transformer technical information

14
8.1.1 Edition 02.11 Technical Information · GB www.kromschroeder.com Electrical ignition of gas burners Ignition and burne r control with a single e lectrode possible For installation in a control cabinet or wall moun ting Complying with EN 61558-2-3 TZI 7,5-20/33R complies with CSA Ignition transformers TZI, TGI

Upload: vishal-v-bhagwat

Post on 12-Feb-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 114

811 Edition 0211

Technical Information middot GB

wwwkromschroedercom

bull Electrical ignition of gas burners

bull Ignition and burner control with a single electrode possible

bull For installation in a control cabinet or wall mounting

bull Complying with EN 61558-2-3

bull TZI 75-2033R complies with CSA

Ignition transformers TZI TGI

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 214

TZI TGI middot Edition 0211

2

983156 = To be continued

ContentsIgnition transformers TZI TGI 1

Contents 2

1 Application 311 Examples of application 5

111 Double-electrode operation 5112 Single-electrode operation 5

2 Certification 6

3 Function 731 Connection diagrams 7

4 Selection 8

41 Selection table 8411 Type code 8

5 Project planning information 951 Operation 952 Installation 953 Cable selection 954 Ignition electrode 955 Reduction of EMC wiring 9

56 Single-electrode operation 1057 Intermittent operationStar electrodes 1058 Duty cycle 10

6 Accessories 1161 High-voltage cable 1162 Radio interference suppressed electrode adapters 11

7 Technical data 12

71 Dimensions 13Feedback 14

Contact 14

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 314

TZI TGI middot Edition 0211

3

TZI 5-1520 TZI 5-15100 TZI 7-2520TZI 75-12100 TZI 75-2033 TGI

1 ApplicationIgnition transformers TZI and TGI are designed for high-voltagespark ignition of gas burners and gas-ignited or directly ig-nited oil burners The ignition transformers can also be usedon burners with single-electrode operation the ignition cur-

rent and ionization current flow over a common electrodeIgnition transformer TZI fulfils the requirements for enclosureIP 20 It is suitable for installation in a control cabinet Igni-tion transformer TGI in its die-cast aluminium housing meetsthe requirements for enclosure IP 65 It is suitable for on-sitemounting near to the burner

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 414TZI TGI middot Edition 0211

4

Bogie hearth forging furnacein the metallurgical industry

Intermittent shuttle kilnin the ceramics industry

Walking beam furnacewith overhead firing

Application

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 514TZI TGI middot Edition 0211

5

IFD 258

BIO

BIC

VAS

VRR

GIK

N

L1

TGI

IFD 258

BIO

BIC

VAS

GIK

NL1

TGI

VRR

Application

11 Examples of application

111 Double-electrode operationIgnition using ignition electrode

Ignition transformer TGI is supplied with voltage via the au-tomatic burner control unit IFD 258 The ignition transformergenerates a high voltage This high voltage creates ignitionsparks between the ignition electrode and burner ground Afterthe burner start a current flows via the ionization electrodefor flame control

112 Single-electrode operationIgnition using an ignition and ionization electrode

After burner start a flame control current flows via the sameelectrode that is also used for ignition

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211

6

2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC

TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211

7

H

empty 7 mm (0275 )

3 Function

31 Connection diagramsIgnition double-electrode operation

Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-

tween ignition and monitoring is performed by the automaticburner control unit

High-voltage connectionCut end of high-voltage cable is inserted into the shroud and

screwed onto the wood screw (H)

Legend

H High-voltage connectionbr Connection cable brown

sw Connection cable black

bl Connection cable blue

gnge Connection cable greenyellow

sw

bl

gnge

H

br

L1

N

Burner control unit

sw

bl

gnge

H

br

I Z

L1

N

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211

8

4 Selection

41 Selection table

R W

TZI 5-1520

TZI 5-15100

TZI 7-2520

TZI 75-12100

TZI 75-2033

TGI 5-15100

TGI 7-2520

TGI 75-12100

TGI 75-2033

rder example

TZI 5-1520W

411 Type code

Code Description

TZI

TGI

Ignition transformer

Ignition transformer enclosed5775

High voltage 5 kV7 kV

75 kV

-12-15-20-25

Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)

20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)

20

33100

Duty cycle 20

33100

RW

Mains voltage 115 V230 V

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211

9

5 Project planning information

51 OperationThe ignition transformers are suitable only for applications

for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created

52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down

Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)

TZILength of the mains cable is 410 mm

The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary

53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations

Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer

Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)

Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity

TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable

gland see page 13 (Dimensions)

