tsdos phasor transformer

Upload: lookitsnichole

Post on 01-Jul-2018

237 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/15/2019 TSDOS Phasor Transformer

    1/248

    Phasor, Transformer, andTransmission Lines

    Wei-Jen Lee, Ph.D., P.E.Professor and Director

    Energy Systems Research Center

    The University of Texas at Arlington

    1

    Text Book: J. Duncan Glover, Mulukutla S. Sarma, and Thomas J.

    Overbye, “Power Systems Analysis and Design”, Fifth Edition.Cengage Learning

  • 8/15/2019 TSDOS Phasor Transformer

    2/248

    Introduction

    2

  • 8/15/2019 TSDOS Phasor Transformer

    3/248

    A Typical Power System

    3

  • 8/15/2019 TSDOS Phasor Transformer

    4/248

    Components of a Modern Power 

    System

    • Every power system has four major 

    components

     – Generation facilities

     – Power delivery system

     –Loads

     – Monitoring, protection, and control system

    4

  • 8/15/2019 TSDOS Phasor Transformer

    5/248

    Challenges of Power System

    Operation

    • Every Generation facility has its own limit.

    • Some generation facilities are difficult tocontrol.

    • Delivery systems also have limitations.

    • Loads are seldom constant

    • Since the power systems are dynamic innature, it is difficult, if not impossible, to

    maintain optimal conditions of a power 

    system.

    5

  • 8/15/2019 TSDOS Phasor Transformer

    6/248

    Notation - Power 

    • Power: Instantaneous consumption of energy

    • Power Units Watts – voltage x current for dc (W) kW – 1 x 103 Watt MW – 1 x 106 Watt GW – 1 x 109 Watt

    • Installed U.S. generation capacity is about900 GW ( about 3 kW per person)

    • Installed generation capacity in the ERCOT is

    around 95GW (Including 10GW wind

    generation)6

  • 8/15/2019 TSDOS Phasor Transformer

    7/248

  • 8/15/2019 TSDOS Phasor Transformer

    8/248

    Power System Examples

    • North American Interconnected System

    8

  • 8/15/2019 TSDOS Phasor Transformer

    9/248

    Power System Examples

    • North American Interconnected System

    9

  • 8/15/2019 TSDOS Phasor Transformer

    10/248

    Power System Examples

    • MicroGrid (Isolated power system)

    • Intentional islanding operation of a power system(Military campus, remote villages, and etc)

    •  Airplanes and Spaceships

    • Ships and submarines

    •  Automobiles: dc with 12 volts standard• Battery operated portable systems

    10

  • 8/15/2019 TSDOS Phasor Transformer

    11/248

    AC versus DC Power System

    • With the flip of a switch at 3 p.m. on Sept. 4,

    1882 at Pearl Station, Thomas Edisonushered in the age of commercial electrical

    power systems.

    • It was a DC MicroGrid and served 240

    customers within one square miles.• Tesla's patents and theoretical work formed

    the basis of modern alternating current

    electric power (AC) systems.11

  • 8/15/2019 TSDOS Phasor Transformer

    12/248

    Concept of Phasor 

    • Since it is relative easy to change the voltage

    level, majority of the power systems are ACsystem (either 50Hz or 60Hz).

    • Since the relationship of the AC system is

    based upon the phase difference between

    two quantities, this evolves the concept of phasor.

    • Goal of phasor analysis is to simplify the

    analysis of constant frequency AC systems. 12

  • 8/15/2019 TSDOS Phasor Transformer

    13/248

    Instantaneous and RMS Values

    • The voltage and current of an AC system can

    be expressed as:

    • The DC equivalent of an AC sinusoidal signal

    is shown below: (RMS value)

    )cos(*)(

    )cos(*)(

    max

    max

    i

    v

    t  I t i

    t V t v

      

      

    2

    )(1

    || max

    0

    2 V dt t v

    V V 

     RMS 

    13

  • 8/15/2019 TSDOS Phasor Transformer

    14/248

    Phasor Representation

    • Euler’s Identity: 

    • Phasor notation is developed by rewriting theEuler’s Identity:

       

    sincos jej

    ]Re[||2)(

    )cos(||2)(

    )( vt  j

    v

    eV t v

    t V t v

      

      

    14

  • 8/15/2019 TSDOS Phasor Transformer

    15/248

    Phasor Representation

    • The RMS cosine-reference voltage and

    current phasors are:

    i

      j

    v

      j

     I e I  I 

    V eV V 

    i

    v

     

     

     

     

    ||||

    ||||

    15

  • 8/15/2019 TSDOS Phasor Transformer

    16/248

    V/I Relationships of R, L, and C

    16

  • 8/15/2019 TSDOS Phasor Transformer

    17/248

    Advantages of Phasor Analysis

    0

    2 2

    Resistor ( ) ( )

    ( )Inductor ( )

    1 1Capacitor ( ) (0)

    C

    Z = Impedance

    R = Resistance

    X = Reactance

    XZ = =arctan( )

    v t Ri t V RI  

    di t v t L V j LI  

    dt 

    i t dt v V I    j C 

     R jX Z 

     R X  R

     

     

     

     

    Device Time Analysis Phasor

    17

  • 8/15/2019 TSDOS Phasor Transformer

    18/248

    Complex Power 

    max

    max

    max max

     

    ( ) ( ) ( )

    v(t) = cos( )

    (t) = cos( )

    1

    cos cos [cos( ) cos( )]2

    1( ) [cos( )

    2

    cos(2 )]

     I 

    V I 

    V I 

     p t v t i t 

    V t 

    i I t 

     p t V I 

     

     

     

     

     

    Power

    18

  • 8/15/2019 TSDOS Phasor Transformer

    19/248

    Complex Power 

    max max

    0

    max max

     

    1

    ( ) [cos( ) cos(2 )]2

    1( )

    1 cos( )2

    cos( )

    = =

    V I V I  

    avg 

    V I 

    V I 

    V I 

     p t V I t 

     P p t dt T 

    V I 

    V I 

     

     

     

     

    Power Factor

    Average P

    Angle

    ower

    19

  • 8/15/2019 TSDOS Phasor Transformer

    20/248

    Complex Power 

    *

    cos( ) sin( )

    P = Real Power (W, kW, MW)

    Q = Reactive Power (var, kvar, Mvar)

    S = Complex power (VA, kVA, MVA)

    Power Factor (pf) = cos

    If current leads voltage then pf is leading

    If current

    V I V I  

    V I 

    S V I j

     P jQ

     

     

    lags voltage then pf is lagging

    For simplicity, we will use V and I as RMSvalues of voltage and current 

    20

  • 8/15/2019 TSDOS Phasor Transformer

    21/248

    Example

    • Instantaneous, real, and reactive power; power 

    factor.• The voltage v(t)=141.4*cos(t) is applied to a load consisting of a 10-W resistor in parallel with an inductive reactance XL =L =3.77 W. Calculate the instantaneous power absorbed by theresistor and by the inductor. Also calculate the real and reactive

    power absorbed by the load, and the power factor 

    21

  • 8/15/2019 TSDOS Phasor Transformer

    22/248

    Example

    • Instantaneous, real, and reactive power; power 

    factor.• The V/I relationship of resistor 

    22

  • 8/15/2019 TSDOS Phasor Transformer

    23/248

    Example

    • Instantaneous, real, and reactive power; power 

    factor.• The V/I relationship of inductor 

    23

  • 8/15/2019 TSDOS Phasor Transformer

    24/248

    Example

    • Instantaneous, real, and reactive power; power 

    factor.• The load voltage is

    • The resistor current is

    • The inductor current is

    • The total load current is• The Instantaneous power absorbed by the resistor is

    24

  • 8/15/2019 TSDOS Phasor Transformer

    25/248

    Example

    • Instantaneous, real, and reactive power; power 

    factor.

    • The Instantaneous power absorbed by the inductor 

    is

    • The real power absorbed by load is

    • The reactive power absorbed by load is

    • The power factor is25

  • 8/15/2019 TSDOS Phasor Transformer

    26/248

    Example

    • Power triangle and power factor correction

    • A single-phase source delivers 100 kW to a loadoperating at a power factor of 0.8 lagging. Calculate

    the reactive power to be delivered by a capacitor 

    connected in parallel with the load in order to raise

    the source power factor to 0.95 lagging.

    26

  • 8/15/2019 TSDOS Phasor Transformer

    27/248

    Example

    • Power triangle and power factor correction

    •Before compensation

    •  After compensation

    27

  • 8/15/2019 TSDOS Phasor Transformer

    28/248

  • 8/15/2019 TSDOS Phasor Transformer

    29/248

    RMS and Instantaneous values

    • When voltages and currents are discussed in

    this text, lowercase letters such as v(t) and

    i(t) indicate instantaneous values, uppercase

    letters such as V and I indicate rms values,

    and uppercase letters in italics such as V and

    I indicate rms phasors. When voltage or current values are specified, they shall be

    rms values unless otherwise indicated.

