tracerco profiler operation and maintenance manual for
TRANSCRIPT
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 1 of 117
Tracerco Profiler Tracerco Profiler Tracerco Profiler Tracerco Profiler Operation and Operation and Operation and Operation and Maintenance Manual for Maintenance Manual for Maintenance Manual for Maintenance Manual for T229T229T229T229----2222 ControllerControllerControllerController
Document Number: MI0027
Revision: B
Date: 30th January 2017
REVISION STATUSREVISION STATUSREVISION STATUSREVISION STATUS SIGNED / DATEDSIGNED / DATEDSIGNED / DATEDSIGNED / DATED
B Updated for T229-2 P.Chow
30/01/2017 S.Rowe
07/03/2017 C.Hart
07/03/2017
A Original Issue D.Swalwell 28/06/2016
P.Chow 28/06/2016
S.Rowe 31/08/2016
REVREVREVREV REVISION DESCRIPTIONREVISION DESCRIPTIONREVISION DESCRIPTIONREVISION DESCRIPTION AUTHORAUTHORAUTHORAUTHOR CHECKEDCHECKEDCHECKEDCHECKED APPROVEDAPPROVEDAPPROVEDAPPROVED
Measurement Technology Centre, The Moat, Belasis Hall Technology Park, Billingham, Cleveland. TS23 4ED Tel: +44 (0) 1642 375500 Fax: +44 (0) 1642 370704 URL: www.tracerco.com
Functional Safety RelatedFunctional Safety RelatedFunctional Safety RelatedFunctional Safety Related ProductProductProductProduct No modifications permitted without the
approval of an authorised person
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 2 of 117
TABLE OF CONTENTS
1.1.1.1. DOCUMENT CONTROLDOCUMENT CONTROLDOCUMENT CONTROLDOCUMENT CONTROL ........................................................................................................................................................................................................................................................................................................................................ 7777
1.1. Notification List ............................................................................................................................................................... 7
1.2. Contact Information ........................................................................................................................................................ 7
1.3. 24 Hours Emergency Callout Numbers ......................................................................................................................... 7
2.2.2.2. INTRODUCTIONINTRODUCTIONINTRODUCTIONINTRODUCTION .................................................................................................................................................................................................................................................................................................................................................................................... 8888
2.1. Principle of Operation for a T240 Profiler ...................................................................................................................... 8
2.2. A Typical Instrument General Arrangement ................................................................................................................ 10
2.3. Detector Configuration ................................................................................................................................................. 10
3.3.3.3. INSTALLATIONINSTALLATIONINSTALLATIONINSTALLATION .................................................................................................................................................................................................................................................................................................................................................................................... 11111111
3.1. Installation of Support Bracket (Optional) ................................................................................................................... 11
3.2. Mechanical Installation (By Site) .................................................................................................................................. 11
3.3. Bolt Torqueing Procedure: ........................................................................................................................................... 11
4.4.4.4. RADIOLOGICAL SAFETYRADIOLOGICAL SAFETYRADIOLOGICAL SAFETYRADIOLOGICAL SAFETY ........................................................................................................................................................................................................................................................................................................................ 12121212
4.1. Source Isolation, Vessel Entry and Controlled Areas ................................................................................................. 12
4.2. Cesium Profiler Variant ................................................................................................................................................. 12
5.5.5.5. T229 HARDWARET229 HARDWARET229 HARDWARET229 HARDWARE .................................................................................................................................................................................................................................................................................................................................................................... 13131313
5.1. Connection Details ........................................................................................................................................................ 13
5.1.1. Connectors ............................................................................................................................................................ 13
5.1.2. Terminal List .......................................................................................................................................................... 13
5.2. Status Indicators ........................................................................................................................................................... 14
6.6.6.6. TRACERCO TOOLBOX SOFTRACERCO TOOLBOX SOFTRACERCO TOOLBOX SOFTRACERCO TOOLBOX SOFTWARETWARETWARETWARE ........................................................................................................................................................................................................................................................ 15151515
6.1. Log in to Toolbox Software .......................................................................................................................................... 20
6.2. Load a Backup Configuration File ............................................................................................................................... 21
6.3. The Calibrator Tool ....................................................................................................................................................... 22
6.3.1. Instrument Configuration ..................................................................................................................................... 25 6.3.1.1. TCP/IP Settings ............................................................................................................................................................26 6.3.1.2. Engineering Units ........................................................................................................................................................26 6.3.1.3. Set the Date and Time .................................................................................................................................................27 6.3.1.4. Set the Instrument Tag ................................................................................................................................................28 6.3.1.5. Verify Modbus Master/Slave Settings .........................................................................................................................29 6.3.1.6. Configure Source Type ................................................................................................................................................31 6.3.1.7. Configure Measurement Range ..................................................................................................................................32 6.3.1.8. Output Smoothing .......................................................................................................................................................33 6.3.1.9. Pressure Correction .....................................................................................................................................................34 6.3.1.10. Density Linearisation ..............................................................................................................................................35 6.3.1.11. Phase Transition Densities ......................................................................................................................................36 6.3.1.12. System Configuration ..............................................................................................................................................38
6.3.1.12.1. Build Device List ..................................................................................................................................................39 6.3.1.12.2. Fault Configuration .............................................................................................................................................40 6.3.1.12.3. Temperature Limits ............................................................................................................................................42
6.3.1.13. Device Configuration ..............................................................................................................................................43 6.3.1.13.1. Sensor Arrangement ...........................................................................................................................................44 6.3.1.13.2. Filtering Incoming Counts ...................................................................................................................................46 6.3.1.13.3. Dead Time Settings .............................................................................................................................................47
6.3.1.14. Stage Configuration ................................................................................................................................................48 6.3.1.14.1. Stage Elevations..................................................................................................................................................49
6.3.1.15. Save and Download Settings ...................................................................................................................................49
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 3 of 117
6.3.2. Calibration Procedure .......................................................................................................................................... 49 6.3.2.1. Define Reference Densities .........................................................................................................................................51 6.3.2.2. Accumulating Counts ..................................................................................................................................................52 6.3.2.3. Setting the Calibration Date ........................................................................................................................................55 6.3.2.4. Save and Download Settings .......................................................................................................................................55
6.3.3. Configuring Alarms and Fault Reporting ............................................................................................................. 56 6.3.3.1. Defining Stage Criticality .............................................................................................................................................57 6.3.3.2. Defining Alarm Criticality ............................................................................................................................................58 6.3.3.3. Save and Download Settings .......................................................................................................................................58
6.3.4. Defining I/O Parameters ....................................................................................................................................... 59 6.3.4.1. Analogue Input Configuration .....................................................................................................................................59
6.3.4.1.1. Time Constant (Seconds) ......................................................................................................................................59 6.3.4.1.2. ADC Settings .........................................................................................................................................................59 6.3.4.1.3. Scaled Engineering Units ......................................................................................................................................59 6.3.4.1.4. Status Word ..........................................................................................................................................................60
6.3.4.2. Analogue Output Configuration ..................................................................................................................................61 6.3.4.2.1. Selecting Active / Passive Outputs ........................................................................................................................62 6.3.4.2.2. Configuring the Source Register ...........................................................................................................................62 6.3.4.2.3. Configuring Settings for 4mA and 20mA ..............................................................................................................62 6.3.4.2.4. Control Mode 0: Source Data is Floating Point .....................................................................................................63 6.3.4.2.5. Control Mode 1: Source Data is Unsigned 16-bit Integer .....................................................................................64 6.3.4.2.6. Control Mode 2: Two State Output, Source Data is a Bit .....................................................................................65 6.3.4.2.7. Control Mode 3: Two State Output, Float Comparison ........................................................................................66 6.3.4.2.8. Control Mode 4: Two State Output, U16 Comparison..........................................................................................67 6.3.4.2.9. Primary Fault Indication Bit Mask .........................................................................................................................68 6.3.4.2.10. Secondary Fault Indication Bit Mask ..................................................................................................................69 6.3.4.2.11. Range Clipping ....................................................................................................................................................70 6.3.4.2.12. Slew Rate Limiting ..............................................................................................................................................70 6.3.4.2.13. Status Word ........................................................................................................................................................70
6.3.4.3. Digital Output Configuration .......................................................................................................................................71 6.3.4.3.1. Control Mode 2: Two State Output with Bit Mask ...............................................................................................71 6.3.4.3.2. Control Mode 3: Two State Output, Float Comparison ........................................................................................72 6.3.4.3.3. Control Mode 4: Two State Output, U16 Comparison..........................................................................................73 6.3.4.3.4. Common Fault Indication .....................................................................................................................................74 6.3.4.3.5. Status Word ..........................................................................................................................................................74 6.3.4.3.6. Output State .........................................................................................................................................................74
6.3.5. Defining Modbus Output Mapping ...................................................................................................................... 75
6.3.6. Overview of the Command Tool .......................................................................................................................... 76 6.3.6.1. Reset to Factory Settings .............................................................................................................................................76 6.3.6.2. Compatibility Mode.....................................................................................................................................................76
6.3.7. Dynamic Density Band Correction ...................................................................................................................... 77 6.3.7.1. Choosing a Density Band to Correct ............................................................................................................................78 6.3.7.2. Calculating an Average Reference Density ..................................................................................................................78 6.3.7.3. Setpoint Offset ............................................................................................................................................................78 6.3.7.4. Calculated Average Reference Density .......................................................................................................................79 6.3.7.5. Calculated Setting for Phase Transition Density ..........................................................................................................79 6.3.7.6. Density Band Correction Status Word .........................................................................................................................79
7.7.7.7. SYSTEM STARTSYSTEM STARTSYSTEM STARTSYSTEM START----UPUPUPUP .................................................................................................................................................................................................................................................................................................................................................... 80808080
8.8.8.8. MAINTENANCEMAINTENANCEMAINTENANCEMAINTENANCE ................................................................................................................................................................................................................................................................................................................................................................................ 81818181
8.1. Wiring Connections ....................................................................................................................................................... 81
8.1.1. Connection in the Safe Area ................................................................................................................................ 81
8.2. Intrinsic Safety Considerations .................................................................................................................................... 81
8.2.1. Safety/Handling Precautions ............................................................................................................................... 81
8.3. Replacing a T240 Processor Board ............................................................................................................................. 82
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 4 of 117
8.4. Routine Maintenance/Inspection ................................................................................................................................. 82
9.9.9.9. TROUBLESHOOTINGTROUBLESHOOTINGTROUBLESHOOTINGTROUBLESHOOTING ............................................................................................................................................................................................................................................................................................................................................ 83838383
10.10.10.10. APPENDIX A: T240 PROAPPENDIX A: T240 PROAPPENDIX A: T240 PROAPPENDIX A: T240 PROFILER VARIANTFILER VARIANTFILER VARIANTFILER VARIANT ............................................................................................................................................................................................................................ 85858585
10.1. Installation ................................................................................................................................................................. 85
10.1.1. Electrical Supply ................................................................................................................................................... 85
10.1.2. Communications Fibre ......................................................................................................................................... 85
10.2. Component Specifications ....................................................................................................................................... 86
10.2.1. Performance Specifications ................................................................................................................................. 86
10.2.2. Dip Pipes ............................................................................................................................................................... 86
10.2.3. Radioactive Sources ............................................................................................................................................ 87
10.2.4. Detector Assembly ............................................................................................................................................... 87
10.2.5. Maximum and Minimum Operating Temperatures ............................................................................................. 87
10.2.6. Storage Temperature ........................................................................................................................................... 87
10.2.7. IP Rating ................................................................................................................................................................ 87
10.2.8. Mechanical Dimensions ....................................................................................................................................... 88
10.2.9. Power Cable and Glands Specification............................................................................................................... 88
10.2.10. Fibre Optic Cable Specification ........................................................................................................................... 88
10.2.11. Electrical Specifications - Supply Details............................................................................................................ 88
10.2.12. Standards and Accreditation (Approval Certificates) ......................................................................................... 89
11.11.11.11. APPENDIX B: REGISTERAPPENDIX B: REGISTERAPPENDIX B: REGISTERAPPENDIX B: REGISTER MAPMAPMAPMAP ........................................................................................................................................................................................................................................................................................ 90909090
11.1. T229 Specific Details and settings .......................................................................................................................... 90
11.2. Register description ............................................................................................................................................... 100
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 5 of 117
TABLE OF FIGURES
Figure 1 – Typical Separation Vessel ......................................................................................................................................... 8
Figure 2 – Typical Modbus System Representation ................................................................................................................. 9
Figure 3 – Typical Representation ............................................................................................................................................ 10
Figure 4 - T240 Detector Cutaway ........................................................................................................................................... 10
Figure 5 - Opening & isolation of Sources ............................................................................................................................... 12
Figure 6 - Side Nearest Ethernet Connector ........................................................................................................................... 13
Figure 7 - Side Furthest from Ethernet Connector .................................................................................................................. 13
Figure 8 – PC to T229 Connection Diagram via Modbus Slave ............................................................................................. 15
Figure 9 – Toolbox Start-up Screen ......................................................................................................................................... 15
Figure 10 – Toolbox Connection Wizard .................................................................................................................................. 16
Figure 11 – Toolbox Connection Protocol ............................................................................................................................... 16
Figure 12 – Toolbox Modbus RTU Settings............................................................................................................................. 17
Figure 13 – Toolbox Connection Successful ........................................................................................................................... 18
Figure 14 – Toolbox Connection Wizard Error ........................................................................................................................ 18
Figure 15 – Toolbox Application ............................................................................................................................................... 19
Figure 16 – Toolbox Available Tools ........................................................................................................................................ 20
Figure 17 – Calibrator ................................................................................................................................................................ 21
Figure 18 - Calibrator Icons ...................................................................................................................................................... 21
Figure 19 – Toolbox Calibrator Reading Data from T229 ....................................................................................................... 23
Figure 20 – Toolbox Calibrator Writing Data to T229 .............................................................................................................. 24
Figure 21 – FLOWCHART FOR INSTRUMENT CONFIGURATION ........................................................................................ 25
Figure 22 – Modbus TCP/IP Settings ....................................................................................................................................... 26
Figure 23 – Engineering Units ................................................................................................................................................... 26
Figure 24 – Calibrator: Setting Real-time Clock ...................................................................................................................... 27
Figure 25 – Calibrator: Setting the Instrument Tag ................................................................................................................. 28
Figure 26 – Calibrator: Modbus Slave Settings ....................................................................................................................... 29
Figure 27 – Calibrator: Source Settings ................................................................................................................................... 31
Figure 28 – Calibrator: Measurement Range ........................................................................................................................... 32
Figure 29 – Calibrator: Output Smoothing ............................................................................................................................... 33
Figure 30 – Calibrator: Pressure Correction ............................................................................................................................ 34
Figure 31 – Calibrator: Density Linearisation ........................................................................................................................... 35
Figure 32 – Calibrator: Phase Densities ................................................................................................................................... 36
Figure 33 – Calibrator: Phase Density Application .................................................................................................................. 37
Figure 34 – FLOWCHART FOR SYSTEM CONFIGURATION ................................................................................................. 38
Figure 35 – Calibrator: Building a Device List .......................................................................................................................... 39
Figure 36 – Calibrator: Modbus Slave Settings ....................................................................................................................... 40
Figure 37 – Calibrator: Setting Temperature Limits ................................................................................................................ 42
Figure 38 – FLOWCHART FOR DEVICE CONFIGURATION ................................................................................................... 43
Figure 39 – Calibrator: Sensor Arrangement Example Detector A ......................................................................................... 44
Figure 40 – Calibrator: Sensor Arrangement Example Detector B ......................................................................................... 45
Figure 41 – Calibrator: Filtering ................................................................................................................................................ 46
Figure 42 – Calibrator: Dead Time Settings ............................................................................................................................. 47
Figure 43 – FLOWCHART FOR STAGE CONFIGURATION .................................................................................................... 48
Figure 44 – Calibrator: Defining Stage Elevation ..................................................................................................................... 49
Figure 45 – FLOWCHART FOR CALIBRATION PROCESS .................................................................................................... 50
Figure 46 – Calibrator: Defining Reference Densities ............................................................................................................. 51
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 6 of 117
Figure 47 – Calibrator: Count Rate Gathering Tool ................................................................................................................. 52
Figure 48 – Calibrator: Count Rates (sample calibration data) ............................................................................................... 54
Figure 49 – Calibrator: Setting the Calibration Date ............................................................................................................... 55
Figure 50 – FLOWCHART FOR DEFINING ALARM HANDLING ............................................................................................ 56
Figure 51 – Calibrator: Stage Criticality ................................................................................................................................... 57
Figure 52 – Calibrator: Alarm Criticality ................................................................................................................................... 58
Figure 53 – Calibrator: Analogue Input Dialog ......................................................................................................................... 59
Figure 54 – Calibrator: Example Analogue Output Configuration .......................................................................................... 61
Figure 55 – Active T229-2 Analogue Output ........................................................................................................................... 62
Figure 56 – Passive T229-2 Analogue Output ......................................................................................................................... 62
Figure 57 – Calibrator: Analogue Output Control Mode 0 Dialogue ...................................................................................... 63
Figure 58 – Calibrator: Analogue Output Control Mode 1 Dialogue ...................................................................................... 64
Figure 59 – Calibrator: Analogue Output Control Mode 2 Dialogue ...................................................................................... 65
Figure 60 – Calibrator: Analogue Output Control Mode 3 Dialogue ...................................................................................... 66
Figure 61 – Calibrator: Analogue Output Control Mode 4 Dialogue ...................................................................................... 67
Figure 62 – Calibrator: Analogue Output Primary Fault Indication Mask............................................................................... 68
Figure 63 – Calibrator: Analogue Output Secondary Fault Indication Mask ......................................................................... 69
Figure 64 – Calibrator: Digital Output Configuration for Control Mode 2 .............................................................................. 71
Figure 65 – Calibrator: Digital Output Configuration for Control Mode 3 .............................................................................. 72
Figure 66 – Calibrator: Digital Output Configuration for Control Mode 4 .............................................................................. 73
Figure 67 – Calibrator: Output Mapping .................................................................................................................................. 75
Figure 68 – Toolbox: Command Tool ....................................................................................................................................... 76
Figure 69 – Dynamic Density Band Correction ....................................................................................................................... 77
Figure 70 - Diagram Showing Profiler Dome and Arming Rod ............................................................................................... 80
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 7 of 117
1.1.1.1. Document ControlDocument ControlDocument ControlDocument Control
1.1. Notification List
This section gives details of those parties who should be notified upon release of each new revision:
Name Organisation Contact Details
Simon Lambert Tracerco (UK) 01642 375500
Steve Roe Tracerco (UK) 01642 375500
Paul Chow Tracerco (UK) 01642 375567
1.2. Contact Information
In the event of any safety or operational queries please contact Tracerco services for information.
TracercoTracercoTracercoTracerco
Measurement Technology Centre
The Moat
Belasis Hall Business Park
Billingham
Cleveland, UK
TS23 4ED
Tel: +44 (0)1642 375500
Fax: +44 (0)1642 370704
Email: [email protected]
URL: www.tracerco.com
1.3. 24 Hours Emergency Callout Numbers
Instrument related problem: Tel: +44 (0) 7885 667494
Radiological Protection Advisor: Fax: +44 (0) 7889 828968
This document is a private and confidential communication and the property of Tracerco Ltd, it must not be loaned or
copied without the prior consent of Tracerco Ltd and must be returned.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 8 of 117
2.2.2.2. IntroductionIntroductionIntroductionIntroduction
Separation vessels contain products such as Gas, Foam, Oil, Emulsion, Water, and Sand which naturally gravitate into
different phases as shown in Figure 1. Each phase has a different density.
The Tracerco ProfilerTM is an advanced Specialist Measurement instrument used to identify different phases within
multiphase systems. Employing award winning and patented techniques it measures the gamma absorption of the
process material. This enables a meaningful and accurate measurement of the vertical density distribution within vessels
to be made.
The instrument uses a vertical array of sources and
detectors (Geiger Müller Tubes), to measure and map the
different process phases with respect to vessel height.
Reliable assessment of both the interface quality and the
level of the interfaces present within the vessel are
achievable.
Measurements can be separated into a maximum of up
to ten different density bands or phases. The elevation of
the various phases can be calculated and outputs given
with respect to the instrument height.
The information provided can then be used to give
outputs to control oil and water interface levels, control
and monitor the effects of chemical additives or establish
effective sand washing regimes.
Figure Figure Figure Figure 1111 –––– Typical Separation VesselTypical Separation VesselTypical Separation VesselTypical Separation Vessel
2.1. Principle of Operation for a T240 Profiler
The T240 Profiler can support either 1 or 2 separate detector arrays depending upon the application. On occasion 2
detectors are required so that the power level in each is low enough to meet the requirements of intrinsic safety over
longer measurement ranges.
Each detector may contain up to 75 Geiger Müller tubes giving a maximum of 150 for this instrument although again, the
number of actual tubes specified and their configuration depends upon the application.
With sources loaded and the arming rod in the open position the process material present between the source and
detector will attenuate the radiation. The amount of attenuation measured by the Geiger Muller is then used to calculate
the density of the intervening material.
The T229 controller collects information from each individual GM tube, and through a series of calculations determines
the density of the material. This enables a density or interface profile of the vessel to be constructed. Density bands are
allocated for each of the phases (typically Gas, Foam, Oil, Emulsion, Water and Sand). Up to 6 interfaces may be
configured. The top level of these phases can then be calculated with respect to instrument height.
.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 9 of 117
Figure Figure Figure Figure 2222 –––– Typical Modbus System RepresentationTypical Modbus System RepresentationTypical Modbus System RepresentationTypical Modbus System Representation
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 10 of 117
2.2. A Typical Instrument General Arrangement
A diagram of a single detector system is shown below. The Profiler is typically located on a flange at the top of a vessel
and consists of 3 main components that make up the outer instrument housing. These are the dip-pipes, neck and dome.
Figure Figure Figure Figure 3333 –––– Typical RepresentationTypical RepresentationTypical RepresentationTypical Representation
The dip-pipes project into the separator through the vessel flange and consist of a source assembly and detector probe(s).
The source assembly holds the source rod in the collimator. This source rod contains a series of sources distributed
along its length. The rod is attached to an arming mechanism allowing the user to isolate the sources within the device.
The collimator has a series of small holes, which align with each source position when the rod is in the open position.
This allows narrow beams of radiation to be directed towards the detectors in the adjacent detector tube(s). When the
arming mechanism is locked in the shut position the alignment of the sources and the collimator is such that the sources
are isolated and the radiation from the gauge is at a safe level.
The dip-pipes are effectively a sleeve and datum for the instrument components and provide the pressure seal with the
vessel flange.
2.3. Detector Configuration
Each detector probe is populated with Geiger Müller tubes positioned along its length and encased within a protective
sleeve. Each probe assembly is housed within the detector dip pipe(s).
A pulse-shaping amplifier, mounted on the detector probe circuit board, is
used to produce a useable pulse signal for each Geiger tube output. The
output of these amplifiers is connected to the signal processing board via a
multi-way cable.
The number and spacing of sources and detectors is configurable and
governs the range and resolution of the instrument.
The tubes are distributed over the range of the instrument to provide the
required range and resolution of the application. On multi-detector systems
the tubes may be offset such that a better resolution is achieved.
Figure Figure Figure Figure 4444 ---- T240 Detector CutawayT240 Detector CutawayT240 Detector CutawayT240 Detector Cutaway
DOME HEIGHTDOME HEIGHTDOME HEIGHTDOME HEIGHT
FLANGE FLANGE FLANGE FLANGE
DIP PIPE
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 11 of 117
3.3.3.3. InstallationInstallationInstallationInstallation
There are two main aspects of the profiler installation:
1. Mechanical
2. Electrical and Communications
The mechanical components are generally shipped as the following components:
1. Assembled Profiler unit consisting of probes, dip pipes, neck, dome, collimator
2. Support bracket
3. Communications breakout boxes.
4. Source, in arming rods and A type container
3.1. Installation of Support Bracket (Optional)
The support bracket is not used in all profiler applications. Where required the project will be issued with job specific
mechanical drawings that include a general arrangement drawing and a lower support arrangement drawing (if required).
Affix bottom support to suitable internal clips or local internal support at the height shown on general arrangement
drawing. Ensuring the arrows on the base are positioned in the direction of liquid flow.
Insert the dip-pipe(s) in to the vessel following review of installation information below. Pass the dip-pipe(s) through the
annulus of the bottom support, tightening the bolts fix the dip pipe in place.
Torque the dip-pipe flange to correct settings. Please refer to project specific pressure vessel calculations for suggested
gasket type and bolt torque settings.
3.2. Mechanical Installation (By Site)
All dip-pipe assemblies will be dispatched packed into a wooden crate(s). Each wooden crate containing a dip-pipe
assembly will be suitable for handling by fork-lift truck and slings and can be stored in a normal store. It is essential the
dip pipes are kept dry. If the crate is opened during storage for inspection then Tracerco recommend the crate is re-
sealed to prevent moisture ingress.
To install carefully remove the lid of the crate, where lifting equipment is required and fix lifting shackles through the lifting
lugs fitted to the titanium flange. It is recommended that the lifting shackle is a 2te rated large 'D' shackle (BS 3032 1958).
For internally mounted dip-pipes, ensure that the flange face of vessel nozzle is clean and place the joint gasket on the
nozzle flange. Using a suitable hoist lift the dip-pipe assembly out of its crate and into position above the vessel nozzle.
Carefully lower the dip-pipe assembly through the nozzle and into the vessel. When the dip-pipe is approximately 200mm
from the vessel nozzle carefully remove the fixing bolts that hold the profiler neck and dome to the titanium flange. With
the neck and dome supported continue to lower the dip-pipe assembly until it mates with the vessel nozzle, ensuring that
the dip-pipe passes through the bottom support bracket as above, if fitted.
The integrity of the titanium dip-pipe assembly must be protected by a suitable sized relief valve fitted to the vessel.
3.3. Bolt Torqueing Procedure:
Please refer to project specific pressure vessel calculations for suggested gasket type and bolt torque settings.
1. All nuts to be capable of being run down their respective bolts by hand.
2. Ensure threads are suitably lubricated.
3. Assemble the joint and secure all nuts by hand.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 12 of 117
4.4.4.4. Radiological SafetyRadiological SafetyRadiological SafetyRadiological Safety
It is our normal practice to supply all equipment as specified except the radioactive sources. These will normally be
shipped to site prior to commissioning by Tracerco Services engineers. The sources will be shipped in a suitable type
“A” container. This ensures that the sources are safely packed and shielded for transport. When shipped to site, the
sources should be kept in a safe area (e.g. Radiographer’s store) until the arrival of Tracerco Services commissioning
engineers, who will install the source array into its dip-pipe. Prior to arrival of the sources, the site registration should be
amended to include the additional sources. Tracerco’s Radiation Protection Advisor (RPA) may be contacted for advice
with regard to licenses, registration, etc.
4.1. Source Isolation, Vessel Entry and Controlled Areas
The sources are contained within a single arming rod which can be locked with the sources in place. The lock must not
be removed by unauthorised persons.
For vessel entry during shutdown the arming rod must be locked shut to isolate the sources. This is achieved by pushing
down on the lever at the neck of the profiler (as shown in Figure 5) and inserting a padlock into the hole provided.
For UK applications a controlled area is mandatory around the Profiler, vessel or any area where a dose of dose > 7.5
micro-Sieverts/hr is measured. For non UK applications limits may differ depending on local regulations.
4.2. Cesium Profiler Variant
These sources emit a high energy (662keV) gamma ray. When entering the vessel a controlled area is required even when
isolated. The application specific radiological operating procedures must be used when dealing with this type of profiler.
Figure Figure Figure Figure 5555 ---- Opening & isolation of SourcesOpening & isolation of SourcesOpening & isolation of SourcesOpening & isolation of Sources
OPENOPENOPENOPEN
SHUTSHUTSHUTSHUT
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 13 of 117
5.5.5.5. T229 T229 T229 T229 HardwareHardwareHardwareHardware
The information contained within this section details how to configure and maintain the functionality of the Tracerco
Profiler TM through the Tracerco Toolbox software.
5.1. Connection Details
The T229 module is housed in a polyamide DIN rail mounting enclosure, 22.5 mm x 99 mmm x 114.5 mm. Connections
are made using 4 way 5mm pitch plug in terminals. The terminals will accommodate wires up to 2.5 mm².
