Page 1: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

TRANSFORMERS

Copyright © 2002-2005 SBA

Page 2: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

Incorporated transformers

Single-phase transformers up to 630 kVA

Three-phase transformers up to 1000 kVA

Control transformers

Safety isolating transformers

Isolating transformers for installation in hospitals

Insulating transformers up to 10000 V

High current transformers up to 2000 A

Autotransformers - starting transformers

Variable voltage transformers for ventilation systems

Transformers for vehicles

Print and flat transformers

Transformers for switched-mode power supplies

������������

Voltage stabilizers

Incorporated versions up to 3000 VA

Portable versions up to 1000 VA

��

DC power supplies

Single-phase types - unsmoothed, up to 1000 A

Single-phase types – C/LC-smoothed, up to 250 V/1000 A

Three-phase versions up to 1000 A

Smoothed DC power supplies

����

Ballasts for lighting equipment

Resin-encapsulated transformers

Reactors and inductors

Special ballasts for gas discharge lamps up to 100 kW

High-reactance transformers

Controlled ballasts (transductors)

Electronic ballasts up to 30 kW

����

Safety isolating transformers, stationary/transportable

Isolating transformers, stationary/transportable

Roof inlet transformers

Thawing transformers

Antifreeze transformers

Print and flat transformers

������

AC reactors up to 320 kVAr, single-phase

AC reactors up to 500 kVAr, three-phase

DC reactors up to LI2 = 1500 Ws

Filter reactors - AF rejector circuits

Transductors - reactors for switched-mode power supplies

�����

Copyright © 2002-2005 SBA

Page 3: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

Introduction in the product range 2 – 7

ETS single-phase power transformers63-2500 VA 8 – 9

UTS single-phase power transformers1-160 kVA 10 – 13

UTL single-phase power transformers1-160 kVA 14 – 17

ETX single-phase power transformers4-50 VA 18 – 19

MTX single-phase power transformers5-250 VA 20 – 21

UTX single-phase power transformers12-630 VA 22 – 23

ETK single-phase control transformers50-2500 VA 24 – 25

ETKS single-phase control transformers50-200 VA 26 – 27

ETKU universal control transformers160-5600 VA 28 – 29

UTK single-phase control transformers1250-5000 VA 30 – 31

ESI single-phase safety isolating transformers50-2500 VA 32 – 33

USI single-phase safety isolating transformers1-10 kVA 34 – 35

ETT single-phase isolating transformers50-2500 VA 36 – 37

UTT single-phase isolating transformers1-25 kVA 38 – 39

UTM single-phase isolating transformersfor installation in medical equipment rooms

3-10 kVA 40 – 41

ETI single-phase insulating transformers63-2000 VA 42 – 43

UTI single-phase insulating transformers1- 10 kVA 44 – 45

ESS single-phase autotransformers63-2000 VA 46 – 47

USS single-phase autotransformers1-25 kVA 48 – 49

ELT single-phase fan transformers1.5-23 A 50 – 51

DTS three-phase power transformers40-250000 VA 52 – 55

DTL three-phase power transformers40-250000 VA 56 – 59

DSI three-phase safety isolating transformers1-16 kVA 60 – 61

DTT three-phase isolating transformers40-40000 kVA 62 – 63

DTM three-phase isolating transformersfor installation in medical equipment rooms

3-10 kVA 64 – 65

DTI three-phase insulating transformers1-10 kVA 66 – 67

DSS Three-phase autotransformers40-32000 VA 68 – 69

General technical information70 – 73

GEH Housings74

General Terms of Business 75

Content

Copyright © 2002-2005 SBA

Page 4: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

The people behind SBA are the

basis of our success. Custom

design of solutions requires a

high degree of flexibility and

customer focus. The best solution

to a customer's problem is

always developed in a team

effort. The result is the optimal

design for every product.

Computer-backed processes,

attractive prices and high-level

logistics are ideal complements

of the advanced know-how of

our employees. Independent,

responsible action is as

important as creative thinking to

meet our customers' requirement

profiles.

voltageto mesaure

We warrant the safe and proper

function of our transformers and

inductive components for a period of

up to five years.

Copyright © 2002-2005 SBA

Page 5: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

SBA - an investment in the future

Permanent innovation and most

advanced materials guarantee

and constantly redefine the high

quality of SBA transformers and

power supplies. The heat resistant

materials from SBA meet highest

demands on safety, life and

quality - VDE and TÜV approved.

Extensive controls in all areas of

production warrant the reliability

of all SBA products.

Every day, new proof of SBA's

performance potential is provided:

Products of special design in small

or medium lots permit individual

solutions for diverse applications in

industry - often within a few

working days. SBA - with strong

technology and mature products in

the new millennium.

Copyright © 2002-2005 SBA

Page 6: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

DC power supplies

– non-stabilized up to 1000 A

– stabilized up to 40 A

– UPS modules for DC power supplies

Voltage stabilizers

– magnetic up to 3 kVA

– motor-controlled up to 1000 kVA

Resin-encapsulated transformers

– Safety isolating transformers (inclu-ding portable versions)

– Isolating transformers (including por-table versions)

– Print and flat transformers

Industriefor many

��

Copyright © 2002-2005 SBA

Page 7: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

Ballasts for lighting equipment

– Transformers for halogen LV lamps from20 W to 500 W

– Special ballasts for all kinds of gas discharge lamp up to 100 kW

– High-reactance transformers

– Controlled ballasts (transductors)

– Electronic ballasts up to 30 kW

Incorporated transformers

– Single-phase transformersup to 630 kVA

– Three-phase transformersup to 1000 kVA

– Isolating transformers for installation inhospitals

– Insulating transformers up to 10 000 V

– High current transformers up to 2000 A

– Auto transformers

– Transformers for rail vehicles

Ring core and variable toroidaltransformers

– Ring core transformers up to 1000 VA

– Variable toroidal transformers, single-pole or three-pole,up to 63 A

s

Reactors and inductors

– AC reactors up to 500 kVAr

– DC reactors

– Line reactors and commutating reactors

– Filter reactors - AF rejector circuits

– Switched-mode power supply components

Copyright © 2002-2005 SBA

Page 8: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type ETSSingle-phase power transformers to VDE 0570-2-1 / EN 61558-2-1

Application

To supply electrical consumers of all kinds, e.g. measuring and control instruments, power electronic modules, etc..Customized specification and dimensions ensure optimal application.

8

Copyright © 2002-2005 SBA

Page 9: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

Specifications

Output range 63 VA – 2500 VAInput voltage max. 750 VOutput voltage max. 750 VOutput current max. 65 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40°C

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� Required space according to DIN 41308

� Connections to safe-to-touch screw clamping terminals in accordance with VBG 4 with self-releasing clamp(additional clamp type terminal on request)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

Internet: www.sba.de

Type ETSSINGLE-PHASE POWER TRANSFORMERS

Overview

9

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr. % appr. kg appr. kg approx. mm

040 63 15.0 1.2 0.25 78 61 56 49 4.8 8 80

041 80 13.0 1.5 0.28 78 71 56 58 4.8 8 80

042 100 12.0 1.6 0.35 84 64 64 50 4.8 8 86

043 125 9.2 2.0 0.40 84 77 64 64 4.8 8 86

071 160 8.9 2.3 0.52 96 81 84 64 5.8 9 96

072 200 7.8 2.8 0.65 96 89 84 73 5.8 9 96

073 250 6.8 3.6 0.72 96 103 84 87 5.8 9 96

074 320 6.0 4.2 1.05 120 93 90 74 5.8 12 111

075 400 5.4 5.2 1.15 120 101 90 85 5.8 12 111

076 500 4.8 6.6 1.40 120 121 90 104 5.8 12 111

077 630 4.5 7.7 2.00 150 113 122 90 7.0 15 132

078 800 3.7 9.9 2.35 150 130 122 106 7.0 15 132

079 1000 3.4 13.1 2.50 150 155 122 133 7.0 15 132

080 1250 3.3 13.7 3.80 174 127 135 102 7.0 15 148

081 1600 3.1 17.2 4.20 174 147 135 122 7.0 15 148

082 2000 2.8 20.5 4.50 174 167 135 142 7.0 15 148

083 2500 2.5 26.0 5.50 192 190 155 154 11.0 18 170

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 10: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type UTSSingle-phase power transformers to VDE 0570-2-1 / EN 61558-2-1

Application

To supply electrical consumers of all kinds, e.g. measuring and control instruments, power electronic modules, etc..Customized specification and dimensions ensure optimal application.

10

Copyright © 2002-2005 SBA

Page 11: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

11

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� Resting on angular feet (DIN 41307)

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

Internet: www.sba.de

Type UTSSINGLE-PHASE POWER TRANSFORMERS

Overview

Specifications

Output range 1 kVA – 25 kVAInput voltage max. 750 VOutput voltage max. 750 VOutput current at–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 2000 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40°C

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

kVA (DB) appr. % appr. kg appr. kg approx. mm

115 1.0 5.3 11.0 3.6 150 90 100 71 7 13 255

116 1.25 4.7 14.5 4.3 150 114 100 95 7 13 255

121 1.6 4.9 16.0 5.5 172 106 112 76 10 18 290

122 2.0 3.6 22.0 6.6 172 132 112 102 10 18 290

123 2.5 3.7 24.0 8.7 196 122 124 94 10 18 325

124 3.2 2.9 30.0 10.0 196 147 124 119 10 18 325

127 4.0 3.0 39.0 15.0 235 153 144 125 10 18 360

127 5.0 3.5 38.0 14.0 235 153 144 125 10 18 360

128 6.3 3.2 45.0 16.0 235 168 144 140 10 18 360

129 8.0 2.5 51.0 17.0 235 183 144 155 10 18 360

130* 10.0 2.2 61.0 24.0 275 173 176 143 12 18 435

131* 12.5 2.1 77.0 27.0 275 203 176 173 12 18 435

133* 16.0 2.0 88.0 36.0 313 193 196 157 13 20 490

134* 20.0 1.7 107.0 39.0 313 220 196 184 13 20 490

135* 25.0 1.3 128.0 43.0 313 250 196 214 13 20 490

The values in the table above are for the thermal steady state at 40°C ambient temperature.* With 2 eyebolts

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Page 12: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type UTSSingle-phase power transformers up to 40 kVA to VDE 0570-2-1 / EN 61558-2-1

from 40 kVA to VDE 0532

Application

To supply electrical consumers with higher power consumption, e.g. furnaces, melting troughs, converter drives,production lines, etc. Customized specification and dimensions ensure optimal application.

