below a ceiling:

The depth (d) of the sensor element, from the ceilingsurface, to be within the following limits:

Smoke: 25mm< d <600mm

Heat: 25mm< d <150mm

2. Detector area of coverage:

Each detector has a maximum area set by a particular circleradius for the type of device. Full coverage of a space isachieved by arranging detector positions to overlap. Usinggeometry, each device has an optimum ‘square of coverage’.

Smoke detector (R=7.5m, L=10.6m, A=112m2)

Heat detector (R=5.3m, L=7.5m, A=56.3m2)

3. Detector spacing in corridors that that are less than 2mwide:

There is no need to allow for overlap of the detector areas, so spacing can be increased (15m – smoke,10.6m – heat).

4. Flat and apex ceilings:

A ceiling is considered flat if the apex is less than 600mm (smoke) or 150mm (heat).

Apex ceilings – increased spacing

The distance between detectors can be increased by 1% per degree of slope (maximum 25%).

5. Minimum mounting distance away from obstructions: To be 500mm:

Where partitions have a gap of <300mm of gap to the ceiling.

Where crossbeams have a depth >10% of the ceiling height.

6. Stairwells and lift lobbies need a detector within 1.5m of any opening.

7. Enclosed stairwells: Place a detector at the top of each stairway and the main landing area.

8. Place detectors away from light fittings by at least twice the width of the fitting.

9. Keep detectors away from ventilation outlets/inlets by at least 1m.

10. Voids less than 800mm in height can be left unless smoke could spread through from an adjoining area.

Manual call points

The travel distance to a manual call point should be less than 45m (25m for a less able person). Call points should bemounted at a height of 1.4m above the floor (±200mm).

Alarm devices

Minimum sound level: 65dBA, or 5dBA above ambient. In sleeping accommodation: 75dBA at the bedhead.Loss effects owing to doors: –20dBA or –30dBA (fire door). Each zone should have redundancy in case of singlecircuit failure. Visual alarms should be mounted at least 2.1m above floor level.

Cabling

Fire resistant cable should be used for all circuits.

Types of detectorThe products of fire that can be detected are heat, smoke, fire and gas. Detectors are designed to monitor eitherone or a combination (multi-sensor) of these products. Basic types:

Fixed heat detector

Rate of rise (R-o-R) heat detector

Ionisation smoke detector

Optical smoke detector

Carbon monoxide detector (CO), also known ascombustion gas detector

Optical beam smoke detector

Aspirating smoke detector (ASD)

Flame detector

Spacing of detectors-to BS5839-1 2000

R A

L

L

Page 96: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Reference and design

Reference and design

www.emergi-lite.co.uk

94

If the building is new and conforming to theBuilding Regulations.

If the building is old, and whether there are anyincreased risks due to any possible lack of fireresistant constructions.

Whether property needs to be protected (categoryP).

Any high value buildings or high value contents(category P).

Whether everyone in the building is awake andalert and any rooms with energised equipment areoccupied (category M).

The number of people, their mobility and wherethey are located (category L).

Whether there are disabled, infirm people, orwhether there is any nursing care.

Whether there is any sleeping risk (category L).

The location of any unoccupied areas, or if atcertain times the building is only partiallyoccupied (e.g. risk to lone workers or risk toproperty).

The number of floors (including any basements).

The escape routes, including stairways.

Any higher risk areas such as kitchens, lockerrooms.

Any industrial processes that may be a hazard.

Any industrial processes that may cause anunwanted alarm.

Any special risk areas, such as computer rooms, orbattery rooms that may need a sprinkler orextinguishing system, to be interfaced with thefire alarm system.

The need for magnetic door retainers.

The need for plant shutdown, lift grounding etc.

The need for connection to an Alarm ReceivingCentre (ARC), particularly where propertyprotection is identified as being required.

The need for a staged alarm (alert signalsfollowing an alarm).