5.1.1. Connectors
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
Figure Figure Figure Figure 6666 ---- Side Nearest Ethernet ConnectorSide Nearest Ethernet ConnectorSide Nearest Ethernet ConnectorSide Nearest Ethernet Connector Figure Figure Figure Figure 7777 ---- Side Furthest from Ethernet ConnectorSide Furthest from Ethernet ConnectorSide Furthest from Ethernet ConnectorSide Furthest from Ethernet Connector
5.1.2. Terminal List
TerminalTerminalTerminalTerminal FunctionFunctionFunctionFunction
1111 Analogue Output Channel 1 (active+ or passive-)
2222 Analogue Output Channel 1 (active- or passive+)
3333 Analogue Output Channel 2 (active+ or passive-)
4444 Analogue Output Channel 2 (active- or passive+)
5555 Analogue Output Channel 3 (active+ or passive-)
6666 Analogue Output Channel 3 (active- or passive+)
7777 Analogue Output Channel 4 (active+ or passive-)
8888 Analogue Output Channel 4 (active- or passive+)
9999 Analogue Output Channel 5 (active+ or passive-)
10101010 Analogue Output Channel 5 (active- or passive+)
11111111 DC Power input 24 Volts ±10%
12121212 DC Power input 0 Volts
13131313 4-20mA Analogue Input +
14141414 Modbus RTU Slave (RS485) - B
15151515 Modbus RTU Slave (RS485) – A
16161616 Modbus RTU Slave (RS485) - GND
17171717 4-20mA Analogue Input – OR Volt Free Contact A
18181818 Modbus RTU Master 1 (RS485) – B
19191919 Modbus RTU Master 1 (RS485) – A
20202020 Modbus RTU Master 1 (RS485) – GND
21212121 Volt Free Contact B
22222222 Modbus RTU Master 2 (RS485) – B
23232323 Modbus RTU Master 2 (RS485) – A
24242424 Modbus RTU Master 2 (RS485) – GND
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 14 of 117
5.2. Status Indicators
Four LEDs are provided to indicate the instrument status, and are visible on the front panel of the module. The functions
of the LEDs are as follows:
LabelLabelLabelLabel StateStateStateState MeaningMeaningMeaningMeaning
M1
Green / black flash
Green / red flash
Steady red
Off
Valid message exchange
Invalid message / message exchange
Communications error, port not operating
Port not enabled
M2
Green / black flash
Green / red flash
Steady red
Off
Valid message exchange
Invalid message / message exchange
Communications error, port not operating
Port not enabled
Host
Green flash
Blue flash
Red flash
Off
Valid message received (Modbus RS485)
Valid message received (Modbus over TCP/IP)
Invalid message received
Port not being polled
Status
Green
Yellow
Red
All devices communicating, instrument OK
Instrument running but a warning reported
Instrument not running, error reported
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 15 of 117
6.6.6.6. Tracerco Toolbox SoftwareTracerco Toolbox SoftwareTracerco Toolbox SoftwareTracerco Toolbox Software
Tracerco provide the ToolBox Software application for the setup, configuration and monitoring of their instrumentation.
Connection to the T229 Controller is achieved using either the ModBus slave port or via one of the two Ethernet TCP/IP
ports on the front of the unit. The ModBus slave port communicates using RS485 so a convertor is required between the
PC and the T229.
USB to RS485 Convertor
Laptop
15(B)
14(A)
16(G) T229 Controller
Mod
bu
s S
lave
1
(B)
(A)
(G)
Figure Figure Figure Figure 8888 –––– PC to T229 Connection DiagramPC to T229 Connection DiagramPC to T229 Connection DiagramPC to T229 Connection Diagram via Modbus Slavevia Modbus Slavevia Modbus Slavevia Modbus Slave
NOTENOTENOTENOTE THE PC/LAPTOP MUST USE WINDOWS 7 OR HIGHER FOR COMPATIBILITY PURPOSES. THE PC/LAPTOP MUST USE WINDOWS 7 OR HIGHER FOR COMPATIBILITY PURPOSES. THE PC/LAPTOP MUST USE WINDOWS 7 OR HIGHER FOR COMPATIBILITY PURPOSES. THE PC/LAPTOP MUST USE WINDOWS 7 OR HIGHER FOR COMPATIBILITY PURPOSES.
TO CONNECT VIA TO CONNECT VIA TO CONNECT VIA TO CONNECT VIA MODBUS TCP/IP MODBUS TCP/IP MODBUS TCP/IP MODBUS TCP/IP USE USE USE USE THE RJ45 CONNECTIONS ON THE FRONT OF THE UNITTHE RJ45 CONNECTIONS ON THE FRONT OF THE UNITTHE RJ45 CONNECTIONS ON THE FRONT OF THE UNITTHE RJ45 CONNECTIONS ON THE FRONT OF THE UNIT
Run the Tracerco Toolbox 2 application from your Windows start menu. The start-up screen below will be shown for a
short time while initialisation takes place:
Figure Figure Figure Figure 9999 –––– Toolbox StartToolbox StartToolbox StartToolbox Start----up Screenup Screenup Screenup Screen
Once initialisation is complete the following dialogue is displayed, click Next >Next >Next >Next > to continue.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 16 of 117
Figure Figure Figure Figure 10101010 –––– Toolbox Connection WizardToolbox Connection WizardToolbox Connection WizardToolbox Connection Wizard
Figure Figure Figure Figure 11111111 –––– Toolbox Connection ProtocolToolbox Connection ProtocolToolbox Connection ProtocolToolbox Connection Protocol
Click on the ModbusModbusModbusModbus or ModbuModbuModbuModbus TCP/IPs TCP/IPs TCP/IPs TCP/IP button to continue depending on your connection to the T229 unit.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 17 of 117
Figure Figure Figure Figure 12121212 –––– Toolbox Toolbox Toolbox Toolbox Modbus Modbus Modbus Modbus RTU RTU RTU RTU SettingsSettingsSettingsSettings
Using the drop down list provided select the Serial PortSerial PortSerial PortSerial Port which is going to be used to make the connection to the T229.
The ModeModeModeMode, Baud RateBaud RateBaud RateBaud Rate, ParityParityParityParity, Stop Bits, Stop Bits, Stop Bits, Stop Bits and Slave AddressSlave AddressSlave AddressSlave Address should be set as shown for a module with default settings.
OR…
Enter the IP AddressIP AddressIP AddressIP Address of the T229 Unit. Note that the IP address of your PC must be on the same network. Leave the
PPPPort ort ort ort setting at 502502502502, this is the default for a ModBus connection. Finally, select the correct Slave AddressSlave AddressSlave AddressSlave Address, you can
determine this by examining the T229 configuration file while offline.
When your selections are complete click Next >Next >Next >Next >
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 18 of 117
Figure Figure Figure Figure 13131313 –––– Toolbox Connection SuccessfulToolbox Connection SuccessfulToolbox Connection SuccessfulToolbox Connection Successful
If the connection is successful then the serial number is reported as 229YYNNNN (where YY is the year of manufacture
and NNNN is a unique T229 Serial Number). At this point select FinishFinishFinishFinish to continue.
If the serial number is reported as zero, then the module has lost its factory settings. Contact Tracerco for advice if this
is the case, contact details are provided in section 1.2. Alternatively, if connection to the T229 is not successful then the
following dialogue box will be displayed.
Figure Figure Figure Figure 14141414 –––– ToolboxToolboxToolboxToolbox Connection Wizard ErrorConnection Wizard ErrorConnection Wizard ErrorConnection Wizard Error
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 19 of 117
At this point verify:
• Wiring details
• Serial settings
• Power is applied to the instrument
• Check the status indicators described in section 5.2
The next screen is the main toolbox screen, showing the connection made, and the tools available. The range of available
tools shown depends on the level of access applied to the user logged in to Toolbox.
Figure Figure Figure Figure 15151515 –––– Toolbox ApplicationToolbox ApplicationToolbox ApplicationToolbox Application
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 20 of 117
6.1. Log in to Toolbox Software
Click on the Log InLog InLog InLog In button located at the top right hand corner of the screen. When the dialogue box appears, click on
the UserUserUserUser drop down list and select the SupervisorSupervisorSupervisorSupervisor option (customer login), Password – BardeenBardeenBardeenBardeen.
When logged in successfully the toolbox software will refresh the overview screen and display the list of tools which are
available for selection.
Figure Figure Figure Figure 16161616 –––– Toolbox Toolbox Toolbox Toolbox Available ToolsAvailable ToolsAvailable ToolsAvailable Tools
The screen will show the tools available to the Supervisor for the connected device. To launch a tool, click on the
appropriate button in the available tools section. To return to the Toolbox screen from any tool, click on DevicesDevicesDevicesDevices.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 21 of 117
6.2. Load a Backup Configuration File
It is possible to download an existing configuration file to a new T229 controller. To do this first connect via Toolbox to
the new T229 unit and login as a supervisor (detailed in section 6.1). Once connected click on the calibrator icon under
available tools. This will load the data currently in the T229 unit and show the following page:
Figure Figure Figure Figure 17171717 –––– CalibratorCalibratorCalibratorCalibrator
Click on the ‘Read from File’ Icon in the top right hand corner:
Figure Figure Figure Figure 18181818 ---- Calibrator IconsCalibrator IconsCalibrator IconsCalibrator Icons
Browse your backup storage media and select the appropriate configuration file.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 22 of 117
Once the backup has opened this can then be written to the device by clicking the ‘Write to Device’ icon
IMPORTANTIMPORTANTIMPORTANTIMPORTANT ENSURE THAT THE CONFIGURATION WITHIN THE BACKUP FILE APPLIES TO THE INSTRUMENT IN ENSURE THAT THE CONFIGURATION WITHIN THE BACKUP FILE APPLIES TO THE INSTRUMENT IN ENSURE THAT THE CONFIGURATION WITHIN THE BACKUP FILE APPLIES TO THE INSTRUMENT IN ENSURE THAT THE CONFIGURATION WITHIN THE BACKUP FILE APPLIES TO THE INSTRUMENT IN
QUESTION AND THAT KEY PARAMETERS SUCH AS THE PHASE TRANSITION DENSITY SETPOINTS AND QUESTION AND THAT KEY PARAMETERS SUCH AS THE PHASE TRANSITION DENSITY SETPOINTS AND QUESTION AND THAT KEY PARAMETERS SUCH AS THE PHASE TRANSITION DENSITY SETPOINTS AND QUESTION AND THAT KEY PARAMETERS SUCH AS THE PHASE TRANSITION DENSITY SETPOINTS AND
CALIBRATION DATA ARE VALIDCALIBRATION DATA ARE VALIDCALIBRATION DATA ARE VALIDCALIBRATION DATA ARE VALID
6.3. The Calibrator Tool
The Calibrator tool provides the user with the ability to configure and store key parameters on the T229 and allows the
user to create a backup of the application on a local storage device.
To launch the Calibrator tool, click on the button in the Available ApplicationsAvailable ApplicationsAvailable ApplicationsAvailable Applications area of the overview screen. To return to
the Toolbox screen from any tool, click on DevicesDevicesDevicesDevices.
Toolbox will read settings from the T229 as shown below. When all the required settings have been entered in the various
Toolbox screens, the Calibrator tool provides functionality to write data to the device or to create a backup file.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 23 of 117
Figure Figure Figure Figure 19191919 –––– Toolbox Calibrator Reading Data from T229Toolbox Calibrator Reading Data from T229Toolbox Calibrator Reading Data from T229Toolbox Calibrator Reading Data from T229
Validate calibration data.
Select this button to write the settings to a file on your chosen storage device.
You will be asked for a file name and location via windows save dialog. The default file extension is .T229C.
Load settings from a file. There is an opportunity to cancel this action, but if you proceed, any settings you
have already entered will be overwritten. This functionality is useful when replacing a T229 as an existing
calibration, stored in a file can easily be transferred to a new T229.
Select this button to write the settings to the TSelect this button to write the settings to the TSelect this button to write the settings to the TSelect this button to write the settings to the T229 instrument229 instrument229 instrument229 instrument.
The screen will show the progress of the writing process.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 24 of 117
Figure Figure Figure Figure 20202020 –––– Toolbox Calibrator Writing Data to T229Toolbox Calibrator Writing Data to T229Toolbox Calibrator Writing Data to T229Toolbox Calibrator Writing Data to T229
This button loads the settings from a T229 into the calibrator tool. This will overwrite settings you have entered.
This function is automatically performed when the calibrator tool is first started.
This button will restore the factory defaults to the calibrator settingsto the calibrator settingsto the calibrator settingsto the calibrator settings, overwriting many of the settings that
may have been entered. There is no opportunity to cancel.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 25 of 117
6.3.1. Instrument Configuration
The following flowchart provides a process for the basic configuration / setup of a T229 based instrument.
Figure Figure Figure Figure 21212121 –––– FLOWCHART FOR INSTRUMENTFLOWCHART FOR INSTRUMENTFLOWCHART FOR INSTRUMENTFLOWCHART FOR INSTRUMENT CONFIGURATIONCONFIGURATIONCONFIGURATIONCONFIGURATION
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 26 of 117
6.3.1.1. TCP/IP Settings
Define the configuration for Modbus TCP/IP Port 1Modbus TCP/IP Port 1Modbus TCP/IP Port 1Modbus TCP/IP Port 1 and Modbus TCP/IP Port 2Modbus TCP/IP Port 2Modbus TCP/IP Port 2Modbus TCP/IP Port 2 in line with project requirements. Useful
sources of information here are the Modbus interface DocumentModbus interface DocumentModbus interface DocumentModbus interface Document and the System HookSystem HookSystem HookSystem Hook----up Diagramup Diagramup Diagramup Diagram.
Figure Figure Figure Figure 22222222 –––– Modbus TCP/IP SettingsModbus TCP/IP SettingsModbus TCP/IP SettingsModbus TCP/IP Settings
6.3.1.2. Engineering Units
Configure the Engineering UnitsEngineering UnitsEngineering UnitsEngineering Units for LengthLengthLengthLength, DensityDensityDensityDensity and PressurePressurePressurePressure as per project requirements.
Figure Figure Figure Figure 23232323 –––– Engineering UnitsEngineering UnitsEngineering UnitsEngineering Units
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 27 of 117
6.3.1.3. Set the Date and Time
The first task is to set the date and time, this is essential for accurate decay correction of the radioactive sources. Select
Real Time ClockReal Time ClockReal Time ClockReal Time Clock to display the following dialogue.
Figure Figure Figure Figure 24242424 –––– Calibrator: Setting RealCalibrator: Setting RealCalibrator: Setting RealCalibrator: Setting Real----time Clocktime Clocktime Clocktime Clock
Clicking the Sync TimeSync TimeSync TimeSync Time button will set the T229 date and time to that of the PC running the toolbox software. If the PC
has the wrong time, you can use the drop down lists or enter the correct information manually. To commit any changes
you make, click the Set TSet TSet TSet Timeimeimeime button.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 28 of 117
6.3.1.4. Set the Instrument Tag
Select TagTagTagTag to enter the customer chosen instrument tag name. The maximum length is 20 characters and the default is
20 spaces.
NOTENOTENOTENOTE THE CORRECT INSTRUMENT THE CORRECT INSTRUMENT THE CORRECT INSTRUMENT THE CORRECT INSTRUMENT TAG NAMES CAN BE FOUND ON PROJECT SPECIFIC INSTRUMENT TAG NAMES CAN BE FOUND ON PROJECT SPECIFIC INSTRUMENT TAG NAMES CAN BE FOUND ON PROJECT SPECIFIC INSTRUMENT TAG NAMES CAN BE FOUND ON PROJECT SPECIFIC INSTRUMENT DATASHEETS.DATASHEETS.DATASHEETS.DATASHEETS.
Figure Figure Figure Figure 25252525 –––– Calibrator: Setting the Instrument TagCalibrator: Setting the Instrument TagCalibrator: Setting the Instrument TagCalibrator: Setting the Instrument Tag
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 29 of 117
6.3.1.5. Verify Modbus Master/Slave Settings
Although not in the order of the calibrator menu, this is an opportune time to check the various port settings. Click
ModbusModbusModbusModbus SettingsSettingsSettingsSettings to review the current configuration as shown below.
Figure Figure Figure Figure 26262626 –––– Calibrator: Modbus Slave SettingsCalibrator: Modbus Slave SettingsCalibrator: Modbus Slave SettingsCalibrator: Modbus Slave Settings
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 30 of 117
As you are connected to the T229, you must be using the settings shown for either Slave 1Slave 1Slave 1Slave 1 or those define in the TCP/IP
Settings in section 6.3.1.1. The slave port and the TCP/IP ports can be used for T229 maintenance or DCS/3rd party
interfaces.
NOTENOTENOTENOTE IT IS POSSIBLE TO ALTER THE DEFAULT SETTINGS, BUT THE CHANGES WILL NOT BE ACTED UPON UNTIL THEY IT IS POSSIBLE TO ALTER THE DEFAULT SETTINGS, BUT THE CHANGES WILL NOT BE ACTED UPON UNTIL THEY IT IS POSSIBLE TO ALTER THE DEFAULT SETTINGS, BUT THE CHANGES WILL NOT BE ACTED UPON UNTIL THEY IT IS POSSIBLE TO ALTER THE DEFAULT SETTINGS, BUT THE CHANGES WILL NOT BE ACTED UPON UNTIL THEY
ARE LOADED INTO THE T22ARE LOADED INTO THE T22ARE LOADED INTO THE T22ARE LOADED INTO THE T229 AND THE T229 IS POWER CYCLED 9 AND THE T229 IS POWER CYCLED 9 AND THE T229 IS POWER CYCLED 9 AND THE T229 IS POWER CYCLED IT WILL THEN BE NECESSARY IT WILL THEN BE NECESSARY IT WILL THEN BE NECESSARY IT WILL THEN BE NECESSARY TO TO TO TO QUIT THE QUIT THE QUIT THE QUIT THE
TOOLBOX AND RECONNECT TOOLBOX AND RECONNECT TOOLBOX AND RECONNECT TOOLBOX AND RECONNECT USING USING USING USING THE NEW PARAMETETHE NEW PARAMETETHE NEW PARAMETETHE NEW PARAMETERSRSRSRS
It is recommended that if the slave port settings need to be changed, then only one port at a time is changed, so that
communications can still be established on the unchanged port in the event of problems with the new settings.
NOTENOTENOTENOTE THERE IS A THERE IS A THERE IS A THERE IS A MECHANISM TO RECOVER FROM UNKNOWN SLAVE PORT SETTINGS IF A VALID MODBUS MESSAGE MECHANISM TO RECOVER FROM UNKNOWN SLAVE PORT SETTINGS IF A VALID MODBUS MESSAGE MECHANISM TO RECOVER FROM UNKNOWN SLAVE PORT SETTINGS IF A VALID MODBUS MESSAGE MECHANISM TO RECOVER FROM UNKNOWN SLAVE PORT SETTINGS IF A VALID MODBUS MESSAGE
IS RECEIVED, WRITING 0XDEFC (DEFAULT COMMUNICATION) TO REGISTER 0001, THE PORT WILL CONTINUE IS RECEIVED, WRITING 0XDEFC (DEFAULT COMMUNICATION) TO REGISTER 0001, THE PORT WILL CONTINUE IS RECEIVED, WRITING 0XDEFC (DEFAULT COMMUNICATION) TO REGISTER 0001, THE PORT WILL CONTINUE IS RECEIVED, WRITING 0XDEFC (DEFAULT COMMUNICATION) TO REGISTER 0001, THE PORT WILL CONTINUE
TO USE THE DEFAULT SETTING AND IGNORE THE REGISTER SETTING ON POWER UP OF THE T229,TO USE THE DEFAULT SETTING AND IGNORE THE REGISTER SETTING ON POWER UP OF THE T229,TO USE THE DEFAULT SETTING AND IGNORE THE REGISTER SETTING ON POWER UP OF THE T229,TO USE THE DEFAULT SETTING AND IGNORE THE REGISTER SETTING ON POWER UP OF THE T229, THE THE THE THE
MODBUS SLAVE PORTS WILL LISTEN FOR 1 SECOND WITH THE DEFAULT SETTINGSMODBUS SLAVE PORTS WILL LISTEN FOR 1 SECOND WITH THE DEFAULT SETTINGSMODBUS SLAVE PORTS WILL LISTEN FOR 1 SECOND WITH THE DEFAULT SETTINGSMODBUS SLAVE PORTS WILL LISTEN FOR 1 SECOND WITH THE DEFAULT SETTINGS
Set up the Master 1Master 1Master 1Master 1 and Master 2Master 2Master 2Master 2 ports to match the parameters of the attached devices. In a conventional two detector
profiler arrangement, both master ports would be used to provide detector redundancy.
The PassPassPassPass----throughthroughthroughthrough settings are not required in a normal set up. Pass through mode is only used for diagnostics and
troubleshooting. This allows the user to map an additional slave device address ((((PassPassPassPass----through Device Addressthrough Device Addressthrough Device Addressthrough Device Address)))) to a
particular device connected to one of the master ports ((((PassPassPassPass----through Device Selectthrough Device Selectthrough Device Selectthrough Device Select)))) allowing a user to interrogate a
detector directly from a slave port.
The Compatibility ModeCompatibility ModeCompatibility ModeCompatibility Mode settings are not required in new configurations. This option is Compatibility mode can be used
to create a register map compatible with a PLC based Profiler solution, when a T229 is being used to replace such as
system. Refer to section 6.3.6.2 for further details.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 31 of 117
6.3.1.6. Configure Source Type
Select the SourceSourceSourceSource option from the list of options on the left of the screen.
Select the application specific IsotopeIsotopeIsotopeIsotope from the drop down list. Note that a selection has been provided for non-standard
sources. Selecting CustomCustomCustomCustom will use the half-life set in the Custom Half LifeCustom Half LifeCustom Half LifeCustom Half Life setting.
The Calibration DateCalibration DateCalibration DateCalibration Date setting is used to set the reference point for the source decay calculation. This will be set later as
a part of the calibration procedure. If you are going to proceed to the calibration stage, then you can set the date now.
Figure Figure Figure Figure 27272727 –––– Calibrator: Source SettingsCalibrator: Source SettingsCalibrator: Source SettingsCalibrator: Source Settings
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 32 of 117
6.3.1.7. Configure Measurement Range
Select the MeasurMeasurMeasurMeasurementementementement RangeRangeRangeRange option from the list of options on the left of the screen.
Figure Figure Figure Figure 28282828 –––– Calibrator: Measurement RangeCalibrator: Measurement RangeCalibrator: Measurement RangeCalibrator: Measurement Range
Enter values for the BottomBottomBottomBottom and TopTopTopTop of the measuring range, from a nominal point. The bottom could for example be
zero, or the distance from the vessel bottom. The same nominal point is used when setting up the sensor arrangement
in the Profiler detectors, or whatever devices are attached to the T229.
NOTENOTENOTENOTE THE UNITS HERE ARE SHOWN AS METRES, HOWEVER THETHE UNITS HERE ARE SHOWN AS METRES, HOWEVER THETHE UNITS HERE ARE SHOWN AS METRES, HOWEVER THETHE UNITS HERE ARE SHOWN AS METRES, HOWEVER THESE UNITS CAN BE SPECIFIED IN THE DETAILS AND SE UNITS CAN BE SPECIFIED IN THE DETAILS AND SE UNITS CAN BE SPECIFIED IN THE DETAILS AND SE UNITS CAN BE SPECIFIED IN THE DETAILS AND
SETTINGS SECTION UNDER ENGINEERING UNITS.SETTINGS SECTION UNDER ENGINEERING UNITS.SETTINGS SECTION UNDER ENGINEERING UNITS.SETTINGS SECTION UNDER ENGINEERING UNITS.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 33 of 117
6.3.1.8. Output Smoothing
This is the filter applied to the incoming pulse rate from the sensors. Select the Output SmoothingOutput SmoothingOutput SmoothingOutput Smoothing option.
Figure Figure Figure Figure 29292929 –––– Calibrator: Output SmoothingCalibrator: Output SmoothingCalibrator: Output SmoothingCalibrator: Output Smoothing
There are two choices for the Filter TypeFilter TypeFilter TypeFilter Type, they are FixedFixedFixedFixed or DynamicDynamicDynamicDynamic.
DynamicDynamicDynamicDynamic FilteringFilteringFilteringFiltering provides a faster response to larger changes in density. Tracerco will recommend/configure a setting
base on the system requirements. The filter response times are specified in section 6.3.1.13.2.
Fixed FilteringFixed FilteringFixed FilteringFixed Filtering provides a linear response to changes in density. This option can be used on applications where the
vessel or storage tank is very large and the overall system response times are slow.
The Number of Standard DeviationsNumber of Standard DeviationsNumber of Standard DeviationsNumber of Standard Deviations should be set to 4 unless Tracerco recommend otherwise. This is only required for
DynamicDynamicDynamicDynamic filtering. A lower value may cause increased noise on the level outputs. A higher value may slow the response
time.
The Filtered Filtered Filtered Filtered Output Maximum Slew RateOutput Maximum Slew RateOutput Maximum Slew RateOutput Maximum Slew Rate controls the rate of change of the reported level outputs. For control systems
where sudden changes cause problems, this setting can be used to prevent sudden changes. The ideal setting will
depend on the required system response time, and possible rate of change of levels within the vessel. The recommended
default value is 0.1m/s.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 34 of 117
6.3.1.9. Pressure Correction
IMPORTANT IMPORTANT IMPORTANT IMPORTANT THIS OPTION IS NOT YET IMPLEMENTED ALL REGISTERS ASSOCIATED WITH PRESSURE CORRECTION THIS OPTION IS NOT YET IMPLEMENTED ALL REGISTERS ASSOCIATED WITH PRESSURE CORRECTION THIS OPTION IS NOT YET IMPLEMENTED ALL REGISTERS ASSOCIATED WITH PRESSURE CORRECTION THIS OPTION IS NOT YET IMPLEMENTED ALL REGISTERS ASSOCIATED WITH PRESSURE CORRECTION
ARE MARKED AS RESERVED IN THE REARE MARKED AS RESERVED IN THE REARE MARKED AS RESERVED IN THE REARE MARKED AS RESERVED IN THE REGISTER LIST AND REGISTER DESCRIPTIONS ENSURE THAT THE GISTER LIST AND REGISTER DESCRIPTIONS ENSURE THAT THE GISTER LIST AND REGISTER DESCRIPTIONS ENSURE THAT THE GISTER LIST AND REGISTER DESCRIPTIONS ENSURE THAT THE
PRESSURE CORRECTION TYPE IS SET TO IS SET TO IS SET TO IS SET TO DISABLED
Select the Pressure CorrectionPressure CorrectionPressure CorrectionPressure Correction option from the list on the left of the screen.
Figure Figure Figure Figure 30303030 –––– Calibrator: Pressure CorrectionCalibrator: Pressure CorrectionCalibrator: Pressure CorrectionCalibrator: Pressure Correction
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 35 of 117
6.3.1.10. Density Linearisation
Up to 11 linearisation points can be defined to perform the density correction. Limits for the correction are defined by
minimum and maximum density values defined for the instrument. These values may be set to 0 and 10000 kg/m3 where
kg/m3 is used as the engineering unit for density.
Corrected density values are exposed in the application specific stage area. When the look up table is not being used,
the corrected density values are the same as the uncorrected values.
Select the DeDeDeDensity Linearisationnsity Linearisationnsity Linearisationnsity Linearisation option from the list on the left of the screen.
Figure Figure Figure Figure 31313131 –––– Calibrator: Density LinearisationCalibrator: Density LinearisationCalibrator: Density LinearisationCalibrator: Density Linearisation
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 36 of 117
6.3.1.11. Phase Transition Densities
To calibrate the system, count rates from each sensor need to be recorded at two known densities. Using the sensor
mapping entered in section 6.3.1.13.1, the system calculates density values for all measurement stages based on the
calibration count rates and the current observed count rates.
The range of densities associated with a particular phase in the vessel must be defined, so that the measured stage
densities can be allocated to the correct phase. It may be necessary to confirm product densities with the operations
staff to provide an accurate configuration. Click on Phase DensitiesPhase DensitiesPhase DensitiesPhase Densities from the list, to set the phase density bands.
Click on Phase DensitiesPhase DensitiesPhase DensitiesPhase Densities from the list, to set the phase density bands.
Figure Figure Figure Figure 32323232 –––– Calibrator: Phase DensitiesCalibrator: Phase DensitiesCalibrator: Phase DensitiesCalibrator: Phase Densities
The Low densityLow densityLow densityLow density and High densityHigh densityHigh densityHigh density limits set the limits of the density calculation. Calculated values outside this range
will be clipped to the appropriate limit.
Up to 6 phases can be measured. For standard separators these are normally:
• Phase 1 Gas
• Phase 2 Foam
• Phase 3 Oil
• Phase 4 Emulsion
• Phase 5 Water
• Phase 6 Sand
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 37 of 117
Enter a value for the Phase 1Phase 1Phase 1Phase 1----2 transition density2 transition density2 transition density2 transition density. Densities below this value will be interpreted as phase 1. Enter a
value for the Phase 2Phase 2Phase 2Phase 2----3 transition density3 transition density3 transition density3 transition density. Densities below this value and above the phase 1-2 transition density will be
interpreted as phase 2. Enter values for the other Phase transition densities as required. Some systems may operate
with fewer phases, for example no foam.
NOTESNOTESNOTESNOTES THE REPORTED LEVEL FOR PHASE 1 WILL ALWAYS BE THE TOP OF THE THE REPORTED LEVEL FOR PHASE 1 WILL ALWAYS BE THE TOP OF THE THE REPORTED LEVEL FOR PHASE 1 WILL ALWAYS BE THE TOP OF THE THE REPORTED LEVEL FOR PHASE 1 WILL ALWAYS BE THE TOP OF THE MEASUREMENT MEASUREMENT MEASUREMENT MEASUREMENT RANGE.RANGE.RANGE.RANGE.
USE PHASE TRANSITION DENSITIES IN ORDER, LEAVING ANUSE PHASE TRANSITION DENSITIES IN ORDER, LEAVING ANUSE PHASE TRANSITION DENSITIES IN ORDER, LEAVING ANUSE PHASE TRANSITION DENSITIES IN ORDER, LEAVING ANY UNUSED ONES AT Y UNUSED ONES AT Y UNUSED ONES AT Y UNUSED ONES AT THE THE THE THE END OF END OF END OF END OF THE THE THE THE LIST. LIST. LIST. LIST.