12

Copyright © 2002-2005 SBA

Page 13: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

13

Internet: www.sba.de

Type UTSSINGLE-PHASE POWER TRANSFORMERS

Overview

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� Resting on U-sections

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

Specifications

Output range 32 KVA – 160 kVA Input voltage max. 750 VOutput voltage max. 750 VOutput current an–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 2000 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40°C

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 d c

kVA (DB) appr. % appr. kg appr. kg approx.mm

137 32 2.70 140.0 45.0 380 500 190 450 13 705

139 40 2.09 170.0 53.0 380 500 190 450 13 705

148 50 2.05 215.0 70.0 480 500 240 450 15 810

141 63 1.65 275.0 81.0 480 500 240 450 15 810

142 80 1.40 320.0 88.0 480 500 240 450 15 810

146 100 1.32 380.0 141.0 600 500 300 450 15 870

147 125 1.10 480.0 157.0 600 500 300 450 15 870

145 160 1.07 560.0 165.0 600 500 300 450 15 870

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 14: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type UTLSingle-phase power transformers to VDE 0570-2-1 / EN 61558-2-1

Application

To supply electrical consumers of all kinds, e.g. measuring and control instruments, power electronic modules,mechanical engineering etc.. Customized specification and dimensions ensure optimal application.

14

Copyright © 2002-2005 SBA

Page 15: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

15

Internet: www.sba.de

Type UTLSINGLE-PHASE POWER TRANSFORMERS

Overview

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� Resting on angular brackets (DIN 41307)

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

Specifications

Output range 1 kVA – 25 kVA Input voltage max. 750 VOutput voltage max. 750 VOutput current at–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 2000 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40°C

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c d

kVA (DB) appr. % appr. kg appr. kg approx. mm

115 1.0 5.3 11.0 3.6 230 150 152 126 9 6 124 19

116 1.25 4.7 14.5 4.3 230 150 152 126 9 6 148 19

121 1.6 4.9 16.0 5.5 260 172 176 146 14 9 141 22

122 2.0 3.6 22.0 6.6 260 172 176 146 14 9 167 22

123 2.5 3.7 24.0 8.7 283 196 200 174 14 9 150 25

124 3.2 2.9 30.0 10.0 283 196 200 174 14 9 175 25

127 4.0 3.0 39.0 15.0 331 236 240 204 14 9 186 30

127 5.0 3.5 38.0 14.0 331 236 240 204 14 9 186 30

128 6.3 3.2 45.0 16.0 331 236 240 204 14 9 201 30

129 8.0 2.5 51.0 17.0 331 236 240 204 14 9 216 30

130* 10.0 2.2 61.0 24.0 383 276 280 234 14 9 205 35

131* 12.5 2.1 77.0 27.0 383 276 280 234 14 9 235 35

133* 16.0 2.0 88.0 35.0 433 314 320 264 20 13 229 40

134* 20.0 1.7 107.0 39.0 433 314 320 264 20 13 256 40

135* 25.0 1.3 128.0 43.0 433 314 320 264 20 13 286 40

The values in the table above are for the thermal steady state at 40°C ambient temperature.

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

* With 2 eyebolts

Page 16: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type UTLSingle-phase power transformers up to 40 kVA to VDE 0570-2-1 / EN 61558-2-1

from 40 kVA to VDE 0532

Application

To supply electrical consumers with higher power consumption, e.g. furnaces, melting troughs, converter drives, production lines, etc. Customized specification and dimensions ensure optimal application.

16

Copyright © 2002-2005 SBA

Page 17: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

17

Internet: www.sba.de

Type UTLSINGLE-PHASE POWER TRANSFORMERS

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� Resting on U-sections

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

Specifications

Output range 32 kVA – 160 kVA Input voltage max. 750 VOutput voltage max. 750 VOutput current at–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 2000 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40°C

Overview

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Short-circuit Total Copper Dimensionsvoltage weight weight a1 b1 a2 b2 d c

kVA (DB) appr. % appr. kg appr.kg approx. mm

137 32 2.70 140.0 45.0 670 460 495 420 11 285

139 40 2.09 170.0 53.0 670 460 495 420 11 310

148 50 2.05 215.0 70.0 770 560 570 520 11 285

141 63 1.65 275.0 81.0 770 560 570 520 11 310

142 80 1.40 320.0 88.0 770 560 570 520 11 340

146 100 1.32 380.0 141.0 830 680 600 640 11 305

147 125 1.10 480.0 157.0 830 680 600 640 11 335

145 160 1.07 560.0 165.0 830 680 600 640 11 370

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 18: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type ETXSingle-phase power transformers to VDE 0570-2-1 / EN 61558-2-1

Application

To supply electrical consumers of all kinds, e.g. measuring and control instruments, power electronic modules, mecha-nical engineering etc.. Customized specification and dimensions ensure optimal application.

18

Copyright © 2002-2005 SBA

Page 19: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

919

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� Resting on angular feet (DIN 41307)

� Connection to solder or screw type terminals

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

Internet: www.sba.de

Type ETXSINGLE-PHASE POWER TRANSFORMERS

Overview

Specifications

Output range 4 VA – 50 VAInput voltage max. 400 VOutput voltage max. 400 VOutput current max. 36 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40°C

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

19

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr. % appr. kg appr. kg approx. mm

034 4 117 0.12 0.036 35 41 28 30 M 3 M 3 46

035 8 66 0.25 0.055 40 47 32 32 M 3 M 3 52

036 14 47 0.35 0.080 45 45 38 34 3.6 7 57

037 20 33 0.50 0.120 50 47 44 36 3.6 7 65

038 32 28 0.65 0.160 55 49 44 38 3.6 7 70

039 50 17 0.90 0.180 55 61 44 50 3.6 7 70

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 20: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type MTXSingle-phase power transformers to VDE 0570-2-1 / EN 61558-2-1

Application

To supply electrical consumers of all kinds, e.g. measuring and control instruments, power electronic modules, etc..Customized specification and dimensions ensure optimal application.

20

Copyright © 2002-2005 SBA

Page 21: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

21

Internet: www.sba.de

Type MTXSINGLE-PHASE POWER TRANSFORMERS

Specifications

Output range 5 VA – 250 VAInput voltage max. 400 VOutput voltage max. 400 VOutput current max. 36 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

Overview

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr. % appr. kg appr. kg approx. mm

013 5 37.0 0.2 0.06 42 46 20 32 M 3 M3 47

014 20 27.0 0.7 0.14 55 48 43 37 3 5 60

015 50 22.0 1.0 0.26 65 51 55 38 4 6 70

016 80 15.0 1.4 0.44 74 64 60 51 4 6 80

017 100 13.0 1.9 0.48 85 64 72 51 4 6 90

018 150 9.5 2.4 0.52 85 77 72 64 4 6 90

019 200 7.5 3.3 0.80 104 77 80 61 6 8 110

020 250 7.0 3.9 0.95 104 94 80 78 6 8 110

The values in the table above are for the thermal steady state at 40°C ambient temperature.

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� Resting on angular feet (DIN 41307)

� Connection to solder or screw type terminals

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30 21

Page 22: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type UTXSingle-phase power transformers to VDE 0570-2-1 / EN 61558-2-1

Application

To supply electrical consumers of all kinds, e.g. measuring and control instruments, power electronic modules, mecha-nical engineering etc. Customized specification and dimensions ensure optimal application.

22

Copyright © 2002-2005 SBA

Page 23: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

Internet: www.sba.de

Type UTXSINGLE-PHASE POWER TRANSFORMERS

Specifications

Output range 12 VA – 630 VAInput voltage max. 400 VOutput voltage max. 400 VOutput current max. 36 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

Overview

23

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� Resting on angular feet (DIN 41307)

� Connections to screw terminals

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr. % appr. kg appr. kg approx. mm

103 12 42.0 0.6 0.12 52 38 43 27 3.2 5.2 105

104 20 30.0 0.8 0.14 52 45 43 34 3.2 5.2 105

105 32 28.0 1.0 0.23 64 47 55 34 4.3 6.3 115

106 50 20.0 1.2 0.30 64 56 55 43 4.3 6.3 115

107 80 17.0 1.4 0.50 80 54 73 40 4.3 6.8 140

108 125 13.5 1.8 0.62 80 64 73 50 4.3 6.8 140

109 200 11.5 2.8 1.00 100 67 81 51 5.3 8.0 175

110 300 7.5 3.6 1.25 100 82 81 65 5.3 8.0 175

111 400 8.0 4.5 1.60 120 76 76 57 7.0 13.0 200

112 630 6.0 6.8 2.30 120 96 76 77 7.0 13.0 200

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 24: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type ETKSingle-phase control transformers to VDE 0570-2-2 / EN 61558-2-2

Application

Control transformers supplying control circuit in switchgear, distribution boards, machines, etc. according to VDE0113 / EN 60204.

For recommended fuses, seeex-stock range

Available ex stock380/400/420//230 Volt380/400/420// 24 Volt ➝ up to 1000 VA220/230/240//230 Volt ➝ up to 1000 VA220/230/240// 24 Volt ➝ up to 1000 VA24

Copyright © 2002-2005 SBA

Page 25: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

25

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� With more severe requirements on test voltages and creepage distance and clearance in air because these transformers are often exposed to overvoltage

� Input-side matching taps

� Required space according to DIN 41308

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(additional clamp type terminal on request)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

Internet: www.sba.de

Type ETKSINGLE-PHASE CONTROL TRANSFORMERS

Specifications

Output range 50 VA – 2500 VAInput voltage max. 750 VOutput voltage max. 250 VFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

Overview

Size Rated output Short time rating uk ur Total Copper- Dimensionscos phi = 1 cos phi = 0,5 weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) VA % % appr. kg appr. kg approx. mm

151 50 115 12.33 12.31 1.2 0.25 78 61 56 49 4.8 8 80

152 63 155 10.41 10.40 1.5 0.28 78 71 56 58 4.8 8 80

153 100 215 11.01 10.98 1.6 0.35 84 64 64 50 4.8 8 86

154 125 290 9.60 9.59 2.0 0.40 84 77 64 64 4.8 8 86

155 160 390 8.06 8.03 2.3 0.52 96 81 84 64 5.8 9 96

156 200 515 7.11 7.05 2.8 0.65 96 89 84 73 5.8 9 96

157 250 680 6.45 6.43 3.6 0.72 96 103 84 87 5.8 9 96

160 320 825 6.46 6.41 4.2 1.05 120 93 90 74 5.8 12 111

161 400 1130 5.34 5.28 5.2 1.15 120 101 90 85 5.8 12 111

162 500 1540 4.78 4.75 6.6 1.40 120 121 90 104 5.8 12 111

163 630 1790 4.83 4.75 7.7 2.00 150 113 122 90 7.0 15 132

164 800 2500 3.83 3.73 9.9 2.35 150 130 122 106 7.0 15 132

165 1000 3520 3.40 3.34 13.1 2.50 150 155 122 133 7.0 15 132

166 1250 2990 4.19 3.71 13.7 3.80 174 127 135 102 7.0 15 148

167 1600 4260 3.51 3.12 17.2 4.20 174 147 135 122 7.0 15 148

168 2000 5740 3.10 2.74 20.5 4.50 174 167 135 142 7.0 15 148

169 2500 7900 2.67 2.34 26.0 5.50 192 190 155 154 11.0 18 170

The values in the table above are for the thermal steady state at 40°C ambient temperature.

