tsdos phasor transformer
TRANSCRIPT
-
8/15/2019 TSDOS Phasor Transformer
1/248
Phasor, Transformer, andTransmission Lines
Wei-Jen Lee, Ph.D., P.E.Professor and Director
Energy Systems Research Center
The University of Texas at Arlington
1
Text Book: J. Duncan Glover, Mulukutla S. Sarma, and Thomas J.
Overbye, “Power Systems Analysis and Design”, Fifth Edition.Cengage Learning
-
8/15/2019 TSDOS Phasor Transformer
2/248
Introduction
2
-
8/15/2019 TSDOS Phasor Transformer
3/248
A Typical Power System
3
-
8/15/2019 TSDOS Phasor Transformer
4/248
Components of a Modern Power
System
• Every power system has four major
components
– Generation facilities
– Power delivery system
–Loads
– Monitoring, protection, and control system
4
-
8/15/2019 TSDOS Phasor Transformer
5/248
Challenges of Power System
Operation
• Every Generation facility has its own limit.
• Some generation facilities are difficult tocontrol.
• Delivery systems also have limitations.
• Loads are seldom constant
• Since the power systems are dynamic innature, it is difficult, if not impossible, to
maintain optimal conditions of a power
system.
5
-
8/15/2019 TSDOS Phasor Transformer
6/248
Notation - Power
• Power: Instantaneous consumption of energy
• Power Units Watts – voltage x current for dc (W) kW – 1 x 103 Watt MW – 1 x 106 Watt GW – 1 x 109 Watt
• Installed U.S. generation capacity is about900 GW ( about 3 kW per person)
• Installed generation capacity in the ERCOT is
around 95GW (Including 10GW wind
generation)6
-
8/15/2019 TSDOS Phasor Transformer
7/248
-
8/15/2019 TSDOS Phasor Transformer
8/248
Power System Examples
• North American Interconnected System
8
-
8/15/2019 TSDOS Phasor Transformer
9/248
Power System Examples
• North American Interconnected System
9
-
8/15/2019 TSDOS Phasor Transformer
10/248
Power System Examples
• MicroGrid (Isolated power system)
• Intentional islanding operation of a power system(Military campus, remote villages, and etc)
• Airplanes and Spaceships
• Ships and submarines
• Automobiles: dc with 12 volts standard• Battery operated portable systems
10
-
8/15/2019 TSDOS Phasor Transformer
11/248
AC versus DC Power System
• With the flip of a switch at 3 p.m. on Sept. 4,
1882 at Pearl Station, Thomas Edisonushered in the age of commercial electrical
power systems.
• It was a DC MicroGrid and served 240
customers within one square miles.• Tesla's patents and theoretical work formed
the basis of modern alternating current
electric power (AC) systems.11
-
8/15/2019 TSDOS Phasor Transformer
12/248
Concept of Phasor
• Since it is relative easy to change the voltage
level, majority of the power systems are ACsystem (either 50Hz or 60Hz).
• Since the relationship of the AC system is
based upon the phase difference between
two quantities, this evolves the concept of phasor.
• Goal of phasor analysis is to simplify the
analysis of constant frequency AC systems. 12
-
8/15/2019 TSDOS Phasor Transformer
13/248
Instantaneous and RMS Values
• The voltage and current of an AC system can
be expressed as:
• The DC equivalent of an AC sinusoidal signal
is shown below: (RMS value)
)cos(*)(
)cos(*)(
max
max
i
v
t I t i
t V t v
2
)(1
|| max
0
2 V dt t v
T
V V
T
RMS
13
-
8/15/2019 TSDOS Phasor Transformer
14/248
Phasor Representation
• Euler’s Identity:
• Phasor notation is developed by rewriting theEuler’s Identity:
sincos jej
]Re[||2)(
)cos(||2)(
)( vt j
v
eV t v
t V t v
14
-
8/15/2019 TSDOS Phasor Transformer
15/248
Phasor Representation
• The RMS cosine-reference voltage and
current phasors are:
i
j
v
j
I e I I
V eV V
i
v
||||
||||
15
-
8/15/2019 TSDOS Phasor Transformer
16/248
V/I Relationships of R, L, and C
16
-
8/15/2019 TSDOS Phasor Transformer
17/248
Advantages of Phasor Analysis
0
2 2
Resistor ( ) ( )
( )Inductor ( )
1 1Capacitor ( ) (0)
C
Z = Impedance
R = Resistance
X = Reactance
XZ = =arctan( )
t
v t Ri t V RI
di t v t L V j LI
dt
i t dt v V I j C
R jX Z
R X R
Device Time Analysis Phasor
17
-
8/15/2019 TSDOS Phasor Transformer
18/248
Complex Power
max
max
max max
( ) ( ) ( )
v(t) = cos( )
(t) = cos( )
1
cos cos [cos( ) cos( )]2
1( ) [cos( )
2
cos(2 )]
V
I
V I
V I
p t v t i t
V t
i I t
p t V I
t
Power
18
-
8/15/2019 TSDOS Phasor Transformer
19/248
Complex Power
max max
0
max max
1
( ) [cos( ) cos(2 )]2
1( )
1 cos( )2
cos( )
= =
V I V I
T
avg
V I
V I
V I
p t V I t
P p t dt T
V I
V I
Power Factor
Average P
Angle
ower
19
-
8/15/2019 TSDOS Phasor Transformer
20/248
Complex Power
*
cos( ) sin( )
P = Real Power (W, kW, MW)
Q = Reactive Power (var, kvar, Mvar)
S = Complex power (VA, kVA, MVA)
Power Factor (pf) = cos
If current leads voltage then pf is leading
If current
V I V I
V I
S V I j
P jQ
lags voltage then pf is lagging
For simplicity, we will use V and I as RMSvalues of voltage and current
20
-
8/15/2019 TSDOS Phasor Transformer
21/248
Example
• Instantaneous, real, and reactive power; power
factor.• The voltage v(t)=141.4*cos(t) is applied to a load consisting of a 10-W resistor in parallel with an inductive reactance XL =L =3.77 W. Calculate the instantaneous power absorbed by theresistor and by the inductor. Also calculate the real and reactive
power absorbed by the load, and the power factor
21
-
8/15/2019 TSDOS Phasor Transformer
22/248
Example
• Instantaneous, real, and reactive power; power
factor.• The V/I relationship of resistor
22
-
8/15/2019 TSDOS Phasor Transformer
23/248
Example
• Instantaneous, real, and reactive power; power
factor.• The V/I relationship of inductor
23
-
8/15/2019 TSDOS Phasor Transformer
24/248
Example
• Instantaneous, real, and reactive power; power
factor.• The load voltage is
• The resistor current is
• The inductor current is
• The total load current is• The Instantaneous power absorbed by the resistor is
24
-
8/15/2019 TSDOS Phasor Transformer
25/248
Example
• Instantaneous, real, and reactive power; power
factor.
• The Instantaneous power absorbed by the inductor
is
• The real power absorbed by load is
• The reactive power absorbed by load is
• The power factor is25
-
8/15/2019 TSDOS Phasor Transformer
26/248
Example
• Power triangle and power factor correction
• A single-phase source delivers 100 kW to a loadoperating at a power factor of 0.8 lagging. Calculate
the reactive power to be delivered by a capacitor
connected in parallel with the load in order to raise
the source power factor to 0.95 lagging.
26
-
8/15/2019 TSDOS Phasor Transformer
27/248
Example
• Power triangle and power factor correction
•Before compensation
• After compensation
27
-
8/15/2019 TSDOS Phasor Transformer
28/248
-
8/15/2019 TSDOS Phasor Transformer
29/248
RMS and Instantaneous values
• When voltages and currents are discussed in
this text, lowercase letters such as v(t) and
i(t) indicate instantaneous values, uppercase
letters such as V and I indicate rms values,
and uppercase letters in italics such as V and
I indicate rms phasors. When voltage or current values are specified, they shall be
rms values unless otherwise indicated.
