811 Edition 0211
Technical Information middot GB
wwwkromschroedercom
bull Electrical ignition of gas burners
bull Ignition and burner control with a single electrode possible
bull For installation in a control cabinet or wall mounting
bull Complying with EN 61558-2-3
bull TZI 75-2033R complies with CSA
Ignition transformers TZI TGI
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 214
TZI TGI middot Edition 0211
2
983156 = To be continued
ContentsIgnition transformers TZI TGI 1
Contents 2
1 Application 311 Examples of application 5
111 Double-electrode operation 5112 Single-electrode operation 5
2 Certification 6
3 Function 731 Connection diagrams 7
4 Selection 8
41 Selection table 8411 Type code 8
5 Project planning information 951 Operation 952 Installation 953 Cable selection 954 Ignition electrode 955 Reduction of EMC wiring 9
56 Single-electrode operation 1057 Intermittent operationStar electrodes 1058 Duty cycle 10
6 Accessories 1161 High-voltage cable 1162 Radio interference suppressed electrode adapters 11
7 Technical data 12
71 Dimensions 13Feedback 14
Contact 14
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 314
TZI TGI middot Edition 0211
3
TZI 5-1520 TZI 5-15100 TZI 7-2520TZI 75-12100 TZI 75-2033 TGI
1 ApplicationIgnition transformers TZI and TGI are designed for high-voltagespark ignition of gas burners and gas-ignited or directly ig-nited oil burners The ignition transformers can also be usedon burners with single-electrode operation the ignition cur-
rent and ionization current flow over a common electrodeIgnition transformer TZI fulfils the requirements for enclosureIP 20 It is suitable for installation in a control cabinet Igni-tion transformer TGI in its die-cast aluminium housing meetsthe requirements for enclosure IP 65 It is suitable for on-sitemounting near to the burner
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 414TZI TGI middot Edition 0211
4
Bogie hearth forging furnacein the metallurgical industry
Intermittent shuttle kilnin the ceramics industry
Walking beam furnacewith overhead firing
Application
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 514TZI TGI middot Edition 0211
5
IFD 258
BIO
BIC
VAS
VRR
GIK
N
L1
TGI
IFD 258
BIO
BIC
VAS
GIK
NL1
TGI
VRR
Application
11 Examples of application
111 Double-electrode operationIgnition using ignition electrode
Ignition transformer TGI is supplied with voltage via the au-tomatic burner control unit IFD 258 The ignition transformergenerates a high voltage This high voltage creates ignitionsparks between the ignition electrode and burner ground Afterthe burner start a current flows via the ionization electrodefor flame control
112 Single-electrode operationIgnition using an ignition and ionization electrode
After burner start a flame control current flows via the sameelectrode that is also used for ignition
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211
6
2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC
TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211
7
H
empty 7 mm (0275 )
3 Function
31 Connection diagramsIgnition double-electrode operation
Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-
tween ignition and monitoring is performed by the automaticburner control unit
High-voltage connectionCut end of high-voltage cable is inserted into the shroud and
screwed onto the wood screw (H)
Legend
H High-voltage connectionbr Connection cable brown
sw Connection cable black
bl Connection cable blue
gnge Connection cable greenyellow
sw
bl
gnge
H
br
L1
N
Burner control unit
sw
bl
gnge
H
br
I Z
L1
N
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211
8
4 Selection
41 Selection table
R W
TZI 5-1520
TZI 5-15100
TZI 7-2520
TZI 75-12100
TZI 75-2033
TGI 5-15100
TGI 7-2520
TGI 75-12100
TGI 75-2033
rder example
TZI 5-1520W
411 Type code
Code Description
TZI
TGI
Ignition transformer
Ignition transformer enclosed5775
High voltage 5 kV7 kV
75 kV
-12-15-20-25
Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)
20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)
20
33100
Duty cycle 20
33100
RW
Mains voltage 115 V230 V
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211
9
5 Project planning information
51 OperationThe ignition transformers are suitable only for applications
for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created
52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down
Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)
TZILength of the mains cable is 410 mm
The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary
53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations
Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer
Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)
Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity
TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable
gland see page 13 (Dimensions)
54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm
55 Reduction of EMC wiringAvoid external electrical interference
Lay cables individually and if possible not in a metal conduit
Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible
Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)
Use an interference suppressed electrode adapter on the
burner (with 1 Ω resistor) see page 11 (Accessories)
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211
10
56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units
For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged
57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On
Off intermittent operation or when using burners with starelectrodes
58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded
-20 0 20 40 60
0
20
40
60
80
100
D u t y c y c l e [ ]
Ambient temperature [degC]
For ignition transformers the duty cycle is dependent on theambient temperature
TZITGI duty cycle in ndash see 12 (Technical data)
Converting the duty cycle into seconds
Duty cycle [s] =Duty cycle [] times 180 s
100
ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC
Duty cycle =20 [] times 180 s
100= 36 s
In an ambient temperature of -20 to +35degC this results in
a maximum duty cycle of 36 s within 180 s for the ignitiontransformer
For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute
0 60 120 180
tZ = 6 s
t [s]Legend
Project planning information
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1114
TZI TGI middot Edition 0211
11
6 Accessories
61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)
Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409
62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308
Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307
Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 214
TZI TGI middot Edition 0211
2
983156 = To be continued
ContentsIgnition transformers TZI TGI 1
Contents 2
1 Application 311 Examples of application 5
111 Double-electrode operation 5112 Single-electrode operation 5
2 Certification 6
3 Function 731 Connection diagrams 7
4 Selection 8
41 Selection table 8411 Type code 8
5 Project planning information 951 Operation 952 Installation 953 Cable selection 954 Ignition electrode 955 Reduction of EMC wiring 9
56 Single-electrode operation 1057 Intermittent operationStar electrodes 1058 Duty cycle 10
6 Accessories 1161 High-voltage cable 1162 Radio interference suppressed electrode adapters 11
7 Technical data 12
71 Dimensions 13Feedback 14
Contact 14
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 314
TZI TGI middot Edition 0211
3
TZI 5-1520 TZI 5-15100 TZI 7-2520TZI 75-12100 TZI 75-2033 TGI
1 ApplicationIgnition transformers TZI and TGI are designed for high-voltagespark ignition of gas burners and gas-ignited or directly ig-nited oil burners The ignition transformers can also be usedon burners with single-electrode operation the ignition cur-
rent and ionization current flow over a common electrodeIgnition transformer TZI fulfils the requirements for enclosureIP 20 It is suitable for installation in a control cabinet Igni-tion transformer TGI in its die-cast aluminium housing meetsthe requirements for enclosure IP 65 It is suitable for on-sitemounting near to the burner
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 414TZI TGI middot Edition 0211
4
Bogie hearth forging furnacein the metallurgical industry
Intermittent shuttle kilnin the ceramics industry
Walking beam furnacewith overhead firing
Application
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 514TZI TGI middot Edition 0211
5
IFD 258
BIO
BIC
VAS
VRR
GIK
N
L1
TGI
IFD 258
BIO
BIC
VAS
GIK
NL1
TGI
VRR
Application
11 Examples of application
111 Double-electrode operationIgnition using ignition electrode
Ignition transformer TGI is supplied with voltage via the au-tomatic burner control unit IFD 258 The ignition transformergenerates a high voltage This high voltage creates ignitionsparks between the ignition electrode and burner ground Afterthe burner start a current flows via the ionization electrodefor flame control
112 Single-electrode operationIgnition using an ignition and ionization electrode
After burner start a flame control current flows via the sameelectrode that is also used for ignition
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211
6
2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC
TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211
7
H
empty 7 mm (0275 )
3 Function
31 Connection diagramsIgnition double-electrode operation
Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-
tween ignition and monitoring is performed by the automaticburner control unit
High-voltage connectionCut end of high-voltage cable is inserted into the shroud and
screwed onto the wood screw (H)
Legend
H High-voltage connectionbr Connection cable brown
sw Connection cable black
bl Connection cable blue
gnge Connection cable greenyellow
sw
bl
gnge
H
br
L1
N
Burner control unit
sw
bl
gnge
H
br
I Z
L1
N
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211
8
4 Selection
41 Selection table
R W
TZI 5-1520
TZI 5-15100
TZI 7-2520
TZI 75-12100
TZI 75-2033
TGI 5-15100
TGI 7-2520
TGI 75-12100
TGI 75-2033
rder example
TZI 5-1520W
411 Type code
Code Description
TZI
TGI
Ignition transformer
Ignition transformer enclosed5775
High voltage 5 kV7 kV
75 kV
-12-15-20-25
Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)
20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)
20
33100
Duty cycle 20
33100
RW
Mains voltage 115 V230 V
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211
9
5 Project planning information
51 OperationThe ignition transformers are suitable only for applications
for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created
52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down
Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)
TZILength of the mains cable is 410 mm
The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary
53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations
Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer
Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)
Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity
TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable
gland see page 13 (Dimensions)
54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm
55 Reduction of EMC wiringAvoid external electrical interference