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Page 26: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

available ex stock380/400/420//230 Volt380/400/420// 24 Volt220/230/240//230 Volt 220/230/240// 24 Volt

Recommended fusessee ex-stock range

26

Typ: ETKS

Art.Nr.:

151-0051

Leistung:

50/115 VA

50-60 H

z

PRI:

380/400/420 V

SEC:

24 V 2,08 A

G5x20 M 2 A

(ext.)

Betr: D

B ta=40°C I-

Kl: T40/B

EN 6155

EN 61

Type ETKSSingle-phase control transformers to VDE 0570-2-2 / EN 61558-2-2

for DIN rail TS 35 (DIN EN 50022)

Application

Control transformers supplying control circuits in switchgear systems,distribution boards, machines, etc. to VDE 0113 / EN 60204.

Copyright © 2002-2005 SBA

Page 27: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

Internet: www.sba.de

Type ETKSSINGLE-PHASE CONTROL TRANSFORMERS

Specifications

Output range 50 VA – 200 VAInput voltage max. 750 VOutput voltage max. 250 VFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

Overview

27

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� With more severe requirements on test voltages and creepage distance and clearance in air because these transformers are often exposed to overvoltage

� Input-side matching taps

� Required space according to DIN 41308

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(additional clamp type terminal on request)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Short time rating uk ur Total Copper- Dimensionscos phi = 1 cos phi = 0,5 weight weight a b c

VA (DB) VA % % appr. kg appr. kg approx. mm

151 50 115 12.33 12.31 1.3 0.25 78 61 80

152 63 155 10.41 10.40 1.6 0.28 78 71 80

153 100 215 11.01 10.98 1.7 0.35 84 64 86

154 125 290 9.60 9.59 2.1 0.40 84 77 86

155 160 390 8.06 8.03 2.4 0.52 96 81 96

156 200 515 7.11 7.05 2.9 0.65 96 89 96

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 28: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

Type ETKUUniversal control transformers to VDE 0570-2-2 / EN 61558-2-2Single-phase isolating transformers to VDE 0570-2-4 / EN 61558-2-4 / UL 506

available ex stock Recommended fuses see ex-stock range

Terminal connection diagramsee ex-stock range

Application

Isolating transformers for general application, e.g., as associated transformers for devices to VDE 0700, 0750, 0805.Transformers supplying control circuits in switchgear systems, distribution boards, machines, etc. to VDE 0113.Adapts to 13 different line-side supply voltages

� Built to UL insulation class B, therefore no output reduction in relation to VDE specifications necessary.� Suitable for UL labeled industrial control panels according to UL guideline UL 508A.

28

E250288

Copyright © 2002-2005 SBA

Page 29: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

Type ETKUUNIVERSAL CONTROL TRANSFORMERS

Overview

Specifications

Output range 160 VA – 5600 VAInput voltage 200/220/240/360/380/

400/420/440/460/480/500/530/550 V

Output voltage 2 x 115 V for optional series or parallel connection

Frequency 50-60 HzVector group IIii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

29

Internet: www.sba.de

Art. no. Rated output Short-time rating Total Copper Dimensionscos � = 1 cos � = 0,5 weight weight a1 b1 a2 b2 a3 b3 cVA (DB) VA appr. kg appr. kg approx. mm

155-0245 160 354 2.3 0.52 96 81 84 64 5.8 9 105

156-0255 200 475 2.8 0.65 96 89 84 73 5.8 9 105

157-0300 250 625 3.6 0.72 96 103 84 87 5.8 9 105

160-0220 320 742 4.2 1.05 120 93 90 74 5.8 12 111

161-0240 400 1035 5.2 1.15 120 101 90 85 5.8 12 111

162-0365 500 1380 6.6 1.40 120 121 90 104 5.8 12 111

163-0260 630 1530 7.7 2.00 150 113 122 90 7 15 132

164-0220 800 2055 9.9 2.35 150 130 122 106 7 15 132

165-0365 1000 2990 13.1 2.50 150 155 122 133 7 15 132

166-0080 1250 2530 13.7 3.80 174 127 135 102 7 15 148

167-0140 1600 3300 17.2 4.20 174 147 135 122 7 15 148

168-0125 2000 4600 20.5 4.50 174 167 135 142 7 15 148

169-0060 2500 6500 26.0 5.50 192 190 155 154 11 18 170

169-0065 3000 6750 26.0 5.50 192 190 155 154 11 18 170

189-0105* 3400 11000 29.0 9.30 283 196 200 174 14 9 170

190-0075* 4800 11200 39.0 15.0 331 236 240 204 14 9 186

190-0080* 5600 13200 38.0 14.0 331 236 240 204 14 9 186

The values in the table above are for the thermal steady state at 40°C ambient temperature.* Different design due to UI cores

With UL/cUL test label

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings by double/extra strong insulation (safe separation)

� With more severe requirements on test voltages and creepage distance and clearance in air because these transformers are often exposed to overvoltage

� Input-side matching taps

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(additional clamp type terminal on request)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

[email protected] [email protected]

Page 30: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type UTKSingle-phase control transformers to VDE 0570-2-2 / EN 61558-2-2

available ex stock

380/400/420//230 Volt ➝ from 2500 VAto 5000 VA

Recommended fuses see ex-stock range

30

Application

Control transformers supplying control circuits in switchgear systems, distribution boards, machines, etc. to VDE 0113 / EN 60204.

Copyright © 2002-2005 SBA

Page 31: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

31

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� With more severe requirements on test voltages and creepage distance and clearance in air because these transformers are often exposed to overvoltage

� Input-side matching taps

� Resting on angular brackets (DIN 41307)

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

Internet: www.sba.de

Type UTKSINGLE-PHASE CONTROL TRANSFORMERS

Specifications

Output range 1250 VA– 5000 VAInput voltage max. 750 VOutput voltage max. 750 VOutput current max. 135 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

Overview

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Short time rating uk ur Total Copper- Dimensionscos phi = 1 cos phi = 0,5 weight weight a1 b1 a2 b2 a3 b3 c d

VA (DB) VA % % appr. kg appr. kg approx. mm

181 1250 4200 4.04 4.01 14.5 4.3 230 150 152 126 9 6 143 19

186 1600 5250 3.71 3.65 16.0 5.5 260 172 176 146 14 9 136 22

187 2000 7560 3.30 3.28 22.0 6.6 260 172 176 146 14 9 162 22

188 2500 8320 3.06 2.92 24.0 8.7 283 196 200 174 14 9 145 25

189 3200 12770 2.55 2.48 30.0 10.0 283 196 200 174 14 9 170 25

190 4000 11140 3.17 2.79 39.0 15.0 331 236 240 204 14 9 186 30

190 5000 14355 3.02 2.66 38.0 14.0 331 236 240 204 14 9 186 30

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 32: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type ESISingle-phase safety isolating transformers to VDE 0570-2-6 / EN 61558-2-6

Application

Transformers supplying electric circuits or devices working with safety extra-low voltage (SELV, max. 50 V) (e.g. hand lamps, portable tools, toys, etc.).

available ex stock380/400/420// 24 Volt ➝ up to 1000 VA220/230/240// 24 Volt ➝ up to 1000 VA

Recommended fuses see ex-stock range

32

Copyright © 2002-2005 SBA

Page 33: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

33

Internet: www.sba.de

Type ESISINGLE-PHASE SAFETY ISOLATING TRANSFORMERS

Specifications

Output range 50 VA – 2500 VAInput voltage max. 750 VOutput voltage max. 50 VOutput current max. 65 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

Overview

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings by double/extra strong insulation (safe separation)

� Required space according to DIN 41308

� Input-side matching taps

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(additional clamp type terminal on request)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Short time rating uk ur Total Copper- Dimensionscos phi = 1 cos phi = 0,5 weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) VA % % appr. kg appr. kg approx. mm

151 50 115 12.33 12.31 1.2 0.25 78 61 56 49 4.8 8 80

152 63 155 10.41 10.40 1.5 0.28 78 71 56 58 4.8 8 80

153 100 215 11.01 10.98 1.6 0.35 84 64 64 50 4.8 8 86

154 125 290 9.60 9.59 2.0 0.40 84 77 64 64 4.8 8 86

155 160 390 8.06 8.03 2.3 0.52 96 81 84 64 5.8 9 96

156 200 515 7.11 7.05 2.8 0.65 96 89 84 73 5.8 9 96

157 250 680 6.45 6.43 3.6 0.72 96 103 84 87 5.8 9 96

160 320 825 6.46 6.41 4.2 1.05 120 93 90 74 5.8 12 111

161 400 1130 5.34 5.28 5.2 1.15 120 101 90 85 5.8 12 111

162 500 1540 4.78 4.75 6.6 1.40 120 121 90 104 5.8 12 111

163 630 1790 4.83 4.75 7.7 2.00 150 113 122 90 7.0 15 132

164 800 2500 3.83 3.73 9.9 2.35 150 130 122 106 7.0 15 132

165 1000 3520 3.40 3.34 13.1 2.50 150 155 122 133 7.0 15 132

166 1250 2990 4.19 3.71 13.7 3.80 174 127 135 102 7.0 15 148

167 1600 4260 3.51 3.12 17.2 4.20 174 147 135 122 7.0 15 148

168 2000 5740 3.10 2.74 20.5 4.50 174 167 135 142 7.0 15 148

169 2500 7900 2.67 2.34 26.0 5.50 192 190 155 154 11.0 18 170

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 34: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type USISingle-phase safety isolating transformers to VDE 0570-2-6 / EN 61558-2-6

Application

Transformers supplying electric circuits or devices working with safety extra-low voltage (SELV, max. 50 V) (e.g., mate-rials testing instruments, film welders, certain equipment in the chemical industry and in mining, etc.).