The need for a phased evacuation (usually for alarge multi storey building)

Risk AssessmentIt is vital that risk assessments are conducted for the building as noted by the Fire Safety Order 2005/Fire (Scotland)Act 2005. A risk assessment should identify hazards, needs and actions for correction. The key sections to be checkedare:

The person doing the risk assessment should be very familiar with the layout and use of the building. It is unlikelythat the fire detection and alarm system designer or sales engineer would be sufficiently familiar with the buildingor its use to complete a full risk assessment, but advice and consultation is usually available. It is therefore veryimportant that the designer consults with, and exchanges information with, the interested parties, rather thanworking in isolation. Having identified the above hazards, factors and needs, a decision would then be maderegarding the category of the fire protection system. At this point the fire detection and alarm system designerwould be asked to design the appropriate system, taking into account the information in the risk assessment processabove.

If the client or specifier is not able to decide on the Category, it may be left to the designer to propose a Category.Further, the contract responsibilities should be clearly agreed, so that any legal implications are defined.

Please note that Emerg-Lite Safety Systems does not undertake risk assessments.

Fire system design and integrityIf a fault occurs the design must take into account the rules of limitation for circuit integrity within the building.The Authoritative guide details the rules of integrity in relation to fire zones and the differences to considerbetween addressable and non-addressable installations. Key points are that a detection circuit fault must not disablemore than 2000m2 (non-addressable). At least two sounder circuits should be employed in a space greater than4000m2, or where the building might accommodate more than 500 members of the public. Small buildings havingless than 300m2 floor area may be treated as having one detection zone.

Full information on advanced scheme design is detailed in the Emergi-Lite Authoritative Guide to Advanced FireAlarm System Design.

Note: Regulatory references in this document are taken from the Fire Safety Order.

Note: All drawings in this publication are for illustration purposes only and are not drawn to scale.

Page 97: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Product index

Product index

www.emergi-lite.co.uk

95

AAir aspirating smoke detection system 82 – 83Air duct detector 84Alarm extender (conventional) 41, 53Alarm fire bell (conventional 4-wire) 69, 70Alarm fire bell ring kit (audio visual upgrade) 79Alarm fire bell, weatherproof (conventional

4-wire) 70Alarm relay (conventional 2-wire) 49Analogue addressable 8 way programmable

alarm 5Analogue addressable 8 way programmable

alarm relay 5Analogue addressable fire panel 4 – 11Analogue addressable integral printer 5Analogue addressable network card 5, 8Analogue addressable repeater panel 5, 7, 8Anatec Pro Discovery fire panel 4 - 7Anatec Pro Discovery panel trim 5Anatec Pro Discovery recessing bezel 5Anatec Pro Discovery repeater panel 5, 7Anatec Pro Explorer fire panel 4 - 7Anatec Pro Explorer repeater panel 5, 7Anatec-Lite fire panel 8 – 11Anatec-Lite repeater panel 8Anatec-Lite network card 8Anatec-Lite spare battery 8Antenna (wireless) 74Audio visual upgrades 79

BBeacon (analogue addressable) 26Beacon (conventional 4-wire) 69Beacon base cap/cover 23Beacon base with isolator (analogue addressable)23Beacon ring kit (audio visual upgrade) 79Beacon, open area (analogue addressable) 25, 27Beam detector (conventional 4-wire) 80 – 81Beam detector reflector set 81

CCall point (analogue addressable) 16, 20Call point (conventional 2-wire) 48Call point (conventional 4-wire) 63, 64Call point (wireless) 74Call point back box 63, 64Call point cover 16, 20, 48, 63, 64, 88Call point cover, weatherproof 20, 48, 88Call point notice sticker 16, 20, 48, 63, 64Call point spare glass 63, 64Call point spare key 16, 63, 64Call point spare re-settable element 63, 64Call point, weatherproof (conventional