    29

  • 8/15/2019 TSDOS Phasor Transformer

    30/248

    Single-Phase and Three-Phase

    Power System

    • Single-phase power system

    • Single-phase-three wire system• Three-phase system

    30

  • 8/15/2019 TSDOS Phasor Transformer

    31/248

    Advantages of Three-Phase Power 

    System

    • More power per kilogram of metal from a

    three-phase machine.

    • Power delivered to a balanced three-phase

    load is constant at all time, instead of pulsing

    as it does in a single-phase system.

    • More power can be delivered.• Total line losses are reduced.

    31

  • 8/15/2019 TSDOS Phasor Transformer

    32/248

    Three-Phase Power System

    •  A three-phase generator consists of three

    single-phase generators with voltages of 

    equal amplitudes and phase differences of 

    1200.

    32

  • 8/15/2019 TSDOS Phasor Transformer

    33/248

    Balanced Three-Phase Power 

    System

    • We can used three

    single-phase system

    differing in phase angle

    by 1200 to represent a

    balanced three-phase

    system.• The current flowing to

    each load can be found

    as V  I 

     Z 

    33

  • 8/15/2019 TSDOS Phasor Transformer

    34/248

    Balanced Three-Phase Power 

    System

    • Therefore, the currents flowing in each

    phase are.0

    0

    0

    0

    120120

    240240

     A

     B

     A

    V  I I 

     Z 

    V  I I 

     Z 

    V  I I 

     Z 

      

      

      

    34

  • 8/15/2019 TSDOS Phasor Transformer

    35/248

    Balanced Three-Phase Power 

    System

    • We will form a three-phase circuit by

    connecting the return path of three-single

    phase load together.

    35

  • 8/15/2019 TSDOS Phasor Transformer

    36/248

    Balanced Three-Phase Power 

    System

    • The current flows through the neutral

    conductor is equal to zero.

    0)240()120( ooC  B A N 

    I  I  I  I  I  I  I     

    36

  • 8/15/2019 TSDOS Phasor Transformer

    37/248

    D and Y Connection of Three-Phase Power System

    • There are two types of connections in

    three-phase circuits: Y and D.

    37

  • 8/15/2019 TSDOS Phasor Transformer

    38/248

    D and Y Connection of Three-Phase Power System

    • General Relations Between Circuit

    Quantities.

      

     

      

    3

    2

    3

    3

    3

    2

    3

    3033*303

    303

    3

    30

    3

    30

    303*

    3

    30

    V V 

     I 

     I 

    V  Z 

     Z 

    V  I  I 

    Connection

    V V 

     I 

    V  Z 

    ConnectionY 

    o

     LL LLo

     LL

     L

    o

     LL LL

     LL

    o

     LL

    o

     L

    o

     LL LL

    o

     LL

     L

     LN 

    D

    D

    D

    D

    D

    38

  • 8/15/2019 TSDOS Phasor Transformer

    39/248

    D and Y Connection of Three-Phase Power System

    • Phase quantity: voltages and currents in a

    given phase.

    • Line quantity: voltages between the lines

    and currents in the lines connected to the

    generators or loads.

    39

  • 8/15/2019 TSDOS Phasor Transformer

    40/248

    Power of a Balanced Three-Phase

    Power System

    • For a balanced Y-connected load with the

    impedance Z  

    = Z  0 :

    0

    0

    ( ) 2 sin

    ( ) 2 sin( 120 )

    ( ) 2 sin( 240 )

    an

    bn

    cn

    v t V t  

    v t V t  

    v t V t  

     

     

     

    0

    0

    ( ) 2 sin( )

    ( ) 2 sin( 120 )

    ( ) 2 sin( 240 )

    a

    b

    c

    i t I t  

    i t I t  

    i t I t  

     

     

     

    40

  • 8/15/2019 TSDOS Phasor Transformer

    41/248

    Power of a Balanced Three-Phase

    Power System

    • The instantaneous power is:

    • The total power on the load is

    0

    0

    ( ) cos cos(2 )( ) cos cos(2 240 )

    ( ) cos cos(2 480 )

    a

    b

    c

     p t VI t  p t VI t 

     p t VI t 

     

     

     

     cos3)()()()( VI t  P t  P t  P t  P cbatotal 

    41

  • 8/15/2019 TSDOS Phasor Transformer

    42/248

    Power Relationship

    • Phase quantities in each phase of a Y- or 

    D-connection: – Real Power:

     – Reactive Power:

     –  Apparent Power:

    23 cos 3 cos P V I I Z     

    23 sin 3 sinQ V I I Z      

    23 3S V I I Z  

     

    42

  • 8/15/2019 TSDOS Phasor Transformer

    43/248

    Power Relationship

    • Line quantities of a Y-connection load:

     – Power consumed by a load:

     – Relationship between line quantities and

    phase quantities:

     – Power:

    3 cos P V I     

    3 L LL

     I I and V V   

    3 cos LL L P V I   

    43

  • 8/15/2019 TSDOS Phasor Transformer

    44/248

    One-Line Diagram and D-YConversion

    44

  • 8/15/2019 TSDOS Phasor Transformer

    45/248

    Power Transformer 

    45

  • 8/15/2019 TSDOS Phasor Transformer

    46/248

    Ideal Transformer 

    • For an ideal transformer, the following are

    assumed:

    • The windings have zero resistance; therefore,

    the I2R losses in the windings are zero.

    • The core permeability mc is infinite, whichcorresponds to zero core reluctance.

    • There is no leakage flux; that is, the entire flux

    Fc is confined to the core and links bothwindings.

    • There are no core losses. 46

  • 8/15/2019 TSDOS Phasor Transformer

    47/248

    Ideal Transformer 

    • For an ideal transformer, whatever goes

    in should come out:

    47

  • 8/15/2019 TSDOS Phasor Transformer

    48/248

    Ideal Transformer 

    • For an ideal transformer, whatever goes

    in should come out:

    48

  • 8/15/2019 TSDOS Phasor Transformer

    49/248

    Example of an Ideal Transformer 

    •  A single-phase two-winding transformer is

    rated 20 kVA, 480/120 V, 60 Hz. A source

    connected to the 480-V winding supplies

    an impedance load connected to the 120-

    V winding. The load absorbs 15 kVA at

    0.8 pf lagging when the load voltage is118V:

    49

  • 8/15/2019 TSDOS Phasor Transformer

    50/248

    Example of an Ideal Transformer 

    50

  • 8/15/2019 TSDOS Phasor Transformer

    51/248

    Example of an Ideal Transformer 

    • Solution:

    • The complex power at load is

    • The load current is

    • The load impedance is

    • The load impedance referred to the 480-V

    winding is 

    51

  • 8/15/2019 TSDOS Phasor Transformer

    52/248

    Equivalent Circuit of a Practical

    Transformer 

    •  A practical transformer :

    The windings have resistance.

    The core permeability mc is finite.

    The magnetic flux is not entirely confined to the core.

    There are real and reactive power losses in the core. 

    52

  • 8/15/2019 TSDOS Phasor Transformer

    53/248

  • 8/15/2019 TSDOS Phasor Transformer

    54/248

  • 8/15/2019 TSDOS Phasor Transformer

    55/248

    Finding Parameters of a Practical

    Single Phase Transformer 

    • Let’s use an example to illustrate the process.   A single-phase two-winding transformer is rated 20

    kVA, 480/120 volts, 60 Hz.

    Short-circuit test: Rated current at rated frequency is

    applied to the 480-volt winding with the 120-volt

    winding shorted.

    Test Results: V1 =35 volts, P1 =300 W

    Open-circuit test: Rated voltage is applied to 120V,

    with 480V terminal open.

    Test Results: I2 =12 A, P2 =200 W

    55

  • 8/15/2019 TSDOS Phasor Transformer

    56/248

    Finding Parameters of a Practical

    Single Phase Transformer 

    • Short-circuit test:

    56

  • 8/15/2019 TSDOS Phasor Transformer

    57/248

    Finding Parameters of a Practical

    Single Phase Transformer 

    • Open-circuit test:

    57

  • 8/15/2019 TSDOS Phasor Transformer

    58/248

    Finding Parameters of a Practical

    Single Phase Transformer 

    • Discussion

    •  Allocate the impedance of primary and secondary

    windings.

    • In general, you can divide Xeq equally for equivalent

    reactance of primary and secondary windings.

    • Perform DC resistance testing to establish the equivalent

    DC resistance ratio between primary and secondarywindings and allocate the Req accordingly.