54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm

55 Reduction of EMC wiringAvoid external electrical interference

Lay cables individually and if possible not in a metal conduit

Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible

Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)

Use an interference suppressed electrode adapter on the

burner (with 1 Ω resistor) see page 11 (Accessories)

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211

10

56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units

For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged

57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On

Off intermittent operation or when using burners with starelectrodes

58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded

-20 0 20 40 60

0

20

40

60

80

100

D u t y c y c l e [ ]

Ambient temperature [degC]

For ignition transformers the duty cycle is dependent on theambient temperature

TZITGI duty cycle in ndash see 12 (Technical data)

Converting the duty cycle into seconds

Duty cycle [s] =Duty cycle [] times 180 s

100

ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC

Duty cycle =20 [] times 180 s

100= 36 s

In an ambient temperature of -20 to +35degC this results in

a maximum duty cycle of 36 s within 180 s for the ignitiontransformer

For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute

0 60 120 180

tZ = 6 s

t [s]Legend

Project planning information

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1114

TZI TGI middot Edition 0211

11

6 Accessories

61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)

Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409

62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308

Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307

Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 214

TZI TGI middot Edition 0211

2

983156 = To be continued

ContentsIgnition transformers TZI TGI 1

Contents 2

1 Application 311 Examples of application 5

111 Double-electrode operation 5112 Single-electrode operation 5

2 Certification 6

3 Function 731 Connection diagrams 7

4 Selection 8

41 Selection table 8411 Type code 8

5 Project planning information 951 Operation 952 Installation 953 Cable selection 954 Ignition electrode 955 Reduction of EMC wiring 9

56 Single-electrode operation 1057 Intermittent operationStar electrodes 1058 Duty cycle 10

6 Accessories 1161 High-voltage cable 1162 Radio interference suppressed electrode adapters 11

7 Technical data 12

71 Dimensions 13Feedback 14

Contact 14

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 314

TZI TGI middot Edition 0211

3

TZI 5-1520 TZI 5-15100 TZI 7-2520TZI 75-12100 TZI 75-2033 TGI

1 ApplicationIgnition transformers TZI and TGI are designed for high-voltagespark ignition of gas burners and gas-ignited or directly ig-nited oil burners The ignition transformers can also be usedon burners with single-electrode operation the ignition cur-

rent and ionization current flow over a common electrodeIgnition transformer TZI fulfils the requirements for enclosureIP 20 It is suitable for installation in a control cabinet Igni-tion transformer TGI in its die-cast aluminium housing meetsthe requirements for enclosure IP 65 It is suitable for on-sitemounting near to the burner

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 414TZI TGI middot Edition 0211

4

Bogie hearth forging furnacein the metallurgical industry

Intermittent shuttle kilnin the ceramics industry

Walking beam furnacewith overhead firing

Application

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 514TZI TGI middot Edition 0211

5

IFD 258

BIO

BIC

VAS

VRR

GIK

N

L1

TGI

IFD 258

BIO

BIC

VAS

GIK

NL1

TGI

VRR

Application

11 Examples of application

111 Double-electrode operationIgnition using ignition electrode

Ignition transformer TGI is supplied with voltage via the au-tomatic burner control unit IFD 258 The ignition transformergenerates a high voltage This high voltage creates ignitionsparks between the ignition electrode and burner ground Afterthe burner start a current flows via the ionization electrodefor flame control

112 Single-electrode operationIgnition using an ignition and ionization electrode

After burner start a flame control current flows via the sameelectrode that is also used for ignition

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211

6

2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC

TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211

7

H

empty 7 mm (0275 )

3 Function

31 Connection diagramsIgnition double-electrode operation

Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-

tween ignition and monitoring is performed by the automaticburner control unit

High-voltage connectionCut end of high-voltage cable is inserted into the shroud and

screwed onto the wood screw (H)

Legend

H High-voltage connectionbr Connection cable brown

sw Connection cable black

bl Connection cable blue

gnge Connection cable greenyellow

sw

bl

gnge

H

br

L1

N

Burner control unit

sw

bl

gnge

H

br

I Z

L1

N

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211

8

4 Selection

41 Selection table

R W

TZI 5-1520

TZI 5-15100

TZI 7-2520

TZI 75-12100

TZI 75-2033

TGI 5-15100

TGI 7-2520

TGI 75-12100

TGI 75-2033

rder example

TZI 5-1520W

411 Type code

Code Description

TZI

TGI

Ignition transformer

Ignition transformer enclosed5775

High voltage 5 kV7 kV

75 kV

-12-15-20-25

Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)

20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)

