transformer - s; e
TRANSCRIPT
TRANSFORMER Knowledge Sharing
Mahersa ALI
• Basic Theory • Definition Of Transformer • Electrical Parameters
• Types of Transformer • Cooling and Insulation • Surface Treatment • Monitoring & Protection Device • Testing • Installation, Operation &
Maintenance
Content
Basic Theory
Definition, Electrical Parameters,
Page 4 Confidential Property of Schneider Electric |
Basic Theory
Transformer is… … an electrical equipment which convert electrical energy from one level voltage to another level voltage at a same frequency
Transformation Ratio
1
2
2
1
2
1
II
UU
nn
==
P = U x I x √3
kVA = kV x A x √3
P = rated power
U = rated voltage (at no-load)
I = rated current
Transformer ratio :
n= number of turns
U1, n1
I1 I2
U2, n2
I1
U1
I2
U2 / √
3
3nn
II
UU
2
1
1
2
2
1
×==
Rated voltage: step-up or step-down • Step-down:
• Primary = the higher voltage
• Secondary = the lower voltage
i.e. 20000/400 V
• Step-up: • Primary = the lower voltage (supply)
• Secondary = the higher voltage (operating)
i.e. 400/20000 V
Tapping
Example: 20 000 V ± 2.5 %
U1 n1
= pos 1 20 500 1904
= pos 2 20 000 1858
= pos 3 19 500 1812
tapping range 2.5 %
46 turns by step
To adjust the rated voltage of the transformer to the system.
⇐ plus tapping
⇐ nominal tapping
⇐ minus tapping
Magnetic core
Page 8 Confidential Property of Schneider Electric |
Iron Core
Sometimes referred as Magnetic Core, it is made of laminations of grain oriented silicone steel insulated with mineral oxide. Its performance depends on the grade of the steel, the cutting pattern and the method of assembly
No Load Loss (P0) and Parameters Related to Magnetic Core
No Load Loss (P0) •Composed of:
– Hysteresis losses (reversing of magnetic flux)
– Eddy - current losses (the magnetic core is an electrical conductor)
No load current • is the current required for the core magnetisation
• is often expressed as a percentage of the rated current of the same winding.
Noise/Sound/Acoustic Level • acoustic power level Lw(A)
• acoustic pressure level Lp(A)
Windings
LV winding HV winding ● Conductor material:
● Copper (Cu) ● Aluminum (Al)
● Conductor shape: ● Round wire
● Rectangular wire ● Foil ● Strip
Iron core
Page 11 Confidential Property of Schneider Electric |
Load Loss (PCU)
Load loss
● Is composed of ohmic losses (R x I2), eddy-current losses and stray-load losses
●Resistance increases as conductor temperature increase
●Reference temperature :
●75°C for the oil immersed transformers
●120°C for the cast resin transformers
● Thus, load loss should be corrected according to reference temperature
Vector Group
• 1st letters group : CAPITAL letters
⇒the higher voltage
if the neutral is brought out : YN or ZN
• 2nd letters group : small letters
⇒the lower voltage
if the neutral is brought out : yn or zn
• 3rd letters group : number ⇒clock-hour figure, indicating phase displacement between HV and LV windings
The vector group of a transformer defines the connection of the HV and LV windings
Page 13 Confidential Property of Schneider Electric |
Vector Group - example
Dyn11 HV : Delta LV : Star Phase Angle =11x30°= 330°
Types of Transformer
Oil Immersed Transformer, Dry Type Transformer
Confidential Property of Schneider Electric
Types of Transformers Based on Cooling and Insulation
Based on insulation and cooling medium:
●Oil immersed transformers
● Sealed type transformer ● Hermetically Sealed Totally Oil Filled
● Sealed type with gas (N2) cushion
● Breathing type with conservator
●Dry type transformers ● Cast Resin
● Encapsulated Resin
● Vacuum Pressure Impregnated (VPI)
Page 16 Confidential Property of Schneider Electric |
Types of Transformers Based on Cooling and Insulation
Dry Type Transformer. Use air as cooling medium Oil Immersed Transformer. Use oil as cooling and insulation medium
Standard solution. Up to 36 kV and 4000 kVA.
