transmission system optimization in electrical power
TRANSCRIPT
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 1
Transmission System Optimization in Electrical
Power system –An Introductory Review
Tarun Mittal1, Amit Bhardwaj
2, Navpreet Singh Tung
3, Vikram Kumar Kamboj
4
1,4Member IEEE
1,2,3M.Tech Scholars, Lovely Professional University, Jalandhar, Punjab, India. 4Assistant Professor and Head of Deptt. (Electrical Engg.), CT Institute of Technology, Jalandhar, India.
___________________________________________________________________________
Abstract- This paper presents the basic principles of transmission system optimization .In recent years greater demands
have been placed on the transmission network and these demands will continue to increase because of the increasing
number of nonutility generators and heightened competition among utilities themselves. Increased demands on transmission
,absence of long term planning, and the need to provide open access to generating companies and customers ,all together
have created tendencies towards less security and reduced quality of supply. So that there is a great need to optimized
transmission system network in order to enhancing its capability ,flexibility and reliability for controlling this deregulated
environment and reducing the power system stresses.
Keywords- Interconnection(IC) ,power-flow(PF), compensation, FACTSs, Loading capability(LC), VSC’s.
___________________________________________________________________________
1. Introduction to Transmission Lines
Transmission lines are basically distributed parameter devices. For the study of fast switching transients, it is
necessary to model them in some detail. For example, the frequency response of a line can be approximated by
cascaded connection of π networks - a lumped parameter model. However for power system dynamic
performance studies involving frequencies below fundamental (synchronous frequency), the representation by a
single π circuit is adequate. As a matter of fact, for studies involving low frequency transients, the transmission
lines can be assumed to be in quasi-steady state - the voltages and currents can be assumed to be sinusoidal with
slowly varying amplitudes and phase angles. A basic assumption in the modelling of three phase transmission
lines is that they are symmetric. This implies that the self impedances of all the three phases are equal. Also, the
mutual impedances between any two phases are equal. An additional assumption is that the line parameters are
constant - the network is linear. It can be shown that, in steady state, a symmetric three phase linear network connected to synchronous generators has only fundamental frequency voltages or currents. On the other hand, a
lack of symmetry leads to unbalanced currents (with negative sequence components) which can result in third
harmonic voltage generation. The symmetry is disturbed during unbalanced faults such as single line to ground
or line to line faults. However, their duration is brief and the presence of harmonics can be neglected.
1.1 Modelling of Transmission Network
A single phase π equivalent of a transmission line is shown in Fig. 1 .1. However it is to be noted that the
coefficient matrices, inductance [L], resistance [R] and capacitance [C] are all 3x3 matrices. These are defined
as
Fig 1.1 A single phase π equivalent of transmission line
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 784
1.2 Transformation to D-Q Components
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 785
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 786
2. Tramsmission-System Parameters And Its Loading Capability
The interrelated parameters that governs the operation of transmission systems including series impedance,
shunt impedance, current, voltage, phase angle and the damping of oscillations at various frequencies below the
rated frequency. If we optimised these parameters by suitable techniques for eg. By FACTS CONTROLLERS
an emerging technology, by other compensating devices that is supplemented by high speed power electronics
switches( VSC’s, GTO’s ,IGBT’s)etc we can made possible to enable a line to carry power closer to its thermal
rating.
LOADING CAPABILITY LIMITS OF A TRANSMISSION SYSTEM-
Basically, there are three kinds of limitations:
1. Thermal
2. Dielectric
3. Stability
Thermal capability of an overhead transmission line is a function of the ambient temperature, wind
conditions, conditions of the conductor and ground clearance. It varies perhaps by a factor 2 to 1 due to
variable environment and loading history .The nominal rating of a line is generally decided on a
conservative basis, envisioning a worst ambient environment case scenario .Then there is a possibility
of upgrading a line by changing the conductor to that of higher current rating, which may in turn
require structural upgrading .Finally there is a possibility of converting a single-circuit to a double
circuit line. once the higher current capability is available, then the question arise how it should be
used. Will the extra power actually flow and be controllable?
Dielectric From an insulation point of view, many lines are designed conservatively. For a given
nominal voltage rating it is often possible to increase normal operation by +10% voltage (i.e ,500 KV-
550KV) or even higher. Care is then needed to ensure that dynamic and transient over voltages are with
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 787
in limits. Compensation techniques could be used to ensure acceptable over- voltage and power flow
conditions.
Stability There are number of stability issues that limits the transmission capability. These include:
1. Transient stability
2. Dynamic stability
3. Steady-state stability
4. Frequency collapse
5. Voltage collapse
6. Sub-synchronous resonance
The various transmission system compensation techniques can certainly be used to overcome any
of the stability limits, in which case the ultimate limit would be thermal and dielectric.
2 Basics of Power Transmission Networks
Transmission lines that carry power from the sources to loads, modern power systems are also highly
interconnected for economic reasons. The interconnected systems benefit by (a) exploiting load diversity (b)
sharing of generation reserves and (c) economy gained from the use of large effcient units without sacrificing
reliability. However, there is also a downside to ac system interconnection { the security can be adversely
affected as the disturbances initiated in a particular area can spread and propagate over the entire system
resulting in major blackouts caused by cascading outages.