20

33100

Duty cycle 20

33100

RW

Mains voltage 115 V230 V

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211

9

5 Project planning information

51 OperationThe ignition transformers are suitable only for applications

for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created

52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down

Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)

TZILength of the mains cable is 410 mm

The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary

53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations

Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer

Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)

Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity

TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable

gland see page 13 (Dimensions)

54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm

55 Reduction of EMC wiringAvoid external electrical interference

Lay cables individually and if possible not in a metal conduit

Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible

Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)

Use an interference suppressed electrode adapter on the

burner (with 1 Ω resistor) see page 11 (Accessories)

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211

10

56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units

For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged

57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On

Off intermittent operation or when using burners with starelectrodes

58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded

-20 0 20 40 60

0

20

40

60

80

100

D u t y c y c l e [ ]

Ambient temperature [degC]

For ignition transformers the duty cycle is dependent on theambient temperature

TZITGI duty cycle in ndash see 12 (Technical data)

Converting the duty cycle into seconds

Duty cycle [s] =Duty cycle [] times 180 s

100

ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC

Duty cycle =20 [] times 180 s

100= 36 s

In an ambient temperature of -20 to +35degC this results in

a maximum duty cycle of 36 s within 180 s for the ignitiontransformer

For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute

0 60 120 180

tZ = 6 s

t [s]Legend

Project planning information

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1114

TZI TGI middot Edition 0211

11

6 Accessories

61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)

Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409

62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308

Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307

Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 314

TZI TGI middot Edition 0211

3

TZI 5-1520 TZI 5-15100 TZI 7-2520TZI 75-12100 TZI 75-2033 TGI

1 ApplicationIgnition transformers TZI and TGI are designed for high-voltagespark ignition of gas burners and gas-ignited or directly ig-nited oil burners The ignition transformers can also be usedon burners with single-electrode operation the ignition cur-

rent and ionization current flow over a common electrodeIgnition transformer TZI fulfils the requirements for enclosureIP 20 It is suitable for installation in a control cabinet Igni-tion transformer TGI in its die-cast aluminium housing meetsthe requirements for enclosure IP 65 It is suitable for on-sitemounting near to the burner

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 414TZI TGI middot Edition 0211

4

Bogie hearth forging furnacein the metallurgical industry

Intermittent shuttle kilnin the ceramics industry

Walking beam furnacewith overhead firing

Application

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 514TZI TGI middot Edition 0211

5

IFD 258

BIO

BIC

VAS

VRR

GIK

N

L1

TGI

IFD 258

BIO

BIC

VAS

GIK

NL1

TGI

VRR

Application

11 Examples of application

111 Double-electrode operationIgnition using ignition electrode

Ignition transformer TGI is supplied with voltage via the au-tomatic burner control unit IFD 258 The ignition transformergenerates a high voltage This high voltage creates ignitionsparks between the ignition electrode and burner ground Afterthe burner start a current flows via the ionization electrodefor flame control

112 Single-electrode operationIgnition using an ignition and ionization electrode

After burner start a flame control current flows via the sameelectrode that is also used for ignition

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211

6

2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC

TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211

7

H

empty 7 mm (0275 )

3 Function

31 Connection diagramsIgnition double-electrode operation

Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-

tween ignition and monitoring is performed by the automaticburner control unit

High-voltage connectionCut end of high-voltage cable is inserted into the shroud and

screwed onto the wood screw (H)

Legend

H High-voltage connectionbr Connection cable brown

sw Connection cable black

bl Connection cable blue

gnge Connection cable greenyellow

sw

bl

gnge

H

br

L1

N

Burner control unit

sw

bl

gnge

H

br

I Z

L1

N

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211

8

4 Selection

41 Selection table

R W

TZI 5-1520

TZI 5-15100

TZI 7-2520

TZI 75-12100

TZI 75-2033

TGI 5-15100

TGI 7-2520

TGI 75-12100

TGI 75-2033

rder example

TZI 5-1520W

411 Type code

Code Description

TZI

TGI

Ignition transformer

Ignition transformer enclosed5775

High voltage 5 kV7 kV

75 kV

-12-15-20-25

Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)

20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)

20

33100

Duty cycle 20

33100

RW

Mains voltage 115 V230 V

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211

9

5 Project planning information

51 OperationThe ignition transformers are suitable only for applications

for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created

52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down

Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)

TZILength of the mains cable is 410 mm

The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary

53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations

Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer

Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)

Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity

TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable

gland see page 13 (Dimensions)

54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm

55 Reduction of EMC wiringAvoid external electrical interference

Lay cables individually and if possible not in a metal conduit

Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible

Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)

Use an interference suppressed electrode adapter on the

burner (with 1 Ω resistor) see page 11 (Accessories)