Oil Immersed Transformer
Suitable for high rating up to 170 kV and 100 MVA. Customized solution. Up to 36 kV and 10 MVA.
Based on method to absorb oil expansion
Hermetically sealed totally oil filled
• Transformers is fully filled with oil.
• Expansion of oil is compensated with deformable fins radiator
Sealed type with gas cushion
• Not fully filled with oil, this transformer has N2 gas cushion on the top of tank to absorb oil expansion.
Breathing Type with Conservator
• Oil expansion is absorbed by conservator tank on top of main tank.
Page 17 Confidential Property of Schneider Electric |
Cooling and Insulation
Page 18 Confidential Property of Schneider Electric |
Temperature Rise
For Oil Immersed Transformer
Part Temperature rise °K
Windings : Temperature class A (measured by resistance)
65, for natural or forced oil circulation, 70, for forced and directed oil circulation
Top oil (measured by thermometer)
60, when the transformer is sealed or equipped with a conservator, 55, when the transformer is not sealed
Part Cooling method Class of temp.
Temp. rise °K
Windings (measurement by resistance)
Air natural or forced A E B F H
60 75 80
100 125 150
For Dry Type Transformer
Cooling
Examples
1st letter 2nd letter 3rd letter 4th letter
Indicating the cooling medium that is in contact with windings Indicating the cooling medium that is in contact with external cooling system
Kind of medium Kind of circulation Kind of medium Kind of circulation
Example :
O N A N
ONAN
AN
Order of symbols
Symbols Kind of cooling medium Symbol
Mineral oil or synthetic insulating fluid with flame point ≤ 300°C Insulating fluid with flame point > 300°C Askarel Gas Water Air Solid insulant
O K L G W A S
Kind of circulation Natural Forced Directed
N F D
Surface Treatment
Page 21 Confidential Property of Schneider Electric |
Corrosivity Categories ISO 12944-2 Standard
EXTERIOR INTERIOR
Atm
ospheric corrosivity category IS
O12944-2
C1 Very Low Corrosivity
- ● Heated buildings with clean atmospheres ● Examples : Offices, shops, schools, hotels
C2 Low Corrosivity
● Atmospheres with very low level of pollution ● Mostly rural areas
● Unheated buildings where condensation may occur ● Examples : Depots, sports halls
C3 Medium Corrosivity
● Urban and industrial atmospheres, moderate sulphur dioxide pollution
● Coastal areas with low salinity
● Productions rooms with high humidity and some air pollution
● Examples : Food-processing plants, laundries, breweries, dairies
C4 High Corrosivity
● Industrial areas and coastal areas with moderate salinity
● Chemical plants, swimming pools, coastal ship-and boatyards
C5Marine Very High Corrosivity
● Coastal and offshore areas with high salinity ● Buildings or areas with almost permanent condensation and with high pollution
C5Industrial Very High Corrosivity
● Industrial areas with high humidity and aggressive atmosphere
● Buildings or areas with almost permanent condensation and with high pollution
Durability Categories ISO 12944-2 Standard
LOW 2 - 5 years
MEDIUM Durability Maintenance : 5 - 15 years
HIGH Durability Maintenance : > 15 years
Atm
ospheric corrosivity category IS
O12944-2
Guarantee Ri 3 – 5 years Ri 2 – 5 years
C3 Medium Corrosivity
> 240 Hours (Neutral Salt Spray Resistance - ISO 7253 standard)
> 480 Hours
C4 High Corrosivity
> 480 Hours > 720 Hours
C5 Marine Very High Corrosivity
> 720 Hours > 1440 Hours
C5 Industrial Very High Corrosivity
> 720 Hours > 168 Hours (Chemical Resistance –
ISO 2812-1)
> 1440 Hours > 168 Hours
Monitoring & Protection Device
Page 24 Confidential Property of Schneider Electric |
Off circuit tap changer
• To adjust the voltage of the transformer at off circuit (not only at no-load) condition, the transformer has to be disconnected from the network.
• Tap changer is operated by means of a handle on the cover or a hand wheel on top or on sidewall of the transformer.