2.1 CONCEPT OF REACTIVE POWER IN AC TRANSMISSION SYSTEM
In this an understanding of reactive power associated with power transmission networks is developed. To make
transmission networks operate within desired voltage limits, methods of making up or taking away reactive
power— hereafter called reactive-power control—are discussed. Before proceeding further, however, a
thorough understanding of the reactive power in ac systems is necessary. Upon energization, the ac networks
and the devices connected to them create associated time-varying electrical fields related to the applied voltage, as well as magnetic fields dependent on the current flow. As they build up, these fields store energy that is
released when they collapse. Apart from the energy dissipation in resistive components, all energy-coupling
devices, including transformers and energy-conversion devices (e.g., motors and generators), operate based on
their capacity to store and release energy. For the ac circuit shown in Fig. 2.1(a), instantaneous power from the
voltage source to the load Z/–f, in terms of the instantaneous voltage v and current i, is given as
where V and I are the respective root mean square (rms) values of v and i. Equations (2.1) and (2.2) are
pictorially represented in Fig. 2.1(b). Equation (2.2) comprises two double-frequency (2q) components. The first
term has an average value as well as a peak magnitude of VI cosf. This average value is the active power, P,
flowing from the source to the load. The second term has a zero average value, but its peak value is VI sin f.
Written in phasor domain, the complex power in the network in Fig. 2.1(a) is given by
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 788
where P is called the active power, which is measured in watts (W), and Q is called the reactive power, which is
measured in volt–ampere reactive (VAR). Comparing Eqs. (2.3) and (2.2), the peak value of the second
component of instantaneous power in Eq. (2.2) is identified as the reactive power. The reactive power is
essential for creating the needed coupling fields for energy devices. It constitutes voltage and current loading of
circuits but does not result in an average (active) power consumption and is, in fact, an important component in
all ac power networks. In high-power networks, active and reactive powers are measured in megawatts (MW) and MVAR, respectively. Figure 2.1(c) shows a commonly used power triangle. Electromagnetic devices store
energy in their magnetic fields. These devices draw lagging currents, thereby resulting in positive values of Q;
therefore, they are frequently referred to as the absorbers of reactive power. Electrostatic devices, on the other
hand, store electric energy in fields. These devices draw leading currents and result in a negative value of Q;
thus they are seen to be suppliers of reactive power. The convention for assigning signs to reactive power is
different for sources and loads, for which reason readers are urged to use a consistent notation of voltage and
current, to rely on the resulting sign of Q, and to not be confused by absorbers or suppliers of reactive power.
2.2.2 UNCOMPENSATED TRANSMISSION LINES
2.2.2.1 A Simple Case
To develop a good, qualitative understanding of the need for reactive-power control, let us consider a simple
case of a lossless short-transmission line connecting a source Vs to a load ZLᶲ (For simplicity, the line is
represented only by its inductive reactance Xl.) Figure 2.2 shows such a network with its parameters, as well as a
phasor diagram showing the relationship between voltages and currents. From Fig. 2.2(b), it is clear that
between the sending- and the receiving-end voltages, a magnitude variation, as well as a phase difference, is
created. The most significant part of the voltage drop in the line reactance (∆V1=ĪxXl) is due to the reactive
component of the load current, Ix. To keep the voltages in the network at nearly the rated value, two control
actions seem possible:
1. load compensation, and
2. system compensation.
1. Load Compensation It is possible to compensate for the reactive current Ix of the load by adding a parallel capacitive load so that Ic= −Ix. Doing so causes the effective power factor of the combination to become unity.
The absence of Ix eliminates the voltage drop ∆V1, bringing Vr closer in magnitude to Vs; this condition is called
load compensation. Actually, by charging extra for supplying the reactive power, a power utility company
makes it advantageous for customers to use load compensation on their premises. Loads compensated to the
unity power factor reduce the line drop but do not eliminate it; they still experience a drop of ∆V2 from jĪrXl..
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 789
2. System Compensation To regulate the receiving-end voltage at the rated value, a power utility may install a
reactive-power compensator as shown in Fig. 2.3. This compensator draws a reactive current toovercome both
components of the voltage drop ∆V1 and ∆V2as a consequence of the load current Il. through the line reactance
Xl. To compensate for ∆V2, an additional capacitive current, ∆Ic, over and above Ic that compensates for Ix, is
drawn by the compensator. When ∆ĪcXl = ∆V2, the receiving-end voltage, Vr, equals the sending-end voltage,
Vs. Such compensators are employed by power utilities to ensure the quality of supply to their customers [1].
2.2.2.2 Lossless Distributed Parameter Lines
Most power-transmission lines are characterized by distributed parameters: series resistance, r; series
inductance, l; shunt conductance, g; and shunt capacitance, c—all per-unit (pu) length. These parameters all
depend on the conductors’ size, spacing, clearance above the ground, and frequency and temperature of
operation. In addition, these parameters depend on the bundling arrangement of the line conductors and the
nearness to other parallel lines. The characteristic behaviour of a transmission line is dominated by its l and c
parameters. Parameters r and g account for the transmission losses. The fundamental equations governing the
propagation of energy along a line are the following wave equations:
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 790
These equations are used to calculate voltage and current anywhere on line, at a distance x from the sending end,
in terms of the sending-end voltage an current and the line parameters. In Eqs. (2.4) and (2.5),
Comparing Eqs. (2.7) and (2.8) and taking the directional notation of Fig. 2.4 into account, it is concluded that for a lossless line, Ps = − Pr , as expected. However, Qs≠ Qr because of the reactive-power
absorption/generation in the line. From Eqs. (2.7) and (2.8), the power flow from the sending end to the
receiving end is expressed as
In electrically short power lines, where βa is very small, it is possible to make a simplifying assumption that sinβa = ba or Z0 sin βa= Z0βa = ωla, where ωla=Xl is the total series reactance of a line. This substitution results
in the following well-recognized power equation:
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 791
Accordingly, the maximum power transfer is seen to depend on the line length. When the power-transfer
requirement for a given length of a line increases, higher transmission voltages of Vs and Vr must be selected.