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211

10

56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units

For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged

57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On

Off intermittent operation or when using burners with starelectrodes

58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded

-20 0 20 40 60

0

20

40

60

80

100

D u t y c y c l e [ ]

Ambient temperature [degC]

For ignition transformers the duty cycle is dependent on theambient temperature

TZITGI duty cycle in ndash see 12 (Technical data)

Converting the duty cycle into seconds

Duty cycle [s] =Duty cycle [] times 180 s

100

ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC

Duty cycle =20 [] times 180 s

100= 36 s

In an ambient temperature of -20 to +35degC this results in

a maximum duty cycle of 36 s within 180 s for the ignitiontransformer

For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute

0 60 120 180

tZ = 6 s

t [s]Legend

Project planning information

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1114

TZI TGI middot Edition 0211

11

6 Accessories

61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)

Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409

62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308

Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307

Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 414TZI TGI middot Edition 0211

4

Bogie hearth forging furnacein the metallurgical industry

Intermittent shuttle kilnin the ceramics industry

Walking beam furnacewith overhead firing

Application

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 514TZI TGI middot Edition 0211

5

IFD 258

BIO

BIC

VAS

VRR

GIK

N

L1

TGI

IFD 258

BIO

BIC

VAS

GIK

NL1

TGI

VRR

Application

11 Examples of application

111 Double-electrode operationIgnition using ignition electrode

Ignition transformer TGI is supplied with voltage via the au-tomatic burner control unit IFD 258 The ignition transformergenerates a high voltage This high voltage creates ignitionsparks between the ignition electrode and burner ground Afterthe burner start a current flows via the ionization electrodefor flame control

112 Single-electrode operationIgnition using an ignition and ionization electrode

After burner start a flame control current flows via the sameelectrode that is also used for ignition

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211

6

2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC

TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211

7

H

empty 7 mm (0275 )

3 Function

31 Connection diagramsIgnition double-electrode operation

Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-

tween ignition and monitoring is performed by the automaticburner control unit

High-voltage connectionCut end of high-voltage cable is inserted into the shroud and

screwed onto the wood screw (H)

Legend

H High-voltage connectionbr Connection cable brown

sw Connection cable black

bl Connection cable blue

gnge Connection cable greenyellow

sw

bl

gnge

H

br

L1

N

Burner control unit

sw

bl

gnge

H

br

I Z

L1

N

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211

8

4 Selection

41 Selection table

R W

TZI 5-1520

TZI 5-15100

TZI 7-2520

TZI 75-12100

TZI 75-2033

TGI 5-15100

TGI 7-2520

TGI 75-12100

TGI 75-2033

rder example

TZI 5-1520W

411 Type code

Code Description

TZI

TGI

Ignition transformer

Ignition transformer enclosed5775

High voltage 5 kV7 kV

75 kV

-12-15-20-25

Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)

20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)

20

33100

Duty cycle 20

33100

RW

Mains voltage 115 V230 V

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211

9

5 Project planning information

51 OperationThe ignition transformers are suitable only for applications

for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created

52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down

Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)

TZILength of the mains cable is 410 mm

The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary

53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations

Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer

Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)

Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity

TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable

gland see page 13 (Dimensions)

54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm

55 Reduction of EMC wiringAvoid external electrical interference

Lay cables individually and if possible not in a metal conduit

Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible

Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)

Use an interference suppressed electrode adapter on the

burner (with 1 Ω resistor) see page 11 (Accessories)

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211

10

56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units

For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged

57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On

Off intermittent operation or when using burners with starelectrodes

58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded

-20 0 20 40 60

0

20

40

60

80

100

D u t y c y c l e [ ]

Ambient temperature [degC]

For ignition transformers the duty cycle is dependent on theambient temperature

TZITGI duty cycle in ndash see 12 (Technical data)

Converting the duty cycle into seconds

Duty cycle [s] =Duty cycle [] times 180 s

100

ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC

Duty cycle =20 [] times 180 s

100= 36 s

In an ambient temperature of -20 to +35degC this results in

a maximum duty cycle of 36 s within 180 s for the ignitiontransformer

For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute

0 60 120 180

tZ = 6 s

t [s]Legend

Project planning information

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1114

TZI TGI middot Edition 0211

11

6 Accessories

61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)

Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409

62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308

Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307

Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 514TZI TGI middot Edition 0211