MAKE SURE TO ASSIGN UNUSED PHASES WITH APPROPRIATE SETPOINTS SO THAT THEY ARE EFFECTIVELY MAKE SURE TO ASSIGN UNUSED PHASES WITH APPROPRIATE SETPOINTS SO THAT THEY ARE EFFECTIVELY MAKE SURE TO ASSIGN UNUSED PHASES WITH APPROPRIATE SETPOINTS SO THAT THEY ARE EFFECTIVELY MAKE SURE TO ASSIGN UNUSED PHASES WITH APPROPRIATE SETPOINTS SO THAT THEY ARE EFFECTIVELY EXCLUDED FROM THE LEVEL CALCULATIONS.EXCLUDED FROM THE LEVEL CALCULATIONS.EXCLUDED FROM THE LEVEL CALCULATIONS.EXCLUDED FROM THE LEVEL CALCULATIONS.
Figure Figure Figure Figure 33333333 –––– Calibrator: Phase Density ApplicatiCalibrator: Phase Density ApplicatiCalibrator: Phase Density ApplicatiCalibrator: Phase Density Applicationononon
As the ideal phase transition densities are dependent on the composition of the separator feed stock, the values can be
re-written by the host system if the composition varies. for example when a different well is producing input for the
separator.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 38 of 117
6.3.1.12. System Configuration
The system configuration portion of the T229 Calibrator tool allows the user to define the quantity and type of detectors
that make up the instrument. There can be up to 40 detectors in a single configuration and a mix of detector types is
possible.
Figure Figure Figure Figure 34343434 –––– FLOWCHART FOR SYSTEM CONFIGURATIONFLOWCHART FOR SYSTEM CONFIGURATIONFLOWCHART FOR SYSTEM CONFIGURATIONFLOWCHART FOR SYSTEM CONFIGURATION
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 39 of 117
6.3.1.12.1. Build Device List
Click on System Configuration System Configuration System Configuration System Configuration and the Device ListDevice ListDevice ListDevice List screen will open as shown below.
Figure Figure Figure Figure 35353535 –––– Calibrator: Building a Device ListCalibrator: Building a Device ListCalibrator: Building a Device ListCalibrator: Building a Device List
Enter the details for the devices connected to the T229 beginning with Device 1 and adding them sequentially thereafter.
NOTES NOTES NOTES NOTES THE UPDATE INTERVAL IS AN INTEGER VALUE IN SECONDSTHE UPDATE INTERVAL IS AN INTEGER VALUE IN SECONDSTHE UPDATE INTERVAL IS AN INTEGER VALUE IN SECONDSTHE UPDATE INTERVAL IS AN INTEGER VALUE IN SECONDS
THE SENSOR ARRANGEMENT WITHIN EACH DEVICE IS SETTHE SENSOR ARRANGEMENT WITHIN EACH DEVICE IS SETTHE SENSOR ARRANGEMENT WITHIN EACH DEVICE IS SETTHE SENSOR ARRANGEMENT WITHIN EACH DEVICE IS SET----UP LATER IN UP LATER IN UP LATER IN UP LATER IN SECTION SECTION SECTION SECTION 6.3.1.136.3.1.136.3.1.136.3.1.13....
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 40 of 117
6.3.1.12.2. Fault Configuration
Click on System Configuration System Configuration System Configuration System Configuration and then Fault Configuration Fault Configuration Fault Configuration Fault Configuration to set-up the device specific error handling.
Figure Figure Figure Figure 36363636 –––– Calibrator: Modbus Slave SettingsCalibrator: Modbus Slave SettingsCalibrator: Modbus Slave SettingsCalibrator: Modbus Slave Settings
Parameter Description Further Information
Comms
Retries
The entry sets the number of times the T229 will try
to read data before reporting a comms error.
Failing
Zeros
Sets the number of consecutive update intervals a
sensor in a device can return zero before the sensor
failing warning is flagged. The setting depends on
the update interval and count rate.
A low value may result in false warnings being
reported at low count rates.
A high value delays reporting of genuine faults.
Failed
Zeros
Sets the number of consecutive update intervals a
sensor in a device can return zero before the sensor
is flagged as failed. The setting depends on the
update interval and count rate.
A low value may result in false failure reporting at low
count rates.
A high value would delay reporting of genuine faults.
High
Count
Factor
The value is a multiplier applied to the empty count
setting for each sensor. This sets the count rate that
triggers a high count alarm for a sensor.
With an empty vessel, the count rate will be high and
this value is set so that the statistical fluctuations on
the count rate do not falsely trigger a high count rate
alarm.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 41 of 117
The boxes at the bottom of the screen can be used to automate the entry of data into the table.
Value Parameter Functionality
3 Comms Retries
The T229 module attempts to talk to each instrument as fast as possible. This is the
number of retries before it reports a communication fault.
The T229 does not perform multiple retries at the same time if there is more than 1
instrument connected to the same port. If it gets no response then it will try and
communicate with the other detector(s) in the system before retrying.
This ensures that a faulty channel does not cause missed updates on the other instrument.
Therefore the amount of time that it takes for a detector to register a communications
error is related the timeout period and the number of instruments on that port.
3 Failing Zeros
The number of successive updates where the value has returned zero. With an update
interval of 3 seconds, a value of 3 in this field would mean that it would take 9 seconds to
register a tube as failing.
6 Failed Zeros
The number of successive updates where the value has returned zero. With an update
interval of 3 seconds, a value of 6 in this field would mean that it would take 18 seconds
to register a tube as Failed.
1.5 High Count Factor Any update where a tube reports more than this factor times its empty count will cause
the tube to marked as faulty.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 42 of 117
6.3.1.12.3. Temperature Limits
IMPORTANIMPORTANIMPORTANIMPORTAN
T T T T
THIS OPTION IS NOT APPLICABLE TO CONVENTIONAL PROFILERS BUT MAY BE USED IN ACCORDANCE THIS OPTION IS NOT APPLICABLE TO CONVENTIONAL PROFILERS BUT MAY BE USED IN ACCORDANCE THIS OPTION IS NOT APPLICABLE TO CONVENTIONAL PROFILERS BUT MAY BE USED IN ACCORDANCE THIS OPTION IS NOT APPLICABLE TO CONVENTIONAL PROFILERS BUT MAY BE USED IN ACCORDANCE
WITH PROJECT SPECIFIC PROCESS CONDITIONS.WITH PROJECT SPECIFIC PROCESS CONDITIONS.WITH PROJECT SPECIFIC PROCESS CONDITIONS.WITH PROJECT SPECIFIC PROCESS CONDITIONS.
To access the option choose System Configuration System Configuration System Configuration System Configuration and then Temperature LimitsTemperature LimitsTemperature LimitsTemperature Limits.
The values for temperature in Tracerco devices is normally in degrees Kelvin, to allow temperature to be represented
simply in a Modbus register. The values shown in this screen are converted to degrees Celsius using an approximate
conversion.
Figure Figure Figure Figure 37373737 –––– Calibrator: Setting Temperature LimitsCalibrator: Setting Temperature LimitsCalibrator: Setting Temperature LimitsCalibrator: Setting Temperature Limits
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 43 of 117
6.3.1.13. Device Configuration
The device configurationdevice configurationdevice configurationdevice configuration option allows the user to configure the quantity of sensors, sensor parameters and the arrangement for each device defined in section 6.3.1.12.1.
Figure Figure Figure Figure 38383838 –––– FLOWCHART FOR DEVICE CONFIGURATIONFLOWCHART FOR DEVICE CONFIGURATIONFLOWCHART FOR DEVICE CONFIGURATIONFLOWCHART FOR DEVICE CONFIGURATION
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 44 of 117
6.3.1.13.1. Sensor Arrangement
Select Device ConfigurationDevice ConfigurationDevice ConfigurationDevice Configuration option from the menu on the left hand side of the page and then select Sensor Sensor Sensor Sensor
ArrangementArrangementArrangementArrangement.
Figure Figure Figure Figure 39393939 –––– Calibrator: Sensor Arrangement Example Detector ACalibrator: Sensor Arrangement Example Detector ACalibrator: Sensor Arrangement Example Detector ACalibrator: Sensor Arrangement Example Detector A
IMPORTANTIMPORTANTIMPORTANTIMPORTANT THE SETTINGS SHOWNTHE SETTINGS SHOWNTHE SETTINGS SHOWNTHE SETTINGS SHOWN ON THIS SCREEN ARE PER DEVICE. THESE PARAMETERS MUST BE CONFIGURED ON THIS SCREEN ARE PER DEVICE. THESE PARAMETERS MUST BE CONFIGURED ON THIS SCREEN ARE PER DEVICE. THESE PARAMETERS MUST BE CONFIGURED ON THIS SCREEN ARE PER DEVICE. THESE PARAMETERS MUST BE CONFIGURED
FOR EACH DEVICE IN THE SYSTEM.FOR EACH DEVICE IN THE SYSTEM.FOR EACH DEVICE IN THE SYSTEM.FOR EACH DEVICE IN THE SYSTEM.
INTERNALLY, SENSOR PARAMETERS ARE STORED IN DEVICE ORDER, SO IN THE SYSTEM DEFINED IN THE INTERNALLY, SENSOR PARAMETERS ARE STORED IN DEVICE ORDER, SO IN THE SYSTEM DEFINED IN THE INTERNALLY, SENSOR PARAMETERS ARE STORED IN DEVICE ORDER, SO IN THE SYSTEM DEFINED IN THE INTERNALLY, SENSOR PARAMETERS ARE STORED IN DEVICE ORDER, SO IN THE SYSTEM DEFINED IN THE
SCREEN ABOVE, THE SETTINGS FOR THE 70 SENSORS IN DEVICE 1 APPEARSCREEN ABOVE, THE SETTINGS FOR THE 70 SENSORS IN DEVICE 1 APPEARSCREEN ABOVE, THE SETTINGS FOR THE 70 SENSORS IN DEVICE 1 APPEARSCREEN ABOVE, THE SETTINGS FOR THE 70 SENSORS IN DEVICE 1 APPEAR IN THE REGISTER MAP, IN THE REGISTER MAP, IN THE REGISTER MAP, IN THE REGISTER MAP,
FOLLOWED BY THE SETTINGS FOR THE 70 SENSORS IN DEVICE 2. IN A CONVENTIONAL INTERLEAVED FOLLOWED BY THE SETTINGS FOR THE 70 SENSORS IN DEVICE 2. IN A CONVENTIONAL INTERLEAVED FOLLOWED BY THE SETTINGS FOR THE 70 SENSORS IN DEVICE 2. IN A CONVENTIONAL INTERLEAVED FOLLOWED BY THE SETTINGS FOR THE 70 SENSORS IN DEVICE 2. IN A CONVENTIONAL INTERLEAVED
PROFILER APPLICATION, THE INTERLEAVING IS ACHIEVED BY MAPPING SENSORS TO STAGES. SETTINGS PROFILER APPLICATION, THE INTERLEAVING IS ACHIEVED BY MAPPING SENSORS TO STAGES. SETTINGS PROFILER APPLICATION, THE INTERLEAVING IS ACHIEVED BY MAPPING SENSORS TO STAGES. SETTINGS PROFILER APPLICATION, THE INTERLEAVING IS ACHIEVED BY MAPPING SENSORS TO STAGES. SETTINGS
ASSOCIATED WITH STAGES ARE STORED IN ORDER INTERNALLY.ASSOCIATED WITH STAGES ARE STORED IN ORDER INTERNALLY.ASSOCIATED WITH STAGES ARE STORED IN ORDER INTERNALLY.ASSOCIATED WITH STAGES ARE STORED IN ORDER INTERNALLY.
To configure the parameters for each device, follow this process:
1. Set the DeviceDeviceDeviceDevice number
2. Set the Number of SensorsNumber of SensorsNumber of SensorsNumber of Sensors
3. Map the individual sensors to SSSStagestagestagestages by entering stage numbers in the column provided
4. Repeat for each device…
IMPORTANTIMPORTANTIMPORTANTIMPORTANT THE THE THE THE SENSOR ELEVATION AND AND AND AND ACTIVE LENGTH SETTINGS ARE NOT REQUIRED IN A CONVENTIONAL PROFILER SETTINGS ARE NOT REQUIRED IN A CONVENTIONAL PROFILER SETTINGS ARE NOT REQUIRED IN A CONVENTIONAL PROFILER SETTINGS ARE NOT REQUIRED IN A CONVENTIONAL PROFILER
APPLICATION AND SHOULD BE IGNORED. APPLICATION AND SHOULD BE IGNORED. APPLICATION AND SHOULD BE IGNORED. APPLICATION AND SHOULD BE IGNORED.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 45 of 117
In keeping with the Toolbox software configuration the boxes at the bottom of the screen can be used to automate the
data entry process on systems with simple sensor arrangements.
Figure Figure Figure Figure 40404040 –––– Calibrator: Sensor Arrangement Example Detector BCalibrator: Sensor Arrangement Example Detector BCalibrator: Sensor Arrangement Example Detector BCalibrator: Sensor Arrangement Example Detector B
The picture above shows the example stage mapping for device 2 in a typical interleaved application.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 46 of 117
6.3.1.13.2. Filtering Incoming Counts
The next sensor parameters to set are the slow and fast filter factors for each sensor. Click on the FilteringFilteringFilteringFiltering option
beneath Device Configuration.Device Configuration.Device Configuration.Device Configuration.
Figure Figure Figure Figure 41414141 –––– Calibrator: FilteringCalibrator: FilteringCalibrator: FilteringCalibrator: Filtering
Normally a system would have the same filter factor for all sensors in the system, however although this will be true for
the majority of applications it is possible to set individual filter factors for each sensor.
To configure dynamic filteringdynamic filteringdynamic filteringdynamic filtering for each device follow this process:
1. Set the Slow Filter FactorSlow Filter FactorSlow Filter FactorSlow Filter Factor(s)(s)(s)(s)
2. Set the Fast Filter FactorFast Filter FactorFast Filter FactorFast Filter Factor(s)(s)(s)(s)
3. Repeat for each device…
To configure fixed filteringfixed filteringfixed filteringfixed filtering for each device follow this process:
1. Set the Slow Filter FactorSlow Filter FactorSlow Filter FactorSlow Filter Factor(s)(s)(s)(s)
2. Repeat for each device…
The default value for the slow and fast filter factors are 30s for slow and 3 for fast.
In keeping with the Toolbox software configuration the boxes at the bottom of the screen can be used to automate the
data entry process on systems with simple sensor arrangements.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 47 of 117
6.3.1.13.3. Dead Time Settings
Click on the Dead TimeDead TimeDead TimeDead Time option beneath Device Configuration.Device Configuration.Device Configuration.Device Configuration.
Figure Figure Figure Figure 42424242 –––– Calibrator: Dead Time SettingsCalibrator: Dead Time SettingsCalibrator: Dead Time SettingsCalibrator: Dead Time Settings
Tube Type Dead Time Usage
ZP1200 90µs Conventional Profiler devices have sensors with dead time.
ZP1210 200uS Tank gauge devices with sensors have a dead time of dead time.
ZP1220 210uS Tank gauge devices with sensors have a dead time of dead time.
You must set a dead time for every sensor in every detector. In keeping with the Toolbox software configuration the
boxes at the bottom of the screen can be used to automate the data entry process.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 48 of 117
6.3.1.14. Stage Configuration
The stagestagestagestage configurationconfigurationconfigurationconfiguration section of the process allows the user to define the actual elevation of each stage. These are
the effective measurement points for each stage, and are used to calculate the contribution of each stage to the overall
phase elevations. These are measured from the same nominal reference point as used in setting the Measurement Measurement Measurement Measurement
RangeRangeRangeRange earlier in the configuration process.
Figure Figure Figure Figure 43434343 –––– FLOWCHART FOR STAGE CONFIGURATIONFLOWCHART FOR STAGE CONFIGURATIONFLOWCHART FOR STAGE CONFIGURATIONFLOWCHART FOR STAGE CONFIGURATION
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 49 of 117
6.3.1.14.1. Stage Elevations
Click on Stage ConfigurationStage ConfigurationStage ConfigurationStage Configuration, and then select the Stage ElevationStage ElevationStage ElevationStage Elevation option.
Figure Figure Figure Figure 44444444 –––– Calibrator: Defining Stage ElevationCalibrator: Defining Stage ElevationCalibrator: Defining Stage ElevationCalibrator: Defining Stage Elevation
These values are measured from the same nominal reference point as used in setting the Measurement RangeMeasurement RangeMeasurement RangeMeasurement Range in section
6.3.1.7. As these are stage parameters, the list is continuous and not split into devices. Use the boxes at the bottom of
the screen to automatically fill the table.
NOTE NOTE NOTE NOTE THE ELEVATION DECREASES WTHE ELEVATION DECREASES WTHE ELEVATION DECREASES WTHE ELEVATION DECREASES WITH INCREASING STAGE NUMBER, SO THE ITH INCREASING STAGE NUMBER, SO THE ITH INCREASING STAGE NUMBER, SO THE ITH INCREASING STAGE NUMBER, SO THE VALUE INCREMENT WILL NEED TO BE WILL NEED TO BE WILL NEED TO BE WILL NEED TO BE
NEGATIVE.NEGATIVE.NEGATIVE.NEGATIVE.
IN PREVIOUS IMPLEMENTATIONS OF THE PROFILER, THE GAP BETWEEN EACH STAGE WAS GIVEN A WEIGHTING IN PREVIOUS IMPLEMENTATIONS OF THE PROFILER, THE GAP BETWEEN EACH STAGE WAS GIVEN A WEIGHTING IN PREVIOUS IMPLEMENTATIONS OF THE PROFILER, THE GAP BETWEEN EACH STAGE WAS GIVEN A WEIGHTING IN PREVIOUS IMPLEMENTATIONS OF THE PROFILER, THE GAP BETWEEN EACH STAGE WAS GIVEN A WEIGHTING
FACTOR WHICH WAS A MULTIPLE OF THE SMALLEST GAP BETWEEN TWO STAGES. ELEVATIONS FACTOR WHICH WAS A MULTIPLE OF THE SMALLEST GAP BETWEEN TWO STAGES. ELEVATIONS FACTOR WHICH WAS A MULTIPLE OF THE SMALLEST GAP BETWEEN TWO STAGES. ELEVATIONS FACTOR WHICH WAS A MULTIPLE OF THE SMALLEST GAP BETWEEN TWO STAGES. ELEVATIONS CAN EASILY CAN EASILY CAN EASILY CAN EASILY
BE CALCULATED FROM THE MINIMUM GAP AND THE WEIGHTING FACTORS IN INSTALLATIONS REPLACING BE CALCULATED FROM THE MINIMUM GAP AND THE WEIGHTING FACTORS IN INSTALLATIONS REPLACING BE CALCULATED FROM THE MINIMUM GAP AND THE WEIGHTING FACTORS IN INSTALLATIONS REPLACING BE CALCULATED FROM THE MINIMUM GAP AND THE WEIGHTING FACTORS IN INSTALLATIONS REPLACING
LEGACY SYSTEMS.LEGACY SYSTEMS.LEGACY SYSTEMS.LEGACY SYSTEMS.
6.3.1.15. Save and Download Settings
At this stage it is important that we save the configuration file to a file storage device and then download the At this stage it is important that we save the configuration file to a file storage device and then download the At this stage it is important that we save the configuration file to a file storage device and then download the At this stage it is important that we save the configuration file to a file storage device and then download the
configuration to the T229. This is essential before we begin the calibration process as these settings affect the configuration to the T229. This is essential before we begin the calibration process as these settings affect the configuration to the T229. This is essential before we begin the calibration process as these settings affect the configuration to the T229. This is essential before we begin the calibration process as these settings affect the
way the T229 gathers count rates from the attached devices.way the T229 gathers count rates from the attached devices.way the T229 gathers count rates from the attached devices.way the T229 gathers count rates from the attached devices.
6.3.2. Calibration Procedure
At this point, the T229 has been configured for the detector devices connected to it, the number of sensors in the devices
and the communications parameters. Assuming the devices are connected to the T229, the M1 and / or M2 LEDs on the
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 50 of 117
front panel should be flashing green, indicating the T229 is communicating correctly with the attached devices. A red M1
or M2 LED indicates a communications or configuration problem which must be resolved before proceeding. It is unlikely
the Status LED will be green. This will be addressed later using the Alarm Status tool to reset any alarms.
Start
Define Reference Densities for
each sensor
Configure vessel and Accumulate
Background Counts while the
Profiler is Disarmed.
Yes
Save New Data? Retain existing countsNo
Configure vessel and accumulate
Empty Counts with the Profiler
armed, sources exposed and
vessel empty.
Save New Data? Retain existing countsNo
Yes
Configure vessel and accumulate
Full Counts with Profiler armed,
sources exposed and vessel full of
a known calibration liquid
Save New Data? Retain existing countsNo
Yes
Set the Calibration Date
Save the configuration file to a
local storage device
Figure Figure Figure Figure 45454545 –––– FLOWCHART FOR CALIBRATION PROCESSFLOWCHART FOR CALIBRATION PROCESSFLOWCHART FOR CALIBRATION PROCESSFLOWCHART FOR CALIBRATION PROCESS
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 51 of 117
6.3.2.1. Define Reference Densities
Click on Stage Configuration Stage Configuration Stage Configuration Stage Configuration and then choose the ReferenceReferenceReferenceReference DensitiesDensitiesDensitiesDensities option to enter values for empty and full at each
stage. Enter reference density values that reflect the vessel conditions applied during the calibration process. In a
conventional Profiler instrument, these values will be the same for all stages.
Figure Figure Figure Figure 46464646 –––– Calibrator: Calibrator: Calibrator: Calibrator: Defining Reference DensitiesDefining Reference DensitiesDefining Reference DensitiesDefining Reference Densities
Use the boxes at the bottom of the screen to automatically fill the table. In the example above the density of air has been
approximated to 1 Kg/m3 and water to 1000 Kg/m3.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 52 of 117
6.3.2.2. Accumulating Counts
Click on the Count Rate Gathering ToolCount Rate Gathering ToolCount Rate Gathering ToolCount Rate Gathering Tool option under the Calibration Counts Calibration Counts Calibration Counts Calibration Counts menu option.
The screen will list all devices and sensors defined in the system. By default, all sensors will be selected for use. Set the
Counting PeriodCounting PeriodCounting PeriodCounting Period to the required counting time. 2000 seconds is the default setting. The longer the extended counting
period is the better the calibration results are and subsequently the operation of the instrument is improved.
The calibration process consists of three simple steps:
1. Gathering Background CountsGathering Background CountsGathering Background CountsGathering Background Counts. This is carried out before the radioactive sources are loaded into the instrument
and accounts for other sources of radiation in the immediate vicinity. The vessel must be completely empty.
2. Gathering Empty CGathering Empty CGathering Empty CGathering Empty Countsountsountsounts. This is carried out after the radioactive sources have been loaded in to the
instrument. The vessel must be completely empty. The density of the substance in the vessel at this point must
match the value entered for Reference Empty in section 6.3.2.1.
3. Gathering Full CountsGathering Full CountsGathering Full CountsGathering Full Counts. This is carried out after the radioactive sources have been loaded in to the instrument.
The vessel must be completely full of a known liquid. The density of the substance in the vessel at this point
must match the value entered for Reference Empty in section 6.3.2.1.
Figure Figure Figure Figure 47474747 –––– Calibrator: Calibrator: Calibrator: Calibrator: Count Rate Gathering ToolCount Rate Gathering ToolCount Rate Gathering ToolCount Rate Gathering Tool
To gather data for one of the 3 required calibration sets follow this process:
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 53 of 117
1. Configure the vessel conditions as described earlier in section 6.3.2.2
2. Set the extended counting period making the value as large as possible for the best results.
3. Click on the StartStartStartStart button. The progress is shown graphically, together with an elapsed time indication.
4. When counting is complete select the appropriate data set from the drop down list as shown below. Be sure
that you have selected the correct one, once the ApplyApplyApplyApply button is clicked the process is irreversible.
5. When the correct data set has been selected click ApplyApplyApplyApply (It is greyed out while counting is in progress)
NOTE NOTE NOTE NOTE THE DATA HAS NOT YET BEEN WRITTEN TO THE T229THE DATA HAS NOT YET BEEN WRITTEN TO THE T229THE DATA HAS NOT YET BEEN WRITTEN TO THE T229THE DATA HAS NOT YET BEEN WRITTEN TO THE T229
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 54 of 117
Click on Calibration CountsCalibration CountsCalibration CountsCalibration Counts and select Count Rates Count Rates Count Rates Count Rates to view the current calibration counts. . . . As these are sensor
parameters, they are listed per device.
Figure Figure Figure Figure 48484848 –––– Calibrator: Count Rates (Calibrator: Count Rates (Calibrator: Count Rates (Calibrator: Count Rates (sample sample sample sample calibration data)calibration data)calibration data)calibration data)
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 55 of 117
6.3.2.3. Setting the Calibration Date
The last setting in the calibration is to set the calibration date. Click on the SourceSourceSourceSource option to configure this property.
Figure Figure Figure Figure 49494949 –––– Calibrator: Setting the Calibration DateCalibrator: Setting the Calibration DateCalibrator: Setting the Calibration DateCalibrator: Setting the Calibration Date
Click on the TodayTodayTodayToday button to set the calibration date to the host PC date. This date is used in the source decay calculation.
Although the isotope should already be configured (section 6.3.1.6), take this opportunity to verify the configuration.
6.3.2.4. Save and Download Settings
At this stage it is important that we save the configuration file to a file storage device. At this stage it is important that we save the configuration file to a file storage device. At this stage it is important that we save the configuration file to a file storage device. At this stage it is important that we save the configuration file to a file storage device. Creating a backup of the Creating a backup of the Creating a backup of the Creating a backup of the
configuration file is configuration file is configuration file is configuration file is simply good practicesimply good practicesimply good practicesimply good practice....
If required we can also download the calibration data to the T229 or we can wait until the alaIf required we can also download the calibration data to the T229 or we can wait until the alaIf required we can also download the calibration data to the T229 or we can wait until the alaIf required we can also download the calibration data to the T229 or we can wait until the alarm configuration is rm configuration is rm configuration is rm configuration is
complete. Refer to section complete. Refer to section complete. Refer to section complete. Refer to section 6.3.36.3.36.3.36.3.3 for details.for details.for details.for details.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 56 of 117
6.3.3. Configuring Alarms and Fault Reporting
The diagnostics built into the T229 and associated devices provide detailed status, warning and fault reporting registers.
These are combined into one overall warning register and one overall alarm register. Depending on the system design
and desired functionality, any of the bits in the alarm register can be programmed to generate a critical alarm in the critical
alarm register.
Most of the bits in the warning and alarm registers will automatically clear if the condition setting them is cleared, so an
additional set of warning and alarm registers are provided with bits that are required to be reset by the user.
Four bits in the alarm register are used to report stage failures. A stage can be deemed critical so that its failure is
reported in the alarm register. A stage can also be associated with up to 3 groups, where the failure is not reported until
a pre-set number of failures have occurred in the group.
Figure Figure Figure Figure 50505050 –––– FLOWCHART FOR DEFINING ALARM HANDLINGFLOWCHART FOR DEFINING ALARM HANDLINGFLOWCHART FOR DEFINING ALARM HANDLINGFLOWCHART FOR DEFINING ALARM HANDLING
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 57 of 117
6.3.3.1. Defining Stage Criticality
To set up the stage failure behaviour, click on Stage CriticalityStage CriticalityStage CriticalityStage Criticality.
Figure Figure Figure Figure 51515151 –––– Calibrator: Stage CriticalityCalibrator: Stage CriticalityCalibrator: Stage CriticalityCalibrator: Stage Criticality
If for example there are 6 stages in a region of interest, and you can tolerate only two stage failures, then assign these
stages to Group AGroup AGroup AGroup A (for example) and set the Stage failure tolerance (Group A)Stage failure tolerance (Group A)Stage failure tolerance (Group A)Stage failure tolerance (Group A) to 2. Stages can be assigned to more
than one group, or not assigned to any group as required. If a stage is important then it can be marked as CriticalCriticalCriticalCritical.
In a system with two interleaved probes or devices, it may be desirable from a redundancy point of view to allow a whole
device to fail without generating an alarm. This can be achieved using the Maximum GapMaximum GapMaximum GapMaximum Gap setting. Setting the Maximum Maximum Maximum Maximum
GapGapGapGap to 1 will result in the failure of a stage not being counted if the adjacent stages are still working. This has the effect
of only counting tube pair failures.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 58 of 117
6.3.3.2. Defining Alarm Criticality
To set whether an alarm register bit generates a critical alarm, click on Alarm CriticalityAlarm CriticalityAlarm CriticalityAlarm Criticality.
Figure Figure Figure Figure 52525252 –––– Calibrator: Alarm CriticalityCalibrator: Alarm CriticalityCalibrator: Alarm CriticalityCalibrator: Alarm Criticality
By default, all the alarm bits are set to Non CriticalNon CriticalNon CriticalNon Critical. These settings can be changed to suit the required system behaviour.
There is also a facility to clear the persistent warning and alarm registers automatically after a pre-set time (in seconds).
Click the Auto clear persistent alarmsAuto clear persistent alarmsAuto clear persistent alarmsAuto clear persistent alarms box if this functionality is required, and set the timer.
6.3.3.3. Save and Download Settings
At this stage it is important that we save the configuration file to a file storage device. At this stage it is important that we save the configuration file to a file storage device. At this stage it is important that we save the configuration file to a file storage device. At this stage it is important that we save the configuration file to a file storage device. Creating a backup of the Creating a backup of the Creating a backup of the Creating a backup of the
configuration file is configuration file is configuration file is configuration file is good practicegood practicegood practicegood practice....