29
-
8/15/2019 TSDOS Phasor Transformer
30/248
Single-Phase and Three-Phase
Power System
• Single-phase power system
• Single-phase-three wire system• Three-phase system
30
-
8/15/2019 TSDOS Phasor Transformer
31/248
Advantages of Three-Phase Power
System
• More power per kilogram of metal from a
three-phase machine.
• Power delivered to a balanced three-phase
load is constant at all time, instead of pulsing
as it does in a single-phase system.
• More power can be delivered.• Total line losses are reduced.
31
-
8/15/2019 TSDOS Phasor Transformer
32/248
Three-Phase Power System
• A three-phase generator consists of three
single-phase generators with voltages of
equal amplitudes and phase differences of
1200.
32
-
8/15/2019 TSDOS Phasor Transformer
33/248
Balanced Three-Phase Power
System
• We can used three
single-phase system
differing in phase angle
by 1200 to represent a
balanced three-phase
system.• The current flowing to
each load can be found
as V I
Z
33
-
8/15/2019 TSDOS Phasor Transformer
34/248
Balanced Three-Phase Power
System
• Therefore, the currents flowing in each
phase are.0
0
0
0
120120
240240
A
B
A
V I I
Z
V I I
Z
V I I
Z
34
-
8/15/2019 TSDOS Phasor Transformer
35/248
Balanced Three-Phase Power
System
• We will form a three-phase circuit by
connecting the return path of three-single
phase load together.
35
-
8/15/2019 TSDOS Phasor Transformer
36/248
Balanced Three-Phase Power
System
• The current flows through the neutral
conductor is equal to zero.
0)240()120( ooC B A N
I I I I I I I
36
-
8/15/2019 TSDOS Phasor Transformer
37/248
D and Y Connection of Three-Phase Power System
• There are two types of connections in
three-phase circuits: Y and D.
37
-
8/15/2019 TSDOS Phasor Transformer
38/248
D and Y Connection of Three-Phase Power System
• General Relations Between Circuit
Quantities.
3
2
3
3
3
2
3
3033*303
303
3
30
3
30
303*
3
30
S
V
S
V V
I
V
I
V Z
V
S
Z
V I I
Connection
S
V
S
V V
I
V Z
ConnectionY
o
LL LLo
LL
L
o
LL LL
LL
o
LL
o
L
o
LL LL
o
LL
L
LN
Y
D
D
D
D
D
38
-
8/15/2019 TSDOS Phasor Transformer
39/248
D and Y Connection of Three-Phase Power System
• Phase quantity: voltages and currents in a
given phase.
• Line quantity: voltages between the lines
and currents in the lines connected to the
generators or loads.
39
-
8/15/2019 TSDOS Phasor Transformer
40/248
Power of a Balanced Three-Phase
Power System
• For a balanced Y-connected load with the
impedance Z
= Z 0 :
0
0
( ) 2 sin
( ) 2 sin( 120 )
( ) 2 sin( 240 )
an
bn
cn
v t V t
v t V t
v t V t
0
0
( ) 2 sin( )
( ) 2 sin( 120 )
( ) 2 sin( 240 )
a
b
c
i t I t
i t I t
i t I t
40
-
8/15/2019 TSDOS Phasor Transformer
41/248
Power of a Balanced Three-Phase
Power System
• The instantaneous power is:
• The total power on the load is
0
0
( ) cos cos(2 )( ) cos cos(2 240 )
( ) cos cos(2 480 )
a
b
c
p t VI t p t VI t
p t VI t
cos3)()()()( VI t P t P t P t P cbatotal
41
-
8/15/2019 TSDOS Phasor Transformer
42/248
Power Relationship
• Phase quantities in each phase of a Y- or
D-connection: – Real Power:
– Reactive Power:
– Apparent Power:
23 cos 3 cos P V I I Z
23 sin 3 sinQ V I I Z
23 3S V I I Z
42
-
8/15/2019 TSDOS Phasor Transformer
43/248
Power Relationship
• Line quantities of a Y-connection load:
– Power consumed by a load:
– Relationship between line quantities and
phase quantities:
– Power:
3 cos P V I
3 L LL
I I and V V
3 cos LL L P V I
43
-
8/15/2019 TSDOS Phasor Transformer
44/248
One-Line Diagram and D-YConversion
44
-
8/15/2019 TSDOS Phasor Transformer
45/248
Power Transformer
45
-
8/15/2019 TSDOS Phasor Transformer
46/248
Ideal Transformer
• For an ideal transformer, the following are
assumed:
• The windings have zero resistance; therefore,
the I2R losses in the windings are zero.
• The core permeability mc is infinite, whichcorresponds to zero core reluctance.
• There is no leakage flux; that is, the entire flux
Fc is confined to the core and links bothwindings.
• There are no core losses. 46
-
8/15/2019 TSDOS Phasor Transformer
47/248
Ideal Transformer
• For an ideal transformer, whatever goes
in should come out:
47
-
8/15/2019 TSDOS Phasor Transformer
48/248
Ideal Transformer
• For an ideal transformer, whatever goes
in should come out:
48
-
8/15/2019 TSDOS Phasor Transformer
49/248
Example of an Ideal Transformer
• A single-phase two-winding transformer is
rated 20 kVA, 480/120 V, 60 Hz. A source
connected to the 480-V winding supplies
an impedance load connected to the 120-
V winding. The load absorbs 15 kVA at
0.8 pf lagging when the load voltage is118V:
49
-
8/15/2019 TSDOS Phasor Transformer
50/248
Example of an Ideal Transformer
50
-
8/15/2019 TSDOS Phasor Transformer
51/248
Example of an Ideal Transformer
• Solution:
• The complex power at load is
• The load current is
• The load impedance is
• The load impedance referred to the 480-V
winding is
51
-
8/15/2019 TSDOS Phasor Transformer
52/248
Equivalent Circuit of a Practical
Transformer
• A practical transformer :
The windings have resistance.
The core permeability mc is finite.
The magnetic flux is not entirely confined to the core.
There are real and reactive power losses in the core.
52
-
8/15/2019 TSDOS Phasor Transformer
53/248
-
8/15/2019 TSDOS Phasor Transformer
54/248
-
8/15/2019 TSDOS Phasor Transformer
55/248
Finding Parameters of a Practical
Single Phase Transformer
• Let’s use an example to illustrate the process. A single-phase two-winding transformer is rated 20
kVA, 480/120 volts, 60 Hz.
Short-circuit test: Rated current at rated frequency is
applied to the 480-volt winding with the 120-volt
winding shorted.
Test Results: V1 =35 volts, P1 =300 W
Open-circuit test: Rated voltage is applied to 120V,
with 480V terminal open.
Test Results: I2 =12 A, P2 =200 W
55
-
8/15/2019 TSDOS Phasor Transformer
56/248
Finding Parameters of a Practical
Single Phase Transformer
• Short-circuit test:
56
-
8/15/2019 TSDOS Phasor Transformer
57/248
Finding Parameters of a Practical
Single Phase Transformer
• Open-circuit test:
57
-
8/15/2019 TSDOS Phasor Transformer
58/248
Finding Parameters of a Practical
Single Phase Transformer
• Discussion
• Allocate the impedance of primary and secondary
windings.
• In general, you can divide Xeq equally for equivalent
reactance of primary and secondary windings.
• Perform DC resistance testing to establish the equivalent
DC resistance ratio between primary and secondarywindings and allocate the Req accordingly.
58
-
8/15/2019 TSDOS Phasor Transformer
59/248
Polarity of the Transformer
59
-
8/15/2019 TSDOS Phasor Transformer
60/248
Per Unit System
•Quantity in per unit =
• Quantity in percent = (Quantity in per
unit)*100
Quantityof Value Base
Quantity Actual
60
-
8/15/2019 TSDOS Phasor Transformer
61/248
Advantages
• More meaningful when comparing differentvoltage levels
• The per unit equivalent impedance of thetransformer remains the same when referredto either the primary or the secondary side
• The per unit impedance of a transformer in athree-phase system is the same, regardlessthe winding connection
• The per unit method is independent of voltage changes and phase shifts throughtransformers61
-
8/15/2019 TSDOS Phasor Transformer
62/248
-
8/15/2019 TSDOS Phasor Transformer
63/248
Selection of the Base
• VA, V, I, and Z are four power quantities
•One has to select two base quantities andderive the other two.