    58

  • 8/15/2019 TSDOS Phasor Transformer

    59/248

    Polarity of the Transformer 

    59

  • 8/15/2019 TSDOS Phasor Transformer

    60/248

    Per Unit System

    •Quantity in per unit =

    • Quantity in percent = (Quantity in per 

    unit)*100

    Quantityof  Value Base

    Quantity Actual 

    60

  • 8/15/2019 TSDOS Phasor Transformer

    61/248

    Advantages

    • More meaningful when comparing differentvoltage levels

    • The per unit equivalent impedance of thetransformer remains the same when referredto either the primary or the secondary side

    • The per unit impedance of a transformer in athree-phase system is the same, regardlessthe winding connection

    • The per unit method is independent of voltage changes and phase shifts throughtransformers61

  • 8/15/2019 TSDOS Phasor Transformer

    62/248

  • 8/15/2019 TSDOS Phasor Transformer

    63/248

    Selection of the Base

    • VA, V, I, and Z are four power quantities

    •One has to select two base quantities andderive the other two.

    • Usually the base voltage VbaseLN and base

    complex power Sbase1 are selected for either 

    a single-phase circuit or for one phase of athree-phase circuit.

    • The per-unit values for current and

    impedance can then be derived.63

  • 8/15/2019 TSDOS Phasor Transformer

    64/248

    Selection of the Base

    64

  • 8/15/2019 TSDOS Phasor Transformer

    65/248

    Per Unit Representation of a

    Transformer 

    •  A single-phase two-winding transformer is

    rated 20 kVA, 480/120 volts, 60 Hz.

    • The equivalent leakage impedance of the

    transformer referred to the 120-volt winding,

    denoted winding 2, is Zeq2=0.0525/78.13oW.

    Using the transformer ratings as basevalues, determine the per-unit leakage

    impedance referred to winding 2 and referred

    to winding 1.

    65

  • 8/15/2019 TSDOS Phasor Transformer

    66/248

    Per Unit Representation of a

    Transformer 

    • Solution

    • The values of Sbase, Vbase1, and Vbase2 are from the

    transformer ratings

    • The base impedance on the 120-volt side of the

    transformer is

    • The per-unit leakage impedance referred to

    winding 2 is

    66

  • 8/15/2019 TSDOS Phasor Transformer

    67/248

    Per Unit Representation of a

    Transformer 

    • Solution

    • If Zeq2 is referred to winding 1

    • The base impedance on the 480-volt side of the

    transformer is

    • The per-unit leakage reactance referred to

    winding 1 is

    67

  • 8/15/2019 TSDOS Phasor Transformer

    68/248

    Per Unit Representation of a

    Transformer 

    The per-unit leakage impedance remains

    unchanged when referred from winding 2 to

    winding 1.

    Form the per unit point of view transformer 

    voltage ratio is 1:1 (Rated to rated)

    68

  • 8/15/2019 TSDOS Phasor Transformer

    69/248

    Base Conversion

    • To convert a per-unit impedance from ‘‘old’’to ‘‘new’’ base values, use.

    or 

    69

  • 8/15/2019 TSDOS Phasor Transformer

    70/248

    Example One: Base Conversion

    •  A 50-MVA, 34.5:161 kV transformer with

    10% reactance is connected to a power 

    system where all the other impedance values

    are on a 100 MVA, 34.5 or 161 kV base. The

    reactance of the transformer under new base

    is:

    2.0*50

    100*1.0

    2

    )(

    2

    )(

    )(

    newbase

    old base

    new pu KV 

     KV  Z 

    70

  • 8/15/2019 TSDOS Phasor Transformer

    71/248

    Example Two: Base Conversion

    •  A generator and transformer, as shown

    below, are to be combined into a single

    equivalent reactance on a 100 MVA, 110 kV

    (high voltage side) base.

    71

  • 8/15/2019 TSDOS Phasor Transformer

    72/248

    Example Two: Base Conversion

    • The transformer is operated at 3.9 kV tap.

    • New base voltage at high side is 110 kV.

    • The base voltage at low side is:

    110*3.9/115 = 3.73 kV

    514.1364.015.1

    364.073.3

    9.3*

    30

    100*1.0

    15.173.3

    4

    *25

    100

    *25.0

    )()(

    2

    2

    )(

    2

    2

    )(

    new Xfer new geneq

    new Xfer 

    new gen

     Z  Z  Z 

     Z 

     Z 

    72

  • 8/15/2019 TSDOS Phasor Transformer

    73/248

    Three Phase Transformer 

    • The American standard for marking three-

    phase transformers substitutes H1, H2, and H3

    on the high-voltage terminals and X1, X2, and

    X3 on the low-voltage terminals in place of the

    polarity dots.

    • The ANSI/IEEE standard for transformersstates that the high voltage should lead the low

    voltage by 30o with Y-D or D-Y banks.

    73

  • 8/15/2019 TSDOS Phasor Transformer

    74/248

    Three Phase Transformer 

    • There are nine possible configurations for 

    three-phase transformer.

    • No Phase Shift: Y – Y, YG  – Y, Y – YG, YG  – YG, andD  – D.

    • With Phase Shift: D  – Y, D  – YG, Y – D, and YG  – D.

    • When describing the configuration of atransformer, it is typical to mention the

    configuration of windings closer to the source

    first.

    74

  • 8/15/2019 TSDOS Phasor Transformer

    75/248

    Three Phase Transformer 

    • Schematic representation of a YG  – YG three-phase transformer.

    75

  • 8/15/2019 TSDOS Phasor Transformer

    76/248

    Three Phase Transformer 

    • Schematic representation of a YG  – D three-phase transformer.

    76

  • 8/15/2019 TSDOS Phasor Transformer

    77/248

    Three Phase Transformer 

    • Per unit equivalent circuit of three-phase

    transformers.

    77

  • 8/15/2019 TSDOS Phasor Transformer

    78/248

    Three-Winding Transformer 

    • Three-winding transformers are connected to

    one source and two loads.

    78

  • 8/15/2019 TSDOS Phasor Transformer

    79/248

    Three-Winding Transformer 

    • Z12: per-unit leakage impedance measured

    from winding 1; with winding 2 shorted and

    winding 3 open

    • Z13: per-unit leakage impedance measured

    from winding 1; with winding 3 shorted and

    winding 2 open• Z23: per-unit leakage impedance measured

    from winding 2; with winding 3 shorted and

    winding 1 open79

  • 8/15/2019 TSDOS Phasor Transformer

    80/248

    Three-Winding Transformer 

    • We can be used to evaluate the per-unit series

    impedances Z1, Z2, and Z3 of the three-winding

    transformer equivalent circuit from the per-unitleakage impedances Z12, Z13, and Z23.

    Z12 = Z1 + Z2 

    Z13 = Z1 + Z3 Z23 = Z2 + Z3 

    Z1 = (Z12 + Z13 - Z23)/2

    Z2 = (Z12 + Z23  – Z13)/2

    Z3 = (Z13 + Z23 – Z12)/280

  • 8/15/2019 TSDOS Phasor Transformer

    81/248

    Per Unit Impedance of a Single-

    Phase Three-Winding Transformer 

    • The ratings of a single-phase three-winding

    transformer are: winding 1: 300 MVA; 13:8 kV winding 2: 300 MVA; 199:2 kV

    winding 3: 50 MVA; 19:92 kV

    • The leakage reactances, from short-circuit

    tests, are: X12: 0.10 per unit on a 300-MVA; 13:8-kV base

    X13: 0.16 per unit on a 50-MVA; 13:8-kV base

    X23: 0.14 per unit on a 50-MVA; 199:2-kV base

    81

  • 8/15/2019 TSDOS Phasor Transformer

    82/248

    Per Unit Impedance of a Single-

    Phase Three-Winding Transformer 

    • Winding resistances and exciting current are

    neglected.

    • Calculate the impedances of the per-unit

    equivalent circuit using a base of 300 MVA and

    13.8 kV for terminal 1

    82

  • 8/15/2019 TSDOS Phasor Transformer

    83/248

    Per Unit Impedance of a Single-

    Phase Three-Winding Transformer 

    • Solution

    • Sbase = 300 MVA is the same for all three terminals.

    • The specified voltage base for terminal 1 is Vbase1 =

    13:8 kV.

    • The base voltages for terminals 2 and 3 are then

    Vbase2 = 199:2 kV and Vbase3 = 19:92 kV.

    • Base Conversion

    83

  • 8/15/2019 TSDOS Phasor Transformer

    84/248

    Per Unit Impedance of a Single-

    Phase Three-Winding Transformer 

    • Solution

    84

  • 8/15/2019 TSDOS Phasor Transformer

    85/248

    Autotransformer 

    85

  • 8/15/2019 TSDOS Phasor Transformer

    86/248

    Autotransformer 

    • Pros and Cons of autotransformer 

    • Pros

    • The autotransformer has smaller per-unit leakage

    • impedances than the usual transformer; this results in both

    smaller series voltage drops.