5

IFD 258

BIO

BIC

VAS

VRR

GIK

N

L1

TGI

IFD 258

BIO

BIC

VAS

GIK

NL1

TGI

VRR

Application

11 Examples of application

111 Double-electrode operationIgnition using ignition electrode

Ignition transformer TGI is supplied with voltage via the au-tomatic burner control unit IFD 258 The ignition transformergenerates a high voltage This high voltage creates ignitionsparks between the ignition electrode and burner ground Afterthe burner start a current flows via the ionization electrodefor flame control

112 Single-electrode operationIgnition using an ignition and ionization electrode

After burner start a flame control current flows via the sameelectrode that is also used for ignition

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211

6

2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC

TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211

7

H

empty 7 mm (0275 )

3 Function

31 Connection diagramsIgnition double-electrode operation

Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-

tween ignition and monitoring is performed by the automaticburner control unit

High-voltage connectionCut end of high-voltage cable is inserted into the shroud and

screwed onto the wood screw (H)

Legend

H High-voltage connectionbr Connection cable brown

sw Connection cable black

bl Connection cable blue

gnge Connection cable greenyellow

sw

bl

gnge

H

br

L1

N

Burner control unit

sw

bl

gnge

H

br

I Z

L1

N

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211

8

4 Selection

41 Selection table

R W

TZI 5-1520

TZI 5-15100

TZI 7-2520

TZI 75-12100

TZI 75-2033

TGI 5-15100

TGI 7-2520

TGI 75-12100

TGI 75-2033

rder example

TZI 5-1520W

411 Type code

Code Description

TZI

TGI

Ignition transformer

Ignition transformer enclosed5775

High voltage 5 kV7 kV

75 kV

-12-15-20-25

Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)

20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)

20

33100

Duty cycle 20

33100

RW

Mains voltage 115 V230 V

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211

9

5 Project planning information

51 OperationThe ignition transformers are suitable only for applications

for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created

52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down

Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)

TZILength of the mains cable is 410 mm

The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary

53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations

Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer

Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)

Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity

TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable

gland see page 13 (Dimensions)

54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm

55 Reduction of EMC wiringAvoid external electrical interference

Lay cables individually and if possible not in a metal conduit

Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible

Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)

Use an interference suppressed electrode adapter on the

burner (with 1 Ω resistor) see page 11 (Accessories)

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211

10

56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units

For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged

57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On

Off intermittent operation or when using burners with starelectrodes

58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded

-20 0 20 40 60

0

20

40

60

80

100

D u t y c y c l e [ ]

Ambient temperature [degC]

For ignition transformers the duty cycle is dependent on theambient temperature

TZITGI duty cycle in ndash see 12 (Technical data)

Converting the duty cycle into seconds

Duty cycle [s] =Duty cycle [] times 180 s

100

ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC

Duty cycle =20 [] times 180 s

100= 36 s

In an ambient temperature of -20 to +35degC this results in

a maximum duty cycle of 36 s within 180 s for the ignitiontransformer

For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute

0 60 120 180

tZ = 6 s

t [s]Legend

Project planning information

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1114

TZI TGI middot Edition 0211

11

6 Accessories

61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)

Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409

62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308

Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307

Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 614TZI TGI middot Edition 0211

6

2 CertificationIgnition transformers TZI and TGI are built for applicationspursuant to the Machinery Directive 200642EC

TZI 75-2033RComplies with Canadian Standards AssociationCSA C222 No 13-1962

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211

7

H

empty 7 mm (0275 )

3 Function

31 Connection diagramsIgnition double-electrode operation

Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-

tween ignition and monitoring is performed by the automaticburner control unit

High-voltage connectionCut end of high-voltage cable is inserted into the shroud and

screwed onto the wood screw (H)

Legend

H High-voltage connectionbr Connection cable brown

sw Connection cable black

bl Connection cable blue

gnge Connection cable greenyellow

sw

bl

gnge

H

br

L1

N

Burner control unit

sw

bl

gnge

H

br

I Z

L1

N

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211

8

4 Selection

41 Selection table

R W

TZI 5-1520

TZI 5-15100

TZI 7-2520

TZI 75-12100

TZI 75-2033

TGI 5-15100

TGI 7-2520

TGI 75-12100

TGI 75-2033

rder example

TZI 5-1520W

411 Type code

Code Description

TZI

TGI

Ignition transformer

Ignition transformer enclosed5775

High voltage 5 kV7 kV

75 kV

-12-15-20-25

Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)

20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)

20

33100

Duty cycle 20

33100

RW

Mains voltage 115 V230 V

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211

9

5 Project planning information

51 OperationThe ignition transformers are suitable only for applications

for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created

52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down

Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)

TZILength of the mains cable is 410 mm

The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary

53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations

Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer

Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)

Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity

TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable

gland see page 13 (Dimensions)