If required we can also download the calibration dIf required we can also download the calibration dIf required we can also download the calibration dIf required we can also download the calibration data to the T229 or we can wait until the alarm configuration is ata to the T229 or we can wait until the alarm configuration is ata to the T229 or we can wait until the alarm configuration is ata to the T229 or we can wait until the alarm configuration is
complete. Refer to section complete. Refer to section complete. Refer to section complete. Refer to section 6.3.36.3.36.3.36.3.3 for details.for details.for details.for details.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 59 of 117
6.3.4. Defining I/O Parameters
6.3.4.1. Analogue Input Configuration
A single 4 to 20mA analogue input is provided, primarily for a pressure signal input, but it can be used for any purpose
determined by the application. The analogue input is presented as a scaled floating point value.
Figure Figure Figure Figure 53535353 –––– Calibrator: Analogue Input DialogCalibrator: Analogue Input DialogCalibrator: Analogue Input DialogCalibrator: Analogue Input Dialog
6.3.4.1.1. Time Constant (Seconds)
The function of the time constanttime constanttime constanttime constant is to filter the incoming analogue signal. To achieve this, we assign a value between 0
and 100s, 0000 being no filtering and 100100100100 maximum filtering.
6.3.4.1.2. ADC Settings
The ADC settings define the values within the T229 hardware that represent 4mA and 20mA and in rare circumstances
they can be adjusted to calibrate the input channel. The default value for 4mA is 11325 and for 20mA is 56626.
NOTE NOTE NOTE NOTE THE PARAMETERS THE PARAMETERS THE PARAMETERS THE PARAMETERS ADC setting for 4mA AND AND AND AND ADC setting for 20mA ARE ADVANCED FUNCTIONS AND SHOULD ONLY ARE ADVANCED FUNCTIONS AND SHOULD ONLY ARE ADVANCED FUNCTIONS AND SHOULD ONLY ARE ADVANCED FUNCTIONS AND SHOULD ONLY
BE ADJUSTED BY THOSE TRAINED TO DO SO.BE ADJUSTED BY THOSE TRAINED TO DO SO.BE ADJUSTED BY THOSE TRAINED TO DO SO.BE ADJUSTED BY THOSE TRAINED TO DO SO.
6.3.4.1.3. Scaled Engineering Units
These parameters allow us to configure an engineering range directly related to the input value which is already scaled
according to the ADC settings described in section 6.3.4.1.2.
For example, to scale the analogue input to engineering units of 0 to 10 bar we would set the Value Represented by Value Represented by Value Represented by Value Represented by
4mA4mA4mA4mA to 0 and the Value Represented by 20mAValue Represented by 20mAValue Represented by 20mAValue Represented by 20mA to 10.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 60 of 117
6.3.4.1.4. Status Word
Registers 61614 contain status information relating to the analogue input channel.
BitBitBitBit Switch output statusSwitch output statusSwitch output statusSwitch output status
0 1= raw analogue input saturated low (3.6 to 3.8mA)
1 1= raw analogue input saturated high (20.5 to 21.0mA)
2 1= raw analogue input failed low (less than 3.6mA)
3 1= raw analogue input failed high (greater than 21.0mA)
4 Reserved
5 Reserved
6 Reserved
7 Reserved
8 ADC initialisation failed (will not retry until after power cycle).
9 Reserved
A Reserved
B ADC communication failed (will auto retry each second).
C Reserved
D Reserved
E Reserved
F Reserved
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 61 of 117
6.3.4.2. Analogue Output Configuration
The T229-2 has a total of 5 analogue output channels, each one providing an active or passive 4-20mA output that can
be configured to represent any register within the controller including but not limited to level, density and status.
To configure a specific channel first of all, select the Analogue OutputsAnalogue OutputsAnalogue OutputsAnalogue Outputs from the menu on the left-hand side of the screen.
The configuration for output channel 1 will appear first. It is possible to select alternative channels using the Analogue Analogue Analogue Analogue
OutputOutputOutputOutput selector provided.
Figure Figure Figure Figure 54545454 –––– Calibrator: Example Analogue Output ConfigurationCalibrator: Example Analogue Output ConfigurationCalibrator: Example Analogue Output ConfigurationCalibrator: Example Analogue Output Configuration
For each analogue output channel, the following configuration options are available.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 62 of 117
6.3.4.2.1. Selecting Active / Passive Outputs
Each channel can be configured independently therefore it is possible to have a combination of active and passive circuits
on a single T229-2 controller. Refer to section 5.1.2 for polarity of terminals as they differ depending on whether active or
passive output has been selected.
Active Active Active Active T229T229T229T229----2 Circuit2 Circuit2 Circuit2 Circuit
When ActiveActiveActiveActive is selected the T229-2 will provide the power for the current loop, the device in the field must be passive.
Figure Figure Figure Figure 55555555 –––– Active T229Active T229Active T229Active T229----2 Analogue Output2 Analogue Output2 Analogue Output2 Analogue Output
PassivePassivePassivePassive T229T229T229T229----2 Circuit2 Circuit2 Circuit2 Circuit
When PassivePassivePassivePassive is selected the field device will provide power for the loop or power can be provided separately.
Figure Figure Figure Figure 56565656 –––– Passive T229Passive T229Passive T229Passive T229----2 Analogue Output2 Analogue Output2 Analogue Output2 Analogue Output
6.3.4.2.2. Configuring the Source Register
The source registersource registersource registersource register points to a floating point, U16 parameter within the T229 database that will be used as source data
for the analogue output channel.
6.3.4.2.3. Configuring Settings for 4mA and 20mA
The ADC settings define the values within the T229 hardware that represent 4mA and 20mA and in rare circumstances
they can be adjusted to calibrate the input channel. The default value for 4mA is 10923 and for 20mA is 54613.
NOTE NOTE NOTE NOTE THE PARAMETERS THE PARAMETERS THE PARAMETERS THE PARAMETERS Setting for 4mA AND AND AND AND Setting for 20mA ARE ADVANCED FUNCTIONS AND SHOULD ONLY BE ARE ADVANCED FUNCTIONS AND SHOULD ONLY BE ARE ADVANCED FUNCTIONS AND SHOULD ONLY BE ARE ADVANCED FUNCTIONS AND SHOULD ONLY BE
ADJUSTED BY THADJUSTED BY THADJUSTED BY THADJUSTED BY THOSE TRAINED TO DO SO.OSE TRAINED TO DO SO.OSE TRAINED TO DO SO.OSE TRAINED TO DO SO.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 63 of 117
6.3.4.2.4. Control Mode 0: Source Data is Floating Point
Control Mode 0 Control Mode 0 Control Mode 0 Control Mode 0 is used when the source registersource registersource registersource register (refer to section 11.1) is a floating point value.
Figure Figure Figure Figure 57575757 –––– Calibrator: Analogue Output Control Mode 0 DialogueCalibrator: Analogue Output Control Mode 0 DialogueCalibrator: Analogue Output Control Mode 0 DialogueCalibrator: Analogue Output Control Mode 0 Dialogue
Once the source registersource registersource registersource register (refer to section 11.1) has been configured it is necessary to define the upper and lower limits
that will allow the controller to represent it as a 4 and 20mA signal. We do this by configuring the Float Float Float Float VVVValue for 4mAalue for 4mAalue for 4mAalue for 4mA
and Float Value for 20mAFloat Value for 20mAFloat Value for 20mAFloat Value for 20mA parameters. Each value must be within the range of the source register and use the same
engineering units.
Example: if we use register 50001 as the source registersource registersource registersource register (refer to section 11.1) knowing that the range of the density
value within that register is between 0.0 and 10,000.0 kg/m3 then we can assign the Float Value for 4mAFloat Value for 4mAFloat Value for 4mAFloat Value for 4mA to be 0.0 and
the Float Value for 20mAFloat Value for 20mAFloat Value for 20mAFloat Value for 20mA to be 10,000.0, this is a typical configuration.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 64 of 117
6.3.4.2.5. Control Mode 1: Source Data is Unsigned 16-bit Integer
Control Mode Control Mode Control Mode Control Mode 1111 is used when the source registersource registersource registersource register (refer to section 11.1) is an unsigned 16-bit integer value.
Figure Figure Figure Figure 58585858 –––– Calibrator: Analogue Output Control Mode 1 DialogueCalibrator: Analogue Output Control Mode 1 DialogueCalibrator: Analogue Output Control Mode 1 DialogueCalibrator: Analogue Output Control Mode 1 Dialogue
Once the source registersource registersource registersource register (refer to section 11.1) has been configured it is necessary to define the upper and lower limits
that will allow the controller to represent it as a 4 and 20mA signal. We do this by configuring the U16U16U16U16 VVVValue for 4alue for 4alue for 4alue for 4mAmAmAmA
and U16U16U16U16 Value for 20mAValue for 20mAValue for 20mAValue for 20mA parameters. Each value must be within the range of the source register and use the same
engineering units.
Example: if we use register 57087 as source registersource registersource registersource register (refer to section 11.1) knowing that the range of the values within
that register are between 0 and 10,000 (%x100) then we can assign the U16U16U16U16 Value for 4mAValue for 4mAValue for 4mAValue for 4mA to be 0 (0%) and the U16U16U16U16
Value for 20mAValue for 20mAValue for 20mAValue for 20mA to be 10,000 (100%), this is a typical configuration.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 65 of 117
6.3.4.2.6. Control Mode 2: Two State Output, Source Data is a Bit
The Bit MaskBit MaskBit MaskBit Mask defines which bits need to be set in order to generate a change in the output state.
A typical application for this might be if we want to change the output signal depending upon the alarm status of the
instrument. Using 57110 as the source registersource registersource registersource register (refer to section 11.1) we can use the mask function to select bits.
Figure Figure Figure Figure 59595959 –––– Calibrator: Analogue Output Control Mode 2 DialogueCalibrator: Analogue Output Control Mode 2 DialogueCalibrator: Analogue Output Control Mode 2 DialogueCalibrator: Analogue Output Control Mode 2 Dialogue
Example: if we want to pick out the Critical stage failure (bit 0) and the New Stage Alarm from register 57110 then:
BitBitBitBit 0000 1111 2222 3333 4444 5555 6666 7777 8888 9999 AAAA BBBB CCCC DDDD EEEE FFFF DecimalDecimalDecimalDecimal HexHexHexHex
57110571105711057110 1 0 0 0 0 0 0 1 0 0 0 0 1 0 0 0 4225 1081h
MASKMASKMASKMASK 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0129 0081h
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 66 of 117
6.3.4.2.7. Control Mode 3: Two State Output, Float Comparison
The Float ComparatorFloat ComparatorFloat ComparatorFloat Comparator allows the user to define setsetsetset and clearclearclearclear values to which the source registersource registersource registersource register (refer to section 11.1),
a floating point value, will be compared to in order to generate a change in the output state.
Figure Figure Figure Figure 60606060 –––– Calibrator: Analogue Output Control Mode 3 DialogueCalibrator: Analogue Output Control Mode 3 DialogueCalibrator: Analogue Output Control Mode 3 DialogueCalibrator: Analogue Output Control Mode 3 Dialogue
Example: With the source registersource registersource registersource register (refer to section 11.1) set to 50001 (stage 1 density), the Float ComparatorFloat ComparatorFloat ComparatorFloat Comparator Set Value Set Value Set Value Set Value
set to 1000.0 kg/m3 and the Float ComparatorFloat ComparatorFloat ComparatorFloat Comparator Clear Value Clear Value Clear Value Clear Value set to 900.0 kg/m3. This means that as the density calculated
at stage 1 rises above 1000.0 kg/m3 then the analogue output signal will be equal to the Current for Comparator Current for Comparator Current for Comparator Current for Comparator
Returning 1Returning 1Returning 1Returning 1. In addition, when the calculated density for stage 1 falls below 900.0 kg/m3 the analogue output signal
will be equal to the Current foCurrent foCurrent foCurrent for Comparator Returning r Comparator Returning r Comparator Returning r Comparator Returning 0000. Note that the set value must be higher than the clear value.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 67 of 117
6.3.4.2.8. Control Mode 4: Two State Output, U16 Comparison
The U16 ComparatorU16 ComparatorU16 ComparatorU16 Comparator defines setsetsetset and clearclearclearclear values to which the source registersource registersource registersource register (refer to section 11.1), an unsigned 16-
bit integer value, will be compared to in order to generate a change in the output state.
Figure Figure Figure Figure 61616161 –––– Calibrator: Calibrator: Calibrator: Calibrator: Analogue Output Control Mode 4 DialogueAnalogue Output Control Mode 4 DialogueAnalogue Output Control Mode 4 DialogueAnalogue Output Control Mode 4 Dialogue
Example: With the source registersource registersource registersource register (refer to section 11.1) set to 58001 (stage 1 density), the Set Value Set Value Set Value Set Value u16u16u16u16 ComparatorComparatorComparatorComparator
set to 1000 kg/m3 and the Clear Value Clear Value Clear Value Clear Value u16u16u16u16 ComparatorComparatorComparatorComparator set to 900 kg/m3. This means that as the density calculated at
stage 1 rises above 1000 kg/m3 then the analogue output signal will be equal to the Current for Comparator Returning Current for Comparator Returning Current for Comparator Returning Current for Comparator Returning
1111. In addition, when the calculated density for stage 1 falls below 900.0 kg/m3 the analogue output signal will be equal
to the Current for Comparator Returning Current for Comparator Returning Current for Comparator Returning Current for Comparator Returning 0000. Note that the set value must be higher than the clear value.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 68 of 117
6.3.4.2.9. Primary Fault Indication Bit Mask
This function provides an overriding current output if the mask conditions are proved to be true. To configure the function,
select a Primary Fault Indication Primary Fault Indication Primary Fault Indication Primary Fault Indication Register PointerRegister PointerRegister PointerRegister Pointer (refer to section 11.1) which will normally refer to an alarm, status or
warning register.
Once a suitable register pointer has been assigned then it is necessary to select the appropriate bits that to create our
alarm condition. To do this we check the bits using the options given under Primary Fault Indication Bit Mask.Primary Fault Indication Bit Mask.Primary Fault Indication Bit Mask.Primary Fault Indication Bit Mask.
Finally, we must choose a Primary Fault CurrentPrimary Fault CurrentPrimary Fault CurrentPrimary Fault Current mA value in the range 0.0 to 24.0mA to apply to the analogue output
channel when the chosen fault(s) are active.
Unchecking all Fault Indication Bit MaskFault Indication Bit MaskFault Indication Bit MaskFault Indication Bit Mask disables this function.
Figure Figure Figure Figure 62626262 –––– Calibrator:Calibrator:Calibrator:Calibrator: Analogue Output Primary Fault Indication MaskAnalogue Output Primary Fault Indication MaskAnalogue Output Primary Fault Indication MaskAnalogue Output Primary Fault Indication Mask
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 69 of 117
6.3.4.2.10. Secondary Fault Indication Bit Mask
This function provides an overriding current output if the mask conditions are proved to be true. To configure the function,
select a SecondarySecondarySecondarySecondary Fault Indication Fault Indication Fault Indication Fault Indication Register PoRegister PoRegister PoRegister Pointerinterinterinter (refer to section 11.1) which will normally refer to an alarm, status
or warning register.
Once a suitable register pointer has been assigned then it is necessary to select the appropriate bits that to create our
alarm condition. To do this we check the bits using the options given under SecondarySecondarySecondarySecondary Fault Indication Bit Mask.Fault Indication Bit Mask.Fault Indication Bit Mask.Fault Indication Bit Mask.
Finally, we must choose a SecondarySecondarySecondarySecondary Fault CurrentFault CurrentFault CurrentFault Current mA value in the range 0.0 to 24.0mA to apply to the analogue output
channel when the chosen fault(s) are active.
Unchecking all Fault Indication Bit MaskFault Indication Bit MaskFault Indication Bit MaskFault Indication Bit Mask disables this function.
Figure Figure Figure Figure 63636363 –––– Calibrator: Analogue Output Secondary Fault Indication MaskCalibrator: Analogue Output Secondary Fault Indication MaskCalibrator: Analogue Output Secondary Fault Indication MaskCalibrator: Analogue Output Secondary Fault Indication Mask
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 70 of 117
6.3.4.2.11. Range Clipping
The 4 – 20mA signal can be Range ClippedRange ClippedRange ClippedRange Clipped during normal operation so that the output cannot exceed predefined limits.
The options available are:
• Low:Low:Low:Low: 3.8mA, 3.8mA, 3.8mA, 3.8mA, High:High:High:High: 20.5mA20.5mA20.5mA20.5mA
• Low:Low:Low:Low: 4.0mA, 4.0mA, 4.0mA, 4.0mA, High:High:High:High: 20.5mA20.5mA20.5mA20.5mA
• Low:Low:Low:Low: 3.8mA, 3.8mA, 3.8mA, 3.8mA, High:High:High:High: 20.0mA20.0mA20.0mA20.0mA
• Low:Low:Low:Low: 4.0mA, 4.0mA, 4.0mA, 4.0mA, High:High:High:High: 20.0mA20.0mA20.0mA20.0mA
• Use custom settingsUse custom settingsUse custom settingsUse custom settings
6.3.4.2.12. Slew Rate Limiting
Slew rate limiting can be used to provide additional smoothing of the output signal. Option 7, 1.2mA/s is the highest
degree of smoothing that can be applied. The options available are:
• 0 = 240mA/s, default maximum slew0 = 240mA/s, default maximum slew0 = 240mA/s, default maximum slew0 = 240mA/s, default maximum slew
• 1 = 100mA/s1 = 100mA/s1 = 100mA/s1 = 100mA/s
• 2 = 50mA/s2 = 50mA/s2 = 50mA/s2 = 50mA/s
• 3 = 20mA/s3 = 20mA/s3 = 20mA/s3 = 20mA/s
• 4 = 10mA/s4 = 10mA/s4 = 10mA/s4 = 10mA/s
• 5 = 5mA/s5 = 5mA/s5 = 5mA/s5 = 5mA/s
• 6 = 2mA/s6 = 2mA/s6 = 2mA/s6 = 2mA/s
• 7 = 1.2mA/s7 = 1.2mA/s7 = 1.2mA/s7 = 1.2mA/s
If the slewing is reconfigured whilst slewing is active, the new slew rate will take effect immediately.
6.3.4.2.13. Status Word
Registers 61136, 61236, 61336, 61436 and 61536 contain status information relating to the analogue output channels 1
through to 5 respectively.
BitBitBitBit Switch output statusSwitch output statusSwitch output statusSwitch output status
0 DAC 1 status bit 0 (1 = over temperature)
1 DAC 1 status bit 1 (1 = slewing active)
2 DAC 1 status bit 2 (1 = current fault)
3 1 = calibration active (output forced)
4 1 = output saturated (clipped low)
5 1 = output saturated (clipped high)
6 1 = Primary alarm active
7 1 = Secondary alarm active
8 1 = DAC initialisation failed
9 Reserved
A Reserved
B Reserved
C Reserved
D Reserved
E Reserved
F Reserved
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 71 of 117
6.3.4.3. Digital Output Configuration
NOTE NOTE NOTE NOTE THE DIGITAL OUTPUT FUNCTION CANNOT BE USED SIMULTANEOUSLY WITH THE ANALOGUE INPUT, THE THE DIGITAL OUTPUT FUNCTION CANNOT BE USED SIMULTANEOUSLY WITH THE ANALOGUE INPUT, THE THE DIGITAL OUTPUT FUNCTION CANNOT BE USED SIMULTANEOUSLY WITH THE ANALOGUE INPUT, THE THE DIGITAL OUTPUT FUNCTION CANNOT BE USED SIMULTANEOUSLY WITH THE ANALOGUE INPUT, THE
OPTIONS ARE MUTUALLY OPTIONS ARE MUTUALLY OPTIONS ARE MUTUALLY OPTIONS ARE MUTUALLY EXCLUSIVE.EXCLUSIVE.EXCLUSIVE.EXCLUSIVE. THEY SHARE A COMMON GROUND TERMINAL.THEY SHARE A COMMON GROUND TERMINAL.THEY SHARE A COMMON GROUND TERMINAL.THEY SHARE A COMMON GROUND TERMINAL.
To configure the digital output, it must first be enabled by selecting the Enable Digital OutputEnable Digital OutputEnable Digital OutputEnable Digital Output tick box
Once the feature has been enabled then a sourcesourcesourcesource registerregisterregisterregister (refer to section 11.1) needs to be defined. This is the data
for the switch operation and can be in the form of any float, U16 or bit field register within the T229.
Once the source registersource registersource registersource register has been defined, this will determine the TypeTypeTypeType Control ModeControl ModeControl ModeControl Mode to be used. The TypeTypeTypeType Control Control Control Control
ModeModeModeMode selector informs the T229 if the intention is to use a bit mask, unsigned 16-bit value or a floating point value to
determine the operation of the switch. Options are:
ContrContrContrControl Modesol Modesol Modesol Modes Description of ModeDescription of ModeDescription of ModeDescription of Mode
0 Switch open
1 Switch closed
2 Two state output, data source is a bit mask result
3 Two state output, float comparison
4 Two state output, U16 comparison
6.3.4.3.1. Control Mode 2: Two State Output with Bit Mask
Figure Figure Figure Figure 64646464 –––– Calibrator: Digital Output Configuration for Control Mode 2Calibrator: Digital Output Configuration for Control Mode 2Calibrator: Digital Output Configuration for Control Mode 2Calibrator: Digital Output Configuration for Control Mode 2
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 72 of 117
The Operating PolarityOperating PolarityOperating PolarityOperating Polarity determines if the result of the bit mask OPENS or CLOSES the digital output.
• Bit 0: 0 = a 1 from the bit mask opens the digital output.
• Bit 0: 1 = a 1 from the bit mask closes the digital output.
• Bits 1 to F are reserved.
The Bit MaskBit MaskBit MaskBit Mask defines which bits need to be set in order to generate a change in the output state.
A typical application for this might be if we want to change the output state depending upon the alarm status of the
instrument. We could use register 57110 as the source registersource registersource registersource register (refer to section 11.1) and then use the mask function
to select certain alarms.
Example 1: if we want to select the Critical stage failure (bit 0) from register 57110 then:
BitBitBitBit 0000 1111 2222 3333 4444 5555 6666 7777 8888 9999 AAAA BBBB CCCC DDDD EEEE FFFF DecimalDecimalDecimalDecimal HexHexHexHex
57110571105711057110 1 0 0 0 0 0 0 1 0 0 0 0 1 0 0 0 4225 1081h
MASKMASKMASKMASK 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0001 0001h
Example 2: if we want to pick out the Critical stage failure (bit 0) and the New Stage Alarm from register 57110 then:
BitBitBitBit 0000 1111 2222 3333 4444 5555 6666 7777 8888 9999 AAAA BBBB CCCC DDDD EEEE FFFF DecimalDecimalDecimalDecimal HexHexHexHex
57110571105711057110 1 0 0 0 0 0 0 1 0 0 0 0 1 0 0 0 4225 1081h
MASKMASKMASKMASK 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0129 0081h
6.3.4.3.2. Control Mode 3: Two State Output, Float Comparison
The Float ComparatorFloat ComparatorFloat ComparatorFloat Comparator defines setsetsetset and clearclearclearclear values to which the source registersource registersource registersource register, a floating point value, will be compared
to in order to generate a change in the output state.
Figure Figure Figure Figure 65656565 –––– Calibrator: Digital Output Configuration for Control Mode 3Calibrator: Digital Output Configuration for Control Mode 3Calibrator: Digital Output Configuration for Control Mode 3Calibrator: Digital Output Configuration for Control Mode 3
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 73 of 117
The Operating PolarityOperating PolarityOperating PolarityOperating Polarity determines if the result of the bit mask OPENS or CLOSES the digital output.
• Bit 0: 0 = a 1 from the comparator opens the digital output.
• Bit 0: 1 = a 1 from the comparator closes the digital output.
• Bits 1 to F are reserved.
The next stage in the configuration is to define SetSetSetSet and Clear value float comparatorsClear value float comparatorsClear value float comparatorsClear value float comparators. Note that these values should
be entered in the same units as the source registersource registersource registersource register (refer to section 11.1) and that the Set value must be higher than the
Clear value.
Example: With the source registersource registersource registersource register set to 50001 (stage 1 density), the Set Value Float ComparatorSet Value Float ComparatorSet Value Float ComparatorSet Value Float Comparator set to 1000.0 kg/m3
and the Clear Value Float ComparatorClear Value Float ComparatorClear Value Float ComparatorClear Value Float Comparator set to 900.0 kg/m3. This means that as the density calculated at stage 1 rises
above 1000.0 kg/m3 then the alarm will be set and the output will change state according to the selected polarity. In
addition, when the calculated density for stage 1 falls below 900.0 kg/m3 the output will again change state according to
the chosen polarity.
6.3.4.3.3. Control Mode 4: Two State Output, U16 Comparison
The U16 ComparatorU16 ComparatorU16 ComparatorU16 Comparator defines setsetsetset and clearclearclearclear values to which the source registersource registersource registersource register (refer to section 11.1), an unsigned 16-
bit integer value, will be compared to in order to generate a change in the output state.
Figure Figure Figure Figure 66666666 –––– Calibrator: Digital Output Configuration for Control Mode 4Calibrator: Digital Output Configuration for Control Mode 4Calibrator: Digital Output Configuration for Control Mode 4Calibrator: Digital Output Configuration for Control Mode 4
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 74 of 117
The Operating PolarityOperating PolarityOperating PolarityOperating Polarity determines if the result of the bit mask OPENS or CLOSES the digital output.
• Bit 0: 0 = a 1 from the comparator opens the digital output.
• Bit 0: 1 = a 1 from the comparator closes the digital output.
• Bits 1 to F are reserved.
The next stage in the configuration is to define SetSetSetSet and Clear value Clear value Clear value Clear value u16u16u16u16 comparatorscomparatorscomparatorscomparators. Note that these values should be
entered in the same units as the source registersource registersource registersource register (refer to section 11.1) and that the Set value must be higher than the
Clear value.
Example: With the source registersource registersource registersource register set to 58001 (stage 1 density), the Set Value Set Value Set Value Set Value u16u16u16u16 ComparatorComparatorComparatorComparator set to 1000 kg/m3 and
the Clear Value Clear Value Clear Value Clear Value u16u16u16u16 ComparatorComparatorComparatorComparator set to 900 kg/m3. This means that as the density calculated at stage 1 rises above
1000 kg/m3 then the alarm will be set and the output will change state according to the selected polarity. In addition,
when the calculated density for stage 1 falls below 900 kg/m3 the output will again change state according to the polarity.
6.3.4.3.4. Common Fault Indication
This function provides access to an overriding fault state that can turn off the digital output irrespective of the control
mode outputs if the specified conditions are found to be true.
To use the Fault Indication function, the Fault Indication RegisterFault Indication RegisterFault Indication RegisterFault Indication Register PointerPointerPointerPointer (refer to section 11.1) must be configured.
This may point to a T229 status or alarm word. The next step is to configure the Fault Indication Bit MaskFault Indication Bit MaskFault Indication Bit MaskFault Indication Bit Mask which allows
you to select specific bits / alarms within the Fault Indication Register.
Setting the Fault Indication Bit MaskFault Indication Bit MaskFault Indication Bit MaskFault Indication Bit Mask to 0 disables this function.
6.3.4.3.5. Status Word
Register 61062 contains status information relating to the digital output.
BitBitBitBit Switch output statusSwitch output statusSwitch output statusSwitch output status
0 Reserved
1 Reserved
2 Reserved
3 Reserved
4 Reserved
5 Reserved
6 1 = Primary alarm active
7 Reserved
8 Reserved
9 Reserved
A Reserved
B Reserved
C Comparator configuration invalid (Set value is less than clear value; will resume operation regardless)
D Source data configuration invalid (Register 61011 or 61061 points to register containing incorrect data value type)
E Reserved
F Reserved
6.3.4.3.6. Output State
Register 61063 contains status information relating to the digital output.
BitBitBitBit Output StateOutput StateOutput StateOutput State
0 Open
1 Close
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 75 of 117
6.3.5. Defining Modbus Output Mapping
All of the set-up and calibration registers, and the results of calculations can be read by the host system however they
are not usually in convenient consecutive locations (refer to section 11.1).
NOTE:NOTE:NOTE:NOTE: REGISTERS 501 TO 1000 ARE AVAILABLE FOR THE USER TO CREATE A CONTINUOUS LIST OF REGISTERS OF REGISTERS 501 TO 1000 ARE AVAILABLE FOR THE USER TO CREATE A CONTINUOUS LIST OF REGISTERS OF REGISTERS 501 TO 1000 ARE AVAILABLE FOR THE USER TO CREATE A CONTINUOUS LIST OF REGISTERS OF REGISTERS 501 TO 1000 ARE AVAILABLE FOR THE USER TO CREATE A CONTINUOUS LIST OF REGISTERS OF
INTEREST. THESE 500 REGISTERS APPEAR AS DUPLICATES OF THE REGISTERS POINTED TO BY A SETINTEREST. THESE 500 REGISTERS APPEAR AS DUPLICATES OF THE REGISTERS POINTED TO BY A SETINTEREST. THESE 500 REGISTERS APPEAR AS DUPLICATES OF THE REGISTERS POINTED TO BY A SETINTEREST. THESE 500 REGISTERS APPEAR AS DUPLICATES OF THE REGISTERS POINTED TO BY A SET OF 500 OF 500 OF 500 OF 500
POINTERS STORED IN REGISTERS 65001 TO 65500. POINTERS STORED IN REGISTERS 65001 TO 65500. POINTERS STORED IN REGISTERS 65001 TO 65500. POINTERS STORED IN REGISTERS 65001 TO 65500.