On Load Tap Changer (OLTC)
• To adjust the voltage automatically, without de-energizing the transformer
1. Integrated Safety Detector
2. Oil Level Indicator
3. Pressure Relief Device
4. Oil Temperature Indicator
5. Winding Temperature Indicator
6. Buchholz Relay
7. Pressure Vacuum Gage
8. Sudden Pressure Relay
Monitoring & Protection Devices
Confidential Property of Schneider Electric
Function:
• Oil level indication
• Oil temperature indication
• Over pressure detection
All functions are provided with contact for alarm and/or trip
Standard monitoring device
Page 28 Confidential Property of Schneider Electric |
Integrated Safety Detector (R.I.S®, DMCR®, DGPT2®) Hermetically Sealed Totally Oil Filled type
Oil Level Indicator For Sealed Type with N2 Gas Cushion Type and Breathing Type
Function : to measure the level reached
by the oil in a transformer conservator
Pressure Relief Device Standard device for all type
Function : A device to relieve large volumes of gas or insulating fluid rapidly when the pressure inside a transformer reaches a pre-determined limit.
Oil Temperature Indicator
For Sealed Type with N2 Gas Cushion Type and Breathing Type with Conservator
Function : to measure the oil temperature inside transformer tank
Winding Temperature Indicator Standard device for high rated power
Function: • to measure the winding temperature by means of a special
bulb surrounded by heating resistance, through which passes a current proportional to the current passing through the transformer winding.
Buchholz Relay for breathing type with conservator
Function : • to trip out the transformer if there is a release of gas arising
from the decomposition of the solid and liquid insulating material due to the action of heat or electric arcing.
Pressure Vacuum Gauge
for sealed type with gas cushion
Function : To check the vacuum pressure inside the tank, applicable for sealed type transformer with N2 gas cushion
Test ing
Page 35 Confidential Property of Schneider Electric |
Transformer Testing
Performed on one unit to validate design. Subject to additional cost. Performed on all units, free of charge.
For distribution transformer, according to IEC 60076
ROUTINE TEST
1. Measurement of Winding Resistance
2. Measurement of Turn Ratio and Vector Group Check
3. Measurement of No Load and No Load Current
4. Measurement of Load Losses and Impedance Voltage
5. Induce Test
6. Applied Test
7. Oil Break Down Voltage Test
TYPE TEST
1. Temperature Rise Test
2. Lightning Impulse Test
Confidential Property of Schneider Electric
Winding Resistance Test
Test Objective: To Measure the resistance in
ohms of each of the windings of the transformer
Confidential Property of Schneider Electric
Turn Ratio Test
Test Objective: To check conformity to specification of the transformer turn ratio and vector group connection Acceptance Criteria: Tolerance : ± 0,5% of theoretical ratio
Confidential Property of Schneider Electric
No Load Losses & Current Measurement
Test Objective: 1. To measure no load losses
and no load current of the transformer
2. To check whether the characteristics conform the applicable standards
Acceptance Criteria: +15% tolerance from declared
value according to IEC 60076
Confidential Property of Schneider Electric
Load Losses & Impedance Measurement
Test Objective: 1. Measurement of the
transformer’s load losses 2. Measurement of impedance
voltage Acceptance Criteria:
•Load losses tolerance: +15% from declared value •Impedance tolerance:± 10% from declared value • All according to IEC 60076
Confidential Property of Schneider Electric
Induce Overvoltage Test
Test Objective: The test the insulation strength
inter turns and inter layer of the windings.
Acceptance Criteria: The transformer is considered to have passed when there is no voltage collapse or variation in current
Confidential Property of Schneider Electric
Applied Voltage Test
Test Objective: To test the insulation strength
between live parts to earth Acceptance Criteria:
The transformer is considered to have passed when there is no voltage collapse in 60 second
HV LV
kV HV side
LV Side
TEST FOR HV SIDE
TEST FOR LV SIDE
HV LV
kV HV side
LV Side
Temperature Rise Test
Test Objective:
1. To determine the temperature rise of the oil (ΔT oil) 2. To determine the temperature rise of the HV and LV windings
3. To confirm the rated power of the transformer Acceptance Criteria:
•According to approved documents and specifications; ex ΔT oil : 60°C, ΔT windings : 65°C
Lightning Impulse Test Test Objective:
•To check the impulse withstand of each winding relative to earth, relative and to other windings and along the tested winding
Acceptance Criteria: •Reduced and full wave should be similar
Function Test of Measuring & Protection Devices
Test Objective: • Check of control and protection devices : relay function, accessories function and
continuity of wiring from devices into wiring box (Regulator Control Panel, Lamp, Power socket, Heater, Oil level gauge, Pressure Relief Device, Oil Thermometer, Winding Thermometer, Buchholz Relay, Junction Relay (RS. 2001, OLTC), Control Panel, Current Transformer (CT), etc.)
