    The Wombat range of intumescent fire dampers includes a large variety ofsub systems for horizontal floor slab mounted applications. These are alldesignated in the following pages as sub systems starting with F. The subsystems categories include individual sub system for FS, FO and FXapplications as defined below.

    FSsub systems

    Floor mounted, Square fire damper assemblies, suppliedcomplete with casing and fixing angles and integralintumescent cell(s). These provide a better alternative tospring loaded curtain type mechanical fire dampers. Theyprovide some insulation (low temperature rise on non fireside of fire separation) and dramatic radiant heat reductionduring a fire making, coupled with the advantage of notincluding moving parts.

    FOsub systemsFloor mounted, circular or rOund fire damper assemblies,supplied complete with casing and fixing angles and integralintumescent cell(s). Unlike mechanical fire dampers whichare difficult and therefore expensive to make in a circularformat, the Wombat intumescent fire dampers are costeffective and therefore ideal where connecting to flexibleducting. Why use square to round connectors and have to

    go to all this additional work and cost if you do not have to?

    FXsub systemsAlternatively Mounted dampers for Floor orientations are

    installed by specialist contractors typically, which allow the

    Wombat intumescent cell or damper grille to be installed

    without (X) a conventional casing and mounting angles.

    These systems are ideal for problematic installations and for

    fire safety upgrades on existing buildings.

    FLOOR DAMPERS

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.auPublished 29.06.10

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    2/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

    SUB SYSTEM

    FS1FRL

    -/120/60

    Max approved size

    1200 x 1200mmor up to 1.44m

    2

    1

    2

    3

    4

    5

    Prepare openingNote: clearance around Trafalgarsintumescent fire dampers is notmandatory

    Ensure mounting flangeshave been ordered 2x thegap between the dampercasing and the wall opening

    ie: if the gap around the damper is20mm the flanges should be 40mm

    Fix one set of mountingflanges to the damperensuring that the damperwill be located within thethickness of the floor onceinstalled

    Note: These systems do not needto be in the centerline of the flooronly somewhere within the floorthickness.

    Insert damper into openingand apply approved firerated sealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or applyto both sides!

    Fit the second set of flangesand ensure that the damperis securely in place

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. All brackets to be minimum 0.6mm thick

    Note: -/240/60For 600mmx600mmMaximum only

    Installation details / instructionsFS Square Damper Floor Sub-SystemConcrete floor slabDuct to DuctSingle Module

    Supplied complete withcasing & mounting angles

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    3/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    Installation details / instructionsFS Square Damper Floor Sub-SystemConcrete floor slabDuct to DuctMultiple Module

    SUB SYSTEM

    FS2FRL

    -/120/-

    Max approved size

    3600 x 1200mmor up to 4.32m

    2

    1

    2

    3

    4

    5

    Prepare openingNote: clearance around Trafalgarsintumescent fire dampers is notmandatory

    Ensure mounting flangeshave been ordered 2x thegap between the dampercasing and the wall openingie: if the gap around the damper is20mm the flanges should be 40mm

    Fix one set of mountingflanges to the damperensuring that the damperwill be located within thethickness of the floor onceinstalled

    Note: These systems do not needto be in the centerline of the flooronly somewhere within the floorthickness.

    Insert damper into opening

    and apply approved firerated sealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or applyto both sides!

    Fit the second set of flangesand ensure that the damperis securely in place

    Supplied complete withcasing & mounting angles

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. All brackets to be minimum 0.6mm thick

    Largest manufactured single cell module up to 600mmx600mm.Case enclosed modules will be supplied in up to 1200mmx1200mm.

    For modulars,Join modules together usingscrews or steel rivets at200mm centres

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    4/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    Installation details / instructionsFS Square Damper Floor Sub-SystemConcrete Floor SlabDuct to gr ille systemSingle Module

    1

    2

    3

    4

    Prepare opening

    Note: clearance around Trafalgarsintumescent fire dampers is notmandatory

    Ensure mounting flangeshave been ordered 2x thegap between the dampercasing and the wall opening

    ie: if the gap around the damper is20mm the flanges should be 40mm

    Insert damper into openingand apply approved fire

    rated sealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or applyto both sides!

    Fit the set of flanges andensure that the damper issecurely in place

    SUB SYSTEM

    FS3FRL

    -/120/60

    Max approved size

    1200 x 1200mmor up to 1.44m

    2

    Supplied complete withcasing & mounting angles

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. All brackets to be minimum 0.6mm thick

    Note: -/240/60For 600mmx600mmMaximum only

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    5/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    Installation details / instructionsFS Square Damper Floor Sub-SystemConcrete Floor SlabDuct to DuctOversized Openings

    1

    2

    3

    4

    Prepare opening to suit

    damper size by upgradingusing 60mm Maxilite Board.Note: clearance around Trafalgarsintumescent fire dampers is notmandatory

    Ensure mounting flangeshave been ordered 2x thegap between the dampercasing and the wall opening

    ie: if the gap around the damper is20mm the flanges should be 40mm

    Insert damper into openingand apply approved firerated sealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or applyto both sides!

