SEER up to 14.50 3 to 5 Tons Cooling Capacity - 32,800 to 92,000 Btuh MODEL NUMBER IDENTIFICATION T S A 036 S 4 N 4 1 Y Major Design Sequence A = 1st Generation B = 2nd Generation Unit Type S = Split System Air Conditioner Brand/Family T = T-Class™ Product Line Cooling Efficiency S = Standard Efficiency Minor Design Sequence 1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision Voltage Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz J = 575V−3 phase−60hz Nominal Cooling Capacity − Tons 036 = 3 Tons 042 = 3.5 Tons 048 = 4 Tons 060 = 5 Tons Refrigerant Type 4 = R−410A Part Load Capability N = No part load, Single Circuit Coil Type 4 = Four-Sided AIR CONDITIONERS TS T−CLASS™ SPLIT SYSTEM UNITS Standard Efficiency - R-410A - 60 HZ Bulletin No. 210461 November 2017 Supersedes August 2017 PRODUCT SPECIFICATIONS

Upload: others

Post on 04-Apr-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

SEER up to 14.503 to 5 Tons

Cooling Capacity - 32,800 to 92,000 BtuhMODEL NUMBER IDENTIFICATION

T S A 036 S 4 N 4 1 Y

Major Design Sequence A = 1st Generation

B = 2nd Generation

Unit Type S = Split System Air Conditioner

Brand/Family T = T-Class™ Product Line

Cooling Efficiency S = Standard Efficiency

Minor Design Sequence 1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision

Voltage Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz J = 575V−3 phase−60hz

Nominal Cooling Capacity − Tons 036 = 3 Tons

042 = 3.5 Tons 048 = 4 Tons 060 = 5 Tons

Refrigerant Type 4 = R−410A

Part Load Capability N = No part load, Single Circuit

Coil Type 4 = Four-Sided

A I R C O N D I T I O N E R S

TST−CLASS™ SPLIT SYSTEM UNITSStandard Efficiency - R-410A - 60 HZ

Bulletin No. 210461 November 2017

Supersedes August 2017P R O D U C T S P E C I F I C AT I O N S

TS 3-5 TON STANDARD EFFICIENCY AIR CONDITIONERS

Page 2: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 2

FEATURES

WARRANTY

Compressor - Limited warranty for five years.

All other covered components - One year.

Refer to Lennox Equipment Limited Warranty certificate included with unit for specific details.

APPROVALSCertified in Accordance with the USE certification program, which is based on AHRI Standard 210/240-2008.Sound rated in Lennox reverberant sound test room in Accordance with test conditions included in AHRI Standard 270-2008.Tested in the Lennox Research Laboratory environmental test room.Rated According to U.S. Department of Energy (DOE) test procedures.Units and components within bonded for grounding to meet safety standards for servicing required by UL, NEC and CEC.Units are ETL certified for the U.S. and Canada.ISO 9001 Registered Manufacturing Quality System.

APPLICATIONSSEER up to 14.50.3 through 5 ton.Three-phase power supply.Sound levels as low as 76 dB.Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof.Matching add-on furnace indoor coils or air handlers provide a wide range of cooling capacities and applications. See AHRI System Matches.See Indoor Coils and Air Handlers sections for data.Units shipped completely factory assembled, piped and wired. Each unit test operated at the factory ensuring proper operation.Installer must set air conditioner, connect refrigerant lines and make electrical connections to complete job.For expanded ratings, see www.LennoxPROs.com.

REFRIGERATION SYSTEMR-410A RefrigerantNon-chlorine, ozone friendly, R-410A.Unit pre-charged with refrigerant.See Specification table.

Outdoor Coil FanDirect drive fan moves large air volumes uniformly through entire condenser coil for high refrigerant cooling capacity.Vertical air discharge minimizes operating sounds and eliminates damage to lawn and shrubs.Fan motor has ball bearings and is inherently protected.Motor totally enclosed for maximum protection from weather, dust and corrosion.Rain shield on motor provides additional protection from moisture.Louvered steel top fan guard furnished as standard.Fan service access accomplished by removal of top panel.

High Pressure SwitchProtects the system from high pressure conditions that can be a result of fan failure or a blocked/dirty coil.Automatic reset.

A

B

B

C

D

E

F

CONTENTSAHRI System Matches............................................... 10AHRI System Matches - Multiple Outdoor Units ........ 46Dimensions .................................................................. 7Electrical Data.............................................................. 6Features....................................................................... 2Installation Clearances ................................................ 8Model Number Identification ........................................ 1Optional Accessories - Order Separately..................... 6Optional Conventional Temperature Control Systems . 5Sound Data .................................................................. 8Specifications............................................................... 6

Page 3: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3

FEATURES

REFRIGERATION SYSTEM (continued)Copper Tube/Enhanced Fin CoilLennox designed and fabricated coil.Ripple-edged aluminum fins.Copper tube construction.Lanced fins provide maximum exposure of fin surface to air stream resulting in excellent heat transfer.Fin collars grip tubing for maximum contact area.Flared shoulder tubing connections/silver soldering construction.Coil is factory tested under high pressure to ensure leakproof construction.Entire coil is accessible for cleaning.PVC coated steel wire coil guard furnished.

Optional Accessories

Expansion Valve KitsMust be ordered separately and field installed on certain indoor units. See Expansion Valve Kit Usage Table.Chatleff-style fittings.

Loss of Charge Switch KitHelps protect the compressor from damage due low refrigerant charge conditions.SPST, normally-closed switch, automatic reset switch mounted on suction line.

Refrigerant Line KitsRefrigerant lines (suction & liquid) are shipped refrigeration clean. Lines are cleaned, dried, pressurized and sealed at factory.Suction line fully insulated.Lines are stubbed at both ends.Not available for -060 models. Must be field fabricated.

C

COMPRESSORScroll CompressorCompressor features high efficiency with uniform suction flow, constant discharge flow and high volumetric efficiency and quiet operation.Compressor consists of two involute spiral scrolls matched together to generate a series of crescent shaped gas pockets between them.During compression, one scroll remains stationary while the other scroll orbits around it.Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates.As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced.When pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls.During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle.Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency.Scroll compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to to be worked toward the center and discharged.Low gas pulses during compression reduces operational sound levels.Compressor motor is internally protected from excessive current and temperature.Compressor is installed in the unit on resilient rubber mounts for vibration free operation.

Compressor Crankcase HeaterProtects against refrigerant migration that can occur during low ambient operation.

Optional Accessories

Compressor Sound CoverA reinforced vinyl compressor cover containing a 1-1/2 inch thick batt of fiberglass insulation.All open edges are sealed with a one-inch wide hook and loop fastening tape.

D

Page 4: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 4

CABINET

Heavy gauge steel cabinet with five station metal wash process.Powder paint finish provides superior rust and corrosion protection.Control box is conveniently located with all controls factory wired.Corner patch plate allows access to compressor components.Drainage holes are provided in base section for moisture removal.

PermaGuard™ Unit BaseDurable zinc-coated base section resists rust and corrosion.

Refrigerant Line Connections, Electrical Inlets, Service ValvesSweat connection suction and liquid lines are located on corner of unit cabinet.Fully serviceable brass service valves prevent corrosion and provide access to refrigerant system. Suction valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system.Refrigerant line connections and field wiring inlets are located in one central area of cabinet for easy access. See dimension drawing.

Optional Accessories

Hail GuardsConstructed of louvered, heavy-gauge steel painted to match cabinet.Surrounds unit on all four sides to prevent damage to the coil.

Unit Stand-Off KitBlack high density polyethylene feet are available to raise unit off of mounting surface away from damaging moisture.Four feet are furnished per order number.

E

F

FEATURES

CONTROLS

Optional Accessories

L Connection® NetworkComplete building automation control system for single or multi-zone applications. Options include local interface, software for local or remote communication, and hardware for networking other control functions. See L Connection Network Product Specifications Bulletin for details.

Compressor Low Ambient Cut-Off SwitchNon-adjustable switch (low ambient cut-out) prevents compressor operation when outdoor temperature is below 35°F.

Compressor Time-Off ControlKit prevents compressor short-cycling and allows time for suction and discharge pressure to equalize.Permits compressor start-up in an unloaded condition.Automatic reset with 5 minute delay between compressor shut-off and start-up.

Indoor Blower Off Delay RelayDelays the indoor blower-off time during the cooling cycle.See AHRI System Matches for usage.

Low Ambient KitAir conditioners operate satisfactorily down to 45°F outdoor air temperature without any additional controls.Two low ambient control options are available for field installation:1. Low Ambient Control Kit (30°F) - Allows unit

operation down to 30°F.2. Low Ambient Control (0°F) - Allows unit operation

down to 0°F. Requires Speed Control and Weatherproof Kit (ordered separately). Available for 208/230V models only.

NOTE - Freezestat should be installed on compressors equipped with a Low Ambient Kit.

FreezestatInstalls on or near the vapor line of the indoor coil or on the suction line.Senses suction line temperature and cycles the compressor off when suction line temperature falls below it’s setpoint.Opens at 29°F and closes at 58°F.

ThermostatThermostat not furnished with unit. See Thermostat bulletins in Controls Section and Lennox Price Book.

Page 5: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 5

OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS

Item Model No.

Catalog No.

COMFORTSENSE® 7500 COMMERCIAL 7-DAY PROGRAMMABLE THERMOSTAT

• Four-Stage Heating / Two-Stage Cooling Universal Multi-Stage• Intuitive Touchscreen Interface• Remote Indoor Temperature Sensing with Averaging• Outside or Discharge Air Temperature Display• Full Seven-Day Programming• Four Time Periods Per Day• Occupancy Scheduling with Economizer Relay Control• Away Mode• Holiday Scheduling• Smooth Setback Recovery (SSR)• Performance Reports• Notifications/Reminders• Dehumidification/Humiditrol® Control for Split Systems and Rooftop Units• Economizer Relay Control• Backlit Display• Wallplate Furnished

C0STAT06FF1L 13H15

Optional Accessories1 Remote non-adjustable wall mount 20k temperature sensor C0SNZN01AE2- 47W361 Remote non-adjustable wall mount 10k temperature sensor C0SNZN73AE1- 47W37Remote non-adjustable discharge air (duct mount) temperature sensor C0SNDC00AE1- 19L22Outdoor temperature sensor C0SNSR03AE1- X2658Locking cover (clear) C0MISC15AE1- 39P211 R emote sensors can be applied in any of the following combinations:

One Sensor - (1) 47W36 Two Sensors - (2) 47W37 Three Sensors - (2) 47W36 and (1) 47W37 Four Sensors - (4) 47W36 Five Sensors - (3) 47W36 and (2) 47W37

COMFORTSENSE® 3000 COMMERCIAL 5-2 DAY PROGRAMMABLE THERMOSTAT

MAINT

Commercial

• Two-Stage Heating / Two-Stage Cooling Conventional Systems• Intuitive Interface• 5-2 Day Programming• Program Hold• Remote Indoor Temperature Sensing• Smooth Setback Recovery (SSR)• Economizer Relay Control• Maintenance/Filter/Service Reminders• Backlit Display• Wallplate Furnished• Simple Up and Down Temperature Control.

C0STAT05FF1L 11Y05

Optional AccessoriesRemote non-adjustable wall mount 10k averaging temperature sensor C0SNZN73AE1- 47W37Optional wall mounting plate C0MISC17AE1- X2659DIGITAL NON-PROGRAMMABLE THERMOSTAT

• One-Stage Heating / Cooling Conventional Systems• Intuitive Interface• Automatic Changeover• Backlit Display• Simple Up and Down Temperature Control.

C0STAT12AE1L 51M32

Optional AccessoriesOutdoor temperature sensor C0SNSR04AE1- X2658Optional wall mounting plate C0MISC17AE1- X2659

Page 6: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 6

SPECIFICATIONSGeneral Data

Model No. TSA036S4 TSA042S4 TSA048S4 TSA060S4Nominal Tonnage 3 3.5 4 5

Connections (sweat)

Liquid line o.d. - in. 3/8 3/8 3/8 3/8Suction line o.d. - in. 7/8 7/8 7/8 1-1/8

1 Refrigerant (R-410A) furnished 5 lbs. 9 oz. 6 lbs. 6 oz. 7 lbs. 8 oz. 10 lbs. 0 oz.Outdoor Coil

Net face area sq. ft.

Outer coil 13.22 16.33 21.00 18.67Inner coil - - - - - - - - - 17.96

Tube diameter - in. 5/16 5/16 5/16 5/16Number of rows 1 1 1 2

Fins per inch 26 26 26 22Outdoor Fan

Diameter - in. 18 22 22 22Number of blades 4 4 4 4

Motor hp 208/230V - 1/5 460/575V - 1/6

1/4 1/4 1/4

Cfm 2400 3500 3670 3600Rpm 1090 825 825 830

Watts 185 310 295 285Shipping Data - lbs. 1 package 135 178 194 218ELECTRICAL DATA

Line voltage data - 60 hz - 3ph 208/230V 460V 575V 208/230V 460V 208/230V 460V 575V 208/230V 460V 575V2 Maximum overcurrent protection (amps) 20 15 15 30 15 30 15 15 35 15 15

3 Minimum circuit ampacity 14.2 7.8 5.3 18.6 8.4 18.8 8.8 7.0 21.3 10.7 8.3Compressor Rated load amps 10.4 5.8 3.8 13.5 6 13.7 6.2 4.8 15.6 7.8 5.8

Locked rotor amps 73 38 36.5 88 44 83.1 41 30.4 110 52 35.5Power factor .85 .84 .83 .88 .83 .90 .92 .88 .90 .91 .90

Condenser Fan Motor

Full load amps 1.1 .55 .55 1.7 1.0 1.7 1.0 1.0 1.7 1.0 1.0Locked rotor amps 1.9 1.1 1.1 3.1 2.3 3.1 2.3 2.3 3.1 2.3 2.3

OPTIONAL ACCESSORIES - ORDER SEPARATELYCompressor Low Ambient Cut-Off Switch

45F08 • • • •

Compressor Sound Cover 69J03 • • • •Compressor Time-Off Control 47J27 • • • •Freezestat 3/8 in. tubing 93G35 • • • •

5/8 in. tubing 50A93 • • • •Hail Guards 24 x 24 x 28 in. 14X09 •

28 x 28 x 28 in. 14X16 •28 x 28 x 36 in. 14X14 •28 x 28 x 32 in. 14X19 •

Indoor Blower Off Delay Relay 58M81 • • • •Loss of Charge Switch 84M23 • • • •4 Low Ambient Kit (Fan Cycling) (30°F)

34M72 • • • •

4 Low Ambient Control (0°F) 208/230V only

Speed Control X5867 • • • •

Weatherproof Kit 56N41 • • • •

Refrigerant Line Sets

L15-65-30, L15-65-40, L15-65-50

• • •

Field Fabricate •Unit Stand-Off Kit 94J45 • • • •NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage.1 Refrigerant charge sufficient for 15 ft. length of refrigerant lines.2 HACR type circuit breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.4 Freezestat is recommended with Low Ambient Control.

Page 7: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 7

DIMENSIONS - INCHES (MM)

SIDE VIEW

SUCTION &LIQUID LINE

CONNECTIONS

INLET

AIR

INLET

AIR

DISCHARGE AIR

SIDE VIEW

TOP VIEW

CONDENSERCOIL FAN

COMPRESSOR

INLET AIR

INLET AIR

SUCTION LINECONNECTION

2-3/4 (70)

A

ELECTRICALINLETS

LIQUID LINECONNECTION

6-3/8(162)

TOP VIEW BASE SECTION

COMPRESSOR

COIL DRAIN OUTLETS(Around perimeter of base)

OPTIONAL UNITSTAND-OFF KIT (4)

(Field Installed)

B

A

OPTIONAL UNITSTAND-OFF KIT (4)

(Field Installed)

2 (51)

3/4(19)

4-3/8(111)

4-3/8(111)

4-3/8(111)

4-3/8(111)

4-3/8(111)

4-3/8(111)

6-3/8(162)

C

Model No.A B C

inches mm inches mm inches mmTSA036S4 24-1/4 616 29-1/4 743 28-1/2 724TSA042S4 28-1/4 718 29-1/4 743 28-1/2 724TSA048S4 28-1/4 718 37-1/4 946 36-1/2 927TSA060S4 28-1/4 718 33-1/4 845 32-1/2 826

Page 8: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 8

SOUND DATA1 Unit

Model No.Octave Band Linear Sound Power Levels dB, re 10-12 Watts Center Frequency - HZ 1 Sound Rating

Number (dB)125 250 500 1000 2000 4000 8000TSA036S4 70.5 67.5 69.5 72.5 69.5 63 59 76TSA042S4 74 76.5 76.5 75.5 72 68 63.5 80TSA048S4 73.5 76 76 76.5 72.5 69.5 64.5 80TSA060S4 73.5 74.5 77 75 72 69 64.5 80NOTE - the octave sound power data does not include tonal correction.1 Tested according to AHRI Standard 270-2008 test conditions.

INSTALLATION CLEARANCES - INCHES (MM)

SeeNOTES

See NOTES

See NOTES

SeeNOTES

CONTROLBOX

NOTES:Service clearance of 30 in. (762 mm) must be maintained on

one of the sides adjacent to the control box.Clearance to one of the other three sides must be 36 in.

(914 mm)Clearance to one of the remaining two sides may be 12 in.

(305 mm) and the final side may be 6 in. (152 mm).A clearance of 24 in. must be maintained between two units.48 in. (1219 mm) clearance required on top of unit.

Page 9: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 9

TXV USAGEUse this table for C33, CH23, CH33, CH35 and CR33 Field Installed TXV Match-Ups.Outdoor Unit Model No.

Thermal Expansion Valve (TXV)

TSA036S4 12J19TSA042S4 12J20TSA048S4 12J20TSA060S4 12J20

CX34 upflow coils and all Lennox air handlers are shipped with a factory installed TXV. In most cases, no change out of the valve is needed.If a change out is required it will be listed in the “TXV SUBSTITUTIONS” table. The correct TXV must be ordered and field installed.C33 coils and all horizontal and downflow coils are shipped without a TXV. The TXV must be ordered and field installed.

AHRI STANDARD 210/240

Cooling or heating capacities are net values, including the effects of blower motor heat, and do not include supplementary heat. Power input is the total power input to the compressor(s) and fan(s), plus any controls and other items required as part of the system for normal operation.

Units which do not have an indoor air-circulating blower furnished as part of the model, i.e., split system with indoor coil only, is established by subtracting from the total cooling capacity 1250 Btu/h per 1,000 cfm, and by adding the same amount to the heating capacity. Total power input for both heating and cooling is increased by 365 W per 1,000 cfm of indoor air circulated.

*TXV SUBSTITUTIONSUse this table to determine if the factory installed TXV in the indoor unit needs to be replaced.Outdoor Unit Model No.

Indoor Coil or Air Handler

Factory TXV

Replacement TXV

TSA036S4 CBX32M-030 12J18 12J19

TSA036S4 CX34-31 12J18 12J19

TSA042S4 CBX32M-036 12J19 12J20

TSA042S4 CX34-38 12J19 12J20* CX34 coils and all air handlers - The factory installed expansion valve must be replaced with the expansion valve listed (ordered separately). If the combination is not listed above, the factory installed TXV is used.

MOST POPULAR MATCHESOutdoor Unit Model No.

Indoor Unit Model No

TSA036S4 CX34-38TSA042S4 CX34-43TSA048S4 CX34-50/60CTSA060S4 CX34-49

Page 10: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 10

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA036S4N (208/230V) TXV 35200 13 11 C35-30A EL180UH045E36A 10248580TSA036S4N (208/230V) TXV 35200 13 11 C35-30A EL180UH045XE36A 10248579TSA036S4N (208/230V) TXV 35000 13 11 C35-30A SL280UH070V36A 10248581TSA036S4N (208/230V) TXV 35000 13 11 C35-30A SL280UH070XV36A 10248582TSA036S4N (208/230V) TXV 35000 14 11 C35-30B EL180UH070E36B 10248583TSA036S4N (208/230V) TXV 35000 14 11 C35-30B EL180UH070XE36B 10248584TSA036S4N (208/230V) TXV 35200 14 11 C35-30B EL180UH090E48B 10248585TSA036S4N (208/230V) TXV 35200 14 11 C35-30B EL180UH090XE48B 10248586TSA036S4N (208/230V) TXV 35000 13 11 C35-30B EL195UH045XE36B 10248587TSA036S4N (208/230V) TXV 34800 13 11 C35-30B EL195UH070XE36B 10248588TSA036S4N (208/230V) TXV 34800 13 11 C35-30B EL296UH045XV36B 10248589TSA036S4N (208/230V) TXV 35000 13 11 C35-30B EL296UH070XV36B 10248590TSA036S4N (208/230V) TXV 35200 14 11 C35-30B SL280UH090V36B 10248591TSA036S4N (208/230V) TXV 32800 13 11 C35-30B SL280UH090V48B 10248592TSA036S4N (208/230V) TXV 32800 13 11 C35-30B SL280UH090XV48B 10248593TSA036S4N (208/230V) TXV 35000 13 11 C35-30B SLP98UH070XV36B 10248594TSA036S4N (208/230V) TXV 35600 14 11 C35-36A EL180UH045E36A 10248595TSA036S4N (208/230V) TXV 35600 14 11 C35-36A EL180UH045XE36A 10248596TSA036S4N (208/230V) TXV 35200 14 11 C35-36A SL280UH070V36A 10248597TSA036S4N (208/230V) TXV 35200 14 11 C35-36A SL280UH070XV36A 10248598TSA036S4N (208/230V) TXV 35000 13 10.7 C35-36A 10248599TSA036S4N (208/230V) TXV 35600 14.5 12 C35-36B EL180UH070E36B 10248600TSA036S4N (208/230V) TXV 35600 14.5 12 C35-36B EL180UH070XE36B 10248601TSA036S4N (208/230V) TXV 35800 14 11 C35-36B EL180UH090E48B 10248602TSA036S4N (208/230V) TXV 35800 14 11 C35-36B EL180UH090XE48B 10248603TSA036S4N (208/230V) TXV 35400 14 11 C35-36B EL195UH070XE36B 10248604TSA036S4N (208/230V) TXV 35200 14 11 C35-36B EL296UH045XV36B 10248605TSA036S4N (208/230V) TXV 35400 14 11 C35-36B EL296UH070XV36B 10248606TSA036S4N (208/230V) TXV 35600 14 11 C35-36B SL280UH090V36B 10248607TSA036S4N (208/230V) TXV 33200 13 11 C35-36B SL280UH090V48B 10248608TSA036S4N (208/230V) TXV 33200 13 11 C35-36B SL280UH090XV48B 10248609TSA036S4N (208/230V) TXV 35000 13 11 C35-36B SLP98UH070XV36B 10248610TSA036S4N (208/230V) TXV 35000 13 10.5 C35-36B 10248611TSA036S4N (208/230V) TXV 35800 14.5 12 C35-48B EL180UH070E36B 10248612TSA036S4N (208/230V) TXV 35800 14.5 12 C35-48B EL180UH070XE36B 10248613TSA036S4N (208/230V) TXV 36000 14 11 C35-48B EL180UH090E48B 10248614TSA036S4N (208/230V) TXV 36000 14 11 C35-48B EL180UH090XE48B 10248615TSA036S4N (208/230V) TXV 35600 14 11 C35-48B EL195UH070XE36B 10248616TSA036S4N (208/230V) TXV 35600 14 11 C35-48B EL296UH070XE36B 10248617TSA036S4N (208/230V) TXV 35600 14 11 C35-48B EL296UH070XV36B 10248618TSA036S4N (208/230V) TXV 35800 14.5 12 C35-48B SL280UH090V36B 10248619TSA036S4N (208/230V) TXV 33400 13.5 11 C35-48B SL280UH090V48B 10248620TSA036S4N (208/230V) TXV 33400 13.5 11 C35-48B SL280UH090XV48B 10248621TSA036S4N (208/230V) TXV 35600 14 11 C35-48B SLP98UH070XV36B 10248622TSA036S4N (208/230V) TXV 35400 13 11 C35-48B 10248623TSA036S4N (208/230V) TXV 36000 14.5 12 C35-48C EL180UH090E60C 10248624TSA036S4N (208/230V) TXV 35800 14.5 12 C35-48C EL180UH110E60C 10248625TSA036S4N (208/230V) TXV 35800 14.5 12 C35-48C EL180UH110XE60C 10248626TSA036S4N (208/230V) TXV 35800 14 11 C35-48C EL195UH090XE48C 10248627NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 11: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 11