• Usually the base voltage VbaseLN and base
complex power Sbase1 are selected for either
a single-phase circuit or for one phase of athree-phase circuit.
• The per-unit values for current and
impedance can then be derived.63
-
8/15/2019 TSDOS Phasor Transformer
64/248
Selection of the Base
64
-
8/15/2019 TSDOS Phasor Transformer
65/248
Per Unit Representation of a
Transformer
• A single-phase two-winding transformer is
rated 20 kVA, 480/120 volts, 60 Hz.
• The equivalent leakage impedance of the
transformer referred to the 120-volt winding,
denoted winding 2, is Zeq2=0.0525/78.13oW.
Using the transformer ratings as basevalues, determine the per-unit leakage
impedance referred to winding 2 and referred
to winding 1.
65
-
8/15/2019 TSDOS Phasor Transformer
66/248
Per Unit Representation of a
Transformer
• Solution
• The values of Sbase, Vbase1, and Vbase2 are from the
transformer ratings
• The base impedance on the 120-volt side of the
transformer is
• The per-unit leakage impedance referred to
winding 2 is
66
-
8/15/2019 TSDOS Phasor Transformer
67/248
Per Unit Representation of a
Transformer
• Solution
• If Zeq2 is referred to winding 1
• The base impedance on the 480-volt side of the
transformer is
• The per-unit leakage reactance referred to
winding 1 is
67
-
8/15/2019 TSDOS Phasor Transformer
68/248
Per Unit Representation of a
Transformer
The per-unit leakage impedance remains
unchanged when referred from winding 2 to
winding 1.
Form the per unit point of view transformer
voltage ratio is 1:1 (Rated to rated)
68
-
8/15/2019 TSDOS Phasor Transformer
69/248
Base Conversion
• To convert a per-unit impedance from ‘‘old’’to ‘‘new’’ base values, use.
or
69
-
8/15/2019 TSDOS Phasor Transformer
70/248
Example One: Base Conversion
• A 50-MVA, 34.5:161 kV transformer with
10% reactance is connected to a power
system where all the other impedance values
are on a 100 MVA, 34.5 or 161 kV base. The
reactance of the transformer under new base
is:
2.0*50
100*1.0
2
)(
2
)(
)(
newbase
old base
new pu KV
KV Z
70
-
8/15/2019 TSDOS Phasor Transformer
71/248
Example Two: Base Conversion
• A generator and transformer, as shown
below, are to be combined into a single
equivalent reactance on a 100 MVA, 110 kV
(high voltage side) base.
71
-
8/15/2019 TSDOS Phasor Transformer
72/248
Example Two: Base Conversion
• The transformer is operated at 3.9 kV tap.
• New base voltage at high side is 110 kV.
• The base voltage at low side is:
110*3.9/115 = 3.73 kV
514.1364.015.1
364.073.3
9.3*
30
100*1.0
15.173.3
4
*25
100
*25.0
)()(
2
2
)(
2
2
)(
new Xfer new geneq
new Xfer
new gen
Z Z Z
Z
Z
72
-
8/15/2019 TSDOS Phasor Transformer
73/248
Three Phase Transformer
• The American standard for marking three-
phase transformers substitutes H1, H2, and H3
on the high-voltage terminals and X1, X2, and
X3 on the low-voltage terminals in place of the
polarity dots.
• The ANSI/IEEE standard for transformersstates that the high voltage should lead the low
voltage by 30o with Y-D or D-Y banks.
73
-
8/15/2019 TSDOS Phasor Transformer
74/248
Three Phase Transformer
• There are nine possible configurations for
three-phase transformer.
• No Phase Shift: Y – Y, YG – Y, Y – YG, YG – YG, andD – D.
• With Phase Shift: D – Y, D – YG, Y – D, and YG – D.
• When describing the configuration of atransformer, it is typical to mention the
configuration of windings closer to the source
first.
74
-
8/15/2019 TSDOS Phasor Transformer
75/248
Three Phase Transformer
• Schematic representation of a YG – YG three-phase transformer.
75
-
8/15/2019 TSDOS Phasor Transformer
76/248
Three Phase Transformer
• Schematic representation of a YG – D three-phase transformer.
76
-
8/15/2019 TSDOS Phasor Transformer
77/248
Three Phase Transformer
• Per unit equivalent circuit of three-phase
transformers.
77
-
8/15/2019 TSDOS Phasor Transformer
78/248
Three-Winding Transformer
• Three-winding transformers are connected to
one source and two loads.
78
-
8/15/2019 TSDOS Phasor Transformer
79/248
Three-Winding Transformer
• Z12: per-unit leakage impedance measured
from winding 1; with winding 2 shorted and
winding 3 open
• Z13: per-unit leakage impedance measured
from winding 1; with winding 3 shorted and
winding 2 open• Z23: per-unit leakage impedance measured
from winding 2; with winding 3 shorted and
winding 1 open79
-
8/15/2019 TSDOS Phasor Transformer
80/248
Three-Winding Transformer
• We can be used to evaluate the per-unit series
impedances Z1, Z2, and Z3 of the three-winding
transformer equivalent circuit from the per-unitleakage impedances Z12, Z13, and Z23.
Z12 = Z1 + Z2
Z13 = Z1 + Z3 Z23 = Z2 + Z3
Z1 = (Z12 + Z13 - Z23)/2
Z2 = (Z12 + Z23 – Z13)/2
Z3 = (Z13 + Z23 – Z12)/280
-
8/15/2019 TSDOS Phasor Transformer
81/248
Per Unit Impedance of a Single-
Phase Three-Winding Transformer
• The ratings of a single-phase three-winding
transformer are: winding 1: 300 MVA; 13:8 kV winding 2: 300 MVA; 199:2 kV
winding 3: 50 MVA; 19:92 kV
• The leakage reactances, from short-circuit
tests, are: X12: 0.10 per unit on a 300-MVA; 13:8-kV base
X13: 0.16 per unit on a 50-MVA; 13:8-kV base
X23: 0.14 per unit on a 50-MVA; 199:2-kV base
81
-
8/15/2019 TSDOS Phasor Transformer
82/248
Per Unit Impedance of a Single-
Phase Three-Winding Transformer
• Winding resistances and exciting current are
neglected.
• Calculate the impedances of the per-unit
equivalent circuit using a base of 300 MVA and
13.8 kV for terminal 1
82
-
8/15/2019 TSDOS Phasor Transformer
83/248
Per Unit Impedance of a Single-
Phase Three-Winding Transformer
• Solution
• Sbase = 300 MVA is the same for all three terminals.
• The specified voltage base for terminal 1 is Vbase1 =
13:8 kV.
• The base voltages for terminals 2 and 3 are then
Vbase2 = 199:2 kV and Vbase3 = 19:92 kV.
• Base Conversion
83
-
8/15/2019 TSDOS Phasor Transformer
84/248
Per Unit Impedance of a Single-
Phase Three-Winding Transformer
• Solution
84
-
8/15/2019 TSDOS Phasor Transformer
85/248
Autotransformer
85
-
8/15/2019 TSDOS Phasor Transformer
86/248
Autotransformer
• Pros and Cons of autotransformer
• Pros
• The autotransformer has smaller per-unit leakage
• impedances than the usual transformer; this results in both
smaller series voltage drops.
• The autotransformer also has lower per-unit losses (higher
efficiency), lower exciting current, and lower cost if the turns
ratio is not too large.
• Cons
• The electrical connection of the windings allows transient
overvoltages to pass through the autotransformer more
easily.86
-
8/15/2019 TSDOS Phasor Transformer
87/248
Autotransformer
• Example
A single-phase two-winding 20-kVA, 480/120-volt
transformer of is connected as a 120V/600Vautotransformer. Determine (a) the kVA rating, and
(c) the per-unit leakage impedance (The original
leakage impedance of the transformer is )
87
-
8/15/2019 TSDOS Phasor Transformer
88/248
Autotransformer
• Solution
As a normal two-winding transformer rated 20 kVA,
the rated current of the 480-volt winding is I2 = IH =20000/480 = 41.667 A. As an autotransformer, the
480-volt winding can carry the same current.