Click on Output MappingOutput MappingOutput MappingOutput Mapping to access the configuration.
Figure Figure Figure Figure 67676767 –––– Calibrator: Output MappingCalibrator: Output MappingCalibrator: Output MappingCalibrator: Output Mapping
Setting a pointer to a value between 501 and 1000 is not permitted as this can create circular references. The table above
shows stage corrected densities (registers start at 50000) mapped to registers 501 onwards.
NOTE:NOTE:NOTE:NOTE: WHEN MAPPING FLOATING POINT VALUES, MAP BOTH REGISTERS MAKING UP THE FLOATING POINT VALUE.WHEN MAPPING FLOATING POINT VALUES, MAP BOTH REGISTERS MAKING UP THE FLOATING POINT VALUE.WHEN MAPPING FLOATING POINT VALUES, MAP BOTH REGISTERS MAKING UP THE FLOATING POINT VALUE.WHEN MAPPING FLOATING POINT VALUES, MAP BOTH REGISTERS MAKING UP THE FLOATING POINT VALUE.
The T229 includes a facility to provide corrected density values, if a user is particularly interested in the true density value
for a particular stage. In some profiler configurations, there is a difference in how much radiation is absorbed between
oil and water. This difference is exagerated in the calculated the oil and water densities, so calibrating using water will
result in the reported oil density being slightly lower than the true value.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 76 of 117
6.3.6. Overview of the Command Tool
The base operating mode of the instrument can have 4 states, made up of a combination of 2 parameters. Write access
to the calibration parameters can be enabled or disabled, and compatibility mode can be enabled or disabled. Click on
the DevicesDevicesDevicesDevices option at any time to return to the main Toolbox screen.
Figure Figure Figure Figure 68686868 –––– Toolbox: Command ToolToolbox: Command ToolToolbox: Command ToolToolbox: Command Tool
NOTE:NOTE:NOTE:NOTE: WHEN THE SETWHEN THE SETWHEN THE SETWHEN THE SET----UP AND CALIBRATION PARAMETERS ARE WRITTEN TO THE T229 BY THE CALIBRATOR TOOL, UP AND CALIBRATION PARAMETERS ARE WRITTEN TO THE T229 BY THE CALIBRATOR TOOL, UP AND CALIBRATION PARAMETERS ARE WRITTEN TO THE T229 BY THE CALIBRATOR TOOL, UP AND CALIBRATION PARAMETERS ARE WRITTEN TO THE T229 BY THE CALIBRATOR TOOL,
THE BASE OPERATING MODE IS SAVED BEFORE THE REQUIRED COMMANDS AND KEYS ARE AUTOMATICALLY THE BASE OPERATING MODE IS SAVED BEFORE THE REQUIRED COMMANDS AND KEYS ARE AUTOMATICALLY THE BASE OPERATING MODE IS SAVED BEFORE THE REQUIRED COMMANDS AND KEYS ARE AUTOMATICALLY THE BASE OPERATING MODE IS SAVED BEFORE THE REQUIRED COMMANDS AND KEYS ARE AUTOMATICALLY
SENT TO SENT TO SENT TO SENT TO ENABLE THE SETENABLE THE SETENABLE THE SETENABLE THE SET----UP PARAMETERS TO BE CHANGED. AFTER THE SETTINGS HAVE BEEN CHANGED, UP PARAMETERS TO BE CHANGED. AFTER THE SETTINGS HAVE BEEN CHANGED, UP PARAMETERS TO BE CHANGED. AFTER THE SETTINGS HAVE BEEN CHANGED, UP PARAMETERS TO BE CHANGED. AFTER THE SETTINGS HAVE BEEN CHANGED,
THE ORIGINAL BASE OPERATING MODE IS RESTORED.THE ORIGINAL BASE OPERATING MODE IS RESTORED.THE ORIGINAL BASE OPERATING MODE IS RESTORED.THE ORIGINAL BASE OPERATING MODE IS RESTORED.
6.3.6.1. Reset to Factory Settings
The Perform Device ResetPerform Device ResetPerform Device ResetPerform Device Reset option is useful if alternative communication port settings are being used, as new port settings
are only acted upon on reset or power up. To carry out a reset run the CommandCommandCommandCommand tool from the main toolbox screen
and select the Perform Device ResetPerform Device ResetPerform Device ResetPerform Device Reset option from the drop down list.
After selecting a command from the drop down menu, click ExecuteExecuteExecuteExecute to complete the process.
6.3.6.2. Compatibility Mode
Compatibility mode is designed to provide compatibility with existing PLC based Density Profiler systems, by providing
an additional slave device, accessible by the host system. This provides duplicates of the output registers 00501 to
01000, but accessed from a separate slave address as registers 00001 to 00500.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 77 of 117
6.3.7. Dynamic Density Band Correction
Dynamic density band correction provides the user with the ability to calculate a single phase transition density setpoint
on the fly based on an average product density. This feature is aimed primarily for use in applications where the average
density of oil and water are likely to become very close. The configuration below uses the oil/emulsion interface as an
example.
Figure Figure Figure Figure 69696969 –––– Dynamic Density Band CorrectionDynamic Density Band CorrectionDynamic Density Band CorrectionDynamic Density Band Correction
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 78 of 117
6.3.7.1. Choosing a Density Band to Correct
The first step in configuring this feature is to select a Phase Transition DensityPhase Transition DensityPhase Transition DensityPhase Transition Density SetpointSetpointSetpointSetpoint to become dynamic, if we were
to make the oil / emulsion phase transition setpoint dynamic in a typical Profiler application the possible interfaces would
look like this:
PhasePhasePhasePhase Transition SetpointTransition SetpointTransition SetpointTransition Setpoint User SelectionUser SelectionUser SelectionUser Selection
1: Gas
Phase 1 to Phase 2 Transition Density Setpoint 0
2: Foam
Phase 2 to Phase 3 Transition Density Setpoint 1
3: Oil
Phase 3 to Phase 4 Transition Density Setpoint 2
4: Emulsion
Phase 4 to Phase 5 Transition Density Setpoint 3
5: Water
Phase 5 to Phase 6 Transition Density Setpoint 4
6: Sand
As can be seen from the table, it is the Phase 3 to Phase 4 Transition Density SetpointPhase 3 to Phase 4 Transition Density SetpointPhase 3 to Phase 4 Transition Density SetpointPhase 3 to Phase 4 Transition Density Setpoint that needs to be corrected to
affect the oil / emulsion interface. To correct the transition setpoint dynamically we must configure the T229 to calculate
an average oil density
6.3.7.2. Calculating an Average Reference Density
To determine the average density within a phase we must carefully select a fixed range of stages that will consistently be
within the desired phase, in this example, oil.
When considering this function, the heavier oil will naturally settle closer to the emulsion therefore it is stages at the
bottom end of the oil phase that we must use to determine the average density.
To achieve this, the first parameter we must configure is the firstfirstfirstfirst rrrreference eference eference eference sssstagetagetagetage, this defines the uppermost stage
guaranteed to be in the chosen reference band. The number of stages and exact location of the first reference stagefirst reference stagefirst reference stagefirst reference stage
will be project specific.
The second parameter is the number of reference stagesnumber of reference stagesnumber of reference stagesnumber of reference stages used to determine the average phase density and guarantee
that all referenced tubes are always within the same phase. Again this value will depend on the number of stages and
exact location of the first reference stage for a specific project.
The calculated average density will be restricted between the Low Clipping Limit of Average Reference DensityLow Clipping Limit of Average Reference DensityLow Clipping Limit of Average Reference DensityLow Clipping Limit of Average Reference Density and
the HighHighHighHigh ClClClClipping Limit of Average Reference Densityipping Limit of Average Reference Densityipping Limit of Average Reference Densityipping Limit of Average Reference Density. . . . Should the calculated average density exceed these limits it
will be clipped and a warning bit will be set in the Density Band Correction Status Density Band Correction Status Density Band Correction Status Density Band Correction Status WWWWordordordord defined in section 6.3.7.6. The
value selected for the Low Clipping Limit of Average Reference DensityLow Clipping Limit of Average Reference DensityLow Clipping Limit of Average Reference DensityLow Clipping Limit of Average Reference Density must not be less than the set-point configured
in section 6.3.1.11 for the phase transition density below after the set-point offset has been subtracted. Also the value
selected for the HighHighHighHigh Clipping Limit of Average Reference DensityClipping Limit of Average Reference DensityClipping Limit of Average Reference DensityClipping Limit of Average Reference Density must not be greater than the set-point configured
in section 6.3.1.11 for the phase transition density above after the set-point offset has been added.
6.3.7.3. Setpoint Offset
The offset is added to or subtracted from the calculated average reference densitycalculated average reference densitycalculated average reference densitycalculated average reference density to produce a calculated phase
transition density. This value will be project specific however a typical offset will be between 10 and 25kg/m3.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 79 of 117
6.3.7.4. Calculated Average Reference Density
Registers 57142 and 57143 (a floating point number, refer to section 11.1) contain the calculated average phase density
resulting from the configuration given in section 6.3.7.2.
6.3.7.5. Calculated Setting for Phase Transition Density
Registers 57144 and 57145 (a floating point number, refer to section 11.1) contain the current calculated phase transition
density setpoint.
6.3.7.6. Density Band Correction Status Word
Register 57146 contains status information relating to the density band correction function.
BitBitBitBit Switch output statusSwitch output statusSwitch output statusSwitch output status
0 1 = Invalid selection in enable register
1 1 = Invalid stage in band definition
2 1 = invalid phase transition and average reference density limit order
3 1 = Offset too large
4 Reserved
5 Reserved
6 Reserved
7 1= Stage deviation from average too large
8 1 = Average clipped at low limit
9 1 = Average clipped at high limit
A Reserved
B Reserved
C Reserved
D Reserved
E 1 = Configuration error
F 1 = Correction not operating
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 80 of 117
7.7.7.7. System StartSystem StartSystem StartSystem Start----UpUpUpUp
The T229 will inhibit normal operation until the instrument has been installed and commissioned. The following
procedures are intended to be followed by production operators during start-up and shutdown of the Profiler.
Prior to start-up check that the plant control system is not using the Profiler for control and the system is switched off.
Move the arming rod as shown in to the open position and switch the system on. Check that the indications coming back
from the system are representative of the vessel conditions. If the vessel is shown as full of sand then the arming rod is
not aligned, re-check that the arming rod is in the fully open position. When the system has stabilised and is
representative of the vessel conditions, switch the plant control system over to Profiler control.
Figure Figure Figure Figure 70707070 ---- Diagram Showing Profiler Dome and Arming RodDiagram Showing Profiler Dome and Arming RodDiagram Showing Profiler Dome and Arming RodDiagram Showing Profiler Dome and Arming Rod
The wire-operated Profiler is isolated and armed in a different manner to the standard profiler. This is detailed in the
project specific documentation.
NECKNECKNECKNECK
DOMEDOMEDOMEDOME
OPENOPENOPENOPEN
SHUTSHUTSHUTSHUT
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 81 of 117
8.8.8.8. MaintenanceMaintenanceMaintenanceMaintenance THE TRACERCO PROFILER IS AN INTRINSICALLY SAFE SYSTEM. AFTER ANY WORK ON THE SYSTEM, IT MUST BE LEFT IN THE TRACERCO PROFILER IS AN INTRINSICALLY SAFE SYSTEM. AFTER ANY WORK ON THE SYSTEM, IT MUST BE LEFT IN THE TRACERCO PROFILER IS AN INTRINSICALLY SAFE SYSTEM. AFTER ANY WORK ON THE SYSTEM, IT MUST BE LEFT IN THE TRACERCO PROFILER IS AN INTRINSICALLY SAFE SYSTEM. AFTER ANY WORK ON THE SYSTEM, IT MUST BE LEFT IN
THE EXACTLY THE SAME CONDITION AS ITTHE EXACTLY THE SAME CONDITION AS ITTHE EXACTLY THE SAME CONDITION AS ITTHE EXACTLY THE SAME CONDITION AS IT WAS WHEN COMMISSIONED.WAS WHEN COMMISSIONED.WAS WHEN COMMISSIONED.WAS WHEN COMMISSIONED. ALL WIRING ON THE HAZARDOUS SIDE MUST ALL WIRING ON THE HAZARDOUS SIDE MUST ALL WIRING ON THE HAZARDOUS SIDE MUST ALL WIRING ON THE HAZARDOUS SIDE MUST
CONFORM TO THE SYSTEM WIRING DIAGRAM CERTIFIED BY BASEEFA. THE CONSTRUCTION OF THE PROFILER AFTER CONFORM TO THE SYSTEM WIRING DIAGRAM CERTIFIED BY BASEEFA. THE CONSTRUCTION OF THE PROFILER AFTER CONFORM TO THE SYSTEM WIRING DIAGRAM CERTIFIED BY BASEEFA. THE CONSTRUCTION OF THE PROFILER AFTER CONFORM TO THE SYSTEM WIRING DIAGRAM CERTIFIED BY BASEEFA. THE CONSTRUCTION OF THE PROFILER AFTER
ANY REPAIR MUST ALWAYS CONFORM TO THE HAZARDOUS AREA CERTIFICATE FOR THE PRODUCT. ONLY QUALIFIANY REPAIR MUST ALWAYS CONFORM TO THE HAZARDOUS AREA CERTIFICATE FOR THE PRODUCT. ONLY QUALIFIANY REPAIR MUST ALWAYS CONFORM TO THE HAZARDOUS AREA CERTIFICATE FOR THE PRODUCT. ONLY QUALIFIANY REPAIR MUST ALWAYS CONFORM TO THE HAZARDOUS AREA CERTIFICATE FOR THE PRODUCT. ONLY QUALIFIED ED ED ED
PERSONNEL MUST CARRY OUT ANY REPAIR TO THE SYSTEM. WE ADVISE THAT TRACERCO SERVICES ENGINEERS PERSONNEL MUST CARRY OUT ANY REPAIR TO THE SYSTEM. WE ADVISE THAT TRACERCO SERVICES ENGINEERS PERSONNEL MUST CARRY OUT ANY REPAIR TO THE SYSTEM. WE ADVISE THAT TRACERCO SERVICES ENGINEERS PERSONNEL MUST CARRY OUT ANY REPAIR TO THE SYSTEM. WE ADVISE THAT TRACERCO SERVICES ENGINEERS
PERFORM ALL REPAIRS.PERFORM ALL REPAIRS.PERFORM ALL REPAIRS.PERFORM ALL REPAIRS.
8.1. Wiring Connections
Please refer to the project specific system hook-up diagram provided by Tracerco.
8.1.1. Connection in the Safe Area
Each signal processing unit has an independent intrinsically safe power supply fed via an isolator / repeater located in
the safe area. Only associated power supplies recommended by Tracerco must be used.
NOTE NOTE NOTE NOTE A SINGLE BARRIER / REPEATER MUST ONLY BE USED TOA SINGLE BARRIER / REPEATER MUST ONLY BE USED TOA SINGLE BARRIER / REPEATER MUST ONLY BE USED TOA SINGLE BARRIER / REPEATER MUST ONLY BE USED TO POWER A SINGLE SIGNAL PROCESSING UNIT.POWER A SINGLE SIGNAL PROCESSING UNIT.POWER A SINGLE SIGNAL PROCESSING UNIT.POWER A SINGLE SIGNAL PROCESSING UNIT.
For connection details, please refer to the project specific system hook-up diagram.
For cable details, please refer to the component specifications in section 10.2 of this document.
8.2. Intrinsic Safety Considerations
The introduction to this section emphasises the constraints placed on modifications/repairs to this intrinsically safe
system. If work on the system is unavoidable then the following points should be considered.
The electrical connection to the Tracerco ProfilerTM must conform to the “systems diagram for hazardous areas” drawing.
The practical route to conforming to the above is described in the system hook-up diagram. If connections need to be
made, then this drawing must be followed. The drawing also shows the screening method necessary for the system to
conform to the EEC directive on Electromagnetic Compatibility.
The Tracerco appointed manufacturer should only make repairs to the printed circuit board(s) of the Tracerco Profiler.
Any deviation from the production standard could invalidate its hazardous area certification. Even applying a soldering
iron to a joint can leave the board in a condition that invalidates the certificate.
Changing the signal processor PCB’s is possible provided it is a straight forward swap and the wiring diagrams are
followed. Any other PCB exchanges are not possible. For anything more than signal processor PCB exchange please
contact Tracerco services.
8.2.1. Safety/Handling Precautions
Precautions on vessel entry will involve the isolation of the sources. This is explained in the appended local rule under
sections Source Isolation, Labelling, Designated Areas, Failure of Source Isolation, Labelling, Designated Areas, Failure of Source Isolation, Labelling, Designated Areas, Failure of Source Isolation, Labelling, Designated Areas, Failure of Shutter to isolate the Arming Rod prior to Vessel Shutter to isolate the Arming Rod prior to Vessel Shutter to isolate the Arming Rod prior to Vessel Shutter to isolate the Arming Rod prior to Vessel
entry and Physical Damage (internal)entry and Physical Damage (internal)entry and Physical Damage (internal)entry and Physical Damage (internal)
Take care in the area of the dip pipes when working in the vessel as any damage may make removal of the source rod or
probes difficult.
For removal of the Arming Rod assembly refer to the section in the appended local rule under the heading Source Source Source Source
Security.Security.Security.Security. The assembly is heavy and may require a crane to ensure safe handling.
When removing the probes from the dip pipes take great care not to bend them. If they are inadequately supported they
bend easily under their own weight to the point where damage may occur. For this reason, we recommend securing the
probes to a suitable support (e.g. length of angle iron) which will facilitate safe handling.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 82 of 117
8.3. Replacing a T240 Processor Board
Note that this procedure only applies to removal of the signal processor board itself and does not cover all of the aspects of site safety, EHS, electrical isolation procedures and local rules which are applicable to safely gain access to the Profiler dome and associated wiring.
1111 Make the operations team aware that a detector is to be turned off – this will have a minor effect on the interface levels.
2222 Identify the serial number and instrument tag for the Profiler in question
3333 Determine if the detector to be repaired is A or B
4444 Go to the appropriate control panel in the safe area and identify the galvanic isolator providing power to the detector in question. There are instrument tags on the terminal group markers and adjacent to the galvanic isolators to speed up the process.
5555 Identify the I.S. terminals associated with the galvanic isolator and disconnect the knife connections.
6666 Verify at the field side of the terminals that there is no outgoing power supply.
7777 Check the label on the Profiler dome, making sure it has the correct serial / tag number and if correct, remove the dome to gain access to the signal processor boxes.
8888 Identify the signal processor box for the detector in question. Each box has a label on the front. Once you have identified the correct box then remove the lid.
9999 Perform a secondary check and verify that there is no power at the signal processor box on terminals 1 and 3 of the orange connector
10101010 Disconnect the orange connector from the signal processing box.
11111111 Disconnect the fibre patch cable paying special attention to colour coding of the cable in association with Rx and Tx on the signal processing board. Make a note of which colour patch cable connects to Rx to make sure we get it right when reconnecting.
12121212 Remove four board retaining screws.
13131313 Remove board from box and install new signal processing board, ensuring jumpers on the new board match the board being removed.
14141414 Reconnect the orange power connector.
15151515 Reconnect the fibre optic patch cable making sure we get the right connections.
16161616 Replace the lid on the signal processing box
17171717 Replace the dome.
18181818 Return to the control panel and connect the I.S. terminal knives to apply power the repaired detector.
19191919 Measure the DC voltage at the outgoing field terminals. If the detector is powered you will measure between 8.5VDC and 9VDC. If the detector is not powered then you will measure 16VDC in which case it will be necessary to verify that the field side wiring is correct.
8.4. Routine Maintenance/Inspection
Radioactive sources require a routine wipe test every 2-3 years depending on local legislation.
The installation requires a monthly inspection to confirm the presence of the sources, warning signs and source shutter
position indicators.
To maintain optimum performance Tracerco also advise a health check on every vessel shutdown.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 83 of 117
9.9.9.9. TroubleshootingTroubleshootingTroubleshootingTroubleshooting
#### FaultFaultFaultFault Indicated ByIndicated ByIndicated ByIndicated By ActionActionActionAction
1 System not powered Power LED not lit on
the T229 system.
1. Verify that the T229 connector block is fully inserted into the
correct slot.
2. Referencing the power distribution diagram check that the
circuit protection is healthy and is of the correct rating.
3. Measure the voltage on the outgoing side of the circuit
protection device. Acceptable readings are 24VDC ±10%
4. Check that the connections to the T229 are correct as shown
in section 5.1.
5. Measure the voltage at the T229 power input terminals.
Acceptable readings are 24VDC ±10%
2 PC not connecting
to the T229.
Connection Wizard
Error dialogue box is
displayed as shown
in Figure 14.
Host LED off or
Flashing Red
1. Check that the T229 is powered up (see 1)
2. Check that the wiring and termination details are correct as
shown in sections 5.1and 6.
3. Using device manager check that the serial port on the PC is
operating correctly, check that associated drivers installed
successfully.
4. Using device manager make a note of the COM port number.
Note that using the same USB to RS485 convertor in different
USB ports will in many cases generate new COM port
numbers.
5. Check that no other applications on the PC are using the
designated serial port, this can cause conflicts.
6. Check that the link for the termination resistor is in place as
shown in section 6.
3 T229 not connecting
to one or more
detectors.
Flashing red/green
or steady red LED
on ports M1 and/or
M2
1. Check that the wiring and termination details are correct as
shown in section 5.1 and on the project specific hook-up
drawing. Ensure that the termination link is in for each
Modbus port used.
2. Check the Modbus master communication settings within the
T229 have been configured to match those in the detector(s).
Read back the settings from the T229 using the Calibrator tool
within Tracerco ToolBox. Refer to section 6.3.1.5 for details.
3. Check that the detector(s) are powered up. If not powered use
the project specific power distribution diagram and work
through from the circuit protection device to the field device
checking for the desired voltages at each stage.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 84 of 117
#### FaultFaultFaultFault Indicated ByIndicated ByIndicated ByIndicated By ActionActionActionAction
4 T229 not connecting
to the DCS
Flashing red Host
LED.
1. Check that the wiring and termination details are correct as
shown in section 5.1 and on the project specific hook-up
drawing. Ensure that the termination link is in for each
Modbus port used.
2. Check the Modbus slave communication settings within the
T229 have been configured to match those at the DCS. Read
back the settings from the T229 using the Calibrator tool within
Tracerco ToolBox. Refer to section 6.3.1.5 for details.
3. Check that the detector(s) are powered up. If not powered use
the project specific power distribution diagram and work
through from the circuit protection device to the field device
checking for the desired voltages at each stage.
4. Ensure that the DCS is using Modbus RTU and not ASCII
5 Failure of an entire
detector array *
Detector x Comms
Failed Alarm.
1. Check the fibre Modbus connections at the panel, patch box
and Profiler field instrument.
2. Check the copper Modbus connections at the panel T241
Fibre Converter and at the T229 Modbus Module.
3. Check the voltage on the I.S. side of the galvanic isolator. 9-
10VDC is expected. If 16-18VDC is measured then the
connection to the signal processor board is open circuit or
reverse polarity.
4. Check that the connections to the T229 are correct as shown
in section 5.1.
5. Possible signal processor board failure – replace with a spare.
6 Failure of a number
of sensors
Stage or Sensor
Failure Registers
1. Possible HT failure on signal processor board - replace board
with a spare.
7 Failure of a single
sensor
Sensor Failure
Registers
1. Geiger failure. Arrange with Tracerco to replace at the next
shutdown period. Once reset the New Tube Alarm will clear
down but the Tube Alarm will remain.
8 Failure of a
measurement stage
Stage Failure
Registers
1. Possible HT failure on signal processor board - replace board
with a spare.
9 Suspect density
readings.
Unexpectedly high
densities throughout
various phases
Sand indication
when not expected.
1. Check to make sure the shutter mechanism on the Profiler
field instrument is fully opened.
2. Possible process anomaly possibly occurring when a
customer begins using a new well.
Contact Tracerco for assistance.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 85 of 117
10.10.10.10. Appendix A: T240 Profiler VariantAppendix A: T240 Profiler VariantAppendix A: T240 Profiler VariantAppendix A: T240 Profiler Variant
A Galvanic Isolator, normally fitted in the main panel, powers each detector probe with 10VDC. Communication between
the probe and the T229 is achieved using Modbus protocol. Communications in the field is over a fibre optic cable. The
Fibre optic signal is converted to an electrical signal in the main panel using a Fibre optic modem.
10.1. Installation
10.1.1. Electrical Supply
Each probe within the Tracerco ProfilerTM has its own independent intrinsically safe power supply. Each supply is a
Pepperl + Fuchs Isolating Power Supply unit mounted in a safe area. These units typically supply 100mA at 10VDC. One
or two probes may be fitted in each profiler depending on the application and range required.
The supply requires a two core screened cable with an outer armour, and 500VAC or 750VDC isolation between cores
and armour.
• The armour at the safe area is to be insulated (not connected to ground).
• The armour at the Profiler will be connected to the neck plate and terminated there so that any RF is not radiated
into the dome.
The inner insulation of the cable carries through the neck plate into the signal processor box via a feed-through gland. It
is necessary to bare about 15mm of the cable screen to allow the shielding to make contact
NOTE NOTE NOTE NOTE ENOUGH CABLE MUST BE PRESENT ENOUGH CABLE MUST BE PRESENT ENOUGH CABLE MUST BE PRESENT ENOUGH CABLE MUST BE PRESENT BETWEEN THE TWO GLANDS TO ALLOW THE SIGNAL PROCESSORS TO BETWEEN THE TWO GLANDS TO ALLOW THE SIGNAL PROCESSORS TO BETWEEN THE TWO GLANDS TO ALLOW THE SIGNAL PROCESSORS TO BETWEEN THE TWO GLANDS TO ALLOW THE SIGNAL PROCESSORS TO
SWING AWAY FROM THE NECK SO ACCESS IS POSSIBLE TO THE PROBES AND SOURCE ASSEMBLYSWING AWAY FROM THE NECK SO ACCESS IS POSSIBLE TO THE PROBES AND SOURCE ASSEMBLYSWING AWAY FROM THE NECK SO ACCESS IS POSSIBLE TO THE PROBES AND SOURCE ASSEMBLYSWING AWAY FROM THE NECK SO ACCESS IS POSSIBLE TO THE PROBES AND SOURCE ASSEMBLY
The two-core cable carries on to the power-in connector. Before connection is made to this two-part connector, the
ferrite bead must be slipped in place (as shown on the hook up drawing) and insulated with amalgamating tape.
Strip the end of the cable for connection to the connector and sleeve the screening. Take the 0V and screen drain wire
(sleeved) to terminal 4 on the power-in connector. This terminal is not identified but is the most left terminal and is shown
clearly on the systems diagram. The +ve wire is connected to terminal 2 (second from the right)
The armoured cable must not be connected to the metalwork of the Profiler, and the armouring should not protrude
through the cable gland into the dome.
10.1.2. Communications Fibre
Data transmission between the field signal processing units (hazardous area) and fibre optic converters in the Tracerco
control panel (safe area) is achieved using multi-mode fibre optic cable supplied and installed by Tracerco or the client.
The optical cables are connected as shown in the hook-up diagram. ST-ST type fibre connectors are used on the signal
processing unit(s) and fibre optic converter(s).
Note: Tracerco recommend an 8-Core fibre optic cable, but could be any number of cores from 6-Core to 12-Core.
The final connection to the Profiler is generally made via a field mounted, fibre optic breakout box, mounted as close to
the Profiler dome as possible. This allows minimum disruption to the field cables as replaceable ST-ST patch leads are
used to make the final connection.
The optical breakout box splits the 8-core cable into four paired optical signals, two cores and two spare for each probe.
Connection within the breakout box can be achieved by splicing the cables or using a suitable adapter and connectors
(ST connectors are recommended). Only one adapter between each cable is to be used.
NOTE NOTE NOTE NOTE A TRANSMIT SIGNAL TX ON THE SIGNAL PROCESSOR BOARD IS CONNECTED TO THE RECEIVE SIGNAL RX ON A TRANSMIT SIGNAL TX ON THE SIGNAL PROCESSOR BOARD IS CONNECTED TO THE RECEIVE SIGNAL RX ON A TRANSMIT SIGNAL TX ON THE SIGNAL PROCESSOR BOARD IS CONNECTED TO THE RECEIVE SIGNAL RX ON A TRANSMIT SIGNAL TX ON THE SIGNAL PROCESSOR BOARD IS CONNECTED TO THE RECEIVE SIGNAL RX ON
THE FIBRE OPTIC CONVERTER, AND VICETHE FIBRE OPTIC CONVERTER, AND VICETHE FIBRE OPTIC CONVERTER, AND VICETHE FIBRE OPTIC CONVERTER, AND VICE----VERSA FOR RECEIVE RX. EACH CONNECTOR HAS A LABEL ON VERSA FOR RECEIVE RX. EACH CONNECTOR HAS A LABEL ON VERSA FOR RECEIVE RX. EACH CONNECTOR HAS A LABEL ON VERSA FOR RECEIVE RX. EACH CONNECTOR HAS A LABEL ON
DENOTING WHETHER IT IS RX OR TX.DENOTING WHETHER IT IS RX OR TX.DENOTING WHETHER IT IS RX OR TX.DENOTING WHETHER IT IS RX OR TX.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 86 of 117
10.2. Component Specifications
This section gives details of the main components of the Tracerco Profiler.