    Fit the set of flanges andensure that the damper issecurely in place

    SUB SYSTEM

    FS4FRL

    -/240/60

    Max approved size

    600 x 600mmor up to 0.36m

    2

    Supplied complete withcasing & mounting angles

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. All brackets to be minimum 0.6mm thick

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    6/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    Installation details / instructionsFO Round Damper Floor Sub-SystemConcrete floor slabAngle tab fixings

    SUB SYSTEM

    FO1FRL

    -/120/-

    Max approved size

    450mm

    1

    2

    Prepare openingNote: clearance around Trafalgarsintumescent fire dampers is notmandatory

    Select mounting options;a) Angle bracketrequired evenly spaced aroundperimeter of damper casing (1 faceonly as minimum)

    b) Clamping methodFit angle bracket as per (a) ontodamper casing, install damper,apply sealant and then fix another

    set of angle brackets to the openingin the same orientation to clampdamper into position

    3

    4

    Fix brackets/tabs to dampercasing in required locationswith min 6 gauge screws

    5 Insert damper into openingand secure to wall with aminimum of 6mm anchors

    Apply approved fire ratedsealant to perimeterNote: while sealant is only required

    to one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or applyto both sides or apply to bothsides !

    Supplied complete withcasing & mounting angles

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. All brackets to be minimum 0.6mm thick

    Stainless Steel model suitable for fume

    cupboards and other aggressive environmentsalso available.

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    7/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    Installation details / instructionsFO Round Damper Floor Sub-SystemConcrete Floor SlabOversized openings

    SUB SYSTEM

    FO2FRL

    -/120/-

    Max approved size

    450mm

    1

    2

    Prepare opening to suitdamper size by upgradingusing 60mm Maxilite Board.Note: clearance around Trafalgarsintumescent fire dampers is notmandatory

    Select mounting options;a) Angle bracketrequired evenly spaced aroundperimeter of damper casing (1 faceonly as minimum)

    b) Clamping method

    Fit angle bracket as per (a) ontodamper casing, install damper,apply sealant and then fix anotherset of angle brackets to the openingin the same orientation to clampdamper into position

    3

    4

    Fix brackets/tabs to dampercasing in required locationswith min 6 gauge screws

    5 Insert damper into openingand secure to the board witha minimum of 6mm anchors

    Apply approved fire ratedsealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or applyto both sides or apply to bothsides !

    Supplied complete withcasing & mounting angles

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. All brackets to be minimum 0.6mm thick

    Stainless Steel model suitable for fume

    cupboards and other aggressive environmentsalso available.

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    8/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    Installation details / instructionsFX-Alternative Mounted Floor Sub-SystemConcrete SlabContinuous Angle FixingsSingle Module

    SUB SYSTEM

    FX1FRL

    -/240/60

    Max approved size

    600 x 600mmor up to 0.36m

    2

    1

    2

    Prepare openingNote: clearance around Trafalgarsintumescent fire dampers is not

    mandatory

    Select mounting options;a) Angle bracketrequired at 200mm centres on allfour sides (1 face only as minimum)

    b) Continuous angle sectionrequired top and bottom OR leftand right vertical sides only

    c) Clamping methodFit continuous angle as per (b) intoopening, install damper, applysealant and then fix another set of

    continuous angles to the opening inthe same orientation to clampdamper into position

    3

    4

    Fix brackets/tabs to damperin required locations withmin 6 gauge screws

    5 Insert damper into openingand secure to floor with aminimum of 6mm anchors

    Apply approved fire ratedsealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is not

    there. Ensure sealant can be seenfrom side to be inspected or applyto both sides or apply to bothsides !

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. Fixing brackets not supplied5. All brackets to be minimum 0.6mm thick

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    9/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    Installation details / instructionsFX-Alternative Mounted Floor Sub-SystemConcrete SlabContinuous Z bracket fixings

    SUB SYSTEM

    FX2FRL

    -/240/60

    Max approved size

    600 x 600mmor up to 0.36m

    2

    1

    2

    Prepare openingNote: clearance around Trafalgarsintumescent fire dampers is not

    mandatory

    Select mounting options;a) Z Bracketrequired at 200mm centres on allfour sides (1 face only as minimum)

    b) Continuous Z sectionrequired top and bottom OR leftand right vertical sides only

    c) Clamping methodFit continuous Z section as per (b)into opening, install damper, apply

    sealant and then fix another set ofcontinuous Z sections to theopening in the same orientation toclamp damper into position

    3

    4

    5

    Fix brackets/tabs to damperion required locations withmin 6 gauge screws

    Insert damper into openingand secure to floor with aminimum of 6mm anchors

    Apply approved fire ratedsealant to perimeterNote: while sealant is only requiredto one side if it cannot be seen

    during maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or applyto both sides!