4-wire) 63, 64Carbon monoxide detector (analogue

addressable) 19Ceiling tile mounting box 20, 65Circuit controller for sounders

(analogue addressable) 31Commissioning services 90Communication module (wireless) 74Component kit (conventional) 41, 53Conventional 2-wire fire panel 38 – 44Conventional 4-wire fire panel 50 – 56

DDetector base (conventional 2-wire) 45Detector base with diode (conventional

4-wire) 57, 60Detector mounting base (analogue

addressable) 13, 17Detector relay base (conventional 4-wire) 57, 60, 61Detector, air duct 84Detector, beam (conventional 4-wire) 80 – 81Detector, carbon monoxide (analogue

addressable) 19Detector, fixed temperature heat

(analogue addressable) 15, 18Detector, fixed temperature heat

(conventional 2-wire) 47Detector, fixed temperature heat

(conventional 4-wire) 59, 62Detector, fixed temperature heat (wireless) 73Detector, integrating optical smoke

(conventional 2-wire) 47Detector, multi-sensor

(analogue addressable) 14,19Detector, multi-sensor (conventional 4-wire) 58Detector, multi-sensor (wireless) 73Detector, optical smoke (analogue

addressable) 14, 18Detector, optical smoke (conventional 2-wire) 47Detector, optical smoke (conventional

4-wire) 58, 61Detector, optical smoke (wireless) 73Detector, rate of rise heat (conventional 2-wire) 47

Detector, rate of rise heat (conventional4-wire) 59, 62

Detector, rate of rise heat (wireless) 73Directional antenna (wireless) 74Disabled refuge telephone communication

system 76 – 77Door retainer 86Door retainer, pole mounted 86

EEurofire alarm extender 41, 53Eurofire conventional 2-wire fire panel 38 – 41Eurofire conventional 4-wire fire panel 50 – 53Eurofire isolator assembly 41, 53Eurofire relay unit 41, 53Eurofire repeater panel 41, 53Eurofire semi-recessing bezel 41, 53Eurofire spares pack 41, 53

FFire panel (analogue addressable) 4 – 11Fire panel (conventional 2-wire) 38 – 44Fire panel (conventional 4-wire) 50 – 56Firetec conventional 2-wire fire panel 42 – 44Firetec conventional 4-wire fire panel 54 – 56Firetec spares pack 54Fixed temperature heat detector (analogue

addressable) 15, 18Fixed temperature heat detector

(conventional 2-wire) 47Fixed temperature heat detector

(conventional 4-wire) 59, 62Fixed temperature heat detector (wireless) 73

HHeat detector, fixed temperature (analogue

addressable) 15, 18Heat detector, fixed temperature

(conventional 2-wire) 47Heat detector, fixed temperature

(conventional 4-wire) 59, 62Heat detector, fixed temperature (wireless) 73Heat detector, rate of rise (conventional

2-wire) 47Heat detector, rate of rise (conventional

4-wire) 59, 62Heat detector, rate of rise (wireless) 73Horn sounder (analogue addressable) 24Horn sounder beacon (analogue addressable) 24Horn sounder beacon, weatherproof (analogue

addressable) 24Horn sounder, weatherproof (analogue

addressable) 24

IInput/output unit with isolator (analogue

addressable) 32, 33Integral printer (analogue addressable) 5Integrated sounder base with isolator (analogue

addressable) 22Integrating optical smoke detector

(conventional 2-wire) 47Interface modules (analogue addressable) 28 – 33Intrinsic safety system 87Isolating base (analogue addressable) 34Isolator assembly (conventional) 41, 53

KKey-switch (conventional 4-wire) 65

LLocal area sounder base (analogue addressable) 22Lone-ALERT 88Loop isolator (analogue addressable) 34

MMains switching input/output unit (analogue

addressable) 33Maintenance services 90Mini switch monitor (analogue addressable) 29, 30Multi-sensor detector

(analogue addressable) 14, 19Multi-sensor detector (conventional 4-wire) 58Multi-sensor detector (wireless) 73