So we examine only those aspects that enhance the understanding of the interplay between voltages on the line
and the resulting reactive-power flows.
2.2.2.3 Symmetrical Lines -When the voltage magnitudes at the two ends of a line are equal, that is, Vs
=Vr = V, the line is said to be symmetrical. Because power networks operate as voltage sources, attempts are
made to hold almost all node voltages at nearly rated values. A symmetrical line, therefore, presents a realistic
situation. From Eqs. (2.7) and (2.8) the following relationships are derived
2.2.2.4 Midpoint Conditions of a Symmetrical Line- The magnitude of the midpoint voltage
depends on the power transfer. This voltage influences the line insulation and therefore needs to be well
understood. For a symmetrical line where the end voltages are held at nominal values, the midpoint voltage
shows the highest magnitude variation. In terms of the midpoint voltage Vm, the receiving-end voltage of a
symmetrical line, from Eq. (2.4), is given as
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 792
2.3 CONCEPT OF POWER FLOW IN AC TRANSMISSION NETWORK-
A large majority of power transmission lines are AC lines operating at different voltages (10 kV to 800 kV). The
distribution networks generally operate below 100 kV while the bulk power is transmitted at higher voltages.
The lines operating at different voltages are connected through transformers which operate at high efficiency.
Traditionally, AC lines have no provision for the control of power flow. The mechanically operated circuit
breakers (CB) are meant for protection against faults (caused by flashovers due to over voltages on the lines or
reduced clearances to ground). A CB is rated for a limited number of open and close operations at a time and
cannot be used for power flow control. (unlike a high power electronic switch such as thyristor, GTO, IGBT,
IGCT, etc.). Fortunately, ac lines have inherent power flow control as the power flow is determined by the
power at the sending end or receiving end. For example, consider a transmission line connecting a generating
station to a load centre in Fig.2.5(a). Assuming the line to be lossless and ignoring the line charging, the power
flow (P) is given by
where X is the series line reactance. Assuming V1 and V2 to be held constants (through voltage regulators at the
two ends), the power injected by the power station determines the flow of power in the line. The difference in
the bus angles is automatically adjusted to enable P = PG (Note that usually there could be more than one line
transmitting power from a generating station to a load centre). If one or more lines trip, the output of the power
station may have to be reduced by tripping generators, so as to avoid overloading the remaining lines in
operation.
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 793
Fig. 2.5(b) shows another situation where a line supplies power to a load located at bus (2). Here also the eq.
(2.16) applies but the power flow in the line is determined by the load supplied. The essential difference
between the two situations is that in Fig. 2.5(a), the load centre is modelled as an infinite bus which can absorb
(theoretically) any amount of power supplied to it from the generating station. This model of the load centre
assumes that the generation available at the load centre is much higher than the power supplied from the remote
power station (obviously, the total load supplied at the load centre is equal to the net generation available at that
bus).
The reliability of the power supply at a load bus can be improved by arranging two (or more) sources of power
as shown in Fig. 2.6. Here, P1 is the output of G1 while P2 is the output of G2 (Note that we are neglecting
losses as before). However, the tripping of any one line will reduce the availability of power at the load bus. This problem can be overcome by providing a line (shown dotted in Fig. 2.6) to interconnect the two power
stations. Note that this results in the creation of a mesh in the transmission network. This improves the system
reliability, as tripping of any one line does not result in curtailment of the load. However, in steady state, P1 can
be higher or lower than PG1 (the output of G1). The actual power flows in the 3 lines forming a mesh are
determined by Kirchhoff's Voltage Law (KVL). In general, the addition of an (interconnecting) line can result in
increase of power flow in a line (while decreasing the power flow in some other line). This is an interesting
feature of AC transmission lines and not usually well understood (in the context of restructuring). In general, it
can be stated that in an uncontrolled AC transmission network with loops (to improve system reliability), the
power flows in individual lines are determined by KVL and do not follow the requirements of the contracts
(between energy producers and customers). In other words, it is almost impossible to ensure that the power flow
between two nodes follows a predetermined path. This is only feasible in radial networks (with no loops), but the reliability is adversely affected as even a single outage can result in load curtailment. Consider two power
systems, each with a single power station meeting its own local load, interconnected by a tie line as shown in
Fig. 2.7(a). In this case, the power flow in the tie line (P) in steady state is determined by the mismatch between
the generation and load in the individual areas. Under dynamic conditions, this power flow is determined from
the equivalent circuit shown in Fig. 2.7(b). If the capacity of the tie is small compared to the size (generation) of
the two areas, the angles ±1 and ±2 are not affected much by the tie line power flow. Thus, power flow in AC tie
is generally uncontrolled and it becomes essential to trip the tie during a disturbance, either to protect the tie line
or preserve system security. In comparison with a AC transmission line, the power flow in a HVDC line in
controlled and regulated. However, HVDC converter stations are expensive and HVDC option is used primarily
for (a) long distance bulk power transmission (b) interconnection of asynchronous systems and (c) underwater
(submarine) transmission. The application of HVDC transmission (using thyristor converters) is also
constrained by the problem of commutation failures affecting operation of multi terminal or multi-feed HVDC systems. This implies that HVDC links are primarily used for point-to-point transmission of power and
asynchronous interconnection (using Back to Back (BTB) links).