Lay cables individually and if possible not in a metal conduit
Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible
Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)
Use an interference suppressed electrode adapter on the
burner (with 1 Ω resistor) see page 11 (Accessories)
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211
10
56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units
For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged
57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On
Off intermittent operation or when using burners with starelectrodes
58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded
-20 0 20 40 60
0
20
40
60
80
100
D u t y c y c l e [ ]
Ambient temperature [degC]
For ignition transformers the duty cycle is dependent on theambient temperature
TZITGI duty cycle in ndash see 12 (Technical data)
Converting the duty cycle into seconds
Duty cycle [s] =Duty cycle [] times 180 s
100
ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC
Duty cycle =20 [] times 180 s
100= 36 s
In an ambient temperature of -20 to +35degC this results in
a maximum duty cycle of 36 s within 180 s for the ignitiontransformer
For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute
0 60 120 180
tZ = 6 s
t [s]Legend
Project planning information
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1114
TZI TGI middot Edition 0211
11
6 Accessories
61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)
Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409
62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308
Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307
Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 314
TZI TGI middot Edition 0211
3
TZI 5-1520 TZI 5-15100 TZI 7-2520TZI 75-12100 TZI 75-2033 TGI
1 ApplicationIgnition transformers TZI and TGI are designed for high-voltagespark ignition of gas burners and gas-ignited or directly ig-nited oil burners The ignition transformers can also be usedon burners with single-electrode operation the ignition cur-
rent and ionization current flow over a common electrodeIgnition transformer TZI fulfils the requirements for enclosureIP 20 It is suitable for installation in a control cabinet Igni-tion transformer TGI in its die-cast aluminium housing meetsthe requirements for enclosure IP 65 It is suitable for on-sitemounting near to the burner
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 414TZI TGI middot Edition 0211
4
Bogie hearth forging furnacein the metallurgical industry
Intermittent shuttle kilnin the ceramics industry
Walking beam furnacewith overhead firing
Application
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 514TZI TGI middot Edition 0211
5
IFD 258
BIO
BIC
VAS
VRR
GIK
N
L1
TGI
IFD 258
BIO
BIC
VAS
GIK
NL1
TGI
VRR
Application
11 Examples of application
111 Double-electrode operationIgnition using ignition electrode
Ignition transformer TGI is supplied with voltage via the au-tomatic burner control unit IFD 258 The ignition transformergenerates a high voltage This high voltage creates ignitionsparks between the ignition electrode and burner ground Afterthe burner start a current flows via the ionization electrodefor flame control
112 Single-electrode operationIgnition using an ignition and ionization electrode
After burner start a flame control current flows via the sameelectrode that is also used for ignition
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211
6
2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC
TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211
7
H
empty 7 mm (0275 )
3 Function
31 Connection diagramsIgnition double-electrode operation
Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-
tween ignition and monitoring is performed by the automaticburner control unit
High-voltage connectionCut end of high-voltage cable is inserted into the shroud and
screwed onto the wood screw (H)
Legend
H High-voltage connectionbr Connection cable brown
sw Connection cable black
bl Connection cable blue
gnge Connection cable greenyellow
sw
bl
gnge
H
br
L1
N
Burner control unit
sw
bl
gnge
H
br
I Z
L1
N
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211
8
4 Selection
41 Selection table
R W
TZI 5-1520
TZI 5-15100
TZI 7-2520
TZI 75-12100
TZI 75-2033
TGI 5-15100
TGI 7-2520
TGI 75-12100
TGI 75-2033
rder example
TZI 5-1520W
411 Type code
Code Description
TZI
TGI
Ignition transformer
Ignition transformer enclosed5775
High voltage 5 kV7 kV
75 kV
-12-15-20-25
Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)
20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)
20
33100
Duty cycle 20
33100
RW
Mains voltage 115 V230 V
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211
9
5 Project planning information
51 OperationThe ignition transformers are suitable only for applications
for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created
52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down
Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)
TZILength of the mains cable is 410 mm
The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary
53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations
Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer
Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)
Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity
TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable
gland see page 13 (Dimensions)
54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm
55 Reduction of EMC wiringAvoid external electrical interference
Lay cables individually and if possible not in a metal conduit
Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible
Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)
Use an interference suppressed electrode adapter on the
burner (with 1 Ω resistor) see page 11 (Accessories)
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211
10
56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units
For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged
57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On
Off intermittent operation or when using burners with starelectrodes
58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded
-20 0 20 40 60
0
20
40
60
80
100
D u t y c y c l e [ ]
Ambient temperature [degC]
For ignition transformers the duty cycle is dependent on theambient temperature
TZITGI duty cycle in ndash see 12 (Technical data)
Converting the duty cycle into seconds
Duty cycle [s] =Duty cycle [] times 180 s
100
ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC
Duty cycle =20 [] times 180 s
100= 36 s
In an ambient temperature of -20 to +35degC this results in
a maximum duty cycle of 36 s within 180 s for the ignitiontransformer
For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute
0 60 120 180
tZ = 6 s
t [s]Legend
Project planning information
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1114
TZI TGI middot Edition 0211
11
6 Accessories
61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)
Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409
62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308
Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307
Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 414TZI TGI middot Edition 0211
4
Bogie hearth forging furnacein the metallurgical industry
Intermittent shuttle kilnin the ceramics industry
Walking beam furnacewith overhead firing
Application
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 514TZI TGI middot Edition 0211
5
IFD 258
BIO
BIC
VAS
VRR
GIK
N
L1
TGI
IFD 258
BIO
BIC
VAS
GIK
NL1
TGI
VRR
Application
11 Examples of application
111 Double-electrode operationIgnition using ignition electrode
Ignition transformer TGI is supplied with voltage via the au-tomatic burner control unit IFD 258 The ignition transformergenerates a high voltage This high voltage creates ignitionsparks between the ignition electrode and burner ground Afterthe burner start a current flows via the ionization electrodefor flame control
112 Single-electrode operationIgnition using an ignition and ionization electrode
After burner start a flame control current flows via the sameelectrode that is also used for ignition
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211
6
2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC
TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211
7
H
empty 7 mm (0275 )
3 Function
31 Connection diagramsIgnition double-electrode operation
Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-
tween ignition and monitoring is performed by the automaticburner control unit
High-voltage connectionCut end of high-voltage cable is inserted into the shroud and
screwed onto the wood screw (H)
Legend
H High-voltage connectionbr Connection cable brown
sw Connection cable black
bl Connection cable blue
gnge Connection cable greenyellow
sw
bl
gnge
H
br
L1
N
Burner control unit
sw
bl
gnge
H
br
I Z
L1
N
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211
8
4 Selection
41 Selection table
R W
TZI 5-1520
TZI 5-15100
TZI 7-2520
TZI 75-12100
TZI 75-2033
TGI 5-15100
TGI 7-2520
TGI 75-12100
TGI 75-2033
rder example
TZI 5-1520W
411 Type code
Code Description
TZI
TGI
Ignition transformer
Ignition transformer enclosed5775
High voltage 5 kV7 kV
75 kV
-12-15-20-25
Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)
20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)
20
33100
Duty cycle 20
33100
RW
Mains voltage 115 V230 V
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211
9
5 Project planning information
51 OperationThe ignition transformers are suitable only for applications
for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created
52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down
Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)
TZILength of the mains cable is 410 mm
The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary
53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations
Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer
Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)
Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity
TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable
gland see page 13 (Dimensions)
54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm
55 Reduction of EMC wiringAvoid external electrical interference
Lay cables individually and if possible not in a metal conduit
Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible
Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)
Use an interference suppressed electrode adapter on the
burner (with 1 Ω resistor) see page 11 (Accessories)
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211
10
56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units
For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged
57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On
Off intermittent operation or when using burners with starelectrodes
58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded
-20 0 20 40 60
0
20
40
60
80
100
D u t y c y c l e [ ]
Ambient temperature [degC]
For ignition transformers the duty cycle is dependent on theambient temperature
TZITGI duty cycle in ndash see 12 (Technical data)
Converting the duty cycle into seconds
Duty cycle [s] =Duty cycle [] times 180 s