54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm

55 Reduction of EMC wiringAvoid external electrical interference

Lay cables individually and if possible not in a metal conduit

Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible

Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)

Use an interference suppressed electrode adapter on the

burner (with 1 Ω resistor) see page 11 (Accessories)

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211

10

56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units

For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged

57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On

Off intermittent operation or when using burners with starelectrodes

58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded

-20 0 20 40 60

0

20

40

60

80

100

D u t y c y c l e [ ]

Ambient temperature [degC]

For ignition transformers the duty cycle is dependent on theambient temperature

TZITGI duty cycle in ndash see 12 (Technical data)

Converting the duty cycle into seconds

Duty cycle [s] =Duty cycle [] times 180 s

100

ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC

Duty cycle =20 [] times 180 s

100= 36 s

In an ambient temperature of -20 to +35degC this results in

a maximum duty cycle of 36 s within 180 s for the ignitiontransformer

For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute

0 60 120 180

tZ = 6 s

t [s]Legend

Project planning information

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1114

TZI TGI middot Edition 0211

11

6 Accessories

61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)

Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409

62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308

Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307

Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 714TZI TGI middot Edition 0211

7

H

empty 7 mm (0275 )

3 Function

31 Connection diagramsIgnition double-electrode operation

Ignition single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units The switchover be-

tween ignition and monitoring is performed by the automaticburner control unit

High-voltage connectionCut end of high-voltage cable is inserted into the shroud and

screwed onto the wood screw (H)

Legend

H High-voltage connectionbr Connection cable brown

sw Connection cable black

bl Connection cable blue

gnge Connection cable greenyellow

sw

bl

gnge

H

br

L1

N

Burner control unit

sw

bl

gnge

H

br

I Z

L1

N

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211

8

4 Selection

41 Selection table

R W

TZI 5-1520

TZI 5-15100

TZI 7-2520

TZI 75-12100

TZI 75-2033

TGI 5-15100

TGI 7-2520

TGI 75-12100

TGI 75-2033

rder example

TZI 5-1520W

411 Type code

Code Description

TZI

TGI

Ignition transformer

Ignition transformer enclosed5775

High voltage 5 kV7 kV

75 kV

-12-15-20-25

Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)

20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)

20

33100

Duty cycle 20

33100

RW

Mains voltage 115 V230 V

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211

9

5 Project planning information

51 OperationThe ignition transformers are suitable only for applications

for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created

52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down

Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)

TZILength of the mains cable is 410 mm

The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary

53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations

Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer

Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)

Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity

TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable

gland see page 13 (Dimensions)

54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm

55 Reduction of EMC wiringAvoid external electrical interference

Lay cables individually and if possible not in a metal conduit

Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible

Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)

Use an interference suppressed electrode adapter on the

burner (with 1 Ω resistor) see page 11 (Accessories)

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211

10

56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units

For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged

57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On

Off intermittent operation or when using burners with starelectrodes

58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded

-20 0 20 40 60

0

20

40

60

80

100

D u t y c y c l e [ ]

Ambient temperature [degC]

For ignition transformers the duty cycle is dependent on theambient temperature

TZITGI duty cycle in ndash see 12 (Technical data)

Converting the duty cycle into seconds

Duty cycle [s] =Duty cycle [] times 180 s

100

ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC

Duty cycle =20 [] times 180 s

100= 36 s

In an ambient temperature of -20 to +35degC this results in

a maximum duty cycle of 36 s within 180 s for the ignitiontransformer

For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute

0 60 120 180

tZ = 6 s

t [s]Legend

Project planning information

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1114

TZI TGI middot Edition 0211

11

6 Accessories

61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)

Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409

62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308

Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307

Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 814TZI TGI middot Edition 0211

8

4 Selection

41 Selection table

R W

TZI 5-1520

TZI 5-15100

TZI 7-2520

TZI 75-12100

TZI 75-2033

TGI 5-15100

TGI 7-2520

TGI 75-12100

TGI 75-2033

rder example

TZI 5-1520W

411 Type code

Code Description

TZI

TGI

Ignition transformer

Ignition transformer enclosed5775

High voltage 5 kV7 kV

75 kV

-12-15-20-25

Output current 12 mA at 50 Hz (9 mA at 60 Hz)15 mA at 50 Hz (11 mA at 60 Hz)

20 mA at 50 Hz (15 mA at 60 Hz)25 mA at 50 Hz (18 mA at 60 Hz)

20

33100

Duty cycle 20

33100

RW

Mains voltage 115 V230 V

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211

9

5 Project planning information

51 OperationThe ignition transformers are suitable only for applications

for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created

52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down

Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)