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA036S4N (208/230V) TXV 36000 14 11 C35-48C EL195UH110XE60C 10248628TSA036S4N (208/230V) TXV 35800 14 11 C35-48C EL296UH090XE48C 10248629TSA036S4N (208/230V) TXV 35800 14 11 C35-48C EL296UH090XV36C 10248630TSA036S4N (208/230V) TXV 35800 14 11 C35-48C EL296UH090XV48C 10248631TSA036S4N (208/230V) TXV 36000 14 11 C35-48C EL296UH110XE60C 10248632TSA036S4N (208/230V) TXV 33800 13.2 11 C35-48C SL280UH090V60C 10248633TSA036S4N (208/230V) TXV 33800 13.5 11 C35-48C SL280UH090XV60C 10248634TSA036S4N (208/230V) TXV 33600 13 11 C35-48C SL280UH110V60C 10248635TSA036S4N (208/230V) TXV 33600 13 11 C35-48C SL280UH110XV60C 10248636TSA036S4N (208/230V) TXV 35800 14 11 C35-48C SLP98UH090XV36C 10248637TSA036S4N (208/230V) TXV 35800 14 11 C35-48C SLP98UH090XV48C 10248638TSA036S4N (208/230V) TXV 36200 14.5 12 C35-48C SLP98UH110XV60C 10248639TSA036S4N (208/230V) TXV 35400 13 11 C35-48C 10248640TSA036S4N (208/230V) TXV 36000 14.5 12 C35-50/60C EL180UH090E60C 10248641TSA036S4N (208/230V) TXV 35600 14 11 C35-50/60C EL180UH110E60C 10248642TSA036S4N (208/230V) TXV 35600 14 11 C35-50/60C EL180UH110XE60C 10248643TSA036S4N (208/230V) TXV 35800 14 11 C35-50/60C EL195UH090XE48C 10248644TSA036S4N (208/230V) TXV 36000 14 11 C35-50/60C EL195UH110XE60C 10248645TSA036S4N (208/230V) TXV 35800 14 11 C35-50/60C EL296UH090XE48C 10248646TSA036S4N (208/230V) TXV 35800 14 11 C35-50/60C EL296UH090XV36C 10248647TSA036S4N (208/230V) TXV 35600 14 11 C35-50/60C EL296UH090XV48C 10248648TSA036S4N (208/230V) TXV 36000 14 11 C35-50/60C EL296UH110XE60C 10248649TSA036S4N (208/230V) TXV 33600 13.2 11 C35-50/60C SL280UH090V60C 10248650TSA036S4N (208/230V) TXV 33600 13.2 11 C35-50/60C SL280UH090XV60C 10248651TSA036S4N (208/230V) TXV 33400 13 11 C35-50/60C SL280UH110V60C 10248652TSA036S4N (208/230V) TXV 33400 13 11 C35-50/60C SL280UH110XV60C 10248653TSA036S4N (208/230V) TXV 35800 14 11 C35-50/60C SLP98UH090XV36C 10248654TSA036S4N (208/230V) TXV 35600 14 11 C35-50/60C SLP98UH090XV48C 10248655TSA036S4N (208/230V) TXV 36000 14 11 C35-50/60C SLP98UH110XV60C 10248656TSA036S4N (208/230V) TXV 35200 13 11 C35-50/60C 10250484TSA036S4N (208/230V) TXV 35000 13 11.5 CBA27UHE-036 10259526TSA036S4N (208/230V) TXV 36000 14.25 12 CBA27UHE-042 10259527TSA036S4N (208/230V) TXV 34200 13 11 CBX25UH-036 5945087TSA036S4N (208/230V) TXV 34600 14 11.5 CBX27UH-036 4188511TSA036S4N (208/230V) TXV 35600 14.5 12 CBX27UH-042 4188513TSA036S4N (208/230V) TXV 33600 13.5 11 CBX32M-030 1286942TSA036S4N (208/230V) TXV 34200 13.5 11 CBX32M-036 1286943TSA036S4N (208/230V) TXV 34200 13.5 11 CBX32M-042 1286944TSA036S4N (208/230V) TXV 35200 13.5 11.6 CBX32M-048 1286945TSA036S4N (208/230V) TXV 34600 14 11.6 CBX32MV-036 1286946TSA036S4N (208/230V) TXV 35600 14 12 CBX32MV-048 1286947TSA036S4N (208/230V) TXV 34600 14 11.6 CBX40UHV-036 3291670TSA036S4N (208/230V) TXV 35600 14 12 CBX40UHV-048 3291758TSA036S4N (208/230V) TXV 33400 13 11 CH33-36A EL180UH045E36A 5733645TSA036S4N (208/230V) TXV 33400 13 11 CH33-36A EL180UH045XE36A 5734024TSA036S4N (208/230V) TXV 35600 14.5 12 CH33-43 EL180UH070E36B 5734320TSA036S4N (208/230V) TXV 35600 14.5 12 CH33-43 EL180UH070XE36B 5734746TSA036S4N (208/230V) TXV 35800 14 12 CH33-43 EL180UH090E48B 5735233TSA036S4N (208/230V) TXV 35600 14.5 12 CH33-43 EL180UH090E60C 5736145NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 12: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 12

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA036S4N (208/230V) TXV 35800 14 12 CH33-43 EL180UH090XE48B 5737225TSA036S4N (208/230V) TXV 35400 14 12 CH33-43 EL180UH110E60C 5737969TSA036S4N (208/230V) TXV 35400 14 12 CH33-43 EL180UH110XE60C 5739036TSA036S4N (208/230V) TXV 35800 14 11.5 CH33-43 EL296UH070XV36B 5057508TSA036S4N (208/230V) TXV 35400 14 12 CH33-43 EL296UH090XV36C 5057509TSA036S4N (208/230V) TXV 35200 14.5 12 CH33-43 EL296UH090XV48C 5057510TSA036S4N (208/230V) TXV 35800 14.5 12 CH33-43 EL296UH110XV60C 5057511TSA036S4N (208/230V) TXV 35600 14.5 12 CH33-43 SL280UH090V36B 4075025TSA036S4N (208/230V) TXV 35800 14 12 CH33-43 SL280UH090V48B 4075026TSA036S4N (208/230V) TXV 36000 14.5 12 CH33-43 SL280UH090V60C 4075027TSA036S4N (208/230V) TXV 35800 14 12 CH33-43 SL280UH090XV48B 4075080TSA036S4N (208/230V) TXV 36000 14.5 12 CH33-43 SL280UH090XV60C 4235657TSA036S4N (208/230V) TXV 35600 14 11.7 CH33-43 SL280UH110V60C 4075028TSA036S4N (208/230V) TXV 35600 14 11.7 CH33-43 SL280UH110XV60C 4075089TSA036S4N (208/230V) TXV 35800 14 11.5 CH33-43 SLP98UH070XV36B 5139738TSA036S4N (208/230V) TXV 35400 14 12 CH33-43 SLP98UH090XV36C 5139739TSA036S4N (208/230V) TXV 35200 14.5 12 CH33-43 SLP98UH090XV48C 5139740TSA036S4N (208/230V) TXV 35800 14.5 12 CH33-43 SLP98UH110XV60C 5139741TSA036S4N (208/230V) TXV 35600 13.5 11.5 CH33-43B EL195UH045XE36B 4698968TSA036S4N (208/230V) TXV 35400 14 11.5 CH33-43B EL195UH070XE36B 4698969TSA036S4N (208/230V) TXV 35600 13.5 11.5 CH33-43B EL296UH045XE36B 5647445TSA036S4N (208/230V) TXV 35400 14 11.5 CH33-43B EL296UH070XE36B 5647446TSA036S4N (208/230V) TXV 35400 14 12 CH33-43C EL195UH090XE48C 4698970TSA036S4N (208/230V) TXV 35600 14.5 12 CH33-43C EL195UH110XE60C 4698971TSA036S4N (208/230V) TXV 35400 14 12 CH33-43C EL296UH090XE48C 5647447TSA036S4N (208/230V) TXV 35600 14.5 12 CH33-43C EL296UH110XE60C 5647463TSA036S4N (208/230V) TXV 34800 14 11.5 CH33-44/48 EL180UH070E36B 5734324TSA036S4N (208/230V) TXV 34800 14 11.5 CH33-44/48 EL180UH070XE36B 5734751TSA036S4N (208/230V) TXV 35000 14 11.5 CH33-44/48 EL180UH090E48B 5735235TSA036S4N (208/230V) TXV 35000 14 11.5 CH33-44/48 EL180UH090XE48B 5737212TSA036S4N (208/230V) TXV 34800 13 11 CH33-44/48 EL195UH045XE36B 4698972TSA036S4N (208/230V) TXV 34800 13.5 11.5 CH33-44/48 EL195UH070XE36B 4698973TSA036S4N (208/230V) TXV 34800 13 11 CH33-44/48 EL296UH045XE36B 5647464TSA036S4N (208/230V) TXV 34800 13.5 11.5 CH33-44/48 EL296UH070XE36B 5647465TSA036S4N (208/230V) TXV 34800 13.5 11.5 CH33-44/48 EL296UH070XV36B 5057512TSA036S4N (208/230V) TXV 35000 14 11.5 CH33-44/48 SL280UH090V36B 4075034TSA036S4N (208/230V) TXV 35000 14 11.5 CH33-44/48 SL280UH090V48B 4075035TSA036S4N (208/230V) TXV 35000 14 11.5 CH33-44/48 SL280UH090XV48B 4075083TSA036S4N (208/230V) TXV 34800 13.5 11.5 CH33-44/48 SLP98UH070XV36B 5139742TSA036S4N (208/230V) TXV 34600 13 11 CH33-44/48 1286928TSA036S4N (208/230V) TXV 35400 14.5 12 CH33-48 EL180UH090E60C 5736148TSA036S4N (208/230V) TXV 35200 14 12 CH33-48 EL180UH110E60C 5737971TSA036S4N (208/230V) TXV 35200 14 12 CH33-48 EL180UH110XE60C 5739038TSA036S4N (208/230V) TXV 35200 14 11.5 CH33-48 EL296UH090XV36C 5057513TSA036S4N (208/230V) TXV 35200 14 12 CH33-48 EL296UH090XV48C 5057514TSA036S4N (208/230V) TXV 35600 14.5 12 CH33-48 EL296UH110XV60C 5057515TSA036S4N (208/230V) TXV 35800 14.25 11.7 CH33-48 SL280UH090V60C 4075036TSA036S4N (208/230V) TXV 35800 14.25 11.7 CH33-48 SL280UH090XV60C 4235658TSA036S4N (208/230V) TXV 35600 14 11.7 CH33-48 SL280UH110V60C 4075037NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 13: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 13

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA036S4N (208/230V) TXV 35600 14 11.7 CH33-48 SL280UH110XV60C 4075090TSA036S4N (208/230V) TXV 35200 14 11.5 CH33-48 SLP98UH090XV36C 5139743TSA036S4N (208/230V) TXV 35200 14 12 CH33-48 SLP98UH090XV48C 5139744TSA036S4N (208/230V) TXV 35600 14.5 12 CH33-48 SLP98UH110XV60C 5139745TSA036S4N (208/230V) TXV 34800 13 11 CH33-48 1286929TSA036S4N (208/230V) TXV 35200 14 11.5 CH33-48C EL195UH090XE48C 4698974TSA036S4N (208/230V) TXV 35400 14 12 CH33-48C EL195UH110XE60C 4698975TSA036S4N (208/230V) TXV 35200 14 11.5 CH33-48C EL296UH090XE48C 5647466TSA036S4N (208/230V) TXV 35400 14 12 CH33-48C EL296UH110XE60C 5647467TSA036S4N (208/230V) TXV 35600 14 11.5 CH33-62D EL296UH090XV60C 8341556TSA036S4N (208/230V) TXV 35600 14.5 12 CH33-62D EL296UH110XV60C 8341557TSA036S4N (208/230V) TXV 33800 14 11.5 CR33-48 EL180DF070E36B 5733388TSA036S4N (208/230V) TXV 33600 13.5 11 CR33-48 EL180DF090E48B 5733469TSA036S4N (208/230V) TXV 34000 14 11.5 CR33-48 EL180DF110E60C 5733518TSA036S4N (208/230V) TXV 33600 13.5 11 CR33-48 EL195DF045XE36B 4698976TSA036S4N (208/230V) TXV 33800 13.5 11.5 CR33-48 EL195DF090XE48C 4698977TSA036S4N (208/230V) TXV 33800 13.5 11.5 CR33-48 EL195DF110XE60C 4698979TSA036S4N (208/230V) TXV 33600 13.5 11 CR33-48 EL296DF045XE36B 5647468TSA036S4N (208/230V) TXV 33800 13.5 11.5 CR33-48 EL296DF090XE48C 5647469TSA036S4N (208/230V) TXV 33800 13.5 11.5 CR33-48 EL296DF110XE60C 5647471TSA036S4N (208/230V) TXV 33600 13.5 11 CR33-48 SL280DF090V48B 4075038TSA036S4N (208/230V) TXV 34000 14 11.5 CR33-48 SL280DF110V60C 4075039TSA036S4N (208/230V) TXV 33600 13.5 11 CR33-48 SLP98DF070XV36B 5139755TSA036S4N (208/230V) TXV 33800 13.5 11.5 CR33-48 SLP98DF090XV36C 5139756TSA036S4N (208/230V) TXV 35200 14 11.5 CR33-50/60 EL195DF090XE48C 4698978TSA036S4N (208/230V) TXV 35200 14 11.5 CR33-50/60 EL296DF090XE48C 5647470TSA036S4N (208/230V) TXV 35000 14 11.5 CR33-50/60 SLP98DF090XV36C 5139757TSA036S4N (208/230V) TXV 35200 13 11 CX35-30A EL180UH045E36A 10250481TSA036S4N (208/230V) TXV 35200 13 11 CX35-30A EL180UH045XE36A 10248657TSA036S4N (208/230V) TXV 35000 13 11 CX35-30A SL280UH070V36A 10248658TSA036S4N (208/230V) TXV 35000 13 11 CX35-30A SL280UH070XV36A 10248659TSA036S4N (208/230V) TXV 35000 14 11 CX35-30B EL180UH070E36B 10248660TSA036S4N (208/230V) TXV 35000 14 11 CX35-30B EL180UH070XE36B 10248661TSA036S4N (208/230V) TXV 35200 14 11 CX35-30B EL180UH090E48B 10248662TSA036S4N (208/230V) TXV 35200 14 11 CX35-30B EL180UH090XE48B 10248663TSA036S4N (208/230V) TXV 35000 13 11 CX35-30B EL195UH045XE36B 10248664TSA036S4N (208/230V) TXV 34800 13 11 CX35-30B EL195UH070XE36B 10248665TSA036S4N (208/230V) TXV 34800 13 11 CX35-30B EL296UH045XV36B 10248666TSA036S4N (208/230V) TXV 35000 13 11 CX35-30B EL296UH070XV36B 10248667TSA036S4N (208/230V) TXV 35200 14 11 CX35-30B SL280UH090V36B 10248668TSA036S4N (208/230V) TXV 35000 13 11 CX35-30B SLP98UH070XV36B 10248669TSA036S4N (208/230V) TXV 35200 14 11 CX35-36A SL280UH070V36A 10248670TSA036S4N (208/230V) TXV 35200 14 11 CX35-36A SL280UH070XV36A 10248671TSA036S4N (208/230V) TXV 35000 13 10.7 CX35-36A 10248672TSA036S4N (208/230V) TXV 35600 14.5 12 CX35-36B EL180UH070E36B 10248673TSA036S4N (208/230V) TXV 35600 14.5 12 CX35-36B EL180UH070XE36B 10248674TSA036S4N (208/230V) TXV 35800 14 11 CX35-36B EL180UH090E48B 10248675TSA036S4N (208/230V) TXV 35800 14 11 CX35-36B EL180UH090XE48B 10248676TSA036S4N (208/230V) TXV 35400 14 11 CX35-36B EL195UH070XE36B 10248677NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 14: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 14

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA036S4N (208/230V) TXV 35200 14 11 CX35-36B EL296UH045XV36B 10248678TSA036S4N (208/230V) TXV 35400 14 11 CX35-36B EL296UH070XV36B 10248679TSA036S4N (208/230V) TXV 35600 14 11 CX35-36B SL280UH090V36B 10248680TSA036S4N (208/230V) TXV 33200 13 11 CX35-36B SL280UH090V48B 10248681TSA036S4N (208/230V) TXV 33200 13 11 CX35-36B SL280UH090XV48B 10248682TSA036S4N (208/230V) TXV 35400 14 11 CX35-36B SLP98UH070XV36B 10248683TSA036S4N (208/230V) TXV 35000 13 10.7 CX35-36B 10248684TSA036S4N (208/230V) TXV 35800 14.5 12 CX35-48B EL180UH070E36B 10248685TSA036S4N (208/230V) TXV 35800 14.5 12 CX35-48B EL180UH070XE36B 10248686TSA036S4N (208/230V) TXV 36000 14 11 CX35-48B EL180UH090E48B 10248687TSA036S4N (208/230V) TXV 36000 14 11 CX35-48B EL180UH090XE48B 10248688TSA036S4N (208/230V) TXV 35600 14 11 CX35-48B EL195UH070XE36B 10248689TSA036S4N (208/230V) TXV 35600 14 11 CX35-48B EL296UH070XE36B 10248690TSA036S4N (208/230V) TXV 35600 14 11 CX35-48B EL296UH070XV36B 10248691TSA036S4N (208/230V) TXV 35800 14.5 12 CX35-48B SL280UH090V36B 10248692TSA036S4N (208/230V) TXV 33400 13.5 11 CX35-48B SL280UH090V48B 10248693TSA036S4N (208/230V) TXV 33400 13.5 11 CX35-48B SL280UH090XV48B 10248694TSA036S4N (208/230V) TXV 35600 14 11 CX35-48B SLP98UH070XV36B 10248695TSA036S4N (208/230V) TXV 35400 13 11 CX35-48B 10248696TSA036S4N (208/230V) TXV 36000 14.5 12 CX35-48C EL180UH090E60C 10248697TSA036S4N (208/230V) TXV 35800 14.5 12 CX35-48C EL180UH110E60C 10248698TSA036S4N (208/230V) TXV 35800 14.5 12 CX35-48C EL180UH110XE60C 10248699TSA036S4N (208/230V) TXV 35800 14 11 CX35-48C EL195UH090XE48C 10248700TSA036S4N (208/230V) TXV 36000 14 11 CX35-48C EL195UH110XE60C 10248701TSA036S4N (208/230V) TXV 35800 14 11 CX35-48C EL296UH090XE48C 10248702TSA036S4N (208/230V) TXV 35800 14 11 CX35-48C EL296UH090XV36C 10248703TSA036S4N (208/230V) TXV 35800 14 11 CX35-48C EL296UH090XV48C 10248704TSA036S4N (208/230V) TXV 36000 14 11 CX35-48C EL296UH110XE60C 10248705TSA036S4N (208/230V) TXV 33800 13.2 11 CX35-48C SL280UH090V60C 10248706TSA036S4N (208/230V) TXV 33800 13.2 11 CX35-48C SL280UH090XV60C 10248707TSA036S4N (208/230V) TXV 33600 13 11 CX35-48C SL280UH110V60C 10248708TSA036S4N (208/230V) TXV 33600 13 11 CX35-48C SL280UH110XV60C 10248709TSA036S4N (208/230V) TXV 35800 14 11 CX35-48C SLP98UH090XV36C 10248710TSA036S4N (208/230V) TXV 35800 14 11 CX35-48C SLP98UH090XV48C 10248711TSA036S4N (208/230V) TXV 36200 14.5 12 CX35-48C SLP98UH110XV60C 10248712TSA036S4N (208/230V) TXV 35400 13 11 CX35-48C 10248713TSA036S4N (208/230V) TXV 36000 14.5 12 CX35-50/60C EL180UH090E60C 10248714TSA036S4N (208/230V) TXV 35600 14 11 CX35-50/60C EL180UH110E60C 10250482TSA036S4N (208/230V) TXV 35600 14 11 CX35-50/60C EL180UH110XE60C 10248715TSA036S4N (208/230V) TXV 35800 14 11 CX35-50/60C EL195UH090XE48C 10248716TSA036S4N (208/230V) TXV 36000 14 11 CX35-50/60C EL195UH110XE60C 10248717TSA036S4N (208/230V) TXV 35800 14 11 CX35-50/60C EL296UH090XE48C 10248718TSA036S4N (208/230V) TXV 35800 14 11 CX35-50/60C EL296UH090XV36C 10248719TSA036S4N (208/230V) TXV 35600 14 11 CX35-50/60C EL296UH090XV48C 10248720TSA036S4N (208/230V) TXV 35600 14 11 CX35-50/60C EL296UH110XE60C 10248721TSA036S4N (208/230V) TXV 33600 13.2 11 CX35-50/60C SL280UH090V60C 10248722TSA036S4N (208/230V) TXV 33600 13.2 11 CX35-50/60C SL280UH090XV60C 10248723TSA036S4N (208/230V) TXV 33400 13 11 CX35-50/60C SL280UH110V60C 10248724TSA036S4N (208/230V) TXV 33400 13 11 CX35-50/60C SL280UH110XV60C 10248725NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 15: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 15

