transformers
TRANSCRIPT
Section 1
Power Transformer
Transformer is a vital link in a power system which has made possible the power
generated at low voltages (6600 to 22000 volts) to be stepped up to extra high
voltages for transmission over long distances and then transformed to low voltages for
utilization at proper load centers. The power transformer adjusts the voltage to a
suitable level of power transmission from generation to the end-user. This means
stepping up the voltage at generation for long transmission with low losses and down
to domestic voltage manageable in the power outlet for home and industry. Power
transformers are used to convert from one voltage to another, at significant power
levels.
Types:
(i) Closed - Core type
The close-core transformer ha s heavily insulated coils wound around a
square metal doughnut. The magnetic field is provided with a continuous
path so that a relatively small amount of magnetic energy is lost. The
transformer core is laminated (made up of thin strips of steel pressed
together). Each strip or layer is insulated by paint or enamel. A laminated
core offers a much higher resistance to t he flow of eddy currents t han a core
of solid construction. The doughnut type of closed-core transformer is
efficient and is commonly utilized in x-ray generating equipment. Usually,
t he high voltage transformer is submerged in a special type of oil to ensure
maximum insulation and cooling.
Core type transformer
(ii) Shell type
The shell-type transformer is considered t he most efficient. Such
transformers are used in transmitting commercial power. The core of t he
1
shell-type transformer is made of laminated silicon steel sheets placed on top
of one another. The coils are wound around t he central section of t he core.
Since t he primary and secondary coils are wound close together around t he
core, t he windings must be highly insulated. A special insulating material is
coated on t he wires of both coils. For t he high voltage used in x-ray, t he
entire transformer is immersed in a container filled with a special insulating
oil or gas. The insulating oil also helps to cool t he transformer during
operation.
Shell type transformer
Power and water Corporation use Core type transformers.
Another classification is,
(i) Step Up or Step Down
A step up transformer works due to the secondary voltage being greater than the
primary voltage. When the secondary voltage is greater, it steps up the voltage input
at the power source. If the primary winding has fewer turns than the secondary
winding, the device becomes a step up transformer that will increase electrical
voltage.
Step up transformer
A step-down transformer is one whose secondary voltage is less than its primary
voltage. The step down transformer is designed to reduce the voltage from the
2
primary winding to the secondary winding. This kind of transformer "steps down" the
voltage applied to it.
Step down pole mounted transformer
(ii) Oil-Filled or Dry
Oil filled transformers are transformers filled with a highly refined mineral oil that is
used to insulate internal live parts of the transformer. The oil prevents corona and
manages temperature control inside the transformer for the prevention of equipment
and machinery overheating during the operation of large job applications. Because of
the oil inside the transformer being of non-combustible properties, these transformers
are very safe and can operate machinery for long periods of time.
Oil Filled transformer
Dry-type transformers have high sound levels, but oil filled transformers are much
quieter due to the immersion of its mechanisms in liquid. This results in less vibration
as well. Oil filled transformers require low maintenance and are quite
environmentally friendly. Dry type means it is cooled by normal air ventilation. The
dry type transformer does not require a liquid such as oil or silicone or any other
liquid to cool the electrical core and coils. Dry type transformers are voltage changing
3
(Step-up or Step-down) or isolation device that is air cooled rather than liquid cooled.
The transformer case is ventilated to allow air to flow and cool the coils.
Dry type transformer
(iii) Pole Mounted or Stationary
Pole mounted transformers are mounted on an electrical service pole, usually at
the level of the overhead cables but occasionally at ground level. Pole-mounted
transformers are the common breadbox transformers used for converting
distribution voltage to the 120/240 volt power used by homes and low-volume
commercial installations. Pole mounted transformers are used in extensive rural
area. These transformers range from 16 kVA to 500kVA and transform 11,000 to
33,000 volts down to a low voltage of 400 volts. Pole mounted transformers are
reasonably small in size and mass so that it is easy to install them on single pole
structures, and larger units on two-pole structures, approximately 5 meters above
the ground. This makes the transformers inaccessible, reducing the risk of injury
to animals and people and minimizing vandalism.
Pole mounted transformer
4
Most other transformers are ground-mounted. It is the broad category of transformers
that are neither pole mounted nor pad mounted, but that has exposed bushings and
therefore must be installed within some kind of enclosure to protect the public. Often,
the enclosures are simply gated chain-link fencing.