TZILength of the mains cable is 410 mm

The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary

53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations

Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer

Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)

Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity

TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable

gland see page 13 (Dimensions)

54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm

55 Reduction of EMC wiringAvoid external electrical interference

Lay cables individually and if possible not in a metal conduit

Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible

Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)

Use an interference suppressed electrode adapter on the

burner (with 1 Ω resistor) see page 11 (Accessories)

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211

10

56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units

For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged

57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On

Off intermittent operation or when using burners with starelectrodes

58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded

-20 0 20 40 60

0

20

40

60

80

100

D u t y c y c l e [ ]

Ambient temperature [degC]

For ignition transformers the duty cycle is dependent on theambient temperature

TZITGI duty cycle in ndash see 12 (Technical data)

Converting the duty cycle into seconds

Duty cycle [s] =Duty cycle [] times 180 s

100

ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC

Duty cycle =20 [] times 180 s

100= 36 s

In an ambient temperature of -20 to +35degC this results in

a maximum duty cycle of 36 s within 180 s for the ignitiontransformer

For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute

0 60 120 180

tZ = 6 s

t [s]Legend

Project planning information

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1114

TZI TGI middot Edition 0211

11

6 Accessories

61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)

Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409

62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308

Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307

Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 914TZI TGI middot Edition 0211

9

5 Project planning information

51 OperationThe ignition transformers are suitable only for applications

for igniting gas burners and gas-ignited or directly ignited oilburners Do not operate the transformers when no ignitionsparks are created

52 InstallationInstallation position for TZI and TGI install in a horizontal posi-tion or with the connections facing down

Install the ignition transformer directly on the burner (recom-mended ignition cable length max 5 m recommended lt 1 m)

TZILength of the mains cable is 410 mm

The ignition transformer has enclosure IP 20 In the event that adifferent enclosure is needed install the ignition transformer ina corresponding housing or in a control cabinet as necessary

53 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations

Install an equipotential bond (4 mm2 compliant with localregulations) between burner and ignition transformer

Use unscreened high-voltage cable for the ignition cable seepage 11 (Accessories)

Recommended ignition cable lengthmax 5 m recommended lt 1 m The longer the ignition ca-ble the lower the ignition capacity

TGIThe TGI housing has two AF 27 cable glands with double sealinserts for two cables up to 7 mm in diameter A seal insert for10 to 14 mm is enclosed and can be used in the AF 27 cable

gland see page 13 (Dimensions)

54 Ignition electrodeThe distance between ignition electrode and burner groundshould be 2 plusmn 05 mm

55 Reduction of EMC wiringAvoid external electrical interference

Lay cables individually and if possible not in a metal conduit

Do not lay UVionization cable and ignition cables togetherand lay them as far apart as possible

Screw the ignition cable securely into the high-voltage connec-tion on the ignition transformer and run to the burner by theshortest possible route see page 7 (High-voltage connection)

Use an interference suppressed electrode adapter on the

burner (with 1 Ω resistor) see page 11 (Accessories)

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211

10

56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units

For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged

57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On

Off intermittent operation or when using burners with starelectrodes

58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded

-20 0 20 40 60

0

20

40

60

80

100

D u t y c y c l e [ ]

Ambient temperature [degC]

For ignition transformers the duty cycle is dependent on theambient temperature

TZITGI duty cycle in ndash see 12 (Technical data)

Converting the duty cycle into seconds

Duty cycle [s] =Duty cycle [] times 180 s

100

ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC

Duty cycle =20 [] times 180 s

100= 36 s

In an ambient temperature of -20 to +35degC this results in

a maximum duty cycle of 36 s within 180 s for the ignitiontransformer

For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute

0 60 120 180

tZ = 6 s

t [s]Legend

Project planning information

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1114

TZI TGI middot Edition 0211

11

6 Accessories

61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)

Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409

62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308

Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307

Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1014TZI TGI middot Edition 0211

10

56 Single-electrode operationSingle-electrode operation is possible only in conjunction withsuitable automatic burner control units

For single-electrode operation wire an equipotential bondbetween the burner and the automatic burner control unitsee page 7 (Ignition single-electrode operation) Ensure thatthe wiring has been done correctly otherwise the connectedunits will be damaged

57 Intermittent operationStar electrodesWe recommend using 75 kV ignition transformers for On

Off intermittent operation or when using burners with starelectrodes

58 Duty cycleThe duty cycle indicates for how long the ignition transformercan be switched on within 180 s without it being overloaded

-20 0 20 40 60

0

20

40

60

80

100

D u t y c y c l e [ ]