Therefore, the kVA rating SH = EHIH = 600*41.667 =
25 kVA.
88
-
8/15/2019 TSDOS Phasor Transformer
89/248
Autotransformer
• Solution
As an autotransformer, the leakage impedance in
ohms is the same as for the normal transformer,since the core and windings are the same for both.
However, the base impedances are different.
Therefore
89
-
8/15/2019 TSDOS Phasor Transformer
90/248
-
8/15/2019 TSDOS Phasor Transformer
91/248
Transformer with Off-Nominal TurnRatio
• For a transformer that V1rated and V2rated satisfy
V1rated = at*V2rated
• The selected voltage bases satisfy Vbase1 =
b*Vbase2. Define c = at/b.
• Then it can be represented as two transformers
in series.
91
-
8/15/2019 TSDOS Phasor Transformer
92/248
Transformer with Off-Nominal TurnRatio
• The per unit model of the transformer
• Set up equations for two-port circuit
92
-
8/15/2019 TSDOS Phasor Transformer
93/248
Transformer with Off-Nominal TurnRatio
• Where
93
-
8/15/2019 TSDOS Phasor Transformer
94/248
Transformer with Off-Nominal TurnRatio
• p circuit representation for real c.
94
-
8/15/2019 TSDOS Phasor Transformer
95/248
Transmission System
95
-
8/15/2019 TSDOS Phasor Transformer
96/248
Transmission System
• Transmission line design consideration
An overhead transmission line consists of
conductors, insulators, support structures, and, inmost cases, shield wires.
Other factors of consideration: Electrical,
Mechanical, Environmental, and Economic
96
-
8/15/2019 TSDOS Phasor Transformer
97/248
Conductors
• Conventional Conductors
ACSR (Aluminum conductor steel reinforced) has
been in service for more than 80 years.
In the last 15 to 20 years, the AAAC
(homogeneous all-aluminum alloy conductor) has
become quite popular, especially for National Grid
in the UK where it is now the standard conductor type employed for new and refurbished lines.
97
-
8/15/2019 TSDOS Phasor Transformer
98/248
Conductors
• High Temperature Conductors
• Research in Japan in the 1960s produced a
series of aluminum-zirconium alloys that resistedthe annealing effects of high temperatures.
• These alloys can retain their strength at
temperatures up to 230 C
• The most common of these alloys—TA1, ZTA1and XTA1—are the basis of a variety of hightemperature conductors.
98
-
8/15/2019 TSDOS Phasor Transformer
99/248
Conductors
• Emerging Conductor Technologies
ACFR: Aluminum conductor carbon fiber
reinforced from Japan makes use of the very-lowexpansion coefficient of carbon fiber.
ACCR: Aluminum Conductor Composite
Reinforced from 3M.
Also in the United States, two more designsbased on glass-fiber composites are emerging.
Aluminum conductor composite core (ACCC),
Composite reinforced aluminum conductor (CRAC).
Aluminum Conductor Steel Supported (ACSS)99
-
8/15/2019 TSDOS Phasor Transformer
100/248
Insulator
• Insulators for transmission lines above 69 kV
are typically suspension-type Insulators.
100
-
8/15/2019 TSDOS Phasor Transformer
101/248
Support Structures
• Transmission lines employ a variety of
support structures.
101
-
8/15/2019 TSDOS Phasor Transformer
102/248
Shield Wires
• Shield wires located above the phase
conductors protect the phase conductors
against lightning.
• They are usually high- or extra-high-strength
steel, Alumoweld, or ACSR with much
smaller cross section than the phaseconductors.
102
-
8/15/2019 TSDOS Phasor Transformer
103/248
Transmission Line Parameters
• Resistance
The dc resistance of a conductor at a specified
temperature T is
103
-
8/15/2019 TSDOS Phasor Transformer
104/248
Transmission Line Parameters
• Resistance
In English units, conductor cross sectional area is
expressed in circular mils (cmil). One inch equals1000 mils and 1 cmil equals p/4 sq mil.
A circle with diameter D in has an area
or
where 1000 D mil = d mil104
-
8/15/2019 TSDOS Phasor Transformer
105/248
Transmission Line Parameters
• Resistance
Resistivity depends on the conductor metal.
Annealed copper is the international standard for measuring resistivity r.
Conductor resistance depends on the following
factors:
Spiraling Temperature
Frequency (‘‘skin effect’’)
Current magnitude—magnetic conductors
105
-
8/15/2019 TSDOS Phasor Transformer
106/248
Transmission Line Parameters
• Resistance
106
-
8/15/2019 TSDOS Phasor Transformer
107/248
-
8/15/2019 TSDOS Phasor Transformer
108/248
Transmission Line Parameters
• Inductance: Solid Cylindrical Conductor
The inductance of a magnetic circuit that has a
constant permeability m can be obtained bydetermining the following:
Magnetic field intensity H, from Ampere’s law.
Magnetic flux density B (B = mH).
Flux linkages l. Inductance from flux linkages per ampere (L = l/I).
108
-
8/15/2019 TSDOS Phasor Transformer
109/248
Transmission Line Parameters
• Inductance: Solid Cylindrical Conductor
For simplicity, assume that the conductor
is sufficiently long that end effects are neglected,
is nonmagnetic (m = m0 = 4p x10-7 H/m)
has a uniform current density (skin effect is neglected)
109
-
8/15/2019 TSDOS Phasor Transformer
110/248
Transmission Line Parameters
• Inductance: Solid Cylindrical Conductor
Ampere’s law states that
The magnetic field inside the conductor
Select the dashed circle of radius x < r
110
-
8/15/2019 TSDOS Phasor Transformer
111/248
Transmission Line Parameters
• Inductance: Solid Cylindrical Conductor
The magnetic field inside the conductor
Flux Density B
The differential flux dF per-unit length of conductor inthe cross-hatched rectangle of width dx shown in
previous figure (dF = Bxdx Wb/m)
Computation of the differential flux linkage dl in therectangle is tricky since only the fraction (x/r)2 of the total
current I is linked by the flux.
111
-
8/15/2019 TSDOS Phasor Transformer
112/248
Transmission Line Parameters
• Inductance: Solid Cylindrical Conductor
The magnetic field inside the conductor
Integrating the dl from x = 0 to x = r determines the totalflux linkages lint inside the conductor.
The internal inductance Lint per-unit length of conductor due to this flux linkage is then
112
-
8/15/2019 TSDOS Phasor Transformer
113/248
Transmission Line Parameters
• Inductance: Solid Cylindrical Conductor
The magnetic field outside the conductor
Select the dashed circle of radius x > r shown in Figureas the closed contour that encloses the entire current I.
113
-
8/15/2019 TSDOS Phasor Transformer
114/248
Transmission Line Parameters
• Inductance: Solid Cylindrical Conductor
The magnetic field outside the conductor
Integrating dl between two external points at distancesD1 and D2 from the conductor center gives the external
flux linkage l12 between D1 and D2.