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA036S4N (208/230V) TXV 35800 14 11 CX35-50/60C SLP98UH090XV36C 10248726TSA036S4N (208/230V) TXV 35600 14 11 CX35-50/60C SLP98UH090XV48C 10248727TSA036S4N (208/230V) TXV 36000 14 11 CX35-50/60C SLP98UH110XV60C 10248728TSA036S4N (208/230V) TXV 35200 13 11 CX35-50/60C 10248729TSA036S4N (208/230V) TXV 33800 13 10.9 CX38-38B 10556638TSA036S4N (460V) TXV 35200 13 11 C35-30A EL180UH045E36A 10248429TSA036S4N (460V) TXV 35200 13 11 C35-30A EL180UH045XE36A 10248428TSA036S4N (460V) TXV 35000 13 11 C35-30A SL280UH070V36A 10248430TSA036S4N (460V) TXV 35000 13 11 C35-30A SL280UH070XV36A 10248431TSA036S4N (460V) TXV 35000 14 11 C35-30B EL180UH070E36B 10248432TSA036S4N (460V) TXV 35000 14 11 C35-30B EL180UH070XE36B 10248433TSA036S4N (460V) TXV 35200 14 11 C35-30B EL180UH090E48B 10248434TSA036S4N (460V) TXV 35200 14 11 C35-30B EL180UH090XE48B 10248435TSA036S4N (460V) TXV 35000 13 11 C35-30B EL195UH045XE36B 10248436TSA036S4N (460V) TXV 34800 13 11 C35-30B EL195UH070XE36B 10248437TSA036S4N (460V) TXV 34800 13 11 C35-30B EL296UH045XV36B 10248438TSA036S4N (460V) TXV 35000 13 11 C35-30B EL296UH070XV36B 10248439TSA036S4N (460V) TXV 35200 14 11 C35-30B SL280UH090V36B 10248440TSA036S4N (460V) TXV 32800 13 11 C35-30B SL280UH090V48B 10248441TSA036S4N (460V) TXV 32800 13 11 C35-30B SL280UH090XV48B 10248442TSA036S4N (460V) TXV 35000 13 11 C35-30B SLP98UH070XV36B 10248443TSA036S4N (460V) TXV 35600 14 11 C35-36A EL180UH045E36A 10248444TSA036S4N (460V) TXV 35600 14 11 C35-36A EL180UH045XE36A 10248445TSA036S4N (460V) TXV 35200 14 11 C35-36A SL280UH070V36A 10248446TSA036S4N (460V) TXV 35200 14 11 C35-36A SL280UH070XV36A 10248447TSA036S4N (460V) TXV 35000 13 10.7 C35-36A 10248448TSA036S4N (460V) TXV 35600 14.5 12 C35-36B EL180UH070E36B 10248449TSA036S4N (460V) TXV 35600 14.5 12 C35-36B EL180UH070XE36B 10248450TSA036S4N (460V) TXV 35800 14 11 C35-36B EL180UH090E48B 10248451TSA036S4N (460V) TXV 35800 14 11 C35-36B EL180UH090XE48B 10248452TSA036S4N (460V) TXV 35400 14 11 C35-36B EL195UH070XE36B 10248453TSA036S4N (460V) TXV 35200 14 11 C35-36B EL296UH045XV36B 10248454TSA036S4N (460V) TXV 35400 14 11 C35-36B EL296UH070XV36B 10248455TSA036S4N (460V) TXV 35600 14 11 C35-36B SL280UH090V36B 10248456TSA036S4N (460V) TXV 33200 13 11 C35-36B SL280UH090V48B 10248457TSA036S4N (460V) TXV 33200 13 11 C35-36B SL280UH090XV48B 10248458TSA036S4N (460V) TXV 35000 13 11 C35-36B SLP98UH070XV36B 10248459TSA036S4N (460V) TXV 35000 13 10.5 C35-36B 10248460TSA036S4N (460V) TXV 35800 14.5 12 C35-48B EL180UH070E36B 10248461TSA036S4N (460V) TXV 35800 14.5 12 C35-48B EL180UH070XE36B 10248462TSA036S4N (460V) TXV 36000 14 11 C35-48B EL180UH090E48B 10248463TSA036S4N (460V) TXV 36000 14 11 C35-48B EL180UH090XE48B 10248464TSA036S4N (460V) TXV 35600 14 11 C35-48B EL195UH070XE36B 10248465TSA036S4N (460V) TXV 35600 14 11 C35-48B EL296UH070XE36B 10248466TSA036S4N (460V) TXV 35600 14 11 C35-48B EL296UH070XV36B 10248467TSA036S4N (460V) TXV 35800 14.5 12 C35-48B SL280UH090V36B 10248468TSA036S4N (460V) TXV 33400 13.5 11 C35-48B SL280UH090V48B 10248469TSA036S4N (460V) TXV 33400 13.5 11 C35-48B SL280UH090XV48B 10248470TSA036S4N (460V) TXV 35600 14 11 C35-48B SLP98UH070XV36B 10248471NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 16: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 16

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA036S4N (460V) TXV 35400 13 11 C35-48B 10248472TSA036S4N (460V) TXV 36000 14.5 12 C35-48C EL180UH090E60C 10248473TSA036S4N (460V) TXV 35800 14.5 12 C35-48C EL180UH110E60C 10248474TSA036S4N (460V) TXV 35800 14.5 12 C35-48C EL180UH110XE60C 10248475TSA036S4N (460V) TXV 35800 14 11 C35-48C EL195UH090XE48C 10248476TSA036S4N (460V) TXV 36000 14 11 C35-48C EL195UH110XE60C 10248477TSA036S4N (460V) TXV 35800 14 11 C35-48C EL296UH090XE48C 10248478TSA036S4N (460V) TXV 35800 14 11 C35-48C EL296UH090XV36C 10248479TSA036S4N (460V) TXV 35800 14 11 C35-48C EL296UH090XV48C 10248480TSA036S4N (460V) TXV 36000 14 11 C35-48C EL296UH110XE60C 10248481TSA036S4N (460V) TXV 33800 13.2 11 C35-48C SL280UH090V60C 10248482TSA036S4N (460V) TXV 33800 13.5 11 C35-48C SL280UH090XV60C 10248483TSA036S4N (460V) TXV 33600 13 11 C35-48C SL280UH110V60C 10248484TSA036S4N (460V) TXV 33600 13 11 C35-48C SL280UH110XV60C 10248485TSA036S4N (460V) TXV 35800 14 11 C35-48C SLP98UH090XV36C 10248486TSA036S4N (460V) TXV 35800 14 11 C35-48C SLP98UH090XV48C 10248487TSA036S4N (460V) TXV 36200 14.5 12 C35-48C SLP98UH110XV60C 10248488TSA036S4N (460V) TXV 35400 13 11 C35-48C 10248489TSA036S4N (460V) TXV 36000 14.5 12 C35-50/60C EL180UH090E60C 10248490TSA036S4N (460V) TXV 35600 14 11 C35-50/60C EL180UH110E60C 10248491TSA036S4N (460V) TXV 35600 14 11 C35-50/60C EL180UH110XE60C 10248492TSA036S4N (460V) TXV 35800 14 11 C35-50/60C EL195UH090XE48C 10248493TSA036S4N (460V) TXV 36000 14 11 C35-50/60C EL195UH110XE60C 10248494TSA036S4N (460V) TXV 35800 14 11 C35-50/60C EL296UH090XE48C 10248495TSA036S4N (460V) TXV 35800 14 11 C35-50/60C EL296UH090XV36C 10248496TSA036S4N (460V) TXV 35600 14 11 C35-50/60C EL296UH090XV48C 10248497TSA036S4N (460V) TXV 36000 14 11 C35-50/60C EL296UH110XE60C 10248498TSA036S4N (460V) TXV 33600 13.2 11 C35-50/60C SL280UH090V60C 10248499TSA036S4N (460V) TXV 33600 13.2 11 C35-50/60C SL280UH090XV60C 10248500TSA036S4N (460V) TXV 33400 13 11 C35-50/60C SL280UH110V60C 10248501TSA036S4N (460V) TXV 33400 13 11 C35-50/60C SL280UH110XV60C 10248502TSA036S4N (460V) TXV 35800 14 11 C35-50/60C SLP98UH090XV36C 10248503TSA036S4N (460V) TXV 35600 14 11 C35-50/60C SLP98UH090XV48C 10248504TSA036S4N (460V) TXV 36000 14 11 C35-50/60C SLP98UH110XV60C 10248505TSA036S4N (460V) TXV 35200 13 11 C35-50/60C 10250479TSA036S4N (460V) TXV 35000 13 11.5 CBA27UHE-036 10259528TSA036S4N (460V) TXV 36000 14.25 12 CBA27UHE-042 10259529TSA036S4N (460V) TXV 34200 13 11 CBX25UH-036 5945086TSA036S4N (460V) TXV 34600 14 11.5 CBX27UH-036 4188510TSA036S4N (460V) TXV 35600 14.5 12 CBX27UH-042 4188512TSA036S4N (460V) TXV 33600 13.5 11 CBX32M-030 1287245TSA036S4N (460V) TXV 34200 13.5 11 CBX32M-036 1287246TSA036S4N (460V) TXV 34200 13.5 11 CBX32M-042 1287247TSA036S4N (460V) TXV 35200 13.5 11.6 CBX32M-048 1287248TSA036S4N (460V) TXV 34600 14 11.6 CBX32MV-036 1287249TSA036S4N (460V) TXV 35600 14 12 CBX32MV-048 1287250TSA036S4N (460V) TXV 34600 14 11.6 CBX40UHV-036 3291669TSA036S4N (460V) TXV 35600 14 12 CBX40UHV-048 3291757TSA036S4N (460V) TXV 33400 13 11 CH33-36A EL180UH045E36A 5733648NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 17: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 17

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA036S4N (460V) TXV 33400 13 11 CH33-36A EL180UH045XE36A 5734029TSA036S4N (460V) TXV 35600 14.5 12 CH33-43 EL180UH070E36B 5734332TSA036S4N (460V) TXV 35600 14.5 12 CH33-43 EL180UH070XE36B 5734755TSA036S4N (460V) TXV 35800 14 12 CH33-43 EL180UH090E48B 5735245TSA036S4N (460V) TXV 35600 14.5 12 CH33-43 EL180UH090E60C 5736154TSA036S4N (460V) TXV 35800 14 12 CH33-43 EL180UH090XE48B 5737235TSA036S4N (460V) TXV 35400 14 12 CH33-43 EL180UH110E60C 5737977TSA036S4N (460V) TXV 35400 14 12 CH33-43 EL180UH110XE60C 5739048TSA036S4N (460V) TXV 35800 14 11.5 CH33-43 EL296UH070XV36B 5057490TSA036S4N (460V) TXV 35400 14 12 CH33-43 EL296UH090XV36C 5057491TSA036S4N (460V) TXV 35200 14.5 12 CH33-43 EL296UH090XV48C 5057492TSA036S4N (460V) TXV 35800 14.5 12 CH33-43 EL296UH110XV60C 5057493TSA036S4N (460V) TXV 35600 14.5 12 CH33-43 SL280UH090V36B 4075097TSA036S4N (460V) TXV 35800 14 12 CH33-43 SL280UH090V48B 4075098TSA036S4N (460V) TXV 36000 14.5 12 CH33-43 SL280UH090V60C 4075099TSA036S4N (460V) TXV 35800 14 12 CH33-43 SL280UH090XV48B 4075152TSA036S4N (460V) TXV 36000 14.5 12 CH33-43 SL280UH090XV60C 4235663TSA036S4N (460V) TXV 35600 14 11.7 CH33-43 SL280UH110V60C 4075100TSA036S4N (460V) TXV 35600 14 11.7 CH33-43 SL280UH110XV60C 4075161TSA036S4N (460V) TXV 35800 14 11.5 CH33-43 SLP98UH070XV36B 5139763TSA036S4N (460V) TXV 35400 14 12 CH33-43 SLP98UH090XV36C 5139764TSA036S4N (460V) TXV 35200 14.5 12 CH33-43 SLP98UH090XV48C 5139765TSA036S4N (460V) TXV 35800 14.5 12 CH33-43 SLP98UH110XV60C 5139766TSA036S4N (460V) TXV 35600 13.5 11.5 CH33-43B EL195UH045XE36B 4699071TSA036S4N (460V) TXV 35400 14 11.5 CH33-43B EL195UH070XE36B 4699072TSA036S4N (460V) TXV 35600 13.5 11.5 CH33-43B EL296UH045XE36B 5647520TSA036S4N (460V) TXV 35400 14 11.5 CH33-43B EL296UH070XE36B 5647521TSA036S4N (460V) TXV 35400 14 12 CH33-43C EL195UH090XE48C 4699073TSA036S4N (460V) TXV 35600 14.5 12 CH33-43C EL195UH110XE60C 4699074TSA036S4N (460V) TXV 35400 14 12 CH33-43C EL296UH090XE48C 5647522TSA036S4N (460V) TXV 35600 14.5 12 CH33-43C EL296UH110XE60C 5647523TSA036S4N (460V) TXV 34800 14 11.5 CH33-44/48 EL180UH070E36B 5734328TSA036S4N (460V) TXV 34800 14 11.5 CH33-44/48 EL180UH070XE36B 5734759TSA036S4N (460V) TXV 35000 14 11.5 CH33-44/48 EL180UH090E48B 5735247TSA036S4N (460V) TXV 35000 14 11.5 CH33-44/48 EL180UH090XE48B 5737237TSA036S4N (460V) TXV 34800 13 11 CH33-44/48 EL195UH045XE36B 4699075TSA036S4N (460V) TXV 34800 13.5 11.5 CH33-44/48 EL195UH070XE36B 4699076TSA036S4N (460V) TXV 34800 13 11 CH33-44/48 EL296UH045XE36B 5647524TSA036S4N (460V) TXV 34800 13.5 11.5 CH33-44/48 EL296UH070XE36B 5647525TSA036S4N (460V) TXV 34800 13.5 11.5 CH33-44/48 EL296UH070XV36B 5057494TSA036S4N (460V) TXV 35000 14 11.5 CH33-44/48 SL280UH090V36B 4075106TSA036S4N (460V) TXV 35000 14 11.5 CH33-44/48 SL280UH090V48B 4075107TSA036S4N (460V) TXV 35000 14 11.5 CH33-44/48 SL280UH090XV48B 4075155TSA036S4N (460V) TXV 34800 13.5 11.5 CH33-44/48 SLP98UH070XV36B 5139767TSA036S4N (460V) TXV 34600 13 11 CH33-44/48 1287231TSA036S4N (460V) TXV 35400 14.5 12 CH33-48 EL180UH090E60C 5736156TSA036S4N (460V) TXV 35200 14 12 CH33-48 EL180UH110E60C 5737980TSA036S4N (460V) TXV 35200 14 12 CH33-48 EL180UH110XE60C 5739050TSA036S4N (460V) TXV 35200 14 11.5 CH33-48 EL296UH090XV36C 5057495NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 18: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 18

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA036S4N (460V) TXV 35200 14 12 CH33-48 EL296UH090XV48C 5057496TSA036S4N (460V) TXV 35600 14.5 12 CH33-48 EL296UH110XV60C 5057497TSA036S4N (460V) TXV 35800 14.25 11.7 CH33-48 SL280UH090V60C 4075108TSA036S4N (460V) TXV 35800 14.25 11.7 CH33-48 SL280UH090XV60C 4235664TSA036S4N (460V) TXV 35600 14 11.7 CH33-48 SL280UH110V60C 4075109TSA036S4N (460V) TXV 35600 14 11.7 CH33-48 SL280UH110XV60C 4075162TSA036S4N (460V) TXV 35200 14 11.5 CH33-48 SLP98UH090XV36C 5139768TSA036S4N (460V) TXV 35200 14 12 CH33-48 SLP98UH090XV48C 5139769TSA036S4N (460V) TXV 35600 14.5 12 CH33-48 SLP98UH110XV60C 5139770TSA036S4N (460V) TXV 34800 13 11 CH33-48 1287232TSA036S4N (460V) TXV 35200 14 11.5 CH33-48C EL195UH090XE48C 4699077TSA036S4N (460V) TXV 35400 14 12 CH33-48C EL195UH110XE60C 4699078TSA036S4N (460V) TXV 35200 14 11.5 CH33-48C EL296UH090XE48C 5647526TSA036S4N (460V) TXV 35400 14 12 CH33-48C EL296UH110XE60C 5647527TSA036S4N (460V) TXV 35600 14 11.5 CH33-62D EL296UH090XV60C 8341554TSA036S4N (460V) TXV 35600 14.5 12 CH33-62D EL296UH110XV60C 8341555TSA036S4N (460V) TXV 33800 14 11.5 CR33-48 EL180DF070E36B 5733389TSA036S4N (460V) TXV 33600 13.5 11 CR33-48 EL180DF090E48B 5733471TSA036S4N (460V) TXV 34000 14 11.5 CR33-48 EL180DF110E60C 5733520TSA036S4N (460V) TXV 33600 13.5 11 CR33-48 EL195DF045XE36B 4699079TSA036S4N (460V) TXV 33800 13.5 11.5 CR33-48 EL195DF090XE48C 4699080TSA036S4N (460V) TXV 33800 13.5 11.5 CR33-48 EL195DF110XE60C 4699082TSA036S4N (460V) TXV 33600 13.5 11 CR33-48 EL296DF045XE36B 5647528TSA036S4N (460V) TXV 33800 13.5 11.5 CR33-48 EL296DF090XE48C 5647529TSA036S4N (460V) TXV 33800 13.5 11.5 CR33-48 EL296DF110XE60C 5647531TSA036S4N (460V) TXV 33600 13.5 11 CR33-48 SL280DF090V48B 4075110TSA036S4N (460V) TXV 34000 14 11.5 CR33-48 SL280DF110V60C 4075111TSA036S4N (460V) TXV 33600 13.5 11 CR33-48 SLP98DF070XV36B 5139730TSA036S4N (460V) TXV 33800 13.5 11.5 CR33-48 SLP98DF090XV36C 5139731TSA036S4N (460V) TXV 35200 14 11.5 CR33-50/60 EL195DF090XE48C 4699081TSA036S4N (460V) TXV 35200 14 11.5 CR33-50/60 EL296DF090XE48C 5647530TSA036S4N (460V) TXV 35000 14 11.5 CR33-50/60 SLP98DF090XV36C 5139732TSA036S4N (460V) TXV 35200 13 11 CX35-30A EL180UH045E36A 10250483TSA036S4N (460V) TXV 35200 13 11 CX35-30A EL180UH045XE36A 10248506TSA036S4N (460V) TXV 35000 13 11 CX35-30A SL280UH070V36A 10248507TSA036S4N (460V) TXV 35000 13 11 CX35-30A SL280UH070XV36A 10248508TSA036S4N (460V) TXV 35000 14 11 CX35-30B EL180UH070E36B 10248509TSA036S4N (460V) TXV 35000 14 11 CX35-30B EL180UH070XE36B 10248510TSA036S4N (460V) TXV 35200 14 11 CX35-30B EL180UH090E48B 10248511TSA036S4N (460V) TXV 35200 14 11 CX35-30B EL180UH090XE48B 10248512TSA036S4N (460V) TXV 35000 13 11 CX35-30B EL195UH045XE36B 10248513TSA036S4N (460V) TXV 34800 13 11 CX35-30B EL195UH070XE36B 10248514TSA036S4N (460V) TXV 34800 13 11 CX35-30B EL296UH045XV36B 10248515TSA036S4N (460V) TXV 35000 13 11 CX35-30B EL296UH070XV36B 10248516TSA036S4N (460V) TXV 35200 14 11 CX35-30B SL280UH090V36B 10248517TSA036S4N (460V) TXV 35000 13 11 CX35-30B SLP98UH070XV36B 10248518TSA036S4N (460V) TXV 35200 14 11 CX35-36A SL280UH070V36A 10248519TSA036S4N (460V) TXV 35200 14 11 CX35-36A SL280UH070XV36A 10248520TSA036S4N (460V) TXV 35000 13 10.7 CX35-36A 10248521NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 19: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 19

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA036S4N (460V) TXV 35600 14.5 12 CX35-36B EL180UH070E36B 10248522TSA036S4N (460V) TXV 35600 14.5 12 CX35-36B EL180UH070XE36B 10248523TSA036S4N (460V) TXV 35800 14 11 CX35-36B EL180UH090E48B 10248524TSA036S4N (460V) TXV 35800 14 11 CX35-36B EL180UH090XE48B 10248525TSA036S4N (460V) TXV 35400 14 11 CX35-36B EL195UH070XE36B 10248526TSA036S4N (460V) TXV 35200 14 11 CX35-36B EL296UH045XV36B 10248527TSA036S4N (460V) TXV 35400 14 11 CX35-36B EL296UH070XV36B 10248528TSA036S4N (460V) TXV 35600 14 11 CX35-36B SL280UH090V36B 10248529TSA036S4N (460V) TXV 33200 13 11 CX35-36B SL280UH090V48B 10248530TSA036S4N (460V) TXV 33200 13 11 CX35-36B SL280UH090XV48B 10248531TSA036S4N (460V) TXV 35400 14 11 CX35-36B SLP98UH070XV36B 10248532TSA036S4N (460V) TXV 35000 13 10.7 CX35-36B 10248533TSA036S4N (460V) TXV 35800 14.5 12 CX35-48B EL180UH070E36B 10248534TSA036S4N (460V) TXV 35800 14.5 12 CX35-48B EL180UH070XE36B 10248535TSA036S4N (460V) TXV 36000 14 11 CX35-48B EL180UH090E48B 10248536TSA036S4N (460V) TXV 36000 14 11 CX35-48B EL180UH090XE48B 10248537TSA036S4N (460V) TXV 35600 14 11 CX35-48B EL195UH070XE36B 10248538TSA036S4N (460V) TXV 35600 14 11 CX35-48B EL296UH070XE36B 10248539TSA036S4N (460V) TXV 35600 14 11 CX35-48B EL296UH070XV36B 10248540TSA036S4N (460V) TXV 35800 14.5 12 CX35-48B SL280UH090V36B 10248541TSA036S4N (460V) TXV 33400 13.5 11 CX35-48B SL280UH090V48B 10248542TSA036S4N (460V) TXV 33400 13.5 11 CX35-48B SL280UH090XV48B 10248543TSA036S4N (460V) TXV 35600 14 11 CX35-48B SLP98UH070XV36B 10248544TSA036S4N (460V) TXV 35400 13 11 CX35-48B 10248545TSA036S4N (460V) TXV 36000 14.5 12 CX35-48C EL180UH090E60C 10248546TSA036S4N (460V) TXV 35800 14.5 12 CX35-48C EL180UH110E60C 10248547TSA036S4N (460V) TXV 35800 14.5 12 CX35-48C EL180UH110XE60C 10248548TSA036S4N (460V) TXV 35800 14 11 CX35-48C EL195UH090XE48C 10248549TSA036S4N (460V) TXV 36000 14 11 CX35-48C EL195UH110XE60C 10248550TSA036S4N (460V) TXV 35800 14 11 CX35-48C EL296UH090XE48C 10248551TSA036S4N (460V) TXV 35800 14 11 CX35-48C EL296UH090XV36C 10248552TSA036S4N (460V) TXV 35800 14 11 CX35-48C EL296UH090XV48C 10248553TSA036S4N (460V) TXV 36000 14 11 CX35-48C EL296UH110XE60C 10248554TSA036S4N (460V) TXV 33800 13.2 11 CX35-48C SL280UH090V60C 10248555TSA036S4N (460V) TXV 33800 13.2 11 CX35-48C SL280UH090XV60C 10248556TSA036S4N (460V) TXV 33600 13 11 CX35-48C SL280UH110V60C 10248557TSA036S4N (460V) TXV 33600 13 11 CX35-48C SL280UH110XV60C 10248558TSA036S4N (460V) TXV 35800 14 11 CX35-48C SLP98UH090XV36C 10248559TSA036S4N (460V) TXV 35800 14 11 CX35-48C SLP98UH090XV48C 10248560TSA036S4N (460V) TXV 36200 14.5 12 CX35-48C SLP98UH110XV60C 10248561TSA036S4N (460V) TXV 35400 13 11 CX35-48C 10248562TSA036S4N (460V) TXV 36000 14.5 12 CX35-50/60C EL180UH090E60C 10248563TSA036S4N (460V) TXV 35600 14 11 CX35-50/60C EL180UH110E60C 10250480TSA036S4N (460V) TXV 35600 14 11 CX35-50/60C EL180UH110XE60C 10248564TSA036S4N (460V) TXV 35800 14 11 CX35-50/60C EL195UH090XE48C 10248565TSA036S4N (460V) TXV 36000 14 11 CX35-50/60C EL195UH110XE60C 10248566TSA036S4N (460V) TXV 35800 14 11 CX35-50/60C EL296UH090XE48C 10248567TSA036S4N (460V) TXV 35800 14 11 CX35-50/60C EL296UH090XV36C 10248568TSA036S4N (460V) TXV 35600 14 11 CX35-50/60C EL296UH090XV48C 10248569NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 20: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 20