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. Fixing brackets not supplied5. All brackets to be minimum 0.6mm thick

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    10/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    SUB SYSTEM

    FX3FRL

    -/240/60

    Max approved size

    600 x 600mmor up to 0.36m

    2

    1

    2

    Prepare face of opening

    Note: damper must overlap openingby 50mm on all four sides. ie. thefire damper must be 100mm largerthan opening

    Select mounting options;a) Angle bracketrequired at 200mm centres on allfour sides (1 face only as minimum)

    b) Continuous angle sectionrequired top and bottom OR leftand right vertical sides only

    3

    4

    5

    Fix brackets/tabs to damperion required locations withmin 6 gauge screws

    Insert damper over openingand secure to floor with aminimum of 6mm anchors

    Apply approved fire ratedsealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or applyto both sides!

    Installation details / instructionsFX-Alternative Mounted Floor Sub-SystemConcrete SlabContinuous Angle FixingsIrregularopenings - access from below only

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. Fixing brackets not supplied5. All brackets to be minimum 0.6mm thick

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    11/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    SUB SYSTEM

    FX4FRL

    -/240/-

    Max approved size

    600 x 600mmor up to 0.36m

    2

    1

    2

    Prepare face of opening

    Note: damper must overlap openingby 50mm on all four sides. ie. thefire damper must be 100mm largerthan opening

    Select mounting options;a) Angle bracketrequired at 200mm centres on allfour sides (1 face only as minimum)

    b) Continuous angle sectionrequired top and bottom OR leftand right vertical sides only

    3

    4

    5

    Fix brackets/tabs to damperion required locations withmin 6 gauge screws

    Insert damper over openingand secure to floor with aminimum of 6mm anchors

    Apply approved fire ratedsealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or applyto both sides!

    Installation details / instructionsFX-Alternative Mounted Floor Sub-SystemConcrete SlabContinuous Angle FixingsIrregularopenings - access from above only

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. Fixing brackets not supplied5. All brackets to be minimum 0.6mm thick

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    12/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    Installation details / instructionsFX-Alternative Mounted Floor Sub-SystemConcrete SlabContinuous Angle FixingsSmall Modular

    2

    Prepare openingNote: clearance around Trafalgarsintumescent fire dampers is not

    mandatory

    Select mounting options;a) Continuous angle sectionrequired along longest length onlyon both faces if using clampingmethod OR on one face if fixing todamper and opening

    b) Clamping methodFit continuous angle as per (a) intoopening, install damper, applysealant and then fix another set ofcontinuous angles to the opening inthe same orientation to clampdamper into position

    3

    4

    Fix brackets/tabs to damperin required locations withmin 6 gauge screws

    5 Insert damper into openingand secure to floor with aminimum of 6mm anchors

    Apply approved fire ratedsealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or apply

    to both sides or apply to bothsides !

    Multiple modules arejoined on site for ease ofinstallation in tight spaces

    Fill with sealantand fix with min6g self drillingscrews at 200mm

    centres

    1

    SUB SYSTEM

    FX5FRL

    -/120/60

    Max approved size

    900mm wide xInfinite length

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. Fixing brackets not supplied5. All brackets to be minimum 0.6mm thick

    Largest manufactured single cellmodule up to 600mmx600mm.Case enclosed modules will besupplied in up to 1200mmx1200mm.

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    13/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    SUB SYSTEM

    FX6FRL

    -/120/60

    Max approved size

    900mm wide xInfinite length

    2

    Prepare openingNote: clearance around Trafalgarsintumescent fire dampers is not

    mandatory

    Select mounting options;a) Continuous angle sectionrequired along longest length onlyon both faces if using clampingmethod OR on one face if fixing todamper and opening

    b) Clamping methodFit continuous angle as per (a) intoopening, install damper, applysealant and then fix another set ofcontinuous angles to the opening inthe same orientation to clampdamper into position

    3

    4

    Fix brackets/tabs to damperin required locations withmin 6 gauge screws

    5 Insert damper into openingand secure to floor with aminimum of 6mm anchors

    Apply approved fire ratedsealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or apply

    to both sides or apply to bothsides !

    Multiple modules arejoined on site for ease ofinstallation in tight spaces

    Fill with sealantand fix with min6g self drillingscrews at 200mm

    centres

    1

    Installation details / instructionsFX-Alternative Mounted Floor Sub-SystemConcrete SlabContinuous Z Bracket FixingsSmallModular

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. Fixing brackets not supplied5. All brackets to be minimum 0.6mm thick

    Largest manufactured single cellmodule up to 600mmx600mm.Case enclosed modules will besupplied in up to 1200mmx1200mm.