Installation, Operation & Maintenance
INSTALLATION Installation should be carried out in compliance with following rules / conditions:
1. All external cables connections are tight and secure
2. All accessories circuits operate properly
3. The tap changer is securely in correct position
4. The neutral and earth connections have been properly installed
5. Fans (if any) has been installed and operates properly
6. Proper clearance is maintained from high voltage bus to terminal equipment
7. All windings are free from un-intended earths
8. There is no dust, dirt or foreign material on core and coils (dry-type transformers)
9. There is no visible moisture on or inside the core and coils (dry-type transformers)
10. All plastic wrappings are removed from the core and coils (dry-type transformers)
11. There are no obstructions in or near the openings for ventilation
12. Commissioning should be carried out prior to energizing
Checklist before operation (part 1)
OPERATION
No.
CHECK ITEMS
DESCRIPTION
SPECIFIED
REMARK 1
Out line drawing
Specification
Compliance with drawing and specification
2
Oil level
Main tank
Level gauge to read correctly for existing level and oil temperature
3
Valve position
1. Valves
Open and close position 2. Radiator valves
3. Other valves 4
Off load tap changer
Manual operation through all tap position
As specified
No.
CHECK ITEMS
DESCRIPTION
SPECIFIED
REMARK
5 Electrical tests
1. Insulation resistance of windings No insulation breakdown
As reference
2. Ratio and polarity Acc. to specification
3. Dielectric strength of oil >30 kV
4. Alarm, tripped, control circuits, and auxiliary circuit 1. Wired properly and comply with wiring 2. Contacts open or close as specified.
6 Earthing Tank and Marshalling kiosk It should be connected to earth
7 Bushing
1. Porcelain Clean Proper continuity and tightness
2. Spark Gap
3. Connected
8 Other Cleans rust Cleans Clean and touch point
Checklist before operation (part 2)
OPERATION
ROUTINE MAINTENANCE No Task Acceptance Criteria Frequency Remarks
1 Check the pressure relief disc No crack Yearly Contact the transformer supplier
2 Check ventilation and ambient temperature inside the transformer room
< 40o C Yearly Ensure adequate ventilation and the compliance with Section 7 - Installation.
3 Check insulating liquid temperature < 100o C Yearly Conduct investigation if the insulating liquid temperature is abnormally high with due respect to the load current and ambient temperature
4 Check for leakage of insulating liquid level No insulating liquid leak Yearly If leakage is found, refer to Appendix 1.1
5 Check insulating liquid level Middle between Max & Min Yearly If level on the RIS insulating liquid level indicator is too low, refer to Appendix 1.2
6 Check the RIS settings Refer to the RIS Catalogue & Instructions 2-yearly Reset the settings if different from that in the RIS
Catalogue & Instruction
7 Check dielectric strength of the insulating liquid
Breakdown voltage test > 30kV/2.5mm 2-yearly For sampling details, please refer to Appendix 1.3
8 Check paintwork No paint peeling or rust 2-yearly The frequency should be increased for hostile environment
9 Arrange outage to check and clean bushings No dust 5-yearly The frequency should be increased to 4 years or
less for hostile environment
Electrical Test: •Winding Resistance •No Load Current •Capacitance •Transmission ratio
Advance (Special Test): •Partial Discharge •Dielectric Response •SFRA
Oil Analysis: •Color •BDV •Water Content •DGA
On Line Monitoring: •Voltage, Current, Temperature •Oil, tap changer, cooling •Bushings
Post Mortem : • Degree of polymerization •Moisture in pressboard/paper
Periodic/Routine Maintenance
Diagnostic Method for Transformer
Questions?
Page 52 Confidential Property of Schneider Electric |