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 794
2.4 CONTROL OF POWER FLOW IN AC TRANSMISSION NETWORK-
We may like to control the power flow in a AC transmission line to (a) enhance power transfer capacity and or
(b) to change power flow under dynamic conditions (subjected to disturbances such as sudden increase in load,
line trip or generator outage) to ensure system stability and security. The stability can be affected by growing
low frequency, power oscillations (due to generator rotor swings), loss of synchronism and voltage collapse
caused by major disturbances.
where ±max (30±{40±) is selected depending on the stability margins and the stiffness of the terminal buses to
which the line is connected. For line lengths exceeding a limit, Pmax is less than the thermal limit on the power
transfer determined by the current carrying capacity of the conductors (Note this is also a function of the
ambient temperature). As the line length increases, X increases in a linear fashion and Pmax reduces as shown in
Fig. 2.8
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 795
The series compensation using series connected capacitors increases Pmax as the compensated value of the
series reactance (Xc) is given by
where kse is the degree of series compensation. The maximum value of kse that can be used depends on several
factors including the resistance of the conductors. Typically kse does not exceed 0.7. Fixed series capacitors have
been used since a long time for increasing power transfer in long lines. They are also most economical solutions
for this purpose. However, the control of series compensation using thyristor based FACTS Controllers in
Power Transmission and Distribution switches has been introduced only 10{15 years ago for fast power flow control. The use of Thyristor Controlled Reactors (TCR) in parallel with fixed capacitors for the control of Xc,
also helps in overcoming a major problem of Sub-synchronous Resonance (SSR) that causes instability of
torsional modes when series compensated lines are used to transmit power from turbo generators in steam power
stations. In tie lines of short lengths, the power flow can be controlled by introducing Phase Shifting
Transformer (PST) which has a complex turns ratio with magnitude of unity. The power flow in a lossless
transmission line with an ideal PST (see Fig. 2.9) is given by
Again, manually controlled PST is not fast enough under dynamic conditions. Thyristor switches can ensure fast
control over discrete (or continuous) values of Á, depending on the configuration of PST used. Pmax can also be
increased by controlling (regulating) the receiving end voltage of the AC line. When a generator supplies a unity
power factor load(see fig:2.5b) , the maximum power occurs when the load resistance is equal to the line
reactance. It is to be noted that V2 varies with the load and can be expressed as
By providing dynamic reactive power support at bus (2) as shown in Fig. (2.10), it is possible to regulate the bus
voltage magnitude. The reactive
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 796
Comparing eq. (2.22) with (2.16), it can be seen that the maximum power transfer can be doubled just by
providing dynamic reactive power support at the receiving end of the transmission line. This is in addition to the
voltage support at the sending end. It is to be noted that while steady state voltage support can be provided by
mechanically switched capacitors, the dynamic voltage support requires synchronous condenser or a power
electronic controller such as Static Var Compensator (SVC) or STATic synchronous COMpensator
(STATCOM).
3 TECHNIQUES OR METHODS TO OPTIMIZED OR COMPENSATE
TRANSMISSION SYSTEM NETWORK-
3.1 CONVENTIONAL CONTROL MECHANISMS
The lack of control on active- and reactive-power flow on a given line, embedded in an interconnected ac transmission network, was stated. Also, to maintain steady-state voltages and, in selected cases, to alter the
power-transmission capacity of lines, traditional use of shunt and series impedances was hinted. In a
conventional ac power system, however, most of the controllability exists at generating stations. For example,
generators called spinning reserves maintain an instantaneous balance between power demand and power
supply. These generators, in fact, are purposely operated at reduced power. Also, to regulate the system
frequency and for maintaining the system at the rated voltage, controls are exercised on selected generators
1. Automatic Generation Control (AGC)
The megawatt (MW) output of a generator is regulated by controlling the driving torque, Tm, provided by a
prime-mover turbine. In a conventional electromechanical system, it could be a steam or a hydraulic turbine.
The needed change in the turbine-output torque is achieved by controlling the steam/water input into the turbine.
Therefore, in situations where the output exceeds or falls below the input, a speed-governing system senses the
deviation in the generator speed because of the load-generation mismatch, adjusts the mechanical driving torque to restore the power balance, and returns the operating speed to its rated value. The speed-governor output is
invariably taken through several stages of mechanical amplification for controlling the inlet (steam/water)
valve/gate of the driving turbine. Figure 3.1 shows the basic speed-governing system of a generator supplying
an isolated load. The operation of this basic feedback-control system is enhanced by adding further control
inputs to help control the frequency of a large interconnection. In that role, the control system becomes an
automatic generation control (AGC) with supplementary signals.