10.2.1. Performance Specifications
Below are the general specifications for the system:
PerformancePerformancePerformancePerformance ValueValueValueValue
Vertical Resolution 30mm one source to one detector. Up to 2% one source to two detectors
Density Range 0-3000kg/m3 (per point)
Density Accuracy ±10 kg/m3 (subject to update / filter factors)
No. of Measurement Points (per detector): Up to 75 points (low pressure range)
Update Interval 1 to 15 seconds (nominally 3s).
10.2.2. Dip Pipes
Dip pipes are designed, manufactured and tested in accordance with ASME VIII or PD 5500 as required by the client.
They are manufactured from Titanium grade 2. All materials in contact with process fluids comply with NACE standard
MR-0175:2000.
ComponentComponentComponentComponent ValueValueValueValue
Material Titanium grade 2 (NACE MR-0175:2000)
Design code ASME VIII or PD5500
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 87 of 117
10.2.3. Radioactive Sources
There are two variations of the T240. Americium and Caesium
ComponentComponentComponentComponent ValueValueValueValue
Type Americium–241 emitting 60 KeV gamma radiation.
Activity 1.11GBq (30 mCi) or 3.7 GBq (100mCi)
ComponentComponentComponentComponent ValueValueValueValue
Type Caesium-137 emitting 661.7 KeV gamma radiation.
Activity Between 37MBq (1 mCi) or 3.7 GBq (100mCi)
10.2.4. Detector Assembly
ComponentComponentComponentComponent ValueValueValueValue
Flexibility Profiler can be jointed for easy access into a vessel, where headroom is an issue
Detector Elements Geiger Muller Tubes
10.2.5. Maximum and Minimum Operating Temperatures
ComponentComponentComponentComponent ValueValueValueValue
Detector Probes (Standard) T240-A-1 -40 to +125˚C
Detector Probes (Water Cooled) -100 to +132˚C (+138˚C)
Detector Probes (Heated) T240-A-2 -40 to (+194˚C – Ambient)
Detector Probes (High temperature) T240-A-3 -20 to +60˚C
Control Units (All Variants) -20 to +50˚C
Additional Ranges Available on request.
10.2.6. Storage Temperature
ComponentComponentComponentComponent ValueValueValueValue
Minimum Storage Temperature -55˚C
10.2.7. IP Rating
ComponentComponentComponentComponent ValueValueValueValue
External Dome and Neck IP66
Fibre Optic Breakout Box IP66
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 88 of 117
10.2.8. Mechanical Dimensions
ComponentComponentComponentComponent ValueValueValueValue
Dome Size 340mm diameter x 436mm H
Neck Size 327mm diameter x 236mm H
Flange Size Vessel specific
10.2.9. Power Cable and Glands Specification
The recommended cable is a 2-core steel wire braided cable, with an inner screening foil that is insulated from the wire
braid. The insulation must have 500VAC or 750VDC isolation between cores and armour. The cable is zero halogen type
and flame retardant.
Note: This cable is supplied by the client.
The power cable requires a Ferrite Bead for EMC purposes. This component is supplied by Tracerco.
ComponentComponentComponentComponent ValueValueValueValue
Dome Gland (Not Supplied) IP68, Size of gland will vary with customer requirements.
Signal Processor Box Gland (Supplied) IP65, M16, cable OD Min = 7.5mm, Max = 10.5mm
10.2.10. Fibre Optic Cable Specification
The recommended cable is an armoured four core 65/125 Multimode fibre optic cable, suitable for petro-chemical
environments. The cable MUST be terminated with ST connectors for connections to the Tracerco Profiler and the
RS232/RS485 converter unit. A minimum of 8 cores is recommended.
The transmission distance from T229 to Profiler including breakout box is up to 1000m. Further distances are achievable
by the use of repeaters.
ComponentComponentComponentComponent ValueValueValueValue
Dome Gland (Not Supplied) IP68, Size of gland will vary with customer requirements.
Signal Processor Box ST to ST Coupler
10.2.11. Electrical Specifications - Supply Details
Galvanic Isolator:Galvanic Isolator:Galvanic Isolator:Galvanic Isolator: Pepperl+Fuchs KFD0-SD2-Ex1.10100
Isolator Voltage Input:Isolator Voltage Input:Isolator Voltage Input:Isolator Voltage Input: 20 – 35VDC (24VDC nominal)
Isolator Current Input:Isolator Current Input:Isolator Current Input:Isolator Current Input: 140mA @ 24VDC (per detector)
Nominal Detector Supply from IsolatorNominal Detector Supply from IsolatorNominal Detector Supply from IsolatorNominal Detector Supply from Isolator 100mA @ 10VDC
Barrier Dimensions:Barrier Dimensions:Barrier Dimensions:Barrier Dimensions: H 100mm x W 20mm x D 112mm
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 89 of 117
10.2.12. Standards and Accreditation (Approval Certificates)
89/336/EEC Electromagnetic Compatibility Directive, amended by 92/31/EEC & 93/68/EEC
2006/95/EC Low voltage directive
94/9/EC ATEX Directive (Equipment for Potentially Explosive Atmospheres)
FM Approved for Hazardous Location Electrical Equipment
FMc Approved for Hazardous Location Electrical Equipment (CSA)
NACE MR0175 Corrosion Resistant Alloys for Sulphide Service Introduction
Check the individual Approval Certificate or declaration of conformity for details.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 90 of 117
11.11.11.11. Appendix B: Appendix B: Appendix B: Appendix B: Register MapRegister MapRegister MapRegister Map
Most registers are readable and this is indicated in the Access column as RRRR. Some are marked WWWW to show they are
writable by the user when not in write protect mode. Access marked as WFWFWFWF indicates they are writable at the factory, via
password protected factory mode access. Access marked as WSWSWSWS indicates they are writable via password protected
set-up mode access. Access marked as WAWAWAWA indicates they are writable at any time regardless of the mode.
11.1. T229 Specific Details and settings
Register Register Register Register OffsetOffsetOffsetOffset
AccessAccessAccessAccess StoreStoreStoreStore TypeTypeTypeType RangeRangeRangeRange UnitsUnitsUnitsUnits Description Description Description Description
00001 R ROM U16 2292 Product Identifier (T229-2)
00002 R ROM U16 2511 Sub assembly number (SA251-1)
00003 R/WF Flash U16 Hardware version number
00004 R ROM U16 Firmware version number
00009 R RAM Bitfield See register description
Operating Mode. Default: 1
00011 R/W RTC U16 0 to 59 sec Time (Seconds 0 - 59)
00012 R/W RTC U16 0 to 59 min Time (Minutes 0 - 59)
00013 R/W RTC U16 0 to 23 hour Time (Hours 0 - 23)
00014 R/W RTC U16 1 to 31 day Date (Day 1 – 31)
00015 R/W RTC U16 1 to 12 month Date (Month 1 – 12)
00016 R/W RTC U16 1900 to 3000 year Date (Year 1900 – 3000)
00017 R/W FRAM U16 1 to 31 day Calibration date (Day 1 – 31)
00018 R/W FRAM U16 1 to 12 month Calibration date (Month 1 – 12)
00019 R/W FRAM U16 1900 to 3000 year Calibration date (Year 1900 – 3000)
00021 - - - - - Reserved
00022 00023
R/WF FRAM U32 - - Serial Number
00024 00033
R/W FRAM - - Tag
00034 R/WS Flash Bitfield - - Modbus master 1 port settings. Default: 0x4301.
00035 R/WS Flash Bitfield - - Modbus master 2 port settings. Default: 0x4301.
00036 R/WS Flash Bitfield - - Modbus slave port settings. Default: 0x4301.
00038 00039
R/WS Flash IP Any except 0.x.x.x or 127.x.x.x
- TCP/IP port 1 IP address. Default: 0xC0A800E5 (192.168.0.229).
00040 00041
R/WS Flash IP See register description
TCP/IP port 1 subnet mask. Default: 0xFFFF0000 (255.255.0.0).
00042 00043
R/WS Flash IP Any except 0.x.x.x or 127.x.x.x
TCP/IP port 1 default gateway IP address. Default: 0xC0A80001 (192.168.0.1).
00044 R/WS Flash U16 1 to 247 TCP/IP port 1 Modbus slave address. Default: 1.
00045 00046
R/WS Flash IP Any except 0.x.x.x or 127.x.x.x
- TCP/IP port 2 IP address. Default: 0xC0A80AE5 (192.168.10.229).
00047 00048
R/WS Flash IP See register description
TCP/IP port 2 subnet mask. Default: 0xFFFF0000 (255.255.0.0).
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 91 of 117
Register Register Register Register OffsetOffsetOffsetOffset
AccessAccessAccessAccess StoreStoreStoreStore TypeTypeTypeType RangeRangeRangeRange UnitsUnitsUnitsUnits Description Description Description Description
00049 00050
R/WS Flash IP Any except 0.x.x.x or 127.x.x.x
TCP/IP port 2 default gateway IP address. Default: 0xC0A80001 (192.168.0.1).
00051 R/WS Flash U16 1 to 247 TCP/IP port 2 Modbus slave address. Default: 1.
00061 R/WU RAM Bitfield See register description
Calibration count control. Default: 0.
00062 R/WU RAM U16 See register description
- Calibration count time remaining. Default: 0.
00063 R/WU RAM U16 100 - 5000 - Calibration count time. Default: 100.
00071 R/WS Flash U16 0 to 3 - Source type. Default: 0.
00072 00073
R/WS Flash Float 0.0 or greater - Source half-life in years. Default: 0.0 (disabled).
00081 R/WS Flash U16 0 to 2 - Filter type. Default: 0.
00082 00083
R/WS Flash Float 1.0 to 10.0 - Number of standard deviations. Default: 2.0.
00074 00075
R Flash Float 0.0 to 1.0 - Relative source strength. Default: 1.0.
00091 00092
R/WS FRAM Float - - Bottom of range elevation from a nominal point in metres
00093 00094
R/WS FRAM Float - - Top of range elevation from a nominal point in metres
00095 00130
- - - - - Reserved
00121 R/WS Flash U16 0 to 65535 - Engineering units code for length. Default: 45 (HART code for metres).
00122 R/WS Flash U16 0 to 65535 - Engineering units code for density. Default: 92 (HART code for kg/m3).
00123 R/WS Flash U16 0 to 65535 - Engineering units code for pressure. Default: 0.
00131 00132
R FRAM U32 - sec Total system run time
00133 00134
R RAM U32 - sec System Up time
00135 R FRAM U16 - - Power ups
00136 R FRAM U16 - - Warm starts
00137 05000
- - - - - Reserved
05001 06000
R/W FRAM Float 0 to 106 cps Calibration empty count rates for sensors 1-500.
06001 07000
R/W FRAM Float 0 to 106 cps Calibration full count rates for sensors 1-500.
07001 08000
R/W FRAM Float 0 to 106 cps Calibration background count rates for sensors 1-500.
08001 11000
- - - - - Reserved
11001 12000
R/W FRAM Float 0 to 106 cps Raw count rates for sensors 1-500.
28001 29000
R/W FRAM Float 0 to 106 cps Combined count rates for stages 1-500.
29001 32000
- - - - - Reserved
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 92 of 117
Register Register Register Register OffsetOffsetOffsetOffset
AccessAccessAccessAccess StoreStoreStoreStore TypeTypeTypeType RangeRangeRangeRange UnitsUnitsUnitsUnits Description Description Description Description
32001 33000
R/W FRAM Float 0 to 10 kg/m3 Calibration empty count rate reference densities for stages 1-500
33001 34000
R/W FRAM Float 0 to 10 kg/m3 Calibration full count rate reference densities for stages 1-500.
34001 48000
- - - - - Reserved
48001 49000
R RAM Float Any finite value
- Density equation k factors for stages 1 to 500.
49001 50000
R RAM Float - kg/m3 Uncorrected density values for stages 1-500.
50001 51000
R RAM Float - kg/m3 Corrected density values for stages 1-500.
57001 57002
R/W FRAM Float 0 to 10000 kg/m3 Low density limit for instrument
57003 57004
R/WA FRAM Float 0 to 10000 kg/m3 Phase 1-2 transition density
57005 57006
R/WA FRAM Float 0 to 10000 kg/m3 Phase 2-3 transition density
57007 57008
R/WA FRAM Float 0 to 10000 kg/m3 Phase 3-4 transition density
57009 57010
R/WA FRAM Float 0 to 10000 kg/m3 Phase 4-5 transition density
57011 57012
R/WA FRAM Float 0 to 10000 kg/m3 Phase 5-6 transition density
57013 57014
R/W FRAM Float 0 to 10000 kg/m3 High density limit for instrument
57015 57059
- - - - - Reserved
57060 57061
R RAM Float - metres Top of phase 1 elevation
57062 57063
R RAM Float - metres Phase 1-2 transition elevation
57064 57065
R RAM Float - metres Phase 2-3 transition elevation
57066 57067
R RAM Float - metres Phase 3-4 transition elevation
57068 57069
R RAM Float - metres Phase 4-5 transition elevation
57070 57071
R RAM Float - metres Phase 5-6 transition elevation
57072 57073
- - - - - Reserved
57074 57075
R RAM Float - metres Top of phase 1 elevation
57076 57077
R RAM Float - metres Slew rate limited phase 1-2 transition elevation
57078 57079
R RAM Float - metres Slew rate limited phase 2-3 transition elevation
57080 57081
R RAM Float - metres Slew rate limited phase 3-4 transition elevation
57082 57083
R RAM Float - metres Slew rate limited phase 4-5 transition elevation
57084 57085
R RAM Float - metres Slew rate limited phase 5-6 transition elevation
57086 R RAM U16 - % x100 % range phase 1 elevation
57087 R RAM U16 - % x100 % range phase 1-2 transition elevation
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 93 of 117
Register Register Register Register OffsetOffsetOffsetOffset
AccessAccessAccessAccess StoreStoreStoreStore TypeTypeTypeType RangeRangeRangeRange UnitsUnitsUnitsUnits Description Description Description Description
57088 R RAM U16 - % x100 % range phase 2-3 transition elevation
57089 R RAM U16 - % x100 % range phase 3-4 transition elevation
57090 R RAM U16 - % x100 % range phase 4-5 transition elevation
57091 R RAM U16 - % x100 % range phase 5-6 transition elevation
57092 57100
- - - - - Reserved
57101 R/W FRAM U16 1-500 - Stage failure tolerance (group A)
57102 R/W FRAM U16 1-500 - Stage failure tolerance (group B)
57103 R/W FRAM U16 1-500 - Stage failure tolerance (group C)
57104 R RAM U16 0 to 500 - Stage failures in group A
57105 R RAM U16 0 to 500 - Stage failures in group B
57106 R RAM U16 0 to 500 - Stage failures in group C
57107 R RAM U16 0 to 500 - Total stage failures
57108 R RAM U16 0 to 500 - Total sensor failures
57109 R RAM - - - Status warnings register
57110 R RAM - - - STATUS ALARMS REGISTER
0 … … … … … 1 = Critical stage failure
1 … … … … … 1 = Group A permitted failures exceeded
2 … … … … … 1 = Group B permitted failures exceeded
3 … … … … … 1 = Group C permitted failures exceeded
4 … … … … … 1 = Stage alarm 0 count rate
5 … … … … … 1 = Stage alarm high count rate
6 … … … … … 1 = Stage alarm configuration error
7 … … … … … 1 = New stage alarm
8 … … … … … 1 = Sensor alarm 0 count rate
9 … … … … … 1 = Sensor alarm high count rate
A … … … … … 1 = Sensor alarm configuration error
B … … … … … 1 = New sensor alarm
C … … … … … 1 = Device communication error
D … … … … … 1 = Pressure signal failed
E … … … … … 1 = RTC error (bit F of register 00020)
F … … … … … 1 = T229-2 internal error
57111 R/W FRAM - - - Alarm criticality
57112 R RAM - - - Critical alarm
57113 WA - - 1 - Reset new sensor / stage alarm flag
57114 R RAM U16 0 to 65535 - Timer tick, 16-bit counter incrementing every second
57115 R/W FRAM U16 0 to 600 sec Persistent status timer
57116 R/WA RAM U16 - - Persistent status warning register
57117 R/WA RAM U16 - - Persistent status alarms register
57118 R/WA RAM U16 - - Persistent critical alarm
57119 W RAM U16 - - Alarm reset / refresh
57120 - - - - - Reserved
57121 R RAM - - - Calibration in progress
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 94 of 117
Register Register Register Register OffsetOffsetOffsetOffset
AccessAccessAccessAccess StoreStoreStoreStore TypeTypeTypeType RangeRangeRangeRange UnitsUnitsUnitsUnits Description Description Description Description
57122 57130
R - - - - Reserved
57131 R/WS Flash - 0 to 10 - Enable Density Band Correction. Default: 0 (disabled).
57132 R/WS Flash U16 1 to 500 - First Reference Density Stage. Default: 1.
57133 R/WS Flash U16 1 to 500 - Number of reference stages. Default: 1.
57134 57135
R/WS Flash Float 0 or greater density Low clipping limit of average reference density. Default: 0.0
57136 57137
R/WS Flash Float 0 or greater density High clipping limit of average reference density. Default: 0.0
57138 57139
R/WS Flash Float 0 or greater density Permitted reference deviation from average reference density. Default: 0.0
57140 57141
R/WS Flash Float 0 or greater density Set point offset. Default: 0.0
57142 57143
R RAM Float 0 or greater density Calculated average reference density
57144 57145
R RAM Float 0 or greater density Calculated setting for selected phase transition density
57146 R RAM Bitfield See register description
- DENSITY BAND CORRECTION STATUS REGISTER
0 … … … … … 1 = Invalid selection in enable register
1 … … … … … 1 = Density band correction disabled (error)
2 … … … … … 1 = Invalid stage in band definition
3 … … … … … 1 = invalid phase transition & average reference density limit order
4 … … … … … 1 = Offset too large
5 … … … … … Reserved
6 … … … … … Reserved
7 … … … … … 1 = Reference density stages: None error-free (error)
8 … … … … … 0, Reserved
9 … … … … … 1= Stage deviation from average too large (warning)
A … … … … … 1 = Average clipped at low limit (warning)
B … … … … … 1 = Average clipped at high limit (warning)
C … … … … … 0, Reserved
D … … … … … 1 = Data warning
E … … … … … 1 = Configuration error
F … … … … … 1 = Correction not operating
57147 57148
R RAM Float 0 or greater density Low density limit for instrument (repeat of registers 57001 to 57002)
57149 57150
R RAM Float 0 or greater density Effective phase 1-2 transition density. This is a repeat of registers 57003 to 57004 unless correction is enabled and operating as per registers 57131 to 57146.
57151 57152
R RAM Float 0 or greater density Effective phase 2-3 transition density. This is a repeat of registers 57005 to 57006 unless correction is enabled and operating as per registers 57131 to 57146.
57153 57154
R RAM Float 0 or greater density Effective phase 3-4 transition density. This is a repeat of registers 57007 to 57008 unless correction is enabled and operating as per registers 57131 to 57146.
57155 57156
R RAM Float 0 or greater density Effective phase 4-5 transition density. This is a repeat of registers 57009 to 57010 unless correction is enabled and operating as per registers 57131 to 57146.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 95 of 117
Register Register Register Register OffsetOffsetOffsetOffset
AccessAccessAccessAccess StoreStoreStoreStore TypeTypeTypeType RangeRangeRangeRange UnitsUnitsUnitsUnits Description Description Description Description
57157 57158
R RAM Float 0 or greater density Effective phase 5-6 transition density. This is a repeat of registers 57011 to 57012 unless correction is enabled and operating as per registers 57131 to 57146.
57159 57160
R RAM Float 0 or greater density High density limit for instrument (repeat of registers 57013 to 57014)
57430 57461
R - - - - Sensor failure alarm bits for up to 500 sensors
57462 57493
R - - - - Stage failure alarm bits for up to 500 stages
57494 R RAM U16 0 to 65535 density Low density limit for instrument as an integer, clipped to range of U16.
57495 R/WU RAM U16 0 to 65535 density Phase 1-2 transition density as an integer, clipped to range of U16.
57496 R/WU RAM U16 0 to 65535 density Phase 2-3 transition density as an integer, clipped to range of U16.
57497 R/WU RAM U16 0 to 65535 density Phase 3-4 transition density as an integer, clipped to range of U16.
57498 R/WU RAM U16 0 to 65535 density Phase 4-5 transition density as an integer, clipped to range of U16.
57499 R/WU RAM U16 0 to 65535 density Phase 5-6 transition density as an integer, clipped to range of U16.
57500 R RAM U16 0 to 65535 density High density limit for instrument as an integer, clipped to range of U16.
57501 58000
R RAM U16 0 to 65535 cps Raw count rates for sensors 1-500 as an integer
58001 58500
R RAM U16 0 to 65535 cps combined count rates for stages 1-500 as an integer
58501 59000
R RAM U16 0 to 65535 kg/m3 Densities for stages 1-500 as an integer
61012 R/WS Flash U16 - -
Pointer for DAC 1 variable. This is the source data for the analogue output 1 and can be a float, U16 or bit field. How this is processed depends on the control mode set in register 61103. Other registers are used to scale the DAC variable to the 4 to 20mA range, and this is scaled by yet more register settings to generate the binary value for the DAC. For float source data registers, point to either the high-word or the low-word register. Default: 1.
61013 R/WS Flash U16 - - Pointer for DAC 2 variable. Default: 1.
61014 R/WS Flash U16 - - Pointer for DAC 3 variable. Default: 1.
61015 R/WS Flash U16 - - Pointer for DAC 4 variable. Default: 1.
61016 R/WS Flash U16 - - Pointer for DAC 5 variable. Default: 1.
61051 R/WS Flash U16 0 to 4 -
Switch output type control mode 0 = Switch open 1 = Switch closed. This can be overridden to the open state by an active fault as with other switch/analogue output modes. 2 = two state output, data source is a bit mask result 3 = two state output, float comparison 4 = two state output, U16 comparison Default: 0 (switch open).
61052 R/WS Flash Bitfield See register description
-
Switch output mode 2, 3 and 4 operating polarity bit 0: 0 = a logic 1 from the bit mask or comparator opens the switch, 1 = a logic 1 from the bit mask or comparator closes the switch. Bits 1 to F reserved. Default: 0.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 96 of 117
Register Register Register Register OffsetOffsetOffsetOffset
AccessAccessAccessAccess StoreStoreStoreStore TypeTypeTypeType RangeRangeRangeRange UnitsUnitsUnitsUnits Description Description Description Description
61053 R/WS Flash
Mode 2: Switch output bit mask. Result of logic 1 opens switch when 61052 bit 0 = 0. Result of logic 1 closes switch when 61052 bit 0 = 1. Default: 0.
61054 to 61055
R/WS Flash Float Any finite value
Mode 3: Switch output float comparator set value. Default: 0.0
61056 to 61057
R/WS Flash Float Any finite value
Mode 3: Switch output float comparator clear value. Default: 0.0
61058 R/WS Flash U16 Any value Mode 4: Switch output U16 comparator set value. Default: 0.0
61059 R/WS Flash U16 Any value Mode 4: Switch output U16 comparator clear value. Default: 0.0
61062 R RAM - - -
Switch output status bits 0-5: 0, reserved bit 6: 1 = Primary alarm active bits 7-B: 0, reserved bit C: Comparator configuration invalid (Set value is less than clear value; will resume operation regardless) bit D: Source data configuration invalid (Register 61011 or 61061 points to register containing incorrect data value type) bits E to F: 0, reserved
61063 R RAM - - - DIGITAL OUTPUT STATE 0: Switch is open 1: Switch is closed
61101 R/WS Flash U16 10923 ± 546 DAC 1 setting for 4mA. Default: 10923.
61102 R/WS Flash U16 54613 ±546 DAC 1 setting for 20mA. Default: 54613.
61103 R/WS Flash U16 0 to 4
Analogue output 1 type control mode 0 = data source is float 1 = data source is U16 2 = two state output, data source is bit 3 = two state output, float comparison 4 = two state output, U16 comparison Default: 0.
61104 R/WS RAM U16 0 to 2
Calibration analogue output override 0 = no override (default) 1 = set to 4mA (contents of 61101) 2 = set to 20mA (contents of 61102) Set to 0 on power up, reset or write protect.
61105 61106
R/WS Flash Float Any finite value
Mode 0: Analogue output 1 float value for 4mA. Default: 0.0
61107 61108
R/WS Flash Float Any finite value
Mode 0: Analogue output 1 float value for 20mA. Default: 0.0
61109 R/WS Flash U16 Any value Mode 1: Analogue output 1 U16 value for 4mA. Default: 0.
61110 R/WS Flash U16 Any value Mode 1: Analogue output 1 U16 value for 20mA. Default: 0.
61111 61112
R/WS Flash Float 2.0 to 22.0 (mA units)
Modes 2, 3 and 4: Analogue output 1 current (in mA) for bit mask or comparator returning 1. (Bit mask can be more than 1 bit, so an OR of them is used for output.) Default: 16 (mA).
61113 61114
R/WS Flash Float 2.0 to 22.0 (mA units)
Modes 2, 3 and 4: Analogue output 1 current (in mA) for bit mask or comparator returning 0. Default: 8 (mA).
61115 R/WS Flash Bitfield See register description
Mode 2: Analogue output 1 bit mask. Default: 0.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 97 of 117
Register Register Register Register OffsetOffsetOffsetOffset
AccessAccessAccessAccess StoreStoreStoreStore TypeTypeTypeType RangeRangeRangeRange UnitsUnitsUnitsUnits Description Description Description Description
61116 61117
R/WS Flash Float Any finite value
Mode 3: Analogue output 1 float comparator set value for applying hysteresis. This must not be less than the clear value in registers 61118 to 61119. Default: 0.0
61118 61119
R/WS Flash Float Any finite value
Mode 3: Analogue output 1 float comparator clear value for applying hysteresis. This must not be greater than the set value in registers 61116 to 61117. Default: 0.0
61120 R/WS Flash U16 Any finite value
Mode 4: Analogue output 1 U16 comparator set value for applying hysteresis. This must not be less than the clear value in register 61121. Default: 0.
61121 R/WS Flash U16 Any finite value
Mode 4: Analogue output 1 U16 comparator clear value for applying hysteresis. This must not be greater than the set value in register 61120. Default: 0.
61122 R/WS Flash Bitfield See register description
Analogue output 1 range clipping bit 0: 0 = 3.8mA, 1 = 4mA (ignored if bit 2 is set to 1) bit 1: 0 = 20.5mA, 1 = 20mA (ignored if bit 2 is set to 1) bit 2: 1 = use settings in 61123 to 61126 bits 3 to F: 0, reserved This output range may be exceeded only by the fault 1 (primary) and fault 2 (secondary) output currents, when active, as configured in registers 61127 to 61128 and 61131 to 61132. Default: 0 (3.8mA and 20.5mA)
61123 61124
R/WS Flash Float 16.0 to 20.5 (mA units)
Analogue output 1 high range clipping (in mA). Default: 20.5 (mA).
61125 61126
R/WS Flash Float 3.8 to 8.0 (mA units)
Analogue output 1 low range clipping (in mA). Default: 3.8 (mA).
61127 61128
R/WS Flash Float 2.0 to 22.0 (mA units)
Analogue output 1 (primary) fault 1 current (in mA). Unlike the normal output, this is not clipped/saturated (see registers 61122 to 61126). Default: 22.0 (mA).
61129 R/WS Flash Bitfield See register description
Analogue output 1 bit mask for fault 1 indication. Set to 0 to disable fault 1 indication. Default: 0 (disabled).
61130 R/WS Flash U16 Valid Register Offset
Analogue output 1 fault 1 indication register pointer. Default: 1.
61131 61132
R/WS Flash Float 2.0 to 22.0 (mA units)
Analogue output 1 (secondary) fault 2 current (in mA). Unlike the normal output, this is not clipped/saturated (see registers 61122 to 61126). Secondary fault indication is ignored if primary indication is active. Default: 2.0 (mA).
61133 R/WS Flash Bitfield See register description
Analogue output 1 bit mask for fault 2 indication. Set to 0 to disable fault 2 indication. Default: 0 (disabled).
61134 R/WS Flash U16 Valid Register Offset
Analogue output 1 fault 2 indication register pointer. Default: 1.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 98 of 117
Register Register Register Register OffsetOffsetOffsetOffset
AccessAccessAccessAccess StoreStoreStoreStore TypeTypeTypeType RangeRangeRangeRange UnitsUnitsUnitsUnits Description Description Description Description
61135 R/WS Flash U16 0 to 7
Analogue output 1 slew rate limiting. This is performed by the DAC, by setting a clock and step value. 0 = (ck A, st 6) 240mA/s, default maximum slew 1 = (ck 5, st 1) 100mA/s 2 = (ck E, st 5) 50mA/s 3 = (ck C, st 3) 20mA/s 4 = (ck C, st 2) 10mA/s 5 = (ck C, st 1) 5mA/s 6 = (ck D, st 0) 2mA/s 7 = (ck F, st 0) 1.2mA/s Slewing is active during any of the selected modes (including two-state output modes), however is temporarily overridden to the default maximum slew (240mA/s when transitioning to/from either a calibration override (when register 61104 is not 0) or a fault state (primary or secondary alarm). The user-defined slew rate configured here is resumed once the override or fault state has ended, and the output has returned to the normal state. If the slewing is reconfigured whilst slewing is active, the new slew rate will take effect immediately, and will not affect the DAC set point. Default: 0 (240mA/s).
