TRANSFORMERS STANDARDS
IS-6600/IEC-60354: LOADING OF THE TRASNFORMER
IEC-60599 : interpretation of DGA results
CIGRE SC 12 Working Group 12.22 : Guidelines for conducting design reviews for transformers & reactor
IS/IEC 60076 and CIGRE SC 12: recommendations for short circuit test/calculations
NEMA TR-1: permitted noise levels.
IS-4253: regarding GASKETS
BS-5500: Post Weld Heat Treatment
BS-4360 / IS 2062: metal plate, bar and sections for fabrication
IS-2099 / IS-3347 / IS-12676/ IEC-60137: Electrical And Mechanical Characteristics Of Bushings & Testing Of Bushing
IS-335: Oil of oil filled transformer and bushings
IS 12463 (2000)/ IEC60296 : Testing of oil prior to energization
IEC 60076 : terminal marking and their physical position may be in bushing
IS:2705/IEC-60185 : Current Transformer
IS-2026 : different standards for OLTCs, Type test, Routine test, special test for transformers and Shunt reactors(IS 5553).
IS 12075 : Vibrations limits for motors
IS 325 : routine test for motors in OLTC
IS 5 : Paint for Motor
CIGRE report WG-12.17 - “Effect of particles on transformer dielectric strength”
IEC 61181/ CIGRE Guidelines : Acceptance Norms With Reference To Various Gas Generation Rates During The Temperature Rise Test
IEC -60599interpretation of DGA results
IEC 60296 Treatment Of New Oil
IS: 1866/IEC: 60422 : Reconditioning Of Used Oil (For Oil In Service)
IEEE C37.20 : Temperatures At Various Locations Of Cabinet/Box
IEC-61850 : for remote communication
IS: 2026 Part-III : HV neutral impulse test
IS:10028 : Criteria for providing oil soak pit and collection pit for various transformers
a) Top & bottom cooler shut-off valves (min. 200 mm) – 04 Nos.
b) Buchholz relay shut-off valve ((min. 80 mm) – 01 No.
c) Conservator shut-off valve at Conservator end (min. 80 mm) – 01 No.
d) Conservator drain valve (min. 25 mm) – 01 No.
e) Gas collection valve (min. 08 mm) – 01 No.
f) Transformer oil drain valve (Minimum 100mm) – 01 No.
g) Radiator shut-off valves (Top & bottom) (80 mm) – as per approved scheme
h) Transformer oil shut-off valves (200 mm) – as per approved scheme
i) Transformer oil reverse flow blocking devices (200 mm) – as per approved scheme
j) Fill & filter valves – Top & bottom (50 mm) – 02 Nos.
k) Cooler drain valves (50 mm) – 02 Nos.
l) Oil inlet valves for cooler bank (150 mm) - as per approved scheme
m) Sampling valves (15 mm) – 02 Nos.
n) Valves for vacuuming Top (25 mm) – 02 Nos.
o) Valves for vacuuming of Cooler circuit – as per approved scheme
p) Valves for vacuuming of Conservator – as per approved scheme
q) Thermo-siphon filter shut-off valves (100 mm) – 02 Nos.
r) Breather isolating valves - as per approved scheme
s) Sludge collection valve at bottom most point of tank - as per approved scheme
Adequate number of air release vents as per approved scheme