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA036S4N (460V) TXV 35600 14 11 CX35-50/60C EL296UH110XE60C 10248570TSA036S4N (460V) TXV 33600 13.2 11 CX35-50/60C SL280UH090V60C 10248571TSA036S4N (460V) TXV 33600 13.2 11 CX35-50/60C SL280UH090XV60C 10248572TSA036S4N (460V) TXV 33400 13 11 CX35-50/60C SL280UH110V60C 10248573TSA036S4N (460V) TXV 33400 13 11 CX35-50/60C SL280UH110XV60C 10248574TSA036S4N (460V) TXV 35800 14 11 CX35-50/60C SLP98UH090XV36C 10248575TSA036S4N (460V) TXV 35600 14 11 CX35-50/60C SLP98UH090XV48C 10248576TSA036S4N (460V) TXV 36000 14 11 CX35-50/60C SLP98UH110XV60C 10248577TSA036S4N (460V) TXV 35200 13 11 CX35-50/60C 10248578TSA036S4N (460V) TXV 33800 13 10.9 CX38-38B 10556554TSA042S4N (208/230V) TXV 41500 13 11 C35-36B EL180UH090E48B 10257228TSA042S4N (208/230V) TXV 41500 13 11 C35-36B EL180UH090XE48B 10257229TSA042S4N (208/230V) TXV 41000 13 11 C35-36B EL296UH070XV36B 10257230TSA042S4N (208/230V) TXV 41000 13 11 C35-36B SL280UH090V48B 10257232TSA042S4N (208/230V) TXV 41000 13 11 C35-36B SL280UH090XV48B 10257231TSA042S4N (208/230V) TXV 41000 13 11 C35-36B SLP98UH070XV36B 10257233TSA042S4N (208/230V) TXV 41000 13 11 C35-36B 10257234TSA042S4N (208/230V) TXV 42000 14 11.5 C35-48B EL180UH090E48B 10257235TSA042S4N (208/230V) TXV 42000 14 11.5 C35-48B EL180UH090XE48B 10257236TSA042S4N (208/230V) TXV 41000 13 11 C35-48B EL296UH070XV36B 10257237TSA042S4N (208/230V) TXV 41500 14 11 C35-48B SL280UH090V48B 10257239TSA042S4N (208/230V) TXV 41500 14 11 C35-48B SL280UH090XV48B 10257238TSA042S4N (208/230V) TXV 41000 13 11 C35-48B SLP98UH070XV36B 10257240TSA042S4N (208/230V) TXV 41000 13 11 C35-48B 10257241TSA042S4N (208/230V) TXV 41500 14 11.5 C35-48C CBWMV-60C-100 10257242TSA042S4N (208/230V) TXV 41500 14 11.5 C35-48C CBWMV-60C-120 10257243TSA042S4N (208/230V) TXV 42000 14 11.5 C35-48C EL180UH090E60C 10257244TSA042S4N (208/230V) TXV 41500 14 11.5 C35-48C EL180UH110E60C 10257245TSA042S4N (208/230V) TXV 41500 14 11.5 C35-48C EL180UH110XE60C 10257246TSA042S4N (208/230V) TXV 41500 14 11.5 C35-48C EL195UH090XE48C 10257247TSA042S4N (208/230V) TXV 42000 14 11.5 C35-48C EL195UH110XE60C 10257248TSA042S4N (208/230V) TXV 41500 14 11.5 C35-48C EL296UH090XE48C 10257249TSA042S4N (208/230V) TXV 41500 13 11.5 C35-48C EL296UH090XV36C 10257250TSA042S4N (208/230V) TXV 41500 14 11.5 C35-48C EL296UH090XV48C 10257251TSA042S4N (208/230V) TXV 42000 14 11.5 C35-48C EL296UH090XV60C 10257252TSA042S4N (208/230V) TXV 42000 14 11.5 C35-48C EL296UH110XE60C 10257253TSA042S4N (208/230V) TXV 42000 14 11.5 C35-48C EL296UH110XV48C 10257254TSA042S4N (208/230V) TXV 42000 14 11.5 C35-48C EL296UH110XV60C 10257255TSA042S4N (208/230V) TXV 41500 14.25 11.5 C35-48C SL280UH090V60C 10257256TSA042S4N (208/230V) TXV 41500 14.25 11.5 C35-48C SL280UH090XV60C 10257257TSA042S4N (208/230V) TXV 41500 14.25 11.5 C35-48C SL280UH110V60C 10257258TSA042S4N (208/230V) TXV 41500 14.25 11.5 C35-48C SL280UH110XV60C 10257259TSA042S4N (208/230V) TXV 42000 14 11.5 C35-48C SLO185B124/141V60 10257260TSA042S4N (208/230V) TXV 42000 14 11.5 C35-48C SLO185UF124/141V60 10257261TSA042S4N (208/230V) TXV 41500 13 11.5 C35-48C SLP98UH090XV36C 10257262TSA042S4N (208/230V) TXV 41500 14 11.5 C35-48C SLP98UH090XV48C 10257263TSA042S4N (208/230V) TXV 41500 14 11.5 C35-48C SLP98UH090XV60C 10257264TSA042S4N (208/230V) TXV 41500 14 11.5 C35-48C SLP98UH110XV60C 10257265TSA042S4N (208/230V) TXV 41000 13 11 C35-48C 10257266NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 21: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 21

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C CBWMV-60C-100 10257267TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C CBWMV-60C-120 10257268TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C EL180UH090E60C 10257269TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C EL180UH110E60C 10257270TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C EL180UH110XE60C 10257271TSA042S4N (208/230V) TXV 41500 14 11.5 C35-49C EL195UH090XE48C 10257272TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C EL195UH110XE60C 10257273TSA042S4N (208/230V) TXV 41500 14 11.5 C35-49C EL296UH090XE48C 10257274TSA042S4N (208/230V) TXV 41500 14 11.5 C35-49C EL296UH090XV36C 10257275TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C EL296UH090XV48C 10257276TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C EL296UH090XV60C 10257277TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C EL296UH110XE60C 10257278TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C EL296UH110XV48C 10257279TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C EL296UH110XV60C 10257280TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C SL280UH090V60C 10257281TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C SL280UH090XV60C 10257282TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C SL280UH110V60C 10257283TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C SL280UH110XV60C 10257284TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C SLO185B124/141V60 10257285TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C SLO185UF124/141V60 10257286TSA042S4N (208/230V) TXV 41500 14 11.5 C35-49C SLP98UH090XV36C 10257287TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C SLP98UH090XV48C 10257288TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C SLP98UH090XV60C 10257289TSA042S4N (208/230V) TXV 42000 14 11.5 C35-49C SLP98UH110XV60C 10257290TSA042S4N (208/230V) TXV 42000 13 11 C35-49C 10257291TSA042S4N (208/230V) TXV 41500 13.5 11.5 C35-50/60C CBWMV-60C-100 10257292TSA042S4N (208/230V) TXV 41500 13.5 11.5 C35-50/60C CBWMV-60C-120 10257293TSA042S4N (208/230V) TXV 41500 14 11.5 C35-50/60C EL180UH090E60C 10257294TSA042S4N (208/230V) TXV 41000 14 11.5 C35-50/60C EL180UH110E60C 10257295TSA042S4N (208/230V) TXV 41000 14 11.5 C35-50/60C EL180UH110XE60C 10257296TSA042S4N (208/230V) TXV 41000 13 11.5 C35-50/60C EL195UH090XE48C 10257297TSA042S4N (208/230V) TXV 41500 13 11.5 C35-50/60C EL195UH110XE60C 10257298TSA042S4N (208/230V) TXV 41000 13 11.5 C35-50/60C EL296UH090XE48C 10257299TSA042S4N (208/230V) TXV 41000 13 11.5 C35-50/60C EL296UH090XV36C 10257300TSA042S4N (208/230V) TXV 41500 13 11.5 C35-50/60C EL296UH090XV48C 10257301TSA042S4N (208/230V) TXV 41000 13 11.5 C35-50/60C EL296UH090XV60C 10257302TSA042S4N (208/230V) TXV 41500 13 11.5 C35-50/60C EL296UH110XE60C 10257303TSA042S4N (208/230V) TXV 41500 13 11.5 C35-50/60C EL296UH110XV60C 10257304TSA042S4N (208/230V) TXV 41500 13 11.5 C35-50/60C SL280UH090V60C 10257305TSA042S4N (208/230V) TXV 41500 13 11.5 C35-50/60C SL280UH090XV60C 10257306TSA042S4N (208/230V) TXV 41000 13 11.5 C35-50/60C SL280UH110V60C 10257307TSA042S4N (208/230V) TXV 41000 13 11.5 C35-50/60C SL280UH110XV60C 10257308TSA042S4N (208/230V) TXV 41000 13 11 C35-50/60C SLO185B124/141V60 10257309TSA042S4N (208/230V) TXV 41500 13 11 C35-50/60C SLO185UF124/141V60 10257310TSA042S4N (208/230V) TXV 41000 13 11 C35-50/60C SLP98UH090XV36C 10257311TSA042S4N (208/230V) TXV 41000 13 11 C35-50/60C SLP98UH090XV48C 10257312TSA042S4N (208/230V) TXV 41500 13 11 C35-50/60C SLP98UH090XV60C 10257313TSA042S4N (208/230V) TXV 41000 13 11 C35-50/60C SLP98UH110XV60C 10257314TSA042S4N (208/230V) TXV 41000 13 10.5 C35-50/60C 10257315NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 22: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 22

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C EL180UH090E60C 10257316TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C EL180UH110E60C 10257317TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C EL180UH110XE60C 10257318TSA042S4N (208/230V) TXV 42000 14 12 C35-60C EL195UH090XE48C 10257319TSA042S4N (208/230V) TXV 42000 14 12 C35-60C EL195UH110XE60C 10257320TSA042S4N (208/230V) TXV 42000 14 12 C35-60C EL296UH090XE48C 10257321TSA042S4N (208/230V) TXV 42000 14 12 C35-60C EL296UH090XV48C 10257322TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C EL296UH090XV60C 10257323TSA042S4N (208/230V) TXV 42000 14 12 C35-60C EL296UH110XE60C 10257324TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C EL296UH110XV48C 10257325TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C EL296UH110XV60C 10257326TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C SL280UH090V60C 10257327TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C SL280UH090XV60C 10257328TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C SL280UH110V60C 10257329TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C SL280UH110XV60C 10257330TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C SLO185B124/141V60 10257331TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C SLO185UF124/141V60 10257332TSA042S4N (208/230V) TXV 42000 14 11.5 C35-60C SLP98UH090XV36C 10257333TSA042S4N (208/230V) TXV 42000 14 12 C35-60C SLP98UH090XV48C 10257334TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C SLP98UH090XV60C 10257335TSA042S4N (208/230V) TXV 42000 14.5 12 C35-60C SLP98UH110XV60C 10257336TSA042S4N (208/230V) TXV 41500 13 11 C35-60C 10257337TSA042S4N (208/230V) TXV 42000 14.5 11.5 C35-60D SLO185B124/141V60 10257338TSA042S4N (208/230V) TXV 42000 14.5 11.5 C35-60D SLO185UF124/141V60 10257339TSA042S4N (208/230V) TXV 41500 13 11 C35-60D 10257340TSA042S4N (208/230V) TXV 42000 14 11.5 CBA27UHE-042 10259530TSA042S4N (208/230V) TXV 42000 14 11.5 CBA27UHE-048 10259531TSA042S4N (208/230V) TXV 41000 13 11 CBX25UH-042 5945089TSA042S4N (208/230V) TXV 41500 14 11.5 CBX27UH-042 4188515TSA042S4N (208/230V) TXV 41500 14 11.5 CBX27UH-048 4188517TSA042S4N (208/230V) TXV 39500 13 10.9 CBX32M-036 1286996TSA042S4N (208/230V) TXV 39500 13 10.9 CBX32M-042 1286997TSA042S4N (208/230V) TXV 41000 13 11 CBX32M-048 1286998TSA042S4N (208/230V) TXV 41500 14 11.6 CBX32MV-048 1286999TSA042S4N (208/230V) TXV 41500 14 11.6 CBX40UHV-048 3291764TSA042S4N (208/230V) TXV 41000 14 11.5 CH23-65 EL180UH090E60C 5736196TSA042S4N (208/230V) TXV 40500 14 11.5 CH23-65 EL180UH110E60C 5738022TSA042S4N (208/230V) TXV 40500 14 11.5 CH23-65 EL180UH110XE60C 5739065TSA042S4N (208/230V) TXV 40500 13.5 11.5 CH23-65 EL195UH090XE48C 4698994TSA042S4N (208/230V) TXV 40500 13.5 11.5 CH23-65 EL195UH110XE60C 4698995TSA042S4N (208/230V) TXV 40500 13.5 11.5 CH23-65 EL296UH090XE48C 5647486TSA042S4N (208/230V) TXV 40500 13.5 11.5 CH23-65 EL296UH090XV36C 5057734TSA042S4N (208/230V) TXV 40500 13.5 11.5 CH23-65 EL296UH090XV48C 5057735TSA042S4N (208/230V) TXV 41000 13.5 11.5 CH23-65 EL296UH090XV60C 5057736TSA042S4N (208/230V) TXV 40500 13.5 11.5 CH23-65 EL296UH110XE60C 5647487TSA042S4N (208/230V) TXV 40500 14 11.5 CH23-65 EL296UH110XV60C 5057754TSA042S4N (208/230V) TXV 41000 14 11.5 CH23-65 SL280UH090V60C 4075228TSA042S4N (208/230V) TXV 41000 14 11.5 CH23-65 SL280UH090XV60C 4235670TSA042S4N (208/230V) TXV 41000 14 11.5 CH23-65 SL280UH110V60C 4075229NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 23: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 23

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (208/230V) TXV 41000 14 11.5 CH23-65 SL280UH110XV60C 4075315TSA042S4N (208/230V) TXV 40500 13.5 11.5 CH23-65 SLP98UH090XV36C 5139784TSA042S4N (208/230V) TXV 40500 13.5 11.5 CH23-65 SLP98UH090XV48C 5139785TSA042S4N (208/230V) TXV 41000 13.5 11.5 CH23-65 SLP98UH090XV60C 5139786TSA042S4N (208/230V) TXV 40500 14 11.5 CH23-65 SLP98UH110XV60C 5139804TSA042S4N (208/230V) TXV 39500 13 10.7 CH23-65 1286981TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-43 EL180UH090E48B 5735291TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43 EL180UH090E60C 5736199TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-43 EL180UH090XE48B 5737244TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43 EL180UH110E60C 5738023TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43 EL180UH110XE60C 5739067TSA042S4N (208/230V) TXV 41500 13.5 11 CH33-43 EL296UH070XV36B 5057755TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43 EL296UH090XV36C 5057756TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43 EL296UH090XV48C 5057757TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-43 EL296UH090XV60C 5057758TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43 EL296UH110XV60C 5057759TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-43 SL280UH090V36B 4075230TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-43 SL280UH090V48B 4075231TSA042S4N (208/230V) TXV 42000 14 12 CH33-43 SL280UH090V60C 4075232TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-43 SL280UH090XV48B 4075309TSA042S4N (208/230V) TXV 42000 14 12 CH33-43 SL280UH090XV60C 4235682TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43 SL280UH110V60C 4075233TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43 SL280UH110XV60C 4075316TSA042S4N (208/230V) TXV 41500 13.5 11 CH33-43 SLP98UH070XV36B 5139805TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43 SLP98UH090XV36C 5139806TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43 SLP98UH090XV48C 5139807TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-43 SLP98UH090XV60C 5139808TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43 SLP98UH110XV60C 5139809TSA042S4N (208/230V) TXV 41000 14 11.5 CH33-43C EL195UH090XE48C 4698996TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43C EL195UH110XE60C 4698997TSA042S4N (208/230V) TXV 41000 14 11.5 CH33-43C EL296UH090XE48C 5647488TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-43C EL296UH110XE60C 5647489TSA042S4N (208/230V) TXV 41000 14 11.5 CH33-44/48 EL180UH090E48B 5735293TSA042S4N (208/230V) TXV 41000 14 11.5 CH33-44/48 EL180UH090XE48B 5737246TSA042S4N (208/230V) TXV 41000 14 11.5 CH33-48 EL180UH090E60C 5736201TSA042S4N (208/230V) TXV 41000 14 11.5 CH33-48 EL180UH110E60C 5738025TSA042S4N (208/230V) TXV 41000 14 11.5 CH33-48 EL180UH110XE60C 5739070TSA042S4N (208/230V) TXV 41000 13.5 11.5 CH33-48 EL296UH090XV36C 5057760TSA042S4N (208/230V) TXV 41000 13.5 11.5 CH33-48 EL296UH090XV48C 5057761TSA042S4N (208/230V) TXV 41500 13.5 11.5 CH33-48 EL296UH090XV60C 5057762TSA042S4N (208/230V) TXV 41500 13.5 11.5 CH33-48 EL296UH110XV60C 5057763TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-48 SL280UH090V60C 4075234TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-48 SL280UH090XV60C 4235683TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-48 SL280UH110V60C 4075235TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-48 SL280UH110XV60C 4075317TSA042S4N (208/230V) TXV 41000 13.5 11.5 CH33-48 SLP98UH090XV36C 5139810TSA042S4N (208/230V) TXV 41000 13.5 11.5 CH33-48 SLP98UH090XV48C 5139811TSA042S4N (208/230V) TXV 41500 13.5 11.5 CH33-48 SLP98UH090XV60C 5139812TSA042S4N (208/230V) TXV 41500 13.5 11.5 CH33-48 SLP98UH110XV60C 5139813NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 24: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 24

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (208/230V) TXV 40000 13 10.8 CH33-48 1286982TSA042S4N (208/230V) TXV 40500 13.5 11.5 CH33-48C EL195UH090XE48C 4698998TSA042S4N (208/230V) TXV 41000 13.5 11.5 CH33-48C EL195UH110XE60C 4698999TSA042S4N (208/230V) TXV 40500 13.5 11.5 CH33-48C EL296UH090XE48C 5647490TSA042S4N (208/230V) TXV 41000 13.5 11.5 CH33-48C EL296UH110XE60C 5647491TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 EL180UH090E60C 5736203TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 EL180UH110E60C 5795835TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 EL180UH110XE60C 5739071TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-49 EL195UH090XE48C 4699000TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 EL195UH110XE60C 4699001TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-49 EL296UH090XE48C 5647492TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-49 EL296UH090XV36C 5057748TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 EL296UH090XV48C 5057737TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 EL296UH090XV60C 5057738TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 EL296UH110XE60C 5647493TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 EL296UH110XV60C 5057739TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 SL280UH090V60C 4075236TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 SL280UH090XV60C 4235684TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 SL280UH110V60C 4075237TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 SL280UH110XV60C 4075318TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-49 SLP98UH090XV36C 5139798TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 SLP98UH090XV48C 5139787TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 SLP98UH090XV60C 5139788TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-49 SLP98UH110XV60C 5139789TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-50/60C EL180UH090E60C 5736162TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-50/60C EL180UH110E60C 5737986TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-50/60C EL180UH110XE60C 5739073TSA042S4N (208/230V) TXV 41000 14 11.5 CH33-50/60C EL195UH090XE48C 4699002TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-50/60C EL195UH110XE60C 4699003TSA042S4N (208/230V) TXV 41000 14 11.5 CH33-50/60C EL296UH090XE48C 5647494TSA042S4N (208/230V) TXV 41500 13.5 11.5 CH33-50/60C EL296UH090XV36C 5057740TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-50/60C EL296UH090XV48C 5057741TSA042S4N (208/230V) TXV 42000 13.5 11.5 CH33-50/60C EL296UH090XV60C 5057742TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-50/60C EL296UH110XE60C 5647495TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-50/60C EL296UH110XV60C 5057743TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-50/60C SL280UH090V60C 4075238TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-50/60C SL280UH090XV60C 4235685TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-50/60C SL280UH110V60C 4075239TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-50/60C SL280UH110XV60C 4075319TSA042S4N (208/230V) TXV 41500 13.5 11.5 CH33-50/60C SLP98UH090XV36C 5139790TSA042S4N (208/230V) TXV 41500 14 11.5 CH33-50/60C SLP98UH090XV48C 5139791TSA042S4N (208/230V) TXV 42000 13.5 11.5 CH33-50/60C SLP98UH090XV60C 5139792TSA042S4N (208/230V) TXV 42000 14 11.5 CH33-50/60C SLP98UH110XV60C 5139793TSA042S4N (208/230V) TXV 41000 13 11 CH33-50/60C 1286983TSA042S4N (208/230V) TXV 41000 14 11.5 CH33-62D EL296UH090XV60C 8341560TSA042S4N (208/230V) TXV 41000 14 11.5 CH33-62D EL296UH110XV60C 8341561TSA042S4N (208/230V) TXV 39500 13 11 CR33-48 EL195DF070XE48B 4699004TSA042S4N (208/230V) TXV 40000 13.5 11 CR33-48 EL195DF090XE48C 4699005TSA042S4N (208/230V) TXV 39500 13 11 CR33-48 EL296DF070XE48B 5647496NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 25: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 25