    • The autotransformer also has lower per-unit losses (higher 

    efficiency), lower exciting current, and lower cost if the turns

    ratio is not too large.

    • Cons

    • The electrical connection of the windings allows transient

    overvoltages to pass through the autotransformer more

    easily.86

  • 8/15/2019 TSDOS Phasor Transformer

    87/248

    Autotransformer 

    • Example

     A single-phase two-winding 20-kVA, 480/120-volt

    transformer of is connected as a 120V/600Vautotransformer. Determine (a) the kVA rating, and

    (c) the per-unit leakage impedance (The original

    leakage impedance of the transformer is )

    87

  • 8/15/2019 TSDOS Phasor Transformer

    88/248

    Autotransformer 

    • Solution

     As a normal two-winding transformer rated 20 kVA,

    the rated current of the 480-volt winding is I2 = IH =20000/480 = 41.667 A. As an autotransformer, the

    480-volt winding can carry the same current.

    Therefore, the kVA rating SH = EHIH = 600*41.667 =

    25 kVA.

    88

  • 8/15/2019 TSDOS Phasor Transformer

    89/248

    Autotransformer 

    • Solution

     As an autotransformer, the leakage impedance in

    ohms is the same as for the normal transformer,since the core and windings are the same for both.

    However, the base impedances are different.

    Therefore

    89

  • 8/15/2019 TSDOS Phasor Transformer

    90/248

  • 8/15/2019 TSDOS Phasor Transformer

    91/248

    Transformer with Off-Nominal TurnRatio

    • For a transformer that V1rated and V2rated satisfy

    V1rated = at*V2rated 

    • The selected voltage bases satisfy Vbase1 =

    b*Vbase2. Define c = at/b.

    • Then it can be represented as two transformers

    in series.

    91

  • 8/15/2019 TSDOS Phasor Transformer

    92/248

    Transformer with Off-Nominal TurnRatio

    • The per unit model of the transformer 

    • Set up equations for two-port circuit

    92

  • 8/15/2019 TSDOS Phasor Transformer

    93/248

    Transformer with Off-Nominal TurnRatio

    • Where

    93

  • 8/15/2019 TSDOS Phasor Transformer

    94/248

    Transformer with Off-Nominal TurnRatio

    • p circuit representation for real c.

    94

  • 8/15/2019 TSDOS Phasor Transformer

    95/248

    Transmission System

    95

  • 8/15/2019 TSDOS Phasor Transformer

    96/248

    Transmission System

    • Transmission line design consideration

     An overhead transmission line consists of 

    conductors, insulators, support structures, and, inmost cases, shield wires.

    Other factors of consideration: Electrical,

    Mechanical, Environmental, and Economic

    96

  • 8/15/2019 TSDOS Phasor Transformer

    97/248

    Conductors

    • Conventional Conductors

     ACSR (Aluminum conductor steel reinforced) has

    been in service for more than 80 years.

    In the last 15 to 20 years, the AAAC

    (homogeneous all-aluminum alloy conductor) has

    become quite popular, especially for National Grid

    in the UK where it is now the standard conductor type employed for new and refurbished lines.

    97

  • 8/15/2019 TSDOS Phasor Transformer

    98/248

    Conductors

    • High Temperature Conductors

    • Research in Japan in the 1960s produced a

    series of aluminum-zirconium alloys that resistedthe annealing effects of high temperatures.

    • These alloys can retain their strength at

    temperatures up to 230 C

    • The most common of these alloys—TA1, ZTA1and XTA1—are the basis of a variety of hightemperature conductors.

    98

  • 8/15/2019 TSDOS Phasor Transformer

    99/248

    Conductors

    • Emerging Conductor Technologies

     ACFR: Aluminum conductor carbon fiber 

    reinforced from Japan makes use of the very-lowexpansion coefficient of carbon fiber.

     ACCR: Aluminum Conductor Composite

    Reinforced from 3M.

     Also in the United States, two more designsbased on glass-fiber composites are emerging.

     Aluminum conductor composite core (ACCC),

    Composite reinforced aluminum conductor (CRAC).

     Aluminum Conductor Steel Supported (ACSS)99

  • 8/15/2019 TSDOS Phasor Transformer

    100/248

    Insulator 

    • Insulators for transmission lines above 69 kV

    are typically suspension-type Insulators.

    100

  • 8/15/2019 TSDOS Phasor Transformer

    101/248

    Support Structures

    • Transmission lines employ a variety of 

    support structures.

    101

  • 8/15/2019 TSDOS Phasor Transformer

    102/248

    Shield Wires

    • Shield wires located above the phase

    conductors protect the phase conductors

    against lightning.

    • They are usually high- or extra-high-strength

    steel, Alumoweld, or ACSR with much

    smaller cross section than the phaseconductors.

    102

  • 8/15/2019 TSDOS Phasor Transformer

    103/248

    Transmission Line Parameters

    • Resistance

    The dc resistance of a conductor at a specified

    temperature T is

    103

  • 8/15/2019 TSDOS Phasor Transformer

    104/248

    Transmission Line Parameters

    • Resistance

    In English units, conductor cross sectional area is

    expressed in circular mils (cmil). One inch equals1000 mils and 1 cmil equals p/4 sq mil.

     A circle with diameter D in has an area

    or 

    where 1000 D mil = d mil104

  • 8/15/2019 TSDOS Phasor Transformer

    105/248

    Transmission Line Parameters

    • Resistance

    Resistivity depends on the conductor metal.

     Annealed copper is the international standard for measuring resistivity r.

    Conductor resistance depends on the following

    factors:

    Spiraling Temperature

    Frequency (‘‘skin effect’’) 

    Current magnitude—magnetic conductors

    105

  • 8/15/2019 TSDOS Phasor Transformer

    106/248

    Transmission Line Parameters

    • Resistance

    106

  • 8/15/2019 TSDOS Phasor Transformer

    107/248

  • 8/15/2019 TSDOS Phasor Transformer

    108/248

    Transmission Line Parameters

    • Inductance: Solid Cylindrical Conductor 

    The inductance of a magnetic circuit that has a

    constant permeability m can be obtained bydetermining the following:

    Magnetic field intensity H, from Ampere’s law.

    Magnetic flux density B (B = mH).

    Flux linkages l. Inductance from flux linkages per ampere (L = l/I).

    108

  • 8/15/2019 TSDOS Phasor Transformer

    109/248

    Transmission Line Parameters

    • Inductance: Solid Cylindrical Conductor 

    For simplicity, assume that the conductor 

    is sufficiently long that end effects are neglected,

    is nonmagnetic (m = m0 = 4p x10-7 H/m)

    has a uniform current density (skin effect is neglected)

    109

  • 8/15/2019 TSDOS Phasor Transformer

    110/248

    Transmission Line Parameters

    • Inductance: Solid Cylindrical Conductor 

     Ampere’s law states that 

    The magnetic field inside the conductor 

    Select the dashed circle of radius x < r 

    110

  • 8/15/2019 TSDOS Phasor Transformer

    111/248

    Transmission Line Parameters

    • Inductance: Solid Cylindrical Conductor 

    The magnetic field inside the conductor 

    Flux Density B

    The differential flux dF per-unit length of conductor inthe cross-hatched rectangle of width dx shown in

    previous figure (dF = Bxdx Wb/m)

    Computation of the differential flux linkage dl in therectangle is tricky since only the fraction (x/r)2 of the total

    current I is linked by the flux.

    111

  • 8/15/2019 TSDOS Phasor Transformer

    112/248

    Transmission Line Parameters

    • Inductance: Solid Cylindrical Conductor 

    The magnetic field inside the conductor 

    Integrating the dl from x = 0 to x = r determines the totalflux linkages lint inside the conductor.

    The internal inductance Lint per-unit length of conductor due to this flux linkage is then

    112

  • 8/15/2019 TSDOS Phasor Transformer

    113/248

    Transmission Line Parameters

    • Inductance: Solid Cylindrical Conductor 

    The magnetic field outside the conductor 

    Select the dashed circle of radius x > r shown in Figureas the closed contour that encloses the entire current I.

    113

  • 8/15/2019 TSDOS Phasor Transformer

    114/248

    Transmission Line Parameters

    • Inductance: Solid Cylindrical Conductor 

    The magnetic field outside the conductor 

    Integrating dl between two external points at distancesD1 and D2 from the conductor center gives the external

    flux linkage l12 between D1 and D2.