100
ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC
Duty cycle =20 [] times 180 s
100= 36 s
In an ambient temperature of -20 to +35degC this results in
a maximum duty cycle of 36 s within 180 s for the ignitiontransformer
For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute
0 60 120 180
tZ = 6 s
t [s]Legend
Project planning information
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1114
TZI TGI middot Edition 0211
11
6 Accessories
61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)
Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409
62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308
Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307
Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 514TZI TGI middot Edition 0211
5
IFD 258
BIO
BIC
VAS
VRR
GIK
N
L1
TGI
IFD 258
BIO
BIC
VAS
GIK
NL1
TGI
VRR
Application
11 Examples of application
111 Double-electrode operationIgnition using ignition electrode
Ignition transformer TGI is supplied with voltage via the au-tomatic burner control unit IFD 258 The ignition transformergenerates a high voltage This high voltage creates ignitionsparks between the ignition electrode and burner ground Afterthe burner start a current flows via the ionization electrodefor flame control
112 Single-electrode operationIgnition using an ignition and ionization electrode
After burner start a flame control current flows via the sameelectrode that is also used for ignition
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211
6
2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC
TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211
7
H
empty 7 mm (0275 )
3 Function
31 Connection diagramsIgnition double-electrode operation
Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-
tween ignition and monitoring is performed by the automaticburner control unit
High-voltage connectionCut end of high-voltage cable is inserted into the shroud and
screwed onto the wood screw (H)
Legend
H High-voltage connectionbr Connection cable brown
sw Connection cable black
bl Connection cable blue
gnge Connection cable greenyellow
sw
bl
gnge
H
br
L1
N
Burner control unit
sw
bl
gnge
H
br
I Z
L1
N
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211
8
4 Selection
41 Selection table
R W
TZI 5-1520
TZI 5-15100
TZI 7-2520
TZI 75-12100
TZI 75-2033
TGI 5-15100
TGI 7-2520
TGI 75-12100
TGI 75-2033
rder example
TZI 5-1520W
411 Type code
Code Description
TZI
TGI
Ignition transformer
Ignition transformer enclosed5775
High voltage 5 kV7 kV
75 kV
-12-15-20-25
Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)
20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)
20
33100
Duty cycle 20
33100
RW
Mains voltage 115 V230 V
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211
9
5 Project planning information
51 OperationThe ignition transformers are suitable only for applications
for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created
52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down
Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)
TZILength of the mains cable is 410 mm
The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary
53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations
Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer
Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)
Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity
TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable
gland see page 13 (Dimensions)
54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm
55 Reduction of EMC wiringAvoid external electrical interference
Lay cables individually and if possible not in a metal conduit
Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible
Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)
Use an interference suppressed electrode adapter on the
burner (with 1 Ω resistor) see page 11 (Accessories)
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211
10
56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units
For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged
57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On
Off intermittent operation or when using burners with starelectrodes
58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded
-20 0 20 40 60
0
20
40
60
80
100
D u t y c y c l e [ ]
Ambient temperature [degC]
For ignition transformers the duty cycle is dependent on theambient temperature
TZITGI duty cycle in ndash see 12 (Technical data)
Converting the duty cycle into seconds
Duty cycle [s] =Duty cycle [] times 180 s
100
ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC
Duty cycle =20 [] times 180 s
100= 36 s
In an ambient temperature of -20 to +35degC this results in
a maximum duty cycle of 36 s within 180 s for the ignitiontransformer
For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute
0 60 120 180
tZ = 6 s
t [s]Legend
Project planning information
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1114
TZI TGI middot Edition 0211
11
6 Accessories
61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)
Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409
62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308
Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307
Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211
6
2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC
TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211
7
H
empty 7 mm (0275 )
3 Function
31 Connection diagramsIgnition double-electrode operation
Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-
tween ignition and monitoring is performed by the automaticburner control unit