114
-
8/15/2019 TSDOS Phasor Transformer
115/248
Transmission Line Parameters
• Inductance: Solid Cylindrical Conductor
The total flux lP linking the conductor out to
external point P at distance D is the sum of theinternal flux linkage and the external flux linkage
from D1 = r to D2 = D.
where
115
-
8/15/2019 TSDOS Phasor Transformer
116/248
-
8/15/2019 TSDOS Phasor Transformer
117/248
Transmission Line Parameters
• Inductance: Solid Cylindrical Conductor
The flux linkage lkPm, which links conductor k out
to P due to Im is:
Assume Dkm>>r
117
-
8/15/2019 TSDOS Phasor Transformer
118/248
Transmission Line Parameters
• Inductance: Solid Cylindrical Conductor
Rearrange the equation:
Replace IM with
118
-
8/15/2019 TSDOS Phasor Transformer
119/248
-
8/15/2019 TSDOS Phasor Transformer
120/248
Transmission Line Parameters
• Inductance: Single-phase two-wire
where
120
-
8/15/2019 TSDOS Phasor Transformer
121/248
Transmission Line Parameters
• Inductance: Single-phase two-wire
121
-
8/15/2019 TSDOS Phasor Transformer
122/248
Transmission Line Parameters
• Inductance: Single-phase two-wire
• Total inductance
• If conductors X and Y are the same
122
-
8/15/2019 TSDOS Phasor Transformer
123/248
Transmission Line Parameters
• Inductance: Three-phase three-wire with
equal spacing
123
-
8/15/2019 TSDOS Phasor Transformer
124/248
Transmission Line Parameters
• Inductance: Composite conductors
124
-
8/15/2019 TSDOS Phasor Transformer
125/248
Transmission Line Parameters
• Inductance: Composite conductors
• Since only the fraction (1/N) of the total conductor
current I is linked by this flux, the flux linkage lk of (the current in) subconductor k is
• The total flux linkage of conductor x is
125
-
8/15/2019 TSDOS Phasor Transformer
126/248
Transmission Line Parameters
• Inductance: Composite conductors
• Using ln A = ln A and ∑ ln Ak = ln Π Ak, we can
rewrite the previous equation as
• The Inductor
126
-
8/15/2019 TSDOS Phasor Transformer
127/248
Transmission Line Parameters
• Inductance: Composite conductors
Dxy is called the geometric mean distance or GMD
between conductors x and y. Dxx is called the geometric mean radius or GMR of
conductor x
Similarly, for conductor y,.
127
-
8/15/2019 TSDOS Phasor Transformer
128/248
Transmission Line Parameters
• Example
For a single-phase multiple conductor circuit
shown below, find GMR, GMD, and Inductance
128
-
8/15/2019 TSDOS Phasor Transformer
129/248
Transmission Line Parameters
• Solution
For N=3 and M=2’, GMD and GMR can be
expressed as:
129
-
8/15/2019 TSDOS Phasor Transformer
130/248
Transmission Line Parameters
• Solution
For N=3 and M=2’, GMD and GMR can be
expressed as:
130
-
8/15/2019 TSDOS Phasor Transformer
131/248
Transmission Line Parameters
• Solution
For N=3 and M=2’, GMD and GMR can be
expressed as:
131
-
8/15/2019 TSDOS Phasor Transformer
132/248
Transmission Line Parameters
• Solution
For N=3 and M=2’, GMD and GMR can be
expressed as:
132
-
8/15/2019 TSDOS Phasor Transformer
133/248
Transmission Line Parameters
• Solution
For N=3 and M=2’, GMD and GMR can be
expressed as:
133
-
8/15/2019 TSDOS Phasor Transformer
134/248
Transmission Line Parameters
• Transposition
If the spacings between phases are unequal, then
balanced positive-sequence flux linkages are notobtained from balanced positive-sequence
currents. Balance can be restored by exchanging
the conductor positions along the line, a technique
called transposition.
134
-
8/15/2019 TSDOS Phasor Transformer
135/248
Transmission Line Parameters
• Transposition
The total flux linking the phase a conductor while it
is in position 1 is
Similarly, the total flux linkage of this conductor
while it is in positions 2 and 3 is
135
-
8/15/2019 TSDOS Phasor Transformer
136/248
Transmission Line Parameters
• Transposition
The average of the above flux linkages is
136
-
8/15/2019 TSDOS Phasor Transformer
137/248
Transmission Line Parameters
• Transposition
The average inductance of phase a is
Defining
Then,
137
-
8/15/2019 TSDOS Phasor Transformer
138/248
Transmission Line Parameters
• Bundle conductors
If the conductors are stranded and the bundle
spacing d is large compared to the conductor outside radius, each stranded conductor is first
replaced by an equivalent solid cylindrical
conductor with GMR = DS. Then the bundle is
replaced by one equivalent conductor with GMR =DSL.
138
-
8/15/2019 TSDOS Phasor Transformer
139/248
Transmission Line Parameters
• Bundle conductors
Two-conductor bundle.
Three-conductor bundle
Four-conductor bundle
139
-
8/15/2019 TSDOS Phasor Transformer
140/248
-
8/15/2019 TSDOS Phasor Transformer
141/248
Transmission Line Parameters
• Series Impedances: Three-phase line with
neutral conductors and earth return
• Each earth return conductor carries the negative of its overhead conductor current, has a GMR
denoted Dk’k’, distance Dkk’ from its overhead
conductor, and resistance Rk’ given by:
where r is the earth resistivity in ohm-meters and f is frequency in hertz.141
-
8/15/2019 TSDOS Phasor Transformer
142/248
Transmission Line Parameters
• Series Impedances: Three-phase line with
neutral conductors and earth return
• Earth resistivities and 60-Hz equivalent conductor distances are shown in the table. It is common
practice to select r = 100 Wm when actual data areunavailable
142
-
8/15/2019 TSDOS Phasor Transformer
143/248
Transmission Line Parameters
• Series Impedances calculation
First, renumber the overhead conductors from 1 to
(3 + N), beginning with the phase conductors, thenoverhead neutral conductors.
The sum of the currents in all the conductors is
zero
the flux linking overhead conductor k is
143
-
8/15/2019 TSDOS Phasor Transformer
144/248
Transmission Line Parameters
• Series Impedances calculation
Convert the flux linkage in matrix format: l = L I . Where
When k = m, Dkk is the GMR of conductor k. When
k ≠ m, Dkm is the distance between conductors k
and m144
-
8/15/2019 TSDOS Phasor Transformer
145/248
Transmission Line Parameters
• Circuit representation of a 1-meter section
series-phase impedances
145
-
8/15/2019 TSDOS Phasor Transformer
146/248
Transmission Line Parameters
• Using this circuit, the vector of voltage drops
across the conductors is
where L is given in previous slide and R is a (3 + N) x (3 + N) matrix
of conductor resistances.146
-
8/15/2019 TSDOS Phasor Transformer
147/248
Transmission Line Parameters
• Our objective now is to reduce the (3 + N)
equations to three equations
147
-
8/15/2019 TSDOS Phasor Transformer
148/248
Transmission Line Parameters
• The diagonal elements of this matrix are
• The off diagonal elements of this matrix are
• Partition the matrix
where
148
-
8/15/2019 TSDOS Phasor Transformer
149/248
Transmission Line Parameters
• Solve the matrix
• ZP is a 3x3 matrix
149
-
8/15/2019 TSDOS Phasor Transformer
150/248
Transmission Line Parameters
• If the line is completely transposed
where
150
Electric Field and Voltage: Solid
-
8/15/2019 TSDOS Phasor Transformer
151/248
Cylindrical Conductors
• The capacitance between conductors in a
medium with constant permittivity e can be
obtained by determining the following: Electric field strength E, from Gauss’s law
Voltage between conductors
Capacitance from charge per unit volt (C = q/V)
151
Electric Field and Voltage: Solid
-
8/15/2019 TSDOS Phasor Transformer
152/248
Cylindrical Conductors
• Gauss’s law states that the total electric fluxleaving a closed surface equals the total charge
within the volume enclosed by the surface.• The normal component of electric flux density
integrated over a closed surface equals the
charge enclosed:
where D ┴ denotes the normal component of electric flux density, E ┴
denotes the normal component of electric field strength, and ds denotes
the differential surface area.152
Electric Field and Voltage: Solid
-
8/15/2019 TSDOS Phasor Transformer
153/248
Cylindrical Conductors
• Electric field lines originate from positive charges
and terminate at negative charges.
• A solid cylindrical conductor withradius r and with charge q coulombs
per meter (assumed positive in the
figure), uniformly distributed on the
conductor surface.