34

Copyright © 2002-2005 SBA

Page 35: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings by two-champer design (safe separation)

� Resting on angular brackets (DIN 43107)

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

Internet: www.sba.de

Type usISINGLE-PHASE SAFETY ISOLATING TRANSFORMERS

Overview

Specifications

Output range 1 kVA – 10 kVAInput voltage max. 750 VOutput voltage max. 50 VOutput current an–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 2000 AVector group Ii0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40° C

* With 2 eyebolts

35

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

kVA (DB) appr. % appr. kg appr. kg approx. mm

115 1.00 5.3 11.0 3.6 270 150 152 126 9 6 124

116 1.25 4.7 14.5 4.3 270 150 152 126 9 6 148

121 1.60 4.9 16.0 5.5 300 172 176 146 14 9 141

122 2.00 3.6 22.0 6.6 300 172 176 146 14 9 167

123 2.50 3.7 24.0 8.7 320 196 200 174 14 9 150

124 3.20 2.9 30.0 10.0 320 196 200 174 14 9 175

127 4.00 3.0 39.0 15.0 365 235 240 204 14 9 186

127 5.00 3.5 38.0 14.0 365 235 240 204 14 9 186

128 6.30 3.2 45.0 16.0 365 235 240 204 14 9 201

129 8.00 2.5 51.0 17.0 365 235 240 204 14 9 216

130* 10.00 2.2 61.0 24.0 420 276 280 243 14 9 205

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 36: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type ETTSingle-phase isolating transformers to VDE 0570-2-4 / EN 61558-2-4

Application

Transformers supplying electric circuits or devices for which an electrical isolation from the feeding electric circuit isprescribed (e.g., electric shavers, portable tools, lawn movers, etc.).

available ex stock380/400/420//230 Volt ➝ up to 2500 VA220/230/240//230 Volt ➝ up to 1000 VA

Recommended fuses see ex-stock range

36

Copyright © 2002-2005 SBA

Page 37: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

37

Internet: www.sba.de

Type ETTSINGLE-PHASE ISOLATING TRANSFORMERS

Specifications

Output range 50 VA – 2500 VAInput voltage max. 750 VOutput voltage max. 750 VOutput current max. 65 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

Overview

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings by double/extra strong insulation (safe separation)

� Required space according to DIN 41308

� Input-side matching taps

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(additional clamp type terminal on request)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Short time rating uk ur Total Copper- Dimensionscos phi = 1 cos phi = 0,5 weight weight a1 b1 a2 b2 a3 b3 c

kVA (DB) VA % % appr. kg appr. kg approx. mm

151 50 115 12.33 12.31 1.2 0.25 78 61 56 49 4.8 8 80

152 63 155 10.41 10.40 1.5 0.28 78 71 56 58 4.8 8 80

153 100 215 11.01 10.98 1.6 0.35 84 64 64 50 4.8 8 86

154 125 290 9.60 9.59 2.0 0.40 84 77 64 64 4.8 8 86

155 160 390 8.06 8.03 2.3 0.52 96 81 84 64 5.8 9 96

156 200 515 7.11 7.05 2.8 0.65 96 89 84 73 5.8 9 96

157 250 680 6.45 6.43 3.6 0.72 96 103 84 87 5.8 9 96

160 320 825 6.46 6.41 4.2 1.05 120 93 90 74 5.8 12 111

161 400 1130 5.34 5.28 5.2 1.15 120 101 90 85 5.8 12 111

162 500 1540 4.78 4.75 6.6 1.40 120 121 90 104 5.8 12 111

163 630 1790 4.83 4.75 7.7 2.00 150 113 122 90 7.0 15 132

164 800 2500 3.83 3.73 9.9 2.35 150 130 122 106 7.0 15 132

165 1000 3520 3.40 3.34 13.1 2.50 150 155 122 133 7.0 15 132

166 1250 2990 4.19 3.71 13.7 3.80 174 127 135 102 7.0 15 148

167 1600 4260 3.51 3.12 17.2 4.20 174 147 135 122 7.0 15 148

168 2000 5740 3.10 2.74 20.5 4.50 174 167 135 142 7.0 15 148

169 2500 7900 2.67 2.34 26.0 5.50 192 190 155 154 11.0 18 170

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 38: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type UTTSingle-phase isolating transformers nach VDE 0570-2-4 / EN 61558-2-4

Application

Transformers supplying electric circuits or devices for which an electrical isolation from the feeding electric circuit isprescribed (e.g., portable tools, certain equipment in the chemical industry and in mining, etc.).

38

Copyright © 2002-2005 SBA

Page 39: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Internet: www.sba.de

Type UTTSINGLE-PHASE ISOLATING TRANSFORMERS

Overview

Specifications

Output range 1 kVA – 25 kVAInput voltage max. 750 VOutput voltage max. 750 VOutput current at –Screw terminals max. 135 A–Studs max. max. 450 A–Flat termination max. 2000 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40° C

* With 2 eyebolts

39

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings by two-chamber design (safe separation)

� Resting on angular brackets (DIN 43107)

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

kVA (DB) appr. % appr. kg appr. kg approx. mm

115 1.0 5.3 11.0 3.6 150 90 100 71 7 13 255

116 1.25 4.7 14.5 4.3 150 114 100 95 7 13 255

121 1.6 4.9 16.0 5.5 172 106 112 76 10 18 290

122 2.0 3.6 22.0 6.6 172 132 112 102 10 18 290

123 2.5 3.7 24.0 8.7 196 122 124 94 10 18 325

124 3.2 2.9 30.0 10.0 196 147 124 119 10 18 325

127 4-0 3.0 39.0 15.0 235 153 144 125 10 18 360

127 5.0 3.5 38.0 14.0 235 153 144 125 10 18 360

128 6.3 3.2 45.0 16.0 235 168 144 140 10 18 360

129 8.0 2.5 51.0 17.0 235 183 144 155 10 18 360

130* 10.0 2.2 61.0 24.0 275 173 176 143 12 18 435

131* 12.5 2.1 77.0 27.0 275 203 176 173 12 18 435

133* 16.0 2.0 88.0 36.0 313 193 196 157 13 20 490

134* 20.0 1.7 107.0 39.0 313 220 196 184 13 20 490

135* 25.0 1.3 128.0 43.0 313 250 196 214 13 20 490

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 40: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type UTMSingle-phase isolating transformers to VDE 0100 part 710

VDE 0570-2-15 / EN 61558-2-15

Application

Transformers supplying electric circuits or equipment in hospital rooms (e.g., bedrooms, examination rooms, operati-on theaters, etc.). Isolating transformers are preferably used in IT systems and rooms with group 2 medical (appli-cation) equipment, i.e. the isolating transformer must not switch off automatically and conform to the standard forpermanent incorporation in protection class II (without protective conductor and with double or extra strong insula-tion of all parts of the transformer). The transformer is available for protection class I on request. The required pro-tection class should expressly be specified in the order

40

Copyright © 2002-2005 SBA

Page 41: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

41

Internet: www.sba.de

Type UTMSINGLE-PHASE ISOLATING TRANSFORMERS

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Due to the integration of a PTC thermistor in each coil, external monitoring arrangement potecting from overload must be provided

� Separated windings by shielding winding and double/extra strong insulation (safe separation)

� Required space according to DIN 41308

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(additional clamp type terminal on request)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

Specifications

Output range 3.2 kVA – 8.0 kVAInput voltage 230 VOutput voltage 115 – 0 – 115 VOutput current max. 34.8 AFrequency 50-60 HzVector group li0 with shielding windingProtection class II (prepared)Protection index IP 00Insulation class BAmbient temperature max. 40° CShort-circuit voltage switching capacity < 3%No-load current < 3%Inrush current < 12 times rated current

Special versions

� With wrapped thermal switches instead of PTC thermistors

� With lower inrush current (8 x) like in prior norm VDE 0107

� Designed to protection class I

� Wider output range (0.5 kVA - 10 kVA)

� Wider Input voltage range (max. 1000 V AC)

Overview

for installation in medical equipment rooms

* With 2 eyebolts

41

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output gl/gl to VDE 0636-31 Total Copper DimensionsRecommended fuse weight weight a1 b1 a2 b2 a3 b3 c

primary ssecondarykVA (DB) A A appr. kg appr. kg approx. mm

127-5069 3.2 25 16 38.0 14.0 235 153 144 125 10 18 360

129-5050 4.0 35 20 51.0 17.0 235 183 144 135 10 18 360

130-5030 5.0 35 25 61.0 24.0 275 173 176 143 12 18 435

131-5020* 6.3 50 35 77.0 27.0 275 203 176 173 12 18 435

132-5002* 8.0 63 35 88.0 36.0 305 233 176 203 12 18 435

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 42: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type ETISingle-phase insulating transformers to VDE 0550 part 3

Application

Insulating transformers are power transformers whose rated voltage at the input side and/or outputside is higher than 1000 V. The same standard applies to power transformers with outputvoltage(s) of more than 1 kV up to 10 kV (e.g., anode voltage generation for transmission tubes).

42

Copyright © 2002-2005 SBA

Page 43: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

43

Internet: www.sba.de

Type ETISINGLE-PHASE INSULATING TRANSFORMERS

Overview

Specifications

Output range 63 VA – 2000 VAInput voltage max. 750 VOutput voltage max. 10 kVOutput current max. 10 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr. % appr. kg appr. kg approx. mm

040 1.2 0.25 78 61 56 49 4.8 8 125

041 1.5 0.28 78 71 56 58 4.8 8 125

042 1.6 0.35 84 64 64 50 4.8 8 121

043 2.0 0.40 84 77 64 64 4.8 8 121

071 2.3 0.52 96 81 84 64 5.8 9 131

072 2.8 0.65 96 89 84 73 5.8 9 131

073 3.6 0.72 96 103 84 87 5.8 9 131

074 4.2 1.05 120 93 90 74 5.8 12 146

075 5.2 1.15 120 101 90 85 5.8 12 146

076 6.6 1.40 120 121 90 104 5.8 12 146

077 7.7 2.00 150 113 122 90 7.0 15 167

078 9.9 2.35 150 130 122 106 7.0 15 167

079 13.1 2.50 150 155 122 133 7.0 15 167

080 13.7 3.80 174 127 135 102 7.0 15 183

081 17.2 4.20 174 147 135 122 7.0 15 183

082 20.5 4.50 174 167 135 142 7.0 15 183

The values in the table above are for the thermal steady state at 40°C ambient temperature.

The rated output depends

strongly on the clearance

in air and creepage

distances which must be

maintained as a function

of the isolation voltage.

43

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� Connection to insulators

� Required space according to DIN 41308

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(additional clamp type terminal on request)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Page 44: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type UTISingle-phase insulating transformers to VDE 0550 part 3

Application

Insulating transformers are power transformers whose rated voltage at the output side is higher than 1000 V. Thesame standard applies to power transformers with output voltage(s) of more than 1 kV up to 10 kV (e.g., anodevoltage generation for transmission tubes.