    114

  • 8/15/2019 TSDOS Phasor Transformer

    115/248

    Transmission Line Parameters

    • Inductance: Solid Cylindrical Conductor 

    The total flux lP linking the conductor out to

    external point P at distance D is the sum of theinternal flux linkage and the external flux linkage

    from D1 = r to D2 = D.

    where

    115

  • 8/15/2019 TSDOS Phasor Transformer

    116/248

  • 8/15/2019 TSDOS Phasor Transformer

    117/248

    Transmission Line Parameters

    • Inductance: Solid Cylindrical Conductor 

    The flux linkage lkPm, which links conductor k out

    to P due to Im is:

     Assume Dkm>>r 

    117

  • 8/15/2019 TSDOS Phasor Transformer

    118/248

    Transmission Line Parameters

    • Inductance: Solid Cylindrical Conductor 

    Rearrange the equation:

    Replace IM with

    118

  • 8/15/2019 TSDOS Phasor Transformer

    119/248

  • 8/15/2019 TSDOS Phasor Transformer

    120/248

    Transmission Line Parameters

    • Inductance: Single-phase two-wire

    where

    120

  • 8/15/2019 TSDOS Phasor Transformer

    121/248

    Transmission Line Parameters

    • Inductance: Single-phase two-wire

    121

  • 8/15/2019 TSDOS Phasor Transformer

    122/248

    Transmission Line Parameters

    • Inductance: Single-phase two-wire

    • Total inductance

    • If conductors X and Y are the same

    122

  • 8/15/2019 TSDOS Phasor Transformer

    123/248

    Transmission Line Parameters

    • Inductance: Three-phase three-wire with

    equal spacing

    123

  • 8/15/2019 TSDOS Phasor Transformer

    124/248

    Transmission Line Parameters

    • Inductance: Composite conductors

    124

  • 8/15/2019 TSDOS Phasor Transformer

    125/248

    Transmission Line Parameters

    • Inductance: Composite conductors

    • Since only the fraction (1/N) of the total conductor 

    current I is linked by this flux, the flux linkage lk of (the current in) subconductor k is

    • The total flux linkage of conductor x is

    125

  • 8/15/2019 TSDOS Phasor Transformer

    126/248

    Transmission Line Parameters

    • Inductance: Composite conductors

    • Using ln A = ln A and ∑ ln Ak = ln Π Ak, we can

    rewrite the previous equation as

    • The Inductor 

    126

  • 8/15/2019 TSDOS Phasor Transformer

    127/248

    Transmission Line Parameters

    • Inductance: Composite conductors

    Dxy is called the geometric mean distance or GMD

    between conductors x and y. Dxx is called the geometric mean radius or GMR of 

    conductor x

    Similarly, for conductor y,.

    127

  • 8/15/2019 TSDOS Phasor Transformer

    128/248

    Transmission Line Parameters

    • Example

    For a single-phase multiple conductor circuit

    shown below, find GMR, GMD, and Inductance

    128

  • 8/15/2019 TSDOS Phasor Transformer

    129/248

    Transmission Line Parameters

    • Solution

    For N=3 and M=2’, GMD and GMR can be

    expressed as:

    129

  • 8/15/2019 TSDOS Phasor Transformer

    130/248

    Transmission Line Parameters

    • Solution

    For N=3 and M=2’, GMD and GMR can be

    expressed as:

    130

  • 8/15/2019 TSDOS Phasor Transformer

    131/248

    Transmission Line Parameters

    • Solution

    For N=3 and M=2’, GMD and GMR can be

    expressed as:

    131

  • 8/15/2019 TSDOS Phasor Transformer

    132/248

    Transmission Line Parameters

    • Solution

    For N=3 and M=2’, GMD and GMR can be

    expressed as:

    132

  • 8/15/2019 TSDOS Phasor Transformer

    133/248

    Transmission Line Parameters

    • Solution

    For N=3 and M=2’, GMD and GMR can be

    expressed as:

    133

  • 8/15/2019 TSDOS Phasor Transformer

    134/248

    Transmission Line Parameters

    • Transposition

    If the spacings between phases are unequal, then

    balanced positive-sequence flux linkages are notobtained from balanced positive-sequence

    currents. Balance can be restored by exchanging

    the conductor positions along the line, a technique

    called transposition.

    134

  • 8/15/2019 TSDOS Phasor Transformer

    135/248

    Transmission Line Parameters

    • Transposition

    The total flux linking the phase a conductor while it

    is in position 1 is

    Similarly, the total flux linkage of this conductor 

    while it is in positions 2 and 3 is

    135

  • 8/15/2019 TSDOS Phasor Transformer

    136/248

    Transmission Line Parameters

    • Transposition

    The average of the above flux linkages is

    136

  • 8/15/2019 TSDOS Phasor Transformer

    137/248

    Transmission Line Parameters

    • Transposition

    The average inductance of phase a is

    Defining

    Then,

    137

  • 8/15/2019 TSDOS Phasor Transformer

    138/248

    Transmission Line Parameters

    • Bundle conductors

    If the conductors are stranded and the bundle

    spacing d is large compared to the conductor outside radius, each stranded conductor is first

    replaced by an equivalent solid cylindrical

    conductor with GMR = DS. Then the bundle is

    replaced by one equivalent conductor with GMR =DSL.

    138

  • 8/15/2019 TSDOS Phasor Transformer

    139/248

    Transmission Line Parameters

    • Bundle conductors

    Two-conductor bundle.

    Three-conductor bundle

    Four-conductor bundle

    139

  • 8/15/2019 TSDOS Phasor Transformer

    140/248

  • 8/15/2019 TSDOS Phasor Transformer

    141/248

    Transmission Line Parameters

    • Series Impedances: Three-phase line with

    neutral conductors and earth return

    • Each earth return conductor carries the negative of its overhead conductor current, has a GMR

    denoted Dk’k’, distance Dkk’ from its overhead

    conductor, and resistance Rk’ given by:

    where r is the earth resistivity in ohm-meters and f is frequency in hertz.141

  • 8/15/2019 TSDOS Phasor Transformer

    142/248

    Transmission Line Parameters

    • Series Impedances: Three-phase line with

    neutral conductors and earth return

    • Earth resistivities and 60-Hz equivalent conductor distances are shown in the table. It is common

    practice to select r = 100 Wm when actual data areunavailable

    142

  • 8/15/2019 TSDOS Phasor Transformer

    143/248

    Transmission Line Parameters

    • Series Impedances calculation

    First, renumber the overhead conductors from 1 to

    (3 + N), beginning with the phase conductors, thenoverhead neutral conductors.

    The sum of the currents in all the conductors is

    zero

    the flux linking overhead conductor k is

    143

  • 8/15/2019 TSDOS Phasor Transformer

    144/248

    Transmission Line Parameters

    • Series Impedances calculation

    Convert the flux linkage in matrix format: l = L I . Where

    When k = m, Dkk is the GMR of conductor k. When

    k ≠ m, Dkm is the distance between conductors k

    and m144

  • 8/15/2019 TSDOS Phasor Transformer

    145/248

    Transmission Line Parameters

    • Circuit representation of a 1-meter section

    series-phase impedances

    145

  • 8/15/2019 TSDOS Phasor Transformer

    146/248

    Transmission Line Parameters

    • Using this circuit, the vector of voltage drops

    across the conductors is

    where L is given in previous slide and R is a (3 + N) x (3 + N) matrix

    of conductor resistances.146

  • 8/15/2019 TSDOS Phasor Transformer

    147/248

    Transmission Line Parameters

    • Our objective now is to reduce the (3 + N)

    equations to three equations

    147

  • 8/15/2019 TSDOS Phasor Transformer

    148/248

    Transmission Line Parameters

    • The diagonal elements of this matrix are

    • The off diagonal elements of this matrix are

    • Partition the matrix

    where

    148

  • 8/15/2019 TSDOS Phasor Transformer

    149/248

    Transmission Line Parameters

    • Solve the matrix

    • ZP is a 3x3 matrix

     

     

    149

  • 8/15/2019 TSDOS Phasor Transformer

    150/248

    Transmission Line Parameters

    • If the line is completely transposed

    where

    150

    Electric Field and Voltage: Solid

  • 8/15/2019 TSDOS Phasor Transformer

    151/248

    Cylindrical Conductors

    • The capacitance between conductors in a

    medium with constant permittivity e can be

    obtained by determining the following: Electric field strength E, from Gauss’s law 

    Voltage between conductors

    Capacitance from charge per unit volt (C = q/V)

    151

    Electric Field and Voltage: Solid

  • 8/15/2019 TSDOS Phasor Transformer

    152/248

    Cylindrical Conductors

    • Gauss’s law states that the total electric fluxleaving a closed surface equals the total charge

    within the volume enclosed by the surface.• The normal component of electric flux density

    integrated over a closed surface equals the

    charge enclosed:

    where D ┴ denotes the normal component of electric flux density, E ┴  

    denotes the normal component of electric field strength, and ds denotes

    the differential surface area.152

    Electric Field and Voltage: Solid

  • 8/15/2019 TSDOS Phasor Transformer

    153/248

    Cylindrical Conductors

    • Electric field lines originate from positive charges

    and terminate at negative charges.