NNetwork card (analogue addressable) 5, 8

OOpen area beacon (analogue addressable) 25, 27Open area sounder (analogue addressable) 25, 27Open area sounder (conventional 4-wire) 68Open area sounder beacon (analogue

addressable) 26, 27

Open area sounder beacon (conventional4-wire) 68

Optical smoke detector (analogueaddressable) 14, 18

Optical smoke detector (conventional 2-wire) 47Optical smoke detector (conventional

4-wire) 58, 61Optical smoke detector (wireless) 73Output unit with isolator (analogue

addressable) 33

PPole mounted door retainer 86Programmable alarm (analogue addressable) 5Programmable alarm relay (analogue

addressable) 5Protective call point cover 20, 48, 88

RRate of rise heat detector (conventional 2-wire) 47Rate of rise heat detector (conventional

4-wire) 59, 62Rate of rise heat detector (wireless) 73Recessing bezel (for Anatec Pro Discovery) 5Redcare remote monitoring 90Reflector set for beam detector 81Relay unit (conventional) 41, 53Remote indicator unit 16, 49, 65Repeater panel (analogue addressable) 5, 7, 8Repeater panel (conventional 2-wire) 41Room sounder (conventional 4-wire) 67Room sounder back box (conventional 4-wire) 67

SSemi recessing bezel (conventional) 41, 53, 54Silent-Touch 2 interface 85Smoke detector, integrating optical

(conventional 2-wire) 47Smoke detector, optical (analogue

addressable) 14, 18Smoke detector, optical (conventional 2-wire) 47Smoke detector, optical (conventional

4-wire) 58, 61Smoke detector, optical (wireless) 73Sounder (conventional 4-wire) 67, 68Sounder (wireless) 74Sounder (voice evacuation) 78Sounder base (analogue addressable) 21, 22, 27Sounder base (conventional 2-wire) 46Sounder base cap/cover 22, 23, 46, 67Sounder base with isolator (analogue

addressable) 21Sounder base, integrated with isolator

(analogue addressable) 22Sounder base, local area (analogue addressable) 22Sounder beacon (wireless) 74Sounder beacon base (conventional 2-wire) 46Sounder beacon base with isolator

(analogue addressable) 23Sounder beacon, open area (analogue

addressable) 26, 27Sounder beacon, open area (conventional

4-wire) 68Sounder circuit controller (analogue

addressable) 31Sounder, open area (analogue addressable) 25, 27Sounder, open area (conventional 4-wire) 68Survey tool (wireless) 74Switch monitor with isolator (analogue

addressable) 29, 30Switch monitor, mini (analogue

addressable) 29, 30

VVoice enhanced sounder 78Voice evacuation handset 76 – 77Voice evacuation outstation 76 – 77Voice evacuation system 76 – 77

WWeatherproof alarm fire bell (conventional

4-wire) 70Weatherproof call point (conventional

4-wire) 63, 64Weatherproof call point cover 20, 48, 88Weatherproof horn sounder (analogue