44

Copyright © 2002-2005 SBA

Page 45: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

* With 2 eyebolts

45

Internet: www.sba.de

Type UTISINGLE-PHASE INSULATING TRANSFORMERS

Overview

Specifications

Output range 1 kVA – 10 kVAInput voltage max. 660 VOutput voltage max. 10 kVOutput current max. 10 AFrequency 50-60 HzVector group Ii0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr. % appr. kg appr.kg approx. mm

115 11.0 3.6 230 150 152 126 9 6 124

116 14.5 4.3 230 150 152 126 9 6 148

121 16.0 5.5 260 172 176 146 14 9 141

122 22.0 6.6 260 172 176 146 14 9 167

123 24.0 8.7 283 196 200 174 14 9 150

124 30.0 10.0 283 196 200 174 14 9 175

127 39.0 15.0 331 236 240 204 14 9 186

127 38.0 14.0 331 236 240 204 14 9 186

128 45.0 16.0 331 236 240 204 14 9 201

129 51.0 17.0 331 236 240 204 14 9 216

130* 61.0 24.0 383 276 280 234 14 9 205

131* 77.0 27.0 383 276 280 234 14 9 235

133* 88.0 36.0 433 314 320 264 20 13 229

134* 107.0 39.0 433 314 320 264 20 13 256

135* 128.0 43.0 433 314 320 264 20 13 286

The values in the table above are for the thermal steady state at 40°C ambient temperature.

The rated output depends

strongly on the clearance

in air and creepage

distances which must be

maintained as a function

of the isolation voltage.

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings (safe separation)

� Resting on angular brackets (DIN 43107)

� Connection to insulators

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Page 46: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type ESSSingle-phase autotransformers to VDE 0570-2-13 / EN 61558-2-13

Application

To supply electrical consumers of all kinds. Substantial savings in comparison with transformers with separate win-dings. Custom sizes and design features ensure optimal application

Design rating=Throughput rating x (highest voltage) - (lowest voltage)

(highest voltage)

Always specify the throughput rating in your order!

46

Copyright © 2002-2005 SBA

Page 47: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

47

Internet: www.sba.de

Type ESSSINGLE-PHASE AUTOTRANSFORMERS

Overview

Specifications

Design rating range 63 VA – 2000 VAInput voltage max. 750 VOutput voltage max. 750 VOutput current max. 65 AFrequency 50-60 HzVector group I0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

47

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Required space according to DIN 41308

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(additional clamp type terminal on request)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Design rating Total Copper Dimensionsweight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr.kg appr.kg approx. mm

040 63 1.2 0.25 78 61 56 49 4.8 8 80

041 80 1.5 0.28 78 71 56 58 4.8 8 80

042 100 1.6 0.35 84 64 64 50 4.8 8 86

043 125 2.0 0.40 84 77 64 64 4.8 8 86

071 160 2.3 0.52 96 81 84 64 5.8 9 96

072 200 2.8 0.65 96 89 84 73 5.8 9 96

073 250 3.6 0.72 96 103 84 87 5.8 9 96

074 320 4.2 1.05 120 93 90 74 5.8 12 111

075 400 5.2 1.15 120 101 90 85 5.8 12 111

076 500 6.6 1.40 120 121 90 104 5.8 12 111

077 630 7.7 2.00 150 113 122 90 7.0 15 132

078 800 9.9 2.35 150 130 122 106 7.0 15 132

079 1000 13.1 2.50 150 155 122 133 7.0 15 132

080 1250 13.7 3.80 174 127 135 102 7.0 15 148

081 1600 17.2 4.20 174 147 135 122 7.0 15 148

082 2000 20.5 4.50 174 167 135 142 7.0 15 148

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 48: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type USSSingle-phase autotransformers to VDE 0532

VDE 0570-2-13 / 61558-2-13

Application

To supply electrical consumers of all kinds. Substantial savings in comparison with transformers with separate win-dings. Custom sizes and design features ensure optimal application.

48

Always specify the throughput rating in your order.

Design rating=Throughput rating x (highest voltage) - (lowest voltage)

(highest voltage)

Copyright © 2002-2005 SBA

Page 49: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

* With 2 eyebolts

49

Internet: www.sba.de

Type USSSINGLE-PHASE AUTOTRANSFORMERS

Specifications

Design rating range 1 kVA – 25 kVAInput voltage max. 750 VOutput voltage max. 750 VOutput current at–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 2000 AFrequency 50-60 HzVector group I0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40° C

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Resting on angular brackets (DIN 43107)

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

OverviewSize Design rating Total Copper Dimensions

weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr.kg appr.kg approx. mm

115 1.0 11.0 3.6 150 90 100 71 7 13 255

116 1.25 14.5 4.3 150 114 100 95 7 13 255

121 1.6 16.0 5.5 172 106 112 76 10 18 290

122 2.0 22.0 6.6 172 132 112 102 10 18 290

123 2.5 24.0 8.7 196 122 124 94 10 18 325

124 3.2 30.0 10.0 196 147 124 119 10 18 325

127 4.0 39.0 15.0 235 153 144 125 10 18 360

127 5.0 38.0 14.0 235 153 144 125 10 18 360

128 6.3 45.0 16.0 235 168 144 140 10 18 360

129 8.0 51.0 17.0 235 183 144 155 10 18 360

130* 10.0 61.0 24.0 275 173 176 143 12 18 435

131* 12.5 77.0 27.0 275 203 176 173 12 18 435

133* 16.0 88.0 36.0 313 193 196 157 13 20 490

134* 20.0 107.0 39.0 313 220 196 184 13 20 490

135* 25.0 128.0 43.0 313 250 196 214 13 20 490

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 50: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type ELTSingle-phase fan transformers to VDE 0570-2-13 / EN 61558-2-13

Application

for speed control of fan motors by applying a 7-step or 5-step output voltage. Suitable for continuous operation.Custom sizes and design features ensure optimal application.

50

available ex stock

Copyright © 2002-2005 SBA

Page 51: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

Specifications

Output range 350 VA – 8000 VAInput voltage 230 V bzw. 400 VOutput voltage 80... 230 V (7 steps) bzw.

140...400 V (5 steps)Rated current max. 23 AFrequency 50-60 HzVector group Ia0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

Input: 400 V (use Vee connection in three-phase systems)Output: 140/180/230/280/400

Input: 230 VOutput: 80/100/125/150/170/190/ 230 V

51

Internet: www.sba.de

Type ELTSINGLE-PHASE FAN TRANSFORMERS

Overview

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Required space according to DIN 41308

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Output current Total Copper Dimensionsweight weight a1 b1 a2 b2 a3 b3 c

A appr. kg appr. kg approx. mm

041-0058 1.5 1.5 0.30 78 71 56 58 4.8 8 80

043-0398 2.4 2.0 0.40 84 77 64 64 4.8 8 86

072-0198 3.8 2.8 0.65 96 89 84 73 5.8 9 96

074-0209 6.0 4.2 1.05 120 93 90 74 5.8 12 111

076-0224 9.5 6.6 1.40 120 121 90 104 5.8 12 111

077-0238 12.0 7.7 2.00 150 113 122 90 7.0 15 132

078-0157 15.0 9.9 2.35 150 130 122 106 7.0 15 132

079-0298 19.0 13.1 2.50 150 155 122 133 7.0 15 132

080-0035 23.0 13.7 3.80 174 127 135 102 7.0 15 148

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Size Output current Total Copper Dimensionsweight weight a1 b1 a2 b2 a3 b3 c

A appr. kg appr.kg approx. mm

071-0263 1.6 2.3 0.52 96 81 84 64 5.8 9 96

073-0379 2.5 3.6 0.72 96 103 84 87 5.8 9 96

076-0341 5.0 6.6 1.40 120 121 90 104 5.8 12 111

078-0232 8.0 9.9 2.35 150 130 122 106 7 15 132

079-0416 10.0 13.1 2.50 150 155 122 133 7 15 132

080-0076 12.5 13.7 3.80 174 127 135 102 7 15 148

081-0062 14.0 17.2 4.20 174 147 135 122 7 15 148

082-0057 20.0 20.5 4.50 174 167 135 142 7 15 148

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 52: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type DTSThree-phase power transformers to VDE 0570-2-1 / EN 61558-2-1

Application

To supply electrical consumers of all kinds, e.g. measuring and control instruments, power electronic modules,mechanical engineering etc.. Customized specification and dimensions ensure optimal application.

52

Copyright © 2002-2005 SBA

Page 53: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

* With 2 eyebolts

53

Internet: www.sba.de

Type DTSTHREE-PHASE POWER TRANSFORMERS

Overview

Specifications

Output range 40 VA – 40 kVAInput voltage max. 750 VOutput voltage max. 750 VOutput current at–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 1500 AFrequency 50-60 HzVector group Yy0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40° C

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings (safe separation)

� Resting on angular brackets (DIN 43107)

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr. % appr. kg appr. kg approx. mm

205 40 19.0 1.1 0.3 95 48 50 34 4 7 116

206 63 15.0 2.0 0.4 95 57 50 43 4 7 116

207 125 16.3 2.6 0.8 120 82 81 46 6 8 134

208 160 11.1 4.2 1.0 120 92 81 57 6 8 134

209 250 9.9 5.0 1.4 150 101 106 61 7 13 172

210 400 7.5 6.0 1.8 150 116 106 76 7 13 172

211 500 8.5 7.5 2.6 180 106 106 66 7 13 188

212 800 5.8 12.0 3.8 180 126 106 86 7 13 188

215 1250 5.8 16.0 5.0 228 110 176 71 7 13 257

216 1600 5.0 20.0 6.0 228 134 176 95 7 13 257

221 2000 5.0 23.0 6.8 264 136 200 76 10 18 294

222 2500 4.2 26.0 8.7 264 162 200 102 10 18 294

223 3200 3.4 33.0 13.5 300 152 224 94 10 18 328

224 5000 3.1 42.0 14.5 300 177 224 119 10 18 328

227* 6300 3.0 53.0 21.0 360 183 264 125 10 18 371

227* 8000 2.8 54.0 22.0 360 183 264 125 10 18 371

228* 10000 2.4 62.0 26.0 360 198 264 140 10 18 371

230* 12500 2.2 90.0 33.0 420 213 316 143 13 20 435

231* 18000 1.5 110.0 36.0 420 243 316 173 13 20 435

233* 25000 1.3 125.0 42.0 480 233 356 157 13 20 490

234* 30000 1.1 165.0 48.0 480 260 356 184 13 20 490

235* 40000 0.9 220.0 62.0 480 290 356 214 13 20 490

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 54: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type DTSThree-phase power transformers to VDE 0532

Application

To supply electrical consumers of all kinds, e.g. measuring and control instruments, power electronic modules,mechanical engineering etc.. Customized specification and dimensions ensure optimal application.