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (208/230V) TXV 40000 13.5 11 CR33-48 EL296DF090XE48C 5647497TSA042S4N (208/230V) TXV 41500 14 11.5 CR33-50/60 EL180DF110E60C 5733521TSA042S4N (208/230V) TXV 41000 13.5 11.5 CR33-50/60 EL195DF090XE48C 4699006TSA042S4N (208/230V) TXV 41500 14 11.5 CR33-50/60 EL195DF110XE60C 4698990TSA042S4N (208/230V) TXV 41000 13.5 11.5 CR33-50/60 EL296DF090XE48C 5647498TSA042S4N (208/230V) TXV 41500 13.5 11.5 CR33-50/60 EL296DF090XV60C 5057775TSA042S4N (208/230V) TXV 41500 14 11.5 CR33-50/60 EL296DF110XE60C 5647482TSA042S4N (208/230V) TXV 41500 14 11.5 CR33-50/60 EL296DF110XV60C 5057776TSA042S4N (208/230V) TXV 41500 14 11.5 CR33-50/60 SL280DF090V60C 4075240TSA042S4N (208/230V) TXV 41500 14 11.5 CR33-50/60 SL280DF110V60C 4075241TSA042S4N (208/230V) TXV 41000 13.5 11.5 CR33-50/60 SLP98DF090XV36C 5139825TSA042S4N (208/230V) TXV 41500 13.5 11.5 CR33-50/60 SLP98DF090XV48C 5139826TSA042S4N (208/230V) TXV 41500 13.5 11.5 CR33-50/60 SLP98DF090XV60C 5139827TSA042S4N (208/230V) TXV 41500 14 11.5 CR33-50/60 SLP98DF110XV60C 5139828TSA042S4N (208/230V) TXV 40000 13 10.8 CR33-50/60 1286984TSA042S4N (208/230V) TXV 41500 13.5 11.5 CR33-60 EL296DF090XV60C 5057777TSA042S4N (208/230V) TXV 41500 14 11.5 CR33-60 EL296DF110XV60C 5057778TSA042S4N (208/230V) TXV 41500 13.5 11.5 CR33-60 SLP98DF090XV60C 5139829TSA042S4N (208/230V) TXV 41500 14 11.5 CR33-60 SLP98DF110XV60C 5139830TSA042S4N (208/230V) TXV 40000 13 10.8 CR33-60 1286985TSA042S4N (208/230V) TXV 41000 13 11 CX35-36B EL296UH045XV36B 10257341TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-48B EL180UH090E48B 10257342TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-48B EL180UH090XE48B 10257343TSA042S4N (208/230V) TXV 41000 13 11 CX35-48B EL296UH070XV36B 10257344TSA042S4N (208/230V) TXV 41500 14 11 CX35-48B SL280UH090V48B 10257345TSA042S4N (208/230V) TXV 41500 14 11 CX35-48B SL280UH090XV48B 10257346TSA042S4N (208/230V) TXV 41000 13 11 CX35-48B SLP98UH070XV36B 10257347TSA042S4N (208/230V) TXV 41000 13 11 CX35-48B 10257348TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-48C CBWMV-60C-100 10257349TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-48C CBWMV-60C-120 10257350TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-48C EL180UH090E60C 10257351TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-48C EL180UH110E60C 10257352TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-48C EL180UH110XE60C 10257353TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-48C EL195UH090XE48C 10257354TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-48C EL195UH110XE60C 10257355TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-48C EL296UH090XE48C 10257356TSA042S4N (208/230V) TXV 41500 13 11.5 CX35-48C EL296UH090XV36C 10257357TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-48C EL296UH090XV48C 10257358TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-48C EL296UH090XV60C 10257359TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-48C EL296UH110XE60C 10257360TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-48C EL296UH110XV48C 10257361TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-48C EL296UH110XV60C 10257362TSA042S4N (208/230V) TXV 41500 14.25 11.5 CX35-48C SL280UH090V60C 10257364TSA042S4N (208/230V) TXV 41500 14.25 11.5 CX35-48C SL280UH090XV60C 10257363TSA042S4N (208/230V) TXV 41500 14.25 11.5 CX35-48C SL280UH110V60C 10257365TSA042S4N (208/230V) TXV 41500 14.25 11.5 CX35-48C SL280UH110XV60C 10257366TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-48C SLO185B124/141V60 10257367TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-48C SLO185UF124/141V60 10257368TSA042S4N (208/230V) TXV 41500 13 11.5 CX35-48C SLP98UH090XV36C 10257369NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 26: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 26

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-48C SLP98UH090XV48C 10257370TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-48C SLP98UH090XV60C 10257371TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-48C SLP98UH110XV60C 10257372TSA042S4N (208/230V) TXV 41000 13 11 CX35-48C 10257373TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C CBWMV-60C-100 10257374TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C CBWMV-60C-120 10257375TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C EL180UH090E60C 10257376TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C EL180UH110E60C 10257377TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C EL180UH110XE60C 10257378TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-49C EL195UH090XE48C 10257379TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C EL195UH110XE60C 10257380TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-49C EL296UH090XE48C 10257381TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-49C EL296UH090XV36C 10257382TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C EL296UH090XV48C 10257383TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C EL296UH090XV60C 10257384TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C EL296UH110XE60C 10257385TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C EL296UH110XV48C 10257386TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C EL296UH110XV60C 10257387TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C SL280UH090V60C 10257388TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C SL280UH110V60C 10257389TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C SL280UH110XV60C 10257390TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C SLO185B124/141V60 10257391TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C SLO185UF124/141V60 10257392TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-49C SLP98UH090XV36C 10257393TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C SLP98UH090XV48C 10257394TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C SLP98UH090XV60C 10257395TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-49C SLP98UH110XV60C 10257396TSA042S4N (208/230V) TXV 42000 13 11 CX35-49C 10257397TSA042S4N (208/230V) TXV 41500 13.5 11.5 CX35-50/60C CBWMV-60C-100 10257398TSA042S4N (208/230V) TXV 41500 13.5 11.5 CX35-50/60C CBWMV-60C-120 10257399TSA042S4N (208/230V) TXV 41500 14 11.5 CX35-50/60C EL180UH090E60C 10257400TSA042S4N (208/230V) TXV 41000 14 11.5 CX35-50/60C EL180UH110E60C 10257401TSA042S4N (208/230V) TXV 41000 14 11.5 CX35-50/60C EL180UH110XE60C 10257402TSA042S4N (208/230V) TXV 41000 13 11.5 CX35-50/60C EL195UH090XE48C 10257403TSA042S4N (208/230V) TXV 41500 13 11.5 CX35-50/60C EL195UH110XE60C 10257404TSA042S4N (208/230V) TXV 41000 13 11.5 CX35-50/60C EL296UH090XE48C 10257405TSA042S4N (208/230V) TXV 41000 13 11.5 CX35-50/60C EL296UH090XV36C 10257406TSA042S4N (208/230V) TXV 41500 13 11.5 CX35-50/60C EL296UH090XV48C 10257407TSA042S4N (208/230V) TXV 41000 13 11.5 CX35-50/60C EL296UH090XV60C 10257408TSA042S4N (208/230V) TXV 41500 13 11.5 CX35-50/60C EL296UH110XE60C 10257409TSA042S4N (208/230V) TXV 41500 13 11.5 CX35-50/60C EL296UH110XV60C 10257410TSA042S4N (208/230V) TXV 41500 13 11.5 CX35-50/60C SL280UH090V60C 10257411TSA042S4N (208/230V) TXV 41500 13 11.5 CX35-50/60C SL280UH090XV60C 10257412TSA042S4N (208/230V) TXV 41000 13 11.5 CX35-50/60C SL280UH110V60C 10257413TSA042S4N (208/230V) TXV 41000 13 11.5 CX35-50/60C SL280UH110XV60C 10257414TSA042S4N (208/230V) TXV 41000 13 11 CX35-50/60C SLO185B124/141V60 10257415TSA042S4N (208/230V) TXV 41500 13 11 CX35-50/60C SLO185UF124/141V60 10257416TSA042S4N (208/230V) TXV 41000 13 11.5 CX35-50/60C SLP98UH090XV36C 10257417TSA042S4N (208/230V) TXV 41000 13 11.5 CX35-50/60C SLP98UH090XV48C 10257418NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 27: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 27

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (208/230V) TXV 41500 13 11.5 CX35-50/60C SLP98UH090XV60C 10257419TSA042S4N (208/230V) TXV 41000 13 11.5 CX35-50/60C SLP98UH110XV60C 10257420TSA042S4N (208/230V) TXV 41000 13 10.5 CX35-50/60C 10257421TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C EL180UH090E60C 10257422TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C EL180UH110E60C 10257423TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C EL180UH110XE60C 10257424TSA042S4N (208/230V) TXV 42000 14 12 CX35-60C EL195UH090XE48C 10257425TSA042S4N (208/230V) TXV 42000 14 12 CX35-60C EL195UH110XE60C 10257426TSA042S4N (208/230V) TXV 42000 14 12 CX35-60C EL296UH090XE48C 10257427TSA042S4N (208/230V) TXV 42000 14 12 CX35-60C EL296UH090XV48C 10257428TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C EL296UH090XV60C 10257429TSA042S4N (208/230V) TXV 42000 14 12 CX35-60C EL296UH110XE60C 10257430TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C EL296UH110XV48C 10257431TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C EL296UH110XV60C 10257432TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C SL280UH090V60C 10257433TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C SL280UH090XV60C 10257434TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C SL280UH110V60C 10257435TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C SL280UH110XV60C 10257436TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C SLO185B124/141V60 10257437TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C SLO185UF124/141V60 10257438TSA042S4N (208/230V) TXV 42000 14 11.5 CX35-60C SLP98UH090XV36C 10257439TSA042S4N (208/230V) TXV 42000 14 12 CX35-60C SLP98UH090XV48C 10257440TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C SLP98UH090XV60C 10257441TSA042S4N (208/230V) TXV 42000 14.5 12 CX35-60C SLP98UH110XV60C 10257442TSA042S4N (208/230V) TXV 41500 13 11 CX35-60C 10257443TSA042S4N (208/230V) TXV 42000 14.5 11.5 CX35-60D SLO185B124/141V60 10257444TSA042S4N (208/230V) TXV 42000 14.5 11.5 CX35-60D SLO185UF124/141V60 10257445TSA042S4N (208/230V) TXV 41500 13 11 CX35-60D 10257446TSA042S4N (208/230V) TXV 41000 13 11 CX38-49C 10557162TSA042S4N (460V) TXV 41500 13 11 C35-36B EL180UH090E48B 10257009TSA042S4N (460V) TXV 41500 13 11 C35-36B EL180UH090XE48B 10257010TSA042S4N (460V) TXV 41000 13 11 C35-36B EL296UH070XV36B 10257011TSA042S4N (460V) TXV 41000 13 11 C35-36B SL280UH090V48B 10257013TSA042S4N (460V) TXV 41000 13 11 C35-36B SL280UH090XV48B 10257012TSA042S4N (460V) TXV 41000 13 11 C35-36B SLP98UH070XV36B 10257014TSA042S4N (460V) TXV 41000 13 11 C35-36B 10257015TSA042S4N (460V) TXV 42000 14 11.5 C35-48B EL180UH090E48B 10257016TSA042S4N (460V) TXV 42000 14 11.5 C35-48B EL180UH090XE48B 10257017TSA042S4N (460V) TXV 41000 13 11 C35-48B EL296UH070XV36B 10257018TSA042S4N (460V) TXV 41500 14 11 C35-48B SL280UH090V48B 10257020TSA042S4N (460V) TXV 41500 14 11 C35-48B SL280UH090XV48B 10257019TSA042S4N (460V) TXV 41000 13 11 C35-48B SLP98UH070XV36B 10257021TSA042S4N (460V) TXV 41000 13 11 C35-48B 10257022TSA042S4N (460V) TXV 41500 14 11.5 C35-48C CBWMV-60C-100 10257023TSA042S4N (460V) TXV 41500 14 11.5 C35-48C CBWMV-60C-120 10257024TSA042S4N (460V) TXV 42000 14 11.5 C35-48C EL180UH090E60C 10257025TSA042S4N (460V) TXV 41500 14 11.5 C35-48C EL180UH110E60C 10257026TSA042S4N (460V) TXV 41500 14 11.5 C35-48C EL180UH110XE60C 10257027TSA042S4N (460V) TXV 41500 14 11.5 C35-48C EL195UH090XE48C 10257028NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 28: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 28

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (460V) TXV 42000 14 11.5 C35-48C EL195UH110XE60C 10257029TSA042S4N (460V) TXV 41500 14 11.5 C35-48C EL296UH090XE48C 10257030TSA042S4N (460V) TXV 41500 13 11.5 C35-48C EL296UH090XV36C 10257031TSA042S4N (460V) TXV 41500 14 11.5 C35-48C EL296UH090XV48C 10257032TSA042S4N (460V) TXV 42000 14 11.5 C35-48C EL296UH090XV60C 10257033TSA042S4N (460V) TXV 42000 14 11.5 C35-48C EL296UH110XE60C 10257034TSA042S4N (460V) TXV 42000 14 11.5 C35-48C EL296UH110XV48C 10257035TSA042S4N (460V) TXV 42000 14 11.5 C35-48C EL296UH110XV60C 10257036TSA042S4N (460V) TXV 41500 14.25 11.5 C35-48C SL280UH090V60C 10257037TSA042S4N (460V) TXV 41500 14.25 11.5 C35-48C SL280UH090XV60C 10257038TSA042S4N (460V) TXV 41500 14.25 11.5 C35-48C SL280UH110V60C 10257039TSA042S4N (460V) TXV 41500 14.25 11.5 C35-48C SL280UH110XV60C 10257040TSA042S4N (460V) TXV 42000 14 11.5 C35-48C SLO185B124/141V60 10257041TSA042S4N (460V) TXV 42000 14 11.5 C35-48C SLO185UF124/141V60 10257042TSA042S4N (460V) TXV 41500 13 11.5 C35-48C SLP98UH090XV36C 10257043TSA042S4N (460V) TXV 41500 14 11.5 C35-48C SLP98UH090XV48C 10257044TSA042S4N (460V) TXV 41500 14 11.5 C35-48C SLP98UH090XV60C 10257045TSA042S4N (460V) TXV 41500 14 11.5 C35-48C SLP98UH110XV60C 10257046TSA042S4N (460V) TXV 41000 13 11 C35-48C 10257047TSA042S4N (460V) TXV 42000 14 11.5 C35-49C CBWMV-60C-100 10257048TSA042S4N (460V) TXV 42000 14 11.5 C35-49C CBWMV-60C-120 10257049TSA042S4N (460V) TXV 42000 14 11.5 C35-49C EL180UH090E60C 10257050TSA042S4N (460V) TXV 42000 14 11.5 C35-49C EL180UH110E60C 10257051TSA042S4N (460V) TXV 42000 14 11.5 C35-49C EL180UH110XE60C 10257052TSA042S4N (460V) TXV 41500 14 11.5 C35-49C EL195UH090XE48C 10257053TSA042S4N (460V) TXV 42000 14 11.5 C35-49C EL195UH110XE60C 10257054TSA042S4N (460V) TXV 41500 14 11.5 C35-49C EL296UH090XE48C 10257055TSA042S4N (460V) TXV 41500 14 11.5 C35-49C EL296UH090XV36C 10257056TSA042S4N (460V) TXV 42000 14 11.5 C35-49C EL296UH090XV48C 10257057TSA042S4N (460V) TXV 42000 14 11.5 C35-49C EL296UH090XV60C 10257058TSA042S4N (460V) TXV 42000 14 11.5 C35-49C EL296UH110XE60C 10257059TSA042S4N (460V) TXV 42000 14 11.5 C35-49C EL296UH110XV48C 10257060TSA042S4N (460V) TXV 42000 14 11.5 C35-49C EL296UH110XV60C 10257061TSA042S4N (460V) TXV 42000 14 11.5 C35-49C SL280UH090V60C 10257062TSA042S4N (460V) TXV 42000 14 11.5 C35-49C SL280UH090XV60C 10257063TSA042S4N (460V) TXV 42000 14 11.5 C35-49C SL280UH110V60C 10257064TSA042S4N (460V) TXV 42000 14 11.5 C35-49C SL280UH110XV60C 10257065TSA042S4N (460V) TXV 42000 14 11.5 C35-49C SLO185B124/141V60 10257066TSA042S4N (460V) TXV 42000 14 11.5 C35-49C SLO185UF124/141V60 10257067TSA042S4N (460V) TXV 41500 14 11.5 C35-49C SLP98UH090XV36C 10257068TSA042S4N (460V) TXV 42000 14 11.5 C35-49C SLP98UH090XV48C 10257069TSA042S4N (460V) TXV 42000 14 11.5 C35-49C SLP98UH090XV60C 10257070TSA042S4N (460V) TXV 42000 14 11.5 C35-49C SLP98UH110XV60C 10257071TSA042S4N (460V) TXV 42000 13 11 C35-49C 10257072TSA042S4N (460V) TXV 41500 13.5 11.5 C35-50/60C CBWMV-60C-100 10257073TSA042S4N (460V) TXV 41500 13.5 11.5 C35-50/60C CBWMV-60C-120 10257074TSA042S4N (460V) TXV 41500 14 11.5 C35-50/60C EL180UH090E60C 10257075TSA042S4N (460V) TXV 41000 14 11.5 C35-50/60C EL180UH110E60C 10257076TSA042S4N (460V) TXV 41000 14 11.5 C35-50/60C EL180UH110XE60C 10257077NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 29: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 29

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (460V) TXV 41000 13 11.5 C35-50/60C EL195UH090XE48C 10257078TSA042S4N (460V) TXV 41500 13 11.5 C35-50/60C EL195UH110XE60C 10257079TSA042S4N (460V) TXV 41000 13 11.5 C35-50/60C EL296UH090XE48C 10257080TSA042S4N (460V) TXV 41000 13 11.5 C35-50/60C EL296UH090XV36C 10257081TSA042S4N (460V) TXV 41500 13 11.5 C35-50/60C EL296UH090XV48C 10257082TSA042S4N (460V) TXV 41000 13 11.5 C35-50/60C EL296UH090XV60C 10257083TSA042S4N (460V) TXV 41500 13 11.5 C35-50/60C EL296UH110XE60C 10257084TSA042S4N (460V) TXV 41500 13 11.5 C35-50/60C EL296UH110XV60C 10257085TSA042S4N (460V) TXV 41500 13 11.5 C35-50/60C SL280UH090V60C 10257086TSA042S4N (460V) TXV 41500 13 11.5 C35-50/60C SL280UH090XV60C 10257087TSA042S4N (460V) TXV 41000 13 11.5 C35-50/60C SL280UH110V60C 10257088TSA042S4N (460V) TXV 41000 13 11.5 C35-50/60C SL280UH110XV60C 10257089TSA042S4N (460V) TXV 41000 13 11 C35-50/60C SLO185B124/141V60 10257090TSA042S4N (460V) TXV 41500 13 11 C35-50/60C SLO185UF124/141V60 10257091TSA042S4N (460V) TXV 41000 13 11 C35-50/60C SLP98UH090XV36C 10257092TSA042S4N (460V) TXV 41000 13 11 C35-50/60C SLP98UH090XV48C 10257093TSA042S4N (460V) TXV 41500 13 11 C35-50/60C SLP98UH090XV60C 10257094TSA042S4N (460V) TXV 41000 13 11 C35-50/60C SLP98UH110XV60C 10257095TSA042S4N (460V) TXV 41000 13 10.5 C35-50/60C 10257096TSA042S4N (460V) TXV 42000 14.5 12 C35-60C EL180UH090E60C 10257097TSA042S4N (460V) TXV 42000 14.5 12 C35-60C EL180UH110E60C 10257098TSA042S4N (460V) TXV 42000 14.5 12 C35-60C EL180UH110XE60C 10257099TSA042S4N (460V) TXV 42000 14 12 C35-60C EL195UH090XE48C 10257100TSA042S4N (460V) TXV 42000 14 12 C35-60C EL195UH110XE60C 10257101TSA042S4N (460V) TXV 42000 14 12 C35-60C EL296UH090XE48C 10257102TSA042S4N (460V) TXV 42000 14 12 C35-60C EL296UH090XV48C 10257103TSA042S4N (460V) TXV 42000 14.5 12 C35-60C EL296UH090XV60C 10257104TSA042S4N (460V) TXV 42000 14 12 C35-60C EL296UH110XE60C 10257105TSA042S4N (460V) TXV 42000 14.5 12 C35-60C EL296UH110XV48C 10257106TSA042S4N (460V) TXV 42000 14.5 12 C35-60C EL296UH110XV60C 10257107TSA042S4N (460V) TXV 42000 14.5 12 C35-60C SL280UH090V60C 10257108TSA042S4N (460V) TXV 42000 14.5 12 C35-60C SL280UH090XV60C 10257109TSA042S4N (460V) TXV 42000 14.5 12 C35-60C SL280UH110V60C 10257110TSA042S4N (460V) TXV 42000 14.5 12 C35-60C SL280UH110XV60C 10257111TSA042S4N (460V) TXV 42000 14.5 12 C35-60C SLO185B124/141V60 10257112TSA042S4N (460V) TXV 42000 14.5 12 C35-60C SLO185UF124/141V60 10257113TSA042S4N (460V) TXV 42000 14 11.5 C35-60C SLP98UH090XV36C 10257114TSA042S4N (460V) TXV 42000 14 12 C35-60C SLP98UH090XV48C 10257115TSA042S4N (460V) TXV 42000 14.5 12 C35-60C SLP98UH090XV60C 10257116TSA042S4N (460V) TXV 42000 14.5 12 C35-60C SLP98UH110XV60C 10257117TSA042S4N (460V) TXV 41500 13 11 C35-60C 10257118TSA042S4N (460V) TXV 42000 14.5 11.5 C35-60D SLO185B124/141V60 10257119TSA042S4N (460V) TXV 42000 14.5 11.5 C35-60D SLO185UF124/141V60 10257120TSA042S4N (460V) TXV 41500 13 11 C35-60D 10257121TSA042S4N (460V) TXV 42000 14 11.5 CBA27UHE-042 10259532TSA042S4N (460V) TXV 42000 14 11.5 CBA27UHE-048 10259533TSA042S4N (460V) TXV 41000 13 11 CBX25UH-042 5945088TSA042S4N (460V) TXV 41500 14 11.5 CBX27UH-042 4188514TSA042S4N (460V) TXV 41500 14 11.5 CBX27UH-048 4188516NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 30: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 30