• For simplicity, assume that theconductor is (1) sufficiently long that
end effects are negligible, and (2) a
perfect conductor (that is, zero
resistivity, r = 0).153
Electric Field and Voltage: Solid
-
8/15/2019 TSDOS Phasor Transformer
154/248
Cylindrical Conductors
• Inside the perfect conductor, Ohm’s law gives Eint = rJ = 0. That is, the internal electric field Eint is
zero.• To determine the electric field outside the
conductor, select the cylinder with radius x > r
and with 1-meter length as the closed surface for
Gauss’s law.
• Due to the uniform charge distribution, the
electric field strength Ex is constant on the
cylinder154
Electric Field and Voltage: Solid
-
8/15/2019 TSDOS Phasor Transformer
155/248
Cylindrical Conductors
• There is no tangential component of Ex, so the
electric field is radial to the conductor.
• For a conductor in free space
155
Electric Field and Voltage: Solid
-
8/15/2019 TSDOS Phasor Transformer
156/248
Cylindrical Conductors
• Concentric cylinders surrounding the conductor
are constant potential surfaces. The potential
difference between two concentric cylinders atdistances D1 and D2 from the conductor center
is.
156
Electric Field and Voltage: Solid
-
8/15/2019 TSDOS Phasor Transformer
157/248
Cylindrical Conductors
• Now apply this equation to the array of M solid
cylindrical conductors shown below:
157
Electric Field and Voltage: Solid
-
8/15/2019 TSDOS Phasor Transformer
158/248
Cylindrical Conductors
• Assume that each conductor m has a charge qm
C/m uniformly distributed along the conductor.
The voltage Vkim between conductors k and i dueto the charge qm acting alone is
• Using superposition, the voltage Vki betweenconductors k and i due to all the charges is
where Dmm = r m when k = m or i = m
158
T i i i P
-
8/15/2019 TSDOS Phasor Transformer
159/248
Transmission Line Parameters
• Capacitance: Single-phase two-wire line
• Assume that the
conductors are energizedby a voltage source such
that conductor x has a
uniform charge q C/m and,
assuming conservation of charge, conductor y has an
equal quantity of negative
charge -q.
159
T i i Li P t
-
8/15/2019 TSDOS Phasor Transformer
160/248
Transmission Line Parameters
• Capacitance: Single-phase two-wire line
• Using Dxy = Dyx = D, Dxx = r x, and Dyy = r y.
• For 1-meter length, the capacitor between conductors
is
160
T i i Li P t
-
8/15/2019 TSDOS Phasor Transformer
161/248
Transmission Line Parameters
• Capacitance: Single-phase two-wire line
• If the two-wire line is supplied by a transformer with a
grounded center tap, then the voltage between eachconductor and ground is one-half of the line to line
voltage (Assume r x = r y).
161
T i i Li P t
-
8/15/2019 TSDOS Phasor Transformer
162/248
Transmission Line Parameters
• Capacitance: Three-phase, three-wire and
equal spacing
• To determine the positive-sequence capacitance,assume positive-sequence charges qa, qb, qc such
that qa + qb + qc = 0. Using Daa = Dbb = r, and Dab =
Dba = Dca = Dcb = D, we can rewrite the equation
162
T i i Li P t
-
8/15/2019 TSDOS Phasor Transformer
163/248
Transmission Line Parameters
• Capacitance: Three-phase, three-wire and equal
spacing
• Similarly,
163
T i i Li P t
-
8/15/2019 TSDOS Phasor Transformer
164/248
Transmission Line Parameters
• Capacitance: Three-phase, three-wire and equal
spacing
• For balanced positive-sequence voltages
• Therefore,164
T i i Li P t
-
8/15/2019 TSDOS Phasor Transformer
165/248
Transmission Line Parameters
• Capacitance: Three-phase, three-wire and equal
spacing
• Therefore,
and
165
T i i Li P t
-
8/15/2019 TSDOS Phasor Transformer
166/248
Transmission Line Parameters
• Capacitance: General forms
• For a complete transpose line, the line to neutral
capacitance can be expressed as:
where
166
T i i Li P t
-
8/15/2019 TSDOS Phasor Transformer
167/248
Transmission Line Parameters
• Capacitance: General forms
• For a three-phase balanced system with bundle
conductors:• qa + qb + qc = 0 for a balanced system. Assume that the
conductors in each bundle, which are in parallel, share the
charges equally.
• Also assume that the phase spacings are much larger than
the bundle spacings.
167
T i i Li P t
-
8/15/2019 TSDOS Phasor Transformer
168/248
Transmission Line Parameters
• Capacitance: General forms
• For a three-phase balanced system with bundle
conductors:• Using the following configuration (Three-phase, two
conductors per bundle) as example.
168
Transmission Line Parameters
-
8/15/2019 TSDOS Phasor Transformer
169/248
Transmission Line Parameters
• Capacitance: General forms
• For a three-phase balanced system with bundle
conductors:
169
Transmission Line Parameters
-
8/15/2019 TSDOS Phasor Transformer
170/248
Transmission Line Parameters
• Capacitance: General forms
• For transposed line
where
• Similarly
• Deq is the geometric mean of the distances between
phases170
Transmission Line Parameters
-
8/15/2019 TSDOS Phasor Transformer
171/248
Transmission Line Parameters
• Shunt Admittances: Line with neutral conductors
and earth return
Single conductor and earth plane
• The effect of the earth plane isdescribed as follows. Consider asingle conductor with uniform charge
distribution and with height H above
a perfectly conducting earth plane,
as shown in Figure. When the
conductor has a positive charge,an equal quantity of negative charge is induced on the earth.
The electric field lines will originate from the positive charges on
the conductor and terminate at the negative charges on the
earth. Also, the electric field lines are perpendicular to the
surfaces of the conductor and earth
171
Transmission Line Parameters
-
8/15/2019 TSDOS Phasor Transformer
172/248
Transmission Line Parameters
• Shunt Admittances: Line with neutral conductors
and earth return
Earth place is replaced by image conductor
• Now replace the earth by theimage conductor which has the
same radius as the original
conductor, lies directly below the
original conductor with conductor
separation H11 = 2H, and has anequal quantity of negative charge.
Therefore, the voltage between
any two points above the earth is
the same in both figures.172
Example: Capacitance on single-phase line
-
8/15/2019 TSDOS Phasor Transformer
173/248
phase line
• If a 20 miles of single-phase line operating at
20kV and 60 Hz consists of two 4/0 12-strand
copper conductors with 5 ft spacing betweenconductor centers, determine the line-to-line
capacitance in F and the line-to-line admittance
in S.
173
Example: Capacitance on single-phase line
-
8/15/2019 TSDOS Phasor Transformer
174/248
phase line
• Solution
• The outside radius of a 4/0 12-strand copper
conductor is 0.023 ft.
174
Example: Capacitance on single-phase line (Consider earth)
-
8/15/2019 TSDOS Phasor Transformer
175/248
phase line (Consider earth)
• For the same single phase line as the previous
example with18-ft average line height. Determine
the effect of the earth on capacitance. Assume aperfectly conducting earth plane.
175
Example: Capacitance on single-phase line (Consider earth)
-
8/15/2019 TSDOS Phasor Transformer
176/248
phase line (Consider earth)
• Solution
• The earth plane is replaced by a separate image
conductor for each overhead conductor with proper charge.
176
Example: Capacitance on single-phase line (Consider earth)
-
8/15/2019 TSDOS Phasor Transformer
177/248
phase line (Consider earth)
• Solution
• The voltage between conductors x and y is
177
Example: Capacitance on single-phase line (Consider earth)
-
8/15/2019 TSDOS Phasor Transformer
178/248
phase line (Consider earth)
• Solution
• The line to line capacitor is
• Using D = 5 ft, r = 0.023 ft, Hxx = 2H = 36 ft, and Hxy =
36.346 ft.
178
Transmission Line Parameters
-
8/15/2019 TSDOS Phasor Transformer
179/248
Transmission Line Parameters
• Shunt Admittances: General form
• For the three-phase line with N
neutral conductors shown inFigure, the perfectly
conducting earth plane is
replaced by a separate image
conductor for each overheadconductor that carry opposite
charge.