54

Copyright © 2002-2005 SBA

Page 55: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

55

Internet: www.sba.de

Type DTSTHREE-PHASE POWER TRANSFORMERS

Specifications

Output range 40 kVA – 250 kVAInput voltage max. 750 VOutput voltage max. 750 VOutput current at max. 65 A–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 1500 AFrequency 50-60 HzVector group Yy0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40° C

Overview

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated winding

� Resting on U sections

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Short-circuit Total- Copper Dimensionsvoltage ur weight weight a1 b1 a2 b2 d c

kVA (DB) appr. % appr. kg appr. kg approx. mm

249 40 3.15 190.0 56.0 570 500 380 450 13 705

237 50 2.70 220.0 64.0 570 500 380 450 13 705

239 63 2.09 270.0 77.0 570 500 380 450 13 705

248 80 2.05 330.0 105.0 720 500 480 450 15 810

241 100 1.65 420.0 122.0 720 500 480 450 15 810

242 125 1.40 490.0 132.0 720 500 480 450 15 810

246 160 1.32 590.0 212.0 900 500 600 450 15 870

247 200 1.10 740.0 236.0 900 500 600 450 15 870

245 250 1.07 860.0 250.0 900 500 600 450 15 870

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 56: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type DTLThree-phase power transformers to VDE 0570-2-1 / EN 61558-2-1

Application

To supply electrical consumers of all kinds, e.g. measuring and control instruments, power electronic modules,mechanical engineering etc.. Customized specification and dimensions ensure optimal application.

56

Copyright © 2002-2005 SBA

Page 57: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

57

Internet: www.sba.de

Type DTLTHREE-PHASE POWER TRANSFORMERS

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� Resting on angular brackets (DIN 41307)

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

Specifications

Output range 40 VA – 40 kVA Input voltage max. 750 VOutput voltage max. 750 VOutput current at–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 1500 AFrequency 50-60 HzVector group Yy0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40°C

Overview

* With 2 eyebolts

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 d c

VA (DB) appr. % appr. kg appr. kg approx. mm

205 40 19.0 1.1 0.3 135 96 95 72 8 6 7 70

206 63 15.0 2.0 0.4 135 96 95 72 8 6 7 80

207 125 16.3 2.6 0.8 160 120 124 80 8 6 8 78

208 160 11.1 4.2 1.0 160 120 124 80 8 6 8 88

209 250 9.9 5.0 1.4 175 185 100 165 10 7 13 85

210 400 7.5 6.0 1.8 175 185 100 165 10 7 13 100

211 500 8.5 7.5 2.6 190 206 120 184 10 7 15 95

212 800 5.8 12.0 3.8 190 206 120 184 10 7 15 115

215 1250 5.8 16.0 5.0 230 254 152 228 10 7 19 124

216 1600 5.0 20.0 6.0 230 254 152 228 10 7 19 148

221 2000 5.0 23.0 6.8 260 290 176 258 14 9 22 141

222 2500 4.2 26.0 8.7 260 290 176 258 14 9 22 167

223 3200 3.4 33.0 13.5 283 330 200 298 14 9 25 150

224 5000 3.1 36.0 14.5 283 330 200 298 14 9 25 175

227* 6300 3.0 53.0 21.0 331 394 240 358 14 9 30 186

227* 8000 2.8 54.0 22.0 331 394 240 358 14 9 30 186

228* 10000 2.4 62.0 26.0 331 394 240 358 14 9 30 201

230* 12500 2.2 90.0 33.0 383 452 280 408 20 13 35 205

231* 18000 1.5 110.0 36.0 383 452 280 408 20 13 35 235

233* 25000 1.3 125.0 42.0 433 526 320 472 20 13 40 229

234* 30000 1.1 165.0 48.0 433 526 320 472 20 13 40 256

235* 40000 0.9 220.0 62.0 433 526 320 472 20 13 40 286

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 58: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type DTLThree-phase transformers to VDE 0532

58

Application

To supply electrical consumers with higher power consumption, e.g. furnaces, melting troughs, converter drives,production lines, etc. Customized specification and dimensions ensure optimal application.

Copyright © 2002-2005 SBA

Page 59: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

59

Internet: www.sba.de

Type DTLTHREE-PHASE TRANSFORMERS

Specifications

Output range 40 kVA – 250 kVA Input voltage max. 750 VOutput voltage max. 750 VOutput current to–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 1500 AFrequency 50-60 HzVector group Yy0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40°C

Overview

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated winding

� Resting on U- sections

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Short-circuit Total- Copper Dimensionsvoltage ur weight weight a1 b1 a2 b2 d c

kVA (DB) appr. % appr. kg appr. kg approx. mm

249 40 3.15 190.0 56.0 670 650 495 610 13 270

237 50 2.70 220.0 64.0 670 650 495 610 13 285

239 63 2.09 270.0 77.0 670 650 495 610 13 310

248 80 2.05 330.0 105.0 770 800 570 760 15 285

241 100 1.63 420.0 122.0 770 800 570 760 15 310

242 125 1.40 490.0 132.0 770 800 570 760 15 340

246 160 1.32 590.0 212.0 830 980 600 940 15 305

247 200 1.10 740.0 236.0 830 890 600 940 15 335

245 250 1.07 860.0 250.0 830 980 600 940 15 370

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 60: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type DSIThree-phase safety isolating transformers to VDE 0570-2-6 / EN 61558-2-6

Application

Transformers supplying electric circuits or devices working with safety extra-low voltage (SELV, max. 50 V) e.g. por-table tools.

60

Copyright © 2002-2005 SBA

Page 61: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Internet: www.sba.de

Type DSITHREE-PHASE SAFETY ISOLATING TRANSFORMERS

Specifications

Output range 40 VA – 18 kVA Input voltage max. 750 VOutput voltage max. 50 VOutput current at–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 1500 AFrequency 50-60 HzVector group Yy0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40°C

Overview

* With 2 eyebolts

61

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings by two-champer design (safe separation)

� Resting on angular brackets (DIN 41307)

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clam(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr. % appr. kg appr. kg approx. mm

205 40 19.0 1.1 0.3 160 96 104 72 8 6 70

206 63 15.0 2.0 0.4 160 96 104 72 8 6 80

207 125 16.3 2.6 0.8 180 120 130 80 8 6 78

208 160 11.1 4.2 1.0 180 120 130 80 8 6 88

209 250 9.9 5.0 1.4 210 185 100 165 10 7 85

210 320 7.5 6.0 1.8 210 185 100 165 10 7 100

211 500 8.5 7.5 2.6 230 206 120 184 10 7 95

212 800 5.8 12.0 3.8 230 206 120 184 10 7 115

215 1250 5.8 16.0 5.0 270 254 152 228 10 7 124

216 1600 5.0 20.0 6.0 270 254 152 228 10 7 148

221 2000 5.0 23.0 6.8 300 290 176 258 14 9 141

222 2500 4.2 26.0 8.7 300 290 176 258 14 9 167

223 3200 3.4 33.0 13.5 320 330 200 298 14 9 150

224 5000 3.1 36.0 14.5 320 330 200 298 14 9 175

227* 6300 3.0 53.0 21.0 365 394 240 358 14 9 186

228* 8000 2.4 62.0 36.0 365 394 240 358 14 9 201

229* 10000 2.4 80.0 32.0 365 394 240 358 14 9 216

230* 12500 2.2 90.0 33.0 420 452 280 408 20 13 205

231* 18000 1.5 110.0 36.0 420 452 280 408 20 13 235

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 62: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type DTTThree-phase isolating transformers to VDE 0570-2-4 / EN 61558-2-4

Application

Transformers supplying electric circuits or devices for which an electrical isolation from the feeding electric circuit isprescribed (e.g., portable tools, certain equipment in the chemical industry and in mining, etc.).

62

Copyright © 2002-2005 SBA

Page 63: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

63

Internet: www.sba.de

Type DTTTHREE-PHASE ISOLATING TRANSFORMERS

Specifications

Output range 40 VA – 40 kVA Input voltage max. 750 VOutput voltage max. 750 VOutput current at–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 1500 AFrequency 50-60 HzVector group Yy0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40°C

Overview

* With 2 eyebolts

63

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings by double/extra strong insulation(safe separation)

� Resting on angular brackets (DIN 41307)

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Voltage rise Total Copper Dimensionsin no-load weight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr. % appr. kg appr. kg approx. mm

205 40 19.0 1.1 0.3 95 48 50 34 4 7 116

206 63 15.0 2.0 0.4 95 57 50 43 4 7 116

207 125 16.3 2.6 0.8 120 82 81 46 6 8 134

208 160 11.1 4.2 1.0 120 92 81 57 6 8 134

209 250 9.9 5.0 1.4 150 101 106 61 7 13 172

210 400 7.5 6.0 1.8 150 116 106 76 7 13 172

211 500 8.5 7.5 2.6 180 106 106 66 7 13 188

212 800 5.8 12.0 3.8 180 126 106 86 7 13 188

215 1250 5.8 16.0 5.0 228 110 176 71 7 13 257

216 1600 5.0 20.0 6.0 228 134 176 95 7 13 257

221 2000 5.0 23.0 6.8 264 136 200 76 10 18 294

222 2500 4.2 26.0 8.7 264 162 200 102 10 18 294

223 3200 3.4 33.0 13.5 300 152 224 94 10 18 328

224 5000 3.1 36.0 14.5 300 177 224 119 10 18 328

227* 6300 3.0 53.0 21.0 360 183 264 125 10 18 371

227* 8000 2.8 54.0 22.0 360 183 264 125 10 18 371

228* 10000 2.4 62.0 26.0 360 198 264 140 10 18 371

230* 12500 2.2 90.0 33.0 420 213 316 143 13 20 435

231* 18000 1.5 110.0 36.0 420 243 316 173 13 20 435

233* 25000 1.3 125.0 42.0 480 233 356 157 13 20 490

234* 30000 1.1 165.0 48.0 480 260 356 184 13 20 490

235* 40000 0.9 220.0 62.0 480 290 356 214 13 20 490

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 64: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type DTMThree-phase isolating transformers to VDE 0100 part 710

VDE 0570-2-15 / EN 61558-2-15

Application

Isolating transformers supplying electric circuits or equipment in hospital rooms (e.g., bedrooms, examinationrooms, operation theaters, etc.).Isolating transformers are preferably used in IT systems and rooms with group 2 medical (application) equipment,i.e. the isolating transformer must not switch off automatically and conform to the standard for permanent incorpo-ration in protection class II (without protective conductor and with double or extra strong insulation of all parts ofthe transformer). The transformer is available for protection class I on request. The required protection class shouldexpressly be specified in the order.