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    14/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    SUB SYSTEM

    FX7FRL

    -/120/60

    Max approved size

    1800mm wide xInfinite length

    2

    Prepare openingNote: clearance around Trafalgarsintumescent fire dampers is not

    mandatory

    Select mounting options;a) Continuous angle sectionrequired along longest length onlyon both faces if using clampingmethod OR on one face if fixing todamper and opening

    b) Clamping methodFit continuous angle as per (a) intoopening, install damper, applysealant and then fix another set ofcontinuous angles to the opening inthe same orientation to clampdamper into position

    3

    4

    Fix brackets/tabs to damperin required locations withmin 6 gauge screws

    5 Insert damper into openingand secure to floor with aminimum of 6mm anchors

    Fix additional top anglestiffener

    Apply approved fire ratedsealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or applyto both sides or apply to both

    1

    Installation details / instructionsFX-Alternative Mounted Floor Sub-SystemConcrete SlabContinuous Angle FixingLargeModular Systems

    Multiple modules arejoined on site for ease ofinstallation and transportFill with sealant and fixwith min 6g self drillingscrews at 200mm centres.

    Notes on the installation of fire dampers1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. Fixing brackets not supplied5. All brackets to be minimum 0.6mm thick

    Largest manufactured single cellmodule up to 600mmx600mm.Case enclosed modules will besupplied in up to 1200mmx1200mm.

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    15/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide

    Sales:1800 888 [email protected]

    www.trafalgarfire.com.au29.06.10

    FLOOR DAMPERS

    SUB SYSTEM

    FX8FRL

    -/120/60

    Max approved size

    1800mm wide xInfinite length

    2

    Prepare openingNote: clearance around Trafalgarsintumescent fire dampers is not

    mandatory

    Select mounting options;a) Continuous angle sectionrequired along longest length onlyon both faces if using clampingmethod OR on one face if fixing todamper and opening

    b) Clamping methodFit continuous angle as per (a) intoopening, install damper, applysealant and then fix another set ofcontinuous angles to the opening inthe same orientation to clampdamper into position

    3

    4

    Fix brackets/tabs to damperin required locations withmin 6 gauge screws

    5 Insert damper into openingand secure to floor with aminimum of 6mm anchors.

    Fix additional top anglestiffener

    Apply approved fire ratedsealant to perimeterNote: while sealant is only requiredto one side if it cannot be seenduring maintenance inspections ithas to be assumed that it is notthere. Ensure sealant can be seenfrom side to be inspected or apply

    to both sides or apply to bothsides !

    1

    Installation details / instructionsFX-Alternative Mounted Floor Sub-SystemConcrete SlabContinuous Z Bracket FixingLargeModular Systems

    Multiple modules arejoined on site for ease ofinstallation and transportFill with sealant and fixwith min 6g self drillingscrews at 200mm centres.

    Largest module section tobe determined at time ofmanufacture

    Notes on the installation of fire dampers 1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. Fixing brackets not supplied5. All brackets to be minimum 0.6mm thick

    Largest manufactured single cellmodule up to 600mmx600mm.Case enclosed modules will besupplied in up to 1200mmx1200mm.

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.

  • 7/26/2019 Trafalgar Wombat Floor Damper Systems

    16/16

    FLOOR

    MOUNTED

    S

    YSTEM

    S

    Our Products are available Nationwide info@trafalgarfire com au

    FLOOR DAMPERS

    Installation detailsFX-Alternative Mounted Floor Sub-SystemExisting mechanical fire damper upgradeusing intumescent damper cell(s)

    SUB SYSTEM

    FX9FRL

    -/120/-

    Max approved size

    4800mm x4800mm

    in 1200x1200modules

    Notes on the installation of fire dampers 1. AS1682.2 requires break away joints for ALL fire damper

    typesthere are no exemptions.2. A fire damper label must be fitted in a prominent position to

    each fire damper installation, refer to your distributor forsupply of the labels at time of purchase

    3. Max annular gap 25mm. For openings much larger thanthe fire damper use Maxilite to reduce the opening size,refer to systems data sheets in this section.

    4. Fixing brackets not supplied5. All brackets to be minimum 0.6mm thick

    1 These damper upgrades shouldonly be conducted by specialistand approved passive firecompanies.Please contact Trafalgar for anapproved company in your area.

    Ideal solution to avoidremoving existing fire dampercasings out of floor slabs

    Note: -/240/60For 600mmx600mmMaximum only

    Largest manufactured single cellmodule up to 600mmx600mm.Case enclosed modules will besupplied in up to 1200mmx1200mm.

    Information given in this publication is given to the best of our knowledge and in good faith. Trafalgar is not responsible ifrecipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on thosemisinterpretations. No liability is accepted for error omissions in this document. Trafalgar reserves the right to changespecification without notice.