addressable) 24Weatherproof horn sounder beacon (analogue

addressable) 24Wireless communication module 74

ZZone monitor with isolator (analogue

addressable) 28

Page 98: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

96

www.emergi-lite.co.uk

Product reference guide

Product reference guide

ANALOGUE ADDRESSABLE CONVENTIONAL 2-WIRE CONVENTIONAL 4-WIRE WIRELESS

Anatec ProExplorerFADYXP

Anatec ProDiscovery

FADY

Anatec-Lite

FANP

EurofireSensaFEWN

FiretecSensaFTEW

Eurofire4-wireFEUN

Firetec

FTEP

Airaspirating

System

FireDetection

SystemFA95

Detectors

Pages 13 - 15 Pages 13 - 15 Pages 13 - 15

FA95

Call points

Page 16 Page 16 Page 16

FA95

Alarms

Pages 21 - 26 Pages 21 - 26 Pages 21 - 26

FA95 Loop

interfaces

Pages 28 - 33 Pages 28 - 33 Pages 28 - 33

FADY

Detectors

Pages 17 - 19 Pages 17 - 19

FADY

Call points

Page 20 Page 20

FAC95

Alarms

Page 27 Page 27 Page 27

FAPW2

Detectors

Page 47 Page 47

FMFW2

Call points

Page 48 Page 48

FAPW2

Alarms

Page 46 Page 46

FAPO Orbis

detectors

Pages 57 - 59 Pages 57 - 59

FAP6

Detectors

Pages 60 - 62 Pages 60 - 62

FMC

Call points

Pages 63 - 65 Pages 63 - 65

FACS

Alarms

Pages 67 - 69 Pages 67 - 69

FACB

Alarms

Pages 69 - 70 Pages 69 - 70

FBEAM

Detectors

Pages 80 - 81 Pages 80 - 81

FAKV

Voice alarms

Page 78 Page 78

FDM Door

retainers

Page 86 Page 86

FASD

Detectors

Pages 82 - 83

FAR Wireless

devices

Pages 73 - 74

Page 99: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

The Emergi-Lite portfolio from Thomas & Bettsdelivers a highly versatile choice of emergencylighting and fire detection products and systemsfor a wide range of applications. Our aim is toenable customers to achieve the maximumbenefit in investment. This is gained throughproduct design, for quick and simple installationwith inherent energy efficiency and minimummaintenance, whilst keeping the protection andsafety of human life paramount.

Since 1998, the Emergi-Lite brand has been included

in the product portfolio of the Thomas & Betts

Corporation.

In 1898 Thomas & Betts was founded in New York.

The corporate headquarters now reside in Memphis,

Tennessee with the company being listed on the

New York stock exchange. Thomas & Betts has now

over 100 years of experience of successfully supplying

quality products to the market by using innovative

design and manufacturing techniques. A truly global

player having a presence in Europe, North & Central

America, Australia and the Far & Middle East.

Worldwide 13,000 employees are dedicated to

ensuring that Thomas & Betts is fast, flexible and

customer focussed.

Whilst one of our main businesses remains in the

electrical products, among which Emergency Lighting

and Fire Detection Systems, Thomas & Betts

also has leading brands along with significant market

share in Steel Structures, Communications, Electronic

Systems Protection and Earthing & Lightning

Protection.

In recent years, Thomas & Betts has developed a

formidable European safety products division, the

principal products of which are emergency lighting

and fire detection systems. This division serves as a key

knowledge platform. Emergi-Lite being one of the

leading brands within this division, benefits from the

economies of scale in product development and

production, facilitating the efficient further

development of emergency lighting and

fire detection technology.

Home to many well known brands and with over 100 years experience, Thomas & Betts provides a truly world-classlevel of quality, service and support. The electrical division in Europe provides the following key products:

Electrical products

An impressive range of high quality products

to fasten, install, insulate, protect and connect

electrical cables, with the confidence to achieve

a highly professional result.

Premium cable ties for the most demanding

applications, including the Ty-Rap® cable ties with a

steel locking barb and the Ty-Met™ self-locking

stainless steel ties.

A wide variety of multi-purpose heat shrink tubing

for use in insulation, protection, identification and

strain relief.

A broad range of solderless termination systems

for a variety of applications, including power

cables, shielded cables and magnet wire.

A range of liquidtight flexible conduits & fittings

for the protection of electrical cables in industrial

applications, in metallic and non-metallic versions

(including Nylon conduits & fittings).

A new range of cast resin joints for splicing and

branching low voltage cables, in applications like

street, leisure and airfield lighting, utility & home

connections.

A range of spring steel fasteners for quick, easy

and reliable fixing of services to steelwork.

Earthing & Lightningprotection solutions

With Furse, T&B is leading in the design,

manufacture and supply of earthing and

lightning protection systems.

Through its range of products, Furse can provide

complete and innovative solutions for lightning

protection, surge protection and earthing

applications.