64

Copyright © 2002-2005 SBA

Page 65: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Internet: www.sba.de

Type DTMSINGLE-PHASE ISOLATING TRANSFORMERS

Specifications

Output range 3.0 kVA – 8.0 kVAInput voltage 3 x 400 VOutput voltage 3 x 230 VOutput current max. 3 x 20,1AFrequency 50-60 HzVector group Yyn0 with shielding windingProtection class II (prepared)Protection index IP 00Insulation class BAmbient temperature max. 40° CShort-circuit voltage < 3%No-load current < 3%Inrush current < 12-times rated current

for installation in medical equipment rooms

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Due to the integration of a PTC thermistor in each coil, external monitoring arrangement protecting from overload must be provided

� Separated windings by shielding winding and double/extra strong insulation (safe separation)

� Required space according to DIN 41308

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(additional clamp type terminal on request)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

Special versions

� With wrapped thermal switches instead of PTC thermistors

� With lower inrush current (8 x) like in prior norm VDE 0107

� Designed to protection class I

� Wider output range (0.5 kVA - 10 kVA)

� Wider Input voltage range (max. 1000 V AC)

65

Overview

* With 2 eyebolts

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output gl/gl to VDE 0636-31 Total Copper- DimensionsRecommended fuse weight weight a1 b1 a2 b2 a3 b3 c

primary secondarykVA (DB) A A appr. kg appr. kg approx. mm

001-5160 3.2 16 10 38.0 16.5 300 192 224 119 10 18 328

227-5061* 4.0 16 10 53.0 22.0 360 183 264 125 10 18 371

2285052* 5.0 20 16 62.0 26.0 360 198 264 140 12 18 371

229-5002* 6.3 25 16 80.0 30.0 360 213 264 155 12 18 371

230-5021* 8.0 35 20 90.0 33.0 420 213 316 143 12 20 435

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 66: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type DTIThree-phase insulating transformers to VDE 0550 part 3

Application

Insulating transformers are power transformers whose rated voltage at the input and/or output side is higher than1000 V. The same standard applies to power transformers with output voltage(s) of more than 1 kV up to 15 kV(e.g., anode voltage generation for transmission tubes).

66

Copyright © 2002-2005 SBA

Page 67: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

* With 2 eyebolts

67

Internet: www.sba.de

Type DTITHREE-PHASE INSULATING TRANSFORMERS

Overview

Specifications

Output range 1 kVA – 10 kVAInput voltage max. 750 VOutput voltage max. 10 kVOutput current max. 10 AFrequency 50-60 HzVector group Yy0Protection class IProtection index IP 00Insulation class BAmbient temperature max. 40° C

[email protected] [email protected]

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Separated windings

� Resting on angular brackets (DIN 41307)

� Connection to insulators

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Rated output Total Copper Dimensionsweight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr. kg appr. kg approx. mm

205 1.1 0.3 135 96 104 72 8 6 75

206 2.0 0.4 135 96 104 72 8 6 85

207 2.6 0.8 160 120 124 92 8 6 94

208 4.2 1.0 160 120 124 92 8 6 94

209 5.0 1.4 175 185 100 165 10 7 90

210 6.0 1.8 175 185 100 165 10 7 105

211 7.5 2.6 190 206 120 184 10 7 100

212 12.0 3.8 190 206 120 184 10 7 120

215 16.0 5.0 230 254 152 228 10 7 130

216 20.0 6.0 230 254 152 228 10 7 155

221 23.0 6.8 260 290 176 258 14 9 148

222 26.0 8.7 260 290 176 258 14 9 174

223 33.0 13.5 283 330 200 298 14 9 156

224 36.0 14.5 283 330 200 298 14 9 182

227* 53.0 21.0 331 394 240 358 14 9 192

228* 62.0 26.0 331 394 240 358 14 9 208

229* 80.0 32.0 331 394 240 358 14 9 222

The values in the table above are for the thermal steady state at 40°C ambient temperature.

The rated output depends

strongly on the clearance

in air and creepage

distances which must be

maintained as a function

of the isolation voltage.

Page 68: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type DSSThree-phase autotransformers to VDE 0532

VDE 0570-2-13 / EN 61558-2-13

Application

To supply electrical consumers of all kinds. Substantial savings in comparison with transformers with separate win-dings. Custom sizes and design features ensure optimal application.

Always specify the throughput rating in your order!

68

Design rating=Throughput rating x (highest voltage) - (lowest voltage)

(highest voltage)

Copyright © 2002-2005 SBA

Page 69: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

Specifications

Design rating 40 VA – 40 kVAInput voltage max. 750 VOutput voltage max. 750 VOutput current at–Screw terminals max. 135 A–Studs max. 450 A–Flat termination max. 1500 AFrequency 50-60 HzVector group Ya0Protection class IProtection index IP 00Insulation class B/FAmbient temperature max. 40° C

Overview

* With 2 eyebolts

Type DssTHREE-PHASE AUTOTRANSFORMERS

69

Internet: www.sba.de

Construction

� Open construction (IP 00, incorporation up to max. IP 23)

� Resting on angular brackets (DIN 41307)

� Connections to safe-to-touch screw terminals in accordance with VBG 4 with self-releasing clamp(higher current ratings to studs or flat termination with bolt)

� High-grade, tropicalized vacuum impregnation in black polyester impregnating resin

� Wear-resistant, heat, UV and solvent resistant nameplate

� Special versions available on request

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Size Design rating Total Copper Dimensionsweight weight a1 b1 a2 b2 a3 b3 c

VA (DB) appr.kg appr. kg approx. mm

205 40 1.1 0.3 95 48 50 34 4 7 116

206 63 2.0 0.4 95 57 50 43 4 7 116

207 125 2.6 0.8 120 82 81 46 6 8 134

208 160 4.2 1.0 120 92 81 57 6 8 134

209 250 5.0 1.4 150 101 106 61 7 13 172

210 400 6.0 1.8 150 116 106 76 7 13 172

211 500 7.5 2.6 180 106 106 66 7 13 188

212 800 12.0 3.8 180 126 106 86 7 13 188

215 1250 16.0 5.0 228 110 176 71 7 13 257

216 1600 20.0 6.0 228 134 176 95 7 13 257

221 2000 23.0 6.8 264 136 200 76 10 18 294

222 2500 26.0 8.7 264 162 200 102 10 18 294

223 3200 33.0 13.5 300 152 224 94 10 18 328

224 5000 36.0 14.5 300 177 224 119 10 18 328

227* 6300 53.0 21.0 360 183 264 125 10 18 371

227* 8000 54.0 22.0 360 183 264 125 10 18 371

228* 10000 62.0 26.0 360 198 264 140 10 18 371

230* 12500 90.0 33.0 420 213 316 143 13 20 435

231* 18000 110.0 36.0 420 243 316 173 13 20 435

233* 25000 125.0 42.0 480 233 356 157 13 20 490

234* 30000 165.0 48.0 480 260 356 184 13 20 490

235* 40000 220.0 62.0 480 290 356 214 13 20 490

The values in the table above are for the thermal steady state at 40°C ambient temperature.

Page 70: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

1470

The following technical explanations provide useful informa-tion on important technical terms used in this catalog.Depending on the proposed use, additional or differentdefinitions may be required. The following explanations aretherefore not exhaustive.

FusingFusing at the primary side is somewhat of a problem becau-se the inrush current can be as high as 20 times the ratedinput current, which depends on the size and type of thetransformer. For this reason, the input side fusing in mostcases provides protection only against short circuit and thefuses are slow-blowing.Picking the right fuse on the secondary side is much easierbecause due to the attenuating effect of the primary win-ding, current peaks are not possible at the secondary side.Possible fuse protection for the secondary side:- Miniature fuse to EN 60127- Automatic circuit breaker type B/C

TapsTransformers can be made with primary side or secondaryside taps. Primary-side taps serve the adaptation to differentmains alternating voltages. If the taps keep within the rangeof +5%, no other transformer size is needed. Taps outsidethis range require the next bigger type.

An exception is when a winding is divided into two equalparts. In this case, no additional winding space is neededand the transformer can still be designed for two input vol-tages.If several secondary voltages are available, the taps aredesigned for the amperage of the highest voltage, unlessthe customer specifies otherwise.

As a consequence of this, the full rated output cannot betapped. If the output is needed at every voltage level, morewinding space is needed, i.e., a bigger transformer mayhave to be used. An exception is again when the winding isdivided into two and is followed by series or parallel con-nection.

Duty ratio, DRThe duty ratio (DR) of a transformer is the ratio betweenload time and cycle duration. Unless specified otherwise,the cycle duration is 10 min.

The reduction factor, f, indicates the possible reduction ofthe size in comparison with continual service.

Insulation structureThe following structures are possible:- Transformers with basic insulation (e.g., power trans-

formers for general service, control transformers)- Transformers with double or extra stroinsulation

(e.g.,safety isolating or isolating transformers)- Transformers without insulation between input and output

(so called autotransformers)

ton

ton + toffDR= X100%

General technical information

2 primary voltages

Secondary voltage

Transformer switched for 115V Transformer switched for 230V

DR % 100 80. 70 60 50 40 30 20 15 10

f 1,0 0.890,840,77 0,710,630,550,450,39 0,35

Page 71: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

71

Internet: www.sba.de

Insulation classesThe provisions of IEC 85 and IEC 216 describe the heat resi-stance if insulation classes.

Normally, we design transformers according to class B alt-hough most materials can resist much higher temperatures(e.g., copper wire and impregnating resin are at leastclass F resistant).

Short time operation If the design rating for continuous operation is smaller thanthe rated output, the transformer can be overloaded forshort periods provided it does not heat to more than the per-mitted overtemperature.

Short-circuit resistanceThe following distinctions are made:

Unconditionally short-circuit resistant transfomersare dimensioned in such a way that the temperature underoverload or short circuit conditions does not exceed the per-mitted limits. To ensure this, the size must at least be double,and the no-load voltage is significantly higher than the ratedvoltage.

Conditionally short-circuit resistant transformershave a built-in protection mechanism which opens the inputor output circuit when the transformer is overloaded or short-circuited (e. g., fuses, thermal links, PTC thermistor, thermalswitch).

Transformers without short-circuit resistance must be protected against overload or short circuit by amechanism that is not integrated in the transformer. This pro-tection must be provided by the user.

OutputThe rated output is the product of the rated output voltageand the rated output current (with 3-phase transformers, it is3 times the product). In case of several output voltages, therated output is the sum of the products of the rated outputvoltage and the rated output current of all circuits underload at a time.The design rating is defined as the output assigned to a sizewhich is defined by design characteristics.

Insulation class Highest permitted temperatureat rated service conditions

AEBFH

105°C120°C130°C155°C180°C

Previous continuous loadin % of rated output

Permitted duration (in minutes) of load in % of the rated output

150% 140% 130% 120% 110%

50 25 30 40 50 80

60 20 25 30 40 65

70 15 20 25 30 50

80 10 15 20 23 35

90 5 10 15 15 20

General technical information

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Page 72: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

Connection symbolsThe interconnection of the windings is identified by connecti-on symbols. A connection symbol consists of a capital, asmall letter and a number designating the phase relation.The capital letter stands for the primary winding and thesmall letter for the secondary winding. If no customization isrequired, 3-phase transformers are normally delivered instar-star connection.

n brought out at "fully loadable"

Loadability of star point with star-star connection (Yy0,Yy6, ya0)

If the star point conductor of the feeding system is solidlyconnected to the input-side star point of the transformer, thestart point can be loaded with the rated current, otherwiseonly with about 10 % of the phase-to-phase current.