High-voltage connectionCut end of high-voltage cable is inserted into the shroud and
screwed onto the wood screw (H)
Legend
H High-voltage connectionbr Connection cable brown
sw Connection cable black
bl Connection cable blue
gnge Connection cable greenyellow
sw
bl
gnge
H
br
L1
N
Burner control unit
sw
bl
gnge
H
br
I Z
L1
N
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211
8
4 Selection
41 Selection table
R W
TZI 5-1520
TZI 5-15100
TZI 7-2520
TZI 75-12100
TZI 75-2033
TGI 5-15100
TGI 7-2520
TGI 75-12100
TGI 75-2033
rder example
TZI 5-1520W
411 Type code
Code Description
TZI
TGI
Ignition transformer
Ignition transformer enclosed5775
High voltage 5 kV7 kV
75 kV
-12-15-20-25
Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)
20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)
20
33100
Duty cycle 20
33100
RW
Mains voltage 115 V230 V
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211
9
5 Project planning information
51 OperationThe ignition transformers are suitable only for applications
for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created
52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down
Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)
TZILength of the mains cable is 410 mm
The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary
53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations
Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer
Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)
Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity
TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable
gland see page 13 (Dimensions)
54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm
55 Reduction of EMC wiringAvoid external electrical interference
Lay cables individually and if possible not in a metal conduit
Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible
Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)
Use an interference suppressed electrode adapter on the
burner (with 1 Ω resistor) see page 11 (Accessories)
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211
10
56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units
For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged
57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On
Off intermittent operation or when using burners with starelectrodes
58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded
-20 0 20 40 60
0
20
40
60
80
100
D u t y c y c l e [ ]
Ambient temperature [degC]
For ignition transformers the duty cycle is dependent on theambient temperature
TZITGI duty cycle in ndash see 12 (Technical data)
Converting the duty cycle into seconds
Duty cycle [s] =Duty cycle [] times 180 s
100
ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC
Duty cycle =20 [] times 180 s
100= 36 s
In an ambient temperature of -20 to +35degC this results in
a maximum duty cycle of 36 s within 180 s for the ignitiontransformer
For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute
0 60 120 180
tZ = 6 s
t [s]Legend
Project planning information
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1114
TZI TGI middot Edition 0211
11
6 Accessories
61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)
Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409
62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308
Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307
Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211
7
H
empty 7 mm (0275 )
3 Function
31 Connection diagramsIgnition double-electrode operation
Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-
tween ignition and monitoring is performed by the automaticburner control unit
High-voltage connectionCut end of high-voltage cable is inserted into the shroud and
screwed onto the wood screw (H)
Legend
H High-voltage connectionbr Connection cable brown
sw Connection cable black
bl Connection cable blue
gnge Connection cable greenyellow
sw
bl
gnge
H
br
L1
N
Burner control unit
sw
bl
gnge
H
br
I Z
L1
N
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211
8
4 Selection
41 Selection table
R W
TZI 5-1520
TZI 5-15100
TZI 7-2520
TZI 75-12100
TZI 75-2033
TGI 5-15100
TGI 7-2520
TGI 75-12100
TGI 75-2033
rder example
TZI 5-1520W
411 Type code
Code Description
TZI
TGI
Ignition transformer
Ignition transformer enclosed5775
High voltage 5 kV7 kV
75 kV
-12-15-20-25
Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)
20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)
20
33100
Duty cycle 20
33100
RW
Mains voltage 115 V230 V
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211
9
5 Project planning information
51 OperationThe ignition transformers are suitable only for applications
for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created
52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down
Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)
TZILength of the mains cable is 410 mm
The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary
53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations
Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer
Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)
Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity
TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable
gland see page 13 (Dimensions)
54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm
55 Reduction of EMC wiringAvoid external electrical interference
Lay cables individually and if possible not in a metal conduit
Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible
Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)
Use an interference suppressed electrode adapter on the