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (460V) TXV 39500 13 10.9 CBX32M-036 1287302TSA042S4N (460V) TXV 39500 13 10.9 CBX32M-042 1287303TSA042S4N (460V) TXV 41000 13 11 CBX32M-048 1287304TSA042S4N (460V) TXV 41500 14 11.6 CBX32MV-048 1287305TSA042S4N (460V) TXV 41500 14 11.6 CBX40UHV-048 3291763TSA042S4N (460V) TXV 41000 14 11.5 CH23-65 EL180UH090E60C 5736176TSA042S4N (460V) TXV 40500 14 11.5 CH23-65 EL180UH110E60C 5738000TSA042S4N (460V) TXV 40500 14 11.5 CH23-65 EL180UH110XE60C 5739088TSA042S4N (460V) TXV 40500 13.5 11.5 CH23-65 EL195UH090XE48C 4699097TSA042S4N (460V) TXV 40500 13.5 11.5 CH23-65 EL195UH110XE60C 4699098TSA042S4N (460V) TXV 40500 13.5 11.5 CH23-65 EL296UH090XE48C 5647583TSA042S4N (460V) TXV 40500 13.5 11.5 CH23-65 EL296UH090XV36C 5057681TSA042S4N (460V) TXV 40500 13.5 11.5 CH23-65 EL296UH090XV48C 5057682TSA042S4N (460V) TXV 41000 13.5 11.5 CH23-65 EL296UH090XV60C 5057683TSA042S4N (460V) TXV 40500 13.5 11.5 CH23-65 EL296UH110XE60C 5647584TSA042S4N (460V) TXV 40500 14 11.5 CH23-65 EL296UH110XV60C 5057690TSA042S4N (460V) TXV 41000 14 11.5 CH23-65 SL280UH090V60C 4075333TSA042S4N (460V) TXV 41000 14 11.5 CH23-65 SL280UH090XV60C 4235671TSA042S4N (460V) TXV 41000 14 11.5 CH23-65 SL280UH110V60C 4075334TSA042S4N (460V) TXV 41000 14 11.5 CH23-65 SL280UH110XV60C 4075420TSA042S4N (460V) TXV 40500 13.5 11.5 CH23-65 SLP98UH090XV36C 5139839TSA042S4N (460V) TXV 40500 13.5 11.5 CH23-65 SLP98UH090XV48C 5139840TSA042S4N (460V) TXV 41000 13.5 11.5 CH23-65 SLP98UH090XV60C 5139841TSA042S4N (460V) TXV 40500 14 11.5 CH23-65 SLP98UH110XV60C 5139848TSA042S4N (460V) TXV 39500 13 10.7 CH23-65 1287287TSA042S4N (460V) TXV 42000 14 11.5 CH33-43 EL180UH090E48B 5735271TSA042S4N (460V) TXV 41500 14 11.5 CH33-43 EL180UH090E60C 5736177TSA042S4N (460V) TXV 42000 14 11.5 CH33-43 EL180UH090XE48B 5737276TSA042S4N (460V) TXV 41500 14 11.5 CH33-43 EL180UH110E60C 5738002TSA042S4N (460V) TXV 41500 14 11.5 CH33-43 EL180UH110XE60C 5739090TSA042S4N (460V) TXV 41500 13.5 11 CH33-43 EL296UH070XV36B 5057706TSA042S4N (460V) TXV 41500 14 11.5 CH33-43 EL296UH090XV36C 5057707TSA042S4N (460V) TXV 41500 14 11.5 CH33-43 EL296UH090XV48C 5057708TSA042S4N (460V) TXV 42000 14 11.5 CH33-43 EL296UH090XV60C 5057709TSA042S4N (460V) TXV 41500 14 11.5 CH33-43 EL296UH110XV60C 5057710TSA042S4N (460V) TXV 42000 14 11.5 CH33-43 SL280UH090V36B 4075335TSA042S4N (460V) TXV 42000 14 11.5 CH33-43 SL280UH090V48B 4075336TSA042S4N (460V) TXV 42000 14 12 CH33-43 SL280UH090V60C 4075337TSA042S4N (460V) TXV 42000 14 11.5 CH33-43 SL280UH090XV48B 4075414TSA042S4N (460V) TXV 42000 14 12 CH33-43 SL280UH090XV60C 4235681TSA042S4N (460V) TXV 41500 14 11.5 CH33-43 SL280UH110V60C 4075338TSA042S4N (460V) TXV 41500 14 11.5 CH33-43 SL280UH110XV60C 4075421TSA042S4N (460V) TXV 41500 13.5 11 CH33-43 SLP98UH070XV36B 5139866TSA042S4N (460V) TXV 41500 14 11.5 CH33-43 SLP98UH090XV36C 5139867TSA042S4N (460V) TXV 41500 14 11.5 CH33-43 SLP98UH090XV48C 5139868TSA042S4N (460V) TXV 42000 14 11.5 CH33-43 SLP98UH090XV60C 5139869TSA042S4N (460V) TXV 41500 14 11.5 CH33-43 SLP98UH110XV60C 5139870TSA042S4N (460V) TXV 41000 14 11.5 CH33-43C EL195UH090XE48C 4699099TSA042S4N (460V) TXV 41500 14 11.5 CH33-43C EL195UH110XE60C 4699100NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 31: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 31

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (460V) TXV 41000 14 11.5 CH33-43C EL296UH090XE48C 5647585TSA042S4N (460V) TXV 41500 14 11.5 CH33-43C EL296UH110XE60C 5647586TSA042S4N (460V) TXV 41000 14 11.5 CH33-44/48 EL180UH090E48B 5735273TSA042S4N (460V) TXV 41000 14 11.5 CH33-44/48 EL180UH090XE48B 5737279TSA042S4N (460V) TXV 41000 14 11.5 CH33-48 EL180UH090E60C 5736180TSA042S4N (460V) TXV 41000 14 11.5 CH33-48 EL180UH110E60C 5738003TSA042S4N (460V) TXV 41000 14 11.5 CH33-48 EL180UH110XE60C 5739091TSA042S4N (460V) TXV 41000 13.5 11.5 CH33-48 EL296UH090XV36C 5057711TSA042S4N (460V) TXV 41000 13.5 11.5 CH33-48 EL296UH090XV48C 5057712TSA042S4N (460V) TXV 41500 13.5 11.5 CH33-48 EL296UH090XV60C 5057713TSA042S4N (460V) TXV 41500 13.5 11.5 CH33-48 EL296UH110XV60C 5057714TSA042S4N (460V) TXV 41500 14 11.5 CH33-48 SL280UH090V60C 4075339TSA042S4N (460V) TXV 41500 14 11.5 CH33-48 SL280UH090XV60C 4235675TSA042S4N (460V) TXV 41500 14 11.5 CH33-48 SL280UH110V60C 4075340TSA042S4N (460V) TXV 41500 14 11.5 CH33-48 SL280UH110XV60C 4075422TSA042S4N (460V) TXV 41000 13.5 11.5 CH33-48 SLP98UH090XV36C 5139871TSA042S4N (460V) TXV 41000 13.5 11.5 CH33-48 SLP98UH090XV48C 5139872TSA042S4N (460V) TXV 41500 13.5 11.5 CH33-48 SLP98UH090XV60C 5139873TSA042S4N (460V) TXV 41500 13.5 11.5 CH33-48 SLP98UH110XV60C 5139874TSA042S4N (460V) TXV 40000 13 10.8 CH33-48 1287288TSA042S4N (460V) TXV 40500 13.5 11.5 CH33-48C EL195UH090XE48C 4699101TSA042S4N (460V) TXV 41000 13.5 11.5 CH33-48C EL195UH110XE60C 4699102TSA042S4N (460V) TXV 40500 13.5 11.5 CH33-48C EL296UH090XE48C 5647587TSA042S4N (460V) TXV 41000 13.5 11.5 CH33-48C EL296UH110XE60C 5647588TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 EL180UH090E60C 5736181TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 EL180UH110E60C 5738005TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 EL180UH110XE60C 5739093TSA042S4N (460V) TXV 41500 14 11.5 CH33-49 EL195UH090XE48C 4699103TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 EL195UH110XE60C 4699104TSA042S4N (460V) TXV 41500 14 11.5 CH33-49 EL296UH090XE48C 5647589TSA042S4N (460V) TXV 41500 14 11.5 CH33-49 EL296UH090XV36C 5057684TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 EL296UH090XV48C 5057685TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 EL296UH090XV60C 5057686TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 EL296UH110XE60C 5647590TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 EL296UH110XV60C 5057687TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 SL280UH090V60C 4075341TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 SL280UH090XV60C 4235676TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 SL280UH110V60C 4075342TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 SL280UH110XV60C 4075423TSA042S4N (460V) TXV 41500 14 11.5 CH33-49 SLP98UH090XV36C 5139842TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 SLP98UH090XV48C 5139843TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 SLP98UH090XV60C 5139844TSA042S4N (460V) TXV 42000 14 11.5 CH33-49 SLP98UH110XV60C 5139845TSA042S4N (460V) TXV 41500 14 11.5 CH33-50/60C EL180UH090E60C 5736184TSA042S4N (460V) TXV 41500 14 11.5 CH33-50/60C EL180UH110E60C 5738008TSA042S4N (460V) TXV 41500 14 11.5 CH33-50/60C EL180UH110XE60C 5739096TSA042S4N (460V) TXV 41000 14 11.5 CH33-50/60C EL195UH090XE48C 4699105TSA042S4N (460V) TXV 41500 14 11.5 CH33-50/60C EL195UH110XE60C 4699106TSA042S4N (460V) TXV 41000 14 11.5 CH33-50/60C EL296UH090XE48C 5647591NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 32: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 32

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (460V) TXV 41500 13.5 11.5 CH33-50/60C EL296UH090XV36C 5057695TSA042S4N (460V) TXV 41500 14 11.5 CH33-50/60C EL296UH090XV48C 5057696TSA042S4N (460V) TXV 42000 13.5 11.5 CH33-50/60C EL296UH090XV60C 5057697TSA042S4N (460V) TXV 41500 14 11.5 CH33-50/60C EL296UH110XE60C 5647592TSA042S4N (460V) TXV 42000 14 11.5 CH33-50/60C EL296UH110XV60C 5057698TSA042S4N (460V) TXV 42000 14 11.5 CH33-50/60C SL280UH090V60C 4075343TSA042S4N (460V) TXV 42000 14 11.5 CH33-50/60C SL280UH090XV60C 4235677TSA042S4N (460V) TXV 42000 14 11.5 CH33-50/60C SL280UH110V60C 4075344TSA042S4N (460V) TXV 42000 14 11.5 CH33-50/60C SL280UH110XV60C 4075424TSA042S4N (460V) TXV 41500 13.5 11.5 CH33-50/60C SLP98UH090XV36C 5139855TSA042S4N (460V) TXV 41500 14 11.5 CH33-50/60C SLP98UH090XV48C 5139856TSA042S4N (460V) TXV 42000 13.5 11.5 CH33-50/60C SLP98UH090XV60C 5139857TSA042S4N (460V) TXV 42000 14 11.5 CH33-50/60C SLP98UH110XV60C 5139858TSA042S4N (460V) TXV 41000 13 11 CH33-50/60C 1287289TSA042S4N (460V) TXV 41000 14 11.5 CH33-62D EL296UH090XV60C 8341558TSA042S4N (460V) TXV 41000 14 11.5 CH33-62D EL296UH110XV60C 8341559TSA042S4N (460V) TXV 39500 13 11 CR33-48 EL195DF070XE48B 4699107TSA042S4N (460V) TXV 40000 13.5 11 CR33-48 EL195DF090XE48C 4699108TSA042S4N (460V) TXV 39500 13 11 CR33-48 EL296DF070XE48B 5647593TSA042S4N (460V) TXV 40000 13.5 11 CR33-48 EL296DF090XE48C 5647594TSA042S4N (460V) TXV 41500 14 11.5 CR33-50/60 EL180DF110E60C 5733522TSA042S4N (460V) TXV 41000 13.5 11.5 CR33-50/60 EL195DF090XE48C 4699109TSA042S4N (460V) TXV 41500 14 11.5 CR33-50/60 EL195DF110XE60C 4699093TSA042S4N (460V) TXV 41000 13.5 11.5 CR33-50/60 EL296DF090XE48C 5647595TSA042S4N (460V) TXV 41500 13.5 11.5 CR33-50/60 EL296DF090XV60C 5057692TSA042S4N (460V) TXV 41500 14 11.5 CR33-50/60 EL296DF110XE60C 5647579TSA042S4N (460V) TXV 41500 14 11.5 CR33-50/60 EL296DF110XV60C 5057693TSA042S4N (460V) TXV 41500 14 11.5 CR33-50/60 SL280DF090V60C 4075345TSA042S4N (460V) TXV 41500 14 11.5 CR33-50/60 SL280DF110V60C 4075346TSA042S4N (460V) TXV 41000 13.5 11.5 CR33-50/60 SLP98DF090XV36C 5139850TSA042S4N (460V) TXV 41500 13.5 11.5 CR33-50/60 SLP98DF090XV48C 5139851TSA042S4N (460V) TXV 41500 13.5 11.5 CR33-50/60 SLP98DF090XV60C 5139852TSA042S4N (460V) TXV 41500 14 11.5 CR33-50/60 SLP98DF110XV60C 5139853TSA042S4N (460V) TXV 40000 13 10.8 CR33-50/60 1287290TSA042S4N (460V) TXV 41500 13.5 11.5 CR33-60 EL296DF090XV60C 5057694TSA042S4N (460V) TXV 41500 14 11.5 CR33-60 EL296DF110XV60C 5057723TSA042S4N (460V) TXV 41500 13.5 11.5 CR33-60 SLP98DF090XV60C 5139854TSA042S4N (460V) TXV 41500 14 11.5 CR33-60 SLP98DF110XV60C 5139883TSA042S4N (460V) TXV 40000 13 10.8 CR33-60 1287291TSA042S4N (460V) TXV 41000 13 11 CX35-36B EL296UH045XV36B 10257122TSA042S4N (460V) TXV 42000 14 11.5 CX35-48B EL180UH090E48B 10257123TSA042S4N (460V) TXV 42000 14 11.5 CX35-48B EL180UH090XE48B 10257124TSA042S4N (460V) TXV 41000 13 11 CX35-48B EL296UH070XV36B 10257125TSA042S4N (460V) TXV 41500 14 11 CX35-48B SL280UH090V48B 10257126TSA042S4N (460V) TXV 41500 14 11 CX35-48B SL280UH090XV48B 10257127TSA042S4N (460V) TXV 41000 13 11 CX35-48B SLP98UH070XV36B 10257128TSA042S4N (460V) TXV 41000 13 11 CX35-48B 10257129TSA042S4N (460V) TXV 41500 14 11.5 CX35-48C CBWMV-60C-100 10257130TSA042S4N (460V) TXV 41500 14 11.5 CX35-48C CBWMV-60C-120 10257131NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 33: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 33

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (460V) TXV 42000 14 11.5 CX35-48C EL180UH090E60C 10257132TSA042S4N (460V) TXV 41500 14 11.5 CX35-48C EL180UH110E60C 10257133TSA042S4N (460V) TXV 41500 14 11.5 CX35-48C EL180UH110XE60C 10257134TSA042S4N (460V) TXV 41500 14 11.5 CX35-48C EL195UH090XE48C 10257135TSA042S4N (460V) TXV 42000 14 11.5 CX35-48C EL195UH110XE60C 10257136TSA042S4N (460V) TXV 41500 14 11.5 CX35-48C EL296UH090XE48C 10257137TSA042S4N (460V) TXV 41500 13 11.5 CX35-48C EL296UH090XV36C 10257138TSA042S4N (460V) TXV 41500 14 11.5 CX35-48C EL296UH090XV48C 10257139TSA042S4N (460V) TXV 42000 14 11.5 CX35-48C EL296UH090XV60C 10257140TSA042S4N (460V) TXV 42000 14 11.5 CX35-48C EL296UH110XE60C 10257141TSA042S4N (460V) TXV 42000 14 11.5 CX35-48C EL296UH110XV48C 10257142TSA042S4N (460V) TXV 42000 14 11.5 CX35-48C EL296UH110XV60C 10257143TSA042S4N (460V) TXV 41500 14.25 11.5 CX35-48C SL280UH090V60C 10257145TSA042S4N (460V) TXV 41500 14.25 11.5 CX35-48C SL280UH090XV60C 10257144TSA042S4N (460V) TXV 41500 14.25 11.5 CX35-48C SL280UH110V60C 10257146TSA042S4N (460V) TXV 41500 14.25 11.5 CX35-48C SL280UH110XV60C 10257147TSA042S4N (460V) TXV 42000 14 11.5 CX35-48C SLO185B124/141V60 10257148TSA042S4N (460V) TXV 42000 14 11.5 CX35-48C SLO185UF124/141V60 10257149TSA042S4N (460V) TXV 41500 13 11.5 CX35-48C SLP98UH090XV36C 10257150TSA042S4N (460V) TXV 41500 14 11.5 CX35-48C SLP98UH090XV48C 10257151TSA042S4N (460V) TXV 41500 14 11.5 CX35-48C SLP98UH090XV60C 10257152TSA042S4N (460V) TXV 41500 14 11.5 CX35-48C SLP98UH110XV60C 10257153TSA042S4N (460V) TXV 41000 13 11 CX35-48C 10257154TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C CBWMV-60C-100 10257155TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C CBWMV-60C-120 10257156TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C EL180UH090E60C 10257157TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C EL180UH110E60C 10257158TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C EL180UH110XE60C 10257159TSA042S4N (460V) TXV 41500 14 11.5 CX35-49C EL195UH090XE48C 10257160TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C EL195UH110XE60C 10257161TSA042S4N (460V) TXV 41500 14 11.5 CX35-49C EL296UH090XE48C 10257162TSA042S4N (460V) TXV 41500 14 11.5 CX35-49C EL296UH090XV36C 10257163TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C EL296UH090XV48C 10257164TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C EL296UH090XV60C 10257165TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C EL296UH110XE60C 10257166TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C EL296UH110XV48C 10257167TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C EL296UH110XV60C 10257168TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C SL280UH090V60C 10257169TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C SL280UH110V60C 10257170TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C SL280UH110XV60C 10257171TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C SLO185B124/141V60 10257172TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C SLO185UF124/141V60 10257173TSA042S4N (460V) TXV 41500 14 11.5 CX35-49C SLP98UH090XV36C 10257174TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C SLP98UH090XV48C 10257175TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C SLP98UH090XV60C 10257176TSA042S4N (460V) TXV 42000 14 11.5 CX35-49C SLP98UH110XV60C 10257177TSA042S4N (460V) TXV 42000 13 11 CX35-49C 10257178TSA042S4N (460V) TXV 41500 13.5 11.5 CX35-50/60C CBWMV-60C-100 10257179TSA042S4N (460V) TXV 41500 13.5 11.5 CX35-50/60C CBWMV-60C-120 10257180NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 34: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 34

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA042S4N (460V) TXV 41500 14 11.5 CX35-50/60C EL180UH090E60C 10257181TSA042S4N (460V) TXV 41000 14 11.5 CX35-50/60C EL180UH110E60C 10257182TSA042S4N (460V) TXV 41000 14 11.5 CX35-50/60C EL180UH110XE60C 10257183TSA042S4N (460V) TXV 41000 13 11.5 CX35-50/60C EL195UH090XE48C 10257184TSA042S4N (460V) TXV 41500 13 11.5 CX35-50/60C EL195UH110XE60C 10257185TSA042S4N (460V) TXV 41000 13 11.5 CX35-50/60C EL296UH090XE48C 10257186TSA042S4N (460V) TXV 41000 13 11.5 CX35-50/60C EL296UH090XV36C 10257187TSA042S4N (460V) TXV 41500 13 11.5 CX35-50/60C EL296UH090XV48C 10257188TSA042S4N (460V) TXV 41000 13 11.5 CX35-50/60C EL296UH090XV60C 10257189TSA042S4N (460V) TXV 41500 13 11.5 CX35-50/60C EL296UH110XE60C 10257190TSA042S4N (460V) TXV 41500 13 11.5 CX35-50/60C EL296UH110XV60C 10257191TSA042S4N (460V) TXV 41500 13 11.5 CX35-50/60C SL280UH090V60C 10257192TSA042S4N (460V) TXV 41500 13 11.5 CX35-50/60C SL280UH090XV60C 10257193TSA042S4N (460V) TXV 41000 13 11.5 CX35-50/60C SL280UH110V60C 10257194TSA042S4N (460V) TXV 41000 13 11.5 CX35-50/60C SL280UH110XV60C 10257195TSA042S4N (460V) TXV 41000 13 11 CX35-50/60C SLO185B124/141V60 10257196TSA042S4N (460V) TXV 41500 13 11 CX35-50/60C SLO185UF124/141V60 10257197TSA042S4N (460V) TXV 41000 13 11.5 CX35-50/60C SLP98UH090XV36C 10257198TSA042S4N (460V) TXV 41000 13 11.5 CX35-50/60C SLP98UH090XV48C 10257199TSA042S4N (460V) TXV 41500 13 11.5 CX35-50/60C SLP98UH090XV60C 10257200TSA042S4N (460V) TXV 41000 13 11.5 CX35-50/60C SLP98UH110XV60C 10257201TSA042S4N (460V) TXV 41000 13 10.5 CX35-50/60C 10257202TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C EL180UH090E60C 10257203TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C EL180UH110E60C 10257204TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C EL180UH110XE60C 10257205TSA042S4N (460V) TXV 42000 14 12 CX35-60C EL195UH090XE48C 10257206TSA042S4N (460V) TXV 42000 14 12 CX35-60C EL195UH110XE60C 10257207TSA042S4N (460V) TXV 42000 14 12 CX35-60C EL296UH090XE48C 10257208TSA042S4N (460V) TXV 42000 14 12 CX35-60C EL296UH090XV48C 10257209TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C EL296UH090XV60C 10257210TSA042S4N (460V) TXV 42000 14 12 CX35-60C EL296UH110XE60C 10257211TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C EL296UH110XV48C 10257212TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C EL296UH110XV60C 10257213TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C SL280UH090V60C 10257214TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C SL280UH090XV60C 10257215TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C SL280UH110V60C 10257216TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C SL280UH110XV60C 10257217TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C SLO185B124/141V60 10257218TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C SLO185UF124/141V60 10257219TSA042S4N (460V) TXV 42000 14 11.5 CX35-60C SLP98UH090XV36C 10257220TSA042S4N (460V) TXV 42000 14 12 CX35-60C SLP98UH090XV48C 10257221TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C SLP98UH090XV60C 10257222TSA042S4N (460V) TXV 42000 14.5 12 CX35-60C SLP98UH110XV60C 10257223TSA042S4N (460V) TXV 41500 13 11 CX35-60C 10257224TSA042S4N (460V) TXV 42000 14.5 11.5 CX35-60D SLO185B124/141V60 10257225TSA042S4N (460V) TXV 42000 14.5 11.5 CX35-60D SLO185UF124/141V60 10257226TSA042S4N (460V) TXV 41500 13 11 CX35-60D 10257227TSA042S4N (460V) TXV 41000 13 11 CX38-49C 10557082TSA048S4N (208/230V) TXV 48500 13 11 C35-48B 10248812NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 35: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 35