    •  A solid cylindrical conductor withradius r and with charge q coulombs

    per meter (assumed positive in the

    figure), uniformly distributed on the

    conductor surface.

    • For simplicity, assume that theconductor is (1) sufficiently long that

    end effects are negligible, and (2) a

    perfect conductor (that is, zero

    resistivity, r = 0).153

    Electric Field and Voltage: Solid

  • 8/15/2019 TSDOS Phasor Transformer

    154/248

    Cylindrical Conductors

    • Inside the perfect conductor, Ohm’s law gives Eint = rJ = 0. That is, the internal electric field Eint is

    zero.• To determine the electric field outside the

    conductor, select the cylinder with radius x > r 

    and with 1-meter length as the closed surface for 

    Gauss’s law.

    • Due to the uniform charge distribution, the

    electric field strength Ex is constant on the

    cylinder154

    Electric Field and Voltage: Solid

  • 8/15/2019 TSDOS Phasor Transformer

    155/248

    Cylindrical Conductors

    • There is no tangential component of Ex, so the

    electric field is radial to the conductor.

    • For a conductor in free space

    155

    Electric Field and Voltage: Solid

  • 8/15/2019 TSDOS Phasor Transformer

    156/248

    Cylindrical Conductors

    • Concentric cylinders surrounding the conductor 

    are constant potential surfaces. The potential

    difference between two concentric cylinders atdistances D1 and D2 from the conductor center 

    is.

    156

    Electric Field and Voltage: Solid

  • 8/15/2019 TSDOS Phasor Transformer

    157/248

    Cylindrical Conductors

    • Now apply this equation to the array of M solid

    cylindrical conductors shown below:

    157

    Electric Field and Voltage: Solid

  • 8/15/2019 TSDOS Phasor Transformer

    158/248

    Cylindrical Conductors

    •  Assume that each conductor m has a charge qm 

    C/m uniformly distributed along the conductor.

    The voltage Vkim between conductors k and i dueto the charge qm acting alone is

    • Using superposition, the voltage Vki betweenconductors k and i due to all the charges is

    where Dmm = r m when k = m or i = m

    158

    T i i i P

  • 8/15/2019 TSDOS Phasor Transformer

    159/248

    Transmission Line Parameters

    • Capacitance: Single-phase two-wire line

    •  Assume that the

    conductors are energizedby a voltage source such

    that conductor x has a

    uniform charge q C/m and,

    assuming conservation of charge, conductor y has an

    equal quantity of negative

    charge -q.

    159

    T i i Li P t

  • 8/15/2019 TSDOS Phasor Transformer

    160/248

    Transmission Line Parameters

    • Capacitance: Single-phase two-wire line

    • Using Dxy = Dyx = D, Dxx = r x, and Dyy = r y.

    • For 1-meter length, the capacitor between conductors

    is

    160

    T i i Li P t

  • 8/15/2019 TSDOS Phasor Transformer

    161/248

    Transmission Line Parameters

    • Capacitance: Single-phase two-wire line

    • If the two-wire line is supplied by a transformer with a

    grounded center tap, then the voltage between eachconductor and ground is one-half of the line to line

    voltage (Assume r x = r y).

    161

    T i i Li P t

  • 8/15/2019 TSDOS Phasor Transformer

    162/248

    Transmission Line Parameters

    • Capacitance: Three-phase, three-wire and

    equal spacing

    • To determine the positive-sequence capacitance,assume positive-sequence charges qa, qb, qc such

    that qa + qb + qc = 0. Using Daa = Dbb = r, and Dab =

    Dba = Dca = Dcb = D, we can rewrite the equation

    162

    T i i Li P t

  • 8/15/2019 TSDOS Phasor Transformer

    163/248

    Transmission Line Parameters

    • Capacitance: Three-phase, three-wire and equal

    spacing

    • Similarly,

    163

    T i i Li P t

  • 8/15/2019 TSDOS Phasor Transformer

    164/248

    Transmission Line Parameters

    • Capacitance: Three-phase, three-wire and equal

    spacing

    • For balanced positive-sequence voltages

    • Therefore,164

    T i i Li P t

  • 8/15/2019 TSDOS Phasor Transformer

    165/248

    Transmission Line Parameters

    • Capacitance: Three-phase, three-wire and equal

    spacing

    • Therefore,

    and

    165

    T i i Li P t

  • 8/15/2019 TSDOS Phasor Transformer

    166/248

    Transmission Line Parameters

    • Capacitance: General forms

    • For a complete transpose line, the line to neutral

    capacitance can be expressed as:

    where

    166

    T i i Li P t

  • 8/15/2019 TSDOS Phasor Transformer

    167/248

    Transmission Line Parameters

    • Capacitance: General forms

    • For a three-phase balanced system with bundle

    conductors:• qa + qb + qc = 0 for a balanced system. Assume that the

    conductors in each bundle, which are in parallel, share the

    charges equally.

    •  Also assume that the phase spacings are much larger than

    the bundle spacings.

    167

    T i i Li P t

  • 8/15/2019 TSDOS Phasor Transformer

    168/248

    Transmission Line Parameters

    • Capacitance: General forms

    • For a three-phase balanced system with bundle

    conductors:• Using the following configuration (Three-phase, two

    conductors per bundle) as example.

    168

    Transmission Line Parameters

  • 8/15/2019 TSDOS Phasor Transformer

    169/248

    Transmission Line Parameters

    • Capacitance: General forms

    • For a three-phase balanced system with bundle

    conductors:

    169

    Transmission Line Parameters

  • 8/15/2019 TSDOS Phasor Transformer

    170/248

    Transmission Line Parameters

    • Capacitance: General forms

    • For transposed line

    where

    • Similarly

    • Deq is the geometric mean of the distances between

    phases170

    Transmission Line Parameters

  • 8/15/2019 TSDOS Phasor Transformer

    171/248

    Transmission Line Parameters

    • Shunt Admittances: Line with neutral conductors

    and earth return

    Single conductor and earth plane

    • The effect of the earth plane isdescribed as follows. Consider asingle conductor with uniform charge

    distribution and with height H above

    a perfectly conducting earth plane,

    as shown in Figure. When the

    conductor has a positive charge,an equal quantity of negative charge is induced on the earth.

    The electric field lines will originate from the positive charges on

    the conductor and terminate at the negative charges on the

    earth. Also, the electric field lines are perpendicular to the

    surfaces of the conductor and earth

    171

    Transmission Line Parameters

  • 8/15/2019 TSDOS Phasor Transformer

    172/248

    Transmission Line Parameters

    • Shunt Admittances: Line with neutral conductors

    and earth return

    Earth place is replaced by image conductor 

    • Now replace the earth by theimage conductor which has the

    same radius as the original

    conductor, lies directly below the

    original conductor with conductor 

    separation H11 = 2H, and has anequal quantity of negative charge.

    Therefore, the voltage between

    any two points above the earth is

    the same in both figures.172

    Example: Capacitance on single-phase line

  • 8/15/2019 TSDOS Phasor Transformer

    173/248

    phase line

    • If a 20 miles of single-phase line operating at

    20kV and 60 Hz consists of two 4/0 12-strand

    copper conductors with 5 ft spacing betweenconductor centers, determine the line-to-line

    capacitance in F and the line-to-line admittance

    in S.

    173

    Example: Capacitance on single-phase line

  • 8/15/2019 TSDOS Phasor Transformer

    174/248

    phase line

    • Solution

    • The outside radius of a 4/0 12-strand copper 

    conductor is 0.023 ft.

    174

    Example: Capacitance on single-phase line (Consider earth)

  • 8/15/2019 TSDOS Phasor Transformer

    175/248

    phase line (Consider earth)

    • For the same single phase line as the previous

    example with18-ft average line height. Determine

    the effect of the earth on capacitance. Assume aperfectly conducting earth plane.

    175

    Example: Capacitance on single-phase line (Consider earth)

  • 8/15/2019 TSDOS Phasor Transformer

    176/248

    phase line (Consider earth)

    • Solution

    • The earth plane is replaced by a separate image

    conductor for each overhead conductor with proper charge.

    176

    Example: Capacitance on single-phase line (Consider earth)

  • 8/15/2019 TSDOS Phasor Transformer

    177/248

    phase line (Consider earth)

    • Solution

    • The voltage between conductors x and y is

    177

    Example: Capacitance on single-phase line (Consider earth)

  • 8/15/2019 TSDOS Phasor Transformer

    178/248

    phase line (Consider earth)

    • Solution

    • The line to line capacitor is

    • Using D = 5 ft, r = 0.023 ft, Hxx = 2H = 36 ft, and Hxy =

    36.346 ft.