Emergency lighting &fire detection systems

Throughout Europe T&B is well represented on

the emergency lighting and fire detection

markets with various leading brands providing

dedicated solutions for safe evacuation of

buildings and sites.

Emergi-Lite Safety Systems is the provider of

advanced emergency lighting and fire detection

systems, with field project support at the design

stage through to commissioning and maintenance.

The emergency lighting engineers, providing

innovation and the latest technology to the OEM

lighting industry.

Kaufel, formerly known as NIFE, is a strong brand

in emergency lighting products and safety power

supply systems, among which product brands are

Sentara, Venter and Twister.

Kaufel supplies a complete range of dedicated

emergency lighting luminaries and central battery

and testing systems with product brands like Brio,

Elitt and Sesam.

VanLien provides a wide range of emergency

Lighting solutions, ranging from luminaries to

central battery systems with product brands like

Optilux, Aqualux and Serenga

Fire Product Catalogue Cover 22/4/08 10:06 Page 2

Page 100: Total Solution Catalogue for web - Request Rejectedtnblnx3.tnb.com/emAlbum/albums/Emergi-Lite PDF/Fire... ·  · 2014-12-05r e P r o d u c t C a t a l o g u e 2 0 0 8 UKOFFICE Thomas&BettsLimited

Fire Product Catalogue 2008

FirePro

du

ctC

ata

log

ue

2008

UK OFFICE

Thomas & Betts Limited

Emergi-Lite Safety Systems

Bruntcliffe Lane

Leeds

West Yorkshire

LS27 9LL

United Kingdom

Tel +44 (0)113 281 0600

Fax +44 (0)113 281 0601

[email protected]

www.emergi-lite.co.uk

All enquiries to UK office

www.tnb-europe.com

MIDDLE EAST OFFICE

Thomas & Betts Ltd. Br.

Office 107 5EA East Wing

Dubai Airport Free Zone

PO Box 54567

Dubai

United Arab Emirates

Tel +9714 - 6091635

Fax +9714 - 6091636

E-mail: [email protected]

SOUTH EAST ASIA OFFICE

Thomas & Betts Asia (Singapore) Pte Ltd

10 Ang Mo Kio Street 65

#06-07 Techpoint

Singapore 569059

Tel +65 6720 8828

Fax +65 6720 8780

The content of this Thomas & Betts catalogue has been carefully checked for accuracy at the time of print. However, Thomas & Bettsdoesn’t give any warranty of any kind, express or implied, in this respect and shall not be liable for any loss or damage that may resultfrom any use or as a consequence of any inaccuracies in or any omissions from the information which it may contain. E&OE.

Copyright Thomas & Betts 2008. Copyright in these pages is owned by Thomas & Betts except where otherwise indicated. No part of thispublication may be reproduced, copied or transmitted in any form or by any means, without our prior written permission. Images, trademarks, brands, designs and technology are also protected by other intellectual property rights and may not be reproduced orappropriated in any manner without written permission of their respective owners. Thomas & Betts reserves the right to change andimprove any product specifications or other mentions in the catalogue at its own discretion and at any time. These conditions of use aregoverned by the laws of the Netherlands and the courts of Amsterdam shall have exclusive jurisdiction in any dispute.

FPC-PG108

HQ ASSESSED TO BS EN ISO9001: 2000FOR THE MANAGEMENT OF EMERGENCY

LIGHTING AND FIRE DETECTIONEQUIPMENT AND THE MODIFICATION OFMAINS LUMINAIRES FR EMERGENCY

LIGHTING APPLICATIONSCert no: FM09470

A member of theLIGHTING INDUSTRY FEDERATION

Note: The Emergi-Fire range from Emergi-Lite focuses on the specific needs of our customers for firealarm and detection solutions. Products, packaging, documentation, imagery and invoicing may displayeither the Emergi-Fire and/or Emergi-Lite logo.

Fire Product Catalogue Cover 22/4/08 10:05 Page 1