179
Transmission Line Parameters
-
8/15/2019 TSDOS Phasor Transformer
180/248
Transmission Line Parameters
• Shunt Admittances: General form
The voltage Vkk’ between any conductor k and its
image conductor k’ is
where Dkk = r k and Dkm is the distance between
overhead conductors k and m. Hkm is the distance
between overhead conductor k and image conductor m.180
Transmission Line Parameters
-
8/15/2019 TSDOS Phasor Transformer
181/248
Transmission Line Parameters
• Shunt Admittances: General form
By symmetry, the voltage Vkn between conductor k
and the earth is one-half of Vkk’.
where (k = a; b; c; n1; n2; . . . ; nN) and (m = a; b; c; n1;
n2; . . . ; nN) Since all the neutral conductors are grounded to the
earth, Vkn = 0 for k = n1; n2; . . . ; nN.
181
Transmission Line Parameters
-
8/15/2019 TSDOS Phasor Transformer
182/248
Transmission Line Parameters
• Shunt Admittances: General form
In matrix form
182
Transmission Line Parameters
-
8/15/2019 TSDOS Phasor Transformer
183/248
Transmission Line Parameters
• Shunt Admittances: General form
The elements of the (3 + N) X (3 + N) matrix P are
where (k = a; b; c; n1; n2; . . . ; nN) and (m = a; b; c; n1;
n2; . . . ; nN)
The matrix can then be partitioned into
183
Transmission Line Parameters
-
8/15/2019 TSDOS Phasor Transformer
184/248
Transmission Line Parameters
• Shunt Admittances: General form
The matrix can be rewritten into
or
where
184
-
8/15/2019 TSDOS Phasor Transformer
185/248
Electric Field at Conductor Surfaces and at Ground Level
-
8/15/2019 TSDOS Phasor Transformer
186/248
Surfaces and at Ground Level
• When the electric field strength at a conductor
surface exceeds the breakdown strength of air,
current discharges occur.• This phenomenon, called corona, causes
additional line losses (corona loss),
communications interference, and audible noise.
• When line capacitances are determined and
conductor voltages are known, the conductor
charges can be calculated.186
Electric Field at Conductor Surfaces and at Ground Level
-
8/15/2019 TSDOS Phasor Transformer
187/248
Surfaces and at Ground Level
• Then the electric field strength at the surface of
one phase conductor, neglecting the electric
fields due to charges on other phase conductorsand neutral wires is
where r is the conductor outside radius
187
-
8/15/2019 TSDOS Phasor Transformer
188/248
Electric Field at Conductor Surfaces and at Ground Level
-
8/15/2019 TSDOS Phasor Transformer
189/248
Surfaces and at Ground Level
• For the arrangement shown in the figure, the
maximum electric field strength at the surface
of one conductor due to all charges in a bundlecan be obtained by the vector addition of
electric fields.
189
Electric Field at Conductor Surfaces and at Ground Level
-
8/15/2019 TSDOS Phasor Transformer
190/248
Surfaces and at Ground Level
• Two-conductor bundle (Nb = 2)
• Three-conductor bundle (Nb = 3)
• Four-conductor bundle (Nb = 4)
190
-
8/15/2019 TSDOS Phasor Transformer
191/248
Electric Field at Conductor Surfaces and at Ground Level
-
8/15/2019 TSDOS Phasor Transformer
192/248
Surfaces and at Ground Level
Transmission-line heights are designed to
maintain discharge currents below prescribed
levels for any equipment that may be on theright-of-way. Table shows examples of
maximum ground level electric field strength.
192
Electric Field at Conductor Surfaces and at Ground Level
-
8/15/2019 TSDOS Phasor Transformer
193/248
Surfaces and at Ground Level
As shown in Figure, the ground-level electric
field strength due to charged conductor k and its
image conductor is perpendicular to the earthplane, will be:
193
-
8/15/2019 TSDOS Phasor Transformer
194/248
Parallel Circuits on Three-PhaseLines
-
8/15/2019 TSDOS Phasor Transformer
195/248
Lines
• Consider the double-circuit line shown below.
• Since both are connected in parallel, they have
the same series-voltage drop for each phase.Following the same procedure as described
before, we can write 2(6 X N) equations.
195
-
8/15/2019 TSDOS Phasor Transformer
196/248
Parallel Circuits on Three-PhaseLines
-
8/15/2019 TSDOS Phasor Transformer
197/248
es
• Adding IP1 and IP2 and solving for EP
• ZPeq is the equivalent 3 X 3 series phaseimpedance matrix of the double circuit line. The
matrices YB and YC account for the inductive
coupling between the two circuits.
where
197
Parallel Circuits on Three-PhaseLines
-
8/15/2019 TSDOS Phasor Transformer
198/248
• Similar procedure can be used to obtain the
shunt admittance matrix.
• Following the same idea, we can write (6 + N)equations. After eliminating the neutral wire
charges, we obtain
where VP is the vector of phase-to-neutral voltages, and qP1 and qP2 are the
vectors of phase-conductor charges for lines 1 and 2. CP is a 6 X 6 capacitance
matrix that is partitioned into four 3 X 3 matrices C A, CB, CC, and CD 198
Parallel Circuits on Three-PhaseLines
-
8/15/2019 TSDOS Phasor Transformer
199/248
• Adding qP1 and qP2.
where
199
Transmission Lines: Steady StateOperation
-
8/15/2019 TSDOS Phasor Transformer
200/248
p
200
Medium and Short LineApproximation
-
8/15/2019 TSDOS Phasor Transformer
201/248
pp
• It is convenient to represent a transmission line
by the two-port network shown below.
• The relation between the sending-end andreceiving-end quantities can be written as:
201
or
Medium and Short LineApproximation
-
8/15/2019 TSDOS Phasor Transformer
202/248
pp
• A, B, C, and D are parameters that depend on
the transmission-line constants R, L, C, and G.
The ABCD parameters are, in general, complexnumbers. A and D are dimensionless. B has
units of ohms, and C has units of Siemens.
• The circuit in previous figure represents a short
transmission line, usually applied to overhead60-Hz lines less than 80 km (50 miles) long.
Only the series resistance and reactance are
included. The shunt admittance is neglected.202
Medium and Short LineApproximation
-
8/15/2019 TSDOS Phasor Transformer
203/248
pp
• The circuit applies to either single-phase or
completely transposed three-phase lines
operating under balanced conditions.• We can derive the two-port circuit and rewrite
the matrix
203
Medium and Short LineApproximation
-
8/15/2019 TSDOS Phasor Transformer
204/248
pp
• For medium-length lines, typically ranging from
80 to 250 km (50 to 150 Miles) at 60 Hz, it is
common to lump the total shunt capacitanceand locate half at each end of the line. Such a
circuit, called a nominal p circuit.
204
Medium and Short LineApproximation
-
8/15/2019 TSDOS Phasor Transformer
205/248
pp
• Following the basic circuit theory to obtain the
ABCD parameters of the nominal p circuit.
205
Medium and Short LineApproximation
-
8/15/2019 TSDOS Phasor Transformer
206/248
pp
• Rewrite the equations into matrix form.
• Note that for both the short and medium-lengthlines, the relation AD - BC = 1 is verified. Note
also that since the line is the same when
viewed from either end, A = D.206
Medium and Short LineApproximation
-
8/15/2019 TSDOS Phasor Transformer
207/248
pp
• Summary of Medium and Short Line
Representation.
207
Medium and Short LineApproximation
-
8/15/2019 TSDOS Phasor Transformer
208/248
• Summary of Medium and Short Line
Representation.
208
Medium and Short LineApproximation
-
8/15/2019 TSDOS Phasor Transformer
209/248
• Voltage Regulation
• The “percent VR” is the percent voltageregulation, |VRNL| is the magnitude of the no-
load receiving-end voltage, and |VRFL
| is the
magnitude of the full load receiving-end
voltage.
209
Medium and Short LineApproximation
-
8/15/2019 TSDOS Phasor Transformer
210/248
• In addition to voltage regulation, line loadability
is an important issue. Three major line-loading
limits are: (1) the thermal limit, (2) the voltage-drop limit, and (3) the steady-state stability limit.