61136 R RAM U16
Analogue output 1 status bit 0: DAC 1 status bit 0 (1 = over temperature) bit 1: DAC 1 status bit 1 (1 = slewing active) bit 2: DAC 1 status bit 2 (1 = current fault) bit 3: 1 = calibration active, output forced bit 4: 1 = output saturated (clipped) low bit 5: 1 = output saturated (clipped) high bit 6: 1 = Primary alarm active bit 7: 1 = Secondary alarm active bit 8: 1 = DAC initialisation failed (DACs will remain inoperative until power cycled). bit 9: 1 = DAC configuration failed (DAC reconfiguration has failed and will auto-retry each second) bit A: 1 = DAC data verify failed (DAC data output failed and will auto-retry each second). The DAC data output is verified every 1 second before it is updated, though the check is more lenient when slewing is active. bit B: 1 = DAC communications failed (DAC communications via SPI has failed and two immediate retries also failed. Will continue to auto-retry each second) bit C: 1 = Comparator configuration invalid whilst mode 3 or 4 is active (Comparator set value is less than clear value; will resume operation regardless). bit D: 1 = Source data configuration invalid (Register 61012, 61130, or 61134 points to register containing incorrect data value type) bits E to F: 0, reserved The status flags will not be set if the analogue output is disabled in register 61001. Unless otherwise specified (as with the “comparator configuration invalid” flag), the status flags are not mutually exclusive, and will be set even if the mode is not active. For example, whilst the calibration override is active, the “source data configuration invalid” flag could be set, despite not being used at the time.
61201 R/WS Flash U16 0 to 65535 DAC 2 setting for 4mA
61202 R/WS Flash U16 0 to 65535 DAC 2 setting for 20mA
61203 61238
Repeat of output 1, but for output 2
61301 R/WS Flash U16 0 to 65535 DAC 3 setting for 4mA
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 99 of 117
Register Register Register Register OffsetOffsetOffsetOffset
AccessAccessAccessAccess StoreStoreStoreStore TypeTypeTypeType RangeRangeRangeRange UnitsUnitsUnitsUnits Description Description Description Description
61302 R/WS Flash U16 0 to 65535 DAC 3 setting for 20mA
61303 61338
Repeat of output 1, but for output 3
61401 R/WS Flash U16 0 to 65535 DAC 4 setting for 4mA
61402 R/WS Flash U16 0 to 65535 DAC 4 setting for 20mA
61403 61438
Repeat of output 1, but for output 4
61501 R/WS Flash U16 0 to 65535 DAC 5 setting for 4mA
61502 R/WS Flash U16 0 to 65535 DAC 5 setting for 20mA
61503 61538
Repeat of output 1, but for output 5
61614 R RAM - - -
Analogue input status bit 0: 1= raw analogue input saturated low (3.6 to 3.8mA) bit 1: 1= raw analogue input saturated high (20.5 to 21.0mA) bit 2: 1= raw analogue input failed low (less than 3.6mA) bit 3: 1= raw analogue input failed high (greater than 21.0mA) bits 4 to 7: 0, reserved. bit 8: ADC initialisation failed (will not retry until after power cycle). bits 9 to A: reserved bit B: ADC comms failed (will auto retry each second). bits C to F: 0, reserved When bits 0 or 1 are set and the input is enabled, bit C in register 57109, the status warning register should be set. When bits 2, 3, 8 or 9 are set and the input is enabled, bit D in register 57110, the status alarm register should be set.
61615 61616
R RAM Float 0.0 to 24.0 (mA units)
Analogue input current in mA (raw ADC reading scaled according to registers 61606 and 61607)
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 100 of 117
11.2. Register description
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
00001000010000100001 Product Product Product Product
identifier (T229)identifier (T229)identifier (T229)identifier (T229)
Fixed at 2292.
00002000020000200002 Sub assembly Sub assembly Sub assembly Sub assembly
number number number number
(SA251(SA251(SA251(SA251----1)1)1)1)
Fixed at 2511.
00003 00003 00003 00003 Hardware Hardware Hardware Hardware
version numberversion numberversion numberversion number
The high byte indicates major revisions, and is the same as the revision 1 indicated in SA251-1. The
low byte indicates minor revisions. The first release will be set to 0x0100. This register is a factory
setting and must be set up during factory configuration.
00004 00004 00004 00004 Firmware Firmware Firmware Firmware
version numberversion numberversion numberversion number
The high byte indicates major revisions; the low byte indicates minor revisions. The first release will
be set to 0x0100. This value is built in to the code and is read only.
00009000090000900009 Operating Operating Operating Operating
ModeModeModeMode Returns the current mode, as defined by the lower 8 bits set by validated commands written to register
00500, or the default mode if a firmware update has occurred after invoking the boot loader. The
upper 8 bits are reserved for alternative application use. At all times, exactly one of the bits 0 to 3 will
be set, indicating the base operating mode. This corresponds with the first 4 commands and is
persistent across reboots. Up to one of the next four temporary mode bits (4 to 7) can be set by the
next 4 commands. This is cleared on reset or when a base command is issued, or when a different
temporary mode command is issued.
BitBitBitBit DescriptionDescriptionDescriptionDescription OutputOutputOutputOutput
0000 1 = Normal operating mode, write protected
Valid (when bits 4 to 7 = 0)
1111 1 = Normal operating mode, write enabled Valid (when bits 4 to 7 = 0) depending on current settings
2222 1 = Compatibility operating mode, write protected
Valid (when bits 4 to 7 = 0)
3333 1 = Compatibility operating mode, write enabled
Valid (when bits 4 to 7 = 0) depending on current settings
4 4 4 4 1 = Enable editing of factory settings Unreliable, major change possible
5555 1 = Enable editing of the set-up registers Unreliable, major change possible
6666 1 = Enable calibration copy mode Unreliable, major change possible
7777 1 = Enable pass through mode Unreliable, pass through device may not provide timely data.
8 8 8 8 to 15to 15to 15to 15 0
00011 to 0001600011 to 0001600011 to 0001600011 to 00016 Current Time Current Time Current Time Current Time
and Dateand Dateand Dateand Date Reading these registers will report the time and date from the RTC chip. The RTC date is used with
the calibration date to provide a correction for source decay. Data written to these registers will be
copied to the RTC. Operation of the RTC is maintained in the event of a power interruption by a
backup capacitor, but only for about 4 days. To help spot RTC failures, when date data is written to
these registers, a backup copy of the date is recorded in Flash.
The backup date must be updated every time the date changes correctly, i.e. the serialised date
increments by 1, but only if there are no RTC errors reported in register 00020 or bit 4 of register
00020 is already set indicating the backup has already been used.
00017 to 00019 00017 to 00019 00017 to 00019 00017 to 00019 Calibration dateCalibration dateCalibration dateCalibration date This information is used with the current date to provide a correction for source decay.
00022 to 0002300022 to 0002300022 to 0002300022 to 00023 Serial NumberSerial NumberSerial NumberSerial Number This is a factory setting in the form PPPVYYSSSS, where PPP is the product 229, Vis the variant 2,
YY is the year of manufacture, and SSSS is the serial number.
00024 to 0003300024 to 0003300024 to 0003300024 to 00033 TagTagTagTag This is in the form of two ASCII characters per register. This is user settable, with the default register
settings 0x2020, i.e. two spaces.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 101 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
00034000340003400034 Modbus Master Modbus Master Modbus Master Modbus Master
Port 1 SettingsPort 1 SettingsPort 1 SettingsPort 1 Settings These are for the first Modbus master port, as defined in the following table:
Function Bit position F E D C B A 9 8 7 6 5 4 3 2 1 0 Baud 2400 X x x x 0 0 0 0 x x x x x x x x Baud 4800 X x x x 0 0 0 1 x x x x x x x x
Baud 9600 X x x x 0 0 1 0 x x x x x x x x Baud 19200 X x x x 0 0 1 1 x x x x x x x x Baud 28800 X x x x 0 1 0 0 x x x x x x x x Baud 38400 X x x x 0 1 0 1 x x x x x x x x Baud 57600 X x x x 0 1 1 0 x x x x x x x x Baud 76800 X x x x 0 1 1 1 x x x x x x x x Baud 115200 X x x x 1 0 0 0 x x x x x x x x Parity Even X x x 0 x x x x x x x x x x x x Parity Odd X x x 1 x x x x x x x x x x x x Parity disabled
X x
0 x x x
x x x x x x
x x x x
Parity enabled X x 1 x x x x x x x x x x x x x One stop bit x 0 x x x x x x x x x x x x x x Two stop bits x 1 0 x x x x x x x x x x x x x RTU mode 0 x x x x x x x x x x x x x x x Reserved 1 x x x x x x x x x x x x x x x
Changes to these settings are only acted upon following a reset.
Bit F is used to set ASCII mode in some Tracerco applications. ASCII mode is not implemented in
the T229-2.
The above table allows the user to select 1 stop bit and no parity, even though this is not supported
in the Modbus standard.
00035000350003500035 Modbus Master Modbus Master Modbus Master Modbus Master
Port 1 SettingsPort 1 SettingsPort 1 SettingsPort 1 Settings
These are for the second Modbus master port. See 00034.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 102 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
00036000360003600036 Modbus slave Modbus slave Modbus slave Modbus slave
port settingsport settingsport settingsport settings These are for the Modbus slave port, as defined in the following table:
Function Bit position F E D C B A 9 8 7 6 5 4 3 2 1 0 Address x x x x 0 0 x x 1 to 247 Baud 2400 x x x x 0 0 0 0 x x x x x x x x
Baud 4800 x x x x 0 0 0 1 x x x x x x x x Baud 9600 x x x x 0 0 1 0 x x x x x x x x Baud 19200 x x x x 0 0 1 1 x x x x x x x x Baud 28800 x x x x 0 1 0 0 x x x x x x x x Baud 38400 x x x x 0 1 0 1 x x x x x x x x Baud 57600 x x x x 0 1 1 0 x x x x x x x x Baud 76800 x x x x 0 1 1 1 x x x x x x x x Baud 115200 x x x x 1 0 0 0 x x x x x x x x Parity Even x x x 0 X x x x x x x x x x x x Parity Odd x x x 1 X x x x x x x x x x x x Parity disabled x x 0 x X x x x x x x x x x x x Parity enabled x x 1 x X x x x x x x x x x x x
One stop bit x 0 x x X x x x x x x x x x x x Two stop bits x 1 0 x X x x x x x x x x x x x RTU mode 0 x x x X x x x x x x x x x x x Reserved 1 x x x X x x x x x x x x x x x
Changes to these settings are only acted upon following a reset. In the event of the port settings
being unknown, on power up, the Modbus slave ports will listen for 1 second with the default settings.
If a valid Modbus message is received, writing 0xDEFC (default communication) to register 0001, the
port will continue to use the default setting and ignore the register setting.
Bit F is used to set ASCII mode in some applications. ASCII mode is not implemented in the T229-2.
Attempts to set an invalid address or bit F should return an invalid data 03 exception response.
The above table allows the user to select 1 stop bit and no parity, even though this is not supported
in the Modbus standard.
00038 to 0003900038 to 0003900038 to 0003900038 to 00039 TCP/IP port 1 TCP/IP port 1 TCP/IP port 1 TCP/IP port 1
IP AddressIP AddressIP AddressIP Address
This setting is used by Ethernet port 1.
00040 to 00040 to 00040 to 00040 to 00041000410004100041 TCP/IP port 1 TCP/IP port 1 TCP/IP port 1 TCP/IP port 1
Subnet MaskSubnet MaskSubnet MaskSubnet Mask
This setting is used by Ethernet port 1.
Valid value can be one of: 255.0.0.0, 255.x.0.0, 255.255.x.0, 255.255.255.y.
Where:
• x is one of: 0, 128, 192, 224, 240, 248, 252, 254, 255
• y is one of: 0, 128, 192, 224, 240
00042 to00042 to00042 to00042 to 00043000430004300043 TCP/IP port 1 TCP/IP port 1 TCP/IP port 1 TCP/IP port 1
Default gateway Default gateway Default gateway Default gateway
IP AddressIP AddressIP AddressIP Address
This setting is used by Ethernet port 1. If this is not on the same subnet as the port 1 IP address, then
the system will fall back to the default IP settings.
00044000440004400044 TCP/IP port 1 TCP/IP port 1 TCP/IP port 1 TCP/IP port 1
Modbus Slave Modbus Slave Modbus Slave Modbus Slave
AddressAddressAddressAddress
Also used for port 2. Attempts to set an address outside the 1 to 247 range should return an invalid
data 03 exception response.
00045 to 0004600045 to 0004600045 to 0004600045 to 00046 TCP/IP port 2 TCP/IP port 2 TCP/IP port 2 TCP/IP port 2
IP AddressIP AddressIP AddressIP Address
This setting is used by Ethernet port 2. If this is identical to the port 1 IP address in registers 38 to
39, then the ports are merged, and both use the settings for port 1
00047 to 0004800047 to 0004800047 to 0004800047 to 00048 TCP/IP port 2 TCP/IP port 2 TCP/IP port 2 TCP/IP port 2
Subnet MaskSubnet MaskSubnet MaskSubnet Mask This setting is used by Ethernet port 2 unless both ports have the same IP address configured.
See description for registers 00040 to 00041
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 103 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
00049 to 0005000049 to 0005000049 to 0005000049 to 00050 TCP/IP port 2 TCP/IP port 2 TCP/IP port 2 TCP/IP port 2
Default gateway Default gateway Default gateway Default gateway
IP AddressIP AddressIP AddressIP Address
This setting is used by Ethernet port 2 unless both ports have the same IP address configured. If this
is not on the same subnet as the port 2 IP address, then the system will fall back to the default IP
settings.
00000000000051515151 TCP/IP port 1 TCP/IP port 1 TCP/IP port 1 TCP/IP port 1
Modbus Slave Modbus Slave Modbus Slave Modbus Slave
AddressAddressAddressAddress
Attempts to set an address outside the 1 to 247 range should return an invalid data 03 exception
response. Not implemented.
00000000000061616161 Calibration Calibration Calibration Calibration
Count ControlCount ControlCount ControlCount Control This register controls and reports the status of the calibration count. Write zero to the register to
initiate a calibration count. Write 1 to the register to terminate the count. The status of the count is
reported as follows:
Bit Description 0 1 = count in progress 1 1 = count complete
2 1 = count time expired with errors 3 1 = count terminated on request
4 to F 0, Reserved
Bit 0 is set to show the gathering of a calibration count is in progress. This should take the time
specified in register 00062 or in register 00063, with an allowance for small differences in update
interval and the size of the update intervals of the attached devices. Bit 0 is cleared when all attached
devices have completed their count gathering, and Bit 1 is set. If a device reports errors, or there are
communications errors with a device and the calibration count cannot be completed in the time set
in 00062 or in 00063 plus 20 seconds, then Bit 1 and Bit 2 will be set. Writing 1 to terminate the count
will result in Bit 1 and Bit 3 being set.
00062000620006200062 Calibration Calibration Calibration Calibration
Count Time Count Time Count Time Count Time
RemainingRemainingRemainingRemaining
This register shows the minimum time in seconds, for the calibration count gathering. If the count
time is not divisible by the update interval of the attached devices, then the actual calibration count
will be nearest longer multiple of the update interval. Note that devices can have different update
intervals, so the actual count times may differ. The actual time taken is recorded with the calibration
count total so that the average rate can be calculated. The permitted write range of this register is
100 to 5000 seconds. When a count is in progress, this register will show the count time remaining.
Writes to this register while a count is in progress will be acted upon, and the count will either continue
or terminate depending on the value written. This setting is the same as the setting in register 00063.
00063000630006300063 Calibration Calibration Calibration Calibration
Count TimeCount TimeCount TimeCount Time
This register sets the minimum time in seconds, for the calibration count gathering. If the count time
is not divisible by the update interval of the attached devices, then the actual calibration count will be
nearest longer multiple of the update interval. Note that devices can have different update intervals,
so the actual count times may differ. The actual time taken is recorded with the calibration count total
so that the average rate can be calculated. The permitted range of this register is 100 to 5000
seconds. Writes to register 00062 will be duplicated in this register. (This is for compatibility with
older versions of T229 where register 00063 was reserved and the count time was set by 00062.)
Writes to this register while a count is in progress will be acted upon, and the count will either continue
or terminate depending on the value written.
00071000710007100071 Source TypeSource TypeSource TypeSource Type This register holds the source type. This information is used to determine the half-life of the radiation
source. Values of 0, 1 2 or 3 are permitted. When set to 0, the half-life is determined by registers
00072 and 00073. Set this register to 1 for 241Am, 2 for 137Cs and 3 for 60Co.
00072 to 0007300072 to 0007300072 to 0007300072 to 00073 Source halfSource halfSource halfSource half----lifelifelifelife These registers contain the half-life in years, to use when register 00071 is set to 0. Setting these
registers to zero and register 00071 to zero disables decay correction.
00074 to 00074 to 00074 to 00074 to 00075000750007500075 Relative Source Relative Source Relative Source Relative Source
StrengthStrengthStrengthStrength These registers contain the calculated source strength based on the half-life setting, the calibration
date and the current date. The value is within the range 0.0 to 1.0 where 1.0 represents 100% of the
calibrated source strength.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 104 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
00081000810008100081 Filter TypeFilter TypeFilter TypeFilter Type This register holds the filter type. This information is used to control how the count information from
the attached devices is filtered. Values of 0, 1 or 2 are permitted. When set to 0, the filtering is
disabled. Set this register to 1 for a conventional IIR filter with a fixed filter factor, 2 for a conventional
IIR filter with a dynamically chosen filter factor. The range of this register will be extended if new
filtering methods are adopted in the future. Note that setting individual sensor filter factors to 0 will
also disable filtering for that particular sensor regardless of the setting in this register. Setting the
individual sensor fast and slow response times to the same value when dynamic filtering is selected
will effectively change the filtering for that sensor to fixed.
00082 to 0008300082 to 0008300082 to 0008300082 to 00083 Number of Number of Number of Number of
Standard Standard Standard Standard
DeviationsDeviationsDeviationsDeviations
These registers contain the number of standard deviations used in the dynamic filtering switching
algorithm. This is normally 4 but can be adjusted to optimise performance.
00091 to 0009200091 to 0009200091 to 0009200091 to 00092 Bottom of Bottom of Bottom of Bottom of
range elevationrange elevationrange elevationrange elevation
This is the distance from the bottom of the measuring range to a nominal point, for example, the
bottom tan line of the vessel. This value must be the same as the elevation of the lowest stage (highest
numbered stage in use) for calculations to be valid, as configured in registers 47001 to 48000, i.e. the
elevation of the centre of the active sensitive length of the sensor(s) in the bottom stage. This value
must be less than the value in registers 00093 to 00094 otherwise bit F of register 57110 status alarms
will be set.
00093 to 0009400093 to 0009400093 to 0009400093 to 00094 Top of range Top of range Top of range Top of range
elevationelevationelevationelevation This is the distance from the top of the measuring range to a nominal point, for example, the bottom
tan line of the vessel. This value must be the same as the elevation of the physically highest stage
(stage 0) for calculations, as configured in registers 47001 to 47002, i.e. the elevation of the centre of
the active sensitive length of the sensor(s) in the top stage. This value must be greater than the value
in registers 00091 to 00092 otherwise bit F of register 57110 status alarms will be set.
00121001210012100121 Engineering Engineering Engineering Engineering
Units for lengthUnits for lengthUnits for lengthUnits for length This register records the engineering units used for length throughout the instrument, with the
exception of the Sensor Active Length settings in registers 40001 to 41000 Reserved, always in
millimetres.
The default value is 45, the HART code for metres. The customer may use an alternative unit, for
example feet, but must be consistent throughout all length settings. The units setting is not used
internally and is only recorded for the benefit of host systems.
00122001220012200122 Engineering Engineering Engineering Engineering
Units for Units for Units for Units for
DensityDensityDensityDensity
This register records the engineering units used for density throughout the instrument. The default
value is 92, the HART code for kg/m3. The customer may use an alternative unit, but must be
consistent throughout all density settings. The units setting is not used internally and is only recorded
for the benefit of host systems.
00123001230012300123 Engineering Engineering Engineering Engineering
Units foUnits foUnits foUnits for r r r
PressurePressurePressurePressure
This register records the engineering units used for pressure in the instrument when pressure
correction is being used. The default value is 0 as pressure correction is not normally used. The
customer may select a zero based pressure unit and must be consistent throughout all pressure
settings. The units setting is not used internally and is only recorded for the benefit of host systems.
00000000131131131131 to 00to 00to 00to 00131313132 2 2 2 Total run timeTotal run timeTotal run timeTotal run time. This is the total run time in seconds. Not necessarily logged with second precision but seconds are
convenient for reporting. This can only be reset by command.
00000000131313133 to 003 to 003 to 003 to 00131313134 4 4 4 Up timeUp timeUp timeUp time. This is the total up time in seconds since the last reset.
00000000131313135 5 5 5 Power upsPower upsPower upsPower ups This is the total number of power ups. This can only be reset by command.
00000000131313136 6 6 6 Warm startsWarm startsWarm startsWarm starts This is the total number of warm starts. This can only be reset by command.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 105 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
00501 to 01000 00501 to 01000 00501 to 01000 00501 to 01000 Output DataOutput DataOutput DataOutput Data These are mainly read only registers reserved for user definable output data. The contents of these
registers are defined by registers 65001 to 65500, used as pointers to any register in the T229.
Unused registers return 0. Writes are only permitted where an alarm reset or user configuration
register has been mapped to the output data space.
Information mapped to these locations can be read from corresponding registers 40501 to 41000.
05001 to 06000 05001 to 06000 05001 to 06000 05001 to 06000
Calibration Calibration Calibration Calibration
empty count empty count empty count empty count
rates for rates for rates for rates for
sensors 1sensors 1sensors 1sensors 1----500500500500
These are the raw observed empty count rates (C0) acquired during calibration at normal pressure.
Only registers up to the total number of sensors need to be used. The remainder should be left set
to zero.
06001 to 07000 06001 to 07000 06001 to 07000 06001 to 07000
Calibration full Calibration full Calibration full Calibration full
count rates for count rates for count rates for count rates for
sensors 1sensors 1sensors 1sensors 1----500500500500
These are the raw observed full count rates (Cx) acquired during calibration at normal pressure. Only
registers up to the total number of sensors need to be used. The remainder should be left set to zero.
07001 to 08000 07001 to 08000 07001 to 08000 07001 to 08000
Calibration Calibration Calibration Calibration
background background background background
count rates for count rates for count rates for count rates for
sensors 1sensors 1sensors 1sensors 1----500500500500
These are the raw observed background count rates (Cb) acquired during calibration at normal
pressure. Only registers up to the total number of sensors need to be used. The remainder should
be left set to zero.
11001 to 1200011001 to 1200011001 to 1200011001 to 12000 Sensor Raw Sensor Raw Sensor Raw Sensor Raw
Count ratesCount ratesCount ratesCount rates
These are the sensor counts divided by the update interval, in counts per second.
28001 to 2900028001 to 2900028001 to 2900028001 to 29000 Stage Stage Stage Stage
Combined Combined Combined Combined
Count rateCount rateCount rateCount rate
Each of these count rates are the sum of the processed count rates of all working sensors mapped
to each stage.
32001 to 3300032001 to 3300032001 to 3300032001 to 33000 Stage Stage Stage Stage
Calibration Calibration Calibration Calibration
Empty Count Empty Count Empty Count Empty Count
Rate Reference Rate Reference Rate Reference Rate Reference
DensityDensityDensityDensity
These are the reference densities (ρ0) during acquisition of the empty count rates at normal pressure.
In most instruments they will all have the same value. These settings have been implemented as
individual stage parameters for future applications.
33001 to 3400033001 to 3400033001 to 3400033001 to 34000 Stage Stage Stage Stage
Calibration Full Calibration Full Calibration Full Calibration Full
Count Rate Count Rate Count Rate Count Rate
Reference Reference Reference Reference
DensityDensityDensityDensity
These are the reference densities (ρx) during acquisition of the full count rates at normal pressure. In
most instruments they will all have the same value. These settings have been implemented as
individual stage parameters for future applications.
48001 to 4948001 to 4948001 to 4948001 to 49000000000000 Stage Density Stage Density Stage Density Stage Density
Calculation K Calculation K Calculation K Calculation K
FactorsFactorsFactorsFactors
These figures are used in the density calculation, and are calculated from the stage combined
corrected empty and full count rates, and the stage calibration reference densities recorded at
calibration time. This value has to be calculated for every update, as a tube in a stage may have
failed, affecting the empty and full count rates. These values are read only and not user adjustable.
� = �����−� �����
Where: ρf = Calibration full count rate reference density ρe = Calibration empty count rate reference density If = Stage combined corrected full count rate Ie = Stage combined corrected empty count rate
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 106 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
49001 to 5049001 to 5049001 to 5049001 to 50000 000 000 000
Stage Stage Stage Stage
uncoruncoruncoruncorrected rected rected rected
density values density values density values density values
for stages 1for stages 1for stages 1for stages 1----
500500500500
Uncorrected density values are calculated from the stage combined count rates, stage combined
empty count rates and the stage density calculation k factors. Stage densities ρ, in the same units as
the reference densities are calculated, using:
� = ��� � ����� � Where: ρe = Calibration empty count rate reference density I = Stage combined count rate Ie = Stage combined corrected empty count rate K = Stage density calculation k factor
If there is at least one working sensor in a stage, then the combined count rates will not include data
for any failed or failing sensors, and the density can be calculated as above. When there is only one
failing sensor (remaining) in a stage, then the density must be frozen at its last value, until the stage
either recovers or fails completely.
When a stage has failed, the density for that stage is interpolated from the nearest above and below
non-failed stages. If the failed stage is the top or bottom stage, then the next lower or next higher
stage density is used.
When an interpolated density is calculated, the value is in proportion to the distances between the
interpolation stage point and the higher and lower stage measurement points.
50001 to 51000 50001 to 51000 50001 to 51000 50001 to 51000
Corrected Corrected Corrected Corrected
density values density values density values density values
for stages 1for stages 1for stages 1for stages 1----
500500500500
Corrected density values are calculated using a linearization table. The normal use for this correction
is to adjust the density value for errors caused by the variation in mass absorption coefficient between
oil and water, particularly in americium based systems. Only registers up to the total number of stages
will be populated. The remainder will read zero.
57001 to 5700257001 to 5700257001 to 5700257001 to 57002 Low density Low density Low density Low density
limit for limit for limit for limit for
instrumentinstrumentinstrumentinstrument
This is the low density limit, normally set to 0 kg/m3. Calculated density values will be clipped at this
value. This is also a fixed end point in the linearization table. Co-ordinate values below this are not
permitted.
57003 to 57012 57003 to 57012 57003 to 57012 57003 to 57012
Phase transition Phase transition Phase transition Phase transition
densities.densities.densities.densities.
These are the densities marking the change from one phase to the next. These values may need to
be changed from time to time because the density of the oil (and other components in the produced
mixture) can vary. Changes are permitted even when the system is write protected. These floating
point values are reproduced in registers 57495 to 57499 for compatibility with older systems. Writes
to the 16 bit integer values in registers 57495 to 57499 are also copied to registers 57003 to 57012
as floats.
The phase transition densities must be in order, lowest first. Unused phases (after the highest density)
will be ignored if the transition density is set to zero.
57013 to 5701457013 to 5701457013 to 5701457013 to 57014 High density High density High density High density
limit for limit for limit for limit for
instrumentinstrumentinstrumentinstrument
This is the high density limit, normally set to 10000 kg/m3. Calculated density values will be clipped
at this value. This is also a fixed end point in the linearization table. Co-ordinate values above this
are not permitted.
57060 to 57071 57060 to 57071 57060 to 57071 57060 to 57071
Elevation of the Elevation of the Elevation of the Elevation of the
phase phase phase phase
transitions.transitions.transitions.transitions.
These 6 values are the calculated phase transition elevations. Phase 1, the gas phase will always
report the top of the measuring range.
57074 to 5708557074 to 5708557074 to 5708557074 to 57085 Slew rate Slew rate Slew rate Slew rate
Limited Limited Limited Limited
elevation of the elevation of the elevation of the elevation of the
phase phase phase phase
transitionstransitionstransitionstransitions
These 6 values are the slew rate limited calculated phase transition elevations. Phase 1, the gas
phase (registers 57074 to 57075) will always report the top of the measuring range and does not
change, so this value is simply a copy of registers 57060 to 57061.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 107 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
57086 to 57091 57086 to 57091 57086 to 57091 57086 to 57091
% range phase % range phase % range phase % range phase
elevation.elevation.elevation.elevation.
These 6 values are the slew rate limited calculated percent range phase transition elevations. Phase
1, the gas phase will always report 100%, scaled by a factor of 100 so 100% = 10000. These values
are the same as registers 57060 to 57071 when the slew rate in registers 57072 to 57073 is set to 0
57101571015710157101 Stage failures Stage failures Stage failures Stage failures
tolerancetolerancetolerancetolerance group group group group
AAAA
This register sets the total number of stage failures assigned to group A permitted before an alarm is
raised.
57102571025710257102 Stage failures Stage failures Stage failures Stage failures
tolerance group tolerance group tolerance group tolerance group
BBBB
This register sets the total number of stage failures assigned to group B permitted before an alarm is raised.
57105710571057103333
Stage failures Stage failures Stage failures Stage failures
tolerance group tolerance group tolerance group tolerance group
CCCC
This register sets the total number of stage failures assigned to group C permitted before an alarm is raised.