100% loadability of the start point can be obtained with thefollowing connections without much a lot of arrangement.

--Star delta connection with secondary bringing out of thestar point (Dyn5)

--Star-interconnected star connection with secondary brin-ging out of the star point (Yzn5)

If a three-phase set is formed of three single-phase transfor-mers, the star point load is avoided.

Laws and regulationsUnless required otherwise, we make our transformers toreflect state-of-the art and comply with the following lawsand regulations:VDE 0100 part 710VDE 0532VDE 0550 part 3VDE 0570

Weights, dimensions and the construction may change asdesign revisions take place.

Protection classThe protection class is a design feature of a product whichdesignates safety against shock current.

Protection class I: Product with safety ground terminal andbasic insulation

Protection class II: Product without safety ground terminaland double or extra strong insulation.

1472

General technical information

DesignationCode letter Connection

symbol

Pictorial indicator Circuit symbolSecondarystar point

not availible

10% loadable

fully loadable

fully loadable

not availible

fully loadable

not availible

10% loadable

fully loadable

fully loadable

10% loadable

fully loadable

10% loadable

Page 73: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

73

Internet: www.sba.de

Protection index

The protection index marking consists of a code of two con-stant letters, viz. "IP" and two digits, e.g., IP 23.

Ambient temperature

If no non-standard ambient conditions are specified in theorder, the transformer is designed for ta=40°C. If the actualtemperature is higher, the rated output must be reduced asshown in the following figure.

WindingsSeparated windingsIn these transformers, the windings must not be in live contactwith each other, i.e., these windings are electrically isolatedfrom each other. Power is transferred only by induction.

Die Leistung wird hier rein induktiv übertragen.

Autotransformer windingsIn autotransformers, the primary and secondary windings arein live contact with each other.Autotransformers are therefore smaller than types with separa-ted windings. The smaller the difference between primary andsecondary voltage, the smaller the transformer.

Second digit Protection

Description Explanation

0 No protection No protection availible

1Protection againstdrops of water fal-ling vertically

Drops of water falling vertically shall have noharmful effect.

3Protection againstspray water

Water falling from any angle less than 60degrees from vertical shall have no harmfuleffect.

4Protection againstsplash water

Water splashing from any direction shall haveno harmful effect.

5

Protection againstwater jets

A jet of water from a nozzle directed at thetransformer from any direction shall have noharmful effect.

6Protection againstflooding

No harmful amount of water to which thetransformer is exposed during a temporaryflooding must enter.

7

Protection againstimmersion

If the transformer is immersed in water underspecified pressure and time, no harmfulamounts of water must enter the transformer

First digit Protection

Description Explanation

0

No protection No protection against contact of live parts

2

Protection againstmedium-size foreignobjects

Protection against contact of live parts byfingers Protection against entry of foreignobjects greater than 12 mm

4Protection againstgranular foreignobjects

Protection against contact of live parts byfingers with tools, wires or the like of morethan 1 mm thickness

5

Protection againstdeposits of dust

Complete protection against contact withlive parts.Protection against harmful dustdeposits. The penetration of dust is notcompletely prevented but the dust must notaffect operation.

6Protection againstpenetration of dust

Complete protection against contact withlive parts.Protection against penetration ofdust

General technical information

Primary voltage

Primary voltage

Secondary voltage

Secondary voltage

Design rating = Throughput rating x (highest voltage) - (lowest voltage)

(highest voltage)

100

95

90

85

80

75

Load

in %

of r

ated

outp

ut

40 45 50 55 60

Ambient conditions ta in °C

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Page 74: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

14

Type GEH

Application

for installation in transformers to comply with Protection index IP 23 and IP 54, resp.Material: 1.5 mm sheet steel, plastic coated, finish: RAL 7035 light gray.

Overview

74

Housing size SBA transformer housing Dimensionsa1 a2 b1 b2 b3 d c

approx. mm

110/1 UTS 127-...,128-...,129-... 520 144 500 460 50 11x15 570

110/2 UTS 130-...,131-..., 520 176 500 460 50 11x15 570

120 UTS 133-...,134-...,135-..., 580 196 550 510 50 11x15 650

130 DTS 223-...,224-... 580 224 440 400 50 11x15 510

140/1 DTS 227-...,228-... 640 264 500 460 50 11x15 570

140/2 DTS 230-...,231-... 640 316 500 460 50 11x15 570

150 DTS 233-...,234-...,235-..., 740 356 550 510 50 11x15 650

160 DTS 233-...,234-...,235-..., 825 356 630 590 50 11x15 710

230 DTS 249-...,237-...,239-... 910 380 650 610 50 11x15 825

240 DTS 248-...,241-...,242... 1060 480 600 560 50 11x15 1100

250 DTS 246-...,247-...,245-..., 1260 600 800 760 50 11x15 1200

Page 75: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

SBA-TrafoTech GmbHWinkelleite 1491332 HeiligenstadtTelefon 0 9198/8 09-19Telefax 0 9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 JenaTelefon 0 36 41/4514-0Telefax 0 36 41/4514-30

Internet: www.sba.de

75

Internet: www.sba.de

General Terms of Business 01/2002II..

I. GeneralBy placing the order, the buyer accepts these "General Terms of Business" asexcusive basis for transaction of business. Buyer's terms, if any, are herebyexpressly excluded and do not apply even in absence of our express objection.Any other agreements are only valid if made in writing.

IIII.. II. PricesOur prices are without obligation and quoted ex works without packaging andin EURO currency, exclusive of value-added tax, which will be charged at therate applicable at the time of delivery. Copper prices of 150.00 EUR or morefor each 100 kg lead to price adjustment prorated the specified weight.

IIIII.. III. Terms of payment/setting off1. Payment due to us is defined in calendar terms (§ 286 cl. 2 no. 1 BGB -

German Civil Code) and mature 30 days after invoice date.

2.-All payments must be made free supplier's point of payment; discount at 2%can be deducted from all payments made within 10 days of the invoice date.Deliveries to unknown buyers are only made COD.

3. The buyer can only set off payments which are not in dispute or are the sub-ject of a final court judgment.

IV. Contract conclusion /deliveries 1. Orders to agents, any collateral agreement, amendments and modifications

are only binding on us if made in writing.

2. Dimensions, output data and illustrations correspond to the specified products;deviations are expressly reserved.

3. All shipments are made ex works at buyer's risk. The risk passes to buyerwhen the consignment in a state ready for use has been shipped or collec-ted. This also applies to all shipments made free, in our own fleet of trucks orif the goods are consigned to buyer's order. Partial shipments which thebuyer can reasonably be expected to accept are permitted.

4. Goods shall be accepted immediately upon completion. If buyer delaysacceptance, we can charge warehousing cost at 0.5% of the invoice amountfor every month, including fractions thereof, subject to a maximum of 5% ofthe value of the goods.

5. All shipments are made by the agreed date as far as possible. We areresponsible for delays only in cases of intent or gross negligence and ifacting under the constraints of law provided the buyer can submit poof of thedamage caused. The damage is limited to 5% of the value partial delivery ordelivery which is delayed. Force majeure is cause for a reasonable extensionof the delivery period.

V. Liability for defectsWe are responsible for defects as defined in §§ 434, 435 BGB as follows:

1. All parts or services which become unusable or whose usability is substantial-ly limited for reasons before the passing of risk, in particular due to defects oftype, defective material or poor workmanship, within 60 months - irrespectiveof the operating time - calculated from the date at which the risk passed, shallat buyer's option be repaired free, delivered new or made new. Any defect must be communicated to us in writing without delay. The term forelectronic devices is 36 months. If buyer's choice (repair or replacement)entails unreasonably high cost, we can refer the buyer to a version which isless expensive for us.

2. Buyer must allow us reasonable time and opportunity for repairing a defect. Otherwise we are released from our liability for the defect.

3. Any other claims by buyer on us are excluded unless such claims are sub-stantiated in applicable law. Damage claims on grounds of impossibility ofperformance for which we are responsible or due to unavoidable statutoryrequirements are limited to 10 % of the value of that part of the deliverywhich cannot be used as intended.

VI. Retention of title1. All goods shipped remain our property until full payment of all amounts due

to us from the business transaction with the buyer is made or if payment ismade by check or draft until paid. The buyer can dispose of the goods in theordinary course of business.

2. The retention of title also extends to the full value of all products made by pro-cessing, mingling or combining our goods and we are also considered to bethe maker of these products. If in the processing, mingling or combination ofour goods with goods belonging to a third party that party's title survives, weacquire co-ownership in the new goods in the value represented by therespective invoice amounts of the processed goods.

3. Buyer assigns to us all claims on third parties created by the sale of the pro-cessed goods as security in the full amount or in the amount of our co-owner-ship (sub-article 2). Buyer can collect these amounts for our account until can-cellation or completion of buyer's payments to us.

4. Any seizure by a third party of goods or moneys belonging to us must becommunicated to us by buyer in writing without delay.

5. The goods and payment claims in lieu of goods must not be pledged or offered as security or assigned unless full payment has been made to us.

6. If the value of the securities exceeds the amount due to us by more than 20%, we will release an appropriate part of the securities in our option if so requested by the buyer

VII. Place of performance / legal venue1. Place of performance for supplies and payments is Heiligenstadt/Ofr. or

Jena.

2. If the buyer is a general merchant, the legal venue, including for summaryproceedings, is Bamberg or Jena.

3. The contract is subject to material German law to the exclusion of the UNConvention on Contracts for the International Sale of Goods (CISG).

VIII. SeverabilityIf a provision of these General Terms of Business should be or become invalid,such invalidity does not affect the other provisions. The provision lacking validitywill be replaced by another provision which as nearly as possible reflects theoriginal intention. If this is not possible, the contract is invalid if continuing itwould entail unreasonable hardship for either party.

[email protected] [email protected]

SBA-TrafoTech GmbHWinkelleite 1491332 Heiligenstadt, Germany Telephone +49 (0)9198/8 09-19Facsimile +49 (0)9198/8 09-30

SBA-Trafobau Jena GmbHIlmstraße 1807743 Jena, GermanyTelephone +49 (0)3641/4514-0Facsimile +49 (0)3641/4514-30

Page 76: TRANSFORMERS - Dewar Electronics · Isolating transformers for installation in hospitals Insulating transformers up to 10000 V High current transformers up to 2000 A Autotransformers

WWW.SBA.DE

2/20

05

SBA-TrafoTech GmbH

Winkelleite 1491332 Heiligenstadt, GermanyTelephone: +49 (0)9198/809-0Facsimile: +49 (0)9198/8 [email protected]

SBA-Trafobau Jena GmbH

Ilmstraße 1807743 Jena, GermanyTelephone: +49 (0)36 41/4514-0Facsimile: +49 (0) 36 41/[email protected]