    178

    Transmission Line Parameters

  • 8/15/2019 TSDOS Phasor Transformer

    179/248

    Transmission Line Parameters

    • Shunt Admittances: General form

    • For the three-phase line with N

    neutral conductors shown inFigure, the perfectly

    conducting earth plane is

    replaced by a separate image

    conductor for each overheadconductor that carry opposite

    charge.

    179

    Transmission Line Parameters

  • 8/15/2019 TSDOS Phasor Transformer

    180/248

    Transmission Line Parameters

    • Shunt Admittances: General form

    The voltage Vkk’ between any conductor k and its

    image conductor k’ is 

    where Dkk = r k and Dkm is the distance between

    overhead conductors k and m. Hkm is the distance

    between overhead conductor k and image conductor m.180

    Transmission Line Parameters

  • 8/15/2019 TSDOS Phasor Transformer

    181/248

    Transmission Line Parameters

    • Shunt Admittances: General form

    By symmetry, the voltage Vkn between conductor k

    and the earth is one-half of Vkk’.

    where (k = a; b; c; n1; n2; . . . ; nN) and (m = a; b; c; n1;

    n2; . . . ; nN) Since all the neutral conductors are grounded to the

    earth, Vkn = 0 for k = n1; n2; . . . ; nN.

    181

    Transmission Line Parameters

  • 8/15/2019 TSDOS Phasor Transformer

    182/248

    Transmission Line Parameters

    • Shunt Admittances: General form

    In matrix form

    182

    Transmission Line Parameters

  • 8/15/2019 TSDOS Phasor Transformer

    183/248

    Transmission Line Parameters

    • Shunt Admittances: General form

    The elements of the (3 + N) X (3 + N) matrix P are

    where (k = a; b; c; n1; n2; . . . ; nN) and (m = a; b; c; n1;

    n2; . . . ; nN)

    The matrix can then be partitioned into

    183

    Transmission Line Parameters

  • 8/15/2019 TSDOS Phasor Transformer

    184/248

    Transmission Line Parameters

    • Shunt Admittances: General form

    The matrix can be rewritten into

    or 

    where

    184

  • 8/15/2019 TSDOS Phasor Transformer

    185/248

    Electric Field at Conductor Surfaces and at Ground Level

  • 8/15/2019 TSDOS Phasor Transformer

    186/248

    Surfaces and at Ground Level

    • When the electric field strength at a conductor 

    surface exceeds the breakdown strength of air,

    current discharges occur.• This phenomenon, called corona, causes

    additional line losses (corona loss),

    communications interference, and audible noise.

    • When line capacitances are determined and

    conductor voltages are known, the conductor 

    charges can be calculated.186

    Electric Field at Conductor Surfaces and at Ground Level

  • 8/15/2019 TSDOS Phasor Transformer

    187/248

    Surfaces and at Ground Level

    • Then the electric field strength at the surface of 

    one phase conductor, neglecting the electric

    fields due to charges on other phase conductorsand neutral wires is

    where r is the conductor outside radius

    187

  • 8/15/2019 TSDOS Phasor Transformer

    188/248

    Electric Field at Conductor Surfaces and at Ground Level

  • 8/15/2019 TSDOS Phasor Transformer

    189/248

    Surfaces and at Ground Level

    • For the arrangement shown in the figure, the

    maximum electric field strength at the surface

    of one conductor due to all charges in a bundlecan be obtained by the vector addition of 

    electric fields.

    189

    Electric Field at Conductor Surfaces and at Ground Level

  • 8/15/2019 TSDOS Phasor Transformer

    190/248

    Surfaces and at Ground Level

    • Two-conductor bundle (Nb = 2)

    • Three-conductor bundle (Nb = 3)

    • Four-conductor bundle (Nb = 4)

    190

  • 8/15/2019 TSDOS Phasor Transformer

    191/248

    Electric Field at Conductor Surfaces and at Ground Level

  • 8/15/2019 TSDOS Phasor Transformer

    192/248

    Surfaces and at Ground Level

    Transmission-line heights are designed to

    maintain discharge currents below prescribed

    levels for any equipment that may be on theright-of-way. Table shows examples of 

    maximum ground level electric field strength.

    192

    Electric Field at Conductor Surfaces and at Ground Level

  • 8/15/2019 TSDOS Phasor Transformer

    193/248

    Surfaces and at Ground Level

     As shown in Figure, the ground-level electric

    field strength due to charged conductor k and its

    image conductor is perpendicular to the earthplane, will be:

    193

  • 8/15/2019 TSDOS Phasor Transformer

    194/248

    Parallel Circuits on Three-PhaseLines

  • 8/15/2019 TSDOS Phasor Transformer

    195/248

    Lines

    • Consider the double-circuit line shown below.

    • Since both are connected in parallel, they have

    the same series-voltage drop for each phase.Following the same procedure as described

    before, we can write 2(6 X N) equations.

    195

  • 8/15/2019 TSDOS Phasor Transformer

    196/248

    Parallel Circuits on Three-PhaseLines

  • 8/15/2019 TSDOS Phasor Transformer

    197/248

    es

    •  Adding IP1 and IP2 and solving for EP

    • ZPeq is the equivalent 3 X 3 series phaseimpedance matrix of the double circuit line. The

    matrices YB and YC account for the inductive

    coupling between the two circuits.

    where

    197

    Parallel Circuits on Three-PhaseLines

  • 8/15/2019 TSDOS Phasor Transformer

    198/248

    • Similar procedure can be used to obtain the

    shunt admittance matrix.

    • Following the same idea, we can write (6 + N)equations. After eliminating the neutral wire

    charges, we obtain

    where VP is the vector of phase-to-neutral voltages, and qP1 and qP2 are the

    vectors of phase-conductor charges for lines 1 and 2. CP is a 6 X 6 capacitance

    matrix that is partitioned into four 3 X 3 matrices C A, CB, CC, and CD 198

    Parallel Circuits on Three-PhaseLines

  • 8/15/2019 TSDOS Phasor Transformer

    199/248

    •  Adding qP1 and qP2.

    where

    199

    Transmission Lines: Steady StateOperation

  • 8/15/2019 TSDOS Phasor Transformer

    200/248

    p

    200

    Medium and Short LineApproximation

  • 8/15/2019 TSDOS Phasor Transformer

    201/248

    pp

    • It is convenient to represent a transmission line

    by the two-port network shown below.

    • The relation between the sending-end andreceiving-end quantities can be written as:

    201

    or 

    Medium and Short LineApproximation

  • 8/15/2019 TSDOS Phasor Transformer

    202/248

    pp

    •  A, B, C, and D are parameters that depend on

    the transmission-line constants R, L, C, and G.

    The ABCD parameters are, in general, complexnumbers. A and D are dimensionless. B has

    units of ohms, and C has units of Siemens.

    • The circuit in previous figure represents a short

    transmission line, usually applied to overhead60-Hz lines less than 80 km (50 miles) long.

    Only the series resistance and reactance are

    included. The shunt admittance is neglected.202

    Medium and Short LineApproximation

  • 8/15/2019 TSDOS Phasor Transformer

    203/248

    pp

    • The circuit applies to either single-phase or 

    completely transposed three-phase lines

    operating under balanced conditions.• We can derive the two-port circuit and rewrite

    the matrix

    203

    Medium and Short LineApproximation

  • 8/15/2019 TSDOS Phasor Transformer

    204/248

    pp

    • For medium-length lines, typically ranging from

    80 to 250 km (50 to 150 Miles) at 60 Hz, it is

    common to lump the total shunt capacitanceand locate half at each end of the line. Such a

    circuit, called a nominal p circuit.

    204

    Medium and Short LineApproximation

  • 8/15/2019 TSDOS Phasor Transformer

    205/248

    pp

    • Following the basic circuit theory to obtain the

     ABCD parameters of the nominal p circuit.

    205

    Medium and Short LineApproximation

  • 8/15/2019 TSDOS Phasor Transformer

    206/248

    pp

    • Rewrite the equations into matrix form.

    • Note that for both the short and medium-lengthlines, the relation AD - BC = 1 is verified. Note

    also that since the line is the same when

    viewed from either end, A = D.206

    Medium and Short LineApproximation

  • 8/15/2019 TSDOS Phasor Transformer

    207/248

    pp

    • Summary of Medium and Short Line

    Representation.

    207

    Medium and Short LineApproximation

  • 8/15/2019 TSDOS Phasor Transformer

    208/248

    • Summary of Medium and Short Line

    Representation.

    208

    Medium and Short LineApproximation

  • 8/15/2019 TSDOS Phasor Transformer

    209/248

    • Voltage Regulation

    • The “percent VR” is the percent voltageregulation, |VRNL| is the magnitude of the no-

    load receiving-end voltage, and |VRFL

    | is the

    magnitude of the full load receiving-end

    voltage.