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 797
To avoid competing control actions, in a multi generator unit station each speed-governor system is provided
with droop (R) characteristics through a proportional feedback loop (R, Hz/MW). Figure 3.2 shows an AGC on
the principal generating unit with supplementary control. In contrast, the second, third, and remaining
generating units in a multiunit station operate with their basic AGCs. In a complex interconnected system, the
supplementary control signal may be determined by a load-dispatch centre.
2. Excitation Control
The basic function of an exciter is to provide a dc source for field excitation of a synchronous generator. A
control on exciter voltage results in controlling the field current, which, in turn, controls the generated voltage.
When a synchronous generator is connected to a large system where the operating frequency and the terminal
voltages are largely unaffected by a generator, its excitation control causes its reactive power output to change.
In older power plants, a dc generator, also called an exciter, was mounted on the main generator shaft. A control
of the field excitation of the dc generator provided a controlled excitation source for the main generator. In
contrast, modern stations employ either a brushless exciter (an inverted 3-phase alternator with a solid-state
rectifier connecting the resulting dc source directly through the shaft to the field windings of the main generator)
or a static exciter (the use of a station supply with static rectifiers). An excitation-control system employs a
voltage controller to control the excitation voltage. This operation is typically recognized as an automatic
voltage regulator (AVR). However, because an excitation control operates quickly, several stabilizing and protective signals are invariably added to the basic voltage regulator. A power-system stabilizer (PSS) is
implemented by adding auxiliary damping signals derived from the shaft speed, or the terminal frequency, or the
power—an effective and frequently used technique for enhancing small-signal stability of the connected system.
Figure 3.3 shows the functionality of an excitation-control system.
3. Transformer Tap-Changer Control
Next to the generating units, transformers constitute the second family of major power-transmission-system
apparatuses. In addition to increasing and decreasing nominal voltages, many transformers are equipped with
tap-changers to realize a limited range of voltage control. This tap control can be carried out manually or
automatically. Two types of tap changers are usually available: offload tap changers, which perform adjustments when de-energized, and on-load tap changers, which are equipped with current-commutation capacity and are
operated under load. Tap changers may be provided on one of the two transformer windings as well as on
autotransformers. Because tap-changing transformers vary voltages and, therefore, the reactive power flow,
these transformers may be used as reactive-power-control devices. On-load tap-changing transformers are
usually employed to correct voltage profiles on an hourly or daily basis to accommodate load variations. Their
speed of operation is generally slow, and frequent operations result in electrical and mechanical wear and tear.
4. Phase-Shifting Transformers
A special form of a 3-phase–regulating transformer is realized by combining a transformer that is connected in
series with a line to a voltage transformer equipped with a tap changer. The windings of the voltage transformer
are so connected that on its secondary side, phase-quadrature voltages are generated and fed into the secondary
windings of the series transformer. Thus the addition of small, phase-quadrature voltage components to the phase voltages of the line creates phase-shifted output voltages without any appreciable change in magnitude.
A phase-shifting transformer is therefore able to introduce a phase shift in a line. Figure 1.4 shows such an
arrangement together with a phasor diagram. The phasor diagram shows the phase shift realized without an
appreciable change in magnitude by the injection of phase-quadrature voltage components in a 3-phase
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 798
system. When a phase-shifting transformer employs an on-load tap changer, controllable phase-shifting is
achieved. The interesting aspect of such phase shifters is that despite their low MVA capacity, by controlling the
phase shift they exercise a significant real-power control. Therefore, they are used to mitigate circulating power
flows in interconnected utilities. A promising application of these devices is in creating active-power regulation
on selected lines and securing active-power damping through the incorporation of auxiliary signals in their
feedback controllers. From this description, it is easy to visualize that an incremental in-phase component can
also be added in lines to alter only their voltage magnitudes, not their phase. The modification of voltage
magnitudes andor their phase by adding a control voltage is an important concept. It forms the basis of some
of the new FACTS devices discussed in this book. The injected voltage need not be realized through electromagnetic transformer–winding arrangements; instead, by using high-speed semiconductor switches such
as gate turn-off (GTO) thyristors, voltage source inverters (VSIs)—synchronized with the system frequency—
are produced. The application of a VSI to compensate the line voltage drop yields a new, fast, controllable
reactive-power compensator: the static synchronous series compensator (SSSC). The application of a VSI to
inject a phase-quadrature voltage in lines yields a new, fast, controllable phase shifter for active- power control.
Once a synchronized VSI is produced, it is indeed easy to regulate both the magnitude and the phase angle of
the injected voltages to yield a new, unified power-flow controller (UPFC).
3.2 Flexible AC Transmission System
Controllers-
3.2.1 General Description The large interconnected transmission networks (made up of predominantly overhead transmission lines) are
susceptible to faults caused by lightning discharges and decrease in insulation clearances by undergrowth. The
power flow in a transmission line is determined by Kirchhoff's laws for a specified power injections (both active
and reactive) at various nodes. While the loads in a power system vary by the time of the day in general, they
are also subject to variations caused by the weather (ambient temperature) and other unpredictable factors. The
generation pattern in a deregulated environment also tends to be variable (and hence less predictable). Thus, the
power flow in a transmission line can vary even under normal, steady state conditions. The occurrence of a
contingency (due to the tripping of a line, generator) can result in a sudden increase/decrease in the power flow.