57104571045710457104 Stage failures in Stage failures in Stage failures in Stage failures in
group Agroup Agroup Agroup A
This register contains the total number of stages assigned to group A currently in the failed state.
57105571055710557105 Stage failures in Stage failures in Stage failures in Stage failures in
group Bgroup Bgroup Bgroup B
This register contains the total number of stages assigned to group B currently in the failed state.
57106 57106 57106 57106
Stage failures in Stage failures in Stage failures in Stage failures in
group Cgroup Cgroup Cgroup C
This register contains the total number of stages assigned to group C currently in the failed state.
57107 57107 57107 57107
Total stage Total stage Total stage Total stage
failuresfailuresfailuresfailures
This register contains the total number of stages in the instrument currently in the failed state.
57108 57108 57108 57108
Total sensor Total sensor Total sensor Total sensor
failuresfailuresfailuresfailures
This register contains the total number of sensors in the instrument currently in the failed state.
57109571095710957109 Status warning Status warning Status warning Status warning
registerregisterregisterregister
This register contains the overall warning status information for the instrument.
BitBitBitBit DeviceDeviceDeviceDevice
0 1 = Counting element malfunction
1 1 = Diagnostic count malfunction
2 1 = Device temperature out of range
3 1 = Device hardware malfunction
4 1 = Device software malfunction
5 1 = Sensor in stage 0 count rate
6 1 = Sensor in stage high count rate
7 1 = Sensor in stage configuration error
8 1 = Comms warning / sequence error
9 1 = Sensor failing
A 0, Reserved
B 0, Reserved
C 0, Reserved
D 0, Reserved
E 1 = Device internal watchdog timeout
F 1 = Device reset
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 108 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
57110571105711057110 Status alarm Status alarm Status alarm Status alarm
registerregisterregisterregister
This register contains the overall alarm status information for the instrument.
BitBitBitBit DeviceDeviceDeviceDevice
0 1 = Critical stage failure
1 1 = Group A permitted failures exceeded
2 1 = Group B permitted failures exceeded
3 1 = Group C permitted failures exceeded
4 1 = Stage alarm 0 count rate
5 1 = Stage alarm high count rate
6 1 = Stage alarm configuration error
7 1 = New stage alarm
8 1 = Sensor alarm 0 count rate
9 1 = Sensor alarm high count rate
A 1 = Sensor alarm configuration error
B 1 = New sensor alarm
C 1 = Device communication error
D 1 = Pressure signal failed
E 1 = RTC error
F 1 = T229 internal error
Bits 6 and A can be reset by the user to allow subsequent sensor or stage failures to be recognised.
All other bits will only be cleared when the alarm condition clears.
Bit F will be set either if the linearisation table is misconfigured or the top and bottom of range values
are not in the correct order.
57111 57111 57111 57111
Alarm Alarm Alarm Alarm criticalitycriticalitycriticalitycriticality This register allows the user to configure which alarms in register 57110 generate a critical alarm.
Setting a bit to 1 will result in a critical alarm if the corresponding bit in register 57110 is set in the
alarm state.
57112571125711257112 Critical Critical Critical Critical alarmalarmalarmalarm This register will be non-zero in the event of a critical alarm, indicating the output of the system cannot
be relied on. The bits set will depend on the settings of registers 57110 and 57111.
57113 57113 57113 57113
Reset new Reset new Reset new Reset new
sensor / stage sensor / stage sensor / stage sensor / stage
alarm flagalarm flagalarm flagalarm flag
This register is write only. Writing 1 to this register will reset the new sensor and new stage alarm
flags. Writing any other value will be ignored. The rest is a transient function and the value is not
retained. This register can still be written in write protect mode.
57114571145711457114 Output timer Output timer Output timer Output timer
ticktickticktick
This register contains a 16-bit counter incrementing every second, used to indicate to a host device
that the instrument is still operating.
57115 57115 57115 57115 Persistent Persistent Persistent Persistent
status timer status timer status timer status timer
This register contains controls how long it takes to clear an alarm or warning bit, even when the original
condition causing the alarm or warning in registers 57109, 57110 and 57112 has cleared. The setting
is in seconds. Setting the timer to zero turns the persistence timer function off, and persistent alarms
or warnings will remain until reset by command written to register 57119 or by a bit pattern written to
registers 57116, 57117 or 57118. Values in the range of 1 to 65535 will set the clear delay timer in
seconds for any persistent alarm or warning bit. Timers are provided for all defined bits in registers
57116 to 57118.
57116 57116 57116 57116
Persistent Persistent Persistent Persistent
status warning status warning status warning status warning
registerregisterregisterregister
This register is the persistent copy of register 57109 and contains the overall warning status
information for the instrument. Individual bits or combinations of bits can be reset by writing 1 to the
appropriate bit positions. This will only clear a warning if the original cause is no longer present.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 109 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
57117 57117 57117 57117
Persistent Persistent Persistent Persistent
status alarm status alarm status alarm status alarm
registerregisterregisterregister
This register is the persistent copy of register 57110 and contains the overall alarm status information
for the instrument. Individual bits or combinations of bits can be reset by writing 1 to the appropriate
bit positions. This will only clear an alarm if the original cause is no longer present. Resetting the new
stage alarm or new sensor alarm bits, (bits 7 or B) will cause the appropriate bits in the status alarm
register (57110) to be reset first, followed by the same bits in the persistent status alarm register
(57117).
57118 57118 57118 57118
PersiPersiPersiPersistent stent stent stent
critical alarmcritical alarmcritical alarmcritical alarm
This register is the persistent copy of register 57112 and will be non-zero in the event of a critical
alarm, indicating the output of the system cannot be relied on. The bit’s set will depend on the settings
of registers 57110 and 57111. Individual bits or combinations of bits can be reset by writing 1 to the
appropriate bit positions. This will only clear an alarm if the original cause is no longer present.
Resetting the new stage alarm or new sensor alarm bits, (bits 7 or B) will cause the appropriate bits
in the status alarm register (57110) to be reset first, followed by the same bits in the persistent critical
alarm register (57118).
57119 57119 57119 57119
Refresh Refresh Refresh Refresh
persistent persistent persistent persistent
status registers.status registers.status registers.status registers.
This register is write only. Writing 1 to this register will refresh registers 57116 to 57118, clearing any
bits that are no longer set in the source registers 57109, 57110 and 57112. Writing any other value
will be ignored. The rest is a transient function and the value is not retained. This register can still be
written in write protect mode.
57121571215712157121 Calibration in Calibration in Calibration in Calibration in
progress. progress. progress. progress.
Returns the current mode, as defined by the last key validated command (written to 00500), or the
default mode if the boot loader has been invoked, AND 0xFFFA. In other word, returns 0 if in normal
or compatibility read only modes. This register is used in the compatibility mode status as a substitute
for the calibration mode flag in the PLC systems.
57131571315713157131 Enable Density Enable Density Enable Density Enable Density
Band Band Band Band
CorrectionCorrectionCorrectionCorrection
This register controls the density band correction function. The usual function of this correction is to
monitor the average density of some of the stages known to be in oil, and use this to modify the phase
transition density between oil and emulsion. The current implementation supports modification of
either the higher phase transition density, in this case the oil/emulsion transition, or the lower phase
transition, in this case the foam/oil transition. The oil phase is normally phase 3, but any phase can
be selected for the correction. Phase 1 does not have a lower transition, so only the high transition
can be modified. Phase 6 does not have a higher transition. The phase and correction are selected
by a value in this register.
Value Function 0 Disable correction 1 1 = Phase 1, correct phase 1-2 transition density 2 1 = Phase 2, correct phase 2-3 transition density 3 1 = Phase 3, correct phase 3-4 transition density 4 1 = Phase 4, correct phase 4-5 transition density 5 1 = Phase 5, correct phase 5-6 transition density 6 1 = Phase 2, correct phase 1-2 transition density 7 1 = Phase 3, correct phase 2-3 transition density 8 1 = Phase 4, correct phase 3-4 transition density 9 1 = Phase 5, correct phase 4-5 transition density 10 1 = Phase 6, correct phase 5-6 transition density 11 to 65535
Reserved
57132571325713257132 First Reference First Reference First Reference First Reference
Density StageDensity StageDensity StageDensity Stage This register defines the uppermost stage guaranteed to be in the chosen reference phase band.
57133571335713357133 Number of Number of Number of Number of
Reference Reference Reference Reference
StageStageStageStagessss
This register defines the total number of stages in the phase reference band.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 110 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
57134 to 5713557134 to 5713557134 to 5713557134 to 57135 Low Clipping Low Clipping Low Clipping Low Clipping
Limit of Limit of Limit of Limit of
Average Average Average Average
Reference Reference Reference Reference
DensityDensityDensityDensity
This register contains the low density value used to constrain the reference band average density. On
clipping, a warning is reported and the calculated phase transition density value is set to this clipped
value.
57136 to 5713757136 to 5713757136 to 5713757136 to 57137 HighHighHighHigh Clipping Clipping Clipping Clipping
Limit of Limit of Limit of Limit of
Average Average Average Average
Reference Reference Reference Reference
DensityDensityDensityDensity
This register contains the high density value used to constrain the reference band average density.
On clipping, a warning is reported and the calculated phase transition density value is set to this
clipped value.
57138 to 5713957138 to 5713957138 to 5713957138 to 57139 Permitted Permitted Permitted Permitted
Reference Reference Reference Reference
Deviation from Deviation from Deviation from Deviation from
Average Average Average Average
Reference Reference Reference Reference
DensityDensityDensityDensity
This register defines the maximum deviation any stage can have from the average reference density.
Any stage with a value outside this limit will generate a warning. The calculated phase transition
density is calculated as normal unless clipped (see registers 57134 to 57137).
57140 to 5714157140 to 5714157140 to 5714157140 to 57141 Set point OffsetSet point OffsetSet point OffsetSet point Offset This value is added to the calculated average reference density to produce a calculated phase
transition density when the correction is acting on a higher phase transition density (register 57131
bits 1 to 5). The value is subtracted when correcting a lower phase transition density (register 57131
bits 9 to D).
57142 to 5714357142 to 5714357142 to 5714357142 to 57143 Calculated Calculated Calculated Calculated
Average Average Average Average
Reference Reference Reference Reference
DensityDensityDensityDensity
This register reports the calculated average density of the stages in the reference band. Failed stages
will be excluded from this calculation, and reported in registers 29001 to 29500.
57157157157144 to 44 to 44 to 44 to 57145571455714557145 Calculated Calculated Calculated Calculated
Setting for Setting for Setting for Setting for
Selected Phase Selected Phase Selected Phase Selected Phase
Transition Transition Transition Transition
DensityDensityDensityDensity
This register reports the modified phase transition density. When the correction is disabled, this
register will report zero. When the correction is enabled, or on start up when previously enabled, this
will report the normal phase transition density until the conditions are valid to calculate a corrected
value.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 111 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
57146571465714657146 Density Band Density Band Density Band Density Band
CorrectionCorrectionCorrectionCorrection
StatusStatusStatusStatus
This register contains the operating and configuration status of the density band correction.
Bit Function 0 1 = Invalid selection in enable register (error) 1 1 = Density band correction disabled (error) 2 1 = Invalid stage in band definition (error)
3 1 = Invalid phase transition and average reference density limit order (error) 4 1 = Offset too large (error)
5 to 6 0, Reserved 7 1 = Reference density stages: None error-free (error) 8 0, Reserved 9 1= Stage deviation from average too large (warning) A 1 = Average clipped at low limit (warning) B 1 = Average clipped at high limit (warning) C 0, Reserved D 1 = Data warning E 1 = Configuration error F 1 = Correction not operating
Bit 0 is set if 57131 contains an invalid setting, though this should be trapped when attempting to
write invalid configurations.
Bit 1 is set when density band correction is disabled.
Bit 2 is set if the stages defined for the reference band are not used in the instrument (either the
reference band stages configured in registers 57132 and 57133 exceed the total number of stages
reported in register 00128, or no sensors have yet been assigned to one or more of the reference
band stages).
Bit 3 is set if the order is not:
phase transition density n-1/n (or lower system density limit when n = 1) < low average density clip
limit < high average density clip limit < phase transition density n/n+1 (or high system density limit
when n = 5)
Bit 4 is set when correcting a higher transition density (register 57131 bits 1 to 5) if:
phase transition density n/n+1 (or high system density limit when n = 5) - high average density clip
limit ≤ set point offset
Bit 4 is set when correcting a lower transition density (register 57131 bits 9 to D) if:
low average density clip limit - phase transition density n-1/n (or lower system density limit when n =
1) ≤ set point offset
Bit 7 is set when none of the reference density stages are error-free.
Bit 9 is set if any of the individual stage densities deviate from the average density for the reference
band, by more than the permitted deviation.
Bits A or B are set if the average density is clipped by the low or high limit.
Bit D is set if any of the warning bits (9 – B) are set.
Bit E is set if any of the configuration error bits (0 to 4) are set. The correction does not take place.
Bit F is set if any of the error bits are set (0 to 4, and 7). The correction does not take place.
When correction is enabled but an error or warning is reported, bit D of register 57109 is set.
57147 to 5714857147 to 5714857147 to 5714857147 to 57148 Low Density Low Density Low Density Low Density
LimitLimitLimitLimit
These read-only registers are a duplicate of the low density limit for the instrument as configured in
registers 57001 to 57002. This is provided as part of the block of registers 57147 to 57160 to simplify
the reading of effective transition densities.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 112 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
57149571495714957149 to 5to 5to 5to 57777158158158158 Effective Phase Effective Phase Effective Phase Effective Phase
Transition Transition Transition Transition
DensitiesDensitiesDensitiesDensities
These read-only registers provide the effective/active phase transition densities, being subject to the
density band correction configured in registers 57131 to 57146 when it is both enabled and valid (no
errors). When bit F of register 57146 is clear, correction is enabled and operating on the selected
phase transition (refer to register 57131) and the corresponding float value in this range of registers is
updated accordingly, whereas each of the other values are a duplicate of the corresponding registers
57003 to 57012.
57159571595715957159 to 5to 5to 5to 57160716071607160 High Density High Density High Density High Density
LimitLimitLimitLimit
These read-only registers are a duplicate of the high density limit for the instrument as configured in
registers 57013 to 57014. This is provided as part of the block of registers 57147 to 57160 to simplify
the reading of effective transition densities.
57430 to 5746157430 to 5746157430 to 5746157430 to 57461 Sensor failure Sensor failure Sensor failure Sensor failure
alarm bits for alarm bits for alarm bits for alarm bits for
up to 500 up to 500 up to 500 up to 500
sensors. sensors. sensors. sensors.
These registers contain the failure alarm bits for sensors starting with the first 16 sensors in the 16 bit
positions of register 57430.
57462 to 5749357462 to 5749357462 to 5749357462 to 57493 Stage alarm Stage alarm Stage alarm Stage alarm
bits for up to bits for up to bits for up to bits for up to
500 stages. 500 stages. 500 stages. 500 stages.
These registers contain the warning failure alarm bits for stages starting with the first 16 stages in the
16 bit positions of register 57462.
57494574945749457494 Low density Low density Low density Low density
limit for limit for limit for limit for
instrument. instrument. instrument. instrument.
This register contains the same information as registers 57001 to 57002 but in U16 integer format, for
reporting in compatibility mode.
57495 to 57499 57495 to 57499 57495 to 57499 57495 to 57499
Phase transition Phase transition Phase transition Phase transition
densities. densities. densities. densities.
These registers contain the same information as registers 57003 to 57012 but in U16 integer format,
for reporting in compatibility mode. These are the densities marking the change from one phase to
the next. These values may need to be changed from time to time because the density of the oil (and
other components in the produced mixture) can vary. Changes are permitted even when the system
is write protected. These 16-bit integer values are copied from the floating point values in registers
57003 to 57012 for compatibility with older systems, however writes to the 16 bit integer values in
registers 57495 to 57499 are also copied to registers 57003 to 57012 as floats.
57500 57500 57500 57500
High density High density High density High density
limit for limit for limit for limit for
instrument. instrument. instrument. instrument.
This register contains the same information as registers 57013 to 57014 but in U16 integer format, for
reporting in compatibility mode.
57501 to 58000 57501 to 58000 57501 to 58000 57501 to 58000
Raw count Raw count Raw count Raw count
rates for rates for rates for rates for
sensors 1sensors 1sensors 1sensors 1----500. 500. 500. 500.
These registers contain the raw count rates for sensors, as U16 integer values in cps.
58001 to 58500 58001 to 58500 58001 to 58500 58001 to 58500
Combined Combined Combined Combined
count rates for count rates for count rates for count rates for
stages 1stages 1stages 1stages 1----500. 500. 500. 500.
These registers contain the stage count rates as U16 integer values in cps.
58501 to 59000 58501 to 59000 58501 to 59000 58501 to 59000 Densities for Densities for Densities for Densities for
stages 1stages 1stages 1stages 1----500. 500. 500. 500.
These registers contain the stage corrected densities as U16 integer values in kg/m3. For un-
corrected densities, the linearisation table must be disabled in register 57015.
61011610116101161011 Device I/ODevice I/ODevice I/ODevice I/O Pointer for switch output variable. This is the source data for the switch operation and can be a float, U16 or bit field. How this is processed depends on the switch control mode set in register 61051.
61012610126101261012 Device I/ODevice I/ODevice I/ODevice I/O
Pointer for DAC 1 variable. This is the source data for the analogue output 1 and can be a float, U16 or bit field. How this is processed depends on the control mode set in register 61103. Other registers are used to scale the DAC variable to the 4 to 20mA range, and this is scaled by yet more register settings to generate the binary value for the DAC. For float source data registers, point to either the high-word or the low-word register.
Default: 1.
61013610136101361013 Device I/ODevice I/ODevice I/ODevice I/O Pointer for DAC 2 variable. Default 1.
61014610146101461014 Device I/ODevice I/ODevice I/ODevice I/O Pointer for DAC 3 variable. Default 1.
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 113 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
61015610156101561015 Device I/ODevice I/ODevice I/ODevice I/O Pointer for DAC 4 variable. Default 1.
61016610166101661016 Device I/ODevice I/ODevice I/ODevice I/O Pointer for DAC 5 variable. Default 1.
61051610516105161051 Device I/ODevice I/ODevice I/ODevice I/O Switch Output Type Control Mode.
61052610526105261052 Device I/ODevice I/ODevice I/ODevice I/O Switch Output Mode 2, 3 and 4 operating bit 0
61053610536105361053 Device I/ODevice I/ODevice I/ODevice I/O Mode 2: Switch output bit mask.
61054 to 6105561054 to 6105561054 to 6105561054 to 61055 Device I/ODevice I/ODevice I/ODevice I/O Mode 3: Switch output float comparator set value.
61056 to 6105761056 to 6105761056 to 6105761056 to 61057 Device I/ODevice I/ODevice I/ODevice I/O Mode 3: Switch output float comparator clear value.
61058610586105861058 Device I/ODevice I/ODevice I/ODevice I/O Mode 4: Switch output U16 comparator set value.
61059610596105961059 Device I/ODevice I/ODevice I/ODevice I/O Mode 4: Switch output U16 comparator clear value.
61062610626106261062 Device Device Device Device I/OI/OI/OI/O Digital output status.
61063610636106361063 Device I/ODevice I/ODevice I/ODevice I/O Digital output state. 0 switch is open and 1 switch is closed.
61101611016110161101 Device I/ODevice I/ODevice I/ODevice I/O DAC 1 Setting for 4mA. Default for this setting is 10923.
61102611026110261102 Device I/ODevice I/ODevice I/ODevice I/O DAC 1 Setting for 20mA. Default for this setting is 54613.
61103611036110361103 Device I/ODevice I/ODevice I/ODevice I/O
Analogue output channel 1 type control mode. There are 5 options available to the user:
Data source is float
Data source is U16
Two state output, data source is bit
Two state output, float comparison
Two state output, U16 comparison
61104611046110461104 Device I/ODevice I/ODevice I/ODevice I/O Calibration Analogue Output Override
61105 to 6110661105 to 6110661105 to 6110661105 to 61106 Device I/ODevice I/ODevice I/ODevice I/O Mode 0 Analogue output channel 1 float value for 4mA
Any finite value can be used for this setting. Example, is the user required Analogue output channel 1 to represent Oil then
61107 to 6110861107 to 6110861107 to 6110861107 to 61108 Device I/ODevice I/ODevice I/ODevice I/O Mode 0 Analogue output channel 1 float value for 20mA
61109611096110961109 Device I/ODevice I/ODevice I/ODevice I/O Mode 1 Analogue output channel 1 U16 value for 4mA
61110611106111061110 Device I/ODevice I/ODevice I/ODevice I/O Mode 1 Analogue output channel 1 U16 value for 20mA
61111 to 6111261111 to 6111261111 to 6111261111 to 61112 Device I/ODevice I/ODevice I/ODevice I/O Modes 2, 3 and 4 Analogue output channel 1 current (in mA) for bit mask or comparator returning 1.
61113 to 6111461113 to 6111461113 to 6111461113 to 61114 Device I/ODevice I/ODevice I/ODevice I/O Modes 2, 3 and 4 Analogue output channel 1 current (in mA) for bit mask or comparator returning 0.
61115611156111561115 Device I/ODevice I/ODevice I/ODevice I/O Mode 2 Analogue output channel 1 bit mask.
61116 to 6111761116 to 6111761116 to 6111761116 to 61117 Device I/ODevice I/ODevice I/ODevice I/O Mode 3 Analogue output channel 1 float comparator set value for applying hysteresis. This must not be less than the clear value in registers 61118 to 61119.
61118 to 6111961118 to 6111961118 to 6111961118 to 61119 Device I/ODevice I/ODevice I/ODevice I/O Mode 3 Analogue output channel 1 float comparator clear value for applying hysteresis. This must not be greater than the clear value in registers 61116 to 61117.
61120611206112061120 Device I/ODevice I/ODevice I/ODevice I/O Mode 4 Analogue output 1 U16 comparator set value for applying hysteresis. This must not be less than the clear value in register 61121
61121611216112161121 Device I/ODevice I/ODevice I/ODevice I/O Mode 4 Analogue output 1 U16 comparator clear value for applying hysteresis. This must not be greater than the set value in register 61120
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 114 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
61122611226112261122 Device I/ODevice I/ODevice I/ODevice I/O
Analogue Output 1 range Clipping. There are 5 options available to the user:
Low: 3.8mA, High 20.5mA (Default)
Low: 4.0mA, High 20.5mA
Low: 3.8mA, High 20.0mA
Low: 4.0mA, High 20.0mA
Use Custom Settings – Allows the user to select any values between 3.8mA and 20.5mA
61123 to 6112461123 to 6112461123 to 6112461123 to 61124 Device I/ODevice I/ODevice I/ODevice I/O Analogue output channel 1 High Range Clipping (in mA).
61125 to 6112661125 to 6112661125 to 6112661125 to 61126 Device I/ODevice I/ODevice I/ODevice I/O Analogue output channel 1 Low Range Clipping (in mA).
61127 to 6112861127 to 6112861127 to 6112861127 to 61128 Device I/ODevice I/ODevice I/ODevice I/O Analogue output 1 (primary) fault 1 current (in mA). Unlike the normal output, this is not clipped/saturated (see registers 61122 to 61126).
61129611296112961129 Device I/ODevice I/ODevice I/ODevice I/O Analogue output 1 bit mask for fault 1 indication. Set to 0 to disable fault 1 indication.
Default: 0 (disabled).
61130611306113061130 Device I/ODevice I/ODevice I/ODevice I/O Analogue output 1 bit mask for fault 1 indication register pointer. Default 1.
61131 to 6113261131 to 6113261131 to 6113261131 to 61132 Device I/ODevice I/ODevice I/ODevice I/O
Analogue output 1 (secondary) fault 2 current (in mA). Unlike the normal output, this is not clipped/saturated (see registers 61122 to 61126). Secondary fault indication is ignored if primary indication is active. Default: 2.0 (mA).
61133611336113361133 Device I/ODevice I/ODevice I/ODevice I/O Analogue output 1 bit mask for fault 2 indication. Set to 0 to disable fault 2 indication.
Default: 0 (disabled).
61134611346113461134 Device I/ODevice I/ODevice I/ODevice I/O Analogue output 1 fault 2 indication register pointer.
Default: 1.
61135611356113561135 Device I/ODevice I/ODevice I/ODevice I/O
Analogue output 1 slew rate limiting. This is performed by the DAC, by setting a clock and step value. 0 = (ck A, st 6) 240mA/s, default maximum slew 1 = (ck 5, st 1) 100mA/s 2 = (ck E, st 5) 50mA/s 3 = (ck C, st 3) 20mA/s 4 = (ck C, st 2) 10mA/s 5 = (ck C, st 1) 5mA/s 6 = (ck D, st 0) 2mA/s 7 = (ck F, st 0) 1.2mA/s Slewing is active during any of the selected modes (including two-state output modes), however is temporarily overridden to the default maximum slew (240mA/s when transitioning to/from either a calibration override (when register 61104 is not 0) or a fault state (primary or secondary alarm). The user-defined slew rate configured here is resumed once the override or fault state has ended, and the output has returned to the normal state. If the slewing is reconfigured whilst slewing is active, the new slew rate will take effect immediately, and will not affect the DAC set point.
Default: 0 (240mA/s).
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 115 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
61136611366113661136 Device I/ODevice I/ODevice I/ODevice I/O
Analogue output 1 status bit 0: DAC 1 status bit 0 (1 = over temperature) bit 1: DAC 1 status bit 1 (1 = slewing active) bit 2: DAC 1 status bit 2 (1 = current fault) bit 3: 1 = calibration active, output forced bit 4: 1 = output saturated (clipped) low bit 5: 1 = output saturated (clipped) high bit 6: 1 = Primary alarm active bit 7: 1 = Secondary alarm active bit 8: 1 = DAC initialisation failed (DACs will remain inoperative until power cycled). bit 9: 1 = DAC configuration failed (DAC reconfiguration has failed and will auto-retry each second) bit A: 1 = DAC data verify failed (DAC data output failed and will auto-retry each second). The DAC data output is verified every 1 second before it is updated, though the check is more lenient when slewing is active. bit B: 1 = DAC communications failed (DAC communications via SPI has failed and two immediate retries also failed. Will continue to auto-retry each second) bit C: 1 = Comparator configuration invalid whilst mode 3 or 4 is active (Comparator set value is less than clear value; will resume operation regardless). bit D: 1 = Source data configuration invalid (Register 61012, 61130, or 61134 points to register containing incorrect data value type) bits E to F: 0, reserved The status flags will not be set if the analogue output is disabled in register 61001.
Unless otherwise specified (as with the “comparator configuration invalid” flag), the status flags are not mutually exclusive, and will be set even if the mode is not active. For example, whilst the calibration override is active, the “source data configuration invalid” flag could be set, despite not being used at the time.
61201612016120161201 Device I/ODevice I/ODevice I/ODevice I/O DAC 2 setting for 4mA
61202612026120261202 Device I/ODevice I/ODevice I/ODevice I/O DAC 2 setting for 20mA
61203 to 6123861203 to 6123861203 to 6123861203 to 61238 Device I/ODevice I/ODevice I/ODevice I/O Repeat of output 1, but for output 2
61301613016130161301 Device I/ODevice I/ODevice I/ODevice I/O DAC 3 setting for 4mA
61302613026130261302 Device I/ODevice I/ODevice I/ODevice I/O DAC 3 setting for 20mA
61303 to 6133861303 to 6133861303 to 6133861303 to 61338 Device I/ODevice I/ODevice I/ODevice I/O Repeat of output 1, but for output 3
61401614016140161401 Device I/ODevice I/ODevice I/ODevice I/O DAC 4 setting for 4mA
61402614026140261402 Device I/ODevice I/ODevice I/ODevice I/O DAC 4 setting for 20mA
61403 to 6143861403 to 6143861403 to 6143861403 to 61438 Device I/ODevice I/ODevice I/ODevice I/O Repeat of output 1, but for output 4
61501615016150161501 Device I/ODevice I/ODevice I/ODevice I/O DAC 5 setting for 4mA
61502615026150261502 Device I/ODevice I/ODevice I/ODevice I/O DAC 5 setting for 20mA
61503 to 6153861503 to 6153861503 to 6153861503 to 61538 Device I/ODevice I/ODevice I/ODevice I/O Repeat of output 1, but for output 5
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 116 of 117
Register(s)Register(s)Register(s)Register(s) FunctionFunctionFunctionFunction DescriptionDescriptionDescriptionDescription
61614616146161461614 Device I/ODevice I/ODevice I/ODevice I/O
Analogue input status bit 0: 1= raw analogue input saturated low (3.6 to 3.8mA) bit 1: 1= raw analogue input saturated high (20.5 to 21.0mA) bit 2: 1= raw analogue input failed low (less than 3.6mA) bit 3: 1= raw analogue input failed high (greater than 21.0mA) bits 4 to 7: 0, reserved. bit 8: ADC initialisation failed (will not retry until after power cycle). bits 9 to A: reserved bit B: ADC comms failed (will auto retry each second). bits C to F: 0, reserved When bits 0 or 1 are set and the input is enabled, bit C in register 57109, the status warning register should be set. When bits 2, 3, 8 or 9 are set and the input is enabled, bit D in register 57110, the status alarm register should be set.
61615 to 6161661615 to 6161661615 to 6161661615 to 61616 Device I/ODevice I/ODevice I/ODevice I/O Analogue input current in mA (raw ADC reading scaled according to registers 61606 and 61607)
OPERATION & MAINTENANCE MANUAL FOR TRACERCOTM T229 PROFILER Page 117 of 117