burner (with 1 Ω resistor) see page 11 (Accessories)
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211
10
56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units
For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged
57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On
Off intermittent operation or when using burners with starelectrodes
58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded
-20 0 20 40 60
0
20
40
60
80
100
D u t y c y c l e [ ]
Ambient temperature [degC]
For ignition transformers the duty cycle is dependent on theambient temperature
TZITGI duty cycle in ndash see 12 (Technical data)
Converting the duty cycle into seconds
Duty cycle [s] =Duty cycle [] times 180 s
100
ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC
Duty cycle =20 [] times 180 s
100= 36 s
In an ambient temperature of -20 to +35degC this results in
a maximum duty cycle of 36 s within 180 s for the ignitiontransformer
For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute
0 60 120 180
tZ = 6 s
t [s]Legend
Project planning information
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1114
TZI TGI middot Edition 0211
11
6 Accessories
61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)
Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409
62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308
Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307
Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211
8
4 Selection
41 Selection table
R W
TZI 5-1520
TZI 5-15100
TZI 7-2520
TZI 75-12100
TZI 75-2033
TGI 5-15100
TGI 7-2520
TGI 75-12100
TGI 75-2033
rder example
TZI 5-1520W
411 Type code
Code Description
TZI
TGI
Ignition transformer
Ignition transformer enclosed5775
High voltage 5 kV7 kV
75 kV
-12-15-20-25
Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)
20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)
20
33100
Duty cycle 20
33100
RW
Mains voltage 115 V230 V
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211
9
5 Project planning information
51 OperationThe ignition transformers are suitable only for applications
for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created
52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down
Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)
TZILength of the mains cable is 410 mm
The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary
53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations
Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer
Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)
Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity
TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable
gland see page 13 (Dimensions)
54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm
55 Reduction of EMC wiringAvoid external electrical interference
Lay cables individually and if possible not in a metal conduit
Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible
Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)
Use an interference suppressed electrode adapter on the
burner (with 1 Ω resistor) see page 11 (Accessories)
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211
10
56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units
For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged
57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On
Off intermittent operation or when using burners with starelectrodes
58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded
-20 0 20 40 60
0
20
40
60
80
100
D u t y c y c l e [ ]
Ambient temperature [degC]
For ignition transformers the duty cycle is dependent on theambient temperature
TZITGI duty cycle in ndash see 12 (Technical data)
Converting the duty cycle into seconds
Duty cycle [s] =Duty cycle [] times 180 s
100
ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC
Duty cycle =20 [] times 180 s
100= 36 s
In an ambient temperature of -20 to +35degC this results in
a maximum duty cycle of 36 s within 180 s for the ignitiontransformer
For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute
0 60 120 180
tZ = 6 s
t [s]Legend
Project planning information
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1114
TZI TGI middot Edition 0211
11
6 Accessories
61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)
Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409
62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308
Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307
Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211
9
5 Project planning information
51 OperationThe ignition transformers are suitable only for applications
for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created
52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down
Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)
TZILength of the mains cable is 410 mm
The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary
53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations
Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer
Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)
Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity
TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable
gland see page 13 (Dimensions)
54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm
55 Reduction of EMC wiringAvoid external electrical interference
Lay cables individually and if possible not in a metal conduit
Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible
Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)
Use an interference suppressed electrode adapter on the
burner (with 1 Ω resistor) see page 11 (Accessories)