Ambient temperature [degC]

For ignition transformers the duty cycle is dependent on theambient temperature

TZITGI duty cycle in ndash see 12 (Technical data)

Converting the duty cycle into seconds

Duty cycle [s] =Duty cycle [] times 180 s

100

ExampleIgnition transformer TZI 7-2520W with a duty cycle of 20 foran ambient temperature of -20 to +35degC

Duty cycle =20 [] times 180 s

100= 36 s

In an ambient temperature of -20 to +35degC this results in

a maximum duty cycle of 36 s within 180 s for the ignitiontransformer

For an automatic burner control unit with an ignition timetZ = 6 s for example the resultant timing cycle is a maximumof 2 ignitions per minute

0 60 120 180

tZ = 6 s

t [s]Legend

Project planning information

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1114

TZI TGI middot Edition 0211

11

6 Accessories

61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)

Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409

62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308

Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307

Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1114

TZI TGI middot Edition 0211

11

6 Accessories

61 High-voltage cableFZLSi 17 -50degC (-58degF) to 180degC (356degF)

Order No 04250410FZLK 17 -5degC (23degF) to 80degC (176degF)Order No 04250409

62 Radio interference suppressed electrode adaptersPlug cap 4 mm (016 inch) interference-suppressedOrder No 04115308

Straight adapter 4 mm (016 inch) interference-suppressedOrder No 04115307

Straight adapter 6 mm (02 inch) interference-suppressedOrder No 04115306

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1214

TZI TGI middot Edition 0211

12

7 Technical dataType Input Output Duty cycle Enclosure Weight

V AC Hz A V mA kg

TZI 5-1520W 230 50 (60) 05 (035) 5000 15 (11) 20 IP 20 09TZI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 20 15

TZI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 20 15

TZI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 20 2

TZI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 20 2

TZI 5-1520R 115 50 (60) 1 (07) 5000 15 (11) 20 IP 20 09

TZI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 20 15

TZI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 20 15

TZI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 20 2TZI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 20 2

TGI 5-15100W 230 50 (60) 045 (035) 5000 15 (11) 100 IP 65 3

TGI 7-2520W 230 50 (60) 11 (08) 7000 25 (18) 20 IP 65 3

TGI 75-12100W 230 50 (60) 06 (045) 7500 12 (9) 100 IP 65 35

TGI 75-2033W 230 50 (60) 09 (07) 7500 20 (15) 33 IP 65 35

TGI 5-15100R 115 50 (60) 09 (07) 5000 15 (11) 100 IP 65 3

TGI 7-2520R 115 50 (60) 22 (16) 7000 25 (18) 20 IP 65 3

TGI 75-12100R 115 50 (60) 12 (09) 7500 12 (9) 100 IP 65 35TGI 75-2033R 115 50 (60) 18 (135) 7500 20 (15) 33 IP 65 35

Values in brackets apply to 60 Hz

For temperatures between -20 and +35degC

Converting the duty cycle into seconds see page 10 (Duty cycle)

Ambient temperature-20 to +60degC

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1314

TZI TGI middot Edition 0211

13

73

7492

7 6986

73

92110

9992

7

TZI 5-1520 TZI 5-15100 TZI 7-2520 TZI 75-12100 TZI 75-2033

TGI

Technical data

71 Dimensions

TZILength of connection cable 410 mm

TGI

140180

95 M20 (AF 27)

M20 (AF 24)

103

165

empty 50

78

6220

60

65

55

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck

7232019 Transformer Technical Information

httpslidepdfcomreaderfulltransformer-technical-information 1414

TZI TGI middot Edition 0211

14

Finally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that wecan improve our documents further and suit them to your needs

ClarityFound information quickly

Searched for a long time

Didnrsquot find information

What is missing

ComprehensionCoherent

Too complicated

No answer

ScopeToo lit tle

Sufficient

Too wide

No answer

No answer

Navigation

I can find my way around

I got ldquolostrdquo

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

My scope of functions

Technical department

Sales

No answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbHPostfach 2809 middot 49018 OsnabruumlckStrotheweg 1 middot 49504 Lotte (Buumlren)

GermanyT +49 541 1214-0F +49 541 1214-370infokromschroedercom

wwwkromschroedercomwwwelstercom

The current addresses of our internationalagents are available on the Internet

wwwkromschroedercom SalesWe reserve the right to make technical

modifications in the interests of progressCopyright copy 2007 Elster GroupAll rights reserved

0 3 2 5 0 8 4 6

Contact

Feedback

Kromschroumlder AG

MichaelRehkamp

mrehkampkromschroedercom

Osnabruumlck