This can result in overloading of some lines and consequent threat to system security.
A major disturbance can also result in the swinging of generator rotors which contribute to power swings in
transmission lines. It is possible that the system is subjected to transient instability and cascading outages as individual components (lines and generators) trip due to the action of protective relays. If the system is
operating close to the boundary of the small signal stability region, even a small disturbance can lead to large
power swings and blackouts. The increase in the loading of the transmission lines sometimes can lead to voltage
collapse due to the shortage of reactive power delivered at the load centres. This is due to the increased
consumption of the reactive power in the transmission network and the characteristics of the load (such as
induction motors supplying constant torque).
The factors mentioned in the previous paragraphs point to the problems faced in maintaining economic and
secure operation of large interconnected systems. The problems are eased if sufficient margins (in power
transfer) can be maintained. This is not feasible due to the difficulties in the expansion of the transmission
network caused by economic and environmental reasons. The required safe operating margin can be
substantially reduced by the introduction of fast dynamic control over reactive and active power by high power
electronic controllers. This can make the AC transmission network `flexible' to adapt to the changing conditions caused by contingencies and load variations. Flexible AC Transmission System (FACTS) is defined as
`Alternating current transmission systems incorporating power electronic-based and other static controllers to
enhance controllability and increase power transfer capability' [1,2]. The FACTS controller is defined as `a
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 799
power electronic based system and other static equipment that provide control of one or more AC transmission
system parameters'.
The FACTS controllers can be classified as-
1. Shunt connected controllers
2. Series connected controllers 3. Combined series-series controllers
4. Combined shunt-series controllers
Depending on the power electronic devices used in the control, the FACTS controllers can be classified as-
(A) Variable impedance type
(B) Voltage Source Converter (VSC) - based.
The variable impedance type controllers include:
(i) Static Var Compensator (SVC), (shunt connected)
(ii) Thyristor Controlled Series Capacitor or compensator (TCSC), (series connected)
(iii) Thyristor Controlled Phase Shifting Transformer (TCPST) of Static PST (combined shunt and series)
The VSC based FACTS controllers are:
(i) Static synchronous Compensator (STATCOM) (shunt connected)
(ii) Static Synchronous Series Compensator (SSSC) (series connected)
(iii) Interline Power Flow Controller (IPFC) (combined series-series)
(iv)Unified Power Flow Controller (UPFC) (combined shunt-series)
Some of the special purpose FACTS controllers are
(a) Thyristor Controller Braking Resistor (TCBR)
(b) Thyristor Controlled Voltage Limiter (TCVL)
(c) Thyristor Controlled Voltage Regulator (TCVR) (d) Inter-phase Power Controller (IPC)
(e) NGH-SSR damping
The FACTS controllers based on VSC have several advantages over the variable impedance type. For example,
a STATCOM is much more compact than a SVC for similar rating and is technically superior. It can supply
required reactive current even at low values of the bus voltage and can be designed to have in built short term
overload capability. Also, a STATCOM can supply active power if it has an energy source or large energy
storage at its DC terminals. The only drawback with VSC based controllers is the requirement of using self
commutating power semiconductor devices such as Gate Turn-off (GTO) thyristors, Insulated Gate Bipolar
Transistors (IGBT), Integrated Gate Commutated Thyristors (IGCT). Thyristors do not have this capability and
cannot be used although they are available in higher voltage ratings and tend to be cheaper with reduced losses.
However, the technical advantages with VSC based controllers coupled will emerging power semiconductor de-vices using silicon carbide technology are expected to lead to the wide spread use of VSC based controllers in
future. It is interesting to note that while SVC was the first FACTS controllers (which utilized the thyristor
valves developed in connection with HVDC line commutated convertors) several new FACTS controller based
on VSC have been developed. This has led to the introduction of VSC in HVDC transmission for ratings up to
300 MW.
3.2.2 EMERGING TRANSMISSION NETWORKS
A historic change is overtaking electrical power utility businesses. Customers are demanding their right to
choose electrical energy suppliers from competing
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 800
vendors—a movement that has arisen from the benefits of lower costs of such services as long-distance
telephone calls, natural-gas purchases, and air travel. The industries embracing these activities have been
recently deregulated, and in these sectors, competition has been introduced. The basic belief is that competition
leads to enhanced efficiency and thus lower costs and improved services. For nearly 100 years, electrical power
utilities worldwide have been vertically integrated, combining generation, transmission, distribution, and
servicing loads. Also, most such utilities have operated as monopolies within their geographic regions. Their method of operation has been ―power at cost,‖ and their principal financers have been governments. Therefore,
to many people the pressure of electrical power utilities to operate efficiently has been missing. Operating the
electrical energy sector competitively requires the unbundling of generation, transmission, and distribution.
Competition is expected to exist among generators as well as retailers. The transmission and distribution (i.e.,
the controlling wires) must, out of necessity, be regulated. The new order requires new agencies taking the
responsibility to link customers (loads) with generators (market operators) and, at the same time, to clearly
understand the limitations and capabilities of power-transmission and -distribution networks [22], [23].