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211
10
56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units
For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged
57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On
Off intermittent operation or when using burners with starelectrodes
58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded
-20 0 20 40 60
0
20
40
60
80
100
D u t y c y c l e [ ]
Ambient temperature [degC]
For ignition transformers the duty cycle is dependent on theambient temperature
TZITGI duty cycle in ndash see 12 (Technical data)
Converting the duty cycle into seconds
Duty cycle [s] =Duty cycle [] times 180 s
100
ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC
Duty cycle =20 [] times 180 s
100= 36 s
In an ambient temperature of -20 to +35degC this results in
a maximum duty cycle of 36 s within 180 s for the ignitiontransformer
For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute
0 60 120 180
tZ = 6 s
t [s]Legend
Project planning information
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1114
TZI TGI middot Edition 0211
11
6 Accessories
61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)
Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409
62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308
Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307
Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211
10
56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units
For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged
57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On
Off intermittent operation or when using burners with starelectrodes
58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded
-20 0 20 40 60
0
20
40
60
80
100
D u t y c y c l e [ ]
Ambient temperature [degC]
For ignition transformers the duty cycle is dependent on theambient temperature
TZITGI duty cycle in ndash see 12 (Technical data)
Converting the duty cycle into seconds
Duty cycle [s] =Duty cycle [] times 180 s
100
ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC
Duty cycle =20 [] times 180 s
100= 36 s
In an ambient temperature of -20 to +35degC this results in
a maximum duty cycle of 36 s within 180 s for the ignitiontransformer
For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute
0 60 120 180
tZ = 6 s
t [s]Legend
Project planning information
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1114
TZI TGI middot Edition 0211
11
6 Accessories
61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)
Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409
62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308
Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307
Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1114
TZI TGI middot Edition 0211
11
6 Accessories
61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)
Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409
62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308
Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307
Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1214
TZI TGI middot Edition 0211
12
7 Technical dataType Input Output Duty cycle Enclosure Weight
V AC Hz A V mA kg
TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15
TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15
TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2
TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2
TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09
TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15
TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15
TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2
TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3
TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3
TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35
TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35
TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3
TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3
TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35
Values in brackets apply to 60 Hz
For temperatures between -20 and +35degC
Converting the duty cycle into seconds see page 10 (Duty cycle)
Ambient temperature-20 to +60degC
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1314
TZI TGI middot Edition 0211
13
73
7492
7 6986
73
92110
9992
7
TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033
TGI
Technical data
71 Dimensions
TZILength of connection cable 410 mm
TGI
140180
95 M20 (AF 27)
M20 (AF 24)
103
165
empty 50
78
6220
60
65
55
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck
7232019 Transformer Technical Information
httpslidepdfcomreaderfulltransformer-technical-information 1414
TZI TGI middot Edition 0211
14
Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs
ClarityFound information quickly
Searched for a long time
Didnrsquot find information
What is missing
ComprehensionCoherent
Too complicated
No answer
ScopeToo lit tle
Sufficient
Too wide
No answer
No answer
Navigation
I can find my way around
I got ldquolostrdquo
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
My scope of functions
Technical department
Sales
No answer
Remarks
(Adobe Reader 7 or higher required)
Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)
GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom
wwwkromschroedercomwwwelstercom
The current addresses of our internationalagents are available on the Internet
wwwkromschroedercom SalesWe reserve the right to make technical
modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved
0 3 2 5 0 8 4 6
Contact
Feedback
Kromschroumlder AG
MichaelRehkamp
mrehkampkromschroedercom
Osnabruumlck