210
Transmission Line DifferentialEquations
-
8/15/2019 TSDOS Phasor Transformer
211/248
• Though we have used lumped model for
medium and short transmission lines, the R, L,
and C of line parameters are uniformlydistributed along the length of the line. The
circuit shown below is the better way for
transmission line representation.
211
G is usually neglected for
overhead 60-Hz lines
Transmission Line DifferentialEquations
-
8/15/2019 TSDOS Phasor Transformer
212/248
• From basic circuit theory:
212
Transmission Line DifferentialEquations
-
8/15/2019 TSDOS Phasor Transformer
213/248
• A1 and A2 are integration constants and
• Using
213
Zc is the characteristic impedance
and is the propagation constant
-
8/15/2019 TSDOS Phasor Transformer
214/248
Transmission Line DifferentialEquations
-
8/15/2019 TSDOS Phasor Transformer
215/248
• Substitute these values into V(x) and I(x).
215
Transmission Line DifferentialEquations
-
8/15/2019 TSDOS Phasor Transformer
216/248
• Use the hyperbolic functions cosh and sinh.
216
where
Transmission Line DifferentialEquations
-
8/15/2019 TSDOS Phasor Transformer
217/248
• The propagation constant is a complexquantity with real and imaginary parts denoted
and ( = + j m-1
).
217
Transmission Line DifferentialEquations
-
8/15/2019 TSDOS Phasor Transformer
218/248
• ABCD parameters for short, medium, long, and
lossless lines.
218
Example: Exact Transmission LineModel
-
8/15/2019 TSDOS Phasor Transformer
219/248
• A three-phase 765-kV, 60-Hz, 300-km,
completely transposed line has the following
positive-sequence impedance and admittance:
• Assuming positive-sequence operation,
calculate the exact ABCD parameters of the
line. Compare the exact B parameter with that
of the nominal p circuit.219
Example: Exact Transmission LineModel
-
8/15/2019 TSDOS Phasor Transformer
220/248
• Solution
220
Example: Exact Transmission LineModel
-
8/15/2019 TSDOS Phasor Transformer
221/248
• Solution
221
Example: Exact Transmission LineModel
-
8/15/2019 TSDOS Phasor Transformer
222/248
• Solution
222
Example: Exact Transmission LineModel
-
8/15/2019 TSDOS Phasor Transformer
223/248
• Solution
• The B parameter for the nominal p circuit is
223
Equivalent p Circuit for LongTransmission Line
-
8/15/2019 TSDOS Phasor Transformer
224/248
• Many computer programs used in power
system analysis and design assume circuit
representations of components.• It is therefore convenient to represent the
terminal characteristics of a transmission line
by an equivalent circuit.
224
Equivalent p Circuit for LongTransmission Line
-
8/15/2019 TSDOS Phasor Transformer
225/248
• The circuit shown
below is called an
equivalent p circuit. Itis identical instructure to the
nominal p circuit
except that Z’ and Y’are used instead of Zand Y.
225
Equivalent p Circuit for LongTransmission Line
-
8/15/2019 TSDOS Phasor Transformer
226/248
• The ABCD parameters of the equivalent p circuit, which has the same structure as the
nominal p, are
226
Lossless Line
-
8/15/2019 TSDOS Phasor Transformer
227/248
• It is easier to use lossless line (R = G = 0) to
explain the concept of surge impedance,
wavelength, surge impedance loading, voltageprofiles, and steady-state stability limit.
227
Surge Impedance
-
8/15/2019 TSDOS Phasor Transformer
228/248
• For a lossless line,
• The characteristic impedance Zc, commonly called
surge impedance for a lossless line, is pure real -
that is, resistive. The propagation constant = j ispure imaginary228
and
where
Wavelength
-
8/15/2019 TSDOS Phasor Transformer
229/248
• A wavelength is the distance required to
change the phase of the voltage or current by
2p radians.• For a lossless line
229
and
Wavelength
-
8/15/2019 TSDOS Phasor Transformer
230/248
• V(x) and I (x) change phase by 2p radianswhen x = 2p/. Denoting wavelength by l.
• is the propagation velocity of voltage
and current waves along a lossless line. This isaround 3X108 m/sec for overhead lines. For
60Hz system, the wavelength is around
5000km.230
Surge Impedance Loading
-
8/15/2019 TSDOS Phasor Transformer
231/248
• Surge impedance loading (SIL) is the power
delivered by a lossless line to a load resistance
equal to the surge impedance Zc.
231
Surge Impedance Loading
-
8/15/2019 TSDOS Phasor Transformer
232/248
• At SIL, the voltage profile is flat. That is, the
voltage magnitude at any point x along a
lossless line at SIL is constant.
232
Surge Impedance Loading
-
8/15/2019 TSDOS Phasor Transformer
233/248
233
• The complex power flowing at any point x
along the line is
Surge Impedance Loading
-
8/15/2019 TSDOS Phasor Transformer
234/248
234
• The real power flow along a lossless line at
SIL remains constant from the sending end to
the receiving end. The reactive power flow iszero.
• At rated line voltage SIL of a line is V2rated/Zc.
Surge Impedance Loading
-
8/15/2019 TSDOS Phasor Transformer
235/248
235
• This table shows surge impedance and SIL
values for typical overhead 60-Hz three-
phase line.
-
8/15/2019 TSDOS Phasor Transformer
236/248
Steady State Stability Limit
-
8/15/2019 TSDOS Phasor Transformer
237/248
237
• The equivalent p circuit can be used to obtainan equation for the real power delivered by a
lossless line.
• Assume that the voltage magnitudes VS and
VR at the ends of the line are held constant.
• Also, let d denote the voltage-phase angle atthe sending end with respect to the receivingend.
Steady State Stability Limit
-
8/15/2019 TSDOS Phasor Transformer
238/248
238
• From circuit theory
• The complex power SR delivered to the
receiving end is
Steady State Stability Limit
-
8/15/2019 TSDOS Phasor Transformer
239/248
239
• The real power is
Steady State Stability Limit
-
8/15/2019 TSDOS Phasor Transformer
240/248
240
• Pmax represents the theoretical steady-state
stability limit of a lossless line.
• It is convenient to express the steady-statestability limit in terms of SIL
Steady State Stability Limit
-
8/15/2019 TSDOS Phasor Transformer
241/248
241
• Transmission line loadability curve
Maximum Power Flow
-
8/15/2019 TSDOS Phasor Transformer
242/248
242
• For lossy lines, their ABCD parameters are
• The receiving end current is
Maximum Power Flow
-
8/15/2019 TSDOS Phasor Transformer
243/248
243
• The complex power delivers to the receiving
end is
Maximum Power Flow
-
8/15/2019 TSDOS Phasor Transformer
244/248
244
• The theoretical maximum real power
delivered (or steady-state stability limit)
occurs when d = Z.
Line Loadability
-
8/15/2019 TSDOS Phasor Transformer
245/248
245
• In practice, power lines are not operated to
deliver their theoretical maximum power.
• Typical loadability is based on the voltage-drop limit VR/VS>0:95 and on a maximum
angular displacement of 30 to 35o across the
line (or about 45o across the line and
equivalent system reactances) to maintainstability during transient disturbances.
Line Loadability
-
8/15/2019 TSDOS Phasor Transformer
246/248
246
• Note that for short lines less than 80 km long,
loadability is limited by the thermal rating of
the conductors or by terminal equipment
ratings, not by voltage drop or stability
considerations.
Reactive Compensation
-
8/15/2019 TSDOS Phasor Transformer
247/248
247
• Inductors and capacitors are used on
medium-length and long transmission lines to
increase line loadability and to maintain
voltages near rated values.
• It can be either series or shunt
compensation.
Reactive Compensation
-
8/15/2019 TSDOS Phasor Transformer
248/248
• Following devices are used in reactive power
compensation:
• Capacitor
• Inductor
• Static Var Compensator (FC-TCR or SC-TCR)