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA048S4N (208/230V) TXV 48500 13 11 C35-48C 10248813TSA048S4N (208/230V) TXV 49000 14 11.7 C35-49C EL180UH090E60C 10248814TSA048S4N (208/230V) TXV 49000 14 11.7 C35-49C EL180UH110E60C 10248815TSA048S4N (208/230V) TXV 49000 14 11.7 C35-49C EL180UH110XE60C 10248816TSA048S4N (208/230V) TXV 49000 14 11.7 C35-49C EL195UH110XE60C 10248817TSA048S4N (208/230V) TXV 49000 14 11.7 C35-49C SL280UH090V60C 10248818TSA048S4N (208/230V) TXV 49500 14 11.7 C35-49C SL280UH090XV60C 10248819TSA048S4N (208/230V) TXV 49500 14 11.7 C35-49C SL280UH110V60C 10248820TSA048S4N (208/230V) TXV 49500 14 11.7 C35-49C SL280UH110XV60C 10248821TSA048S4N (208/230V) TXV 49000 13 11 C35-49C 10248822TSA048S4N (208/230V) TXV 47500 13 11 C35-50/60C 10248823TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C EL180UH090E60C 10248824TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C EL180UH110E60C 10248825TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C EL180UH110XE60C 10248826TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C EL195UH090XE48C 10248827TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C EL195UH110XE60C 10248828TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C EL296UH090XE48C 10248829TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C EL296UH090XV48C 10248830TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C EL296UH090XV60C 10248831TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C EL296UH110XE60C 10248832TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C EL296UH110XV48C 10248833TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C EL296UH110XV60C 10248834TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C SL280UH090V60C 10248835TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C SL280UH090XV60C 10248836TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C SL280UH110V60C 10248837TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C SL280UH110XV60C 10248838TSA048S4N (208/230V) TXV 49500 14 11.7 C35-60C SLP98UH090XV48C 10248839TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C SLP98UH090XV60C 10248840TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60C SLP98UH110XV60C 10248841TSA048S4N (208/230V) TXV 50000 13 11 C35-60C 10248842TSA048S4N (208/230V) TXV 49500 14 11.7 C35-60D EL180UH135E60D 10248843TSA048S4N (208/230V) TXV 50000 14 11.7 C35-60D EL296UH135XV60D 10248844TSA048S4N (208/230V) TXV 49500 14 11.7 C35-60D SL280UH135V60D 10248845TSA048S4N (208/230V) TXV 49000 14 11.7 C35-60D SLP98UH135XV60D 10248846TSA048S4N (208/230V) TXV 49000 13 11 C35-60D 10248847TSA048S4N (208/230V) TXV 48000 13 11.5 CBA27UHE-060 10259534TSA048S4N (208/230V) TXV 48500 14 11.5 CBX25UH-048 5945091TSA048S4N (208/230V) TXV 48000 13.5 11 CBX27UH-048 4188519TSA048S4N (208/230V) TXV 48500 14 11.5 CBX27UH-060 4188521TSA048S4N (208/230V) TXV 45500 13 10.7 CBX32M-042 1287071TSA048S4N (208/230V) TXV 48000 14 11.5 CBX32M-048 1287072TSA048S4N (208/230V) TXV 48500 14 11.5 CBX32M-060 1287073TSA048S4N (208/230V) TXV 48000 14 11.5 CBX32MV-048 1287074TSA048S4N (208/230V) TXV 48000 14 11.5 CBX32MV-060 1287075TSA048S4N (208/230V) TXV 48000 13.5 11 CBX40UHV-048 3291772TSA048S4N (208/230V) TXV 48500 13.5 11 CBX40UHV-060 3291828TSA048S4N (208/230V) TXV 49000 14.5 12 CH23-68 EL180UH135E60D 5756467TSA048S4N (208/230V) TXV 49000 14 11.5 CH23-68 EL195UH135XE60D 4699026TSA048S4N (208/230V) TXV 49000 14 11.5 CH23-68 EL296UH135XE60D 5647414NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 36: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 36

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA048S4N (208/230V) TXV 49000 14.5 12 CH23-68 SL280UH135V60D 4075482TSA048S4N (208/230V) TXV 49000 14.5 12 CH23-68 SLP98UH135XV60D 5139919TSA048S4N (208/230V) TXV 48500 13.5 11 CH23-68 1287048TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-43 EL180UH090E60C 5736252TSA048S4N (208/230V) TXV 47500 14 11.5 CH33-43 EL180UH110E60C 5738028TSA048S4N (208/230V) TXV 47500 14 11.5 CH33-43 EL180UH110XE60C 5739108TSA048S4N (208/230V) TXV 48000 13.5 11 CH33-43 EL296UH090XV48C 5057963TSA048S4N (208/230V) TXV 48000 13.5 11 CH33-43 EL296UH090XV60C 5057964TSA048S4N (208/230V) TXV 48000 13.5 11 CH33-43 EL296UH110XV60C 5057937TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-43 SL280UH090V48B 4075483TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-43 SL280UH090V60C 4075484TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-43 SL280UH090XV48B 4075560TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-43 SL280UH090XV60C 4235691TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-43 SL280UH110V60C 4075485TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-43 SL280UH110XV60C 4075574TSA048S4N (208/230V) TXV 48000 13.5 11 CH33-43 SLP98UH090XV48C 5139920TSA048S4N (208/230V) TXV 48000 13.5 11 CH33-43 SLP98UH090XV60C 5139921TSA048S4N (208/230V) TXV 48000 13.5 11 CH33-43 SLP98UH110XV60C 5139893TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-43C EL195UH090XE48C 4699027TSA048S4N (208/230V) TXV 47500 14 11.5 CH33-43C EL195UH110XE60C 4699028TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-43C EL296UH090XE48C 5647415TSA048S4N (208/230V) TXV 47500 14 11.5 CH33-43C EL296UH110XE60C 5647416TSA048S4N (208/230V) TXV 47000 13.5 11 CH33-44/48 EL180UH090E48B 5735295TSA048S4N (208/230V) TXV 47000 13.5 11 CH33-44/48 EL180UH090XE48B 5737282TSA048S4N (208/230V) TXV 47000 13 11 CH33-44/48 SL280UH090V48B 4075486TSA048S4N (208/230V) TXV 47000 13 11 CH33-44/48 SL280UH090XV48B 4075561TSA048S4N (208/230V) TXV 47000 13 11 CH33-44/48 1287050TSA048S4N (208/230V) TXV 47500 14 11.5 CH33-48 EL180UH090E60C 5736206TSA048S4N (208/230V) TXV 47000 14 11.5 CH33-48 EL180UH110E60C 5738030TSA048S4N (208/230V) TXV 47000 14 11.5 CH33-48 EL180UH110XE60C 5739109TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-48 EL296UH090XV48C 5057938TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-48 EL296UH090XV60C 5057939TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-48 EL296UH110XV60C 5057940TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-48 SL280UH090V60C 4075487TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-48 SL280UH090XV60C 4235692TSA048S4N (208/230V) TXV 47500 13.5 11.5 CH33-48 SL280UH110V60C 4075488TSA048S4N (208/230V) TXV 47500 13.5 11.5 CH33-48 SL280UH110XV60C 4075566TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-48 SLP98UH090XV48C 5139894TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-48 SLP98UH090XV60C 5139895TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-48 SLP98UH110XV60C 5139896TSA048S4N (208/230V) TXV 47500 13 11 CH33-48 1287049TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-48C EL195UH090XE48C 4699029TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-48C EL195UH110XE60C 4699030TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-48C EL296UH090XE48C 5647417TSA048S4N (208/230V) TXV 47500 13.5 11 CH33-48C EL296UH110XE60C 5647418TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-49 EL180UH090E60C 5736207TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-49 EL180UH110E60C 5738031TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-49 EL180UH110XE60C 5739111TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-49 EL195UH090XE48C 4699031NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 37: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 37

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-49 EL195UH110XE60C 4699032TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-49 EL296UH090XE48C 5647419TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-49 EL296UH090XV48C 5057941TSA048S4N (208/230V) TXV 48500 13.5 11 CH33-49 EL296UH090XV60C 5057942TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-49 EL296UH110XE60C 5647420TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-49 EL296UH110XV60C 5057943TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-49 SL280UH090V60C 4075489TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-49 SL280UH090XV60C 4235693TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-49 SL280UH110V60C 4075490TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-49 SL280UH110XV60C 4075567TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-49 SLP98UH090XV48C 5139897TSA048S4N (208/230V) TXV 48500 13.5 11 CH33-49 SLP98UH090XV60C 5139898TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-49 SLP98UH110XV60C 5139899TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-50/60C EL180UH090E60C 5736210TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-50/60C EL180UH110E60C 5738034TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-50/60C EL180UH110XE60C 5739114TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-50/60C EL195UH090XE48C 4699033TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-50/60C EL195UH110XE60C 4699034TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-50/60C EL296UH090XE48C 5647421TSA048S4N (208/230V) TXV 48000 13.5 11.5 CH33-50/60C EL296UH090XV48C 5057944TSA048S4N (208/230V) TXV 48000 13.5 11.5 CH33-50/60C EL296UH090XV60C 5057945TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-50/60C EL296UH110XE60C 5647422TSA048S4N (208/230V) TXV 48500 13.5 11 CH33-50/60C EL296UH110XV60C 5057965TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-50/60C SL280UH090V60C 4075491TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-50/60C SL280UH090XV60C 4235694TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-50/60C SL280UH110V60C 4075495TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-50/60C SL280UH110XV60C 4075568TSA048S4N (208/230V) TXV 48000 13.5 11.5 CH33-50/60C SLP98UH090XV48C 5139900TSA048S4N (208/230V) TXV 48000 13.5 11.5 CH33-50/60C SLP98UH090XV60C 5139901TSA048S4N (208/230V) TXV 48500 13.5 11 CH33-50/60C SLP98UH110XV60C 5139922TSA048S4N (208/230V) TXV 48000 13.5 11 CH33-50/60C 1287051TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-60D EL180UH135E60D 5756468TSA048S4N (208/230V) TXV 48000 13.5 11 CH33-60D EL195UH135XE60D 4699035TSA048S4N (208/230V) TXV 48000 13.5 11 CH33-60D EL296UH135XE60D 5647423TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-60D EL296UH135XV60D 5057946TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-60D SL280UH135V60D 4075496TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-60D SLP98UH135XV60D 5139902TSA048S4N (208/230V) TXV 47500 13 11 CH33-60D 1287052TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-62D EL180UH135E60D 5756469TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-62D EL195UH135XE60D 4699036TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-62D EL296UH090XV60C 8341564TSA048S4N (208/230V) TXV 47500 13.5 11.5 CH33-62D EL296UH110XV60C 8341565TSA048S4N (208/230V) TXV 48000 14 11.5 CH33-62D EL296UH135XE60D 5647424TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-62D EL296UH135XV60D 5057947TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-62D SL280UH135V60D 4075497TSA048S4N (208/230V) TXV 48500 14 11.5 CH33-62D SLP98UH135XV60D 5139903TSA048S4N (208/230V) TXV 48000 13.5 11 CH33-62D 1287053TSA048S4N (208/230V) TXV 47500 14 11.5 CR33-50/60 EL180DF110E60C 5733524TSA048S4N (208/230V) TXV 47000 14 11 CR33-50/60 EL195DF090XE48C 4699037NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 38: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 38

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA048S4N (208/230V) TXV 47000 14 11 CR33-50/60 EL195DF110XE60C 4699038TSA048S4N (208/230V) TXV 47000 14 11 CR33-50/60 EL296DF090XE48C 5647425TSA048S4N (208/230V) TXV 47000 13.5 11 CR33-50/60 EL296DF090XV60C 5057951TSA048S4N (208/230V) TXV 47000 14 11 CR33-50/60 EL296DF110XE60C 5647426TSA048S4N (208/230V) TXV 47000 13.5 11 CR33-50/60 EL296DF110XV60C 5057952TSA048S4N (208/230V) TXV 47500 14 11.5 CR33-50/60 SL280DF090V60C 4075498TSA048S4N (208/230V) TXV 47500 14 11.5 CR33-50/60 SL280DF110V60C 4075499TSA048S4N (208/230V) TXV 47000 13.5 11 CR33-50/60 SLP98DF090XV48C 5139907TSA048S4N (208/230V) TXV 47000 13.5 11 CR33-50/60 SLP98DF090XV60C 5139908TSA048S4N (208/230V) TXV 47000 13.5 11 CR33-50/60 SLP98DF110XV60C 5139909TSA048S4N (208/230V) TXV 47000 13 11 CR33-50/60 1287054TSA048S4N (208/230V) TXV 47500 13 11 CR33-60 EL296DF090XV60C 5057953TSA048S4N (208/230V) TXV 47500 13 11 CR33-60 EL296DF110XV60C 5057954TSA048S4N (208/230V) TXV 47500 13 11 CR33-60 SLP98DF090XV60C 5139910TSA048S4N (208/230V) TXV 47500 13 11 CR33-60 SLP98DF110XV60C 5139911TSA048S4N (208/230V) TXV 47500 13 11 CR33-60 1287055TSA048S4N (208/230V) TXV 48500 13 11 CX35-48B 10248848TSA048S4N (208/230V) TXV 48500 13 11 CX35-48C 10248849TSA048S4N (208/230V) TXV 49000 14 11.7 CX35-49C EL180UH090E60C 10248850TSA048S4N (208/230V) TXV 49000 14 11.7 CX35-49C EL180UH110E60C 10248851TSA048S4N (208/230V) TXV 49000 14 11.7 CX35-49C EL180UH110XE60C 10248852TSA048S4N (208/230V) TXV 49000 14 11.7 CX35-49C EL195UH110XE60C 10248853TSA048S4N (208/230V) TXV 49000 14 11.7 CX35-49C EL296UH110XE60C 10248854TSA048S4N (208/230V) TXV 49500 14 11.7 CX35-49C SL280UH090V60C 10248855TSA048S4N (208/230V) TXV 49500 14 11.7 CX35-49C SL280UH090XV60C 10248856TSA048S4N (208/230V) TXV 49500 14 11.7 CX35-49C SL280UH110V60C 10248857TSA048S4N (208/230V) TXV 49500 14 11.7 CX35-49C SL280UH110XV60C 10248858TSA048S4N (208/230V) TXV 49000 13 11 CX35-49C 10248859TSA048S4N (208/230V) TXV 47500 13 11 CX35-50/60C 10248860TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C EL180UH090E60C 10248861TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C EL180UH110E60C 10248862TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C EL180UH110XE60C 10248863TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C EL195UH090XE48C 10248864TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C EL195UH110XE60C 10248865TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C EL296UH090XE48C 10248866TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C EL296UH090XV48C 10248867TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C EL296UH090XV60C 10248868TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C EL296UH110XE60C 10248869TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C EL296UH110XV48C 10248870TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C EL296UH110XV60C 10248871TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C SL280UH090V60C 10248872TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C SL280UH090XV60C 10248873TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C SL280UH110V60C 10248874TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C SL280UH110XV60C 10248875TSA048S4N (208/230V) TXV 49500 14 11.7 CX35-60C SLP98UH090XV48C 10248876TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C SLP98UH090XV60C 10248877TSA048S4N (208/230V) TXV 50000 14 11.7 CX35-60C SLP98UH110XV60C 10248878TSA048S4N (208/230V) TXV 50000 13 11 CX35-60C 10248879TSA048S4N (208/230V) TXV 49500 14 11.7 CX35-60D EL180UH135E60D 10248880NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 39: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 39

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA048S4N (208/230V) TXV 49500 14 11.7 CX35-60D SL280UH135V60D 10248881TSA048S4N (208/230V) TXV 49000 14 11.7 CX35-60D SLP98UH135XV60D 10248882TSA048S4N (208/230V) TXV 49000 13 11 CX35-60D 10248883TSA048S4N (460V) TXV 48500 13 11 C35-48B 10248740TSA048S4N (460V) TXV 48500 13 11 C35-48C 10248741TSA048S4N (460V) TXV 49000 14 11.7 C35-49C EL180UH090E60C 10248742TSA048S4N (460V) TXV 49000 14 11.7 C35-49C EL180UH110E60C 10248743TSA048S4N (460V) TXV 49000 14 11.7 C35-49C EL180UH110XE60C 10248744TSA048S4N (460V) TXV 49000 14 11.7 C35-49C EL195UH110XE60C 10248745TSA048S4N (460V) TXV 49000 14 11.7 C35-49C SL280UH090V60C 10248746TSA048S4N (460V) TXV 49500 14 11.7 C35-49C SL280UH090XV60C 10248747TSA048S4N (460V) TXV 49500 14 11.7 C35-49C SL280UH110V60C 10248748TSA048S4N (460V) TXV 49500 14 11.7 C35-49C SL280UH110XV60C 10248749TSA048S4N (460V) TXV 49000 13 11 C35-49C 10248750TSA048S4N (460V) TXV 47500 13 11 C35-50/60C 10248751TSA048S4N (460V) TXV 50000 14 11.7 C35-60C EL180UH090E60C 10248752TSA048S4N (460V) TXV 50000 14 11.7 C35-60C EL180UH110E60C 10248753TSA048S4N (460V) TXV 50000 14 11.7 C35-60C EL180UH110XE60C 10248754TSA048S4N (460V) TXV 50000 14 11.7 C35-60C EL195UH090XE48C 10248755TSA048S4N (460V) TXV 50000 14 11.7 C35-60C EL195UH110XE60C 10248756TSA048S4N (460V) TXV 50000 14 11.7 C35-60C EL296UH090XE48C 10248757TSA048S4N (460V) TXV 50000 14 11.7 C35-60C EL296UH090XV48C 10248758TSA048S4N (460V) TXV 50000 14 11.7 C35-60C EL296UH090XV60C 10248759TSA048S4N (460V) TXV 50000 14 11.7 C35-60C EL296UH110XE60C 10248760TSA048S4N (460V) TXV 50000 14 11.7 C35-60C EL296UH110XV48C 10248761TSA048S4N (460V) TXV 50000 14 11.7 C35-60C EL296UH110XV60C 10248762TSA048S4N (460V) TXV 50000 14 11.7 C35-60C SL280UH090V60C 10248763TSA048S4N (460V) TXV 50000 14 11.7 C35-60C SL280UH090XV60C 10248764TSA048S4N (460V) TXV 50000 14 11.7 C35-60C SL280UH110V60C 10248765TSA048S4N (460V) TXV 50000 14 11.7 C35-60C SL280UH110XV60C 10248766TSA048S4N (460V) TXV 49500 14 11.7 C35-60C SLP98UH090XV48C 10248767TSA048S4N (460V) TXV 50000 14 11.7 C35-60C SLP98UH090XV60C 10248768TSA048S4N (460V) TXV 50000 14 11.7 C35-60C SLP98UH110XV60C 10248769TSA048S4N (460V) TXV 50000 13 11 C35-60C 10248770TSA048S4N (460V) TXV 49500 14 11.7 C35-60D EL180UH135E60D 10248771TSA048S4N (460V) TXV 50000 14 11.7 C35-60D EL296UH135XV60D 10248772TSA048S4N (460V) TXV 49500 14 11.7 C35-60D SL280UH135V60D 10248773TSA048S4N (460V) TXV 49000 14 11.7 C35-60D SLP98UH135XV60D 10248774TSA048S4N (460V) TXV 49000 13 11 C35-60D 10248775TSA048S4N (460V) TXV 48000 13 11.5 CBA27UHE-060 10259535TSA048S4N (460V) TXV 48500 14 11.5 CBX25UH-048 5945090TSA048S4N (460V) TXV 48000 13.5 11 CBX27UH-048 4188518TSA048S4N (460V) TXV 48000 13.5 11 CBX27UH-048-460 7635244TSA048S4N (460V) TXV 48500 14 11.5 CBX27UH-060 4188520TSA048S4N (460V) TXV 48500 14 11.5 CBX27UH-060-460 7635246TSA048S4N (460V) TXV 45500 13 10.7 CBX32M-042 1287379TSA048S4N (460V) TXV 48000 14 11.5 CBX32M-048 1287380TSA048S4N (460V) TXV 48500 14 11.5 CBX32M-060 1287381TSA048S4N (460V) TXV 48000 14 11.5 CBX32MV-048 1287382NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 40: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 40

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA048S4N (460V) TXV 48000 14 11.5 CBX32MV-060 1287383TSA048S4N (460V) TXV 48000 13.5 11 CBX40UHV-048 3291771TSA048S4N (460V) TXV 48500 13.5 11 CBX40UHV-060 3291827TSA048S4N (460V) TXV 49000 14.5 12 CH23-68 EL180UH135E60D 5756460TSA048S4N (460V) TXV 49000 14 11.5 CH23-68 EL195UH135XE60D 4699129TSA048S4N (460V) TXV 49000 14 11.5 CH23-68 EL296UH135XE60D 5647549TSA048S4N (460V) TXV 49000 14.5 12 CH23-68 SL280UH135V60D 4075587TSA048S4N (460V) TXV 49000 14.5 12 CH23-68 SLP98UH135XV60D 5139945TSA048S4N (460V) TXV 48500 13.5 11 CH23-68 1287356TSA048S4N (460V) TXV 48000 14 11.5 CH33-43 EL180UH090E60C 5736227TSA048S4N (460V) TXV 47500 14 11.5 CH33-43 EL180UH110E60C 5738051TSA048S4N (460V) TXV 47500 14 11.5 CH33-43 EL180UH110XE60C 5739132TSA048S4N (460V) TXV 48000 13.5 11 CH33-43 EL296UH090XV48C 5057895TSA048S4N (460V) TXV 48000 13.5 11 CH33-43 EL296UH090XV60C 5057896TSA048S4N (460V) TXV 48000 13.5 11 CH33-43 EL296UH110XV60C 5057900TSA048S4N (460V) TXV 48500 14 11.5 CH33-43 SL280UH090V48B 4075588TSA048S4N (460V) TXV 48000 14 11.5 CH33-43 SL280UH090V60C 4075589TSA048S4N (460V) TXV 48500 14 11.5 CH33-43 SL280UH090XV48B 4075665TSA048S4N (460V) TXV 48000 14 11.5 CH33-43 SL280UH090XV60C 4235704TSA048S4N (460V) TXV 48000 14 11.5 CH33-43 SL280UH110V60C 4075590TSA048S4N (460V) TXV 48000 14 11.5 CH33-43 SL280UH110XV60C 4075679TSA048S4N (460V) TXV 48000 13.5 11 CH33-43 SLP98UH090XV48C 5139946TSA048S4N (460V) TXV 48000 13.5 11 CH33-43 SLP98UH090XV60C 5139947TSA048S4N (460V) TXV 48000 13.5 11 CH33-43 SLP98UH110XV60C 5139951TSA048S4N (460V) TXV 47500 13.5 11 CH33-43C EL195UH090XE48C 4699130TSA048S4N (460V) TXV 47500 14 11.5 CH33-43C EL195UH110XE60C 4699131TSA048S4N (460V) TXV 47500 13.5 11 CH33-43C EL296UH090XE48C 5647550TSA048S4N (460V) TXV 47500 14 11.5 CH33-43C EL296UH110XE60C 5647551TSA048S4N (460V) TXV 47000 13.5 11 CH33-44/48 EL180UH090E48B 5735297TSA048S4N (460V) TXV 47000 13.5 11 CH33-44/48 EL180UH090XE48B 5737285TSA048S4N (460V) TXV 47000 13 11 CH33-44/48 SL280UH090V48B 4075591TSA048S4N (460V) TXV 47000 13 11 CH33-44/48 SL280UH090XV48B 4075666TSA048S4N (460V) TXV 47000 13 11 CH33-44/48 1287358TSA048S4N (460V) TXV 47500 14 11.5 CH33-48 EL180UH090E60C 5736229TSA048S4N (460V) TXV 47000 14 11.5 CH33-48 EL180UH110E60C 5738053TSA048S4N (460V) TXV 47000 14 11.5 CH33-48 EL180UH110XE60C 5739134TSA048S4N (460V) TXV 47500 13.5 11 CH33-48 EL296UH090XV48C 5057901TSA048S4N (460V) TXV 47500 13.5 11 CH33-48 EL296UH090XV60C 5057902TSA048S4N (460V) TXV 47500 13.5 11 CH33-48 EL296UH110XV60C 5057903TSA048S4N (460V) TXV 48000 14 11.5 CH33-48 SL280UH090V60C 4075592TSA048S4N (460V) TXV 48000 14 11.5 CH33-48 SL280UH090XV60C 4235705TSA048S4N (460V) TXV 47500 13.5 11.5 CH33-48 SL280UH110V60C 4075593TSA048S4N (460V) TXV 47500 13.5 11.5 CH33-48 SL280UH110XV60C 4075671TSA048S4N (460V) TXV 47500 13.5 11 CH33-48 SLP98UH090XV48C 5139952TSA048S4N (460V) TXV 47500 13.5 11 CH33-48 SLP98UH090XV60C 5139953TSA048S4N (460V) TXV 47500 13.5 11 CH33-48 SLP98UH110XV60C 5139954TSA048S4N (460V) TXV 47500 13 11 CH33-48 1287357TSA048S4N (460V) TXV 47500 13.5 11 CH33-48C EL195UH090XE48C 4699132TSA048S4N (460V) TXV 47500 13.5 11 CH33-48C EL195UH110XE60C 4699133NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 41: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 41