On becoming responsible for its own business, a power-transmission company must make the best use of its
transmission capacity and ensure that transmission losses are reduced to their lowest values. Also, any loss of
transmission capacity means loss of income for the company; therefore, all actions must be taken to ensure that
unwanted circulating power is not clogging the available transmission capacity. In addition, energy congestion
in critical transmission corridors must be avoided to eliminate the risk of missed business opportunities. Finally, to offer the greatest flexibility to market operators, a transmission company must create the maximum safe
operating limits to allow power injection and tapping from its buses without risking stable operation. The
success of a transmission company depends on offering the maximum available transmission capacity (ATC) on
its lines. From the foregoing discussion, it is evident that in the emerging electrical energy business,
transmission companies have a greater need to make their networks more flexible. Fortunately, advances in
power-electronics technology now offer new fast, controllable FACTS controllers to secure the needed
flexibility[15], [22], [23].The subject matter contained in this book is intended to assist engineers seeking
FACTS knowledge and help utilities meet the energy challenge.
Conclusion In this paper,we introduced basic principles and optimization techniques of transmission system which will help
future researchers to dig out the innovative solution for transmission system.
REFERENCES [1] C. Adamson and N. G. Hingorani, High-Voltage Direct Current Power Transmission, Garraway, 1960.
[2] E. W. Kimbark, Direct Current Transmission, Vol. 1, John Wiley and Sons, New York, 1971.
[3] E. Uhlmann, Power Transmission by Direct Current, Springer-Verlag, 1975.
[4] J. Arrillaga, High-Voltage Direct Current Transmission, Peter Peregrinus, 1983.
[5] K. R. Padiyar , HVDC Power Transmission Systems, Wiley Eastern Limited, New Delhi, India, 1990.
[6] IEEE Power Engineering Society/CIGRE, FACTS Overview, Publication 95TP108, IEEE Press, New York, 1995.
[7] N. G. Hingorani and L. Gyugyi, Understanding FACTS, IEEE Press, New York, 1999.
[8] Y. H. Song and A. T. Johns, Eds., Flexible AC Transmission Systems (FACTS), IEE Press, London, 1999.
[9] IEEE Power Engineering Society, FACTS Applications, Publication 96TP116-0, IEEE Press, New York, 1996.
[10] W. H. Litzenberger, Ed., ―An Annotated Bibliography of High-Voltage Direct-Current Transmission, 1989–1991,‖ Published by the
Bonneville Power Administration (BPA) and the Western Area Power Administration, Portland, OR, 1992.
[11] W. H. Litzenberger, Ed., ―An Annotated Bibliography of High-Voltage Direct-Current Transmission and Flexible AC Transmission
(FACTS) Devices, 1991–1993,‖Published by the Bonneville Power Admnistration (BPA) and the Western Area Power Administration,
Portland, OR, 1994.
[12] W. H. Litzenberger and R. K. Varma, Eds., ―An Annotated Bibliography of High- Voltage Direct-Current Transmission and FACTS
Devices, 1994–1995,‖ Published by the Bonneville Power Administration (BPA) and the U.S. Department of Energy, Portland, OR, 1996.
[13] W. H. Litzenberger, R. K. Varma, and J. D. Flanagan, Eds., ―An Annotated Bibliography of High-Voltage Direct-Current Transmission
and FACTS Devices, 1996–1997,‖ Published by the Electric Power Research Institute (EPRI) and the Bonneville Power Administration
(BPA), Portland, OR, 1998.
[14] CIGRE Working Group 14.29, ―Coordination of Controls of Multiple FACTSHVDC Links in the Same System,‖ CIGRE Technical
Brochure No. 149, Paris, December 1999.
[15] Electric Power Research Institute (EPRI) Report, ―Guide for Economic Evaluation of Flexible AC Transmission Systems (FACTS) in
Open Access Environments,‖ EPRI TR 108500, Final report prepared by General Electric Company (GE), Schenectady, NY, August 1997.
[16] C. E. Grund et al., ―Dynamic Performance Characteristics of North American HVDC Systems for Transient and Dynamic Stability
Evaluations,‖ IEEE Committee Report, IEEE Transactions on Power Apparatus and Systems, Vol. PAS–100, No. 7, July 1981, pp. 3356–
3364.
[17] IEEE Committee Report, ―A Description of Discrete Supplementary Controls for Stability,‖ IEEE Transactions on Power Apparatus
and Systems, Vol. PAS–97, No. 1, JanuaryFebruary 1978, pp. 146–165.
[18] R.W. De Doncker, O. Demirci, S. Arthur, and V. Temple, ―Characteristics of GTOs and High-Voltage MCTs in High Power Soft-
Switching Converters,‖ IEEE Transactions on Industry Applications, Vol. 30, No. 6, NovemberDecember 1994, pp. 1548–1556.
[19] Silicon Power Corporation Product Catalog, ―Introduction to MTO,‖ August 1995.
[20] I. A. Erinmez and A. M. Foss, Eds., ―Static Synchronous Compensator (STATCOM),‖ Working Group 14.19, CIGRE Study
Committee 14, Document No. 144, August 1999.
[21] CIGRE Task Force 14-27, ―Unified Power Flow Controller,‖ CIGRE Technical Brochure, 1998.
[22] CIGRE Task Force 38.02.17, ―Advanced Angle Stability Controls,‖ CIGRE Technical Brochure No. 155, Paris, April 2000.