    209

    Medium and Short LineApproximation

  • 8/15/2019 TSDOS Phasor Transformer

    210/248

    • In addition to voltage regulation, line loadability

    is an important issue. Three major line-loading

    limits are: (1) the thermal limit, (2) the voltage-drop limit, and (3) the steady-state stability limit.

    210

    Transmission Line DifferentialEquations

  • 8/15/2019 TSDOS Phasor Transformer

    211/248

    • Though we have used lumped model for 

    medium and short transmission lines, the R, L,

    and C of line parameters are uniformlydistributed along the length of the line. The

    circuit shown below is the better way for 

    transmission line representation.

    211

    G is usually neglected for 

    overhead 60-Hz lines

    Transmission Line DifferentialEquations

  • 8/15/2019 TSDOS Phasor Transformer

    212/248

    • From basic circuit theory:

    212

     

     

     

    Transmission Line DifferentialEquations

  • 8/15/2019 TSDOS Phasor Transformer

    213/248

    •  A1 and A2 are integration constants and

    • Using

    213

    Zc is the characteristic impedance

    and is the propagation constant

  • 8/15/2019 TSDOS Phasor Transformer

    214/248

    Transmission Line DifferentialEquations

  • 8/15/2019 TSDOS Phasor Transformer

    215/248

    • Substitute these values into V(x) and I(x).

    215

    Transmission Line DifferentialEquations

  • 8/15/2019 TSDOS Phasor Transformer

    216/248

    • Use the hyperbolic functions cosh and sinh.

    216

      where

    Transmission Line DifferentialEquations

  • 8/15/2019 TSDOS Phasor Transformer

    217/248

    • The propagation constant is a complexquantity with real and imaginary parts denoted

    and ( = + j m-1

    ).

    217

    Transmission Line DifferentialEquations

  • 8/15/2019 TSDOS Phasor Transformer

    218/248

    •  ABCD parameters for short, medium, long, and

    lossless lines.

    218

    Example: Exact Transmission LineModel

  • 8/15/2019 TSDOS Phasor Transformer

    219/248

    •  A three-phase 765-kV, 60-Hz, 300-km,

    completely transposed line has the following

    positive-sequence impedance and admittance:

    •  Assuming positive-sequence operation,

    calculate the exact ABCD parameters of the

    line. Compare the exact B parameter with that

    of the nominal p circuit.219

    Example: Exact Transmission LineModel

  • 8/15/2019 TSDOS Phasor Transformer

    220/248

    • Solution

    220

    Example: Exact Transmission LineModel

  • 8/15/2019 TSDOS Phasor Transformer

    221/248

    • Solution

    221

    Example: Exact Transmission LineModel

  • 8/15/2019 TSDOS Phasor Transformer

    222/248

    • Solution

    222

    Example: Exact Transmission LineModel

  • 8/15/2019 TSDOS Phasor Transformer

    223/248

    • Solution

    • The B parameter for the nominal p circuit is

    223

    Equivalent p Circuit for LongTransmission Line

  • 8/15/2019 TSDOS Phasor Transformer

    224/248

    • Many computer programs used in power 

    system analysis and design assume circuit

    representations of components.• It is therefore convenient to represent the

    terminal characteristics of a transmission line

    by an equivalent circuit.

    224

    Equivalent p Circuit for LongTransmission Line

  • 8/15/2019 TSDOS Phasor Transformer

    225/248

    • The circuit shown

    below is called an

    equivalent p circuit. Itis identical instructure to the

    nominal p circuit

    except that Z’ and Y’are used instead of Zand Y.

    225

    Equivalent p Circuit for LongTransmission Line

  • 8/15/2019 TSDOS Phasor Transformer

    226/248

    • The ABCD parameters of the equivalent p circuit, which has the same structure as the

    nominal p, are

    226

    Lossless Line

  • 8/15/2019 TSDOS Phasor Transformer

    227/248

    • It is easier to use lossless line (R = G = 0) to

    explain the concept of surge impedance,

    wavelength, surge impedance loading, voltageprofiles, and steady-state stability limit.

    227

    Surge Impedance

  • 8/15/2019 TSDOS Phasor Transformer

    228/248

    • For a lossless line,

    • The characteristic impedance Zc, commonly called

    surge impedance for a lossless line, is pure real -

    that is, resistive. The propagation constant = j ispure imaginary228

    and

    where

    Wavelength

  • 8/15/2019 TSDOS Phasor Transformer

    229/248

    •  A wavelength is the distance required to

    change the phase of the voltage or current by

    2p radians.• For a lossless line

    229

    and

    Wavelength

  • 8/15/2019 TSDOS Phasor Transformer

    230/248

    • V(x) and I (x) change phase by 2p radianswhen x = 2p/. Denoting wavelength by l.

    • is the propagation velocity of voltage

    and current waves along a lossless line. This isaround 3X108 m/sec for overhead lines. For 

    60Hz system, the wavelength is around

    5000km.230

    Surge Impedance Loading

  • 8/15/2019 TSDOS Phasor Transformer

    231/248

    • Surge impedance loading (SIL) is the power 

    delivered by a lossless line to a load resistance

    equal to the surge impedance Zc.

    231

    Surge Impedance Loading

  • 8/15/2019 TSDOS Phasor Transformer

    232/248

    •  At SIL, the voltage profile is flat. That is, the

    voltage magnitude at any point x along a

    lossless line at SIL is constant.

    232

    Surge Impedance Loading

  • 8/15/2019 TSDOS Phasor Transformer

    233/248

    233

    • The complex power flowing at any point x

    along the line is

    Surge Impedance Loading

  • 8/15/2019 TSDOS Phasor Transformer

    234/248

    234

    • The real power flow along a lossless line at

    SIL remains constant from the sending end to

    the receiving end. The reactive power flow iszero.

    •  At rated line voltage SIL of a line is V2rated/Zc.

    Surge Impedance Loading

  • 8/15/2019 TSDOS Phasor Transformer

    235/248

    235

    • This table shows surge impedance and SIL

    values for typical overhead 60-Hz three-

    phase line.

  • 8/15/2019 TSDOS Phasor Transformer

    236/248

    Steady State Stability Limit

  • 8/15/2019 TSDOS Phasor Transformer

    237/248

    237

    • The equivalent p circuit can be used to obtainan equation for the real power delivered by a

    lossless line.

    •  Assume that the voltage magnitudes VS and

    VR at the ends of the line are held constant.

    •  Also, let d denote the voltage-phase angle atthe sending end with respect to the receivingend.

    Steady State Stability Limit

  • 8/15/2019 TSDOS Phasor Transformer

    238/248

    238

    • From circuit theory

    • The complex power SR delivered to the

    receiving end is

    Steady State Stability Limit

  • 8/15/2019 TSDOS Phasor Transformer

    239/248

    239

    • The real power is

    Steady State Stability Limit

  • 8/15/2019 TSDOS Phasor Transformer

    240/248

    240

    • Pmax represents the theoretical steady-state

    stability limit of a lossless line.

    • It is convenient to express the steady-statestability limit in terms of SIL

    Steady State Stability Limit

  • 8/15/2019 TSDOS Phasor Transformer

    241/248

    241

    • Transmission line loadability curve

    Maximum Power Flow

  • 8/15/2019 TSDOS Phasor Transformer

    242/248

    242

    • For lossy lines, their ABCD parameters are

    • The receiving end current is

    Maximum Power Flow

  • 8/15/2019 TSDOS Phasor Transformer

    243/248

    243

    • The complex power delivers to the receiving

    end is

    Maximum Power Flow

  • 8/15/2019 TSDOS Phasor Transformer

    244/248

    244

    • The theoretical maximum real power 

    delivered (or steady-state stability limit)

    occurs when d = Z.

    Line Loadability

  • 8/15/2019 TSDOS Phasor Transformer

    245/248

    245

    • In practice, power lines are not operated to

    deliver their theoretical maximum power.

    • Typical loadability is based on the voltage-drop limit VR/VS>0:95 and on a maximum

    angular displacement of 30 to 35o across the

    line (or about 45o across the line and

    equivalent system reactances) to maintainstability during transient disturbances.

    Line Loadability

  • 8/15/2019 TSDOS Phasor Transformer

    246/248

    246

    • Note that for short lines less than 80 km long,

    loadability is limited by the thermal rating of 

    the conductors or by terminal equipment

    ratings, not by voltage drop or stability

    considerations.

    Reactive Compensation

  • 8/15/2019 TSDOS Phasor Transformer

    247/248

    247

    • Inductors and capacitors are used on

    medium-length and long transmission lines to

    increase line loadability and to maintain

    voltages near rated values.

    • It can be either series or shunt

    compensation.

    Reactive Compensation

  • 8/15/2019 TSDOS Phasor Transformer

    248/248

    • Following devices are used in reactive power 

    compensation:

    • Capacitor 

    • Inductor 

    • Static Var Compensator (FC-TCR or SC-TCR)