Ground-mounted transformer
Pad-mounted transformers are designed to be mounted on concrete pads. Pad mounted
transformers are usually three-phase (weight is less of a concern), and they are
generally intended for use in applications with the high and low voltage cables enter
the transformer from below such as in underground distribution applications. Pad
mounts are almost always contained within grounded metal housings that protect the
public from high voltage.
Pad-mounted transformer
(iv) Tapped or Center Tapped
A center tapped transformer is a transformer with a tap in the middle of the secondary
winding, usually used as a grounded neutral connection, intended to provide an option
for the secondary side to use the full available voltage output or just half of it
according to need. This is often done in North American residential wiring.
5
A tap on a transformer is an additional connection somewhere in the middle of the
winding, used either in conjunction with or instead of the connections at the ends of
the winding to provide different winding ratios. A center tap is a special case in which
the tap is halfway between the ends of the secondary winding, such that it can be used
to split the voltage output in half.
Center tapped pole mounted transformer
(v) Three Phases, Delta or Wye
Three-phase transformers are connected in delta or wye configurations. A delta
system is a good short-distance distribution system. It is used for neighbourhood and
small commercial loads close to the supplying substation. Only one voltage is
available between any two wires in a delta system. The delta system can be illustrated
by a simple triangle. A wire from each point of the triangle would represent a three-
phase, three-wire delta system. The voltage would be the same between any two
wires.
Delta Connection
In a wye system the voltage between any two wires will always give the same amount
of voltage on a three phase system. However, the voltage between any one of the
phase conductors (X1, X2, X3) and the neutral (X0) will be less than the power
conductors. For example, if the voltage between the power conductors of any two
phases of a three wire system is 208v, then the voltage from any phase conductor to
6
ground will be 120v. This is due to the square root of three phase power. In a wye
system, the voltage between any two power conductors will always be 1.732 (which is
the square root of 3) times the voltage between the neutral and any one of the power
phase conductors. The phase-to-ground voltage can be found by dividing the phase-
to-phase voltage by 1.732.
Wye Connection
Section 2
Instrumental Transformer
Instrument transformers are used for measuring voltage and current in electrical
power systems, and for power system protection and control. Where a voltage or
current is too large to be conveniently used by an instrument, it can be scaled down to
a standardized, low value. Instrument transformers isolate measurement, protection
and control circuitry from the high currents or voltages present on the circuits being
measured or controlled. There are two types of instrumental transformers:
(i) Voltage transformer and
(ii) Current transformer
1. Voltage Transformer:
Voltage transformers (VT) or potential transformers (PT) are another type of
instrument transformer, used for metering and protection in high-voltage circuits.
They are designed to present negligible load to the supply being measured and to have
a precise voltage ratio to accurately step down high voltages so that metering and
protective relay equipment can be operated at a lower potential.
Types:
Two types of voltage transformer are used for protective-relaying purposes. They are
(i) Instrument potential transformer or potential transformer and
(ii) Capacitance potential device.
7
A potential transformer is a conventional transformer having primary and secondary
windings. The primary winding is connected directly to the power circuit either
between two phases or between one phase and ground, depending on the rating of the
transformer and on the requirements of the application.
Potential transformer
A capacitance potential device is voltage-transforming equipment using a capacitance
voltage divider connected between phase and ground of a power circuit.
Two types of capacitance potential device are used for protective relaying:
(1) Coupling-capacitor potential device and
(2) Bushing potential device.
The two devices are basically alike, the principal difference being in the type of
capacitance voltage divider used, which in turn affects their rated burden.
The coupling-capacitor device uses as a voltage divider a coupling capacitor
consisting of a stack of series-connected capacitor units, and an auxiliary capacitor.
The bushing device uses the capacitance coupling of a specially constructed bushing
of a circuit breaker or power transformer. Both of these relaying potential devices are
called "Class A" devices. They are also sometimes called "In-phase" or "Resonant"
devices.
Other types of potential devices are "Class C" or "Out-of-phase" or "Non-resonant".
But they are not generally suitable for protective relaying.
Coupling Capacitor
8
Coupling-capacitor potential device Bushing potential device
2. Current Transformer:
Current transformer which is widely known as 'CT' converts line current (primary
current) in to small standard current values which are suitable for the devices to which
it is connected e.g. measuring instruments, meters, protection relays. Basic functions
of CTs are,
To reduce line current to a value which is suitable for standard measuring
instruments, relays etc.
To isolate the measuring instruments, meters, relays etc. from line voltage of an
installation.
To protect measuring instruments against short circuit currents.
To sense abnormalities in current and give current signals to protective relays to
isolate the defective system.