International Journal of Emerging trends in Engineering and Development ISSN 2249-6149
Available online on http://www.rspublication.com/ijeted/ijeted_index.htm Issue 2, Vol.5 (July 2012)
Page 801
[23] CIGRE Task Force 38.02.16, ―Impact of Interactions Among Power System Controls,‖ CIGRE Technical No. Brochure 166, Paris,
August 2000
[24]. T.J.E. Miller, Reactive Power Control in Electric Systems, John Wiley (New York), 1982
[25] L. Barthold et aI, "Static shunt device for reactive power control", CIGRE, Paper 31-08, 1974
[26] K. Reichert, "Controllable reactive compensation", Int. J. of Electric Power and Energy Systems, Vol. 4, No.1, 1982, pp. 51-61
[27] L.Gyugyi, "Power electronics in electric utilities: Static var compensators", Proc. IEEE, Vol. 76, No.4, 1988, pp. 483-494
[28] L. Gyugyi, "Reactive power generation and control by thyristor circuits" , IEEE Trans. on Ind. Applications, Vol. IA-15, No.5, 1979,
pp. 521-531
[29] R.L. Hauth and R.J. Moran, "Introduction to static var systems for voltage and var control", IEEE Thtorial Course, 'Power Electronics
Applications in Power Systems', 78, EH 0135-4-PWR, 1978
[30] M.M. Govrilovic et aI, "Bibliography of static var compensators", IEEE Trans. on Power Apparatus and Syste!lls, Vol. PAS-102, No.
12, 1983, pp. 3744-3752
[31] D. Mc Gillis et aI, "Role of static compensations particular to James Bay System", Proc. lEE, Vol. 128, Pt. C, No.6, 1981, pp. 389-393
[32] C.W. Edwards et al, "Advanced static var generator employing GTO thyristors", IEEE Trans. on Power Delivery, PWRD-3, No.4,
1988, pp. 1622-1627
[33] L. Gyugyi et aI, "Advanced static var compensator using gate turn-off thyristors for utility applications", CIGRE Paper 23-203, 1990
[34] H. Mehta et al, "Static condenser for flexible AC transmission systems", FACTS EPRI Workshop, May 1992
[35] J. Douglas, "FACTS - The delivery system of the future", EPRI Journal, Oct/Nov. 1992, pp. 5-11
[36] M.H. Kent et al, "Dynamic modelling of loads in stability studies", IEEE Trans. Vol. PAS-88, No.5, 1969, pp. 756-763
[38] C.T. Nguyen et al, "Determination of power system load characteristics using a digital data-acquisition system", CIGRE Conf., Paper
31-05, 1978
[39] C. T. Nguyen et al, "Load characteristics and stability of the Hydro-Quebec system", Paper A 79 438-3 presented at IEEE PES Summer
Meeting, July 1979
[40] M.S. Chen et aI, "Determining the static and dynamic characteristics of power system loads", CIGRE Conf., Paper 31-11, 1978
[41] K. Srinivasan et aI, "Closed loop load response to random perturbations" , IEEE Trans. Vol PAS-98, No.5, 1979, pp. 1591-1595
[42]. K.R. Padiyar and P. Rajasekharam, "Effects of induction motor load on dynamic stability of power systems", Int. J. of Elec. Machines
and Power Systems, Vol. 9, 1984, pp. 269-283
[43]. K.R. Padiyar and N. Prabhakaran, "Digital simulation of three phase induction motors using hybrid models", J. of loot. of Enggrs (I),
Vol. 63, pt ELI, Aug. 1982, pp. 23-31
[44] D.J. Hill, "Nonlinear dynamic load models with recovery for voltage stability studies", IEEE Trans. on Power Systems, Vol. 8, No.1,
1993, pp. 166-176
BIOGRAPHIES-
Tarun Mittal is an M-Tech Scholar in Electrical Engg., School of Electrical and Electronic., Lovely
Professional University, India. He received his B-Tech in Electrical Engg. from PTU Jalandhar. His area of interest involves Power Electronics, FACTS Devices,Transmission System, Application of power electronics in power quality issues. (email -mittal.9009@ gmail.com)
Navpreet Singh Tung is an M-Tech Scholar in Electrical Engg., School of Electrical and Electronics Engineering. , Lovely Professional University, India. He received his B-Tech in Instrumentation and Control from NIT Jalandhar. His area of interest involves Power system planning, Power Converters, Unit Commitment,Application..of..power..electronics in power quality issues. He is an IEEE member.(e-mail: navpreet.tung@ ieee.org).
Amit Bhardwaj was born in district Rohtak, Haryana, India in 1990. He received his B.Tech. degree in
Electrical Engineering from Maharishi Markandeshwar University, Ambala, Haryana, INDIA in 2011. He is currently pursuing M.Tech. in Electrical Engg. from Lovely Professional University, Jalandhar, India . His area of interests are the development of methodologies for the Optimization and Planning of Electrical Power Systems. (e-mail: amitbdwj47@ gmail.com).
Vikram Kumar Kamboj is Ph.D Research scholar in Punjab Technical University, Jalandhar, Punjab (INDIA). Presently, he is working as Assistant Professor and Head of the Department, EEE in CT Institute of Technology, Jalandhar, Punjab, INDIA. His area of interests includes Reliability, Optimization and Planning of Electrical Power System. (e-mail: kamboj.vikram@
gmail.com).