Page 1: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

Transitional Cluster Study

Attachment A

Group 2011 Cluster Study Transient Stability Plots

Page 2: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

1

2011 Heavy Summer Pre-Cluster Base Case No Outage Transient Bus Voltage Plots

2011 Heavy Summer Pre-Cluster Base Case No Outage Transient Frequency Plots

Page 3: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

2

2011 Heavy Summer Pre-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Pre-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 4: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

3

2011 Heavy Summer Pre-Cluster Base Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Pre-Cluster Base Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 5: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

4

2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 6: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

5

2011 Heavy Summer Pre-Cluster Base Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Pre-Cluster Base Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 7: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

6

2011 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 8: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

7

2011 Heavy Summer Pre-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Pre-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 9: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

8

2011 Heavy Summer Pre-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2011 Heavy Summer Pre-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 10: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

9

2011 Heavy Summer Pre-Cluster Base Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2011 Heavy Summer Pre-Cluster Base Case Path 42 outage w/RAS Transient Frequency Plots

Page 11: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

10

2011 Heavy Summer Pre-Cluster Base Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Bus Voltage Plots

2011 Heavy Summer Pre-Cluster Base Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Frequency Plots

Page 12: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

11

2011 Heavy Summer Post-Cluster Base Case No Outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster Base Case No Outage Transient Frequency Plots

Page 13: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

12

2011 Heavy Summer Post-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 14: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

13

2011 Heavy Summer Post-Cluster Base Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster Base Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 15: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

14

2011 Heavy Summer Post-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 16: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

15

2011 Heavy Summer Post-Cluster Base Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster Base Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 17: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

16

2011 Heavy Summer Post-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 18: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

17

2011 Heavy Summer Post-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 19: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

18

2011 Heavy Summer Post-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 20: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

19

2011 Heavy Summer Post-Cluster Base Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster Base Case Path 42 outage w/RAS Transient Frequency Plots

Page 21: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

20

2011 Heavy Summer Post-Cluster Base Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster Base Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Frequency Plots

Page 22: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

21

2011 Heavy Summer Post-Cluster w/ Mitigation Case No Outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster w/ Mitigation Case No Outage Transient Frequency Plots

Page 23: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

22

2011 Heavy Summer Post-Cluster w/ Mitigation Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster w/ Mitigation Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 24: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

23

2011 Heavy Summer Post-Cluster w/ Mitigation Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster w/ Mitigation Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 25: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

24

2011 Heavy Summer Post-Cluster w/ Mitigation Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster w/ Mitigation Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 26: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

25

2011 Heavy Summer Post-Cluster w/ Mitigation Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster w/ Mitigation Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 27: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

26

2011 Heavy Summer Post-Cluster w/ Mitigation Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster w/ Mitigation Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 28: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

27

2011 Heavy Summer Post-Cluster w/ Mitigation Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster w/ Mitigation Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 29: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

28

2011 Heavy Summer Post-Cluster w/ Mitigation Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster w/ Mitigation Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 30: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

29

2011 Heavy Summer Post-Cluster w/ Mitigation Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster w/ Mitigation Case Path 42 outage w/RAS Transient Frequency Plots

Page 31: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

30

2011 Heavy Summer Post-Cluster w/ Mitigation Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Bus Voltage Plots

2011 Heavy Summer Post-Cluster w/ Mitigation Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Frequency Plots

Page 32: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

31

2011 Light Winter Transient Stability Plots

Page 33: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

32

2011 Light Winter Pre-Cluster Base Case No Outage Transient Bus Voltage Plots

2011 Light Winter Pre-Cluster Base Case No Outage Transient Frequency Plots

Page 34: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

33

2011 Light Winter Pre-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2011 Light Winter Pre-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 35: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

34

2011 Light Winter Pre-Cluster Base Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2011 Light Winter Pre-Cluster Base Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 36: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

35

2011 Light Winter Pre-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2011 Light Winter Pre-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 37: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

36

2011 Light Winter Pre-Cluster Base Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2011 Light Winter Pre-Cluster Base Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 38: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

37

2011 Light Winter Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2011 Light Winter Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 39: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

38

2011 Light Winter Pre-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2011 Light Winter Pre-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 40: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

39

2011 Light Winter Pre-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2011 Light Winter Pre-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 41: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

40

2011 Light Winter Pre-Cluster Base Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2011 Light Winter Pre-Cluster Base Case Path 42 outage w/RAS Transient Frequency Plots

Page 42: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

41

2011 Light Winter Pre-Cluster Base Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Bus Voltage Plots

2011 Light Winter Pre-Cluster Base Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Frequency Plots

Page 43: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

42

2011 Light Winter Post-Cluster Base Case No Outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster Base Case No Outage Transient Frequency Plots

Page 44: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

43

2011 Light Winter Post-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 45: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

44

2011 Light Winter Post-Cluster Base Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster Base Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 46: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

45

2011 Light Winter Post-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 47: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

46

2011 Light Winter Post-Cluster Base Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster Base Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 48: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

47

2011 Light Winter Post-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 49: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

48

2011 Light Winter Post-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 50: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

49

2011 Light Winter Post-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2011 Light Winter Post-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 51: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

50

2011 Light Winter Post-Cluster Base Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2011 Light Winter Post-Cluster Base Case Path 42 outage w/RAS Transient Frequency Plots

Page 52: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

51

2011 Light Winter Post-Cluster Base Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Bus Voltage Plots

2011 Light Winter Post-Cluster Base Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Bus Voltage Plots

Page 53: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

52

2011 Light Winter Post-Cluster w/ Mitigation Case No Outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster w/ Mitigation Case No Outage Transient Frequency Plots

Page 54: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

53

2011 Light Winter Post-Cluster w/ Mitigation Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster w/ Mitigation Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 55: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

54

2011 Light Winter Post-Cluster w/ Mitigation Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster w/ Mitigation Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 56: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

55

2011 Light Winter Post-Cluster w/ Mitigation Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster w/ Mitigation Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 57: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

56

2011 Light Winter Post-Cluster w/ Mitigation Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster w/ Mitigation Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 58: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

57

2011 Light Winter Post-Cluster w/ Mitigation Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster w/ Mitigation Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 59: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

58

2011 Light Winter Post-Cluster w/ Mitigation Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2011 Light Winter Post-Cluster w/ Mitigation Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 60: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

59

2011 Light Winter Post-Cluster w/ Mitigation Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2011 Light Winter Post-Cluster w/ Mitigation Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 61: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

60

2011 Light Winter Post-Cluster w/ Mitigation Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2011 Light Winter Post-Cluster w/ Mitigation Case Path 42 outage w/RAS Transient Frequency Plots

Page 62: Transitional Cluster Study · 2012-07-13 · Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots 2011 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage

61

2011 Light Winter Post-Cluster w/ Mitigation Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Bus Voltage Plots

2011 Light Winter Post-Cluster w/ Mitigation Case Coachella –Devers & Coachella-Ramon outage w/ RAS Transient Frequency Plots