Current transformer
9
TYPES:
Current transformers are broadly classified as,
1. RING TYPE CTs: A CT which has an opening in the center to accommodate a
primary conductor (busbar or cable) through it.
Ring type
High grade silicon steel toroidal cores are carefully selected, then insulated and
protected by resin impregnated cotton/epoxy resin coating on which the secondary
winding is wound. Insulation taping and winding is done by computer controlled
machines. The enamel coated secondary winding wire is protected by self bonding
PVC insulation. Insulation levels, construction and treatment ensure maximum
reliability.
2. BAR - PRIMARY CTs: A CT in which the primary winding consists of bar of
suitable size and, material forming an integral part of the CT.
Bus - bar Primary
3. WOUND TYPE CTs: A CT having a primary winding of more than one full turn
wound on the core.
Wound type
10
Wound primary current transformers have primary windings that usually consist of
more that one turn. Wound primary transformers have an internal primary winding
and have no windows for the primary conductor to pass through. They have an
advantage in that the designer can make units with low current ratios that therefore
have better accuracy and burden capabilities. The primary of the transformer is
inserted in series with the conductor that is being monitored. For this reason there is
some hesitation to use wound primary transformers even though they may be the most
effective way to achieve the desired performance, especially for the low current ratio
requirements. The wound primary types may be designed using the toroidal cores
because of its excellent efficiency. The wound primary current transformers are more
common in the higher (greater than 600V class) voltage class current transformers as
it makes the problems of the higher voltages easier for the design engineer to cope
with, while keeping the design as cost effective as possible.
Ring type (or rectangular type) CTs are normally preferred over other types of CTs
because they are simple in construction, mechanically stronger and cheaper. In a ring
type/bar primary type CTs the working ampere-turns are determined by the primary
current and therefore the accuracy of these CTs becomes higher as the rated primary
current decreases. If higher accuracy and burdens are required for CTs of low primary
current, wound types CTs are used.
Current transformers are also classified in accordance with their nature of application,
i.e.
1. MEASURING CURRENT TRANSFORMER and
2. PROTECTIVE CURRENT TRANSFORMER.
MEASURING CT PROTECTIVE CT
11
CTs can be manufactured to suit above individual application or combined dual
purpose application. Following are general type of CTs;
1) INTERPOSING CTs: These CTs are used in conjunction with main CTs to alter
the ratio of main CT or to provide isolation to meters or relays from main CTs
secondary circuit. Primary current of these CTs are generally lower than 10 amps.
Due to which they are always wound primary types.
Interposing CT
2) SUMMATION CTs: When current flowing, in more than one feeder is required to
be metered summation current transformer are used. These CTs are provided with
more than one primary winding and one common secondary. The standard primary &
secondary currents are 5 or 1 amp.
Summation CT
3) BUSHING TYPE OR BUSDUCT CTs: These CTs are Ring type construction &
can be mounted on Bus-duct or Bushing turret of power transformer.
12
Siemens SF6 Circuit Breaker With externally mounted bushing CTs
4) CORE BALANCE CTs: These are ring type CTs & suitable for the measurement
of the sum of three phase currents in a 3-ph cable. Under normal operating conditions
this sum is zero. In the event of an earth-fault the sum of the current is equal to the
zero sequence current. These CTs are generally used with English Electric make
CTUM 15 static relay.
Core Balance CT
5) FURNACE CTs: These transformers are generally split core type which can be
easily mounted on the bus of furnace transformer. Primary current of these
transformers are o value 10,000 Amp & above. Special precaution is necessary to
reduce the heat developed in the transformers due to eddy current during design.
Furnace CT
6) PRECISION GRADE CTs: These CTs are of accuracy of 0.1, 0.2 or 0.5 and used
as a standard current transformer to check accuracies of other transformer. These
13
current transformers are either wound primary or ring type and manufactured in
teakwood cases.
Precision Grade CT
Section 3
Difference between Power and Instrument transformers for
oil sampling
Power transformer Instrument transformer
Tests conducted are more (DGA and
FURANS)
Tests conducted are less
Volume of oil content is more Volume of oil content is less
No pressure is applied for power
transformers
Instrument transformers may be
pressurised
No need to apply high purity nitrogen Need to apply high purity nitrogen if the
pressure is below its rated value
No need to check for Positive or Negative Pressure
Need to check for Positive or Negative Pressure
Need to do test every year Need to do test only within 2years or more
Power transformers can be live whilst sampling
Instrument transformers are not sampled live
14