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA048S4N (460V) TXV 47500 13.5 11 CH33-48C EL296UH090XE48C 5647552TSA048S4N (460V) TXV 47500 13.5 11 CH33-48C EL296UH110XE60C 5647553TSA048S4N (460V) TXV 48500 14 11.5 CH33-49 EL180UH090E60C 5736232TSA048S4N (460V) TXV 48000 14 11.5 CH33-49 EL180UH110E60C 5738055TSA048S4N (460V) TXV 48000 14 11.5 CH33-49 EL180UH110XE60C 5739135TSA048S4N (460V) TXV 48000 14 11.5 CH33-49 EL195UH090XE48C 4699134TSA048S4N (460V) TXV 48500 14 11.5 CH33-49 EL195UH110XE60C 4699135TSA048S4N (460V) TXV 48000 14 11.5 CH33-49 EL296UH090XE48C 5647554TSA048S4N (460V) TXV 48500 14 11.5 CH33-49 EL296UH090XV48C 5057904TSA048S4N (460V) TXV 48500 13.5 11 CH33-49 EL296UH090XV60C 5057905TSA048S4N (460V) TXV 48500 14 11.5 CH33-49 EL296UH110XE60C 5647555TSA048S4N (460V) TXV 48500 14 11.5 CH33-49 EL296UH110XV60C 5057906TSA048S4N (460V) TXV 48500 14 11.5 CH33-49 SL280UH090V60C 4075594TSA048S4N (460V) TXV 48500 14 11.5 CH33-49 SL280UH090XV60C 4235706TSA048S4N (460V) TXV 48500 14 11.5 CH33-49 SL280UH110V60C 4075595TSA048S4N (460V) TXV 48500 14 11.5 CH33-49 SL280UH110XV60C 4075672TSA048S4N (460V) TXV 48500 14 11.5 CH33-49 SLP98UH090XV48C 5139955TSA048S4N (460V) TXV 48500 13.5 11 CH33-49 SLP98UH090XV60C 5139956TSA048S4N (460V) TXV 48500 14 11.5 CH33-49 SLP98UH110XV60C 5139957TSA048S4N (460V) TXV 48000 14 11.5 CH33-50/60C EL180UH090E60C 5736234TSA048S4N (460V) TXV 48000 14 11.5 CH33-50/60C EL180UH110E60C 5738057TSA048S4N (460V) TXV 48000 14 11.5 CH33-50/60C EL180UH110XE60C 5739138TSA048S4N (460V) TXV 48000 14 11.5 CH33-50/60C EL195UH090XE48C 4699136TSA048S4N (460V) TXV 48000 14 11.5 CH33-50/60C EL195UH110XE60C 4699137TSA048S4N (460V) TXV 48000 14 11.5 CH33-50/60C EL296UH090XE48C 5647556TSA048S4N (460V) TXV 48000 13.5 11.5 CH33-50/60C EL296UH090XV48C 5057907TSA048S4N (460V) TXV 48000 13.5 11.5 CH33-50/60C EL296UH090XV60C 5057908TSA048S4N (460V) TXV 48000 14 11.5 CH33-50/60C EL296UH110XE60C 5647557TSA048S4N (460V) TXV 48500 13.5 11 CH33-50/60C EL296UH110XV60C 5057909TSA048S4N (460V) TXV 48500 14 11.5 CH33-50/60C SL280UH090V60C 4075596TSA048S4N (460V) TXV 48500 14 11.5 CH33-50/60C SL280UH090XV60C 4235707TSA048S4N (460V) TXV 48000 14 11.5 CH33-50/60C SL280UH110V60C 4075600TSA048S4N (460V) TXV 48000 14 11.5 CH33-50/60C SL280UH110XV60C 4075673TSA048S4N (460V) TXV 48000 13.5 11.5 CH33-50/60C SLP98UH090XV48C 5139958TSA048S4N (460V) TXV 48000 13.5 11.5 CH33-50/60C SLP98UH090XV60C 5139959TSA048S4N (460V) TXV 48500 13.5 11 CH33-50/60C SLP98UH110XV60C 5139960TSA048S4N (460V) TXV 48000 13.5 11 CH33-50/60C 1287359TSA048S4N (460V) TXV 48000 14 11.5 CH33-60D EL180UH135E60D 5756461TSA048S4N (460V) TXV 48000 13.5 11 CH33-60D EL195UH135XE60D 4699138TSA048S4N (460V) TXV 48000 13.5 11 CH33-60D EL296UH135XE60D 5647558TSA048S4N (460V) TXV 48000 14 11.5 CH33-60D EL296UH135XV60D 5057910TSA048S4N (460V) TXV 48000 14 11.5 CH33-60D SL280UH135V60D 4075601TSA048S4N (460V) TXV 48000 14 11.5 CH33-60D SLP98UH135XV60D 5139961TSA048S4N (460V) TXV 47500 13 11 CH33-60D 1287360TSA048S4N (460V) TXV 48500 14 11.5 CH33-62D EL180UH135E60D 5756462TSA048S4N (460V) TXV 48000 14 11.5 CH33-62D EL195UH135XE60D 4699139TSA048S4N (460V) TXV 48000 14 11.5 CH33-62D EL296UH090XV60C 8341562TSA048S4N (460V) TXV 47500 13.5 11.5 CH33-62D EL296UH110XV60C 8341563TSA048S4N (460V) TXV 48000 14 11.5 CH33-62D EL296UH135XE60D 5647560NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 42: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 42

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA048S4N (460V) TXV 48500 14 11.5 CH33-62D EL296UH135XV60D 5057911TSA048S4N (460V) TXV 48500 14 11.5 CH33-62D SL280UH135V60D 4075602TSA048S4N (460V) TXV 48500 14 11.5 CH33-62D SLP98UH135XV60D 5139962TSA048S4N (460V) TXV 48000 13.5 11 CH33-62D 1287361TSA048S4N (460V) TXV 47500 14 11.5 CR33-50/60 EL180DF110E60C 5733526TSA048S4N (460V) TXV 47000 14 11 CR33-50/60 EL195DF090XE48C 4699140TSA048S4N (460V) TXV 47000 14 11 CR33-50/60 EL195DF110XE60C 4699141TSA048S4N (460V) TXV 47000 14 11 CR33-50/60 EL296DF090XE48C 5647561TSA048S4N (460V) TXV 47000 13.5 11 CR33-50/60 EL296DF090XV60C 5057926TSA048S4N (460V) TXV 47000 14 11 CR33-50/60 EL296DF110XE60C 5647562TSA048S4N (460V) TXV 47000 13.5 11 CR33-50/60 EL296DF110XV60C 5057927TSA048S4N (460V) TXV 47500 14 11.5 CR33-50/60 SL280DF090V60C 4075603TSA048S4N (460V) TXV 47500 14 11.5 CR33-50/60 SL280DF110V60C 4075604TSA048S4N (460V) TXV 47000 13.5 11 CR33-50/60 SLP98DF090XV48C 5139977TSA048S4N (460V) TXV 47000 13.5 11 CR33-50/60 SLP98DF090XV60C 5139978TSA048S4N (460V) TXV 47000 13.5 11 CR33-50/60 SLP98DF110XV60C 5139979TSA048S4N (460V) TXV 47000 13 11 CR33-50/60 1287362TSA048S4N (460V) TXV 47500 13.5 11 CR33-60 EL296DF090XV60C 5057928TSA048S4N (460V) TXV 47500 13 11 CR33-60 EL296DF110XV60C 5057929TSA048S4N (460V) TXV 47500 13 11 CR33-60 SLP98DF090XV60C 5139980TSA048S4N (460V) TXV 47500 13 11 CR33-60 SLP98DF110XV60C 5139981TSA048S4N (460V) TXV 47500 13 11 CR33-60 1287363TSA048S4N (460V) TXV 48500 13 11 CX35-48B 10248776TSA048S4N (460V) TXV 48500 13 11 CX35-48C 10248777TSA048S4N (460V) TXV 49000 14 11.7 CX35-49C EL180UH090E60C 10248778TSA048S4N (460V) TXV 49000 14 11.7 CX35-49C EL180UH110E60C 10248779TSA048S4N (460V) TXV 49000 14 11.7 CX35-49C EL180UH110XE60C 10248780TSA048S4N (460V) TXV 49000 14 11.7 CX35-49C EL195UH110XE60C 10248781TSA048S4N (460V) TXV 49000 14 11.7 CX35-49C EL296UH110XE60C 10248782TSA048S4N (460V) TXV 49500 14 11.7 CX35-49C SL280UH090V60C 10248783TSA048S4N (460V) TXV 49500 14 11.7 CX35-49C SL280UH090XV60C 10248784TSA048S4N (460V) TXV 49500 14 11.7 CX35-49C SL280UH110V60C 10248785TSA048S4N (460V) TXV 49500 14 11.7 CX35-49C SL280UH110XV60C 10248786TSA048S4N (460V) TXV 49000 13 11 CX35-49C 10248787TSA048S4N (460V) TXV 47500 13 11 CX35-50/60C 10248788TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C EL180UH090E60C 10248789TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C EL180UH110E60C 10248790TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C EL180UH110XE60C 10248791TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C EL195UH090XE48C 10248792TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C EL195UH110XE60C 10248793TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C EL296UH090XE48C 10248794TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C EL296UH090XV48C 10248795TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C EL296UH090XV60C 10248796TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C EL296UH110XE60C 10248797TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C EL296UH110XV48C 10248798TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C EL296UH110XV60C 10248799TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C SL280UH090V60C 10248800TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C SL280UH090XV60C 10248801TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C SL280UH110V60C 10248802NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 43: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 43

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C SL280UH110XV60C 10248803TSA048S4N (460V) TXV 49500 14 11.7 CX35-60C SLP98UH090XV48C 10248804TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C SLP98UH090XV60C 10248805TSA048S4N (460V) TXV 50000 14 11.7 CX35-60C SLP98UH110XV60C 10248806TSA048S4N (460V) TXV 50000 13 11 CX35-60C 10248807TSA048S4N (460V) TXV 49500 14 11.7 CX35-60D EL180UH135E60D 10248808TSA048S4N (460V) TXV 49500 14 11.7 CX35-60D SL280UH135V60D 10248809TSA048S4N (460V) TXV 49000 14 11.7 CX35-60D SLP98UH135XV60D 10248810TSA048S4N (460V) TXV 49000 13 11 CX35-60D 10248811TSA048S4N (460V) TXV 49000 13.5 11 CX38-62C 10557482TSA060S4N (208/230V) TXV 57500 13 11 C35-49C 10248735TSA060S4N (208/230V) TXV 59000 13 11 C35-60C 10248736TSA060S4N (208/230V) TXV 58000 13 11 C35-60D 10248737TSA060S4N (208/230V) TXV 60000 13.5 11 CBX25UH-060 5945093TSA060S4N (208/230V) TXV 59000 13.5 11 CBX27UH-060 5754105TSA060S4N (208/230V) TXV 57000 13.5 11 CBX32M-048 1287159TSA060S4N (208/230V) TXV 58500 13 11 CBX32M-060 1287160TSA060S4N (208/230V) TXV 58500 13.5 11 CBX32MV-048 1287161TSA060S4N (208/230V) TXV 59000 13.5 11 CBX32MV-060 1287162TSA060S4N (208/230V) TXV 59000 13.5 11 CBX32MV-068 1399219TSA060S4N (208/230V) TXV 58500 13.5 11 CBX40UHV-048 3291780TSA060S4N (208/230V) TXV 59000 13.5 11 CBX40UHV-060 3291836TSA060S4N (208/230V) TXV 60000 13.5 11 CH23-68 EL180UH135E60D 5754106TSA060S4N (208/230V) TXV 60000 13.5 11.5 CH23-68 EL195UH135XE60D 4699049TSA060S4N (208/230V) TXV 60000 13.5 11.5 CH23-68 EL296UH135XE60D 5647450TSA060S4N (208/230V) TXV 60000 13.5 11.5 CH23-68 EL296UH135XV60D 5058034TSA060S4N (208/230V) TXV 60000 13.5 11 CH23-68 SL280UH135V60D 4075684TSA060S4N (208/230V) TXV 60000 13.5 11.5 CH23-68 SLP98UH135XV60D 5139982TSA060S4N (208/230V) TXV 59500 13.5 11 CH23-68 1287147TSA060S4N (208/230V) TXV 58500 13 11 CH33-50/60C EL180UH090E60C 5736255TSA060S4N (208/230V) TXV 58000 13 11 CH33-50/60C EL180UH110E60C 5738080TSA060S4N (208/230V) TXV 58000 13 11 CH33-50/60C EL180UH110XE60C 5739150TSA060S4N (208/230V) TXV 59500 13 11 CH33-50/60C EL195UH110XE60C 4699050TSA060S4N (208/230V) TXV 58500 13 11 CH33-50/60C EL296UH090XV60C 5058035TSA060S4N (208/230V) TXV 59500 13 11 CH33-50/60C EL296UH110XE60C 5647451TSA060S4N (208/230V) TXV 58500 13 11 CH33-50/60C EL296UH110XV60C 5058036TSA060S4N (208/230V) TXV 59000 13 11 CH33-50/60C SL280UH090V60C 4075685TSA060S4N (208/230V) TXV 59000 13 11 CH33-50/60C SL280UH090XV60C 4235713TSA060S4N (208/230V) TXV 58500 13 11 CH33-50/60C SL280UH110V60C 4075686TSA060S4N (208/230V) TXV 58500 13 11 CH33-50/60C SL280UH110XV60C 4075718TSA060S4N (208/230V) TXV 58500 13 11 CH33-50/60C SLP98UH090XV60C 5139983TSA060S4N (208/230V) TXV 58500 13 11 CH33-50/60C SLP98UH110XV60C 5139984TSA060S4N (208/230V) TXV 59000 13 11 CH33-50/60C 1287148TSA060S4N (208/230V) TXV 58500 13 11 CH33-60D EL180UH135E60D 5754107TSA060S4N (208/230V) TXV 58500 13 11 CH33-60D EL195UH135XE60D 4699051TSA060S4N (208/230V) TXV 58500 13 11 CH33-60D EL296UH135XE60D 5647452TSA060S4N (208/230V) TXV 58500 13.5 11 CH33-60D EL296UH135XV60D 5058037TSA060S4N (208/230V) TXV 58500 13 11 CH33-60D SL280UH135V60D 4075687TSA060S4N (208/230V) TXV 58500 13.5 11 CH33-60D SLP98UH135XV60D 5139985NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 44: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 44

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA060S4N (208/230V) TXV 58500 13 11 CH33-60D 1287149TSA060S4N (208/230V) TXV 59000 13 11 CH33-62D EL180UH135E60D 5754108TSA060S4N (208/230V) TXV 59000 13 11 CH33-62D EL195UH135XE60D 4699052TSA060S4N (208/230V) TXV 58500 13 11 CH33-62D EL296UH090XV60C 8341568TSA060S4N (208/230V) TXV 58500 13.5 11 CH33-62D EL296UH110XV60C 8341569TSA060S4N (208/230V) TXV 59000 13 11 CH33-62D EL296UH135XE60D 5647453TSA060S4N (208/230V) TXV 59000 13.5 11 CH33-62D EL296UH135XV60D 5058038TSA060S4N (208/230V) TXV 59000 13 11 CH33-62D SL280UH135V60D 4075688TSA060S4N (208/230V) TXV 59000 13.5 11 CH33-62D SLP98UH135XV60D 5139986TSA060S4N (208/230V) TXV 58500 13 11 CH33-62D 1287150TSA060S4N (208/230V) TXV 57500 13 11 CR33-60 1287151TSA060S4N (208/230V) TXV 57500 13 11 CX35-49C 10250478TSA060S4N (208/230V) TXV 59000 13 11 CX35-60C 10248738TSA060S4N (208/230V) TXV 58000 13 11 CX35-60D 10248739TSA060S4N (208/230V) TXV 59000 13 11 CX38-49C 10557729TSA060S4N (460V) TXV 57500 13 11 C35-49C 10248730TSA060S4N (460V) TXV 59000 13 11 C35-60C 10248731TSA060S4N (460V) TXV 58000 13 11 C35-60D 10248732TSA060S4N (460V) TXV 60000 13.5 11 CBX25UH-060 5945092TSA060S4N (460V) TXV 59000 13.5 11 CBX27UH-060 5746283TSA060S4N (460V) TXV 59000 13.5 11 CBX27UH-060-460 7621706TSA060S4N (460V) TXV 57000 13.5 11 CBX32M-048 1287467TSA060S4N (460V) TXV 58500 13 11 CBX32M-060 1287468TSA060S4N (460V) TXV 58500 13.5 11 CBX32MV-048 1287469TSA060S4N (460V) TXV 59000 13.5 11 CBX32MV-060 1287470TSA060S4N (460V) TXV 59000 13.5 11 CBX32MV-068 1399220TSA060S4N (460V) TXV 58500 13.5 11 CBX40UHV-048 3291779TSA060S4N (460V) TXV 59000 13.5 11 CBX40UHV-060 3291835TSA060S4N (460V) TXV 60000 13.5 11 CH23-68 EL180UH135E60D 5746284TSA060S4N (460V) TXV 60000 13.5 11.5 CH23-68 EL195UH135XE60D 4699152TSA060S4N (460V) TXV 60000 13.5 11.5 CH23-68 EL296UH135XE60D 5647573TSA060S4N (460V) TXV 60000 13.5 11.5 CH23-68 EL296UH135XV60D 5058017TSA060S4N (460V) TXV 60000 13.5 11 CH23-68 SL280UH135V60D 4075723TSA060S4N (460V) TXV 60000 13.5 11.5 CH23-68 SLP98UH135XV60D 5139999TSA060S4N (460V) TXV 59500 13.5 11 CH23-68 1287455TSA060S4N (460V) TXV 58500 13 11 CH33-50/60C EL180UH090E60C 5736265TSA060S4N (460V) TXV 58000 13 11 CH33-50/60C EL180UH110E60C 5738090TSA060S4N (460V) TXV 58000 13 11 CH33-50/60C EL180UH110XE60C 5739159TSA060S4N (460V) TXV 59500 13 11 CH33-50/60C EL195UH110XE60C 4699153TSA060S4N (460V) TXV 58500 13 11 CH33-50/60C EL296UH090XV60C 5058018TSA060S4N (460V) TXV 59500 13 11 CH33-50/60C EL296UH110XE60C 5647574TSA060S4N (460V) TXV 58500 13 11 CH33-50/60C EL296UH110XV60C 5058019TSA060S4N (460V) TXV 59000 13 11 CH33-50/60C SL280UH090V60C 4075724TSA060S4N (460V) TXV 59000 13 11 CH33-50/60C SL280UH090XV60C 4235718TSA060S4N (460V) TXV 58500 13 11 CH33-50/60C SL280UH110V60C 4075725TSA060S4N (460V) TXV 58500 13 11 CH33-50/60C SL280UH110XV60C 4075757TSA060S4N (460V) TXV 58500 13 11 CH33-50/60C SLP98UH090XV60C 5140000TSA060S4N (460V) TXV 58500 13 11 CH33-50/60C SLP98UH110XV60C 5140001TSA060S4N (460V) TXV 59000 13 11 CH33-50/60C 1287456NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 45: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 45

AHRI SYSTEM MATCHESNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

TSA060S4N (460V) TXV 58500 13 11 CH33-60D EL180UH135E60D 5746285TSA060S4N (460V) TXV 58500 13 11 CH33-60D EL195UH135XE60D 4699154TSA060S4N (460V) TXV 58500 13 11 CH33-60D EL296UH135XE60D 5647602TSA060S4N (460V) TXV 58500 13.5 11 CH33-60D EL296UH135XV60D 5058020TSA060S4N (460V) TXV 58500 13 11 CH33-60D SL280UH135V60D 4075726TSA060S4N (460V) TXV 58500 13.5 11 CH33-60D SLP98UH135XV60D 5140002TSA060S4N (460V) TXV 58500 13 11 CH33-60D 1287457TSA060S4N (460V) TXV 59000 13 11 CH33-62D EL180UH135E60D 5746286TSA060S4N (460V) TXV 59000 13 11 CH33-62D EL195UH135XE60D 4699155TSA060S4N (460V) TXV 58500 13 11 CH33-62D EL296UH090XV60C 8341566TSA060S4N (460V) TXV 58500 13.5 11 CH33-62D EL296UH110XV60C 8341567TSA060S4N (460V) TXV 59000 13 11 CH33-62D EL296UH135XE60D 5647603TSA060S4N (460V) TXV 59000 13.5 11 CH33-62D EL296UH135XV60D 5058021TSA060S4N (460V) TXV 59000 13 11 CH33-62D SL280UH135V60D 4075727TSA060S4N (460V) TXV 59000 13.5 11 CH33-62D SLP98UH135XV60D 5140003TSA060S4N (460V) TXV 58500 13 11 CH33-62D 1287458TSA060S4N (460V) TXV 57500 13 11 CR33-60 1287459TSA060S4N (460V) TXV 57500 13 11 CX35-49C 10250477TSA060S4N (460V) TXV 59000 13 11 CX35-60C 10248733TSA060S4N (460V) TXV 58000 13 11 CX35-60D 10248734TSA060S4N (460V) TXV 59000 13 11 CX38-49C 10557688TSA060S4N (575V) TXV 58500 13 11 CBX32M-060 8935137NOTES: TXV = Matched with Thermostatic Expansion Valve.Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 46: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 46

AHRI SYSTEM MATCHES - MULTIPLE OUTDOOR UNITSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

(2) TSA048S4N (208/230V) TXV 92,000 11.60 11.40 TAA090S4D 5178752(2) TSA048S4N (460V) TXV 92,000 11.60 11.40 TAA090S4D 5178753Ratings are AHRI certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 47: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox
Page 48: TS 3-5 TON STANDARD EFFICIENCY AIR …TS - 3 to 5 Ton Standard-Efficiency R-410A Air Conditioners / Page 3 FEATURES REFRIGERATION SYSTEM (continued) Copper Tube/Enhanced Fin Coil Lennox

NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2017 Lennox Industries, Inc.

REVISIONS

Sections Description of Change

AHRI System Matches Updated

Visit us at www.lennox.com

For the latest technical information, www.lennoxcommercial.com

Contact us at 1-800-4-LENNOX

REVISIONS