DESCRIPTION
Transmission & Substation 3 HURRICANE CHARLEY August 13, 2004 Distribution Substations Out of Service ……………………14 Failed Substation Transformers …………………………….. 1 Substation Regulators Effected ……………………………... 4 Switches Effected …………………………….………………… 0 Arrester Failures (# of Substations) ………………………… 5 Breaker Failures (Total) ………………………………………. 8 Transmission Breakers …………………………….. 2 Distribution Breakers ………………………………. 6 Restoration (# of Days After Storm Passes) ……………… 2TRANSCRIPT
Transmission Substation2004 Storm Season
Transmission & Substation
2
HURRICANE CHARLEYAugust 13, 2004
Transmission Sections Locked Out ………………………… 44
Transmission Structures Effected ………………………….. 220Transmission Structures Reported Down ……… 75Transmission Structures Reported Leaning …… 145
Transmission Phases Down …………………………………. 146
Sections Locked Out with Trees on Line …………………… 20
Transmission & Substation
3
HURRICANE CHARLEYAugust 13, 2004
Distribution Substations Out of Service …………………… 14
Failed Substation Transformers …………………………….. 1
Substation Regulators Effected ……………………………... 4
Switches Effected …………………………….………………… 0
Arrester Failures (# of Substations) ………………………… 5
Breaker Failures (Total) ………………………………………. 8Transmission Breakers …………………………….. 2Distribution Breakers ………………………………. 6
Restoration (# of Days After Storm Passes) ……………… 2
Transmission & Substation
4
HURRICANE CHARLEYAugust 13, 2004
Arcadia-Charlotte 69 kV Section
Transmission & Substation
5
HURRICANE CHARLEYAugust 13, 2004
Charlotte-Deepcreek 230 kV SectionPeace River Crossing
FiberCable
Transmission & Substation
6
HURRICANE CHARLEYAugust 13, 2004
Arcadia-Charlotte 69 kV Section
Transmission & Substation
7
HURRICANE CHARLEYAugust 13, 2004
Charlotte-Polo 230 kV Section
Transmission & Substation
8
HURRICANE FRANCESSeptember 3, 2004
Transmission Sections Locked Out ………………………… 108
Transmission Structures Effected ………………………….. 150Transmission Structures Reported Down ……… 56Transmission Structures Reported Leaning …… 94
Transmission Phases Down …………………………………. 47
Sections Locked Out with Trees on Line …………………… 29
Transmission & Substation
9
HURRICANE FRANCESSeptember 3, 2004
Distribution Substations Out of Service …………………… 54
Failed Substation Transformers …………………………….. 1
Substation Regulators Effected ……………………………... 5
Switches Effected …………………………….………………… 2
Arrester Failures (# of Substations) ………………………… 5
Breaker Failures (Total) ………………………………………. 20Transmission Breakers …………………………….. 1Distribution Breakers ………………………………. 19
Restoration (# of Days After Storm Passes) ……………… 2
Transmission & Substation
10
HURRICANE FRANCESSeptember 3, 2004
Port Mayaca-Bryant 69 kV Section
Transmission & Substation
11
HURRICANE FRANCESSeptember 3, 2004
Alva-Orange River 230 kV Section
Transmission & Substation
12
HURRICANE JEANNESeptember 25, 2004
Transmission Sections Locked Out ………………………… 80
Transmission Structures Effected ………………………….. 129Transmission Structures Reported Down ……… 48Transmission Structures Reported Leaning …… 81
Transmission Phases Down …………………………………. 88
Sections Locked Out with Trees on Line …………………… 9
Transmission & Substation
13
HURRICANE JEANNESeptember 25, 2004
Distribution Substations Out of Service …………………… 30
Failed Substation Transformers …………………………….. 1
Substation Regulators Effected ……………………………... 1
Switches Effected …………………………….………………… 4
Arrester Failures (# of Substations) ………………………… 2
Breaker Failures (Total) ………………………………………. 14Transmission Breakers …………………………….. 0Distribution Breakers ………………………………. 14
Restoration (# of Days After Storm Passes) ……………… 2
Transmission & Substation
14Saint Lucie Substation
HURRICANE JEANNESeptember 25, 2004